TECO E510s General Vector Control Drives

Our E510s brings motor control, built-in PLC functions and PID control together for stand-alone machinery and straightforward system integration. Choose an IP20 configuration for the appropriate installation or an IP66 version where the application calls for greater enclosure protection. We can help match the drive, motor, supply and controls to the job.

Choose by model, enclosure and duty

Our local range page describes 0.4–2.2 kW single-phase input and 0.75–18.5 kW three-phase input, with three-phase motor output. Its collected selection table also includes an E510-430-SH3F sheet rated 22 kW/45 A HD or 30 kW/58 A ND. The broader catalogue and manual extend further, while the short local brochure describes IP20 up to 55 kW and IP66 up to 11 kW. These are different published scopes; please confirm the exact model and availability with us.

Selection How to use the source information
200–240 V single-phase input Local page range 0.4–2.2 kW. The short brochure starts at 0.75 kW. Confirm enclosure and exact code. Output is three-phase.
380–480 V three-phase input Match the individual current, kW, duty and enclosure schedule. Do not use the catalogue's ambiguous “Single/Three phase 400V” heading as evidence of a 400 V single-phase option.
IP20 versus IP66 Separate model and dimensional schedules apply. NEMA1, NEMA4 and NEMA4X wording varies between documents; use the selected unit's actual marking and instructions.
Heavy Duty versus Normal Duty Retain the paired power/current values. A higher ND power is not the HD rating of the same unit. Overload duration differs between some sources and requires confirmation.

Our collected register has 23 website rows, 36 PDF memberships and 23 distinct technical PDFs. Shared files appear once with every row association retained. The complete brochure, manual, quick-guide and configuration references follow below; dimensions are taken from their own model schedules, not transferred between enclosures.

Control that fits the application

The E510s documentation covers V/F, sensorless vector (SLV) and PM sensorless vector (PMSLV) control, with auto-tuning and PM motor parameters. The published starting-torque figures are 150% at 3 Hz in V/F and 150% at 1 Hz in SLV under the source conditions. They do not establish the same performance for every motor or load.

The general frequency specification is 0.01–599 Hz, but the manual gives lower SLV and Normal Duty limits by model, carrier frequency and mode. Use those detailed limits. The control features include preset speeds, acceleration/deceleration and S-curve settings, skip frequencies, torque boost, fault monitoring, parameter locking, PID and constant-pressure multi-pump functions. Older E510-labelled sheets and E510s sheets contain different curve counts, function counts and time ranges; we keep them separate.

Interfaces, operator controls and options

We describe built-in Modbus RTU/RS485, BACnet, PLC and PID functions for integration with machine and building controls. Keypad, external terminals and communication commands provide different run and speed-reference choices. Follow the applicable manual for signal range, jumper positions, shielding, addressing and termination; connector labels alone are not a wiring diagram.

Keypad and accessory arrangements depend on the configuration. The catalogue identifies an LED display code, while the local page also describes an LCD keypad and the manual lists an LCD operator accessory. The catalogue identifies N4 with a built-in potentiometer and N4S with power switch and potentiometer. Filter/STO, communications cards, copy units, mounting accessories and cable lengths must be checked against their exact model and frame. An option in a catalogue is not automatically included in every drive.

Fire mode and Safe Torque Off have different purposes

Fire mode is a specialist function described for smoke extraction. It can override normal commands and selected protections, continuing until a hardware protection operates or the drive is damaged. It is disabled by default in the manual, and the manual states that it does not support the PUMP function. Its detailed speed-source settings include a specified fire speed, PID or AI2; the headline “full-speed” description does not replace those settings. We do not present this as a general emergency-stop function or a complete fire-safety design.

Safe Torque Off (STO) removes motor-driving torque and allows the motor to coast; it does not provide electrical isolation or controlled braking. The manual restricts STO to built-in EMC-filter models. Its safety appendix contains model-specific installation, testing and risk-assessment requirements, with historical SIL2/Category3/PLd statements. Confirm the supplied hardware and applicable safety documentation with us. Those statements do not certify the complete machine or validate current certificate status.

Installation, environment and maintenance

Use the nameplate, complete manual, exact outline and qualified installation personnel. Allow the required clearances and cooling, select protective devices and cables for the specific model, earth and shield correctly, and follow the brake-resistor and EMC guidance. IP66 does not establish unrestricted outdoor, chemical or washdown suitability. Keep the original wiring and enclosure details with the installation.

The manual's IP20/NEMA1 temperature conditions distinguish −10°C to +50°C without the upper dust cover/sticker and −10°C to +40°C with it, with further current, carrier-frequency and temperature derating conditions. Its general altitude section and its STO environment have different limits. These must not be combined into a universal maximum for every model.

Isolate, allow the model-specific discharge time and verify the required voltage condition before work. The main manual includes a longer wait for larger units and the safety appendix requires zero-voltage verification; elapsed time alone is not proof of isolation. Auto-restart and fault reset can restart machinery when enabled. For long storage, use the complete capacitor-reforming procedure, and follow the inspection and replacement instructions for the drive actually installed.

Quick setup and complete technical references

We retain both the IP20 and IP66 quick setup guides. They cover motor nameplate entries, run/stop source, two- and three-wire control, and keypad or external speed references. Their group numbering and defaults must be checked against the full manual and firmware: for example, the quick guides label PM parameters Group 21 and pump parameters Group 22, whereas the E510s manual uses Group 22 for PM parameters. Do not transpose settings between documents without checking the installed drive.

The following references keep the original parameter identifiers, defaults, units, blank cells, model suffixes, HD/ND columns and source conditions. They are reference material to use with the complete PDFs, including adjacent-page notes and diagrams. Our team can help confirm discrepancies before selection or commissioning.

Catalogue — E510s brochure cover — page 1

E510sEn210205-1.pdf · P009 · source page 1

E510s General Vector Control Drive. IP20/NEMA1 and IP66/NEMA4X.

Context: Product brochure, not an operating manual. Product photos do not establish model-specific ratings.

Catalogue — Product description and four feature groups — page 2

E510sEn210205-1.pdf · P009 · source page 2

E510s belongs to the 510 series. Source describes stand-alone machine control and simple system integration, PM motor control, Safety Torque Off, built-in PLC, internal communication module and IP66 enclosure.

Table conditions: Historical supplier statements only; not current certification verification.

Feature groups — PDF page 2

Feature Source description
High-end vector control Supports induction motor (IM) and permanent magnet (PM) motor control
Multiple auto-tuning modes Rotational, static and stator resistance measurement
Global standards RoHS, CE, UL and TUV certified STO supplier claims
Applications Fan and pump, conveyor, woodworking, packaging, textile and machine tools

Catalogue — Starting torque auto-tuning PM parameters and motor noise — page 3

E510sEn210205-1.pdf · P009 · source page 3

Sensorless vector (SLV) starting torque: 150% at 1Hz. Torque graph refers to a 4-pole induction motor; torque axis 0–150%, motor speed axis 0–2000, legend 1/3/5/10/20/30/40/50/60Hz.

PM motor control illustrations identify Surface Permanent Magnet Motor (SPM) and Interior Permanent Magnet Motor (IPM).

Soft PWM supplier claim: reduces radio frequency interference and motor noise. Traditional PWM output and Soft PWM output illustrations retained in original PDF.

Context: Torque curves and waveform/equivalent-circuit geometry are not digitized into performance values. Original figures remain authority. Image-only PM parameter table was enlarged and manually read; default KVA printed for both rated power and rated current, without interpretation.

Table conditions: Source mode-to-situation associations.

Table conditions: Image-only table; enlarged source crop retained. KVA is literal text in Default column, not inferred units or numeric default. Printed ranges do not establish suitability for a particular application.

Advanced auto-tuning — PDF page 3

Mode Situation
Rotational When the load can be uncoupled
Static When the load cannot be uncoupled
Stator resistance measurement When the motor cable is too long

Group 22 PM motor parameters — PDF page 3

Code Parameter Setting range Default Unit
22-00 PM Motor Rated Power 0.00–600.00 KVA kW
22-02 PM Motor Rated Current 25%–200% inverter rated current KVA A
22-03 PM Motor pole number 2–96 8 Poles
22-04 PM Motor rotation speed 0–60000 1500 RPM
22-05 PM Motor maximum rotation speed 0–60000 1500 RPM
22-06 PM Motor rated frequency 4.8–599.0 75.0 Hz
22-10 PM SLV start current 20%–200% Motor Rated Current 50 %
22-11 V/F mode start frequency switching point 1.0–20.0 10.0 %
22-14 Armature resistance of PM motor 0.001–30.000 1.000 Ω
22-15 D-axis inductance of PM motor 0.01–300.00 10.00 mH
22-16 Q-axis inductance of PM motor 0.01–300.00 10.00 mH
22-18 Flux-weakening limit 0–100 0 %
22-21 PM motor tuning 0: PM Motor Tuning is not Active. / 1: Parameter Auto-tune 0 -

Catalogue — Fire mode BACnet and STO — page 4

E510sEn210205-1.pdf · P009 · source page 4

Fire mode: source describes full-speed forward or reverse, ignoring all software protections until hardware protection triggers or the drive is damaged; smoke extraction application. Illustration: smoke sensor signal, fire mode, fan runs until the drive fails.

BACnet: information exchange, alarm management, scheduling, parameter trending, equipment and network management.

STO illustration contrasts traditional emergency-stop/controller/two-contactors/drive/motor arrangement with integrated E510s STO arrangement. Supplier claims reduced installation space and wiring cost and rapid reliable protection.

Context: Fire mode statement retained with destructive-operation qualification; not an operating instruction or safety recommendation. STO standards are historical supplier claims, not verified certificates. Source prints Cat/PLd without a category number.

Table conditions: Preserve incomplete Cat/PLd literally; do not insert a category number.

Printed STO references — PDF page 4

Standard Printed class
EN ISO 13849-1 Cat/PLd
EN 60204-1 Category 0
EN 61508 SIL2
EN 62061 SIL CL2

Catalogue — Application environments — page 5

E510sEn210205-1.pdf · P009 · source page 5

Context: Application photographs and captions are supplier examples. Suitability is conditional on the correct enclosure/model and installation; no broader waterproof claim inferred.

Table conditions: Source describes sealed IP66 design with waterproof/dustproof characteristics; no additional protection rating inferred.

Application examples — PDF page 5

Enclosure scope Application Printed context
IP20/NEMA1 Textiles General application
IP20/NEMA1 Woodworking General application
IP20/NEMA1 Small handling machine General application
IP20/NEMA1 Simple metal processing General application
IP20/NEMA1 Machine tools General application
IP20/NEMA1 Packaging and labeling General application
IP20/NEMA1 Food processing General application
IP20/NEMA1 Fan and pumps General application
IP20/NEMA1 HVAC General application
IP66/NEMA4X Food Washdown
IP66/NEMA4X Textiles High heat and humid dyeing
IP66/NEMA4X Petrochemical Corrosive environment
IP66/NEMA4X Livestock Washdown
IP66/NEMA4X Woodworking Dusty environment

Catalogue — Power rating and general specifications — page 6

E510sEn210205-1.pdf · P009 · source page 6

Normal Duty (N.D) overload capability: 120% for 60s. Heavy Duty (H.D): 150% for 60s.

Context: Rating table group header says Single/Three phase 400V, while general input specification says Three Phase 380–480Vac and listed 400V catalog numbers end SH3. Preserve conflicting source scopes; do not claim single-phase 400V availability. ND kW column is shared across voltage groups; a dash in a model output ND cell remains a dash.

Table conditions: Source headers Single/Three phase 200V and Single/Three phase 400V. HD/ND rating columns remain associated with their voltage-group catalog number. Absent 200V models at 50/60/75HP have a single merged dash spanning HD/ND, explicitly represented as merged source context, not two ratings.

Table conditions: Literal supplier specification; no output capability calculated from input or model codes.

Power rating matrix — PDF page 6

HP kW HD kW ND 200V catalog number 200V output HD 200V output ND 200V braking transistor 200V frame 400V catalog number 400V output HD 400V output ND 400V braking transistor 400V frame
0.5 0.4 - E510-2P5-SH 3.1A - Built-in 1 - - - - -
1 0.75 - E510-201-SH 4.5A - Built-in 1 E510-401-SH3 2.5A - Built-in 1
2 1.5 - E510-202-SH 7.5A - Built-in 2 E510-402-SH3 3.8A - Built-in 1
3 2.2 - E510-203-SH 10.5A - Built-in 2 E510-403-SH3 5.3A - Built-in 2
5 4 - E510-205-SH3 17.5A - Built-in 2 E510-405-SH3 9.2A - Built-in 2
7.5 5.5 - E510-208-SH3 26A - Built-in 3 E510-408-SH3 13A - Built-in 3
10 7.5 - E510-210-SH3 35A - Built-in 3 E510-410-SH3 17.5A - Built-in 3
15 11 - E510-215-SH3 48A - Built-in 4 E510-415-SH3 24A - Built-in 3
20 15 - E510-220-SH3 64A - Built-in 4 E510-420-SH3 32A - Built-in 4
25 18.5 22 E510-225-SH3 73A 80A Built-in 5 E510-425-SH3 40A - Built-in 4
30 22 30 E510-230-SH3 85A 110A Optional Add-ON 6 E510-430-SH3 45A 58A Built-in 5
40 30 37 E510-240-SH3 115A 138A Optional Add-ON 6 E510-440-SH3 60A 73A Optional Add-ON 6
50 37 45 - [merged source dash spanning HD and ND] [merged source dash spanning HD and ND] - - E510-450-SH3 75A 88A Optional Add-ON 6
60 45 55 - [merged source dash spanning HD and ND] [merged source dash spanning HD and ND] - - E510-460-SH3 91A 103A Optional Add-ON 6
75 55 75 - [merged source dash spanning HD and ND] [merged source dash spanning HD and ND] - - E510-475-SH3 118A 145A Optional Add-ON 6

General specifications first page — PDF page 6

Group Item Source value
Input power Rated voltage Single/Three Phase 200–240Vac / Three Phase 200–240Vac / Three Phase 380–480Vac
Input power Rated frequency 50/60Hz
Input power Allowable voltage fluctuation -15% to +10%
Input power Allowable frequency fluctuation ±5%
Output rating Output voltage 200V Class: Three Phase 0–240Vac / 400V Class: Three Phase 0–480Vac
Output rating Output frequency 0.01–599Hz
Control Mode V/F, SLV, PMSLV
Frequency Output frequency 0.01–599.00Hz
Frequency Starting torque V/F: 150% / 3Hz. SLV: 150% / 1Hz
Frequency Resolution Digital input: 0.01Hz. Analog input: 0.06Hz/60Hz
Frequency Setting Keypad ▲▼ or VR / AI1-AI2 (0/2–10V, 0/4–20mA) / digital UP-DOWN / RS485
Frequency Skip frequency 3 configurable ranges

Catalogue — General specifications continuation — page 7

E510sEn210205-1.pdf · P009 · source page 7

Context: Source operating-temperature text says IP66 / NEMA4 tape; enclosure row says IP66/NEMA4X. Retain both. Certification and standards statements are historical supplier claims. Digital input operation-command continuation includes 2/3-wire selection and JOG; not a blank value.

Table conditions: Manufacturer statements with conditions. No unqualified inference that every model has filter/STO; catalog-code definition page14 retained separately.

General specifications continuation — PDF page 7

Group Item Source value
Run Operation command Keypad RUN/STOP / Digital input: Multi-operation mode 2/3 wires selection, JOG operation / RS485
Main control V/F curve 15 fixed curves and 1 customized curve
Main control Carrier frequency 1k–16kHz (factory 5kHz)
Main control Multifunction input 6 digital input points
Main control Multifunction output 2 digital output points (1a x1, 1c x1)
Main control Multifunction analog input 2 analog input points (0–10V / 0–20mA)
Main control Multifunction analog output 1 analog output point (0–10V)
Main control Main features Overload detection, 16 preset speeds, Auto-run, Acc/Dec curves setting, Main/Alternative run command, Main/Alternative frequency command, PID, Torque boost, Auto restart, Speed search start, Fire mode, Constant-Pressure Pump control
Display LED display Parameter, parameter value, frequency, line speed, DC voltage, output voltage, output current, PID feedback, input/output terminal status, heat sink temperature, firmware version, fault list
Display LED status Run/Stop, Forward/Reverse, Frequency screen, Parameter screen
Protective functions Motor overload OL1 Electrical overload protection curves selectable
Protective functions Drive overload OL2 HD: 150% for 60s, 200% for 2s. ND: 120% for 60s
Protective functions Over voltage 200V Class DC bus >410Vdc. 400V Class DC bus >820Vdc
Protective functions Under voltage 200V Class DC bus <190V. 400V Class DC bus <380V
Protective functions Momentary power loss restart Inverter can be set to restart automatically
Protective functions Stall prevention Acceleration/deceleration operation
Protective functions Short-circuit fault Electronic circuit protection
Protective functions Ground fault Electronic circuit protection
Protective functions Others Heat sink overtemperature, reverse prohibit, parameter lock up, Safety Torque Off (STO,SIL2), motor PTC feedback, phase loss detection, communication error detection
Communication Built-in RS485 / BACnet
Communication Optional add-on module Profibus / DeviceNet / CANopen / Ethernet
Environment Operating temperature IP20/NEMA1: -10–50°C without sticker or upper dust cover, -10–40°C with sticker or upper dust cover. IP66 / NEMA4 tape: -10–40°C
Environment Storage temperature -20–60°C
Environment Humidity <95% RH, no condensation. IEC60068-2-78
Environment Vibration 1G (9.8m/s²) for <20Hz. 0.6G (5.88m/s²) 20–50Hz. IEC60068-2-6
Environment Enclosure IP20/NEMA1 / IP66/NEMA4X
PLC Function Built-in: 80 ladder lines, 4 elements per line
EMI protection Built-in noise filter EN61800-3
EMS protection Standard EN61800-3
Certifications CE EN61800-3 (CE/RE), EN61800-5-1 (LVD)
Certifications UL UL508C
Options Accessories Copy Unit, LCD Display, Internal Communication Card

Catalogue — Wiring diagram terminal labels defaults and five remarks — page 8

E510sEn210205-1.pdf · P009 · source page 8

Context: Labels and explicit defaults only; wiring topology and safety design are not reconstructed. Original figure and appropriate operating manual remain authority. SF/SG shorthand in remark retained alongside SF1/SF2/SG diagram.

Context: Frequency reference label: 10K ohm or PID input. Diagram legend distinguishes cable shield, P cable shield twisted pair, power wire connection and control wire connection; symbols retained in original PDF.

Table conditions: No contact state or cable connection is implied beyond the printed labels and defaults.

Table conditions: Pin numbering is from printed connector label list, not an inferred connector orientation.

Table conditions: Source statements retained; not installation instructions validated by this review.

Wiring terminal and jumper labels — PDF page 8

Label Source description
L1(L), L2, L3(N) Main power through NFB, MC and fast acting fuse as illustrated
T1, T2, T3 Output to induction motor
P, BR Braking resistor connection, limited by remark1
S1 Forward/stop default
S2 Reverse/stop default
S3, S4, S5 Preset speed default
S6 Reset default
COM Common point for NPN input
+24V Common point for PNP input
E Cable shield connection
SF1, SF2, SG Functional safety input (STO), see remarks2 and4
10V Power of analog input
AI1 Multifunction analog input1, 0–10V/0–20mA
AI2 Multifunction analog input2, 0–10V/0–20mA
AGND Common point for analog signal
AO, AGND Frequency indicator DC 0–10V
R1A, R1B, R1C, R2A, R2B Relay output: 250VAC 1A / 30VDC 1A
S(+), S(-) RS485/Modbus
CON2 RS485 connector
JP1 NPN/PNP selection
JP2 / AI1 / AV1 I (Default), V
JP3 / AI2 / AV2 I, V (Default)

CON2 printed pin assignments — PDF page 8

Pin Label
1 Data+
2 Data-
3 Data+
4 RXD0
5 TXD0
6 Data-
7 5V
8 GND

Wiring remarks — PDF page 8

Remark Source statement
1 BR only exists for IP20 200V 0.5–25HP and 400V 1–30HP. Braking resistor can connect directly between P and BR
2 Safety input SF/SG default shorted. Remove short-pin between SF/SG when safety input used
3 S1–S6 can be Sink (NPN) or Source (PNP) by JP1
4 SG: +24V for SF1/SF2 only
5 Only 200V 25–40HP and 400V 30–75HP provide P1/P2 for external DC reactor between P1/P2. P1/P2 factory short-circuited

Catalogue — Dimensions 9 — page 9

E510sEn210205-1.pdf · P009 · source page 9

Context: Dimensions and weights retained as printed, including inconsistent unit pairs. Exact listed catalog groups only; original drawing geometry remains authority.

Table conditions: Figure A; IP20 Frame 1. Dimensions mm (inch), mounting Q or Φ as printed. Merged values expanded only over explicitly listed model rows. No inferred additional models.

Table conditions: Figure B; IP20 Frame 2. Dimensions mm (inch), mounting Q or Φ as printed. Merged values expanded only over explicitly listed model rows. No inferred additional models.

Figure A — IP20 Frame 1 — PDF page 9

Catalog number W W1 W2 H H1 D E t Q Net weight kg (lb)
E510-2P5-SH 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5 (3.3)
E510-201-SH 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5 (3.3)
E510-2P5-SH1F 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5 (3.3)
E510-201-SH1F 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5 (3.3)
E510-202-SH3 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5 (3.3)
E510-401-SH3 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5 (3.3)
E510-402-SH3 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5 (3.3)
E510-401-SH3F 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.58 (3.48)
E510-402-SH3F 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.58 (3.48)

Figure B — IP20 Frame 2 — PDF page 9

Catalog number W W1 W2 H H1 H2 D D1 E t Q Net weight kg (lb)
E510-202-SH 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0 (4.41)
E510-203-SH 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0 (4.41)
E510-202-SH1F 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0 (4.41)
E510-203-SH1F 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0 (4.41)
E510-205-SH3 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0 (4.41)
E510-403-SH3 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0 (4.41)
E510-405-SH3 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0 (4.41)
E510-403-SH3F 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.2 (4.81)
E510-405-SH3F 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.2 (4.81)

Catalogue — Dimensions 10 — page 10

E510sEn210205-1.pdf · P009 · source page 10

Context: Dimensions and weights retained as printed, including inconsistent unit pairs. Exact listed catalog groups only; original drawing geometry remains authority.

Table conditions: Figure C; IP20 Frame 3. Dimensions mm (inch), mounting Q or Φ as printed. Merged values expanded only over explicitly listed model rows. No inferred additional models.

Table conditions: Figure D; IP20 Frame 4. Dimensions mm (inch), mounting Q or Φ as printed. Merged values expanded only over explicitly listed model rows. No inferred additional models.

Figure C — IP20 Frame 3 — PDF page 10

Catalog number W W1 W2 H H1 H2 D D1 E t Q Net weight kg (lb)
E510-208-SH3 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.0 (13.23)
E510-210-SH3 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.0 (13.23)
E510-408-SH3 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.0 (13.23)
E510-410-SH3 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.0 (13.23)
E510-415-SH3 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.0 (13.23)
E510-408-SH3F 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.5 (14.33)
E510-410-SH3F 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.5 (14.33)
E510-415-SH3F 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 10.0 (22.05)

Figure D — IP20 Frame 4 — PDF page 10

Catalog number W W1 W2 H H1 H2 D D1 E t Q Net weight kg (lb)
E510-215-SH3 224.6 (8.84) 207 (8.15) 207 (8.15) 321.6 (12.66) 303.5 (11.95) 330.9 (13.03) 206.1 (8.11) 201.1 (7.92) 94 (3.7) 8 (0.31) M5 10.0 (22.05)
E510-220-SH3 224.6 (8.84) 207 (8.15) 207 (8.15) 321.6 (12.66) 303.5 (11.95) 330.9 (13.03) 206.1 (8.11) 201.1 (7.92) 94 (3.7) 8 (0.31) M5 10.0 (22.05)
E510-420-SH3 224.6 (8.84) 207 (8.15) 207 (8.15) 321.6 (12.66) 303.5 (11.95) 330.9 (13.03) 206.1 (8.11) 201.1 (7.92) 94 (3.7) 8 (0.31) M5 10.0 (22.05)
E510-425-SH3 224.6 (8.84) 207 (8.15) 207 (8.15) 321.6 (12.66) 303.5 (11.95) 330.9 (13.03) 206.1 (8.11) 201.1 (7.92) 94 (3.7) 8 (0.31) M5 10.0 (22.05)

Catalogue — Dimensions 11 — page 11

E510sEn210205-1.pdf · P009 · source page 11

Context: Dimensions and weights retained as printed, including inconsistent unit pairs. Exact listed catalog groups only; original drawing geometry remains authority.

Table conditions: Figure E; IP20 Frame 5. Dimensions mm (inch), mounting Q or Φ as printed. Merged values expanded only over explicitly listed model rows. No inferred additional models.

Table conditions: Figure F; IP20 Frame 6. Dimensions mm (inch), mounting Q or Φ as printed. Merged values expanded only over explicitly listed model rows. No inferred additional models.

Figure E — IP20 Frame 5 — PDF page 11

Catalog number W W1 W2 H H1 D D1 t Q Net weight kg (lb)
E510-225-SH3 265 (10.43) 245 (9.65) 245 (9.65) 360 (14.17) 340 (13.39) 238.2 (9.38) 233.2 (9.18) 1.6 (0.06) M8 10.0 (22.05)
E510-430-SH3 265 (10.43) 245 (9.65) 245 (9.65) 360 (14.17) 340 (13.39) 238.2 (9.38) 233.2 (9.18) 1.6 (0.06) M8 10.0 (22.05)

Figure F — IP20 Frame 6 — PDF page 11

Catalog number W W1 W2 H H1 D t Q Net weight kg (lb)
E510-230-SH3 286.5 (11.28) 220 (8.66) 220 (8.66) 525 (20.67) 505 (19.88) 269.8 (10.62) 3.3 (0.13) M8 23.2 (51.15)
E510-240-SH3 286.5 (11.28) 220 (8.66) 220 (8.66) 525 (20.67) 505 (19.88) 269.8 (10.62) 3.3 (0.13) M8 23.2 (51.15)
E510-440-SH3 286.5 (11.28) 220 (8.66) 220 (8.66) 525 (20.67) 505 (19.88) 269.8 (10.62) 3.3 (0.13) M8 23.2 (51.15)
E510-450-SH3 286.5 (11.28) 220 (8.66) 220 (8.66) 525 (20.67) 505 (19.88) 269.8 (10.62) 3.3 (0.13) M8 23.2 (51.15)
E510-460-SH3 286.5 (11.28) 220 (8.66) 220 (8.66) 525 (20.67) 505 (19.88) 269.8 (10.62) 3.3 (0.13) M8 23.2 (51.15)
E510-475-SH3 286.5 (11.28) 220 (8.66) 220 (8.66) 525 (20.67) 505 (19.88) 269.8 (10.62) 3.3 (0.13) M8 23.2 (51.15)

Catalogue — Dimensions 12 — page 12

E510sEn210205-1.pdf · P009 · source page 12

Context: Dimensions and weights retained as printed, including inconsistent unit pairs. Exact listed catalog groups only; original drawing geometry remains authority.

Table conditions: Figure G; IP20 Frame 5, with filter. Dimensions mm (inch), mounting Q or Φ as printed. Merged values expanded only over explicitly listed model rows. No inferred additional models.

Table conditions: Figure H; IP20 Frame 6, with filter. Dimensions mm (inch), mounting Q or Φ as printed. Merged values expanded only over explicitly listed model rows. No inferred additional models.

Figure G — IP20 Frame 5, with filter — PDF page 12

Catalog number W W1 H H1 D D1 E E1 t Q Net weight kg (lb)
E510-420-SH3F 235.6 (9.28) 180 (7.09) 400 (15.75) 381.5 (15.02) 267.1 (10.52) 262.1 (10.32) 62 (2.44) 237 (9.33) 4 (0.16) M6 18.9 (41.67)
E510-425-SH3F 235.6 (9.28) 180 (7.09) 400 (15.75) 381.5 (15.02) 267.1 (10.52) 262.1 (10.32) 62 (2.44) 237 (9.33) 4 (0.16) M6 18.9 (41.67)

Figure G — IP20 Frame 5, with filter — PDF page 12

Catalog number W W1 H H1 D D1 E E1 t Q Net weight kg (lb)
E510-430-SH3F 269 (10.59) 230 (9.05) 462 (18.19) 440 (17.32) 318.2 (12.53) 313.2 (12.33) 80 (3.15) 267.6 (10.54) 4 (0.16) M8 22.8 (50.27)

Figure H — IP20 Frame 6, with filter — PDF page 12

Catalog number W W1 W2 H H1 D E E1 t Q Net weight kg (lb)
E510-440-SH3F 288.9 (11.37) 220 (8.66) 220 (8.66) 652 (25.67) 620 (24.41) 369.8 (14.56) 90 (3.54) 331.1 (13.04) 4 (0.16) M8 47.2 (104.07)
E510-450-SH3F 288.9 (11.37) 220 (8.66) 220 (8.66) 652 (25.67) 620 (24.41) 369.8 (14.56) 90 (3.54) 331.1 (13.04) 4 (0.16) M8 47.2 (104.07)
E510-460-SH3F 288.9 (11.37) 220 (8.66) 220 (8.66) 652 (25.67) 620 (24.41) 369.8 (14.56) 90 (3.54) 331.1 (13.04) 4 (0.16) M8 47.2 (104.07)
E510-475-SH3F 288.9 (11.37) 220 (8.66) 220 (8.66) 652 (25.67) 620 (24.41) 369.8 (14.56) 90 (3.54) 331.1 (13.04) 4 (0.16) M8 47.2 (104.07)

Catalogue — Dimensions I and J — page 13

E510sEn210205-1.pdf · P009 · source page 13

Context: Dimensions and weights retained as printed, including inconsistent unit pairs. Exact listed catalog groups only; original drawing geometry remains authority.

Table conditions: Figure I; IP66 Frame 1. Dimensions mm (inch), mounting Q or Φ as printed. Merged values expanded only over explicitly listed model rows. No inferred additional models.

Table conditions: Figure J; IP66 Frame 2. Dimensions mm (inch), mounting Q or Φ as printed. Merged values expanded only over explicitly listed model rows. No inferred additional models.

Figure I — IP66 Frame 1 — PDF page 13

Catalog number W W1 H H1 D D1 D2 Φ Net weight kg (lb)
E510-2P5-SH1FN4S 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0 (6.6)
E510-201-SH1FN4S 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0 (6.6)
E510-2P5-SH1FN4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0 (6.6)
E510-201-SH1FN4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0 (6.6)
E510-2P5-SHN4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0 (6.6)
E510-201-SHN4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0 (6.6)
E510-401-SH3FN4S 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0 (6.6)
E510-402-SH3FN4S 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0 (6.6)
E510-401-SH3FN4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0 (6.6)
E510-402-SH3FN4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0 (6.6)
E510-401-SH3N4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0 (6.6)
E510-402-SH3N4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0 (6.6)

Figure J — IP66 Frame 2 — PDF page 13

Catalog number W W1 H H1 D D1 D2 Φ Net weight kg (lb)
E510-202-SH1FN4S 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)
E510-203-SH1FN4S 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)
E510-202-SH1FN4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)
E510-203-SH1FN4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)
E510-202-SHN4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)
E510-203-SHN4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)
E510-205-SH3N4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)
E510-403-SH3FN4S 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)
E510-405-SH3FN4S 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)
E510-403-SH3FN4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)
E510-405-SH3FN4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)
E510-403-SH3N4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)
E510-405-SH3N4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9 (13.0)

Catalogue — Dimensions K and catalog identification — page 14

E510sEn210205-1.pdf · P009 · source page 14

Context: Dimensions and weights retained as printed, including inconsistent unit pairs. Exact listed catalog groups only; original drawing geometry remains authority.

Context: Catalog diagram is a code dictionary, not proof every combination is available. Combined EMC Filter & STO box retained without separating or extending its applicability.

Table conditions: Figure K; IP66 Frame 3. Dimensions mm (inch), mounting Q or Φ as printed. Merged values expanded only over explicitly listed model rows. No inferred additional models.

Table conditions: Example segments E510 / 2 / 01 / S / H / 1 / F / N4S. No unlisted combinations constructed.

Table conditions: Catalog-number HP meanings as printed.

Figure K — IP66 Frame 3 — PDF page 14

Catalog number W W1 H H1 D D1 D2 Φ Net weight kg (lb)
E510-208-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-210-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-215-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-220-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-408-SH3FN4S 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-410-SH3FN4S 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-415-SH3FN4S 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-408-SH3FN4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-410-SH3FN4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-415-SH3FN4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-408-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-410-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-415-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-420-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)
E510-425-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0 (28.6)

Catalog number identification — PDF page 14

Segment Code Source meaning
Input voltage 2 200–240V
Input voltage 4 380–480V
Product series S 510s series
Display type H LED
Input phase [blank code] Single/Three phase
Input phase 1 Single phase
Input phase 3 Three phase
EMC Filter & STO [blank code] Without built-in
EMC Filter & STO F Built-in
Protection level [blank code] IP20
Protection level N4 IP66 with built-in VR
Protection level N4S IP66 with built-in power switch and VR

Horsepower code legend — PDF page 14

Code HP
P5 0.5
01 1
02 2
03 3
05 5
08 7.5
10 10
15 15
20 20
25 25
30 30
40 40
50 50
60 60
75 75

Catalogue — Accessories — page 15

E510sEn210205-1.pdf · P009 · source page 15

Context: Catalog numbers and explicit frame/length applicability retained. Photos are illustrative; no extra compatibility inferred.

Table conditions: 19 source rows. Current stock or compatibility beyond printed scope not verified.

Accessory catalog — PDF page 15

Accessory category Description Catalog number
Connection cable Operator extension cable 1m JN5-CB-01M
Connection cable Operator extension cable 2m JN5-CB-02M
Connection cable Operator extension cable 3m JN5-CB-03M
Connection cable Operator extension cable 5m JN5-CB-05M
Connection cable RJ45 to USB connecting cable 1.8m JN5-CM-USB
Integrated communication card Profibus communication card JN5-CMI-PDP
Integrated communication card Ethernet TCP/IP communication card JN5-CMI-TCPIP
Integrated communication card DeviceNet communication card JN5-CMI-DNET
Integrated communication card CANopen communication card JN5-CMI-CAN
Integrated communication card EtherNet/IP communication card JN5-CMI-EIP
NEMA1 kit NEMA1 kit for frame1 JN5-NK-SE01
NEMA1 kit NEMA1 kit for frame2 JN5-NK-SE02
NEMA1 kit NEMA1 kit for frame3 JN5-NK-SE03
NEMA1 kit NEMA1 kit for frame4 JN5-NK-SE04
LCD operator interface IP20 LCD operator interface JN5-OP-A02
Din-rail kit Din-rail for frame1 JN5-DINF1
Din-rail kit Din-rail for frame2 JN5-DINF2
Others Copy unit JN5-CU
Others Remote keypad holder JN5-KEYBOX

Catalogue — Manufacturer contact and printed edition — page 16

E510sEn210205-1.pdf · P009 · source page 16

Specifications covered in this brochure may be subject to change without notice.

Context: Historical printed contact details; not live-verified. Decorative photos and QR graphic carry no additional extracted engineering values.

Table conditions: Printed edition preserved independently of filename and acquisition date.

Manufacturer and edition — PDF page 16

Label Source value
Manufacturer TECO Electric & Machinery Co., Ltd.
Address 10F, No. 3-1, Park St., Nan-Kang, Taipei 115, Taiwan
Telephone 886-2-6615-9111 Ext.1725
Fax 886-2-6615-1033
Website http://www.teco.com.tw
Edition GJ-86-03 2021-02-05

Catalogue — TECO-E510.pdf PDF1 — page 1

TECO-E510.pdf · P009 · source page 1

TECO Variable Speed Drives Solutions

OPTIMISED CONTROL & EFFICIENCY

TECO manufactures and stocks a comprehensive range of LV Variable Speed Drives, designed to enhance motor control, improve energy efficiency, and optimise performance across various applications. Engineered with advanced technology, our drives deliver precision, reliability, and cost savings for your operations.

To find out more click the QR code.

electricmotors.teco.com.au

Catalogue — TECO-E510.pdf PDF2 — page 2

TECO-E510.pdf · P009 · source page 2

E510s

General Vector Control Drive

IP66/ NEMA 4 up to 11kW IP20/ NEMA 1 up to 55kW FEATURES

BENEFITS

electricmotors.teco.com.au

Manual — Preface and safety classifications; source thresholds retained — page 6

Manual reference: physical PDF page 6. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 0 Preface

0.1 Preface

To extend the performance of the product and ensure personnel safety, please read this manual thoroughly before using the inverter. Should there be any problem in using the product that cannot be solved with the information provided in the manual, contact Our’s technical or sales representative who will be willing to help you.

※ Precautions

The inverter is an electrical product. For your safety, there are symbols such as “Danger”, “Caution” in this manual as a reminder to pay attention to safety instructions on handling, installing, operating, and checking the inverter. Be sure to follow the instructions for highest safety.

Warning Indicates a potential hazard that could cause death or serious personal injury if misused.

Caution Indicates that the inverter or the mechanical system might be damaged if misused.

Danger

➢ Risk of electric. The DC link capacitors remains charged for five minutes after power has been removed. If it not permissible to open the equipment until 5 minutes after the power has been removed. ( If the power rating of inverter is 20HP above, please open the equipment until 15 minutes after the power has been removed.) ➢ Do not make any connections when the inverter is powered on. Do not check parts and signals on circuit boards during the inverter operation. ➢ Do not disassemble the inverter or modify any internal wires, circuits, or parts. ➢ Ensure that the Inveter Ground terminal is connected correctly.

Caution

➢ Do not perform a voltage test on parts inside the inverter. High voltage can destroy the semiconductor components. ➢ Do not connect T1, T2, and T3 terminals of the inverter to any AC input power supply. ➢ CMOS ICs on the inverter’s main board are susceptible to static electricity. Do not touch the main circuit board.

Manual — Before power up and during power up safety — page 7

Manual reference: physical PDF page 7. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 1 Safety Precautions

1.1 Before Power Up

Danger

➢ Make sure the main circuit connections are correct Single phase L1(L),L3(N), Three phase L1(L),L2,L3(N) are power-input terminals and must not be mistaken for T1,T2 and T3. Otherwise, inverter damage can result.

Caution

➢ The line voltage applied must comply with the inverter’s specified input voltage.(See the nameplate) ➢ To avoid the front cover from disengaging, or other damge do not carry the inverter by its covers. Support the drive by the heat sink when transporting. Improper handling can damage the inverter or injure personnel and should be avoided. ➢ To avoid the risk of fire, do not install the inverter on a flammable object.Install on nonflammable objects such as metal ➢ This product provides the 10V/24V for internal use only, do not use as the power supply sources for other external components, such as sensors, electronic components ... etc., otherwise it will cause adverse situation. ➢ When disconnecting the remote keypad, turn the power off first to avoid any damage to the keypad or the inverter.

➢ This product is sold subject to EN 61800-3 and EN 61800-5-1. In a domestic environment this product may cause radio interference in which case the user may be required to apply corrective measures.

➢ This product offers motor over temperature protection function.

➢ Work on the device/system by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious damage to material. Only suitably qualified personnel trained in the setup, installation, commissioning and operation of the product should carry out work on the device/system.

➢ Only permanently-wired input power connections are allowed. 1.2 During Power Up

➢ Always turn OFF the power supply before attempting inverter installation and wiring of the user terminals. ➢ Wiring must be performed by a qualified personnel / certified electrician. ➢ Make sure the inverter is properly grounded. (200V Class: Grounding impedance shall be less than 100Ω. 400V Class: Grounding impedance shall be less than 10Ω.) Please connect to the earth according to EN61800-5-1 standard request, For system 430, 440, 450, 460 and 470, wiring size must be at least 10mm2(8 AWG) only can comply the standard of leakage current.

Independent parser superscript/order differences checked against original second rendered page; literal units and shared-model cell retained.

Manual — Power restoration conditions and before operation — page 8

Manual reference: physical PDF page 8. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ RCD is required to be in compliance with the protection norm of B-type leakage current. ➢ Please check and test emergency stop circuits after wiring. (Installer is responsible for the correct wiring.) ➢ Never touch any of the input or output power lines directly or allow any input of output power lines to come in contact with the inverter case. ➢ Do not perform a dielectric voltage withstand test (megger) on the inverter this will result in inverter damage to the semiconductor components.

Caution

➢ The line voltage applied must comply with the inverter’s specified input voltage. ➢ Connect braking resistor and braking unit to the designated terminals. ➢ Do not connect a braking resistor directly to the DC terminals P (+) and N (-), otherwise fire may result. ➢ Use wire gauge recommendations and torque specifications. ➢ Never connect input power to the inverter output terminals U/T1, V/T2, W/T3. ➢ Do not connect a power factor correction capacitor or surge suppressor to the inverter output. ➢ Ensure the interference generated by the inverter and motor does not affect peripheral devices.

Danger

➢ When the momentary power loss is longer than 2 seconds, the inverter will not have sufficient stored power for its control circuit. Therefore, when the power is re-applied, the run operation of the inverter will be based on the setting value of parameter 00-02(or 00-03) and 07-04 status of external run switch. ➢ When the momentary power loss is shorter, inverter still can control the power. Therefore, when the power is re-applied, the run operation of inverter will be based on the setting value of parameter 07-00. ➢ When the power is re-applied, the run operation of inverter will be based on the setting value of 00- 02(or 00- 03), 07- 04 and the status of power and operation switch(FWD/REVswitch)(and 07- 00/07- 01/07- 02): (1) If the parameter 00-02(or 00- 03)=0, inverter will not start automatically when the power in re-applied. (2) If the parameter 00- 02(or 00- 03)=1 and the power or operation switch is open, inverter will not start automatically when the power is re-applied. (3) If 00- 02(or 00- 03)=1, then power and operation switch are open (07- 04=0), inverter will restart automatically when the power is re-applied. For the safety, please turn off the power and operation switch after powered off. ➢ For the safety, please read the function explanation from the manual. 1.3 Before Operation

➢ Make sure the inverter model and rating are the same as that set in parameter 13-00.

Manual — Before operation, during operation and maintenance precautions — page 9

Manual reference: physical PDF page 9. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Reduce the carrier frequency (parameter 11-01) If the cable from the inverter to the motor is greater than 80 ft (25m). A high-frequency current can be generated by stray capacitance between the cables and result in an overcurrent trip of the inverter, an increase in leakage current, or an inaccurate current readout

Caution

➢ When the power is applied, inverter will show the voltage rating on display for 2 seconds according to the setting value of parameter 01-14. ➢ Do not connect a load to the motor while performing a rotational auto-tune. ➢ Make sure it is safe to operate the inverter and motor before performing a rotational auto-tune. 1.4 During Operation

Danger

➢ Be sure to install all covers before turning on power ➢ Do not connect or disconnect the motor during operation. Otherwise, It may cause the inverter to trip or damage the unit. ➢ Please do not close to the equipment when the reset function is performed, equipment will restart the fault has been removed. ➢ Do not operate switches with wet hands, otherwise electric shock may result ➢ The motor will restart automatically after stop when auto-restart function is enabled. In this case, care must be taken while working around the drive and associated equipment. ➢ Confirm that no run command is active upon resetting the alarm or fault, otherwise accidents may occur. ➢ If automatic restart after power recovery (parameter 07-00) is enabled, the inverter will start automatically after power is restored ➢ Do not touch inverter terminals when energized even if inverter has stopped, otherwise electric shock may result. ➢ It is not permissible to open the equipment until 5 minutes after the power has been removed.。(if the inverter rating is 15HP above, please open the equipment until 15 minutes after the power has been removed.

➢ Do not touch heat-generating components such as heat sink and braking resistors. ➢ Carefully check the performance of motor or machine before operating at high speed, otherwise Injury may result. ➢ Note the parameter settings related to the braking unit when applicable. ➢ After the power is turned off, the cooling fan may continue to run for some time. ➢ Do not check signals on circuit boards while the inverter is running. 1.5 Maintenance, Inspection and Replacement

Warning

➢ Wait a minimum of five minutes after power has been turned OFF before starting an inspection. Also confirm that the charge light is OFF and that the DC bus voltage has dropped below 25Vdc. ➢ Never touch high voltage terminals in the inverter.

Manual — Maintenance, operating environment and disposal — page 10

Manual reference: physical PDF page 10. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Make sure power to the inverter is disconnected before disassembling the inverter. ➢ Only authorized personnel should perform maintenance, inspection, and replacement operations. (Take off metal jewelry such as watches and rings and use insulated tools.)

Caution

➢ The Inverter can be used in an environment with a temperature range from 14° ~104(°F) or -10~+50(°C1.6) and relative humidity of 95% non-condensing. ➢ The inverter must be operated in a dust, gas, mist and moisture free environment. * -10℃~+50℃ (suitable for the product which without dust cover or sticker) * -10℃~+40℃ (suitable for the product which with dust cover or sticker) 1.6 Disposal of the Inverter

➢ Please dispose of this unit with care as an industrial waste and according to your required local regulations. ➢ The capacitors of inverter main circuit and printed circuit board are considered as hazardous waste and must not be burned. ➢ The Plastic enclosure and parts of the inverter such as the top cover board will release harmful gases if burned. Equipment containing electrical components may not be disposed of together with domestic waste. It must be separately collected with electrical and electronic waste according to local and currently valid legislation.

Manual — Nameplate example and model identification key — page 11

Manual reference: physical PDF page 11. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 2 Model Description

2.1 Nameplate Data

2.2 Model Identification

2.2.1 Inverter Model Name Identification

Nameplate illustration only: PRODUCT:E510-2P5-SH; MOTOR RATING:0.5HP; INPUT:AC1/3PH200-240V(+10%,-15%)50/60Hz8.5/4.5A; OUTPUT:AC3PH0-240V0-599Hz3.1A; IP20/NEMA1; MODEL:11-201-20-2P5-00. P/N code and S/N code placeholders. TECO Electric & Machinery Co., Ltd. Displayed conformity marks and cULus LISTED16KJ IND.CONT.EQ.E177007 are historical nameplate artwork, not certification validation.

Model identification A B-C D E-F G-H I J-K L. A Product:1 Inverter;2 SERVO;3 PLC. B UL Category:0 UL Recognized;1 UL Listed. C-E Serial number001-999. F Standard voltage:1 100-120V;2 200-240V;4 380-480V. G Phase:0 Single/Three phase;1 Single phase;3 Three phase. H-J Horse Power:0P5 0.5HP;001 1HP;075 75HP. K EMC Filter:0 Without built-in;3 Built-in+STO. L Protection level:0 IP20;3 NEMA1;6 IP66.

Manual — Inverter product name identification key — page 12

Manual reference: physical PDF page 12. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

2.2.2 Inverter Product Name Identification

75: 75HP

Product name key E510-2-01-S H-1-F-N4S. Standard voltage:2 200-240V;4 380-480V. S:510s series. H:Standard Product. Phase:1 Single phase;3 Three phase;Blank Single/Three phase. Horse Power:P5 0.5HP;01 1.0HP;02 2.0HP;03 3.0HP;05 5.0HP;08 7.5HP;10 10HP;15 15HP;20 20HP;25 25HP;30 30HP;40 40HP;50 50HP;60 60HP;75 75HP. EMC Filter:F Built-in+STO;Blank Without built-in. N4S:IP66 type. N4:Built-in VR. N4S:Built-in power switch,VR,EMC filter and STO.

Manual — IP20 200V class standard product specifications — page 13

Manual reference: physical PDF page 13. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

2.3 Standard Product Specification

IP20 type 200V Class

IP20 200V class standard product specifications

Model Name / TECO Product Name / Supply voltage (VAC) / Horse power (HP) / Motor (kW) / EMC filter / STO function / Frame size — PDF page 13

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows)
1 Model Name TECO Product Name Supply voltage (VAC) Horse power (HP) Motor (kW) EMC filter STO function Frame size
2 11-201-20-2P5-00 E510-2P5-SH 1/3 Phase 200~240V +10% ~ -15% 50/60Hz 0.5 0.4 ⟦blank source cell⟧ ⟦blank source cell⟧ 1
3 11-201-20-201-00 E510-201-SH 1/3 Phase 200~240V +10% ~ -15% 50/60Hz 1 0.75 ⟦blank source cell⟧ ⟦blank source cell⟧ 1
4 11-201-20-202-00 E510-202-SH 1/3 Phase 200~240V +10% ~ -15% 50/60Hz 2 1.5 ⟦blank source cell⟧ ⟦blank source cell⟧ 2
5 11-201-20-203-00 E510-203-SH 1/3 Phase 200~240V +10% ~ -15% 50/60Hz 3 2.2 ⟦blank source cell⟧ ⟦blank source cell⟧ 2
6 11-301-21-2P5-30 E510-2P5-SH1F 1 Phase 200~240V +10% ~ -15% 50/60Hz 0.5 0.4 ◎ ◎ 1
7 11-301-21-201-30 E510-201-SH1F 1 Phase 200~240V +10% ~ -15% 50/60Hz 1 0.75 ◎ ◎ 1
8 11-301-21-202-30 E510-202-SH1F 1 Phase 200~240V +10% ~ -15% 50/60Hz 2 1.5 ◎ ◎ 2
9 11-301-21-203-30 E510-203-SH1F 1 Phase 200~240V +10% ~ -15% 50/60Hz 3 2.2 ◎ ◎ 2
10 11-201-23-202-00 E510-202-SH3 3 Phase 200~240V +10% ~ -15% 50/60Hz 2 1.5 ⟦blank source cell⟧ ⟦blank source cell⟧ 1
11 11-201-23-205-00 E510-205-SH3 3 Phase 200~240V +10% ~ -15% 50/60Hz 5 4 ⟦blank source cell⟧ ⟦blank source cell⟧ 2
12 11-201-23-208-00 E510-208-SH3 3 Phase 200~240V +10% ~ -15% 50/60Hz 7.5 5.5 ⟦blank source cell⟧ ⟦blank source cell⟧ 3
13 11-201-23-210-00 E510-210-SH3 3 Phase 200~240V +10% ~ -15% 50/60Hz 10 7.5 ⟦blank source cell⟧ ⟦blank source cell⟧ 3
14 11-201-23-215-00 E510-215-SH3 3 Phase 200~240V +10% ~ -15% 50/60Hz 15 11 ⟦blank source cell⟧ ⟦blank source cell⟧ 4
15 11-201-23-220-00 E510-220-SH3 3 Phase 200~240V +10% ~ -15% 50/60Hz 20 15 ⟦blank source cell⟧ ⟦blank source cell⟧ 4
16 11-201-23-225-00 E510-225-SH3 3 Phase 200~240V +10% ~ -15% 50/60Hz 25 18.5 / 22 ⟦blank source cell⟧ ⟦blank source cell⟧ 5
17 11-201-23-230-00 E510-230-SH3 3 Phase 200~240V +10% ~ -15% 50/60Hz 30 22 / 30 ⟦blank source cell⟧ ⟦blank source cell⟧ 6
18 11-201-23-240-00 E510-240-SH3 3 Phase 200~240V +10% ~ -15% 50/60Hz 40 30 / 37 ⟦blank source cell⟧ ⟦blank source cell⟧ 6
19 *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function.

Manual — IP20 400V class standard product specifications — page 14

Manual reference: physical PDF page 14. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

IP20 type 400V Class

※ Uses Footprint type EMC filter

IP20 400V class standard product specifications

Model Name / TECO Product Name / Supply voltage (VAC) / Horse power (HP) / Motor (kW) / EMC filter / STO function / Frame size — PDF page 14

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows)
1 Model Name TECO Product Name Supply voltage (VAC) Horse power (HP) Motor (kW) EMC filter STO function Frame size
2 11-201-43-401-00 E510-401-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 1 0.75 ⟦blank source cell⟧ ⟦blank source cell⟧ 1
3 11-201-43-402-00 E510-402-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 2 1.5 ⟦blank source cell⟧ ⟦blank source cell⟧ 1
4 11-201-43-403-00 E510-403-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 3 2.2 ⟦blank source cell⟧ ⟦blank source cell⟧ 2
5 11-201-43-405-00 E510-405-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 5 4 ⟦blank source cell⟧ ⟦blank source cell⟧ 2
6 11-201-43-408-00 E510-408-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 7.5 5.5 ⟦blank source cell⟧ ⟦blank source cell⟧ 3
7 11-201-43-410-00 E510-410-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 10 7.5 ⟦blank source cell⟧ ⟦blank source cell⟧ 3
8 11-201-43-415-00 E510-415-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 15 11 ⟦blank source cell⟧ ⟦blank source cell⟧ 3
9 11-201-43-420-00 E510-420-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 20 15 ⟦blank source cell⟧ ⟦blank source cell⟧ 4
10 11-201-43-425-00 E510-425-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 25 18.5 ⟦blank source cell⟧ ⟦blank source cell⟧ 4
11 11-201-43-430-00 E510-430-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 30 22 / 30 ⟦blank source cell⟧ ⟦blank source cell⟧ 5
12 11-201-43-440-00 E510-440-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 40 30 / 37 ⟦blank source cell⟧ ⟦blank source cell⟧ 6
13 11-201-43-450-00 E510-450-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 50 37 / 45 ⟦blank source cell⟧ ⟦blank source cell⟧ 6
14 11-201-43-460-00 E510-460-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 60 45 / 55 ⟦blank source cell⟧ ⟦blank source cell⟧ 6
15 11-201-43-475-00 E510-475-SH3 3 Phase 380~480V +10% ~ -15% 50/60Hz 75 55 / 75 ⟦blank source cell⟧ ⟦blank source cell⟧ 6
16 11-301-43-401-30 E510-401-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 1 0.75 ◎ ◎ 1
17 11-301-43-402-30 E510-402-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 2 1.5 ◎ ◎ 1
18 11-301-43-403-30 E510-403-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 3 2.2 ◎ ◎ 2
19 11-301-43-405-30 E510-405-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 5 4 ◎ ◎ 2
20 11-301-43-408-30 E510-408-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 7.5 5.5 ◎ ◎ 3
21 11-301-43-410-30 E510-410-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 10 7.5 ◎ ◎ 3
22 11-301-43-415-30 E510-415-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 15 11 ◎ ◎ 3
23 11-301-43-420-30 E510-420-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 20 15 ◎ ◎ 4
24 11-301-43-425-30 E510-425-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 25 18.5 ◎ ◎ 4
25 11-301-43-430-30 E510-430-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 30 22 / 30 ◎ ◎ 5
26 11-301-43-440-30 E510-440-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 40 30 / 37 ◎ ◎ 6
27 11-301-43-450-30 E510-450-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 50 37 / 45 ◎ ◎ 6
28 11-301-43-460-30 E510-460-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 60 45 / 55 ◎ ◎ 6
29 11-301-43-475-30 E510-475-SH3F 3 Phase 380~480V +10% ~ -15% 50/60Hz 75 55 / 75 ◎ ◎ 6
30 *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function. *** EMC filter models are built-in STO function.

Manual — IP66 200V class standard product specifications; conflicting power/name values retained — page 15

Manual reference: physical PDF page 15. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

IP66 type 200V Class

IP66 200V class standard product specifications; conflicting power/name values retained

Model Name / TECO Product Name / Supply voltage (VAC) / Horse power (HP) / Motor (kW) / Power Switch / EMC filter / STO function / Frame size — PDF page 15

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Model Name TECO Product Name Supply voltage (VAC) Horse power (HP) Motor (kW) Power Switch EMC filter STO function Frame size
2 11-301-21-2P5-36S E510-2P5-SH1FN4S 1 Phase 200~240V +10% ~ -15% 50/60Hz 0.5 0.4 ◎ ◎ ◎ 1
3 11-301-21-201-36S E510-201-SH1FN4S 1 Phase 200~240V +10% ~ -15% 50/60Hz 1 0.75 ◎ ◎ ◎ 1
4 11-301-21-202-36S E510-202-SH1FN4S 1 Phase 200~240V +10% ~ -15% 50/60Hz 2 1.5 ◎ ◎ ◎ 2
5 11-301-21-203-36S E510-203-SH1FN4S 1 Phase 200~240V +10% ~ -15% 50/60Hz 3 2.2 ◎ ◎ ◎ 2
6 11-301-21-2P5-36 E510-2P5-SH1FN4 1 Phase 200~240V +10% ~ -15% 50/60Hz 0.5 0.4 ⟦blank source cell⟧ ◎ ◎ 1
7 11-301-21-201-36 E510-201-SH1FN4 1 Phase 200~240V +10% ~ -15% 50/60Hz 1 0.75 ⟦blank source cell⟧ ◎ ◎ 1
8 11-301-21-202-36 E510-202-SH1FN4 1 Phase 200~240V +10% ~ -15% 50/60Hz 2 1.5 ⟦blank source cell⟧ ◎ ◎ 2
9 11-301-21-203-36 E510-203-SH1FN4 1 Phase 200~240V +10% ~ -15% 50/60Hz 3 2.2 ⟦blank source cell⟧ ◎ ◎ 2
10 11-201-20-2P5-06 E510-2P5-SHN4 1/3 Phase 200~240V +10% ~ -15% 50/60Hz 2 1.5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 1
11 11-201-20-201-06 E510-201-SHN4 1/3 Phase 200~240V +10% ~ -15% 50/60Hz 5 4 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 1
12 11-201-20-202-06 E510-202-SHN4 1/3 Phase 200~240V +10% ~ -15% 50/60Hz 7.5 5.5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 2
13 11-201-20-203-06 E510-203-SHN4 1/3 Phase 200~240V +10% ~ -15% 50/60Hz 10 7.5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 2
14 11-201-23-205-06 E510-205-SH3N4 3 Phase 200~240V +10% ~ -15% 50/60Hz 15 11 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 2
15 11-201-23-208-06 E510-208-SH3N4 3 Phase 200~240V +10% ~ -15% 50/60Hz 20 15 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 3
16 11-201-23-210-06 E510-210-SH3N4 3 Phase 200~240V +10% ~ -15% 50/60Hz 25 18.5 /22 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 3
17 11-201-23-215-06 E510-215-SH3N4 3 Phase 200~240V +10% ~ -15% 50/60Hz 30 22 / 30 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 3
18 11-201-23-220-06 E510-220-SH3N4 3 Phase 200~240V +10% ~ -15% 50/60Hz 40 30 / 37 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 3

Manual — IP66 400V class standard product specifications — page 16

Manual reference: physical PDF page 16. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

IP66 type 400V Class

IP66 400V class standard product specifications

Model Name / TECO Product Name / Supply voltage (VAC) / Horse power (HP) / Motor (kW) / Power Switch / EMC filter / STO function / Frame size — PDF page 16

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Model Name TECO Product Name Supply voltage (VAC) Horse power (HP) Motor (kW) Power Switch EMC filter STO function Frame size
2 11-301-43-401-36S E510-401-SH3FN4S 3 Phase 380~480V +10% ~ -15% 50/60Hz 1 0.75 ◎ ◎ ◎ 1
3 11-301-43-402-36S E510-402-SH3FN4S 3 Phase 380~480V +10% ~ -15% 50/60Hz 2 1.5 ◎ ◎ ◎ 1
4 11-301-43-403-36S E510-403-SH3FN4S 3 Phase 380~480V +10% ~ -15% 50/60Hz 3 2.2 ◎ ◎ ◎ 2
5 11-301-43-405-36S E510-405-SH3FN4S 3 Phase 380~480V +10% ~ -15% 50/60Hz 5 4 ◎ ◎ ◎ 2
6 11-301-43-408-36S E510-408-SH3FN4S 3 Phase 380~480V +10% ~ -15% 50/60Hz 7.5 5.5 ◎ ◎ ◎ 3
7 11-301-43-410-36S E510-410-SH3FN4S 3 Phase 380~480V +10% ~ -15% 50/60Hz 10 7.5 ◎ ◎ ◎ 3
8 11-301-43-415-36S E510-415-SH3FN4S 3 Phase 380~480V +10% ~ -15% 50/60Hz 15 11 ◎ ◎ ◎ 3
9 11-301-43-401-36 E510-401-SH3FN4 3 Phase 380~480V +10% ~ -15% 50/60Hz 1 0.75 ⟦blank source cell⟧ ◎ ◎ 1
10 11-301-43-402-36 E510-402-SH3FN4 3 Phase 380~480V +10% ~ -15% 50/60Hz 2 1.5 ⟦blank source cell⟧ ◎ ◎ 1
11 11-301-43-403-36 E510-403-SH3FN4 3 Phase 380~480V +10% ~ -15% 50/60Hz 3 2.2 ⟦blank source cell⟧ ◎ ◎ 2
12 11-301-43-405-36 E510-405-SH3FN4 3 Phase 380~480V +10% ~ -15% 50/60Hz 5 4 ⟦blank source cell⟧ ◎ ◎ 2
13 11-301-43-408-36 E510-408-SH3FN4 3 Phase 380~480V +10% ~ -15% 50/60Hz 7.5 5.5 ⟦blank source cell⟧ ◎ ◎ 3
14 11-301-43-410-36 E510-410-SH3FN4 3 Phase 380~480V +10% ~ -15% 50/60Hz 10 7.5 ⟦blank source cell⟧ ◎ ◎ 3
15 11-301-43-415-36 E510-415-SH3FN4 3 Phase 380~480V +10% ~ -15% 50/60Hz 15 11 ⟦blank source cell⟧ ◎ ◎ 3
16 11-201-43-401-06 E510-401-SH3N4 3 Phase 380~480V +10% ~ -15% 50/60Hz 1 0.75 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 1
17 11-201-43-402-06 E510-402-SH3N4 3 Phase 380~480V +10% ~ -15% 50/60Hz 2 1.5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 1
18 11-201-43-403-06 E510-403-SH3N4 3 Phase 380~480V +10% ~ -15% 50/60Hz 3 2.2 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 2
19 11-201-43-405-06 E510-405-SH3N4 3 Phase 380~480V +10% ~ -15% 50/60Hz 5 4 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 2
20 11-201-43-408-06 E510-408-SH3N4 3 Phase 380~480V +10% ~ -15% 50/60Hz 7.5 5.5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 3
21 11-201-43-410-06 E510-410-SH3N4 3 Phase 380~480V +10% ~ -15% 50/60Hz 10 7.5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 3
22 11-201-43-415-06 E510-415-SH3N4 3 Phase 380~480V +10% ~ -15% 50/60Hz 15 11 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 3
23 11-201-43-420-06 E510-420-SH3N4 3 Phase 380~480V +10% ~ -15% 50/60Hz 20 15 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 3
24 11-201-43-425-06 E510-425-SH3N4 3 Phase 380~480V +10% ~ -15% 50/60Hz 25 18.5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 3

Manual — Installation environment, conditions and current/temperature plot — page 17

Manual reference: physical PDF page 17. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter3 Environment & Installation

3.1 Environment

Installation environment has a direct effect on the correct operation and the life expectancy of the inverter, Install the inverter in an environment complying with the following conditions:

Installation side

Install in an environment that will not have an adverse effect on the operation of the unit and ensure that there is no exposure to areas such as that listed below: ➢ Direct sunlight, Rain or moisture. ➢ Oil mist, salt, corrosive liquid and gas. ➢ Electromagnetic interference, radioactive and flammable materials ➢ Excessive vibration from machines such as stamping, punching machines, add a vibration-proof pads if necessary.

Inverter Rated Current v.s Ambient Temperature plot. Vertical(A) labels100%,85%,80%,70%; horizontal(T) labels40°,50°,60°. Red line level100% to40°, descending to70% at60°. Dashed reference lines at85%,80%,70%; no additional values interpolated. Plot does not explicitly separate cover/sticker configurations; textual temperature conditions retained separately.

Installation environment, conditions and current/temperature plot

Protection — PDF page 17

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Protection Protection
2 Protection class IP20 / NEMA 1 & IP66
3 Suitable Environment Suitable Environment
4 Operation temperature IP20 / NEMA 1 type:(please refer the ambient temperature and rating current curves in section 3.4.3) Insdie distributor:-10~50°C(without sticker or dust cover)( up to 60°C) Output distributor:-10~40°C(with sticker or dust cover)( up to 50°C) (It is required to derate 1.5% of output current at each additional degrees once the ambient temperature is higher than 50 degrees.) If several inverters are installed in the same Operator panel, ensure adequate spacing and provide the necessary cooling and ventilation for successful operation. **Please does not exceed 70% rated current of inverter with dust sticker or over.
5 Storage temperature -20~60℃
6 Relative Humidity Relative humidity 5% to 95%, free of moisture. (Follow IEC60068-2-78 standard)
7 Vibration Frequency : 10Hz to 150Hz and return to 10Hz Amplitude : 0.3mm (10Hz to 50Hz) Acceleration : 2G (50Hz to 150Hz) (According to IEC60068-2-6 standard)
8 Altitude It’s required to derate 1% of output current at each additional 100m. (2000m max)

Manual — Wire gauges, crimp terminals, sleeves, tools and tightening torque — page 18

Manual reference: physical PDF page 18. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Wire gauges and tighting torque

To comply with UL standards, use UL approved copper wires (rated 75° C) and round crimp terminals (UL Listed products) as shown in table below when connecting to the main circuit terminals. TECO recommends using crimp terminals manufactured by NICHIFU Terminal Industry Co., Ltd and the terminal crimping tool recommended by the manufacturer for crimping terminals and the insulating sleeve.

Wire gauges, crimp terminals, sleeves, tools and tightening torque

Wire size mm2 (AWG) / Terminal Screw size / Model of the round crimp terminal / Fastening torque kgf.cm (in.lbs) / Model of insulating sleeve / Model of crimp tool — PDF page 18

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Wire size mm2 (AWG) Terminal Screw size Model of the round crimp terminal Fastening torque kgf.cm (in.lbs) Model of insulating sleeve Model of crimp tool
2 0.75 (18) M3.5 R1.25-3.5 8.2 to 10 (7.1 to 8.7) TIC 1.25 NH 1
3 0.75 (18) M4 R1.25-4 12.2 to 14 (10.4 to 12.1) TIC 1.25 NH 1
4 1.25 (16) M3.5 R1.25-3.5 8.2 to 10 (7.1 to 8.7) TIC 1.25 NH 1
5 1.25 (16) M4 R1.25-4 12.2 to 14 (10.4 to 12.1) TIC 1.25 NH 1
6 2 (14) M3.5 R2-3.5 8.2 to 10 (7.1 to 8.7) TIC 2 NH 1 / 9
7 2 (14) M4 R2-4 12.2 to 14 (10.4 to 12.1) TIC 2 NH 1 / 9
8 2 (14) M5 R2-5 22.1 to 24 (17.7 to 20.8) TIC 2 NH 1 / 9
9 2 (14) M6 R2-6 25.5 to 30.0 (22.1 to 26.0) TIC 2 NH 1 / 9
10 3.5/5.5 (12/10) M4 R5.5-4 12.2 to 14 (10.4 to 12.1) TIC 3.5/5.5 NH 1 / 9
11 3.5/5.5 (12/10) M5 R5.5-5 20.4 to 24 (17.7 to 20.8) TIC 3.5/5.5 NH 1 / 9
12 3.5/5.5 (12/10) M6 R5.5-6 25.5 to 30.0 (22.1 to 26.0) TIC 3.5/5.5 NH 1 / 9
13 3.5/5.5 (12/10) M8 R5.5-8 61.2 to 66.0 (53.0 to 57.2) TIC 3.5/5.5 NH 1 / 9
14 8 (8) M4 R8-4 12.2 to 14 (10.4 to 12.1) TIC 8 NOP 60
15 8 (8) M5 R8-5 20.4 to 24 (17.7 to 20.8) TIC 8 NOP 60
16 8 (8) M6 R8-6 25.5 to 30.0 (22.1 to 26.0) TIC 8 NOP 60
17 8 (8) M8 R8-8 61.2 to 66.0 (53.0 to 57.2) TIC 8 NOP 60
18 14 (6) M4 R14-4 12.2 to 14 (10.4 to 12.1) TIC 14 NH 1 / 9
19 14 (6) M5 R14-5 20.4 to 24 (17.7 to 20.8) TIC 14 NH 1 / 9
20 14 (6) M6 R14-6 25.5 to 30.0 (22.1 to 26.0) TIC 14 NH 1 / 9
21 14 (6) M8 R14-8 61.2 to 66.0 (53.0 to 57.2) TIC 14 NH 1 / 9
22 22 (4) M6 R22-6 25.5 to 30.0 (22.1 to 26.0) TIC 22 NOP 60/ 150H
23 22 (4) M8 R22-8 61.2 to 66.0 (53.0 to 57.2) TIC 22 NOP 60/ 150H
24 30/38 (3 / 2) M6 R38-6 25.5 to 30.0 (22.1 to 26.0) TIC 38 NOP 60/ 150H
25 30/38 (3 / 2) M8 R38-8 61.2 to 66.0 (53.0 to 57.2) TIC 38 NOP 60/ 150H
26 50 / 60 (1 / 1/ 0) M8 R60-8 61.2 to 66.0 (53.0 to 57.2) TIC 60 NOP 60/ 150H
27 50 / 60 (1 / 1/ 0) M10 R60-10 102 to 120 (88.5 to 104) TIC 60 NOP 150H
28 70 (2/0) M8 R70-8 61.2 to 66.0 (53.0 to 57.2) TIC 60 NOP 150H
29 70 (2/0) M10 R70-10 102 to 120 (88.5 to 104) TIC 60 NOP 150H
30 80 (3/0) M10 R80-10 102 to 120 (88.5 to 104) TIC 80 NOP 150H
31 80 (3/0) M16 R80-16 255 to 280 (221 to 243) TIC 80 NOP 150H
32 100 (4/0) M10 R100-10 102 to 120 (88.5 to 104) TIC 100 NOP 150H
33 100 (4/0) M12 R100-12 143 to 157 (124 to 136) TIC 100 NOP 150H
34 100 (4/0) M16 R80-16 255 to 280 (221 to 243) TIC 80 NOP 150H

Manual — Power and control terminal torque, wiring and terminal ratings — page 19

Manual reference: physical PDF page 19. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Tighting Torque for Terminals

Specifications for terminals

Power and control terminal torque, wiring and terminal ratings

Model / TM1(Power Terminal) — PDF page 19

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Model TM1(Power Terminal) TM1(Power Terminal) TM1(Power Terminal) TM1(Power Terminal) TM1(Power Terminal)
2 Model Wiring Size Wiring Size Tighting Torque Tighting Torque Tighting Torque
3 Model AWG mm2 kgf.cm lbf.in Nm
4 Frame 1(200V) 14 2.5 9.8 8.5 0.96
5 Frame 1(400V) 14-12 2.5-10 9.8 8.5 0.96
6 Frame 2(200V) 14-12 2.5-4 18.4 15.9 1.8
7 Frame 2(400V) 14-8 2.5-10 18.4 15.9 1.8
8 Frame 3 12-6 4-16 24.5 21.2 2.4
9 Frame 4 8 10 24.5 21.2 2.4
10 Frame 5 6 16 30 26 2.9
11 Frame 6 0 50 81.7 70.7 8

Model / TM2(Control Terminal) — PDF page 19

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Model TM2(Control Terminal) TM2(Control Terminal) TM2(Control Terminal) TM2(Control Terminal) TM2(Control Terminal)
2 Model Wiring Size Wiring Size Tighting Torque Tighting Torque Tighting Torque
3 Model AWG mm2 kgf.cm lbf.in Nm
4 Frame 1~2 26~18 0.5~0.15 5.7 5 0.56
5 Frame 3~4 16 0.5~0.15 8 7 0.79
6 Frame 5~6 14 0.5~0.15 8 7 0.79

Frame size / Horsepower / Power specification / Voltage (Volt) / Current (A) — PDF page 19

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Frame size Horsepower Power specification Voltage (Volt) Current (A)
2 Frame1 0.5/1/2(-H3) 200V~240V 600 20
3 Frame1 1/2 380V~480V 600 20
4 Frame2 2(-H)/3/5 200V~240V 600 45
5 Frame2 3/5 380V~480V 600 45
6 Frame 3/4 7.5/10/15/20 200V~240V 600 100
7 Frame 3/4 7.5/10/15/20/25 380V~480V 600 65
8 Frame 5 25 200V~240V 600 100
9 Frame 5 30 380V~480V 600 75
10 Frame 6 30/40 200V~240V 600 175
11 Frame 6 40/50/60/75 380V~480V 600 175

Manual — Model-specific wiring specifications and brake circuit specifications — page 20

Manual reference: physical PDF page 20. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Wiring specifications

Brake Circuit Specifications

Independent parser superscript/order differences checked against original second rendered page; literal units and shared-model cell retained.

Model-specific wiring specifications and brake circuit specifications

Model No. / Case Frame / Total weight / Input wiring / Output wiring — PDF page 20

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Model No. Case Frame Total weight Input wiring Output wiring
2 11-301-21-2P5-30 11-301-21-201-30 Frame 1, 174 x 91 x 149 mm 1.9 kg 14 AWG (2.5 mm2) 14 AWG (2.5 mm2)
3 11-301-21-202-30 11-301-21-203-30 Frame 2, 198 x 129 x 150 mm 2.8 kg 14 – 8 AWG (2.5 – 10 mm2) 14 – 8 AWG (2.5 – 10 mm2)
4 11-301-43-401-30 11-301-43-402-30 Frame 1, 174 x 91 x 149 mm 1.9 kg 14 – 12 AWG (2.5 – 4.0 mm2) 14 – 12 AWG (2.5 – 4.0 mm2)
5 11-301-43-403-30 11-301-43-405-30 Frame 2, 198 x 129 x 150 mm 2.8 kg 14 – 8 AWG (2.5 – 10 mm2) 14 – 8 AWG (2.5 – 10 mm2)
6 11-301-43-408-30 11-301-43-410-30 11-301-43-415-30 Frame 3, 273 x 187 x 198 mm 7.1 kg 12 – 6 AWG (4.0 – 16 mm2) 12 – 6 AWG (4.0 – 16 mm2)
7 11-301-43-420-30 11-301-43-425-30 Frame 4, 400 x 236 x 261 mm 13.9 kg 8 AWG (10 mm2) 8 AWG (10 mm2)
8 11-301-43-430-30 Frame 5, 463 x 269 x 313 mm 15.56 kg 6 AWG (16 mm2) 6 AWG (16 mm2)
9 11-301-43-440-30 11-301-43-450-30 11-301-43-460-30 11-301-43-475-30 Frame 6, 653 x 289 x 364 mm 38.72 kg 0 AWG (50 mm2) 0 AWG (50 mm2)

Model / Manufacturer / Type / Rating — PDF page 20

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Model Manufacturer Type Rating
2 11-301-21-2P5-XX Bussmann 16CT 690V 16A
3 11-301-21-201- XX Bussmann 20CT 690V 20A
4 11-301-21-202- XX Bussmann 32FE 690V 32A
5 11-301-21-203- XX Bussmann 50FE 690V 50A
6 11-301-43-401- XX Bussmann 10CT 690V 10A
7 11-301-43-402- XX Bussmann 16CT 690V 16A
8 11-301-43-403- XX Bussmann 16CT 690V 16A
9 11-301-43-405- XX Bussmann 20CT 690V 20A
10 11-301-43-408- XX Bussmann 32FE 690V 32A
11 11-301-43-410- XX Bussmann 40FE 690V 40A
12 11-301-43-415- XX Bussmann 63FE 690V 63A
13 11-301-43-420- XX Bussmann 71FE 690V 71A
14 11-301-43-425- XX Bussmann 100FEa 690V 100A
15 11-301-43-430-30 Bussmann 100FEa 690V 100A
16 11-301-43-440-30 FERRAZ SHAWMUT A50QS125-4 500V 125A
17 11-301-43-450-30 FERRAZ SHAWMUT A50QS175-4 500V 175A
18 11-301-43-460-30 FERRAZ SHAWMUT A50QS200-4 500V 200A
19 11-301-43-475-30 FERRAZ SHAWMUT A50QS300-4 500V 300A

Manual — IP20/NEMA1 standard installation (a), IP20;200V0.5–1HP/400V1–2HP/200V2HP three-phase — page 21

Manual reference: physical PDF page 21. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

3.2 Installation

3.2.1 Installation method

➢ IP20 / NEMA 1 standard installation

(a) 200V 0.5HP~1HP / 400V 1HP~2HP / 200V 2HP(Three phase)

■ IP20

Step1:Remove the terminal cover

Step2:Wire & Re-install cover

Step3:Put the terminal cover back

Installation hardware illustrations accompany the explicitly transcribed numbered steps. Arrows and mechanical positions retained in original source image; no wiring topology, terminal mapping or dimension inferred. Tiny embedded keypad/hardware inscriptions are not fully readable in this overview and remain pending; numbered procedure captions are retained separately.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded keypad/hardware inscriptions remain unresolved after both full-page visual readings and a6xsourcecrop. All explicit numbered installation procedure captions and enclosure/power contexts retained. No inferred labels or wiring.

Manual — Installation (a) continued: NEMA1; scope inherited from physical21 — page 22

Manual reference: physical PDF page 22. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

■ NEMA1

Step1:Remove the terminal cover

Step2:Wire&Re-install the cover

Step3:Put the terminal cover back

Installation hardware illustrations accompany the explicitly transcribed numbered steps. Arrows and mechanical positions retained in original source image; no wiring topology, terminal mapping or dimension inferred. Tiny embedded keypad/hardware inscriptions are not fully readable in this overview and remain pending; numbered procedure captions are retained separately.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded keypad/hardware inscriptions remain unresolved after both full-page visual readings and a6xsourcecrop. All explicit numbered installation procedure captions and enclosure/power contexts retained. No inferred labels or wiring.

Manual — Installation (b) IP20;200V2HP single/three-phase,200V3–20HP,400V3–25HP — page 23

Manual reference: physical PDF page 23. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

(b) 200V 2HP(single/three phase) / 200V 3HP~20HP / 400V 3HP~25HP

■ IP20

Step1:Loosen the screws

Step2:Remove the terminal cover

Step3:Wirie&Re-install the cover Step4:Tighten the screws

Installation hardware illustrations accompany the explicitly transcribed numbered steps. Arrows and mechanical positions retained in original source image; no wiring topology, terminal mapping or dimension inferred. Tiny embedded keypad/hardware inscriptions are not fully readable in this overview and remain pending; numbered procedure captions are retained separately.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded keypad/hardware inscriptions remain unresolved after both full-page visual readings and a6xsourcecrop. All explicit numbered installation procedure captions and enclosure/power contexts retained. No inferred labels or wiring.

Manual — Installation (b) continued NEMA1; scope inherited from physical23 — page 24

Manual reference: physical PDF page 24. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

■ NEMA1

Step1:Loosen the screws

Step2:Remove the terminal cover

Step3:Wirie&Re-install the cover Step4:Tighten the screws

Installation hardware illustrations accompany the explicitly transcribed numbered steps. Arrows and mechanical positions retained in original source image; no wiring topology, terminal mapping or dimension inferred. Tiny embedded keypad/hardware inscriptions are not fully readable in this overview and remain pending; numbered procedure captions are retained separately.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded keypad/hardware inscriptions remain unresolved after both full-page visual readings and a6xsourcecrop. All explicit numbered installation procedure captions and enclosure/power contexts retained. No inferred labels or wiring.

Manual — Installation (c)200V25HP/400V30HP — page 25

Manual reference: physical PDF page 25. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

(c) 200V 25HP / 400V 30HP

Step1: Loosen the screws

Step2: Remove the terminal cover

Step3:Wirie&Re-install the cover Step4:Tighten the screws

Installation hardware illustrations accompany the explicitly transcribed numbered steps. Arrows and mechanical positions retained in original source image; no wiring topology, terminal mapping or dimension inferred. Tiny embedded keypad/hardware inscriptions are not fully readable in this overview and remain pending; numbered procedure captions are retained separately. Legible enlarged illustration branding: TECO and E510s. Other tiny key legends remain unresolved.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded keypad/hardware inscriptions remain unresolved after both full-page visual readings and a6xsourcecrop. All explicit numbered installation procedure captions and enclosure/power contexts retained. No inferred labels or wiring.

Manual — Installation (d)200V30–40HP/400V40–75HP — page 26

Manual reference: physical PDF page 26. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

(d) 200V 30HP~40HP / 400V 40HP~75HP

Step1: Loosen the screws

Step2: Remove the terminal cover

Step3:Wirie&Re-install the cover Step4:Tighten the screws

Installation hardware illustrations accompany the explicitly transcribed numbered steps. Arrows and mechanical positions retained in original source image; no wiring topology, terminal mapping or dimension inferred. Tiny embedded keypad/hardware inscriptions are not fully readable in this overview and remain pending; numbered procedure captions are retained separately. Legible enlarged illustration branding: TECO and E510s. Other tiny key legends remain unresolved.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded keypad/hardware inscriptions remain unresolved after both full-page visual readings and a6xsourcecrop. All explicit numbered installation procedure captions and enclosure/power contexts retained. No inferred labels or wiring.

Manual — Installation (e)400V20–75HP with EMC filter — page 27

Manual reference: physical PDF page 27. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

(e) 400V 20HP~75HP(with EMC filter)

Step1: Loosen the screws

Step2: Remove the terminal cover

Step3:Wirie&Re-install the cover Step4:Tighten the screws

Four mechanical installation illustrations accompany steps1–4. No wiring topology inferred. Tiny embedded keypad legends not fully legible; explicit step captions and400V20–75HP with EMC filter scope retained separately.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/model inscriptions remain partly unresolved after both full-page visual readings and enlarged bounded crops. Explicit callouts, mechanical instructions, legible labels and source context retained; no inferred terminal labels or topology.

Manual — Frame1 installation clearances and side-by-side ventilation — page 28

Manual reference: physical PDF page 28. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

3.2.2 Installation space

Provide sufficient air circulation space for cooling as shown in examples below. Install the Inverter on surfaces that provide good heat dissipation。 Frame1 models:2P5/201/202(three phase)/401/402

Side by side installation: Provide te necessary physical space and cooling based on the ambient temperature and the heat loss in the panel.(2P5/201/202/401/402)

Frame1 models2P5/201/202(threephase)/401/402. Front view clearances:12cm above,12cm below,5cm left,5cm right; Distributor inside. Side view:Distributor inside, airflow arrows. Cooling fan icon. Front illustration label1PH-220V-0.75kW; DANGER:Cut off the power and wait for5minutes before inspecting components. CAUTION:See manual before operation. Keypad key labels remain partly unresolved; no model applicability inferred from illustration label.

Side-by-side illustration:Operator panel;5cm between two shown drives; airflow arrows; note twin-ellipse symbol means cooling fan. Source prose requires physical space/cooling according to ambient temperature and panel heat loss. Embedded tiny keypad labels remain partly unresolved.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/model inscriptions remain partly unresolved after both full-page visual readings and enlarged bounded crops. Explicit callouts, mechanical instructions, legible labels and source context retained; no inferred terminal labels or topology.

Manual — External view IP20/NEMA1:200V0.5–1HP,400V1–2HP,200V2HP3PH — page 29

Manual reference: physical PDF page 29. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

3.2.3 External View

3.2.3.1 IP20/NEMA 1

(a) 200V 0.5HP~1HP / 400V 1HP~2HP / 200V 2HP(3PH)

■ IP20

■ NEMA1

IP20 external view labels:Mounting hole,Heat sink,Name plate label,Fan cover,Digital operator,Terminal cover. Keypad visible legends:FWD/REV,DISP/FUN,RESET,READ/ENTER,RUN,STOP,FREQ.SET; up/down and left-arrow symbols. Small indicator legends and hardware inscriptions remain partly unresolved. No terminal mapping inferred.

NEMA1 external view labels:Mounting hole,Heat sink,Name plate label,Fan cover,Digital operator,Terminal cover,NEMA kit. Keypad visible legends:FWD/REV,DISP/FUN,RESET,READ/ENTER,RUN,STOP,FREQ.SET; up/down and left-arrow symbols. Small indicator legends and hardware inscriptions remain partly unresolved. No terminal mapping inferred.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/model inscriptions remain partly unresolved after both full-page visual readings and enlarged bounded crops. Explicit callouts, mechanical instructions, legible labels and source context retained; no inferred terminal labels or topology.

Manual — External view IP20/NEMA1:200V2HP1/3PH,200V3–20HP,400V3–25HP — page 30

Manual reference: physical PDF page 30. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

(b) 200V 2HP(1/3PH) / 200V 3HP~20HP / 400V 3HP~25HP

■ IP20

■ NEMA1

IP20 external view labels:Mounting hole,Heat sink,Name plate label,Fan cover,Digital operator,Terminal cover. Keypad visible legends:FWD/REV,DISP/FUN,RESET,READ/ENTER,RUN,STOP,FREQ.SET; up/down and left-arrow symbols. Small indicator legends and hardware inscriptions remain partly unresolved. No terminal mapping inferred.

NEMA1 external view labels:Mounting hole,Heat sink,Name plate label,Fan cover,Digital operator,Terminal cover,NEMA1 kit. Keypad visible legends:FWD/REV,DISP/FUN,RESET,READ/ENTER,RUN,STOP,FREQ.SET; up/down and left-arrow symbols. Small indicator legends and hardware inscriptions remain partly unresolved. No terminal mapping inferred.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/model inscriptions remain partly unresolved after both full-page visual readings and enlarged bounded crops. Explicit callouts, mechanical instructions, legible labels and source context retained; no inferred terminal labels or topology.

Manual — Component identification, figures(c) and(d) — page 31

Manual reference: physical PDF page 31. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Caption associations preserved per figure. No physical dimensions, mounting-hole geometry or dimensions inferred from drawings. Original remains authoritative for component locations.

Labels for figure(c) only; applicability is the printed caption, not the full product range.

Labels for figure(d) only; source explicitly labels4rings. No weight/lifting-capacity inference.

Figure(c):200V25HP /400V30HP — PDF page 31

Source row Source label/context Source value
1 Printed applicability (c) 200V 25HP / 400V 30HP
2 Component Anti-dust cover
3 Component Front cover
4 Component Digital operator
5 Component Terminal cover
6 Component Mounting hole
7 Component Name plate label

Figure(d):200V30HP–40HP /400V40HP–75HP — PDF page 31

Source row Source label/context Source value
1 Printed applicability (d) 200V 30HP~40HP / 400V 40HP~75HP
2 Component Front cover
3 Component Digital operator
4 Component Terminal cover
5 Component Mounting hole
6 Component Rings(4 rings)
7 Component Name plate label

Manual — Interior layouts (a)/(b); literal component and keypad labels — page 32

Manual reference: physical PDF page 32. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh 6x first interior-view crop resolves the separate illustration inscription 200V 0.75KW. The adjacent model string and small control-terminal labels remain obscured by dashed callout lines; do not assign the inscription to every model in the heading.

■ Interior layout

(a) 200V 0.5HP~1HP / 400V 1HP~2HP / 200V 2HP(three phase)

(b) 200V 2HP(single/three) / 200V 3HP~20HP / 400V 3HP~25HP

(a)200V0.5–1HP/400V1–2HP/200V2HPthreephase interior figure:Operator panel,RJ45communication port,TM2terminal,TM1terminal,Ground terminal. Keypad labels Hz/RPM,FWD,REV,FUN; FWD/REV,DISP/FUN,RESET,READ/ENTER,RUN,STOP,FREQ.SET and arrow symbols. Legible main terminal labelsL1,L2,L3,T1,T2,T3,P,BR,ground symbols. Illustration nameplate/model and tiny control-terminal inscriptions remain partly unresolved; do not infer connections or applicability.

(b)200V2HPsingle/three,200V3–20HP,400V3–25HP interior figure:Operator panel,RJ45communication port,TM2terminal,TM1terminal,Ground terminal. Keypad labels Hz/RPM,FWD,REV,FUN; FWD/REV,DISP/FUN,RESET,READ/ENTER,RUN,STOP,FREQ.SET and arrow symbols. Legible main terminal labelsL1,L2,L3,T1,T2,T3,P,BR,ground symbols. Illustration nameplate/model and tiny control-terminal inscriptions remain partly unresolved; do not infer connections or applicability.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/model inscriptions remain partly unresolved after both full-page visual readings and enlarged bounded crops. Explicit callouts, mechanical instructions, legible labels and source context retained; no inferred terminal labels or topology.

200V 0.75KW

Manual — Interior layouts(c)/(d) and size-specific English/French warning labels — page 33

Manual reference: physical PDF page 33. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

(c) 200V 25HP / 400V 30HP (d) 200V 30HP~40HP / 400V 40HP~75HP

■ Warning label

(a) 200V 0.5HP~20HP / 400V 1HP~25HP

(b) 200V 25HP~40HP / 400V 30HP~75HP

Interior layout(c)200V25HP/400V30HP and(d)200V30–40HP/400V40–75HP. Common callouts:Operator panel,RJ45communication port,TM2terminal,TM1terminal,Ground terminal. TECO and E510s keypad branding. Tiny embedded terminal/keypad inscriptions unresolved; no wiring inferred.

Warning label(a)200V0.5–20HP/400V1–25HP:WARNING/AVERTISSEMENT. Risk of electrical shock. Shut off main power and wait for5minutes before servicing. Risque de choc électrique. Coupez l'alimentation principale et attendre5minutes avant l'entretien. Hot surface. Risk of burn./Surface chaude. Risque de brûlure. CAUTION/ATTENTION. See manual before operation./Consultez le manuel avant l'opération.

Warning label(b)200V25–40HP/400V30–75HP:WARNING/AVERTISSEMENT. Risk of electrical shock. Shut off main power and wait for15minutes before servicing. Risque de choc électrique. Coupez l'alimentation principale et attendre15minutes avant l'entretien. CAUTION/ATTENTION. See manual before operation./Consultez le manuel avant l'opération.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/model inscriptions remain partly unresolved after both full-page visual readings and enlarged bounded crops. Explicit callouts, mechanical instructions, legible labels and source context retained; no inferred terminal labels or topology. Both English/French warning labels were enlarged and fully transcribed; the partial scope concerns interior hardware illustrations only.

Manual — Power cables and dedicated/shared power-source figures — page 34

Manual reference: physical PDF page 34. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3 Wiring Guidelines

3.3.1. Power cables:

➢ L1(L)、L2、L3(N) for three phase input models. ➢ L1(L) and L3(N) for single phase input models. (L2 terminal will be removed) ➢ Motor cable must be connected T1, T2, T3 of TM1 terminals.

Power cables should be selected by the following conditions: ➢ Only can use copper wires, and the diameter needs to use 105 degrees Celsius level. ➢ The minimum power cable rated voltage level of 240V system is 300V. ➢ For the safety, power cables should be connected by “O” type terminal.

Warning

Connection of supply line cable to terminals T1,T2, T3 will result in serious damage to the drive components. Power cables should be separated with the other high voltage and high current cables to prevent the noise intereference, please refer the photo below:

➢ Inverter with dedicated power line

➢ Install a supply RFI filter or Isolation transformer when the power source is shared with other high power electrical equipment as shown below

Dedicated power line figure labels:Power,MCCB,Inverter,IM. Source drawing retained; no inferred wiring topology.

Shared source and supply RFI-filter figure labels:Power,MCCB,RFI Filter,Inverter,IM,Machine. Source drawing retained; no inferred wiring topology.

Shared source and transformer figure labels:Power,MCCB,Inverter,IM,Insulation transformer,Machine. Source drawing retained; no inferred wiring topology.

Manual — Control cable selection and shielding — page 35

Manual reference: physical PDF page 35. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3.2 Control cable selection and wiring

Control cables should be connected to terminal block TM2, Choose power & Control cables according to the following criteria: ➢ Use copper wires with correct diameter and temperature rating of 65/70°C ➢ Minimum cable voltage rating for 200V type inverters should be 300VAC. Minimum cable voltage rating for 400V type inverters should be 600VAC ➢ Route all cables away from other high voltage or high current power lines to reduce interference effects。 ➢ Use a twisted pair shielded cable and connect the shield (screen) wire to the ground terminal at the inverter end only. Cable length should not exceed 50 meters

Cable illustration labels:Shielding sheath;Protective covering;Connect the shield to inverter ground terminal;Do not connect this end. Preserve original arrows; no inferred wiring. Prose explicitly requires screen grounded at inverter end only and maximum50metres.

Manual — Wiring and EMC guidelines with numbered component legend — page 36

Manual reference: physical PDF page 36. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3.3. Wiring and EMC guidelines

➢ For effective interference suppression, do not route power and control cables in the same conduit or trunking ➢ To prevent radiated noise, motor cable should be put in a metal Conduit. Alternatively an armored or shielded type motor cable should be used ➢ Motor cable and signal lines of other control equipment should be at the least 30 cm apart ➢ For effective suppression of noise emissions the cable armor or shield must be grounded at both ends to the motor and the inverter ground. These connections should be as short as possible

  1. Protective Earth Conductor. Conductor size for

enclosure & Back plate must comply with the

local electrical standards. Min 10mm²

  1. Back plate. Galvanised steel (Unpainted)

  2. Ferrite core / Output reactor ferrite cores can

be used to reduce radiated noise due to long

motor cables. If ferrite core is used loop motor

wires, 3 times round the core. Install core as

close to the inverter as possible. Output

reactors provide additional benefit of reducing

dv/dt for protection of motor windings.)

  1. Metal Cable clamp. no more than 150mm from

the inverter.

Note:

If no enclosure & back plate is used then connect

the cable shield by a good 360 degree termination

to the Inverter output terminal E.

  1. Screened (Shielded four core cable)

  2. Separate Protective Earth wire, routed outside

motor cable separated be at least 100mm.

This is the preferred method specially for large

output cables and long length.

Multi-core screened (3 core & protective earth)

can be used for small power and short length

  1. Connect the cable shield by a good 360º

termination and connect to the motor

protective earth terminal. This link must be as

short as possible.

  1. Motor Earth terminal(Protective Earth)

EMC figure labels:L1(L),L3(N),E;Drive input labelsL1,L2,E;output labelsT1,T2,T3,E;M. Circled1–8 refer to adjacent original numbered legend. Preserve figure without correcting L3(N)/L2 mismatch or inferring wiring.

Manual — Supplier failure-liability conditions — page 37

Manual reference: physical PDF page 37. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3.4. Failure liability

Teco bears no responsibility for any failures or damaged caused to the inverter if the recommendations in this instruction manual have not been followed specifically points listed below: ➢ If a correctly rated Fuse or Circuit breaker has not been installed between the power source and the inverter. ➢ If a magnetic contactor, a phase capacitor, burst absorber and LC or RC circuits have been connected between the inverter and the motor. ➢ If an incorrectly rated three-phase squirrel cage induction motor has been used ➢ When one inverter is driving several motors, the total current of all motors running simultaneously must be less than the rated current of the inverter, and each motor has to be equipped with a correctly rated thermal overload relay. ➢ “Only Intended For Use In A Pollution Degree 2 Environment” or equivalent. ➢ Since there is no over speed protection there will be no liablity due to overspeed damage.

Manual — Peripheral equipment and phase-voltage formula — page 38

Manual reference: physical PDF page 38. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3.5 Considerations for peripheral equipment

Peripheral component images correspond to adjacent table rows:power,circuitbreaker/RCD,magneticcontactor,ACreactor,inputnoisefilter,inverter,motor. Two Ground labels;no inferred additional ratings or topology.

Formula correction: visually drawn √ before3 restored; both text parsers omitted the radical. This is source transcription only, not engineering validation.

Peripheral equipment and phase-voltage formula

Power / Ensure that the supply voltage is correct. A molded-case circuit breaker or fused disconnect must be installed between the AC source and the inverter — PDF page 38

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Power Ensure that the supply voltage is correct. A molded-case circuit breaker or fused disconnect must be installed between the AC source and the inverter
2 Circuit Breaker & RCD Use a molded-case circuit breaker that conforms to the rated voltage and current of the inverter. Do not use the circuit breaker as the run/stop switch for the inverter. Residual Current Circuit Breaker(RCD) Current setting should be 200mA or above and the operating time at 0.1 second or longer to prevent malfunctions.
3 Magnetic contactor Normally a magnetic contactor is not needed. A contactor can be used to perform functions such as external control and auto restart after power failure. Do not use the magnetic contactor as the run/stop switch of the inverter.
4 AC reactor for power quality improvement When a 200V/400V inverter with rating below 15KW is connected to a high capacity power source (600KVA or above) then an AC reactor can be connected for power factor improvement and reducing harmonics.
5 Input noise filter E510s has a built-in filter (Class A/First Environment Category C2, except for Frame 4) To satisfy the required EMC regulations for your specific application you may require an additional EMC filter.
6 Inverter Connect the single phase power to Terminals, L1(L) & L3(N). Warning! Connecting the input terminals T1, T2, and T3 to AC input power will damage the inverter. Output terminals T1, T2, and T3 are connected to U, V, and W terminals of the motor. To reverse the motor rotation direction just swap any two wires at terminals T1, T2, and T3. Ground the Inverter and motor correctly. Ground Resistance for 200V have to less than 100 Ohms. Ground Resistance for 400V have to less than 10 Ohms
7 Motor Three-phase induction motor. Voltage drop on motor due to long cable can be calculated, volts drop should be less than 10%. The formula of Phase-to-phase voltage drop is (V) = √3 ×resistance of wire (Ω/km)×length of line(m)×current×10-3

Manual — Ground connections, voltage-drop formula and carrier/cable-length table — page 39

Manual reference: physical PDF page 39. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

3.3.6 Ground connection

Inverter ground terminal must be connected to installation ground correctly and according to the required local wiring regulations ➢ Ground cable size must be according to the required local wiring regulations. Ground connection should be as short as possible ➢ Do not share the ground of the inverter with other high current loads (Welding machine, high power motors). Ground each unit separately ➢ Ensure that all ground terminals and connections are secure ➢ Do not make ground loops when several inverters share a common ground point. Please leave at least 5cm while installing inverter side by side in order to provide enough cooling space.

➢ Input power cable length The length of the cables between the power source and/or the motor and inverter can casue a significant phase to phase voltage reduction due to the voltage drop across the cables. The maximum voltage drop is 2%, if this value is exceeded, a wire size having large diameter is needed. To calculate phase to phase voltage drop by the following formula. Phase-to-phase voltage drop(V)=

➢ Installing an AC line reactor If the inverter is connected to a large-capacity power source (600kVA or more), install an optional AC reactor on the input side of the inverte, it can improve the power factor on the power supply side. ➢ Cable length & Carrier frequency The followable setting of the PWM carrier frequency is also determined by motor cable length and is specified in the following table.

※ The minimum carrier frequency of SLV control mode is 4K, please confirm the cable length.

Ground examples labelled(a)Corrent,(b)Correct,(c)Incorrect, as printed; retain original topology image without deriving connection instructions. TECO/E510s branding; tiny embedded warning/keypad inscriptions unresolved.

Displayed phase-to-phase voltage drop(V)=√3 × resistance of wire(Ω/km) × length of line(m) × current(A) ×10^-3. Formula literal source transcription, not engineering validation.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/model inscriptions remain partly unresolved after both full-page visual readings and enlarged bounded crops. Explicit callouts, mechanical instructions, legible labels and source context retained; no inferred terminal labels or topology.

Ground connections, voltage-drop formula and carrier/cable-length table

Cable length of motor in m (ft.) / <30m (100) / 30m ~ 50m (100~165) / 50m ~100m (166~328) / ≧100m (329) — PDF page 39

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Cable length of motor in m (ft.) <30m (100) 30m ~ 50m (100~165) 50m ~100m (166~328) ≧100m (329)
2 Recommanded carrier frequenc allowed parameter 11-01 16kHz(max) 10kHz(max) 5kHz(max) 2kHz(max)

Manual — Voltage-type single/multi-pump diagrams; see continuation41–42 for notes — page 40

Manual reference: physical PDF page 40. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3.7 Single / Multi Pump Dedicated Wiring Diagram PUMP Wiring Diagram for Pressure Sensor of Voltage Type Single Pump:

Multi-Pump:

E510s Single Pump Operation.00-02=1(Control Circuit Terminal);04-00=0(0~10V);10-00=0(Target Source:KeyPad);10-01=2(Feedback Source:AI2);10-03=XXX1B(PID is enabled);23-00=1(PUMP);23-01=0(Single Pump). TM2 terminal label rows:upper R2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2;lower(S+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. Operation Switch;Pressure Converter. JP1 NPN/PNP marker atNPN;JP3 I/V marker atV. Pressure converter + and - marks. Diagram labels and displayed switch positions only; no inferred wiring. Continuation notes on41–42 retained.

E510s Multi-Pump Operation:Master.00-02=1(Control Circuit Terminal);04-00=0(0~10V);10-00=0(Target Source:KeyPad);10-01=2(Feedback Source:AI2);10-03=XXX1b(PID is enbaled);23-00=1(PUMP);23-01=1(Master). TM2 terminal label rows:upper R2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2;lower(S+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. CON2 port;A,B labels. Settings are literal source; retain notes1–5on41–42; no inferred wiring.

E510s Multi-Pump Operation:Follower1.00-02=1(Control Circuit Terminal);04-00=0(0~10V);10-00=0(Target Source:KeyPad);10-01=2(Feedback Source:AI2);10-03=XXX1b(PID is enbaled);23-00=1(PUMP);23-01=2(Follower1). TM2 terminal label rows:upper R2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2;lower(S+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. CON2 port;A,B labels. Settings are literal source; retain notes1–5on41–42; no inferred wiring.

E510s Multi-Pump Operation:Follower2.00-02=1(Control Circuit Terminal);04-00=0(0~10V);10-00=0(Target Source:KeyPad);10-01=2(Feedback Source:AI2);10-03=XXX1b(PID is enbaled);23-00=1(PUMP);23-01=3(Follower2). TM2 terminal label rows:upper R2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2;lower(S+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. CON2 port;A,B labels. Settings are literal source; retain notes1–5on41–42; no inferred wiring.

E510s Multi-Pump Operation:Follower3.00-02=1(Control Circuit Terminal);04-00=0(0~10V);10-00=0(Target Source:KeyPad);10-01=2(Feedback Source:AI2);10-03=XXX1b(PID is enbaled);23-00=1(PUMP);23-01=4(Follower3). TM2 terminal label rows:upper R2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2;lower(S+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. CON2 port;A,B labels. Settings are literal source; retain notes1–5on41–42; no inferred wiring.

Multi-pump voltage schematic:JP1 NPN/PNP marker atNPN;SW2 heading aboveJP3 I/V marker atV. Operation Switch;Pressure Converter +,- marks. All coloured lines and junctions retained only in original; no inferred topology. Card settings separately bounded. Read all continuation notes through42.

Manual — Current-type single/multi-pump diagrams and notes1–2; continuation42 mandatory — page 41

Manual reference: physical PDF page 41. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

PUMP Wiring Diagram for PressureSensor of Current Type

Single Pump:

Multi-Pump:

Notes1: The position of dip switch requires being correct (JP1,JP3), it is required to reconnect

the power after setting Master/Slave.

Notes2: When the communication modes is selected to be multiple pumps in parallel

connection (09-01=3), the baud rate settings 09-02 of Master and Slave are required

to be consistent.

E510s Single Pump Operation.00-02=1(Control Circuit Terminal);04-00=1(4~20mA);10-00=0(Target Source:KeyPad);10-01=2(Feedback Source:AI2);10-03=XXX1B(PID is enabled);23-00=1(PUMP);23-01=0(Single Pump). TM2 terminal label rows:upper R2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2;lower(S+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. Operation Switch;Pressure Converter. JP1 NPN/PNP marker atNPN;JP3 I/V marker atI. AI2 closing character in source is malformed. Diagram labels and displayed switch positions only; no inferred wiring. Continuation notes on41–42 retained.

E510s Multi-Pump Operation:Master.00-02=1(Control Circuit Terminal);04-00=1(4~20mA);10-00=0(Target Source:KeyPad);10-01=2(Feedback Source:AI2);10-03=XXX1b(PID is enbaled);23-00=1(PUMP);23-01=1(Master). TM2 terminal label rows:upper R2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2;lower(S+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. CON2 port;A,B labels. Settings are literal source; retain notes1–5on41–42; no inferred wiring.

E510s Multi-Pump Operation:Follower1.00-02=1(Control Circuit Terminal);04-00=1(4~20mA);10-00=0(Target Source:KeyPad);10-01=2(Feedback Source:AI2);10-03=XXX1b(PID is enbaled);23-00=1(PUMP);23-01=2(Follower1). TM2 terminal label rows:upper R2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2;lower(S+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. CON2 port;A,B labels. Settings are literal source; retain notes1–5on41–42; no inferred wiring.

E510s Multi-Pump Operation:Follower2.00-02=1(Control Circuit Terminal);04-00=1(4~20mA);10-00=0(Target Source:KeyPad);10-01=2(Feedback Source:AI2);10-03=XXX1b(PID is enbaled);23-00=1(PUMP);23-01=3(Follower2). TM2 terminal label rows:upper R2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2;lower(S+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. CON2 port;A,B labels. Settings are literal source; retain notes1–5on41–42; no inferred wiring.

E510s Multi-Pump Operation:Follower3.00-02=1(Control Circuit Terminal);04-00=1(4~20mA);10-00=0(Target Source:KeyPad);10-01=2(Feedback Source:AI2);10-03=XXX1b(PID is enbaled);23-00=1(PUMP);23-01=4(Follower3). TM2 terminal label rows:upper R2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2;lower(S+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. CON2 port;A,B labels. Settings are literal source; retain notes1–5on41–42; no inferred wiring.

Multi-pump current schematic:Master JP1 NPN/PNP marker atNPN,JP3 I/V marker atI;Follower JP1 NPN/PNP marker atNPN,JP3 I/V marker atV. Operation Switch;Pressure Converter. All coloured lines and junctions retained only in original; no inferred topology. Card settings separately bounded. Read all continuation notes through42.

Manual — Continuation of pump wiring notes3–5 from40–41 — page 42

Manual reference: physical PDF page 42. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Notes3: Refer to parameter 23-31 for the actions in parallel connection modes.

Notes4: In the wiring of multi-pump current type pressure sensor, it is required to adjust

Slave to be 04-07=252.0% and 04-08=-25.0%

Notes5: In multi-pump operation, if one of the inverter does not Power ON, the 24V of

connection is also need to disconnect to avoid magnetoresistance effect.

Manual — 200V product specifications; single/single-three/three phase and single-phase derating note — page 43

Manual reference: physical PDF page 43. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.4 Specifications 3.4.1 Product specifications

200V Class:Single phase

200V Class:Single/Three phase

200V Class:Three phase (If connected to single-phase input, the output current must not exceed 50% of the rated current)

200V product specifications; single/single-three/three phase and single-phase derating note

Model:E510-□□□-SH1F / 2P5 / 201 / 202 / 203 — PDF page 43

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Model:E510-□□□-SH1F 2P5 201 202 203
2 Horse power (HP) 0.5 1 2 3
3 Suitable motor capacity (KW) 0.4 0.75 1.5 2.2
4 Rated output current (A) 3.1 4.5 7.5 10.5
5 Rated capacity (KVA) 1.2 1.7 2.90 4.00
6 Input voltage range(V) Single phase:200~240V, 50/60Hz Single phase:200~240V, 50/60Hz Single phase:200~240V, 50/60Hz Single phase:200~240V, 50/60Hz
7 Allowable voltage fluctuation -15%~+10% -15%~+10% -15%~+10% -15%~+10%
8 Output voltage range(V) Three phase:0~240V Three phase:0~240V Three phase:0~240V Three phase:0~240V
9 Input current (A)* 8.5 12 16 23.9
10 Inverter net weight (KG) 1.5 1.5 2.0 2.0
11 Allowable momentary power loss time(s) 2.0 2.0 2.0 2.0
12 Enclosure IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1

Model:E510-□□□-SH / 2P5 / 201 / 202 / 203 — PDF page 43

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Model:E510-□□□-SH 2P5 201 202 203
2 Horse power (HP) 0.5 1 2 3
3 Suitable motor capacity (KW) 0.4 0.75 1.5 2.2
4 Rated output current (A) 3.1 4.5 7.5 10.5
5 Rated capacity (KVA) 1.2 1.7 2.90 4.00
6 Input voltage range(V) Single/Three:200~240V, 50/60Hz Single/Three:200~240V, 50/60Hz Single/Three:200~240V, 50/60Hz Single/Three:200~240V, 50/60Hz
7 Allowable voltage fluctuation -15%~+10% -15%~+10% -15%~+10% -15%~+10%
8 Output voltage range(V) Three phase:0~240V Three phase:0~240V Three phase:0~240V Three phase:0~240V
9 Input current (A)* 8.5/4.5 12/6.5 16/11 23.9/12.5
10 Inverter net weight (KG) 1.5 1.5 2.0 2.0
11 Allowable momentary power loss time(s) 2.0 2.0 2.0 2.0
12 Enclosure IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1

Model:E510-□□□-SH3 / 202 / 205 / 208 / 210 / 215 / 220 — PDF page 43

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Model:E510-□□□-SH3 202 205 208 210 215 220
2 Horse power (HP) 2 5 7.5 10 15 20
3 Suitable motor capacity (KW) 1.5 4 5.5 7.5 11 15
4 Rated output current (A) 7.5 17.5 26 35 48 64
5 Rated capacity (KVA) 2.9 6.7 9.9 13.3 20.6 27.4
6 Input voltage range(V) Three phase:200~240V,50/60Hz Three phase:200~240V,50/60Hz Three phase:200~240V,50/60Hz Three phase:200~240V,50/60Hz Three phase:200~240V,50/60Hz Three phase:200~240V,50/60Hz
7 Allowable voltage fluctuation -15%~+10% -15%~+10% -15%~+10% -15%~+10% -15%~+10% -15%~+10%
8 Output voltage range(V) Three phase:0~240V Three phase:0~240V Three phase:0~240V Three phase:0~240V Three phase:0~240V Three phase:0~240V
9 Input current (A)* 11 20.5 33 42 57 70
10 Inverter net weight (KG) 1.5 2.0 6.0 6.0 10.0 10.0
11 Allowable momentary power loss time(s) 2.0 2.0 2.0 2.0 2.0 2.0
12 Enclosure IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1

Manual — 200V higher-power and400V specifications; preserve HD/ND, filter weight and model columns — page 44

Manual reference: physical PDF page 44. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

400V Class:Three phase

200V higher-power and400V specifications; preserve HD/ND, filter weight and model columns

Model:E510-□□□-SH3 / 225 / 230 / 240 — PDF page 44

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Model:E510-□□□-SH3 225 230 240
2 Horse power (HP) 25 30 40
3 HD/ND Suitable motor capacity (kW) 18.5/22 22/30 30/37
4 HD/ND Rated output current (A) 73/80 85/110 115/138
5 HD/ND Rated capacity (KVA) 27.8/30.1 32.4/41.9 43.8/52.6
6 Input voltage range(V) Three phase:200~240V,50/60Hz Three phase:200~240V,50/60Hz Three phase:200~240V,50/60Hz
7 Allowable voltage fluctuation -15%~+10% -15%~+10% -15%~+10%
8 Output voltage range(V) Three phase:0~240V Three phase:0~240V Three phase:0~240V
9 Input current (A)* 79.4/85.9 92.4/119.6 125/150
10 Inverter net weight (KG) 10.0 23.2 23.2
11 Allowable momentary power loss time(s) 2.0 2.0 2.0
12 Enclosure IP20/NEMA1 IP20/NEMA1 IP20/NEMA1

Model:E510-□□□-SH3(F) / 401 / 402 / 403 / 405 — PDF page 44

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Model:E510-□□□-SH3(F) 401 402 403 405
2 Horse power (HP) 1 2 3 5
3 Suitable motor capacity (KW) 0.75 1.5 2.2 4.0
4 Rated output current (A) 2.5 3.8 5.3 9.2
5 Rated capacity (KVA) 1.7 2.9 4.0 6.7
6 Input voltage range(V) Three phase:380~480V,50/60Hz Three phase:380~480V,50/60Hz Three phase:380~480V,50/60Hz Three phase:380~480V,50/60Hz
7 Allowable voltage fluctuation -15%~+10% -15%~+10% -15%~+10% -15%~+10%
8 Output voltage range(V) Three phase:0~480V Three phase:0~480V Three phase:0~480V Three phase:0~480V
9 Input current (A)* 4.2 5.6 7.3 11.6
10 Inverter net weight (KG) 1.5 1.5 2.0 2.0
11 Inverter net weight(with Filter) (KG) 1.58 1.58 2.2 2.2
12 Allowable momentary power loss time(s) 2.0 2.0 2.0 2.0
13 Enclosure IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1

Model:E510-□□□-SH3(F) / 408 / 410 / 415 / 420 / 425 — PDF page 44

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Model:E510-□□□-SH3(F) 408 410 415 420 425
2 Horse power (HP) 7.5 10 15 20 25
3 Suitable motor capacity (KW) 5.5 7.5 11 15 18.5
4 Rated output current (A) 13.0 17.5 24 32 40
5 Rated capacity (KVA) 9.9 13.3 19.1 24 30.5
6 Input voltage range(V) Three phase:380~480V,50/60Hz Three phase:380~480V,50/60Hz Three phase:380~480V,50/60Hz Three phase:380~480V,50/60Hz Three phase:380~480V,50/60Hz
7 Allowable voltage fluctuation -15%~+10% -15%~+10% -15%~+10% -15%~+10% -15%~+10%
8 Output voltage range(V) Three phase:0~480V Three phase:0~480V Three phase:0~480V Three phase:0~480V Three phase:0~480V
9 Input current (A)* 17 23 31 38 48
10 Inverter net weight (KG) 6.0 6.0 6.0 10.0 10.0
11 Inverter net weight(with Filter) (KG) 6.5 6.5 18.0 18.0 22.0
12 Allowable momentary power loss time(s) 2.0 2.0 2.0 2.0 2.0
13 Enclosure IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1

Manual — 400V high-power HD/ND specifications and carrier-range table; note6continues46 — page 45

Manual reference: physical PDF page 45. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Notes: 1. Take standard 4-poles induction motor as the base. 2. E510s model is designed to use inheavy duty conritions, the factory setting is HD (Heavy Duty type) mode. 3. The overload capacity of E510s model HD (Heavy Duty) is 150%/1min, 200%/2sac. See the table below for the carrier frequency default setting and range. 4. The overload capacity of E510s model ND (Normal Duty) is 120%/1min, carrier frequency range is 1kHz~16kHz, the default setting is 2kHz. 5. If the carrier frequency is greater than default, it need to adjust the load current based on the de-rating curve.

400V high-power HD/ND specifications and carrier-range table; note6continues46

Model:E510-□□□- SH3(F) / 430 / 440 — PDF page 45

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Model:E510-□□□- SH3(F) 430 440
2 Horse power (HP) 30 40
3 HD/ND Suitable motor capacity (kW) 22/30 30/37
4 HD/ND Rated output current (A) 45/58 60/73
5 HD/ND Rated capacity (KVA) 34.3/44.2 45.7/55.6
6 Input voltage range(V) Three phase : 380~480V,50/60Hz Three phase : 380~480V,50/60Hz
7 Allowable voltage fluctuation +10%-15% +10%-15%
8 Output voltage range(V) Three phase : 0~480V Three phase : 0~480V
9 Input current (A)* 48.9/63 65.2/78.3
10 Inverter net weight (KG) 10.0 23.2
11 Inverter net weight(with Filter) (KG) 42.5 42.5
12 Allowable momentary power loss time(s) 2.0 2.0
13 Enclosure IP20/NEMA1 IP20/NEMA1

Model:E510-□□□- SH3(F) / 450 / 460 / 475 — PDF page 45

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Model:E510-□□□- SH3(F) 450 460 475
2 Horse power (HP) 50 60 75
3 HD/ND Suitable motor capacity (kW) 37/45 45/55 55/75
4 HD/ND Rated output current (A) 75/88 91/103 118/145
5 HD/ND Rated capacity (KVA) 57.2/67.1 69.3/78.5 89.9/111
6 Input voltage range(V) Three phase : 380~480V,50/60Hz Three phase : 380~480V,50/60Hz Three phase : 380~480V,50/60Hz
7 Allowable voltage fluctuation +10%-15% +10%-15% +10%-15%
8 Output voltage range(V) Three phase : 0~480V Three phase : 0~480V Three phase : 0~480V
9 Input current (A)* 81.5/95.7 98.9/112 130/159
10 Inverter net weight (KG) 23.2 23.2 23.2
11 Inverter net weight(with Filter) (KG) 42.5 42.5 42.5
12 Allowable momentary power loss time(s) 2.0 2.0 2.0
13 Enclosure IP20/NEMA1 IP20/NEMA1 IP20/NEMA1

Inverter voltage and capacity / HD mode carrier frequency range / ND mode carrier frequency range — PDF page 45

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Inverter voltage and capacity Inverter voltage and capacity HD mode carrier frequency range HD mode carrier frequency range HD mode carrier frequency range ND mode carrier frequency range
2 200V Class 400V Class V/F SLV PMSLV ND mode carrier frequency range
3 1~20HP 1~25HP 1~16kHz 4~16kHz 4~8kHz 5kHz
4 ⟦blank source cell⟧ 30HP 1~16kHz 4~16kHz(6) 4~8kHz 5kHz
5 25~40HP 40~50HP 1~12kHz 4~12kHz(6) 4~8kHz 5kHz
6 ⟦blank source cell⟧ 60~75HP 1~10kHz 4~10kHz 4~8kHz 5kHz

Manual — Continuation note6; control-mode/duty frequency limits and model electrical ratings — page 46

Manual reference: physical PDF page 46. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

  1. If control mode (00-00) is set to 2 (SLV mode) and maximum frequency (01-02) is larger than 80Hz, the carrier frequency range is 2~8kHz.

The following table shows maximum output frequency for each control mode.

➢ For 11-301-43-430/40/50/60/75-30, these models have two operation modes for setting. ➢ N.D:Normal Duty operation mode. H.D:Heavy Duty operation mode.

Continuation note6; control-mode/duty frequency limits and model electrical ratings

Duty Cycle / Control Mode / Other Setings / Max. Output Frequency — PDF page 46

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Duty Cycle Control Mode Other Setings Max. Output Frequency
2 Heavy Duty (00-27=0) V/F Maximum output frequency is 599Hz 599Hz
3 Heavy Duty (00-27=0) SLV 200V 1~10HP, 400V 1~15HP 150Hz
4 Heavy Duty (00-27=0) SLV 200V 15~20HP, 400V 20HP 110Hz
5 Heavy Duty (00-27=0) SLV 400V 25HP 100Hz
6 Heavy Duty (00-27=0) SLV 200V 25~40HP, 400V 30~75HP, carrier (11-01) is set as 8K or below 8K 100Hz
7 Heavy Duty (00-27=0) SLV 200V 25~40HP, 400V 30~75HP, carrier (11-01) is above 8K 80Hz
8 Heavy Duty (00-27=0) PMSLV Please refer parameter group 22 of chapter 4.3 (PM motor parameter group) 599Hz
9 Normal Duty (00-27=1) V/F 200V 25~40HP, 400V 30~75HP The maximum frequency is 120Hz 120Hz
10 Normal Duty (00-27=1) SLV /PMSLV Without standard loading mode -

Model No. / Input Voltage (V) / Input Current (A) / Max. Output Voltage (V) / Rated Output Current (A) / Output Power (KW) — PDF page 46

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Model No. Input Voltage (V) Input Current (A) Max. Output Voltage (V) Rated Output Current (A) Output Power (KW)
2 11-301-21-xxx-30 series 11-301-21-xxx-30 series 11-301-21-xxx-30 series 11-301-21-xxx-30 series 11-301-21-xxx-30 series 11-301-21-xxx-30 series
3 11-301-21-2P5-30 200-240 / 1Ф 8.5 240/3Ф 3.1 0.4
4 11-301-21-201-30 200-240 / 1Ф 12 240/3Ф 4.5 0.75
5 11-301-21-202-30 200-240 / 1Ф 16 240/3Ф 7.5 1.5
6 11-301-21-203-30 200-240 / 1Ф 23.9 240/3Ф 10.5 2.2
7 11-301-43-xxx-30 series 11-301-43-xxx-30 series 11-301-43-xxx-30 series 11-301-43-xxx-30 series 11-301-43-xxx-30 series 11-301-43-xxx-30 series
8 11-301-43-401-30 380-480 / 3Ф 4.2 480/3Ф 2.3 0.75
9 11-301-43-402-30 380-480 / 3Ф 5.6 480/3Ф 3.8 1.5
10 11-301-43-403-30 380-480 / 3Ф 7.3 480/3Ф 5.2 2.2
11 11-301-43-405-30 380-480 / 3Ф 11.6 480/3Ф 9.2 4.0
12 11-301-43-408-30 380-480 / 3Ф 17.0 480/3Ф 13.0 5.5
13 11-301-43-410-30 380-480 / 3Ф 23.0 480/3Ф 17.5 7.5
14 11-301-43-415-30 380-480 / 3Ф 31.0 480/3Ф 24 11
15 11-301-43-420-30 380-480 / 3Ф 38.0 480/3Ф 32 15
16 11-301-43-425-30 380-480 / 3Ф 48.0 480/3Ф 40 18.5
17 11-301-43-430-30 380-480 / 3Ф 48.9/63.0 480/3Ф 45/58 22/30
18 11-301-43-440-30 380-480 / 3Ф 65.2/78.3 480/3Ф 60/73 30/37
19 11-301-43-450-30 380-480 / 3Ф 81.5/95.7 480/3Ф 75/88 37/45
20 11-301-43-460-30 380-480 / 3Ф 98.9/112 480/3Ф 91/103 45/55
21 11-301-43-475-30 380-480 / 3Ф 130/159 480/3Ф 118/145 55/75

Manual — General specifications, controls and protection; continued48 — page 47

Manual reference: physical PDF page 47. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.4.2 General specifications

General specifications, controls and protection; continued48

Item / E510s — PDF page 47

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Item Item E510s
2 Control mode Control mode V/F, SLV, PMSLV control mode
3 Frequency Output Frequency 0.01~599.00Hz
4 Frequency Starting Torque 150% / 1Hz (SLV mode),150% / 3Hz(V/F mode)
5 Frequency Frequency resolution Digital input:0.01Hz Analog input:0.06Hz/60Hz
6 Frequency Frequency setting Keypad:set directly with ▲▼keys or the VR on the keypad External input terminals: AI1、AI2 (0/2-10V, 0/4-20mA) Multifunction input UP/DOWN function(Group 3) Set frequency by communication method
7 Frequency Frequency limit Lower and upper frequency limits 3 skip frequency settings.
8 Run Operation set Keypad RUN/STOP buttom External terminals: Multi-operation mode 2/3 wires selection JOG operation Run signal by communication method
9 Main Control Features V / F curve setting 15 fixed curves and 1 customized curve
10 Main Control Features Carrier frequency 1~16kHz (factory setting is 5kHz)
11 Main Control Features Acceleration and deceleration control 2 off acceleration/deceleration time parameters 4 off S curves parameters
12 Main Control Features Multifunction input Refer to description on Group 3
13 Main Control Features Multifunction output Refer to description on Group 3
14 Main Control Features Multifunction analog output Refer to description on Group 4
15 Main Control Features Main features Overload detection, 16 preset speed, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, Fault reset, Fire mode, Multi-Pump function.
16 Display LED display Parameter, Paramete value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list.
17 Display LED status indicator Run, Stop, Forward, Reverse and etc.
18 Protective Functions Overload protection (OL1) Electrical overload protection curve
19 Protective Functions Overload protection (OL2) H.D mode:150% for 60s (200% for 2s) N.D mode:120% for 60s
20 Protective Functions Over voltage 200V Class:DC bus voltage higher than 410Vdc 400V Class:DC bus voltage higher than 820Vdc
21 Protective Functions Under Voltage 200V Class:DC bus voltage lower than 190V 400V Class:DC bus voltage lower than 380V
22 Protective Functions Momentary Power Loss Restart Inverter auto-restart after a momentary power loss
23 Protective Functions Stall Prevention Stall prevention for acceleration/deceleration operation
24 Protective Functions Short-circuit output terminal Electronic circuit protection
25 Protective Functions Grounding Fault Electronic circuit protection
26 Protective Functions Other protection features Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off).

Manual — General specifications continuation and derating prose/legend/firstcurve — page 48

Manual reference: physical PDF page 48. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.4.3 De-rating curve

The curves are showing the applicable output current de-rate due to setting of carrier frequency and the ambient operating temperatures of 40 and 50 degrees. ➢ When the carrier frequency under than 10KHz, ambient temperature will not effect rated current. ➢ When the carrier frequency higher than 10KHz: If the ambient temperature is under 40℃, inverter can output 100% rated current on 2-10KHz. 16KHz only can be used 85% output current. If the ambient temperature is under 50℃, inverter only can output 85% rated current on 2-16KHz. ➢ It is required to derate 1.5% of output current at each additional degrees once the ambient inverter is higher than 50 degrees (The maximum ambient temperqture is 60 degrees).

Note: --------------- De-rating curve of 40℃ ambient temperature ……………………. De-rating curve of 50℃ ambient temperature

Frame 1/2/3/4 (Single phase/Three phase 200V 2HP, Three phase200V 0.5~2HP/5HP~20HP)

First derating plot title in adjacent source:Frame1/2/3/4(Single phase/Three phase200V2HP,Three phase200V0.5~2HP/5HP~20HP). Rated Current(In)100%,85%;Carrier Frequency(KHz)2,4,6,8,10,12,14,16. Dashed curve100%from2to10 then85%at16. Solid horizontal85%reference. No values interpolated; source legend/prose above preserved.

General specifications continuation and derating prose/legend/firstcurve

Communication control / Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system) — PDF page 48

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Communication control Communication control Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system)
2 Environment Operating temperature IP20/NEMA1 type: -10~50°C(without sticker or upper dust cover) -10~40°C(with sticker or upper dust cover)
3 Environment Storage temperature -20~60℃
4 Environment Humidity 95% RH or less (no condensation) (Follow IEC60068-2-78 standard)
5 Environment Vibration Frequency : 10Hz to 150Hz and return to 10Hz Amplitude : 0.3mm (10Hz to 50Hz) Acceleration : 2G (50Hz to 150Hz) (According to IEC60068-2-6 standard)
6 Environment Enclosure IP20/NEMA1

Manual — 200V model-specific derating plots — page 49

Manual reference: physical PDF page 49. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Frame2 (Three phase 200V 3HP)

Frane 5/6 (Three 200V 25HP)

Frame 5/6 (Three phase 200V 30HP、40HP)

Frame2(Three phase200V3HP). Rated Current(In)labels:100%,90%,81%,70%,60%,50%. Carrier Frequency(KHz)labels:2,4,6,8,10,12,14,16. Dashed100%to10;81%at16. No interpolation or unlabelled current value inferred. Source40°C/50°C legend on48 retained; dotted guides are not treated as independent engineering curves.

Frane5/6(Three200V25HP). Rated Current(In)labels:ND,100%HD,90%HD,80%HD,70%,60%,50%. Carrier Frequency(KHz)labels:0,2,4,6,8,10,12. DashedNDthrough2;break at6unlabelledcurrent;80%HDat12. No interpolation or unlabelled current value inferred. Source40°C/50°C legend on48 retained; dotted guides are not treated as independent engineering curves.

Frame5/6(Three phase200V30HP、40HP). Rated Current(In)labels:ND,100%HD,90%HD,80%HD,70%,60%,50%. Carrier Frequency(KHz)labels:0,2,4,5,6,8,10,12. DashedNDthrough2;break at5unlabelledcurrent;80%HDat12. No interpolation or unlabelled current value inferred. Source40°C/50°C legend on48 retained; dotted guides are not treated as independent engineering curves.

Manual — 400V1–25HP model-specific derating plots — page 50

Manual reference: physical PDF page 50. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Frame 1/2/3 (Three phase 400V 1HP~5HP, 10HP, 20HP~25HP)

Frame 3 (Three phase 400V 8HP)

Frame 3 (Three phase 400V 15HP)

Frame1/2/3(Three phase400V1HP~5HP,10HP,20HP~25HP). Rated Current(In)labels:100%,90%,85%,70%,60%,50%. Carrier Frequency(KHz)labels:2,4,6,8,10,12,14,16. Dashed100%to10;85%at16. No interpolation or unlabelled current value inferred. Source40°C/50°C legend on48 retained; dotted guides are not treated as independent engineering curves.

Frame3(Three phase400V8HP). Rated Current(In)labels:100%,90%,83%,70%,60%,50%. Carrier Frequency(KHz)labels:2,4,6,8,10,12,14,16. Dashed100%to10;83%at16. No interpolation or unlabelled current value inferred. Source40°C/50°C legend on48 retained; dotted guides are not treated as independent engineering curves.

Frame3(Three phase400V15HP). Rated Current(In)labels:100%,90%,80%,70%,60%,50%. Carrier Frequency(KHz)labels:2,4,6,8,10,12,14,16. Dashed100%to10;80%at16. No interpolation or unlabelled current value inferred. Source40°C/50°C legend on48 retained; dotted guides are not treated as independent engineering curves.

Adjacent source context — repeated to preserve continuation:

Manual — 400V30–75HP model-specific derating plots — page 51

Manual reference: physical PDF page 51. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Frame 5 (Three phase 400V 30HP)

Frame 6 (Three phase 400V 40HP~50HP)

Frame 6 (Three phase 400V 60HP~75HP)

Frame5(Three phase400V30HP). Rated Current(In)labels:ND,100%HD,90%HD,82%HD,70%,60%,50%. Carrier Frequency(KHz)labels:0,2,4,6,8,10,12,14,16. DashedNDthrough2;100%HDat10;82%HDat16. No interpolation or unlabelled current value inferred. Source40°C/50°C legend on48 retained; dotted guides are not treated as independent engineering curves.

Frame6(Three phase400V40HP~50HP). Rated Current(In)labels:ND,100%HD,90%HD,80%HD,70%,60%,50%. Carrier Frequency(KHz)labels:0,2,4,5,6,8,10,12. DashedNDthrough2;break at5unlabelledcurrent;80%HDat12. No interpolation or unlabelled current value inferred. Source40°C/50°C legend on48 retained; dotted guides are not treated as independent engineering curves.

Frame6(Three phase400V60HP~75HP). Rated Current(In)labels:ND,100%HD,90%HD,80%HD,70%HD,60%,50%. Carrier Frequency(KHz)labels:2,4,5,6,8,10. DashedNDthrough2;break at5above100%HDreference;70%HDat10. No interpolation or unlabelled current value inferred. Source40°C/50°C legend on48 retained; dotted guides are not treated as independent engineering curves.

Adjacent source context — repeated to preserve continuation:

Manual — Capacitor reforming after storage, rated-voltage reference — page 52

Manual reference: physical PDF page 52. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.4.4 Capacitor Reforming Guide After Long Storage

For correct performance of this product after long storage before use it is important that Inverter Capacitors are reformed according to the guide below:

Note1:Please refer the rated voltage according to model label of inverter.

Capacitor reforming after storage, rated-voltage reference

Storage time / Procedure to re-apply voltage — PDF page 52

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Storage time Procedure to re-apply voltage
2 ≦1year Apply rated voltage of inverter in the normal way
3 Between 1-2 years Apply rated voltage of inverter(Note1) to the product for one hour before using the inverter
4 ≧2 years Use a variable AC power supply to 1. Connecting 25% rated voltage of inverter for 30 minutes. 2. Connecting 50% rated voltage of inverter for 30 minutes. 3. Connecting 75% rated voltage of inverter for 30 minutes. 4. Connecting 100% rated voltage of inverter for 210 minutes. Once the procedures completed, inverter just can be used normally

Manual — Standard wiring; source remarks1–4 mandatory — page 53

Manual reference: physical PDF page 53. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.5 Standard Wiring

Remark:

(*1) Models 200V 0.5-25HP and 400V 1-40HP with built-in braking transistor, braking transistor can be

connected directly between P and BR.

(*2) Safety input connector (SF/SG) should be shorted so that inverter outputs properly. When the safety

input is used, please be sure to remove the short-pin between SF/SG.

(*3) The multi-function digital input terminals S1-S6 can be set to Sink(NPN) and Source(PNP) by JP1.

(*4) Models 200V 25HP and 400V 30HP and higher ratings provides P1 terminal for DCL connected, please

connect wiring correctly according to the next section.

Standard wiring figure labels only; no topology inferred. Power:Main circuit power,NFB,MC,Fast acting fuse,L1(L),L2,L3(N),P,BR,Braking resistor,Output T1/T2/T3,Inductor motor,IM,Ground. Default Setting:S1Forward/stop,S2Reverse/stop,S3–S5Multi-speed,S6Reset;Multi-function input;COM(Common point for NPN input);+24V(Common point for PNP input);JP1NPN/PNP and(3);E Connection of shielding wire. Functional safety input(STO):SF1,SF2,SG,(2). Frequency reference(10K ohm or PID input):10V(Power of analog input);AI1(Multi-function analog input1),AI2(Multi-function analog input1)as printed;two0-10V/0-20mAlabels;AGND(Common terminal of analog signal). AI1/AV1 JP2 I/V(Default);AI2/AV2 JP3 I(Default)/V. CON2 RS485:Pin1Data+,Pin2Data-,Pin3Data+,Pin4RXD0,Pin5TXD0,Pin6Data-,Pin7 5V,Pin8GND. Relay outputR1A/R1B/R1C andR2A/R2B:250VAC1A,30VDC1A. S(+),S(-):RS485/MODBUS. AO/AGND:Frequency indicatorDC0-10V. Screened cable and screened twisted pairP;double-circlemaincircuit/single-circlecontrolcircuit symbol legend. Remarks(1),(4)bybrakingresistor retained in source prose below.

Manual — Main circuit terminals by voltage/power and terminal-strip illustrations — page 54

Manual reference: physical PDF page 54. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.6 Terminal description

3.6.1 Description of main circuit terminal

➢ Main power terminal of Single phase 200V Class 0.5~1HP

Notes:The screw on L2 terminal will be removed for single phase input supply models.

➢ Main power terminal of Single/Three phase 200V Class 0.5~1HP and Three phase 400V Class

1~2HP.

First terminal-strip illustration:singlephase200V0.5–1HP. Upperleft-to-rightL1(L),L2,L3(N),T1,T2,T3;lowerP,BR. L2screw visibly absent;separate source note retained. No inferred wiring.

Second terminal-strip illustration:single/threephase200V0.5–1HP andthreephase400V1–2HP. UpperL1(L),L2,L3(N),T1,T2,T3;lowerP,BR. Source scopes preserved without harmonization.

Main circuit terminals by voltage/power and terminal-strip illustrations

Terminal symbol / 200V:0.5-20HP 400V:1-25HP / 200V:25HP 400V:30HP / 200V:30-40HP 400V:40-75HP — PDF page 54

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Terminal symbol 200V:0.5-20HP 400V:1-25HP 200V:25HP 400V:30HP 200V:30-40HP 400V:40-75HP
2 L1(L), R/L1 Main power input 1 phase:L1(L)-L3(N) 3 phase:L1(L)-L2-L3(N) Main power input 3 phase:R/L1-S/L2-T/L3 Main power input 3 phase:R/L1-S/L2-T/L3
3 L2, S/L2 Main power input 1 phase:L1(L)-L3(N) 3 phase:L1(L)-L2-L3(N) Main power input 3 phase:R/L1-S/L2-T/L3 Main power input 3 phase:R/L1-S/L2-T/L3
4 L3(N), T/L3 Main power input 1 phase:L1(L)-L3(N) 3 phase:L1(L)-L2-L3(N) Main power input 3 phase:R/L1-S/L2-T/L3 Main power input 3 phase:R/L1-S/L2-T/L3
5 P Externally connected braking resistor - -
6 BR Externally connected braking resistor - -
7 ⊖ - - ⊖-P1: Externally connected braking resistor P1-P2: Externally connected DCL
8 P1 - P1-P2/B1: Externally connected DCL P2/B1-B2: Externally connected braking resistor ⊖-P1: Externally connected braking resistor P1-P2: Externally connected DCL
9 P2/B1 - P1-P2/B1: Externally connected DCL P2/B1-B2: Externally connected braking resistor ⊖-P1: Externally connected braking resistor P1-P2: Externally connected DCL
10 B2 - P1-P2/B1: Externally connected DCL P2/B1-B2: Externally connected braking resistor ⊖-P1: Externally connected braking resistor P1-P2: Externally connected DCL
11 P2 - P1-P2/B1: Externally connected DCL P2/B1-B2: Externally connected braking resistor ⊖-P1: Externally connected braking resistor P1-P2: Externally connected DCL
12 T1 Inverter output, connect to U/V/W terminals of motor Inverter output, connect to U/V/W terminals of motor Inverter output, connect to U/V/W terminals of motor
13 T2 Inverter output, connect to U/V/W terminals of motor Inverter output, connect to U/V/W terminals of motor Inverter output, connect to U/V/W terminals of motor
14 T3 Inverter output, connect to U/V/W terminals of motor Inverter output, connect to U/V/W terminals of motor Inverter output, connect to U/V/W terminals of motor
15 [circled ground symbol] Ground terminal Ground terminal Ground terminal

Manual — Main power terminal-strip model/power associations — page 55

Manual reference: physical PDF page 55. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Main power terminal of Single/Three phase 200V Class 2~3HP

➢ Main power terminal of Single/Three phase 200V Class 2~3HP, Three phase 200V Class 5HP and

Three phase 400V Class 3~5HP

➢ Main power terminal of Three phase 200V Class 7.5~20HP and Three phase 400V Class 7.5~20HP

➢ Main power terminal of Three phase 200V Class 25HP and Three phase 400V Class 30HP

➢ Main power terminal of Three phase 200V Class 30~40HP and Three phase 400V Class 40~75HP

single/threephase200V2–3HP terminal strip, left-to-rightlabels:L1(L),L2,L3(N),P,BR,T1,T2,T3;L2screw absent. Symbol⊖transcribescircledminus;noinferredwiring.

single/threephase200V2–3HP,threephase200V5HP,threephase400V3–5HP terminal strip, left-to-rightlabels:L1(L),L2,L3(N),P,BR,T1,T2,T3;allpositionsshowscrews. Symbol⊖transcribescircledminus;noinferredwiring.

threephase200V7.5–20HP and400V7.5–20HP terminal strip, left-to-rightlabels:L1(L),L2,L3(N),P,BR,T1,T2,T3. Symbol⊖transcribescircledminus;noinferredwiring.

threephase200V25HP and400V30HP terminal strip, left-to-rightlabels:R/L1,S/L2,T/L3,⊖,P1,P2/B1,B2,U/T1,V/T2,W/T3. Symbol⊖transcribescircledminus;noinferredwiring.

threephase200V30–40HP and400V40–75HP terminal strip, left-to-rightlabels:R/L1,S/L2,T/L3,⊖,P1,P2,U/T1,V/T2,W/T3. Symbol⊖transcribescircledminus;noinferredwiring.

Manual — Control circuit terminal functions and signal levels — page 56

Manual reference: physical PDF page 56. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.6.2 Description of control circuit terminal

Control terminal:

Control terminal layout:upperR2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2;lowerS(+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. Physical label order only;no wiring inferred.

Control circuit terminal functions and signal levels

Type / Terminal / Function / Signal level — PDF page 56

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Type Terminal Function Function Signal level
2 Digital Input S1 Please refer to group3 (digital input functions) for default setting and setting range. Please refer to group3 (digital input functions) for default setting and setting range. 24 VDC, 8 mA photocoupler isolation. (The max. input voltage is 30 Vdc, input resistance is 4.3kΩ) High Logic: 13V Low Logic: 10V
3 Digital Input S2 Please refer to group3 (digital input functions) for default setting and setting range. Please refer to group3 (digital input functions) for default setting and setting range. 24 VDC, 8 mA photocoupler isolation. (The max. input voltage is 30 Vdc, input resistance is 4.3kΩ) High Logic: 13V Low Logic: 10V
4 Digital Input S3 Please refer to group3 (digital input functions) for default setting and setting range. Please refer to group3 (digital input functions) for default setting and setting range. 24 VDC, 8 mA photocoupler isolation. (The max. input voltage is 30 Vdc, input resistance is 4.3kΩ) High Logic: 13V Low Logic: 10V
5 Digital Input S4 Please refer to group3 (digital input functions) for default setting and setting range. Please refer to group3 (digital input functions) for default setting and setting range. 24 VDC, 8 mA photocoupler isolation. (The max. input voltage is 30 Vdc, input resistance is 4.3kΩ) High Logic: 13V Low Logic: 10V
6 Digital Input S5 Please refer to group3 (digital input functions) for default setting and setting range. Please refer to group3 (digital input functions) for default setting and setting range. 24 VDC, 8 mA photocoupler isolation. (The max. input voltage is 30 Vdc, input resistance is 4.3kΩ) High Logic: 13V Low Logic: 10V
7 Digital Input S6 Please refer to group3 (digital input functions) for default setting and setting range. Please refer to group3 (digital input functions) for default setting and setting range. 24 VDC, 8 mA photocoupler isolation. (The max. input voltage is 30 Vdc, input resistance is 4.3kΩ) High Logic: 13V Low Logic: 10V
8 Relay Output R1A Normal Open Please refer to group3 (digital output functions) for default setting and setting range. 250VAC/1A (30VDC/1A)
9 Relay Output R1B Normal Close Please refer to group3 (digital output functions) for default setting and setting range. 250VAC/1A (30VDC/1A)
10 Relay Output R1C Common Point Please refer to group3 (digital output functions) for default setting and setting range. 250VAC/1A (30VDC/1A)
11 Relay Output R2A Normal Open Please refer to group3 (digital output functions) for default setting and setting range. 250VAC/1A (30VDC/1A)
12 Relay Output R2B Normal Open Please refer to group3 (digital output functions) for default setting and setting range. 250VAC/1A (30VDC/1A)
13 24Vdc Supply 24V Common point of PNP input (JP1 switch to PNP) Common point of PNP input (JP1 switch to PNP) ±15% (max output current is 60mA)
14 24Vdc Supply COM Common point of NPN input (JP1 switch to NPN) Common point of NPN input (JP1 switch to NPN) ±15% (max output current is 60mA)
15 Analog Input 10V Built-in power for external potentiometer Built-in power for external potentiometer 10V (max current is 20mA)
16 Analog Input AI1/AV1 Multi-analog input 1 (0-10V/0-20mA) (Please use JP2 to select voltage or current input) Multi-analog input 1 (0-10V/0-20mA) (Please use JP2 to select voltage or current input) Resistance for voltage input is 153KΩ; for current input is :500Ω
17 Analog Input AI2/AV2 Multi-analog input 2 (0-10V/0-20mA) (Please use JP3 to select voltage or current input) Multi-analog input 2 (0-10V/0-20mA) (Please use JP3 to select voltage or current input) Resistance for voltage input is 153KΩ; for current input is :500Ω
18 Analog Input AGND Analog input common point. Analog input common point. ----
19 Analog Input [circled ground symbol] Ground terminal. Ground terminal. ----
20 Analog Output AO Analog output terminal. Analog output terminal. 0-10V,(max current is 2mA)
21 Analog Output AGND Analog input common point. Analog input common point. ----
22 STO Terminal SF1,SF2 The default status of safety switch is normal close, when the terminal becames to normal open status, output voltage of inverter will be cut off. The default status of safety switch is normal close, when the terminal becames to normal open status, output voltage of inverter will be cut off. ⟦blank source cell⟧
23 STO Terminal SG The default status of safety switch is normal close, when the terminal becames to normal open status, output voltage of inverter will be cut off. The default status of safety switch is normal close, when the terminal becames to normal open status, output voltage of inverter will be cut off. 24V for SF1/SF2
24 RS485 Modbus S(+) RS485/MODBUS (Baud rate setting 9600~38400) RS485/MODBUS (Baud rate setting 9600~38400) Differential input and output
25 RS485 Modbus S(-) RS485/MODBUS (Baud rate setting 9600~38400) RS485/MODBUS (Baud rate setting 9600~38400) Differential input and output

Manual — Jumper function description; physical pin positions — page 57

Manual reference: physical PDF page 57. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Jumper function description

JP1 NPN input:visiblejumperrectangleenclosespins1and2;labels1,2,3top-to-bottom. This describes visible symbols only;sourcefunction/settingnotesretainedintable.

JP1 PNP input:visiblejumperrectangleenclosespins2and3;labels1,2,3top-to-bottom. This describes visible symbols only;sourcefunction/settingnotesretainedintable.

JP2/JP3 current0-20mA/4-20mA:visiblejumperrectangleenclosespins1and2;labels1,2,3top-to-bottom. This describes visible symbols only;sourcefunction/settingnotesretainedintable.

JP2/JP3 voltage0/2-10V:visiblejumperrectangleenclosespins2and3;labels1,2,3top-to-bottom. This describes visible symbols only;sourcefunction/settingnotesretainedintable.

Jumper function description; physical pin positions

Jumper / Symbol / Function / Signal reference / Note — PDF page 57

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Jumper Symbol Function Signal reference Note
2 JP1 [jumper rectangle surrounds pins1 and2; pins1,2,3top-to-bottom] NPN/PNP selectable NPN input Factory default setting
3 JP1 [jumper rectangle surrounds pins2 and3; pins1,2,3top-to-bottom] NPN/PNP selectable PNP input Factory default setting
4 JP2 /JP3 [jumper rectangle surrounds pins1 and2; pins1,2,3top-to-bottom] External signal type selection 0-20mA / 4-20mA Analog signal Set parameter 00-05/00-06 to 2 or 3 (External analog input) to become effective
5 JP2 /JP3 [jumper rectangle surrounds pins2 and3; pins1,2,3top-to-bottom] External signal type selection 0/2-10V Analog signal Set parameter 00-05/00-06 to 2 or 3 (External analog input) to become effective

Manual — IP20 outline dimensions:200V0.5–1HP single,2HP three;400V1–2HP three — page 58

Manual reference: physical PDF page 58. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

3.7 Outline dimensions

➢ IP20 dimensions

200V Class single phase:0.5HP~1HP

200V Class three phase:2HP

400V Class three phase:1HP~2HP

Outline drawing labels:W,W1,W2,H,H1,D,E,t,Q. Numerical model-linked dimensions andunits preserved in adjacent originaltable;no unlabelleddimensions inferred. Tinyembeddedkeypad/nameplateinscriptions unresolved;dimensionlabelsreviewed separately.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/nameplate inscriptions remain partly unresolved after two visual full-page readings and5xbounded hardware crop. All explicit dimension labels, model-linked numeric tables, source units and procedure text retained. No inferred inscriptions or wiring.

IP20 outline dimensions:200V0.5–1HP single,2HP three;400V1–2HP three

Inverter Model / Dimensions in mm (inch) / Net Weight Kg/(lbs) — PDF page 58

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows) Physical column 11 (source headings retained in rows)
1 Inverter Model Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Net Weight Kg/(lbs)
2 Inverter Model W W1 W2 H H1 D E t Q Net Weight Kg/(lbs)
3 E510-2P5-SH 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5/(3.3)
4 E510-201-SH 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5/(3.3)
5 E510-2P5-SH1F 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5/(3.3)
6 E510-201-SH1F 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5/(3.3)
7 E510-202-SH3 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5/(3.3)
8 E510-401-SH3 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5/(3.3)
9 E510-402-SH3 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.5/(3.3)
10 E510-401-SH3F 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.58/(3.48)
11 E510-402-SH3F 90.6 (3.57) 80.5 (3.17) 80.5 (3.17) 164 (6.46) 153 (6.02) 151.4 (5.96) 47 (1.85) 5 (0.19) M4 1.58/(3.48)

Manual — IP20 outline dimensions continuation; multiple model groups — page 59

Manual reference: physical PDF page 59. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

200V Class single/three phase:2HP

400V Class three phase:3~25HP 200V Class three phase:3~20HP

Outline drawing labels:W,W1,W2,H,H1,H2,D,D1,E,t,Q. Numerical model-linked dimensions andunits preserved in adjacent originaltable;no unlabelleddimensions inferred. Tinyembeddedkeypad/nameplateinscriptions unresolved;dimensionlabelsreviewed separately.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/nameplate inscriptions remain partly unresolved after two visual full-page readings and5xbounded hardware crop. All explicit dimension labels, model-linked numeric tables, source units and procedure text retained. No inferred inscriptions or wiring.

IP20 outline dimensions continuation; multiple model groups

Inverter Model / Dimensions in mm (inch) / Net Weight Kg/(lbs) — PDF page 59

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows) Physical column 11 (source headings retained in rows) Physical column 12 (source headings retained in rows) Physical column 13 (source headings retained in rows)
1 Inverter Model Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Net Weight Kg/(lbs)
2 Inverter Model W W1 W2 H H1 H2 D D1 E t Q Net Weight Kg/(lbs)
3 E510-202-SH 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0/(4.41)
4 E510-203-SH 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0/(4.41)
5 E510-202-SH1F 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0/(4.41)
6 E510-203-SH1F 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0/(4.41)
7 E510-205-SH3 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0/(4.41)
8 E510-403-SH3 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0/(4.41)
9 E510-405-SH3 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.0/(4.41)
10 E510-403-SH3F 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.2/(4.81)
11 E510-405-SH3F 128.7 (5.07) 118 (4.65) 118 (4.65) 187.6 (7.39) 177.6 (6.99) 197.5 (7.78) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 5 (0.19) M4 2.2/(4.81)
12 E510-208-SH3 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.0/(13.23)
13 E510-210-SH3 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.0/(13.23)
14 E510-408-SH3 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.0/(13.23)
15 E510-410-SH3 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.0/(13.23)
16 E510-415-SH3 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.0/(13.23)
17 E510-408-SH3F 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.5/(14.33)
18 E510-410-SH3F 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 6.5/(14.33)
19 E510-415-SH3F 186.9 (7.36) 175 (6.89) 176 (6.93) 260.9 (10.27) 249.8 (9.83) 273 (10.75) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 6.5 (0.26) M4 10.0/(22.05)
20 E510-215-SH3 224.6 (8.84) 207 (8.15) 207 (8.15) 321.6 (12.66) 303.5 (11.95) 330.9 (13.03) 206.1 (8.11) 201.1 (7.92) 94 (3.7) 8 (0.31) M5 10.0/(22.05)
21 E510-220-SH3 224.6 (8.84) 207 (8.15) 207 (8.15) 321.6 (12.66) 303.5 (11.95) 330.9 (13.03) 206.1 (8.11) 201.1 (7.92) 94 (3.7) 8 (0.31) M5 10.0/(22.05)
22 E510-420-SH3 224.6 (8.84) 207 (8.15) 207 (8.15) 321.6 (12.66) 303.5 (11.95) 330.9 (13.03) 206.1 (8.11) 201.1 (7.92) 94 (3.7) 8 (0.31) M5 10.0/(22.05)
23 E510-425-SH3 224.6 (8.84) 207 (8.15) 207 (8.15) 321.6 (12.66) 303.5 (11.95) 330.9 (13.03) 206.1 (8.11) 201.1 (7.92) 94 (3.7) 8 (0.31) M5 10.0/(22.05)

Manual — IP20 outline dimensions:200V25–40HP,400V30–75HP — page 60

Manual reference: physical PDF page 60. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

200V Class three phase:25HP

400V Class three phase:30HP

200V Class three phase:30~40HP

400V Class three phase:40~75HP

Outline drawing labels:W,W1,W2,H,H1,D,D1,Q. Numerical model-linked dimensions andunits preserved in adjacent originaltable;no unlabelleddimensions inferred. Tinyembeddedkeypad/nameplateinscriptions unresolved;dimensionlabelsreviewed separately.

Outline drawing labels:W,W1,W2,H,H1,D,t,Q. Numerical model-linked dimensions andunits preserved in adjacent originaltable;no unlabelleddimensions inferred. Tinyembeddedkeypad/nameplateinscriptions unresolved;dimensionlabelsreviewed separately.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/nameplate inscriptions remain partly unresolved after two visual full-page readings and5xbounded hardware crop. All explicit dimension labels, model-linked numeric tables, source units and procedure text retained. No inferred inscriptions or wiring.

IP20 outline dimensions:200V25–40HP,400V30–75HP

Inverter Model / Dimensions in mm (inch) / Net Weight Kg/(lbs) — PDF page 60

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows) Physical column 11 (source headings retained in rows)
1 Inverter Model Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Net Weight Kg/(lbs)
2 Inverter Model W W1 W2 H H1 D D1 t Q Net Weight Kg/(lbs)
3 E510-225-SH3 265 (10.43) 245 (9.65) 245 (9.65) 360 (14.17) 340 (13.39) 238.2 (9.38) 233.2 (9.18) 1.6 (0.06) M8 10.0/(22.05)
4 E510-430-SH3 265 (10.43) 245 (9.65) 245 (9.65) 360 (14.17) 340 (13.39) 238.2 (9.38) 233.2 (9.18) 1.6 (0.06) M8 10.0/(22.05)

Inverter Model / Dimensions in mm (inch) / Net Weight in Kg/(lbs) — PDF page 60

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Inverter Model Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Net Weight in Kg/(lbs)
2 Inverter Model W W1 W2 H H1 D t Q Net Weight in Kg/(lbs)
3 E510-230-SH3 286.5 (11.28) 220 (8.66) 220 (8.66) 525 (20.67) 505 (19.88) 269.8 (10.62) 3.3 (0.13) M8 23.2/(51.15)
4 E510-240-SH3 286.5 (11.28) 220 (8.66) 220 (8.66) 525 (20.67) 505 (19.88) 269.8 (10.62) 3.3 (0.13) M8 23.2/(51.15)
5 E510-440-SH3 286.5 (11.28) 220 (8.66) 220 (8.66) 525 (20.67) 505 (19.88) 269.8 (10.62) 3.3 (0.13) M8 23.2/(51.15)
6 E510-450-SH3 286.5 (11.28) 220 (8.66) 220 (8.66) 525 (20.67) 505 (19.88) 269.8 (10.62) 3.3 (0.13) M8 23.2/(51.15)
7 E510-460-SH3 286.5 (11.28) 220 (8.66) 220 (8.66) 525 (20.67) 505 (19.88) 269.8 (10.62) 3.3 (0.13) M8 23.2/(51.15)
8 E510-475-SH3 286.5 (11.28) 220 (8.66) 220 (8.66) 525 (20.67) 505 (19.88) 269.8 (10.62) 3.3 (0.13) M8 23.2/(51.15)

Manual — NEMA1 dimensions:200V0.5–1HPsingle,2HPthree;400V1–2HP — page 61

Manual reference: physical PDF page 61. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

➢ NEMA 1 dimensions

200V Class single phase:0.5~1HP

400V Class three phase:1~2HP

200V Class three phase:2HP

Outline drawing labels:W,W1,H,H1,D,E,E1,t,Q. Numerical model-linked dimensions andunits preserved in adjacent originaltable;no unlabelleddimensions inferred. Tinyembeddedkeypad/nameplateinscriptions unresolved;dimensionlabelsreviewed separately. Enlarged visible first front-view label: 1PH-220V-0.75kW;DANGER:Cut off the power and wait for5minutes before inspecting components. CAUTION:See manual before operation.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/nameplate inscriptions remain partly unresolved after two visual full-page readings and5xbounded hardware crop. All explicit dimension labels, model-linked numeric tables, source units and procedure text retained. No inferred inscriptions or wiring.

NEMA1 dimensions:200V0.5–1HPsingle,2HPthree;400V1–2HP

Inverter Model / Dimensions in mm (inch) / Net Weight in Kg/(lbs) — PDF page 61

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows) Physical column 11 (source headings retained in rows)
1 Inverter Model Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Net Weight in Kg/(lbs)
2 Inverter Model W W1 H H1 D E E1 t Q Net Weight in Kg/(lbs)
3 E510-2P5-SH 90.6 (3.57) 80.5 (3.17) 186.2 (7.33) 189.2 (7.45) 151.4 (5.96) 47 (1.85) 120.5 (4.74) 5 (0.19) M4 1.9/(4.19)
4 E510-201-SH 90.6 (3.57) 80.5 (3.17) 186.2 (7.33) 189.2 (7.45) 151.4 (5.96) 47 (1.85) 120.5 (4.74) 5 (0.19) M4 1.9/(4.19)
5 E510-2P5-SH1F 90.6 (3.57) 80.5 (3.17) 186.2 (7.33) 189.2 (7.45) 151.4 (5.96) 47 (1.85) 120.5 (4.74) 5 (0.19) M4 1.9/(4.19)
6 E510-201-SH1F 90.6 (3.57) 80.5 (3.17) 186.2 (7.33) 189.2 (7.45) 151.4 (5.96) 47 (1.85) 120.5 (4.74) 5 (0.19) M4 1.9/(4.19)
7 E510-202-SH3 90.6 (3.57) 80.5 (3.17) 186.2 (7.33) 189.2 (7.45) 151.4 (5.96) 47 (1.85) 120.5 (4.74) 5 (0.19) M4 1.9/(4.19)
8 E510-401-SH3 90.6 (3.57) 80.5 (3.17) 186.2 (7.33) 189.2 (7.45) 151.4 (5.96) 47 (1.85) 120.5 (4.74) 5 (0.19) M4 1.9/(4.19)
9 E510-402-SH3 90.6 (3.57) 80.5 (3.17) 186.2 (7.33) 189.2 (7.45) 151.4 (5.96) 47 (1.85) 120.5 (4.74) 5 (0.19) M4 1.9/(4.19)
10 E510-401-SH3F 90.6 (3.57) 80.5 (3.17) 186.2 (7.33) 189.2 (7.45) 151.4 (5.96) 47 (1.85) 120.5 (4.74) 5 (0.19) M4 2.0/(4.41)
11 E510-402-SH3F 90.6 (3.57) 80.5 (3.17) 186.2 (7.33) 189.2 (7.45) 151.4 (5.96) 47 (1.85) 120.5 (4.74) 5 (0.19) M4 2.0/(4.41)

Manual — NEMA1 dimensions continuation with model-specific weight groups — page 62

Manual reference: physical PDF page 62. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and8x side-view crop confirm D,D1,E,t; E1 occurs in the table header only. Existing diagram-label summary is correct. Tiny embedded keypad/nameplate inscriptions remain unresolved; table values and prior fields unchanged.

200V Class single phase/three phase:2HP

400V Class three phase:3~25HP

200V Class three phase:3~20HP

Outline drawing labels:W,W1,H,H1,D,D1,E,t,Q. Numerical model-linked dimensions andunits preserved in adjacent originaltable;no unlabelleddimensions inferred. Tinyembeddedkeypad/nameplateinscriptions unresolved;dimensionlabelsreviewed separately. Enlarged visible first front-view label: 3PH-220V-2.2kW;DANGER:Cut off the power and wait for5minutes before inspecting components. CAUTION:See manual before operation.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/nameplate inscriptions remain partly unresolved after two visual full-page readings and5xbounded hardware crop. All explicit dimension labels, model-linked numeric tables, source units and procedure text retained. No inferred inscriptions or wiring.

NEMA1 dimensions continuation with model-specific weight groups

Inverter Model / Dimensions in mm (inch) / Net Weight Kg/(lbs) — PDF page 62

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows) Physical column 11 (source headings retained in rows) Physical column 12 (source headings retained in rows)
1 Inverter Model Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Net Weight Kg/(lbs)
2 Inverter Model W W1 H H1 D D1 E E1 t Q Net Weight Kg/(lbs)
3 E510-202-SH 128.7 (5.06) 118 (4.65) 210.6 (8.29) 213.6 (8.41) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 121.1 (4.77) 5 (0.19) M4 2.9/(6.39)
4 E510-203-SH 128.7 (5.06) 118 (4.65) 210.6 (8.29) 213.6 (8.41) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 121.1 (4.77) 5 (0.19) M4 2.9/(6.39)
5 E510-202-SH1F 128.7 (5.06) 118 (4.65) 210.6 (8.29) 213.6 (8.41) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 121.1 (4.77) 5 (0.19) M4 2.9/(6.39)
6 E510-203-SH1F 128.7 (5.06) 118 (4.65) 210.6 (8.29) 213.6 (8.41) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 121.1 (4.77) 5 (0.19) M4 2.9/(6.39)
7 E510-205-SH3 128.7 (5.06) 118 (4.65) 210.6 (8.29) 213.6 (8.41) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 121.1 (4.77) 5 (0.19) M4 2.9/(6.39)
8 E510-403-SH3 128.7 (5.06) 118 (4.65) 210.6 (8.29) 213.6 (8.41) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 121.1 (4.77) 5 (0.19) M4 2.9/(6.39)
9 E510-405-SH3 128.7 (5.06) 118 (4.65) 210.6 (8.29) 213.6 (8.41) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 121.1 (4.77) 5 (0.19) M4 2.9/(6.39)
10 E510-403-SH3F 128.7 (5.06) 118 (4.65) 210.6 (8.29) 213.6 (8.41) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 121.1 (4.77) 5 (0.19) M4 2.9/(6.39)
11 E510-405-SH3F 128.7 (5.06) 118 (4.65) 210.6 (8.29) 213.6 (8.41) 152.4 (6) 147.4 (5.8) 48.2 (1.9) 121.1 (4.77) 5 (0.19) M4 2.9/(6.39)
12 E510-208-SH3 186.9 (7.36) 175 (6.89) 291 (11.47) 293.5 (11.56) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 170.6 (6.72) 6.5 (0.26) M4 7.4/(16.3)
13 E510-210-SH3 186.9 (7.36) 175 (6.89) 291 (11.47) 293.5 (11.56) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 170.6 (6.72) 6.5 (0.26) M4 7.4/(16.3)
14 E510-408-SH3 186.9 (7.36) 175 (6.89) 291 (11.47) 293.5 (11.56) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 170.6 (6.72) 6.5 (0.26) M4 7.4/(16.3)
15 E510-410-SH3 186.9 (7.36) 175 (6.89) 291 (11.47) 293.5 (11.56) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 170.6 (6.72) 6.5 (0.26) M4 7.4/(16.3)
16 E510-415-SH3 186.9 (7.36) 175 (6.89) 291 (11.47) 293.5 (11.56) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 170.6 (6.72) 6.5 (0.26) M4 7.4/(16.3)
17 E510-408-SH3F 186.9 (7.36) 175 (6.89) 291 (11.47) 293.5 (11.56) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 170.6 (6.72) 6.5 (0.26) M4 7.4/(16.3)
18 E510-410-SH3F 186.9 (7.36) 175 (6.89) 291 (11.47) 293.5 (11.56) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 170.6 (6.72) 6.5 (0.26) M4 7.4/(16.3)
19 E510-415-SH3F 186.9 (7.36) 175 (6.89) 291 (11.47) 293.5 (11.56) 202.6 (7.98) 197.6 (7.78) 76.7 (3.02) 170.6 (6.72) 6.5 (0.26) M4 7.4/(16.3)
20 E510-215-SH3 224.6 (8.84) 207 (8.15) 358.3 (14.1) 363.3 (14.3) 206.1 (8.11) 201.1 (7.92) 94 (3.7) 174 (6.85) 8 (0.31) M4 11.0/(24.25)
21 E510-220-SH3 224.6 (8.84) 207 (8.15) 358.3 (14.1) 363.3 (14.3) 206.1 (8.11) 201.1 (7.92) 94 (3.7) 174 (6.85) 8 (0.31) M4 11.0/(24.25)
22 E510-420-SH3 224.6 (8.84) 207 (8.15) 358.3 (14.1) 363.3 (14.3) 206.1 (8.11) 201.1 (7.92) 94 (3.7) 174 (6.85) 8 (0.31) M4 11.4/(25.13)
23 E510-425-SH3 224.6 (8.84) 207 (8.15) 358.3 (14.1) 363.3 (14.3) 206.1 (8.11) 201.1 (7.92) 94 (3.7) 174 (6.85) 8 (0.31) M4 11.4/(25.13)

Manual — NEMA1 built-in EMC-filter dimensions:400V20–75HP — page 63

Manual reference: physical PDF page 63. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

400V Class three phase:20~30HP (built-in EMC filter)

400V Class three phase:40~75HP (built-in EMC filter)

Outline drawing labels:W,W1,H,H1,D,D1,E,E1,t,Q. Numerical model-linked dimensions andunits preserved in adjacent originaltable;no unlabelleddimensions inferred. Tinyembeddedkeypad/nameplateinscriptions unresolved;dimensionlabelsreviewed separately.

Outline drawing labels:W,W1,W2,H,H1,D,E,E1,t,Q. Numerical model-linked dimensions andunits preserved in adjacent originaltable;no unlabelleddimensions inferred. Tinyembeddedkeypad/nameplateinscriptions unresolved;dimensionlabelsreviewed separately.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/nameplate inscriptions remain partly unresolved after two visual full-page readings and5xbounded hardware crop. All explicit dimension labels, model-linked numeric tables, source units and procedure text retained. No inferred inscriptions or wiring.

NEMA1 built-in EMC-filter dimensions:400V20–75HP

Inverter Model / Dimensions in mm (inch) / Net Weight Kg/(lbs) — PDF page 63

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows) Physical column 11 (source headings retained in rows) Physical column 12 (source headings retained in rows)
1 Inverter Model Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Net Weight Kg/(lbs)
2 Inverter Model W W1 H H1 D D1 E E1 t Q Net Weight Kg/(lbs)
3 E510-420-SH3F 235.6 (9.28) 180 (7.09) 400 (15.75) 381.5 (15.02) 267.1 (10.52) 262.1 (10.32) 62 (2.44) 237 (9.33) 4 (0.16) M6 18.9/(41.67)
4 E510-425-SH3F 235.6 (9.28) 180 (7.09) 400 (15.75) 381.5 (15.02) 267.1 (10.52) 262.1 (10.32) 62 (2.44) 237 (9.33) 4 (0.16) M6 18.9/(41.67)
5 E510-430-SH3F 269 (10.59) 230 (9.05) 462 (18.19) 440 (17.32) 318.2 (12.53) 313.2 (12.33) 80 (3.15) 267.6 (10.54) 4 (0.16) M8 22.8/(50.27)

Inverter Model / Dimensions in mm (inch) / Net Weight Kg/(lbs) — PDF page 63

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows) Physical column 11 (source headings retained in rows) Physical column 12 (source headings retained in rows)
1 Inverter Model Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Net Weight Kg/(lbs)
2 Inverter Model W W1 W2 H H1 D E E1 t Q Net Weight Kg/(lbs)
3 E510-440-SH3F 288.9 (11.37) 220 (8.66) 220 (8.66) 652 (25.67) 620 (24.41) 369.8 (14.56) 90 (3.54) 331.1 (13.04) 4 (0.16) M8 47.2 (104.07)
4 E510-450-SH3F 288.9 (11.37) 220 (8.66) 220 (8.66) 652 (25.67) 620 (24.41) 369.8 (14.56) 90 (3.54) 331.1 (13.04) 4 (0.16) M8 47.2 (104.07)
5 E510-460-SH3F 288.9 (11.37) 220 (8.66) 220 (8.66) 652 (25.67) 620 (24.41) 369.8 (14.56) 90 (3.54) 331.1 (13.04) 4 (0.16) M8 47.2 (104.07)
6 E510-475-SH3F 288.9 (11.37) 220 (8.66) 220 (8.66) 652 (25.67) 620 (24.41) 369.8 (14.56) 90 (3.54) 331.1 (13.04) 4 (0.16) M8 47.2 (104.07)

Manual — IP66 dimensions:200V0.5–1HP;400V1–2HP — page 64

Manual reference: physical PDF page 64. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

IP66 Dimensions

200V Single phase:0.5~1HP

200V Single/Three phase:0.5~1HP

400V Three phase:1~2HP

Outline drawing labels:W,W1,H,H1,D,D1,D2,diameter6.8. Numerical model-linked dimensions andunits preserved in adjacent originaltable;no unlabelleddimensions inferred. Tinyembeddedkeypad/nameplateinscriptions unresolved;dimensionlabelsreviewed separately.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/nameplate inscriptions remain partly unresolved after two visual full-page readings and5xbounded hardware crop. All explicit dimension labels, model-linked numeric tables, source units and procedure text retained. No inferred inscriptions or wiring.

IP66 dimensions:200V0.5–1HP;400V1–2HP

Inverter Model / Dimensions in mm (inch) / Net Weight in Kg/(lbs) — PDF page 64

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Inverter Model Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Net Weight in Kg/(lbs)
2 Inverter Model W W1 H H1 D D1 D2 Ø Net Weight in Kg/(lbs)
3 E510-2P5-SH1FN4S 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0/(6.6)
4 E510-201-SH1FN4S 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0/(6.6)
5 E510-2P5-SH1FN4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0/(6.6)
6 E510-201-SH1FN4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0/(6.6)
7 E510-2P5-SHN4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0/(6.6)
8 E510-201-SHN4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0/(6.6)
9 E510-401-SH3FN4S 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0/(6.6)
10 E510-402-SH3FN4S 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0/(6.6)
11 E510-401-SH3FN4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0/(6.6)
12 E510-402-SH3FN4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0/(6.6)
13 E510-401-SH3N4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0/(6.6)
14 E510-402-SH3N4 229 (9.01) 211 (8.30) 298 (11.73) 269 (10.59) 202.6 (7.97) 122.1 (4.80) 82.1 (3.23) M6 3.0/(6.6)

Manual — IP66 dimensions:200V2–3HPsingle,5HPthree;400V3–5HP — page 65

Manual reference: physical PDF page 65. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

200V Single phase:2~3HP 200V Three phase:5HP 400V Three phase:3~5HP

Outline drawing labels:W,W1,H,H1,D,D1,D2,diameter7. Numerical model-linked dimensions andunits preserved in adjacent originaltable;no unlabelleddimensions inferred. Tinyembeddedkeypad/nameplateinscriptions unresolved;dimensionlabelsreviewed separately.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/nameplate inscriptions remain partly unresolved after two visual full-page readings and5xbounded hardware crop. All explicit dimension labels, model-linked numeric tables, source units and procedure text retained. No inferred inscriptions or wiring.

IP66 dimensions:200V2–3HPsingle,5HPthree;400V3–5HP

Inverter Model / Dimensions in mm (inch) / Net Weight Kg/(lbs) — PDF page 65

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Inverter Model Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Net Weight Kg/(lbs)
2 Inverter Model W W1 H H1 D D1 D2 Ø Net Weight Kg/(lbs)
3 E510-202-SH1FN4S 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)
4 E510-203-SH1FN4S 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)
5 E510-202-SH1FN4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)
6 E510-203-SH1FN4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)
7 E510-202-SHN4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)
8 E510-203-SHN4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)
9 E510-205-SH3N4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)
10 E510-403-SH3FN4S 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)
11 E510-405-SH3FN4S 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)
12 E510-403-SH3FN4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)
13 E510-405-SH3FN4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)
14 E510-403-SH3N4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)
15 E510-405-SH3N4 198 (9.63) 115 (5.59) 335 (16.30) 315 (15.33) 235.3 (11.45) 153.6 (7.47) 113.6 (5.53) M6 5.9/(13.0)

Manual — IP66 dimensions:200V7.5–20HP,400V7.5–25HP — page 66

Manual reference: physical PDF page 66. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

200V Three phase:7.5~20HP

400V Three phase:7.5~25HP

Outline drawing labels:W,W1,H,H1,D,D1,D2,diameter7. Numerical model-linked dimensions andunits preserved in adjacent originaltable;no unlabelleddimensions inferred. Tinyembeddedkeypad/nameplateinscriptions unresolved;dimensionlabelsreviewed separately.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/nameplate inscriptions remain partly unresolved after two visual full-page readings and5xbounded hardware crop. All explicit dimension labels, model-linked numeric tables, source units and procedure text retained. No inferred inscriptions or wiring.

IP66 dimensions:200V7.5–20HP,400V7.5–25HP

Inverter Model / Dimensions in mm (inch) / Net Weight Kg/(lbs) — PDF page 66

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Inverter Model Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Dimensions in mm (inch) Net Weight Kg/(lbs)
2 Inverter Model W W1 H H1 D D1 D2 Ø Net Weight Kg/(lbs)
3 E510-208-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
4 E510-210-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
5 E510-215-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
6 E510-220-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
7 E510-408-SH3FN4S 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
8 E510-410-SH3FN4S 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
9 E510-415-SH3FN4S 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
10 E510-408-SH3FN4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
11 E510-410-SH3FN4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
12 E510-415-SH3FN4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
13 E510-408-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
14 E510-410-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
15 E510-415-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
16 E510-420-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)
17 E510-425-SH3N4 223 (10.58) 140 (6.81) 460 (22.39) 440 (21.42) 263.5 (12.82) 180 (8.76) 130 (6.32) M6 13.0/(28.6)

Manual — EMC filter disconnection, supply-system conditions and four steps — page 67

Manual reference: physical PDF page 67. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

3.8 EMC filter disconnection

EMC filter may be disconnected: Inverter drives with built-in EMC filter are not suitable for connection to certain type of supply systems, such as listed below; in these cases the RFI filter can be disabled. In all such cases consult your local electrical standards requirements. IT type supply systems (ungrounded) & certain supply systems for medical equipment. For ungrounded supply systems If the filter is not disconnected the supply system becomes connected to Earth through the Y capacitors on the filter circuit. This could result in danger and damage to the Drive. Disconnection steps : (1) Remove the front cover. (2) Loosen the screw. (3) Remove the metal link. (4) Tighten the screw. Note:Disconnecting the EMC filter link will disable the filter function, please consult your local EMC standards requirement.

(1) (2) (3) (4)

Four mechanical pictures numbered(1),(2),(3),(4)correspond to foursourceprose steps;source warning conditionsabove retained. Tinyembeddedkeypad/nameplate/controlterminalinscriptionsunresolved. Noadditionalconnectioninstructions inferred. Enlarged visible first front-view label: 1PH-220V-0.75kW;DANGER:Cut off the power and wait for5minutes before inspecting components. CAUTION:See manual before operation.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/nameplate inscriptions remain partly unresolved after two visual full-page readings and5xbounded hardware crop. All explicit dimension labels, model-linked numeric tables, source units and procedure text retained. No inferred inscriptions or wiring.

Manual — Operator-panel dimensions and surface installation — page 68

Manual reference: physical PDF page 68. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Operator-panel and surface-installation dimensions have no printed unit on this page. All visible values/tolerances/M3 and labels retained; unit/applicability not inferred.

3.9 The dimension and installation of operator panel

3.9.1 Description of dimension and installation

(IP20/NEMA1) The operator panel has a LED display and can be removed for remote

installation. Installation and dimension information are as follows:

➢ Dimension

➢ Surface installation diagram

Operator-paneldimension drawing:front59horizontalmountspacing,88verticalmountspacing,71overallwidth,100overallheight. SideM3,18.2,28.4,16,11.2,14.9. Lowerplan6.4,8.8,2,31,18,11.3,8.3. Dimensions exactlyasdrawn;unitnotprintedonthispage,notassumed. KeylabelsHz/RPM,FWD,REV,FUN;FWD/REV,DSP/FUN,RESET,READ/ENTER,RUN,STOP andarrowkeys.

Surfaceinstallationdimension drawing:42.2±0.15,71.9±0.15,88.0±0.15,59.0±0.15;slot20by20. Here is the slot to connect the line of RJ45. Use M3 screw to secure the operator panel to the mounting surface. No unitprintedonthispage;noinference.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Operator-panel and surface-installation dimensions have no printed unit on this page. All visible values/tolerances/M3 and labels retained; unit/applicability not inferred.

Manual — Operator-panel protective cover installation — page 69

Manual reference: physical PDF page 69. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh full-page and 6x bounded illustration read confirm explicit procedures/callouts/dimensions already captured; some tiny embedded keypad or nameplate glyphs remain pixelated or obscured. The separate readable keypad description on PDF70 is context only, not a license to fill this drawing.

3.9.2 Description of protective cover

For remote installation of the operator panel, to avoid ingress of dust, use the supplied protective

cover.

Step3:Mount the self-adhesive protective cover as per diagram below. Push into position to locate.

Step 4:Installation is completed.

Here is the bottom of the slot

Step1:Loosen the four screws of the operator panel

Step2:Take out the operator panel

Here is the ligulate structure

Protective-coverinstallationpicturesstep1loosenfourscrews;step2takeoutoperatorpanel;step3mountself-adhesiveprotectivecover,pushintoposition;step4completed. Callouts:Here is the bottom of the slot;Here is the ligulate structure. Embeddedplatelegible1PH-220V-0.75kW,DANGER,CAUTION,butremainingtinywarning/keypadinscriptionsunresolved. Explicitprosekeptseparately. Enlarged visible first front-view label: 1PH-220V-0.75kW;DANGER:Cut off the power and wait for5minutes before inspecting components. CAUTION:See manual before operation. Keypad firstview:Hz/RPM,FWD,REV,FUN,FWD/REV,DSP/FUN,RESET,READ/ENTER,RUN,STOP,FREQ.SET andarrowkeys;otherangledfiguresremainpartial.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded hardware/keypad/nameplate inscriptions remain partly unresolved after two visual full-page readings and5xbounded hardware crop. All explicit dimension labels, model-linked numeric tables, source units and procedure text retained. No inferred inscriptions or wiring.

Manual — Operator-panel functions and digital display/keypad labels — page 70

Manual reference: physical PDF page 70. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 4 Software Index

4.1 Keypad description

4.1.1 Operator panel functions

Operatorpanelphoto:Hz/RPM,FWD,REV,FUN;FWD/REV,DSP/FUN,RESET,leftarrow,up/downarrows,READ/ENTER;FREQ.SET;greenRUN,redSTOP. Allunlitdisplaysegmentsillustrative;notameasurement.

Operator-panel functions and digital display/keypad labels

Type / Item / Functions — PDF page 70

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Type Item Functions
2 Digital display & LEDs Main digital displays Frequency Display, Parameter, voltage, Current, Temperature, Fault messages.
3 Digital display & LEDs LED Status Hz/RPM:ON, when the frequency or line speed is displayed. OFF, when parameters are displayed. FWD:ON, while the inverter is running forward, flashes while stopping. REV:ON, while the inverter is running reverse, flashes while stopping. FUN:ON, when parameters are displayed. OFF, when the frequency is displayed.
4 Variable Resistor FREQ SET Used to set the frequency
5 Function keys (8 bottons) RUN Run at the set frequency.
6 Function keys (8 bottons) STOP Decelerate or Coast to Stop.
7 Function keys (8 bottons) ▲ Increment parameter number and preset Values.
8 Function keys (8 bottons) ▼ Decrement parameter number and preset Values.
9 Function keys (8 bottons) FWD/REV (Dual function keys) FWD:Forward Run REV:Reverse Run
10 Function keys (8 bottons) DSP/FUN (Dual function keys) DSP:Switch between available displays FUN:Used to examine the parameter content
11 Function keys (8 bottons) </ RESET (Dual function keys) < (Left Shift):Changing the parameters or parameter Values RESET:Use to Reset alarms or resettable faults
12 Function keys (8 bottons) READ/ENTER (Dual function keys) Used to display the preset Value of parameters and for saving the changed parameter Values.

Manual — Alphanumeric LED glyphs and flashing instructions — page 71

Manual reference: physical PDF page 71. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.2 Digital display description

Alpha numerical display format

Digital tube lights flashing instructions

LED alphabet row1:Digit0shownasLED0;LetterAshownasLEDA;LetterLshownasLEDL;SymbolYshownasy.Segmentshapeinterpretationlimitedtovisibleglyph;sourcecropretained.

LED alphabet row2:Digit1shownasLED1;LetterBshownasLEDb;LetternshownasLEDn;Symbol-shownasmiddlebar.Segmentshapeinterpretationlimitedtovisibleglyph;sourcecropretained.

LED alphabet row3:Digit2shownasLED2;LetterCshownasLEDC;LetteroshownasLEDO-shaped full-heightglyph;Symbol°shownasupperloop.Segmentshapeinterpretationlimitedtovisibleglyph;sourcecropretained.

LED alphabet row4:Digit3shownasLED3;LetterDshownasLEDd;LetterPshownasLEDP;Symbol_shownasbottomsegment.Segmentshapeinterpretationlimitedtovisibleglyph;sourcecropretained.

LED alphabet row5:Digit4shownasLED4;LetterEshownasLEDE;LetterqshownasLEDq;Symbol.shownasdot.Segmentshapeinterpretationlimitedtovisibleglyph;sourcecropretained.

LED alphabet row6:Digit5shownasLED5;LetterFshownasLEDF;LetterrshownasLEDr;Symbol/LEDlastpairblank.Segmentshapeinterpretationlimitedtovisibleglyph;sourcecropretained.

LED alphabet row7:Digit6shownasLED6;LetterGshownasLEDG;LetterSshownasLEDS;Symbol/LEDlastpairblank.Segmentshapeinterpretationlimitedtovisibleglyph;sourcecropretained.

LED alphabet row8:Digit7shownasLED7;LetterHshownasLEDH;LettertshownasLEDt;Symbol/LEDlastpairblank.Segmentshapeinterpretationlimitedtovisibleglyph;sourcecropretained.

LED alphabet row9:Digit8shownasLED8;LetterIshownasLEDI;LetterushownasLEDu;Symbol/LEDlastpairblank.Segmentshapeinterpretationlimitedtovisibleglyph;sourcecropretained.

LED alphabet row10:Digit9shownasLED9;LetterJshownasLEDJ;LetterVshownasLEDU-shaped full-heightglyph;Symbol/LEDlastpairblank.Segmentshapeinterpretationlimitedtovisibleglyph;sourcecropretained.

Digitaltubeillustrations:Actualoutputfrequency5.00,DigitsarelitContinually;Setfrequency5.00,presetdigitsflashing;Setfrequency5.00,selecteddigitflashing. Blacktrianglesmarkflashing;grayunlitsegmentsnottranscribedasdigits.

Alphanumeric LED glyphs and flashing instructions

Digit / LED / Letter / Symbol — PDF page 71

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows)
1 Digit LED Letter LED Letter LED Symbol LED
2 0 [LED glyph: 0] A [LED glyph: A] L [LED glyph: L] Y [LED glyph: y]
3 1 [LED glyph: 1] B [LED glyph: b] n [LED glyph: n] - [LED glyph: middlebar]
4 2 [LED glyph: 2] C [LED glyph: C] o [LED glyph: O-shaped full-heightglyph] ° [LED glyph: upperloop]
5 3 [LED glyph: 3] D [LED glyph: d] P [LED glyph: P] _ [LED glyph: bottomsegment]
6 4 [LED glyph: 4] E [LED glyph: E] q [LED glyph: q] . [LED glyph: dot]
7 5 [LED glyph: 5] F [LED glyph: F] r [LED glyph: r] ⟦blank source cell⟧ ⟦blank source cell⟧
8 6 [LED glyph: 6] G [LED glyph: G] S [LED glyph: S] ⟦blank source cell⟧ ⟦blank source cell⟧
9 7 [LED glyph: 7] H [LED glyph: H] t [LED glyph: t] ⟦blank source cell⟧ ⟦blank source cell⟧
10 8 [LED glyph: 8] I [LED glyph: I] u [LED glyph: u] ⟦blank source cell⟧ ⟦blank source cell⟧
11 9 [LED glyph: 9] J [LED glyph: J] V [LED glyph: U-shaped full-heightglyph] ⟦blank source cell⟧ ⟦blank source cell⟧

Actual output frequency / Set frequency — PDF page 71

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Actual output frequency Set frequency Set frequency
2 Digits are lit Continually Preset digits flashing Selected digit flashing
3 [LED illustration: 5.00 continuously lit] [LED illustration: 5.00 preset digits flashing] [LED illustration: 5.00 selected digit flashing]

Manual — LED display examples and meanings — page 72

Manual reference: physical PDF page 72. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED display examples

LEDdisplayexample row1:litblackglyphs005.00. Grayoutlineunlitsegmentsnotvalues. Correspondingdescriptionretainedintablerow;literalrenderingnotengineeringmeasurement.

LEDdisplayexample row2:litblackglyphs00-01. Grayoutlineunlitsegmentsnotvalues. Correspondingdescriptionretainedintablerow;literalrenderingnotengineeringmeasurement.

LEDdisplayexample row3:litblackglyphs00000 (no decimal point visibly lit). Grayoutlineunlitsegmentsnotvalues. Correspondingdescriptionretainedintablerow;literalrenderingnotengineeringmeasurement.

LEDdisplayexample row4:litblackglyphs220u (lastcellunlit). Grayoutlineunlitsegmentsnotvalues. Correspondingdescriptionretainedintablerow;literalrenderingnotengineeringmeasurement.

LEDdisplayexample row5:litblackglyphs001.1A (black decimal point after third digit). Grayoutlineunlitsegmentsnotvalues. Correspondingdescriptionretainedintablerow;literalrenderingnotengineeringmeasurement.

LEDdisplayexample row6:litblackglyphs03100 (no decimal point visibly lit). Grayoutlineunlitsegmentsnotvalues. Correspondingdescriptionretainedintablerow;literalrenderingnotengineeringmeasurement.

LEDdisplayexample row7:litblackglyphs024°C. Grayoutlineunlitsegmentsnotvalues. Correspondingdescriptionretainedintablerow;literalrenderingnotengineeringmeasurement.

LEDdisplayexample row8:litblackglyphs000--. Grayoutlineunlitsegmentsnotvalues. Correspondingdescriptionretainedintablerow;literalrenderingnotengineeringmeasurement.

LEDdisplayexample row9:litblackglyphsErr1 (lastcellunlit). Grayoutlineunlitsegmentsnotvalues. Correspondingdescriptionretainedintablerow;literalrenderingnotengineeringmeasurement.

LEDdisplayexample row10:litblackglyphs000P (firstcellunlit). Grayoutlineunlitsegmentsnotvalues. Correspondingdescriptionretainedintablerow;literalrenderingnotengineeringmeasurement.

LED display examples and meanings

Display / Description — PDF page 72

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Display Description
2 [LED lit glyphs: 005.00] In stop mode shows the set frequency In run mode shows the actual output frequency
3 [LED lit glyphs: 00-01] Selected Parameter
4 [LED lit glyphs: 00000 (no decimal point visibly lit)] Parameter Value
5 [LED lit glyphs: 220u (lastcellunlit)] Output Voltage
6 [LED lit glyphs: 001.1A (black decimal point after third digit)] Output Current in Amps
7 [LED lit glyphs: 03100 (no decimal point visibly lit)] DC Bus voltage
8 [LED lit glyphs: 024°C] Temperature
9 [LED lit glyphs: 000--] PID feedback Value, based on setting value of 12-01
10 [LED lit glyphs: Err1 (lastcellunlit)] Error display, please refer the contents in chapter 5
11 [LED lit glyphs: 000P (firstcellunlit)] Analogue Current / Voltage AI1 / AI2 . Range ( 0~100%)

Manual — LED status and12-00display setup — page 73

Manual reference: physical PDF page 73. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED status description

4.1.3 LED display setup

On power up, digital display screens will be shown below.

User selectable display formats:

The highest bit of 12-00 sets the power on the display, other bits set the selected display from range

0-7, as the liste above.

LEDstatustablegreenindicators:Hz/RPM,FUN,FWD,REV;flashingblacktrianglesforFUNfiremode,FWDstoppedforward,REVstoppedreverse. Exactstatusprosepreservedintable.

Power-updisplayflow:220u Powersupply(flashing),2sec later005.00 Frequency(flashing);DSP/FUN switches to00-01Parameter;DSP/FUNreturnsFrequency. Onlylitblackglyphstranscribed.

LED status and12-00display setup

/ LED indicator light status / LED indicator flashing status — PDF page 73

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 ⟦blank source cell⟧ LED indicator light status LED indicator light status LED indicator flashing status LED indicator flashing status
2 Frequency / Line speed Indicator Hz/RPM ON while displaying frequency or linear speed ON while displaying frequency or linear speed ON while displaying frequency or linear speed
3 Menu mode indicator FUN ON while not displaying frequency or line speed ⟦blank source cell⟧ Flashing while fire mode enabled
4 FWD indicator FWD ON while running forward FWD Flashing while stopped in Forward mode.
5 REV indicator REV ON while running reverse REV Flashing while stopped in Reverse mode

12- 00 / Display mode — PDF page 73

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 12- 00 Display mode
2 Range 0 0 0 0 0 High Low Each of the 5 digis can be set to any of the selections below from 0~8. 【0】:Display display 【1】:Output current 【2】:Output voltage 【3】:DC voltage 【4】:Temperature 【5】:PID feedback 【6】:AI1 input value 【7】:AI2 input value 【8】:Counter Value

Manual — Display examples12-00=10000/12345 and increment/decrement keys — page 74

Manual reference: physical PDF page 74. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example1:Set parameter 12- 00=【10000】to obtain display format shown below.

Example 2. Set parameter 12- 00=【12345】 to obtain the display format shown below

Increment/ Decrement key functions:

“▲key”/ “▼key”:

Short time press

Long time press

T2

T1

Quick pressing of these kwys will increment or decrement the selected digit by one. Extended pressing will increment or decrement the selected digit continuously.

Example1parameter12-00=10000:220u Display:Power supply;3sec later000.0A Outputcurrent;DSP/FUNtoggles005.00Setfrequency(flashing),00-01Parameter,backtoOutputcurrent asarrowsdrawn. Noengineeringbehaviorinferredbeyondsourceexample.

Example2parameter12-00=12345:220u Display:powersupply;3sec later000.0A Outputcurrent<1>. DSP/FUNsequence005.00Setfrequency,00-01Parameter,000.0u Outputvoltage<2>,03100DCvoltage<3>,024°CHeatsinktemperature<4>,00000PIDfeedback<5>,backtoOutputcurrent. Grayunlitsegmentsnotvalues;literalillustration.

Increment/decrementkeytimingplot:Short time press withT1;Long time presswithT2. NeitherT1norT2numericdurationisprinted. Prosequickenpressincrements/decrementsselecteddigitbyone;extendedpresscontinuously.

Manual — 4.1.4 Example of keypad operation — Example1: Modifying parameters — page 75

Manual reference: physical PDF page 75. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example display values only, not recommended settings. Arrow order transcribed; blinking-cursor locations and unlit display segments remain visible in original.

No duration assumed for Short press or the dashed automatic display transition.

Illustrative workflow, including repeated00-01screens with different cursor positions. Do not omit repeated screens or infer missing key presses.

Example1 display/action sequence — PDF page 75

Source row Step From display Printed action or arrow To display
1 1 005.00 (Frequency display) Short press DSP/FUN once 00-01
2 2 00-01 Short press </RESET once 00-01
3 3 00-01 Short press </RESET once 00-01
4 4 00-01 Short press ▲ once 00-02
5 5 00-02 Short press DATA/ENTER once 00001
6 6 00001 Short press ▲ once 00002
7 7 00002 Short press DATA/ENTER once -End-
8 8 -End- Dashed arrow; no key or duration printed 00002
9 9 00002 Short press DSP/FUN once 00-02

Manual — Modify frequency from keypad: stopped and operating examples — page 76

Manual reference: physical PDF page 76. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example 2:Modifying the frequency from keypad in run and stop modes

Modify frequency in stopping Modify frequency in operating

3sec later

Press RUN once

Power supply Power supply

Actual frequency

Set frequency display

Frequency setting complete

Modify bit <unit>

Press READ / ENTER once

Press < / RESET once

Without pressing the botton</ENT, display will be returned 5 seconds later

Short

press ▲ once

Press ▲ once

Modify bit <ten> Modify bit <ten>

Press < / RESET once Press < / RESET once

Modify bit <hundred> Modify bit <hundred>

Short press ▲once Short press ▲once

Modify bit <hundred+1> Modify bit <hundred+1>

Example2frequencykeypadflow,stoppedandoperating. Bothstart220upowersupply,3sec later005.00setfrequency. Stopped:shortpress▲once005.01modifybit<unit>;press▲once005.00asprinted;alternativepress</RESEToncedirectly005.00modifybit<unit>. Further</RESEToncechangesselectedbit<ten>,then<hundred>;shortpress▲once006.00<hundred+1>;READ/ENTERonce006.00frequencysettingcomplete. Operating:RUNonce005.00actualfrequency;three</RESETonceoperationsselect<unit>,<ten>,<hundred>;shortpress▲once006.00<hundred+1>;READ/ENTERonce006.00actualfrequency. Sourceannotation:Withoutpressingthebutton</ENT,displaywillbereturned5secondslater. Preservecaption/hardwareglyphdiscrepancy;nooperationalvalidation.

Manual — 4.1.5 Operation control — page 77

Manual reference: physical PDF page 77. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Qualitative frequency/command/LED diagram. No frequency amplitudes, durations or acceleration rates printed; none inferred. Original retains trace geometry and exact edge alignments.

LED states below describe visible glyphs, not an independently inferred meaning of filled/hollow/flashing. Seven displayed intervals read left-to-right; not a row of one state per command event.

Sequence labels preserve source case; no numeric timing or control setting implied.

Literal glyph transcription; source waveform and vertical boundaries remain original-only visual information.

Diagram labels — PDF page 77

Source row Source label/context Source value
1 Top status regions Stop; Run; Stop
2 Trace Actual output frequency
3 Command arrows left-to-right Power on; REV; FWD; Run; REV; FWD; Stop
4 Indicator rows FWD LED; REV LED

Visible indicator glyphs by displayed interval — PDF page 77

Source row Interval left-to-right FWD LED glyph REV LED glyph
1 1 Filled circle with rays Hollow circle
2 2 Hollow circle Filled circle with rays
3 3 Filled circle with rays Hollow circle
4 4 Filled circle Hollow circle
5 5 Hollow circle Filled circle
6 6 Filled circle Hollow circle
7 7 Filled circle with rays Hollow circle

Manual — JN5-OP-A02 LCD keypad, indicators and modes — page 78

Manual reference: physical PDF page 78. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.6 LCD keypad

LCD display (JN5-OP-A02) built-in internal memory can upload or download from one inverter to

another one, please refer the functions of LCD keypad.

LCDphotoandcallouts:LEDFAULTonfault/alarm,FWDforward,REVreverse,SEQruncommandfromexternalcontrolorcommunication,REFfrequencyreferencecommandfromexternalcontrolorcommunication. LCDdisplay8lines×25letters;monitoringvalueandparametersetting;modedisplayupperleft. Monitor:drivemode;Group:modesetting;PARA:parametersettingmode;Edit:editorauto-tunemode. DisplayliteralMonitor,Fref Ref,12-16=005.00Hz,12-17=000.00Hz,12-18=0000.0A. KeysFWD/REV,DSP/FUN,</RESET,READ/ENTER,▲,▼,RUN,STOP. FunctionkeysreferLEDkeypad. Figure4.1.6.1LCDdisplay;JN5-OP-A02memoryprosepreserved.

Manual — Keypad main-menu structure and auto-tune conditions — page 79

Manual reference: physical PDF page 79. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.7 Keypad menu structure

➢ Main menu The E510s inverter parameters consists of four main modes. The DSP/FUN key is used to switch between these modes. (Please refer Fig.4.1.7.1)

Power On

Power Up

Monitor Mode

Parameter Group Mode

Parameter Edit Mode

View inverter status, signals and fault data

Assess to available parameter groups

Select parameter group

Auto-tune function of motor

Auto-tune Mode

Change parameter setting

Fig. 4.1.7.1 Parameter Group Structure

Notes:

➢ Always perform an auto-tune on the motor before operating the inverter in sensorless vector control. Auto-tune mode will not be displayed when the inverter is running or when a fault is active. ➢ To scroll through the available modes, parameter groups or parameter list press and hold the up or down key.

Mainmenuflowlabels:PowerOn→PowerUp→MonitorMode(Viewinverterstatus,signalsandfaultdata). DSP/FUNdown→ParameterGroupMode(Assesstoavailableparametergroups);READ/ENTERdown→ParameterGroupMode(Selectparametergroup),literalduplicatedheading;READ/ENTERdown→ParameterEditMode(Changeparametersetting);RUNdown→Auto-tuneMode(Auto-tunefunctionofmotor). EachupreturnarrowDSP/FUN. Sourceprosefourmainmodesretained;noinferredcorrectedmodename.

Manual — 4.1.8 Monitoring Mode; LCD examples and navigation — page 80

Manual reference: physical PDF page 80. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.8 Monitoring Mode

In monitor mode inverter signals can be monitored such as output frequency, output current and

output voltage, etc…) as well as fault information and fault trace. See Fig.4.1.8.1.

Fig.4.1.8.1 Monitoring Mode

Fig.4.1.8.1 Monitoring Mode. Power ON enters Monitor/Freq Ref:12-16=005.00Hz;12-17=000.00Hz;12-18=0000.0A. Down/up keys move to Monitor/Flt Freq Ref:12-15=000.00Hz;12-17=000.00Hz;12-18=0000.0A, then Monitor/Flt DC Voltage:12-14=0000.0V;12-17=000.00Hz;12-18=0000.0A. Each has DSP/FUN arrow to Group:00 Basic Func.,01 V/F Pattern.,02 Motor Parameter; DSP/FUN returns to monitor. Display examples only.

Manual — 4.1.9 Programming Mode; LCD examples and notes — page 81

Manual reference: physical PDF page 81. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.9 Programming Mode

In programming mode inverter can be read or changed. Please refer Fig.4.1.9.1。

Fig.4.1.9.1 Programming Mode

Notes:

(1) The parameters value can be changed from the edit screen with the function keys.

(2) To save a parameter press the READ/ENTER key.

(3) Refer to section 4.3 for parameter details.

(4) Press the ▲ (up) or ▼ (down) key to scroll parameter groups or parameter list.

Fig.4.1.9.1 Programming Mode. Monitoring Mode:Power ON;Monitor Freq Ref12-16=000.00Hz;12-17=000.00Hz;12-18=000.00Hz [literal source unit differs from80]. DSP/FUN enters Parameter Group Selection Mode:Group00 Basic Fun.,01 V/F Pattern,02 Motor Parameter; up/down select. READ/ENTER enters Parameter Group Mode/PARA00:-00 Control Method,-01 Motor Direction,-02 Run Source. Up/down move selection and continuation markers1/2. READ/ENTER enters Parameter Edit Mode:00-00 Control Method,0 V/F,(0~4),<0>;00-01 Motor Direction,0 Forward,(0~1),<0>;00-02 Run Source,0 Digital Op,(0~4),<1>. DSP/FUN returns from edit; left RESET returns first selected parameter to group list. Groups01/02 READ/ENTER arrows:To parameters;DSP/FUN returns. Group down/up continuation A/B. These are literal illustrative screens; parameter list conflicts are flagged.

Manual — Parameter group setting diagram and procedure — page 82

Manual reference: physical PDF page 82. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig.4.1.9.2 Parameter group setting

➢ Use ▲(up)/▼(down) key or <(left) key to change the parameter setting value, when you press

READ/ENTER key, setting value will be saved and then display will flash again after a few seconds.

Fig.4.1.9.2 Parameter group setting. Example screen:Group/G01-01;Language;0 English;(0~0);<0>. Callouts:Parameter group setting→Group;Parameter→G01-01;Function name→Language;Setting value→0 English;Setting ragne [source spelling]→(0~0);Factory setting→<0>. Example identifier/range differs from00-34 language list on87; preserved separately.

Manual — 4.1.10 Auto-tune Mode; flowchart and notes continued on84 — page 83

Manual reference: physical PDF page 83. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Two key symbols in auto-tune warning are box-like/unrendered even at6x source crop. Warning against rotational tuning with coupled load and all other flow/procedure/safety notes retained; no key identity inferred.

4.1.10 Auto-tune mode

In the auto-tune mode, motor parameters can be calculated ans set automatically based on the

selected control mode. See Fig.4.1.10.1 for keypad navigation。

Notes:

(1) Use the up and down keys to scroll though the auto-tuning parameter list. Depending on the selected control

mode in parameter 00-00, part of auto-tuning parameters will not be accessible.

(Refer to the Auto-tuning Group 17 parameters).

(2) After entering the motor nameplate rated output power (17-01), rated current (17-02), rated voltage (17-03),

rated frequency (17-04), rated speed (17-05) and number of motor poles (17-06), select the automatic tuning

mode and press the RUN key to perform the auto-tuning operation. When auto-tuning is successful the

calculated motor parameters will be saved into parameter group 02 (motor parameter). (3) When inverter executes auto-tune function:

(a) (Rotational) will be displayed during rotational auto-tuning (17-00=0) and the motor will rotate

during auto-tuning. Ensure that it is safe to operate the motor before pressing the RUN key.

(b) (Stationary) will be displayed during stationary auto-tuning (17-00=1), the motor shaft does not rotate.

(c) (R1 Tuning) will be displayed during stationary auto-tuning (17-00=2), the motor shaft does not rotate.

Fig.4.1.10.1 Auto-tune Mode. Group17 Auto-tuning,18 Slip Compen,19 Traverse Func. READ/ENTER→PARA17:-01 Tune Mode Sel,-02 Motor Rated Power,-03 Motor Rated Curr.; up/down changes selection. READ/ENTER→Edit17-00 Tune Mode Sel:0 Rotational,(0~2),<0>;Edit17-01 Motor Rated Power:5.50KW,(0.00–600.00),<5.50>;Edit17-02 Motor Sel:0006.8A,(0000.9~0009.2),<0006.8>. *1HP=0.746KW. Edit warning:Press [unresolved box-like key glyph] or [unresolved box-like key glyph] key to change the value. Warning:Do not use “0”,Rotation Auto-tune,when load is coupled with the motor. Literal parameter numbers/labels differ between list and edit displays; flagged, not corrected.

Auto-tune lower flow:PARA17:-08 Mtr No-Load Volt,-10 Auto-tuning Run,-11 Auto-tuning Err. READ/ENTER→Edit17-10 Auto-tuning Run,1 Enable,(0~1),<0>. READ/ENTER→Edit Autotuning ?,000.00Hz–000.0A,(Press Run Key). RUN→Edit Autotuning,progress chevrons,48.0Hz–14.0A,(Rotational). STOP branch→Autotuning,0.0Hz–0.0A,Aborted. Tuning successful→Autotuning,48.0Hz–14.0A,Successful. Tuning fault→ATE01,Motor Data Error,Uncompleted. DSP/FUN returns group. Procedure and safety notes continue83–84; screen examples are not engineering instructions independently of those notes.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Two key symbols in auto-tune warning are box-like/unrendered even at6x source crop. Warning against rotational tuning with coupled load and all other flow/procedure/safety notes retained; no key identity inferred.

Manual — Auto-tune notes continued from83; abort, fault and success conditions — page 84

Manual reference: physical PDF page 84. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(d) The RUN LED (in the upper left corner of the RUN key) will be lit during auto-tuning.

(e) The LCD display shows “>>>” or "Atund" during the auto-tuning process.

(4) Press the STOP key on the keypad to abort the auto-tuning operation。

(5) In case of an auto-tuning fault, a fault message and the uncompleted message are displayed on the keypad.

The RUN LED will be flashing and the motor will coast to stop. (Refer to section 10.4 for the Auto-tuning

Faults.) The auto-tuning fault can be cleared by pressing the RESET key after which the keypad displays the

auto-tuning mode again.

(6) Upon successful completion of an auto-tune, the RUN LED will turn off. Press the DSP/FUN key to return to

the main menu to select the next operation. The auto-tuning procedure takes approximately 50 seconds.

Manual — 4.2 Parameter Group listing and attribute definitions — page 85

Manual reference: physical PDF page 85. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.2 Parameters

4.2 Parameter Group listing and attribute definitions

Parameter group / Group Name — PDF page 85

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Parameter group Group Name
2 Group 00 Basic Parameters
3 Group 01 V/F Control Parameters
4 Group 02 IM Motor Parameters
5 Group 03 External Digital Input and Output Parameters
6 Group 04 External Analog Input and Output Parameters
7 Group 05 Multi-Speed Parameters
8 Group 06 Automatic Program Operation Parameters
9 Group 07 Start /Stop Parameters
10 Group 08 Protection Parameters
11 Group 09 Communication Parameters
12 Group 10 PID Parameters
13 Group 11 Auxiliary Parameters
14 Group 12 Monitoring Parameters
15 Group 13 Maintenance Parameters
16 Group 14 PLC Parameters
17 Group 15 PLC Monitoring Parameters
18 Group 16 LCD Parameters
19 Group 17 Automatic Tuning Parameters
20 Group 18 Slip Compensation Parameters
21 Group 20 Speed Control Parameters
22 Group 21 Torque And Position Control Parameters
23 Group 22 PM Motor Parameters
24 Group 23 Constant Pressure PUMP Parameters

Parameter Attribute — PDF page 85

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Parameter Attribute Parameter Attribute
2 *1 Parameters can be changed during run operation.
3 *2 Reserved
4 *3 Parameter will not reset to default during a factory reset (initialization).
5 *4 Read-only parameter
6 *5 Parameter will be displayed in being coupled with the option card.
7 *6 Parameter will be displayed only in LED keypad.
8 *7 Parameter will be displayed only in LCD keypad.
9 *8 When 13-08 setting is changed, the value will be also changed.

Manual — Group00 Basic Parameters; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 86

Manual reference: physical PDF page 86. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group00 Basic Parameters; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 00 Basic Parameters — PDF page 86

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 00-00 Control Mode Selection 0:V/F 2:SLV 5:PMSLV 0 - O O O *3
5 00-01 Motor’s Rotation Direction 0:Forward 1:Reverse 0 - O O O *1
6 00-02 Main Run Command Source Selection 0:Keypad 1:External Terminal (Control Circuit) 2:Communication Control (RS-485) 3:PLC 1 - O O O ⟦blank source cell⟧
7 00-03 Alternative Run Command Selection 0:Keypad 1:External Terminal (Control Circuit) 2:Communication Control (RS-485) 3:PLC 0 - O O O ⟦blank source cell⟧
8 00-04 Operation Modes For External Terminals 0:Forward/Stop-Reverse/Stop 1:Run/Stop- Reverse/Forward 2:3 Wire Control Mode Run/Stop 0 - O O O ⟦blank source cell⟧
9 00-05 Main Frequency Command Source Selection 0:UP/DOWM of Keypad 1:Potentiometer on Keypad 2:External AI1 Analog Signal Input 3:External AI2 Analog Signal Input 4:External Up/Down Frequency 5:Communication Setting Frequency 6:Reserved 7:Pulse Input(*6) 2 - O O O ⟦blank source cell⟧
10 00-06 Alternative Frequency Command Source Selection 0:UP/DOWM of Keypad 1:Potentiometer on Keypad 2:External AI1 Analog Signal Input 3:External AI2 Analog Signal Input 4:External Up/Down Frequency 5:Communication Setting Frequency 6:Reserved 7:Pulse Input(*6) 0 - O O O ⟦blank source cell⟧
11 00-07 Main and Alternative Frequency Command Modes 0:Main or Alternative Frequency 1:Main Frequency+ Alternative Frequency 0 - O O O ⟦blank source cell⟧
12 00-08 Communication Frequency Command 0.00~599.00 0.00 Hz O O O *4
13 00-09 Frequency Command Save on Power Down 0:Disable 1:Enable 0 - O O O ⟦blank source cell⟧

Manual — Group00 Basic Parameters continued; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 87

Manual reference: physical PDF page 87. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

*:

***:

Refer to the following attachment 1.

If parameter 00-27 is set to ND mode, group 02 motor 1 parameter will automatically adjust to more

than 1 class of it.

If parameter 00-27 is set to HD mode, group 02 motor 1 parameter will automatically adjust to the

same class of it.

It is suggested that parameter 00-27 be set first before motor performs auto-tuning because the parameter

will make the motor parameter automatically be changed.

Group00 Basic Parameters continued; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 00 Basic Parameters — PDF page 87

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters Group 00 Basic Parameters
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 00-10 Initial Frequency Selection (keypad mode) 0:by Current Frequency Command 1:by 0 Frequency Command 2:by 00-11 0 - O O O ⟦blank source cell⟧
5 00-11 Initial Frequency Setpoint 0.00-599.00 50/60 Hz O O O *1
6 00-12 Frequency Upper Limit 0.01-599.00 0.0 Hz O O O ⟦blank source cell⟧
7 00-13 Frequency Lower Limit 0.00-599.00 0.0 Hz O O O ⟦blank source cell⟧
8 00-14 Acceleration Time 1 0.1~6000.0 * s O O O *1
9 00-15 Deceleration Time 1 0.1~6000.0 * s O O O *1
10 00-16 Acceleration Time 2 0.1~6000.0 * s O O O *1
11 00-17 Deceleration Time 2 0.1~6000.0 * s O O O *1
12 00-18 Jog Frequency 0.00~599.00 2.00 Hz O O O *1
13 00-19 Jog Acceleration Time 0.1~0600.0 * s O O O *1
14 00-20 Jog Deceleration Time 0.1~0600.0 * s O O O *1
15 00-21 Acceleration Time 3 0.1~6000.0 * s O X X *1
16 00-22 Deceleration Time 3 0.1~6000.0 * s O X X *1
17 00-23 Acceleration Time 4 0.1~6000.0 * s O X X *1
18 00-24 Deceleration Time 4 0.1~6000.0 * s O X X *1
19 00-26 Emergency Stop Time 0.1~6000.0 5.0 s O O O ⟦blank source cell⟧
20 00-27 HD/ND Mode (F5/F6 Only)(***) 0:HD (Heavy Duty Mode) 1:ND (Normal Duty Mode) 0 - O X X *3
21 00-34 Language 0:English 1:Simplified Chinese 2:Traditional Chinese 3:Turkish 0 - O O O *7
22 00-35 Minimum Frequeny Detection 0:Alarm 1:Keep Running At Lower Frequency 0 - O O O ⟦blank source cell⟧
23 00-36 PID Lower Frequency Selection 0:Disable (Lower Frequency of PID Sleep Mode) 1:Enable (0Hz of PID Sleep Mode) 0 - O O O ⟦blank source cell⟧

Manual — Group01 V/F Pattern Selection; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 88

Manual reference: physical PDF page 88. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group01 V/F Pattern Selection; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 01 V/F Control Parameters — PDF page 88

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Group 01 V/F Control Parameters Group 01 V/F Control Parameters Group 01 V/F Control Parameters Group 01 V/F Control Parameters Group 01 V/F Control Parameters Group 01 V/F Control Parameters Group 01 V/F Control Parameters Group 01 V/F Control Parameters Group 01 V/F Control Parameters Group 01 V/F Control Parameters
2 Code Parameter Name Setting Range Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Setting Range Default Unit V/F SLV PM SLV Attribute
4 01-00 Volts/Hz Patterns 0~FF 0~FF F - O X X *3
5 01-02 Maximum Output Frequency of Motor 1 4.8~599.0 4.8~599.0 50.0/60.0 Hz O O X *8
6 01-03 Maximum Output Voltage of Motor 1 200V:0.1~255.0 200V:0.1~255.0 230.0 V O X X *8
7 01-03 Maximum Output Voltage of Motor 1 400V:0.2~510.0 400V:0.2~510.0 400.0 V O X X *8
8 01-04 Middle Output Frequency 2 of Motor 1 0.0~599.0 0.0~599.0 0.0 Hz O X X ⟦blank source cell⟧
9 01-05 Middle Output Voltage 2 of Motor 1 200V:0.0~255.0 400V:0.0~510.0 200V:0.0~255.0 400V:0.0~510.0 0.0 V O X X *8
10 01-06 Middle Output Frequency 1 of Motor 1 0.0~599.0 0.0~599.0 2.5/3.0 Hz O X X *8
11 01-07 Middle Output Voltage 1 of Motor 1 200V:0.0~255.0 400V:0.0~510.0 200V:0.0~255.0 400V:0.0~510.0 KVA V O X X *8
12 01-08 Minimum Output Frequency of Motor 1 0.0~599.0 V/F: 1.3/1.5 Hz O O O ⟦blank source cell⟧
13 01-08 Minimum Output Frequency of Motor 1 0.0~599.0 SLV: 0.5/0.6 Hz O O O ⟦blank source cell⟧
14 01-08 Minimum Output Frequency of Motor 1 0.0~599.0 PMSLV: 10.0 Hz O O O ⟦blank source cell⟧
15 01-09 Minimum Output Voltage of Motor 1 200V:0.0~255.0 400V:0.0~510.0 200V:0.0~255.0 400V:0.0~510.0 KVA V O X X *8
16 01-10 Torque Compensation Gain 0.0~2.0 0.0~2.0 0.5 - O X X *1
17 01-11 Selection of Torque Compensation Mode 0:Mode 0 (Normal) 1:Mode 1 (High Speed) 0:Mode 0 (Normal) 1:Mode 1 (High Speed) 0 - O X X ⟦blank source cell⟧
18 01-12 Base Frequency of Motor 1 4.8~599.0 4.8~599.0 50.0/60.0 Hz O O X *8
19 01-13 Base Output Voltage of Motor 1 200V:0.0~255.0 200V:0.0~255.0 230.0 V O X X *8
20 01-13 Base Output Voltage of Motor 1 400V:0.0~510.0 400V:0.0~510.0 400.0 V O X X *8
21 01-14 Input Voltage Setting 200V:55.0~255.0 200V:55.0~255.0 230.0 V O O O *8
22 01-14 Input Voltage Setting 400V:10.0~510.0 400V:10.0~510.0 400.0 V O O O *8
23 01-15 Torque Compensation Time 0~10000 0~10000 200 ms O X X ⟦blank source cell⟧
24 01-16 Maximum Output Frequency of Motor 2 4.8~599.0 4.8~599.0 50.0/60.0 Hz O X X *8
25 01-17 Maximum Output Voltage of Motor 2 200V:0.1~255.0 200V:0.1~255.0 230.0 V O X X *8
26 01-17 Maximum Output Voltage of Motor 2 400V:0.2~510.0 400V:0.2~510.0 400.0 V O X X *8
27 01-18 Middle Output Frequency 2 of Motor 2 0.0~599.0 0.0~599.0 0.0 Hz O X X ⟦blank source cell⟧
28 01-19 Middle Output Voltage 2 of Motor 2 200V:0.0~255.0 400V:0.0~510.0 200V:0.0~255.0 400V:0.0~510.0 0.0 V O X X ⟦blank source cell⟧
29 01-20 Middle Output Frequency 1 of Motor 2 0.0~599.0 0.0~599.0 2.5/3.0 Hz O X X *8
30 01-21 Middle Output Voltage 1 of Motor 2 200V:0.0~255.0 400V:0.0~510.0 200V:0.0~255.0 400V:0.0~510.0 KVA V O X X *8
31 01-22 Minimum Output Frequency of Motor 2 0.0~599.0 0.0~599.0 1.3/1.5 Hz O X X ⟦blank source cell⟧
32 01-23 Minimum Output Voltage of Motor 2 200V: 0.0~255.0 400V: 0.0~510.0 200V: 0.0~255.0 400V: 0.0~510.0 KVA V O X X *8
33 01-24 Base Frequency of Motor 2 4.8~599.0 4.8~599.0 50.0/60.0 Hz O X X *8
34 01-25 Base Output Voltage of Motor 2 200V: 0.0~255.0 200V: 0.0~255.0 230.0 V O X X *8
35 01-25 Base Output Voltage of Motor 2 400V: 0.0~510.0 400V: 0.0~510.0 400.0 V O X X *8
36 01-26 V/F Curve Selection of Motor 2 0~FF 0~FF F - O X X *3

Manual — Group02 Motor Parameters; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 89

Manual reference: physical PDF page 89. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group02 Motor Parameters; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 02 IM Motor Parameters — PDF page 89

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 02 IM Motor Parameters Group 02 IM Motor Parameters Group 02 IM Motor Parameters Group 02 IM Motor Parameters Group 02 IM Motor Parameters Group 02 IM Motor Parameters Group 02 IM Motor Parameters Group 02 IM Motor Parameters Group 02 IM Motor Parameters
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 02-00 No-Load Current of Motor1 0.01~600.00 KVA A O X X ⟦blank source cell⟧
5 02-01 Rated Current of Motor1 Lower limit: 10% Inverter rated current (V/F) 25% Inverter rated current (SLV) Upper limit: Based on inverter capacity KVA A O O X ⟦blank source cell⟧
6 02-03 Rated Rotation Speed of Motor1 0~60000 KVA RPM O O X *8
7 02-04 Rated Voltage of Motor1 200V: 50.0~240.0 230.0 V O O X *8
8 02-04 Rated Voltage of Motor1 400V: 100.0~480.0 400.0 V O O X *8
9 02-05 Rated Power of Motor1 0.01~600.00 KVA kW O O X ⟦blank source cell⟧
10 02-06 Rated Frequency of Motor1 4.8~599.0 50.0/60.0 Hz O O X *8
11 02-07 Poles of Motor 1 2~16(Even) 4 Poles O O X ⟦blank source cell⟧
12 02-09 Excitation Current of Motor 1 15%~70% of motor rated current KVA % X O X ⟦blank source cell⟧
13 02-10 Core Saturation Coefficient 1 1~100 KVA % X O X ⟦blank source cell⟧
14 02-11 Core Saturation Coefficient 2 of Motor 1 1~100 KVA % X O X ⟦blank source cell⟧
15 02-12 Core Saturation Coefficient 3 of Motor 1 80~300 KVA % X O X ⟦blank source cell⟧
16 02-13 Core loss of Motor 1 0.0~15.0 KVA % O X X ⟦blank source cell⟧
17 02-15 Resistance Between Wires of Motor 1 1~60.000 KVA Ω O O X ⟦blank source cell⟧
18 02-16 Rotor Resistance Gain of Motor 1 1~60.000 KVA Ω O O X ⟦blank source cell⟧
19 02-17 Leakage Inductance of Motor 1 0.001~60.000 KVA mH O O X ⟦blank source cell⟧
20 02-19 No-Load Voltage of Motor 1 200V:50~240 400V:100~480 - V X O X *8
21 02-20 No-Load Current of Motor 2 0.01~600.00 KVA A O X X ⟦blank source cell⟧
22 02-21 Rated Current of Motor 2 10%~200% of inverter rated current KVA A O X X ⟦blank source cell⟧
23 02-22 Rated Rotation Speed of Motor 2 0~60000 KVA RPM O X X *8
24 02-23 Rated Voltage of Motor 2 200V:50.0~240.0 230.0 V O X X *8
25 02-23 Rated Voltage of Motor 2 400V:100.0~480.0 400.0 V O X X *8
26 02-24 Rated Power of Motor 2 0.01~600.00 KVA kW O X X ⟦blank source cell⟧
27 02-25 Rated Frequency of Motor 2 4.8~599.0 50.0/60.0 Hz O X X *8
28 02-26 Poles of Motor 2 2~16(Even) 4 Poles O X X ⟦blank source cell⟧
29 02-32 Resistance between Wires of Motor 2 0.001~60.000 KVA Ω O X X ⟦blank source cell⟧
30 02-33 Proportion of Motor Leakage Inductance 0.1~15.0 KVA % X O X ⟦blank source cell⟧
31 02-34 Slip Frequency of Motor 0.10~20.00 KVA Hz X O X ⟦blank source cell⟧

Manual — Group03 External Terminals; shared digital-input option list; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. Physical adjacency of terminal parameter blocks and the shared setting-option list does not mean exclusive applicability of options to the terminal on that row. Parameter/default blocks and option/control-mode blocks must be read independently. Source repeats Terminal S5 at03-03 and03-04; not corrected. — page 90

Manual reference: physical PDF page 90. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Default remains unspecified in summary90. Do not infer zero.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: 03-06 Up/Down frequency step has blank default and unit cells in source. Range0.00~5.00 retained; no default/unit inferred. All printed table content and separate shared-option context reviewed.

The table is a physical-layout transcript. Adjacent terminal names and option list rows are not semantic pairs. Machine field row_context separates parameter/default from shared options/control-mode columns. Do not derive terminal-specific applicability from source row adjacency.

Group03 External Terminals; shared digital-input option list; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. Physical adjacency of terminal parameter blocks and the shared setting-option list does not mean exclusive applicability of options to the terminal on that row. Parameter/default blocks and option/control-mode blocks must be read independently. Source repeats Terminal S5 at03-03 and03-04; not corrected.

Source row 4: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 4: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 4: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 5: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 5: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 5: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 6: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 6: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 6: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 7: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 7: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 7: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 8: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 8: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 8: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 9: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 9: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 9: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 10: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 10: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 10: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 11: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 11: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 11: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 12: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 12: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 12: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 13: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 13: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 13: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 14: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 14: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 14: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 15: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 15: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 15: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 16: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 16: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 16: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 17: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 17: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 17: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 18: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 18: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 18: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 19: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 19: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 19: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 20: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 20: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 20: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 21: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 21: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 21: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 22: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 22: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 22: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 23: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 23: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 23: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 24: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 24: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 24: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 25: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 25: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 25: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 26: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 26: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 26: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 27: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 27: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 27: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 28: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 28: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 28: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 29: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 29: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 29: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 30: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 30: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 30: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 31: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 31: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 31: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 32: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 32: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 32: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 33: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 33: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 33: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 34: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 34: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 34: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 35: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 35: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 35: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 36: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 36: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 36: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 37: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 37: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 37: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 38: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 38: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 38: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 39: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 39: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 39: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 40: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 40: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 40: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 41: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 41: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 41: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 42: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 42: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 42: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 43: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 43: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 43: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 44: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 44: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 44: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 45: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 45: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 45: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Group 03 External Digital Input and Output Parameters — PDF page 90

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 03-00 Multifunction Input Terminal S1 0:Forward/Stop Command 0 - O O O ⟦blank source cell⟧
5 03-00 Multifunction Input Terminal S1 1:Reverse/Stop Command 0 - O O O ⟦blank source cell⟧
6 03-00 Multifunction Input Terminal S1 2:Multi-Speed/Position Setting Command 0 0 - O O O ⟦blank source cell⟧
7 03-00 Multifunction Input Terminal S1 3:Multi-Speed/Position Setting Command 1 0 - O O O ⟦blank source cell⟧
8 03-00 Multifunction Input Terminal S1 4:Multi-Speed/Position Setting Command 2 0 - O O O ⟦blank source cell⟧
9 03-00 Multifunction Input Terminal S1 5:Multi-Speed/Position Setting Command 3 0 - O O O ⟦blank source cell⟧
10 03-00 Multifunction Input Terminal S1 6:Forward Jog Run Command 0 - O O O ⟦blank source cell⟧
11 03-01 Multifunction Input Terminal S2 7:Reverse Jog Run Command 1 - O O O ⟦blank source cell⟧
12 03-01 Multifunction Input Terminal S2 8:UP Frequency Increasing Command 1 - O O O ⟦blank source cell⟧
13 03-01 Multifunction Input Terminal S2 9:DOWN Frequency Decreasing Command 1 - O O O ⟦blank source cell⟧
14 03-01 Multifunction Input Terminal S2 10:Acceleration/ Deceleration Time Selection 2 1 - O O O ⟦blank source cell⟧
15 03-01 Multifunction Input Terminal S2 11:Inhibit Acceleration/ Deceleration Command 1 - O O O ⟦blank source cell⟧
16 03-01 Multifunction Input Terminal S2 12:Main/ Alternative Run Switch Function 1 - O O O ⟦blank source cell⟧
17 03-01 Multifunction Input Terminal S2 13:Main/ Alternative Frequency Switch Function 1 - O O O ⟦blank source cell⟧
18 03-02 Multifunction Input Terminal S3 14:Emergency Stop (decelerate to zero and stop) 2 - O O O ⟦blank source cell⟧
19 03-02 Multifunction Input Terminal S3 15:External Baseblock Command (rotation freely to stop) 2 - O O O ⟦blank source cell⟧
20 03-02 Multifunction Input Terminal S3 16:PID Control Disable 2 - O O O ⟦blank source cell⟧
21 03-02 Multifunction Input Terminal S3 17:Fault Reset 2 - O O O ⟦blank source cell⟧
22 03-02 Multifunction Input Terminal S3 18:Auto Run Mode Enable 2 - O O O ⟦blank source cell⟧
23 03-02 Multifunction Input Terminal S3 19:Speed Search 1 2 - O O X ⟦blank source cell⟧
24 03-02 Multifunction Input Terminal S3 20:Energy Saving (V/F only) 2 - O X X ⟦blank source cell⟧
25 03-03 Multifunction Input Terminal S5 21:Reset PID integral value to Zero 3 - O O O ⟦blank source cell⟧
26 03-03 Multifunction Input Terminal S5 22:Counter Input 3 - O O O ⟦blank source cell⟧
27 03-03 Multifunction Input Terminal S5 23:Counter reset 3 - O O O ⟦blank source cell⟧
28 03-03 Multifunction Input Terminal S5 24:PLC Input 3 - O O O ⟦blank source cell⟧
29 03-03 Multifunction Input Terminal S5 25:Pulse-In width measure(S3) 3 - O O O ⟦blank source cell⟧
30 03-03 Multifunction Input Terminal S5 26:Pulse-In frequency measure(S3) 3 - O O O ⟦blank source cell⟧
31 03-04 Multifunction Input Terminal S5 27:Local/Romote selection 4 - O O O ⟦blank source cell⟧
32 03-04 Multifunction Input Terminal S5 28:Remote mode selection 4 - O O O ⟦blank source cell⟧
33 03-04 Multifunction Input Terminal S5 29:Jog Frequency Selection 4 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
34 03-04 Multifunction Input Terminal S5 33:DC Braking 4 - O O O ⟦blank source cell⟧
35 03-05 Multifunction Input Terminal S6 34:Speed Search 2 17 - O O X ⟦blank source cell⟧
36 03-05 Multifunction Input Terminal S6 40:Switching between Motor 1/Motor 2 17 - O O X ⟦blank source cell⟧
37 03-05 Multifunction Input Terminal S6 41:PID Sleep 17 - O O O ⟦blank source cell⟧
38 03-05 Multifunction Input Terminal S6 47:Fire mode 17 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
39 03-05 Multifunction Input Terminal S6 48:KEB Acceleration 17 ⟦blank source cell⟧ O X X ⟦blank source cell⟧
40 03-05 Multifunction Input Terminal S6 57:Forced Frequency Run 17 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
41 03-05 Multifunction Input Terminal S6 63:Switch to Constant Pressure 2 17 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
42 03-05 Multifunction Input Terminal S6 65:Short-circuit braking 17 - X X O ⟦blank source cell⟧
43 03-05 Multifunction Input Terminal S6 66:PID Control Disable 2 17 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
44 03-05 Multifunction Input Terminal S6 68:External Fault 17 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
45 03-05 Multifunction Input Terminal S6 69:External Overload 17 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
46 03-06 Up/Down frequency step 0.00~5.00 ⟦blank source cell⟧ ⟦blank source cell⟧ O O O ⟦blank source cell⟧

Manual — Group03 External Terminals; shared relay-output option list continued on92; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. Relay option list spans03-11 on91 through03-12 on92: options37/54 at bottom91 and55/59 at top92 retained as list continuation. Physical adjacency does not restrict options to one relay. Separate parameter/default and option/control-mode blocks. — page 91

Manual reference: physical PDF page 91. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

The table is a physical-layout transcript. Adjacent terminal names and option list rows are not semantic pairs. Machine field row_context separates parameter/default from shared options/control-mode columns. Do not derive terminal-specific applicability from source row adjacency.

Group03 External Terminals; shared relay-output option list continued on92; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. Relay option list spans03-11 on91 through03-12 on92: options37/54 at bottom91 and55/59 at top92 retained as list continuation. Physical adjacency does not restrict options to one relay. Separate parameter/default and option/control-mode blocks.

Source row 8: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 8: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 8: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 9: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 9: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 9: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 10: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 10: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 10: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 11: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 11: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 11: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 12: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 12: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 12: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 13: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 13: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 13: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 14: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 14: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 14: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 15: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 15: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 15: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 16: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 16: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 16: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 17: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 17: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 17: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 18: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 18: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 18: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 19: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 19: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 19: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 20: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 20: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 20: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 21: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 21: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 21: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 22: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 22: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 22: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 23: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 23: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 23: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 24: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 24: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 24: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 25: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 25: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 25: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 26: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 26: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 26: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 27: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 27: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 27: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 28: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 28: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 28: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 29: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 29: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 29: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 30: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 30: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 30: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 31: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 31: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 31: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Group 03 External Digital Input and Output Parameters — PDF page 91

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 03-07 Up/Down Keep Frequency Status after Stop Command 0:When Up/Down is used, the preset frequency is held as the inverter stops, and the UP/Down function is disabled 1:When Up/Down is used, the preset frequency is reset to 0 Hz as the inverter stops. 2:When Up/Down is used, the preset frequency is held as the inverter stops, and the UP/Down is available. 3:When acceleration is used, the output frequency will be updated. 0 - O O O ⟦blank source cell⟧
5 03-08 S1~S6 DI scan Time 1~200 1 ms O O O ⟦blank source cell⟧
6 03-09 Multi-Function Terminal S1~ S4 type selection xxx0b:S1 A Contact, xxx1b:S1 B Contact xx0xb:S2 A Contact, xx1xb:S2 B Contact x0xxb:S3 A Contact, x1xxb:S3 B Contact 0xxxb:S4 A Contact, 1xxxb:S4 B Contact 0000b - O O O ⟦blank source cell⟧
7 03-10 Multi-Function Terminal S5~ S6 type selection xxx0b:S5A Contact, xxx1b:S5 B Contact xx0xb:S6 A Contact, xx1xb:S6 B Contact 0000b - O O O ⟦blank source cell⟧
8 03-11 Relay (R1A-R1C) Output 0:During Running 1 - - O O O ⟦blank source cell⟧
9 03-11 Relay (R1A-R1C) Output 1:Fault Contact Output 1 - - O O O ⟦blank source cell⟧
10 03-11 Relay (R1A-R1C) Output 2:Frequency Agree 1 - - O O O ⟦blank source cell⟧
11 03-11 Relay (R1A-R1C) Output 3:Setting Frequency Agree (03-13±03-14) 1 - - O O O ⟦blank source cell⟧
12 03-11 Relay (R1A-R1C) Output 4:Frequency Detection 1 (≧03-13+03-14) 1 - - O O O ⟦blank source cell⟧
13 03-11 Relay (R1A-R1C) Output 5:Frequency Detection 2 (≦ 03-13+03-14) 1 - - O O O ⟦blank source cell⟧
14 03-11 Relay (R1A-R1C) Output 6:Automatic Restart 1 - - O O O ⟦blank source cell⟧
15 03-11 Relay (R1A-R1C) Output 7:Momentary AC Power Loss 1 - - O O O ⟦blank source cell⟧
16 03-11 Relay (R1A-R1C) Output 8:Rapid Stop 1 - - O O O ⟦blank source cell⟧
17 03-11 Relay (R1A-R1C) Output 9:Base Block 1 - - O O O ⟦blank source cell⟧
18 03-11 Relay (R1A-R1C) Output 10:Motor Overload Protection (OL1) 1 - - O O O ⟦blank source cell⟧
19 03-11 Relay (R1A-R1C) Output 11:Drive Overload Protection (OL2) 1 - - O O O ⟦blank source cell⟧
20 03-11 Relay (R1A-R1C) Output 12:Over-torque Threshold Level (OT) 1 - - O O O ⟦blank source cell⟧
21 03-11 Relay (R1A-R1C) Output 13:Preset Output Current Reached 1 - - O O O ⟦blank source cell⟧
22 03-11 Relay (R1A-R1C) Output 14:Brake Control 1 - - O O O ⟦blank source cell⟧
23 03-11 Relay (R1A-R1C) Output 15:PID Feedback Signal Loss 1 - - O O O ⟦blank source cell⟧
24 03-11 Relay (R1A-R1C) Output 16:Single pre-set count (3-22~23) 1 - - O O O ⟦blank source cell⟧
25 03-11 Relay (R1A-R1C) Output 17:Dual pre-set count (3-22~23) 1 - - O O O ⟦blank source cell⟧
26 03-11 Relay (R1A-R1C) Output 18:PLC Status Indicator (00-02) 1 - - O O O ⟦blank source cell⟧
27 03-11 Relay (R1A-R1C) Output 19:PLC control * 1 - - O O O ⟦blank source cell⟧
28 03-11 Relay (R1A-R1C) Output 20:Zero Speed 1 - - O O O ⟦blank source cell⟧
29 03-11 Relay (R1A-R1C) Output 30:Motor 2 Selection 1 - - O X X ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧ 37:Detection Output of PID Feedback Loss ⟦blank source cell⟧ ⟦blank source cell⟧ O O O ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧ 54:Turn on short-circuit braking ⟦blank source cell⟧ ⟦blank source cell⟧ X X O ⟦blank source cell⟧

Manual — Group03 External Terminals; relay options continued from91; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. Relay option list spans03-11 on91 through03-12 on92: options37/54 at bottom91 and55/59 at top92 retained as list continuation. Physical adjacency does not restrict options to one relay. Separate parameter/default and option/control-mode blocks. — page 92

Manual reference: physical PDF page 92. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

The table is a physical-layout transcript. Adjacent terminal names and option list rows are not semantic pairs. Machine field row_context separates parameter/default from shared options/control-mode columns. Do not derive terminal-specific applicability from source row adjacency.

Group03 External Terminals; relay options continued from91; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. Relay option list spans03-11 on91 through03-12 on92: options37/54 at bottom91 and55/59 at top92 retained as list continuation. Physical adjacency does not restrict options to one relay. Separate parameter/default and option/control-mode blocks.

Source row 4: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 4: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 4: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Source row 5: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: PARAMETER_DEFAULT

Source row 5: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SHARED_OPTIONS_CONTROL_MODES

Source row 5: layout_warning: Shared setting options are independent from adjacent terminal/default block; no exclusive terminal applicability inferred.; semantic_block: SOURCE_UNIT_OR_ATTRIBUTE_ONLY

Group 03 External Digital Input and Output Parameters — PDF page 92

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 03-12 Relay (R2A-R2B) Output 55:Low Current Detection 59:OH Detection 0 - O O O ⟦blank source cell⟧
5 03-12 Relay (R2A-R2B) Output 55:Low Current Detection 59:OH Detection 0 - O O O ⟦blank source cell⟧
6 03-13 Frequency Detection Level 0.0~599.0 0.0 Hz O O O ⟦blank source cell⟧
7 03-14 Frequency Detection Width 0.1~25.5 2.0 Hz O O O ⟦blank source cell⟧
8 03-15 Current Agree Level 0.1~999.9 0.1 A O O O ⟦blank source cell⟧
9 03-16 Delay Time of Current Agree Detection 0.1~10.0 0.1 s O O O ⟦blank source cell⟧
10 03-17 * Mechanical Braking Release Level 0.00~20.00 0.00 Hz O O O ⟦blank source cell⟧
11 03-18 * Mechanical Braking Level Set 0.00~20.00 0.00 Hz O O O ⟦blank source cell⟧
12 03-19 Relay (R1A-R2B) Type xxx0b:R1 A Contact, xxx1b:R1 B Contact xx0xb:R2 A Contact, xx1xb:R2 B Contact 0000b - O O O ⟦blank source cell⟧
13 03-20 Internal / External Multi-Function Input Terminal Selection 0~63 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
14 03-21 Action To Set The Internal Multi-Function Input Terminals 0~63 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
15 03-22 Pre-Set Count 1 0~9999 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
16 03-23 Pre-Set Count 2 0~9999 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
17 03-24 Output Under Current Detection 0:Invalid 1:Valid 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
18 03-25 Output Under Current Detection Level 0~999.9 0.1 A O O O ⟦blank source cell⟧
19 03-26 Output Under Current Detection Delay Time 0.0~655.34s 0.01 s O O O ⟦blank source cell⟧
20 03-27 Pulse Frequency 50~25000 200 Hz O O O *1
21 03-28 Pulse Input Gain 0.0~1000.0 100.0 % O O O *1
22 03-30 Selection of Pulse Input 0:General Pulse Input 1:PWM 2:PLC Encoder input 0 - O O O ⟦blank source cell⟧
23 03-33 Pulse Input Bias -100.0~100.0 0.0 % O O O *1
24 03-34 Filter Time of Pulse Input 0.00~2.00 0.1 s O O O *1
25 03-53 Current Agree Level 2 0.0~999.9 0.1 A O O O ⟦blank source cell⟧

Manual — Group03 final row and Group04 analog terminals; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 93

Manual reference: physical PDF page 93. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

*:If the maximum output frequency of motor is over 300HZ, the frequency resolution is changed to 0.1Hz

Group03 final row and Group04 analog terminals; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 03 External Digital Input and Output Parameters — PDF page 93

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters Group 03 External Digital Input and Output Parameters
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 03-54 Emergency Stop Action Run command disable and emergency Stop command disable. 0:Restart after Inverter Stop 1:Restart after External Reset Command 0 - O O O ⟦blank source cell⟧

Group 04 Analog signal inputs / Analog output — PDF page 93

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 04 Analog signal inputs / Analog output Group 04 Analog signal inputs / Analog output Group 04 Analog signal inputs / Analog output Group 04 Analog signal inputs / Analog output Group 04 Analog signal inputs / Analog output Group 04 Analog signal inputs / Analog output Group 04 Analog signal inputs / Analog output Group 04 Analog signal inputs / Analog output Group 04 Analog signal inputs / Analog output
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 04-00 Analog Input Signal Type 0:AI1 0~10V AI2 0~10V / 0~20mA 1:AI1 0~10V AI2 4~20mA / 2~10V 2:AI1 2~10V AI2 0~10V / 0~20mA 3:AI1 2~10V AI2 4~20mA / 2~10V 1 - O O O ⟦blank source cell⟧
5 04-01 AI1 Signal Scanning and Filtering Time 0.00~2.00 0.03 s O O O ⟦blank source cell⟧
6 04-02 AI1 Gain 0.0~1000.0 100.0 % O O O *1
7 04-03 AI1 Bias -100.0~100.0 0 % O O O *1
8 04-05 AI1 Slope 0:Positive 1:Negative 0 - O O O ⟦blank source cell⟧
9 04-06 AI2 Signal Scanning and Filtering Time 0.00~2.00 0.03 s O O O ⟦blank source cell⟧
10 04-07 AI2 Gain 0.0~1000.0 100.0 % O O O *1
11 04-08 AI2 Bias -100.0~100.0 0 % O O O *1
12 04-10 AI2 Slope 0:Positive 1:Negative 0 - O O O ⟦blank source cell⟧
13 04-11 Analog Output (AO) Mode 0:Output Frequency 1:Frequency Command 2:Output Voltage 3:DC Bus Voltage 4:Output Current 0 - O O O ⟦blank source cell⟧
14 04-12 AO Gain 0.0~1000.0 100.0 % O O O *1
15 04-13 AO Bias -100.0~100.0 0 % O O O *1
16 04-15 AO Slope 0:Positive 1:Negative 0 - O O O ⟦blank source cell⟧
17 04-16 F-Gain 0:Disable 1:Enable 0 - O O O ⟦blank source cell⟧
18 04-20 AO Signal Scanning and Filtering Time 0.00~0.50 0.00 s O O O *1
19 04-22 AO voltage correction 0:Disable 1:Enable 0 - O O O ⟦blank source cell⟧

Manual — Group05 Preset Frequency Selection; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 94

Manual reference: physical PDF page 94. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group05 Preset Frequency Selection; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 05 Preset Frequency Selection — PDF page 94

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 05-00 Preset Speed Control Mode Selection 0:Accel/Decel 1~4 apply to all speeds 1:Individual Accel/Decel for each preset speed 0 - O O O ⟦blank source cell⟧
5 05-01 * Preset Speed 0 0.00~599.00 5.00 Hz O O O *1
6 05-02 * Preset Speed 1 0.00~599.00 5.00 Hz O O O *1
7 05-03 * Preset Speed 2 0.00~599.00 10.00 Hz O O O *1
8 05-04 * Preset Speed 3 0.00~599.00 20.00 Hz O O O *1
9 05-05 * Preset Speed 4 0.00~599.00 30.00 Hz O O O *1
10 05-06 * Preset Speed 5 0.00~599.00 40.00 Hz O O O *1
11 05-07 * Preset Speed 6 0.00~599.00 50.00 Hz O O O *1
12 05-08 * Preset Speed 7 0.00~599.00 50.00 Hz O O O *1
13 05-09 * Preset Speed 8 0.00~599.00 5.00 Hz O O O *1
14 05-10 * Preset Speed 9 0.00~599.00 5.00 Hz O O O *1
15 05-11 * Preset Speed 10 0.00~599.00 5.00 Hz O O O *1
16 05-12 * Preset Speed 11 0.00~599.00 5.00 Hz O O O *1
17 05-13 * Preset Speed 12 0.00~599.00 5.00 Hz O O O *1
18 05-14 * Preset Speed 13 0.00~599.00 5.00 Hz O O O *1
19 05-15 * Preset Speed 14 0.00~599.00 5.00 Hz O O O *1
20 05-16 * Preset Speed 15 0.00~599.00 5.00 Hz O O O *1
21 05-17 Preset Speed 0-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
22 05-18 Preset Speed 0-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
23 05-19 Preset Speed 1-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
24 05-20 Preset Speed 1-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
25 05-21 Preset Speed 2-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
26 05-22 Preset Speed 2-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
27 05-23 Preset Speed 3-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
28 05-24 Preset Speed 3-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
29 05-25 Preset Speed 4-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
30 05-26 Preset Speed 4-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
31 05-27 Preset Speed 5-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
32 05-28 Preset Speed 5-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
33 05-29 Preset Speed 6-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
34 05-30 Preset Speed 6-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
35 05-31 Preset Speed 7-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
36 05-32 Preset Speed 7-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧

Manual — Group05 Preset Frequency Selection continued; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 95

Manual reference: physical PDF page 95. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group05 Preset Frequency Selection continued; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 05 Preset Frequency Selection — PDF page 95

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection Group 05 Preset Frequency Selection
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 05-33 Preset Speed 8-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
5 05-34 Preset Speed 8-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
6 05-35 Preset Speed 9-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
7 05-36 Preset Speed 9-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
8 05-37 Preset Speed 10-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
9 05-38 Preset Speed 10-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
10 05-39 Preset Speed 11-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
11 05-40 Preset Speed 11-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
12 05-41 Preset Speed 12-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
13 05-42 Preset Speed 12-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
14 05-43 Preset Speed 13-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
15 05-44 Preset Speed 13-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
16 05-45 Preset Speed 14-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
17 05-46 Preset Speed 14-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
18 05-47 Preset Speed 15-Acc time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
19 05-48 Preset Speed 15-Dec time 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧

Manual — Group06 Automatic Program Opera; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 96

Manual reference: physical PDF page 96. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group06 Automatic Program Opera; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 06 Automatic Program Opera — PDF page 96

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 06-00 Auto Run Mode Selection 0:Disabled 1:Execute a single cycle operation mode. Restart speed is based on the previous stopped speed. 2:Execute continuous cycle operation mode. Restart speed is based on the previous stopped speed. 3:After the completion of a single cycle, the on-going operation speed is based on the speed of the last stage. Restart speed is based on the previous stopped speed. 4:Execute a single cycle operation mode. Restart speed will be based on the speed of stage 0. 5:Execute continuous cycle operation mode. Restart speed will be based on the speed of stage 0. 6:After the completion of a single cycle, the on-going operation speed is based on the speed of the last stage. Restart speed is based on the speed of stage 0. 0 - O O X ⟦blank source cell⟧
5 06-01 * Frequency Setting of Operation-Stage 1 0.00~599.00 0.0 Hz O O X *1
6 06-02 * Frequency Setting of Operation-Stage 2 0.00~599.00 0.0 Hz O O X *1
7 06-03 * Frequency Setting of Operation-Stage 3 0.00~599.00 0.0 Hz O O X *1
8 06-04 * Frequency Setting of Operation-Stage 4 0.00~599.00 0.0 Hz O O X *1
9 06-05 * Frequency Setting of Operation-Stage 5 0.00~599.00 0.0 Hz O O X *1
10 06-06 * Frequency Setting of Operation-Stage 6 0.00~599.00 0.0 Hz O O X *1
11 06-07 * Frequency Setting of Operation-Stage 7 0.00~599.00 0.0 Hz O O X *1
12 06-08 * Frequency Setting of Operation-Stage 8 0.00~599.00 0.0 Hz O O X *1
13 06-09 * Frequency Setting of Operation-Stage 9 0.00~599.00 0.0 Hz O O X *1
14 06-10 * Frequency Setting of Operation-Stage 10 0.00~599.00 0.0 Hz O O X *1

Manual — Group06 Automatic Program Opera continued; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 97

Manual reference: physical PDF page 97. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group06 Automatic Program Opera continued; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 06 Automatic Program Opera — PDF page 97

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 06-11 * Frequency Setting of Operation-Stage 11 0.00~599.00 0.0 Hz O O X *1
5 06-12 * Frequency Setting of Operation-Stage 12 0.00~599.00 0.0 Hz O O X *1
6 06-13 * Frequency Setting of Operation-Stage 13 0.00~599.00 0.0 Hz O O X *1
7 06-14 * Frequency Setting of Operation-Stage 14 0.00~599.00 0.0 Hz O O X *1
8 06-15 * Frequency Setting of Operation-Stage 15 0.00~599.00 0.0 Hz O O X *1
9 06-16 Operation Time Setting of Speed-Stage 0 0.0~6000.0 0.0 s O O X *1
10 06-17 Operation Time Setting of Speed-Stage 1 0.0~6000.0 0.0 s O O X *1
11 06-18 Operation Time Setting of Speed-Stage 2 0.0~6000.0 0.0 s O O X *1
12 06-19 Operation Time Setting of Speed-Stage 3 0.0~6000.0 0.0 s O O X *1
13 06-20 Operation Time Setting of Speed-Stage 4 0.0~6000.0 0.0 s O O X *1
14 06-21 Operation Time Setting of Speed-Stage 5 0.0~6000.0 0.0 s O O X *1
15 06-22 Operation Time Setting of Speed-Stage 6 0.0~6000.0 0.0 s O O X *1
16 06-23 Operation Time Setting of Speed-Stage 7 0.0~6000.0 0.0 s O O X *1
17 06-24 Operation Time Setting of Speed-Stage 8 0.0~6000.0 0.0 s O O X *1
18 06-25 Operation Time Setting of Speed-Stage 9 0.0~6000.0 0.0 s O O X *1
19 06-26 Operation Time Setting of Speed-Stage 10 0.0~6000.0 0.0 s O O X *1
20 06-27 Operation Time Setting of Speed-Stage 11 0.0~6000.0 0.0 s O O X *1
21 06-28 Operation Time Setting of Speed-Stage 12 0.0~6000.0 0.0 s O O X *1
22 06-29 Operation Time Setting of Speed-Stage 13 0.0~6000.0 0.0 s O O X *1
23 06-30 Operation Time Setting of Speed-Stage 14 0.0~6000.0 0.0 s O O X *1
24 06-31 Operation Time Setting of Speed-Stage 15 0.0~6000.0 0.0 s O O X *1

Manual — Group06 Automatic Program Opera continued; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 98

Manual reference: physical PDF page 98. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group06 Automatic Program Opera continued; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 06 Automatic Program Opera — PDF page 98

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera Group 06 Automatic Program Opera
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 06-32 Operation Direction Selection of Speed Stage 0 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
5 06-33 Operation Direction Selection of Speed Stage 1 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
6 06-34 Operation Direction Selection of Speed Stage 2 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
7 06-35 Operation Direction Selection of Speed Stage 3 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
8 06-36 Operation Direction Selection of Speed Stage 4 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
9 06-37 Operation Direction Selection of Speed Stage 5 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
10 06-38 Operation Direction Selection of Speed Stage 6 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
11 06-39 Operation Direction Selection of Speed Stage 7 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
12 06-40 Operation Direction Selection of Speed Stage 8 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
13 06-41 Operation Direction Selection of Speed Stage 9 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
14 06-42 Operation Direction Selection of Speed Stage 10 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
15 06-43 Operation Direction Selection of Speed Stage 11 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
16 06-44 Operation Direction Selection of Speed Stage 12 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
17 06-45 Operation Direction Selection of Speed Stage 13 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
18 06-46 Operation Direction Selection of Speed Stage 14 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧
19 06-47 Operation Direction Selection of Speed Stage 15 0:Stop 1:Forward 2:Reverse 0 - O O X ⟦blank source cell⟧

Manual — Group07 Start/Stop Parameters; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 99

Manual reference: physical PDF page 99. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group07 Start/Stop Parameters; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 07 Start/Stop Parameters — PDF page 99

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 07-00 Momentary Power Loss and Restart 0:Disable 1:Enable 0 - O O X ⟦blank source cell⟧
5 07-01 Fault Reset Time 0~7200 0 s O O O ⟦blank source cell⟧
6 07-02 Number of Auto Restart Attempts 0~10 0 - O O O ⟦blank source cell⟧
7 07-03 Reset Mode Setting 0:Enable Reset Only when Run Command is Off 1:Enable Reset when Run Command is On or Off 0 - O O O ⟦blank source cell⟧
8 07-04 Momentary Power Loss and Restart 0:Enable Direct run on power up 1:Disable Direct run on power up 1 - O O O ⟦blank source cell⟧
9 07-05 Delay-ON Timer 1.0~300.0 1.0 s O O O ⟦blank source cell⟧
10 07-06 DC Injection Braking Start Frequency 0.0~10.0 1.5 Hz O O O ⟦blank source cell⟧
11 07-07 DC Injection Braking Level (Current Mode) 0~100 50 % O O O ⟦blank source cell⟧
12 07-08 DC Injection Braking Time 0.00~100.00 0.50 s O O O ⟦blank source cell⟧
13 07-09 Stop Mode Selection 0:Deceleration to Stop 1:Coast to Stop 2:DC Braking Stop in All Fields 3:Coast to Stop with Timer 0 - O O X ⟦blank source cell⟧
14 07-10 Speed Search Mode Selection 0:Normal Start 1:Execute Speed Search Once 2:Speed Search Start 0 - O O O ⟦blank source cell⟧
15 07-13 Low Voltage Detection Level 200V:100~300 190 V O O O ⟦blank source cell⟧
16 07-13 Low Voltage Detection Level 400V:250~600 380 V O O O ⟦blank source cell⟧
17 07-15 DC Injection Brake Mode 0:Current Mode 1:Voltage Mode 1 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
18 07-16 DC Injection Braking Time at Start 0.00~100.00 0.00 s O O O ⟦blank source cell⟧
19 07-18 Minimum Base block Time 0.1~5.0 KVA s O O O ⟦blank source cell⟧
20 07-19 Speed Direction Search Operation Current 0~100 50 % O O X ⟦blank source cell⟧
21 07-20 Speed Search Operating Current 0~100 20 % O O X ⟦blank source cell⟧
22 07-21 Integral Time of Speed Searching 0.1~10.0 2.0 s O O X ⟦blank source cell⟧
23 07-22 Delay Time of Speed Searching 0.0~20.0 0.2 s O O X ⟦blank source cell⟧
24 07-23 Voltage Recovery Time 0.1~5.0 2.0 s O O X ⟦blank source cell⟧
25 07-24 Direction-Detection Speed Search Selection 0:Invalid 1:Valid 1 - O O X ⟦blank source cell⟧
26 07-25 Low Voltage Detection Time 0.00~1.00 0.02 s O O O ⟦blank source cell⟧

Manual — Group07 Start/Stop Parameters continued; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 100

Manual reference: physical PDF page 100. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group07 Start/Stop Parameters continued; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Adjacent source context — repeated to preserve continuation:

Group 07 Start/Stop Parameters — PDF page 100

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters Group 07 Start/Stop Parameters
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 07-26 Start-up Mode Selection of SLV Coast to Stop 0:Start With Speed Search 1:Normal Start 0 - X O X ⟦blank source cell⟧
5 07-27 Start Selection after Fault During SLV Mode 0:Start With Speed Search 1:Normal Start 0 - X O X ⟦blank source cell⟧
6 07-28 Start after External BaseBlock 0:Start With Speed Search 1:Normal Start 0 - O O X ⟦blank source cell⟧
7 07-29 Run Command Selection at the Action of DC Braking 0:Not Allowable to Run 1:Allowable to Run 0 - O X X ⟦blank source cell⟧
8 07-33 Start Frequency of Speed Search Selection 0:Maximum Output Frequency 1:Frequency Command 0 - O O X ⟦blank source cell⟧
9 07-34 Start Short-Circuit Braking Time 0.00~100.00 0.00 s X X O ⟦blank source cell⟧
10 07-35 Stop Short-Circuit Braking Time 0.00~100.00 0.50 s X X O ⟦blank source cell⟧
11 07-36 Short-Circuit Braking Current Limited 0.0~200.0 100.0 % X X O ⟦blank source cell⟧
12 07-37 Pre-Excitation Time 0.00~10.00 2.00 s X O X ⟦blank source cell⟧
13 07-38 Pre-Excitation Level 50~200 100 % X O X ⟦blank source cell⟧
14 07-39 Short-Circuit Braking Time of PM Motor Speed Search Function 0.00~100.00 0.00 s X X O ⟦blank source cell⟧
15 07-40 DC Injection Braking Time of PM Motor Speed Search Function 0.00~100.00 0.00 s X X O ⟦blank source cell⟧
16 07-45 STP2 function selection 0:STP2 is enabled 1:STP2 is disabled 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧

Manual — Group08 Protection Parameters; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 101

Manual reference: physical PDF page 101. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group08 Protection Parameters; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Adjacent source context — repeated to preserve continuation:

Group 08 Protection Parameters — PDF page 101

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 08-00 Stall Prevention Function xxx0b:Stall prevention is enabled in acceleration. xxx1b:Stall prevention is disabled in acceleration. xx0xb:Stall prevention is enabled in deceleration. xx1xb:Stall prevention is disabled in deceleration. x0xxb:Stall prevention is enabled in operation x1xxb:Stall prevention is disabled in operation 0xxxb:Stall prevention in operation is based on deceleration time of speed-stage 1. 1xxxb:Stall prevention in operation is based on deceleration time of speed-stage 2. 0000b - O O O ⟦blank source cell⟧
5 08-01 Stall Prevention Level During Acceleration 20~200 HD:150 ND:120 % O O O ⟦blank source cell⟧
6 08-02 Stall Prevention Level During Deceleration 200V:330V~410V 385V V O O O ⟦blank source cell⟧
7 08-02 Stall Prevention Level During Deceleration 400V:660V~820V 770V V O O O ⟦blank source cell⟧
8 08-03 Stall Prevention Level During Run 30~200 HD:160 % O X X ⟦blank source cell⟧
9 08-03 Stall Prevention Level During Run 30~200 ND:120 % O X X ⟦blank source cell⟧
10 08-05 Selection for Motor Overload Protection (OL1) xxx0b:Overload Protection is disabled. xxx1b:Overload Protection is enabled. xx0xb:Cold Start of Motor Overload xx1xb:Hot Start of Motor Overload x0xxb:Standard Motor x1xxb:Inverter Duty Motor 0xxxb:Reserved 1xxxb:Reserved 0001b - O O O ⟦blank source cell⟧
11 08-06 Start-up Mode of Overload Protection Operation (OL1) 0:Stop Output after Overload Protection 1:Continuous Operation after Overload Protection. 0 - O O O ⟦blank source cell⟧
12 08-07 Cooling Fan Control 0:Start in High Temperature 1:Start in Operation 2:Always Run 3:Stop Operation 1 - O O O ⟦blank source cell⟧
13 08-08 Auto Voltage Regulation (AVR) 0:Enable 1:Disable 0 - O O O ⟦blank source cell⟧
14 08-09 Selection of Input Phase Loss Protection 0:Disable 1:Enable 0 - O O O ⟦blank source cell⟧
15 08-10 Selection of Output Phase Loss Protection 0:Disable 1:Enable 0 - O O O ⟦blank source cell⟧
16 08-13 Selection of Over-Torque Detection 0:Over-Torque Detection is Disabled. 1:Start to Detect when Reaching the Set Frequency. 2:Start to Detect when the Operation is Begun. 0 - O O O ⟦blank source cell⟧

Manual — Group08 Protection Parameters continued; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 102

Manual reference: physical PDF page 102. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group08 Protection Parameters continued; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 08 Protection Parameters — PDF page 102

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 08-14 Selection of Over-Torque Action 0:Deceleration to Stop when Over Torque is Detected. 1:Display Warning when Over Torque is Detected. Go on Operation. 2:Coast to Stop when Over Torque is Detected 0 - O O O ⟦blank source cell⟧
5 08-15 Level of Over-Torque Detection 0~300 160 % O O O ⟦blank source cell⟧
6 08-16 Time of Over-Torque Detection 0.0~10.0 0.1 s O O O ⟦blank source cell⟧
7 08-21 Limit of Stall Prevention During Acceleration 1~100 50 % O O O ⟦blank source cell⟧
8 08-22 Stall Prevention Detection Time During Run 2~100 100 ms O O O ⟦blank source cell⟧
9 08-23 Ground Fault (GF) Selection 0:Disable 1:Enbale 0 - O O O ⟦blank source cell⟧
10 08-24 Operation Selection of External Fault 0:Deceleration to Stop 1:Coast to Stop 2:Continuous Operation 0 - O O O ⟦blank source cell⟧
11 08-25 Detection Selection of External Fault 0:Immediately Detect When the Power is Supplied 1:Start to Detect during Operation 0 - O O O ⟦blank source cell⟧
12 08-35 Motor Overheating Fault Selection 0:Disable 1:Deceleration to Stop 2:Coast to Stop 3:Keep Running 0 - O O O ⟦blank source cell⟧
13 08-36 PTC Input Filter Time Constant 0.00 ~ 5.00 2.00 s O O O ⟦blank source cell⟧
14 08-38 Delay Time of Fan Off 0~600 60 s O O O ⟦blank source cell⟧
15 08-39 Delay Time of Motor Overheat Protection 1~300 60 s O O O ⟦blank source cell⟧
16 08-40 Motor2 Acceleration Stall Prevention Level 20~200 HD: 150 % O O X ⟦blank source cell⟧
17 08-40 Motor2 Acceleration Stall Prevention Level 20~200 ND: 120 % O O X ⟦blank source cell⟧
18 08-41 Motor2 Acceleration Stall Prevention Limit 1~100 50 % O O X ⟦blank source cell⟧
19 08-42 PTC Protection Level 0.1~10.0V 0.7 V O O O ⟦blank source cell⟧
20 08-43 PTC Restart Level 0.1~10.0V 0.3 V O O O ⟦blank source cell⟧
21 08-44 PTC Warning Level 0.1~10.0V 0.5 V O O O ⟦blank source cell⟧
22 08-46 Temperature Agree Level 0~254°C 0 °C O O O ⟦blank source cell⟧
23 08-47 Temperature Reset Level 0~254°C 0 °C O O O ⟦blank source cell⟧

Manual — Group08 Fire Mode parameters and source STO note; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 103

Manual reference: physical PDF page 103. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

***STO function only be designed in EMC filter built-in models.

Group08 Fire Mode parameters and source STO note; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 08 Protection Parameters — PDF page 103

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters Group 08 Protection Parameters
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 08-48 Selection of Fire Mode 0:Disable 1:Enable 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
5 08-49 Multi-Function Input Terminal Status of Fire Mode 0:Reset after Power Off 1:Reset after Terminal Removed 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
6 08-50 Multi-Function Terminal Status of Fire Mode xxx0b:S6 A Contact xxx1b:S6 B Contact 0000b - O O O ⟦blank source cell⟧
7 08-51 Motor Speed Setting Source of Fire Mode 0:Fire Mode Speed(08-52) 1:PID Control 2:AI2 0 - O O O ⟦blank source cell⟧
8 08-52 Motor Speed of Fire Mode 0.00~100.00 100.00 % O O O ⟦blank source cell⟧
9 08-53 PID Detection Level of Fire Mode 0~100 0 % O O O ⟦blank source cell⟧
10 08-54 Delay Time of Fire Mode PID Loss 0.0~10.0 0.0 s O O O ⟦blank source cell⟧
11 08-55 PID Feedback Loss Detection Selection of Fire Mode 0:Keep Running 1:Fire Mode Speed(08-52) 2:Max. Output Frequency of Motor 1 (01-02) 0 - O O O ⟦blank source cell⟧
12 08-56 Detection Level of Fire Mode AI2 Signal 0~100 0 % O O O ⟦blank source cell⟧
13 08-57 Delay Time of Fire Mode AI2 Signal Loss 0.0~10.0 0.0 s O O O ⟦blank source cell⟧
14 08-58 Selection of Fire Mode AI2 Signal Loss 0:Keep Running 1:Fire Mode Speed(08-52) 2:Maximun Output Frequency (01-02) 0 - O O O ⟦blank source cell⟧
15 08-59 Fire Mode Motor Direction 0:Forward 1:Reverse 0 - O O O ⟦blank source cell⟧
16 08-60 Fire Mode Password 00000~65534 0 - O O O ⟦blank source cell⟧

Manual — Group09 Communication Parameters; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values. — page 104

Manual reference: physical PDF page 104. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

*3:Parameter group 09 will not be effected by factory setting. (13-08).

Group09 Communication Parameters; attribute definitions on physical85 retained. O/X, KVA, asterisks and blank cells are literal source symbols, not inferred values.

Group 09 Communication Parametes — PDF page 104

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 09 Communication Parametes Group 09 Communication Parametes Group 09 Communication Parametes Group 09 Communication Parametes Group 09 Communication Parametes Group 09 Communication Parametes Group 09 Communication Parametes Group 09 Communication Parametes Group 09 Communication Parametes
2 Code Parameter Name Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 09-00 INV Communication Station Address 1~32 1 - O O O *3
5 09-01 Communication Mode Selection 0:MODBUS 1:BACnet 3:PUMP in Parallel Connection 0 ⟦blank source cell⟧ O O O *3
6 09-02 Baud Rate Setting (bps) 2:4800 3:9600 4:19200 5:38400 4 - O O O *3
7 09-03 Stop Bit Selection 0:1 Stop Bit 1:2 Stop Bit 0 - O O O *3
8 09-04 Parity Selection 0:No Parity 1:Even Bit 2:Odd Bit 0 - O O O *3
9 09-05 Communication Data Bit Selection 0:8 Bit Data 1:7 Bit Data 0 - O O O *3
10 09-06 Communication Error Detection Time 0.0~25.5 0.0 s O O O *3
11 09-07 Fault Stop Selection 0:Deceleration to Stop By Deceleration Time 1 1:Coast to Stop 2:Deceleration to Stop By Deceleration Time 2 3:Keep Operating 3 - O O O *3
12 09-08 Comm. Fault Tolerance Count 1~20 1 - O O O *3
13 09-09 Waiting Time 5~65 5 ms O O O *3
14 09-10 BACNET Device Instance Number 1~254 1 ⟦blank source cell⟧ O O O *3

Manual — Group10 PID Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 105

Manual reference: physical PDF page 105. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group10 PID Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 10 PID Parameters — PDF page 105

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 10-00 PID Target Value Source Setting 0:Keypad given 1:AI1 given 2:AI2 given 3:Communication given 4:10-02 given 1 - O O O ⟦blank source cell⟧
5 10-01 PID Feedback Value Source Setting 0:Keypad given 1:AI1 given 2:AI2 given 3:Communication given 2 - O O O ⟦blank source cell⟧
6 10-02 PID Target Value 0.00~100.00 0.00 % O O O *1
7 10-03 PID Control Mode xxx0b:PID Disable xxx1b:PID Enable xx0xb:PID Positive Characteristic xx1xb:PID Negative Characteristic x0xxb:PID Error Value of D Control x1xxb:PID Feedback Value of D Control 0xxxb:PID Output 1xxxb:PID Output+Frequency Command 0000b - O O O ⟦blank source cell⟧
8 10-04 Feedback Gain 0.01~10.00 1.00 - O O O *1
9 10-05 Proportional Gain (P) 0.00~10.00 1.00 - O O O *1
10 10-06 Integral Time (I) 0.00~100.00 1.00 s O O O *1
11 10-07 Differential Time (D) 0.00~10.00 0.00 s O O O *1
12 10-08 Primary Delay Filter Time 1~250 4 ms O O O *1
13 10-09 PID Bias -100.0~100.0 0 % O O O *1
14 10-11 PID Feedback Loss Detection Selection 0:Disable 1:Warning 2:Fault 0 - O O O *1
15 10-12 PID Feedback Loss Det. Lev. 0~100 0 % O O O ⟦blank source cell⟧
16 10-13 PID Feedback Loss Det. Time 0.0~25.5 1.0 s O O O ⟦blank source cell⟧
17 10-14 PID Integral Limit 0.0~100.0 100.0 % O O O *1
18 10-17 * Start Frequency of PID Sleep 0.00~599.00 0.00 Hz O O O ⟦blank source cell⟧
19 10-18 Delay Time of PID Sleep 0.0~255.5 0.0 s O O O ⟦blank source cell⟧
20 10-19 * Frequency of PID Waking up 0.00~599.00 0.00 Hz O O O ⟦blank source cell⟧
21 10-20 Delay Time of PID Waking up 0.0~255.5 0.0 s O O O ⟦blank source cell⟧
22 10-23 PID Output Limit 0.00~100.0 100.0 % O O O *1
23 10-24 PID Output Gain 0.0~25.0 1.0 - O O O ⟦blank source cell⟧
24 10-25 PID Reversal Output Selection 0:No Allowing Reversal Output 1:Allow Reversal Output 0 - O O O ⟦blank source cell⟧
25 10-26 PID Target Acceleration/ Deceleration Time 0.0~25.5 0.0 s O O O ⟦blank source cell⟧

Manual — Group10 PID Parameters continued; PID units literalSPI; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 106

Manual reference: physical PDF page 106. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group10 PID Parameters continued; PID units literalSPI; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 10 PID Parameters — PDF page 106

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters Group 10 PID Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 10-27 PID Feedback Display Bias -99.99~99.99 0 - O O O ⟦blank source cell⟧
5 10-29 PID Sleep Selection 0:Disable 1:Enable 2:Set By DI 1 - O O O ⟦blank source cell⟧
6 10-30 Upper Limit of PID Target 0.0 ~ 100.0 100.0 % O O O ⟦blank source cell⟧
7 10-31 Lower Limit of PID Target 0.0 ~ 100.0 0.0 % O O O ⟦blank source cell⟧
8 10-33 Maximum Value of PID Feedback 1 ~ 10000 999 - O O O ⟦blank source cell⟧
9 10-34 PID Decimal Width 0 ~ 4 1 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
10 10-35 PID Unit 0:% 1:FPM 2:CFM 3:SPI 4:GPH 5:GPM 6:IN 7:FT 8:/s 9:/m 10:/h 11:°F 12:inW 13:HP 14:m/s 15:MPM 16:CMM 17:W 18:KW 19:m 20:°C 21:RPM 22:Bar 23:Pa 24:kPa 0 ⟦blank source cell⟧ O O O *7
11 10-39 * Output Frequency Setting of PID Disconnection 00.00~599.00 30.00 Hz O O O ⟦blank source cell⟧
12 10-40 Selection of PID Sleep Compensation Frequency 0:Disable 1:Enable 0 - O O O ⟦blank source cell⟧
13 10-47 Proportional Gain (P) of Fire Mode 0.00~10.00 1.00 ⟦blank source cell⟧ O O O *1
14 10-48 Integral Time (I) of Fire Mode 0.00~100.00 1.00 s O O O *1
15 10-49 Differential Time (D) of Fire Mode 0.00~10.00 0.00 s O O O *1

Manual — Group11 Auxiliary Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 107

Manual reference: physical PDF page 107. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group11 Auxiliary Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 11 Auxiliary Parameters — PDF page 107

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters
2 Code Parameters Setting Range DefaultUnit ⟦blank source cell⟧ Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range DefaultUnit ⟦blank source cell⟧ V/F SLV PM SLV Attribute
4 11-00 Direction Lock Selection 0:Allow Forward and Reverse Rotation 1:Only Allow Forward Rotation 2:Only Allow Reverse Rotation 0 - O O O ⟦blank source cell⟧
5 11-01 Carrier frequency 0:Carrier Output Frequency Tuning 1~16:1~16KHz * - O O O ⟦blank source cell⟧
6 11-02 Soft PWM Function Selection 0:Disable 1:Soft PWM 0 - O O O ⟦blank source cell⟧
7 11-03 Automatic carrier lowering selection 0:Disable 1:Enable 0 - O X X ⟦blank source cell⟧
8 11-04 S-curve Time Setting at the Start of Acceleration 0.00~2.50 0.20 s O O O ⟦blank source cell⟧
9 11-05 S-curve Time Setting at the Stop of Acceleration 0.00~2.50 0.20 s O O O ⟦blank source cell⟧
10 11-06 S-curve Time Setting at the Start of Deceleration 0.00~2.50 0.20 s O O O ⟦blank source cell⟧
11 11-07 S-curve Time Setting at the Stop of Deceleration 0.00~2.50 0.20 s O O O ⟦blank source cell⟧
12 11-08 Jump Frequency 1 0.0~599.0 0.0 Hz O O O ⟦blank source cell⟧
13 11-09 Jump Frequency 2 0.0~599.0 0.0 Hz O O O ⟦blank source cell⟧
14 11-10 Jump Frequency 3 0.0~599.0 0.0 Hz O O O ⟦blank source cell⟧
15 11-11 Jump Frequency Width 0.00 ~ 30.00 1.0 Hz O O O ⟦blank source cell⟧
16 11-12 Manual Energy Saving Gain (V/F) 0~100 80 % O X X ⟦blank source cell⟧
17 11-14 OV Prevention Selection 230V:200V~400V 370 ⟦blank source cell⟧ O X X ⟦blank source cell⟧
18 11-14 OV Prevention Selection 400V:400V~800V 740 ⟦blank source cell⟧ O X X ⟦blank source cell⟧
19 11-17 Acceleration/Deceleration Gain 0.1~10.0 1 ⟦blank source cell⟧ O X X ⟦blank source cell⟧
20 11-18 Manual Energy Saving Frequency 0.0~599.0 0.0 Hz O X X ⟦blank source cell⟧
21 11-28 Frequency Gain of Over Voltage Prevention 2 1~200 100 % O X X ⟦blank source cell⟧
22 11-33 DC Voltage Filter Rise Amount 0.1~10.0 0.1 Vdc O X X ⟦blank source cell⟧
23 11-34 DC Voltage Filter Fall Amount 0.1~10.0 5.0 Vdc O X X *1
24 11-35 DC Voltage Filter Deadband Level 0.0~99.0 10.0 Vdc O X X *1
25 11-36 Frequency gain of OV Prevention 0.000~1.000 0.050 - O X X *1
26 11-37 Frequency limit of OV Prevention *0.00~599.00 5.00 Hz O X X *1

Manual — Group11 Auxiliary Parameters continued;carrier/frequency-resolution notes; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 108

Manual reference: physical PDF page 108. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note:The parameter of 11-01 can be changed during run operation, the range is 1~16KHz.

Group11 Auxiliary Parameters continued;carrier/frequency-resolution notes; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 11 Auxiliary Parameters — PDF page 108

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters Group 11 Auxiliary Parameters
2 Code Parameters Setting Range DefaultUnit ⟦blank source cell⟧ Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range DefaultUnit ⟦blank source cell⟧ V/F SLV PM SLV Attribute
4 11-38 Deceleration start voltage of OV prevention 200V: 200~400V 300 V O X X ⟦blank source cell⟧
5 11-38 Deceleration start voltage of OV prevention 400V: 400~800V 700 V O X X ⟦blank source cell⟧
6 11-39 Deceleration end voltage of OV Prevention 200V: 300~400V 350 V O X X ⟦blank source cell⟧
7 11-39 Deceleration end voltage of OV Prevention 400V: 600~800V 750 V O X X ⟦blank source cell⟧
8 11-40 OV Prevention Selection 0~3 0 ⟦blank source cell⟧ O X X ⟦blank source cell⟧
9 11-47 KEB Deceleration Time 0.0~25.5 0.0 s O X X *1
10 11-48 KEB Detection Level 230V:190~210 200V V O X X ⟦blank source cell⟧
11 11-48 KEB Detection Level 400V:380~420 400V V O X X ⟦blank source cell⟧
12 11-55 STOP Key Selection 0:Stop Key is Disabled when the Operation Command is not Provided by Operator. 1:Stop Key is Enabled when the Operation Command is not Provided by Operator. 1 - O O O ⟦blank source cell⟧
13 11-59 Gain of Preventing Oscillation 0.00~2.50 * ⟦blank source cell⟧ O X X ⟦blank source cell⟧
14 11-60 Upper Limit of Preventing Oscillation 0~100 * % O X X ⟦blank source cell⟧
15 11-61 Time Parameter of Preventing Oscillation 0~100 0 ⟦blank source cell⟧ O X X ⟦blank source cell⟧
16 11-62 Selection of Preventing Oscillation 0:Mode 1 1:Mode 2 2:Mode 3 1 - O X X ⟦blank source cell⟧
17 11-63 Strong Magnetic Selection 0:Disable 1:Enable 1 - X O X ⟦blank source cell⟧
18 11-69 Gain of Preventing Oscillation 2 0.00~200.00 5.00 % O X X ⟦blank source cell⟧
19 11-70 Upper Limit of Preventing Oscillation 2 0.01~100.00 5.00 % O X X ⟦blank source cell⟧
20 11-71 Time of Preventing Oscillation 2 0~30000 100 ms O X X ⟦blank source cell⟧
21 11-72 Switch Frequency 1 of Preventing Oscillation 2 0.01~300.00 30.00 Hz O X X ⟦blank source cell⟧
22 11-73 Switch Frequency 2 of Preventing Oscillation 2 0.01~300.00 50.00 Hz O X X ⟦blank source cell⟧

Manual — Group12 Monitoring Parameters;12-05 LCD display and LED continuation110; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 109

Manual reference: physical PDF page 109. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

12-05 LCD digital-input/output status diagram. Twelve displayed0 boxes, left-to-right:Output Terminal(R1),Output Terminal(R2),Output Terminal(DO1),Output Terminal(PLC),Input Terminal(S1),Input Terminal(S2),Input Terminal(S3),Input Terminal(S4),Input Terminal(S5),Input Terminal(S6),Input Terminal(S7),Input Terminal(S8). Legend0:OPEN,1:CLOSE. Connections are printed display callouts, not wiring. Presence of S7/S8/DO1 labels does not establish terminal hardware availability. LED display continues110.

Group12 Monitoring Parameters;12-05 LCD display and LED continuation110; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 12 Monitoring Parameters — PDF page 109

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 12-00 Display Screen Selection (LED) 00000~88888 From the leftmost bit, it displays the screen when press DSP key in order. 0:no display 1:Output Current 2:Output Voltage 3:DC Bus Voltage 4:Heatsink Temperature* 5:PID Feedback 6:AI1 Value 7:AI2 Value 8:Counter Value 00000 - O O O *1 *6
5 12-01 PID Feedback Display Mode (LED) 0:Display the Feedback Value by Integer (xxx) 1:Display the Feedback Value by the Value with One Decimal Place (xx.x) 2:Display the Feedback Value by the Value with Two Decimal Places (x.xx) 0 ⟦blank source cell⟧ O O O *6
6 12-02 PID Feedback Display Unit Setting (LED) 0:xxxxx (no unit) 1:xxxPb (pressure) 2:xxxFL (flow) 0 ⟦blank source cell⟧ O O O *6
7 12-03 Line Speed Display (LED) 0~60000 1500/ 1800 RPM O O O *1 *6
8 12-04 Modes of Line Speed Display (LED) 0:Display Inverter Output Frequency 1:Display Line Speed with integer (xxxxx) 2:Display Line Speed with the First Decimal Place (xxxx.x) 3:Display Line Speed with the Second Decimal Place (xxx.xx) 4:Display Line Speed with the Third Decimal Place (xx.xxx) 0 - O O O *1 *6
9 12-05 Status Display of Digital Input & Output Terminal (LED/LCD) LCD display is shown as below 0 0 0 0 0 0 0 0 Input Terminal(S8) Input Terminal(S7) Input Terminal(S6) Input Terminal(S5) Input Terminal(S4) Input Terminal(S3) Input Terminal(S2) Input Terminal(S1) 0:OPEN 1:CLOSE 0 0 0 Output Terminal(DO1) Output Terminal(R2) Output Terminal(R1) 0 Output Terminal(PLC) LED display is shown as below - ⟦blank source cell⟧ O O O *4

Manual — Group12 Monitoring Parameters;12-05 LED continuation from109; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 110

Manual reference: physical PDF page 110. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

12-05 LED continuation from109. No input illustration has five lit central horizontal dashes. Input correspondence:the firstfour digit positions each show upper-left andupper-right black segments; arrows labelS1,S2,S3,S4,S5,S6,S7,S8 fromlefttoright. Fifth digit isunlit grayoutline. Output correspondence:lowerfour-segment loops (central,bottom,lowerleft,lowerright) in firstfour digits; arrowsR1,R2,DO1,PLC fromlefttoright; fifthdigitunlit. These illustrate displaysegments, not numeric2222 or current signals or wiring.

Second visual reading corrected detector column boundary at original x156.300003; first-reading raw values/bounds and independent recheck retained. Display graphics are separately bounded; no terminal hardware inferred.

Group12 Monitoring Parameters;12-05 LED continuation from109; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 12 Monitoring Parameters — PDF page 110

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 ⟦blank source cell⟧ ⟦blank source cell⟧ no input Correspondences to input and output ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
5 12-11 Output Current of Current Fault Display the output current of current fault - A O O O *4
6 12-12 Output Voltage of Current Fault Display the output voltage of current fault - V O O O *4
7 12-13 Output Frequency of Current Fault Display the output frequency of current fault - Hz O O O *4
8 12-14 DC Voltage of Current Fault Display the DC voltage of current fault - V O O O *4
9 12-15 Frequency Command of Current Fault Display the frequency command of current fault - Hz O O O *4
10 12-16 Frequency Command If LED enters this parameter, it only allows monitoring frequency command. - Hz O O O *4
11 12-17 Output Frequency Display the current output frequency - Hz O O O *4
12 12-18 Output Current Display the current output current - A O O O *4
13 12-19 Output Voltage Display the current output voltage - V O O O *4
14 12-20 DC Voltage (Vdc) Display the current DC voltage - V O O O *4
15 12-21 Output Power Display the current output power - kW O O O *4
16 12-28 Motor Torque Current (Iq) Display the current q-axis current ⟦blank source cell⟧ % X O O *4
17 12-29 Motor Excitation Current (Id) Display the current d-axis current ⟦blank source cell⟧ % X O O *4
18 12-36 PID Input Display input error of the PID controller (PID target value - PID feedback) (100% corresponds to the maximum frequency set by 01-02 or 01-16) ⟦blank source cell⟧ % O O O *4
19 12-37 PID Output Display output of the PID controller (100% corresponds to the maximum frequency set by 01-02 or 01-16) ⟦blank source cell⟧ % O O O *4
20 12-38 PID Setting Display the target value of the PID controller (100% corresponds to the maximum frequency set by 01-02 or 01-16) ⟦blank source cell⟧ % O O O *4

Manual — Group12 Monitoring Parameters;12-43 bit display and enclosure/type monitor; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 111

Manual reference: physical PDF page 111. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: 12-41 has unexplained local * and ** temperature qualifiers. All printed table/diagram content retained; Attachment1 on128 says YES, but no missing qualifier invented.

12-43 Inverter Status diagram:8displayedzero boxes. Rightmost box callout1:Inverter ready; nextleft1:During running; nextleft1:During zero speed; nextleft1:During speed agree; nextleft1:During fault detection(minor fault); nextleft1:During fault detection(major fault); remainingtwoleftmostboxes bracketedReserved. This is printed display-bit correspondence, not a current device state.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: 12-41 has unexplained local * and ** temperature qualifiers. All printed table/diagram content retained; Attachment1 on128 says YES, but no missing qualifier invented.

Group12 Monitoring Parameters;12-43 bit display and enclosure/type monitor; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 12 Monitoring Parameters — PDF page 111

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters Group 12 Monitoring Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 12-39 PID Feedback Display the feedback value of the PID controller (100% corresponds to the maximum frequency set by 01-02 or 01-16) ⟦blank source cell⟧ % O O O *4
5 12-41 Heatsink Temperature* Display the heatsink temperature of IGBT temperature** ⟦blank source cell⟧ ℃ O O O *4
6 12-43 Inverter Status 0 0 0 0 0 0 0 0 1: Inverter ready 1: During running 1: During zero speed 1: During speed agree 1: During fault detection (minor fault) 1: During fault detection (major fault) Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ O O O *4
7 12-74 Operation Pressure Setting 0.01~25.50 2.00 PSI O X X ⟦blank source cell⟧
8 12-75 Pressure Feedback Value 0.01~25.50 - PSI O X X ⟦blank source cell⟧
9 12-82 Motor Loading Display the loading current of motor - % O O O *4
10 12-83 Type of E510s 0:IP20 NFS(without functional safety) 1:IP20 FS(with functional safety) 2:IP66 NFS(without functional safety) 3:IP66 FS(with functional safety) - - O O O *4

Manual — Group13 Maintenance Parameters;factory-reset options and fault-history beginning; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 112

Manual reference: physical PDF page 112. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Reset13-08 options2,9,10 each literally60Hz220V/380V; option1 is50Hz. Distinct codes retained.

Group13 Maintenance Parameters;factory-reset options and fault-history beginning; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 13 Maintance Parameters — PDF page 112

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 13-00 Inverter Capacity Selection ---- - - O O O *3*4
5 13-01 Software Version 0.00-9.99 - - O O O *3*4
6 13-02 Fault Record ⟦blank source cell⟧ 0 - O O O *4
7 13-03 Cumulative Operation Hours 1 0~23 - hr O O O *3*4
8 13-04 Cumulative Operation Hours 2 0~65534 - day O O O *3*4
9 13-05 Selection of Cumulative Operation Time 0:Cumulative time in power on 1:Cumulative time in operation 0 - O O O *1
10 13-06 Parameters Locked 0:Parameters are read-only except 13-06 and main frequency 1 : Reserved 2 : All Parameters are Writable 2 - O O O ⟦blank source cell⟧
11 13-07 Parameter Password Function 00000~65534 00000 - O O O ⟦blank source cell⟧
12 13-08 Restore Factory Setting 1:2 wire initialization (50Hz) (220V/380V) 2:2 wire initialization (60Hz) (220V/380V) 3:2 wire initialization (50Hz) (230V/400V) 4:2 wire initialization (60Hz) (230V/460V) 5:2 wire initialization (50Hz) (220V/415V) 6:2 wire initialization (60Hz) (230V/400V) 7:2 wire initialization (50Hz) (220V/440V) 8:2 wire initialization (60Hz) (220V/440V) 9:2 wire initialization (60Hz) (220V/380V) 10:2 wire initialization (60Hz) (220V/380V) 1112:PLC initialization (RESET) - - O O O ⟦blank source cell⟧
13 13-09 Fault History Clearance Function 0:No Clearing Fault History 1 : Clear Fault History 0 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
14 13-10 Situation 0~9999 - - O O O ⟦blank source cell⟧
15 13-21 Last Time Fault History Exhibit last time fault history ⟦blank source cell⟧ ⟦blank source cell⟧ O O O ⟦blank source cell⟧
16 13-22 Previous Two Fault History Exhibit previous two fault history ⟦blank source cell⟧ ⟦blank source cell⟧ O O O ⟦blank source cell⟧
17 13-23 Previous Three Fault History Exhibit previous three fault history ⟦blank source cell⟧ ⟦blank source cell⟧ O O O ⟦blank source cell⟧
18 13-24 Previous Four Fault History Exhibit previous four fault history ⟦blank source cell⟧ ⟦blank source cell⟧ O O O ⟦blank source cell⟧
19 13-25 Previous Five Fault History Exhibit previous five fault history ⟦blank source cell⟧ ⟦blank source cell⟧ O O O ⟦blank source cell⟧
20 13-26 Previous Six Fault History Exhibit previous six fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧

Manual — Group13 fault-history continuation; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 113

Manual reference: physical PDF page 113. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group13 fault-history continuation; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 13 Maintance Parameters — PDF page 113

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 13-27 Previous Seven Fault History Exhibit previous seven fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
5 13-28 Previous Eight Fault History Exhibit previous eight fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
6 13-29 Previous Nine Fault History Exhibit previous nine fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
7 13-30 Previous Ten Fault History Exhibit previous ten fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
8 13-31 Previous Eleven Fault History Exhibit previous eleven fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
9 13-32 Previous Twelve Fault History Exhibit previous twelve fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
10 13-33 Previous Thirteen Fault History Exhibit previous thirteen fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
11 13-34 Previous Fourteen Fault History Exhibit previous fourteen fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
12 13-35 Previous Fifteen Fault History Exhibit previous fifteen fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
13 13-36 Previous Sixteen Fault History Exhibit previous sixteen fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
14 13-37 Previous Seventeen Fault History Exhibit previous seventeen fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
15 13-38 Previous Eighteen Fault History Exhibit previous eighteen fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
16 13-39 Previous Nineteen Fault History Exhibit previous nineteen fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
17 13-40 Previous Twenty Fault History Exhibit previous twenty fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
18 13-41 Previous Twenty one Fault History Exhibit previous twenty one fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
19 13-42 Previous Twenty Two Fault History Exhibit previous twenty two fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
20 13-43 Previous Twenty Three Fault History Exhibit previous twenty three fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
21 13-44 Previous Twenty Four Fault History Exhibit previous twenty four fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
22 13-45 Previous Twenty Five Fault History Exhibit previous twenty five fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
23 13-46 Previous Twenty Six Fault History Exhibit previous twenty six fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
24 13-47 Previous Twenty Seven Fault History Exhibit previous twenty seven fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧

Manual — Group13 final fault histories and operation-time clearing; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 114

Manual reference: physical PDF page 114. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group13 final fault histories and operation-time clearing; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 13 Maintance Parameters — PDF page 114

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters Group 13 Maintance Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 13-48 Previous Twenty Eight Fault History Exhibit previous twenty eight fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
5 13-49 Previous Twenty Nine Fault History Exhibit previous twenty nine fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
6 13-50 Previous Thirty Fault History Exhibit previous thirty fault history ⟦blank source cell⟧ - O O O ⟦blank source cell⟧
7 13-51 Operation Time Clearance Function 0:Do not clear operation time 1:Clear operation time 0 - O O O *1

Manual — Group14 PLC Setting Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 115

Manual reference: physical PDF page 115. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group14 PLC Setting Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 14 PLC Setting Parameters — PDF page 115

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 14-00 T1 Set Value 1 0~9999 0 - O O O ⟦blank source cell⟧
5 14-01 T1 Set Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
6 14-02 T2 Set Value 1 0~9999 0 - O O O ⟦blank source cell⟧
7 14-03 T2 Set Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
8 14-04 T3 Set Value 1 0~9999 0 - O O O ⟦blank source cell⟧
9 14-05 T3 Set Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
10 14-06 T4 Set Value 1 0~9999 0 - O O O ⟦blank source cell⟧
11 14-07 T4 Set Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
12 14-08 T5 Set Value 1 0~9999 0 - O O O ⟦blank source cell⟧
13 14-09 T5 Set Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
14 14-10 T6 Set Value 1 0~9999 0 - O O O ⟦blank source cell⟧
15 14-11 T6 Set Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
16 14-12 T7 Set Value 1 0~9999 0 - O O O ⟦blank source cell⟧
17 14-13 T7 Set Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
18 14-14 T8 Set Value 1 0~9999 0 - O O O ⟦blank source cell⟧
19 14-15 T8 Set Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
20 14-16 C1 Set Value 0~65534 0 - O O O ⟦blank source cell⟧
21 14-17 C2 Set Value 0~65534 0 - O O O ⟦blank source cell⟧
22 14-18 C3 Set Value 0~65534 0 - O O O ⟦blank source cell⟧
23 14-19 C4 Set Value 0~65534 0 - O O O ⟦blank source cell⟧
24 14-20 C5 Set Value 0~65534 0 - O O O ⟦blank source cell⟧
25 14-21 C6 Set Value 0~65534 0 - O O O ⟦blank source cell⟧
26 14-22 C7 Set Value 0~65534 0 - O O O ⟦blank source cell⟧
27 14-23 C8 Set Value 0~65534 0 - O O O ⟦blank source cell⟧
28 14-24 AS1 Set Value 1 0~65534 0 - O O O ⟦blank source cell⟧
29 14-25 AS1 Set Value 2 0~65534 0 - O O O ⟦blank source cell⟧
30 14-26 AS1 Set Value 3 0~65534 0 - O O O ⟦blank source cell⟧
31 14-27 AS2 Set Value 1 0~65534 0 - O O O ⟦blank source cell⟧
32 14-28 AS2 Set Value 2 0~65534 0 - O O O ⟦blank source cell⟧
33 14-29 AS2 Set Value 3 0~65534 0 - O O O ⟦blank source cell⟧
34 14-30 AS3 Set Value 1 0~65534 0 - O O O ⟦blank source cell⟧
35 14-31 AS3 Set Value 2 0~65534 0 - O O O ⟦blank source cell⟧
36 14-32 AS3 Set Value 3 0~65534 0 - O O O ⟦blank source cell⟧
37 14-33 AS4 Set Value 1 0~65534 0 - O O O ⟦blank source cell⟧
38 14-34 AS4 Set Value 2 0~65534 0 - O O O ⟦blank source cell⟧
39 14-35 AS4 Set Value 3 0~65534 0 - O O O ⟦blank source cell⟧
40 14-36 MD1 Set Value 1 0~65534 1 - O O O ⟦blank source cell⟧
41 14-37 MD1 Set Value 2 0~65534 1 - O O O ⟦blank source cell⟧

Manual — Group14 PLC Setting Parameters continued; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 116

Manual reference: physical PDF page 116. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group14 PLC Setting Parameters continued; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 14 PLC Setting Parameters — PDF page 116

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters Group 14 PLC Setting Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 14-38 MD1 Set Value 3 1~65534 1 - O O O ⟦blank source cell⟧
5 14-39 MD2 Set Value 1 0~65534 1 - O O O ⟦blank source cell⟧
6 14-40 MD2 Set Value 2 0~65534 1 - O O O ⟦blank source cell⟧
7 14-41 MD2 Set Value 3 1~65534 1 - O O O ⟦blank source cell⟧
8 14-42 MD3 Set Value 1 0~65534 1 - O O O ⟦blank source cell⟧
9 14-43 MD3 Set Value 2 0~65534 1 - O O O ⟦blank source cell⟧
10 14-44 MD3 Set Value 3 1~65534 1 - O O O ⟦blank source cell⟧
11 14-45 MD4 Set Value 1 0~65534 1 - O O O ⟦blank source cell⟧
12 14-46 MD4 Set Value 2 0~65534 1 - O O O ⟦blank source cell⟧
13 14-47 MD4 Set Value 3 1~65534 1 - O O O ⟦blank source cell⟧

Manual — Group15 PLC Monitoring Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 117

Manual reference: physical PDF page 117. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group15 PLC Monitoring Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 15 PLC Monitoring Parameters — PDF page 117

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 15 PLC Monitoring Parameters Group 15 PLC Monitoring Parameters Group 15 PLC Monitoring Parameters Group 15 PLC Monitoring Parameters Group 15 PLC Monitoring Parameters Group 15 PLC Monitoring Parameters Group 15 PLC Monitoring Parameters Group 15 PLC Monitoring Parameters Group 15 PLC Monitoring Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 15-00 T1 Current Value1 0~9999 0 - O O O *4
5 15-01 T1 Current Value 2 (Mode7) 0~9999 0 - O O O *4
6 15-02 T2 Current Value 1 0~9999 0 - O O O *4
7 15-03 T2 Current Value 2 (Mode7) 0~9999 0 - O O O *4
8 15-04 T3 Current Value 1 0~9999 0 - O O O *4
9 15-05 T3 Current Value 2 (Mode7) 0~9999 0 - O O O *4
10 15-06 T4 Current Value 1 0~9999 0 - O O O *4
11 15-07 T4 Current Value 2 (Mode7) 0~9999 0 - O O O *4
12 15-08 T5 Current Value 1 0~9999 0 - O O O *4
13 15-09 T5 Current Value 2 (Mode7) 0~9999 0 - O O O *4
14 15-10 T6 Current Value 1 0~9999 0 - O O O *4
15 15-11 T6 Current Value 2 (Mode7) 0~9999 0 - O O O *4
16 15-12 T7 Current Value 1 0~9999 0 - O O O *4
17 15-13 T7 Current Value 2 (Mode7) 0~9999 0 - O O O *4
18 15-14 T8 Current Value 1 0~9999 0 - O O O *4
19 15-15 T8 Current Value 2 (Mode7) 0~9999 0 - O O O *4
20 15-16 C1 Current Value 0~65534 0 - O O O *4
21 15-17 C2 Current Value 0~65534 0 - O O O *4
22 15-18 C3 Current Value 0~65534 0 - O O O *4
23 15-19 C4 Current Value 0~65534 0 - O O O *4
24 15-20 C5 Current Value 0~65534 0 - O O O *4
25 15-21 C6 Current Value 0~65534 0 - O O O *4
26 15-22 C7 Current Value 0~65534 0 - O O O *4
27 15-23 C8 Current Value 0~65534 0 - O O O *4
28 15-24 AS1 Current Value 0~65534 0 - O O O *4
29 15-25 AS2 Current Value 0~65534 0 - O O O *4
30 15-26 AS3 Current Value 0~65534 0 - O O O *4
31 15-27 AS4 Current Value 0~65534 0 - O O O *4
32 15-28 MD1 Current Value 0~65534 0 - O O O *4
33 15-29 MD2 Current Value 0~65534 0 - O O O *4
34 15-30 MD3 Current Value 0~65534 0 - O O O *4
35 15-31 MD4 Current Value 0~65534 0 - O O O *4
36 15-32 TD Current Value 0~65534 0 - O O O *4

Manual — Group16 LCD Function Parameters;16-04 unit options continue119; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 118

Manual reference: physical PDF page 118. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group16 LCD Function Parameters;16-04 unit options continue119; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 16 LCD Function Parameters — PDF page 118

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 16-00 Main Screen Monitoring 5~83 when using LCD to operate, the monitored item displays in the first line. (default: frequency command) 16 - O O O *1*7
5 16-01 Sub-Screen Monitoring 1 5~83 when using LCD to operate, the monitored item displays in the second line. (default: output frequency) 17 - O O O *1*7
6 16-02 Sub-Screen Monitoring 2 5~83 when using LCD to operate, the monitored item displays in the third line. (default is output current)) 18 - O O O *1*7
7 16-03 Display Unit 0~39999 Determine the display way and unit of frequency command 0:Frequency display unit is 0.01Hz 1:Frequency display unit is 0.01% 2:Frequency display unit is RPM. 3~39:Reserved 40~9999: Users specify the format, Input 0XXXX represents the display of XXXX at 100%. 10001~19999: Users specify the format; Input 1XXXX represents the display of XXX.X at 100%. 20001~29999: Users specify the format, Input 2XXXX represents the display of XX.XX at 100%. 30001~39999: Users specify the format, Input 3XXXX represents the display of X.XXX at 100%. 0 - O O O *7
8 16-04 Engineering Unit 0:No Unit 1:FPM 2:CFM 3:PSI 4:GPH 5:GPM 6:IN 7:FT 8:/s 9:/m 10:/h 11:°F 12:inW 13:HP 14:m/s 15:MPM 16:CMM 0 - O O O *7

Manual — Group16 LCD Function Parameters continued from118; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 119

Manual reference: physical PDF page 119. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group16 LCD Function Parameters continued from118; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 16 LCD Function Parameters — PDF page 119

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters Group 16 LCD Function Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 ⟦blank source cell⟧ ⟦blank source cell⟧ 17:W 18:kW 19:m 20:°C 21:RPM 22:Bar 23:Pa 24:kPa ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
5 16-05 LCD Backlight 0~7 5 - O O O *1*7
6 16-07 Copy Function Selection 0:Do not copy parameters 1:Read inverter parameters and save them to the operator. 2:Write the operator parameters to inverter. 3:Compare parameters of inverter and operator. 0 - O O O *7
7 16-08 Selection of Allowing Reading 0:Do not allow to read inverter parameters or save them to the operator. 1:Allow to read inverter parameters and save to the operator. 0 - O O O *7
8 16-09 Selection of Operator Removed (LCD) 0:Keep operating when LCD operator is removed. 1:Display fault when LCD operator is removed 0 - O O O *1*7

Manual — Group17 Automatic Tuning Parameters and capacity-dependent default note; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. KVA is explicitly defined here:default value changes by inverter capacity; do not substitute one universal number. Mode17-00 table defaultsV/F2/SLV6 and general note6 kept separately. Auto-tune coupled-load warning and procedure on83–84 remain applicable context, not replaced by this table. — page 120

Manual reference: physical PDF page 120. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

KVA:The default value of this parameter will be changed by different capacities of inverter

It is suggested that HD/ ND mode (00-27) be selected first before motor performs auto-tuning.

Note:The value of mode selection of automatic tuning is 6 (Static Auto-tuning Combination). When do

auto-tuning with no-load motor, it is suggested to select 17-00=5 (Rotation Auto-tuning Combination)

Group17 Automatic Tuning Parameters and capacity-dependent default note; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. KVA is explicitly defined here:default value changes by inverter capacity; do not substitute one universal number. Mode17-00 table defaultsV/F2/SLV6 and general note6 kept separately. Auto-tune coupled-load warning and procedure on83–84 remain applicable context, not replaced by this table.

Group 17 Automatic Tuning Parameters — PDF page 120

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 17 Automatic Tuning Parameters Group 17 Automatic Tuning Parameters Group 17 Automatic Tuning Parameters Group 17 Automatic Tuning Parameters Group 17 Automatic Tuning Parameters Group 17 Automatic Tuning Parameters Group 17 Automatic Tuning Parameters Group 17 Automatic Tuning Parameters Group 17 Automatic Tuning Parameters
2 Code Parameter Name Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameter Name Setting Range Default Unit V/F SLV PM SLV Attribute
4 17-00 Mode Selection of Automatic Tuning* 0:Rotation Auto-tuning 1:Static Auto-tuning 2:Stator Resistance Measurement 3:Reserved 4:Loop Tuning 5:Rotation Auto-tuning Combination (item: 4+2+0) 6:Static Auto-tuning Combination (item: 4+2+1) V/F:2 SLV:6 - O O X ⟦blank source cell⟧
5 17-01 Motor Rated Output Power 0.00~600.00 KVA kW O O X ⟦blank source cell⟧
6 17-02 Motor Rated Current 0.1~1200.0 KVA A O O X ⟦blank source cell⟧
7 17-03 Motor Rated Voltage 200V:50.0~240.0 220 V O O X ⟦blank source cell⟧
8 17-03 Motor Rated Voltage 400V:100.0~480.0 440 V O O X ⟦blank source cell⟧
9 17-04 Motor Rated Frequency 4.8~599.0 60.0 Hz O O X ⟦blank source cell⟧
10 17-05 Motor Rotated Speed 0~24000 KVA RPM O O X ⟦blank source cell⟧
11 17-06 Pole Number of Motor 2~16(Even) 4 Pole O O X ⟦blank source cell⟧
12 17-08 Motor no-load Voltage 200V:50~240 400V:100~480 KVA V O O X ⟦blank source cell⟧
13 17-09 Motor Excitation Current 0.01~600.00 KVA A X O X ⟦blank source cell⟧
14 17-10 Automatic Tuning Start 0:Disable 1:Enable 0 - O O X ⟦blank source cell⟧
15 17-11 Error History of Automatic Tuning 0:No error 1:Motor data error 2:Stator resistance tuning error 3:Leakage induction tuning error 4:Rotor resistance tuning error 5:Mutual induction tuning error 6:DT Error 7:Encoder error 8:Motor’s acceleration error 9:Warning 0 - O O X ⟦blank source cell⟧
16 17-12 Proportion of Motor Leakage Inductance 0.1~15.0 KVA % X O X ⟦blank source cell⟧
17 17-13 Motor Slip Frequency 0.10~20.00 KVA Hz X O X ⟦blank source cell⟧
18 17-14 Selection of Rotation Auto-tuning 0: VF Rotation Auto-tuning 1: Vector Rotation Auto-tuning 0 - O O X ⟦blank source cell⟧

Manual — Group18 Slip Compensation Parameters;model defaults inAttachment1 on128; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 121

Manual reference: physical PDF page 121. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

***:Refer to the following attachment 1

Group18 Slip Compensation Parameters;model defaults inAttachment1 on128; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 18 Slip Compensation Parameters — PDF page 121

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 18 Slip Compensation Parameters Group 18 Slip Compensation Parameters Group 18 Slip Compensation Parameters Group 18 Slip Compensation Parameters Group 18 Slip Compensation Parameters Group 18 Slip Compensation Parameters Group 18 Slip Compensation Parameters Group 18 Slip Compensation Parameters Group 18 Slip Compensation Parameters
2 Code Parameters Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 18-00 Slip Compensation Gain at Low Speed. 0.00~2.50 VF:0.00 - O O X *1
5 18-00 Slip Compensation Gain at Low Speed. 0.00~2.50 SLV:*** - O O X *1
6 18-01 Slip Compensation Gain at High Speed. -1.00~1.00 0.0 - O O X *1
7 18-02 Slip Compensation Limit 0~250 200 % O X X ⟦blank source cell⟧
8 18-03 Slip Compensation Filter Time 0.0~10.0 1.0 s O X X ⟦blank source cell⟧
9 18-04 Regenerative Slip Compensation Selection 0:Disable 1:Enable 0 - O X X ⟦blank source cell⟧
10 18-05 FOC Delay Time 1~1000 100 ms X O X ⟦blank source cell⟧
11 18-06 FOC Gain 0.00~2.00 0.1 - X O X ⟦blank source cell⟧

Manual — Group20 Speed Control Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 122

Manual reference: physical PDF page 122. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group20 Speed Control Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 20 Speed Control Parameters — PDF page 122

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 20 Speed Control Parameters Group 20 Speed Control Parameters Group 20 Speed Control Parameters Group 20 Speed Control Parameters Group 20 Speed Control Parameters Group 20 Speed Control Parameters Group 20 Speed Control Parameters Group 20 Speed Control Parameters Group 20 Speed Control Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 20-00 ASR Gain 1 0.00~250.00 - - X O O *1
5 20-01 ASR Integral Time 1 0.001~10.000 - s X O O *1
6 20-02 ASR Gain 2 0.00~250.00 - - X O O *1
7 20-03 ASR Integral Time 2 0.001~10.000 - s X O O *1
8 20-04 ASR Integral Time Limit 0~300 200 % X O O ⟦blank source cell⟧
9 20-07 Selection of Acceleration and Deceleration of P/PI 0:PI speed control will be enabled only in constant speed. For the speed acceleration and deceleration, only use P control 1:Speed control is enabled either in acceleration or deceleration. 0 - X O X ⟦blank source cell⟧
10 20-08 ASR Delay Time 0.000~0.500 0.004 s X O O ⟦blank source cell⟧
11 20-09 Speed Observer Proportional (P) Gain1 0.00~2.55 0.61 - X O X *1
12 20-10 Speed Observer Integral(I) Time 1 0.01~10.00 0.05 s X O X *1
13 20-11 Speed Observer Proportional (P) Gain2 0.00~2.55 0.61 - X O X *1
14 20-12 Speed Observer Integral(I) Time 2 0.01~10.00 0.06 s X O X *1
15 20-13 Low-pass Filter Time Constant of Speed Feedback 1 1~1000 4 ms X O X ⟦blank source cell⟧
16 20-14 Low-pass Filter Time Constant of Speed Feedback 2 1~1000 30 ms X O X ⟦blank source cell⟧
17 20-15 ASR Gain Change Frequency 1 0.0~599.0 4.0 Hz X O O ⟦blank source cell⟧
18 20-16 ASR Gain Change Frequency 2 0.0~599.0 8.0 Hz X O O ⟦blank source cell⟧
19 20-17 Torque Compensation Gain at Low Speed 0.00~2.50 1.00 - X O X *1
20 20-18 Torque Compensation Gain at High Speed -10~10 0 % X O X *1
21 20-33 Detection Level at Constant Speed 0.1~5.0 1.0 ⟦blank source cell⟧ X O O *1
22 20-34 Compensation Gain of Derating 0~25600 0 ⟦blank source cell⟧ X O O *1
23 20-35 Compensation Time of Derating 0~30000 100 ms X O O *1

Manual — Group21 Torque And Position Control Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 123

Manual reference: physical PDF page 123. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group21 Torque And Position Control Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 21 Torque And Position Control Parameters — PDF page 123

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 21 Torque And Position Control Parameters Group 21 Torque And Position Control Parameters Group 21 Torque And Position Control Parameters Group 21 Torque And Position Control Parameters Group 21 Torque And Position Control Parameters Group 21 Torque And Position Control Parameters Group 21 Torque And Position Control Parameters Group 21 Torque And Position Control Parameters Group 21 Torque And Position Control Parameters
2 Code Parameters Setting Range Default Unit Control mode Control mode Control mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 21-05 Positive Torque Limit 0~300 150 % X O O *1
5 21-06 Negative Torque Limit 0~300 150 % X O O *1
6 21-07 Forward Regenerative Torque Limit 0~300 150 % X O O *1
7 21-08 Reversal Regenerative Torque Limit 0~300 150 % X O O *1

Manual — Group22 PM Motor Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 124

Manual reference: physical PDF page 124. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group22 PM Motor Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 22 PM Motor Parameters — PDF page 124

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 22 PM Motor Parameters Group 22 PM Motor Parameters Group 22 PM Motor Parameters Group 22 PM Motor Parameters Group 22 PM Motor Parameters Group 22 PM Motor Parameters Group 22 PM Motor Parameters Group 22 PM Motor Parameters Group 22 PM Motor Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 22-00 PM Motor Rated Power 0.00~600.00 KVA kW X X O ⟦blank source cell⟧
5 22-02 PM Motor Rated Current 25%~200% inverter rated current KVA A X X O ⟦blank source cell⟧
6 22-03 PM Motor‘s Pole Number 2~96 8 Poles X X O ⟦blank source cell⟧
7 22-04 PM Motor’s Rotation Speed 0~60000 1500 RPM X X O ⟦blank source cell⟧
8 22-05 PM Motor’s Maximum Rotation Speed 0~60000 1500 RPM X X O ⟦blank source cell⟧
9 22-06 PM Motor Rated Frequency 4.8~599.0 75.0 Hz X X O ⟦blank source cell⟧
10 22-07 PM Motor Type Selection 0: SPM 1: IPM 0 - X X O ⟦blank source cell⟧
11 22-10 PM SLV Start Current 20% ~ 200% Motor Rated Current 50 % X X O ⟦blank source cell⟧
12 22-11 I/F Mode Start Frequency Switching Point 1.0 ~ 20.0 10.0 % X X O ⟦blank source cell⟧
13 22-14 Armature Resistance of PM Motor 0.001 ~ 30.000 1.000 Ω X X O ⟦blank source cell⟧
14 22-15 D-axis Inductance of PM Motor 0.01 ~300.00 10.00 mH X X O ⟦blank source cell⟧
15 22-16 Q-axis Inductance of PM Motor 0.01 ~ 300.00 10.00 mH X X O ⟦blank source cell⟧
16 22-18 Flux-Weakening Limit 0~100 0 % X X O ⟦blank source cell⟧
17 22-21 PM Motor Tuning 0:PM Motor Tuning is not Active. 1:Parameter Auto-tune Mode 1 2:Parameter Auto-tune Mode 2 0 - X X O ⟦blank source cell⟧
18 22-22 Fault History of PM Motor Tuning 0:None 1:Static Magnetic Alignment Fault 5:Loop Adjustment is Time Out 7:Other Errors of Motor Tuning 9:Current Abnormity Occurs when Loop Adjustment 0 - X X O *4
19 22-23 PMSLV acceleration time 0.1~10.0 1.0 Sec X X O ⟦blank source cell⟧
20 22-25 Detection Mode Selection of Initial Magnetic Pole 0:Upon the angle before stopping 1:Detection Mode 1 2:Detection Mode 2 2 - X X O ⟦blank source cell⟧
21 22-26 Estimator Mode 0~1 (in PMSLV mode) 0 - X X O ⟦blank source cell⟧
22 22-27 Voltage Command of Mode 2 5~120 (22-25=2 or 22-26=1 is enabled) 50 % X X O ⟦blank source cell⟧
23 22-28 Divider Ratio of Mode 2 0~8 (22-25=2 or 22-26=1 is enabled) 2 - X X O ⟦blank source cell⟧
24 22-29 Flux-weakening Voltage Command Restriction 80~110 (related to parameter 22-18) 100 % X X O ⟦blank source cell⟧
25 22-34 IPM Estimator Gain 1~300.0 180 ⟦blank source cell⟧ X X O ⟦blank source cell⟧

Manual — Group23 PUMP & HVAC Function Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 125

Manual reference: physical PDF page 125. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group23 PUMP & HVAC Function Parameters; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 23 PUMP & HVAC Function Parameters — PDF page 125

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 23-00 Function Selection 0: Disable 1: PUMP 2: HVAC 3: Compressor 0 - O X X ⟦blank source cell⟧
5 23-01 Setting of Single & Multiple Pumps and Master & Slave Machines 0: Single Pump 1: Master 2: Slave 1 3: Slave 2 4: Slave 3 0 - O X X ⟦blank source cell⟧
6 23-02 Operation Pressure Setting 0.10 ~ 650.00 2.00 PSI O X X ⟦blank source cell⟧
7 23-03 Maximum Pressure Setting of Pressure Transmitter 0.10 ~ 650.00 10.00 PSI O X X ⟦blank source cell⟧
8 23-04 Pump Pressure Command Source 0:Set by 23-02 1:Set by AI 0 ⟦blank source cell⟧ O X X ⟦blank source cell⟧
9 23-05 Display Mode Selection 0: Display of Target and Pressure Feedback 1: Target Pressure Only 2: Feedback Pressure Only 0 ⟦blank source cell⟧ O X X ⟦blank source cell⟧
10 23-06 Proportion Gain(P) 0.00~10.00 3.00 - O X X ⟦blank source cell⟧
11 23-07 Integral Time(I) 0.0~100.0 0.5 Sec O X X ⟦blank source cell⟧
12 23-08 Differential Time(D) 0.00~10.00 0.00 Sec O X X ⟦blank source cell⟧
13 23-09 Tolerance Range of Constant Pressure 0.01 ~ 650.00 0.5 PSI O X X ⟦blank source cell⟧
14 23-10 Sleep Frequency of Constant Pressure 0.00 ~ 599.00 30.00 Hz O X X ⟦blank source cell⟧
15 23-11 Sleep Time of Constant Pressure 0.0 ~ 255.5 0.0 Sec O X X ⟦blank source cell⟧
16 23-12 Maximun Presure Limit 0.00 ~ 650.00 5 PSI O X X ⟦blank source cell⟧
17 23-13 Warning Time of High Pressure 0.0 ~ 600.0 10.0 Sec O X X ⟦blank source cell⟧
18 23-14 Stop Time of High Pressure 0.0 ~ 600.0 20.0 Sec O X X ⟦blank source cell⟧
19 23-15 Minimum Pressure Limit 0.00 ~ 650.00 5 %/P SI O X X ⟦blank source cell⟧
20 23-16 Warning Time of Low Pressure 0.0 ~ 600.0 0.0 Sec O X X ⟦blank source cell⟧
21 23-17 Fault Stop Time of Low Pressure 0.0 ~ 600.0 0.0 Sec O X X ⟦blank source cell⟧

Manual — Group23 PUMP & HVAC Function Parameters continued; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 126

Manual reference: physical PDF page 126. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group23 PUMP & HVAC Function Parameters continued; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 23 PUMP & HVAC Function Parameters — PDF page 126

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 23-18 Time of Loss Pressure Detection 0.0 ~ 600.0 0.0 Sec O X X ⟦blank source cell⟧
5 23-19 Proportion of Loss Pressure Detection 0 ~ 100 0 % O X X ⟦blank source cell⟧
6 23-22 Slave Trip Frequency 0.00 ~ 599.00 45.00 Hz O X X ⟦blank source cell⟧
7 23-23 Direction of Water Pressure Detection 0: Upward Detection 1: Downward Detection 1 - O X X ⟦blank source cell⟧
8 23-24 Range of Water Pressure Detection 0.00 ~ 65.00 0.1 PSI O X X ⟦blank source cell⟧
9 23-25 Period of Water Pressure Detection 0.0 ~ 200.0 30.0 Sec O X X ⟦blank source cell⟧
10 23-26 Acceleration Time of Water Pressure Detection 0.1 ~ 6000.0 KVA Sec O X X ⟦blank source cell⟧
11 23-27 Deceleration Time of Water Pressure Detection 0.1 ~ 6000.0 KVA Sec O X X ⟦blank source cell⟧
12 23-28 Forced Run Command 0.00 ~ 599.00 0.00 Hz O X X ⟦blank source cell⟧
13 23-29 Switching Time of Water Pressure Detection 0 ~ 240 3 Hr/ min O X X ⟦blank source cell⟧
14 23-30 Detection Time of Multiple Pumps in Parallel Running Start 0.0 ~ 30.0 5.0 Sec O X X ⟦blank source cell⟧
15 23-31 Synchronous Selection of Multiple Pumps in Parallel 0: Disable 1: Pressure Setting Run/Stop 2: Pressure Setting 3: Run/Stop 1 ⟦blank source cell⟧ O X X ⟦blank source cell⟧
16 23-34 Tolerance Range of Constant Pressure 2 0.01 ~ 650.00 0.5 PSI O X X ⟦blank source cell⟧
17 23-35 Selection of Multiple Pumps Shift Operation 0: No Function 1: Timer Alternately Selection 2: Sleep Stop Alternately Selection 3: Timer and Sleep Stop Alternately Selection 4: Multiple Pumps Test Mode 1 ⟦blank source cell⟧ O X X ⟦blank source cell⟧
18 23-37 Leakage Detection Time 0.0~100.0 0.0 Sec O X X ⟦blank source cell⟧
19 23-38 Pressure Variation of Leakage Detection Restart 0.01 ~ 65.00 0.1 PSI O X X ⟦blank source cell⟧
20 23-39 Pressure Tolerance Range of Leakage Detection Restart 0.01 ~ 650.00 0.5 PSI O X X ⟦blank source cell⟧

Manual — Group23 PUMP & HVAC Function Parameters continued; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred. — page 127

Manual reference: physical PDF page 127. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group23 PUMP & HVAC Function Parameters continued; attribute definitions fromphysical85 retained. O/X, symbols and blanks are literal source; no applicability or missing values inferred.

Group 23 PUMP & HVAC Function Parameters — PDF page 127

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters Group 23 PUMP & HVAC Function Parameters
2 Code Parameters Setting Range Default Unit Control Mode Control Mode Control Mode Attribute
3 Code Parameters Setting Range Default Unit V/F SLV PM SLV Attribute
4 23-71 Maximum Pressure Setting 0.10~650.00 10.00 PSI O X X ⟦blank source cell⟧
5 23-72 Switching Time of Alternation in Parallel 0: Hour 1: Minute 0 ⟦blank source cell⟧ O X X ⟦blank source cell⟧
6 23-73 Slave Wake-Up Selection 0: Disable 1: Enable 0 ⟦blank source cell⟧ O X X ⟦blank source cell⟧
7 23-74 High Pressure Setting 0: Disable 1: High Pressure Warning 2: High Pressure Warning or Error 2 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
8 23-75 Low Pressure Setting 0: Disable 1: Low Pressure Warning 2: Low Pressure Warning or Error 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
9 23-78 Selection of Loss Pressure Detection 0: Disable 1: Loss Pressure Warning 2: Low Pressure Error 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧

Manual — Attachment1: model/frame-specific maximumSLVoutput and low-speed slip defaults Read each actual merged source cell against its model row;11-01<=8K and>8K columns must not be conflated. AllYES temperature flags literal; source does not validate hardware or engineering. — page 128

Manual reference: physical PDF page 128. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Attachment 1:Different factory setting and maximum setting value of each models

Attachment1: model/frame-specific maximumSLVoutput and low-speed slip defaults Read each actual merged source cell against its model row;11-01<=8K and>8K columns must not be conflated. AllYES temperature flags literal; source does not validate hardware or engineering.

Model / Frame / When 11-01 <= 8K, the maximum output of SLV mode (Hz) / When 11-01 > 8K, the maximum output of SLV mode (Hz) / Whether 12-41 displayed inverter temperature? / SLV initial value(18-00) (Low speed slip compensation — PDF page 128

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Model Frame When 11-01 <= 8K, the maximum output of SLV mode (Hz) When 11-01 > 8K, the maximum output of SLV mode (Hz) Whether 12-41 displayed inverter temperature? SLV initial value(18-00) (Low speed slip compensation
2 2P5 1 150 150 YES 1.00
3 201 1 150 150 YES 1.00
4 202H3 1 150 150 YES 1.00
5 202H1 2 150 150 YES 1.00
6 203 2 150 150 YES 1.00
7 205 2 150 150 YES 1.00
8 208 3 150 150 YES 1.00
9 210 3 150 150 YES 1.00
10 215 4 110 110 YES 1.00
11 220 4 110 110 YES 1.00
12 225 5 100 80 YES 0.70
13 230 6 100 80 YES 0.70
14 240 6 100 80 YES 0.70
15 401 1 150 150 YES 1.00
16 402 1 150 150 YES 1.00
17 403 2 150 150 YES 1.00
18 405 2 150 150 YES 1.00
19 408 3 150 150 YES 1.00
20 410 3 150 150 YES 1.00
21 415 3 150 150 YES 1.00
22 420 4 110 110 YES 1.00
23 425 4 100 100 YES 1.00
24 430 5 100 80 YES 0.70
25 440 6 100 80 YES 0.70
26 450 6 100 80 YES 0.70
27 460 6 100 80 YES 0.70
28 475 6 100 80 YES 0.70

Manual — Attachment1: model-specific torque/ASR/initial settings and HD carrier limits Exact source header says initial00-14~00-17 /00-23~00-27; this overlapsHD/ND00-27 and absent00-25 in prior table. Preserve literal header and flag ambiguous applicability. ASR20-08 model initial values differ from general table122; no preferred value inferred. No units printed for several columns; values and parameter references retained. — page 129

Manual reference: physical PDF page 129. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Attachment initial-setting header00-14~00-17 /00-23~00-27 overlaps HD/ND00-27 and absent00-25; exact applicability unresolved. Several numeric columns lack local units. All literal values/model associations retained without inferred correction.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Attachment initial-setting header00-14~00-17 /00-23~00-27 overlaps HD/ND00-27 and absent00-25; exact applicability unresolved. Several numeric columns lack local units. All literal values/model associations retained without inferred correction.

Attachment1: model-specific torque/ASR/initial settings and HD carrier limits Exact source header says initial00-14~00-17 /00-23~00-27; this overlapsHD/ND00-27 and absent00-25 in prior table. Preserve literal header and flag ambiguous applicability. ASR20-08 model initial values differ from general table122; no preferred value inferred. No units printed for several columns; values and parameter references retained.

Model / Initial value of 21-05~21-08 (Torque limit) / Initial value of 20-08 (ASR filter time) / Initial value of 00-14~00-17 00-23~00-27 / Factory setting of 11-01 in HD mode / The maximum value of 11-01 in HD mode (SLV control mode) / The maximum value of 11-01 in HD mode (Other control modes) — PDF page 129

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Model Initial value of 21-05~21-08 (Torque limit) Initial value of 20-08 (ASR filter time) Initial value of 00-14~00-17 00-23~00-27 Factory setting of 11-01 in HD mode The maximum value of 11-01 in HD mode (SLV control mode) The maximum value of 11-01 in HD mode (Other control modes)
2 2P5 150% 0.001 10.0 5 16 16
3 201 150% 0.001 10.0 5 16 16
4 202H3 150% 0.001 10.0 5 16 16
5 202H1 150% 0.001 10.0 5 16 16
6 203 150% 0.001 10.0 5 16 16
7 205 150% 0.001 10.0 5 16 16
8 208 150% 0.001 10.0 5 16 16
9 210 150% 0.001 10.0 5 16 16
10 215 150% 0.002 15.0 5 16 16
11 220 150% 0.002 15.0 5 16 16
12 225 150% 0.002 20.0 5 8 12
13 230 150% 0.004 20.0 5 8 12
14 240 150% 0.004 20.0 5 8 12
15 401 150% 0.001 10.0 5 16 16
16 402 150% 0.001 10.0 5 16 16
17 403 150% 0.001 10.0 5 16 16
18 405 150% 0.001 10.0 5 16 16
19 408 150% 0.001 10.0 5 16 16
20 410 150% 0.001 10.0 5 16 16
21 415 150% 0.001 10.0 5 16 16
22 420 150% 0.002 15.0 5 16 16
23 425 150% 0.002 15.0 5 16 16
24 430 150% 0.002 20.0 5 8 16
25 440 150% 0.004 20.0 5 8 12
26 450 150% 0.004 20.0 5 8 12
27 460 150% 0.004 20.0 5 8 10
28 475 150% 0.004 20.0 5 8 10

Manual — Low voltage start function: backup supply, contactor timing and all disabling conditions — page 130

Manual reference: physical PDF page 130. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

The function of Low Voltage Start:

Wiring diagram:

Contactor 1 and 3 will b3 enable before the backup power is powered on, contactor 2 needs to keep opened.

Contactor 3 will be opened after contactor 1. Contactor 1 and 3 should keep closed before backup power was

removed and contactor 2 was be closed.

Notes of Low Voltage Start function:

  1. When low voltage start function is enabled (DI=62), cooling fan will not run, it can prevent the input voltage

be dropped.

  1. When low voltage start function is enabled, the function of input phase loss protection will be disabled.

  2. When low voltage start function is enabled, the output frequency of motor will be based on 07-31.

Low-voltage-start wiring diagram labels:Single phase UPS or Battery;3~ supply;Inverter R/L1,S/L2,T/L3;contactors circled1,2,3;Input terminal of low voltage start function;S1~S8;24VG. Source supply specification440V Class207~380Vac,or292~537Vdc. Literal source labels only; no wiring topology or terminal availability inferred.

Timing chart of Electromagnetic contactor:three stacked traces1,2,3, dashed synchronized boundaries. Trace2 changes low before1/3 rise;1/3 fall before2rises. Source prose states1and3enabledbeforebackup power,2open;3openedafter1;1/3openbeforebackuppowerremovedand2closed. No timing duration shown; no timing values inferred.

Manual — Elevator riding comfort and DC injection/zero-speed control; supplier statements not standards verification — page 131

Manual reference: physical PDF page 131. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Enhance the Riding Confort of Elevator

If there is any uncomfortable feeling during acceleration and deceleration period when you take the elevator.

Please try to adjust the parameters as follows.

Notes:

During the deceleration of S curve, if the output frequency is lower than 01-08, the function of S curve will be

stopped and then transfer to DC injection braking (Zero Speed Control).

Function of DC Injection Braking and Zero Speed Control.

Note 1:

According to the standards of European market, when the elevator is stop, the inverter and the motor has to be

separated by contactor. For emergency situation, the inverter and the motor just can be separated by DC injection

braking disabled and base block enabled (base block signal is ON)

Note 2:

When inverter control is separated from motor control or DC injection braking control (Zero speed control).

Sometimes, inverter will occur fault by pulse voltage.

Besides, when the contactor is installed between inverter and motor, please et 08-10=1 (Selection of output phase

loss protection).

Elevator output-frequency/time plot:11-04 atinitialaccelerationbend;11-05atupperaccelerationbend;11-06upperdecelerationbend;11-07lowerdecelerationbend.00-14Acceleration1 rising ramp;00-15Deceleration1 falling ramp. DCinjectionbrakingatstop (whenusingPGvectorcontrol,itwillbezerocontrol) marked atblackstopblock. No numeric timing inferred.

DCInjectionBraking/ZeroSpeedControl plot:OutputFrequency decreases;07-08DCInjectionBrakingTimeatStop(ZeroSpeedBrakingTimeatStop)0.3~0.5s betweenverticaldashedboundaries. FrequencyOutput traceONbeforefirstboundary,OFFafter. DCBrake traceOFFbeforefirstboundary,risesbetweenboundaries,ONaftersecond. Labels reflectsourceillustration,not validatedoperationalstate.

Manual — Group00 basic controls;V/F,SLV,PMSLV motor/auto-tune conditions — page 132

Manual reference: physical PDF page 132. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.3 Description of parameters

Group 00 Basic Parameters

➢ The inverter offers the following control modes:

(1) 00-00=0 (V/F Mode)

➢ Select the required V/F curve (01-00) based on your motor and applications.

➢ Perform a stationary auto-tune (17-00=2), if the motor cable is longer than 50m

(165ft), see parameter group 17 for details.

(2) 00-00=2 (SLV Control)

➢ Verify the inverter rating matches the motor rating. Perform rotational auto-tune to

measure and store motor parameters for higher performance operation. Perform

non-rotational auto-tune if it is not possible to rotate the motor during auto-tune.

Refer to parameter group 17 for details on auto-tuning.

(3) 00-00=5 (PMSLV)

➢ PMSLV control mode has to connect motor, otherwise “CF08” error will be displayed.

➢ Verify the inverter rating matches the motor rating. Perform rotational auto-tune to measure

and store motor parameters for higher performance operation.

➢ Perform auto-tuning before operation to enhance the performance of PMSLV mode. Refer to

parameter 22-21 for the descriptions of PM motor tuning function.

➢ Select the appropriate motor rating and braking resistor based on your motor and

applications. Please install the braking module in the models of 200V 30HP/ 400V

40HP or the above.

Note:Parameter 00-00 is excluded from initialization.

Group00 basic controls;V/F,SLV,PMSLV motor/auto-tune conditions

00- 00 / Control Mode Selection — PDF page 132

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 00 Control Mode Selection
2 Range 【0】: V/F 【2】: SLV 【5】: PMSLV

00-00 Value / Mode / Information / Application — PDF page 132

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 00-00 Value Mode Information Application
2 0 V/F V/F Control without PG General Purpose applications which do not require high precision speed control, auto- tuning is not required.
3 2 SLV Sensorless Vector Control without PG General Purpose Applications that require higher precision speed control and torque response without the use of an encoder.
4 5 PMSLV Sensorless Current Vector Control without PG (for Permanent magnet motor) Without PG Applications. Provide the requirements of high precision speed and torque

Manual — Motor direction/main and alternative run-command sources;PLC3second stop condition — page 133

Manual reference: physical PDF page 133. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Use the FWD/REV key to change motor direction when Run Command Selection

(00-02=0) is set to keypad control.

(1) 00-02=0:Keypad

➢ Use the keypad to start and stop the inverter and set direction with the forward /

reverse key). Refer to section 4-1 for details on the keypad.

(2) 00-02=1:External Terminal

➢ External terminals (00-04) can be used to start and stop the inverter and select motor direction.

➢ Please refer Fig. 4.3.1 for two wire control mode.

➢ Please refer Fig. 4.3.2 for three wire control mode.

(3) 00-02=2:Communication

➢ Communication port (RS485) can be used to start and stop.

➢ Please refer parameter 09 for RS-422/485communication control.

(4) 00-02=3:PLC

➢ Parameter 00-05 is invalid when the run and stop command is used by PLC function.

➢ PLC function can be stopped by RUN/STOP (keep pressing for 3 seconds) key of the keypad.

(1) 00-03=0:Keypad Control

➢ Use the keypad to start and stop the inverter and set direction with the forward / reverse key).

Refer to section 4-1 for details on the keypad.

(2) 00-03=1:External terminal control

➢ External terminals are used to start and stop the inverter and select motor direction.

Note:It is required to be used with multi-function digital input

(12:main and alternative run switch function).

Motor direction/main and alternative run-command sources;PLC3second stop condition

00- 01 / Motor’s Rotation Direction — PDF page 133

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 01 Motor’s Rotation Direction
2 Range 【0】:Forward 【1】:Reverse

00- 02 / Main Run Command Source Selection — PDF page 133

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 02 Main Run Command Source Selection
2 Range 【0】:Keypad 【1】:External Terminal (Control Circuit) 【2】:Communication Control (RS-485) 【3】:PLC

00- 03 / Alternative RUN Command Selection — PDF page 133

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 03 Alternative RUN Command Selection
2 Range 【0】:Keypad 【1】:External terminal control 【2】:Communication control 【3】:PLC

Manual — External two-wire/three-wire operation and settings; source diagram labels only — page 134

Manual reference: physical PDF page 134. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ 00-04 is valid when run command is set to external mode by 00- 02/00- 03 =1.

➢ Set 00-04=【0/1】first, before setting (03- 00~03- 05) to【0】or【1】.

➢ 00- 04=【0】, Set external terminals (03-00 to 03-05) function to 0 for FWD/Stop or Set to 1 for

REV/Stop.

➢ 00- 04=【1】, Set external terminals (03-00 to 03-05) function to 0 for Run/Stop or Set to 1 for

FWD/REV

➢ 00-04 =【2】Terminals S1, S2, S3 are used in a combination to enable 3 wire run/stop mode.

➢ Settings for 03-00, 03-01, 03–02 will not be effective. Please refer Fig.4.3.1 for 2 wire operation

mode.

■ 2-wire operation

➢ For 2-wire operation set 03-00 (S1 terminal selection) to 0 and 03-01 (S2 terminal

selection) to 1.

Figure 4.3.1 wiring example of 2-wire

■ 3-wire operation

Figure 4.3.2 3 wiring example of 3-wire

Figure4.3.1two-wirewiringexample:ForwardRun/Stop,S1;ReverseRun/Stop,S2;24VG. Switch/contactsymbols retained byimage. No wiring instructions inferred.

Figure4.3.2three-wirewiringexample:Operation(normallyopenMomentaryswitch),Stop(NormallyclosedMomentaryswitch),S1RunCommand(On:Run),S2StopCommand(Off:Stop),S3Forward/Reverse selection,24VG. Exactsource labels; image retainsconnections; no inferred topology.

External two-wire/three-wire operation and settings; source diagram labels only

00- 04 / Alternative RUN Command Selection — PDF page 134

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 04 Alternative RUN Command Selection
2 Range 【0】:Forward/Stop-Reverse/Stop 【1】:Run/Stop- Reverse/ Forward 【2】:3 Wire Control Mode - Run/Stop

Manual — Three-wire timing continuation and main/alternative frequency sources — page 135

Manual reference: physical PDF page 135. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Terminal S1 must be closed for a minimum of 50ms to activate operation, please refer

below.

Figure 4.3.3 3-wire operation

(1) 00-05/00-06=0

➢ Use the digital operator to enter frequency reference or to set parameter 05-01 (frequency

reference 1), please refer section 4.1.4 for the details.

➢ If 00-06=0, the value of alternative frequency command only can be set in parameter 05-01.

(2) 00-05/00-06=1

➢ Use the potentiometer to enter frequency source

(3) 00-05/00-06=2 or 3

➢ Use analog reference from analog input AI1 or AI2 to set the frequency reference (as shown in

Figure 4.4.4). Refer to parameters 04-00 to select the signal type

➢ If the main frequency input signal is analog voltage signal, please set JP1 (AI1) to V. If the main

frequency input signal is analog current signal, please set JP1 (AI1) to I.

Figure4.3.3three-wireoperation timing:RunCommandOnpulse>=50ms thenOff;StopCommandOff(Stop) interval;Forward/ReverseCommandOff(forward),On(Reversal);MotorSpeed sequenceStop,Forward,Reverse,Stop,Forward. TimingaxesTime. SourceproseS1closedminimum50ms. No unlabelled durations or speeds inferred.

Three-wire timing continuation and main/alternative frequency sources

00- 05 / Main Frequency Command Source Selection — PDF page 135

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 05 Main Frequency Command Source Selection
2 00- 06 Alternative Frequency Command Source Selection
3 Range 【0】:Up/Down of Keypad 【1】:Potentiometer on Keypad 【2】:External AI1 Analog Signal Input 【3】:External AI2 Analog Signal Input 【4】:External Up/Down Frequency Control 【5】:Communication Setting Frequency 【6】:Reserved 【7】:Pulse Input

Manual — Analog and pulse command inputs; preserve jumper and terminal-name contradictions — page 136

Manual reference: physical PDF page 136. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Pulse input frequency range literally50to25KHz leaves unit of50 unspecified;PI/S3andJP3/JP2source conflicts retained. No missing unit or hardware configuration inferred.

Figure 4.3.4 Analog input as main frequency reference command

Note:

  1. When analog current input signal connectes to AI2, please set JP3 to I (default setting) and set

04-00=0~3 (AI2=0~20mA / 4~20mA)。

  1. When analog voltage input sognal connectes to AI2, please set JP3 to V (default setting) and

set 04-00=0~3 (AI2=0~10V / 2~10V)。

  1. Please set parameter 04-00 correctly according to your AI1/AI2 signal.

(4) 00-05/00-06=4

➢ The inverter accelerates with the UP command closed and decelerates with the DOWN

command closed. Please refer to parameter 03-00~03-05 for additional information.

(5) 00-05/00-06=5

➢ Please use MODICON series PLC or othe devices which uses MODBUS protocol to

communicate, please set thecorrect baud-rate for communication according to the details in

chapter 09.

(6) 00-05/00-06=7

➢ To use this function a pulse train input is required to be connected to the PI input and

GND, please refer the photo as Fig.4.3.5. PI input terminal, built-in resistance, is not required to

connect the resistance if open collector input mode is used

Figure 4.3.5 Frequency reference from pulse input

Figure4.3.4analoginput example: +10V,2KΩpotentiometer,AI1MainSpeedFrequencyReferenceCommand(VoltageInput);AI2MainSpeedFrequencyReferenceCommand(CurrentInput);GND. JP1 I/V graphic filledrightV;JP2 I/V graphicfilledleftI. Theseprintedjumperlabels conflictwithJP3prosebelow;retainboth,do not selecthardwareconfiguration.

Figure4.3.5pulseinput:terminalS3,groundGND/0V,Serialpulseinput(Internalresistance:3.89K). SpecificationsLowInputLevel0.0to0.5V;HighInputLevel4.0to13.5V;Dutycycle(ON/OFF)30%to70%;PulseInputFrequencyRange50to25KHz literal. Prose callsPIinput;do not resolvePI/S3or unitrangeambiguity.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Pulse input frequency range literally50to25KHz leaves unit of50 unspecified;PI/S3andJP3/JP2source conflicts retained. No missing unit or hardware configuration inferred.

Manual — Frequency selection,initial value and upper/lower limits — page 137

Manual reference: physical PDF page 137. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Local00-11unit remains unprinted; exact same-parameter/same-range PDF87 supplies separate Hz context only. Additionally00-13summaryPDF87range0.00–599.00 conflicts with detailPDF137range0.00–598.99Hz; intended upper limit is unresolved. Preserve both literal ranges and local omission.

➢ When 00-07=0, the frequency source is set by the Main frequency parameter 00-05.

➢ When 00-07=1, The frequency command will be the result of setting of main and alternative

frequencies. The inverter will display the SE01 error when 00-07=1 and parameter 00-05 and

00-06 are set to the same selection.

➢ When parameter 00-06 is set to 0 (Keypad) the alternative frequency reference is set by

parameter 05-01 (Frequency setting of speed-stage 0).

➢ This parameter only can be used to read the set frequency in communication mode.

➢ This parameter is only effective in the communication mode.

➢ This parameter is only enabled in communication mode

➢ The parameter only can be used when main frequencysource comes from keypad.

➢ When 00-10=0, the initial frequency is set by the current frequency.

➢ When 00-10=1, the initial frrquency will be reset to 0.

➢ When 00-10=2, the initial frequency will be set by 00-11.

➢ Set the maximum frequency reference is 100% of the 01-02 or 01-16.

➢ The inverter will display the SE01 error when 00-12 value is lower than 00-13. Frequency upper

and lower limit is active for all frequency reference modes.

➢ When 00-13>0 and output frequency<00-13, inverter output frequency will be based on 00-13.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: 00-11 Initial Frequency Setpoint range0.00–599.00 has no printed unit in its row. Exact source retained; no unit inferred.

Frequency selection,initial value and upper/lower limits

00- 07 / Main and Alternative Frequency Command modes — PDF page 137

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 07 Main and Alternative Frequency Command modes
2 Range 【0】:Main frequency 【1】:Main frequency + alternative frequency

00- 08 / Communication frequency command — PDF page 137

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 08 Communication frequency command
2 Range 【0.00~599.00】Hz

00- 09 / Frequency Command save on power down — PDF page 137

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 09 Frequency Command save on power down
2 Range 【0】:Disable 【1】:Enable

00- 10 / Initial Frequency Selection of Stop — PDF page 137

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 10 Initial Frequency Selection of Stop
2 Range 【0】:By Current Frequency Command 【1】:By Zero Frequency Command 【2】:By Parameter 00-11

00- 11 / Initial Frequency Setpoint — PDF page 137

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 11 Initial Frequency Setpoint
2 Range 0.00-599.00
3 00-12 Frequency Upper limit
4 Range 【0.01-599.00】Hz
5 00-13 Frequency Lower limit
6 Range 【0.00-598.99】 Hz

Manual — Acceleration/deceleration parameters and capacity-specific defaults;selection continues139 — page 138

Manual reference: physical PDF page 138. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.6 Frequency reference upper and lower limits

Preset Acceleration and Deceleration times set by above parameters.

Factory setting of acceleration timeis 00-14, factory setting of deceleration time is 00-15.

➢ Acceleration time is the time required to accelerate from 0 to 100% of maximum output

frequency (01-02 or 01-16).

➢ Deceleration time is the time required to decelerate from 100 to 0% of maximum output

The default values for the accele. / decal. times are dependent on the inverter size.

A. Select acceleration and deceleration time via the digital input terminals

The following table shows the acceleration / deceleration selected when the digital input function

Accel/ Decel time 1 is used.

Figure4.3.6frequencyreferenceupperandlowerlimits:verticalOutputFrequency,horizontalFrequencyReference,100%referenceandoutputmarks,lowerplateau00-13,risinglinearsegment,upperplateau00-12. No intermediatevaluesinferred.

Acceleration/deceleration parameters and capacity-specific defaults;selection continues139

00-14 / Acceleration time 1 — PDF page 138

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00-14 Acceleration time 1
2 Range 【0.1~6000.0】 Sec
3 00-15 Deceleration time 1
4 Range 【0.1~6000.0】 Sec
5 00-16 Acceleration time 2
6 Range 【0.1~6000.0】 Sec
7 00-17 Deceleration time 2
8 Range 【0.1~6000.0】 Sec
9 00-21 Acceleration time 3
10 Range 【0.1~6000.0】 Sec
11 00-22 Deceleration time 3
12 Range 【0.1~6000.0】 Sec
13 00-23 Acceleration time 4
14 Range 【0.1~6000.0】 Sec
15 00-24 Deceleration time 4
16 Range 【0.1~6000.0】 Sec

Size / Acceleration / Deceleration Default Value — PDF page 138

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Size Size Acceleration / Deceleration Default Value
2 200V series 400V series Acceleration / Deceleration Default Value
3 1~10HP 1~15HP 10s
4 15~20HP 20~25HP 15s
5 25~40HP 30~75HP 20s

Manual — Digital input/motor-specific ramp selection and jog conditions — page 139

Manual reference: physical PDF page 139. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.1 Acceleration/Deceleration Time Selection

Figure 4.3.7 Didital input S5 switch between Tacc1/Tacc2 and Tdec1/Tdec2

B. Switch of Acceleration/Deceleration time according to motors

03-00~03-06 set to 40 (Switching between motor 1/motor 2), it can switch motors by digital input.

(Motor 1 and Motor 2 selection function only for V/F control mode.)

➢ When motor 1 selected, please refer table 4.3.1 for acceleration/deceleration time selection.

➢ When motor 2 selected, please refer the table below of acceleration/deceleration time selection.

➢ Jog acceleration time (00-19) is the time required to accelerate from 0 to 100% of maximum

output frequency (01-02 or 01-16). Jog deceleration time (00-20) is the time required to

decelerate from 100 to 0% of maximum output frequency (01-02 or 01-16).

➢ The JOG function is operational by using the multi-function input terminals S1 to S6 (00-02=1)

and setting the relevant parameters 03-00~03-05 to 6 or 7, the motor will run by the setting.

Refer to parameter group 3.

Figure4.3.7DigitalinputS5(03-04=10):OutputFrequencyrisesTacc1thenTacc2,fallsTdec2thenTdec1. S5tracehighduringTacc2/plateau/Tdec2,lowoutside. Timeaxes.No ramp durationinferred.

Digital input/motor-specific ramp selection and jog conditions

Accel/decel time 1 (Set 03-00 to 03-05=10) / Acceleration Time / Deceleration Time — PDF page 139

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Accel/decel time 1 (Set 03-00 to 03-05=10) Acceleration Time Deceleration Time
2 0 Taccc1(00-14) Tdec1(00-15)
3 1 Taccc2(00-16) Tdec2(00-17)
4 0 : OFF 1 : ON 0 : OFF 1 : ON 0 : OFF 1 : ON

Motor 2 selected — PDF page 139

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Motor 2 selected Motor 2 selected Motor 2 selected
2 Acceleration/Deceleratio Selection (Set 03-00 to 03-05 = 10) Acceleration Time Deceleration Time
3 0 Taccc3(00-21) Tdec3(00-22)
4 1 Taccc4(00-23) Tdec4(00-24)

00-18 / Jog frequency — PDF page 139

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00-18 Jog frequency
2 Range 【0.00~599.00】Hz
3 00-19 Jog acceleration time
4 Range 【0.1~600.0】Sec
5 00-20 Jog deceleration time
6 Range 【0.1~600.0】Sec

Manual — Emergency stop example andHD/ND mode limits;SLVlimitscontinue141 — page 140

Manual reference: physical PDF page 140. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When emergency stop input is activated the inverter will decelerate to a stop using the Emergency

stop time

➢ When digital input set to 14, inverter will decelerate to stop by emergency stop time (00-26).

➢ To cancel the emergency stop condition the run command has to be removed and emergency stop

input deactivated

Figure 4.3.9 Emergency stop example

➢ The inverter overload curve, carrier frequency, stalls prevention level, rated input/output current and maximum frequency are automatically set based on the inverter duty (HD/ND) selection. Please refer to table 4.3.2 for detailed information.。

Table 4.3.2 Heavy Duty (Constant torque) / Normal Duty (Variable torque)

Note:ND mode only can be used for 25-40HP of 200V class and 30-75HP of 400V class.

➢ Select V/F curve (Group 1) and enter motor data (Group 2) to match the application. ➢ In H/D mode, the maximum output frequency is 599Hz for all control modes, except for SLV where the maximum output frequency is limited based on the inverter rating, see table below.

Figure4.3.9emergencystoexample:EmergencyStopCommandS5(03-04=14)tracehasONlabelatlowlevelandOFFlabelathighlevel;RunCommandONatfirstpulse;OutputFrequencyrises,thenrampsdownatsecondverticalboundarywithEmergencyStopdecelerationtimecallout,thenlaterrestarts. Preserveinverted-lookingON/OFFlabelpositions;no wiringpolarityinferred.

Emergency stop example andHD/ND mode limits;SLVlimitscontinue141

00- 26 / Emergency stop time — PDF page 140

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 26 Emergency stop time
2 Range 【0.1~6000.0】 Sec

00- 27 / HD/ND Mode — PDF page 140

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 27 HD/ND Mode
2 Range 【0】: HD (Heavy Duty / Constant Torque) 【1】: ND (Normal Duty / Variable Torque)

00-27 / Overload capacity / Carrier frequency / Maximum output frequency / Stall prevention level / Rated input / output current — PDF page 140

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 00-27 Overload capacity Carrier frequency Maximum output frequency Stall prevention level Rated input / output current
2 0 (H/D mode) 150%, 1min 2-16KHz 599.00Hz 150% (08-00, 08-01) Refer to section 3.7
3 1 (N/D mode) 120%, 1min 2-16KHz 120.00Hz 120% (08-00, 08-01) Refer to section 3.7

Manual — SLVmodel limits;NDonlyV/F;language andminimum/PIDfrequency — page 141

Manual reference: physical PDF page 141. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note:In normal duty mode only applies to control modes V/F . All other modes must

use the Heavy Duty settings.

It is required to be with LCD keypad to display the language selection of parameter 00-34

➢ 00-34=0, LCD keypad displays in English.

➢ 00-34=1, LCD keypad displays in Simplified Chinese.

➢ 00-34=2, LCD keypad displays in Traditional Chinese.

➢ 00-34=3, LCD keypad displays in Turkish.

Note:It will not restore to the default value when this parameter performs initialization.

➢ 00-35=0, when output frequency lower than minimum frequency (01-08), display will

show STP0 alarm.

➢ 00-35=1, when the frequency command is lower than minimum frequency, inverter will

keeping running at minimum frequency.

➢ When 00-36=0, the lower frequency of PID sleep mode will base on 10-17~10-20.

➢ When 00-36=1, the lower frequency of PID sleep mode is 0Hz.

SLVmodel limits;NDonlyV/F;language andminimum/PIDfrequency

Horsepower / Special circumtances / Maximum output frequency — PDF page 141

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Horsepower Special circumtances Maximum output frequency
2 220V 1~10HP, 440V 1~15HP - 150Hz
3 220V 15~20HP, 440V 20HP - 110Hz
4 440V 25HP - 100Hz
5 220V 25~40HP, 440V 30~75HP, 11-01 set to 8KHz(included) or below 100Hz
6 220V 25~40HP, 440V 30~75HP, 11-01 set to 8KHz or higher 80Hz

00- 34 / Language — PDF page 141

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 34 Language
2 Range 【0】:English 【1】:Simplified Chinese 【2】:Traditional Chinese 【3】:Turkish

00- 35 / Minumum Frequency Detection — PDF page 141

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 35 Minumum Frequency Detection
2 Range 【0】:Alarm 【1】:Keep Running at Lower Frequency

00- 36 / PID Lower Frequency Selection — PDF page 141

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 36 PID Lower Frequency Selection
2 Range 【0】:Lower Frequency of PID Sleep Mode 【1】:0Hz of PID Sleep Mode

Manual — Group01V/Fpatterns, output-voltage limit and source initialization conditions — page 142

Manual reference: physical PDF page 142. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 01 V/F Control Parameters

➢ Make sure to set the inverter input voltage parameter 01-14 ➢ There are three ways to set V/F curve: (1) 01-00 = 0 to E:Choose any of the 15 predefined curves (0 to E) (2) 01-00 =0F:Use 01-02~01-09 and 01-12~01-13, with voltage limit (3) 01-00 = FF:Use 01-02~01-09 and 01-12~01-13, without voltage limit. Refer to the following figure:

➢ The default parameters (01-02~01-09) are the same when 01-00 is set to F (default) and 01-00

is set to 1.

➢ Parameters 01-02 to 01-13 are automatically set when any of the predefined V/F curves are

selected. Please refer table 4.3.3~4.3.5 for the features of V/F pattern.。

➢ When V/F curves are selected, frequency will be limited by 00-12 and 00-13.

➢ This parameter is not affected by the initialization parameter (13-08)

OutputVoltageLimitCurve:verticalOutputVoltage5V,40V,250V;horizontalOutputFrequency0,01-02/40 (fraction shown),01-02(theoutputfrequencyinthemax.voltage). Source saysvoltagelimitof400Vclassistwotimes. Curve risesfrom5Vthrough40Vto250V; no othernumericalpointsinferred.

Group01V/Fpatterns, output-voltage limit and source initialization conditions

01- 00 / Volts/Hz Patterns — PDF page 142

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01- 00 Volts/Hz Patterns
2 Range 【0~FF】

Manual — Table 4.3.3: 2P5 - 2HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 143

Manual reference: physical PDF page 143. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Plots9/10 lower glyph in stacked6-over0 tick is clipped inside original graphic. Preserve raw visible glyphs without asserting repaired60Hz breakpoint; need unclipped supplier graphic for complete label.

Table 4.3.3 2P5 - 2HP V/F curve selection (200V)

PDF 143 plot 1; Table 4.3.3: 2P5 - 2HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 7.2, 13.5, 200; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 143 plot 2; Table 4.3.3: 2P5 - 2HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 7.2, 13.5, 200; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 143 plot 3; Table 4.3.3: 2P5 - 2HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 7.2, 13.5, 200; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 143 plot 4; Table 4.3.3: 2P5 - 2HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [6.5, 7.2]. At 25 Hz, code (4) lower line is labelled 35 V; code (5) upper line is labelled 50 V. Final voltage label 200 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 143 plot 5; Table 4.3.3: 2P5 - 2HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [6.5, 7.2]. At 30 Hz, code (6) lower line is labelled 35 V; code (7) upper line is labelled 50 V. Final voltage label 200 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 143 plot 6; Table 4.3.3: 2P5 - 2HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 7.3, 7.4; at 2.5 Hz lower code (8) line label 14 V and upper code (9) line label 14.6 V. Final voltage 200 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 143 plot 7; Table 4.3.3: 2P5 - 2HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 7.3, 7.4; at 3 Hz lower code (A) line label 14 V and upper code (B) line label 14.6 V. Final voltage 200 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 143 plot 8; Table 4.3.3: 2P5 - 2HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 7.2, 13.5, 200; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 143 plot 9; Table 4.3.3: 2P5 - 2HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, [stacked 6 over clipped lower glyph], 120]. Printed voltage labels, low to high: 7.2, 13.5, 200; origin 0. Code (D); rising line to the tick printed as stacked 6 over clipped lower glyph, plateau with axis break toward 120 Hz. Raw label layout: stacked 6 over partly clipped lower glyph within original graphic; retain rawlayout.

PDF 143 plot 10; Table 4.3.3: 2P5 - 2HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, [stacked 6 over clipped lower glyph], 180]. Printed voltage labels, low to high: 7.2, 13.5, 200; origin 0. Code (E); rising line to the tick printed as stacked 6 over clipped lower glyph, plateau with axis break toward 180 Hz. Raw label layout: stacked 6 over partly clipped lower glyph within original graphic.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Plots9/10 lower glyph in stacked6-over0 tick is clipped inside original graphic. Preserve raw visible glyphs without asserting repaired60Hz breakpoint; need unclipped supplier graphic for complete label.

Table 4.3.3: 2P5 - 2HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 143

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General purpose 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General purpose 50Hz 50Hz F (50Hz Default setting) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General purpose 60 Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General purpose 60 Hz 60Hz Saturation F (60Hz Default setting.) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General purpose 60 Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz High Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque(Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50 Hz Variable Torque 1 4 ⟦blank source cell⟧ ⟦blank source cell⟧ 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50 Hz Variable Torque 2 5 ⟦blank source cell⟧ ⟦blank source cell⟧ 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60 Hz Variable Torque 3 6 ⟦blank source cell⟧ ⟦blank source cell⟧ 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60 Hz Variable Torque 4 7 ⟦blank source cell⟧ ⟦blank source cell⟧ 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.4: 3 - 30HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 144

Manual reference: physical PDF page 144. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.4 3 - 30HP V/F curve selection (200V)

PDF 144 plot 1; Table 4.3.4: 3 - 30HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 6.8, 12.7, 200; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 144 plot 2; Table 4.3.4: 3 - 30HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 6.8, 12.7, 200; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 144 plot 3; Table 4.3.4: 3 - 30HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 6.8, 12.7, 200; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 144 plot 4; Table 4.3.4: 3 - 30HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [6, 6.8]. At 25 Hz, code (4) lower line is labelled 35 V; code (5) upper line is labelled 50 V. Final voltage label 200 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 144 plot 5; Table 4.3.4: 3 - 30HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [6, 6.8]. At 30 Hz, code (6) lower line is labelled 35 V; code (7) upper line is labelled 50 V. Final voltage label 200 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 144 plot 6; Table 4.3.4: 3 - 30HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 6.9, 7; at 2.5 Hz lower code (8) line label 13.3 V and upper code (9) line label 13.8 V. Final voltage 200 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 144 plot 7; Table 4.3.4: 3 - 30HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 6.9, 7; at 3 Hz lower code (A) line label 13.3 V and upper code (B) line label 13.8 V. Final voltage 200 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 144 plot 8; Table 4.3.4: 3 - 30HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 6.8, 12.7, 200; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 144 plot 9; Table 4.3.4: 3 - 30HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 6.8, 12.7, 200; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 144 plot 10; Table 4.3.4: 3 - 30HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 6.8, 12.7, 200; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.4: 3 - 30HP V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 144

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F (50Hz Default setting) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F (60Hz Default setting.) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz High Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.5: 40HP and above V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 145

Manual reference: physical PDF page 145. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.5 40HP and above V/F curve selection (200V)

PDF 145 plot 1; Table 4.3.5: 40HP and above V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 7.7, 13.6, 200; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 145 plot 2; Table 4.3.5: 40HP and above V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 7.7, 13.6, 200; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 145 plot 3; Table 4.3.5: 40HP and above V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 7.7, 13.6, 200; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 145 plot 4; Table 4.3.5: 40HP and above V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [7.7]. At 25 Hz, code (4) lower line is labelled 36.4 V; code (5) upper line is labelled 52.3 V. Final voltage label 200 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 145 plot 5; Table 4.3.5: 40HP and above V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [7.7]. At 30 Hz, code (6) lower line is labelled 36.4 V; code (7) upper line is labelled 52.3 V. Final voltage label 200 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 145 plot 6; Table 4.3.5: 40HP and above V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 7.7, 8.2; at 2.5 Hz lower code (8) line label 13.9 V and upper code (9) line label 14.5 V. Final voltage 200 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 145 plot 7; Table 4.3.5: 40HP and above V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 7.7, 8.2; at 3 Hz lower code (A) line label 13.9 V and upper code (B) line label 14.5 V. Final voltage 200 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 145 plot 8; Table 4.3.5: 40HP and above V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 7.7, 13.6, 200; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 145 plot 9; Table 4.3.5: 40HP and above V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 7.7, 13.6, 200; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 145 plot 10; Table 4.3.5: 40HP and above V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 7.7, 13.6, 200; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.5: 40HP and above V/F curve selection (200V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 145

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F (50Hz Default setting) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F (60Hz Default setting) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz High Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.6: 2P5 - 2HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 146

Manual reference: physical PDF page 146. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Plots9/10 lower glyph in stacked6-over0 tick is clipped inside original graphic. Plot2 stacked5-over0 is legible and retained as50. Need unclipped supplier graphic for complete9/10label; do not infer.

Table 4.3.6 2P5- 2HP V/F curve selection (220V)

PDF 146 plot 1; Table 4.3.6: 2P5 - 2HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 7.9, 14.8, 220; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 146 plot 2; Table 4.3.6: 2P5 - 2HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 7.9, 14.8, 220; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred. Raw label layout: 50 printed as5 over0.

PDF 146 plot 3; Table 4.3.6: 2P5 - 2HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 7.9, 14.8, 220; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 146 plot 4; Table 4.3.6: 2P5 - 2HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [7.1, 7.9]. At 25 Hz, code (4) lower line is labelled 38.5 V; code (5) upper line is labelled 55 V. Final voltage label 220 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 146 plot 5; Table 4.3.6: 2P5 - 2HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [7.1, 7.9]. At 30 Hz, code (6) lower line is labelled 38.5 V; code (7) upper line is labelled 55 V. Final voltage label 220 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 146 plot 6; Table 4.3.6: 2P5 - 2HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 8, 8.1; at 2.5 Hz lower code (8) line label 15.4 V and upper code (9) line label 16.1 V. Final voltage 220 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 146 plot 7; Table 4.3.6: 2P5 - 2HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 8, 8.1; at 3 Hz lower code (A) line label 15.4 V and upper code (B) line label 16.1 V. Final voltage 220 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 146 plot 8; Table 4.3.6: 2P5 - 2HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 7.9, 14.8, 220; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 146 plot 9; Table 4.3.6: 2P5 - 2HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, [stacked 6 over clipped lower glyph], 120]. Printed voltage labels, low to high: 7.9, 14.8, 220; origin 0. Code (D); rising line to the tick printed as stacked 6 over clipped lower glyph, plateau with axis break toward 120 Hz. Raw label layout: stacked 6 over partly clipped lower glyph within original graphic.

PDF 146 plot 10; Table 4.3.6: 2P5 - 2HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, [stacked 6 over clipped lower glyph], 180]. Printed voltage labels, low to high: 7.9, 14.8, 220; origin 0. Code (E); rising line to the tick printed as stacked 6 over clipped lower glyph, plateau with axis break toward 180 Hz. Raw label layout: stacked 6 over partly clipped lower glyph within original graphic.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Plots9/10 lower glyph in stacked6-over0 tick is clipped inside original graphic. Plot2 stacked5-over0 is legible and retained as50. Need unclipped supplier graphic for complete9/10label; do not infer.

Table 4.3.6: 2P5 - 2HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 146

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.7: 3 - 30HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 147

Manual reference: physical PDF page 147. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.7 3 - 30HP V/F curve selection (220V)

PDF 147 plot 1; Table 4.3.7: 3 - 30HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 7.5, 14, 220; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 147 plot 2; Table 4.3.7: 3 - 30HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 7.5, 14, 220; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 147 plot 3; Table 4.3.7: 3 - 30HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 7.5, 14, 220; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 147 plot 4; Table 4.3.7: 3 - 30HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [6.6, 7.5]. At 25 Hz, code (4) lower line is labelled 38.5 V; code (5) upper line is labelled 55 V. Final voltage label 220 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 147 plot 5; Table 4.3.7: 3 - 30HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [6.6, 7.5]. At 30 Hz, code (6) lower line is labelled 38.5 V; code (7) upper line is labelled 55 V. Final voltage label 220 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 147 plot 6; Table 4.3.7: 3 - 30HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 7.6, 7.7; at 2.5 Hz lower code (8) line label 14.6 V and upper code (9) line label 15.2 V. Final voltage 220 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 147 plot 7; Table 4.3.7: 3 - 30HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 7.6, 7.7; at 3 Hz lower code (A) line label 14.6 V and upper code (B) line label 15.2 V. Final voltage 220 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 147 plot 8; Table 4.3.7: 3 - 30HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 7.5, 14, 220; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 147 plot 9; Table 4.3.7: 3 - 30HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 7.5, 14, 220; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 147 plot 10; Table 4.3.7: 3 - 30HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 7.5, 14, 220; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.7: 3 - 30HP V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 147

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A (Hz) 220 0 (V) (B) 60 1.5 3 (A) 15.2 14.6 7.7 7.6
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A (Hz) 220 0 (V) (B) 60 1.5 3 (A) 15.2 14.6 7.7 7.6
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B (Hz) 220 0 (V) (B) 60 1.5 3 (A) 15.2 14.6 7.7 7.6
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.8: 40HP and above V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 148

Manual reference: physical PDF page 148. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.8 40HP and above V/F curve selection (220V)

PDF 148 plot 1; Table 4.3.8: 40HP and above V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 8.5, 15, 220; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 148 plot 2; Table 4.3.8: 40HP and above V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 8.5, 15, 220; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 148 plot 3; Table 4.3.8: 40HP and above V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 8.5, 15, 220; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 148 plot 4; Table 4.3.8: 40HP and above V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [8.5]. At 25 Hz, code (4) lower line is labelled 40 V; code (5) upper line is labelled 57.5 V. Final voltage label 220 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 148 plot 5; Table 4.3.8: 40HP and above V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [8.5]. At 30 Hz, code (6) lower line is labelled 40 V; code (7) upper line is labelled 57.5 V. Final voltage label 220 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 148 plot 6; Table 4.3.8: 40HP and above V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 8.5, 9; at 2.5 Hz lower code (8) line label 15.3 V and upper code (9) line label 16 V. Final voltage 220 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 148 plot 7; Table 4.3.8: 40HP and above V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 8.5, 9; at 3 Hz lower code (A) line label 15.3 V and upper code (B) line label 16 V. Final voltage 220 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 148 plot 8; Table 4.3.8: 40HP and above V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 8.5, 15, 220; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 148 plot 9; Table 4.3.8: 40HP and above V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 8.5, 15, 220; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 148 plot 10; Table 4.3.8: 40HP and above V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 8.5, 15, 220; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.8: 40HP and above V/F curve selection (220V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 148

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.9: 2P5 - 2HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 149

Manual reference: physical PDF page 149. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Plot5 horizontal unit is visibly clipped as(H… inside original image, confirmed by expanded-source crop. Numeric ticks retained without inventing missing unit characters; need unclipped source.

Table 4.3.9 2P5 - 2HP V/F curve selection (230V)

PDF 149 plot 1; Table 4.3.9: 2P5 - 2HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 8.3, 15.5, 230; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 149 plot 2; Table 4.3.9: 2P5 - 2HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 8.3, 15.5, 230; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 149 plot 3; Table 4.3.9: 2P5 - 2HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 8.3, 15.5, 230; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 149 plot 4; Table 4.3.9: 2P5 - 2HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [7.4, 8.3]. At 25 Hz, code (4) lower line is labelled 40.3 V; code (5) upper line is labelled 57.5 V. Final voltage label 230 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 149 plot 5; Table 4.3.9: 2P5 - 2HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit clipped as (H…; missing characters not inferred. Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [7.4, 8.3]. At 30 on the horizontal axis, code (6) lower line is labelled 40.3 V; code (7) upper line is labelled 57.5 V. Final voltage label 230 V; endpoint 60 on the horizontal axis. No extra low voltage value inferred where only one label printed. Expanded-source crop confirms original graphic clips the horizontal unit; it is not a crop-tool artifact.

PDF 149 plot 6; Table 4.3.9: 2P5 - 2HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 8.4, 8.5; at 2.5 Hz lower code (8) line label 16.1 V and upper code (9) line label 16.8 V. Final voltage 230 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 149 plot 7; Table 4.3.9: 2P5 - 2HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 8.4, 8.5; at 3 Hz lower code (A) line label 16.1 V and upper code (B) line label 16.8 V. Final voltage 230 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 149 plot 8; Table 4.3.9: 2P5 - 2HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 8.3, 15.5, 230; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 149 plot 9; Table 4.3.9: 2P5 - 2HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 8.3, 15.5, 230; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 149 plot 10; Table 4.3.9: 2P5 - 2HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 8.3, 15.5, 230; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Plot5 horizontal unit is visibly clipped as(H… inside original image, confirmed by expanded-source crop. Numeric ticks retained without inventing missing unit characters; need unclipped source.

Table 4.3.9: 2P5 - 2HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 149

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 (Hz) 230 60 01.5 (V) (2) (1),(F) 50 8.3 3 15.5 ⟦blank source cell⟧ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) (Hz) 230 60 01.5 (V) (2) (1),(F) 50 8.3 3 15.5 ⟦blank source cell⟧ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 (Hz) 230 60 01.5 (V) (2) (1),(F) 50 8.3 3 15.5 ⟦blank source cell⟧ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 (Hz) 72 0 (V) (3) 60 1.5 3 8.3 15.5 230 Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D (Hz) 230 120 0 (V) (D) 60 1.5 8.3 3 15.5
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D (Hz) 230 120 0 (V) (D) 60 1.5 8.3 3 15.5
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E (Hz) 230 180 0 (V) (E) 60 1.5 8.3 3 15.5
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E (Hz) 230 180 0 (V) (E) 60 1.5 8.3 3 15.5

Manual — Table 4.3.10: 3 - 30HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 150

Manual reference: physical PDF page 150. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.10 3 - 30HP V/F curve selection (230V)

PDF 150 plot 1; Table 4.3.10: 3 - 30HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 7.8, 14.6, 230; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 150 plot 2; Table 4.3.10: 3 - 30HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 7.8, 14.6, 230; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 150 plot 3; Table 4.3.10: 3 - 30HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 7.8, 14.6, 230; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 150 plot 4; Table 4.3.10: 3 - 30HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [6.9, 7.8]. At 25 Hz, code (4) lower line is labelled 40.3 V; code (5) upper line is labelled 57.5 V. Final voltage label 230 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 150 plot 5; Table 4.3.10: 3 - 30HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [6.9, 7.8]. At 30 Hz, code (6) lower line is labelled 40.3 V; code (7) upper line is labelled 57.5 V. Final voltage label 230 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 150 plot 6; Table 4.3.10: 3 - 30HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 7.9, 8.1; at 2.5 Hz lower code (8) line label 15.3 V and upper code (9) line label 15.9 V. Final voltage 230 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 150 plot 7; Table 4.3.10: 3 - 30HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 7.9, 8.7; at 3 Hz lower code (A) line label 15.3 V and upper code (B) line label 15.9 V. Final voltage 230 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 150 plot 8; Table 4.3.10: 3 - 30HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 7.8, 14.6, 230; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 150 plot 9; Table 4.3.10: 3 - 30HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 7.8, 14.6, 230; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 150 plot 10; Table 4.3.10: 3 - 30HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 7.8, 14.6, 230; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.10: 3 - 30HP V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Adjacent source context — repeated to preserve continuation:

Type / Specification / 01-00 / V/F curve — PDF page 150

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 (Hz) 0 (V) (5) 50 1.3 25 (4) 230 6.9 7.8 57.5 40.3 Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 (Hz) 0 (V) (5) 50 1.3 25 (4) 230 6.9 7.8 57.5 40.3 Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.11: 40HP and above V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 151

Manual reference: physical PDF page 151. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.11 40HP and above V/F curve selection (230V)

PDF 151 plot 1; Table 4.3.11: 40HP and above V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 8.9, 15.7, 230; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 151 plot 2; Table 4.3.11: 40HP and above V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 8.9, 15.7, 230; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 151 plot 3; Table 4.3.11: 40HP and above V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 8.9, 15.7, 230; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 151 plot 4; Table 4.3.11: 40HP and above V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [8.9]. At 25 Hz, code (4) lower line is labelled 41.8 V; code (5) upper line is labelled 60.1 V. Final voltage label 230 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 151 plot 5; Table 4.3.11: 40HP and above V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [8.9]. At 30 Hz, code (6) lower line is labelled 41.8 V; code (7) upper line is labelled 60.1 V. Final voltage label 230 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 151 plot 6; Table 4.3.11: 40HP and above V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 8.9, 9.4; at 2.5 Hz lower code (8) line label 16 V and upper code (9) line label 16.7 V. Final voltage 230 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 151 plot 7; Table 4.3.11: 40HP and above V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 8.9, 9.4; at 3 Hz lower code (A) line label 16 V and upper code (B) line label 16.7 V. Final voltage 230 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 151 plot 8; Table 4.3.11: 40HP and above V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 8.9, 15.7, 230; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 151 plot 9; Table 4.3.11: 40HP and above V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 8.9, 15.7, 230; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 151 plot 10; Table 4.3.11: 40HP and above V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 8.9, 15.7, 230; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.11: 40HP and above V/F curve selection (230V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Adjacent source context — repeated to preserve continuation:

Type / Specification / 01-00 / V/F curve — PDF page 151

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.12: 2P5 - 2HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 152

Manual reference: physical PDF page 152. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Tbale 4.3.12 2P5 - 2HP V/F curve selection (380V)

PDF 152 plot 1; Table 4.3.12: 2P5 - 2HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 13.6, 25.6, 380; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 152 plot 2; Table 4.3.12: 2P5 - 2HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 13.6, 25.6, 380; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 152 plot 3; Table 4.3.12: 2P5 - 2HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 13.6, 25.6, 380; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 152 plot 4; Table 4.3.12: 2P5 - 2HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [12.3, 13.6]. At 25 Hz, code (4) lower line is labelled 66.5 V; code (5) upper line is labelled 95 V. Final voltage label 380 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 152 plot 5; Table 4.3.12: 2P5 - 2HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [12.3, 13.6]. At 30 Hz, code (6) lower line is labelled 66.5 V; code (7) upper line is labelled 95 V. Final voltage label 380 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 152 plot 6; Table 4.3.12: 2P5 - 2HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 13.8, 14; at 2.5 Hz lower code (8) line label 26.6 V and upper code (9) line label 27.8 V. Final voltage 380 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 152 plot 7; Table 4.3.12: 2P5 - 2HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 13.8, 14; at 3 Hz lower code (A) line label 26.6 V and upper code (B) line label 27.8 V. Final voltage 380 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 152 plot 8; Table 4.3.12: 2P5 - 2HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 13.6, 25.6, 380; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 152 plot 9; Table 4.3.12: 2P5 - 2HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 13.6, 25.6, 380; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 152 plot 10; Table 4.3.12: 2P5 - 2HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 13.6, 25.6, 380; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.12: 2P5 - 2HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 152

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.13: 3 - 30HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 153

Manual reference: physical PDF page 153. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.13 3 - 30HP V/F curve selection (380V)

PDF 153 plot 1; Table 4.3.13: 3 - 30HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 13, 24.2, 380; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 153 plot 2; Table 4.3.13: 3 - 30HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 13, 24.2, 380; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 153 plot 3; Table 4.3.13: 3 - 30HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 13, 24.2, 380; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 153 plot 4; Table 4.3.13: 3 - 30HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [11.4, 13]. At 25 Hz, code (4) lower line is labelled 66.5 V; code (5) upper line is labelled 95 V. Final voltage label 380 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 153 plot 5; Table 4.3.13: 3 - 30HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [11.4, 13]. At 30 Hz, code (6) lower line is labelled 66.5 V; code (7) upper line is labelled 95 V. Final voltage label 380 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 153 plot 6; Table 4.3.13: 3 - 30HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 13.1, 13.3; at 2.5 Hz lower code (8) line label 25.2 V and upper code (9) line label 26.3 V. Final voltage 380 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 153 plot 7; Table 4.3.13: 3 - 30HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 13.1, 13.3; at 3 Hz lower code (A) line label 25.2 V and upper code (B) line label 26.3 V. Final voltage 380 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 153 plot 8; Table 4.3.13: 3 - 30HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 13, 24.2, 380; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 153 plot 9; Table 4.3.13: 3 - 30HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 13, 24.2, 380; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 153 plot 10; Table 4.3.13: 3 - 30HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 13, 24.2, 380; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.13: 3 - 30HP V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 153

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 (Hz) 0 (V) (5) 50 1.3 25 (4) 380 11.4 13 95 66.5 Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 (Hz) 0 (V) (5) 50 1.3 25 (4) 380 11.4 13 95 66.5 Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.14: 40HP and above V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 154

Manual reference: physical PDF page 154. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.14 40HP and above V/F curve selection (380V)

PDF 154 plot 1; Table 4.3.14: 40HP and above V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 14.7, 25.9, 380; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 154 plot 2; Table 4.3.14: 40HP and above V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 14.7, 25.9, 380; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 154 plot 3; Table 4.3.14: 40HP and above V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 14.7, 25.9, 380; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 154 plot 4; Table 4.3.14: 40HP and above V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [14.7]. At 25 Hz, code (4) lower line is labelled 69.1 V; code (5) upper line is labelled 99.3 V. Final voltage label 380 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 154 plot 5; Table 4.3.14: 40HP and above V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [14.7]. At 30 Hz, code (6) lower line is labelled 69.1 V; code (7) upper line is labelled 99.3 V. Final voltage label 380 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 154 plot 6; Table 4.3.14: 40HP and above V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 14.7, 15.5; at 2.5 Hz lower code (8) line label 26.4 V and upper code (9) line label 27.6 V. Final voltage 380 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 154 plot 7; Table 4.3.14: 40HP and above V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 14.7, 15.5; at 3 Hz lower code (A) line label 26.4 V and upper code (B) line label 27.6 V. Final voltage 380 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 154 plot 8; Table 4.3.14: 40HP and above V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 14.7, 25.9, 380; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 154 plot 9; Table 4.3.14: 40HP and above V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 14.7, 25.9, 380; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 154 plot 10; Table 4.3.14: 40HP and above V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 14.7, 25.9, 380; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.14: 40HP and above V/F curve selection (380V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 154

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.15: 1 - 2HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 155

Manual reference: physical PDF page 155. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.15 1 - 2HP V/F curve selection (400V)

PDF 155 plot 1; Table 4.3.15: 1 - 2HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 14.4, 26.9, 400; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 155 plot 2; Table 4.3.15: 1 - 2HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 14.4, 26.9, 400; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 155 plot 3; Table 4.3.15: 1 - 2HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 14.4, 26.9, 400; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 155 plot 4; Table 4.3.15: 1 - 2HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [12.9, 14.4]. At 25 Hz, code (4) lower line is labelled 70 V; code (5) upper line is labelled 100 V. Final voltage label 400 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 155 plot 5; Table 4.3.15: 1 - 2HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [12.9, 14.4]. At 30 Hz, code (6) lower line is labelled 70 V; code (7) upper line is labelled 100 V. Final voltage label 400 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 155 plot 6; Table 4.3.15: 1 - 2HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 14.5, 14.7; at 2.5 Hz lower code (8) line label 28 V and upper code (9) line label 29.3 V. Final voltage 400 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 155 plot 7; Table 4.3.15: 1 - 2HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 14.5, 14.7; at 3 Hz lower code (A) line label 28 V and upper code (B) line label 29.3 V. Final voltage 400 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 155 plot 8; Table 4.3.15: 1 - 2HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 14.4, 26.9, 400; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 155 plot 9; Table 4.3.15: 1 - 2HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 14.4, 26.9, 400; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 155 plot 10; Table 4.3.15: 1 - 2HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 14.4, 26.9, 400; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.15: 1 - 2HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 155

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.16: 3 - 30HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 156

Manual reference: physical PDF page 156. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.16 3 - 30HP V/F curve selection (400V)

PDF 156 plot 1; Table 4.3.16: 3 - 30HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 13.6, 25.5, 400; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 156 plot 2; Table 4.3.16: 3 - 30HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 13.6, 25.5, 400; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 156 plot 3; Table 4.3.16: 3 - 30HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 13.6, 25.5, 400; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 156 plot 4; Table 4.3.16: 3 - 30HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [12, 13.6]. At 25 Hz, code (4) lower line is labelled 70 V; code (5) upper line is labelled 100 V. Final voltage label 400 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 156 plot 5; Table 4.3.16: 3 - 30HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [12, 13.6]. At 30 Hz, code (6) lower line is labelled 70 V; code (7) upper line is labelled 100 V. Final voltage label 400 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 156 plot 6; Table 4.3.16: 3 - 30HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 13.8, 14; at 2.5 Hz lower code (8) line label 26.5 V and upper code (9) line label 27.6 V. Final voltage 400 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 156 plot 7; Table 4.3.16: 3 - 30HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 13.8, 14; at 3 Hz lower code (A) line label 26.5 V and upper code (B) line label 27.6 V. Final voltage 400 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 156 plot 8; Table 4.3.16: 3 - 30HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 13.6, 25.5, 400; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 156 plot 9; Table 4.3.16: 3 - 30HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 13.6, 25.5, 400; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 156 plot 10; Table 4.3.16: 3 - 30HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 13.6, 25.5, 400; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.16: 3 - 30HP V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 156

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ ⟦blank source cell⟧ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 (Hz) 0 (V) (5) 50 1.3 25 (4) 400 12 13.6 100 70 Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 (Hz) 0 (V) (5) 50 1.3 25 (4) 400 12 13.6 100 70 Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.17: 40HP and above V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 157

Manual reference: physical PDF page 157. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.17 40HP and above V/F curve selection (400V)

PDF 157 plot 1; Table 4.3.17: 40HP and above V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 15.5, 27.3, 400; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 157 plot 2; Table 4.3.17: 40HP and above V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 15.5, 27.3, 400; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 157 plot 3; Table 4.3.17: 40HP and above V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 15.5, 27.3, 400; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 157 plot 4; Table 4.3.17: 40HP and above V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [15.5]. At 25 Hz, code (4) lower line is labelled 72.7 V; code (5) upper line is labelled 104.5 V. Final voltage label 400 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 157 plot 5; Table 4.3.17: 40HP and above V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [15.5]. At 30 Hz, code (6) lower line is labelled 72.7 V; code (7) upper line is labelled 104.5 V. Final voltage label 400 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 157 plot 6; Table 4.3.17: 40HP and above V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 15.5, 16.4; at 2.5 Hz lower code (8) line label 27.8 V and upper code (9) line label 29.1 V. Final voltage 400 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 157 plot 7; Table 4.3.17: 40HP and above V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 15.5, 16.4; at 3 Hz lower code (A) line label 27.8 V and upper code (B) line label 29.1 V. Final voltage 400 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 157 plot 8; Table 4.3.17: 40HP and above V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 15.5, 27.3, 400; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 157 plot 9; Table 4.3.17: 40HP and above V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 15.5, 27.3, 400; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 157 plot 10; Table 4.3.17: 40HP and above V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 15.5, 27.3, 400; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.17: 40HP and above V/F curve selection (400V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 157

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.18: 1 - 2HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 158

Manual reference: physical PDF page 158. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.18 1 - 2HP V/F curve selection (415V)

PDF 158 plot 1; Table 4.3.18: 1 - 2HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 14.9, 27.9, 415; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 158 plot 2; Table 4.3.18: 1 - 2HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 14.9, 27.9, 415; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 158 plot 3; Table 4.3.18: 1 - 2HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 14.9, 27.9, 415; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 158 plot 4; Table 4.3.18: 1 - 2HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [13.4, 14.9]. At 25 Hz, code (4) lower line is labelled 72.6 V; code (5) upper line is labelled 103.8 V. Final voltage label 415 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 158 plot 5; Table 4.3.18: 1 - 2HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [13.4, 14.9]. At 30 Hz, code (6) lower line is labelled 72.6 V; code (7) upper line is labelled 103.8 V. Final voltage label 415 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 158 plot 6; Table 4.3.18: 1 - 2HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 15.1, 15.3; at 2.5 Hz lower code (8) line label 29.1 V and upper code (9) line label 30.4 V. Final voltage 415 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 158 plot 7; Table 4.3.18: 1 - 2HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 15.1, 15.3; at 3 Hz lower code (A) line label 29.1 V and upper code (B) line label 30.4 V. Final voltage 415 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 158 plot 8; Table 4.3.18: 1 - 2HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 14.9, 27.9, 415; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 158 plot 9; Table 4.3.18: 1 - 2HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 14.9, 27.9, 415; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 158 plot 10; Table 4.3.18: 1 - 2HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 14.9, 27.9, 415; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.18: 1 - 2HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 158

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.19: 3 - 30HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 159

Manual reference: physical PDF page 159. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.19 3 - 30HP V/F curve selection (415V)

PDF 159 plot 1; Table 4.3.19: 3 - 30HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 14.1, 26.4, 415; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 159 plot 2; Table 4.3.19: 3 - 30HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 14.1, 26.4, 415; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 159 plot 3; Table 4.3.19: 3 - 30HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 14.1, 26.4, 415; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 159 plot 4; Table 4.3.19: 3 - 30HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [12.5, 14.1]. At 25 Hz, code (4) lower line is labelled 72.6 V; code (5) upper line is labelled 103.8 V. Final voltage label 415 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 159 plot 5; Table 4.3.19: 3 - 30HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [12.5, 14.1]. At 30 Hz, code (6) lower line is labelled 72.6 V; code (7) upper line is labelled 103.8 V. Final voltage label 415 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 159 plot 6; Table 4.3.19: 3 - 30HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 14.3, 14.5; at 2.5 Hz lower code (8) line label 27.5 V and upper code (9) line label 28.7 V. Final voltage 415 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 159 plot 7; Table 4.3.19: 3 - 30HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 14.3, 14.5; at 3 Hz lower code (A) line label 27.5 V and upper code (B) line label 28.7 V. Final voltage 415 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 159 plot 8; Table 4.3.19: 3 - 30HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 14.1, 26.4, 415; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 159 plot 9; Table 4.3.19: 3 - 30HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 14.1, 26.4, 415; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 159 plot 10; Table 4.3.19: 3 - 30HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 14.1, 26.4, 415; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.19: 3 - 30HP V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 159

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 (Hz) 0 (V) (5) 50 1.3 25 (4) 415 12.5 14.1 103.8 72.6 Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 (Hz) 0 (V) (5) 50 1.3 25 (4) 415 12.5 14.1 103.8 72.6 Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.20: 40HP and above V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 160

Manual reference: physical PDF page 160. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.20 40HP and above V/F curve selection (415V)

PDF 160 plot 1; Table 4.3.20: 40HP and above V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 16, 28.3, 415; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 160 plot 2; Table 4.3.20: 40HP and above V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 16, 28.3, 415; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 160 plot 3; Table 4.3.20: 40HP and above V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 16, 28.3, 415; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 160 plot 4; Table 4.3.20: 40HP and above V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [16]. At 25 Hz, code (4) lower line is labelled 75.5 V; code (5) upper line is labelled 108.5 V. Final voltage label 415 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 160 plot 5; Table 4.3.20: 40HP and above V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [16]. At 30 Hz, code (6) lower line is labelled 75.5 V; code (7) upper line is labelled 108.5 V. Final voltage label 415 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 160 plot 6; Table 4.3.20: 40HP and above V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 16, 17; at 2.5 Hz lower code (8) line label 28.9 V and upper code (9) line label 30.2 V. Final voltage 415 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 160 plot 7; Table 4.3.20: 40HP and above V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 16, 17; at 3 Hz lower code (A) line label 28.9 V and upper code (B) line label 30.2 V. Final voltage 415 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 160 plot 8; Table 4.3.20: 40HP and above V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 16, 28.3, 415; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 160 plot 9; Table 4.3.20: 40HP and above V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 16, 28.3, 415; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 160 plot 10; Table 4.3.20: 40HP and above V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 16, 28.3, 415; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.20: 40HP and above V/F curve selection (415V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 160

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.21: 1 - 2HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 161

Manual reference: physical PDF page 161. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.21 1 - 2HP V/F curve selection (440V)

PDF 161 plot 1; Table 4.3.21: 1 - 2HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 15.8, 29.6, 440; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 161 plot 2; Table 4.3.21: 1 - 2HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 15.8, 29.6, 440; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 161 plot 3; Table 4.3.21: 1 - 2HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 15.8, 29.6, 440; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 161 plot 4; Table 4.3.21: 1 - 2HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [14.2, 15.8]. At 25 Hz, code (4) lower line is labelled 77 V; code (5) upper line is labelled 110 V. Final voltage label 440 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 161 plot 5; Table 4.3.21: 1 - 2HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [14.2, 15.8]. At 30 Hz, code (6) lower line is labelled 77 V; code (7) upper line is labelled 110 V. Final voltage label 440 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 161 plot 6; Table 4.3.21: 1 - 2HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 16, 16.2; at 2.5 Hz lower code (8) line label 30.8 V and upper code (9) line label 32.2 V. Final voltage 440 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 161 plot 7; Table 4.3.21: 1 - 2HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 16, 16.2; at 3 Hz lower code (A) line label 30.8 V and upper code (B) line label 32.2 V. Final voltage 440 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 161 plot 8; Table 4.3.21: 1 - 2HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 15.8, 29.6, 440; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 161 plot 9; Table 4.3.21: 1 - 2HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 15.8, 29.6, 440; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 161 plot 10; Table 4.3.21: 1 - 2HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 15.8, 29.6, 440; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.21: 1 - 2HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 161

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.22: 3 - 30HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 162

Manual reference: physical PDF page 162. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.22 3 - 30HP V/F curve selection (440V)

PDF 162 plot 1; Table 4.3.22: 3 - 30HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 15, 28, 440; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 162 plot 2; Table 4.3.22: 3 - 30HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 15, 28, 440; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 162 plot 3; Table 4.3.22: 3 - 30HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 15, 28, 440; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 162 plot 4; Table 4.3.22: 3 - 30HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [13.2, 15]. At 25 Hz, code (4) lower line is labelled 77 V; code (5) upper line is labelled 110 V. Final voltage label 440 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 162 plot 5; Table 4.3.22: 3 - 30HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [13.2, 15]. At 30 Hz, code (6) lower line is labelled 77 V; code (7) upper line is labelled 110 V. Final voltage label 440 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 162 plot 6; Table 4.3.22: 3 - 30HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 15.2, 15.4; at 2.5 Hz lower code (8) line label 29.2 V and upper code (9) line label 30.4 V. Final voltage 440 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 162 plot 7; Table 4.3.22: 3 - 30HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 15.2, 15.4; at 3 Hz lower code (A) line label 29.2 V and upper code (B) line label 30.4 V. Final voltage 440 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 162 plot 8; Table 4.3.22: 3 - 30HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 15, 28, 440; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 162 plot 9; Table 4.3.22: 3 - 30HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 15, 28, 440; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 162 plot 10; Table 4.3.22: 3 - 30HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 15, 28, 440; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.22: 3 - 30HP V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 162

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 (Hz) 0 (V) (5) 50 1.3 25 (4) 440 13.2 15 110 77 Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 (Hz) 0 (V) (5) 50 1.3 25 (4) 440 13.2 15 110 77 Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.23: 40HP and above V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 163

Manual reference: physical PDF page 163. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.23 40HP and above V/F curve selection (440V)

PDF 163 plot 1; Table 4.3.23: 40HP and above V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 17, 30, 440; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 163 plot 2; Table 4.3.23: 40HP and above V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 17, 30, 440; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 163 plot 3; Table 4.3.23: 40HP and above V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 17, 30, 440; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 163 plot 4; Table 4.3.23: 40HP and above V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [17]. At 25 Hz, code (4) lower line is labelled 80 V; code (5) upper line is labelled 115 V. Final voltage label 440 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 163 plot 5; Table 4.3.23: 40HP and above V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [17]. At 30 Hz, code (6) lower line is labelled 80 V; code (7) upper line is labelled 115 V. Final voltage label 440 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 163 plot 6; Table 4.3.23: 40HP and above V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 17, 18; at 2.5 Hz lower code (8) line label 30.6 V and upper code (9) line label 32 V. Final voltage 440 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 163 plot 7; Table 4.3.23: 40HP and above V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 17, 18; at 3 Hz lower code (A) line label 30.6 V and upper code (B) line label 32 V. Final voltage 440 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 163 plot 8; Table 4.3.23: 40HP and above V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 17, 30, 440; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 163 plot 9; Table 4.3.23: 40HP and above V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 17, 30, 440; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 163 plot 10; Table 4.3.23: 40HP and above V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 17, 30, 440; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.23: 40HP and above V/F curve selection (440V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 163

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.24: 1 - 2HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 164

Manual reference: physical PDF page 164. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.24 1 - 2HP V/F curve selection (460V)

PDF 164 plot 1; Table 4.3.24: 1 - 2HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 16.5, 30.9, 460; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 164 plot 2; Table 4.3.24: 1 - 2HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 16.5, 30.9, 460; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 164 plot 3; Table 4.3.24: 1 - 2HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 16.5, 30.9, 460; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 164 plot 4; Table 4.3.24: 1 - 2HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [14.8, 16.5]. At 25 Hz, code (4) lower line is labelled 80.5 V; code (5) upper line is labelled 115 V. Final voltage label 460 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 164 plot 5; Table 4.3.24: 1 - 2HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [14.8, 16.5]. At 30 Hz, code (6) lower line is labelled 80.5 V; code (7) upper line is labelled 115 V. Final voltage label 460 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 164 plot 6; Table 4.3.24: 1 - 2HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 16.7, 16.9; at 2.5 Hz lower code (8) line label 32.2 V and upper code (9) line label 33.7 V. Final voltage 460 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 164 plot 7; Table 4.3.24: 1 - 2HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 16.7, 16.9; at 3 Hz lower code (A) line label 32.2 V and upper code (B) line label 33.7 V. Final voltage 460 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 164 plot 8; Table 4.3.24: 1 - 2HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 16.5, 30.9, 460; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 164 plot 9; Table 4.3.24: 1 - 2HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 16.5, 30.9, 460; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 164 plot 10; Table 4.3.24: 1 - 2HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 16.5, 30.9, 460; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.24: 1 - 2HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 164

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.25: 3 - 30HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 165

Manual reference: physical PDF page 165. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.25 3 - 30HP V/F curve selection (460V)

PDF 165 plot 1; Table 4.3.25: 3 - 30HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 15.7, 29.3, 460; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 165 plot 2; Table 4.3.25: 3 - 30HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 15.7, 29.3, 460; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 165 plot 3; Table 4.3.25: 3 - 30HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 15.7, 29.3, 460; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 165 plot 4; Table 4.3.25: 3 - 30HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [13.8, 15.7]. At 25 Hz, code (4) lower line is labelled 80.5 V; code (5) upper line is labelled 115 V. Final voltage label 460 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 165 plot 5; Table 4.3.25: 3 - 30HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [13.8, 15.7]. At 30 Hz, code (6) lower line is labelled 80.5 V; code (7) upper line is labelled 115 V. Final voltage label 460 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 165 plot 6; Table 4.3.25: 3 - 30HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 15.9, 16.1; at 2.5 Hz lower code (8) line label 30.5 V and upper code (9) line label 31.8 V. Final voltage 460 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 165 plot 7; Table 4.3.25: 3 - 30HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 15.9, 16.1; at 3 Hz lower code (A) line label 30.5 V and upper code (B) line label 31.8 V. Final voltage 460 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 165 plot 8; Table 4.3.25: 3 - 30HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 15.7, 29.3, 460; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 165 plot 9; Table 4.3.25: 3 - 30HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 15.7, 29.3, 460; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 165 plot 10; Table 4.3.25: 3 - 30HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 15.7, 29.3, 460; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.25: 3 - 30HP V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 165

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 (Hz) 0 (V) (5) 50 1.3 25 (4) 460 13.8 15.7 115 80.5 Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 (Hz) 0 (V) (5) 50 1.3 25 (4) 460 13.8 15.7 115 80.5 Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Table 4.3.26: 40HP and above V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. — page 166

Manual reference: physical PDF page 166. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.26 40HP and above V/F curve selection (460V)

PDF 166 plot 1; Table 4.3.26: 40HP and above V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 0, F(50Hz). Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed voltage labels, low to high: 17.8, 31.4, 460; origin 0. Codes (0),(F) appear on the same rising line; 50 Hz endpoint.

PDF 166 plot 2; Table 4.3.26: 40HP and above V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 1, F(60Hz), 2. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 50, 60]. Printed voltage labels, low to high: 17.8, 31.4, 460; origin 0. Code (2) reaches the plateau at 50 Hz; codes (1),(F) reach at 60 Hz; no intermediate values inferred.

PDF 166 plot 3; Table 4.3.26: 40HP and above V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 3. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 72]. Printed voltage labels, low to high: 17.8, 31.4, 460; origin 0. Code (3); rising line to 60 Hz, plateau ending at 72 Hz.

PDF 166 plot 4; Table 4.3.26: 40HP and above V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 4, 5. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 25, 50]. Printed low voltage labels: [17.8]. At 25 Hz, code (4) lower line is labelled 83.6 V; code (5) upper line is labelled 120.2 V. Final voltage label 460 V; endpoint 50 Hz. No extra low voltage value inferred where only one label printed.

PDF 166 plot 5; Table 4.3.26: 40HP and above V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 6, 7. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 30, 60]. Printed low voltage labels: [17.8]. At 30 Hz, code (6) lower line is labelled 83.6 V; code (7) upper line is labelled 120.2 V. Final voltage label 460 V; endpoint 60 Hz. No extra low voltage value inferred where only one label printed.

PDF 166 plot 6; Table 4.3.26: 40HP and above V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options 8, 9. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.3, 2.5, 50]. Printed low voltage labels 17.8, 18.8; at 2.5 Hz lower code (8) line label 32 V and upper code (9) line label 33.5 V. Final voltage 460 V at 50 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 166 plot 7; Table 4.3.26: 40HP and above V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options A, B. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60]. Printed low voltage labels 17.8, 18.8; at 3 Hz lower code (A) line label 32 V and upper code (B) line label 33.5 V. Final voltage 460 V at 60 Hz. Row specifications remain literal, including where B is described Low Starting Torque.

PDF 166 plot 8; Table 4.3.26: 40HP and above V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options C. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 90]. Printed voltage labels, low to high: 17.8, 31.4, 460; origin 0. Code (C); rising line to 60 Hz, plateau ending at 90 Hz.

PDF 166 plot 9; Table 4.3.26: 40HP and above V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options D. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 120]. Printed voltage labels, low to high: 17.8, 31.4, 460; origin 0. Code (D); rising line to 60 Hz, plateau with axis break toward 120 Hz.

PDF 166 plot 10; Table 4.3.26: 40HP and above V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Options E. Vertical unit (V); horizontal unit (Hz). Printed x-axis labels: [0, 1.5, 3, 60, 180]. Printed voltage labels, low to high: 17.8, 31.4, 460; origin 0. Code (E); rising line to 60 Hz, plateau with axis break toward 180 Hz.

Table 4.3.26: 40HP and above V/F curve selection (460V). Parameter 01-00 selection codes; source table and plotted label values preserved separately. No unlabelled curve point interpolated. Columns5and10 contain plot artwork. Empty native cells do not mean missing curves: separately bounded plot records preserve visible labels. Raw native graphic text remains unordered evidence; use accompanying visual plot record for associations.

Type / Specification / 01-00 / V/F curve — PDF page 166

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Type Specification Specification 01-00 V/F curve Type Specification Specification 01-00 V/F curve
2 General application 50Hz 50Hz 0 ⟦blank source cell⟧ High Staring Torque‡ 50Hz Low Starting Torque 8 ⟦blank source cell⟧
3 General application 50Hz 50Hz F ( 50Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 50Hz High Starting Torque 9 ⟦blank source cell⟧
4 General application 60Hz 60Hz Saturation 1 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
5 General application 60Hz 60Hz Saturation F ( 60Hz Default setting ) ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque A ⟦blank source cell⟧
6 General application 60Hz 50Hz Saturation 2 ⟦blank source cell⟧ High Staring Torque‡ 60Hz Low Starting Torque B ⟦blank source cell⟧
7 Variable Torque Characteristic 72Hz 72Hz 3 ⟦blank source cell⟧ Constant-power torque (Reducer) 90Hz 90Hz C ⟦blank source cell⟧
8 Variable Torque Characteristic 50Hz Variable Torque 1 4 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
9 Variable Torque Characteristic 50Hz Variable Torque 2 5 ⟦blank source cell⟧ Constant-power torque (Reducer) 120Hz 120Hz D ⟦blank source cell⟧
10 Variable Torque Characteristic 60Hz Variable Torque 3 6 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧
11 Variable Torque Characteristic 60Hz Variable Torque 4 7 ⟦blank source cell⟧ Constant-power torque (Reducer) 180Hz 180Hz E ⟦blank source cell⟧

Manual — Motor1 custom V/F settings and strict frequency ordering; graph continues168 — page 167

Manual reference: physical PDF page 167. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

V/F curve setting (01-02~01-09 and 01-12~01-13) ➢ Select any of the predefined V/F curves setting 0 to E that best matches your application and the load characteristic of your motor, choose a custom curve setting F or FF to set a custom curve. ➢ When setting the frequency related parameters for a custom V/F curve values make sure as follows, the SE03 V/F curve tuning error is displayed when the frequency values are set incorrectly. (01-02) (01-12) (01-04) (01-06) (01-08)

➢ When 01-04 and 01-05 (or 01-18 and 01-19) are set to 0, the inverter ignores the set

values of Fmin2 and Vmin2

➢ The voltage values for 01-02~01-09 are irrelevant.

➢ The value for maximum output voltage of motor 1(01-03) and the value for base output voltage

of motor 1(01-13) will depend on restore factory setting(13-08) to set the value of voltage.

➢ When the control mode is changed parameter 00-00, 01-08 (Fmin) and 01-09 (Vmin) will

automatically be changed to the default setting of the selected control mode.

➢ Custom V/F Curve Setting.

Custom V/F frequency-order inequality: Fmax(01-02) > Fbase(01-12) > Fmid2(01-04) > Fmid1(01-06) > Fmin(01-08). Source calls01-02Basefrequency in table butFmax here;retainboth.

Motor1 custom V/F settings and strict frequency ordering; graph continues168

01- 02 / Base frequency of motor 1 — PDF page 167

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01- 02 Base frequency of motor 1
2 Range 【4.8~599.0】Hz
3 01- 03 Maximum output voltage of motor 1
4 Range 200V:【0.1~255.0】V 400V:【0.2~510.0】V
5 01- 04 Middle output frequency 2 of motor 1
6 Range 【0.0~599.0】Hz
7 01- 05 Middle output voltage 2 of motor 1
8 Range 200V:【0.0~255.0】V 400V:【0.0~510.0】V
9 01- 06 Middle output frequency 1 of motor 1
10 Range 【0.0~599.0】Hz
11 01- 07 Middle output voltage 1 of motor 1
12 Range 200V:【0.0~255.0】V 400V:【0.0~510.0】V
13 01- 08 Minimum output frequency of motor 1
14 Range 【0.0~599.0】Hz
15 01- 09 Minimum output voltage of the motor 1
16 Range 200V:【0.0~255.0】V 400V:【0.0~510.0】V
17 01- 12 Base frequency of motor 1
18 Range 【4.8~599.0】Hz
19 01- 13 Base output voltage of motor 1
20 Range 200V:【0.0~255.0】V 400V:【0.0~510.0】V

Manual — Custom V/F graph, cooling conditions andSLV tuning; literal contradictory voltage discussion preserved — page 168

Manual reference: physical PDF page 168. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ For low torque or high speed applications, the motor may overheat. Make sure to provide

adequate cooling when operating the motor under these conditions for a longer period of time

➢ If the automatic torque boost function is enabled (parameter 01-10), the applied motor voltage

will automatically change to provide adequate motor torque during start or operating at low

frequency. SLV Mode (Sensorless Vector Control) In the SV and SLV mode the V/F curve normally does not have to be re-adjusted after a successful

auto-tune.

➢ The maximum output frequency setting 01-02 (Fmax), base frequency 01-12 (Fbase), minimum

output frequency 01-08 (Fmin), maximum output voltage 01-03 (Vmax) or base output voltage

01-13 (Vbase) can be adjusted but the voltage is automatically adjusted by the internal current

controller.

➢ Perform the auto-tuning procedure after adjusting parameters 02-19 or 17-04 to

reduce the voltage at no-load operation.

➢ Motor jitter can be reduced by lowering the no-load voltage. Please note that lowering the no-

load voltage increases the current at no-load.

➢ Set the base frequency (01-12, Fbase) to the motor rated frequency on the motor nameplate.

Figure4.3.12CustomV/Fcurve. VerticalOutputVoltage(V):Vmin01-09,Vmid1 01-07,Vmid2 01-05,Vmax01-03,Vbase01-13. HorizontalOutputFrequency(Hz):Fmin01-08,Fmid1 01-06,Fmid2 01-04,Fbase01-12,Fmax01-02. Rising plotted segments join labellednodes;Vmax/Vbase shareupperlevel thenplateautoFmax. No numeric points or interpolation inferred.

Figure4.3.13TorqueBoosting. VerticalOutputVoltage(V):Vmin,Vmid1,Vmid2,Vmax. Horizontal:Fmin01-08,Fmid1 01-06,Fmid2 01-04,Fbase01-12,Fmax01-02. Solidcurve risesfromVminatFmin toVmid2atFmid1,drops toVmid1atFmid2,risestoVmaxatFbase thenplateau. Dashedreference ramps retained byimage;no unlabelledvalueinferred.

Manual — Torque compensation gain/mode and input-voltage reference — page 169

Manual reference: physical PDF page 169. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Torque compensation gain (01-10)

➢ In V/F mode the inverter automatically adjusts the output voltage to adjust the output torque

during start or during load changes based on the calculated loss of motor voltage.

➢ Torque compensation gain (01-10) can adjust in the running time. No need to adjust in general

except the following:

 If the wire between inverter and motor is too long, add the value of 01-10

 If the capacity of motor is smaller than inverter, add the value of 01-10.

 If the motor vibrates, reduce the value of 01-10

➢ Refer to the torque compensation gain adjustment shown in Figure 4.3.14.

Selection of Torque compensation mode (01-11)

➢ Torque compensation mode 0 is the general mode.

➢ Torque Compensation Mode 1 is the high speed mode (120~160Hz) and the compensation

amount decreases as the increasing frequency. When the speed is at 0~120Hz, the

compensation amount is the same as that in torque compensation mode 0.

Figure 4.3.14 Torque compensation gain to increase/decrease output torque

➢ The minimum input voltage of inverter is 0.1V.

➢ Set the input voltage (200V/208V/230V/240V or 380V/415V/440V/460V/480V).

➢ This parameter is used as a reference for predefined V/F curve calculation (01-00=0 to E),

over-voltage protection level, stall prevention, etc…

➢ If the setting value of 01-14 is lower than actual input voltage, the value of output voltage

(12-19) and output power (12-21) on display will incorrect.

Note:

It will depend on restore factory setting (13-08) to set the value of voltage.

Figure4.3.14torquecompensationgain. AxesOutputVoltage/ Basefrequency;100%uppervoltagemark;three risinglineslabelled01-10,upwardTorqueIncreasearrow,left;downwardTorqueDecreasearrow,right. No numericgain implied.

Torque compensation gain/mode and input-voltage reference

01-10 / Torque compensation gain — PDF page 169

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01-10 Torque compensation gain
2 Range 【0.0~2.0】
3 01-11 Selection of Torque Compensation Mode
4 Range 0:Mode 0 1:Mode 1

01-14 / Input voltage setting — PDF page 169

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01-14 Input voltage setting
2 Range 200V:【155.0~255.0】V 400V:【310.0~510.0】V

Manual — Motor2 V/F parameters;source explicitly shares Motor1 curve settings — page 170

Manual reference: physical PDF page 170. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Set the torque compensation delay time in milliseconds.

➢ Only adjust in the following situations:

①. Increase the value when experiencing motor vibration.

②. Decrease the value when motor torque response is too slow.

Note 1:Motor 2 V/F curve uses the same settings as motor 1.

Note 2:Motor 2 V/F curve is the same as Motor 1, please refer to Table 4.4.3~26P

Note 3:Parameter 01-16~01-25 will be changed when the value of 01-26 is changed.

Motor2 V/F parameters;source explicitly shares Motor1 curve settings

01-15 / Torque compensation time — PDF page 170

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01-15 Torque compensation time
2 Range 【0~10000】ms

01- 16 / Maximum output frequency of motor 2 — PDF page 170

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01- 16 Maximum output frequency of motor 2
2 Range 【4.8~599.0】Hz
3 01- 17 Maximum output voltage of motor 2
4 Range 200V:【0.1~255.0】V 400V:【0.2~510.0】V
5 01- 18 Middle output frequency 2 of motor 2
6 Range 【0.0~599.0】Hz
7 01- 19 Middle output voltage 2 of motor 2
8 Range 200V:【0.0~255.0】V 400V:【0.0~510.0】V
9 01- 20 Middle output frequency 1 of motor 2
10 Range 【0.0~599.0】Hz
11 01- 21 Middle output voltage 1 of motor 2
12 Range 200V:【0.0~255.0】V 400V:【0.0~510.0】V
13 01- 22 Minimum output frequency of motor 2
14 Range 【0.0~599.0】Hz
15 01-23 Minimum output voltage of motor 2
16 Range 200V:【0.0~255.0】V 400V:【0.0~510.0】V
17 01- 24 Base frequency of motor 2
18 Range 【4.8~599.0】Hz
19 01- 25 Base voltage of motor 2
20 Range 200V:【0.0~255.0】V 400V:【0.0~510.0】V
21 01- 26 V/F Curve Selection of Motor 2
22 Range 【0~FF】

Manual — Group02 IM motor parameters;no-load/rated current,voltage,power,core coefficients — page 171

Manual reference: physical PDF page 171. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Source <1> qualifiers on excitation/core coefficients have no identified definition in native text across the manual. Preserve qualifier without inferring applicability.

Group 02 IM Motor Parameters

Motor parameters are automatically set when performing an auto-tune (17-10=1). In most

case no adjustment is required after performing an auto-tune except when using the

inverter in special applications (e.g. machine tool, positioning, etc…).

Please refer to parameter group 22 for permanent magnet motor parameters.

➢ Motor no-load current (02-00).

Value is calculated based on the motor rated frequency (17-05) and motor rated current (17-03).

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Source <1> qualifiers on excitation/core coefficients have no identified definition in native text across the manual. Preserve qualifier without inferring applicability.

Group02 IM motor parameters;no-load/rated current,voltage,power,core coefficients

02- 00 / No-load current of motor 1 — PDF page 171

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02- 00 No-load current of motor 1
2 Range 【0.01~600.00】A
3 02- 01 Rated current of motor 1
4 Range Lower limit: 10% rated current of V/F mode, 25% rated current of SLV mode Upper limit: According to inverter’s rated current
5 02-03 Rated rotation speed of motor1
6 Range 【0~60000】rpm
7 02- 04 Rated voltage of motor1
8 Range 200V:【50.0~240.0】V 400V:【100.0~480.0】V
9 02- 05 Rated voltage of motor1
10 Range 【0.01~600.00】KW
11 02-06 Rated frequency of motor 1
12 Range 【4.8~599.0】Hz
13 02-07 Pole of motor 1
14 Range 【2~16】
15 02-09 Excitation current of motor 1 <1>
16 Range 【15~70】% motor rated current
17 02-10 Core saturation coefficient 1 of motor 1 <1>
18 Range 【1~100】%
19 02-11 Core saturation coefficient 2 of motor 1 <1>
20 Range 【1~100】%
21 02-12 Core saturation coefficient 3 of motor 1 <1>
22 Range 【80~300】%
23 02-13 Core loss of motor 1
24 Range 【0.0~15.0】%
25 02-19 No-Load Voltage of motor 1
26 Range 200V:【50~240】V 400V:【100~480】V

Manual — Nameplate motor settings and excitation/core tuning procedure continuation — page 172

Manual reference: physical PDF page 172. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Motor rated current (02-01)

Set the motor rated current according to the motor nameplate.

(1) The value of 02-01 needs to be greater than the value set in parameter 02-00, otherwise

warning message "SE01" out of range error will be displayed.

(2) In V/F control mode, slip compensation function will be active whn output current is greater

than motor no load current.

(3) In V / F control mode, the output current is greater than the no-load current with slip

compensation is enabled.

➢ Rated rotation speed of motor 1 (02-03)

Set the motor rpm according to the motor nameplate.

➢ Motor rated voltage (02-04)

Set the motor rated voltage according to the motor nameplate.

Set the motor rated voltage and it will adjust maximum output voltage of V/F curve.

➢ Motor rated power (02-05)

Set the motor power according to the motor nameplate.

➢ Rated frequency of motor 1 (02-06)

Set the motor rated frequency according to the motor nameplate.

➢ Number of motor poles (02-07)

Set the number of motor pole according to the motor nameplate.

➢ Motor excitation current (02-09)

(1) The current is obtained from rotational auto-tuning. It is required to perform manual tuning if

the inverter cannot rotational auto-tune.

(2) When the manual tuning is performed, tune it from 33% and observe no-load voltage (the

output value) of parameter 12-67. If parameter 12-67 is higher than no-load voltage (the

setting value) of parameter 17-08, perform downward revision in parameter 02-09; if it is lower

than that, perform upward revision in parameter 02-09.

(3) Tuning motor excitation current of parameter 02-09 will change motor leakage inductance of

parameter 02-17 and motor mutual inductance of parameter 02-18.

(4) It is required to refer to the actual no-load voltage of parameter 12-76 to tune the motor

excitation current of parameter 02-09. Change of the excitation current will also affect the

relative actual no-load voltage fluctuation so it is required to tune to the similar setting value of

no-load voltage (17-08).

➢ Setting of motor core’s saturation coefficient 1, 2 and 3 (02-10, 02-11, 02-12)

These parameters are automatically set during auto-tune. No adjustment required. Parameters are

set to 50% for 02-10, 75% for 02-11 and 137.5% for 02-12 to reduce the impact of core saturation.

The motor core’s saturation coefficient is defined as a percentage of the motor excitation current.

When the motor flux reaches 137.5% level, the core’s saturation coefficient shall be greater than

137.5%. When the motor flux is 50% or 75%, the core’s saturation coefficient is required to be less

than 50% and 75%.

Manual — Core saturation graph/core-loss formula and Motor1/Motor2 parameter tables — page 173

Manual reference: physical PDF page 173. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: 02-17 name/range conflict,02-19 voltage/A conflict and<1> definition remain source-boundary questions.

➢ Motor core loss (02-13)

Set motor core loss as the percentage of the motor rated power

Note:In V/F mode motor core loss (o2-13) is used to for torque compensation.

Core saturation plot:horizontalFlux marks50%,75%,100%,137.5%;verticalKs1Im,Ks2Im,Im,Ks3*Im atrespective labellednodes. LegendIm=02-09ExcitationCurrent;Ks1=02-10MotorCoreSaturationCoefficients1;Ks2=02-11...2;Ks3=02-12...3. No unlabelledinterpolation.

%Wcore(02-13) = [3 x Motor core loss(Watt) x 100%] / [Motor rated power(Watt,02-05)]. Exact displayed source fraction; no engineering formula validation.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: 02-15/16/17 unit absent; <1> qualifier definition not identified. 02-19 voltage label/ampere range conflict retained.

Core saturation graph/core-loss formula and Motor1/Motor2 parameter tables

02-15 / Resistance between wires of motor 1 — PDF page 173

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02-15 Resistance between wires of motor 1
2 Range 1~60.000
3 02-16 Rotor resistance gain
4 Range 1~60.000
5 02-17 Resistance between wires of motor <1>
6 Range 1~60.000
7 02- 19 No-Load Voltage of motor 1
8 Range 【0.01~600.00】A
9 02- 20 No-Load Current of motor 2
10 Range 【0.01~600.00】A
11 02- 21 Rated current of motor 2
12 Range 10%~200% of inverter rated current
13 02-22 Rated rotation speed of motor 2
14 Range 【0~60000】rpm
15 02- 23 Rated voltage of motor 2
16 Range 200V:【50.0~240.0】V 400V:【100.0~480.0】V
17 02- 24 Rated power of motor 2
18 Range 【0.01~600.00】KW
19 02-25 Rated frequency of motor 2
20 Range 【4.8~599.0】Hz
21 02-26 Pole of motor 2
22 Range 【2~16】
23 02-32 Resistance between wires of motor 2
24 Range 【0.001~60.000】Ω
25 02-33 Proportion of Motor Leakage Inductance <1>
26 Range 【0.1~15.0】%

Manual — Induction-motor equivalent model,no-load voltage,leakage proportion andslip example — page 174

Manual reference: physical PDF page 174. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Source <1> qualifiers on leakage/slip lack identified definition; retain literal formulas and statements, no applicability inferred.

➢ Motor line to line resistance (02-15)

Refer to figure 4.3.15, Y-equivalent model an induction motor

➢ No-load motor voltage (02-19)

Parameter determines the rated flux during motor rated rotation in SLV control mode. Set the value

of this parameter to the same value as parameter 17-08. A value of 10~50V below the input voltage

level ensures that the motor is capable of providing adequate torque performance when operating

at nominal speed (or higher speed). Setting the value to small can result in a reduction in no-load

current, weakened motor flux and an increase in motor current while the motor is loaded.

➢ Proportion of Motor Leakage Inductance <1> (02-33)

(1) It is set by manual tuning function. Normally, it does not need to be adjusted because magnetic

function does not exist in this adjustment.

(2) Definition of leakage inductance proportion is the ratio of leakage inductance to rotor

inductance. If the default value is set to 3.4%, adjust this ratio will affect the motor leakage

inductance parameter to be changed.

(3) When the adjustment of leakage inductance proportion is larger or smaller, it will cause the

motor jittering with abnormal noise and the motor cannot run. Generally, the adjusted value is

3.0%~5.0%. 4.0% is the universal adjustment value that can make the motor run normally. The

adjustment of leakage inductance proportion depends on the motor rating.

(1) Normally, it is not required to be adjusted. It can be obtained via manual tuning parameter f

unction. Such tuning does not have magnetic function.

(2) The default value of motor slip is set to 1 Hz. Motor slip is obtained from the nameplate.

Take 60Hz, 4-pole motor for example, synchronous speed:

Figure4.3.15Y-equivalentmodel aninductionmotor. LabelsR1,Llkg,Iq,Id,Lm,R2/s,s:slip. Circuit graphic retained;no inferred winding/wiring topology.

Leakageinductanceproportion formula ξ = LlKg / Lr. Exactsourceglyph/formula;symboldefinitionlimitedtosourceprose.

Sourceexample60Hz4-polemotor: N = (120 x Frequency)/Pole = (120 x 60)/4 = 1800rpm. Displayed arithmetic retained; continuation175uses1700rpm.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Source <1> qualifiers on leakage/slip lack identified definition; retain literal formulas and statements, no applicability inferred.

Induction-motor equivalent model,no-load voltage,leakage proportion andslip example

02-34 / Motor Slip <1> — PDF page 174

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02-34 Motor Slip <1>
2 Range 【0.1~20.0】Hz

Manual — Motor slip example continuation;Group02 update byGroup17auto-tune — page 175

Manual reference: physical PDF page 175. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Rated speed in the nameplate is 1700 rpm, then

(3) Adjusting motor slip will change the rotor resistance parameter. The motor slip is adjusted

depending on the motor performance.

(4) When inverter is performing auto-tune successful, the parameters of group 2 will be updated

by group 17, please refer to group 17 for the details.

Sourceexamplecontinuation:Slip = (1800 - 1700)/60 = 1.67 Hz. Exactsourceformula,not engineering validation;parentexample174 specifies60Hz4pole.

Manual — Group03 digital inputs S1–S6 and shared function option list — page 176

Manual reference: physical PDF page 176. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 03 External Digital Input and Output Parameters

Refer to the multi-function digital input and parameters in the following figure 4.3.16

Group03 digital inputs S1–S6 and shared function option list

03- 00 / Multi-function input terminal S1 — PDF page 176

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 00 Multi-function input terminal S1
2 03- 01 Multi-function input terminal S2
3 03- 02 Multi-function input terminal S3
4 03- 03 Multi-function input terminal S4
5 03- 04 Multi-function input terminal S5
6 03- 05 Multi-function input terminal S6
7 Range 【0】: Forward/Stop command 【1】: Reverse/Stop command 【2】: Multi-speed/position setting command 0 【3】: Multi-speed/position setting command 1 【4】: Multi-speed/position setting command 2 【5】: Multi-speed/position setting command 3 【6】: Forward jog run command 【7】: Reverse jog run command 【8】: UP frequency increasing command 【9】: DOWN frequency decreasing command 【10】: Acceleration/deceleration time selection 2 【11】: Inhibit Acceleration/deceleration command 【12】: Main/ Alternative Run Switch Function 【13】: Main/ Alternative Frequency Switch Function 【14】: Emergency Stop (decelerate to zero and stop) 【15】: External Baseblock Command(rotation freely to stop) 【16】: PID control disable 【17】: Fault reset (Reset) 【18】: Auto Run Mode Enable 【19】: Speed Search (ffrom the maximum frequency) 【20】: Energy Saving (V/F mode only) 【21】: Reset PID Integral Value to Zero 【22】: Counter Input 【23】: Counter Reset 【24】: PLC Input 【25】: Pulse-In Width Measure(S3) 【26】: Pulse-In Frequency Measure (S3) 【27】: Local/Remote Selection 【28】: Remote Mode Selection 【29】: Jog Frequency Selection 【33】: DC Braking 【34】: Speed Search 2 (From The Frequency Command) 【40】: Switching Between Motor 1/Motor 2 【41】: PID Sleep 【47】: Fire Mode (S6 terminal only) 【48】: KEB Acceleration 【57】: Forced Frequency Run 【63】: Switch to Constant Pressure 2 【65】: Short-Circuit Breaking 【66】: PID Control Disable 2 【68】: External Fault 【69】: External Overload

Manual — Digital input terminal diagram and function/mode table options0–14;continues178–179 — page 177

Manual reference: physical PDF page 177. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.16 Multi-function digital input and related parameters

Table 4.3.27 Multi-function digital input setting ( 03-00 to 03-05 ) (“O”:Enable, “X”:Disable)

Figure4.3.16multifunctiondigitalinputandrelatedparameters. PrintedpairsS1 03-00,S2 03-01,S3 03-02,S4 03-03,S5 03-04,S6 03-05;common24VG. Switchsymbols retainedbysourceimage;no topology inferred.

Digital input terminal diagram and function/mode table options0–14;continues178–179

Value / Function / Description / Control Mode — PDF page 177

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Value Function Function Description Control Mode Control Mode Control Mode
2 Value Name LCD Display Description V/F SLV PM SLV
3 0 Forward/Stop command 2-Wire (FWD-RUN) 2- wire Forward/Stop command (ON:Forward operation command). O O O
4 1 Reverse/Stop command 2-Wire (REV-RUN) 2- wire Reverse/Stop command (ON:Reverse operation command). O O O
5 2 Multi-speed/position setting command 0 Muti-Spd/Pos Ref 0 Multi-Speed Reference / Position Reference 0 O O O
6 3 Multi-speed/position setting command 1 Muti-Spd/Pos Ref 1 Multi-Speed Reference /Position Reference 1 O O O
7 4 Multi-speed/position setting command 2 Muti-Spd/Pos Ref 2 Multi-Speed Reference /Position Reference 2 O O O
8 5 Multi-speed/position setting command 3 Muti-Spd/Pos Ref 3 Multi-Speed Reference /Position Reference 3 O O O
9 6 Forward jog run command FJOG ON:Forward operation in jog mode (00- 18). O O O
10 7 Reverse jog run command RJOG ON:Reverse operation in jog mode (00- 18). O O O
11 8 UP frequency increasing command UP command ON:Command of output frequency increasing (only used by support of DOWN command). O O O
12 9 DOWN frequency decreasing command DOWN command ON:Command of output frequency decreasing (only used by support of UP command). O O O
13 10 Acceleration/decelerati on time selection 2 Acc/Decel Time Selection 1 Acceleration/deceleration time selection command 1 O O O
14 11 Inhibit Acceleration /deceleration command ACC/DEC Inhibit ON:Acceleration/ deceleration prohibition O O O
15 12 Main/ Alternative Run Switch Function Run Change Sel Run Command Source is set in parameter of alternative frequency command (00- 03) O O O
16 13 Main/ Alternative Frequency Switch Function Freq Change Sel Frequency Command Source is set in parameter of alternative frequency command (00-06) O O O
17 14 Emergency Stop (decelerate to zero and stop) E-Stop ON:Emergency stop input O O O

Manual — Digital input function/mode continuation15–45 — page 178

Manual reference: physical PDF page 178. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Digital input function/mode continuation15–45

Value / Function / Description / Control Mode — PDF page 178

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Value Function Function Description Control Mode Control Mode Control Mode
2 Value Name LCD Display Description V/F SLV PM SLV
3 15 External Baseblock Command (rotation freely to stop) Ext. BB ON:Inverter base interdiction O O O
4 16 PID control disable PID Disable ON:PID control disabled O O O
5 17 Fault reset (Reset) Fault Reset Fault reset O O O
6 18 Auto Run Mode Enable ⟦blank source cell⟧ ON:Auto run mode enable(06-00) - - -
7 19 Speed Search (from the maximum frequency) Speed Search 1 ON:Search the speed from the maximum output frequency O O X
8 20 Energy Saving Energy saving ON:Manual energy saving control is based on the settings of 11-12 and 11-18. O X X
9 21 Reset PID Integral Value to Zero PID I-Reset ON:PID integral reset O O O
10 22 Counter Input Cnt Input ON:Counter input by digital input O O O
11 23 Counter Reset Cnt Reset ON:Counter reset by digital input O O O
12 24 PLC Input PLC Input ON:PLC input O O O
13 25 Pulse-In Width Measure (S3) Pulse Input-Width Measure ON:Switch S3 to pulse-in width measure O O O
14 26 Pulse-In Frequency Measure (S3) Pulse Input-Freqency Measure ON:Switch S3 to pulse-infrequency measure O O O
15 27 Local/Remote Selection Local/Remote ON:Local mode (via the digital operator) OFF:Frequency command and operation command will be determined according to the setting of parameter (00-02 and 00-05). O O O
16 28 Remote Mode Selection Remote Mode Sel ON:RS-485 communication OFF:Control circuit terminal O O O
17 29 Jog Frequency Selection JOG Freq sel ON:RS-485 communication O O O
18 30 Reserved Reserved Reserved - - -
19 31 Reserved Reserved Reserved - - -
20 32 Reserved Reserved Reserved - - -
21 33 DC Braking DC Brake Command ON:Perform DC braking O O O
22 34 Speed Search 2 (From The Frequency Command) Speed Search 2 ON:Search speed from set frequency O O X
23 35 Reserved Reserved Reserved - - -
24 36 Reserved Reserved Reserved - - -
25 37 Reserved Reserved Reserved - - -
26 38 Reserved Reserved Reserved - - -
27 39 Reserved Reserved Reserved - - -
28 40 Switching Between Motor 1/Motor 2 Motor 2 Switch ON:Start motor 2 O O X
29 41 PID Sleep PID Sleep ON: PID sleep function enabled O O O
30 42 Reserved Reserved Reserved - - -
31 43 Reserved Reserved Reserved - - -
32 44 Reserved Reserved Reserved - - -
33 45 Reserved Reserved Reserved - - -

Manual — Digital input function/mode continuation46–69 and speed selection prose — page 179

Manual reference: physical PDF page 179. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Options 66–69 have physically blank V/F, SLV and PMSLV cells; option 66 description is only ON:. PDF189 also gives PID Control Disable 2 (03-0X=66) as a heading with no explanatory body. PDF189 gives separate 68/69 instructions, not control-mode applicability. Keep all blanks and do not copy applicability from adjacent options.

(1) 2-wire control forward operation (03-0X=00)

(2) 2-wire control: reverse operation (03-0X=01)

(3) Multi-speed/position setting command 1 (03-0X=02)

(4) Multi-speed/position setting command 2 (03-0X=03)

(5) Multi-speed/position setting command 3 (03-0X=04)

(6) Multi-speed/position setting command 4 (03-0X=05)

(7) Jog frequency selection, select frequency

reference using the multi-function digital

input.

(03-0X=29)

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Options66–69 control mode cells are blank; option66 description only ON:. No applicability or missing operation filled.

Digital input function/mode continuation46–69 and speed selection prose

Value / Function / Description / Control Mode — PDF page 179

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Value Function Function Description Control Mode Control Mode Control Mode
2 Value Name LCD Display Description V/F SLV PM SLV
3 46 Reserved Reserved Reserved - - -
4 47 Fire Mode Fire Mode ON:Based on max frequency of 01-02 (Fire mode will be stopped by hardware protection such as OC, SC, STO…) O O O
5 48 KEB Acceleration KEB Accel. ON:KEB acceleration start O O O
6 49 Reserved Reserved Reserved - - -
7 50 Reserved Reserved Reserved - - -
8 51 Reserved Reserved Reserved - - -
9 52 Reserved Reserved Reserved - - -
10 53 Reserved Reserved Reserved - - -
11 54 Reserved Reserved Reserved - - -
12 55 Reserved Reserved Reserved - - -
13 56 Reserved Reserved Reserved - - -
14 57 Forced Frequency Run Forced Frequency Run ON:Forced Frequency Run Enable O X X
15 58 Reserved Reserved Reserved - - -
16 59 Reserved Reserved Reserved - - -
17 60 Reserved Reserved Reserved - - -
18 61 Reserved Reserved Reserved - - -
19 62 Reserved Reserved Reserved - - -
20 63 Switch to Tolerance Range of Constant Pressure 2 Switch to Tolerance Range of Constant Pressure 2 Reserved O O O
21 64 Reserved Reserved Reserved - - -
22 65 Short-Circuit Breaking SC Brk ON:Short-Circuit Breaking turn on X X O
23 66 PID Control Disable 2 PID Control Disable 2 ON: ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
24 67 Reserve Reserve Reserve ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
25 68 External Fault External Fault ON:External Fault Input ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
26 69 External Overload External Overload ON:External Overload Input ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Multi-speed binary selection table and footnotes;wiring/timingcontinues181 — page 180

Manual reference: physical PDF page 180. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Multi-function input header 4 has no local definition; footnotes 1–3 retained.

Figure 4.3.28 Multi-speed operation selection

“0”:OFF, “1”:ON, “-“:Ignore

*1: Jog frequency terminal has a higher priority than multi-speed reference 1 to 4.

*2: When parameter 00-05=0 (frequency reference input = digital operator), multi-speed

frequency 1 will be set by 05-01 frequency reference setting1). When parameter 00-05=2

(frequency reference input=control circuit terminal), multi-speed frequency command 1 is

input through analog command terminal AI1 or AI2).

*3: Multi-speed operation is disabled when PID is enabled.

Wiring Example: Figure 4.3.17 and 4.3.18 is the example of a 9 speed operation selection

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Multi-function input header 4 has no local definition; footnotes 1–3 retained.

Multi-speed binary selection table and footnotes;wiring/timingcontinues181

Speed / Multi-function digital input (S1 to S6)*4 / Frequency selection — PDF page 180

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Speed Multi-function digital input (S1 to S6)*4 Multi-function digital input (S1 to S6)*4 Multi-function digital input (S1 to S6)*4 Multi-function digital input (S1 to S6)*4 Multi-function digital input (S1 to S6)*4 Frequency selection
2 Speed Jog frequency reference Multi- speed frequency 3 Multi- speed frequency 2 Multi- speed frequency 1 Multi- speed frequency 0 Frequency selection
3 1 0 0 0 0 0 Frequency command 0( 05-01) or main speed frequency *2
4 2 0 0 0 0 1 frequency reference 1 ( 05-02) *3
5 3 0 0 0 1 0 Frequency command 2 ( 05-03)
6 4 0 0 0 1 1 Frequency command 3 ( 05-04)
7 5 0 0 1 0 0 Frequency command 4 ( 05-05)
8 6 0 0 1 0 1 Frequency command 5 ( 05-06)
9 7 0 0 1 1 0 Frequency command 6 ( 05-07)
10 8 0 0 1 1 1 Frequency command 7 ( 05-08)
11 9 0 1 0 0 0 Frequency command 8 ( 05-09)
12 10 0 1 0 0 1 Frequency command 9 ( 05-10)
13 11 0 1 0 1 0 Frequency command 10( 05-11)
14 12 0 1 0 1 1 Frequency command 11 ( 05-12)
15 13 0 1 1 0 0 Frequency command 12 ( 05-13)
16 14 0 1 1 0 1 Frequency command 13( 05-14)
17 15 0 1 1 1 0 Frequency command 14 ( 05-15)
18 16 0 1 1 1 1 Frequency command 15 ( 05-16)
19 17 1*1 ─ ─ ─ ─ Jog frequency command (00-18)

Manual — Multi-speed wiring and9speed timing diagrams;forward/reverse jog conditions — page 181

Manual reference: physical PDF page 181. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Timing plot *2 aux speed ref lacks local footnote explanation; conflicting terminal labels retained.

Figure 4.3.17 Control Terminal Wiring Example

*1:When 00-05=2, multi-speed frequency reference is set by analog input AI1 or AI2.

When 00-05=0, multi-speed frequency reference is set by 05-01.

(8) Forward jog run command (03-0X=06)

(9) Reverse jog run command (03-0X=07)

 Jog command has a higher priority than other frequency reference commands.

 Jog command uses stop mode set in parameter 07-09 when Jog command is active > 500ms

(10) 03-0X =08:UP frequency command

Figure4.3.17ControlTerminalWiringExample labels:S1ForwardRUN/STOP(03-00=0);S2ReverseRUN/STOP(03-01=1);S3ExternalFault(03-02=25);S4FaultReset(03-03=17);S5Multi-stepSpeedRef1(03-04=2);S6Multi-stepSpeedRef2(03-05=3);24VG. Literalcaptiononly;S3=25conflictswithsourceoptiontable,not corrected.

Figure4.3.18 9-speedtimingdiagram:FrequencyReferencevs t. Speed1..8 corresponding05-01,05-02,05-03,05-04,05-05,05-06,05-07,05-08;speed9 00-18jog. Initialrampmarker1master speed ref,2auxspeedref. Forwardrun(S1)highthroughspeeds1..9. Three Multi-StepSpeedRef1 traceslabelledS2,S3,S4: S2bits0,1,0,1,0,1,0,1,0;S3bits0,0,1,1,0,0,1,1,0;S4bits0,0,0,0,1,1,1,1,0. JOGFrequencyRef(S5)highonlyspeed9(label1). Wiringexampleaboveusesdifferentterminalassignments;no reconciliation inferred. Source *2meaningnotexplained bylocalfootnote.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Timing plot *2 aux speed ref lacks local footnote explanation; conflicting terminal labels retained.

Manual — UP/DOWN input settings,SE02conditions andsource truth table — page 182

Manual reference: physical PDF page 182. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(11) 03-0X =09:Down frequency command

➢ Inverter can use digital operator and external digital input (S1~S6) to increase or decrease

output frequency while motor is running.

➢ When inverter uses external digital input to perform UP/DOWN, set 00-02=4, 00-05=4

and 03-00~03-05=8 and 9, it requires both UP and DOWN functions 08 and 09 to be

programmed to the two digital input terminals.

➢ UP/DOWN frequency command follows standard acceleration and deceleration times

➢ “SE02” DI terminal error will be displayed when:

①. When only the UP or DOWN command function is programmed to the digital inputs.

②. When both DOWN command and Inhibit Acceleration/deceleration command are activated

simultaneously

③. When both UP command and Inhibit Acceleration/deceleration command are activated

simultaneously.

➢ For the examples of UP/DOWN control wiring and operation, please refer to figure 4.3.19 and

figure 4.3.20。

Figure4.3.19UP/DOWNandoperationexample. WiringlabelsS1ForwardRun/Stop(03-00=0),S5UPcommand(03-04=8),S6DOWNcommand(03-05=9),24VG. Rastertableliteral columns:UPCommand(TerminalS5):0|1|0|1;DOWNCommand(TerminalS6):1|0|0|1;Operation:Accel(UP)|Decel(DWN)|Hold|Hold. Legend0OFF,1ON. Table appears reversed versusnamedcommands andtiming183;retainexactsource,not operational recommendation.

Manual — UP/DOWN timing,limits,ramps andinhibit function continuation — page 183

Manual reference: physical PDF page 183. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Timing plot 1/2 markers are undefined locally; all trace labels and source states retained.

➢ When the Forward Run command is active and the UP or Down command is momentarily

activated the inverter will accelerate the motor up to the lower limit of the frequency reference

(00-13).

➢ When using the UP / Down command, the output frequency is limited to the upper limit of

frequency reference (00-12) and the lower limit of frequency reference (00-13).

➢ The UP / DOWN command uses acceleration 1 or 2 / deceleration time 1 or 2 for normal

operation Tacc1 / Tdec1 (00-14, 00-15) or Tacc2 / Tdec 2 (00-16, 00-17).

➢ The other applications of UP / Down function, please refer 03-06 (UP/DOWN frequency step).

(12) Acceleration/deceleration 1 selection (03-0X=10)

➢ Refer to the "multi-function digital input terminals select acceleration / deceleration time” .

(13) Inhibit Acceleration/deceleration command (03-0X=11)

➢ Operation of inhibit Acceleration/deceleration function, please refer figure 4.3.21。

➢ The frequency reference value is saved when the acceleration/deceleration inhibit command is

active, the frequency reference value is saved even when powering down the inverter.

Figure4.3.20Up/Downcommandtiming. TracesPowerSupply,ForwardRun,UpCommand,DownCommand,OutputFrequency. LimitsFUL(00-12),FLL(00-13);upperhorizontalmarker1atintermediateheldlevel,lower2atFLL. Upaloneincreases;simultaneousUp/Downhold;neitherhold;Downalonedecelerates. ForwardRunofframpsdown;briefsupplylossthenrestoredsupplyandRunstartsagain. Holddurationarrowsno numericalduration. Marker1/2notdefinedonpage;no missingmeaninginferred.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Timing plot 1/2 markers are undefined locally; all trace labels and source states retained.

Manual — Inhibit timing,alternative commands,emergency stop andexternal baseblock — page 184

Manual reference: physical PDF page 184. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.21 Inhibit acceleration / deceleration command operation

(14) Main/ Alternative Run Switch Function (03-0X =12)

➢ When function terminals conduct, run command source is set in alternative run command

(00-03). When functional terminal is set to 27 (Local/ Remote control selection), it will be

precedential to main/alternative run switch.

(15) Main/ Alternative Frequency Switch Function (03-0X =13)

➢ When function terminals conduct, frequency command source is set in alternative frequency

command (00-06). When functional terminal is set to 27 (Local/ Remote control selection), it

will be precedential to main/alternative frequency switch. When PID function is

active(10-03=XXX1B), this function is invalid and main frequency is switched to PID function.

When PID function is invalid, Main/ Alternative frequency switch function is valid then.

(16) Emergency stop (decelerate to zero and stop) (03-0X =14)

➢ Refer to the "deceleration time of emergency stop" of parameter 00-26

(17) External Baseblock Command (coast to stop) (03-0X =15)

➢ Execute the base block command by the use of ON / OFF way of multi-function digital

input terminal, and prohibit the inverter output.

During run:

When an external base block command is activated, the keypad displays "BBn BaseBlock (Sn)",

indicating the inverter output is turned off (n indicates the digital input number 1 – 6). Upon

removing the base block signal, the motor will run at the frequency reference. If speed search from

frequency reference is active the inverter output frequency starts from the frequency reference and

searches for the coasting motor speed and continue to operate. If speed search is not active the

output frequency starts at 0Hz.

Figure4.3.21Inhibitacceleration/decelerationcommandoperation. TracesPowerSupplyON/OFF/ON,ForwardRunON/OFF/ON,InhibitAcc/DecCommandOFF/ON/OFF/ON,FrequencyReferencehighthenlow,OutputFrequency. TwoHoldintervals alignInhibitON;outputdecelerateswhenRunOFFandresumesafterRunON. Sourceplot only;no durations/inferredlogic.

Manual — External baseblock continuation,faultreset,autorun andenergy saving — page 185

Manual reference: physical PDF page 185. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fault reset RESET.* marker has no local explanation. No omitted safety qualifier inferred.

During deceleration:

When an external base block command is activated, the keypad displays "BBn BaseBlock (Sn)",

indicating the inverter output is turned off (n indicates the digital input number 1 – 8). Upon

removing the base block signal, the motor is stopped or will coast to a stop and the inverter will

remains in the stop condition.

During acceleration: When an external base block command is activated, the keypad displays "BBn

BaseBlock (Sn)", indicating the inverter output is turned off (n indicates the digital input number 1 –

8). Upon removing the base block signal, the motor will run at the frequency reference. If speed search

from frequency reference is active the inverter output frequency starts from the frequency reference

and searches for the coasting motor speed and continue to operate. If speed search is not active the

output frequency starts at 0Hz.

Please refer figure 4.322 for external base block operation。

(18) PID control disabled (03-0X =16)

(19) Fault reset (03-0X =17)

➢ The output becomes active when the inverter trips on a fault. Upon an inverter fault the inverter

output will turn off (base block) and the keypad displays the dedicated fault message. When

fault occurs, the following actions can be used to reset the fault:

(a) One of the multi-function digital inputs (03-00 to 03-05) to 17 (reset fault) and active input.

(b) Press the reset key of the digital operator (RESET).*

(c) Recycle power to the inverter.

(20) Auto run mode enable (03-0X=18)

➢ Digital input set to “18”, auto run mode function will be enabled, please refer to group 06.

(21) Speed Search 1 (from the maximum frequency) (03-0X=19)

(22) Energy saving enabled (03-0X=20)

➢ Manual energy savings function is set with parameters 11-12 and 11-18, for the manual energy

saving operation, please refer to figure 4.3.88。

Figure4.3.22Externalbaseblockoperation. TracesRunCommand,ExternalBaseblock,OutputFrequency,time. BaseblockfirstpulsewhileRunhigh:outputgap/CoasttoStop followedSpeedsearchactive notch/recovery. SecondpulseafterRunoff:CoasttoStopdashedslope. Unlabelledtimings/frequenciesnot inferred.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Fault reset RESET.* marker has no local explanation. No omitted safety qualifier inferred.

Manual — Counter,pulse measurements andlocal/remote selection — page 186

Manual reference: physical PDF page 186. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(23) Reset PID integral value to zero (03-0X=21)

(24) Counter Input 1 (03-0X=22)

➢ When digital input set to “22”, the counter value will be added once when the digital input

from "OFF" to "ON" status.

(25) Counter Reset (03-0X=23) ➢ Counter counts can be reset to 0 at any time by using an external input connected to one of the multi-function inputs (S1~S6) and by setting the relevant parameter (03-00 ~03-05) to 23, inverter will display “C0000”. Inverter can receive counter signal again when the reset signal is removed. (26) PLC Input (03-0X=24) ➢ When anyone of the extermal terminals S1 to S6 set to 24 and turned on, the PLC program inputs will be enabled. (27) Pulse-In Width Measure (S3) (03-0X=25) ➢ When one of S1~S6 (except S3) set to 25, it will switch pulse width measurement function from S3. In this mode, the pulse input frequency range is 10Hz~200Hz, the other digital input can not set to 26 (pulse input-frequency measurement) (28) Pulse Input Frequency Measure (03-0X=26) ➢ When one of S1~S6 (except S3) set to 26, it will switch pulse width measurement function from S3. In this mode, the pulse input frequency range is 0.05kHz~25.00kHz, the other digital input can not set to 25 (pulse input-width measurement) Note: The priority of digital input pulse input measurement function is higher than 03-30. (29) Local/Romote selection (03-0X=27) ➢ Switch the inverter frequency reference source between Local (keypad) or Remote (control circuit terminals or RS485). Use parameter 00-05 (Main frequency command source selection) and 00-02 (Run command selection) to select the remote source. ➢ Local/Remote function can be set by one of digital inputs (S3~S6), and be switched by 03-03~03-05 which the parameter setting is to “27”.In 3 wire operation control, S1/S2/S3 are reserved for run/stop/forward-reverse operation, please refer the table below.

Note:Local and remote mode only can be switched when inverter stop running.

Countertimingplot:Countdisplaysetby12-00=00008;sequenceC0001,C0002,C0003,C0004,C0005,C0001,C0002. CountinputMulti-functioninputpulses;Singlepresetcount1setbyParameter03-22;03-22=5lowerpulseatthefifthcount. Triggerwidthannotation2msandThewidthofthetriggersignalshouldbelargethan2ms. Sourceplotliteral;no implicitresetimplementationinferred.

Manual — Local/remote table,source diagram,jog andDCbraking — page 187

Manual reference: physical PDF page 187. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(30) Local/Romote selection (03-0X=28)

➢ In Remote mode, indicators of SEQ and REF are on; you can use terminals AI1 and AI2 to

control the frequency command, and use terminals S1, S2 or communication terminal RS-485

to control the operation command.

➢ When one of 03-02~03-05=28 (Remote mode selection),inverter can switch between external

terminal source (S1~S6) or communication (RS-485) source. Please refer the figure 4.3.23。

Figure 4.3.23 Remote mode operation selection

(31) Jog Frequency Selection (03-0X=29)

➢ When jog frequency selection is ON, the inverter will depend on the parameter 00-18 (jog

frequency) as the command.

(32) DC Braking (03-0X=33)

➢ When DC-Injection braking is enabled during start and stop of the inverter.

➢ DC injection braking is disabled when a run or jog command is active.

Refer to the DC braking time diagram in Figure 4.3.24.

(33) Speed search 2 (03-0X =34)

Figure4.3.23RemoteModeoperationselection. LocalModeLCDdigitalOperator;ONlocalbranch;OFFremote branch. UppercaptionSetoneof03-00to03-07=27. RemoteModeRS-422/RS-485communicationsON;ControlcircuitterminalsOFF;lowercaptionSetoneof03-00to03-05=28. OutputFrequencyReferenceandRunCommand. Preserve03-07/RS-422labelswithoutestablishingterminal/hardwareavailability.

DCbrakingtimingreferencedasFigure4.3.24. RunorJogCommandOFF/ON;DCInjectionBrakingCommandOFF/ONwithlongerhighinterval. OutputFrequencyrisesduringRunthenfalls;hatchedDCInjectionBrakebeforeRunandafterrampdown. Labels01-08(Fmin),07-06(Fdc-inj);calloutsFout>01-08(Fmin),Fout>07-06(DCInjStartFreq.). No unlabelledtimeorfrequency inferred.

Local/remote table,source diagram,jog andDCbraking

Input / Mode / Frequency Reference & Run/Stop Command Source — PDF page 187

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Input Mode Frequency Reference & Run/Stop Command Source
2 ON Local mode  Frequency eference and Run-Stop from keypad.  LEDs SEQ and REF are off.
3 OFF Remote mode  Frequency reference source selected by parameter 00-05 and Run/Stop source selected by parameter 00-02  LEDs SEQ and REF are on.

Manual — PID sleep,firemode,KEB,forcedfrequency,pressure andshortcircuitbraking conditions — page 188

Manual reference: physical PDF page 188. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(34) Switching between motor 1 and motor 2 (03-0X =40)

(35) PID Sleep (03-0X=41)

➢ Please set 10-29=2 (PID sleep function enabled by digital input) and follow the instructions

of 10-27~10-20.

(36) Fire mode (03-0X=47)

➢ When input is active (03-00~03-05=47) disables all inverter warning and hardware protections.

This function is commonly used in commercial applications where the inverter controls an

exhaust fan and needs run to destruction in case of a fire.

➢ When DI terminal becomes to N.C, fire mode will be turned on according to the value of 08-49.

(37) KEB acceleration (03-0X=48)

➢ When input is active enables KEB (Kinetic Energy Braking) during acceleration. Refer to the

parameter description of 11-47 and 11-48. Note: To enable set parameter 11-47 to a value

greater than 0.

(38) Forced Frequency Run (03-0X=57)

➢ This function enables with the corresponding of parameter 23-28 and the source of frequency

command of parameter 00-05 set to the value of 5 (PID given, namely the parameter of 10-03

needs to be active.)

➢ When any one of the multi-function digital input terminal (S1~S6) is set to the value of 16 (the

interdiction of PID function), pump will not depend on feedback to do any PID output

adjustment; simultaneously another one is set to the value of 57 (forced frequency run) and

inverter will have the frequency run setting depending on the parameter of 23-28. Inverter will

stop output when digital input terminals (S1~S6) are removed.

➢ This function is applied to inverter output being controlled by external pressure sensor (eg.

differential pressure switch) when pressure sensor disconnects.

(39) Switch to Tolerance Range of Constant Pressure (03-0X=63)

➢ When using in PUMP mode (23-00=1), the tolerance range of constant pressure (23-09) will be

used for walking up the inverter. When digital input terminal enables, the tolerance range of

constant pressure 2 (23-24) will be used.

(40) Short-circuit braking (03-0X=65)

➢ To stop inverter by turning on Short-circuit braking with setting terminal. If executing run

command or jog command, short-circuit braking command will erased and start to run. The

following picture is short-circuit braking time process.

Manual — Shortcircuitbraking diagram,externalfault/overload conditions,UP/DOWNstep modes — page 189

Manual reference: physical PDF page 189. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: PID Control Disable2 option66 heading has no explanatory body; table179 also only ON: and blank modes. Retain missing functional conditions explicitly.

(41) PID Control Disable 2 (03-0X=66)

(42) External Fault (03-0X=68)

➢ When this function is enabled, inverter will stop running and motor will coast to stop.

➢ When digital input (S3) set to external fault, keypad will display “EF3 Ext. Fault (S3)”.

➢ All digital input terminals can be set to external fault.

(43) Externl Overload (03-0X=69), input terminal is N.C type.

➢ When digital input (S5) set to external fault, keypad will display “TOL Ext. OverLoad”

➢ Fire mode needs to be enabled first (08-48=1) when external overload function needs to be

used. Only S5 terminal can be set to external overload input.

➢ External overload function will be set to normal close contact. Pleae do not set run command

from external source.

When 03-06=0Hz, UP/DOWN function will be kept.

When 03-06≠0Hz, frequency command becomes operation frequency plus 03-06 value.

Example:

03- 00=8 (S1 terminal is increasing frequency command)

03- 01=9 (S2 terminal is decreasing frequency command)

03- 06=△Hz

Mode 1: When 03-06=0, UP/DOWN function will be kept. Mode 2: When 03-06≠0 and the turned on period is less than 2 secs, for every ON operation frequency changes by △Hz.

ShortCircuitBrakingtimingcontinuation188. RunCommandorJogCommandOFFthenONthenOFF. ShortCircuitBrakingCommandOFFthenlongONinterval. OutputFrequencyrisesduringRunthenfalls;hatchedShortCircuitBrakeintervalsoutsideRun. Labels01-08(Fmin);Thelargeof01-08or07-07. Exactsourcecallout;no correctionto07-06orengineeringvalidation.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: PID Control Disable2 option66 heading has no explanatory body; table179 also only ON: and blank modes. Retain missing functional conditions explicitly.

Shortcircuitbraking diagram,externalfault/overload conditions,UP/DOWNstep modes

03- 06 / UP/DOWN Frequency Step — PDF page 189

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 06 UP/DOWN Frequency Step
2 Range 【0.00~5.00】Hz

Manual — UP/DOWNstep timing andsource formulas;glyph/modeboundary limitations retained — page 190

Manual reference: physical PDF page 190. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Source diagram glyphs before Hz/H1/H2 render as boxes; exact2-second mode boundary is not specified. Prose triangles and literal H2 acceleration denominator retained separately.

Mode 3: When 03-06≠0, and the turned on period is greater than 2 secs, frequency will be changed by acceleration/deceleration time.

Note:

△H1: Difference of acceleration frequency

t1: Input terminal turned on time of acceleration time

△H2: Difference of deceleration frequency

t2: Input terminal turned on time of deceleration time.

UP/DOWNstepMode2timing. VerticalHz,Upperfrequencylimit,Lowerfrequencylimit;horizontalT. ActualoutputfrequencyincreasesstepswiththreeS1ONpulses,then decreaseswiththreeS2ONpulses. StepheightlabelcontainsunrenderedboxbeforeHz; no repairedglyphinferred.

UP/DOWNstepMode3timing. Actualoutputfrequency,upper/lowerfrequencylimits,Hz,T. S1ONthenOFF;S2OFFthenON. Durations2Sec,t1;2Sec,t2. VerticaldifferenceslabelledboxH1,boxHz,boxH2;originalmissingglyphsnotinferred. Lastdecelerationreacheshorizontalaxisbelowdrawnlowerlimit; no extra numericlimitinferred.

Sourceformulas: △H1 = [Upperfrequencylimit / Accelerationtime2] x inputterminalturnedontime(t1). △H2 = [Upperfrequencylimit / Accelerationtime2] x inputterminalturnedontime(t2). BothdenominatorsliterallyAccelerationtime2;proseH2describesdeceleration. No silentcorrection.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Source diagram glyphs before Hz/H1/H2 render as boxes; exact2-second mode boundary is not specified. Prose triangles and literal H2 acceleration denominator retained separately.

Manual — UP/DOWNmemory,scan filtering,switch contact binary settings andsafety condition — page 191

Manual reference: physical PDF page 191. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ 03-07=0, When run signal is removed (Stop Command), the output frequency is stored in

parameter 05-01( Key pad Frequency).

➢ 03-07=1, when run command is removed, the output frequency of deceleration will be clear.

➢ 03-07=2, when run command is not available, the UP/DOWN command will be written into

frequency command.

➢ 03-07=3, when frequency command is used, then resend the run command, the frequency command will be updated by operation frequency when you press UP/DOWN key.

➢ Multifunction input terminal On/Off periods will be scanned for the number of cycles according to

the set value in parameter 03-08. If the signal status for ON or OFF period is less than the set

period it will be treated as noise.

➢ Use this parameter if unstable input signal is expected, however setting long scan time periods

results in slower response times.

Parameter 03-09 and 03-10 selects the digital input type between a normally open and a normally

closed switch/contact.

Example:S1 and S2 wired to a normally closed contact/switch set 03- 09=0011。

Note:

Do not set the operation command parameter 00-02 to terminal control before setting the digital

input type. Failure to comply may cause death or serious injury.

Eachbitof03-09/03-10presentsaninput.03-09=0000 orderedlefttorightS4,S3,S2,S1;0normallyopenswitch,1normallycloseswitch.03-10=0000withS6,S5undertwolowbits;0normallyopen,1normallyclose. ExampleS1andS2normallyclosed→03-09=0011. Preserveallprosewarningbelow;no livewiringinstructioninferred.

UP/DOWNmemory,scan filtering,switch contact binary settings andsafety condition

03- 07 / UP/DOWN Keep Frequency Status after Stop Command — PDF page 191

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 07 UP/DOWN Keep Frequency Status after Stop Command
2 Range 【0】:When UP/DOWN is used, the preset frequency is held as the inverterstops, and the UP/DOWN function is disable. 【1】:When UP/DOWN is used, the preset frequency is reset to 0 Hz as the inverter stops. 【2】:When UP/DOWN is used, the preset frequency is held as the inverter stops, and the UP/DOWN is available. 【3】:When acceleration is used, the output frequency will be updated.

03- 08 / S1~S6 scan time confirmation — PDF page 191

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 08 S1~S6 scan time confirmation
2 Range 1~200ms

03- 09 / S1~S4 switch type select — PDF page 191

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 09 S1~S4 switch type select
2 Range 【xxx0b】:S1 A Contact 【xxx1b】:S1 B Contact 【xx0xb】:S2 A Contact 【xx1xb】:S2 B Contact 【x0xxb】:S3 A Contact 【x1xxb】:S3 B Contact 【0xxxb】:S4 A Contact 【1xxxb】:S4 B Contact
3 03- 10 S5~S6 switch type select
4 Range 【xxx0b】:S5 A Contact 【xxx1b】:S5 B Contact 【xx0xb】:S6 A Contact 【xx1xb】:S6 B Contact

Manual — Relay outputs and shared options; terminal diagram — page 192

Manual reference: physical PDF page 192. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure4.3.25 digital outputs. Source diagram labels R1A,R1B,R1C with default Fault signal /03-11;R2A,R2B with default Zero speed /03-12. Table labels R2A-R2C instead. Switch symbols retained in image;no inferred wiring topology.

Relay outputs and shared options; terminal diagram

03-11 / Relay (R1A-R1C) output — PDF page 192

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03-11 Relay (R1A-R1C) output
2 03-12 Relay (R2A-R2C) output
3 Range 【0】:During Running 【1】:Fault Contact Output 【2】:Frequency Agree 【3】:Setting Frequency Agree (03-13 ± 03-14) 【4】:Frequency Detection 1 (≧ 03-13, hysteresis range is the setting value of 03-14) 【5】:Frequency Detection 2 (≦03-13, hysteresis range is the setting value of 03-14) 【6】:Automatic Restart 【7】:Momentary AC Power Loss 【8】:Rapid Stop 【9】:Base Block 【10】:Motor Overload Protection (OL1) 【11】:Drive Overload Protection (OL2) 【12】:Over Torque Threshold Level (OT) 【13】:Preset Output Current Reached 【14】:Brake Control 【15】:PID Feedback Signal Loss 【16】:Single Pre-set Count (03-22~03-23) 【17】:Dual Pre-set Count (03-22~03-23) 【18】:PLC Status Indicator (00-02) 【19】:PLC Control 【20】:Zero Speed 【30】:Motor 2 Selection 【37】:Detection Output of PID Feedback Loss 【54】:Turn On Short-Circuit Braking 【55】:Low Current Detection 【59】:OH Detection

Manual — Digital output function and control-mode table0–22 — page 193

Manual reference: physical PDF page 193. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.29 Function table of multi-function digital output

Digital output function and control-mode table0–22

Value / Function / Contents / Control mode — PDF page 193

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Value Function Function Contents Control mode Control mode Control mode
2 Value Name LCD display Contents V/F SLV PM SLV
3 0 During Running Running ON:Dring running (Run command is ON) O O O
4 1 Fault Contact Output Fault ON:Fault contact output (except CF00 and CF01) O O O
5 2 Frequency Agree Freq. Agree ON:Frequency agree (frequency agree width detection is set by 03-14 ) O O O
6 3 Setting Frequency Agree (03-13 ± 03- 14) Setting Freq Agree ON:Output frequency = allowed frequency detection level (03-13) ± frequency bandwidth (03-14) O O O
7 4 Frequency Detection 1 (≧ 03-13, hysteresis range is the setting value of 03-14) Freq. Detect 1 ON:Output frequency > 03-13, Hysteresis range is 03-14 O O O
8 5 Frequency Detection 2 (≦03-13, hysteresis range is the setting value of 03-14) Freq. Detect 2 OFF:Output frequency > 03-13, Hysteresis range is 03-14 O O O
9 6 Automatic Restart Auto Restart ON:the period of automatic restart O O O
10 7 Momentary AC Power Loss Power Loss ON:Momentary AC Power Loss Happen O O O
11 8 Rapid Stop Invalid Do Func. Reserved O O O
12 9 Base Block Baseblock ON:During Baseblock O O O
13 10 Motor Overload Protection (OL1) Invalid Do Func. Reserved O O O
14 11 Drive Overload Protection (OL2) Invalid Do Func. Reserved O O O
15 12 Over Torque Threshold Level (OL3) Over Torque ON:Over torque detection is ON O O O
16 13 Preset Output Current Reached Currebt Agree ON:When output current > 03-15 is ON O O O
17 14 Brake Control Brake E510s ON:Mechanical braking release frequency OFF:Mechanical braking run frequency O O O
18 15 PID Feedback Signal Loss Invalid Do Func. Reserved O O O
19 16 Single Pre-set Count (03-22~03-23) Invalid Do Func. Reserved O O O
20 17 Dual Pre-set Count (03-22~03-23) Invalid Do Func. Reserved O O O
21 18 PLC Status Indicator (00-02) PLC statement ON:When 00-02 is set to 3 (PLC operation command source) O O O
22 19 PLC Control Control From PLC ON:Control from PLC O O O
23 20 Zero Speed Zero Speed ON:Output frequency < Minimum output frequency (Fmin) O O O
24 21 Reserved Reserved Reserved - - -
25 22 Reserved Reserved Reserved - - -

Manual — Digital output function table23–59 and running/fault conditions — page 194

Manual reference: physical PDF page 194. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Output option 46 Reserved has physically blank control-mode cells. Adjacent reserved options 45 and 47 have printed dashes, so a blank must not become a dash or inferred applicability. Exact row geometry and three blank cells were freshly bounded.

(1) During Running (03-1X=0) ➢ ON:Run command is ON or output frequency is greater than 0. ➢ OFF:Run command is OFF and the inverter is stopped. (2) Fault Contact Output (03-1X=1) ➢ Output is active during fault condition.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Output46 Reserved control-mode cells are blank; no applicability inferred.

Digital output function table23–59 and running/fault conditions

Value / Function / Contents / Control mode — PDF page 194

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Value Function Function Contents Control mode Control mode Control mode
2 Value Name LCD display Contents V/F SLV PM SLV
3 23 Reserved Reserved Reserved - - -
4 24 Reserved Reserved Reserved - - -
5 25 Reserved Reserved Reserved - - -
6 26 Reserved Reserved Reserved - - -
7 27 Reserved Reserved Reserved - - -
8 28 Reserved Reserved Reserved - - -
9 29 Reserved Reserved Reserved - - -
10 30 Motor 2 Selection Motor 2 Selection ON:Switch to Motor 2 O O X
11 31 Reserved Reserved Reserved - - -
12 32 Reserved Reserved Reserved - - -
13 33 Reserved Reserved Reserved - - -
14 34 Reserved Reserved Reserved - - -
15 35 Reserved Reserved Reserved - - -
16 36 Reserved Reserved Reserved - - -
17 37 Detection Output of PID Feedback Loss PID Fbk Loss ON:Detection Output of PID Feedback Loss O O O
18 38 Reserved Reserved Reserved - - -
19 39 Reserved Reserved Reserved - - -
20 40 Reserved Reserved Reserved - - -
21 41 PID Sleep PID Sleep ON:PID Sleep O O O
22 42 Reserved Reserved Reserved - - -
23 43 Reserved Reserved Reserved - - -
24 44 Reserved Reserved Reserved - - -
25 45 Reserved Reserved Reserved - - -
26 46 Reserved Reserved Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
27 47 Reserved Reserved Reserved - - -
28 48 Reserved Reserved Reserved - - -
29 49 Reserved Reserved Reserved - - -
30 50 Reserved Reserved Reserved - - -
31 51 Reserved Reserved Reserved - - -
32 52 Reserved Reserved Reserved - - -
33 53 Reserved Reserved Reserved - - -
34 54 Turn On Short-Circuit Braking SC Brk ON:Turn on short-circuit bbraking X X O
35 55 Low Current Detection Low Current Detect ON:Output Current ≦ 03-48 Low Current detection level O O O
36 59 OH Detection OH Detect Output ON:OH Detect Output O O O

Manual — Digital output functions2–14: detection thresholds, restart and overload conditions — page 195

Manual reference: physical PDF page 195. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(3) Frequency Agree (03-1X=2) ➢ Output is active when the output frequency falls within the frequency detection width (03-14) of the set frequency detection level (o3-13)

(4) Setting Frequency Agree (03-13 ± 03-14) (03-1X=3)

➢ Output is active when the output frequency falls within the frequency detection width

(03-14) of the set frequency detection level (o3-13).

(5) Frequency Detection 1 (≧ 03-13, hysteresis range is the value of 03-14) (03-1X=4)

➢ Output is active when the output frequency rises above the frequency detection level (03-13) +

frequency detection width (o3-14) and deactivates when the output frequency falls below

frequency detection level (o3-13).

(6) Frequency Detection 2 (≦ 03-13, hysteresis range is the value of 03-14) (03-1X=5)

➢ Output is active when the output frequency is below the frequency detection level

(03-13) + frequency detection width (03-14) and turns off when the output frequency

falls below frequency detection level.

(7) Automatic restart (03-1X=6)

➢ Output is active during an auto-restart operation.

(8) Momentary AC Power Loss (03-1X=7)

➢ Please set 07-01=1 first then this function will be enabled.

➢ When momentary AC power loss function is enable, output relay will be ON.

(9) Rapid Stop (03-1X=8)

➢ Output is active during a rapid stop.

(10) Base Block (03-1X=9)

➢ Output is active when the inverter output is turned off during a Baseblock command.

(11) Motor Overload Protection (OL1) (03-1X=10)

➢ Output is active during an overload detection of motor.

(12) Drive Overload Protection (OL2) (03-1X=11)

➢ Output is active during an overload detection of inverter.

(13) Over Torque Threshold Level (OL3) (03-1X=12)

➢ Output is active during an over torque detection of inverter.

(14) Preset Output Current Reached (03-1X=13)

➢ When output current > 03-15 and output current > 03-15 duration > 03-16, it is ON.

(15) Brake Control (03-1X=14)

➢ Output is active when the brake control is active.

Manual — Output functions15–59 and frequency detection parameters — page 196

Manual reference: physical PDF page 196. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(16) PID Feedback Signal Loss (03-1X=15)

➢ Output is active when PID feedback signal loss.

(17) PLC Status Indicator (03-1X=18)

➢ Output is active when operation command parameter 00-02 is set to PLC control.

(18) PLC Control (03-1X=19)

➢ Output is controlled by the PLC logic.

(19) Zero Speed (03-1X=20)

➢ When zero speed is active, output frequency < minimum output frequency (01-08).

➢ When zero speed is off, output frequency ≧ minimum output frequency.

(20) Motor 2 Selection (03-1X=30)

➢ Output is active when motor 2 is selected.

(21) Detection Output of PID Feedback Loss (03-1X=37)

➢ Output is active when PID feedback loss.

(22) Turn On Short Circuit Braking (03-1X=54)

➢ Output is active when truning on short circuit braking.

(23) Low Current Detection (03-1X=55)

➢ Output is active when low current detection function is active.

(24) OH Detection (03-1X=59)

➢ Output is active when temperature setting is agreed.

When inverter temperature higher than the value of 08-46, digital output will become to ON.

When inverter temperature lower than the value of 08-47, digital output will become to OFF.

➢ Frequency detection level:the multi-function output terminals R1A-R1C, R2A-R2C or PH1

(03-11, 03-12) to the desired detection level and bandwidth for use with multi-function output

functions 1 to 6.

Figure4.3.26 zero-speed operation. OutputFrequency descends through01-08(Fmin);ZeroSpeed signal changes OFF toON at marked crossing. Horizontal axes t. Prose distinguishes outputfrequency<minimum asactive and >=minimum asoff;no unlabelled timing inferred.

Output functions15–59 and frequency detection parameters

03-13 / Frequency detection Level — PDF page 196

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03-13 Frequency detection Level
2 Range 【0.0~599.0】 Hz
3 03-14 Frequency detection width
4 Range 【0.1~25.5】 Hz

Manual — Table4.3.30 frequency detection timing and descriptions — page 197

Manual reference: physical PDF page 197. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ The time charts of the frequency agree detection operation are shown in table 4.3.30.

Frequency-agree plot:OutputFrequency has FWD positive ramp/plateau and REV negative ramp/plateau. FreqReference and03-14 band marks;FrequencyAgreeSignal OFF thenON near each reference plateau,OFF between. Source table description supplies exact conditions.

Set-frequency-agree plot:OutputFrequency FWD/REV,03-13 threshold and03-14 band marks. SettingFrequencyAgreeSignal shows ON windows while crossing each marked band;OFF outside. No unlabelled limits inferred.

Output-frequency-detection1 plot:positive and negative excursions,threshold03-13 and hysteresis03-14. Signal OFF,ON,OFF,ON,OFF. ON at outer threshold crossing,OFF at inner threshold return. Exact source prose and directional signs retained separately.

Output-frequency-detection2 plot uses same03-13/03-14 marks with complementary signal ON,OFF,ON,OFF,ON. Source description literally says rises above below frequency detection level;no repaired engineering logic.

FrequencyOutput plot:Runcommand OFF/ON/OFF;BaseBlock OFF/ON/OFF;OutputFrequency ramp,plateau,gap duringbaseblock,recovery then rampdown. DCBrake shaded regions at start/end. FrequencyOutputIng trace OFF/ON/OFF/ON/OFF aligned with output;no numeric duration inferred.

Table4.3.30 frequency detection timing and descriptions

Function / Detection operation of frequency confirmation / Description — PDF page 197

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Function Detection operation of frequency confirmation Description
2 Frequency agree time time ON OFF FWD REV 03-14 03-14 Freq Reference Output Frequency Frequency Agree Signal ON Freq Reference  Output is active when the output frequency falls within the frequency reference minus the frequency detection width (03-14).  Any of the digital outputs function (03- 11, 03-12 or 03-28) can be set to 2 (Frequency agree).
3 Set frequency agree time time ON OFF FWD REV 03-14 Output Frequency Setting Frequency Agree Signal ON 03-13 03-13 03-14  Output is active the output frequency falls within the frequency detection width (03-14) of the set frequency detection level (03-13).  Any of the digital outputs function (03- 11, 03-12 or 03-28) can be set to 3 (Set frequency agree).
4 Output frequency detection 1 ON ON OFF OFF 03-14 03-14 03-13 03-13 03-13 03-13 time time Output Frequency Output Frequency Detection 1 Signal  Output is active when the output frequency rises above the frequency detection level (03-13) + frequency detection width (o3-14) and deactivates when the output frequency falls below frequency detection level (03-13).  Any of the digital outputs function (03- 11, 03-12 or 03-28) can be set to 4 (Output frequency detection 1).
5 Output frequency detection 2 ⟦blank source cell⟧  Output is active when the output frequency is below the frequency detection level (03-13) + frequency detection width (03-14) and turns off when the output frequency rises above below frequency detection level.  Any of the digital outputs function (03- 11, 03-12 or 03-28) can be set to 5 (Output frequency detection 2).
6 Frequency Output DC Brake DC Brake ON ON OFF OFF Output Frequency Frequency Output Ing OFF OFF OFF OFF OFF ON ON Run command Base Block  When the inverter output frequency is active, the output terminal is closed.

Manual — Current-agree delay and mechanical-brake thresholds — page 198

Manual reference: physical PDF page 198. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Load-current diagram includes an unrendered glyph before its label; no missing symbol inferred.

➢ When 03-11=13 and then when the output current > 03-15, output relay will active. ➢ 03-15:The suggest setting value is 0.1 to motor rated current. ➢ 03-16:The delay time performs depending one the setting value. ➢ When output current lower than 03-53, delay time from ON to OFF in the signal of relay is 100ms (constant).

Time diagram:

➢ When 03-11=14, (1) In acceleration mode, output relay will be ON as soon as the actual output frequency reaches the external brake release set in parameter 03-17. (2) In deceleration mode, output relay will be OFF as soon as the actual output frequency reachesthe external brake engage level set in parameter 03-18. ➢ Timing diagram for 03-17 ≤ 03-18 is shown below.

Current-agree timing:vertical100%,threshold03-15,Load current trace with unrendered glyph before label.03-11 OutputRelay rises after03-16 delay beyond threshold;falls after100ms(Constant) delay. Source prose references03-53for falling threshold;diagram03-15. HorizontalT.

Mechanical brake timing for03-17<=03-18. VerticalHz,horizontalT;03-18 upperthreshold,03-17 lowerthreshold. RunCommand RUN thenSTOP;03-11=14 ON at rising03-17 crossing,OFF at falling03-18 crossing. No unlabelledvalues inferred.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Load-current diagram includes an unrendered glyph before its label; no missing symbol inferred.

Current-agree delay and mechanical-brake thresholds

03-15 / Current Agree Level — PDF page 198

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03-15 Current Agree Level
2 Range 【0.1~999.9】A
3 03-16 Delay Time of Current Agree Detection
4 Range 【0.1~10.0】 Sec

03-17 / Machanical Braking Release Level — PDF page 198

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03-17 Machanical Braking Release Level
2 Range 【0.00~20.00】 Hz
3 03-18 Machanical Braking Level Set
4 Range 【0.00~20.00】 Hz

Manual — Brake continuation, relay contacts and internal/external input bit selection — page 199

Manual reference: physical PDF page 199. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Time diagram for 03-17 ≥ 03-18 is shown below.

➢ If 03-19=0, When the set conditions of 03-11,03-12 are met , relay contact is closed.

➢ If 03-19=1, When the set conditions of 03-11,03-12 are met ,relay contact will open.

➢ The parameter is decided which terminal will be used. (input or output terminal). If you select internal terminal, the corresponded point will be set to 1, if the you select external terminal, the correspond point will be set to 0.

0:External Multi-function terminal (remote control) 1:Internal Multi-function terminal (based on 03-21) Example: S2、S4、S6 terminal decided to internal multi-function terminal (decided by 03-21) S1、S3、S5 terminal decided to external multi-function terminal (remote control) Please set 03-20=101010, summarized the total value of 03-20 is 42 (32+8+2=42).

Mechanical brake timing for03-17>=03-18.03-17upperthreshold,03-18lowerthreshold;Hz/T,RunCommand RUN/STOP;03-11=14 ON at rising03-17 andOFF at falling03-18.

03-20 bit diagram: six bits ordered S6,S5,S4,S3,S2,S1 left-to-right;display000000. Source0externalremote,1internalbased03-21. ExampleS2/S4/S6internal,S1/S3/S5external,101010=42(32+8+2).

03-21 bit diagram:000000 orderedS6,S5,S4,S3,S2,S1. Meaning and example continue200;no independently inferred state.

Brake continuation, relay contacts and internal/external input bit selection

03- 19 / Relay (R1A-R2B) Type — PDF page 199

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 19 Relay (R1A-R2B) Type
2 Range 【xxx0b】:R1 A Contact 【xxx1b】:R1 B Contact 【xx0xb】:R2 A Contact 【xx1xb】:R2 B Contact

03- 20 / Internal/External Multi-Function Input Terminal Selection — PDF page 199

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 20 Internal/External Multi-Function Input Terminal Selection
2 Range 【0~63】

DI / S6 / S5 / S4 / S3 / S2 / S1 — PDF page 199

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 DI S6 S5 S4 S3 S2 S1
2 Binary 2^5 2^4 2^3 2^2 2^1 2^0
3 Decimal 32 16 8 4 2 1

03- 21 / Action to Set The Internal Multi-Function Input Terminals — PDF page 199

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 21 Action to Set The Internal Multi-Function Input Terminals
2 Range 【0~63】

Manual — Internal input continuation, counters and undercurrent settings — page 200

Manual reference: physical PDF page 200. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

0:Internal Multi-function terminal opened 1:Internal Multi-function terminal closed Example: If we need to set S2, S4 closed and S1, S3, S5, S6 opened, please set 03- 21=001010. summarized the total value of 03-21 is 10 (8+2=10).

➢ 03-22 is used to set the counter value for internal counter, the counter can be enabled by one of multi-digital inputs (03-00~03-05 set to 22), when counter value equal to the value of 03-22, connter value will be reset. ➢ If the counter needs to re-count when 03-22 value not reached setting value, please set one the multi-digital input to 23 (03-00~03-05=23). ➢ The status of counter can be monitoring by 12-00=0008. ➢ Refer to the photo below, if 03-11=17 (Dual Pre-set Count), 03-22=4 (Pre-Set Count 1),03-23=2 (Pre-Set Count 2). When counter cumulative to 2, RY1 will be active. When counter value cumulative to 4, the counter value will be reset when trigged signal is removd. ➢ If 03-12=16 and 03-22=4, when counter cumulative to 4, RY2 will be active when trigged signal is removd. ➢ 03-22 value must be higher than 03-23.

Counter diagram:12-00=00008,displayC0000,C0001,C0002,C0003,C0004,C0000,C0001,C0002,C0003.03-11=17,Set03-22=4/03-23=2:relay high fromcount2 untilresetafter4;repeats.03-12=16,Set03-22=4:high atcount4 untilreset. Redverticalresetline atcount4fallingedge. Signalwidth shouldhighthan2ms. Exact plottedstates;no inferred implementation.

Internal input continuation, counters and undercurrent settings

Adjacent source context — repeated to preserve continuation:

03- 22 / Setting Counter Agree — PDF page 200

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 22 Setting Counter Agree
2 Range 【0~9999】
3 03- 23 Specify Setting Counter Agree
4 Range 【0~9999】

03-24 / Output Under Current Detection — PDF page 200

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03-24 Output Under Current Detection
2 Range 【0】:Invalid 【1】:Valid
3 03-25 Output Under Current Detection Level
4 Range 【0~999.9】A
5 03-26 Output Under Current Detection Delay Time
6 Range 【0.0~655.34】 Sec

Manual — Undercurrent timing and pulse input selection — page 201

Manual reference: physical PDF page 201. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ If 03-11=55, when output current ≦ 03-25, output relay is active. ➢ When 03-25=0, the function will be disabled. ➢ When output current lower than 03-25 for a preset time (03-26), output relay is active. The delay time of output relay from ON to OFF is 100ms (constant). The timing chart:

➢ There are two ways for pulse input selection: (1) General pulse input: PI=Cutoff frequency divided by pulse input scale set by 03-27, corresponding to the maximum output frequency of motor 1 (01-02). (2) PWM:It is required to input the correct frequency PWM= Time of negative edge pulse divided by the time period of pulse, corresponding to the maximum output frequency of motor 1 (01-02). Note: Deviation of pulse time period in PWM is ±12.5%. If it is over the deviation range, pulse input is not active.

Diagram for pulse input selection:

Undercurrent plot:100%vertical,I(Loadingcurrent),threshold03-25,T. OperationCommandON;03-11RelayON after03-26 undercurrent delay;OFF afterFixed100msec whenabove threshold. Later dip labelledSmallerthan03-26 Relaydoesnotwork. Source conditions preserved.

Undercurrent timing and pulse input selection

Adjacent source context — repeated to preserve continuation:

03-27 / Pulse Frequency Selection (S3) — PDF page 201

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03-27 Pulse Frequency Selection (S3)
2 Range 50~25000Hz
3 03- 28 Pulse Frequency Gain
4 Range 【0.0~1000.0】%
5 03- 30 Pulse Input Selection
6 Range 【0】:General Pulse input 【1】:PWM 【2】:PLC Encoder Input

Manual — Pulse/PWM examples and connection conditions — page 202

Manual reference: physical PDF page 202. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Pulse/PWM period labels contain unrendered separator glyphs; formulas and explicit source conditions retained without symbol reconstruction.

Example of pulse input setting: 1. Normal pulse input (Both NPN/PNP connection can be used) 03-30=0 00-05=7 (Main Frequency Command Source Selection) 03-27=200Hz (Pulse Frequency) 03-28=100.0~1000% (Pulse Input Gain) When 03-27 with different value, the ouput frequency of display will be different. ➢ 03-27=100Hz, 00-12=60.00, 03-28=100.0, keypad display will be 30.00Hz ➢ 03-27=200Hz, 00-12=60.00, 03-28=100.0, keypad display will be 60.00Hz ➢ 03-27=100Hz, 00-12=60.00, 03-28=200.0, keypad display will be 60.00Hz 2. PWM Input (NPN connection only) 03-30=1 00-05=7 (Main Frequency Command Source Selection) 03-27=200Hz (Pulse Frequency) 03-28=100.0~1000% (Pulse Input Gain) When PWM input with different duty, the ouput frequency of display will be different. ➢ When 200Hz pulse with 50% duty, 00-12=60.00, 03-28=100.0, keypad display will be 50% ×60.00=30.00Hz, ➢ When 200Hz pulse with 30% duty, 00-12=60.00, 03-28=200.0, keypad display will be 30% ×60.00 ×2=36.00Hz。 ➢ When 200Hz pulse with 15% duty, 00-12=599.00, 03-28=500.0, keypad display will be 15%×599.00×5.00=449.25Hz。 Note: In this mode, the pulse input frequency range is 10Hz~200 Hz. Pulse input only can select S3 terminal, also can use NPN or PNP connection. ➢ PNP connection: PLC pulse ourput (Y0) connects to S3 terminal, the common terminal of PLC pulse output connects to external 24V terminal of inverter, it’s PNP connection. ➢ NPN connection: PLC pulse ourput (Y0) connects to S3 terminal, the common terminal of PLC pulse outputconnects to external COM terminal of inverter, it’s PNP connection.

Normalpulse03-30=0:samplepulse train,periodT with unrendered glyph. F=1/T(Period);Pulsecommand=Frequency/PulseFrequency(03-27) x100%(01-02). Exact displayed formulas.

PWM03-30=1:samplepulse train,periodT andnegative-edgeintervalT1 both with unrendered separator glyphs. PulseInputCommand=T1(Period)/T(Period) x100%(01-02). No missing glyph repaired.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Pulse/PWM period labels contain unrendered separator glyphs; formulas and explicit source conditions retained without symbol reconstruction.

Manual — PLC encoder, pulse adjustment and emergency-stop reset conditions — page 203

Manual reference: physical PDF page 203. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Pulse-adjustment T/K separator glyphs render as boxes; retain visible labels and conflicting selector references, no missing symbols inferred.

  1. PLC Encodert Input (This function have to collocate with PLC encoder function of DriveLink, only S3 terminal can be set to encoder input channel) ➢ 03-30=2 (Set S3 terminal to be PLC encoder input source), please refer section 4.4 for encoder input function instruction.

➢ Refer to section 3.4 table 2 control terminals for details.

Refer to figure 4.3.27 for the pulse input specification.

➢ Set Pulse Input Setup as Frequency Reference

(1) Set parameter 00-05 to 7 and 03-30 to 0 to use the pulse input terminal PI as the frequency,

reference source, refer the figure 4.3.5.

(2) Set parameter 01-02 (maximum output frequency) and 03-27 (scale of pulse input terminal) PI

as the frequency source. Set parameter 03-34 (pulse input filter time) if the performance of

inverter is effected.

(1) 03-54=0:After the emergency stop command input, it cannot be restarted before the inverter

stops. If you need to cancel the emergency stop, please turn off the run command and

emergency stop command, and the emergency stop state will be released after the inverter

stops.

(2) 03-54=1:An additional reset command (DI function: 17) is required to release the emergency

stop state.

Figure4.3.27 pulse-input adjustment:Pulsetrain→Filter1/(1+ST),T Pulseinputfiltertime03-34→1/K,K Pulseinputfrequency03-27→GainandBias plot03-28/03-33→00-05=4→Frequencyreference. Plot horizontal0%,10% literal;unrendered separator glyphs afterT/K. Source prose below uses00-05=7;no repair.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Pulse-adjustment T/K separator glyphs render as boxes; retain visible labels and conflicting selector references, no missing symbols inferred.

PLC encoder, pulse adjustment and emergency-stop reset conditions

03-33 / Pulse Input Bias — PDF page 203

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03-33 Pulse Input Bias
2 Range 【-100.0~100.0】%
3 03-34 Filter Time of Pulse Input
4 Range 【0.00~2.00】Sec

03-53 / Current Agree Level 2 — PDF page 203

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03-53 Current Agree Level 2
2 Range 【0.0~999.9】A

03-54 / Emergency Stop Action — PDF page 203

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03-54 Emergency Stop Action
2 Range Run command disable and emergency Stop command disable. 【0】:Restart after Inverter Stop 【1】:Restart after External Reset Command

Manual — Analog input types, scaling, gain/bias/slope and jumpers — page 204

Manual reference: physical PDF page 204. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 04 Analog Signal Inputs / Analog Output

➢ Refer to the follows for 04-00 AI input signal type:

 If AI1 is 0~10V, switch JP2 of control board to V, set parameter 04-00 to 0 or 1.

 If AI1 is 2~10V, switch JP2 of control board to V, set parameter 04-00 to 2 or 3.

 If AI1 is 0~20mA, switch JP2 of control board to I, set parameter 04-00 to 0 or 1.

 If AI1 is 4~20mA, switch JP2 of control board to I, set parameter 04-00 to 2 or 3.

 If AI2 is 0~10V, switch JP3 of control board to V, set parameter 04-00 to 1 or 3.

 If AI2 is 2~10V, switch JP3 of control board to V, set parameter 04-00 to 2 or 4.

 If AI2 is 0~20mA, switch JP3 of control board to I, set parameter 04-00 to 1 or 3.

 If AI2 is 4~20mA, switch JP3 of control board to I, set parameter 04-00 to 2 or 4.

(1) Analog input level adjustment AI1/AI2(04-02, 04-03,04-07, 04-08)

➢ Each input signal AI1 and AI2 has a separate gain and bias parameter associated.

➢ Analog input signal AI1 can be adjusted with parameter 04-02 and 04-03. Analog input

signal AI2 can be adjusted with parameter 04-07 and 04-08.Refer the figure 4.3.35。

Analog input types, scaling, gain/bias/slope and jumpers

04- 00 / Analog Input Signal Type — PDF page 204

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 04- 00 Analog Input Signal Type
2 Range 【0】: AI1 0~10V / 0~20mA AI2 0~10V / 0~20mA 【1】: AI1 0~10V / 0~20mA AI2 2~10V / 4~20mA 【2】: AI1 2~10V / 4~20mA AI2 0~10V / 0~20mA 【3】: AI1 2~10V / 4~20mA AI2 2~10V / 4~20mA
3 04- 01 AI1 Signal Scaling and Filter Time
4 Range 【0.00~2.00】Sec
5 04- 02 AI1 Gain
6 Range 【0.0~1000.0】%
7 04- 03 AI1 Bias
8 Range 【-100~100.0】%
9 04- 05 AI1 Slope
10 Range 【0】:Positive 【1】:Negative
11 04- 06 AI2 Signal Scaling and Filter Time
12 Range 【0】:Positive 【1】:Negative
13 04- 07 AI2 Gain
14 Range 【0.0~1000.0】%
15 04- 08 AI2 Bias
16 Range 【-100.0~100.0】%
17 04- 10 AI2 Gain
18 Range 【0】:Positive 【1】:Negative

Manual — Analog input diagrams, gain/bias and filter response — page 205

Manual reference: physical PDF page 205. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Please refer fig 4.3.36 for gain and bias operations.

Gain setting:

Sets the level in % that corresponds to a 10V or 20mA signal at the analog input. (Set the maximum

output frequency 01-02 to 100 %)

Bias setting:

Sets the level in % that corresponds to a 0V or 4mA signal at the analog input.(Set the maximum

output frequency 01-02 to 100%)

Figure 4.3.36 Gain and bias operations (for frequency reference signal) (2) AI1 signal scanning and filtering time (04-01) (3) AI2 signal scanning and filtering time (04-06) ➢ All analog input (AI1、AI2) has their own order programmable input filter that can be adjusted when noise is preset on each of the incoming analog signal to prevent erratic drive control. ➢ The filtering time constant (range:0.00 to 2.00 seconds) is defined as the time that the input step signal reaches 63% of the final value.

Figure4.3.35analoginputs:JP1 I/V besideAI1 labelled0~10V,-10V~+10V;JP2 I/V besideAI2 labelled0~10V/0~20mA and4–20mA/2–10V. +10V,GND. AI1related04-00signaltype,04-02gain,04-03bias,04-05slope;AI2related04-06scanning/filtering,04-07gain,04-08bias,04-10slope. Labels differ from204JP2/JP3;no wiring inferred.

Figure4.3.36 gain/bias plots. Gain verticalFrequencyReference200%,100%,-100%,-200%;horizontal0V(4mA) to10V(20mA),TerminalAI1/AI2analoginput;Gain200% and100% risinglines. Bias plot +100%top and100%bottom literal;Biaspositive/0%/Negative parallel risinglines,0V(4mA),10V(20mA). Preserve missingminus onbottom100% withoutrepair.

Figure4.3.37filtertimeconstant. Percentaxis100 and63;taxis. Unfilteredsignal step to100;Filteredsignal exponential rise;filtertimeconstant04-01 arrowfromstepstart to63%crossing. No time value inferred.

Manual — Analog output settings and output-level adjustment — page 206

Manual reference: physical PDF page 206. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

For the analog output and related parameters, please refer to figure 4.3.50.

(1) Analog output adjustment (04-12, 04-13)。

➢ Use parameter 04-12 to select the analog output signal for AO and parameter 04-13 to adjust

the bias to AO.

➢ Adjust the gain so that the analog output (10V) matches 100% of the selected analog output

signal.

➢ Adjust the bias so that the analog output (0V/4mA) matches 0% of selected analog output

➢ Please refer fig 4.3.51 for analog output level adjustment.

Figure4.3.50 AO relatedparameters04-11AnalogOutputMode,04-12AOGain,04-13AOBias;terminalAO. Sourcegraphiclabels only.

Figure4.3.51analogoutputleveladjustment. VerticalAnalogOutputSignal:10V(or20mA)xGain,(20mA)10V,Biasbrace,(4mA)0V. HorizontalMonitoreditems0%to100%. Solidlinefrompositivebiasrisesandsaturatesat10V;dashedreference extends toupper gainlevel. No unlabellednumbers inferred.

Analog output settings and output-level adjustment

04-11 / AO function setting — PDF page 206

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 04-11 AO function setting
2 Range 【0】:Output frequency 【1】:Frequency command 【2】:Output voltage 【3】:DC voltage 【4】:Output current
3 04-12 AO gain
4 Range 【0.0~1000.0】%
5 04-13 AO bias
6 Range 【-100.0~100.0】%
7 04-15 AO Slope
8 Range 【0】:Positive 【1】:Nagetive
9 04-16 Proportio Gearing function
10 Range 【0】:Disable 【1】:Enable

Manual — Analog output monitor mappings and F-Gain example — page 207

Manual reference: physical PDF page 207. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(2) Analog output terminal function selection (04-11)。

➢ Please refer to the following table 4.3.33。

Table 4.3.33 Selection of analog output terminals function (04-11)

(3) F-Gain(04-16):

➢ Please refer fig 4.3.52 for F- Gain function, this function provides the facility for setting the

frequency reference to more than one inverter set by a master potentiometer then the master

frequency can be scaled by three individual potentiometers for each inverter as show in the

diagram below.

➢ Please refer table 4.3.34, when 04-16=1 and 00-05=2, AI1 will be master signal, AI2 will be ratio

signal.

Table 4.3.34 Parameter setting of F-Gain

Figure4.3.52F-Gainexample:threeblocksA0–100Hz,B0–200Hz,C0–50Hz;each10V,AI1,AI2,AGND;MasterpotentiometerandratioA/B/C. Wireimage retained;no topology supplied beyond labels.

Figure4.3.53F-Gainplot:verticalFrequencyupperlimit(Hz),horizontalAnalogInputSignalMaster. Three raysB200Hz,A100Hz,C50Hz;dashedguides toB/A/C andrateC/rateA/rateB. No interpolation inferred.

Analog output monitor mappings and F-Gain example

04-11 parameter setting / Function (Keypad display) / Monitoring Parameters 12 Group / Control Mode — PDF page 207

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 04-11 parameter setting Function (Keypad display) Monitoring Parameters 12 Group Control Mode Control Mode Control Mode
2 04-11 parameter setting Function (Keypad display) Monitoring Parameters 12 Group VF SLV PMSLV
3 0 Output Freq 12-17 O O O
4 1 Freq Ref 12-16 O O O
5 2 Output Voltage 12-19 O O O
6 3 DC Voltage 12-20 O O O
7 4 Output Current 12-18 O O O

A / B / C — PDF page 207

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 A B C
2 00-05=2 00-05=2 00-05=2
3 00-12=100 00-12=200 00-12=50
4 04-16=1 04-16=1 04-16=1

Manual — Analog output filtering and voltage correction — page 208

Manual reference: physical PDF page 208. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Setting of parameter 04-20 is used for filtering momentary change in analog output signal.

When it is enabled, system response will lower down and interference protection will enhance.

➢ This function is used for analog voltage correction. Normally, analog voltage does not need to be correction. If necessary, please connect AO and AI2 terminal and set 04-22=1, inverter will execute analog voltage correction. 04-22 will be cleaned to 0 automatically when voltage correction function finished.

Analog output filtering and voltage correction

04-20 / AO signal scanning and filtering time — PDF page 208

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 04-20 AO signal scanning and filtering time
2 Range 【0.00~0.50】Sec

04-22 / AO Voltage Correction Selection — PDF page 208

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 04-22 AO Voltage Correction Selection
2 Range 【0~1】

Manual — Group05 preset speeds and individual ramp parameters;continues210 — page 209

Manual reference: physical PDF page 209. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 05 Preset Frequency Selection

Group05 preset speeds and individual ramp parameters;continues210

05- 00 / Preset Speed Control Mode Selection — PDF page 209

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 05- 00 Preset Speed Control Mode Selection
2 Range 【0】:Acceleration and deceleration time 1 ~ 4 used. 【1】:Use independent acceleration and deceleration time for each multi-speed setting.
3 05- 01 Preset Speed 0
4 05- 02 Preset Speed 1
5 05- 03 Preset Speed 2
6 05- 04 Preset Speed 3
7 05- 05 Preset Speed 4
8 05- 06 Preset Speed 5
9 05- 07 Preset Speed 6
10 05- 08 Preset Speed 7
11 05- 09 Preset Speed 8
12 05- 10 Preset Speed 9
13 05- 11 Preset Speed 10
14 05- 12 Preset Speed 11
15 05- 13 Preset Speed 12
16 05- 14 Preset Speed 13
17 05- 15 Preset Speed 14
18 05- 16 Preset Speed 15
19 Range 【0.0~599.00】 Hz
20 05-17 Preser Speed 0-Acc time
21 05-18 Preser Speed 0-Dec time
22 05-19 Preser Speed 1-Acc time
23 05- 20 Preser Speed 1-Dec time
24 05- 21 Preser Speed 2-Acc time
25 05- 22 Preser Speed 2-Dec time
26 05- 23 Preser Speed 3-Acc time
27 05- 24 Preser Speed 3-Dec time
28 05- 25 Preser Speed 4-Acc time
29 05- 26 Preser Speed 4-Dec time
30 05- 27 Preser Speed 5-Acc time
31 05- 28 Preser Speed 5-Dec time
32 05- 29 Preser Speed 6-Acc time
33 05- 30 Preser Speed 6-Dec time
34 05- 31 Preser Speed 7-Acc time
35 05- 32 Preser Speed 7-Dec time
36 05- 33 Preser Speed 8-Acc time
37 05- 34 Preser Speed 8-Dec time
38 05- 35 Preser Speed 9-Acc time
39 05- 36 Preser Speed 9-Dec time

Manual — Individual ramp continuation, formulas and examples — page 210

Manual reference: physical PDF page 210. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ When 05-00=0, accel/decal set by parameter 00-14~00-17/00-21~00-24. ➢ When 05-00=1, individual accel/decal apply to each preset speed 0~15, parameters 05-17~05-48. ➢ Formula for calculating acceleration and deceleration time:

➢ When 01-00=F, maximum output frequency set by 01-02.

➢ When 01-00≠F, maximum output frequency is 50.00 (or 60.00/90.00/120.0/180.0)

Example:

01-00≠F, 01-02=50Hz (maximum output frequency), 05-02=10Hz (presser speed 1),

05-17=5s (Accel-time), 05-18=20s (Decel-time)

Acceleration/Deceleration timing when 05-00=1 is set to 1.

In this example the following parameters are set:

00-02=1 (External terminal operation)

S1:03- 00=0 (Terminal S1:Forward/stop)

S2:03- 01=1 (Terminal S2:Reverse/stop)

S3:03- 02=2 (Terminal S3:Preset speed 1)

S4:03- 03=3 (Terminal S4:Preset speed 2)

S5:03- 03=4 (Terminal S5:Preset speed 3)

Source formulas:Actualacceltime=[Timeofaccel1or2 xPresetFrequency]/BaseFrequency;Actualdeceltime=[Timeofdecel1or2 xPresetFrequency]/BaseFrequency. Exactsourceformula,not validated.

Sourcepreset-speed1example:actualaccel=[(05-17)x10(Hz)]/01-02=1(s);actualdecel=[(05-18)x10(Hz)]/01-02=4(s). Earlier05-17/18rowslabelspeed0;retainconflict.

Individual ramp continuation, formulas and examples

05- 37 / Preser Speed 10-Acc time — PDF page 210

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 05- 37 Preser Speed 10-Acc time
2 05- 38 Preser Speed 10-Dec time
3 05- 39 Preser Speed 11-Acc time
4 05- 40 Preser Speed 11-Dec time
5 05- 41 Preser Speed 12-Acc time
6 05- 42 Preser Speed 12-Dec time
7 05- 43 Preser Speed 13-Acc time
8 05- 44 Preser Speed 13-Dec time
9 05- 45 Preser Speed 14-Acc time
10 05- 46 Preser Speed 14-Dec time
11 05- 47 Preser Speed 15-Acc time
12 05- 48 Preser Speed 15-Dec time
13 Range 【0.0~6000.0】 Sec

Manual — Mode1 acceleration/deceleration timing and formulas;priorreviewed212containsMode2 — page 211

Manual reference: physical PDF page 211. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Acceleration/Deceleration calculation of mode 1:

Example:

Mode1timing:Hz/T,threeFWDcyclesPresetSpeed0/05-01,Speed1/05-02,Speed2/05-03. RuncommandRUN/STOPeachcycle;S2OFF;S3ONsecondcycle;S4ONthirdcycle. Rampslabelsa/b,c/d,e/f respectively. No frequency values inferred.

Sourceformulas unit(sec):a=(05-17)x(05-01)/(01-02);b=(05-18)x(05-01)/(01-02);c=(05-19)x(05-02)/(01-02);d=(05-20)x(05-02)/(01-02);e=(05-21)x(05-03)/(01-02);f=(05-22)x(05-03)/(01-02).

Manual — Acceleration/Deceleration calculation of mode2 — page 212

Manual reference: physical PDF page 212. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source mode2 only. Every hyphenated code is a parameter identifier, not arithmetic subtraction inside the identifier. Formulas transcribed, not evaluated. No absolute-value or sign correction added.

Timing plot and merged signal regions retained in original. Labels, parameter associations and formulas captured; no geometric duration inferred.

Source final timing formula i uses05-19 and final lower plot label repeats19/20. Preserve these literals; do not silently replace with05-28 or27/28.

Printed state words only; merged spans do not imply one value per uniform time interval. Read original timing chart for edges and spans.

Command4 plotted below horizontal axis. No numeric frequency or parameter sign invented.

Each interval equals numerator divided by denominator. Source x multiplication and bracket structure preserved. Unit(sec) printed after formula block applies to calculations; no values calculated.

Diagram labels — PDF page 212

Source row Source label/context Source value
1 Vertical axis Hz
2 Horizontal axis T
3 Direction label Forward
4 Command/time markers a; b; c; d; e; f; g; h; i
5 Input traces S1; S2; S3; S4; S5
6 S1 printed states ON; OFF; STOP
7 S2 printed states OFF; ON
8 S3 printed states left-to-right OFF; ON; OFF; ON; OFF; ON; ON
9 S4 printed states left-to-right OFF; OFF; ON; ON; OFF
10 S5 printed states left-to-right OFF; OFF; OFF; OFF; ON; OFF
11 Lower parameter-pair labels left-to-right 17/18; 19/20; 21/22; 23/24; 25/26; 27/28; 19/20

Speed-command labels — PDF page 212

Source row Printed speed command Parameter label
1 Speed Command0 05-01
2 Speed Command1 05-02
3 Speed Command2 05-03
4 Speed Command3 05-04
5 Speed Command4 05-05
6 Speed Command5 05-06

Mode2 calculation formulas — PDF page 212

Source row Interval Printed numerator Printed denominator Printed unit
1 a (05-17) x (05-01) 01-02 sec
2 b (05-19) x [(05-02)-(05-01)] 01-02 sec
3 c (05-21) x [(05-03)-(05-02)] 01-02 sec
4 d (05-24) x [(05-03)-(05-04)] 01-02 sec
5 e (05-26) x (05-04) 01-02 sec
6 f (05-25) x (05-05) 01-02 sec
7 g (05-27) x (05-05) 01-02 sec
8 h (05-27) x (05-06) 01-02 sec
9 i (05-19) x (05-06) 01-02 sec

Manual — Group06 auto-run choices, frequency stages and operation time;continues214 — page 213

Manual reference: physical PDF page 213. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 06 Automatic Program Operation

Group06 auto-run choices, frequency stages and operation time;continues214

06- 00 / Auto Run Mode Select — PDF page 213

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 06- 00 Auto Run Mode Select
2 Range 【0】:Disable 【1】:Execute a single cycle operation. Restart speed is based on the previous stopped speed. 【2】:Execute continuous cycle operation. Restart speed is based on the previous cycle stop speed. 【3】:After completion of a single cycle, the on-going operation speed is based on the speed of the last stage. Restart speed is based on the previous stopped speed. 【4】:Execute a single cycle operation. Restart speed is based on the Speed-Stage 0. 【5】:Execute continuous cycle operation. Restart speed is based on the Speed-Stage 0. 【6】:After completion of a single cycle, the on-going operation speed is based on the speed of the last stage. Restart speed is based on the Speed-Stage 0

Range / 【0.00~599.00】Hz — PDF page 213

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Range 【0.00~599.00】Hz
2 Frequency setting of speed-stage 0 is based on parameter 05-01 Frequency setting of speed-stage 0 is based on parameter 05-01
3 06- 01 Frequency setting of speed-stage 1
4 06- 02 Frequency setting of speed-stage 2
5 06- 03 Frequency setting of speed-stage 3
6 06- 04 Frequency setting of speed-stage 4
7 06- 05 Frequency setting of speed-stage 5
8 06- 06 Frequency setting of speed-stage 6
9 06- 07 Frequency setting of speed-stage 7
10 06- 08 Frequency setting of speed-stage 8
11 06- 09 Frequency setting of speed-stage 9
12 06- 10 Frequency setting of speed-stage 10
13 06- 11 Frequency setting of speed-stage 11
14 06- 12 Frequency setting of speed-stage 12
15 06- 13 Frequency setting of speed-stage 13
16 06- 14 Frequency setting of speed-stage 14
17 06- 15 Frequency setting of speed-stage 15

Range / 【0.0~6000.0】Sec — PDF page 213

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Range 【0.0~6000.0】Sec
2 06- 16 Operation time setting of speed-stage 0
3 06- 17 Operation time setting of speed-stage 1
4 06- 18 Operation time setting of speed-stage 2
5 06- 19 Operation time setting of speed-stage 3
6 06- 20 Operation time setting of speed-stage 4

Manual — Auto-run time/direction continuation and exclusions — page 214

Manual reference: physical PDF page 214. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Auto run mode uses frequency reference parameters (05-01, 06-01~06-15), operation time parameters (06-16~06-31) and direction of operation parameter (06-32~06-47) ➢ Auto run mode can not be used when “Wobble Frequency function” or “PID function” is enabled. ➢ In auto run mode, multi-speed frequency reference of external signal 1~4 (03-00~03-07=2~5) is disabled.

Auto-run time/direction continuation and exclusions

06- 21 / Operation time setting of speed-stage 5 — PDF page 214

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 06- 21 Operation time setting of speed-stage 5
2 06- 22 Operation time setting of speed-stage 6
3 06- 23 Operation time setting of speed-stage 7
4 06- 24 Operation time setting of speed-stage 8
5 06- 25 Operation time setting of speed-stage 9
6 06- 26 Operation time setting of speed-stage 10
7 06- 27 Operation time setting of speed-stage 11
8 06- 28 Operation time setting of speed-stage 12
9 06- 29 Operation time setting of speed-stage 13
10 06- 30 Operation time setting of speed-stage 14
11 06- 31 Operation time setting of speed-stage 15

Range / 【0】:Stop 【1】:Forward 【2】:Reverse — PDF page 214

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Range 【0】:Stop 【1】:Forward 【2】:Reverse
2 06- 32 Operation direction selection of speed-stage 0
3 06- 33 Operation direction selection of speed-stage 1
4 06- 34 Operation direction selection of speed-stage 2
5 06- 35 Operation direction selection of speed-stage 3
6 06- 36 Operation direction selection of speed-stage 4
7 06- 37 Operation direction selection of speed-stage 5
8 06- 38 Operation direction selection of speed-stage 6
9 06- 39 Operation direction selection of speed-stage 7
10 06- 40 Operation direction selection of speed-stage 8
11 06- 41 Operation direction selection of speed-stage 9
12 06- 42 Operation direction selection of speed-stage 10
13 06- 43 Operation direction selection of speed-stage 11
14 06- 44 Operation direction selection of speed-stage 12
15 06- 45 Operation direction selection of speed-stage 13
16 06- 46 Operation direction selection of speed-stage 14
17 06- 47 Operation direction selection of speed-stage 15

Manual — Auto-run single/periodic cycle examples — page 215

Manual reference: physical PDF page 215. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Auto Run examples are shown as following.

(1) Single cycle (06-00=1,4) The inverter will run for a single full cycle based on the specified number of sequnces, thenit will stop. In this example, 4 sequences are set, three in forward direction and one in reverse direction.

(2) Periodic Cycle Run (06-00=2,5)

The inverter will repeat the same cycle periodically.

All other parameters are set same as “Example 1” shown above.

Figure4.3.52Singlecycleoperation(Stop). Printedsettings06-00=1;06-32~34=1;06-47=2(stage15reverse);06-35~46=0(stage3~14stop);05-01=15Hz(stage0);06-01=30Hz(stage1);06-02=50Hz(stage2);06-15=20Hz(stage15);06-16=20sec;06-17=25sec;06-18=30sec;06-31=40sec. Frequencyplot15,30,50Hzforward then20Hzbelowzero reverse,with20/25/30/40sduration arrows andthoseparameters. Source plottingonly.

Figure4.3.53Periodiccycle:two repetitions15Hz05-01/20s06-16;30Hz06-01/25s06-17;50Hz06-02/30s06-18;20Hzbelowzero labelled06-03/40s06-19. Prose says allparameterssameExample1,butupperexampleuses06-15/06-31. Literalplotlabels retained.

Manual — Auto-run held final stage and restart behaviour;Group06 concludes — page 216

Manual reference: physical PDF page 216. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(3) Auto Run Mode for Single Cycle (06-00=3,6)

The speed of final step will be held to run. (The final step must be put in stage 15)

All other parameters are set same as “Example 1” shown above.

➢ When 06-00=1~3:After a restart, it continues to run from the unfinished step.

➢ When 06-00=4~6:After a restart, it will begin a new cycle.

➢ ACC/DEC time in Auto run mode will be according to the setting of 00-14/00-15.

➢ For Auto sequence 0.The run frequency will be according to keypad frequency set by parameter

05-01.Parameters 06-16 and 06-31 are used to set the sequence Run time and Run direction.

Figure4.3.54AutoRunSingleCycle:15Hz05-01 for20s06-16,30Hz06-01for25s06-17,50Hz06-02for30s06-18,20Hzbelowzero06-15for40s06-31andcontinuesheld. Prose requiresfinalstepstage15.

Restart comparison table:06-00=1~3 left versus4~6right;RunCommandrun/stop/run. LeftOutputFrequencycontinuerunningfromunfinishedstep;rightbeginanewcycle. Bothtimeaxes;no numericfrequencyortimeinferred.

Manual — Group07 restart settings, eligible faults and source conditions — page 217

Manual reference: physical PDF page 217. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 07 Start/Stop Parameters

When 07-00=1, If the input power supply due to sudden increase in supply demand by

other equipment results in voltage drops below the under voltage level, the inverter will

stop its output at once.

➢ 07-00=0:When power loss exceed 2ms, “UV fault” will be detected.

➢ 07-00=1:Aafter a momentary power loss, inverter will restart with half frequency

before power loss, and there is no limitation on number of restarts.

The automatic restart function is active for the following faults. Please note that when the fault is not

listed in the table the inverter will not attempt an automatic restart.

Notes:

(1) Fault restart function contains momentary power loss restart and auto reset restart.

(2) Refer to chapter 10 for the details of troubleshooting and fault diagnostics.

(3) Refer to speed search function (07-19~07-24) for the selection of speed search modes.

Group07 restart settings, eligible faults and source conditions

07- 00 / Momentary power loss and restart — PDF page 217

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 00 Momentary power loss and restart
2 Range 【0】:Disable 【1】:Enable
3 07- 01 Fault reset time
4 Range 【0~7200】 Sec
5 07- 02 Number of restart attempts
6 Range 【0~10】
7 07- 03 Reset Mode Setting
8 Range 【0】:Enable Reset Only when Run Command is Off 【1】:Enable Reset when Run Command is On or Off

Parameter / Faults / Number of Restart — PDF page 217

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Parameter Faults Number of Restart
2 07-00 UV (Under Voltage) Unlimited
3 07-01 07-02 OC: Over current OCA: Over current in acceleration OCC: Over current in constant speed OCd: Over current in deceleration OL1: motor overload UT: Under torque detection IPL: Input phase loss GF: Ground failure OV: Overvoltage OL2: Inverter overload OT: Over-torque detection OPL: Output phase loss CF07: SLV motor control setting fault CF08: PMSLV motor control setting fault Depend on parameter 07-02

Manual — Automatic restart interval, counter reset and operating sequence — page 218

Manual reference: physical PDF page 218. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Fault reset time (07-01)

Restart time of momentary power loss is the same as Fault reset time.

07-01 <07-18:Automatic restart time interval is set by minimum baseblock time (07-18).

07-01> 07-18:Automatic restart time interval is set by fault reset time (07-01).

Note:

Automatic restart time interval is time of 07-18 plus 07-01 and delay time of peed search (07-22).

Refer to Figure 4.3.55 for automatic restart interval.

Figure 4.3.55 Automatic restart interval

➢ Number of restart attempts (07-02)

If numbers of fault reset reaches the setting value of 07-02, then inverter stops running. So manual

to restart the inverter after eliminating fault causes.

When the automatic restart function is enabled the internal automatic restart attempt counter is

reset to 0 based on the following actions。

(1) No fault occurs in 10 minutes or longer after the automatic restart

(2) Reset command to clear fault via input terminal or using keypad (press reset/ key)

(3) Power to the inverter is turned off and back on again

Note:

Multi-function digital output R1A-R1C, R2A-R2B, or optocoupler output can be programmed to

activate during an automatic reset attempt, refer to parameter 03-11, 03-12.

➢ Automatic restart operation: (1) Fault is detected. The inverter turn off the output, displays the fault on the keypad and waits for the minimum baseblock time parameter 07-18 to expire before accepting another run /automatic restart command. (2) After the minimum baseblock time (07-18) and delay time of speed search have expired, the active fault is reset and a speed search operation is performed. The time between each fault restart attempt is set by parameter 07-01. (3) When the total number of restart attempts exceed the number of automatic restartattempts set in parameter 07-02, the inverter will turn off the output and the fault contact is activated.

Figure4.3.55 automatic restart interval:ten pulses numbered1–10,10arrow07-02. Period label07-01+07-22 or07-18+07-22. No numeric duration inferred. Prose above separately sums07-18+07-01+07-22;retain difference.

Manual — Restart mode, power-up run conditions and danger warnings — page 219

Manual reference: physical PDF page 219. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Please refer to figure 4.3.56 for the automatic restart operation.

Figure 4.3.56 Auto-restart operation

➢ Reset Mode Setting (07-03)

When 07-03=0, after inverter fault detection, the input power must be turned off and then turn on

to perform reset function. Otherwise, inverter can not be restarted.

(When 00-02=1, reset mode function is active)

Important : Inverter will be damaged when auto restart function executes frequently.

➢ Momentary Power Loss and Restart (07-04)

07-04=0:When direct run on power up is selected by 07-04=0 and the inverter is set to external

run by (00-02/00-03=1), if the run switch is ON as power is applied, the inverter will auto

start.

07-04=1:When direct run on power up is disabled by 07-04=1 and if the inverter is set to external

run by (00-02/00-03=1), if the run switch is ON as power is applied, the inverter will not

auto start and the display will flash with STP1. It will be necessary to turn OFF the run

switch and then turn ON again to start normally

➢ Delay-ON Timer (07-05)

If 07-04=0, it will count the delay time set by 07-05 first when the inverter starts directly at

power on. When the delay time is completed, it starts to run.

!DANGER: When 07-04=0 and the external run is set (00-02/00-03=1) If the operation switch is conducted at power up, the inverter starts automatically. It is suggested to turn off the power switch and operation switch at power failure to avoid the damage to the user or the machine when the inverter reconnects. When 07-04=1 and the external run is set (00-02/00-03=1) If the operation switch is not conducted at power up, the inverter is not able to start and the warning signal of STP1 flashes. It is required to turn off the operation switch first and they delay of direct start at power up is completed. The make it be conducted to start the inverter.

Figure4.3.56 autorestart:FaultMessage high whileOutputFrequency zero;labelled07-18+07-22 interval. Outputfrequency then resumes,descends and ramps back to original plateau. Timeaxes;no numericfrequency/duration inferred.

Restart mode, power-up run conditions and danger warnings

07- 04 / Momentary Power Loss and Restart — PDF page 219

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 04 Momentary Power Loss and Restart
2 Range 【0】:Enable Direct Running on Power Up 【1】:Disable Direct Running on Power Up
3 07- 05 Delay-ON Timer
4 Range 【1.0~300.0】 Sec

Manual — VF/SLV DC braking and PMSLV short-circuit braking — page 220

Manual reference: physical PDF page 220. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Both braking figures have a visible box after Note. All visible numeric labels and separate V/F or SLV (00-00=0,2) versus PMSLV (00-00=5) contexts are retained. The box is not a missing numeric value; no replacement punctuation is asserted.

➢ The braking act according to the different control modes (00-00), please refer to the following descriptions

(1) When control mode is V/F or SLV (00-00=0, 2):

➢ It start DC injection braking by the time 07-16. Deceleration to stop is according to 07-06 and

07-08. When output frequency is lower than 07-06 in deceleration time, it start DC injection

braking by the time 07-08.

Figure 4.3.57a VF and SLV DC injection braking

Note:When 07-06 < 01-08, it start DC injection braking by the setting frequency (01-08).

(2) When control mode is PMSLV (00-00=5): ➢ Please refer fig 4.3.57b for short-circuit braking function. ➢ DC braking current level is setting by parameter 07-07, based on 100% rated current of inverter. Besdies, if the DC braking current level is higher than motor rated current, DC braking current will be locked at motor rated current. ➢ Short-circuit braking current limit is setting by parameter 07-36, based on 100% rated current of inverter.

Figure 4.3.57b PMSLV short-circuit braking

Note:

When 07-06 < 01-08, it start short-circuit braking by the setting frequency (01-08)

Figure4.3.57a VF/SLV:Outputfrequency rises frominitial DCinjectionbraking interval07-16,plateaus,decelerates to07-06or01-08 thenDCinjectionbraking interval07-08. Note boxglyph unrendered.07-06brakingstartfrequency,01-08minimumfrequency. No plot-derived numericvalue.

Figure4.3.57b PMSLV:Outputfrequency starts afterShort-Circuitbraking07-34,rises/plateaus/falls to07-06or01-08 thenShort-Circuitbraking07-35. Note boxglyph unrendered;samefrequencydefinitions. Source labels only.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Both braking plots show unrendered glyph after Note; visible definitions and conditions preserved, missing glyph not inferred.

VF/SLV DC braking and PMSLV short-circuit braking

07- 06 / DC Injection Braking Start Frequency — PDF page 220

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 06 DC Injection Braking Start Frequency
2 Range 【0.0~10.0】Hz

Manual — Braking times/current and terminal control — page 221

Manual reference: physical PDF page 221. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Set parameter 07-06, 07-08 and 07-16 for DC injection braking related function.

➢ When inverter executes speed search function, DC injection braking function should be

disabled.

➢ To enable DC injection braking during a start operation set the DC injection braking current

(07-07) and the DC injection braking time (07-16) at start to a value greater than 0. DC injection

braking at start can be used to prevent “wind milling effect” in fan applications.

➢ To enable DC injection braking during a stop operation set the DC injection braking current

(07-07) and the DC injection braking time at stop (07-08) to a value greater than 0.

➢ When parameter 07-16 is set to 0 sec (DC injection braking off). the inverter will start from the

minimum output frequency duration of DC injection braking during a stop operation. DC

injection braking at stop is disabled when parameter 07-08 is set to 0 sec. If output frequency is

less than 07-06, injection braking function will be enabled. Inverter output will be cut off and

then DC injection braking is started.

➢ During stop operation: If the DC braking start frequency < minimum output frequency (01-08),

DC braking is active when the output frequency reaches the minimum output frequency level.

➢ DC injection braking level can be set by parameter 07-07 in acceleration and deceleration, DC

injection current can be part of output rated current. (Suppose rated current of inverter is

100%)

➢ Increasing the DC braking current (07-07) can reduce the motor stop time.

➢ DC braking operation can be controlled via any one of the multi-function input terminals(03-00

to 05) function 33. Refer to figure 4.3.57 for DC braking operation.

➢ PMSLV is available for short-circuit braking. Short-circuit braking is the way to switch IGBT to

produce braking torque. 07-06, 07-34 and 07-36 can adjust the braking process.

➢ If 07-35=0, Inverter start from the minimum frequency.

➢ The value of 07-36 is depend on differential motor rated current.

➢ 03-00~03-07=65 can control Short-circuit braking.

Braking times/current and terminal control

07- 07 / DC Injection Braking Level — PDF page 221

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 07 DC Injection Braking Level
2 Range 【0~100】%
3 07- 08 DC Injection Braking time
4 Range 【0.00~100.00】Sec
5 07- 16 DC injection braking time at start
6 Range 【0.00~100.00】Sec

07- 34 / Start short-circuit braking time — PDF page 221

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 34 Start short-circuit braking time
2 Range 【0.00~100.00】Sec
3 07- 35 Stop Short-circuit braking time
4 Range 【0.00~100.00】Sec
5 07- 36 Short-circuit braking current limited
6 Range 【0.0~200.0】%

Manual — Stop modes and deceleration/coast conditions;continues223 — page 222

Manual reference: physical PDF page 222. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When a stop command is issued the inverter stops according to the stop mode selected. There are

four types of stop modes.

Note:PM motor only can select “deceleration to stop mode” and “coast to stop mode”.

(1) 07-09=0:Deceleration to stop ➢ When a stop command is issued, the motor will decelerate to the minimum output frequency (01-08) Fmin and then stop. Deceleration rate depends on the deceleration ime (factory default is 00-15). ➢ When the output frequency reaches the DC braking stop frequency (07-06) or the minimum output frequency (01-08), DC injection braking is activated and the motor stops.

S curve setting will add to the overall stop time, refer to figure 4.3.58

Figure 4.3.58 Deceleration to stop

(2) 07-09=1:Coast to stop

➢ When a stop command is issued, the motor will coast to a stop. Stop time depends on motor

load and friction of the system.

➢ The inverter waits for the time set in the minimum baseblock time (07-18) before accepting the

next run command.

➢ In SLV mode (00-00=2) the speed search function is automatically enabled upon the next run

command. If the mechanical barking will be used to stop the motor when run command is

removed, please set 07-26=1.

Deceleration time=[Output frequency when stop command is issued / Maximum output frequency(01-02)] x deceleration time setting. Literalsourceformula.

Figure4.3.58:RunCommand Run→Stop;OutputFrequency decelerationramp to07-06,thenT DCbrakingtimeatstop(07-08). HorizontalTime;S-curve addition described inprose.

Stop modes and deceleration/coast conditions;continues223

07- 09 / Stop Mode Selection — PDF page 222

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 09 Stop Mode Selection
2 Range 【0】:Deceleration to stop 【1】:Coast to stop 【2】:DC braking to stop 【3】:Coast to stop with timer

Manual — Coast/DC braking/timed-coast continuation — page 223

Manual reference: physical PDF page 223. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: The tb.b and tDCDB definition separators visibly render boxes. Prose literally references Figure 4.4.60, while the displayed caption is Figure 4.3.60. Preserve both references and the visible fraction formula; do not repair the figure number or infer the missing separator.

Figure 4.3.59 Coast to Stop

(3) 07-09=2:DC braking to stop

➢ When a stop command is issued, the inverter will turn off the output (Baseblock) and after the

minimum Baseblock time (07-18) has expired activate DC braking (07-07).

➢ The DC braking time (tDCDB) of Figure 4.4.60 is determined by the value of 07-08 (DC Braking

start time) and the output frequency at the time the stop command was issued.

➢ Increase the minimum Baseblock time (07-18) in case an Overcurrent trip occurs during the DC

braking.

Figure 4.3.60 DC braking to stop

(4) 07-09=3:Coast to stop with timer

➢ When a stop command is issued the motor will coast to a stop after the minimum

Baseblock time (07-18) has expired. The inverter ignores the run command until the

total time of the timer has expired.

➢ The total time of the timer is determined by the deceleration time (00-15, 17, 22 or 24) and the

output frequency upon stop.

➢ Refer to figure 4.3.61.

Figure4.3.59CoasttoStop:RunCommand Run/Stop/Run;OutputFrequency drops tozero duringstop,rampsafterlaterRun. tbb intervalMinimum baseblocktime07-18.

tDCDB=[(07-08)x10xOutputFrequency]/Fmax(01-02). Literal DCbrakingtime formula.

Figure4.3.60 left:OutputFrequency label,Run/Stoptrace,lowerbrakingtrace separatedby tb.b andtDCDB. tb.b Minimum baseblocktime07-18,tDCDB DCbrakingtime;definitionseparatorsrenderboxes. RighttDCDB vertical labels07-08x1/07-08x10 againstMaximumoutputfrequencyFmax01-02 horizontal10%/100%;linebetweenmarkedpoints andOutputfrequencyuponstopcommand. No interpolation.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: DC-braking plot tb.b and tDCDB definition separators render as boxes. No replacement symbol inferred.

Manual — Timed-coast plot, speed search selection and low-voltage detection — page 224

Manual reference: physical PDF page 224. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Figure 4.3.61 has a visible box between T1 and Total time. Other trace labels are readable. Preserve the explicit restriction that speed search is unavailable for PMSLV 00-00=5 Frame1 and Frame2; the box does not authorize a timing relationship beyond the printed diagram.

Figure 4.3.61 Coast to stop with timer

➢ Speed search function is used to find the speed of a coasting motor and continue operation from that point. The speed search function is active after a momentary power loss. (1) When 07-10=0, the inverter start to run from the lowest output frequency but it won’t limit the other functions of trigger speed search. (2) When 07-10=1, the inverter executes a speed search at power on when entering first run command. It start the motor from found frequency. (3) When 07-10=2, the speed search function is performed every time when the run command in input. Notes: When 00-00=5 (PMSLV control mode), Frame1 and Frame2 models without this function.

➢ Adjust the 07-13 voltage level from 150 to 300 Vdc (200V class) or from250 to 600 Vdc

(400V class).

➢ When the AC input voltage is lower than the 07-13 value (07-13/ 1.414=AC voltage detection

level) for the time specified in 07-25 the low-voltage error "UV" will displayed. If 07-25=0.00

sec., the UV error will be displayed immediately.

Set preventive measures:

(1) The inverter input voltage will limit the output voltage. If the input voltage drops excessively, or

if the load is too big, the motor may stall.

(2) If the input voltage drops below the value set in 07-13 then the output is turned off

momentarily. The inverter will not automatically start when power is restored.

Figure4.3.61 timedcoast:leftRun/Stop/Run/Stop/Runcommand;outputzero untilfinalRunafterT1total-timeinterval. T1definitionseparatorunrendered. RightT1vsMaximumoutputfrequencyFmax01-02:10%atminimum baseblocktime tb.b07-18;100%atdecelerationtime(e.g.00-15). No numeric seconds inferred.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Timed-coast T1 definition separator renders as box. Visible timing labels retained.

Timed-coast plot, speed search selection and low-voltage detection

07- 10 / Speed Search Mode Selection — PDF page 224

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 10 Speed Search Mode Selection
2 Range 【0】:Disable 【1】:Execute speed search once 【2】:Speed Search Start

07- 13 / Low voltage detection level — PDF page 224

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 13 Low voltage detection level
2 Range 【200V Class:150~300V】 【400V Class:250~600V】
3 07- 25 Low voltage detection time
4 Range 【0.00~1.00】Sec

Manual — Minimum baseblock and speed-search parameters — page 225

Manual reference: physical PDF page 225. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ In case of a momentary power failure, the inverter continues to operate after the power has

been restored when parameter 07-00 is set to 1.

➢ Once the momentary power failure is detected; the inverter will automatically shut

down the output and maintain B.B for a set time (07-18).

➢ When the momentary power failure time exceeds the minimum base block time

(07-18), the inverter will automatically perform a speed search upon return of power.

Refer to the following figure 4.3.63。

Figure 4.3.63 Minimum B.B time and momentary power loss time

➢ Minimum base block time (07-18) is also used to for the DC braking function

➢ Set the minimum base block time required (07-18).

➢ Increase minimum Baseblock time if over-current "OC" condition occurs.

➢ Speed search function is used to find the speed of a coasting motor and continue operation

from that point. The speed search function is active after a momentary power loss.

Figure4.3.63 comparison:three tracesMomentarypowerloss,MinimumB.B.Time07-18,InverterB.B.time. (a)07-18greaterthanpowerlosstime:inverterB.B.remainsuntil07-18end. (b)07-18shorterthanpowerlosstime:inverterB.B.lastsuntilpowerreturn. Allhorizontalaxes t;no durations inferred.

Minimum baseblock and speed-search parameters

07- 18 / Minimum base block time — PDF page 225

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 18 Minimum base block time
2 Range 【0.1~5.0】Sec

07- 19 / Speed Direction Search Operation Current — PDF page 225

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 19 Speed Direction Search Operation Current
2 Range 【0~100】%
3 07- 20 Speed Search Operating Current
4 Range 【0~100】%
5 07- 21 Integral time of speed searching
6 Range 【0.1~10.0】Sec
7 07- 22 Delay time of speed searching
8 Range 【0.0~20.0】Sec
9 07-23 Voltage recovery time
10 Range 【0.1~5.0】Sec
11 07- 24 Direction-Detection Speed Search Selection
12 Range 【0】:Disable 【1】:Enable
13 07- 33 Start Frequency of Speed Search Selection
14 Range 【0】:Maximum Output Frequency of Motor 【1】:Frequency Command

Manual — External search command conditions, tuning and current/delay settings — page 226

Manual reference: physical PDF page 226. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Set the multi-function digital input to external speed search command 1 or 2. External speed

search command 1 (value = 19) and 2 (value = 34) cannot be set at the same time, otherwise

"SE02" (digital input terminal error) warning occurs.

➢ Speed search function must be enabled before applying the run command to ensure proper

operation.

Figure 4.3.64 Speed search and operation commands

➢ The speed search cannot be used when the motor rated power is greater than the inverter

rated power.

➢ In V / F mode, it is necessary to perform a static auto-tune.

➢ In SLV mode, it is necessary to perform a rotational auto-tune. Perform a static auto-tune when

using long motor leads.

➢ Speed Direction Search Operating Current (07-19)

(1) Used in bidirectional speed search only (07-24 = 1).

(2) Set bidirectional current level.

(3) Increase value if speed search is not successful at low speeds (above 5Hz)

Note:

If value is too high may cause DC braking effect.

➢ Speed Search Operating Current (07-20)

(1) Can be used for bidirectional (07-24 = 1) or unidirectional (07-24 = 0) speed search.

(2) Sets speed search current Level.

(3) The set value must be lower than the excitation current (02-09) and must equal to the no-load

current. If the no-load current is unknown it is recommended to set value at 20%.

(4) Excessive speed search current will cause inverter output to saturate.

(5) It is recommended to use speed search in case of a momentary power loss. Increase the

minimum base block time (07-18) in case of an over-current condition.

➢ Integral time of speed searching (07-21)

(2) Set the integral time during speed search.

(3) If OV occurs, increase the set value to increase the speed search time. Decrease the value if a

quick start is required.

➢ Delay time of speed searching (07-22)

(1) Use delay time (07-22) when using a contactor on the inverter output side.

(2) Speed search delay time is disabled when set to 0.0 sec. (07-22 = 0.0)

Figure4.3.64 source schematic labelsRy1,Speedsearchcommand;Rv1contact,Ry2,Runcommand. Labels and visible symbols retained in image; no inferred wiring topology.

Manual — Search direction, recovery and SLV/baseblock restart selections — page 227

Manual reference: physical PDF page 227. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Voltage recovery time (07-23). (1) Sets the voltage recovery time. (2) Sets the time for the inverter to restore the output voltage from 0V to the specified V/f level after speed search function is completed.

➢ Direction-Detection Speed Search (07-24):

(1) 07-24=1, enable direction-detection speed search:

At start the current controller will send a step current to the motor (07-19) to determine the motor

direction. Once direction is determined the current controller will perform a speed search using

speed search operating current defined in parameter 07-20. Speed search is executed after a

momentary power loss (external speed search command 2, 03-00 to 03-05=34) or from max.

frequency (external speed search command 1, 03-00 to 03-05=19). Speed search direction will

follow the speed command.

(2) 07-24=0, disable direction-detection speed search:

Speed search is executed using speed search operating current defined in parameter 07-20. In case

speed search is not successful (e.g. motor speed is too low) a speed search time-out warning is

displayed. Set 07-19 to value greater than 0 to enable DC braking at speed search if a time-out

occurs frequently.

➢ Start-Up Mode Selection of SLV Coast to Stop (07-26)

(1) When 07-26=0,speed search function is enabled. (default setting)

(2) When 07-26=1,normal start

(3) In SLV mode (00-00=2) set the stop mode to the coast stop (07-09=1) or to the coast to stop

with timer (07-09=3). After a stop command is issued (coast to stop or coast to stop with times)

the speed search function is automatically actived for the next start. ➢ Start Selection after Fault During SLV Mode (07-27)

(1) When 07-27=0,speed search function is enabled. (default setting)

(2) When 07-27=1,normal start

Notes:

Set the parameter to 1 (normal start) after fault has occurred and mechanical brake is used to

stop the motor.

➢ Start after External BaseBlock (07-28)

(1) When 07-28=0,speed search function is enabled. (default setting)

(2) When 07-28=1,normal start

Set parameter to 1 for the control mode of V/F mode (00-00=0) or SLV mode (00-00=2) when the

external base blockactive time is longer than the time the motor needs to come to a complete stop.

After the external base block command is removed, the inverter will accelerate from minimum

frequency.

Manual — Speed-search start and power-recovery timing — page 228

Manual reference: physical PDF page 228. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Start Frequency of Speed Search Selection (07-33)

(1) When 07-33=0, the start speed search from the maximum output frequency of motor.

(2) When 07-33=1, the inverter start speed search from setting frequency command.

(a) Speed search at starting

Figure 4.3.65 Speed search at starting

(b) Speed search in recovery period of momentary power failure

Figure 4.3.66 Speed search in recovery period of momentary power failure

Note:

➢ If the minimum base block time (07-18) is longer than the momentary power failure

time, the speed search starts operation after the minimum base block time (07-18).

➢ If the minimum base block time (07-18) is too short, the speed search operation begins

immediately after power has been restored.

Figure4.3.65 start:Searchcommand precedesRuncommand;07-22delay beforeoutput. Outputfrequency initiallyhigh thenfalls/levels/rises;declinelabel07-21. Outputvoltage initialramp,V/Fduringspeedsearch,returntonormalvoltage,recovery07-23. Currenttracearound07-20;Speedsearchoperation interval labelled. No unlabeled limits inferred.

Figure4.3.66 powerrecovery:Momentarypowerlossbriefdrop;MinimumB.B.time07-18longerdrop;Run/Searchcommandsremainhigh. Outputfrequency/voltage/currentdropthenrecover after07-18;frequencyfalllabel07-21;voltageV/Fduringspeedsearch and07-23recovery;current07-20;Speedsearchoperationinterval. Prose retains short/long powerloss cases.

Manual — Run during DC braking and pre-excitation settings — page 229

Manual reference: physical PDF page 229. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ After DC braking action starts, if run command selection is set to 0, it will not run until DC

braking action ends. If run command election is set to 1, it is not required to wait for the ending

of DC braking action. It can run during DC braking action process.

➢ If a high starting torque is required for the application, especially for a large horsepower motors,

the pre-excitation operation can be used to pre-flux (magnetize) the motor.

(1) When an operation command (forward or reverse) is activated, the inverter will automatically

start pre-excitation based on the time set in parameter 07-37.

(2) The time for the flux to reach 100% is a function value of motor’s electrical time constant, see

figure 4.3.62.

(3) Electrical time constant (quadratic by-pass circuit time constant) can be calculated by

motor parameter setting (group 02).

(4) Set the pre-excitation time (07-37) based on the electrical time constant T2

(1) Use the pre-excitation initial level (07-38) to provide a higher excitation current during the pre-excitation time (07-37), which will increase the speed and stability for motors. (2) In order to quickly magnetize the motor, reduce the pre-excitation time (07-37) and set the pre-excitation level (07-38) to a high level. (3) If 07-38 is set greater than 100%, providing a high excitation current during the pre-excitation time (07-37), motor’s magnetization time is shorted. When the setting reaches 200%, magnetization is reduced by roughly half. (4) A high pre-excitation level (07-15) might result in excessive motor sound during pre-excitation. (5) When the flux reaches 100%, pre-excitation current reverts back to 100% and pre-excitation is completed, refer figure 4.3.62。

ElectricaltimeconstantT2=[Motorleakageinductance02-17+motormutualinductance02-18]/Motorleakageresistance. Exactsourceformula,denominatornoexplicitparameteridentifier.

Run during DC braking and pre-excitation settings

07- 29 / Run Command Selection at the Action of DC Braking — PDF page 229

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 29 Run Command Selection at the Action of DC Braking
2 Range 【0】:Not Allowed to Run 【1】:Allowed to Run

07- 37 / Pre-excitation time — PDF page 229

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 37 Pre-excitation time
2 Range 【0.00~10.00】Sec

07- 38 / Pre-excitation level — PDF page 229

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 38 Pre-excitation level
2 Range 【50~200】%

Manual — Pre-excitation plot, PM braking and STP2 — page 230

Manual reference: physical PDF page 230. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.62 Pre-excitation operation

➢ If the motor speed lower than inverter control speed, inverter can stop the motor by parameter 07-39 and 07-40 and restart. If the motor speed higher than inverter control speed, inverter will be started by actual speed, no matter the setting value of parameter 07-39 and 07-40.

➢ If STP2 is enabled, when 00-02=1 and external operation signal is tripped, keypad will display “Terminal STOP” error when stop command comes from keypad. ➢ If STP2 is disabled, when 00-02=1 and external operation signal is tripped, keypad will not display “Terminal STOP” error when stop command comes from keypad.

Figure4.3.62:RuncommandON;Excitationcurrent steps toPre-excitationinitiallevel07-38 then100%whenMagneticflux reaches100%;Motorspeed then ramps. Pre-excitationtimearrow spans excitationstepuntilflux100%. No numericseconds inferred.

Pre-excitation plot, PM braking and STP2

07- 39 / Short-Circuit Braking Time of PM Motor Speed Search Function — PDF page 230

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 39 Short-Circuit Braking Time of PM Motor Speed Search Function
2 Range 【0.00~100.00】Sec
3 07- 40 DC injection Braking Time of PM Motor Speed Search Function
4 Range 【0.00~100.00】Sec

07- 45 / STP2 Function Selection — PDF page 230

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 45 STP2 Function Selection
2 Range 【0】:STP2 is enabled 【1】:STP2 is disabled

Manual — Group08 stall prevention parameters and VF-only scope — page 231

Manual reference: physical PDF page 231. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 08 Protection Parameters

Note:Stall prevention function only can be set in V/F control mode.

➢ Stall prevention during acceleration (08-00=xxx0b)

(1) Prevents the inverter from faulting (Overcurrent, Motor overload, Inverter overload) when

accelerating with heavy loads.

(2) When the inverter output current reaches the level set in parameter 08-01 minus 15% the

acceleration rate starts to decrease. When the inverter output current reaches the level set in

parameter 08-01 the motor stops accelerating.

(3) Reduce stall prevention level during acceleration (08-01) in case the motor stalls (when the

motor power is smaller than the inverter rating.

Group08 stall prevention parameters and VF-only scope

08- 00 / Stall prevention function — PDF page 231

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 00 Stall prevention function
2 Range 【xxx0b】:Stall prevention function is enabled during acceleration. 【xxx1b】:Stall prevention function is disabled during acceleration. 【xx0xb】:Stall prevention function is enabled during deceleration. 【xx1xb】:Stall prevention function is disabled during deceleration. 【x0xxb】:Stall prevention function is enabled during operation. 【x1xxb】:Stall prevention function is disabled during run. 【0xxxb】:Stall prevention function during run is based on the first deceleration time. 【1xxxb】:Stall prevention function during run is based on the second deceleration time.
3 08- 01 Stall prevention level during acceleration
4 Range 【20~200】%
5 08- 02 Stall prevention level during deceleration
6 Range 200V :【330V~410V】 400V :【660V~820V】
7 08- 03 Stall prevention level during run
8 Range 【30~200】%
9 08-21 Limit of stall prevention during acceleration
10 Range 【1~100】%
11 08-22 Stall prevention detection time during run
12 Range 【2~100】mSec
13 08- 40 Motor 2 Acceleration Stall Prevention Level
14 Range 【20~200】%
15 08-41 Motor 2 Acceleration Stall Prevention Limit
16 Range 【1~100】%

Manual — Acceleration stall formulas/limits and deceleration conditions — page 232

Manual reference: physical PDF page 232. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Please refer fig.4.3.67 for stall prevention during acceleration.

Figure 4.3.67 Stall prevention during acceleration

(4) If the motor is used in the constant power (CH) region, the stall prevention level (08-01) is

automatically reduced to prevent the stall.

(5) Stall prevention level during acceleration (Constant horsepower)

(6) Parameter 08-21 is the stall prevention limit value in Constant Horsepower region.

Please refer figure 4.3.68

Figure 4.3.68 Stall prevention level and limit in acceleration

(7) Motor2 Acceleration Stall Prevention Level (08-40) and Motor2 Acceleration Stall Prevention

Limit (08-41) are Used when 03-00~03-07=40 (Switching between Motor 1/Motor 2)

➢ Stall prevention selection during deceleration (08-00=xx0xb)

(1) Stall prevention during deceleration automatically increases the deceleration time according

based on the DC-bus voltage to prevent over-voltage during deceleration.

(2) When the DC-bus voltage exceeds the stall prevention level deceleration will stop and the

inverter will wait for the DC-bus voltage to fall below the stall prevention level before

continuing deceleration

Figure4.3.67:currenthumpcrosses08-01 with15%lowerband;Outputfrequencyincreases,holdswhilecurrenthigh,resumesrising. Stallpreventionintervalmarked;horizontal t.

StallPrev.Lev.Acceleration(CH)=[Stallpreventionlevelinacceleration08-01 x Fbase01-12]/Outputfrequency. Literalformula.

Figure4.3.68:levelconstant08-01inConstantTorqueRegion;fallsinConstantHorsepowerRegion until08-21limit,thenflat;dashedunlimitedcontinuation. HorizontalOutputfrequency;no unprintedfrequency inferred.

Manual — Deceleration/run stall thresholds and timing — page 233

Manual reference: physical PDF page 233. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Stall prevention level can be set by 08-02, see table 4.3.34。

Table 4.3.34 Stall prevention level

Please refer fig.4.3.69 for stall prevention during deceleration.

➢ When external braking function is starting (braking resistor or braking module), stall prevention

during deceleration function (08-00 to xx1xb) is disabled.

Figure 4.3.69 Stall prevention selection in deceleration

➢ Stall prevention selection during run (08-00=x0xxb)

(1) This function prevents the motor from stalling by automatically reducing the output

frequency during run.

(2) If the inverter output current rises above the level set in parameter 08-03 for the time specified

in parameter 08-22, the inverter output frequency is automatically decreased following

deceleration time 1 (00-15) or deceleration time 2 (00-17).

(3) When the inverter output current falls below the level set in parameter (08-03) minus 2%,

normal operation continues and the output frequency increases to the frequency reference

using the acceleration time 1 or acceleration time 2. Refer to the following figure 4.3.70.

Figure 4.3.70 Stall prevention selection during operation

Figure4.3.69:Outputfrequency decreaseswiththreeflatsegments;decelerationextendedtopreventovervoltage. Dashedstraightoriginaldecelerationtime shown againstt;no values inferred.

Figure4.3.70:Loadstepup/down;currenthumpat08-03with2%hysteresis;outputfrequencyreducedafter08-22detectiontime. Two traceslabeldecelerationtime1(00-15)and2(00-17);recoverywhenbelowhysteresis. No inferrednumericduration.

Deceleration/run stall thresholds and timing

Inverter model / 08-02 default value — PDF page 233

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Inverter model 08-02 default value
2 200V class 385VDC
3 400V class 770VDC

Manual — Motor overload selection, hot/cold curves and conditions — page 234

Manual reference: physical PDF page 234. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(1) Please set motor overload protection function by parameter 08-05 according to currently

motor.

(2) Turn off the motor overload protection when using two or more motors connected to the

inverter (set 08-05=xxx0b), and provide external overload protection for each motor

(3) With hot start enabled (08-05=xx1xb), motor overload protection occurs in 3 and a half minutes

when operating the motor at 150% of the motor rated current at an output frequency greater

than 60Hz.

(4) When 08-05=x0xxb, overload protection function is based on 70% of the motor rated current

for an output frequency of 20Hz. If the output frequency is lower than 1Hz, the overload

protection function uses 40% of the motor rated current to determine an overload condition.

(5) When 08-05=x1xxb, overload protection function is based on motor rated current for output

frequencies between 6 and 60Hz. If the output frequency is lower than 1Hz, the overload

protection function uses 83% of the motor rated current to determine an overload condition.

(6) To use the built-in motor overload protection function parameter 02-01 (motor rated current)

has to match the motor rated current on the motor nameplate.

Hot Start curve:

(Low speed curve) (High Speed curve) Cold Start Curve:

(Low speed curve) (High Speed curve)

HotStart low-speed0Hzcurve:OverloadProtectTime(min) vsMotorLoadCurrent%(02-01=100%). Marked100%→7.9min;150%→2.9min;200%→1.5min. Continuouscurve retained withoutinterpolation.

HotStart high-speed60Hzcurve:marked116%→28.8min(startactivatedpoint),150%→3.9min,200%→1.7min. Motorloadcurrent%(02-01=100%). Prose separately3.5minat150%andgreaterthan60Hz;differentconditionsretained.

ColdStart low-speed0Hzcurve:100%→12.4min;150%→4.5min;200%→2.4min. Motorloadcurrent%(02-01=100%);nointerpolation.

ColdStart high-speed60Hzcurve:116%→45.2min(startactivatedpoint),150%→6.1min,200%→2.7min. Motorloadcurrent%(02-01=100%);nointerpolation.

Motor overload selection, hot/cold curves and conditions

08- 05 / Selection for motor overload protection (OL1) — PDF page 234

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 05 Selection for motor overload protection (OL1)
2 Range 【xxx0b】:Motor overload is disabled 【xxx1b】:Motor overload is enabled 【xx0xb】:Cold start of motor overload 【xx1xb】:Hot start of motor overload 【x0xxb】:Standard motor 【x1xxb】:Special motor 【0xxxb】:Reserved 【1xxxb】:Reserved

Manual — OL1 action, fan controls and AVR source conflicts — page 235

Manual reference: physical PDF page 235. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ 08-06=0:When the inverter detects a motor overload the inverter output is turned off and the

OL1 fault message will flash on the keypad. Press RESET button on the keypad or

activate the reset function through the multi-function inputs to reset the OL1 fault.

➢ 08-06=1:When the inverter detects a motor overload the inverter will continue running and

the OL1 alarm message will flash on the keypad until the motor current falls within

the normal operating range.

➢ Over heat protection (Cooling fan control) (08-07)

(1) When 08-07=0, the inverter start to run, when IGBT temperature is higher than setting

level, the fan start to run. If the temperature drops period higher than 08-38, the fan stop.

(2) When 08-07=1, The inverter is supplied by power, the fan start to run. If inverter stop to run

longer than 08-30, the fan start to stop.

(3) When 08-07=2, The inverter is supplied by power, the fan start to run.

(4) When 08-08=3, The fan will not run.

Note:

When 08-07=0, if inverter sto, but the heatsink terperature is still too high, the cooling fan will start

to run.

➢ Automatic voltage regulation stabilizes the motor voltage independent of fluctuation to the

input voltage.

(1) When 08-08=0, automatic voltage regulation is active. It will limit the maximum output voltage.

When input three-phase voltage fluctuates and the voltage is smaller than the value of 01-14,

the output voltage will fluctuate with the fluctuation of input voltage.

(2) When 08-08=1, automatic voltage regulation is not active, motor voltage follows the input

voltage fluctuation. When input three-phase voltage fluctuates, the output voltage won’t

fluctuate with the fluctuation of input voltage.

OL1 action, fan controls and AVR source conflicts

08- 06 / Start-up mode of overload protection operation (OL1) — PDF page 235

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 06 Start-up mode of overload protection operation (OL1)
2 Range 【0】:Stop output after overload protection 【1】:Continuous operation after overload protection.

08- 07 / Over heat protection (Cooling fan control) — PDF page 235

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 07 Over heat protection (Cooling fan control)
2 Range 【0】:Auto (Depends on temperature) 【1】:Operate while in Run Mode 【2】:Always Run 【3】:Stop Operation
3 08 - 38 Delay Time of Fan Off
4 Range 【0 ~ 600】Seconds

Models / Fan start to run / Fan start to stop — PDF page 235

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Models Fan start to run Fan start to stop
2 2P5-210, 401-415 IGBT≧90℃ IGBT<70℃
3 215-240, 420-475 IGBT≧95℃ IGBT<75℃

08- 08 / Automatic voltage regulation (AVR) — PDF page 235

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 08 Automatic voltage regulation (AVR)
2 Range 【0】:AVR is enabled 【1】:AVR is disabled

Manual — Phase-loss and over-torque protection — page 236

Manual reference: physical PDF page 236. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(1) When 08-09=0:Input phase loss detection is disabled.

When 08-09=1:Input phase loss detection is enabled.

(2) Keypad shows "IPL input Phase Loss" (IPL), when an input phase loss is detected the inverter

output is turned off and the fault contact is activated.

(3) The input phase loss detection is disabled when the output current is less than 30% of the

inverter rated current.

(1) When 08-10=0:Output phase loss detection is disabled. When 08-10=1:Output phase loss detection is enabled. (2) Keypad shows "OPL Output Phase Loss" (OPL), when an output phase loss is detected and the inverter output is turned off and the fault contact is activated. (3) The output phase loss detection is disabled when the output current is less than 10% of the inverter rated current.

➢ The over torque detection function monitor the inverter output current or motor torque and can be used to detect increase in inverter current or motor torque. load). ➢ The low torque detection function monitor the inverter output current or motor torque and can be used to detect a decrease in inverter current or motor torque ➢ The torque detection levels (08-15, 08-19) are based on the inverter rated output current. (1) In V/F control mode, based on 100% rated output curent of inverter. (2) In SLV mode, based on 100% rated torque of inverter. ➢ Over and low torque detection condition can be output to the multi-function digital outputs (R1A-R1C, R2A-R2C) by setting parameters 03-11 to 03-12 to 12. Refer to figure 4.3.72

Phase-loss and over-torque protection

08- 09 / Selection of input phase loss protection — PDF page 236

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 09 Selection of input phase loss protection
2 Range 【0】:Disable 【1】:Enable

08- 10 / Selection of output phase loss protection — PDF page 236

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 10 Selection of output phase loss protection
2 Range 【0】:Disable 【1】:Enable

08- 13 / Selection of over-torque detection — PDF page 236

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 13 Selection of over-torque detection
2 Range 【0】:Over-torque detection is disabled 【1】:Start to detect when reaching the set frequency 【2】:Start to detect when the operation is begun
3 08- 14 Selection of over-torque action
4 Range 【0】:Deceleration to stop when over-torque is detected. 【1】:Displays warning when over-torque is detected. Continue operation. 【2】:Coast to stop when over-torque is detected
5 08- 15 Level of over-torque detection
6 Range 【0~300】%
7 08- 16 Time of over-torque detection
8 Range 【0.0~10.0】Sec

Manual — Torque timing, ground fault and external fault settings — page 237

Manual reference: physical PDF page 237. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.72 Over/Low torque detection for DI/DO terminals

➢ Example for over torque detection:

Figure 4.3.73 for Over-torque detection operation

➢ When 08-23=0:Ground fault function is disable When 08-23=1:Ground fault function is enable ➢ If the inverter leakage current is greater than 50% of inverter rated current and the ground fault function is enabled (08-23), the keypad will display a "GF Ground Fault" (GF), motor will coast to a stop and fault contact is activated.

➢ When multi-function digital input terminal is set to 25 (the external fault) and this terminal signal is triggered off, parameter 08-24 (Operation Selection of External Fault) can be selected to stop it. The selection of stop modes is the same as 07-09.

➢ The reson for the detection of external faults is determined by parameter 08-25. (1) When 08-25=0, faults are immediately detected at power up. (2) When 08-25=1, faults are detected when the inverter is running.

Figure4.3.72 relay labelsR1A,R1B,R1Cbracket03-11;R2A,R2Bbracket03-12. Contactsymbolsretainedinimage;no inferred topology.236proseR2A-R2C differs.

Figure4.3.73:Inverteroutputcurrent(ormotoroutputtorque),detectionlevel08-15,10%hysteresiswidth,twohighhumps. Over-torquedetectionsignalONafter08-16delayabovelevel,OFFatfallinglowerhysteresisthreshold. No inferred numericamplitude/time.

Torque timing, ground fault and external fault settings

08- 23 / Ground Fault (GF) selection — PDF page 237

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 23 Ground Fault (GF) selection
2 Range 【0】:Disable 【1】:Enable

08- 24 / Operation Selection of External Fault — PDF page 237

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 24 Operation Selection of External Fault
2 Range 【0】:Deceleration to Stop 【1】:Coast to Stop 【2】:Continous Operation

08- 25 / Detection Selection of External Fault — PDF page 237

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 25 Detection Selection of External Fault
2 Range 【0】:Immediately Detect when the Power is Supplied 【1】:Start to Detect During Operation

Manual — PTC overheat settings, calculation and source contradictions — page 238

Manual reference: physical PDF page 238. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Local08-36unit remains unprinted; PDF102supplies separate seconds context, not a filled cell.08-35option1differs between summary102Deceleration to Stop and detail238Coast to Stop; option2summaryCoast to Stop, detailtableFree run to top, detailprosefree runs to stop. Intended option behaviour unresolved; no preferred meaning.

Motor Overheat Fault Selection: ➢ It executes motor overheat protection by the resistor (PTC) that built-in the motor. ➢ The resistor (PTC) is between AI2 and GND and a divided resistor R ,as the pic 4.3.65(b) (1) When motor occurs overheating: 08-35 = 0:Motor overheats fault function is off. 08-35 = 1:When the motor is overheating, it coasts to stop. 08-35 = 2:When the motor is overheating, it free runs to stop 08-35 = 3:When the motor is overheating, it keeps running until reach the value of 08-42 (2) 08-35=1 or 2, if the temperature is getting higher for the motor and AI2 voltage level is higher than the value of 08-44, the display will show 『OH4 Motor Overheating』 and the motor will stop by 08-35=1 or 2. (3) 08-35=3, When the temperature is getting higher for the motor and AI2 voltage level is higher than the value of 08-44, the display will show 『OH3 Motor Temp Warning』but the motor continues running. But AI2 voltage level is higher than the value of 08-42 and the time reach to 08-39, the motor free runs to stop. (4) When 08-35 = 1 or 2 or 3,When the motor cools down and AI2 voltage level is lower the value of 08-43, 『OH4 Motor overheat』will reset. (5) The resistor (PTC) conform the British Standards Institution:

When Tr is 150 ℃in Class F and is 180℃ in Class H ● Tr-5℃:RT≦ 550Ω,put RT in formula (1), the V value by calculation is the value of 08-43. ● Tr+5℃:RT≧1330Ω,put RT in formula (1), the V value by calculation is the value of 08-44. (6) It gets reference value by using formula (1) even in the different spec of resistor (PTC).

(7) Please follow the rule of PTC protection function setting, prevent the error occors. PTC restart level(08-43) > PTC warning level(08-44) > PTCprotection level(08-42)

PTCformula(1):V=(1/2)x10x[(RPTC // 200)/(R+(RPTC // 200))]. Literalparallel-symbolformula,not validated;units/connectionsremainasprintedon239.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: PTC input filter time08-36 unit is absent; range0.00~5.00 retained without assumed seconds.

PTC overheat settings, calculation and source contradictions

08 - 35 / Motor Overheat Fault Selection — PDF page 238

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08 - 35 Motor Overheat Fault Selection
2 Range 【0】:Disable 【1】:Coast to Stop 【2】:Free run to top 【3】:Keep running
3 08 - 36 PTC Input Filter Time Constant
4 Range 【0.00 ~ 5.00】
5 08 - 39 Delay Time of Motor Overheat Protection
6 Range 【1 ~ 300】Sec
7 08 - 42 PTC Protection Level
8 Range 【0.1 ~ 10.0】V
9 08 - 43 PTC Restart Level
10 Range 【0.1 ~ 10.0】V
11 08 - 44 PTC Warning Level
12 Range 【0.1 ~ 10.0】V

Manual — PTC characteristics/connections and temperature relay timing — page 239

Manual reference: physical PDF page 239. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: The Tr definition separator and a glyph beside the 10V terminal render as boxes. The 550/1330 ohm levels, Class F 150°C, Class H 180°C, Tr±5 and JP3 V / 04-00=0 or 2 instructions remain literal supplier text. No hidden glyph or wiring topology is inferred.

Figure 4.3.65 (a) PTC Thermistor Characteristics (b)PTC Thermistor Connections

Notes:

For PTC thermistor connections, JP3 switch needs to set V, 04-00 needs to ser 0 or 2.

Selection of temperature agree level and temperature reset level ➢ When 03-11=59: ➢ 08-46:When temperature of inverter is higher than 08-46, output relay will active. ➢ 08-47:When temperature of inverter is less than 08-47, output signal of relay will turn to off.

Diagram:

Figure 4.3.66 Inverter temperature agree and reset detection

Figure4.3.65(a):ResistanceΩ vsTemperature;twoPTCcurvesClassF150°C/ClassH180°C;550Ω/1330Ωguides;Tr−5,Tr,Tr+5andTrprime markers;Trtemperaturethresholdlabelseparatorunrendered. No interpolationorcertificationclaim.

Figure4.3.65(b)PTCconnection labelsDividerResistorR(1~2KΩ),PTCThermistor,10V,AI2,GND,200KΩ,Internalcircuit;boxglyphnear10Vunrendered. Sourceimagepreserveslines,no inferred wiring topology.

Figure4.3.66:InvertertemperatureT°C risespast08-46andlaterfallsbelow08-47.03-11OutputrelayONbetweenthosecrossings;Timeaxis. Thresholdvaluesnotplotted.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: PTC Tr definition separator and glyph adjacent10V render as boxes; visible source labels retained, no missing glyph or wiring topology inferred.

PTC characteristics/connections and temperature relay timing

08 - 46 / Temperature Agree Level — PDF page 239

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08 - 46 Temperature Agree Level
2 Range 【0 ~ 254】°C
3 08 – 47 Temperature Reset Level
4 Range 【0 ~ 254】°C

Manual — Fire mode enable/reset, ignored faults and danger warning — page 240

Manual reference: physical PDF page 240. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ When 08-48=0, Fire Mode is disabled. When 08-48=1, Fire Mode is enabled. ➢ When fire mode is enabled, S6 will be defined to signal input of fire mode (Parameter 03-05 will be set to 47 automatically). When fire mode is enabled, inverter will become to fire mode. No matter inverter is running or stopping, run and frequency command source will be covered by the setting of fire mode, keypad display will show “ FIRE ”, some of protect functions will be ignored, please refer the table 4.3.35, inverter will not stop. When fire mode (03-0X=47) and outour overload (03-0X=68) function is triggered, the other digital inputs will be ignored, the parameters just can be read by communication or keypad display.

➢ When 08-49=0, pelase disconnect the power first, remove external trigger signal and then connect the power. ➢ When 08-49=1, no need to disconnect the power, inverter will become to normal mode, run and frequency will reture to original setting. Notes: Fire Mode function does not support PUMP fumction.

Table 4.3.35 These functions will be ignoed when fire mode is triggered

!Danger:

Fire mode:

The drive will run at full speed either in forward or reverse direction and ignore all software

protections until any one of the hardware protection is triggered or drive is damaged to achieve the

requirement of smoke extraction and reduce the hazard to humans.

Fire mode enable/reset, ignored faults and danger warning

08 - 48 / Selection of Fire Mode — PDF page 240

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08 - 48 Selection of Fire Mode
2 Range 【0】: Disable 【1】: Enable

08 - 49 / Multi-Function Input Terminal Status of Fire Mode — PDF page 240

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08 - 49 Multi-Function Input Terminal Status of Fire Mode
2 Range 【0】: Reset after Power Off 【1】: Reset after Terminal Removed

0x2521H / Fault Description — PDF page 240

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 0x2521H Fault Description
2 4 OH1 (Heat sink over heat)
3 5 OL1 (Motor overload)
4 6 OL2 (Inverter overload)
5 7 OT (Over torque)
6 25 FB (PID feedback signal error)
7 26 Keypad Removed
8 28 CE (Communication error)
9 46 OH4 (Motor over heat)
10 49 MtrSw (DI Motor Switch Fault)
11 58 PF(Protection error)

Manual — Fire mode contact, speed and PID loss selections;continues242 — page 241

Manual reference: physical PDF page 241. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Each bit of 08-50 presents an input :

Notes:

Please set 08-40=0 (fire mode disabled) before setting normal open or normal close contact.

Failure to comply may cause death or serious injury.

➢ When 08-51=0, motor speed setting will follow 08-52. If the value of 08-52 is 100%, inverter output frequency will follow the value of 01-02. ➢ When 08-51=1, motor speed setting will follow PID control; when fire mode is enabled, PID control will base on 10-47/10-48/10-49 (please refer the setting value of group 10) ➢ When 08-51=2, frequency reference will become to 4-20mA (default setting of 04-00)

➢ When 08-51=1, PID feedback loss detection function will be opened automatically.

➢ When fire mode is enabled, if 08-51=1 and then PID feedback, inverter will be stopped after the setting value of 08-54.

➢ When 08-51=0, output frequency will be fixed on current frequency. ➢ When 08-51=1, output frequency will be based on the setting value of parameter 08-52. ➢ When 08-51=2, output frequency will be based on the setting value of parameter 01-02. When PID feedback value less than 08-53 and then longer than 08-54, inverter will keep running, but the frequency reference will be switched to 08-55, output frequency will not less than the setting value of 08-52.

08-50inputbitdisplay:fiveprintedzeros;0Normalopen,1Normalclose;S6labelbeneathlow-orderposition. SourceproseEachbitpresentsaninput butonlyS6contacttable;no additionalterminalmapping inferred.

Fire mode contact, speed and PID loss selections;continues242

08 - 50 / Multi-Function Terminal Status of Fire Mode — PDF page 241

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08 - 50 Multi-Function Terminal Status of Fire Mode
2 Range 【xxx0b】: S6 A Contact 【xxx1b】: S6 B Contact

08 - 51 / Motor Speed Setting Source of Fire Mode — PDF page 241

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08 - 51 Motor Speed Setting Source of Fire Mode
2 Range 【0】:Fire Mode Speed (08-52) 【1】:PID Control 【2】:AI2

08 - 53 / PID Detection Level of Fire Mode — PDF page 241

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08 - 53 PID Detection Level of Fire Mode
2 Range 【0~100】%

08 - 54 / Delay Time of Fire Mode PID Loss — PDF page 241

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08 - 54 Delay Time of Fire Mode PID Loss
2 Range 【0.0~10.0】Sec

08 - 55 / PID Feedback Loss Detection Selection of Fire Mode — PDF page 241

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08 - 55 PID Feedback Loss Detection Selection of Fire Mode
2 Range 【0】:Keep Running 【1】:Fire Mode Speed(08-52) 【2】:Max. Output Frequency of Motor 1 (01-02)

Manual — PID loss plot, AI2 loss parameters and timing;continues243 — page 242

Manual reference: physical PDF page 242. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig 4.3.75 PID feedback loss detection

Notes: If there is no any feedback signal and then feedback loss level also be set to 0%, feedback loss detection function will not be triggered.

➢ When 08-51=2 (AI2), inverter will trigger AI2 feedback loss detection function automatically.

➢ Selection of Fire Mode AI2 Signal Loss (08-58) :

(1) When 08-58=0, output frequency will be fixed on current frequency. (2) When 08-58=1, output frequency will be based on the setting value of parameter 08-52. (3) When 08-58=2, output frequency will be based on the setting value of parameter 01-02.

➢ If AI2 signal is less than the setting value of 08-56 in 360ms, and the time longer than setting value of 08-57, the frequency reference will be considered to loss. ➢ Analog signal will compare with the previous value at 360ms, if inverter ensure the frequency reference already loss, frequency reference will base on the value of 08-58. Following is the description of the Frequency Loss Function: When the inverter is in operation and the selected analog command source AI2 disappears, the command will operate according to the setting ratio of 08-58. The following figure (fig 4.3.76) is the operating diagram of analog frequency instruction AI2 when the frequency instruction is lost.

Figure4.3.75PIDfeedbackloss:FeedbackValuevs08-53threshold;firstdipdurationt1shorterthan08-54doesnottriggerFBL;laterbelowthresholdfor08-54triggersFBLdetectionhigh. Source0%no-feedbackexceptionretainedinprose.

PID loss plot, AI2 loss parameters and timing;continues243

08 – 56 / Detection Level of Fire Mode AI2 Signal — PDF page 242

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08 – 56 Detection Level of Fire Mode AI2 Signal
2 Range 【0~100】%
3 08 - 57 Delay Time of Fire Mode AI2 Signal Loss
4 Range 【0.0~10.0】Sec
5 08 - 58 Selection of Fire Mode AI2 Signal Loss
6 Range 【0】:Keep Running 【1】:Fire Mode Speed(08-52) 【2】:Max. Output Frequency of Motor 1 (01-02)

Manual — AI2 loss plot, fire mode direction and password restrictions — page 243

Manual reference: physical PDF page 243. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig 4.3.76 AI2 frequency reference loss

➢ When fire mode is enabled, motor direction will base on the setting of 08-59, the priority of

08-59 is higher than keypad and digital input.

➢ When fire mode is enabled, use can set password in parameter 08-60, please refer the

process of parameter 13-07.

➢ In order to prevent the parameters of fire mode being modified, keypad display will just

show the related parameters of fire mode when fire mode is enabled. (Parameter

08-48~08-60 will be read only).

➢ Parameter 08-60(password of fire mode) and 13-07(parameter password), only one

parameter can be allowed to set at the same time.

Figure4.3.76AI2loss:FrequencyCommandinitiallyByAI2setting,declinesbelow08-56;360msintervalthen08-57delay,AI2SignalLossDetectiongoeshigh andfrequencyramps toBy08-58setting. Horizontal t;no unprintedfrequencyvalue inferred.

AI2 loss plot, fire mode direction and password restrictions

08 - 59 / Fire Mode Motor Direction — PDF page 243

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08 - 59 Fire Mode Motor Direction
2 Range 【0】: Forward 【1】: Reverse

08 - 60 / Fire Mode Password — PDF page 243

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08 - 60 Fire Mode Password
2 Range 【00000 ~ 65534】

Manual — Group09 communication configuration and timeout behaviour — page 244

Manual reference: physical PDF page 244. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 09 Communication Parameters

➢ The Modbus communication port RJ45 and TM2 terminal (S+, S-) can be used to monitor,

control, program and trouble-shoot the inverter.

➢ Modbus communication can perform the following operations, independent of the frequency

command selection (00-05) setting and Operation command selection (00-02) setting.

(1) Monitoring the status from controller.

(2) Please do not write and read the parameters by communication very often because the

EEPROM component will be damaged.

(3) Control multi-function inputs.

Group09 communication configuration and timeout behaviour

09- 00 / INV Communication Station Address — PDF page 244

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 09- 00 INV Communication Station Address
2 Range 【1~254】
3 09- 01 Communication Mode Selection
4 Range 【0】:MODBUS 【1】:BACNet 【3】:PUMP parallel communication
5 09- 02 Baud Rate Setting (bps)
6 Range 【2】:4800 【3】:9600 【4】:19200 【5】:38400
7 09- 03 Stop Bit Selection
8 Range 【0】:1 stop bit 【1】:2 stop bits
9 09- 04 Parity Selection
10 Range 【0】:No Parity 【1】:Even bit 【2】:Odd bit
11 09- 05 Communication Data Bit Selection
12 Range 【0】:8 Bit Data 【1】:7 Bit Data
13 09- 06 Communication Error Detection Time
14 Range 【0.0~25.5】Sec
15 09- 07 Fault Stop Selection
16 Range 【0】:Deceleration to stop based on deceleration time 1 【1】:Coast to stop when communication fault occurs 【2】:Deceleration to stop based on deceleration time 2 【3】:Keep operating when communication fault occurs
17 09- 08 Comm. Fault Tolerance Count
18 Range 【1~20】
19 09- 09 Waiting Time
20 Range 【5~65】mSec
21 09- 10 BACNET Device Instance Number
22 Range 1~254

Manual — Serial communication specifications and setup sequence — page 245

Manual reference: physical PDF page 245. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note:

When 09-01=0 (MODBUS), it can identify the communication format for ASCII and RTU. If the

controller uses RTU format, it can not support communication data bit of 7 bit data. (09-05=1).

Modbus (RS-485) communication specification:

Please refer the detail instruction to “Appendix 3-Modbus”. ➢ Commnuication wiring and setup

(1) Turn off power supply and connect communication lines of the controller to the inverter (RJ45).

(2) Turn power on.

(3) Set the required communication parameters (09-00) via the keypad.

(4) Turn off power to the inverter and wait until keypad is completely off.

(5) Turn power on again.

(6) Start communication between controller and inverter.

➢ Modbus (485) communication architecture (1) Modbus communication configuration uses a master controller (PC, PLC), communicating to a maximum of 31 inverters. (2) The master controller is directly connected to the inverter via the RS-485 interface. If the master controller has a RS-232, a converter must be installed to convert signals to RS-485 to connect the master controller to the inverter. A maximum 31 inverters can be connected to a network, following the Modbus communication standard. Communication parameters as follows:

➢ Inverter station addresses (09-00)

Setting range is 1-31.

➢ RS-485 Communication baud rate setting (09-02)

09-02= 2:4800 bps (bit/second)

09-02= 3:9600 bps

09-02= 4:19200 bps

09-02= 5:38400 bps

Serial communication specifications and setup sequence

Items / Specifications — PDF page 245

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Items Specifications
2 Interface RS-485
3 Communication period Asynchronous (start - stop synchronization).
4 Communication parameters Baud rate:4800, 9600, 19200 and 38400 bps. Data Length:8 bits (Fixed). Parity:options of none, even and odd bit. For even and odd selection stop bit is fixed at 1 bit.
5 Communication protocol Modbus (included RTU mode and ASCII mode).
6 Number of inverters Maximum 31 units.

Manual — Communication formats, fault behaviour and response timing — page 246

Manual reference: physical PDF page 246. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Stop bit selection (09-03, 09-04)

09-03= 0:1 stop bit

09-03= 1:2 stop bits

09-04= 0:No parity.

09-04= 1:even parity

09-04= 2:odd parity.

➢ Communication Data Bit Selection (09-05)

09-05= 0:8 bits data

09-06= 1:7 bits data

➢ RS-485 communication error detection time(09-06)

➢ Stop selection of RS-485 communication failure (09-07)

09-07= 0:Deceleration to stop by deceleration time (00-15)

09-07= 1:Coast to stop

09-07= 2:Deceleration to stop using the deceleration time of 00-26 (emergency stop time)

09-07= 3:Keep running(warning message only, press the stop button to stop operation)

➢ Communication fault tolerance count (09-08)

When the number of communication errors exceeds the value set in parameter 09-08 the inverter

will display the communication fault alarm.

➢ Wait time of inverter transmission (09-09)

Sets the inverter response delay time. This is the time between the controller message and the start

of the inverter response message. Refer to figure 4.3.76. Set the controller receive time-out to a

greater value than the wait time parameter (09-09).

Figure 4.3.76 Communication message timing

Figure4.3.76 communication timing: Master→Inverter Command Message; Inverter→Master Response Message; first gap labelled24bits long, subsequent waiting interval09-09 setting; horizontal time t. Exact labels retained; no inferred protocol timing.

Manual — PID target and feedback sources and display scaling — page 247

Manual reference: physical PDF page 247. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 10 PID Parameters

➢ When 10-00=0 Keypad can adjust the PID target value. ➢ When 10-00=1 or 2 The source of signal is proportional to be corresponding to PID target via analog input terminal. For example: 0~10V is corresponding to 0~100% target value, when being given 2V, 20% is obtained. ➢ When 10-00=3, PID target value is communication input. 00-05=5, 10-03=0001, communication address 0X2502H (communication frequency). ➢ When 10-00=4, (1) For general purpose of PID setting, set 10-00=4 to set the PID target value by 10-02. (2) 10-02(PID target value) is set at percentage and PID setting is at main screen monitor (12-38). (3) Maximum target value is set by parameter 10-33 (PID feedback maximum value), the decimals is determined by parameter10-34 (PID decimal width), and the unit is set by parameter 10-35 (PID unit). Example: Set 10-33=999, 10-34=1, 10-35=3, and set 10-02 to 10%. Then 9.9PSI is displayed at the main screen monitor (12-38) and can be modified at this monitor. Maximum value is 99.9 PSI (limited to the setting value of parameter 10-33).

Note:Parameter 10-00 and 10-01 cannot be set to the same source. If both parameters are set to the same source the keypad will show a SE05 alarm.

PID target and feedback sources and display scaling

10- 00 / PID target value source setting — PDF page 247

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 00 PID target value source setting
2 Range 【0】:Keypad given 【1】:AI1 given 【2】:AI2 given 【3】:Communication given 【4】:Use 10-02 setting

10- 01 / PID feedback value source setting — PDF page 247

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 01 PID feedback value source setting
2 Range 【0】:Keypad given 【1】:AI1 given 【2】:AI2 given 【3】:Communication given

Manual — PID modes, gain and response parameters — page 248

Manual reference: physical PDF page 248. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ PID target value source setting (10-00)/PID feedback value source setting(10-01).

Please confirm parameter 04-00 conform the need (0~10V or 4~20mА), if AI2 as PID target or PID

feedback. And switch SW2 from control board to the input type (V or I), please refer to wiring

diagram for more detail.

➢ PID control mode (10-03)

(1) When 10-03= xxx1b:PID is enabled,

LCD keypad will be switched automatically (16-00) and main screen monitoring displays PID

target value (12-38). Sub-screen monitoring 1 (16-01) displays PID feedback value (12-39) and

sub-screen monitoring 2 (16-02) displays frequency output (12-17). If PID is disabled, the

keypad will switch automatically to frequency command setting as the main page.

(2) When 10-03= xx1xb:PID output is reverse.

PID output is chosen to reverse, and if PID input is negative, the output frequency of PID will

gain. On the contrary, PID output is chosen to forward, and if PID input is negative, the output

frequency of PID will decrease.

(3) When 10-03= 0xxxb:PID output corresponds 100% to the frequency of 01-02.

When 10-03=1xxxxb, PID output + frequency command, it will cumulate the output percentage

of frequency command, (corresponding to 01-02 main frequency main frequency command set

by parameter 00-05/ 00-06) at the beginning of running and then start PID control.

PID modes, gain and response parameters

10- 02 / PID target value — PDF page 248

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 02 PID target value
2 Range 【0.00~100.00】%
3 10- 03 PID control mode
4 Range 【xxx0b】:PID disable 【xxx1b】:PID enable 【xx0xb】:PID positive characteristic 【xx1xb】:PID negative characteristic 【x0xxb】:PID error value of D control 【x1xxb】:PID feedback value of D control 【0xxxb】:PID output 【1xxxb】:PID output + Frequency Command

10- 04 / Feedback gain — PDF page 248

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 04 Feedback gain
2 Range 【0.01~10.00】
3 10- 05 Proportional gain (P)
4 Range 【0.00~10.00】
5 10- 06 Integral time (I)
6 Range 【0.0~100.0】Sec
7 10- 07 Differential time (D)
8 Range 【0.00~10.00】Sec
9 10- 08 Primary Delay Filter Time
10 Range 【1~250】ms
11 10- 09 PID bias
12 Range 【-100~100】%

Manual — PID limits, output gain, reversal and response terms — page 249

Manual reference: physical PDF page 249. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ PID Adjustments

P control:

The error signal (deviation) between the input command (set value) and the actual control value

(feedback). This error signal or deviation is amplified by the proportional gain (P) to control the

offset between the set value and the feedback value.

I control:

The output of this control is the integral of the error signal (difference between set value and

feedback value) and is used to minimize the offset signal that is left over from the gain control.

When the integral time (I) is increased, the system response becomes slower

D control:

This control is the inverse from integral control and tries to guess the behavior of the error signal by

multiplying the error with the differential time. The result is added to the PID input. Differential

control slows down the PID controller response and may reduce system oscillation.

Note:

Most applications that PID control (fan and pump) do not require differential control.

Figure 4.3.77 PID Control

➢ PID Control Type, the inverter offers two type of PID control.

(1) PID control with differential feedback (10-03=x1xxb)

Make sure to adjust the PID parameters without causing system instability. Refer to 4.3.78

for PID control for feedback value differential.

Figure4.3.77: step Deviation above Control response; P constant component, I rising ramp, D decaying component and combined PID response initially falls then rises. Axes t; no numeric response values.

PID limits, output gain, reversal and response terms

10-14 / PID integral limit — PDF page 249

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-14 PID integral limit
2 Range 【0.0~100.0】%
3 10-23 PID limit
4 Range 【0.00~100.0】%
5 10-24 PID output gain
6 Range 【0.0~25.0】
7 10-25 PID reversal output selection
8 Range 【0】: Do not allow the reversal output 【1】: Allow the reversal output
9 10-26 PID target acceleration / deceleration time
10 Range 【0.0~25.5】Sec

Manual — PID derivative paths and setup instructions — page 250

Manual reference: physical PDF page 250. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.78 PID control for feedback differential value

(2) Basic PID control(10-03=x0xxb)

This is the basic type of PID control. Refer to the figure 4.3.79.

Figure 4.3.79 Basic PID control ➢ PID Setup:

Enable PID control by parameter 10-03, PID target value (10-00) and PID feedback value (10-01).

(1) Select PID trget value:PID target value selection(10-00)

10-00=0:Keypad given

10-00=1:Analog AI1 given (default)

10-00=2:Analog AI2 given

10-00=3:Communication given

10-00=4:10-02 given

(2) Select PID feedback vale:PID feedback value selection(10-01)

10-01= 0:Keypad given

10-01= 1:Analog AI1 given

10-02= 2:Analog AI2 given

10-03= 3:Communication given

Figure4.3.78: Set value and Feedback, plus/minus summing signs, P, I, D and Control labels. D path is on feedback for10-03=x1xxb; feedback and D enter a plus summation before negative error input. Bounded diagram labels; no inferred wiring.

Figure4.3.79 basic PID10-03=x0xxb: Set value positive, Feedback negative, P, I, D, Control and plus summation signs; feedback loop shown. Source control diagram labels retained without engineering validation.

Adjacent source context — repeated to preserve continuation:

Manual — PID source selectors and detailed control block labels — page 251

Manual reference: physical PDF page 251. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Intended reversal/integral limits and missing integral minus remain unvalidated; engineering values must not be inferred.

Figure 4.3.80 PID input selection

➢ PID Control Setting

PID control block disgram, the following figure shows PID control block diagram.

Figure 4.3.81 PID control block diagram

Figure4.3.80 source selector: Keypad display10-00=0, AI1=1, AI2=2, Communication=3,10-02 setting=4;10-26 PID target SFS, ON/PID setting point, Target Value. Feedback selector Keypad display10-01=0, AI1=1, AI2=2, Communication=3; Feedback Value;10-27/10-28 PID feedback display unit conversion and PID feedback.

Figure4.3.81 detailed PID labels: target Keypad display10-00=0,AI1=1,AI2=2,Communication=3,10-02 setting=4. Feedback10-01 then10-04 gain;10-03=x0xxb orx1xxb derivative path10-07. Deviation;10-05P;10-06I;10-14 integral limit upper100%,lower100% printed without minus; Integral reset Using multifunction digital input.10-23 PID limit100%/−100%;10-10 Primary delay.10-03=xx0xb×1/xx1xb×−1;Bias10-09;10-24 output gain;PID Output±200%limit.10-03=1xxxb frequency feedforward or0xxxb direct. Reversal10-25=0 block+109%;10-25=1 block+109%/−109% as provisionally read from overprinted raster; numeric limit not fully verified. PID=OFF/PID=ON;Frequency reference. OFF conditions printed10-03=0,During JOG,03-00~03-05=29. Source labels preserved; no inferred topology or correction of source references.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Reversal-limit numeral raster is overprinted/low-resolution, visually resembling109%; retain provisional literal with separate enlarged evidence. Do not use it as a verified engineering limit. Integral lower100% lacks visible minus.

Adjacent source context — repeated to preserve continuation:

Manual — PID tuning instructions and conditional qualifications — page 252

Manual reference: physical PDF page 252. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ PID Tunning, use the following procedures to start PID control (1) Enable PID control  Set 10-03 to a value greater than "xxx0b").  Increase the proportional gain (10-05) to the highest value possible without causing the system to become unstable.  Decrease the integral time (10-06) to the lowest value possible without causing the system to become unstable.  Increase the differential time (10-07) to the highest value possible without causing the system to become unstable. (2) The PID control serves to maintain a given process within certain limits whether it is pressure, flow etc. To do this the feedback signal is compared to the set value and the difference becomes the error signal for the PID control. (3) PID output polarity can be selected with parameter 10-03 (setting = xx0xb: PID output forward, setting = xx1xb: PID output reversal). When PID output is chosen to reverse, and if PID input is

negative, the output frequency of PID will gain. On the contrary, PID output is chosen to

forward, and if PID input is minus, the output frequency of PID will decrease.

(4) PID feedback value can be adjusted using parameter 10-04 (PID feedback gain) as well as with

the analog input gain and bias for terminal AI1 or AI2.10-14 (Integral Limit) Used to limit the

integral output to prevent motor stall or damage to the system in case of a rapid change in the

feedback signal. Reduce the value of 10-14 to increase the inverter response.

➢ PID Bias (10-09)

Used to adjust the offset of the PID control. The offset value is added to the frequency reference as

compensation. Use parameter 10-24 (PID output gain) to control the amount of compensation.

➢ PID Limit (10-23)

Used to limit the output of the PID control. Maximum output frequency is 100%.

➢ PID Output gain (10-24)

Used to adjust the compensation. Use parameter 10-24 to adjust the compensation to output

frequency.

➢ PID reversal output selection (10-25)

In case the PID control output value goes negative, parameter 10-25 (PID reversal output selection)

can be used to reverse the motor direction.

➢ PID target acceleration/deceleration time (10-26)

Sets the PID target value acceleration and deceleration ramp time. The acceleration/deceleration

time is set to 00-14~17 and 00-21~24. Reduce the acceleration/deceleration time in case load

resonance or system instability is encountered.

Manual — PID adjustment response examples — page 253

Manual reference: physical PDF page 253. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ PID Fine Tunning

All PID control parameters are related to each other and require to be adjusted to the appropriate

values. Therefore, the procedure achieving the minimum steady-state is shown as following

(1) Increase or decrease the proportion (P) gain until the system is stable using the smallest

possible control change.

(2) The integral (I) reduces the system stability which is similar to increasing the gain. Adjust the

integral time so that the highest possible proportional gain value can be used without affecting

the system stability. An increase in the integral time reduces system response.

(3) Adjust the differential time if necessary to reduce overshoot on startup. The acceleration/

deceleration time can also be used for the same purpose.

➢ Fine-tuning PID control parameters:

(1) Reduce overshoot

In case overshoot occurs, reduce the derivative

time (D) and increase the integral time (I).

(2) Stabilize PID control

To quickly stabilize the PID control, reduce the

integral time (I) and increase the differential

time (D) in case overshoot occurs.

(3) Reduce long-period oscillation

Adjust the integral time (I) in case of

long-periodical system oscillation.

(4) Reduce short-period oscillation

Adjusting the differential time (D) and

proportional (P) gain when experiencing

short-periodical oscillation.

PID adjustment example1 Output versus t: Before overshoots, After response reduces overshoot; source adjacent instruction decreases D and increases I.

PID adjustment example2 Output versus t: Before slower response, After faster response with overshoot; adjacent instructions reduce integral time and increase derivative time if overshoot.

PID adjustment example3 Output versus t: Before long-period oscillation, After damped response; source discusses integral-time adjustment.

PID adjustment example4 Output versus t: Before short-period oscillation, After reduced oscillation; source discusses derivative and proportional gain adjustment.

Manual — PID feedback loss detection and timing — page 254

Manual reference: physical PDF page 254. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

The PID control function provides closed-loop system control. In case PID feedback is lost, the

inverter output frequency may be increase to the maximum output frequency.

➢ Warning (10-11=1)

A feedback loss condition is detected when the PID feedback value falls below the value set in

parameter 10-12 (PID feedback loss detection level) for the time set in parameter 10-13 (PID

feedback loss detection time). PID feedback loss warning message "Fb" will be displayed on the

keypad and the inverter will continue to operate.

➢ Fault (10-11=2)

feedback loss detection time). PID feedback loss fault message "Pb" will be displayed on the keypad,

the inverter stops and the fault contact is activated.

➢ Refer to figure 4.3.82

Figure 4.3.82 PID feedback loss detction

Figure4.3.82 feedback-loss timing: PID feedback compared with10-12 detection level. First dip duration t1<10-13 does not trigger; later low interval reaches10-13, FBL signal ON. Curves and labels retained, no interpolated time.

PID feedback loss detection and timing

10-11 / PID feedback loss detection selection — PDF page 254

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-11 PID feedback loss detection selection
2 Range 【0】:Disable 【1】:Warning 【2】:Fault
3 10-12 PID feedback loss detection level
4 Range 【0~100】%
5 10-13 PID feedback loss detection time
6 Range 【0.0~25.5】Sec

Manual — PID sleep and wakeup settings and normal control — page 255

Manual reference: physical PDF page 255. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ For energy saving requirement, motor will start/stop according to PID sleep/wake up function.

➢ Refer to figure 4.3.83 (a), (b) and (c) for PID sleep/wakeup operation:

Figure 4.3.83 (a) PID control block diagram

Figure 4.3.83 (b) Timing diagram PID sleep / wakeup

Figure4.3.83a: Target positive/Feedback negative into PID Frequency;10-40=0 Sleep/Wakeup or10-40=1 Sleep Compensation/Wakeup;10-29=0 bypass,10-29=1or2 control; PID OFF/ON; Soft Start f/t; Output Frequency Fout. Block labels only.

Figure4.3.83b normal sleep: Output frequency and Frequency reference;10-19 wakeup frequency above10-17 sleep frequency; Fmin01-08;10-18 sleep delay, output falls to zero;10-20 wakeup delay before output ramps. Exact conditions retained with adjacent source prose.

PID sleep and wakeup settings and normal control

10-17 / Start frequency of PID sleep — PDF page 255

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-17 Start frequency of PID sleep
2 Range 【0.00~599.00】Hz
3 10-18 Delay time of PID sleep
4 Range 【0.0~255.5】Sec
5 10-19 Frequency of PID wakeup
6 Range 【0.00~599.00】Hz
7 10-20 Delay time of PID wakeup
8 Range 【0.0~255.5】Sec
9 10-29 PID sleep selection
10 Range 【0】:Disable 【1】:Enable 【2】:Set by DI
11 10-40 Selection of PID Sleep Compensation Frequency
12 Range 【0】:Disable 【1】:Enbale

Manual — PID sleep compensation and invalid-setting conditions — page 256

Manual reference: physical PDF page 256. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.83 (c) Timing diagram of PID sleep compensation/ wakeup

➢ 10-40=0, refer to Figure 4.3.83(b)

The PID sleep timer is enabled when the output frequency (Fout) falls below the PID sleep frequency

(10-17). When the sleep timer reaches the set PID sleep delay time (10-18) the inverter will

decelerate to a stop and enter the sleep mode.

➢ 10-40=1, refer to Figure 4.3.83(c)

When output frequency (Fout) is lower than PID sleep frequency set by 10-17, Timer of PID sleep

mode will run and the output frequency changes with the reference frequency (Fref) until it reaches

the minimum output frequency (Fmin) set by 01-08. When the PID sleep delay time (10-18) is

completed, the motor will run gradually to the PID sleep frequency set by 10-17.

While sleep mode is active and the motor has stopped, the internal PID control is still in operating.

When the reference frequency increases and exceeds the wakeup frequency parameter 10-19 for

the time specified in the wakeup delay time parameter 10-20, the inverter will restart and the output

frequency will ramp up to the reference frequency.

Example:

(1) When wakeup frequency less than sleep frequency, inverter starts by the sleep frequency and

sleeps depending on sleep frequency.

(2) When wakeup frequency greater than sleep frequency, inverter starts by the wakeup frequency

and sleeps depending on sleep frequency.

➢ Parameter 10-00 and 10-01 can not be set to the same source. If both parameters are set to the

same source the keypad will show a “ SE05 ” alarm.

➢ When 10-29=1 or 2 and then 10-25=1, inverter will show a “ SE05 ” alarm.

➢ When 10-29=1 or 2, and then set 10-03=1xxxb, inverter will show a “ SE05 ” alarm.

➢ When 10-29= 0:PID sleep function is disabled.

When 10-29= 1:PID sleep operation is based on parameter 10-17 and 10-18.

When 10-29= 2:PID sleep function is started by multi-function digital input terminal.

Figure4.3.83c compensation: Output frequency/Frequency reference;10-19 wakeup frequency,10-17 sleep frequency,Fmin01-08;10-18 delay and10-20 delay. Output returns and holds sleep frequency during depicted compensation interval. No inference that this is the same motor-stop behaviour as uncompensated mode.

Manual — PID display scaling and upper/lower limits — page 257

Manual reference: physical PDF page 257. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ PID feedback value bias can be monitored by parameter 10-27 (PID feedback bias display). ➢ Example:The feedback signal of 0-10V / 4-20mA is a pressure transducer. Refer to the figure 4.3.84 for displaying the unit conversion.

Figure 4.3.84 Feedback signal scaling Example: Feedbacl signal:0V=0%=1.0 PSI,10V=100%=20.0 PSI Parameter setting:10-27=10 (0% feedback value) 10-33=200 (100% feedback value)

➢ Target value of PID will be limited to the range of upper & lower limit of PID target.

➢ When 10-33 (the maximum value of PID feedback) is active, it will become 100% the

corresponding value of 10-02.

➢ Parameter 10-34 (PID decimal width) is used for rounding up setting.

For example:set 10-34=1, it displays XXX.X ; set 10-34=2, it displays XX.XX.

➢ Parameter 10-35 (PID unit) is selected depending on user’s needs.

Note:When user switches PID in LED keypad, 10-33 is required to be lower than 1000 and 10-34=1,

otherwise the keypad will show a “SE05” alarm (PID setting error).

Figure4.3.84 display conversion: vertical Display unit10-27 lower and10-28 upper; horizontal0V(4mA)to10V(20mA);0V0%=1PSI and10V100%=20PSI. Figure prints10-27=1.0; below example prints10-27=10 and10-33=200. Raw scaling conventions remain unharmonised.

PID display scaling and upper/lower limits

10-27 / PID Feedback Display Bias — PDF page 257

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-27 PID Feedback Display Bias
2 Range 【0~9999】

10-30 / Upper Limit of PID Target — PDF page 257

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-30 Upper Limit of PID Target
2 Range 【0 ~ 100】%
3 10-31 Lower Limit of PID Target
4 Range 【0 ~ 100】%

10- 33 / Maximum Value of PID Feedback — PDF page 257

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 33 Maximum Value of PID Feedback
2 Range 【1~10000】
3 10- 34 PID Decimal Width
4 Range 【0~4】
5 10- 35 PID Unit
6 Range 【0~23】

Manual — PID feedback-disconnection frequency and fire-mode gains — page 258

Manual reference: physical PDF page 258. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ When PID feedback disconnection is in alarm, frequency command output depends on the setting value of 10-39. If the warning is lifted, PID control is restored.

➢ PID functions of ire mode, please refer to parameter group 08.

PID feedback-disconnection frequency and fire-mode gains

10- 39 / Output Frequency Setting of PID Disconnection — PDF page 258

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 39 Output Frequency Setting of PID Disconnection
2 Range 【0.00~599.00】Hz

10- 47 / Proportioanl Gain (P) of Fire Mode — PDF page 258

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 47 Proportioanl Gain (P) of Fire Mode
2 Range 【0.00~10.00】
3 10- 48 Integral Time (I) of Fire Mode
4 Range 【0.0~100.0】Sec
5 10- 49 Differential Time (D) of Fire Mode
6 Range 【0.00~10.00】Sec

Manual — Group11 direction, carrier frequency and cable-length recommendations — page 259

Manual reference: physical PDF page 259. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Cable-length columns literally read <30m, <50m, <100m and >100m with maximum carrier values 16,10,5,2 kHz respectively. The columns overlap and exact 100m is not represented. Do not manufacture disjoint intervals or an equality rule.

Group 11 Auxiliary Parameters

➢ If motor operation direction is set to 1 or 2, the motor can only operate in that specific

direction. Run commands in the opposite direction are not accepted.

➢ Forward or reverse commands can be issued via the control terminals or keypad.

➢ Parameter 11-00 can be used in fan and pump application where reverse rotation is prohibited.

(1) Setting range from 1 to 16 represents kHz. (2) Setting range is determined by the inverter rating (13-00) and HD/ND mode (00-27). A low carrier frequency decreases RFI, EMI interference and motor leakage current. Please refer to the carrier frequency table 4.3.35

Table 4.3.35 Carrier frequency settings

➢ Refer to section 3 inverter derating based on carrier frequency. ➢ Lower capacity inverter can use higher carrier frequency, please refer section 3. ➢ A low carrier frequency increases motor noise but reduces motor losses and temperature. ➢ If cable length between the inverter and the motor is too long, the high-frequency leakage current will cause an increase in inverter output current, which might affect peripheral devices. Adjust the carrier frequency to avoid this as shown in table 4.3.36.

Table 4.3.36 Cable length and carrier frequency

➢ Reduce the carrier frequency if the torque does not match the speed.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Cable recommendations use overlapping <30m,<50m,<100m,>100m inequalities and do not cover exactly100m. No missing boundary inferred.

Group11 direction, carrier frequency and cable-length recommendations

Group11 direction, carrier frequency and cable-length recommendations Source body cells span all four carrier columns: full High-to-Low or Bad-to-Good-to-Bad trends are repeated only to preserve original merged geometry. They are not individual values for1,6,10or16kHz. Do not infer an exact Good range.

Source row 2: semantic_block: SHARED_TREND_ACROSS_ALL_FOUR_CARRIER_COLUMNS; layout_warning: Repeated original merged region; not a separate rating for each frequency. No exact Good interval inferred.

Source row 3: semantic_block: SHARED_TREND_ACROSS_ALL_FOUR_CARRIER_COLUMNS; layout_warning: Repeated original merged region; not a separate rating for each frequency. No exact Good interval inferred.

Source row 4: semantic_block: SHARED_TREND_ACROSS_ALL_FOUR_CARRIER_COLUMNS; layout_warning: Repeated original merged region; not a separate rating for each frequency. No exact Good interval inferred.

Source row 5: semantic_block: SHARED_TREND_ACROSS_ALL_FOUR_CARRIER_COLUMNS; layout_warning: Repeated original merged region; not a separate rating for each frequency. No exact Good interval inferred.

Source row 6: semantic_block: SHARED_TREND_ACROSS_ALL_FOUR_CARRIER_COLUMNS; layout_warning: Repeated original merged region; not a separate rating for each frequency. No exact Good interval inferred.

11-00 / Direction Lock Selection — PDF page 259

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11-00 Direction Lock Selection
2 Range 【0】:Allow forward and reverse rotation 【1】:Only allow forward rotation 【2】:Only allow reverse rotation

11-01 / Carrier frequency — PDF page 259

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11-01 Carrier frequency
2 Range 【1~16】kHz

Carrier Frequency / 1kHz / 6kHz / 10kHz / 16kHz — PDF page 259

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Carrier Frequency 1kHz 6kHz 10kHz 16kHz
2 Motor noise High ------------------------ Low High ------------------------ Low High ------------------------ Low High ------------------------ Low
3 Output current waveform (similar to sinusoidal wave) Bad -------- Good ------- Bad Bad -------- Good ------- Bad Bad -------- Good ------- Bad Bad -------- Good ------- Bad
4 Noise interference Low ------------------------ High Low ------------------------ High Low ------------------------ High Low ------------------------ High
5 Leakage current Low ------------------------ High Low ------------------------ High Low ------------------------ High Low ------------------------ High
6 Heat loss Low ------------------------- High Low ------------------------- High Low ------------------------- High Low ------------------------- High

Wire length / < 30m (<98ft) / <50m (<164ft) / <100m (<328ft) / >100m (>328ft) — PDF page 259

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Wire length < 30m (<98ft) <50m (<164ft) <100m (<328ft) >100m (>328ft)
2 Carrier frequency (11-01 value) Max value 16kHz (11-01=16kHz) Max value 10kHz (11-01=10kHz) Max value 5kHz (11-01=5kHz) Max value 2kHz (11-01=2kHz)

Manual — PWM controls and S-curve timings — page 260

Manual reference: physical PDF page 260. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ 11-02=1:Soft PWM

Soft PWM control can improve the metal noise produced by the motor, more comfortable for the

human ear. At the same time, Soft PWM also limits RFI noise to a minimum level. The default setting

of Soft PWM control is disabled. The maximum carrier frequency of soft PWM mode is 8kHz.

If inverter detects overheating situation, carrier will be reduce automatically. When overheating

situation is removed, carrier will back to the value of 11-01.

➢ When 11-03=0, carrier frequency operation will be set by 11-01.

➢ When 11-03=1, carrier frequency is automatically lowered when the inverter temperature is

higher than the setting value, to reduce the heat loss and avoid the over-heat trip of inverter.

➢ When inverter temperature (12-41) higher than 80°C, carrier frequency will decrease to 4KHz

automatically and will go back to the value of 11-01 once inverter terperature lower than 70°C.

➢ The S curve function for acceleration / deceleration is used to reduce mechanical impact caused

by the load during momentary starting and stopping of the inverter. To use the S curve

function set the time for acceleration start point (11-04), acceleration end point (11-05),

deceleration start point (11-06) and deceleration end point (11-07). Refer to figure 4.3.85.

Figure 4.3.85 S curve characteristic

➢ Total acceleration and deceleration time when S curve is used:

Figure4.3.85 S-curve: Run command ON/OFF; Output frequency rising and falling; S1=11-04 acceleration start,S2=11-05 acceleration end,S3=11-06 deceleration start,S4=11-07 deceleration end. Time axis; no inferred duration.

PWM controls and S-curve timings

11-02 / Soft PWM Function Selection — PDF page 260

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11-02 Soft PWM Function Selection
2 Range 【0】:Disable 【1】:Soft PWM

11-03 / Automatic Carrier Lowering Selection — PDF page 260

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11-03 Automatic Carrier Lowering Selection
2 Range 【0】:Disable 【1】:Enable

11-04 / S Curve Time Setting at the Start of Acceleration — PDF page 260

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11-04 S Curve Time Setting at the Start of Acceleration
2 11-05 S curve time setting at the End of Acceleration
3 11-06 S curve time setting at the Start of Deceleration
4 11-07 S curve time setting at the End of Deceleration
5 Range 【0.00~2.50】Sec

Manual — S-curve formulas and skip-frequency settings — page 261

Manual reference: physical PDF page 261. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ These parameters allow “jumping over” of certain frequencies that can cause unstable

operation due to resonance within certain applications.

➢ Prohibit any operation within the jump frequency range. During acceleration and deceleration

the frequency is continuous without skipping the jump frequency.

➢ To enable jump frequency 1-3 (11-08 to 11-10) set the frequency to a value greater than 0.0Hz.

➢ Use the jump frequency width (11-11) to create a jump frequency range.

➢ Refer to figure 4.3.86

Figure 4.3.86 Jump frequency operation

➢ Set parameter 04-05 (AI2 function selection) to 9 (frequency jump setting 4) to control the jump frequency via analog input AI2. Refer to figure 4.3.48. ➢ When jump frequency overlap the sum of the overlapped jump frequencies will be used as the jump frequency range. Refer to figure 4.3.87。

Figure 4.3.87 Jump frequency overlap

S-curve formulas as printed: Acceleration time=Acceleration time1(or2)+[(11-04)+(11-05)]/2. Deceleration time=Deceleration time1(or2)+[(11-06)+(11-07)]/2.

Figure4.3.86 Output Frequency against Frequency Reference: skip-frequency11-10 lowest,11-09 middle,11-08 highest; each band labelled11-11 width. Source prohibitions and acceleration/deceleration exception retained separately.

Figure4.3.87 overlapping skip bands: Jump frequency2 left,Jump frequency1 right; Actual jump frequency width spans depicted combined band. No numerical interval calculated.

S-curve formulas and skip-frequency settings

11-08 / Jump Frequency 1 — PDF page 261

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11-08 Jump Frequency 1
2 11-09 Jump Frequency 2
3 11-10 Jump Frequency 3
4 Range 【0.0~599.0】Hz
5 11-11 Jump Frequency Width
6 Range 【0.0~30.0】Hz

Manual — Energy saving and DC-bus over-voltage-prevention gains — page 262

Manual reference: physical PDF page 262. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ To enable manual energy savings to one of the digital input (03-00 to 03-05=20) to 20.

➢ Manual energy savings reduces the output voltage for the purpose of saving energy

➢ Manual energy saving gain (11-12) (1) When manual energy savings is enabled, output voltage of inverter will be determined by parameter 11-12, output voltage is percentage gain times the V/F voltage. (2) Manual energy saving control uses the voltage recovery time (07-23) to change the output voltage. ➢ Manual energy saving frequency (11-18) Setting parameter 11-18 manual energy savings frequency to 0.0 Hz disables the manual energy savings frequency activation function. Refer to figure 4.3.88

Figure 4.3.88 Manual energy saving operation

➢ Parameter setting: (1) If “OV” alarm still happened when 11-40=3, please increase the value of 11-17 in 0.1 unit. (2) If the setting value of 11-17 is not suitable, the ripple of speed and current will be higher. (11-14 is the target voltage of over-voltage prevention mode 3, it’s the voltage inhibition level.)

Figure4.3.88 Run OFF/ON; Manual energy saving command OFF/ON/OFF; Frequency reference≥11-18; voltage drop during command then recovery07-23; printed V/F pattern(01-02to01-09)×11-12. Timing relationships only as drawn.

Energy saving and DC-bus over-voltage-prevention gains

11- 12 / Manual Energy Saving Gain (VF) — PDF page 262

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 12 Manual Energy Saving Gain (VF)
2 Range 【0~100】%
3 11- 18 Manual Energy Saving Frequency
4 Range 【0.0~599.0】Hz

11- 14 / OV Prevention Level — PDF page 262

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 14 OV Prevention Level
2 Range 230V :【200~400】V 400V :【400~800】V
3 11- 17 Acceleration/Deceleration Gain
4 Range 【0.1~10.0】

11- 28 / Frequency Gain of Over Voltage Prevention 2 — PDF page 262

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 28 Frequency Gain of Over Voltage Prevention 2
2 Range 【1~200】%
3 11- 33 DC Voltage Filter Rise Amount
4 Range 【0.1~10.0】V
5 11- 34 DC Voltage Filter Fall Amount
6 Range 【0.1~10.0】V

Manual — Over-voltage-prevention thresholds and stamping applications — page 263

Manual reference: physical PDF page 263. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Over-voltage suppression is used for the application of likely causing to energy recharge.

Example:

There are two situations causing excessive energy to recharge the inverter in stamping application.

(1) When cam clutch is not engaged, the motor will accelerate and start flywheel. When motor

decelerates, the rotation speed will higher than motor speed owing to the large flywheel’s

inertia and then recharge the inverter.

(2) When cam clutch is engaged, the motor will start flywheel and compress the spring. When the

highest point of the cam moves beyond its center, the spring will release the power to the

flywheel and excessive energy output recharge the inverter.

Figure 4.3.90 Stamping Operation

Figure4.3.90 stamping application labels: Inverter fout,Motor fmotor,Gearbox,Flywheel,cam clutch,spring. Motoring fout>fmotor and Overhauling fout<fmotor. Mechanical illustration retained as bounded source label scope, no dimensions inferred.

Over-voltage-prevention thresholds and stamping applications

11- 35 / DC Voltage Filter Deadband Level — PDF page 263

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 35 DC Voltage Filter Deadband Level
2 Range 【0.0~99.0】V
3 11- 36 Frequency gain of OV Prevention
4 Range 【0.000~1.000】
5 11- 37 Frequency limit of OV Prevention
6 Range 【0.00~599.00】Hz
7 11- 38 Deceleration start voltage of OV prevention
8 Range 230V:【200~400】V 400V:【400~800】V
9 11- 39 Deceleration end voltage of OV Prevention
10 Range 230V:【300~400】V 400V:【600~800】V
11 11- 40 OV Prevention Selection
12 Range 【0】:Disable 【1】:OV prevention Mode 1 【2】:OV prevention Mode 2 【3】:OV prevention Mode 3

Manual — OVP control blocks and DC voltage filtering — page 264

Manual reference: physical PDF page 264. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Over-voltage prevention (OVP) function monitors the DC-bus voltage and adjusts the speed

reference, acceleration and deceleration rate, to prevent the inverter from tripping on an

overvoltage.

➢ When the speed reference is reduced, the motor will start to decelerate. When the inverter is

operating at a fixed output frequency and excessive regenerative energy back to the inverter is

detected, the inverter will accelerate the motor in order to reduce the DC-bus voltage. Refer to

figure 4.3.91.

Figure 4.3.91 OVP Operatrion

➢ When 11-40=1:OV Prevention Mode 1

(1) DC voltage filter is used to provide a stable reference value for determining the change in DC

voltage change during regenerative operation.

 Adjust the DC voltage filtering increase rate parameter 11-33 (DC Voltage Filter Rise

Amount). When the DC voltage exceeds 11-33 +11-35 (DC Voltage Filter Deadband Level),

the output of the filter will increase.

 Adjust the DC voltage filtering decrease rate parameter 11-34 (DC Voltage Filter Fall

the output of the filter will decrease.

 Monitor the DC voltage filter output by 12-20 (DC voltage filter value).

 Set the DC voltage filter decrease rate (11-34) to a greater value than the value of the DC

voltage filtering increase rate (11-33).

(2) When the inverter is operation at a fixed output frequency, the OVP function will monitor the DC-bus voltage to detect regenerative operation

 In case of a regenerative condition the inverter calculates the delta DC bus voltage value

and multiplies the value with parameter 11-36, the result is added to the frequency reference accelerating the motor to prevent on an overvoltage condition.

 When the regenerative energy decreases, the inverter output frequency will return to the

actual frequency reference. Deceleration rate is based on the DC voltage, as shown in figure 4.3.92.

Figure4.3.91 OVP block labels: DC bus voltage12-20; filter11-33/11-34/11-35; subtraction;gain11-36;limiter11-37;OVP Acc/Dec. OVP2 gain11-28→OVP2 Acc/Dec→limiter11-37;11-40=1or2 selections;11-40=0 bypass;Output Frequency After SFS and Output Frequency. Source signs and branch labels remain in image; no inferred wiring or algorithm validation.

Manual — OVP deceleration timing and tuning examples — page 265

Manual reference: physical PDF page 265. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.92 OVP deceleration time

(3) When the inverter is stopped, the deceleration rate can be set with parameter 00-15(Tdec1). In

case the DC voltage is too high, the inverter will decelerate based on the OVP deceleration time

as shown in figure 4.3.92

 Set DC-bus voltage in parameter 11-38 (start voltage of OVP deceleration) and set OVP

deceleration rate in 00-22 (Tdec3).

 When the DC voltage reaches this level, it is necessary to decelerate rapidly in order to

prevent the delta DC voltage of becoming too large.

 When DC voltage reaches the setting of 11-39 (stop voltage of OVP deceleration), it will

decelerate based on the set value of 00-24 (Tdec4)

 Deceleration rate is linear based on the slope defined by the start point (11-38) and end

point (11-39).

(4) Parameter 11-40 can enable and disable the OVP function, when 11-40=1, some functions will go back to default setting. 00-14(Tacc1)=5.0 sec (Acceleration speed reference of higher DC voltage) 00-22(Tdec3)=20.0 sec (OVP deceleration lower setting point) 00-24(Tdec4)=100.0 sec (OVP deceleration higher setting point) 11-04=0.0 sec 11-05=0.0 sec (OVP S-curve function needs to disable) 11-06=0.0 sec 11-07=0.0 sec

➢ When 11-40=2:OV prevention Mode 2

The process of OV prevention mode 2 is the same as that of OV prevention mode 1 but it

strengthens more the part of DC BUS over the deceleration stop voltage of OV prevention (11-39) in

Fig.4.3.92. It can accelerate frequency compensation to avoid OV protection by increasing

frequency gain of OV prevention 2 (11-28).

➢ When 11-40=3:OV prevention Mode 3

The inverter raise the output frequency temporarily to avoid OV, the output frequency won’t higher

than 01-02 (Maximum Output Frequency of Motor 1).Please adjust 01-02 according to each

application. If it still occurs “OV” in this mode, please raise the value of 11-17 in 0.1 unit.

(When 11-17 value is higher, the speed and current ripple will be raised.)

Figure4.3.92 OVP deceleration example: vertical OVP deceleration time Tdec;20sec at700V(11-38),100sec at750V(11-39); straight rising segment. Example labels only; no interpolated settings.

Manual — KEB settings, recovery conditions and Stop key — page 266

Manual reference: physical PDF page 266. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

KEB function can be used to keep the inverter from tripping on a under voltage condition due to a

momentary power-loss. To enable the KEB function set parameter 11-47 to a value greater than 0.0

sec. Upon detection of a power-loss the inverter uses the KEB deceleration time (11-47) to

decelerate the motor and using the regenerative energy from the motor to maintain the DC-bus at

a nominal level.

➢ KEB Deceleration Time (11-47)

(1) When 11-47=0, KEB function is disabled.

(2) Set 11-47 (KEB deceleration time) from 0.0 to 25.5.

➢ KEB Detection Level (11-48) If the DC-bus voltage falls below the value set in 11-48, the KEB is activated and the inverter starts decelerating according to the value set in 11-47. To accelerate back to the original output frequency one of the digital inputs (03-00 to 03-07) set for 48 (KEB acceleration) has to be activated and the DC voltage has to rise above 11-48 + delta V (Delta V = +10V for 230V series, Delta V = +20 V for 400V Series), refer to the example in figure 4.3.95.

Figure 4.3.95 KEB operation

This function can enable or disable the stop key of keypad display when 00-02=1 (external terminal)

or 00-02=3 (communication).

➢ 11-55= 0:Stop botton disabled.

➢ 11-55= 1:Stop botton enabled.

Figure4.3.95 KEB: DC bus dips below11-48; recovery margin10V for230V class or20V for400V class; Output frequency decelerates then reaccelerates; Run command and KEB reacceleration command shown as hatched active intervals. Full conditions remain in source prose.

KEB settings, recovery conditions and Stop key

11- 47 / KEB Deceleration Time — PDF page 266

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 47 KEB Deceleration Time
2 Range 【0.0~25.5】Sec
3 11- 48 KEB Detection Level
4 Range 230V :【190~210】V 400V :【380~420】V

11- 55 / STOP Key Selection — PDF page 266

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 55 STOP Key Selection
2 Range 【0】:Stop key is disabled when the operation command is not provided by operator 【1】:Stop key is enabled when the operation command is not provided by operator

Manual — Oscillation, strong magnetisation and random PWM parameters — page 267

Manual reference: physical PDF page 267. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Printed units absent for11-61 time and11-66/11-67/11-68 frequency values. Literal ranges retained; units not inferred.

➢ It is used to adjust preventing oscillation function.

➢ If the oscillation in driving motor occurs at normal duty, it is required to increase the

setting value gradually in the unit of 0.01.

➢ It is required to limit the preventing oscillation upper limit within the setting value.

➢ Adjust the response of oscillation function. (Time parameter of adjust preventing

oscillation function delay.)

➢ When 11-62=0 (Mode1) and 1 (Mode 2):The response to preventing oscillation is slower.

➢ When 11-62=2 (Mode 3):The response to preventing oscillation is faster.

➢ When 11-63=0: It has no function of flux-strengthening, the no-load current of high speed and low speed are the same. ➢ When 11-63=1: It has function of flux-strengthening, the torque of low speed is higher, but the no-load current is also higher, it is suitable for big load in low speed.

➢ Inverter will switch the PWM mode automatically when the output frequency is higher than

11-66.

➢ When inverter output frequency is higher than 11-68, the noise detection function will be

enabled. Inverter will change the ecectricmagnetic noise in operation according to the different

setting value of parameter 11-67.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Printed units absent for11-61 time and11-66/11-67/11-68 frequency values. Literal ranges retained; units not inferred.

Oscillation, strong magnetisation and random PWM parameters

11- 59 / Gain of Preventing Oscillation — PDF page 267

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 59 Gain of Preventing Oscillation
2 Range 【0.00~2.50】

11- 60 / Upper Limit of Preventing Oscillation — PDF page 267

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 60 Upper Limit of Preventing Oscillation
2 Range 【0~100】%

11- 61 / Time Parameter of Preventing Oscillation — PDF page 267

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 61 Time Parameter of Preventing Oscillation
2 Range 【0~100】

11- 62 / Selection of Preventing Oscillation — PDF page 267

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 62 Selection of Preventing Oscillation
2 Range 【0】:Mode 1 【1】:Mode 2 【2】:Mode 3

11- 63 / Strong Magnetic Selection — PDF page 267

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 63 Strong Magnetic Selection
2 Range 【0】:Disable 【1】:Enable

11- 66 / 2/3 Phase PWM Switch Frequency — PDF page 267

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 66 2/3 Phase PWM Switch Frequency
2 Range 【6.00~60.00】

11- 67 / RPWM Frequency Bias — PDF page 267

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 67 RPWM Frequency Bias
2 Range 【0~12000】
3 11- 68 RPWM Switch Frequency
4 Range 【6.00~60.00】

Manual — Random PWM and second oscillation-prevention settings — page 268

Manual reference: physical PDF page 268. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note:

When 11-02=2, the sum of 11-01+11-67 can not higher than the upper limit of carrier frequency,

please refer to the following points:

(1) If it gets error for setting 11-01, it means 11-02=2 and the sum of 11-66+11-67 is higher than

the ipper limit of carrier frequency, please try to adjust the value of 11-02 or 11-67.

(2) If it gets error for setting 11-67, it means 11-02=2 and the sum of 11-66+11-67 is higher than

the ipper limit of carrier frequency, please try to adjust the value of 11-02 or 11-01.

(3) When 11-01=2, then gets error for setting 11-01 or 11-67, please check whether the sum of

11-66+11-67 is higher than the upper limit of carrier frequency.

(4) If it gets error for setting 11-02=2, it means the sum of 11-66+11-67 is higher than the upper

limit of carrier frequency, please adjust the value of 11-01 or 11-67 for suitable range, then set

11-02=2.

➢ Adjust the response of Gain of Preventing Oscillation 3.

➢ If occur vibration with motor in ND mode, please increase by 0.01 unit to set.

➢ It is required to limit the preventing oscillation 3 upper limit within the setting value.

➢ Adjust the response of oscillation 3 function.

(Time parameter of adjust preventing oscillation function delay.)

11-72(Switching Frequency 1) and 11-73(Preventing Oscillation 2) setting as the photo below.

Oscillation plot prints Preventing Oscillation3 Gain; level11-69 to switch frequency1(11-72), declining to zero at switch frequency2(11-73); Output Frequency horizontal. Source headings call this second gain; discrepancy retained.

Random PWM and second oscillation-prevention settings

11- 69 / Gain of Preventing Oscillation 2 — PDF page 268

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 69 Gain of Preventing Oscillation 2
2 Rang 【0.00~200.00】%

11- 70 / Upper Limit of Preventing Oscillation 2 — PDF page 268

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 70 Upper Limit of Preventing Oscillation 2
2 Rang 【0.01~100】%

11- 71 / Time Parameter of Preventing Oscillation 2 — PDF page 268

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 71 Time Parameter of Preventing Oscillation 2
2 Rang 【0~30000】mSec

11- 72 / Switching Frequency 1 of Preventing Oscillation 2 — PDF page 268

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 72 Switching Frequency 1 of Preventing Oscillation 2
2 Rang 【0.01~300.00】Hz
3 11- 73 Switching Frequency 2 of Preventing Oscillation 2
4 Rang 【0.01~300.00】Hz

Manual — Group12 LED monitoring selections and digital input display — page 269

Manual reference: physical PDF page 269. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 12 Monitoring Parameters

Notes:

The highest bit is used for power-up monitor. The 4 least significant bits can be used to customize

the display sequence see page 4-4.

➢ When 12-04=0, Inverter displays the line speed at stop, operation or the modification of frequency. ➢ When 12-04≠0, 12-03 is set to the maximum line speed and corresponds to the maximum output frequency. For example: If the line speed display of 12-03 is 1800, the keypad display is 900 when frequency output is 30Hz.

➢ Terminal S1~S6 are represented using two segments of each digit. Segment turns on when input is active.

Group12 LED monitoring selections and digital input display

12- 00 / Display Screen Selection (LED) — PDF page 269

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 12- 00 Display Screen Selection (LED)
2 Range (Highest bit) 0 0 0 0 0 (Lowest bit) The value range if each bit is 0~8 from the highest bit to the lowest bit 【0】:No display 【1】:Output current 【2】:No display 【3】:DC busvoltage 【4】:heatsink temperature 【5】:PID feedback 【6】:AI1 value 【7】:AI2 value 【8】:Counter

12- 01 / PID Feedback Display Mode (LED) — PDF page 269

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 12- 01 PID Feedback Display Mode (LED)
2 Range 【0】:Display the feedback value in integer (xxx) 【1】:Display the feedback value with one place after the decimal point (xx.x) 【2】:Display the feedback value (x.xx) with two places after the decimal point
3 12- 02 PID Feedback Display Unit Setting (LED)
4 Range 【0】:xxxxx (no unit) 【1】:xxxPb (pressure) 【2】:xxxFL (flow)
5 12- 03 Line Speed Display (LED)
6 Range 【0~60000】RPM
7 12- 04 Line Speed Display Mode (LED)
8 Range 【0】:Display Inverter Output Frequency 【1】:Line Speed Display at Integer. (xxxxx) 【2】:Line Speed Display at One Decimal Place. (xxxx.x) 【3】:Line Speed Display at Two Decimal Places. (xxx.xx) 【4】:Line Speed Display at Three Decimal Places. (xx.xxx)

12- 05 / Status display of digital input terminal (LED / LCD) — PDF page 269

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 12- 05 Status display of digital input terminal (LED / LCD)
2 Range Read-only

Manual — Digital terminal display examples and inverter status bits — page 270

Manual reference: physical PDF page 270. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Example 3 has twelve displayed zero positions and three connector lines without labels; visible S6–S1, PLC, R2 and R1 labels remain. Separate examples above do not identify the three unlabelled positions. No terminal identity is assigned.

Example 1:

S1/S3/S5/S6 are ON, S2/S4 are OFF, 12-05 will turn on when RY1 without output. (LED)

Example 2:

S2/S3/S4 are ON, S1/S5/S6 are OFF, 12-05 will turn on when RY1/RY2/DO1 output at the same time.

➢ Please refer section 4.2 for instruction of parameter 12-11~12-43. ➢ Please refer parameter setting of 12-38/12-39 for PID feedback and 10-33~10-35 for display.

Example 3:S1~S6, RY1 and RY2 are OFF

➢ 12-43 Inverter status definition (some different with communication redister 2520H)

Bit 0 : Inverter Ready 1 : Ready 0 : Not ready yet Bit 1 : During Running 1 : Operation 0 : Stop Bit 2 : During Zero Speed 1 :“ON” Bit 3 : During Speed Agree 1 :“ON” Bit 4 : During Warning Detection 1 :“ON” Bit 5 : During Fault Dtection 1 : Abnormal Example:When inverter stop running at zero speed, parameter 12-43 will display below (LCD display)

LED Example1: six input indicators S1,S2,S3,S4,S5,S6 across first three digits. Active upper segments S1/S3/S5/S6;S2/S4 inactive. Source prose additionally mentionsRY1 without output; no output state inferred beyond source.

LED Example2: upper active segmentsS2/S3/S4, inactiveS1/S5/S6; lower outputsRY1/RY2/DO1active; PLC label at fourth digit inactive as drawn. Labels and active segments only, no wiring inference.

LCD Example3: twelve zero cells,0 OPEN,1 CLOSE; labels Input TerminalS6,S5,S4,S3,S2,S1 and Output TerminalPLC,R2,R1. Three connecting lines lack printed terminal names; unlabelled positions retained without assigning outputs. Example text saysS1~S6,RY1,RY2OFF.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Three LCD example3terminal position lines lack printed labels; identities not inferred.

Digital terminal display examples and inverter status bits

12- 43 / Inverter Status (LED/LCD) — PDF page 270

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 12- 43 Inverter Status (LED/LCD)
2 Range Read Only(Only on keypad display)

Manual — LCD inverter status example and monitoring cross-references — page 271

Manual reference: physical PDF page 271. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Refer to section 4.2 for other monitor parameters 12-11~12-83 Monitor parameter 12-38 (PID setting) and 12-39 PID (PID feedback) is required to refer to the descriptions of parameter 10-33~10-35.

LCD12-43 example00000101: bit0Inverter ready,bit1During running,bit2During zero speed,bit3During speed agree,bit4During warning detection(minor fault),bit5During fault detection(major fault),upper two bitsReserved. Each label prefixed1 indicates active state, not that every bit is1 in this example.

Manual — Group13 capacity codes, hours and parameter lock — page 272

Manual reference: physical PDF page 272. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 13 Maintenance Parameters

➢ When 13-05=0, Inverter logs the time while the inverter is powered-up. ➢ When 13-05=1, Inverter logs the time when the inverter is running.

Note:

Main frequency setting is 12-16. The value is equal to frequency setting of speed-stage 0 (05-01)

Group13 capacity codes, hours and parameter lock

Group13 capacity codes, hours and parameter lock Two independent Model/Display blocks. Last two rows have no left-hand physical cells; empty padding is explicitly NOT_APPLICABLE and contains no model or value.

Source row 1: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 2: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 3: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 4: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 5: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 6: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 7: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 8: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 9: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 10: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 11: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 12: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 13: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 14: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

Source row 15: semantic_block: INDEPENDENT_MODEL_DISPLAY_PAIR

13- 00 / Inverter Capacity Selection — PDF page 272

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 00 Inverter Capacity Selection
2 Range ----

Inverter Model / 13- 00 Display — PDF page 272

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Inverter Model 13- 00 Display Inverter Model 13- 00 Display
2 E510s-2P5 2P5 E510s-401 401
3 E510s-201 201 E510s-402 402
4 E510s-202 202 E510s-403 403
5 E510s-203 203 E510s-405 405
6 E510s-205 205 E510s-408 408
7 E510s-208 208 E510s-410 410
8 E510s-210 210 E510s-415 415
9 E510s-215 215 E510s-420 420
10 E510s-220 220 E510s-425 425
11 E510s-225 225 E510s-430 430
12 E510s-230 230 E510s-440 440
13 E510s-240 240 E510s-450 450
14 ⟦blank source cell⟧ ⟦blank source cell⟧ E510s-460 460
15 ⟦blank source cell⟧ ⟦blank source cell⟧ E510s-475 475

13- 01 / Software Version — PDF page 272

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 01 Software Version
2 Range ----
3 13- 02 Fault Record
4 Range ----
5 13- 03 Cumulative Operation Hours 1
6 Range 【0~23】hours
7 13- 04 Cumulative Operation Hours 2
8 Range 【0~65534】days
9 13- 05 Selection of Cumulative Operation Time
10 Range 【0】:Accumulative operation time while power on 【1】:Accumulative operation time when it is operating.

13- 06 / Parameters lock — PDF page 272

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 06 Parameters lock
2 Range 【0】:Parameters are read-only except 13-06 and main frequency 【1】:Reserved 【2】:All parameters are writable

Manual — Password setting and unlocking display sequences — page 273

Manual reference: physical PDF page 273. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ When 13- 07≠0, all parameter except main frequency can’t be modified. Only unlock the key

code, modify the parameters is allowable.

➢ Setting parameter lock key number example:

Step 1:

Step 2:

Lifting lock key code (password):

Password Step1:1st entry13-07→READ/ENTER→00000→Up or Down→12345→READ/ENTER→End→12345→DSP/FUN→13-07. Display text and drawn arrows retained as source procedure.

Password Step2:2nd entry13-07→READ/ENTER→00001;Up/Down incorrect10000→READ/ENTER→Err2;Set Password Failed path shows10000 andDSP/FUNreturn13-07. Correct12345→READ/ENTER→LOC;Set Password Successfully path12345andDSP/FUNreturn13-07.

Lifting lock key code:13-07→READ/ENTER→00002;Up/Down incorrect10000→READ/ENTER→LOC;Password failed to lift path10000/DSP/FUNreturn. Correct12345→READ/ENTER→End;Password successfully lifted path12345/DSP/FUNreturn13-07.

Password setting and unlocking display sequences

13- 07 Parameter / Lock Key Code — PDF page 273

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 07 Parameter Lock Key Code
2 Range 【00000~65534】

Manual — Factory initialization settings1–5 — page 274

Manual reference: physical PDF page 274. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Use parameter 13-08 to initialize the inverter to factory default. It is recommended to write down

the modified parameters before initializing the inverter. After initialization, the value of 13-08 will

return to zero automatically.

➢ 13-08=1:2 wires initialization (220V/380V)

(1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2

controls reverse operation / stop command. Refer to figure 4.3.1.

(2) Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 380V (440V calss).

(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.

➢ 13-08=2:2 wires initialization (220V/380V)

(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.

➢ 13-08=3:2 wires initialization (230V/400V)

(2) Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 400V (440V calss).

➢ 13-08=4:2 wires initialization (230V/460V)

(2) Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 460V (440V calss).

➢ 13-08=5:2 wires initialization (220V /415V)

(2) Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 415V (440V calss).

Factory initialization settings1–5

13- 08 / Restore factory setting / Initialize — PDF page 274

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 08 Restore factory setting / Initialize
2 Range 【1】:2 wires initialization (50Hz) (220V/380V) 【2】:2 wires initialization (60Hz) (220V/380V) 【3】:2 wires initialization (50Hz) (230V/400V) 【4】:2 wires initialization (60Hz) (220V/460V) 【5】:2 wires initialization (50Hz) (220V/415V) 【6】:2 wires initialization (60Hz) (230V/400V) 【7】:2 wires initialization (50Hz) (220V/440V) 【8】:2 wires initialization (60Hz) (220V/440V) 【9】:2 wires initialization (60Hz) (220V/380V) 【10】:2 wires initialization (60Hz) (220V/380V) 【1112】:PLC initialization (RESET)

Manual — Factory initialization6–10 and parameters preserved by reset — page 275

Manual reference: physical PDF page 275. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ 13-08=6:2 wires initialization (230V/400V)

(1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2

controls reverse operation / stop command. Refer to figure 4.3.1.

(2) Inverter input voltage (01-14) is automatically set to 230V (220V calss) or 400V (440V calss).

(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.

➢ 13-08=7:2 wires initialization (220V/440V)

(2) Inverter input voltage (01-14) is automatically set to 220V(220V calss) or 440V(440V calss).

(3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.

➢ 13-08=8:2 wires initialization (220V/440V)

➢ 13-08=9:2 wires initialization (220V/380V) (1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation / stop command. Refer to figure 4.3.1. (2) Inverter input voltage (01-14) is automatically set to 220V(220V calss) or 380V(440V calss). (3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz. ➢ 13-08=10:2 wires initialization (220V/380V) (1) Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation / stop command. Refer to figure 4.3.1. (2) Inverter input voltage (01-14) is automatically set to 220V(220V calss) or 380V(440V calss). (3) When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz. ➢ 13-08=1112:PLC initialization Clear built-in PLC ladder logic and related values. ➢ The following parameters will not be influenced by restore factory setting (13-08)

Factory initialization6–10 and parameters preserved by reset

No. / Parameters — PDF page 275

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 No. Parameters
2 00-00 Control Mode Selection
3 00-34 Language selection
4 00-27 HD/ND Mode Selection
5 01-00 V/F Curve Selection
6 01-26 V/F Curve Selection of Motor 2
7 13-00 Inverter Capacity Selection
8 13-03 Cumulative Operation Hours 1
9 13-04 Cumulative Operation Hours 2
10 13-05 Selection of Cumulative Operation Time

Manual — Password function2 and cumulative-hours reset — page 276

Manual reference: physical PDF page 276. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Password function2 and cumulative-hours reset

13- 10 / Parameter Password Function 2 — PDF page 276

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 10 Parameter Password Function 2
2 Range 【0~9999】
3 13- 51 Clear Cumulative Operation Hours
4 Range 【0】:Disable to Clear Cumulative Operation Hours 【1】:Clear Cumulative Operation Hours

Manual — Group14 PLC timer, counter and analog set values — page 277

Manual reference: physical PDF page 277. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 14 PLC Parameters

Group14 PLC timer, counter and analog set values

14- 00 / T1 set value 1 — PDF page 277

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 14- 00 T1 set value 1
2 14- 01 T1 set value 2 (mode 7)
3 14- 02 T2 set value 1
4 14- 03 T2 set value 2 (mode 7)
5 14- 04 T3 set value 1
6 14- 05 T3 set value 2 (mode 7)
7 14- 06 T4 set value 1
8 14- 07 T4 set value 2 (mode 7)
9 14- 08 T5 set value 1
10 14- 09 T5 set value 2 (mode 7)
11 14- 10 T6 set value 1
12 14- 11 T6 set value 2 (mode 7)
13 14- 12 T7 set value 1
14 14- 13 T7 set value 2 (mode 7)
15 14- 14 T8 set value 1
16 14- 15 T8 set value 2 (mode 7)
17 Range 【0~9999】

14- 16 / C1 set value — PDF page 277

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 14- 16 C1 set value
2 14- 17 C2 set value
3 14- 18 C3 set value
4 14- 19 C4 set value
5 14- 20 C5 set value
6 14- 21 C6 set value
7 14- 22 C7 set value
8 14- 23 C8 set value
9 Range 【0~65534】

14- 24 / AS1 set value 1 — PDF page 277

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 14- 24 AS1 set value 1
2 14- 25 AS1 set value 2
3 14- 26 AS1 set value 3
4 14- 27 AS2 set value 1
5 14- 28 AS2 set value 2
6 14- 29 AS2 set value 3
7 14- 30 AS3 set value 1
8 14- 31 AS3 set value 2
9 14- 32 AS3 set value 3
10 14- 33 AS4 set value 1
11 14- 34 AS4 set value 2
12 14- 35 AS4 set value 3
13 Range 【0~65534】

Manual — PLC MD set values and division minimum — page 278

Manual reference: physical PDF page 278. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Please refer to section 4.4 for built-in PLC function

PLC MD set values and division minimum

14- 36 / MD1 set value 1 — PDF page 278

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 14- 36 MD1 set value 1
2 14- 37 MD1 set value 2
3 14- 39 MD2 set value 1
4 14- 40 MD2 set value 2
5 14- 42 MD3 set value 1
6 14- 43 MD3 set value 2
7 14- 45 MD4 set value 1
8 14- 46 MD4 set value 2
9 Range 【0~65534】
10 14- 38 MD1 set value 3
11 14- 41 MD2 set value 3
12 14- 44 MD3 set value 3
13 14- 47 MD4 set value 3
14 Range 【1~65534】

Manual — Group15 PLC monitoring values — page 279

Manual reference: physical PDF page 279. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 15 PLC Monitoring Parameters

Group15 PLC monitoring values

15- 00 / T1 Current Value1 — PDF page 279

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 15- 00 T1 Current Value1
2 15- 01 T1 Current Value 2 (Mode7)
3 15- 02 T2 Current Value 1
4 15- 03 T2 Current Value 2 (Mode7)
5 15- 04 T3 Current Value 1
6 15- 05 T3 Current Value 2 (Mode7)
7 15- 06 T4 Current Value 1
8 15- 07 T4 Current Value 2 (Mode7)
9 15- 08 T5 Current Value 1
10 15- 09 T5 Current Value 2 (Mode7)
11 15- 10 T6 Current Value 1
12 15- 11 T6 Current Value 2 (Mode7)
13 15- 12 T7 Current Value 1
14 15- 13 T7 Current Value 2 (Mode7)
15 15- 14 T8 Current Value 1
16 15- 15 T8 Current Value 2 (Mode7)
17 Range 【0~9999】

15-16 / C1 Current Value — PDF page 279

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 15-16 C1 Current Value
2 15-17 C2 Current Value
3 15-18 C3 Current Value
4 15-19 C4 Current Value
5 15-20 C5 Current Value
6 15-21 C6 Current Value
7 15-22 C7 Current Value
8 15-23 C8 Current Value
9 Range 【0~65534】

15-24 / AS1 Current Value — PDF page 279

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 15-24 AS1 Current Value
2 15-25 AS2 Current Value
3 15-26 AS3 Current Value
4 15-27 AS4 Current Value
5 15-28 MD1 Current Value
6 15-29 MD2 Current Value
7 15-30 MD3 Current Value
8 15-31 MD4 Current Value
9 15-32 TD Current Value
10 Range 【0~65534】

Manual — Group16 LCD monitoring and engineering display units — page 280

Manual reference: physical PDF page 280. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: 16-03 option 3~39 is literally Reverse here but Reserved on PDF281. Listed intervals omit exactly 10000/20000/30000, while local engineering-unit prose says 00040–39999 continuously. Preserve both descriptions without choosing intended behaviour. PDF281 also has the separate final-example bound 30001–9999.

Group 16 LCD Function Group

➢ At power-up the inverter shows two monitor section on the display, main monitor section and

the sub-screen monitor section (smaller font).

➢ Choose the monitor signal to be displayed as the main-screen monitor screen in parameter

16-00, and the monitor signals to be displayed on the sub-screen monitor in parameters 16-01

and 16-02, similar to monitor parameters 12-5~12-83.

➢ Display unit of digital operator(16-03)

Set the units of the following items to be displayed, the frequency reference (05-01, 00-18,

06-01~06-15) and the monitoring frequency 12-16, 12-17 (Output frequency).

➢ Display unit of engineering (16-04)

When 16-03 = 00040-39999, engineering units are enabled. The displayed set range and the

frequency range of unit (05-01, 06-01~06-15) as well as the monitoring frequency (12-16, 12-17)

are changed by parameters 16-04 and 16-03.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: 16-03 listed ranges omit exact10000/20000/30000; no display behaviour inferred at these boundaries.

Group16 LCD monitoring and engineering display units

16- 00 / Main Screen Monitoring — PDF page 280

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 16- 00 Main Screen Monitoring
2 Range 【5~83】
3 16- 01 Sub-Screen Monitoring 1
4 Range 【5~83】
5 16- 02 Sub-Screen Monitoring 2
6 Range 【5~83】

16- 03 / Display unit — PDF page 280

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 16- 03 Display unit
2 Range 【0】:Frequency display unit is Hz (Resolution is 0.01Hz) 【1】:Frequency display unit is % (Resolution is 0.01%) 【2】:Frequency display unit is RPM 【3~39】:Reverse 【40~9999】:100% is XXXX with no decimals (integer only) 【10001~19999】:100% is XXX.X with 1 decimal 【20001~29999】:100% is XX.XX with 2 decimals 【30001~39999】:100% is X.XXX with 3 decimals
3 16- 04 Engineering Unit
4 Range 【0】: No Unit 【1】: FPM 【2】: CFM 【3】: PSI 【4】: GPH 【5】: GPM 【6】: IN 【7】: FT 【8】: /s 【9】: /m 【10】: /h 【11】: °F 【12】: inW 【13】: HP 【14】: m/s 【15】: MPM 【16】: CMM 【17】: W 【18】: kW 【19】: m 【20】: °C 【21】: RPM 【22】: Bar 【23】: Pa 【24】: kPa

Manual — LCD scaling examples and backlight — page 281

Manual reference: physical PDF page 281. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: 16-03 option 3–39 is Reserved here versus Reverse on PDF280. Final example prints 30001–9999, while the diagram above prints 30001–39999. Main intervals omit 10000/20000/30000 despite continuous 00040–39999 wording. Preserve literal ranges, including the 32555 / 2.555 m/s example, without correcting any bound.

➢ Adjust the screen contrast of the digital operator. If it is set to 0, the screen backlight is turned off.

LCD scaling graphic: leftmost fifth place selects number of decimal places;remaining four places set full display scaling excluding decimals.00040–09999 integer example1000;10001–19999 one decimal10.0;20001–29999 two decimals10.00;30001–39999 three decimals10.000. Source square symbols denote digit positions, not missing numeric values.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: 16-03 last example lower/upper range30001–9999 conflicts with30001–39999 above; exact10000/20000/30000 not specified. Literal bounds retained.

LCD scaling examples and backlight

16-03 / Set / displayed contents — PDF page 281

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 16-03 Set / displayed contents Set / displayed contents Set / displayed contents Set / displayed contents
2 0 0.01 Hz 0.01 Hz 0.01 Hz 0.01 Hz
3 1 0.01 % (maximum output frequency 01-02=100%) 0.01 % (maximum output frequency 01-02=100%) 0.01 % (maximum output frequency 01-02=100%) 0.01 % (maximum output frequency 01-02=100%)
4 2 Frequency display unit is RPM Frequency display unit is RPM Frequency display unit is RPM Frequency display unit is RPM
5 3- 39 Reserved Reserved Reserved Reserved
6 00040 - 39999 Set the decimal point by using the fifth place i.e. □ □□□□ Sets full display scaling excluding decimals Set the number of decimal places 00040 - 09999: □□□□ (Integer only e.g. 1000 ) 10001 - 19999: □□□. □ (1 decimal place e.g. 10.0) 20001 - 29999: □□. □□ (2 decimal places, e.g. 10.00) 30001 - 39999: □. □□□ (3 decimal places, e.g. 10.000) <Example>: Set the decimal point by using the fifth place i.e. □ □□□□ Sets full display scaling excluding decimals Set the number of decimal places 00040 - 09999: □□□□ (Integer only e.g. 1000 ) 10001 - 19999: □□□. □ (1 decimal place e.g. 10.0) 20001 - 29999: □□. □□ (2 decimal places, e.g. 10.00) 30001 - 39999: □. □□□ (3 decimal places, e.g. 10.000) <Example>: Set the decimal point by using the fifth place i.e. □ □□□□ Sets full display scaling excluding decimals Set the number of decimal places 00040 - 09999: □□□□ (Integer only e.g. 1000 ) 10001 - 19999: □□□. □ (1 decimal place e.g. 10.0) 20001 - 29999: □□. □□ (2 decimal places, e.g. 10.00) 30001 - 39999: □. □□□ (3 decimal places, e.g. 10.000) <Example>: Set the decimal point by using the fifth place i.e. □ □□□□ Sets full display scaling excluding decimals Set the number of decimal places 00040 - 09999: □□□□ (Integer only e.g. 1000 ) 10001 - 19999: □□□. □ (1 decimal place e.g. 10.0) 20001 - 29999: □□. □□ (2 decimal places, e.g. 10.00) 30001 - 39999: □. □□□ (3 decimal places, e.g. 10.000) <Example>:
7 00040 - 39999 16-03 Display Display Unit Display example
8 00040 - 39999 00040-09999 □□□□ Use 16-04 Setting  100 % speed is 0200  Set 16-03=00200 (from 05-01, 06-01 to 06-15, set range from 0040 to 9999).  Set 16-04=0 (no unit)
9 00040 - 39999 10001–19999 □□□. □ Use 16-04 Setting  100 % speed is 200.0 CFM  Set 16-03=12000 (05-01, 06-01 to 06-15, set range from 0000 to 9999).  set 16-04=2 (CFM)  60% speed will be displayed as 120.0 CFM
10 00040 - 39999 20001–29999 □□. □□ Use 16-04 Setting  100 % speed is 65.00ºC  Set 16-03=26500 (05-01, 06-01 to 06-15, set range from 0000 to 9999)  Set 16-04=20 (ºC)  60% of speed is displayed as 39.00 ºC
11 00040 - 39999 30001- 9999 □. □□□ Use 16-04 Setting  100 % speed is 2.555 m/s  Set 16-03=32555  Set 16-04=14 (m/s)  60% speed is displayed as 1.533 m/s

16- 05 / LCD Backlight — PDF page 281

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 16- 05 LCD Backlight
2 Range 【0~7】

Manual — Keypad copy, read protection and compatibility requirements — page 282

Manual reference: physical PDF page 282. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ LCD digital operator can be used to store and retrieve parameters

(1) Read:Save inverter parameters to the digital operator (INV → OP).

(2) Write:Write the parameters from the digital operator to the inverter (OP → INV)

(3) Verify:Compare the inverter parameters with the parameters in the digital operator.

➢ 16-07= 0:No action (1) 16-07= 1:Read (all parameters are copied from the inverter to the keypad) (2) 16-07= 2:Write (all parameter are copied from the keypad to the inverter) (3) 16-07= 3:Verify (Compare the set value to the parameter of the digital operator)

➢ Set 16-08=0

In order to prevent the saved parameter data stored in the digital operator fromaccidentally being

overwritten. When parameter 16-08=0 and the read operation is executed (16-07=1) a warning

message of "RDP Read Prohibited" will be displayed on the keypad and the read operation is

cancelled.

➢ For the write-in operation requires the following items to match.

(1) Inverter type

(2) Inverter rated capacity and voltage

Keypad copy, read protection and compatibility requirements

16- 07 / Copy Function Selection — PDF page 282

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 16- 07 Copy Function Selection
2 Range 【0】:Do not copy parameter 【1】:Read inverter parameters and save to the keypad 【2】:Write the keypad parameters to inverter 【3】:Compare parameters of inverter and keypad
3 16- 08 Selection of allowing reading
4 Range 【0】:Do not allow to read inverter parameters and save to the keypad 【1】:Allow to read inverter parameters and save to the keypad

Manual — READ copy procedure: inverter to keypad — page 283

Manual reference: physical PDF page 283. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ READ:Copy inverter parameters to the keypad

LCD source screen1: Group14 PLC Setting;15 PLC Monitor;16 LCD Keypad Func.(selected).

LCD source screen2: PARA16;−07:Copy Sel(selected);−08:READ Sel;−09:Keypad Loss Sel.

LCD source screen3: Edit16-07 Copy Sel;0 Normal selected;(0−3);<0>.

LCD source screen4: Edit16-07 Copy Sel;1 READ selected;(0−3);<0>.

LCD source screen5: −ADV− READ INV→OP with partial progress bar.

LCD source screen6: −ADV− READ COMPLETE with full progress bar.

LCD source screen7: RDP Read Prohibited

LCD source screen8: Edit16-07 Copy Sel;1 READ selected;(0−3);<0>.

READ copy procedure: inverter to keypad Three original outer columns,9physical rows including header;step6split success/error with original shared step cell. Eight bounded LCD records provide raster labels and inverse numeric selections. No instructions repaired.

Steps / LCD Display (English) / Description — PDF page 283

Source row Physical column1: Steps Physical column2: LCD Display (English) Physical column3: Description
1 Steps LCD Display (English) Description
2 1 ⟦blank source cell⟧ Select the copy function group (16) from the group menu.
3 2 ⟦blank source cell⟧ Press the Read / Enter key and select parameter (16-07) copy selection.
4 3 ⟦blank source cell⟧ Press the Read / Enter key to display the data setting / read screen (LCD display is inversed).
5 4 ⟦blank source cell⟧ Change the set value to 1 (read) by using the up arrow key.
6 5 ⟦blank source cell⟧ (1) Use Read / Enter key to enable the read operation, the display is shown as the left. (2) The bottom of LCD display will show a bar to indicate the read progress.
7 6 ⟦blank source cell⟧ (3) “READ COMPLETE” will be displayed on the keypad when reading was successful.
8 6 ⟦blank source cell⟧ (1) The error message of "RDP Read Prohibited" may occur on the keypad when reading parameters from the inverter is prohibited. (2) If the error is displayed, press any key to remove the error message and go back to parameter 16-07.
9 7 ⟦blank source cell⟧ When DSP/FUN key is pressed, the display returns to parameter 16-07.

Manual — WRITE copy procedure: keypad to inverter — page 284

Manual reference: physical PDF page 284. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

WRITE:Copy Keypad parameters to the Inverter

LCD source screen1: Group14 PLC Setting;15 PLC Monitor;16 LCD Keypad Func.(selected).

LCD source screen2: PARA16;−07:Copy Sel(selected);−08:READ Sel;−09:Keypad Loss Sel.

LCD source screen3: Edit16-07 Copy Sel;0 Normal selected;(0−3);<0>.

LCD source screen4: Edit16-07 Copy Sel;2 WRITE selected;(0−3);<0>.

LCD source screen5: −ADV− WRITE INV→OP with partial progress bar.

LCD source screen6: −ADV− WRITE COMPLETE with full progress bar.

LCD source screen7: WRE Write Error

LCD source screen8: Edit16-07 Copy Sel;2 WRITE selected;(0−3);<0>.

WRITE copy procedure: keypad to inverter Three original outer columns,9physical rows including header;step6split success/error with original shared step cell. Eight bounded LCD records provide raster labels and inverse numeric selections. No instructions repaired.

Steps / LCD Display (English) / Description — PDF page 284

Source row Physical column1: Steps Physical column2: LCD Display (English) Physical column3: Description
1 Steps LCD Display (English) Description
2 1 Group 14 PLC Setting 15 PLC Monitor 16 LCD Keypad Func. Select the copy function group (16) from the group menu.
3 2 ⟦blank source cell⟧ Press the Read / Enter key and select parameter (16-07) copy sel.
4 3 ⟦blank source cell⟧ Press the Read / Enter key to display the data setting / read screen (LCD display is inversed).
5 4 ⟦blank source cell⟧ Change the set value to 2 (write) by using the up arrow key.
6 5 ⟦blank source cell⟧ (1) Use Read / Enter key to enable the read operation, the display is shown as the left. (2) The bottom of LCD display will show a bar to indicate the read progress.
7 6 ⟦blank source cell⟧ “WRITE COMPLETE” will be displayed on the keypad when writing was successful. Inverter will show “WRITE Syslnit” after 3 seconds, please re-power again, inverter will start to download the parameters.
8 6 ⟦blank source cell⟧  The error message of “WRE Write Error” may occur on the keypad when writing parameters to the inverter is prohibited.  If the error is displayed, press any key to remove the error message and go back to parameter 16-07.
9 7 ⟦blank source cell⟧ When DSP/FUN key is pressed, the display returns to parameter 16-07.

Manual — VERIFY copy procedure and keypad-removal behaviour — page 285

Manual reference: physical PDF page 285. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Verify:Compare Inverter Parameters against Keypad Parameters

If 00-02=0, this parameter will decide whether inverter stops after digital operator removed.

LCD source screen1: Group14 PLC Setting;15 PLC Monitor;16 LCD Keypad Func.(selected).

LCD source screen2: PARA16;−07:Copy Sel(selected);−08:READ Sel;−09:Keypad Loss Sel.

LCD source screen3: Edit16-07 Copy Sel;0 Normal selected;(0−3);<0>.

LCD source screen4: Edit16-07 Copy Sel;3 VERIFY selected;(0−3);<0>.

LCD source screen5: −ADV− VERIFY INV→OP with partial progress bar.

LCD source screen6: −ADV− VERIFY COMPLETE with full progress bar.

LCD source screen7: VERY Verify Error

LCD source screen8: Edit16-07 Copy Sel;3 VERIFY selected;(0−3);<0>.

VERIFY copy procedure and keypad-removal behaviour Three original outer columns,9physical rows including header;step6split success/error with original shared step cell. Eight bounded LCD records provide raster labels and inverse numeric selections. No instructions repaired.

VERIFY copy procedure and keypad-removal behaviour

Steps / LCD Display (English) / Description — PDF page 285

Source row Physical column1: Steps Physical column2: LCD Display (English) Physical column3: Description
1 Steps LCD Display (English) Description
2 1 Group 14 PLC Setting 15 PLC Monitor 16 LCD Keypad Func.  Select the copy function group (16) from the group menu.
3 2 ⟦blank source cell⟧  Press the Read / Enter key and select parameter (16-07) copy sel.
4 3 ⟦blank source cell⟧  Press the Read / Enter key to display the data setting / read screen (LCD display is inversed).
5 4 ⟦blank source cell⟧  Change the set value to 3 (verify) by using the up arrow key.
6 5 ⟦blank source cell⟧ (1) Use Read / Enter key to enable the read operation, the display is shown as the left. (2) The bottom of LCD display will show a bar to indicate the read progress.
7 6 ⟦blank source cell⟧ (3) “VERIFY COMPLETE” will be displayed on the keypad when writing was successful.
8 6 ⟦blank source cell⟧ (3) The error message of “VRYE Verify Error” may occur on the keypad when writing parameters to the inverter is prohibited. (4) If the error is displayed, press any key to remove the error message and go back to parameter 16-07.
9 7 ⟦blank source cell⟧  When DSP/FUN key is pressed, the display returns to parameter 16-07.

16- 09 / Selection of keypad removed (LCD) — PDF page 285

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 16- 09 Selection of keypad removed (LCD)
2 Range 【0】:Keep operating when LCD keypad is removed 【1】:Display fault when LCD keypad is removed

Manual — Group17 automatic tuning parameters and ranges — page 286

Manual reference: physical PDF page 286. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Footnotes (1) and (2) have no explicit parameter-cell anchors. Footnote (2) lists HD 0–400Hz, ND 0–120Hz and high frequency 0–599Hz. PDF120 independently prints 17-04 as 4.8–599.0Hz, default60.0Hz, with no corresponding footnote anchor. Do not automatically apply footnote (2) to 17-04 or replace its range.

Group 17 Automatic Tuning Parameters

(1) Values are for 200V class, double the values for 400V class

(2) In HD mode (00-27=0) the range is 0.0 to 400.0 Hz, 0.0 to 120.0Hz in for ND mode (00-27=1)

and 0.0 to 599.0Hz is high frequency mode.

(3) Based on the motor nameplate set the motor rated output power (17-01), motor output rated

current (17-02), motor rated voltage (17-03), motor rated frequency (17-04), motor rated speed

(17-05) and number of motor poles (17-06) to perform an auto-tune.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Footnotes1and2 have no explicit table-row anchors; doubling400Vvalues and0Hzfrequency lower limit cannot be safely assigned to a parameter. Preserve detached notes without inference.

Group17 automatic tuning parameters and ranges

17- 00 / Mode selection of automatic tuning — PDF page 286

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 17- 00 Mode selection of automatic tuning
2 Range 【0】:Rotational auto-tuning 【1】:Static auto-tuning 【2】:Stator resistance measurement 【3】:Reserved 【4】:Loop tuning 【5】:Rotational Auto-tuning Combination (Item: 4+2+0) 【6】:Static Auto-tuning Combination (Item: 4+2+1)
3 17- 01 Motor rated output power
4 Range 【0.00~600.00】kW
5 17- 02 Motor rated current
6 Range VF mode:10%~120% of the inverter rated current SLV mode:25%~120% of the inverter rated current
7 17- 03 Motor rated voltage
8 Range 200V:【50.0~240.0】V 400V:【100.0~480.0】V
9 17- 04 Motor rated frequency
10 Range 【4.8~599.00】 Hz
11 17- 05 Motor rated speed
12 Range 【0~24000】RPM
13 17- 06 Pole number of motor
14 Range 【2~16】pole
15 17- 08 Motor no-load voltage
16 Range 200V:【50~240】V 400V:【100~480】V
17 17- 09 Motor excitation current
18 Range 【15~70】% of motor rated current
19 17- 10 Automatic tuning start
20 Range 【0】:Disable 【1】:Enable
21 17- 12 Proportion of Motor Leakage Inductance
22 Range 【0.1~15.0】%
23 17- 13 Motor Slip Frequency
24 Range 【0.10~20.00】Hz
25 17- 14 Rotational Auto-tuning
26 Range 【0】:VF type rotational auto-tuning 【1】:Vector type rotational auto-tuning

Manual — Auto-tuning methods and nameplate input requirements — page 287

Manual reference: physical PDF page 287. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Rotational auto-tuning (17-00=0)

Inverter can provide higher quality for motors. After executing Rotational auto-tuning (17-00),

Excitation current of motor 1 (02-09)、Core saturation coefficient 1 of motor 1(02-10)、Core

saturation coefficient 2 of motor 1 and Core saturation coefficient 3 of motor 1 (02-12) will renew

the value.

➢ Static auto-tuning (17-00=1)

Static auto-tuning won’t rotate the motor while auto-tuning. After executing Static auto-tuning

(17-00=1), Proportion of motor leakage inductance (02-33) and Motor slip (02-34) will renew the

value.

➢ Stator resistance measurement (17-00=2)

Stator resistance measurement provides for long motor length (exceed 50 meters). After executing

Stator resistance measurement (17-00=2), Resistance between wires of motor 1(02-15) will renew

➢ Loop tuning (17-00=4)

Loop tuning (17-00=4) provide great response of current circuit, it can improve frequency

bandwidth of current and torque.

➢ Rotation Auto-tuning Combination (17-00=5)

Rotation Auto-tuning Combination is the auto-tuning for three in one, including Loop tuning

(17-00=4), Stator resistance measurement (17-00=2) and Rotational auto-tuning (17-00=0).

➢ Static Auto-tune Combination (17-00=6)

Static Auto-tune Combination (17-00=6) is the auto-tuning for three in one, including Loop tuning

(17-00=4)、Stator resistance measurement (17-00=2) and Static auto-tuning (17-00=1)

➢ Motor rated output power (17-01)

Set by inverter capacity (13-00) according to the nameplate of motor.

➢ Motor rated current (17-02)

(1) Set by inverter capacity (13-00) according to the nameplate of motor.

(2) In V/F mode, set the range to 10~120 % of the inverter rated current.

(3) In SLV mode, set the range to 25~120% of the inverter rated current.

➢ Motor rated voltage (17-03)

Prevent the inverter output voltage from saturation when the motor rated voltage is higher than the

inverter input voltage (see Example 1).

➢ Motor rated frequency (17-04)

Please set the value according to motor nameplate

➢ Motor rated speed (17-05)

Manual — Auto-tuning voltage, current and measurement conditions — page 288

Manual reference: physical PDF page 288. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Number of poles (17-06)

Set the motor pole number with its range is 2~16 poles. (even)

➢ Motor no-load voltage (17-08)

(1) Motor no-load voltage is mainly used in SLV mode, set to value 10~50V lower than the input

voltage to ensure good torque performance at the motor rated frequency.

(2) When 17-08 set to 85~95% of the motor rated voltage. In general, the no-load voltage can be

closer to the motor rated voltage for larger motors, but cannot exceed the motor rated voltage.

(3) The motor no-load voltage can be set to a value greater than the actual input voltage. In this

case, the motor can only operates under relatively low frequency. If the motor operates at the

rated frequency an over voltage condition may occur.

(4) The higher the motor power is, the higher the no-load voltage is.

(5) A smaller no-load voltage will reduce the no-load current. When load is applied the magnetic

flux is weakened and the motor current increases.

(6) A higher no-load voltage results in a higher the no-load current. When load is applied the

magnetic flux weakens and the motor current increases. Increasing the magnetic flux generates

back EMF and results in poor torque control.

➢ Motor excitation current (17-09)

(1) Only the static-type or stator resistance measurement auto-tune (17-00=1 or 2) can be set.

(2) Motor excitation current is used for rotational auto-tune.

(3) Set motor excitation current to 33% of the motor rated current. During auto-tune the keypad

will display “Atune“ for Auto-tune in progress. When the motor is successfully tuned, the

keypad shows "AtEnd".

➢ Error history of automatic tuning (17-11)

(1) If auto-tuning fails the keypad will display the AtErr" message and the auto-tune cause is shown

in parameter 17-11.

(2) Refer to section 5 for troubleshooting and possible automatic tuning error causes.

Note:

The motor tuning error history (17-11) shows the tuning result of the last auto-tune. No error is

displayed when auto-tune is aborted or when the last auto-tune was successful.

➢ Proportion of Motor Leakage Inductance (17-12)

(1) Only the stator resistance auto tune (17-00=2) can be set.

(2) The static non-rotational type and rotational type auto tune will automatically measure the

proportion of motor leakage inductance so this parameter is not active.

(3) It is set the value to 4%. Refer to parameter 02-33 for test run to adjust.

➢ Motor Slip Frequency (17-13)

(3) Refer to parameter 02-34 for counting the setting value.

Manual — Auto-tuning examples and rotational method selection — page 289

Manual reference: physical PDF page 289. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example 1:

Motor rated voltage (440V/60Hz) is higher than the inverter input voltage (380V/50 Hz).

Figure 4.3.98 Rated voltageand frequency settings

Step 1: Set auto-tuning (17-00), and set motor rated output power (17-01) and the

motor rated current (17-02) by label of the motor.

Step 2: Set the value of motor rated voltage (17-03) =440V by label of the motor.

Step 3: Set the value of motor rated frequency (17-04) =60Hz

Step 4: Set the value of motor rated speed (17-05) 、pole number of motor (17-06)

Step 5: Set the value of motor no-load voltage (17-08) =360V, the set value for torque

control is 20V lower than input voltage.

Step6: Execute auto-tuning. Set auto-tuning (17-10=1) and enter to standby screen. Enter

RUN command to start auto-tuning. The value of motor rated frequency (17-04)

adjusts automatically to the same as the value of base frequency of motor 1.If the

value of maximum output frequency of motor 1(01-02) is different form base

frequency of motor 1 (01-12), the system will adjusts the value of maximum output

frequency of motor 1(01-02) the same as base frequency of motor 1 (01-12)

automatically.

➢ When the inverter input voltage (or frequency) is higher than the motor rated voltage

(or frequency), set the motor rated voltage (17-03) and the motor rated frequency

(17-04) to the rated frequency on the motor nameplate.

Example 2:

The inverter input voltage and frequency (460V/50Hz) are higher than the motor rated voltage and

frequency (380V/33Hz), set 17-03 to 380V (rated motor voltage) and 17-04 to 33Hz (motor rated

frequency).

➢ Rotational Auto-tuning (17-14)

(1) The parameter can be set (17-14) only when rotational auto-tuning (17-00=0) or Rotational

auto-tuning combination (17-00=5).

Figure4.3.98 example: inverter input380V/50Hz, motor nameplate440V/60Hz. Output Voltage versus Output Frequency;440Vnameplate upperline,17-03motor-rated-voltage forauto-tuning lowerline;60Hznameplate rightline,17-04motor-rated-frequency forauto-tuning leftline. Plot and adjacent setup instructions retained separately without reconciling their setting relationships.

Manual — Rotational auto-tuning method qualifications — page 290

Manual reference: physical PDF page 290. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(2) VF type rotational auto-tuning (17-14=0) applies the standard IM motor that won’t shake

without loading for V/F mode. This function is highly applicable.

(3) Vector type rotational auto-tuning (17-14=1) applies the special IM motor that will shake

without loading for V/F mode. This function applies for high speed motor. If execute VF type

rotational auto-tuning (17-14=0) unsuccessfully, try Vector type rotational auto-tuning

(17-14=1) again.

(4) Vector type rotational auto-tuning (17-14=1) measures no-loading current of motor by inner

current vector method. It avoid the problem appears oscillating current easily in V/F mode.

Manual — Group18 slip compensation parameters and formulas — page 291

Manual reference: physical PDF page 291. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 18 Slip Compensation Parameters

➢ The slip compensation function compensates for the motor slip to match the actual motor

speed to the reference frequency

➢ Slip compensation automatically adjusts the output frequency based on the motor load to

improve the speed accuracy of the motor mainly in V/F mode.

Slip compensation adjustment in V/F mode

➢ Slip compensation gain at low speed (18-00)

The default setting of 18-00 is “0.0”, when 18-00=0, the slip compensation function is disabled.

The adjustment of slip compensation gain at low speed follows the below procedure:

(1) Set the rated slip and the motor no-load current (02-00)

(2) Set the slip compensation (18-00) to1.0 (factory default setting is 0.0 in V / F control mode)

(3) For the operation with a load attached, measure the speed and adjust the slip gain (18-00)

accordingly (increase in steps of 0.1)

 If the motor speed is lower than frequency reference, increase the value of 18-00

 If the motor speed is higher than frequency reference, decrease the value of 18-00

When the output current(12-18) is greater than the no-load current(02-00, the slip

compensation is enabled and then output frequency increase from f1 to f2. Refer to figure

4.3.99, the slip compensation value is calculated as follows:

Slip compensation value=Motor rated slip frequency×[Output current(12-18)−no-load current ofMotor1(02-00)]/[Rated current ofMotor1(02-01)−no-load current ofMotor1(02-00)]. Motor Rated Slip Frequency(f)=[(Motor no-load synchronous speed−Motor full load rated speed)(N)×Motor Poles(P)]/120. Source formula labels and parentheses retained; no engineering evaluation.

Group18 slip compensation parameters and formulas

18- 00 / Slip compensation gain at low speed — PDF page 291

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 18- 00 Slip compensation gain at low speed
2 Range 【0.00~2.50 】
3 18- 01 Slip compensation gain at high speed
4 Range 【-1.00~1.00】
5 18- 02 Slip compensation limit
6 Range 【0~250】%
7 18- 03 Slip compensation filter
8 Range 【0.0~10.0】Sec
9 18- 04 Regenerating slip compensation selection
10 Range 【0】:Disable 【1】:Enable
11 18- 05 FOC delay time
12 Range 【1~1000】mSec
13 18- 06 FOC gain
14 Range 【0.00~2.00】

Manual — Slip compensation gain and torque/speed plots — page 292

Manual reference: physical PDF page 292. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.99 Slip compensation output frequency ➢ Slip compensation gain at high speed (18-01)

(1) It is not required to adjust the Slip compensation gain at high speed if the motor is loaded.

(2) After adjusting parameter 18-00 it is recommended to increase the reference frequency and

check the motor speed. In case of a speed error increase the value of 18-01 to adjust the

compensation.

(3) Increase the motor rated frequency (01-12 base frequency) and increase the value of 18-01 to

reduce the speed error.

(4) Compared to 18-00, 18-01 serves as a variable gain for the full speed range.

(5) If the speed accuracy becomes worse due to an increase in motor temperature it is

recommended to use a combination of 18-00 and 18-01 for adjustment.

Parameter 18-01 determines the slip compensation at the motor rated speed and is calculated follows:

Figure 4.3.102 18-00/18-01 Slip compensation gain versus frequency reference

Figure 4.3.103 18-01 Effect on torque speed curve

Figure4.3.99 Load Torque versus Speed: Smaller Load f1 and Larger Load f2, two torque curves shift right fromf1tof2; no numeric readings.

Source formula: Slip Compensation Gain=(Slip Compensation Gain at low speed+Slip Compensation Gain at high speed)×Reference Frequency/Motor rated frequency(01-12). Formula retained with the separately drawn gain plot; no repair.

Figure4.3.102 Slip compensation versus Frequency Reference: intercept/basegain18-00, incremental uppergain18-01 at markedreference. Ascending line from base; no numeric interpolation.

Figure4.3.103 Torque versus Speed: four centres with dashed flanking lines;leftarrowDecrease18-01 andrightarrowIncrease18-01 above first andlast group. Labels only; no calculated torque curves.

Manual — Slip limit, regeneration and SLV adjustment — page 293

Manual reference: physical PDF page 293. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ Slip compensation limit (18-02)

(1) Sets slip compensation limit in constant torque and the constant power operation

(Figure 4.3.100)

(2) When 18-02 is 0%, the slip compensation limit is disabled.

Figure 4.3.100 Slip compensation limit

When the slip compensation gain 18-00 at low speed is adjusted, and the actual motor speed is still

lower than the reference frequency, the motor may be limited by the slip compensation limit.

➢ Slip compensation filter (18-03)

Set slip compensation filter time in V/F mode

➢ Regenerating slip compensation selection (18- 04)

(1) Slip compensation selection enable or disable during regeneration period.

(2) To enable slip compensation during regeneration caused by deceleration (SLV mode), set

18-04 to 1 in case speed accuracy is required.

(3) When the slip compensation function is used regenerative energy might increase temporarily

(18-04= 1) therefore a braking module might be required.

SLV mode adjustment

➢ Slip compensation gain

(1) Slip compensation can be used to control the full rang speed accuracy under load condition.

(2) If the speed is lower than 2 Hz and the motor speed decreases, increase the value of 18-00.

(3) If the speed is lower than 2 Hz and the motor speed increases, reduce the value of 18-00.

Slip compensation gain uses a single value for the whole speed range. As a result the slip

compensation accuracy at low speed is high but slight inaccuracies might occur at high speeds.

For the speed control accuracy of full range, 18-00 is a fixed value. If inverter adjust speed accuracy

at lower speed, speed accuracy will also be happened at higher speed. If the speed accuracy at

higher speed is not acceptable, please adjust 18-00 or 18-01, but adjusting these parameters might

impact the accuracy at lower speeds.

Figure4.3.100 Slip Compensation Limit: constant18-02 untilFbase(01-12), then rising to[(01-02)/(01-12)]×18-02atFmax(01-02). No interpolation beyond printed formula.

Manual — Slip gain effect and FOC tuning conditions — page 294

Manual reference: physical PDF page 294. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

The impact of 18-00 on the torque and the speed are shown in figure 4.3.101

Figure 4.3.101 18-00 Effect on the torque and speed ➢ FOC (Flux Orient Control) delay time (18-05)

(1) In the SLV mode, the slip compensation of the magnetic flux depends on the torque current

and excitation current.

(2) If the motor load rises above 100% while running at the motor rated frequency, the motor

voltage and resistance drops sharply, which may cause the inverter output to saturate and

current jitter occur.

(3) The magnetic flux slip compensation will independently control the torque current and the

excitation current to prevent current jitter.

(4) For slow speed or fixed speed operation, 18-05 may be increased. For fast operation adjust

18-06.

➢ Slip compensation gain (18-06)

If the motor is jittering at the rated frequency under full load, the value of 18-06 may gradually be

reduced to zero to reduce current jitter.

Figure4.3.101 Torque versus Speed: vertical centreline with dashedflanks;leftDecrease18-00 andrightIncrease18-00. No numeric torque or speed values.

Manual — Group20 speed-control parameters, ASR gain and integral settings — page 295

Manual reference: physical PDF page 295. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 20 Speed Control Parameters

Parameter 20-33 is used when 20-07 is set to 0 and frequency command source is set to analog

input mode. Analog input signal, owing to the noise, will cause the system to determine the

operation does not reach the constant speed so the problem may occur. Thus, adjust parameter

20-33 to avoid this situation occurring.

Group20 speed-control parameters, ASR gain and integral settings

20- 00 / ASR gain 1 — PDF page 295

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 20- 00 ASR gain 1
2 Range 【0.00~250.00】
3 20- 01 ASR integral time 1
4 Range 【0.001~10.000】Sec
5 20- 02 ASR gain 2
6 Range 【0.00~250.00】
7 20- 03 ASR integral time 2
8 Range 【0.001~10.000】Sec
9 20- 04 ASR integral time limit
10 Range 【0~300】%
11 20- 07 Selection of acceleration and deceleration of P/PI
12 Range 【0】: PI speed control will be enabled only in constant speed. For the speed acceleration and deceleration, only use P control. 【1】: Speed control is enabled either in acceleration or deceleration.
13 20- 08 ASR delay time
14 Range 【0.000~0.500 】Sec
15 20- 09 Speed Observer Proportional(P) Gain1
16 Range 【0.00~2.55】
17 20- 10 Speed Observer Integral(I) Time 1
18 Range 【0.01~10.00】Sec
19 20- 11 Speed Observer Proportional(P) Gain2
20 Range 【0.00~2.55】
21 20- 12 Speed Observer Integral(I) Time 2
22 Range 【0.01~10.00】Sec
23 20- 13 Low-pass filter Time constant of speed feedback 1
24 Range 【1~1000】mSec
25 20- 14 Low-pass filter Time constant of speed feedback 2
26 Range 【1~1000】mSec
27 20- 15 ASR gain change frequency 1
28 Range 【0.0~599.0】Hz
29 20- 16 ASR gain change frequency 2
30 Range 【0.0~599.0】Hz
31 20- 17 Torque compensation gain at low speed
32 Range 【0.00~2.50】
33 20- 18 Torque compensation gain at high speed
34 Range 【-10~10】%
35 20-33 Detection Level at Constant Speed
36 Range 【0.1~5.0】%

Manual — ASR SLV block diagram and SLV/PMSLV settings — page 296

Manual reference: physical PDF page 296. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ The following figure an overview of the automatic speed regulator (ASR) block.

SLV control mode:

(1) The ASR function adjusts the output frequency to control the motor speed to minimize the

difference between the frequency reference and actual motor speed.

(2) The ASR controller in SLV mode uses a speed estimator to estimate the motor speed. In order

to reduce speed feedback signal interference, a low-pass filter and speed feedback

compensator can be enabled.

(3) The ASR integrator output can be disabled or limited. (03-00 to 03-05= 43). The ASR output is

passed through a low-pass filter.

Figure 4.3.108 ASR speed control diagram (SLV mode)

ASR Setting (SLV/PMSLV control mode)

(1) In SLV mode the ASR gain is divided into a high-speed and low-speed section. The speed

controller has a high-speed gain 20-00/20-01 and a low-speed gain 20-02/20-03 that can be

set independently. The switch between the high-speed and the low-speed is set by parameter

20-15 and 20-16.

(2) The high/low switch frequency can be set with parameter 20-15 and 20-16. Similar to the ASR

gain, the speed estimator has a high-speed gain 20-09/20-10 and a low-speed gain

20-11/20-12.

(3) The speed estimator has a low-pass filter to reduce the speed feedback interference, parameter

20-13 and 20-14 are active at high speed as well as low speed.The switch between the

high-speed and the low-speed is set by parameter 20-15 and 20-16.

(4) 20-17 sets the low-speed compensation gain of the speed feedback.

(5) 20-18 sets the high-speed compensation gain of the speed feedback.

(6) When the frequency reference is rises above the value set in 20-16, the ASR gain used is set by

parameters 20-00 and 20-01. When the frequency reference falls below the value set in 20-15,

the ASR gain used is set by parameters 20-02 and 20-03. Gain time constant is adjusted linearly

when the speed command falls within the range of 20-15 to 20-16, for a smooth operation.

Figure4.3.108 ASR speed control diagram(SLV): Frequency Reference positive and Speed Observer Feedback negative; P20-00/20-02 and I20-01/20-03; upper L/P Filter20-35 and P20-34; I Limit; ASR Delay time20-08; Torque Limit; Torque Reference. Integral branch labels20-07=1(During accel/decel) and20-07=0; Speed Control Integral Reset03-00to03-07=43. Feedback L/P Filter20-13/20-14; Speed Feedback Compensator20-17/20-18; Speed Observer inputs Motor Voltage and Motor Current; Observer Error, P20-09/20-11 and I20-10/20-12. Exact diagram labels retained without inferred wiring or mathematical model.

ASR procedure spans296–298; retain both instability warnings and exact switch/gain references. Source claims do not constitute engineering validation.

Manual — ASR gain curves and tuning procedure steps1–10 — page 297

Manual reference: physical PDF page 297. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.112 ASR gain setting (SLV mode)

➢ Tune the speed control gain

During ASR gain tuning, the multi-function analog output (AO1 terminal) can be used to monitor

the output frequency and motor speed (as shown in figure 4.3.112)。

➢ SLV mode gain tuning (20-00~20-03 , 20-09~20-18)

(1) Tune the low-speed ASR P and I gain 20-02 ~ 20-03, make sure the reference frequency is

below the value of parameter 20-15.

(2) Tune the high-speed ASR PI gain 20-00~20-01, make sure the reference frequency is above

parameter 20-16 value.

(3) Both low-speed ASR gain and the high-speed gain can be set to the same values and only

require to be adjusted in case of system instability.

(4) In case tuning of the ASR P and I gain 20-00~20-03 does not improve the system response,

reduce the low-pass filter time constant 20-13~20-14 to decrease the bandwidth of the

feedback system and re-tune the ASR gain.

(5) Tune low-speed low-pass filter time constant 20-14, make sure the reference frequency is

below parameter 20-15 value.

(6) Tune high-speed low-pass filter time constant 20-13 at frequency reference, make sure the

reference frequency is above parameter 20-16 value.

(7) Increasing the low-pass filter time constant can limit the bandwidth of the speed feedback

system and may reduce the system response. Increasing the low-pass time reduces the speed

feedback signal interference but may results in sluggish system response when the load

suddenly changes. Adjust the low-pass filter time if the load stays fairly constant during

normal operation. The low bandwidth of the speed feedback must be supported by the low

gain of ASR to ensure the stable operation.

(8) Decreasing the low-pass filter time constant may increase the bandwidth of the speed

feedback and the system response. Decreasing the low-pass time may increase the speed

feedback interference resulting in system instability when the load suddenly changes.

Decrease the low-pass filter time is a quick system response is required for rapidly changing

loads. The high bandwidth of the speed feedback allows for a relative high ASR gain.

(9) In case tuning 20-00~20-03 and the low-pass filter time constant 20-13~20-14 do not

improve the system response time, tuning the PI gain 20-09~20-12 of the speed estimator

may be required.

(10) Setting a high gain for the speed estimator (high proportion (P) gain and small integral

(I)time) increases the bandwidth of the speed feedback, but may cause speed feedback

interference resulting in system instability.

Figure4.3.112 ASR gain setting(SLV): three plots. First P,I versus Frequency Reference: low P=20-02,I=20-03 until20-15, rising to high P=20-00,I=20-01 at20-16. Second plot repeats high P=20-00,I=20-01 and20-15/20-16; no low-gain labels printed in this second plot. Third Time Constant:20-14 up to20-15, descending to20-13 at20-16. Source curves only; no numeric interpolation.

ASR procedure spans296–298; retain both instability warnings and exact switch/gain references. Source claims do not constitute engineering validation.

Manual — ASR tuning continuation steps11–18 and low-speed compensation — page 298

Manual reference: physical PDF page 298. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(11) Setting a low gain for the speed estimator (small proportion (P) gain and high integral

(I) time) decreases the bandwidth of the speed feedback, may improve speed feedback

interference resulting in a more stable system.

(12) The default values for the ASR can be used in most applications, no adjustment is required.

Adjusting the low-pass filter time and speed estimator gains requires a good understanding

of the overall system. If a high-speed system response in combination with stable operation is

required consider using SLV control mode.

(13) Parameter 20-15 sets the gain switch frequency at low-speed and parameter 20-16 sets the

gain switch frequency at high-speed.

(14) Operating at a speed below 20-15 will result in a larger excitation current for low-speed

operation accuracy. When the frequency reference rises above 20-16, the inverter will output

the rated excitation current at the no-load voltage (02-19).

(15) For general purpose applications parameter 20-15 should be set to a value of 5~50% of the

motor base frequency. If this value is too high, the inverter output may saturate. Parameter

20-16 should be set to a value of 4Hz or more above the value of 20-08.

(16) When experiencing speed jitter at high speed and stable operation during mid-range speed

while operating a heavy load (>100%), it is recommended to reduce the no-load voltage

(02-19) or tune the FOC parameters (18-05 ~ 18-06).

(17) Parameter 20-17 and 20-18 are for compensating speed feedback at low speed and high

speed.

(18) Use parameter 20-17 to adjust the torque compensation gain for the low speed range. By

tuning 20-17an offset is added to the torque-speed curve. Increase 20-17 when the no-load

speed is lower than the frequency reference. Decrease 20-17 when the no-load speed is

higher than the frequency reference.

The effect on the torque-speed curve from 20-17 is shown as the following figure

Figure 4.3.115 20-17 Effect on the torque-speed curve from

Use parameter 20-18 to adjust the torque compensation gain for middle to high speed range. For

most general purpose applications it is not necessary to adjust the 20-18. The effect on the

torque-speed curve from 20-18 is shown as the following figure 4.3.116.

Figure4.3.115 low-speed compensation: Torque vertical; Speed horizontal; Decrease20-17 arrow left, Increase20-17 arrow right; central solid and adjacent dashed vertical lines. No numeric torque or speed values.

ASR procedure spans296–298; retain both instability warnings and exact switch/gain references. Source claims do not constitute engineering validation.

Manual — High-speed compensation, ASR limit and derating compensation — page 299

Manual reference: physical PDF page 299. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.116 Effect on the torque-speed curve from 20-18

➢ ASR integral limit (20-04)

Setting a small value may prevent system response when the load suddenly changes.

➢ ASR main delay time (20-08).

(1) Does not require to be adjusted for general purpose applications.

(2) When the set value of 20-08 is set high, the speed response will be reduced, but the system is

more stable.

Refer to Fig.4.3.108 and Fig. 4.3.109. Torque compensation function of derating can reduce the

characteristics of ASR turning around under shock load.

➢ This gain effect is the same as ASR proportional gain (20-00, 20-02). And if this parameter is

coupled with low-pass filter time constant (20-35), it can avoid oscillation.

➢ This time constant is used for suppressing the oscillation produced by 20-34. But too large

compensation time constant will cause slower output response and then is unfavorable for

turned compensation.

➢ It is suggested that the setting value of parameter 20-34 is 30~50ms and 20-35 is 50~100ms.

Figure4.3.116 high-speed compensation: Torque vertical, Speed horizontal. Two sets of left Decrease20-18 and right Increase20-18 arrows, solid/dashed vertical curve markers. No numerical speed or torque readings.

High-speed compensation, ASR limit and derating compensation

20- 34 / Compensation Gain of Derating — PDF page 299

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 20- 34 Compensation Gain of Derating
2 Range 【0 ~25600】
3 20- 35 Compensation Time of Derating
4 Range 【0~30000】mSec

Manual — Group21 four torque limits and quadrant diagram — page 300

Manual reference: physical PDF page 300. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 21 Torque Limit Parameters

➢ In SLV and PMSLV control mode, there are four torque limits that can be set separately:

I. Positive torque limit in forward direction (21-05 positive torque limit)

II. Positive torque limit of reverse direction (21-06 negative torque limit)

III. Negative torque limit in reverse direction (21-07 forward regenerating torque limit)

IV. Negative torque limit in forward direction (21-08 reversal regenerating torque limit)

Figure 4.3.117 Torque limit setting

Figure4.3.117 torque-limit setting: Output Torque(T) vertical, Motor Speed horizontal. Quadrant I upper right21-05, II upper left21-08, III lower left21-06, IV lower right21-07. Positive torque above, Negative torque below; Reverse direction left, Forward direction right. Legend I Forward rotation positive torque;II Reverse rotation positive torque;III Reverse rotation negative torque;IV Forward Rotation negative torque. Keep labels distinct from inconsistent preceding prose mapping; no engineering correction.

Group21 four torque limits and quadrant diagram

Adjacent source context — repeated to preserve continuation:

21- 05 / Positive torque limit — PDF page 300

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 21- 05 Positive torque limit
2 Range 【0~300】%
3 21- 06 Negative torque limit
4 Range 【0~300】%
5 21- 07 Forward regenerating torque limit
6 Range 【0~300】%
7 21- 08 Reversal regenerating torque limit
8 Range 【0~300】%

Manual — Group22 PM motor nameplate parameters, SPM/IPM choice — page 301

Manual reference: physical PDF page 301. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 22 PM Motor Parameters

➢ The PM parameter group can be restored to factory setting (13-08), please confirm

the motor rating before initializing the inverter (13-00).

(1) PM motor rated power (22-00)

Set the motor power according to the motor nameplate.

(2) PM motor rated current (22-02)

Set the motor full load according to the motor nameplate.

(3) PM motor pole number (22-03).

Set the number of motor poles according to the motor nameplate.

(4) PM motor rated speed (22-04)

Set parameter 22-04 or 22-06, the inverter will automatically calculate the one or the other.

Set the motor rated speed in rpm according to the motor nameplate.

(5) PM motor maximum rotation speed (22-05) When using the flux-weakening function, the PM motor’s maximum rotation speed (22-05) must be set higher than the PM motor’s rated rotation speed (22-04).

(6) PM motor rated frequency (22-06)

Set the motor rated frequency according to the motor nameplate.

(7) PM type selection (22-07) When using the SPM motor, the recommended setting is 0. Related adjustable parameters are the

Printed formula: (PM motor rated speed)N = [120 × f(PM motor rated frequency)] / [P(PM motor pole number)]. Closing parenthesis after frequency is absent in rendered numerator; formula labels retained without inferring additional terms.

SPM/IPM selection sentence continues301→302:SPM0 uses22-30/22-31;IPM1 uses22-34/22-35. Preserve the page-linked continuation.

Group22 PM motor nameplate parameters, SPM/IPM choice

Adjacent source context — repeated to preserve continuation:

22- 00 / PM Motor Rated Power — PDF page 301

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 22- 00 PM Motor Rated Power
2 Range 【0.00~600.00】kW
3 22- 02 PM Motor Rated Current
4 Range 25%~200% inverter’s rated current
5 22- 03 PM Motor’s Pole Number
6 Range 【2~96】Poles
7 22- 04 PM Motor’s Rated Rotation Speed
8 Range 【0~60000】RPM
9 22- 05 PM Motor’s Maximum Rotation Speed
10 Range 【0~60000】RPM
11 22- 06 PM Motor Rated Frequency
12 Range 【4.8~599.0】Hz
13 22-07 PM type selection
14 Range 【0】SPM 【1】IPM

Manual — PM tuning, magnetic-pole detection and estimator parameter ranges — page 302

Manual reference: physical PDF page 302. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

speed estimated gain (22-30) and the speed estimated filter value (22-31). When using the IPM motor, the recommended setting is 1. Related adjustable parameters are the speed estimated gain (22-34) and the speed estimated filter value (22-35).

(8) PMSLV Start Current (22-10)

Set torque current at start and the unit is the percentage of motor rated current.

(9) I/F Mode Start Frequency Switching Point (22-11)

This function is for the switching point from open-loop to close-loop in PMSLV mode. The unit is

SPM/IPM selection sentence continues301→302:SPM0 uses22-30/22-31;IPM1 uses22-34/22-35. Preserve the page-linked continuation.

22-11unit explanation continues302→303:percentage of motor rated speed; source recommendationover5%for400Vandover10%for200V. PM tuning procedure must retain303warning of unexpected starting,death/seriousinjury andclear surrounding motor/load.

PM tuning, magnetic-pole detection and estimator parameter ranges

22- 10 / PM SLV Start Current — PDF page 302

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 22- 10 PM SLV Start Current
2 Range 【20.0 ~ 200.0】%
3 22- 11 I/F Mode Start Frequency Switching Point
4 Range 【1.0 ~ 20.0】%
5 22- 14 Armature Resistance of PM Motor
6 Range 【0.001 ~ 30.000】Ω
7 22- 15 D-axis Inductance of PM Motor
8 Range 【0.01 ~ 300.00】mH
9 22- 16 Q-axis Inductance of PM Motor
10 Range 【0.01 ~ 300.00】mH
11 22-18 Flux-Weakening Limit
12 Range 【0 ~ 100】%
13 22- 21 PM motor tuning
14 Range 【0】: PM Motor Tuning is not Active 【1】: Parameter Auto-tune Mode 1 【2】: Parameter Auto-tune Mode 2
15 22- 22 Fault History of PM Motor Tuning
16 Range 【0】: None 【1】: Static Magnetic Alignment Fault 【5】: Loop Adjustment is Time Out 【7】: Other Errors of Motor Tuning 【9】: Current Abnormity Occurs when Loop Adjustment
17 22- 23 PM SLV acceleration time
18 Range 【0.1~10.00】 Sec
19 22- 25 Detection Mode Selection of Initial Magnetic Pole
20 Range 【0】: Disable 【1】: Detection Mode 1 【2】: Detection Mode 2
21 22-26 Estimator Mode
22 Range 0~1 (in PMSLV mode)
23 22-27 Voltage Command of Mode 2
24 Range 【5 ~ 120】% (22-25=2 or 22-26=1 is enabled)
25 22-28 Divider Ratio of Mode 2
26 Range 【0~8】 (22-25=2 or 22-26=1 is enabled)
27 22-29 Flux-weakening Voltage Command Restriction
28 Range 【80 ~ 110】% (related to parameter 22-18)
29 22-34 IPM Estimator Gain
30 Range 【1 ~ 180】%

Manual — PM parameter units, tuning warnings, procedure and last fault — page 303

Manual reference: physical PDF page 303. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

percentage for rated speed of motor. It recommends that over 5% for 400V and over 10% for 200V.

(10) Armature Resistance of PM Motor (22-14)

Set resistor for each phase of the motor in unit of 0.001Ω. It is set automatically when the motor

auto-tunes (22-21).

(11) D-axis Inductance of PM Motor (22-15)

Set motor’s D-axis inductance in unit of 0.001mH. It is set automatically when the motor auto-tunes

(22-21).

(12) Q-axis Inductance of PM Motor (22-16),

Set motor’s Q-axis Inductance in unit of 0.001mH. It is set automatically when the motor auto-tunes

(13) Flux-Weakening Limit (22-18)

If the motor’s maximum rotation speed (22-05) is set to be higher than the motor’s rated rotation

speed (22-04), it will automatically start the flux-weakening control. It is set to limit the maximum

flux-weakening energy and the unit is the percentage of motor rated current.

(14) PM Motor Tuning (22-21)

WARNING!

The inverter and motor may start unexpectedly during Auto-Tuning, which could result in death or

serious injury. Make sure the area surrounding of the motor and load are clear before proceeding

with Auto-Tuning.

(1) Please set 00-00=5 and then set 22-21=1, before selecting PM motor tuning, enter the motor

data (22-00)~(22-06) according to the motor nameplate and the number of encoder pulses

(20-27).

(2) When 22-21=1, press the enter key to go to the PM motor tuning screen. The keypad will

display the message of “IPrdy” (Ready to Tune), press run to start the PM motor tuning. The

keypad will display the “IPtun” message during auto-tune.

(3) If the motor is successfully tuned, the message of “IPEnd” will be displayed. If auto-tune is

aborted with the stop key, the operator will display the message of “IPbrd“(PM motor tuning

aborted).

Note:

If inverter already performed motor auto tuning, it is not required to perform motor tuning

again when re-powered up.

(15) Fault History of PM Motor Tuning (22-22)

If PM motor tuning has field, the“IPErr”message is shown on the keypad (PM motor tuing failure).

Refer to section 5 for the possible error causes and trouble shooting.

PM motor tuning fault history (22-22) only stores the result of the last auto-tune performed. If

auto-tuning was successful or aborted, no error will be displayed.

22-11unit explanation continues302→303:percentage of motor rated speed; source recommendationover5%for400Vandover10%for200V. PM tuning procedure must retain303warning of unexpected starting,death/seriousinjury andclear surrounding motor/load.

PM tuning302offersmodes1and2;303procedure specifically uses22-21=1and00-00=5. Do not extend procedure to mode2 without source confirmation.

Manual — PM acceleration, rotor detection, estimator and flux weakening — page 304

Manual reference: physical PDF page 304. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(16) PM SLV acceleration time (22-23)

PM SLV acceleration time is the acceleration time from static to I/F Mode Start Frequency Switching

Point (22-11).

Note:

If occur error or vibration in PMSLV mode. Suggest to increase or decrease acceleration time. Please

adjust acceleration time by different application.

(17) Detection Mode Selection of Initial Magnetic Pole (22-25) Select the motor activation’s rotor position detection method Method 0: Do not detect rotor position, start by directly using the angle when the motor was previously stopped Method 1: Use input pulse signal to detect rotor position. Method 2: Use input continuous variable frequency signal to detect rotor position.

(18) Estimator Mode (22-26) It is suggested to set 22-26=0 when SPM motor is used. Inverter starts in I/f mode and the relevant adjustable parameters are 22-10 & 22-11. It is suggested to set 22-26=1 when IPM motor is used and speed control mode is performed by the speed control ratio 1:50. Inverter will input the continuously variable frequency signal to motor and the relevant adjustable parameters are 22-27 & 22-28. (19) Voltage Command of Mode 2 (22-27)

When 22-25=2 or setting of parameter 22-26 is enabled, input of the voltage amplitude setting for the continuously variable frequency signal will influence the motor jittering. When the motor starts and the rotor jitter occurs, it is required to increase the voltage amplitude to ensure the accuracy of detection angle. Note: When the voltage value is set too high, overcurrent error may occur. (20) Divider Ratio of Mode 2 (22-28)

When 22-25=2 or setting of parameter 22-26 is enabled, the input of continuous signal frequency depends on the parameter (11-01) carrier setting. If the carrier setting is higher, it is required to appropriately increase the divider ratio so as to reduce the input of continuous signal frequency and ensure the accuracy of detection angle.

(21) Flux-weakening Voltage Command Restriction (22-29)

It is set for preventing the saturation of the output voltage. Inverter performs flux-weakening control by the percentage of input power supply voltage as the limit of output voltage command. If flux-weakening current command restriction (22-18) is set too low, inverter output voltage may exceed the voltage command limit. (22) IPM Estimator Gain (22-34)

When the estimator mode (22-26) setting is 1, the estimator gain is the multiple of the bandwidth. The larger the setting value, the faster the motor response. However, if the value is too high, the control item will exhibit vibration and become unstable. The smaller the setting value, the greater the speed deviation. Please adjust the appropriate setting value according to the site equipment.

Manual — Group23 pump/HVAC/compressor functions and pump assignments — page 305

Manual reference: physical PDF page 305. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Note2 identifies control-mode parameter 00-00 but omits its setting value when disabling 23-00=1 or3. The nearby function choices do not supply that missing mode. Preserve the incomplete restriction without guessing a setting.

Group 23 Pump & HVAC Function Parameters

➢ Refer the wiring diagram of single/multi-pump in chapter 3.3. • Select function of pump or HVAC via parameter 23-00. This function is enabled if PID control mode (10-03) is enabled. Function of pump or HVAC affects PID target value and if parameter group 23 are enabled.。 • When 23-00=1, LCD keypad switches automatically the main screen monitoring (16-00) to operating pressure setting (12-74), the sub-screen monitoring 1 (16-01) to pressure feedback value (12-75) and sub-screen monitoring 2 (16-02) to output frequency (12-17). • When 23-00=2, LCD keypad switches automatically the main screen monitoring (16-00) to flow meter target setting (12-77), the sub-screen monitoring 1 (16-01) to flow meter feedback (12-71) and sub-screen monitoring 2 (16-02) to output frequency (12-17). • When 23-00=3, selection of main frequency command source (00-05) can be set except PID mode and V/F curve is limited to F (01-00). Middle output voltage (01-07) is automatically set to the half of maximum output voltage and parameter 01-00 will be hidden.

Note1 : Refer to the setting value of parameter 23-05 for the display of LED keypad.

Note2 : When the control mode switched to 00-00, the selection of 23-00=1 or 3 is disabled

➢ Set the inverter as the Master or Slave 1~3 via parameter 23-01. Refer to Fig 4.3.119 for the functional process of dual pump start to enable multiple pumps in parallel. It is required to reconnect to write in the parameter after it is set.

➢ Set the pressure value depending on the pressure transmitter of pump system after setting 10-00 to 0 (keypad given).

➢ Set the maximum pressure value depending on the pressure transmitter of pump system. Parameter 23-02 is limited to this maximum value.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Control-mode restriction inNote2 identifies00-00parameter but omits its setting value. Exact disabling condition cannot be reconstructed.

Group23 pump/HVAC/compressor functions and pump assignments

23- 00 / Function Selection — PDF page 305

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 00 Function Selection
2 Range 【0】: Disable 【1】: Pump 【2】: HVAC 【3】: Compressor

23- 01 / Setting of Single & Multiple Pumps and Master & Alternative — PDF page 305

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 01 Setting of Single & Multiple Pumps and Master & Alternative
2 Range 【0】: Single Pump 【1】: Master 【2】: Slave 1 【3】: Slave 2 【4】: Slave 3

23- 02 / Operation Pressure Setting — PDF page 305

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 02 Operation Pressure Setting
2 Range 【0.10 ~ 650.00】PSI

23- 03 / Maximum Pressure of Pressure Transmitter — PDF page 305

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 03 Maximum Pressure of Pressure Transmitter
2 Range 【0.10 ~ 650.00】PSI

Manual — Pressure command, LED displays and pump PID parameters — page 306

Manual reference: physical PDF page 306. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: 23-05header*2footnote marker lacks a matched note on this page. Applicability remains unresolved; displayed values and adjacent limits retained.

➢ Pressure command source is given the value set by 23-02 (Operation Pressure Setting) or AI. Refer to parameter 10-00 for the setting of AI terminal.

➢ This function can have the common display of target & feedback pressure or display separately

• When 23-05=0000, LED keypad displays pressure setting value and pressure feedback

Two-digit in the left is the pressure value setting and two-digit in the right is the pressure feedback value in the seven-segment monitor. When 23-00=2 (HVAC), the unit will be multiplied by 1000 times. If the display value is 5.0, it means 5000GPM

• When 23-05=0001:LED keypad only displays the pressure setting value.

• When 23-05=0002:LED keypad only displays the pressure feedback value.

Note:

If Pump mode is used LED keypad, parameter 23-03 is required to ≦ 99.0 PSI. If Pump mode is used PID mode, the value of 10-33 is required to ≦ 999 and 10-34=1.

23-05=0000 LED display visually reads2.0 on left and1.8 on right; source prose defines left pair pressure setting and right pair pressure feedback.

23-05=0001 LED display: left upper horizontal indicator followed by02.0; setting-pressure-only example. Indicator is kept as a graphic, not a minus sign or negative pressure.

23-05=0002 LED display: left lower horizontal indicator followed by01.8; feedback-pressure-only example. Indicator is kept as a graphic, not a minus sign or negative pressure.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: 23-05header*2footnote marker lacks a matched note on this page. Applicability remains unresolved; displayed values and adjacent limits retained.

Pressure command, LED displays and pump PID parameters

23- 04 / Pump Pressure Command Source — PDF page 306

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 04 Pump Pressure Command Source
2 Range 【0】: Set by 23-02 【1】: Set by AI

23- 05 / Display Mode Selection *2 — PDF page 306

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 05 Display Mode Selection *2
2 Range 【0】: Display of Target and Preesure Feedback 【1】: Only Display Target Pressure 【2】: Only Display Pressure Feedback

23- 06 / Proportion Gain (P) — PDF page 306

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 06 Proportion Gain (P)
2 Range 【0.00~10.00】
3 23- 07 Integral Time (I)
4 Range 【0.0~100.0】Sec
5 23- 08 Differential Time (D)
6 Range 【0.00~10.00】Sec

Manual — Pump PID adjustment, response illustrations and tolerance ranges — page 307

Manual reference: physical PDF page 307. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 4.4.103 Diagram of pressure feedback value

Table 4.3.17 Guide for PID parameter adjustment

Fig. 4.3.102 PID Diagram for PID parameter adjustment

• PID parameters can be modified during the inverter is running. • Cons: Disadvantage , Pros: Advantage

➢ When pressure feedback value is higher than 23-02 (operation pressure setting), inverter output frequency will decrease downward into sleep status. PID starts (output frequency will

Fig.4.4.103 pressure feedback: Overshooting,23-02 Target Pressure Value,Pressure Feedback Signal,Stablized Deviation and Stablized Time. Red feedback overshoots and settles below dashed target. No numeric scale.

Fig.4.3.102 PID adjustment: top Output after PID adjustment has small variation around dashed target; bottom Output before PID adjustment has larger repeated variation. Red outlined regions emphasize variation; no numeric values.

Constant-pressure tolerance sentence continues307→308:PID output frequency increases when feedback less than(23-02)-(23-09).

Pump PID adjustment, response illustrations and tolerance ranges

/ Increase Setting Value / Decrease Setting Value / Main Feature — PDF page 307

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 ⟦blank source cell⟧ Increase Setting Value Decrease Setting Value Main Feature
2 Proportional Gain (P) (Pros) Increase response time (Cons) Might cause pump jittering (Pros) Reduce jittering (Cons) Slow down response Increase stabilized time
3 Integral Time (I) (Pros) Smooth output frequency (Cons) Slow down response (Pros) Fast response (Cons) Change rapidly output frequency For smooth feedback variations
4 Differential Time (D) (Pros) Avoid overshooting (Cons) System instability or motor jittering (Pros) System stability (Cons) Overshooting easily Respond to system rapid variations

23- 09 / Tolerance Range of Constant Pressure — PDF page 307

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 09 Tolerance Range of Constant Pressure
2 Range 【0.01 ~ 650.00】PSI
3 23- 34 Tolerance Range of Constant Pressure 2
4 Range 【0.01 ~ 650.00】PSI

Manual — Pressure tolerance continuation, sleep frequency/time and pressure limits — page 308

Manual reference: physical PDF page 308. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

increase) when pressure feedback value is less than (23-02) – (23-09).

➢ When inverter output frequency falls below 23-10 (sleep frequency of constant pressure), it starts to count the sleep time (23-11). * : (When the motor’s maximum output frequency is over than 300Hz, the frequency resolution is 0.1Hz.)

➢ When the inverter finishes counting the sleep time (23-11), the output frequency falls downward at the deceleration time (00-15) and gets into sleep status. Parameter 23-10 (sleep frequency of constant pressure) is dedicated by the pump and it is not applied to parameter 10-17 (start frequency of PID sleep).

Fig. 4.3.103 Diagram for stop time of constant pressure

➢ It is convenient for user to limit maximum pressure. When pressure feedback value is higher than maximum pressure limit, the inverter displays warning signal and then stops.

➢ It is convenient for user to limit minimum pressure. When pressure feedback value is lower than minimum pressure limit, the inverter displays warning signal and then stops.

Fig.4.3.103 constant-pressure stop timing: upper Bar versus time,23-09 Sleep Tolerance Range,Pressure Feedback Signal,23-02 Target Pressure Value; lower Hz versus time,Output Frequency,23-11 Sleep Delay Time,23-10 Sleep Frequency. Footer formula Sleep Tolerance Range:[(23-02)-PID Feedback]<23-09. Plot uses Bar while tables use PSI; no unit conversion inferred.

Constant-pressure tolerance sentence continues307→308:PID output frequency increases when feedback less than(23-02)-(23-09).

Pressure tolerance continuation, sleep frequency/time and pressure limits

23- 10 / Sleep Frequency of Constant Pressure — PDF page 308

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 10 Sleep Frequency of Constant Pressure
2 Range 【0.0~400.0】Hz

23- 11 / Sleep Time of Constant Pressure — PDF page 308

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 11 Sleep Time of Constant Pressure
2 Range 【0.0~255.5】Sec

23- 12 / Maximum Pressure Limit — PDF page 308

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 12 Maximum Pressure Limit
2 Range 【0.00 ~ 650.00】PSI

23- 15 / Minimum Pressure Limit — PDF page 308

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 15 Minimum Pressure Limit
2 Range 【0.00 ~ 650.00】PSI

Manual — Pressure feedback limits, high-pressure warning and stop timing — page 309

Manual reference: physical PDF page 309. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 4.3.104 Diagram for pressure feedback limit

➢ The pressure under the control of PID is between the maximum pressure limit (23-12) and minimum pressure limit (23-15).

➢ When pressure feedback value is higher than maximum pressure limit, warning time of high pressure starts to count. If pressure feedback value is lower than maximum pressure limit during counting time, the warning time will recount and the inverter will display the warning signal of HIPb when the warning time ends.

➢ When the warning signal of high pressure occurs and pressure feedback value is higher than maximum pressure limit, stop time of high pressure starts to count. If pressure feedback value is lower than maximum pressure limit during counting time, the stop time will recount and the inverter will display stop error signal of OPbFt when the stop time ends. Note: When user does not want the inverter to be restricted by the maximum pressure, set 23-74=0 (disable) to disable the function of high pressure limit.

Fig.4.3.104 pressure feedback limit: vertical Pb,horizontal time;23-12 Maximum Pressure Limit above23-02 Target Pressure Value above23-15 Minimum Pressure Limit. Blue Pressure Feedback Signal around target. No numeric scale.

Pressure feedback limits, high-pressure warning and stop timing

23- 13 / Warning Time of High Pressure — PDF page 309

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 13 Warning Time of High Pressure
2 Range 【0.0 ~ 600.0】Sec

23- 14 / Stop Time of High Pressure — PDF page 309

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 14 Stop Time of High Pressure
2 Range 【0.0 ~ 600.0】Sec

Manual — High/low-pressure warning/stop plots and low-pressure settings — page 310

Manual reference: physical PDF page 310. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 4.3.105 Diagram for warning to stop at high pressure limit

➢ When pressure feedback value is lower than minimum pressure limit, warning time of low pressure starts to count. If pressure feedback value is higher than minimum pressure limit during counting time, the warning time will recount and the inverter will display the warning signal of LoPb when the warning time ends.

➢ When the warning signal of low pressure occurs and pressure feedback value is lower than minimum pressure limit, stop time of low pressure starts to count. If pressure feedback value is higher than minimum pressure limit during counting time, the stop time will recount and the inverter will display stop error signal of LPbFt when the stop time ends.

Fig. 4.3.106 Diagram for warning to stop at low pressure limit Note: When user does not want the inverter to be restricted by the minimum pressure, set 23-75=0

Fig.4.3.105 high-pressure stop: Bar/time Pressure feedback output above23-12Maximum pressure limit during highlighted intervals;23-02Target pressure value and23-15Minimum pressure limit below. Hz/time output held then Stop along deceleration time(00-15). T1<(23-13):Recounting afterT1;T2=(23-13):Keypad flashes and displaysHIPb;T3=(23-14):Keypad flashes and displaysOPbFt.

Fig.4.3.106 low-pressure stop as printed: Bar/time blue Pressure feedback output drawn near/above23-12Maximum pressure limit;23-02Target pressure value and23-15Minimum pressure limit below. Hz/time output held then Stop along deceleration time(00-15). T1<(23-16):Recounting afterT1;T2=(23-16):Keypad flashes and displaysLoPb;T3=(23-17):Keypad flashes and displaysLPbFt. Curve differs from preceding low-pressure prose; literal source retained.

Low-pressure note continues310→311:23-75=0disables lowpressurelimit.

High/low-pressure warning/stop plots and low-pressure settings

23- 16 / Warning Time of Low Pressure — PDF page 310

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 16 Warning Time of Low Pressure
2 Range 【0.0 ~ 600.0】Sec

23- 17 / Fault Stop Time of Low Pressure — PDF page 310

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 17 Fault Stop Time of Low Pressure
2 Range 【0.0 ~ 600.0】Sec

Manual — Loss-pressure detection, slave trip and water-pressure detection — page 311

Manual reference: physical PDF page 311. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Detail range for 23-22 is 0.0–599.0Hz; its operating cases cover exactly0Hz and1–599Hz. PDF126 summary confirms0.00–599.00Hz, default45.00Hz, V/F O and SLV/PMSLV X, but supplies no behaviour strictly between0 and1Hz. Counterpart confirms a range, not the missing operational rule.

(disable) to disable the function of low pressure limit.

➢ When 23-19 = 0 or 23-78 = 0, function of loss pressure detection is disabled. ➢ When 23-19 > 0, If the feedback pressure value is lower than the value of 【(23-02) x (23-19)】 and the detection time of loss pressure (23-18) passes, the inverter jumps to fault signal (FBLSS).

If Master and Slave start to run at the same time, Slave will stop depend on the condition listed as below: (1) When 23-22=0 Hz, if output frequency of Slave is lower than 23-10 (Sleep Frequency of constant Pressure) and after the time of 23-11 (Sleep Time of Constant Pressure), the Slave will be stop automatically.。 (2) When 23-22 = 1~599 Hz (The maximum frequency follow 01-02), if the output frequency of slave is lower than 23-22, Master will inform Slave to stop and enter sleep mode, or output frequency of Slave is lower than 23-10 (Sleep Frequency of Constant Pressure) and after the time of 23-11 (Sleep Time of Constant Pressure), the Slave will be stop automatically.

➢ When upward detection of water pressure starts, water pressure will slightly increase. At this time, it may cause shortly pressure fluttering or instability if water consumption continues. It is recommended to reduce the range of water pressure detection (23-24) but it will extend the time of inverter jumping into sleep without water consumption or with mild water consumption.

➢ 23-25 = 0.0 (sec) means to disable the function of water pressure detection. ➢ When function of water pressure detection is enabled, it can shorten the time of jumping into sleep without water consumption or with mild water consumption. ➢ If water consumption frequenctly continues, it is recommended to extend the cycle of water pressure detection (23-25) so as the detection times can be reduced and the occurrence of fluttering or instability during water pressure detection in constant pressure can be avoided.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: 23-22range0.0–599.0Hz but operation prose covers0Hz and1–599Hz; behaviour between0and1Hz not stated. No fractional boundary inferred.

Low-pressure note continues310→311:23-75=0disables lowpressurelimit.

Loss-pressure detection, slave trip and water-pressure detection

23- 18 / Time of Loss Pressure Detection — PDF page 311

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 18 Time of Loss Pressure Detection
2 Range 【0.0 ~ 600.0】Sec
3 23- 19 Proportion of Loss Pressure Detection
4 Range 【0 ~ 100.0】%

23- 22 / Slave Trip Frequency — PDF page 311

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 22 Slave Trip Frequency
2 Range 【0.0~599.0】Hz

23-23 / Direction of Water Pressure Detection — PDF page 311

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23-23 Direction of Water Pressure Detection
2 Range 【0】: Upward Detection 【1】: Downward Detection
3 23- 24 Range of Water Preesure Detection
4 Range 【0.00 ~ 65.00】PSI

23- 25 / Period of Water Preesure Detection — PDF page 311

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 25 Period of Water Preesure Detection
2 Range 【0.0 ~ 200.0】Sec

23- 26 / Acceleration Time of Water Pressure Detection — PDF page 311

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 26 Acceleration Time of Water Pressure Detection
2 Range 【0.1 ~ 6000.0】Sec
3 23- 27 Deceleration Time of Water Pressure Detection
4 Range 【0.1 ~ 6000.0】Sec

Manual — Water-pressure detection timing plots and downward-detection procedure — page 312

Manual reference: physical PDF page 312. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ 23-26 and 23-27 are corresponding to 00-16 and 00-17, so the setting of 23-26 changed with the setting of 00-16. When 23-26 value changed, the value of 00-16 will be changd automatically, avoid using multi-speed application function while using PUMP function.

Fig. 4.3.107 Diagram for upward detection of water pressure

Fig. 4.3.108 Diagram for download detection of water pressure

➢ When downward detection of water pressure starts, the output frequency will decelerate with the deceleration time of water pressure detection (23-27). Water pressure reduces with the deceleration when water consumption continues and pressure feedback value rises if the value is lower than that of target pressure value (23-02) - range of water pressure detection (23-24). It may cause shortly fluttering or instability during water detection process. User can appropriately adjust the range of water pressure detection (23-24) to avoid the occurrence of

Fig.4.3.107 upward water-pressure detection:23-23=0;Bar/time Pressure Feedback Value;23-24Range of Water Pressure Detection above23-02Target Pressure Value;Hz/time Output Frequency;23-26Acceleration Time Water Pressure Detection;23-25Period of Water Pressure Detection;23-11Sleep Time of Constant Pressure;23-10Sleep Frequency. Water Consumption Continues then Water Consumption Stops; no numerical time derived.

Fig.4.3.108 caption says download detection; diagram says23-23=1Downward Detection of Water Pressure. Bar/time Pressure Feedback Value;23-24Range of Water Pressure Detection below23-02Target Pressure Value;Hz/time Output Frequency;23-27Deceleration Time of Water Pressure Detection;23-25Period;23-11Sleep Time of Constant Pressure;23-10Sleep Frequency. Water Consumption Continues then Consumption Stops.

Downward pressure detection procedure continues312→313, including severe-flutter and reacceleration condition.

Manual — Water-pressure direction comparison, forced run and parallel settings — page 313

Manual reference: physical PDF page 313. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

severe flutter. Mild water consumption result in pressure reducing during deceleration and the inverter’s output frequency may decrease to sleep frequency. But if pressure feedback value is lower than that of target pressure value (23-02) - range of water pressure detection (23-24), the output frequency will accelerate again. Table 4.3.18 Guide for comparison of water pressure detection direction

➢ This function is enabled when PID mode (10-03) is selected. Pump will not depend on the feedback to make any PID output adjustment and runs the frequency of 00-05 (Frequency command) when multi-function digital input (S1~S6) is set to 16 (PID control disable). ➢ When the other digital input is set to 57 (forced frequency run), inverter sets the frequency to run depending on the parameter 23-28 (forced run command). If PID function disable is removed, the inverter is controlled by PID.

➢ If function of multiple pumps in parallel is enabled, the switching way is Master→Slave1→ Slave2→Slave3 → Master → … and the switching time is set via parameter 23-72.

➢ When parameter 23-31 is set to 1 or 3, detection time of multiple pumps in parallel running start is enabled. If water pressure can not reach the error range of constant pressure and water flow time is over the detection time (23-30), Master will inform Slave of running start.

Downward pressure detection procedure continues312→313, including severe-flutter and reacceleration condition.

23-31parameter options313continue as detailed descriptions314; all role and emergency-stop claims remain attributed supplier text.

Water-pressure direction comparison, forced run and parallel settings

/ Pros / Cons — PDF page 313

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 ⟦blank source cell⟧ Pros Cons
2 Upward detection of water pressure Keep the pressure above the target pressure during this process for strict and precise applications 1. If “Pump lift” is too high, operation frequency is higher without water consumption or with mild water consumption. So this detection effect is too restricted to jump into sleep. 2. Energy-saving of water flow is not obvious and Slave is not easy to sleep under the multiple pumps in parallel.
3 Downward detection of water pressure 1. Jump into sleep status without water consumption or with mild water consumption. 2. For energy-saving purpose, under the multiple pumps in parallel regulate the pumps to the optimum operation state during this process. 3. Startup sequency is by Master, Slave 1, Slave 2, and Slave 3. Sleep sequency is by Slave 1, Slave 2, and Slave 3 and Master. After the switching time is allowable, alternate Master and Slave reach the average of life expectancy. Pressure fluctuations may occur during this process if user inappropriately regulates the range of water pressure detection (23-24) and the deceleration time of water pressure detection (23-27).

23- 28 / Foreced Run Command — PDF page 313

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 28 Foreced Run Command
2 Range 【0.00 ~ 599.00】Hz

23-29 / Switching Time of Multiple Pumps in Parallel — PDF page 313

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23-29 Switching Time of Multiple Pumps in Parallel
2 Range 【0 ~ 240】hour/min

23- 30 / Detection Time of Multiple Pumps in Parallel Running Start — PDF page 313

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 30 Detection Time of Multiple Pumps in Parallel Running Start
2 Range 【0.0 ~ 30.0】Sec

23- 31 / Synchronous Selection of Multiple Pumps in Parallel — PDF page 313

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 31 Synchronous Selection of Multiple Pumps in Parallel
2 Range 【0】: Disable 【1】: Pressure Setting and Run/ Stop 【2】: Pressure Setting 【3】: Run/Stop

Manual — Parallel synchronisation details and dual-pump start sequence — page 314

Manual reference: physical PDF page 314. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ When 23-31=0 : Disabled ➢ When 23-31=1 : Set 23-01 to 1, Pressure setting and Run/ Stop command are modified by master and Slave follows Master’s command. Run/Stop command from Slave can be regarded as the emergency stop command with the highest priority. ➢ When 23-31=2 : Pressure setting is modified by Master and Slave follows Master’s command to update synchronously. ➢ When 23-31=3 : Run/ Stop command is set by Master and Slave follows Master’s command. Run/Stop command from Slave can be regarded as the emergency stop command with the highest priority. Note: 1. When Master modifies the pressure setting, it requires pressing ENTER key to modify the pressure setting of Slave. 2. When the switching time of multiple pumps in parallel (23-29) changes and reconnection, it will recount the time.

Fig. 4.3.109 Dual pumps start up process

A. Dual pumps are enabled during this time. Master starts up first and Slave is in standby to enter constant-pressure operation. B. Large water consumption results in the higher operation frequency of Master. If water pressure is not lower than the tolerance range of constant-pressure and the operation time is not over the detection time (23-30), Slave is still in standby. C. If it is over the detection time (23-30), and Master runs at 60Hz, Master informs Slave of auxiliary kicking water. After Slave operates, the operation frequency of Master and Slave reduces to the operation of constant-pressure if water consumption is stable. D. If water consumption is mild, the operation frequency of Master and Slave reduces. Because the water consumption is less than that of the operation of dual pumps, Slave stops to sleep (please refer to parameter 23-22 for dual pump slave sleep requirements) and only Master runs to reach constant-pressure operation.

Fig.4.3.109 Dual pumps start up: upper Bar/time pressure plot labels23-29Tolerance Range of Constant Pressure,23-30Detection Time,23-02Target Pressure Value,Pressure Feedback Value. Middle Master Hz/time Output Frequency reaches60Hz; lower Slave Hz/time Output Frequency starts in intervalC and stops afterD. IntervalsA,B,C,D align with adjacent source steps.23-29 label retained although source table calls it switching time.

23-31parameter options313continue as detailed descriptions314; all role and emergency-stop claims remain attributed supplier text.

Manual — Dual-pump sleep-stop alternation and roles — page 315

Manual reference: physical PDF page 315. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note 1: When 23-35=3, If the operation time is over the switching time (23-29) or sleep to stop under the operation of dual pumps, the dominance between Master and Slave will exchange to operate. Note 2: When 23-01≠0, the parameter 23-01 of these two inverters can not be simultaneously set to 1 or 2. That is, the parameter 23-01 of one inverter is set to 1 and that of the other inverter should be set to 2 and vice versa.

Diagram of sleep stop alternative selection action

Note: A. Dual pumps are enabled during this time. Higher operation pressure occurs, Master keeps operation and Slave output frequency decreases. B. Master operation frequency maintains 60Hz. If water pressure doesn’t decrease to the target constant pressure and Slave continuously decreases to the set trip frequency (23-22), Slave detection time (23-30) starts and Slave decelerates to stop. C. If milder water consumption and higher water pressure occur and Slave operation command is in sleep status, Master output frequency decreases to let the water pressure be in constant status when the detection time (23-30) is over. D. When Master operation frequency decreases to the sleep frequency of constant pressure (23-10), Master will decrease to stop, water consumption is continuously mild and water pressure will reduce slowly.。 E. When water consumption stops, Master jumps into sleep and the pressure remains the same. and Slave’s detection time (23-30) starts. F. When the detection time (23-30) is over, shift operation stops and virtual Master starts to become Slave. The inverter operates in constant pressure under the target pressure value.

Sleep stop alternative selection action: Bar/time Pressure Feedback Signal,23-09Tolerance Range of Constant Pressure,23-02Operation Pressure Setting. Master Hz/time Output Frequency initially60Hz,23-10Sleep Frequency of Constant Pressure; Slave Hz/time initially60Hz,23-22Slave Trip Frequency, two23-30Detection Time intervals. TimelineA,B,C,D,E,F ties to adjacent source steps; no inferred absolute timings.

Manual — Multiple-pump shift modes and leakage detection case1 — page 316

Manual reference: physical PDF page 316. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ When 23-35=1, the Master and Slave of multiple pumps in parallel will be exchange, after the switching time of multiple pumps in parallel.。 ➢ When 23-35=2, when the Master and Slave of multiple pumps in parallel are both in sleep mode, and after the detecting time (23-30), the Master and Slave of multiple pumps in parallel will be exchange. Every time the multiple pumps start, the exchange will be processed. Please refer to the diagram of sleep stop alternative selection action. ➢ When 23-35=3, Timer alternately selected and sleep stop alternately selected will be enabled at the same time. ➢ When 23-35=4, When master stop running and the slave need to run, please set 23-35=4, and no exchange between Master and Slave.

➢ To limit single inverter to use leakage detection. ➢ When 23-37 = 0.0 (sec), switch off this function.

Leakage Detection Case1:Pressure Variation>23-38. UpperBar/time Pressure Feedback Value;23-02Operation Pressure Setting;two23-37Leakage Detection Time intervals;ΔP1 andΔP2. LowerHz/time Output Frequency;Sleep then Leakage Detection Restart. Printed footer Pressure Variation of Leakage Detection Restart:ΔP1<23-38;ΔP2<23-38. Both less-than signs retained despite case heading and restart prose.

Multiple-pump shift modes and leakage detection case1

23-35 / Selection of Multiple Pumps Shift Operation — PDF page 316

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23-35 Selection of Multiple Pumps Shift Operation
2 Range 【0】: No function 【1】: Timer Alternative Selection 【2】: Sleep Stop Alternative Selection 【3】: Timer and Sleep Stop Alternative Selection 【4】: Multiple Pumps Test Mode

23-37 / Leakage Detection Time — PDF page 316

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23-37 Leakage Detection Time
2 Range 【0.0~100.0】Sec
3 23-38 Pressure Variation of Leakage Detection Restart
4 Range 【0.01~65.00】PSI
5 23-39 Pressure Tolerance Range of Leakage Detection Restart
6 Range 【0.01~650.00】PSI

Manual — Leakage detection case2, maximum pressure and switching units — page 317

Manual reference: physical PDF page 317. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ When pump is at shutdown state, pressure will drop over time if pipeline leaks. Pump will restart if pressure variation is larger than the value of parameter 23-38 in every detection time (23-37).

➢ When 23-37=0.0 (sec), switch off this function. ➢ When pump is at shutdown state, pressure will drop over time if pipeline leaks. Inverter will keep sleep state if pressure variation is lower than the value of parameter 23-38 in every detection time (23-37) and pump will restart if pressure variation is larger than that of 23-38 or pressure tolerance range is over the value of parameter 23-39 in the detection time. ➢ Properly adjust the relevant leakage detection parameters 23-37, 23-38 and 23-39 to improve the condition of frequenct pump start and stop caused from the dropping pressure of water system due to leakage. ➢ Function of leakage detection is enabled only in the setting of single pump.

➢ 23-02 (Operation pressure setting) is limited by 23-71 (Maximum pressure setting). 23-71 is limited by 23-03 (Maximum Pressure of Pressure Transmitter)

➢ When 23-72=0, parameter 23-29 will be in the unit of hour. ➢ When 23-72=1, parameter 23-29 will be in the unit of minute.

Leakage Detection Case2:Pressure Variation<23-18 printed in title. Bar/time Pressure Feedback Value;23-02Operation Pressure Setting;23-39Pressure Tolerance Range of Leakage Detection Restart;three23-37Leakage Detection Time intervals;ΔP1/ΔP2/ΔP3. Hz/time Output Frequency;Sleep then Leakage Detection Restart. Footer:ΔP1<23-38;ΔP2<23-28;ΔP3<23-28. Preserve these source references, not harmonised to23-38.

Leakage detection case2, maximum pressure and switching units

23-71 / Maximum Pressure Setting — PDF page 317

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23-71 Maximum Pressure Setting
2 Range 【0.10 ~ 650.00】PSI

23-72 / Switching Time of Alternation in Parallel — PDF page 317

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23-72 Switching Time of Alternation in Parallel
2 Range 【0】: Hour 【1】: Minute

Manual — Slave wakeup, ratio condition and high/low-pressure enabling — page 318

Manual reference: physical PDF page 318. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ When multiple pumps are in parallel and the requirements of slave wake-up can not be achieved in tolerance range, user can set parameter 23-73=1 and refer to the following conditions to wake up Slave. (1) Master is in full speed operation (01-02 maximum output frequency) but pressure feedback value can not achieve the target pressure value. (2) After the period of 30 seconds + time of (23-30), slave will be forced to start (even if the requirement of sleep to wake-up is not achieved and the pressure feedback value is under the tolerance range of constant pressure) and keeps operation to achieve the target pressure value. (3) It is required to follow the formula (the set method 1) and refer to the following diagram to set the wake-up requirements.

Diagram of requirements for waking up slave When the 23-22 (Slave Disconnect Frequency) setting value is too high or 23-30 (Parallel Start Pump Detection Time) is too short, it will make the Slave enter the Sleep Mode, to make the setting ineffective.

➢ When 23-74=0, High pressure warning or error is disabled. ➢ When 23-74=1, High pressure warning is enabled. High pressure error is disabled. ➢ When 23-74=2, High pressure warning or error is enabled. Refer to the instruction of Fig. 4.3.105.

➢ When 23-75=0, Low pressure warning or error is disabled. ➢ When 23-75=1, Low pressure warning is enabled. Low pressure error is disabled.

Slave wake-up diagram: verticalF; rising line from origin to01-02; horizontal level23-22; horizontal-axis markers23-30 and00-14. Formula:(23-30)/(00-14) ≥ (23-22)/(01-02), Set method1. No numerical ratio inferred; adjacent source conditions remain attached.

23-75lowpressure options318continue319:option2enableslowpressure warning/error and referencesFig4.3.106.319endssection;320startsPLC.

Slave wakeup, ratio condition and high/low-pressure enabling

23-73 / Slave Wake-up Selection — PDF page 318

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23-73 Slave Wake-up Selection
2 Range 【0】Disable 【1】Enable

23- 74 / High Pressure Setting — PDF page 318

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 74 High Pressure Setting
2 Range 【0】 Disable 【1】 High Pressure Warning 【2】 High Pressure Warning or Error

23- 75 / Low Pressure Setting — PDF page 318

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 75 Low Pressure Setting
2 Range 【0】Disable 【1】Low Pressure Warning 【2】Low Pressure Warning or Error

Manual — Low-pressure continuation and loss-pressure warning/error selector — page 319

Manual reference: physical PDF page 319. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ When 23-75=2, Low pressure warning or error is enabled. Refer to the instruction of Fig.4.3.106.

➢ When 23-78=1, the inverter will display warning signal when detecting the loss pressure.

➢ When 23-78=2, the inverter will display error signal when detecting the loss pressure.

23-75lowpressure options318continue319:option2enableslowpressure warning/error and referencesFig4.3.106.319endssection;320startsPLC.

Low-pressure continuation and loss-pressure warning/error selector

23- 78 / Selection of Loss Pressure Detection — PDF page 319

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 23- 78 Selection of Loss Pressure Detection
2 Range 【0】Disable 【1】Loss Pressure Warning 【2】Low Pressure Error

Manual — PLC basic command symbols,ranges and registers — page 320

Manual reference: physical PDF page 320. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4- 251

4.4 Built-in PLC function

The PLC ladder logic can be created and downloaded by TECO DriveLink software.

4.4.1 Basic Command

Description of special registers

Basic-command header glyphs columns2–7:normal output bracket;SET up-arrow;RESET down-arrow;P;normally-open contact;normally-closed contact. Column8NO/NC. Glyphs are command symbols,not extra data columns.

Other command symbol:SET up-arrow,RESET down-arrow,PcommandP. Upper DifferentialD and Lower Differentiald remain source columns.

Connection symbols top to bottom:horizontal line;T-junction left/right/top;cross left/right/top/bottom;T-junction left/right/bottom. Adjacent source text defines connections;no external wiring inferred.

PLC basic command symbols,ranges and registers

/ ↑ / ↓ / P / NO / NC — PDF page 320

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows)
1 ⟦blank source cell⟧ ⟦blank source cell⟧ ↑ ↓ P ⟦blank source cell⟧ ⟦blank source cell⟧ NO / NC
2 Inputs ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ I i I1~I8 / i1~i8
3 Outputs Q Q Q Q Q q Q1~Q2 / q1~q2
4 Auxiliary command M M M M M m M1~MF / m1~mF
5 Special registers ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ V1~V7
6 Counter function C ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ C c C1~C8 / c1~c8
7 Timer function T ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ T t T1~T8 / t1~t8
8 Analog comparison function G ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ G g G1~G8 / g1~g8
9 Operation control function F ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ F f F1~F8 / f1~f8
10 summation and subtraction function AS ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ AS1~4
11 Multiplication and division function MD ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ MD1~4
12 Encoder input comparsion command H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ H h H1~H4/h1~h4

V1:Set frequency / Range:0.1~599.0Hz — PDF page 320

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 V1:Set frequency Range:0.1~599.0Hz
2 V2:Operation frequency Range:0.1~599.0Hz
3 V3:AI1 input value Range:0~1000
4 V4:AI2 input value Range:0~1000
5 V5:Keypad input value Range:0~1000
6 V6:Operation current Range:0.1~999.9A
7 V7:Torque value Range:0.1~200.0%

Command / Upper Differential / Lower Differential / Other command symbol — PDF page 320

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Command Upper Differential Lower Differential Other command symbol
2 Differential command D d ⟦blank source cell⟧
3 SET command ⟦blank source cell⟧ ⟦blank source cell⟧ ↑
4 RESET command ⟦blank source cell⟧ ⟦blank source cell⟧ ↓
5 P command ⟦blank source cell⟧ ⟦blank source cell⟧ P

Open circuit / “ “ / — PDF page 320

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Open circuit “ “ ⟦blank source cell⟧
2 Short circuit “--” ⟦blank source cell⟧

Connection symbol / Definition — PDF page 320

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Connection symbol Definition
2 ─ Connect components on the left and right side
3 ┴ Connects components on the left , right and top side
4 ┼ Connects components on the left , right , top and bottom side
5 ┬ Connects components on the left , right and bottom side

Manual — Differential,normal,set and reset commands — page 321

Manual reference: physical PDF page 321. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4- 252

4.4.2 Basic command function

◎ D(d)command function

◎ NORMAL( -[ ) Output

D example1:I1—D—[Q1. I1OFF→ON→OFF;D andQ1 eachONforoneNew scanning cycleatI1risingedge,otherwiseOFF.

d example2:i1—d—[Q1. i1is inverse logic ofI1;I1OFF→ON→OFF,i1ON→OFF→ON. d1andQ1singleONpulseforNew scanning cycleatI1rising/i1fallingedge,otherwiseOFF.

NORMAL(-[)Output:I1—[Q1. I1OFF→ON→OFFandQ1OFF→ON→OFFaligned;no numeric period.

SET output:I1—SET-symbolQ1. I1OFF→ON→OFF;Q1OFFthenONandremainsONafterinputOFF.

RESET output:I1—RESET-symbolQ1. I1OFF→ON→OFF;Q1initiallyONthenOFFatinputONandremainsOFF.

Manual — P-mode inverse-input example — page 322

Manual reference: physical PDF page 322. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4- 253

P mode output:i1—PQ1;i1is inverse logic ofI1. I1highinitiallythenOFF/ON/OFF/ON/OFF/ON/OFF. Q1OFFinitially,togglesONatfirsti1risingedge,OFFatsecond,ONatthird,OFFatfourth. Source waveform relationships only,no scan period inferred.

Manual — Counter definitions and mode1 — page 323

Manual reference: physical PDF page 323. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4- 254

4.4.3 Application functions

  1. Counter Function

Counter modes:

Mode 1: Counter value is locked to the set value.

The value will not be retained when the power is cut off.

Mode 2: Counter value is not locked.

Mode 3: Counter value is locked.

The value will be retained when the power is cut off.

Mode 4: Counter value is not locked.

(1) Counter mode 1

Counter schematic numbered positions:1topinside;2upperleftinput;3lowerleftinput;4upperinternal;5lowerinternal;6rightoutput. Meanings retained in source table.

Counter mode1timing:compare⑤=20. Internal④sequence0,0,0,1,1,2,2,1,1,0,[blank],19,19,20,20,20,0,20,20. Counter input pulse;②directionOFFthenON,OFFthenON;③resetONinitiallythenOFFthenON;⑥outputOFF,briefON,OFF,ON,OFF. Blank timing-cell remains blank.

Counter modes and retention continue323–325. Blank timing cells stay blank; retention is stated for modes3/4. No values inserted into power-off interval.

Counter definitions and mode1

① / Counter mode (1 ~ 4) — PDF page 323

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 ① Counter mode (1 ~ 4)
2 ② UP/Down counting modes can be set by (I1 ~ f8).
3 ② OFF: Count up (0, 1, 2, 3…)
4 ② ON: Count down (…3,2,1,0)
5 ③ Use (I1~f8) to reset counting value
6 ③ ON: Internal count value is reset and counter output ⑥ is OFF
7 ③ OFF: Internal counter value retained
8 ④ Internal counter value
9 ⑤ Counter compare value (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7,constant)
10 ⑥ Counter output (C1 to C8, there are a total of 8 counters)

Manual — Counter example and mode2 — page 324

Manual reference: physical PDF page 324. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4- 255

Example:

(2) Counter mode 2

Note:

In this mode the internal counter may increase past the counter compare value, unlike mode 1

where the internal counter value is limited to the counter compare value.

Counter example:ladder labelsI1,i2,[C3],C3,[Q1],m1,q1,[M2],M2. C3inputpulse determinedbyI1andi2. FunctionM2Up/downcounting,I3ONreset;internal0000;compare0020;outputC3. Callout:C3turnsONwhencounterreachesSetValue,andC3inputinladderturnsONaswell. No inferred topology.

Counter mode2timing:⑤=20;④sequence0,19,19,20,20,21,21,20,20,19,20,18,18,19,19,20,0,20,20. Counterinputpulse;②OFF→ON→OFF→ON;③OFFthenONlate;⑥OFF→ON→OFF→briefON→OFF. Adjacent note allowsinternalcountpastcomparevalueunlikemode1.

Counter modes and retention continue323–325. Blank timing cells stay blank; retention is stated for modes3/4. No values inserted into power-off interval.

Manual — Counter retention and timer definition — page 325

Manual reference: physical PDF page 325. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4- 256

(1) Counter mode 3 is similar to the counter mode 1, with the exception that the counter value is saved when the drive is powered down and reloaded at power up. (2) Counter mode 4 is similar to the counter mode 2, with the exception that the counter value is saved when the drive is powered down and reloaded at power up.

  1. Timer Function

Retention timing:⑤=20.④Mode1&2visible1,1,2,2,blankinterval,0,1,1,2,2.④Mode3&4visible1,1,2,2,3,blankinterval,3,4,4,5,5. Counterinputpulse;PowerswitchONthenOFFthenON;⑥outputlow. Blankcellsnotfilled;proseexplainsretentionformodes3/4.

Timer schematic:1topinternal;2upperleftinput;3lowerleftreset;4current;5set;6rightoutput. Meanings/timingunits retained in table.

Counter modes and retention continue323–325. Blank timing cells stay blank; retention is stated for modes3/4. No values inserted into power-off interval.

Counter retention and timer definition

Symbol / Description — PDF page 325

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Symbol Description
2 ① Timer mode (1-7)
3 ② Timing unit 1:0.0~999.9 second
4 ② 2:0~9999 second
5 ② 3:0~9999 minute
6 ③ Use (I1~f8) to reset timing value
7 ③ ON:Internal timing value is reset and timer output ⑥ is OFF
8 ③ OFF:Internal timer stays running
9 ④ Internal timer value
10 ⑤ Timer set value (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7,constant)
11 ⑥ Timer output (T1 to T8, there are a total of 8 timers)

Manual — Timer modes1/2 and T5example — page 326

Manual reference: physical PDF page 326. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4- 257

Timer mode description:

(1) Timer mode 1 (ON-delay Timer mode 1)

Example:

(2) Timer mode 2 (ON-delay Timer mode 2)

ON-delay mode1:Timer startOFF→ON→OFF;④Internal timer value begins atstartON;⑤T=timer set value;⑥outputOFFthenONafterT,OFFwhenstartOFF.③Timer reset/internal timer value=0left;Reset internal timer value and outputright.

T5example:ladderI1,[T5],T5,[Q1]. CalloutWhenI1=0,the5thtimerstarts. Function:Timing unit0.1second;TimerMode1;unit1,mode1,current000.0,set010.0,outputT5. At10.0seconds,outputT5ON. PreserveI1=0calloutwithoutreinterpretingrising-edgeplot.

ON-delay mode2:TimerstarttwoONintervalst1andt2;⑤T=t1+t2;⑥outputONwhenaccumulatedTmetandremainsONuntil③Reset timer and outputON;resetthenOFF.④Internal timer value;T=timer setvalue.

Timer definitions325 and modes326–327 retain source waveform relationships. Prior reviewed328 contains later modes and is not reprocessed; no signal topology inferred.

Manual — Timer modes3/4/5 — page 327

Manual reference: physical PDF page 327. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4- 258

(3) Timer mode 3 (OFF-delay Timer mode 1)

(4) Timer mode 4 (OFF-delay Timer mode 2)

(5) Timer mode 5 (FLASH Timer mode 1)

OFF-delay mode1firstdiagram:TimerstartbriefON;⑥outputONwithstartthenholdsTafterstartOFF,thenOFF.③ResetOFFthroughout;④Internal timer value;T=timer setvalue. PrintedboilerplatelabelsaysWhensetvaluereachedoutputturnson;waveformretainedseparately.

OFF-delay mode1second:TimerstartON/OFFpulses;outputONwithfirstpulse,reset③ONinterruptsfirstdelay;laterstartpulsesextendoutputONuntilTafterlastfall. Noabsoluteperiods.

OFF-delay mode2:TimerstartshortON;⑥outputONatstartfallingedgeforTthenOFF;resetOFF;internalvalue/resetannotations;T=timer setvalue.

FLASH mode1:TimerstartONinterval;outputalternatesON/OFFatTintervalswhileenabledthenOFFatend. Presenttimingvaluestartschangefortiming;resetinternalvalue/outputatend;T=timer setvalue.

Timer definitions325 and modes326–327 retain source waveform relationships. Prior reviewed328 contains later modes and is not reprocessed; no signal topology inferred.

Manual — Timer modes6 and7 flash timing diagrams — page 328

Manual reference: physical PDF page 328. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Qualitative timing diagrams; retain original waveform shapes/edges. T,t1,t2 are symbolic and no numeric time assigned.

Mode7 has t1/t2 labels but no definitions on this page; do not assume t1=t2 or copy mode6 T definition.

Mode6 labels; reset/output waveform remains original. No numerical timing or wiring inferred.

Mode7 labels only; no timing-value definitions inferred from geometry.

(6) Timer mode6 (FLASH Timer mode2) — PDF page 328

Source row Source label/context Source value
1 Initial state label Timer reset; Internal timer value = 0
2 Timing state label Internal timer value
3 Ending state label Reset internal timer value and output
4 Input trace Timer start
5 Output trace When the set value is reached, the output point (T1 to T8)
6 Reset trace Reset timer and output
7 Repeated interval labels T; T; T; T
8 Definition T=timer set value

(7) Timer mode7 (FLASH Timer mode3) — PDF page 328

Source row Source label/context Source value
1 Initial state label Timer reset; Internal timer value = 0
2 Timing state label Internal timer value
3 Ending state label Reset internal timer value and output
4 Input trace Timer start
5 Output trace When the set value is reached, the timer output turns on (T1 to T8)
6 Interval labels t1; t2

Manual — Analog comparison and registers — page 329

Manual reference: physical PDF page 329. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4- 260

3、Analog comparator function

The description of analog comparison mode: (1) Analog comparison mode 1 (③ ≤ ⑤, ⑥ ON) (2) Analog comparison mode 2 (③ ≥ ④, ⑥ ON) (3) Analog comparison mode (⑤ ≤ ③ ≤ ④, ⑥ ON)

Input comparison value selection (V1~V7) (1) Input comparison value selection = V1:Set frequency (2) Input comparison value selection = V2:Operation frequency (3) Input comparison value selection = V3:AI1 input value (4) Input comparison value selection = V4:AI2 input value (5) Input comparison value selection = V5:Keypad input value (6) Input comparison value selection = V6:Operation current (7) Input comparison value selection = V7:Torque value

Analog comparator:1mode;2leftinputselection;3current;4upperlimit;5lowerlimit;6rightoutput. Source inequalities retain circledpositionnumbers.

Analog comparison and registers

Symbol / Description — PDF page 329

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Symbol Description
2 ① Analog comparator mode (1~3)
3 ② Input comparison value selection (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7)
4 ③ Current analog input value
5 ④ Set the reference comparison value (Upper limit) (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7, constant )
6 ⑤ Set the reference comparison value (lower limit) (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7, constant )
7 ⑥ Comparator output (G1 to G8, there are a total of 8 comparators)

Manual — Operation control and F1example — page 330

Manual reference: physical PDF page 330. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Operation-control example shows10.00,10.00,60.0,30.0 without units. Labels and values retained; no units inferred.

4- 261

  1. Operation control function

Example:

Operation control:1leftupperdirection;2leftlowerspeedcontrol;3topsetfrequency;4speedfrequency;5acceleration;6deceleration;7rightoutput.

F1example ladderI1→(F1),F1→(Q1);RUN/STOPofF1determinedbyON/OFFofI1. FunctionleftM1,M2,n,n;internaltop10.00,10.00,60.0,30.0;rightF1. CalloutF1ON,inverterstartsrunningandF1inputinladderONaswell. No units added to unlabeled example.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Operation-control example shows10.00,10.00,60.0,30.0 without units. Labels and values retained; no units inferred.

Operation control and F1example

Symbol / Description — PDF page 330

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Symbol Description
2 ① Forward /Reversal control can be set by ( I1~f8 ) OFF:Forward(FWD) ON:Reversal(REV)
3 ② Speed terminal control can be set by ( I1~f8 )
4 ② OFF:Operation based on ③ set frequency
5 ② ON:Operation based on frequency of speed ④
6 ③ Set frequency (can be constant or V3、V4,V5 )
7 ④ Speed frequency (can be constant or V3、V4,V5)
8 ⑤ Acceleration time (ACC Time)
9 ⑥ Deceleration time (DEC Time)
10 ⑦ Operation command output (F1 to F8, there are a total of 8 operation control functions)

Manual — Arithmetic commands — page 331

Manual reference: physical PDF page 331. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4- 262

  1. Summation and subtraction functions

RESULT(calculation result)= V1+ V2- V3

  1. Multiplication and division modes

RESULT(calculation result)=V1*V2/V3

Addition/subtraction:1RESULT;2V1;3V2;4V3;5rightuppererrorcoil;6rightlowermode. PrintedRESULT=V1+V2-V3.

Multiplication/division:1RESULT;2V1;3V2;4V3;5errorcoil;6mode. PrintedRESULT=V1*V2/V3;nozero-divisorhandlingadded.

Arithmetic commands

Symbol / Description — PDF page 331

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Symbol Description
2 ① Calculation result : RESULT
3 ② Addend V1(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7, constant )
4 ③ Addend V2(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7, constant )
5 ④ Subtrahend V3(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7, constant )
6 ⑤ Coil output of error signal (M1~MF)
7 ⑥ Addition and subtraction modes number (AS1~AS4)

Symbol / Description — PDF page 331

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Symbol Description
2 ① Calculation result : RESULT
3 ② Multiplier V1(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7, constant )
4 ③ Multiplier V2(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7, constant )
5 ④ Divisor V3(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7, constant )
6 ⑤ Coil output of error signal(M1~MF)
7 ⑥ Multiplication and division modes number (MD1~ MD4)

Manual — Encoder comparison — page 332

Manual reference: physical PDF page 332. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4- 263

7、Encoder Input Comparsion command

(1) Control mode 1 Encoder comparsion function: A1/C ≧ A2 compare to output.

(2) Contro mode 2 Encoder comparsion function: A1/C ≦ A2 compare to output.

※ Encoder input comparsion is enable or disable, which is decided by ON /OFF in

LADDER program.

Encoder comparator:1mode;2direction;3reset;4A1;5A2;6dividerateC;7H1–H4output. Table describesA1ascurrentvalue/dividerateC;prosecomparesA1/C;referencesretained.

Encoder comparison

Symbol / Description — PDF page 332

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Symbol Description
2 ① Encoder control mode (1-2)
3 ② Up/ Down selection can use ( I1~f8 ) to setup OFF: Up ON: Down
4 ③ Reset can use ( I1~f8 ) to setup
5 ④ A1, Encoder current value / divide rate C (divide rate please refer to item ⑥)
6 ⑤ A2, Setting comparsion value
7 ⑥ C, Encoder divide rate
8 ⑦ Encoder comparsion output point, H1~H4

Manual — Fault:overcurrent and ground — page 333

Manual reference: physical PDF page 333. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 5 Troubleshooting and Fault Diagnostics

5.1 General

5.1.1 Fault detection function

Table 1 Fault information and possible solutions

LED source table1,physical fault row1:visible display OC; source label Over Current. Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display OCA; source label Over Current. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display OCC; source label Over Current. Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row4:visible display OCd; source label Over Current. Original first-column region exactly bounded; paired description/cause/solution is source row5. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row5:visible display GF; source label Ground Fault. Original first-column region exactly bounded; paired description/cause/solution is source row6. Flash marks retained only when visible. No inferred fault meaning.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Fault:overcurrent and ground

LED display / Description / Cause / Possible solutions — PDF page 333

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 Over Current The inverter output current exceeds the overcurrent level (200% of the inverter rated current). • Acceleration / Deceleration time is too short. • Contactor at the inverter output side. • A special motor or applicable capacity is greater than the inverter rated value. • Short circuit or ground fault. • Extend acceleration / deceleration time. • Check the motor wiring. • Disconnect motor and try running inverter.
3 Over Current The inverter output current exceeds the overcurrent level in acceleration time • Acceleration time is too short • Capacity of motor is bigger than inverter • Short circuit between winding and shell of motor • Short circuit between wire and ground of motor • IGBT broken module • Set the longer acceleration time • Change to bigger capacity of inverter • Examine motor • Check the wire • Replace IGBT module
4 Over Current The inverter output current exceeds the overcurrent level in acceleration time • Acceleration time is too short • Capacity of motor is bigger than inverter • Short circuit between winding and shell of motor • Short circuit between wire and ground of motor • IGBT broken module • Set the longer acceleration time • Change to bigger capacity of inverter • Examine motor • Check the wire • Replace IGBT module
5 Over Current The inverter output current exceeds the overcurrent level in deceleration time • Deceleration time is too short • Set the longer acceleration time
6 Ground Fault The current to ground exceeds 50% of the inverter rated output current (08-23 = 1, GF function is enabled). • Motor damaged (insulation). • Wire damage or deterioration. • Inverter DCCT sensors defect. • Replace motor. • Check the motor wiring. • Disconnect motor and try running inverter. • Check resistance between cables and ground. • Reduce carrier frequency.

Manual — Fault:voltage,phases,heat — page 334

Manual reference: physical PDF page 334. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED source table1,physical fault row1:visible display OU; source label Over voltage. Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display LU; source label Low Voltage. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display IPL; source label Input phase loss. Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row4:visible display OPL; source label Output phase loss. Original first-column region exactly bounded; paired description/cause/solution is source row5. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row5:visible display OH1; source label OH1 Heatsink overheat. Original first-column region exactly bounded; paired description/cause/solution is source row6. Flash marks retained only when visible. No inferred fault meaning.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Fault:voltage,phases,heat

LED display / Description / Cause / Possible solutions — PDF page 334

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 Over voltage DC bus voltage exceeds the OV detection level: 200V class: 410Vdc 400V class: 820Vdc • Deceleration time set too short, resulting in regenerative energy flowing back from motor to the inverter. • The inverter input voltage is too high. • Use of power factor correction capacitors. • Excessive braking load. • Braking transistor or resistor defective. • Speed search parameters set incorrectly. • Increase deceleration time • Reduce input voltage to comply with the input voltage requirements or install an AC line reactor to lower the input voltage. • Remove the power factor correction capacitor. • Use dynamic braking unit. • Replace braking transistor or resistor. • Adjust speed search parameters.
3 Low Voltage DC bus voltage is lower than the UV detection level or the pre-charge contactor is not active while the inverter is running. 200V class: 190Vdc 400V class: 380Vdc The detection value can be adjusted by 07-13). • The input voltage is too low. • Input phase loss. • Acceleration time set too short. • Input voltage fluctuation. • Pre-charge contactor damaged. • DC bus voltage feedback signal value not incorrect. • Check the input voltage. • Check input wiring. • Increase acceleration time. • Check power source • Replace pre-charge contactor • Replace control board or complete inverter.
4 Input phase loss Phase loss at the input side of the inverter or input voltage imbalance, active when 08-09 = 1 (enabled). • Wiring loose in inverter input terminal. • Momentary power loss. • Input voltage imbalance. • Check input wiring / faster screws. • Check power supply.
5 Output phase loss Phase loss at the output side of the inverter, active when 08-10 = 1 (enabled). • Wiring loose in inverter output terminal. • Motor rated current is less than 10% of the inverter rated current. • Check output wiring / faster screws. • Check motor & inverter rating.
6 OH1 Heatsink overheat The temperature of the heat sink is too high. Note: when OH1 fault occurs three times within five minutes, it is required to wait 10 minutes before resetting the fault. • Ambient temperature too high. • Cooling fan failed • Carrier frequency set too high. • Load too heavy. • Install fan or AC to cool surroundings. • Replace cooling fan. • Reduce carrier frequency. • Reduce load / Measure output current

Manual — Fault:heat,overload,torque,communications — page 335

Manual reference: physical PDF page 335. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED source table1,physical fault row1:visible display OH4; source label OH4 Motor overheating. Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display OL1; source label OL1 Motor overload. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display OL2; source label OL2 Inverter overload. Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row4:visible display Ot; source label OT Over torque detection. Original first-column region exactly bounded; paired description/cause/solution is source row5. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row5:visible display CE; source label Comm. Error. Original first-column region exactly bounded; paired description/cause/solution is source row6. Flash marks retained only when visible. No inferred fault meaning.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Fault:heat,overload,torque,communications

LED display / Description / Cause / Possible solutions — PDF page 335

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 OH4 Motor overheating • Motor overheating • The input of PTC (Positive Temperature Coefficient ) exceeds the overheat protection level. • The surrounding temperature of motor is too high. • The input of PTC (Positive Temperature Coefficient ) exceeds the overheat protection level. (08-42) • Check the surrounding temperature of motor. • Check the MT and GND terminal wiring be correct.
3 OL1 Motor overload Internal motor overload protection tripped, active when protection curve 08-05 = xxx1. • Voltage setting V/F mode too high, resulting in over-excitation of the motor. • Motor rated current (02-01) set incorrectly. • Load too heavy. • Check V/f curve. • Check motor rated current • Check and reduce motor load, check and operation duty cycle.
4 OL2 Inverter overload Inverter thermal overload protection tripped. If an inverter overload occurs 4 times in five minutes, it is required to wait 4 minutes before resetting the fault. • Voltage setting V/F mode too high, resulting in over-excitation of the motor. • Inverter rating too small. • Load too heavy. • Check V/f curve. • Replace inverter with larger rating. • Check and reduce motor load, check and operation duty cycle.
5 OT Over torque detection Inverter output torque is higher than 08-15 (over torque detection level) for the time specified in 08-16. Parameter 08-14 = 0 to activate. • Load too heavy. • Check over torque detection parameters (08-15 / 08-16). • Check and reduce motor load, check and operation duty cycle.
6 Comm. Error No Modbus communication received in for the time specified in 09-06 (communication error detection time). Active when 09-07(= 0 to 2). • Connection lost or wire broken. • Host stopped communicating. • Check connection • Check host computer / software.

Manual — Fault:PID,STO model distinctions,external — page 336

Manual reference: physical PDF page 336. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED source table1,physical fault row1:visible display Fb; source label PID Feedback Loss. Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display PO; source label PO Voltage Off. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display StO1; source label Safety 1 Error. Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row4:visible display PO2; source label PO2 Voltage Off. Original first-column region exactly bounded; paired description/cause/solution is source row5. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row5:visible display StO2; source label Safety 2 Error. Original first-column region exactly bounded; paired description/cause/solution is source row6. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row6:visible display PO3; source label PO3 Voltage Off. Original first-column region exactly bounded; paired description/cause/solution is source row7. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row7:visible display StO3; source label Safety 3 Error. Original first-column region exactly bounded; paired description/cause/solution is source row8. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row8:visible display EF0; source label External fault 0. Original first-column region exactly bounded; paired description/cause/solution is source row9. Flash marks retained only when visible. No inferred fault meaning.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Fault:PID,STO model distinctions,external

LED display / Description / Cause / Possible solutions — PDF page 336

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 PID Feedback Loss PID feedback signal falls below level specified in 10-12 (PID feedback loss detection level) for the time specified in 10-13 (Feedback loss detection time). Active when parameter (10-11 = 2). • Feedback signal wire broken • Feedback sensor broken. • Check feedback wiring • Replace feedback sensor.
3 PO Voltage Off STO terminal 1 error (Without STO/Filter model only) Terminal board Input SF1 and SG are not connected Check SF1 and SG connection
4 Safety 1 Error STO terminal 1 error (With STO/Filter model only) Terminal board Input SF1 and SG are not connected Check SF1 and SG connection
5 PO2 Voltage Off STO terminal 2 error (Without STO/Filter model only) Terminal board Input SF2 and SG are not connected Check SF2 and SG connection
6 Safety 2 Error STO terminal 2 error (With STO/Filter model only) Terminal board Input SF2 and SG are not connected Check SF2 and SG connection
7 PO3 Voltage Off STO terminal 3 error (Without STO/Filter model only) Transformer voltage output of inverter is not stable. • Replace the power board • Contact with TECO
8 Safety 3 Error STO terminal 3 error (With STO/Filter model only) Transformer voltage output of inverter is not stable. • Replace the power board • Contact with TECO
9 External fault 0 External fault (Modbus) Modbus communication 0x2501 bit 2= "1" • Reset Modbus communication 0x2501 bit 2= "1"

Manual — Fault:terminals,motor control,operator — page 337

Manual reference: physical PDF page 337. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED source table1,physical fault row1:visible display EF1; source label External fault 1. Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display EF2; source label External fault 2. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display EF3; source label External fault 3. Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row4:visible display EF4; source label External fault 4. Original first-column region exactly bounded; paired description/cause/solution is source row5. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row5:visible display EF5; source label External fault 5. Original first-column region exactly bounded; paired description/cause/solution is source row6. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row6:visible display EF6; source label External fault 6. Original first-column region exactly bounded; paired description/cause/solution is source row7. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row7:visible display CF07; source label Motor control fault. Original first-column region exactly bounded; paired description/cause/solution is source row8. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row8:visible display CF08; source label Motor control fault. Original first-column region exactly bounded; paired description/cause/solution is source row9. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row9:visible display CF00; source label Operator Communication Error. Original first-column region exactly bounded; paired description/cause/solution is source row10. Flash marks retained only when visible. No inferred fault meaning.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Fault:terminals,motor control,operator

LED display / Description / Cause / Possible solutions — PDF page 337

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 External fault 1 External Fault (Terminal S1) External Fault Input Terminal • Check the fault reason • Reset external fault of digital input
3 External fault 2 External Fault (Terminal S2) External Fault Input Terminal • Check the fault reason • Reset external fault of digital input
4 External fault 3 External Fault (Terminal S3) External Fault Input Terminal • Check the fault reason • Reset external fault of digital input
5 External fault 4 External Fault (Terminal S4) External Fault Input Terminal • Check the fault reason • Reset external fault of digital input
6 External fault 5 External Fault (Terminal S5) External Fault Input Terminal • Check the fault reason • Reset external fault of digital input
7 External fault 6 External Fault (Terminal S6) External Fault Input Terminal • Check the fault reason • Reset external fault of digital input
8 Motor control fault Motor control fault SLV mode is unable to run motor • Performrotational or stationary auto-tune • Increase minimum output frequency (01-08)
9 Motor control fault Motor control fault Start or Run fault in PMSLV mode. • Increase the value of 22-10 and 22-23 properly. • Re auto-tune (22-21) • Check if the load is too heavy to raise torque output limit.
10 Operator Communication Error Errors of data transmission occur in LCD keypad. LCD keypad and inverter cannot transmit data after power on 5 seconds. • Disconnect the operator and then reconnect. • Replace the control board

Manual — Fault:operator,pressure,short circuit,protection — page 338

Manual reference: physical PDF page 338. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED source table1,physical fault row1:visible display CF01; source label Operator Communication Error 2. Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display OPr; source label Operator Disconnection. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display FbLSS; source label FBLSS. Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row4:visible display SC; source label Short Circuit. Original first-column region exactly bounded; paired description/cause/solution is source row5. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row5:visible display run; source label run Motor1/Motor2 Switch. Original first-column region exactly bounded; paired description/cause/solution is source row6. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row6:visible display PF; source label PF Protection Error. Original first-column region exactly bounded; paired description/cause/solution is source row7. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row7:visible display LPbFt; source label LPBFT. Original first-column region exactly bounded; paired description/cause/solution is source row8. Flash marks retained only when visible. No inferred fault meaning.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Fault:operator,pressure,short circuit,protection

LED display / Description / Cause / Possible solutions — PDF page 338

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 Operator Communication Error 2 Errors of data transmission occur in LCD keypad. LCD keypad and inverter can transmit data but transmission error occurs for more than 2 seconds • Disconnect the operator and then reconnect. • Replace the control board
3 Operator Disconnection When 00-02=0, if operator is disconnected during inverter running, the action of operator disconnected will be based on the setting of parameter 16-09. When 00-02=0, the warning of keypad operator disconnected. Check the keypad operator connection
4 FBLSS PID Feedback Signal Loss • Since proportion of loss pressure (23-19) is enabled and over high, the inverter trips to fault. Thus, feedback sensor cannot operate properly or is not installed correctly. • Check if the proportion of loss pressure (23-19) is set correctly. • Make sure the feedback sensor is installed correctly and PID feedback signal operates normally.
5 Short Circuit Inverter output short circuit or ground fault. • Short circuit or ground fault (08-23 = 1). • Motor damaged (insulation). • Wire damage or deterioration. • Check the motor wiring. • Disconnect motor and try running inverter.
6 run Motor1/Motor2 Switch Motor1/Motor2 switch during operation Input motor 2 switch command during operation. Improve the control sequence, motor can be switched in stop.
7 PF Protection Error 1. OH1/OL2 error occurs three times in 5 minutes. 2. Digital input or communication run command not removed Digital input or communication runcommand not removed. Remove the digital input or communication run command.
8 LPBFT Low pressure fault • The feedback signal is not connected. • Since feedback value of pump pressure is lower than limit of minimum flow. • Check feedback signal is correct and with connection. • Check if feedback value of pressure is lower than limit of minimum pressure (23-15).

Manual — Fault continuation and warning voltage/heat — page 339

Manual reference: physical PDF page 339. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 2 Warning/Self-diagnosis and Corrective actions

LED source table1,physical fault row1:visible display OPbFt; source label OPBFT. Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display tOL; source label TOL. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display Fb(flash); source label FB(Flash). Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table2,physical fault row1:visible display OU(flash); source label OV (flash) Over voltage. Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table2,physical fault row2:visible display LU(flash); source label UV (flash) under voltage. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table2,physical fault row3:visible display OH1(flash); source label OH1 (flash) Heatsink overheat. Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Fault continuation and warning voltage/heat

LED display / Description / Cause / Possible solutions — PDF page 339

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 OPBFT High pressure fault • Since feedback value of pump pressure is lower than limit of maximum flow. • Check feedback signal is correct. • Check if feedback value of pressure is lower than limit of maximum pressure (23-12).
3 TOL External Overload (For fire mode only) • External Overload signal receied by digital input terminal • Check the reason for external overload • Reset digital input terminal of external overload
4 FB(Flash) PID feedback breaking • Feedback signal wire broken • Feedback sensor broken. • Check feedback wiring • Replace feedback sensor.

LED display / Description / Cause / Possible solutions — PDF page 339

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 OV (flash) Over voltage DC bus voltage exceeds the OV detection level: 200V class:410Vdc 400V class:820Vdc (for 400V class, if input voltage 01-14 is set lower than 400V, the OV detection value will is decreased to 700Vdc) • Deceleration time set too short, resulting in regenerative energy flowing back from motor to the inverter. • The inverter input voltage is too high. • Speed search parameters set incorrectly. • Increase deceleration time • Reduce input voltage to comply with the input voltage requirements or install an AC line reactor to lower the input voltage. • Adjust speed search parameters.
3 UV (flash) under voltage DC bus voltage is lower than the UV detection level or the pre-charge contactor is not active while the inverter is running. 190Vdc:200V class; 380Vdc:400V class (the detection value can be adjusted by 07-13) • The input voltage is too low. • Input phase loss. • DC bus voltage feedback signal value not incorrect. • Check the input voltage. • Check input wiring. • Replace control board or complete inverter.
4 OH1 (flash) Heatsink overheat The temperature of the heat sink is too high. Note: when OH1 fault occurs three times within five minutes, it is required to wait 10 minutes before resetting the fault. • Ambient temperature too high. • Cooling fan failed • Carrier frequency set too high. • Load too heavy. • Install fan or AC to cool surroundings. • Replace cooling fan. • Reduce carrier frequency. • Reduce load / Measure output current

Manual — Warning:heat,overload,retry,emergency — page 340

Manual reference: physical PDF page 340. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED source table1,physical fault row1:visible display OH3(flash); source label OH3 (flash) Motor over Heating warning. Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display Ot(flash); source label OT (flash) Over torque detection. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display OL1; source label OL1 Motor Overload. Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row4:visible display OL2; source label OL2 Inverter overload. Original first-column region exactly bounded; paired description/cause/solution is source row5. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row5:visible display CE(flash); source label Comm. Error. Original first-column region exactly bounded; paired description/cause/solution is source row6. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row6:visible display rEtrY(flash); source label Retry (flash). Original first-column region exactly bounded; paired description/cause/solution is source row7. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row7:visible display ES(flash); source label ES (flash) External Emergency Stop. Original first-column region exactly bounded; paired description/cause/solution is source row8. Flash marks retained only when visible. No inferred fault meaning.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Warning:heat,overload,retry,emergency

LED display / Description / Cause / Possible solutions — PDF page 340

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 OH3 (flash) Motor over Heating warning Motor over heating • PTC input level is higher than 08-43 • Multi-function input function set incorrectly. • Check wiring
3 OT (flash) Over torque detection Inverter output torque is higher than 08-15 (over torque detection level) for the time specified in 08-16. Parameter 08-14 = 0 to activate. • Load too heavy. • Check over torque detection parameters (08-15 / 08-16). • Check and reduce motor load, check and operation duty cycle.
4 OL1 Motor Overload Internal motor overload protection tripped, active when protection curve 08-05=xxx1 • Voltage setting V/F modetoo high, resulting in over-excitation of the motor. • Motor overload current (02-01) set incorrectly. • Motor load too heavy • Check V/F curve. • Check motor load current • Check and reduce motor load, check and operation duty cycle.
5 OL2 Inverter overload Inverter thermal overload protection tripped. If an inverter overload occurs 4 times in five minutes, it is required to wait 4 minutes before resetting the fault. • Voltage setting V/F mode too high, resulting in over-excitation of the motor. • Inverter rating too small. • Load too heavy. • Check V/f curve. • Replace inverter with larger rating. • Check and reduce motor load, check and operation duty cycle.
6 Comm. Error No Modbus communication received in for the time specified in 09-06 (communication error detection time). Active when 09-07(= 0 to 2). • Connection lost or wire broken. • Host stopped communicating. • Check connection • Check host computer / software.
7 Retry (flash) Automatic reset activated, warning is displayed until restart delay time set (07-01) expires. • Parameter 07-01 set to a value greater than 0. • Parameter 07-02 set to a value greater than 0. • Warning disappears after automatic reset.
8 ES (flash) External Emergency Stop External emergency stop Enabled. • 03-00~03-05 set to 14, and the digital input enabled. • Turn off run command, and remove external emergency stop command.

Manual — Warning:baseblock and forward/reverse — page 341

Manual reference: physical PDF page 341. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED source table1,physical fault row1:visible display bb1(flash); source label bb1 (flash) External baseblock. Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display bb2(flash); source label bb2 (flash) External baseblock. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display bb3(flash); source label bb3 (flash) External baseblock. Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row4:visible display bb4(flash); source label bb4 (flash) External baseblock. Original first-column region exactly bounded; paired description/cause/solution is source row5. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row5:visible display bb5(flash); source label bb5 (flash) External baseblock. Original first-column region exactly bounded; paired description/cause/solution is source row6. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row6:visible display bb6(flash); source label bb6 (flash) External baseblock. Original first-column region exactly bounded; paired description/cause/solution is source row7. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row7:visible display EF9(flash); source label EF9 ( flash ) error of forward/reve rsal rotation. Original first-column region exactly bounded; paired description/cause/solution is source row8. Flash marks retained only when visible. No inferred fault meaning.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Warning:baseblock and forward/reverse

LED display / Description / Cause / Possible solutions — PDF page 341

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 bb1 (flash) External baseblock External base block (Terminal S1) Multifunction digital input external baseblock active. • Multi-function input function set incorrectly. • Check wiring
3 bb2 (flash) External baseblock External base block (Terminal S2) Multifunction digital input external baseblock active. • Multi-function input function set incorrectly. • Check wiring
4 bb3 (flash) External baseblock External base block (Terminal S3) Multifunction digital input external baseblock active. • Multi-function input function set incorrectly. • Check wiring
5 bb4 (flash) External baseblock External base block (Terminal S4) Multifunction digital input external baseblock active. • Multi-function input function set incorrectly. • Check wiring
6 bb5 (flash) External baseblock External base block (Terminal S5) Multifunction digital input external baseblock active. • Multi-function input function set incorrectly. • Check wiring
7 bb6 (flash) External baseblock External base block (Terminal S6) Multifunction digital input external baseblock active. • Multi-function input function set incorrectly. • Check wiring
8 EF9 ( flash ) error of forward/reve rsal rotation Forward run and reverse run are active within 0.5 sec of each other. Stop method set by parameter 07-09. Forward run and reverse run active (see 2-wire control). Check run command wiring

Manual — Warning:range,terminal,V/F,PID,model,current — page 342

Manual reference: physical PDF page 342. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: SE01 examples literally contain or20>02-21 and2.00-12>00-13. In contrast, PDF137 says SE01 when00-12 is lower than00-13. Because the342 expression is already malformed, retain this as a literal direction conflict requiring clarification, not a repaired comparison. SE03 also has no operator between01-06(Fmid1) and01-08(Fmin).

LED source table1,physical fault row1:visible display SE01(flash); source label Rang setting error. Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display SE02(flash); source label Digital input terminal error. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display SE03(flash); source label V/f curve error. Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row4:visible display SE05(flash); source label PID selection error. Original first-column region exactly bounded; paired description/cause/solution is source row5. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row5:visible display HPErr(flash); source label Model selection error. Original first-column region exactly bounded; paired description/cause/solution is source row6. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row6:visible display CLb(flash); source label Over current protection level B. Original first-column region exactly bounded; paired description/cause/solution is source row7. Flash marks retained only when visible. No inferred fault meaning.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: SE01 printed reference or20>02-21 and2.00-12>00-13 incomplete/malformed; SE03 comparison omits operator between01-06(Fmid1)and01-08(Fmin). Exact rules remain unresolved.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Warning:range,terminal,V/F,PID,model,current

LED display / Description / Cause / Possible solutions — PDF page 342

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 Rang setting error Parameter setting falls outside the allowed range. Some parameter ranges are determined by other inverter parameters which could cause an out of range warning when the dependency parameter is adjusted. Example: (1) 02-00>02-01,or 20>02-21 (2) 2.00-12>00-13, (3) 00-07 =1, 00-05=00-06 (4) 02-03>02-06 or 02-22>02-25 (5) 20-16<20-15 Check parameter setting.
3 Digital input terminal error Multi-function input setting error. Multi-function digital input terminals (03-00 to 03-05) are set to the same function (not including ext. fault and not used.) or: (1) UP/DOWN commands are not set at the same time( they must be used together). (2) UP/DOWN commands (08 and 09) and ACC/DEC commands (11) are set at the same time. (3) Speed search 1(19,maximum frequency) and Speed search 2 (34,from the set frequency)are set at the same time. (4) 03-00~03-05 set two-wire and three-wire in the same time. Check multi-function input setting.
4 V/f curve error V/f curve setting error. • V/F curve setting error. (1) 01-02(Fmax) > 01-12 (Fbase) > 01-06 (Fmid1) 01-08(Fmin) (2) 01-16(Fmax2) > 01-24(Fbase2) > 01-20(Fmid1) > 01-22(Fmin2) Check V/F parameters
5 PID selection error PID selection error. • 10-00 and10-01 set to 1(AI1) or set to 2(AI2) • When 23-05=0 and 10-33 >= 1000 or 10-34≠1. • Check 10-00 and 10-01 • Check 10-33,10-34, 23-05.
6 Model selection error Inverter capacity setting error: Inverter capacity setting 13-00 does not match the rated voltage. Inverter capacity setting does not match voltage class (13-00). Check inverter capacity setting 13-00.
7 Over current protection level B Inverter current reaches the current protection level B. • Inverter current too high. • Load too heavy. Check load and duty cycle operation.

Manual — Warning:terminals,PI,PID continuation — page 343

Manual reference: physical PDF page 343. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED source table1,physical fault row1:visible display EF1(flash); source label EF1 ( flash ) External fault (S1). Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display EF2(flash); source label EF2 ( flash ) External fault (S2). Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display EF3(flash); source label EF3 ( flash ) External fault (S3). Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row4:visible display EF4(flash); source label EF4 ( flash ) External fault (S4). Original first-column region exactly bounded; paired description/cause/solution is source row5. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row5:visible display EF5(flash); source label EF5 ( flash ) External fault (S5). Original first-column region exactly bounded; paired description/cause/solution is source row6. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row6:visible display EF6(flash); source label EF6 ( flash ) External fault (S6). Original first-column region exactly bounded; paired description/cause/solution is source row7. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row7:visible display SE09(flash); source label PI setting error. Original first-column region exactly bounded; paired description/cause/solution is source row8. Flash marks retained only when visible. No inferred fault meaning.

PID warning row spans343→344; complete condition10-11=1 comes from344. Blank continuation cause/solution remain blank; cause/solution on343 retained. Distinct from fault33610-11=2.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Warning:terminals,PI,PID continuation

LED display / Description / Cause / Possible solutions — PDF page 343

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 EF1 ( flash ) External fault (S1) External fault (Terminal S1) Active when 03-00= 25, and Inverter external fault selection 08-24=2. Multifunction digital input external fault active and parameter 08-24=2 for operation to continue. • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring
3 EF2 ( flash ) External fault (S2) External fault (Terminal S2) Active when 03-01= 25, and Inverter external fault selection 08-24=2. Multifunction digital input external fault active and parameter 08-24=2 for operation to continue. • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring
4 EF3 ( flash ) External fault (S3) External fault (Terminal S3) Active when 03-02= 25, and Inverter external fault selection 08-24=2. Multifunction digital input external fault active and parameter 08-24=2 for operation to continue. • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring
5 EF4 ( flash ) External fault (S4) External fault (Terminal S4) Active when 03-03= 25, and Inverter external fault selection 08-24=2. Multifunction digital input external fault active and parameter 08-24=2 for operation to continue. • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring
6 EF5 ( flash ) External fault (S5) External fault (Terminal S5) Active when 03-04= 25, and Inverter external fault selection 08-24=2. Multifunction digital input external fault active and parameter 08-24=2 for operation to continue. • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring
7 EF6 ( flash ) External fault (S6) External fault (Terminal S6) Active when 03-05= 25, and Inverter external fault selection 08-24=2. Multifunction digital input external fault active and parameter 08-24=2 for operation to continue. • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring
8 PI setting error Inverter PI setting error Inverter pulse input selection (03-30) selection conflicts with PID source (10-00 and 10-01). Check pulse input selection (03-30) and PID source (10-00 and 10-01).
9 FB (flash) PID feedback breaking PID feedback signal falls below level specified in 10-12 (PID feedback loss • Feedback signal wire broken • Feedback sensor broken. • Check feedback wiring • Replace feedback sensor.

Manual — Warning continuation:PID,fire,settings,control — page 344

Manual reference: physical PDF page 344. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED source table1,physical fault row1:visible display Fb(flash); source label . Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display FIrE(flash); source label Fire mode enabled. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display PArEr(flash); source label Parameter setting Error. Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row4:visible display StP1(flash); source label Direct start warning. Original first-column region exactly bounded; paired description/cause/solution is source row5. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row5:visible display StP2(flash); source label External Terminal Stop Error. Original first-column region exactly bounded; paired description/cause/solution is source row6. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row6:visible display EPErr(flash); source label EEPROM Save Error. Original first-column region exactly bounded; paired description/cause/solution is source row7. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row7:visible display bdErr(flash); source label Control Board Error. Original first-column region exactly bounded; paired description/cause/solution is source row8. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row8:visible display rUnEr(flash); source label Wrong Running Direction Error. Original first-column region exactly bounded; paired description/cause/solution is source row9. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row9:visible display LOC(flash); source label Parameter Lock. Original first-column region exactly bounded; paired description/cause/solution is source row10. Flash marks retained only when visible. No inferred fault meaning.

PID warning row spans343→344; complete condition10-11=1 comes from344. Blank continuation cause/solution remain blank; cause/solution on343 retained. Distinct from fault33610-11=2.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Warning continuation:PID,fire,settings,control

LED display / Description / Cause / Possible solutions — PDF page 344

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 ⟦blank source cell⟧ detection level) for the time specified in 10-13 (Feedback loss detection time). Active when parameter (10-11 = 1). ⟦blank source cell⟧ ⟦blank source cell⟧
3 Fire mode enabled Fire mode enabled Fire mode enabled. Check the environment and confirm the fire status. If no fire, turn off the power and power on again.
4 Parameter setting Error Parameter setting error The parameter setting is wrong Please refer to the manual for correct setting
5 Direct start warning The inverter can’t start directly, due to 07-04=1 Run command from the terminal is enabled and 07-04=1 Remove the run command from the terminal first, and enabled later.
6 External Terminal Stop Error External Terminal is main run command source selection (00-02=1) and run command executes but executes stop command from keypad. Run command executes from external terminal but executes stop command from keypad. Remove the run command from external terminal
7 EEPROM Save Error The data save in EEPROM is wrong. • EEPROM circuit failure • Parameter check error after power on • Restore factory setting, then cut off the power and power on again. • If warning again, replace control board.
8 Control Board Error Firmware can’t meet Control board. Firmware can’t meet Control board. Replace the control board.
9 Wrong Running Direction Error Running direction is different from 11-00 Check the command among 11-00, jog and DI control to see if any difference. Revise the command among 11-00, jog and DI control to see if any difference
10 Parameter Lock Parameter lock key code (password) already locked Parameter lock key code already enable (13-07) Lifting the parameter lock key code, to enter the correct parameter for 13-07

Manual — Warning:password,run,emergency,zero-speed — page 345

Manual reference: physical PDF page 345. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED source table1,physical fault row1:visible display Err2(flash); source label Set password failed. Original first-column region exactly bounded; paired description/cause/solution is source row2. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row2:visible display EF(flash); source label Run Command Error. Original first-column region exactly bounded; paired description/cause/solution is source row3. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row3:visible display ES(flash); source label ES (flash) External Emergency Stop. Original first-column region exactly bounded; paired description/cause/solution is source row4. Flash marks retained only when visible. No inferred fault meaning.

LED source table1,physical fault row4:visible display StP0(flash); source label Zero Speed Stop Error. Original first-column region exactly bounded; paired description/cause/solution is source row5. Flash marks retained only when visible. No inferred fault meaning.

Source troubleshooting instructions retained as supplier text, not independent safety or engineering approval. LED glyph regions separately bounded and linked to physical description row; grouped cells preserve original geometry.

Warning:password,run,emergency,zero-speed

LED display / Description / Cause / Possible solutions — PDF page 345

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LED display Description Cause Possible solutions
2 Set password failed Parameter lock key code cannot enable To enable the parameter lock key code (password) function, but the password is not correct Enter the correct parameter for 13-07 to enable the parameter lock key
3 Run Command Error One direction opertion only, inverter can not receive reverse operation command at the same time. Check the terminal of reverse operation command Remove the reverse operation command from external terminal
4 ES (flash) External Emergency Stop External emergency stop Enabled. 03-00~03-05 set to 14, and the digital input enabled. Turn off run command, and remove external emergency stop command.
5 Zero Speed Stop Error Frequency command is smaller than 01-08 without DC brake. Frequency command is smaller than motor minimum output frequency. Adjust frequency command

Manual — LCD warning messages only — page 346

Manual reference: physical PDF page 346. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Warning Message (LCD display only)

LCD warning messages only

LCD display / Description / Cause / Possible solutions — PDF page 346

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 LCD display Description Cause Possible solutions
2 Operator Copy Error Parameters can not upload to operator Inverter data transmission error, can not upload the data to operator Check operator and control connection
3 RDE Parameters can not upload to operator Inverter data transmission error, can not upload the data to operator Check operator and control connection
4 Operator Write Error Operator can not write data to inverter • The control mode in the operator does not match the inverter. • The model name in the operator does not match the inverter. • The firmware version in the operator does not match the inverter. Check the control mode, model name and firmware version of inverter.
5 WRE Operator can not write data to inverter • The control mode in the operator does not match the inverter. • The model name in the operator does not match the inverter. • The firmware version in the operator does not match the inverter. Check the control mode, model name and firmware version of inverter.
6 Operator Compare Error Data compare incorrect between operator and inverter. When operator upload or download the data, user can compare the data of operator and inverter, when data of both side does not match, operator will show “VRYE” error. Check operator and control connection
7 VRYE Data compare incorrect between operator and inverter. When operator upload or download the data, user can compare the data of operator and inverter, when data of both side does not match, operator will show “VRYE” error. Check operator and control connection
8 Does Not Allow to Read and Save Data Operator can not read or save inverter parameters When 16-08=0, does not allow to read inverter parameters or save them to the operator. Check parameter setting of parameter (16-08)
9 RDP Operator can not read or save inverter parameters When 16-08=0, does not allow to read inverter parameters or save them to the operator. Check parameter setting of parameter (16-08)

Manual — General troubleshooting — page 347

Manual reference: physical PDF page 347. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.2 General Troubleshooting

General troubleshooting

Status / Checking point / Remedy — PDF page 347

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Status Checking point Remedy
2 Motor runs in wrong direction Is the wiring for the output terminals correct? Wiring must match U, V, and W terminals of the motor.
3 Motor runs in wrong direction Is the wiring for forward and reverse signals correct? Check for correct wiring.
4 The motor speed can not be regulated. Is the wiring for the analog frequency inputs correct? Check for correct wiring.
5 The motor speed can not be regulated. Is the setting of operation mode correct? Check the Frequency Source set in parameters 00-05/00-06.
6 The motor speed can not be regulated. Is the load too excessive? Reduce the load.
7 Motor running speed too high or too low Check the motor specifications (poles, voltage… ) correct? Confirm the motor specifications.
8 Motor running speed too high or too low Is the gear ratio correct? Confirm the gear ratio.
9 Motor running speed too high or too low Is the setting of the highest output frequency correct? Confirm the highest output frequency
10 Motor speed varies unusually Is the load too excessive? Reduce the load.
11 Motor speed varies unusually Does the load vary excessively? (1) Minimize the variation of the load. (2) Consider increasing the capacities of the inverter and the motor.
12 Motor speed varies unusually Is the input power erratic or is there a phase loss ? (1) Consider adding an AC reactor at the power input side if using single-phase power. (2) Check wiring if using three-phase power.
13 Motor can not run Is the power connected to the correct L1(L), L2, and L3(N) terminals? is the charging indicator lit ? (1) Is the power applied ? (2) Turn the power OFF and then ON again. (3) Make sure the power voltage is correct. Make sure screws are secured firmly.
14 Motor can not run Is there voltage across the output terminals T1, T2, and T3? Turn the power OFF and then ON again.
15 Motor can not run Is overload causing the motor to stall? Reduce the load so the motor will run.
16 Motor can not run Are there any abnormalities in the inverter? See error descriptions to check wiring and correct if necessary.
17 Motor can not run Is there a forward or reverse run command ? See error descriptions to check wiring and correct if necessary.
18 Motor can not run Has the analog frequency signal been input? (1) Is analog frequency input signal wiring correct? (2) Is voltage of frequency input correct?
19 Motor can not run Is the operation mode setting correct? Operate through the digital keypad

Manual — Quick inverter troubleshooting part1 — page 348

Manual reference: physical PDF page 348. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.3 Troubleshooting of the Inverter

5.3.1 Quick troubleshooting of inverter

INV Fault

Visually check controller and Drive boards

*to next page

Check burnt and damaged parts

Consult with the supplier

Replace fuse

Check according to displayed fault messages

Replace the pre-charge resistor

Check terminals and wiring

Perform detailed check and consult with the supplier

Is fault known?

Symptoms other than burn out, damage, or fuse meltdown in the inverter?

Any Symptoms of burn out and damage?

Is the main circuit DM intact? Fault signal?

Is the fuse intact?

Is the main circuit I.G.B.T intact?

Any visual abnormalities?

Are displays and indicators of the operating unit working normally?

Is +5V control voltage correct?

Is the DC input voltage controlling the power correct Any fault display?

What the message ?

Is LED lit?

Replace control board and digital operating unit

Is the error eliminated after replacing control board?

YES

NO

NO YES

NO NO

Apply the power

Source flow relationships:INV Fault→Is fault known? NO→Any symptoms of burn out and damage? YES→Check burnt and damaged parts;NO→main circuitDMintact? YES→fuseintact? YES→main circuitIGBTintact? YES→visually check controller/Drive boards→Any visual abnormalities? YES→supplier;NO→apply power. DMNO→supplier;fuseNO→replacefuse;IGBTNO→supplier. FaultknownYES→Symptoms other than burn out,damage,fusemeltdown? NO→burnoutquestion;YES→Fault signal? YES→check displayed fault messages;NO→DMquestion. Applypower→displays/indicatorsnormal? YES→Anyfaultdisplay? YES→Whatmessage?→displayedfaultmessages;NO→nextpage349. DisplaysnormalNO→LEDlit? NO→replacepre-chargeresistor;YES→DCinputvoltagecontrollingpowercorrect? NO→checkterminals/wiring;YES→+5Vcontrolvoltagecorrect? NO→supplier;YES→replacecontrolboardanddigitaloperatingunit→erroreliminated? YES→applypower;NO→detailedcheck/supplier. Source branch text only; not independently validated repair guidance.

Flow continues348→349; retain all printed branch labels and supplier escalation endpoints. No engineering validation.

Manual — Quick inverter troubleshooting continuation — page 349

Manual reference: physical PDF page 349. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Check Inverter parameters

Replace the control board

Perform parameter initializations

Specify operation control mode

Does the FWD or REV LED light flash?

Is the frequency value displayed on the display?

Are there voltage outputs at terminals U, V and W

Is there any fault display?

Are output currents of each phase even?

The inverter is OK

Perform detailed check and consult with the supplier.

Does the control Board function after replacement

YES

NO

From previous page

Set up frequency command

Connect the motor to run

Continuation from348:Checkinverterparameters→parameterinitializations→specifyoperationcontrolmode→FWDorREVLEDflash? NO→replacecontrolboard;YES→frequencycommand→frequencyvaluedisplayed? NO→replacecontrolboard;YES→voltageoutputsU,V,W? NO→replacecontrolboard→boardfunctionsafterreplacement? YES→connectmotortorun;NO→detailedcheck/supplier. VoltageoutputsYES→connectmotortorun→arrowlabelNO→Anyfaultdisplay? YES→detailedcheck/supplier;NO→outputcurrenteachphaseeven? YES→inverterOK;NO→detailedcheck/supplier. NOafterconnectmotoris printed at action-box exit, not assigned to a hidden condition.

Flow continues348→349; retain all printed branch labels and supplier escalation endpoints. No engineering validation.

Manual — OC/OL troubleshooting — page 350

Manual reference: physical PDF page 350. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Downward branches from Any abnormal indications? to Input operation command and from output-voltage question to Connect the motor to run have no YES/NO label. Both arrows are visible. Preserve unlabelled edges rather than inventing decision values.

5.3.2 Troubleshooting for OC、OL error display

The inverter displays OC, OL errors

The inverter output is OK

Is the output current of each phase even?

Any fault values displayed?

Is there Voltage at U,V and W output terminals?

Is the output frequency of the operating unit displayed?

Is FWD LED illuminated?

Is the main circuit I.G.B.T working

Any visual abnormalities?

Is the current detector OK? Any abnormal indications?

Is the inverter operation OK after board replacement ?

Replace the current controller

Replace control board

Replace faulty circuit board

Replace I.G.B.T

The inverter is faulted (Perform detailed check)

YES

NO

NO NO

Apply power

Input operation command

Input frequency command

Connect the motor to run

OC/OL source flow:IGBTworking? NO→replaceIGBT;YES→visualabnormalities? YES→replacefaultycircuitboard;NO→applypower→abnormalindications? YES→currentdetectorOK? YES→replacecurrentcontroller;NO→replacecontrolboard. Unlabelled downwardexitfromabnormalindications→inputoperationcommand→FWDLEDilluminated? NO→replacecontrolboard;YES→frequencycommand→outputfrequencydisplayed? NO→replacecontrolboard;YES→voltageU,V,W? NO→replacecontrolboard→operationOKafterreplacement? YES→connectmotortorun;NO→inverterfaulted/detailedcheck. Unlabelleddownwardexitfromvoltagequestion→connectmotortorun→faultvalues? YES→faulted/detailedcheck;NO→currenteachphaseeven? YES→outputOK;NO→faulted/detailedcheck. No missing branch labels inferred.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Two decision exits have no YES/NO labels: abnormal indications downward and output voltage downward. No branch meaning inferred.

Adjacent source context — repeated to preserve continuation:

Manual — OV/LV troubleshooting — page 351

Manual reference: physical PDF page 351. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: The downward edge after Any abnormal indications? is unlabelled. A literal NO is printed after the action Connect the motor to run, without a decision question at that action. Keep the diagram and do not convert that NO into a new inferred question.

5.3.3 Troubleshooting for OV, LV error display

The inverter displays OV, LV

The inverter’s output is OK

Is the current on all phases even?

Any abnormal value?

Is there Voltage at T1,T2,T3 output terminals?

Is the output frequency of the operating unit displayed?

Is FWD LED still illuminated after flash

Is the main circuit fuse intact?

Any visual abnormalities?

Any abnormal indications?

Is the inverter operation OK after board replacement?

Replace the control board

Perform detailed check and consult with the supplier

YES

NO

Connect the motor to run

Input frequency commands

Input operation command

Apply power

Consult with the supplier

OV/LV source flow:fuseintact? NO→supplier;YES→visualabnormalities? YES→supplier;NO→applypower→abnormalindications? YES→supplier;unlabelleddownwardexit→inputoperationcommand→FWDLEDstillilluminatedafterflash? NO→supplier;YES→frequencycommands→outputfrequencydisplayed? NO→replacecontrolboard;YES→voltageT1,T2,T3? NO→replacecontrolboard→operationOKafterreplacement? YES→connectmotortorun;NO→detailedcheck/supplier. VoltageYES→connectmotortorun→printedNOexit→abnormalvalue? YES→detailedcheck/supplier;NO→currentallphaseseven? YES→outputOK;NO→detailedcheck/supplier. Source missing labels not filled.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Abnormal-indications downward exit unlabelled; NO at connect-motor action exit has no explicit question. No hidden decision inferred.

Adjacent source context — repeated to preserve continuation:

Manual — Motor not running flowchart — page 352

Manual reference: physical PDF page 352. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: The switch question visibly says Is the operation switch in UN??. Its NO action says the switch is set to RUN position. The action is context, not proof of missing letters in the question; keep the malformed question and do not silently replace it with RUN.

5.3.4 Motor not running

The motor can not run

Is MCCB On?

Can MCCB be turned On?

Are voltages between power terminals correct?

Is LED lit?

Is the operation switch in UN? ?

Are there outputs between the U,V, and W terminals of the motor?

Are outputs between U,V,W the same?

  1. Motor 2. Motor faults 3. Incorrect wiring

INVfault

The operation switch is set to “RUN” position

1.The power is abnormal 2.Incorrect wiring

Short circuited wiring

NO

YES

Motor cannotrun source flow:MCCBOn? YES→powerterminalvoltagescorrect;NO→canMCCBturnOn? NO→shortcircuitedwiring;YES→powerterminalvoltagescorrect? NO→powerabnormal/incorrectwiring;YES→LEDlit? NO→INVfault;YES→operation-switch question visiblyprints UN??(missingleadingtext);NO→switchsettoRUNposition;YES→outputsbetweenU,V,W? NO→INVfault;YES→outputsU,V,Wsame? NO→INVfault;YES→terminalbox1.Motor2.Motorfaults3.Incorrectwiring. No missing text restored.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Operation-switch question visibly lacks leading text before UN??. Exact condition not reconstructed.

Manual — Motor overheating flowchart — page 353

Manual reference: physical PDF page 353. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: The final Incorrect connection between inverter and the motor decision has only a YES arrow to Correct the connection. No NO exit is drawn. The absent exit is not extraction loss; retain the source boundary rather than adding an endpoint.

5.3.5 Motor overheating

Y E S

N O

Is load or current exceeding the specified value?

C onsider reducing the load and increasing the capacities of the inverter and m otor

M otor O verheating

Is m otor running at low speed for a long tim e?

Is m otor voltage betw een U- V ,V -W ,W -U correct?

Is there any deterrence preventing cooling of the m otor

Incorrect connection betw een inverter and the m otor

S elect the m otor again

IN V faults

C lear the deterrence

C orrect the connection

Overheating source flow:load/currentexceedsspecifiedvalue? YES→reduceload/increaseinverterandmotorcapacity;NO→motorlowspeedlongtime? YES→selectmotoragain;NO→U-V,V-W,W-Uvoltagecorrect? NO→INVfaults;YES→deterrencepreventingcooling? YES→cleardeterrence;NO→incorrectconnectionbetweeninverterandmotor? YES→correctconnection. No NOexitfromfinalquestionshown; do not invent one.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Final incorrect-connection question has only YES branch; NO outcome absent.

Manual — Motor unbalanced flowchart — page 354

Manual reference: physical PDF page 354. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: The initial question visibly says during eceleration?. A following question refers to acceleration time, while its action says Acc/Dec time. These do not prove which prefix was omitted from the first word. Preserve the damaged word.

5.3.6 Motor runs unbalanced

NO

YES

Does it happen during eceleration?

Motor runs unbalanced

Is the acceleration time correct?

Are the output voltages between U-V,V-W,W-U balanced?

Is the load fluctuating?

Any mechanical vibration or gear backlash

Increase the Acc/ Dec time

Reduce the load.Increase capacities of INV and the motor.

INV faults

Reduce the load fluctuation or add a flywheel.

Inspect the mechanical system

Unbalanced source flow:Doesithappenduringeceleration?(printedmisspelling)YES→accelerationtimecorrect? NO→increaseAcc/Dectime;YES→reduceloadandincreaseINV/motorcapacities. InitialNO→U-V,V-W,W-Uoutputvoltagesbalanced? NO→INVfaults;YES→loadfluctuating? YES→reduceloadfluctuationoraddflywheel;NO→mechanicalvibrationorgearbacklash? YES→inspectmechanicalsystem;NO→INVfaults. Missingprefixofecelerationnotreconstructed.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Initial question prints eceleration, leaving acceleration/deceleration condition unresolved.

Manual — Standard AC and PM auto-tune errors — page 355

Manual reference: physical PDF page 355. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.3.7 Auto-tuning Error

When a fault occurs during auto-tuning of a standard AC motor, the display will show the “AtErr” fault and the motor stops. The fault information is displayed in parameter 17-11. Refer to Table 10.4.1, for fault information during tuning, cause and corrective action.

Table 3 Auto-tuning fault and corrective actions

5.3.8 PM Motor Auto-tuning Error

When a fault occurs during auto-tuning of a PM motor, the display will show the “IPErr” fault and the

motor stops. The fault information is displayed in parameter 22-22. Refer to Table 4 for fault

information during tuning, cause and corrective action.

Table 4 Auto-tuning fault and corrective actions for PM motor

Standard AC auto-tune errors01/02/03/04/05/07/08/09; PM errors01/05/07/09 are distinct tables. No missing06 fabricated. PM faults use22-22,standard uses17-11.

Standard AC and PM auto-tune errors

Error / Description / Cause / Corrective action — PDF page 355

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Error Description Cause Corrective action
2 01 Motor data input error. • Motor Input data error during auto-tuning. • Inverter output current does not match motor rated current. • Check the motor tuning data (17-00 to 17-09). • Check inverter capacity
3 02 Motor lead to lead resistance R1 tuning error. • Auto-tuning is not completed within the specified time • Auto-tuning results fall outside parameter setting range. • Motor rated current exceeded. • Motor was disconnected. • Check the motor tuning data (17-00 to 17-09). • Check motor connection. • Disconnect motor load. • Check inverter current detection circuit and DCCTs. • Check motor installation.
4 03 Motor leakage inductance tuning error. • Auto-tuning is not completed within the specified time • Auto-tuning results fall outside parameter setting range. • Motor rated current exceeded. • Motor was disconnected. • Check the motor tuning data (17-00 to 17-09). • Check motor connection. • Disconnect motor load. • Check inverter current detection circuit and DCCTs. • Check motor installation.
5 04 Motor rotor resistance R2 tuning error. • Auto-tuning is not completed within the specified time • Auto-tuning results fall outside parameter setting range. • Motor rated current exceeded. • Motor was disconnected. • Check the motor tuning data (17-00 to 17-09). • Check motor connection. • Disconnect motor load. • Check inverter current detection circuit and DCCTs. • Check motor installation.
6 05 Motor mutual inductance Lm tuning error. • Auto-tuning is not completed within the specified time • Auto-tuning results fall outside parameter setting range. • Motor rated current exceeded. • Motor was disconnected. • Check the motor tuning data (17-00 to 17-09). • Check motor connection. • Disconnect motor load. • Check inverter current detection circuit and DCCTs. • Check motor installation.
7 07 Deadtime compensation detection error • Auto-tuning is not completed within the specified time • Auto-tuning results fall outside parameter setting range. • Motor rated current exceeded. • Motor was disconnected. • Check the motor tuning data (17-00 to 17-09). • Check motor connection. • Disconnect motor load. • Check inverter current detection circuit and DCCTs. • Check motor installation.
8 08 Motor acceleration error (Rotational type auto-tuning only). • Motor fails to accelerate in the specified time (00-14= 20sec). • Increase acceleration time (00-14). • Disconnect motor load.
9 09 Other auto-tuning errors • No load current is higher than 70% of the motor rated current. • Torque reference exceeds 100%. • Errors other than ATE01~ATE08. • Check the motor tuning data (17-00 to 17-09). • Check motor connection.

Error / Description / Cause / Corrective action — PDF page 355

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Error Description Cause Corrective action
2 01 Magnetic pole alignment tuning failure (static). Inverter output current does not match motor current. Check parameter 22-02 • Check inverter capacity
3 05 Circuit tuning time out. System abnormality during circuit tuning. • Check for active protection functions preventing auto-tuning.
4 07 Other motor tuning errors. Other tuning errors. Check parameter 22-02 • Check motor connection.
5 09 Current out of range during circuit tuning. Inverter output current does not match motor current. • Check parameter 22-02 • Check inverter capacity

Manual — Inspection checklist part1 — page 356

Manual reference: physical PDF page 356. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.4 Routine and periodic inspection

To ensure stable and safe operation, check and maintain the inverter at regular intervals. Use the checklist below to carry out inspection. Disconnect power after approximately 5 minutes to make sure no voltage is present on the output terminals before any inspection or maintenance.

Capacitor detail356Anyphysicaldamageor continues357protrusion. Daily and1Year inspection columns are distinct.357grey header band ends at97.15198PDFpoints; its labels must not repeat into unruled blank continuation cells.

Source safety sequence conflict:356Disconnectpowerafterapproximately5minutes vs358Turnpoweroffandwaitminimum5minutesbeforeinspectiontoavoidstored-capacitor shock. Preserve both as source statements; not an approved procedure.

Inspection checklist part1

Items / Details / Checking period / Methods / Criteria / Remedies — PDF page 356

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Items Details Checking period Checking period Methods Criteria Remedies
2 Items Details Daily 1Year Methods Criteria Remedies
3 Environment & Ground connection Environment & Ground connection Environment & Ground connection Environment & Ground connection Environment & Ground connection Environment & Ground connection Environment & Ground connection
4 Ambient conditions at the installation Confirm the temperature and humidity at the machine ◎ ⟦blank source cell⟧ Measure with thermometer and hygrometer Temperature: -10~40oC (14-120℉) Humidity: Below 95%RH Improve the ambient or relocate the drive to a better area.
5 Ambient conditions at the installation Are there inflammable materials in the vicinity? ◎ ⟦blank source cell⟧ Visual check Keep area clear Improve the ambient or relocate the drive to a better area.
6 Installation Grounding Any unusual vibration from the machine ◎ ⟦blank source cell⟧ Visual, hearing check Keep area clear Secure screws
7 Installation Grounding Is the grounding resistance correct? ⟦blank source cell⟧ ◎ Measure the resistance with a multi-tester 200Vclass: below 100Ω Improve the grounding if needed.
8 Terminals & Wiring Terminals & Wiring Terminals & Wiring Terminals & Wiring Terminals & Wiring Terminals & Wiring Terminals & Wiring
9 Connection terminals Any loose parts or terminals? ⟦blank source cell⟧ ◎ Visual check Check with a screwdriver Correct installation requirement Secure terminals and remove rust
10 Connection terminals Any damage to the base ? ⟦blank source cell⟧ ◎ Visual check Check with a screwdriver Correct installation requirement Secure terminals and remove rust
11 Connection terminals Any corroded Terminals? ⟦blank source cell⟧ ◎ Visual check Check with a screwdriver Correct installation requirement Secure terminals and remove rust
12 Wiring Any broken wires? ⟦blank source cell⟧ ◎ Visual check Correct wiring requirement Rectify as necessary
13 Wiring Any damage to the wire insulation? ⟦blank source cell⟧ ◎ Visual check Correct wiring requirement Rectify as necessary
14 Voltage Voltage Voltage Voltage Voltage Voltage Voltage
15 Input power voltage Is the voltage of the main circuit correct? ◎ ⟦blank source cell⟧ Measure the voltage with a multi-tester Voltage must conform with the spec. Improve input voltage if necessary.
16 Circuit boards and components Circuit boards and components Circuit boards and components Circuit boards and components Circuit boards and components Circuit boards and components Circuit boards and components
17 Printed circuit board Any contamination or damage to printed circuit board? ⟦blank source cell⟧ ◎ Visual check Correct component condition Clean or replace the circuit board
18 Printed circuit board Discolored, overheated, or burned parts ⟦blank source cell⟧ ◎ Visual check Correct component condition Clean or replace the circuit board
19 Capacitor Any unusual odor or leakage ◎ ⟦blank source cell⟧ Visual check Correct component condition Replace capacitor or inverter
20 Capacitor Any physical damage or ⟦blank source cell⟧ ◎ Visual check Correct component condition Replace capacitor or inverter

Manual — Inspection checklist continuation — page 357

Manual reference: physical PDF page 357. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Capacitor detail356Anyphysicaldamageor continues357protrusion. Daily and1Year inspection columns are distinct.357grey header band ends at97.15198PDFpoints; its labels must not repeat into unruled blank continuation cells.

Inspection checklist continuation

Items / Details / Checking period / Methods / Criteria / Remedies — PDF page 357

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Items Details Checking period Checking period Methods Criteria Remedies
2 Items Details Daily 1Year Methods Criteria Remedies
3 ⟦blank source cell⟧ protrusion ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
4 Power component Any dust or debris ⟦blank source cell⟧ ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ Clean components
5 Power component Check resistance between each terminals ⟦blank source cell⟧ ◎ Measure with a multi-tester No short circuit or broken circuit in three-phase output Consult with the supplier
6 Peripheral device Peripheral device Peripheral device Peripheral device Peripheral device Peripheral device Peripheral device
7 Rheostat Whether rheostat wiring or connector are damaged ⟦blank source cell⟧ ◎ Visual check No abnormalities Replacement rheostat
8 Electromagnetic Contactor Check contacts and connections for any abnormality. ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ No abnormalities Replacement Contactor
9 Electromagnetic Contactor Unusual vibration and noise ◎ ⟦blank source cell⟧ hearing check No abnormalities Replacement Contactor
10 Reactor Is there any abnormalities? ◎ ⟦blank source cell⟧ Visual check No abnormalities Replacement Reactor
11 Cooling System Cooling System Cooling System Cooling System Cooling System Cooling System Cooling System
12 Cooling fan Unusual vibration and noise ⟦blank source cell⟧ ◎ Visual or hearing check Correct cooling Consult with the supplier
13 Cooling fan Excessive dust or debris ◎ ⟦blank source cell⟧ Visual check Correct cooling Clean the fan
14 Heat sink Excessive dust or debris ◎ ⟦blank source cell⟧ Visual check Correct cooling Clean up debris or dust
15 Ventilation Path Is the ventilation path blocked? ◎ ⟦blank source cell⟧ Visual check Correct cooling Clear the path

Manual — Maintenance checklist and insulation-test labels — page 358

Manual reference: physical PDF page 358. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.5 Maintenance

To ensure long-term reliability, follow the instructions below to perform regular inspection. Turn the power off and wait for a minimum of 5 minutes before inspection to avoid potential shock hazard from the charge stored in high-capacity capacitors.

  1. Maintenance Check List:

➢ Ensure that temperature and humidity around the inverters is as required in the instruction manual, installed away from any sources of heat and the correct ventilation is provided..

➢ For replacement of a failed or damaged inverter consult with the local supplier.

➢ Ensure that the installation area is free from dust and any other contamination.

➢ Check and ensure that the ground connections are secure and correct.

➢ Terminal screws must be tight, especially on the power input and output of the inverter.

➢ Do not perform any insulation test on the control circuit.

  1. Insulation test Method

Single Phase:

Three Phase:

SinglePhaseinsulation-test source labels:PowerSource,L1(L),L2,L3(N),Inverter,T1,T2,T3,Motor,DielectricWithstandVoltageTest,groundsymbol. Line drawing retained as visual evidence only; no test voltage,procedure or new wiring topology inferred.

ThreePhaseinsulation-test source labels:PowerSource,L1(L),L2,L3(N),Inverter,T1,T2,T3,Motor,DielectricWithstandVoltageTest,groundsymbol. Source labels not generalized to a wiring instruction; no test voltage printed.

Source safety sequence conflict:356Disconnectpowerafterapproximately5minutes vs358Turnpoweroffandwaitminimum5minutesbeforeinspectiontoavoidstored-capacitor shock. Preserve both as source statements; not an approved procedure.

Explicit source prohibition: Do not perform any insulation test on the control circuit. Diagram labels do not constitute a newly inferred test or wiring procedure.

Manual — Reactor model/current/3%reactance inductance — page 359

Manual reference: physical PDF page 359. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 6 Peripherals Components

6.1 Reactor specifications

Reactor model/current/3%reactance inductance

Model:E510-□□□-SXXX / Specification — PDF page 359

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Model:E510-□□□-SXXX Specification Specification
2 Model:E510-□□□-SXXX Current (A) Calculated Inductance Based on 3% Reactance (mH)
3 2P5 8.5 2.1
4 201 12 2.1
5 202 19.0 1.1
6 203 25.0 0.71
7 205 20 0.53
8 208 33.0 0.35
9 210 42.0 0.265
10 215 60 0.18
11 220 80 0.13
12 225 95 0.13
13 230 140 0.09
14 240 170 0.07
15 401 4.5 8.4
16 402 6 4.2
17 403 7.5 3.6
18 405 12 2.2
19 408 17.0 1.42
20 410 23.0 1.06
21 415 31.0 0.7
22 420 40 0.53
23 425 50 0.42
24 430 70 0.35
25 440 90 0.28
26 450 110 0.23
27 460 130 0.20
28 475 180 0.14

Manual — Circuit-breaker/contactors and standard fuses — page 360

Manual reference: physical PDF page 360. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.2 Electromagnetic contactor circuit breaker

6.3 Fuse specification

Circuit-breaker/contactors and standard fuses

Model:E510-□□□-SXXX / Circuit breaker made by TECO / Magnetic contactor made by TECO — PDF page 360

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Model:E510-□□□-SXXX Circuit breaker made by TECO Magnetic contactor made by TECO
2 2P5 TO-50E 15A CN-11
3 201/202 TO-50E 20A CN-11
4 203/205 TO-50E 30A CN-11
5 208 TO-50E 50A CN-18
6 210 TO-100E 60A CN-25
7 215 TO-100E 100A CN-50
8 220 TO-100E 100A CN-60
9 225 TO-225S (100A) CU-80
10 230 TO-225S (150A) CN-100
11 240 TO-225S(175A) CN-125
12 401/402/403/405 TO-50EC 15A CN-11
13 408 TO-50EC 20A CN-16
14 410 TO-50EC 30A CN-18
15 415 TO-50EC 50A CN-25
16 420 TO-100EB 50A CN-35
17 425 TO-100EB 75A CN-50
18 430 TO-100S(75A) CU-50
19 440 TO-100S(100A) CU-65
20 450 TO-100S(100A) CU-80
21 460 TO-225S(150A) CN-100
22 475 TO-225S(175A) CN-125

Model:E510-□□□-SXXX / Fuse Type — PDF page 360

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Model:E510-□□□-SXXX Fuse Type
2 2P5/201 15A, 300VAC
3 202/203/205 30A, 300VAC
4 208/210 60A, 300VAC
5 215/220 100A, 300VAC
6 225 200A, 300VAC
7 230 250A, 300VAC
8 240 300A, 300VAC
9 401 5 A, 600VAC
10 402 10A, 600VAC
11 403 15A, 600VAC
12 405 20A, 600VAC
13 408/410 40A, 600VAC
14 415/420 70A, 600VAC
15 425 100A, 600VAC
16 430 120A, 600VAC
17 440 150A, 600VAC
18 450 200A, 600VAC
19 460 250A, 600VAC
20 475 300A, 600VAC

Manual — Recommended UL-model fuse variants — page 361

Manual reference: physical PDF page 361. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.4 Fuse specification (UL model recommended)

SH1(F),SH3andSH3(F) variants retained separately. E510-215-SH3 has two fuse options in a single row:120FEE690V120A andA50QS150-4500V150A; both remain tied to this row. Dashes stay unknown; historicalULrecommendationnotcertificate.

Recommended UL-model fuse variants

Model / Manufacture / Type / Rating — PDF page 361

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Model Manufacture Type Rating
2 E510-2P5/201- SH1(F) Bussmann 20CT 690V 20A
3 E510-202-SH1(F) Bussmann 30FE 690V 30A
4 E510-203-SH1(F) Bussmann 50FE 690V 50A
5 E510-2P5/201-SH3 Bussmann 20CT 690V 20A
6 E510-202-SH3 Bussmann 20CT 690V 20A
7 E510-203-SH3 Bussmann 30FE 690V 30A
8 E510-205-SH3 Bussmann 50FE 690V 50A
9 E510-208-SH3 Bussmann 63FE 690V 63A
10 E510-210-SH3 Ferraz Shawmut A50QS100-4 500V 100A
11 E510-215-SH3 Bussmann or Ferraz Shawmut 120FEE A50QS150-4 690V 120A 500V 150A
12 E510-220-SH3 Ferraz Shawmut A50QS150-4 500V 150A
13 E510-225-SH3 - - 500V 200A
14 E510-230-SH3 - - 500V 250A
15 E510-240-SH3 - - 500V 300A
16 E510-401-SH3(F) Bussmann 10CT 690V 10A
17 E510-402/403- SH3(F) Bussmann 16CT 690V 16A
18 E510-405-SH3(F) Bussmann 25ET 690V 25A
19 E510-408-SH3(F) Bussmann 40FE 690V 40A
20 E510-410-SH3(F) Bussmann 50FE 690V 50A
21 E510-415-SH3(F) Bussmann 63FE 690V 63A
22 E510-420-SH3(F) Bussmann 80FE 690V 80A
23 E510-425-SH3(F) Ferraz Shawmut A50QS100-4 500V 100A
24 E510-430-SH3(F) - - 690V 120A
25 E510-440-SH3(F) - - 690V 150A
26 E510-450-SH3(F) - - 690V 200A
27 E510-460-SH3(F) - - 690V 250A
28 E510-475-SH3(F) - - 690V 300A

Manual — Brake resistor ratings and dimensions part1 — page 362

Manual reference: physical PDF page 362. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.5 Brake resistor

Brake table continues362→363; blank363voltagecell remains blank with preceding400V3Ph block context explicitly cited. Resistor specification quantity and dimension quantity are separate columns, never summed or equated.10%ED braking-torque heading retained; no missing torque unit invented.

Brake resistor ratings and dimensions part1

Model / Braking Unit / Specifications of Braking Resistor / Dimension of Braking Resistor / Braking Torque / Minimum Resistance — PDF page 362

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows) Physical column 11 (source headings retained in rows) Physical column 12 (source headings retained in rows) Physical column 13 (source headings retained in rows) Physical column 14 (source headings retained in rows)
1 Model Model Model Braking Unit Braking Unit Specifications of Braking Resistor Specifications of Braking Resistor Specifications of Braking Resistor Specifications of Braking Resistor Dimension of Braking Resistor Dimension of Braking Resistor Braking Torque Minimum Resistance Minimum Resistance
2 V HP KW Model Qty Number of Braking Resistor Qty (W) (Ω) (LxWxH) mm Qty 10% ED (Ω) (W)
3 220V 1/3Ph 0.5 0.4 - - JNBR-150W400 1 150 400 150W/400Ω (251x28x60) 1 119 50 350
4 220V 1/3Ph 1 0.75 - - JNBR-150W200 1 150 200 150W/200Ω (251x28x60) 1 119 50 350
5 220V 1/3Ph 2 1.5 - - JNBR-150W100 1 150 100 150W/100Ω (251x28x60) 1 119 50 350
6 220V 1/3Ph 3 2.2 - - JNBR-260W70 1 260 70 260W/70Ω (274x40x78) 1 115 50 350
7 220V 3Ph 5 4 - - JNBR-390W40 1 390 40 390W/40Ω (395x40x78) 1 119 19 1000
8 220V 3Ph 7.5 5.5 - - JNBR-520W30 1 520 30 520W/30Ω (400x50x100) 1 108 10 1600
9 220V 3Ph 10 7.5 - - JNBR-780W20 1 780 20 780W/20Ω (400x50x100) 1 119 10 1600
10 220V 3Ph 15 11 - - JNBR-2R4KW13R6 1 2400 13.6 2400W/13.6Ω (400x50x100) 2 117 10 1600
11 220V 3Ph 20 15 - - JNBR-3KW10 1 3000 10 1500W/20Ω (615x60x110) 2 119 6.6 2400
12 220V 3Ph 25 18.5 - - JNBR-4R8KW8 1 4800 8 1200W/32Ω (535x60x110) 4 119 6.6 2400
13 220V 3Ph 30 22 JNTBU-230 1 JNBR-4R8KW6R8 1 4800 6.8 1200W/27.2Ω (535x60x110) 4 117 5.5 3000
14 220V 3Ph 40 30 JNTBU-230 2 JNBR-3KW10 2 3000 10 1500W/20Ω (615x60x110) 4 119 5.5 3000
15 400V 3Ph 1 0.75 - - JNBR-150W750 1 150 750 150W/750Ω (251x28x60) 1 126 125 600
16 400V 3Ph 2 1.5 - - JNBR-150W400 1 150 400 150W/400Ω (251x28x60) 1 119 125 600
17 400V 3Ph 3 2.2 - - JNBR-260W250 1 260 250 260W/250Ω (274x40x78) 1 126 84 800
18 400V 3Ph 5 4 - - JNBR-400W150 1 400 150 400W/150Ω (395x40x78) 1 126 56 1200
19 400V 3Ph 7.5 5.5 - - JNBR-600W130 1 600 120 600W/130Ω (395x40x78) 1 102 67 1000
20 400V 3Ph 10 7.5 - - JNBR-800W100 1 800 100 800W/100Ω (535x60x110) 1 99 67 1000
21 400V 3Ph 15 11 - - JNBR-1R6KW50 1 1600 50 1600W/50Ω (615x60x110) 1 126 25 2500

Manual — Brake resistor continuation and noise filters — page 363

Manual reference: physical PDF page 363. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note: Formula for brake resistor:W= (Vpnb * Vpnb) * ED% / Rmin (1) W:braking resistor power (Watts) (2) Vpnb:braking voltage (220V=380VDC, 440V=760VDC) (3) ED%:braking effective period (4) Rmin:braking resistor minimum value (ohms) 6.6 Input noise filter Install a noise filter on power supply side to eliminate noise transmitted between the power line and the inverter. The inverter noise filter shown in table belowmeets the EN61800-5-1.

Brake table continues362→363; blank363voltagecell remains blank with preceding400V3Ph block context explicitly cited. Resistor specification quantity and dimension quantity are separate columns, never summed or equated.10%ED braking-torque heading retained; no missing torque unit invented.

Filter alternatives separated by slash keep their source order and current pairs10/16and27/16. Noise-filter standard claim remains supplier text. Braking formulaVpnb220V=380VDC,440V=760VDCretained independently of400Vtable label.

Brake resistor continuation and noise filters

Model / Braking Unit / Specifications of Braking Resistor / Dimension of Braking Resistor / Braking Torque / Minimum Resistance — PDF page 363

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows) Physical column 11 (source headings retained in rows) Physical column 12 (source headings retained in rows) Physical column 13 (source headings retained in rows) Physical column 14 (source headings retained in rows)
1 Model Model Model Braking Unit Braking Unit Specifications of Braking Resistor Specifications of Braking Resistor Specifications of Braking Resistor Specifications of Braking Resistor Dimension of Braking Resistor Dimension of Braking Resistor Braking Torque Minimum Resistance Minimum Resistance
2 V HP KW Model Qty Number of Braking Resistor Qty (W) (Ω) (LxWxH) mm Qty 10% ED (Ω) (W)
3 ⟦blank source cell⟧ 20 15 - - JNBR-1R5KW40 1 1500 40 1500W/40Ω (615x60x110) 1 119 20 3200
4 ⟦blank source cell⟧ 25 18.5 - - JNBR-4R8KW32 1 4800 32 1200W/32Ω (535x60x110) 4 117 20 3200
5 ⟦blank source cell⟧ 30 22 - - JNBR-4R8KW27R2 1 4800 27.2 1200W/27.2Ω (535x60x110) 4 117 20 3200
6 ⟦blank source cell⟧ 40 30 - - JNBR-6KW20 1 6000 20 1500W/20Ω (615x60x110) 4 119 10 6200
7 ⟦blank source cell⟧ 50 37 TBU-430 2 JNBR-4R8KW32 2 4800 32 1200W/32Ω (535x60x110) 8 119 19.2 3600
8 ⟦blank source cell⟧ 60 45 TBU-430 2 JNBR-4R8KW27R2 2 4800 27.2 1200W/27.2Ω (535x60x110) 8 117 19.2 3600
9 ⟦blank source cell⟧ 75 55 TBU-430 2 JNBR-6KW20 2 6000 20 1500W/20Ω (615x60x110) 8 126 19.2 3600

Frame / Model / Input Voltage / External Number of Filter / (A) — PDF page 363

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Frame Model Input Voltage External Number of Filter (A)
2 1 2P5/201-SH 1Φ/3Φ 200~240V E2F-2102/FN3258-16-45 10/16
3 2 202/203-SH1(F) 1Φ/3Φ 200~240V FS6146-27-07/FN3258-16-45 27/16
4 1 202-SH3 3Φ 200~240V FN3258-16-45 16
5 2 205-SH3 3Φ 200~240V FS20500-22-99 22
6 3 208/210-SH3 3Φ 200~240V T-096.05001.00 50
7 4 215/220-SH3 3Φ 200~240V T-097.08004.00 80
8 5 225-SH3 3Φ 200~240V FS32125-86-99 86
9 6 230/240-SH3 3Φ 200~240V FS32125-150-99 150
10 1 401/402-SH3(F) 3Φ 380~480V FN3258-16-45 16
11 2 403/405-SH3(F) 3Φ 380~480V FN3258-16-45 16
12 3 408/410/415-SH3(F) 3Φ 380~480V T-097.08004.00 80
13 4 420/425-SH3(F) 3Φ 380~480V FS42500-50-99 80
14 5 430-SH3(F) 3Φ 380~480V JN5-FLT-63A 63
15 6 440/450/460-SH3(F) 3Φ 380~480V JN5-FLT-112A 112
16 6 475-SH3(F) 3Φ 380~480V FS32126-181-99 181

Manual — Accessory models and applicability — page 364

Manual reference: physical PDF page 364. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.7 Accessories

Din-rail kit model: Including sheet metal base and plastic base, fixed with screws.

DINkit photographs labelsJN5-DINF1left andJN5-DINF2right. SummarytableinsteadJN5-DIN01/02. Photos show installedsheetmetal/plasticbase only; no dimensions inferred.

Extension-cable prefix CM in364 vsCB in365 remains discrepancy; no equivalence inferred. Dust-sticker remote-keypad andTOP models are distinct;70%ratedcurrent restriction applies toTOP sticker source row.

Accessory models and applicability

Accessories / Instruction / Model / Note — PDF page 364

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Accessories Instruction Model Note
2 Connection cable Operator extension cable JN5-CM-01M 1m
3 Connection cable Operator extension cable JN5-CM-02M 2m
4 Connection cable Operator extension cable JN5-CM-03M 3m
5 Connection cable Operator extension cable JN5-CM-05M 5m
6 Connection cable RJ45 to USB connecting cable JN5-CM-USB 1.8m
7 Dust Sticker (For remote keypad) If remote keypad function is necessary, please stick the dust sticker, to prevent dust enter 4KA92X2253 For Frame 1~4
8 Dust Sticker (For remote keypad) If remote keypad function is necessary, please stick the dust sticker, to prevent dust enter 4KA92X1936 For Frame 5
9 Dust Sticker (For remote keypad) If remote keypad function is necessary, please stick the dust sticker, to prevent dust enter 4KA92X1937 For Frame 6
10 NEMA1 kits NEMA1 kit can upgrade the protection level of inverter, it can be installed at the bottom of inverter. (Frame5/6 already built-in NEMA 1 design) JN5-NK-SE01 For Frame 1
11 NEMA1 kits NEMA1 kit can upgrade the protection level of inverter, it can be installed at the bottom of inverter. (Frame5/6 already built-in NEMA 1 design) JN5-NK-SE02 For Frame 2
12 NEMA1 kits NEMA1 kit can upgrade the protection level of inverter, it can be installed at the bottom of inverter. (Frame5/6 already built-in NEMA 1 design) JN5-NK-SE03 For Frame 3
13 NEMA1 kits NEMA1 kit can upgrade the protection level of inverter, it can be installed at the bottom of inverter. (Frame5/6 already built-in NEMA 1 design) JN5-NK-SE04 For Frame 4
14 Copy Unit Copy the inverter parameters to another inverter by copy unit. (Support E510s series after v1.4firmware) JN5-CU ⟦blank source cell⟧
15 LCD Operator IP20 LCD Operator JN5-OP-A02 ⟦blank source cell⟧
16 LCD Operator LCD remote keypad panel base 4KA82X880 ⟦blank source cell⟧
17 Remote Keypad Panel Base For remote keypad to be mounted on the panel more easily JN5-KEYBOX ⟦blank source cell⟧
18 Communication Card Profibus communication card JN5-CMI-PDP Integrated Type
19 Communication Card TCP-IP communication card JN5-CMI-TCPIP Integrated Type
20 Communication Card DeviceNet communication card JN5-CMI-DNET Integrated Type
21 Communication Card CANopen communication card JN5-CMI-CAN Integrated Type
22 Dust Sticker (TOP) The options can upgrade the protection level to avoid the entry of foreign matter. (When inverter installed with dust sticker, please does not exceed 70% rated current of inverter) 4KA92X1944 For frame 1
23 Dust Sticker (TOP) The options can upgrade the protection level to avoid the entry of foreign matter. (When inverter installed with dust sticker, please does not exceed 70% rated current of inverter) 4KA92X1945 For frame 2
24 Dust Sticker (TOP) The options can upgrade the protection level to avoid the entry of foreign matter. (When inverter installed with dust sticker, please does not exceed 70% rated current of inverter) 4KA92X1946 For frame 3
25 Dust Sticker (TOP) The options can upgrade the protection level to avoid the entry of foreign matter. (When inverter installed with dust sticker, please does not exceed 70% rated current of inverter) 4KA92X1947 For frame 4
26 Din-rail kit The options can fixed the drive on 35mm din-rail. JN5-DIN01 For frame 1
27 Din-rail kit The options can fixed the drive on 35mm din-rail. JN5-DIN02 For frame 2

Manual — Remote keypad and RJ45/USB cable — page 365

Manual reference: physical PDF page 365. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Local365 unit omission and1.8m versus explicit413mm dimensional context are not normalized or silently reconciled.

(1) Blank cover and operator extension cable

➢ When used for remote control purposes, the keypad can be removed and remotely connected

with an extension cable (figure a).

➢ If inverter controlled by remote keypad, please put the dust sticker on the position of display to

prevent the foreign material fall into inverter (figure b).

Dust Sticker For remote keypad

➢ Extension cables are available in the following length.

(2) RJ45 to USB connecting cable (1.8m)

➢ JN5-CM-USB has the function of converting USB communication format to RS485 to achieve the

inverter communication control being similar with PC or other control equipment with USB port.

➢ Exterior:

➢ Connecting:

Figurea shows remote keypad and extension cable;Figureb dust sticker over keypadopening. Nearby table assignsframe1–4/5/6specificstickers; no external wiring inferred.

RJ45/USB exterior drawing:longitudinaldimension180.0±1.5;leftconnectorheight20,leftstub12,connectorbody45.5;rightconnectorlength12.3,height11.6. No dimensionalunitprinted; do not assume or reconcile with1.8mheading. Enlarged detail365 confirms11.6.

Connecting illustration showsUSBcableandopenkeypad/terminalarea. No numberedterminals,extra ratings or wiring topology transcribed from illustration.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Exterior cable drawing has no unit for180.0±1.5,20,12,45.5,12.3,11.6. Heading1.8m not used to infer dimensional unit.

Extension-cable prefix CM in364 vsCB in365 remains discrepancy; no equivalence inferred. Dust-sticker remote-keypad andTOP models are distinct;70%ratedcurrent restriction applies toTOP sticker source row.

Remote keypad and RJ45/USB cable

Corresponding frame / Model — PDF page 365

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Corresponding frame Model
2 Frame 1~4 4KA92X2253
3 Frame 5 4KA92X1936
4 Frame 6 4KA92X1937

Name / Model / Specification — PDF page 365

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Name Model Specification
2 Operator extension cable JN5-CB- 01M 1m (3.3 ft)
3 Operator extension cable JN5-CB- 02M 2m (6.6 ft)
4 Operator extension cable JN5-CB- 03M 3m (10 ft)
5 Operator extension cable JN5-CB- 05M 5m (16.4 ft)

Manual — NEMA1 options and copy unit — page 366

Manual reference: physical PDF page 366. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh 6x copy-unit control crop confirms direction arrows and INV prefix; the final abbreviation still cannot be unambiguously transcribed. Keep exact dimensional and compatibility context, do not guess CPM/CPY.

(3) NEMA1 option

➢ Inverter can reach NEMA1 protection level when NEMA1 options installed.

*Frame 5/6 models already built-in NEMA1 design

(4) Copy unit (JN5-CU)(Copy unit can be used on E510s with v1.4 and above)

➢ Parameters can be copied from one inverter to other inverters.

➢ Installation dimensions of copy unit (unit : mm)

NEMA1option installed below drive; source table describesframe1–4andweights,frame5/6built-in. No certification validity inferred.

Copy-unit illustration and face:JN5-CU;indicatorSEQ,FRQ,FWD,REV,Hz/RPM,VOLT,FUN,AMP;keysup/down with tiny INV direction abbreviations unresolved,MODE,returnarrow,RUN/CLEAR,STOP/RESET,OK/ENTER. Source illustration only;v1.4andabove requirement inheading.

Copy-unitinstallationdimensions explicitlyunitmm:frontwidth62.0,height85.0;sidebodythickness14.2;otherprofiledepth22.7. Face labelsSEQ,FRQ,FWD,REV,Hz/RPM,VOLT,FUN,AMP,MODE,CopyUnit,RUN/CLEAR,STOP/RESET,OK/ENTERandarrowkeys; no missing hole dimensions inferred.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Copy-unit up/down button small abbreviation after INV direction marker remains uncertain even enlarged; dimensions and clear controls retained.

Copy-unitcompatibility continues366→367: same-series/sameHP keypadandmotor copied; same-series/differentHP keypadonly; differentseriesneither. Oldversion→newallowed,reverseNOTallowed. Firmware wording discrepancyretained.

NEMA1 options and copy unit

Name / Model / Note / Weight (Kg) — PDF page 366

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Name Model Note Weight (Kg)
2 NEMA1 options JN5-NK- SE01 For frame 1 models 0.24
3 NEMA1 options JN5-NK- SE02 For frame 2 models 0.27
4 NEMA1 options JN5-NK- SE03 For frame 3 models 0.45
5 NEMA1 options JN5-NK- SE04 For frame 4 models 0.56

Manual — Copy-unit compatibility and LCD operator — page 367

Manual reference: physical PDF page 367. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: LCD drawing has no explicit unit; copy-unit mm on previouspage does not establish LCD unit.

➢ Connection Conditions of Copy Unit (JN5-CU)

(5) LCD Operator (JN5-OP-A02)

Installation dimensions of LCD keypad display

(6) Keypad holder (JN5-KEYBOX)

➢ Remote keypad can be installed more easily by this option.

LCDoperator photograph:FAULT,FWD,REV,REMOTEbracketoverSEQ/REF;LOC/REM,DSP/FUN,left/RESET,READ/ENTER,up/down,RUN,STOP. No active displayvalue.

LCDkeypaddrawing:frontoverallwidth85.0,height130.0;mountingcentres74.0horizontal,119.0vertical. Side15.5and9.9separatehorizontalspans. Rear74.0mountingwidth,119.0vertical;connector22.5verticalabove20.8bottomoffset;7.8leftoffsetand23.0horizontalspan. No unitprinted on this drawing; unitfrompreviouscopyunitnotinherited. Enlarged detail367retained.

Keypad-holder photographs frontwithE510skeypadandemptyrear. TECO,E510s,FAULT,FWD,REV,FUN,FRQ,FREQ.SETvisible; smallerbuttonmarkingsnotreliedon for instructions.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: LCD drawing has no explicit unit; copy-unit mm on previouspage does not establish LCD unit.

Copy-unitcompatibility continues366→367: same-series/sameHP keypadandmotor copied; same-series/differentHP keypadonly; differentseriesneither. Oldversion→newallowed,reverseNOTallowed. Firmware wording discrepancyretained.

Copy-unit compatibility and LCD operator

Inverter / Keypad Parameters / Motor Parameters / NOTE — PDF page 367

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Inverter Keypad Parameters Motor Parameters NOTE
2 Same Series Inverter Same HorsePower Can be Copied Can be Copied Old version parameters can be copied to New version New version parameters can NOT be copied to old version.
3 Same Series Inverter Different HorsePower Can be Copied Can not be Copied Old version parameters can be copied to New version New version parameters can NOT be copied to old version.
4 Different Series Inverter Can not be Copied Can not be Copied ⟦blank source cell⟧

Manual — Keypad-holder dimensions and communication cards — page 368

Manual reference: physical PDF page 368. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Keypad-holder dimension drawing lacks explicit unit; no unit inferred.

➢ Installation dimensions of keypad holder

(7) Integrated communication card

(a) PROFIBUS communication card

For wiring example and communication setup refer to JN5-CMI-

PDP communication option manual.

(b) DEVICENET communication card

For wiring example and communication setup refer to JN5-

CMI-DNET communication option manual.

Keypadholderdrawing:overallfrontwidth128.2,height151.8;upperhorizontaloffset20.1,span88andinner68;leftvertical10.1topoffset,131.6span,97innerspan;rightvertical13.6topoffsetand124.6span;bottom12.1offsetand104span;4-Ø8outerholes,4-Ø4.5,4-M3innerlocations,4-R10corners. Side20.5overallspan,9.1and2.1subspans. No unitprinted. Preserve leaders rather than inferring extra dimensions.

PROFIBUS card photograph;sourcecaptionlinksJN5-CMI-PDPmanualforwiring/setup. PCBswitch/terminaltopology notinferred.

DEVICENETcardphotograph;sourcecaptionlinksJN5-CMI-DNETmanualforwiring/setup. No switchsettings inferred.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Keypad-holder dimension drawing lacks explicit unit; no unit inferred.

Manual — Communication cards and frame1DINkit — page 369

Manual reference: physical PDF page 369. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(c) CANOPEN communication card

For wiring example and communication setup refer to JN5-

CMI-CAN communication option manual.

(d) TCP-IP communication card

CMI-TCPIP communication option manual.

(8) Din-rail kit

➢ The options can fixed the drive on 35mm din-rail.

➢ Exterior:

CANOPENcardphotograph;sourcecaptionreferencesJN5-CMI-CANmanualforwiring/setup. No terminalassignmentinferred.

TCP-IPcardphotograph;sourcecaptionreferencesJN5-CMI-TCPIPmanualforwiring/setup;LANTRONIXlabelvisible,notanadditionalproductrating.

Frame1DINassembly/disassembly illustration labelsScrews,Metalplateadaptor,Plasticadaptor,Snaphooks,Middlesnaphooks. Assemblynumberedarrows1upatmetalplate,2downatdrive,3upatplastic,4curvedsnap. Disassembly1upatscrewdriver,2curvedatmiddlehooks,3downatplastic,4upatdrive,5downatplate. Source directions only; no inferred torque/toolspec.

DINkit frame1illustration369 andframe2/parts370 linked; no hidden screwtorque or railprofileinferred. 35mmdinrailfromsourceprose retained.

Manual — Frame2DINkit and component parts — page 370

Manual reference: physical PDF page 370. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ JN5-DINF1/F2 including the following parts

Frame2DINassembly/disassembly labelsScrews,Metalplateadaptor,Plasticadaptor,Snaphooks,Middlesnaphooks. Assemblyarrows1upplate,2downdrive,3upplastic,4curvedsnap;disassembly1upscrewdriver,2curvedmiddlehooks,3downplastic,4updrive,5downplate. Partnumbersretainedintable.

Mountingdiagram:step1downalongtilteddrive,step2curvedbottomsnapCLICK. Dismountingstep1downnearbottomandupatscrewdriver,step2leftawayfromrail. Railprofileiconsincludeonecrossedoutshape; no unnamedrailprofileidentified. Prose369requires35mmdinrail.

DINkit frame1illustration369 andframe2/parts370 linked; no hidden screwtorque or railprofileinferred. 35mmdinrailfromsourceprose retained.

Frame2DINkit and component parts

Item / JN5-DINF1(Frame1) / JN5-DINF2(Frame2) — PDF page 370

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Item JN5-DINF1(Frame1) JN5-DINF2(Frame2)
2 1 Metal plate adaptor(4KA76X1391T01) Metal plate adaptor (4KA76X1392T01)
3 2 Chamfer head screw M4×12(4KA77X011T11) Chamfer head screw M4×12(4KA77X011T11)
4 3 Plastic adaptor(4KA82X442T01) Plastic adaptor(4KA82X442T01)

Manual — Appendix1 UL instructions: electrical shock and personnel precautions — page 371

Manual reference: physical PDF page 371. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 Instructions for UL

AP 1‐1

Appendix 1 Instructions for UL  Safety Precautions

DANGER Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. WARNING Electrical Shock Hazard

Do not operate equipment with covers removed.

Failure to comply could result in death or serious injury.

The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or

shields before operating the drives and run the drives according to the instructions described in this manual.

Always ground the motor-side grounding terminal.

Improper equipment grounding could result in death or serious injury by contacting the motor case.

Do not touch any terminals before the capacitors have fully discharged.

Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power

supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching

any components.

Do not allow unqualified personnel to perform work on the drive.

Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with

installation, adjustment, and maintenance of AC drives.

Do not perform work on the drive while wearing loose clothing, jewelry, or lack of eye protection.

Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work

on the drive.

Do not remove covers or touch circuit boards while the power is on.

Manual — Appendix1 fire precautions, notices and UL source claims — page 372

Manual reference: physical PDF page 372. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 Instructions for UL

Fire Hazard Tighten all terminal screws to the specified tightening torque.

Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.

Do not use an improper voltage source.

Failure to comply could result in death or serious injury by fire.

Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.

Do not use improper combustible materials.

Attach the drive to metal or other noncombustible material.

NOTICE

Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance.

Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.

NOTICE Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. Teco is not responsible for any modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices.

Failure to comply could result in damage to the drive.  UL Standards The UL/cUL mark applies to products in the United States and Canada and it means that UL has performed product

testing and evaluation and determined that their stringent standards for product safety have been met. For a product

to receive UL certification, all components inside that product must also receive UL certification.

UL/cUL Mark

Illustration of UL/cUL mark with c, UL, US and LISTED labels. Historical supplier illustration only; no certification validity established.

Manual — Appendix1 installation and 11-201 crimp-terminal models — page 373

Manual reference: physical PDF page 373. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 Instructions for UL

AP 1‐3

 UL Standards Compliance

This drive is tested in accordance with UL standard UL508C and complies with UL requirements. To ensure continued

compliance when using this drive in combination with other equipment, meet the following conditions:  Installation Area

Do not install the drive to an area greater than pollution severity 2 (UL standard).  Main Circuit Terminal Wiring

UL approval requires crimp terminals when wiring the drive’s main circuit terminals. Use crimping tools as

specified by the crimp terminal manufacturer. Teco recommends crimp terminals made by NICHIFU for the

insulation cap. The table below matches drives models with crimp terminals and insulation caps. Orders can be

placed with a Teco representative or directly with the Teco sales department. Closed-Loop Crimp Terminal Size

Literal appendix codes11-201/11-301 have no explicit mapping here to E510 model suffixes used elsewhere. Do not substitute or merge recommendations on presumed equivalence. SourceULclaim not validated.

Appendix1 installation and 11-201 crimp-terminal models

Drive Model / Wire Gauge mm2 (AWG) / Terminal / Crimp Terminal / Tool / Insulation — PDF page 373

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Drive Model Wire Gauge mm2 (AWG) Wire Gauge mm2 (AWG) Terminal Crimp Terminal Tool Insulation
2 11-201(series) R/L1, S/L2, T/L3 U/T1, V/T2, W,T3 Screws Model No. Machine No. Model No.
3 11-201-20-2P5-00 2 (14) 2 (14) M3.5 R2-3.5 Nichifu NH 1/9 TIC 2
4 11-201-20-201-00 2 (14) 2 (14) M3.5 R2-3.5 Nichifu NH 1/9 TIC 2
5 11-201-20-202-00 3.5 (12) 3.5 (12) M4 R5.5-4 Nichifu NH 1/9 TIC 3.5
6 11-201-20-203-00 5.5 (10) 5.5 (10) M4 R5.5-4 Nichifu NH 1/9 TIC 5.5
7 11-201-23-202-00 3.5 (12) 3.5 (12) M4 R5.5-4 Nichifu NH 1/9 TIC 3.5
8 11-201-23-205-00 5.5 (10) 5.5 (10) M4 R5.5-4 Nichifu NH 1/9 TIC 5.5
9 11-201-23-208-00 8 (8) 8 (8) M4 R8-4 Nichifu NOP 60 TIC 8
10 11-201-23-210-00 8 (8) 8 (8) M4 R8-4 Nichifu NOP 60 TIC 8
11 11-201-23-215-00 22 (4) 22 (4) M6 R22-6 Nichifu NOP 60/150H TIC 22
12 11-201-23-220-00 22 (4) 22 (4) M6 R22-6 Nichifu NOP 60/150H TIC 22
13 11-201-23-225-00 22 (4) 22 (4) M6 R22-6 Nichifu NOP 60/150H TIC 22
14 11-201-23-230-00 60 (1/0) 60 (1/0) M8 R60-8 Nichifu NH 1/9 TIC 60
15 11-201-23-240-00 60 (1/0) 60 (1/0) M8 R60-8 Nichifu NH 1/9 TIC 60
16 11-201-43-401-00 2 (14) 2 (14) M3.5 R2-3.5 Nichifu NH 1/9 TIC 2
17 11-201-43-402-00 2 (14) 2 (14) M3.5 R2-3.5 Nichifu NH 1/9 TIC 2
18 11-201-43-403-00 2 (14) 2 (14) M4 R2-4 Nichifu NH 1/9 TIC 2
19 11-201-43-405-00 2 (14) 2 (14) M4 R2-4 Nichifu NH 1/9 TIC 2
20 11-201-43-408-00 8 (8) 8 (8) M4 R8-4 Nichifu NOP 60 TIC 8
21 11-201-43-410-00 8 (8) 8 (8) M4 R8-4 Nichifu NOP 60 TIC 8
22 11-201-43-415-00 8 (8) 8 (8) M4 R8-4 Nichifu NOP 60 TIC 8
23 11-201-43-420-00 8 (8) 8 (8) M4 R8-4 Nichifu NOP 60 TIC 8
24 11-201-43-425-00 8 (8) 8 (8) M4 R8-4 Nichifu NOP 60 TIC 8
25 11-201-43-430-00 14 (6) 14 (6) M6 R14-6 Nichifu NOP 60/150H TIC 14
26 11-201-43-440-00 38 (2) 38 (2) M8 R38-8 Nichifu NOP 60/150H TIC 38
27 11-201-43-450-00 38 (2) 38 (2) M8 R38-8 Nichifu NOP 60/150H TIC 38
28 11-201-43-460-00 38 (2) 38 (2) M8 R38-8 Nichifu NOP 60/150H TIC 38
29 11-201-43-475-00 38 (2) 38 (2) M8 R38-8 Nichifu NOP 60/150H TIC 38

Manual — Appendix1 11-301 crimp terminals, field wiring and short-circuit rating — page 374

Manual reference: physical PDF page 374. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 Instructions for UL

AP 1‐4

Closed-Loop Crimp Terminal Size

 Motor Overtemperature Protection

Motor overtemperature protection shall be provided in the end use application.  Field Wiring Terminals

All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the

proper connections that are to be made to each terminal and indicate that copper conductors, rated 75°C are to be

used.  Drive Short-Circuit Rating

This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current

flow will not rise above value. Please see electrical ratings for maximum voltage and table below for current. The MCCB

and breaker protection and fuse ratings (refer to the preceding table) shall be equal to or greater than the short-circuit

tolerance of the power supply being used.

Raster short-circuit-rating table. Columns: Horse Power (Hp), Current (A), Voltage (V). Row1: 1–50 | 5000 | 240/480. Row2: 51–200 | 10000 | 240/480. Values copied from source image; no applicability beyond source section inferred.

Literal appendix codes11-201/11-301 have no explicit mapping here to E510 model suffixes used elsewhere. Do not substitute or merge recommendations on presumed equivalence. SourceULclaim not validated.

Raster short-circuit-rating table retained separately with nine manually bounded header/data cells in raster-table-cell-evidence.json. Source requires end-use motor overtemperature protection and75°C copper conductors; short-circuit prose not an engineering validation.

Appendix1 11-301 crimp terminals, field wiring and short-circuit rating

Drive Model / Wire Gauge mm2 (AWG) / Terminal / Crimp Terminal / Tool / Insulation — PDF page 374

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Drive Model Wire Gauge mm2 (AWG) Wire Gauge mm2 (AWG) Terminal Crimp Terminal Tool Insulation
2 11-301(series) R/L1, S/L2, T/L3 U/T1, V/T2, W,T3 Screws Model No. Machine No. Model No.
3 11-301-21-2P5-30 2 (14) 2 (14) M3.5 R2-3.5 Nichifu NH 1/9 TIC 2
4 11-301-21-201-30 2 (14) 2 (14) M3.5 R2-3.5 Nichifu NH 1/9 TIC 2
5 11-301-21-202-30 3.5 (12) 3.5 (12) M4 R5.5-4 Nichifu NH 1/9 TIC 3.5
6 11-301-21-203-30 5.5 (10) 5.5 (10) M4 R5.5-4 Nichifu NH 1/9 TIC 5.5
7 11-301-43-401-30 2 (14) 2 (14) M3.5 R2-3.5 Nichifu NH 1/9 TIC 2
8 11-301-43-402-30 2 (14) 2 (14) M3.5 R2-3.5 Nichifu NH 1/9 TIC 2
9 11-301-43-403-30 2 (14) 2 (14) M4 R2-4 Nichifu NH 1/9 TIC 2
10 11-301-43-405-30 2 (14) 2 (14) M4 R2-4 Nichifu NH 1/9 TIC 2
11 11-301-43-408-30 8 (8) 8 (8) M4 R8-4 Nichifu NOP 60 TIC 8
12 11-301-43-410-30 8 (8) 8 (8) M4 R8-4 Nichifu NOP 60 TIC 8
13 11-301-43-415-30 8 (8) 8 (8) M4 R8-4 Nichifu NOP 60 TIC 8
14 11-301-43-420-30 8 (8) 8 (8) M4 R8-4 Nichifu NOP 60 TIC 8
15 11-301-43-425-30 8 (8) 8 (8) M4 R8-4 Nichifu NOP 60 TIC 8
16 11-301-43-430-30 14 (6) 14 (6) M6 R14-6 Nichifu NOP 60/150H TIC 14
17 11-301-43-440-30 38 (2) 38 (2) M8 R38-8 Nichifu NOP 60/150H TIC 38
18 11-301-43-450-30 38 (2) 38 (2) M8 R38-8 Nichifu NOP 60/150H TIC 38
19 11-301-43-460-30 38 (2) 38 (2) M8 R38-8 Nichifu NOP 60/150H TIC 38
20 11-301-43-475-30 38 (2) 38 (2) M8 R38-8 Nichifu NOP 60/150H TIC 38

Manual — Appendix1 recommended input fuses for literal 11-201/11-301 codes — page 375

Manual reference: physical PDF page 375. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 Instructions for UL

AP 1‐5

Recommended Input Fuse Selection

Literal appendix codes11-201/11-301 have no explicit mapping here to E510 model suffixes used elsewhere. Do not substitute or merge recommendations on presumed equivalence. SourceULclaim not validated.

Literal lastmodel11-301-43-476-30 differs from374crimp11-301-43-475-30. Preserve both.

Appendix1 recommended input fuses for literal 11-201/11-301 codes

Drive Model 11-201/11-301 / Fuse Type — PDF page 375

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Drive Model 11-201/11-301 Fuse Type Fuse Type
2 Drive Model 11-201/11-301 Manufacturer: Bussmann / Ferraz Shawmut Manufacturer: Bussmann / Ferraz Shawmut
3 Drive Model 11-201/11-301 Model Fuse Ampere Rating
4 11-201-20-2P5-00 Bussmann 20CT 690V / 20A
5 11-201-20-201-00 Bussmann 20CT 690V / 20A
6 11-201-20-202-00 Bussmann 32FE 690V / 32A
7 11-201-20-203-00 Bussmann 50FE 690V / 50A
8 11-201-23-202-00 Bussmann 20CT 690V / 20A
9 11-201-23-205-00 Bussmann50FE 690V / 50A
10 11-201-23-208-00 Bussmann 63FE 690V / 63A
11 11-201-23-210-00 Ferraz Shawmut A50QS100-4 500V / 100A
12 11-201-23-215-00 Ferraz Shawmut A50QS150-4 500V / 150A
13 11-201-23-220-00 Ferraz Shawmut A50QS150-4 500V / 150A
14 11-201-23-225-00 Ferraz Shawmut A50QS200-4 500V / 200A
15 11-201-23-230-00 Ferraz Shawmut A50QS250-4 500V / 250A
16 11-201-23-240-00 Ferraz Shawmut A50QS300-4 500V / 300A
17 11-201-43-401-00 Bussmann 10CT 690V / 10A
18 11-201-43-402-00 Bussmann 16CT 690V / 16A
19 11-201-43-403-00 Bussmann 16CT 690V / 16A
20 11-201-43-405-00 Bussmann 25ET 690V / 25A
21 11-201-43-408-00 Bussmann 40FE 690V / 40A
22 11-201-43-410-00 Bussmann 50FE 690V / 50A
23 11-201-43-415-00 Bussmann 63FE 690V / 63A
24 11-201-43-420-00 Bussmann 80FE 690V / 80A
25 11-201-43-425-00 Ferraz Shawmut A50QS100-4 500V / 100A
26 11-201-43-430-00 Bussmann 120FEE 690V / 120A
27 11-201-43-440-00 Ferraz Shawmut A50QS150-4 500V / 150A
28 11-201-43-450-00 Ferraz Shawmut A50QS200-4 500V / 200A
29 11-201-43-460-00 Ferraz Shawmut A50QS250-4 500V / 250A
30 11-201-43-475-00 Ferraz Shawmut A50QS300-4 500V / 300A
31 11-301-21-2P5-30 Bussmann 16CT 690V / 16A
32 11-301-21-201-30 Bussmann 20CT 690V / 20A
33 11-301-21-202-30 Bussmann 32FE 690V / 32A
34 11-301-21-203-30 Bussmann 50FE 690V / 50A
35 11-301-43-401-30 Bussmann 10CT 690V / 10A
36 11-301-43-402-30 Bussmann 16CT 690V / 16A
37 11-301-43-403-30 Bussmann 16CT 690V / 16A
38 11-301-43-405-30 Bussmann 20CT 690V / 20A
39 11-301-43-408-30 Bussmann 32FE 690V / 32A
40 11-301-43-410-30 Bussmann 40FE 690V / 40A
41 11-301-43-415-30 Bussmann 63FE 690V / 63A
42 11-301-43-420-30 Bussmann 71FE 690V / 71A
43 11-301-43-425-30 Bussmann 100FEa 690V / 100A
44 11-301-43-430-30 Bussmann 100FEa 690V / 100A
45 11-301-43-440-30 Ferraz Shawmut A50QS125-4 500V / 125A
46 11-301-43-450-30 Ferraz Shawmut A50QS175-4 500V / 175A
47 11-301-43-460-30 Ferraz Shawmut A50QS200-4 500V / 200A
48 11-301-43-476-30 Ferraz Shawmut A50QS300-4 500V / 300A

Manual — Modbus network, termination and CN6 pin definitions — page 386

Manual reference: physical PDF page 386. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-1

Appendix 3 Modbus Protocol Description

Communication Connection and Data Frame The inverter can communicate with a PC or PLC via RS485 or RS232 using the Modbus RTU or Modbus ACSII protocol. The maximum frame length is 80 bytes.

Network Connection

** Terminate the communications line with a (120 ohm, 1/4 watt) resistor at both ends.**

CN6 Pin out:

For RS-485 communication use pin 1 or pin 3 for S (+) and pin 2 or pin 6 for S (-).

Network figure: Controller(PLC/HMIorPC),RS-485Interface; four SlaveE510s nodes labelled Address01,Address02,Address03,AddressFE. Each CN6 shows S(+)left,S(-)right. Two horizontal bus lines connect illustrated terminals; endpoints each label120Ω1/4w. Source prose requires120ohm1/4w termination bothends. No additional wiring inferred.

CN6 jack outline pin labels left-to-right8,7,6,5,4,3,2,1; source orientation as drawn, not a generic connector orientation.

Modbus network, termination and CN6 pin definitions

PIN / Signal — PDF page 386

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 PIN Signal PIN Signal
2 1 RS485 Data+ signal 5 Tx signal
3 2 RS485 Data- signal 6 RS485 Data- signal
4 3 RS485 Data+ signal 7 VCC of isolated 5V power supply
5 4 Reserved 8 GND of isolated 5V power supply

Manual — ASCII/RTU framing, response timing and node addresses — page 387

Manual reference: physical PDF page 387. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-2

Data Format Frame

FOR ASCII MODE

➢ FOR RTU MODE

Master (PLC etc.) sends request to follower (inverter), and the follower sends a response to

the master (PC, PLC). The data received is illustrated here.

**The inverter response time is 10ms.

➢ Node Address

00H:Broadcast to all the drivers

01H:to the No. 01 inverter

0FH:to the No.15 inverter

10H:to the No.16 inverter and so on...., max to No.31 (1FH)

RTU frame top-to-bottom: SLAVEAddress,FunctionCode,DATA,CRCCHECK,SignalInterval. No bit lengths printed in this stack.

ASCII/RTU framing, response timing and node addresses

STX(3AH) / Start Bit = 3AH — PDF page 387

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 STX(3AH) Start Bit = 3AH
2 Address Hi Communication Address(Station): 2-digit ASCII Code
3 Address Lo Communication Address(Station): 2-digit ASCII Code
4 Function Hi Function Code (command): 2-digit ASCII Code
5 Function Lo Function Code (command): 2-digit ASCII Code
6 Command Start Address Command Start byte: 4-digit ASCII Code
7 Command Start Address Command Start byte: 4-digit ASCII Code
8 Command Start Address Command Start byte: 4-digit ASCII Code
9 Command Start Address Command Start byte: 4-digit ASCII Code
10 Data length The length of the command: 4-digit ASCII Code
11 Data length The length of the command: 4-digit ASCII Code
12 Data length The length of the command: 4-digit ASCII Code
13 Data length The length of the command: 4-digit ASCII Code
14 LRC Check Hi LRC Check Code: 2-digit ASCII Code
15 LRC Check Lo LRC Check Code: 2-digit ASCII Code
16 END Hi End Byte: END Hi=CR(0DH), END Li = LF(0AH)
17 END Lo End Byte: END Hi=CR(0DH), END Li = LF(0AH)

Manual — Function codes and source checksum calculation — page 388

Manual reference: physical PDF page 388. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-3

➢ Function Code 03H:Read the register contents 06H:Write a WORD to register 08H:Loop test 10H:Write several data to register (complex number register write)

➢ Checksum Calculation

LRC

CRC

CRC Check: CRC code covers the content from node address to DATA. Please calculate it according to the following methods. (1) Load a 16-bit register with FFFF hex (all1’s). Call this CRC register. (2) Exclusive OR the first 8-bit byte of the message, the low-order byte of the 16-bit CRC register, putting the result in the CRC register. (3) Shift the CRC register one bit to the right (toward the LSB), Zero-filling the MSB, Extract and examines the LSB. (4) (If the LSB was 0): Repeat Steps (3) (another shift) (If the LSB was 1): Exclusive OR the CRC register with the polynomial value A001 hex (1010 0000 0000 0001), putting the result in CRC register. (5) Repeat Steps (3) and (4) until 8 shifts been performed. When this is done, a complete 8-bit byte will be processed. (6) Repeat Steps (2) through (5) for next 8-bit byte of the message, Continue doing this until all bytes have been processed. The final content in the CRC register is the CRC value. When sending the CRC value, the Low-order byte should be sent firstly, then the High-order byte. For example, CRC value: 1241 Hex, the high-order byte should be set to 41hex and low-order byte 12hex.

LRC worked layout: ADDRESS01H;FUNCTION03H;COMMAND01Hthen00H;plus DATALENGTH0AH;sum0FH,2’scomplement;ChecksumF1H;CS(H)=46H(ASCII),CS(L)=31H(ASCII). Source example copied without protocol validity inference.

Manual — Source CRC program and exception-code examples — page 389

Manual reference: physical PDF page 389. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-4

➢ CRC calculate program

UWORD ch_sum ( UBYTE long , UBYTE *rxdbuff ) {

BYTE i = 0;

UWORD wkg = 0xFFFF;

while ( long-- ) {

wkg ^= rxdbuff++;

for ( i = 0 ; i < 8; i++ ) {

if ( wkg & 0x0001 ) {

wkg = ( wkg >> 1 ) ^ 0xa001;

}

else {

wkg = wkg >> 1;

return( wkg );

➢ Error Code

ASCII Mode RTU Mode

During a communication error the drive will response with an Exception Code and send a message back to the main system consisting of a Function Code that is “ANDED (and 80h)” with 80 Hex.

CRC code retained as historical literal text with line boundaries in prose-line-evidence.json; not executed, compiled or repaired.

Source CRC program and exception-code examples

STX / ‘:’ — PDF page 389

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 STX ‘:’
2 Address ‘0’
3 Address ‘1’
4 Function ‘8’
5 Function ‘6’
6 Exception code ‘5’
7 Exception code ‘1’
8 LRC Check ‘2’
9 LRC Check ‘8’
10 END ‘CR’
11 END ‘LF’

SLAVE Address / 02H — PDF page 389

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 SLAVE Address SLAVE Address 02H
2 Function Function 83H
3 Exception code Exception code 52H
4 CRC-16 High C0H
5 CRC-16 Low CDH

Error Code / Content — PDF page 389

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Error Code Content
2 01 Function code error
3 02 Register number error
4 03 DATA setting error
5 04 Register number is over 32

Manual — Read/write command registers and bit mappings — page 390

Manual reference: physical PDF page 390. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-5

➢ Register and Data Format

Command Data (Read/Write)

Note : Write in zero for Not used BIT, do not write in data for the reserved register.

Dotted bit row boundaries at147.96+16.5*i explicitly recovered before first extraction. VerticalOperationSignalnativeboxmisplacement corrected with full raw/bounds retained; only2501Hbits0–F receive sharedlabel.

Read/write command registers and bit mappings

Register No. / Bit / Content — PDF page 390

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Register No. ⟦blank source cell⟧ Bit Content Bit Content Bit Content
2 2500H ⟦blank source cell⟧ Reserved Reserved Reserved
3 2501H ⟦blank source cell⟧ Operation Signal 0 Operation Command 1 : Run 0 : Stop
4 2501H ⟦blank source cell⟧ Operation Signal 1 Reverse Command 1 : Reverse 0 : Forward
5 2501H ⟦blank source cell⟧ Operation Signal 2 External Fault 1 : Fault
6 2501H ⟦blank source cell⟧ Operation Signal 3 Fault Reset 1 : Reset
7 2501H ⟦blank source cell⟧ Operation Signal 4 Reserved
8 2501H ⟦blank source cell⟧ Operation Signal 5 Reserved
9 2501H ⟦blank source cell⟧ Operation Signal 6 Multi-function Comm S1 1 :“ON”
10 2501H ⟦blank source cell⟧ Operation Signal 7 Multi-function Comm S2 1 :“ON”
11 2501H ⟦blank source cell⟧ Operation Signal 8 Multi-function Comm S3 1 :“ON”
12 2501H ⟦blank source cell⟧ Operation Signal 9 Multi-function Comm S4 1 :“ON”
13 2501H ⟦blank source cell⟧ Operation Signal A Multi-function Comm S5 1 :“ON”
14 2501H ⟦blank source cell⟧ Operation Signal B Multi-function Comm S6 1 :“ON”
15 2501H ⟦blank source cell⟧ Operation Signal C Reserved
16 2501H ⟦blank source cell⟧ Operation Signal D Reserved
17 2501H ⟦blank source cell⟧ Operation Signal E Inverter mode 1 : “ON”
18 2501H ⟦blank source cell⟧ Operation Signal F Reserved
19 2502H ⟦blank source cell⟧ ⟦blank source cell⟧ *Frequency Command (Unit: 0.01Hz) *Frequency Command (Unit: 0.01Hz)
20 2503H ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved
21 2504H ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved
22 2505H ⟦blank source cell⟧ ⟦blank source cell⟧ AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V)
23 2506H ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved
24 2507H ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved
25 2508H ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved
26 2509H ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved
27 250AH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved
28 250BH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved
29 250CH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved
30 250DH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved
31 250EH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved
32 250FH ⟦blank source cell⟧ ⟦blank source cell⟧ Static Auto Tune 1:”ON” Static Auto Tune 1:”ON”
33 2510H ⟦blank source cell⟧ ⟦blank source cell⟧ G12-00 H-WORD G12-00 H-WORD
34 2511H ⟦blank source cell⟧ ⟦blank source cell⟧ G12-00 L-WORD G12-00 L-WORD

Manual — Read-only status and fault-code register mapping — page 391

Manual reference: physical PDF page 391. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-6

➢ Monitor Data (Read-only)

2521Herror-description block continues391→392;392top24–30 and55–61 retain blankregistercell, with explicit preceding2521Hcontext. Sharedphysical cells repeat exactgeometry, not separate facts.

Read-only status and fault-code register mapping

Register No. / / Bit Content — PDF page 391

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Register No. ⟦blank source cell⟧ Bit Content Bit Content Bit Content Bit Content Bit Content
2 2520H ⟦blank source cell⟧ State Signal 0 Operation 1 : Run 0 : Stop Operation 1 : Run 0 : Stop Operation 1 : Run 0 : Stop
3 2520H ⟦blank source cell⟧ State Signal 1 Direction 1 : Reverse 0 : Forward Direction 1 : Reverse 0 : Forward Direction 1 : Reverse 0 : Forward
4 2520H ⟦blank source cell⟧ State Signal 2 Inverter ready 1 : ready 0 : unready Inverter ready 1 : ready 0 : unready Inverter ready 1 : ready 0 : unready
5 2520H ⟦blank source cell⟧ State Signal 3 Fault 1 : Abnormal Fault 1 : Abnormal Fault 1 : Abnormal
6 2520H ⟦blank source cell⟧ State Signal 4 Warning 1 :“ON” Warning 1 :“ON” Warning 1 :“ON”
7 2520H ⟦blank source cell⟧ State Signal 5 Zero Speed 1 :“ON” Zero Speed 1 :“ON” Zero Speed 1 :“ON”
8 2520H ⟦blank source cell⟧ State Signal 6 Is440V 1 :“ON” Is440V 1 :“ON” Is440V 1 :“ON”
9 2520H ⟦blank source cell⟧ State Signal 7 Frequency Agree 1 :“ON” Frequency Agree 1 :“ON” Frequency Agree 1 :“ON”
10 2520H ⟦blank source cell⟧ State Signal 8 Set Frequency Agree 1 :“ON” Set Frequency Agree 1 :“ON” Set Frequency Agree 1 :“ON”
11 2520H ⟦blank source cell⟧ State Signal 9 Frequency Detection 1 1 :“ON” Frequency Detection 1 1 :“ON” Frequency Detection 1 1 :“ON”
12 2520H ⟦blank source cell⟧ State Signal A Frequency Detection 2 1 :“ON” Frequency Detection 2 1 :“ON” Frequency Detection 2 1 :“ON”
13 2520H ⟦blank source cell⟧ State Signal B Under Voltage 1 :“ON” Under Voltage 1 :“ON” Under Voltage 1 :“ON”
14 2520H ⟦blank source cell⟧ State Signal C Baseblock 1 :“ON” Baseblock 1 :“ON” Baseblock 1 :“ON”
15 2520H ⟦blank source cell⟧ State Signal D Freq Ref. not from Comm. 1 :“ON” Freq Ref. not from Comm. 1 :“ON” Freq Ref. not from Comm. 1 :“ON”
16 2520H ⟦blank source cell⟧ State Signal E Seq. not from Comm. 1 :“ON” Seq. not from Comm. 1 :“ON” Seq. not from Comm. 1 :“ON”
17 2520H ⟦blank source cell⟧ State Signal F Reserved 1 :“ON” Reserved 1 :“ON” Reserved 1 :“ON”
18 2521H ⟦blank source cell⟧ Error Description 0 Reserved 31 Reserved
19 2521H ⟦blank source cell⟧ Error Description 1 UV 32 Reserved
20 2521H ⟦blank source cell⟧ Error Description 2 OC 33 Reserved
21 2521H ⟦blank source cell⟧ Error Description 3 OV 34 Reserved
22 2521H ⟦blank source cell⟧ Error Description 4 OH1 35 Reserved
23 2521H ⟦blank source cell⟧ Error Description 5 OL1 36 Reserved
24 2521H ⟦blank source cell⟧ Error Description 6 OL2 37 Reserved
25 2521H ⟦blank source cell⟧ Error Description 7 OT 38 CF07
26 2521H ⟦blank source cell⟧ Error Description 8 Reserved 39 Reserved
27 2521H ⟦blank source cell⟧ Error Description 9 SC 40 Reserved
28 2521H ⟦blank source cell⟧ Error Description 10 Ground OC 41 Reserved
29 2521H ⟦blank source cell⟧ Error Description 11 Reserved 42 LPBFT(Low Pressure Fault)
30 2521H ⟦blank source cell⟧ Error Description 12 Input Phase Loss 43 OPBFT(High Pressure Fault)
31 2521H ⟦blank source cell⟧ Error Description 13 Output Phase Loss 44 FBLSS(PID Feedback Signal Loss)
32 2521H ⟦blank source cell⟧ Error Description 14 Reserved 45 Reserved
33 2521H ⟦blank source cell⟧ Error Description 15 Reserved 46 OH4
34 2521H ⟦blank source cell⟧ Error Description 16 Reserved 47 Reserved
35 2521H ⟦blank source cell⟧ Error Description 17 EF1(External Terminal S1 fault) 48 Reserved
36 2521H ⟦blank source cell⟧ Error Description 18 EF2(External Terminal S2 fault) 49 MtrSw (DI Motor Switch Fault)
37 2521H ⟦blank source cell⟧ Error Description 19 EF3(External Terminal S3 fault) 50 OC_A
38 2521H ⟦blank source cell⟧ Error Description 20 EF4(External Terminal S4 fault) 51 OC_D
39 2521H ⟦blank source cell⟧ Error Description 21 EF5(External Terminal S5 fault) 52 OC_C
40 2521H ⟦blank source cell⟧ Error Description 22 EF6(External Terminal S6 fault) 53 Reserved
41 2521H ⟦blank source cell⟧ Error Description 23 Reserved 54 CF_08

Manual — Continuation2521H, DI2522H and warning2528H mapping — page 392

Manual reference: physical PDF page 392. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-7

2521Herror-description block continues391→392;392top24–30 and55–61 retain blankregistercell, with explicit preceding2521Hcontext. Sharedphysical cells repeat exactgeometry, not separate facts.

2528Hwarning-description block continues392→393;393topfourpairedcode/descriptioncolumns retain blankregisterlabel. Code78absent;notinvented.

Continuation2521H, DI2522H and warning2528H mapping

Register No. / / Bit Content — PDF page 392

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows) Physical column 11 (source headings retained in rows)
1 Register No. ⟦blank source cell⟧ Bit Content Bit Content Bit Content Bit Content Bit Content Bit Content Bit Content Bit Content Bit Content
2 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 24 Reserved Reserved Reserved 55 STO2 STO2 STO2
3 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 25 PID Feedback Error PID Feedback Error PID Feedback Error 56 STO3 STO3 STO3
4 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 26 Keypad Removed Keypad Removed Keypad Removed 57 PO PO PO
5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 27 Reserved Reserved Reserved 58 PF PF PF
6 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 28 CE CE CE 59 TOL(External Overload) TOL(External Overload) TOL(External Overload)
7 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 29 STO1 STO1 STO1 60 Reserved Reserved Reserved
8 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 30 Reserved Reserved Reserved 61 Reserved Reserved Reserved
9 2522H ⟦blank source cell⟧ DI State 0 Terminal S1 Terminal S1 Terminal S1 Terminal S1 Terminal S1 Terminal S1 Terminal S1
10 2522H ⟦blank source cell⟧ DI State 1 Terminal S2 Terminal S2 Terminal S2 Terminal S2 Terminal S2 Terminal S2 Terminal S2
11 2522H ⟦blank source cell⟧ DI State 2 Terminal S3 Terminal S3 Terminal S3 Terminal S3 Terminal S3 Terminal S3 Terminal S3
12 2522H ⟦blank source cell⟧ DI State 3 Terminal S4 Terminal S4 Terminal S4 Terminal S4 Terminal S4 Terminal S4 Terminal S4
13 2522H ⟦blank source cell⟧ DI State 4 Terminal S5 Terminal S5 Terminal S5 Terminal S5 Terminal S5 Terminal S5 Terminal S5
14 2522H ⟦blank source cell⟧ DI State 5 Terminal S6 Terminal S6 Terminal S6 Terminal S6 Terminal S6 Terminal S6 Terminal S6
15 2522H ⟦blank source cell⟧ DI State 6 Reserved Reserved Reserved Reserved Reserved Reserved Reserved
16 2522H ⟦blank source cell⟧ DI State 7 Reserved Reserved Reserved Reserved Reserved Reserved Reserved
17 2522H ⟦blank source cell⟧ DI State 8 Reserved Reserved Reserved Reserved Reserved Reserved Reserved
18 2522H ⟦blank source cell⟧ DI State 9 Reserved Reserved Reserved Reserved Reserved Reserved Reserved
19 2522H ⟦blank source cell⟧ DI State A Reserved Reserved Reserved Reserved Reserved Reserved Reserved
20 2522H ⟦blank source cell⟧ DI State B Reserved Reserved Reserved Reserved Reserved Reserved Reserved
21 2522H ⟦blank source cell⟧ DI State C Reserved Reserved Reserved Reserved Reserved Reserved Reserved
22 2522H ⟦blank source cell⟧ DI State D Reserved Reserved Reserved Reserved Reserved Reserved Reserved
23 2522H ⟦blank source cell⟧ DI State E Reserved Reserved Reserved Reserved Reserved Reserved Reserved
24 2522H ⟦blank source cell⟧ DI State F Reserved Reserved Reserved Reserved Reserved Reserved Reserved
25 2523H ⟦blank source cell⟧ ⟦blank source cell⟧ Frequency command (0.01Hz) Frequency command (0.01Hz) Frequency command (0.01Hz) Frequency command (0.01Hz) Frequency command (0.01Hz) Frequency command (0.01Hz) Frequency command (0.01Hz) Frequency command (0.01Hz)
26 2524H ⟦blank source cell⟧ ⟦blank source cell⟧ Output frequency (0.01Hz) Output frequency (0.01Hz) Output frequency (0.01Hz) Output frequency (0.01Hz) Output frequency (0.01Hz) Output frequency (0.01Hz) Output frequency (0.01Hz) Output frequency (0.01Hz)
27 2525H ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved
28 2526H ⟦blank source cell⟧ ⟦blank source cell⟧ DC voltage command (0.1V) DC voltage command (0.1V) DC voltage command (0.1V) DC voltage command (0.1V) DC voltage command (0.1V) DC voltage command (0.1V) DC voltage command (0.1V) DC voltage command (0.1V)
29 2527H ⟦blank source cell⟧ ⟦blank source cell⟧ Output current (0.1A) Output current (0.1A) Output current (0.1A) Output current (0.1A) Output current (0.1A) Output current (0.1A) Output current (0.1A) Output current (0.1A)
30 2528H ⟦blank source cell⟧ Warning Description 0 No alarm 20 EF4 40 EF9 60 Reserved
31 2528H ⟦blank source cell⟧ Warning Description 1 OV 21 EF5 41 Reserved 61 RETRY
32 2528H ⟦blank source cell⟧ Warning Description 2 UV 22 EF6 42 Reserved 62 Reserved
33 2528H ⟦blank source cell⟧ Warning Description 3 OL2 23 Reserved 43 RDP 63 Reserved
34 2528H ⟦blank source cell⟧ Warning Description 4 Reserved 24 Reserved 44 Reserved 64 Reserved
35 2528H ⟦blank source cell⟧ Warning Description 5 OH3 25 Reserved 45 OL1 65 OH1
36 2528H ⟦blank source cell⟧ Warning Description 6 OT 26 Reserved 46 Reserved 66 FIRE
37 2528H ⟦blank source cell⟧ Warning Description 7 Reserved 27 Reserved 47 Reserved 67 ES
38 2528H ⟦blank source cell⟧ Warning Description 8 Reserved 28 Reserved 48 COPUP 68 STP1
39 2528H ⟦blank source cell⟧ Warning Description 9 Reserved 29 Reserved 49 BB1 69 BDERR
40 2528H ⟦blank source cell⟧ Warning Description 10 Reserved 30 RDE 50 BB2 70 EPERR

Manual — Continuation2528H warnings and monitor registers — page 393

Manual reference: physical PDF page 393. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Fresh table read confirms 77/LOC then79/C0000, with78 absent. 2529H has no bit map;2536H/2537H/253BH/253CH are named values without explicit units/scales. PDF392 input-bit map2522H and PDF109 display12-05 do not establish2529H output-bit mapping.

AP 3-8

Note : Do not write in data for the reserved register.

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Digital-output2529H bit definitions and2536/2537/253B/253C value units/scales absent.

2528Hwarning-description block continues392→393;393topfourpairedcode/descriptioncolumns retain blankregisterlabel. Code78absent;notinvented.

Continuation2528H warnings and monitor registers

Register No. / / Bit Content — PDF page 393

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows) Physical column 11 (source headings retained in rows)
1 Register No. ⟦blank source cell⟧ Bit Content Bit Content Bit Content Bit Content Bit Content Bit Content Bit Content Bit Content Bit Content
2 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 11 Reserved 31 WRE 51 BB3 71 Reserved
3 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 12 Reserved 32 FB 52 BB4 72 Reserved
4 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 13 CE 33 VRYE 53 BB5 73 STP0
5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 14 Reserved 34 SE01 54 BB6 74 Reserved
6 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 15 Reserved 35 SE02 55 Reserved 75 STP2
7 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 16 EF0 36 SE03 56 Reserved 76 RUNER
8 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 17 EF1 37 Reserved 57 LOPb 77 LOC
9 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 18 EF2 38 SE05 58 HIPb 79 C0000
10 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 19 EF3 39 HPERR 59 Reserved 80 INIT
11 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 81 FBLSS
12 2529H ⟦blank source cell⟧ ⟦blank source cell⟧ Digital Output State Digital Output State Digital Output State Digital Output State Digital Output State Digital Output State Digital Output State Digital Output State
13 252AH ⟦blank source cell⟧ ⟦blank source cell⟧ AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V)
14 252BH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved
15 252CH ⟦blank source cell⟧ ⟦blank source cell⟧ AI 1 Input (0.1%) AI 1 Input (0.1%) AI 1 Input (0.1%) AI 1 Input (0.1%) AI 1 Input (0.1%) AI 1 Input (0.1%) AI 1 Input (0.1%) AI 1 Input (0.1%)
16 252DH ⟦blank source cell⟧ ⟦blank source cell⟧ AI 2 Input (0.1%) AI 2 Input (0.1%) AI 2 Input (0.1%) AI 2 Input (0.1%) AI 2 Input (0.1%) AI 2 Input (0.1%) AI 2 Input (0.1%) AI 2 Input (0.1%)
17 252EH ⟦blank source cell⟧ ⟦blank source cell⟧ Keypad analog input(1000 / 5V) Keypad analog input(1000 / 5V) Keypad analog input(1000 / 5V) Keypad analog input(1000 / 5V) Keypad analog input(1000 / 5V) Keypad analog input(1000 / 5V) Keypad analog input(1000 / 5V) Keypad analog input(1000 / 5V)
18 252FH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved
19 2531H ⟦blank source cell⟧ ⟦blank source cell⟧ AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V) AO1 (0.00V ~ 10.00V)
20 2533H ⟦blank source cell⟧ ⟦blank source cell⟧ Heat Sink Temperature (℃) Heat Sink Temperature (℃) Heat Sink Temperature (℃) Heat Sink Temperature (℃) Heat Sink Temperature (℃) Heat Sink Temperature (℃) Heat Sink Temperature (℃) Heat Sink Temperature (℃)
21 2534H ⟦blank source cell⟧ ⟦blank source cell⟧ Output Power (kw) Output Power (kw) Output Power (kw) Output Power (kw) Output Power (kw) Output Power (kw) Output Power (kw) Output Power (kw)
22 2536H ⟦blank source cell⟧ ⟦blank source cell⟧ OL1 Value OL1 Value OL1 Value OL1 Value OL1 Value OL1 Value OL1 Value OL1 Value
23 2537H ⟦blank source cell⟧ ⟦blank source cell⟧ OL2 Value OL2 Value OL2 Value OL2 Value OL2 Value OL2 Value OL2 Value OL2 Value
24 253BH ⟦blank source cell⟧ ⟦blank source cell⟧ IPL Value IPL Value IPL Value IPL Value IPL Value IPL Value IPL Value IPL Value
25 253CH ⟦blank source cell⟧ ⟦blank source cell⟧ OPL Value OPL Value OPL Value OPL Value OPL Value OPL Value OPL Value OPL Value

Manual — 03H read-register ASCII/RTU command and responses — page 394

Manual reference: physical PDF page 394. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-9

➢ Read Holding Register [03H] Read consecutive holding registers. The address of the first holding register is specified in the protocol Example: Read frequency command from the inverter with node address 1.

ASCII Mode

Command Message Response Message (Normal) Response Message (Error)

+

RTU Mode

03H read-register ASCII/RTU command and responses ASCII Command Message; source bytes and placeholders literal, not validated protocol messages.

03H read-register ASCII/RTU command and responses ASCII Response Message (Normal); source bytes and placeholders literal, not validated protocol messages.

03H read-register ASCII/RTU command and responses ASCII Response Message (Error); source bytes and placeholders literal, not validated protocol messages.

03H read-register ASCII/RTU command and responses RTU Command Message; source bytes and placeholders literal, not validated protocol messages.

03H read-register ASCII/RTU command and responses RTU Response Message (Normal); source bytes and placeholders literal, not validated protocol messages.

03H read-register ASCII/RTU command and responses RTU Response Message (Error); source bytes and placeholders literal, not validated protocol messages.

ASCII Command Message — PDF page 394

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H Node Address
3 31H Node Address
4 30H Function
5 33H Function
6 30H Starting Register
7 43H Starting Register
8 31H Starting Register
9 30H Starting Register
10 30H Number of Registers
11 30H Number of Registers
12 30H Number of Registers
13 31H Number of Registers
14 44H LRC CHECK
15 46H LRC CHECK
16 0DH END
17 0AH END

ASCII Response Message (Normal) — PDF page 394

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H Node Address
3 31H Node Address
4 30H Function
5 33H Function
6 30H Data Length
7 32H Data Length
8 31H Initial Save Register
9 37H Initial Save Register
10 37H Initial Save Register
11 30H Initial Save Register
12 37H LRC CHECK
13 33H LRC CHECK
14 0DH END
15 0AH END

ASCII Response Message (Error) — PDF page 394

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H Node Address
3 31H Node Address
4 38H Function
5 33H Function
6 30H Exception code
7 34H Exception code
8 34H LRC CHECK
9 30H LRC CHECK
10 0DH END
11 0AH END

RTU Command Message — PDF page 394

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Node Address Node Address 01 H
2 Function Function 03H
3 Starting Register High 0CH
4 Starting Register Low 10H
5 Number of Registers High 00H
6 Number of Registers Low 01H
7 CRC-16 High 86H
8 CRC-16 Low 9FH

RTU Response Message (Normal) — PDF page 394

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Node Address Node Address 01H
2 Function Function 03H
3 DATA Length DATA Length 02H
4 Initial Save Register High 17H
5 Initial Save Register Low 70H
6 CRC-16 High B6H
7 CRC-16 Low 50H

RTU Response Message (Error) — PDF page 394

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Node Address Node Address 01H
2 Function Function 83H
3 Exception Code Exception Code 04H
4 CRC-16 High 40H
5 CRC-16 Low F3H

Manual — 08H loopback ASCII/RTU command and responses — page 395

Manual reference: physical PDF page 395. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-10

➢ Loop back test [08H] Check the communication between the master and the follower (inverter). The data used can be arbitrary.

ASCII Mode

Command Message Response Message (Normal) Response Message (Error)

RTU Mode

08H loopback ASCII/RTU command and responses ASCII Command Message; source bytes and placeholders literal, not validated protocol messages.

08H loopback ASCII/RTU command and responses ASCII Response Message (Normal); source bytes and placeholders literal, not validated protocol messages.

08H loopback ASCII/RTU command and responses ASCII Response Message (Error); source bytes and placeholders literal, not validated protocol messages.

08H loopback ASCII/RTU command and responses RTU Command Message; source bytes and placeholders literal, not validated protocol messages.

08H loopback ASCII/RTU command and responses RTU Response Message (Normal); source bytes and placeholders literal, not validated protocol messages.

08H loopback ASCII/RTU command and responses RTU Response Message (Error); source bytes and placeholders literal, not validated protocol messages.

ASCII Command Message — PDF page 395

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H Node Address
3 31H Node Address
4 30H Function
5 38H Function
6 30H Test Code
7 30H Test Code
8 30H Test Code
9 30H Test Code
10 41H DATA
11 35H DATA
12 33H DATA
13 37H DATA
14 31H LRC CHECK
15 42H LRC CHECK
16 0DH END
17 0AH END

ASCII Response Message (Normal) — PDF page 395

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H Node Address
3 31H Node Address
4 30H Function
5 38H Function
6 30H Test Code
7 30H Test Code
8 30H Test Code
9 30H Test Code
10 41H DATA
11 35H DATA
12 33H DATA
13 37H DATA
14 31H LRC CHECK
15 42H LRC CHECK
16 0DH 0AH END

ASCII Response Message (Error) — PDF page 395

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H Node Address
3 31H Node Address
4 38H Function
5 38H Function
6 30H Exception code
7 33H Exception code
8 30H LRC CHECK
9 36H LRC CHECK
10 0DH END
11 0AH END

RTU Command Message — PDF page 395

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Node Address Node Address 01 H
2 Function Function 08H
3 Test Code High 00H
4 Test Code Low 00H
5 Number of Registers High A5H
6 Number of Registers Low 37H
7 CRC-16 High DAH
8 CRC-16 Low 8DH

RTU Response Message (Normal) — PDF page 395

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Node Address Node Address 01H
2 Function Function 08H
3 Test Code High 00H
4 Test Code Low 00H
5 Number of Registers High A5H
6 Number of Registers Low 37H
7 CRC-16 High DAH
8 CRC-16 Low 8DH

RTU Response Message (Error) — PDF page 395

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Node Address Node Address 01H
2 Function Function 88H
3 Exception code Exception code 03H
4 CRC-16 High 06H
5 CRC-16 Low 01H

Manual — 06H single-write ASCII/RTU source examples — page 396

Manual reference: physical PDF page 396. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Normal RTU response physically prints Exception code in Start No High value cell; command prints25H. ASCII example is a separate encoding. Preserve both, do not repair missing normal-response byte from the command.

AP 3-11

➢ Write Single Holding Register [06H] Write single holding register. The register address of the holding register is specified in the message. Example: Write a 60.00Hz frequency command to node address 1.

ASCII Mode

Command Message esponse Message (Normal) Response Message (Error)

RTU Mode

Command Message Response Message (Normal) Response Message (Error)

Function

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: NormalRTU responseStartNoHigh value replaced in source by Exception code; missing byte not inferred.

06H single-write ASCII/RTU source examples ASCII Command Message; source bytes and placeholders literal, not validated protocol messages.

06H single-write ASCII/RTU source examples ASCII Response Message (Normal); source bytes and placeholders literal, not validated protocol messages.

06H single-write ASCII/RTU source examples ASCII Response Message (Error); source bytes and placeholders literal, not validated protocol messages.

06H single-write ASCII/RTU source examples RTU Command Message; source bytes and placeholders literal, not validated protocol messages.

06H single-write ASCII/RTU source examples RTU Response Message (Normal); source bytes and placeholders literal, not validated protocol messages.

06H single-write ASCII/RTU source examples RTU Response Message (Error); source bytes and placeholders literal, not validated protocol messages.

ASCII Command Message — PDF page 396

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H Node Address
3 31H Node Address
4 30H Function
5 36H Function
6 32H Starting Register
7 35H Starting Register
8 30H Starting Register
9 32H Starting Register
10 31H DATA
11 37H DATA
12 37H DATA
13 30H DATA
14 34H LRC CHECK
15 42H LRC CHECK
16 0DH END
17 0AH END

ASCII Response Message (Normal) — PDF page 396

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H Node Address
3 31H Node Address
4 30H Function
5 36H Function
6 32H Starting Register
7 35H Starting Register
8 30H Starting Register
9 32H Starting Register
10 31H DATA
11 37H DATA
12 37H DATA
13 30H DATA
14 34H LRC CHECK
15 42H LRC CHECK
16 0DH 0AH END

ASCII Response Message (Error) — PDF page 396

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H Node Address
3 31H Node Address
4 38H Function
5 36H Function
6 30H Exception code
7 33H Exception code
8 30H LRC CHECK
9 32H LRC CHECK
10 0DH END
11 0AH END

RTU Command Message — PDF page 396

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Node Address Node Address 01 H
2 Function Function 06H
3 Start No High 25H
4 Start No Low 02H
5 Number of Registers High 17H
6 Number of Registers Low 70H
7 CRC-16 High 2DH
8 CRC-16 Low 12H

RTU Response Message (Normal) — PDF page 396

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Node Address Node Address 01H
2 Function Function 06H
3 Start No High Exception code
4 Start No Low 02H
5 Number of Registers High 17H
6 Number of Registers Low 70H
7 CRC-16 High 2DH
8 CRC-16 Low 12H

RTU Response Message (Error) — PDF page 396

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Node Address Node Address 01H
2 Function Function 86H
3 Exception code Exception code 03H
4 CRC-16 High 02H
5 CRC-16 Low 61H

Manual — 10H multiple-write ASCII source example, continued398 — page 397

Manual reference: physical PDF page 397. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-12

➢ Write Multiple Holding Register [10H] Write multiple holding registers. The address of the first holding register is specified in the message. Example: Write a 60.00Hz frequency command to node address 1 and enable FWD run command. ASCII Mode

Command Message Response Message (Normal) Response Message (Error)

397ASCII and398RTU are the same source10H multiple-write example,60.00HzandFWD.397functionbytes31H30Hbothvisible;398normalresponseplaceholdersretained.

10H multiple-write ASCII source example, continued398 ASCII Command Message; source bytes and placeholders literal, not validated protocol messages.

10H multiple-write ASCII source example, continued398 ASCII Response Message (Normal); source bytes and placeholders literal, not validated protocol messages.

10H multiple-write ASCII source example, continued398 ASCII Response Message (Error); source bytes and placeholders literal, not validated protocol messages.

ASCII Command Message — PDF page 397

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H Node Address
3 31H Node Address
4 31H Function
5 30H Function
6 32H Starting Register
7 35H Starting Register
8 30H Starting Register
9 31H Starting Register
10 30H Number of Registers
11 30H Number of Registers
12 30H Number of Registers
13 32H Number of Registers
14 30H Number of DATA
15 34H Number of DATA
16 30H DATA 1
17 30H DATA 1
18 30H DATA 1
19 31H DATA 1
20 31H DATA 2
21 37H DATA 2
22 37H DATA 2
23 30H DATA 2
24 33H LRC CHECK
25 42H LRC CHECK
26 0DH END
27 0AH END

ASCII Response Message (Normal) — PDF page 397

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H Node Address
3 31H Node Address
4 31H Function
5 30H Function
6 32H Starting Register
7 35H Starting Register
8 30H Starting Register
9 31H Starting Register
10 30H Number of Registers
11 30H Number of Registers
12 30H Number of Registers
13 32H Number of Registers
14 43H LRC CHECK
15 37H LRC CHECK
16 0DH END
17 0AH END

ASCII Response Message (Error) — PDF page 397

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H Node Address
3 31H Node Address
4 39H Function
5 30H Function
6 30H Exception code
7 33H Exception code
8 30H LRC CHECK
9 43H LRC CHECK
10 0DH END
11 0AH END

Manual — 10H multiple-write RTU source example continued397 — page 398

Manual reference: physical PDF page 398. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Normal RTU response physically prints Exception code as Starting Register High and High as CRC-16 High value. PDF397 is ASCII counterpart; neither it nor command bytes authorize substituting missing RTU response bytes.

AP 3-13

RTU Mode

Command Message Response Message (Normal) Response Message (Error)

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: NormalRTUresponseStartingRegisterHigh literallyExceptioncode,CRC-16High literallyHigh; missing bytes not inferred.

397ASCII and398RTU are the same source10H multiple-write example,60.00HzandFWD.397functionbytes31H30Hbothvisible;398normalresponseplaceholdersretained.

10H multiple-write RTU source example continued397 RTU Command Message; source bytes and placeholders literal, not validated protocol messages.

10H multiple-write RTU source example continued397 RTU Response Message (Normal); source bytes and placeholders literal, not validated protocol messages.

10H multiple-write RTU source example continued397 RTU Response Message (Error); source bytes and placeholders literal, not validated protocol messages.

RTU Command Message — PDF page 398

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Node Address Node Address 01 H
2 Function Function 10H
3 Starting Register High 25H
4 Starting Register Low 01H
5 Number of Registers High 00H
6 Number of Registers Low 02H
7 Number of DATA Number of DATA 04H
8 DATA 1 High 00H
9 DATA 1 Low 01H
10 DATA 2 High 17H
11 DATA 2 Low 70H
12 CRC-16 High 60H
13 CRC-16 Low 27H

RTU Response Message (Normal) — PDF page 398

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Node Address Node Address 01H
2 Function Function 10H
3 Starting Register High Exception code
4 Starting Register Low 01H
5 Number of Registers High 00H
6 Number of Registers Low 02H
7 CRC-16 High High
8 CRC-16 Low 04H

RTU Response Message (Error) — PDF page 398

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Node Address Node Address 01H
2 Function Function 90H
3 Exception code Exception code 03H
4 CRC-16 High 0CH
5 CRC-16 Low 01H

Manual — Parameter function/register mappings; preserve blanks, dashes and source anomalies — page 399

Manual reference: physical PDF page 399. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-14

Parameter Data

Parameter function/register mappings; preserve blanks, dashes and source anomalies

Function / Register No — PDF page 399

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No Function Register No
2 Group 0 Group 0 Group 1 Group 1 Group 2 Group 2
3 0 – 00 0000H 1 – 00 0100H 2 – 00 0200H
4 0 – 01 0001H 1 – 01 0101H 2 – 01 0201H
5 0 – 02 0002H 1 – 02 0102H 2 – 02 0202H
6 0 – 03 0003H 1 – 03 0103H 2 – 03 0203H
7 0 – 04 0004H 1 – 04 0104H 2 – 04 0204H
8 0 – 05 0005H 1 – 05 0105H 2 – 05 0205H
9 0 – 06 0006H 1 – 06 0106H 2 – 06 0206H
10 0 – 07 0007H 1 – 07 0107H 2 – 07 0207H
11 0 – 08 0008H 1 – 08 0108H 2 – 08 0208H
12 0 – 09 0009H 1 – 09 0109H 2 – 09 0209H
13 0 – 10 000AH 1 – 10 010AH 2 – 10 020AH
14 0 – 11 000BH 1 – 11 010BH 2 – 11 020BH
15 0 – 12 000CH 1 – 12 010CH 2 – 12 020CH
16 0 – 13 000DH 1 – 13 010DH 2 – 13 020DH
17 0 – 14 000EH 1 – 14 010EH 2 – 14 020EH
18 0 – 15 000FH 1 – 15 010FH 2 – 15 020FH
19 0 – 16 0010H 1 – 16 0110H 2 – 16 0210H
20 0 – 17 0011H 1 – 17 0111H 2 – 17 0211H
21 0 – 18 0012H 1 – 18 0112H 2 – 18 0212H
22 0 – 19 0013H 1 – 19 0113H 2 – 19 0213H
23 0 – 20 0014H 1 – 20 0114H 2 – 20 0214H
24 0 – 21 0015H 1 – 21 0115H 2 – 21 0215H
25 0 – 22 0016H 1 – 22 0116H 2 – 22 0216H
26 0 – 23 0017H 1 – 23 0117H 2 – 23 0217H
27 0 – 24 0018H 1 – 24 0118H 2 – 24 0218H
28 0 – 25 0019H 1 – 25 0119H 2 – 25 0219H
29 0 – 26 001AH 1 – 26 011AH 2 – 26 021AH
30 0 – 27 001BH ⟦blank source cell⟧ ⟦blank source cell⟧ 2 – 27 021BH
31 0 – 28 001CH ⟦blank source cell⟧ ⟦blank source cell⟧ 2 – 28 021CH
32 0 – 29 001DH ⟦blank source cell⟧ ⟦blank source cell⟧ 2 – 29 021DH
33 0 – 30 001EH ⟦blank source cell⟧ ⟦blank source cell⟧ 2 – 30 021EH
34 0 – 31 001FH ⟦blank source cell⟧ ⟦blank source cell⟧ 2 – 31 021FH
35 0 – 32 0020H ⟦blank source cell⟧ ⟦blank source cell⟧ 2 – 32 0220H
36 0 – 33 0021H ⟦blank source cell⟧ ⟦blank source cell⟧ 2 – 33 0221H
37 0 – 34 0022H ⟦blank source cell⟧ ⟦blank source cell⟧ 2 – 34 0222H
38 0 – 35 0023H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
39 0 – 36 0024H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter function/register mappings; preserve blanks, dashes and source anomalies — page 400

Manual reference: physical PDF page 400. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Group3 map visibly stops3-34/0322H. PDF92 separately documents03-53 Current Agree Level2; its register address is not supplied here. Unlisted parameter numbers must not be assumed valid solely from the sequence.

AP 3-15

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Group3registermap ends3–34;addresses for3–35..54 from parameter form not present.

Parameter function/register mappings; preserve blanks, dashes and source anomalies

Adjacent source context — repeated to preserve continuation:

Function / Register No — PDF page 400

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No Function Register No
2 Group 3 Group 3 Group 4 Group 4 Group 5 Group 5
3 3 – 00 0300H 4 – 00 0400H 5 – 00 0500H
4 3 – 01 0301H 4 – 01 0401H 5 – 01 0501H
5 3 – 02 0302H 4 – 02 0402H 5 – 02 0502H
6 3 – 03 0303H 4 – 03 0403H 5 – 03 0503H
7 3 – 04 0304H 4 – 04 0404H 5 – 04 0504H
8 3 – 05 0305H 4 – 05 0405H 5 – 05 0505H
9 3 – 06 0306H 4 – 06 0406H 5 – 06 0506H
10 3 – 07 0307H 4 – 07 0407H 5 – 07 0507H
11 3 – 08 0308H 4 – 08 0408H 5 – 08 0508H
12 3 – 09 0309H 4 – 09 0409H 5 – 09 0509H
13 3 – 10 030AH 4 – 10 040AH 5 – 10 050AH
14 3 – 11 030BH 4 – 11 040BH 5 – 11 050BH
15 3 – 12 030CH 4 – 12 040CH 5 – 12 050CH
16 3 – 13 030DH 4 – 13 040DH 5 – 13 050DH
17 3 – 14 030EH 4 – 14 040EH 5 – 14 050EH
18 3 – 15 030FH 4 – 15 040FH 5 – 15 050FH
19 3 – 16 0310H 4 – 16 0410H 5 – 16 0510H
20 3 – 17 0311H 4 – 17 0411H 5 – 17 0511H
21 3 – 18 0312H 4 – 18 0412H 5 – 18 0512H
22 3 – 19 0313H 4 – 19 0413H 5 – 19 0513H
23 3 – 20 0314H 4 – 20 0414H 5 – 20 0514H
24 3 – 21 0315H 4 – 21 0415H 5 – 21 0515H
25 3 – 22 0316H 4 – 22 0416H 5 – 22 0516H
26 3 – 23 0317H ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 23 0517H
27 3 – 24 0318H ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 24 0518H
28 3 – 25 0319H ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 25 0519H
29 3 – 26 031AH ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 26 051AH
30 3 – 27 031BH ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 27 051BH
31 3 – 28 031CH ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 28 051CH
32 3 – 29 031DH ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 29 051DH
33 3 – 30 031EH ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 30 051EH
34 3 – 31 031FH ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 31 051FH
35 3 – 32 0320H ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 32 0520H
36 3 – 33 0321H ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 33 0521H
37 3 – 34 0322H ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 34 0522H
38 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 35 0523H
39 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 36 0524H
40 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 37 0525H
41 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 38 0526H
42 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 39 0527H
43 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 40 0528H
44 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 41 0529H
45 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 42 052AH
46 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 43 052BH
47 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 44 052CH
48 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 45 052DH
49 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 46 052EH
50 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 47 052FH

Manual — Parameter function/register mappings; preserve blanks, dashes and source anomalies — page 401

Manual reference: physical PDF page 401. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-16

Parameter function/register mappings; preserve blanks, dashes and source anomalies

Adjacent source context — repeated to preserve continuation:

Function / Register No — PDF page 401

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No Function Register No
2 Group 5 Group 5 Group 6 Group 6 Group 6 Group 6
3 5 – 48 0530H 6 – 00 0600H 6 – 41 0629H
4 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 01 0601H 6 – 42 062AH
5 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 02 0602H 6 – 43 062BH
6 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 03 0603H 6 – 44 062CH
7 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 04 0604H 6 – 45 062DH
8 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 05 0605H 6 – 46 062EH
9 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 06 0606H 6 – 47 062FH
10 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 07 0607H ⟦blank source cell⟧ ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 08 0608H ⟦blank source cell⟧ ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 09 0609H ⟦blank source cell⟧ ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 10 060AH ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 11 060BH ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 12 060CH ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 13 060DH ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 14 060EH ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 15 060FH ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 16 0610H ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 17 0611H ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 18 0612H ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 19 0613H ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 20 0614H ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 21 0615H ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 22 0616H ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 23 0617H ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 24 0618H ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 25 0619H ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 26 061AH ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 27 061BH ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 28 061CH ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 29 061DH ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 30 061EH ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 31 061FH ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧ 6 – 32 0620H ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter function/register mappings; preserve blanks, dashes and source anomalies — page 402

Manual reference: physical PDF page 402. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-17

Parameter function/register mappings; preserve blanks, dashes and source anomalies

Function / Register No — PDF page 402

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No Function Register No
2 Group 7 Group 7 Group 8 Group 8 Group 9 Group 9
3 7 – 00 0700H 8 – 00 0800H 9 – 00 0900H
4 7 – 01 0701H 8 – 01 0801H 9 – 01 0901H
5 7 – 02 0702H 8 – 02 0802H 9 – 02 0902H
6 7 – 03 0703H 8 – 03 0803H 9 – 03 0903H
7 7 – 04 0704H 8 – 04 0804H 9 – 04 0904H
8 7 – 05 0705H 8 – 05 0805H 9 – 05 0905H
9 7 – 06 0706H 8 – 06 0806H 9 – 06 0906H
10 7 – 07 0707H 8 – 07 0807H 9 – 07 0907H
11 7 – 08 0708H 8 – 08 0808H 9 – 08 0908H
12 7 – 09 0709H 8 – 09 0809H 9 – 09 0909H
13 7 – 10 070AH 8 – 10 080AH 9 – 10 090AH
14 7 – 11 070BH 8 – 11 080BH ⟦blank source cell⟧ ⟦blank source cell⟧
15 7 – 12 070CH 8 – 12 080CH ⟦blank source cell⟧ ⟦blank source cell⟧
16 7 – 13 070DH 8 – 13 080DH ⟦blank source cell⟧ ⟦blank source cell⟧
17 7 – 14 070EH 8 – 14 080EH ⟦blank source cell⟧ ⟦blank source cell⟧
18 7 – 15 070FH 8 – 15 080FH ⟦blank source cell⟧ ⟦blank source cell⟧
19 7 – 16 0710H 8 – 16 0810H ⟦blank source cell⟧ ⟦blank source cell⟧
20 7 – 17 0711H 8 – 17 0811H ⟦blank source cell⟧ ⟦blank source cell⟧
21 7 – 18 0712H 8 – 18 0812H ⟦blank source cell⟧ ⟦blank source cell⟧
22 7 – 19 0713H 8 – 19 0813H ⟦blank source cell⟧ ⟦blank source cell⟧
23 7 – 20 0714H 8 – 20 0814H ⟦blank source cell⟧ ⟦blank source cell⟧
24 7 – 21 0715H 8 – 21 0815H ⟦blank source cell⟧ ⟦blank source cell⟧
25 7 – 22 0716H 8 – 22 0816H ⟦blank source cell⟧ ⟦blank source cell⟧
26 7 – 23 0717H 8 – 23 0817H ⟦blank source cell⟧ ⟦blank source cell⟧
27 7 – 24 0718H 8 – 24 0818H ⟦blank source cell⟧ ⟦blank source cell⟧
28 7 – 25 0719H 8 – 25 0819H ⟦blank source cell⟧ ⟦blank source cell⟧
29 7 – 26 071AH 8 – 26 081AH ⟦blank source cell⟧ ⟦blank source cell⟧
30 7 – 27 071BH 8 – 27 081BH ⟦blank source cell⟧ ⟦blank source cell⟧
31 7 – 28 071CH 8 – 28 081CH ⟦blank source cell⟧ ⟦blank source cell⟧
32 7 – 29 071DH 8 – 29 081DH ⟦blank source cell⟧ ⟦blank source cell⟧
33 7 – 30 071EH 8 – 30 081EH ⟦blank source cell⟧ ⟦blank source cell⟧
34 7 – 31 071FH 8 – 31 081FH ⟦blank source cell⟧ ⟦blank source cell⟧
35 7 – 32 0720H 8 – 32 0820H ⟦blank source cell⟧ ⟦blank source cell⟧
36 7 – 33 0721H 8 – 33 0821H ⟦blank source cell⟧ ⟦blank source cell⟧
37 7 – 34 0722H 8 – 34 0822H ⟦blank source cell⟧ ⟦blank source cell⟧
38 7 – 35 0723H 8 – 35 0823H ⟦blank source cell⟧ ⟦blank source cell⟧
39 7 – 36 0724H 8 – 36 0824H ⟦blank source cell⟧ ⟦blank source cell⟧
40 7 – 37 0725H 8 – 37 0825H ⟦blank source cell⟧ ⟦blank source cell⟧
41 7 – 38 0726H 8 – 38 0826H ⟦blank source cell⟧ ⟦blank source cell⟧
42 7 – 39 0727H 8 – 39 0827H ⟦blank source cell⟧ ⟦blank source cell⟧
43 7 – 40 0728H 8 – 40 0828H ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 41 0829H ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter function/register mappings; preserve blanks, dashes and source anomalies — page 403

Manual reference: physical PDF page 403. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: 8-45/46/47 register cells are visibly blank;11-15 literally prints0D0FH among0Bxx rows. Do not fill or normalize addresses from neighbouring sequences.

AP 3-18

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Registeraddresses8–45/46/47 blank;literal11–15=0D0FH anomaly retained.

Parameter function/register mappings; preserve blanks, dashes and source anomalies

Function / Register No — PDF page 403

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No Function Register No
2 Group 7 Group 7 Group 8 Group 8 Group 9 Group 9
3 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 42 082AH ⟦blank source cell⟧ ⟦blank source cell⟧
4 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 43 082BH ⟦blank source cell⟧ ⟦blank source cell⟧
5 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 44 082CH ⟦blank source cell⟧ ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 45 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
7 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 46 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
8 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 47 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 48 0830H ⟦blank source cell⟧ ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 49 0831H ⟦blank source cell⟧ ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 50 0832H ⟦blank source cell⟧ ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 51 0833H ⟦blank source cell⟧ ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 52 0834H ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 53 0835H ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 54 0836H ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 55 0837H ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 56 0838H ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 57 0839H ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 58 083AH ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 59 083BH ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 – 60 083CH ⟦blank source cell⟧ ⟦blank source cell⟧

Function / Register No — PDF page 403

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No Function Register No
2 Group 10 Group 10 Group 11 Group 11 Group 11 Group 11
3 10 – 00 0A00H 11 – 00 0B00H 11 – 46 0B2EH
4 10 – 01 0A01H 11 – 01 0B01H 11 – 47 0B2FH
5 10 – 02 0A02H 11 – 02 0B02H 11 – 48 0B30H
6 10 – 03 0A03H 11 – 03 0B03H 11 – 49 0B31H
7 10 – 04 0A04H 11 – 04 0B04H 11 - 50 0B32H
8 10 – 05 0A05H 11 – 05 0B05H 11 - 51 0B33H
9 10 – 06 0A06H 11 – 06 0B06H 11 – 52 0B34H
10 10 – 07 0A07H 11 – 07 0B07H 11 – 53 0B35H
11 10 – 08 0A08H 11 – 08 0B08H 11 – 54 0B36H
12 10 – 09 0A09H 11 – 09 0B09H 11 – 55 0B37H
13 10 – 10 0A0AH 11 – 10 0B0AH 11 – 56 0B38H
14 10 – 11 0A0BH 11 – 11 0B0BH 11 – 57 0B39H
15 10 – 12 0A0CH 11 – 12 0B0CH 11 – 58 0B3AH
16 10 – 13 0A0DH 11 – 13 0B0DH 11 – 59 0B3BH
17 10 – 14 0A0EH 11 – 14 0B0EH 11 – 60 0B3CH
18 10 – 15 0A0FH 11 – 15 0D0FH 11 – 61 0B3DH
19 10 – 16 0A10H 11 – 16 0B10H 11 – 62 0B3EH
20 10 – 17 0A11H 11 – 17 0B11H 11 – 63 0B3FH
21 10 – 18 0A12H 11 – 18 0B12H 11 – 64 0B40H

Manual — Parameter function/register mappings; preserve blanks, dashes and source anomalies — page 404

Manual reference: physical PDF page 404. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: 10-41 through10-45 address cells are blank;10-46 contains a dash. Preserve the distinction. Fresh word-centre reads exclude next-row text that MuPDF textbox overlaps.

AP 3-19

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Registeraddresses10–41..45 blank and10–46 dash.

Parameter function/register mappings; preserve blanks, dashes and source anomalies

Function / Register No — PDF page 404

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No Function Register No
2 Group 10 Group 10 Group 11 Group 11 Group 11 Group 11
3 10 – 19 0A13H 11 – 19 0B13H 11 – 65 0B41H
4 10 – 20 0A14H 11 – 20 0B14H 11 – 66 0B42H
5 10 – 21 0A15H 11 – 21 0B15H 11 – 67 0B43H
6 10 – 22 0A16H 11 – 22 0B16H 11 – 68 0B44H
7 10 – 23 0A17H 11 – 23 0B17H 11 – 69 0B45H
8 10 – 24 0A18H 11 – 24 0B18H 11 – 70 0B46H
9 10 – 25 0A19H 11 – 25 0B19H 11 – 71 0B47H
10 10 – 26 0A1AH 11 – 26 0B1AH 11 – 72 0B48H
11 10 – 27 0A1BH 11 – 27 0B1BH 11 – 73 0B49H
12 10 – 28 0A1CH 11 – 28 0B1CH ⟦blank source cell⟧ ⟦blank source cell⟧
13 10 – 29 0A1DH 11 – 29 0B1DH ⟦blank source cell⟧ ⟦blank source cell⟧
14 10 – 30 0A1EH 11 – 30 0B1EH ⟦blank source cell⟧ ⟦blank source cell⟧
15 10 – 31 0A1FH 11 – 31 0B1FH ⟦blank source cell⟧ ⟦blank source cell⟧
16 10 – 32 0A20H 11 – 32 0B20H ⟦blank source cell⟧ ⟦blank source cell⟧
17 10 – 33 0A21H 11 – 33 0B21H ⟦blank source cell⟧ ⟦blank source cell⟧
18 10 – 34 0A22H 11 – 34 0B22H ⟦blank source cell⟧ ⟦blank source cell⟧
19 10 – 35 0A23H 11 – 35 0B23H ⟦blank source cell⟧ ⟦blank source cell⟧
20 10 – 36 0A24H 11 – 36 0B24H ⟦blank source cell⟧ ⟦blank source cell⟧
21 10 – 37 0A25H 11 – 37 0B25H ⟦blank source cell⟧ ⟦blank source cell⟧
22 10 – 38 0A26H 11 – 38 0B26H ⟦blank source cell⟧ ⟦blank source cell⟧
23 10 – 39 0A27H 11 – 39 0B27H ⟦blank source cell⟧ ⟦blank source cell⟧
24 10 – 40 0A28H 11 – 40 0B28H ⟦blank source cell⟧ ⟦blank source cell⟧
25 10 – 41 ⟦blank source cell⟧ 11 – 41 0B29H ⟦blank source cell⟧ ⟦blank source cell⟧
26 10 – 42 ⟦blank source cell⟧ 11 – 42 0B2AH ⟦blank source cell⟧ ⟦blank source cell⟧
27 10 – 43 ⟦blank source cell⟧ 11 – 43 0B2BH ⟦blank source cell⟧ ⟦blank source cell⟧
28 10 – 44 ⟦blank source cell⟧ 11 – 44 0B2CH ⟦blank source cell⟧ ⟦blank source cell⟧
29 10 – 45 ⟦blank source cell⟧ 11 – 45 0B2DH ⟦blank source cell⟧ ⟦blank source cell⟧
30 10 – 46 - ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
31 10 – 47 0A2FH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
32 10 – 48 0A30H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
33 10 – 49 0A31H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Function / Register No — PDF page 404

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No Function Register No
2 Group 12 Group 12 Group 13 Group 13 Group 14 Group 14
3 12 – 00 High WORD: 2510H Low WORD: 2511H 13 – 00 0D00H 14 – 00 0E00H
4 12 – 01 0C01H 13 – 01 0D01H 14 – 01 0E01H
5 12 – 02 0C02H 13 – 02 0D02H 14 – 02 0E02H
6 12 – 03 0C03H 13 – 03 0D03H 14 – 03 0E03H

Manual — Parameter function/register mappings; preserve blanks, dashes and source anomalies — page 405

Manual reference: physical PDF page 405. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-20

Parameter function/register mappings; preserve blanks, dashes and source anomalies

Function / Register No — PDF page 405

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No Function Register No
2 Group 12 Group 12 Group 13 Group 13 Group 14 Group 14
3 12 – 04 0C04H 13 – 04 0D04H 14 – 04 0E04H
4 12 – 05 0C05H 13 – 05 0D05H 14 – 05 0E05H
5 12 – 06 0C06H 13 – 06 0D06H 14 – 06 0E06H
6 12 – 07 0C07H 13 – 07 0D07H 14 – 07 0E07H
7 12 – 08 0C08H 13 – 08 0D08H 14 – 08 0E08H
8 12 – 09 0C09H 13 – 09 0D09H 14 – 09 0E09H
9 12 – 10 0C0AH 13 – 10 0D0AH 14 – 10 0E0AH
10 12 – 11 0C0BH 13 – 21 0D15H 14 – 11 0E0BH
11 12 – 12 0C0CH 13 – 22 0D16H 14 – 12 0E0CH
12 12 – 13 0C0DH 13 – 23 0D17H 14 – 13 0E0DH
13 12 – 14 0C0EH 13 – 24 0D18H 14 – 14 0E0EH
14 12 – 15 0C0FH 13 – 25 0D19H 14 – 15 0E0FH
15 12 – 16 0C10H 13 – 26 0D1AH 14 – 16 0E10H
16 12 – 17 0C11H 13 – 27 0D1BH 14 – 17 0E11H
17 12 – 18 0C12H 13 – 28 0D1CH 14 – 18 0E12H
18 12 – 19 0C13H 13 – 29 0D1DH 14 – 19 0E13H
19 12 – 20 0C14H 13 – 30 0D1EH 14 – 20 0E14H
20 12 – 21 0C15H 13 – 31 0D1FH 14 – 21 0E15H
21 12 – 22 0C16H 13 – 32 0D20H 14 – 22 0E16H
22 12 – 23 0C17H 13 – 33 0D21H 14 – 23 0E17H
23 12 – 24 0C18H 13 – 34 0D22H 14 – 24 0E18H
24 12 – 25 0C19H 13 – 35 0D23H 14 – 25 0E19H
25 12 – 26 0C1AH 13 – 36 0D24H 14 – 26 0E1AH
26 12 – 27 0C1BH 13 – 37 0D25H 14 – 27 0E1BH
27 12 – 28 0C1CH 13 – 38 0D26H 14 – 28 0E1CH
28 12 – 29 0C1DH 13 – 39 0D27H 14 – 29 0E1DH
29 12 – 30 0C1EH 13 – 40 0D28H 14 – 30 0E1EH
30 12 – 31 0C1FH 13 – 41 0D29H 14 – 31 0E1FH
31 12 – 32 0C20H 13 – 42 0D2AH 14 – 32 0E20H
32 12 – 33 0C21H 13 – 43 0D2BH 14 – 33 0E21H
33 12 – 34 0C22H 13 – 44 0D2CH 14 – 34 0E22H
34 12 – 35 0C23H 13 – 45 0D2DH 14 – 35 0E23H
35 12 – 36 0C24H 13 – 46 0D2EH 14 – 36 0E24H
36 12 – 37 0C25H 13 – 47 0D2FH 14 – 37 0E25H
37 12 – 38 0C26H 13 – 48 0D30H 14 – 38 0E26H
38 12 – 39 0C27H 13 – 49 0D31H 14 – 39 0E27H
39 12 - 40 0C28H 13 – 50 0D32H 14 – 40 0E28H
40 12 - 41 0C29H 13 - 51 0D33H 14 – 41 0E29H
41 12 - 42 0C2AH ⟦blank source cell⟧ ⟦blank source cell⟧ 14 – 42 0E2AH
42 12 - 43 0C2BH ⟦blank source cell⟧ ⟦blank source cell⟧ 14 – 43 0E2BH
43 12 - 74 0C28H ⟦blank source cell⟧ ⟦blank source cell⟧ 14 - 44 0E2CH
44 12 – 75 0C4BH ⟦blank source cell⟧ ⟦blank source cell⟧ 14 - 45 0E2DH

Manual — Parameter function/register mappings; preserve blanks, dashes and source anomalies — page 406

Manual reference: physical PDF page 406. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-21

Parameter function/register mappings; preserve blanks, dashes and source anomalies

Function / Register No — PDF page 406

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No Function Register No
2 Group 12 Group 12 Group 13 Group 13 Group 14 Group 14
3 12 – 82 0C52H ⟦blank source cell⟧ ⟦blank source cell⟧ 14 - 46 0E2EH
4 12 - 83 0C53H ⟦blank source cell⟧ ⟦blank source cell⟧ 14 - 47 0E2FH

Function / Register No — PDF page 406

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No Function Register No
2 Group 15 Group 15 Group 16 Group 16 Group 17 Group 17
3 15 – 00 0F00H 16 – 00 1000H 17 – 00 1100H
4 15 – 01 0F01H 16 – 01 1001H 17 – 01 1101H
5 15 – 02 0F02H 16 – 02 1002H 17 – 02 1102H
6 15 – 03 0F03H 16 – 03 1003H 17 – 03 1103H
7 15 – 04 0F04H 16 – 04 1004H 17 – 04 1104H
8 15 – 05 0F05H 16 – 05 1005H 17 – 05 1105H
9 15 – 06 0F06H 16 – 06 1006H 17 – 06 1106H
10 15 – 07 0F07H 16– 07 1007H 17 – 07 1107H
11 15 – 08 0F08H 16 – 08 1008H 17 – 08 1108H
12 15 – 09 0F09H 16 – 09 1009H 17– 09 1109H
13 15 – 10 0F0AH ⟦blank source cell⟧ ⟦blank source cell⟧ 17 – 10 110AH
14 15 – 11 0F0BH ⟦blank source cell⟧ ⟦blank source cell⟧ 17 – 11 110BH
15 15 – 12 0F0CH ⟦blank source cell⟧ ⟦blank source cell⟧ 17 – 12 110CH
16 15 – 13 0F0DH ⟦blank source cell⟧ ⟦blank source cell⟧ 17 – 13 110DH
17 15 – 14 0F0EH ⟦blank source cell⟧ ⟦blank source cell⟧ 17 – 14 110EH
18 15 – 15 0F0FH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
19 15 – 16 0F10H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
20 15 – 17 0F11H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
21 15 – 18 0F12H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
22 15 – 19 0F13H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 15 – 20 0F14H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
24 15 – 21 0F15H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
25 15 – 22 0F16H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
26 15 – 23 0F17H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
27 15 – 24 0F18H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
28 15 – 25 0F19H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
29 15 – 26 0F1AH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
30 15 – 27 0F1BH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
31 15 – 28 0F1CH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
32 15 – 29 0F1DH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
33 15 – 30 0F1EH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
34 15 – 31 0F1FH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
35 15 – 32 0F20H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter function/register mappings; preserve blanks, dashes and source anomalies — page 407

Manual reference: physical PDF page 407. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-22

Parameter function/register mappings; preserve blanks, dashes and source anomalies

Function / Register No — PDF page 407

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No Function Register No
2 Group 18 Group 18 Group 20 Group 20 Group 21 Group 21
3 18 – 00 1200H 20 – 00 1400H 21 – 00 1500H
4 18 – 01 1201H 20 – 01 1401H 21 – 01 1501H
5 18 – 02 1202H 20 – 02 1402H 21 – 02 1502H
6 18 – 03 1203H 20 – 03 1403H 21 – 03 1503H
7 18 – 04 1204H 20 – 04 1404H 21 – 04 1504H
8 18 – 05 1205H 20 – 05 1405H 21 – 05 1505H
9 18 – 06 1206H 20 – 06 1406H 21 – 06 1506H
10 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 07 1407H 21 – 07 1507H
11 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 08 1408H 21 – 08 1508H
12 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 09 1409H ⟦blank source cell⟧ ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 10 140AH ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 11 140BH ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 12 140CH ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 13 140DH ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 14 140EH ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 15 140FH ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 16 1410H ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 17 1411H ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 18 1412H ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 19 1413H ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 20 1414H ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 21 1415H ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 22 1416H ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 23 1417H ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 24 1418H ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 25 1419H ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 26 141AH ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 27 141BH ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 28 141CH ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 29 141DH ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 30 141EH ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 31 141FH ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 32 1420H ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 33 1421H ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 34 1422H ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧ 20 – 35 1423H ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter function/register mappings; preserve blanks, dashes and source anomalies — page 408

Manual reference: physical PDF page 408. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: 23-21/22/36 visibly contain dashes;22 group ends22-25 and23 group jumps39 to71. Omitted addresses are not inferred from the sequential rows.

AP 3-23

PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Registeraddresses23–21/22/36 dash;22–26..29/34 and23–40..70/74..78 omitted relative to parameter form; no fill.

Parameter function/register mappings; preserve blanks, dashes and source anomalies

Function / Register No / — PDF page 408

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Function Register No Function Register No ⟦blank source cell⟧ ⟦blank source cell⟧
2 Group 22 Group 22 Group 23 Group 23 ⟦blank source cell⟧ ⟦blank source cell⟧
3 22 – 00 1600H 23 – 00 1700H ⟦blank source cell⟧ ⟦blank source cell⟧
4 22 – 01 1601H 23 – 01 1701H ⟦blank source cell⟧ ⟦blank source cell⟧
5 22 – 02 1602H 23 – 02 1702H ⟦blank source cell⟧ ⟦blank source cell⟧
6 22 – 03 1603H 23 – 03 1703H ⟦blank source cell⟧ ⟦blank source cell⟧
7 22 – 04 1604H 23 – 04 1704H ⟦blank source cell⟧ ⟦blank source cell⟧
8 22 – 05 1605H 23 – 05 1705H ⟦blank source cell⟧ ⟦blank source cell⟧
9 22 – 06 1606H 23 – 06 1706H ⟦blank source cell⟧ ⟦blank source cell⟧
10 22 – 07 1607H 23 – 07 1707H ⟦blank source cell⟧ ⟦blank source cell⟧
11 22 – 08 1608H 23 – 08 1708H ⟦blank source cell⟧ ⟦blank source cell⟧
12 22 – 09 1609H 23 – 09 1709H ⟦blank source cell⟧ ⟦blank source cell⟧
13 22 – 10 160AH 23 – 10 170AH ⟦blank source cell⟧ ⟦blank source cell⟧
14 22 – 11 160BH 23 – 11 170BH ⟦blank source cell⟧ ⟦blank source cell⟧
15 22 – 12 160CH 23 – 12 170CH ⟦blank source cell⟧ ⟦blank source cell⟧
16 22 – 13 160DH 23– 13 170DH ⟦blank source cell⟧ ⟦blank source cell⟧
17 22 – 14 160EH 23 – 14 170EH ⟦blank source cell⟧ ⟦blank source cell⟧
18 22 – 15 160FH 23 – 15 170FH ⟦blank source cell⟧ ⟦blank source cell⟧
19 22 – 16 1610H 23 – 16 1710H ⟦blank source cell⟧ ⟦blank source cell⟧
20 22 – 17 1611H 23 – 17 1711H ⟦blank source cell⟧ ⟦blank source cell⟧
21 22 – 18 1612H 23 – 18 1712H ⟦blank source cell⟧ ⟦blank source cell⟧
22 22 – 19 1613H 23 – 19 1713H ⟦blank source cell⟧ ⟦blank source cell⟧
23 22 – 20 1614H 23 – 20 1714H ⟦blank source cell⟧ ⟦blank source cell⟧
24 22 – 21 1615H 23 – 21 - ⟦blank source cell⟧ ⟦blank source cell⟧
25 22 – 22 1616H 23 – 22 - ⟦blank source cell⟧ ⟦blank source cell⟧
26 22 – 23 1617H 23 – 23 1717H ⟦blank source cell⟧ ⟦blank source cell⟧
27 22 – 24 1618H 23 – 24 1718H ⟦blank source cell⟧ ⟦blank source cell⟧
28 22 – 25 1619H 23 – 25 1719H ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 26 171AH ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 27 171BH ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 28 171CH ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 29 171DH ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 30 171EH ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 31 171FH ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 32 1720H ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 33 1721H ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 34 1722H ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 35 1723H ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 36 - ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 37 1735H ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 38 1736H ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 39 1737H ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 71 1747H ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 72 1748H ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧ 23 – 73 1749H ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — BACnet object/property support matrix — page 409

Manual reference: physical PDF page 409. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-24

BACnet Specifications Description

Inverter E510s model is built-in standard BACnet MS/TP communication protocol structure to meet the

demand of automatic communication equipment. Control or monitor E510s via BACnet to be allowable

to read and modify specific parameter. E510s includes the following supports of standard objects:

 Inverter Objects  Analog Output  Analog Value  Analog Input  Digital Output  Digital Value  Digital Input E510s is supporting the property information of object classification. User can collect related properties of objects required via the dedicated communication software of BACnet to give control or monitor command for each object:

BACnet object/property support matrix

BACnet Object / Property support matrix — PDF page 409

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows)
1 Proerty Inverter (DEV) Analog Input (AI) Analog Output (AO) Analog Value (AV) Digital Input (BI) Digital Output (BO) Digital Value (BV)
2 Object_Identifier V V V V V V V
3 Object_Name V V V V V V V
4 Object_Type V V V V V V V
5 System_Status V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
6 Vendor_Name V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
7 Vendor_ Identifier V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
8 Model_Name V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
9 Firmware_Revision V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
10 Applocation_Software_Supported V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
11 Protocol_Version V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
12 Protocol_Revision V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
13 Protocol_Services_Supported V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
14 Protocol_Object_Type_Supported V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
15 Object_List V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
16 Max_APDU_Length_Accepted ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
17 Segmentation_Supported ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
18 APDU_Timeout ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
19 Number_Of_APDU_Retries ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
20 Max_Masters V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
21 Max_Info_Frames V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
22 Device_Address_Binding ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 Location V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
24 Presnent_Value ⟦blank source cell⟧ V V V V V V
25 Status_Flags ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
26 Event_State ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
27 Relibility ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
28 Out_Of_Service ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
29 Units ⟦blank source cell⟧ V V V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
30 Priority_Array ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
31 Relinquish_Default ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — BACnet device properties and analog inputs part1 — page 410

Manual reference: physical PDF page 410. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: AI5 and AI7 Range cells blank in source; engineering ranges unresolved.

AP 3-25

BACnet Object Properties:

This section provides the predetermined configuration of the inverter. User can achieve the optimizazed

situation at any necessary modification. Refer to Table 2 for the property information of inverter objects

and user can learn the inverter messages from the inverter objects. Refer to Table 3 ~ 8 for the related

object information that inverter supports. User can control/ read each object with the application

requirements.

Table 2 Inverter property list

Table 3 Analog input property list (Read)

First table continues support matrix409. AI0–7 continues411AI8–15. AI5 and AI7 range cells are blank; no inferred values.

BACnet device properties and analog inputs part1

BACnet Object / Property support matrix continued — PDF page 410

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows)
1 Proerty Inverter (DEV) Analog Input (AI) Analog Output (AO) Analog Value (AV) Digital Input (BI) Digital Output (BO) Digital Value (BV)
2 Polarity ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
3 Inactive_Text ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
4 Active_Text ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Table 2 Inverter property list — PDF page 410

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Property Inverter
2 Object_Identifier DEV
3 Object_Name VFD
4 Object_Type 8
5 System_Status 0
6 Vendor_Name VFD
7 Vendor_ Identifier 461
8 Model_Name VFD
9 Firmware_Revision 0.14
10 Applocation_Software_Supported 0.14
11 Protocol_Version 1
12 Protocol_Revision 5
13 Protocol_Services_Supported { readProperty , writeProperty , who is }
14 Protocol_Object_Type_Supported { Analog_Input , Analog_Output, Analog_Value Binary_ Input, Binary_Output, Binary_Value, Device}
15 Max_Masters 127
16 Max_Info_Frames 1

Table 3 Analog input property list (Read) — PDF page 410

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classification Range
2 AI0 TM2 AIN AVI input Volt R 0-10
3 AI1 TM2 AIN2 ACI input Volt R 0-10
4 AI2 Error code Recent fault message No Units R 0-45
5 AI3 Freq cmd Frequency command Hz R 0-60
6 AI4 Frequency Output frequency Hz R 0-60
7 AI5 Current Output current Amps R ⟦blank source cell⟧
8 AI6 Control Mode Control mode No Units R 0-2
9 AI7 Motor R-Volt Motor rated voltage Volt R ⟦blank source cell⟧

Manual — BACnet analog inputs continuation and analog outputs — page 411

Manual reference: physical PDF page 411. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: AI8, AI9 and AI10 Range cells blank in source; engineering ranges unresolved.

AP 3-26

Table 4 Analog output property list (Read/Write)

AI8–15 continues410. AI8/AI9/AI10 ranges are blank; AO Read/Write heading does not override row R classification.

BACnet analog inputs continuation and analog outputs

Table 3 Analog input property list (Read) continued — PDF page 411

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classification Range
2 AI8 Motor R-HP Motor rated power horsepower R ⟦blank source cell⟧
3 AI9 Motor R-RPM Motor rated rotation speed No Units R ⟦blank source cell⟧
4 AI10 Motor R-Hz Motor rated frequency Hz R ⟦blank source cell⟧
5 AI11 CarrierFreq Carrier frequency KiloHertz R 4-16
6 AI12 Comm Station INV communication station No Units R 1-254
7 AI13 BaudRate Baudrate setting No Units R 0-3
8 AI14 BacnetSel Communication mode selection No Units R 0-1
9 AI15 DevInstance Inverter number No Units R 1-254

Table 4 Analog output property list (Read/Write) — PDF page 411

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classification Range
2 AO0 Set frequency Frequency command Hz R/W 0-599
3 AO1 TB2 AO1 Analog output voltage 1 Volt R 0-10
4 AO2 - - - - -
5 AO3 Motor R-Amp Motor rated current Amps R/W 0-65535
6 AO4 PwrL Sel Momentary stop and restart selection No Units R 0-1
7 AO5 RestartSel Number of Fault Auto-Restart Attempts No Units R 0-10
8 AO6 RestartDelay Fault Auto-Restart Time seconds R 0-7200
9 AO7 FreqCommand1 Speed frequency setting-stage 0 Hz R/W 0-599
10 AO8 FreqCommand2 Speed frequency setting-stage 1 Hz R/W 0-599
11 AO9 FreqCommand3 Speed frequency setting-stage 2 Hz R/W 0-599
12 AO10 FreqCommand4 Speed frequency setting-stage 3 Hz R/W 0-599
13 AO11 FreqCommand5 Speed frequency setting-stage 4 Hz R/W 0-599
14 AO12 FreqCommand6 Speed frequency setting-stage 5 Hz R/W 0-599
15 AO13 FreqCommand7 Speed frequency setting-stage 6 Hz R/W 0-599
16 AO14 FreqCommand8 Speed frequency setting-stage 7 Hz R/W 0-599
17 AO15 FreqCommand9 Speed frequency setting-stage 8 Hz R/W 0-599
18 AO16 FreqCommand10 Speed frequency setting-stage 9 Hz R/W 0-599
19 AO17 FreqCommand11 Speed frequency setting-stage 10 Hz R/W 0-599
20 AO18 FreqCommand12 Speed frequency setting-stage 11 Hz R/W 0-599
21 AO19 FreqCommand13 Speed frequency setting-stage 12 Hz R/W 0-599
22 AO20 FreqCommand14 Speed frequency setting-stage 13 Hz R/W 0-599
23 AO21 FreqCommand15 Speed frequency setting-stage 14 Hz R/W 0-599
24 AO22 FreqCommand16 Speed frequency setting-stage 15 Hz R/W 0-599
25 AO23 RunMode Main run command source No Units R/W 0-2
26 AO24 ReverseOper Direction locked command No Units R/W 0-1
27 AO25 StoppingSel Stop modes selection No Units R/W 0-1
28 AO26 FrequenceComm Main frequency command source No Units R/W 0-5
29 AO27 FreqUpperLim Upper limit frequency Hz R/W 0-599
30 AO28 FreqLowerLim Lower limit frequency Hz R/W 0-598.99
31 AO29 Acc Time1 Acceleration time 1 seconds R/W 0-6000.0
32 AO30 Dec Time1 Deceleration time 1 seconds R/W 0-6000.0

Manual — BACnet analog values, digital inputs/outputs/values — page 412

Manual reference: physical PDF page 412. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 3-27

Table 5 Analog value property list (Read/Write)

Table 6 Digital input property list (Read)

Table 7 Digital output property list (Read/Write)

Table 8 Digital value property list (Read/Write)

BO1 source ObjectName RY2 status but Description Relay output1 status; BI9 DI_6 status description Operation status. Literal source retained.

BACnet analog values, digital inputs/outputs/values

Table 5 Analog value property list (Read/Write) — PDF page 412

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classification Range
2 AV0 PID-P Gain Proportional gain (P) No Units R/W 0-10
3 AV1 PID-I Time Integral time (I) No Units R/W 0-100
4 AV2 PID-D Time Differential time (D) No Units R/W 0-10

Table 6 Digital input property list (Read) — PDF page 412

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classification Range
2 BI0 Run/Stop Operation status Stop / Run R 0-1
3 BI1 Direction Operation direction FWD/REV R 0-1
4 BI2 status Inverter status OK/Fault R 0-1
5 BI3 Abnormal Error occurs Close/Open R 0-1
6 BI4 DI_1 status S1 status Close/Open R 0-1
7 BI5 DI_2 status S2 status Close/Open R 0-1
8 BI6 DI_3 status S3 status Close/Open R 0-1
9 BI7 DI_4 status S4 status Close/Open R 0-1
10 BI8 DI_5 status S5 status Close/Open R 0-1
11 BI9 DI_6 status Operation status Close/Open R 0-1

Table 7 Digital output property list (Read/Write) — PDF page 412

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classification Range
2 BO0 RY1 status Relay output 1 status Close/Open R 0-1
3 BO1 RY2 status Relay output 1 status Close/Open R 0-1
4 BO2 - - - - -

Table 8 Digital value property list (Read/Write) — PDF page 412

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classification Range
2 BV0 RUN/STOP RUN/STOP Stop / Run R/W 0-1
3 BV1 FWD/REV FWD/REV FWD/REV R/W 0-1

Manual — JN5-CM-USB exterior dimensions and connection illustration — page 413

Manual reference: physical PDF page 413. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 4-1

Appendix 4 JN5-CM-USB Instruction

  1. Model & Specification 1.1 Instruction

JN5-CM-USB has the function of converting USB communication format to RS485 to achieve the

inverter communication control being similar with PC or other control equipment with USB port.

1.2 Exterior(Unit:mm)

1.3 Connecting

JN5-CM-USB exterior drawing; heading explicitly Unit:mm. Lengthbetweenconnector-bodyendpoints180.0±1.5;leftheight20,leftstub12,leftbody45.5;rightconnectorlength12.3,height11.6. Preserve source dimensions; accessory table415says cable1.8meters. No conversion or correction inferred.

Connection illustration shows laptop/PC,USB cable and drive with opened upper terminal area. No labelled terminal assignments or wiring topology added; tiny incidental casing markings are not used as operating instructions.

Dimension drawing explicitly states Unit:mm and180.0±1.5.415 accessory table says1.8meters for same model. Do not silently scale. Same-model365 drawing previously lacked its own unit; additive cross-reference proposal provided without changing that frozen packet.

Manual — JN5-CM-USB connector pin definitions and notices — page 414

Manual reference: physical PDF page 414. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AP 4-2

  1. USB interface cable pin definition

2.1 RS232/USB interface

USB interface, connects with PC or other USB interface devices

2.2 RS485/RJ45 interface

2.3 RS485/RJ45 pin definition

Note: A/B phase signal (pin1&pin2) is differential mode data signal of RS485. VCC&GND is the +5Vdc power supply provided by inverter internal power source.

  1. Notice  Please turn off the power before you connect the cable..  When inverter is powered off during communication. PC software will show “communication error”.  If any error occurs during communication, check the wiring connection and restart the pc software.

USB connector illustration: left upperpinlabel4, lowerpinlabel1;USBtrident symbol. HeadingliterallyRS232/USBinterface, while413describesUSBtoRS485conversion.

RJ45connector illustration: pin1atupperright,pin8atlowerright in shown orientation. No alternative viewpoint inferred; explicit pin functions retained in source table.

Cable pins are distinct connector context from inverter CN6 on386; do not substitute pin functions. USB connector heading literallyRS232/USB. Turn-off-before-connection warning retained.

JN5-CM-USB connector pin definitions and notices

2.3 RS485/RJ45 pin definition — PDF page 414

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Pin No., 1 2 3 4 5 6 7 8
2 Define A B NC NC NC NC VCC GND

Manual — Appendix5 accessory model descriptions and restrictions — page 415

Manual reference: physical PDF page 415. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

App 5-1

Appendix 5:Accessories

JN5-CU remote keypad function restriction explicitly L510s series only; table placement in E510s manual does not extend applicability.

Appendix5 accessory model descriptions and restrictions

Appendix 5 Accessories — PDF page 415

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Accessories Model Description Note
2 Cables JN5-CB-01M IP20 Digital operator extension cable 1 meter
3 Cables JN5-CB-02M IP20 Digital operator extension cable 2 meters
4 Cables JN5-CB-03M IP20 Digital operator extension cable 3 meters
5 Cables JN5-CB-05M IP20 Digital operator extension cable 5 meters
6 Cables JN5-CM-USB RJ45 to USB connecting cable 1.8 meters
7 NEMA1 Kits JN5-NK-SE01 Mechanical device consisting of anti-dust cover on the upper part and wiring box on the bottom to meet NEMA1. (Frame 5/6 has been designed to NEMA1 protection level, does not need to add the accessories) Frame 1
8 NEMA1 Kits JN5-NK-SE02 Mechanical device consisting of anti-dust cover on the upper part and wiring box on the bottom to meet NEMA1. (Frame 5/6 has been designed to NEMA1 protection level, does not need to add the accessories) Frame 2
9 NEMA1 Kits JN5-NK-SE03 Mechanical device consisting of anti-dust cover on the upper part and wiring box on the bottom to meet NEMA1. (Frame 5/6 has been designed to NEMA1 protection level, does not need to add the accessories) Frame 3
10 NEMA1 Kits JN5-NK-SE04 Mechanical device consisting of anti-dust cover on the upper part and wiring box on the bottom to meet NEMA1. (Frame 5/6 has been designed to NEMA1 protection level, does not need to add the accessories) Frame 4
11 Copy Module JN5-CU ① Duplicating parameters setting of same series inverter from one inverter to another inverter. ② As a remote keypad to be used Remote keypad function only can be used in L510s series
12 LCD Digital Operator JN5-OP-A02 IP20 LCD type for remote control (Built-in parameter copy function) Option only
13 Keypad Display Holder JN5-KEYBOX Keypad display can be fixed on the panel. Dual direction installation
14 Communication Card JN5-CMI-PDP For connection of Profibus-DP communication protocol Profibus DP
15 Communication Card JN5-CMI-TCPIP For connection of TCP-IP communication protocol TCP-IP
16 Communication Card JN5-CMI-DNET For connection of Devicenet communication protocol DeviceNet
17 Communication Card JN5-CMI-CAN For connection of CAN open communication protocol CANopen

Manual — 11-301 Safety stop instruction manual cover and contents — page 416

Manual reference: physical PDF page 416. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

INVERTER 11-301 series

Safety stop function instruction manual

CONTENTS

  1. General description ..................................................................................... 1

  2. Installation and wiring ................................................................................ 2

  3. Example of safety system configuration ................................................ 5

  4. Test and checking failure ........................................................................... 7

  5. Safety parameters of 11-301 ..................................................................... 8

Manual — STO functional safety warnings and cautions — page 417

Manual reference: physical PDF page 417. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Compliance with the EU Machinery Directive – Functional Safety

WARNING Safe Torque off function may not be an appropriate method for stopping your machine. Activating this function will result in no output voltage to the Motor hence motor will coast down to stop under the influence of the load inertia.

WARNING Any misuse of safety function could lead to personal injury or death, property damage, or economic loss. To ensure that the system complies fully with requirement of safety, make a system-level risk assessment. TECO Electric Co. cannot assume responsibility for any system to comply with safety directive.

CAUTION The information of this manual is merely a guide for proper installation. TECO Electric Co. cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.

WARNING To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before performing any work on the drive. Measure the DC bus voltage at the P(+) and N(-) terminals or test points (refer to your drive’s User Manual for locations and discharging time). The voltage must bezero.

WARNING To avoid an electric shock hazard, disconnect/isolate power to the drive and verify to ensure that the voltage is zero before performing any work on the motor (refer to your drive’s User Manual for discharging time).

CAUTION In order to maintain the pollution degree 2 the devices shall be mounted in a cabinet of IP 54 type .or pollution controlled environment.

CAUTION Ensure that the external safety relay unit and the E510s drive are mounted close to each other all interconnection wiring is as short as possible and protected against open and short circuit faults. Refer EN/ISO13849-1.

CAUTION To avoid systematic faults, a test even for faulty demands of the safety function has to be performed in order to check the correct function of the monitor signal. This test shall be carried out at system installation, any software changes, parameterization changes, and/or at least once per year. Refer to “Chapter 5 Troubleshooting and Fault Diagnostics”.

STO content retained as historical supplier instructions/claims, not safety-system design validation or current certification. Isolation, zero-voltage, risk assessment and stopping-time conditions retained with their context.

Manual — STO introduction, directives and installation environment — page 418

Manual reference: physical PDF page 418. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Shock row is physically clipped after IEC60068- and Atmosphere after dust and. PDF425 has complete-looking corresponding text, but explicitly introduces TECO11-301 safety stop function, while418 is E510s STO. Retain425 as separately scoped source context, not a replacement, certification proof or assumed applicability.

  1. Introduction

This document describes the main design specification of the E510s Safe Torque Off ( STO ) and the requirements for its installation and integration within safety related applications. The correct Installation and integration of the E510s STO is the responsibility of the Installer and it is expected that the installer follows the safety guide and is a trained technician and experienced in the design of safety systems. E510s STO (Safe Torque Off) circuit and function is certified by Tuv to:  Safety Integrated category SIL2 according to EN/IEC 62061, IEC 61508, EN61800-5-2  Performance level. Category 3/ Pl(d). according to EN/ISO 13849-1 Stop category 0. According to EN60204-1

  1. Safety-Related Requirements 2.1 Directives

2.2 Installation Environment E510s safety stop function should only be used under the following condition and environment.

Table 1.

Shock and Atmosphere rows visibly clipped; separately complete425context retained, not substituted into418.

STO content retained as historical supplier instructions/claims, not safety-system design validation or current certification. Isolation, zero-voltage, risk assessment and stopping-time conditions retained with their context.

STO introduction, directives and installation environment

2.1 Directives — PDF page 418

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 IEC/EN 61800- 5-2 : 2007 Adjustable Speed Electrical Power Drive Systems. Part 5-2: Safety Requirements – Functional
2 EN ISO 13849-1: 2008 Safety of Machinery – Safety-related parts of control systems. Part 1: General Principles for Design
3 IEC 61508- 1~7 Functional Safety of Electrical/Electronic/Programmable Electronic Safety-related systems
4 IEC 62061: 2005 Safety of Machinery – Functional safety of safety-related electrical, electronic and programmable electronic control systems
5 EN 60204-1 Safety of machinery - Electrical equipment of machines. General requirements.

Table 1 Installation Environment — PDF page 418

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Item Item Condition
2 Temperature range Operation -10°C~50°C inside distributor (without dust cover) -10°C~40°C inside distributor (with dust cover)
3 Temperature range Storage -20°C to +60°C
4 Ambient humidity Ambient humidity 95%RH maximum (non-condensing)
5 Shock Shock 1G. (9.8m/s²) for 20Hz and below. 0.6G (5.88m/s²) from 20Hz to 50Hz (Compliance with IEC 60068-
6 Altitude Altitude maximum 1000m above sea level
7 Atmosphere Atmosphere Indoors (without corrosive gas, flammable gas, oil mist, dust and
8 Over voltage category Over voltage category II or less
9 Pollution degree Pollution degree II or less
10 Mounting Mounting wall mounting / verticalorientation

Manual — STO product ranges, ratings and E510 product identification — page 419

Manual reference: physical PDF page 419. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

  1. Product Information

3.1 Product models & range

 230V single Phase. IP 20 0.40 ~ 2.2KW. (3hp)

 400V three phase. IP20 0.75 ~ 55 KW. (75hp)

Table 2

3.2 Product Identification

Product identification diagram: E510 / 2 / 01 / S / H / 1 / F. Inputvoltage2:200V,4:400V. HPcodesP5:0.5HP,01:1HP,02:2HP,03:3HP,05:5HP,08:7.5HP,10:10HP,15:15HP,20:20HP,25:25HP,30:30HP,40:40HP,50:50HP,60:60HP,75:75HP. S:510sseries;H:Standard;inputvoltagetypeBlank:Single/Threephase,1:Singlephase,3:Threephase. EMCfilterBlank:Without,F:Built-in(withSTOfunction). Source label associations only.

STO product ranges, ratings and E510 product identification

Table 2 Product models and range — PDF page 419

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Model Horsepower Power Specification Voltage (Volt) Current (A)
2 Frame1 0.5/1 200V~240V 600 20
3 Frame1 1/2 380V~480V 600 20
4 Frame2 2/3/5 200V~240V 600 45
5 Frame2 3/5 380V~480V 600 45
6 Frame 3/4 7.5/10/15/20 200V~240V 600 100
7 Frame 3/4 7.5/10/15/20/25 380V~480V 600 165
8 Frame 5 25 200V~240V 600 100
9 Frame 5 30 380V~480V 600 75
10 Frame 6 30/40 200V~240V 600 175
11 Frame 6 40/50/60/75 380V~480V 600 175

Manual — 11-301 model identification and exact E510 cross-reference — page 420

Manual reference: physical PDF page 420. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Model G Phase legend lacks3 despite43codes; do not infer missing model-code legend.

3.3 Model Identification

3.4 Product name /Model name cross reference

Table 3

  1. Safety Stop / Safe Torque Off. (STO). E510s STO is a functional safety feature that complies with the safety functions in adjustable speed drives according to IEC 61800-5-2 ( type A safety component) and when put in use within a safety control system according to the required safety standards will provide safe Torque off (no output voltage) and Prevents an unintentional restart.

Model identification A B – CDE – F – G – HIJ – K – L. AProduct1:Inverter,2:SERVO,3:PLC. BULCategory0:ULRecognized,1:ULListed. C-Eserial001–999. FStandardvoltage1:100–120V,2:200–240V,4:380–480V. GPhase0:Single/Threeph,1:Singlephase; no3legend printed despite43modelcodesbelow. H-JHorsePower0P5:0.5HP,001:1HP,075:75HP. KEMCfilter0:Notbuilt-in,3:Built-in+STO. LProtectionLevel0:IP20,3:NEMA1. Literal source historical classifications, not validation.

Model G Phase legend lacks3 despite43codes; do not infer missing model-code legend.

Explicit18-model cross-reference preserved. May add cross-reference to earlier373–375 literal model records only for exact match;11-201 and476not mapped here.

11-301 model identification and exact E510 cross-reference

Table 3 Product name / Model name cross reference — PDF page 420

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Model Name Product Name Model Name Product Name Model Name Product Name
2 11‐301‐21‐2P5‐30 E510‐2P5‐SH1F 11‐301‐43‐403‐30 E510‐403‐SH3F 11‐301‐43‐425‐30 E510‐425‐SH3F
3 11‐301‐21‐201‐30 E510‐201‐SH1F 11‐301‐43‐405‐30 E510‐405‐SH3F 11‐301‐43‐430‐30 E510‐430‐SH3F
4 11‐301‐21‐202‐30 E510‐202‐SH1F 11‐301‐43‐408‐30 E510‐408‐SH3F 11‐301‐43‐440‐30 E510‐440‐SH3F
5 11‐301‐21‐203‐30 E510‐203‐SH1F 11‐301‐43‐410‐30 E510‐410‐SH3F 11‐301‐43‐450‐30 E510‐450‐SH3F
6 11‐301‐43‐401‐30 E510‐401‐SH3F 11‐301‐43‐415‐30 E510‐415‐SH3F 11‐301‐43‐460‐30 E510‐460‐SH3F
7 11‐301‐43‐402‐30 E510‐402‐SH3F 11‐301‐43‐420‐30 E510‐420‐SH3F 11‐301‐43‐475‐30 E510‐475‐SH3F

Manual — Safe torque off coast-stop and electromechanical comparison — page 421

Manual reference: physical PDF page 421. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Caution

 The STO Function by itself is not an Emergency Stop and may be used as part of an

Emergency Stop control system but all relevant standards must be consulted.

 Decision to use STO in a control system must be based on risk assessment, refer to the

relevant standards EN/IEC 62061or EN/ISO 13849-1.

 In application of STO due to the coast to stop function take into consideration the

stopping time of the driven load.

 For further information on STO refer to EN61800-5-2 and For stop categories Refer to

EN60204-1

  1. Electromechanical and Safety integrated interface Comparison

Diagrams below show simple Inverter drive configurations for comparison between safe stop

interfaces using electromechanical and Safety integrated type solutions.

Fig1 Safe torque Off. STOActivated→IGBToutputsare shutdown→MotorSpeedCoaststo zero→StopCategory0toEN60204-1. Graphaxesv,t withSTOarrowanddecayingcurve; no numeric scale. Samefigurealso prints Electromechanical.WithoutSTOfunction/NoSIL.StopCategory0, inconsistent withSTOActivatedheading; bothretained.

Electromechanical.WithoutSTOfunction / NoSIL.StopCategory0. IllustrationlabelsEmergency stop,SafetyInterlocks,Contactor,Inverter,Motor withflowarrows. No inferred wiring/ratings.

STO content retained as historical supplier instructions/claims, not safety-system design validation or current certification. Isolation, zero-voltage, risk assessment and stopping-time conditions retained with their context.

Manual — STO system comparison and Frame1 terminal layout — page 422

Manual reference: physical PDF page 422. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Typical Frame1 drawing clearly shows main-terminal face labels L1 L2 L3 T1 T2 T3 P BR in enlarged crop. Add as literal illustration labels only. Incidental control-terminal/keypad glyphs and upper product-photo inscriptions remain unresolved; no topology or applicability inference.

  1. Terminal designation & interface

6.1 Power & Control terminals.

Frame 1. Terminal layout is shown as a typical example.

Electromechanical.WithoutSTOfunction / SIL2.StopCategory0. LabelsEmergency stop,SafetyInterlocks,Contactor,Inverter,Motor; conceptual flow/feedbackarrows only; no wiring validation.

IntegratedSTOFUNCTION / SIL2.StopCategory0. LabelsEmergency stop,SafetyInterlocks,SafetyRelay,E510s,Motor. No systemcertification inference.

Frame1E510s typicalterminal illustration; arrowslabelTM1Powerterminals,TM2Controlterminals,GroundTerminals. Incidental tiny keypad/terminal face glyphs not fully resolved and not used as instructions.

Tiny incidental keypad and terminal face glyphs unresolved; explicit TM1/TM2/Ground callouts transcribed.

L1; L2; L3; T1; T2; T3; P; BR

Manual — SF1/SF2/SG safety terminals and external24V option — page 423

Manual reference: physical PDF page 423. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.2 Control terminals & wiring

Table 3. Safety related terminals

6.3 External 24Vdc supply (Connection option).

Controlterminalstrip shown staggered two rows. Upperlefttoright:R2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2. Lowerlefttoright:S(+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. Callout:SafetyTerminals.SF1/SF2&SG(Common). Removejumperlinkforexternalinterface. Jumpergraphic alignsSF1/SG/SF2; retain depiction, no implementationinference.

External24Vdc connectionoption. Upperstrip:R2A,R2B,R1A,R1B,R1C,[blank],S1,S3,S5,24V,AI1,AI2; lower:S(+),S(-),SF1,SG,SF2,COM,S2,S4,S6,AGND,10V,AO. Externalpowersupplyboxlabels+24V and0V; two depicted contacts andlines. No inferred connector topology or instruction beyond sourcefigure.

SF1/SF2/SG source names retained separately from S1/S2/SC used elsewhere. SG description literally Common terminal for S1,S2; +24VDC remains source rating.

SF1/SF2/SG safety terminals and external24V option

Table 3 Safety related terminals — PDF page 423

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Terminal Symbol Description Rating
2 SF1 Safety Input 1 & SG connection. Open:Safe stop mode. Linked : Normal run mode. Input resistance:4.22kΩ Input Current:5 to 6.5 mA Input Voltage:21.6 to 26.4 V
3 SF2 Safety Input 2 & SG connection.. Open:Safe stop mode. Linked:Normal run mode. Input resistance:4.22kΩ Input Current:5 to 6.5 mA Input Voltage:21.6 to 26.4 V
4 SG Common terminal for S1, S2 +24VDC

Manual — 11-301 safety input logic and electrical-isolation warning — page 424

Manual reference: physical PDF page 424. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

  1. Safety Input logic & Status

TECO 11-301 safety stop function prevents a drive from supplying rotational energy to motors.

Dual safety channels “S1” and “S2” cut off the gate-drive power for IGBT to turn off.

Diagram below shows the basic block diagram design of the safety and interface

for the safety inputs.

Figure 1 11-301 safety stop function diagram

WARNING

The safety stop function does not isolate electrically between drive and motor. To avoid an electric shock hazard, disconnect/isolate power to the drive and verify to ensure that the voltage is zero before performing any work on the motor (refer to your drive’s User Manual for discharging time).

Directives

TECO 11-301 safety stop function meets the following directives and categories:

 ISO13849-1:2008 Category 3/PLd

 IEC62061:2005

 IEC61800-5-2:2007

 IEC61508 SIL2

 IEC60204-1:2006 Stop category 0

Figure1 11-301safetystopfunctiondiagram. LabelsExternalSafetyDeviceApprovedtoSIL2/PLd;Inputpower;S2,V2,S2prime,S2doubleprime;S1,V1,S1prime,S1doubleprime;SC,+24V;CPU;GateDriverIC;GateDriverPhoto;IGBTs;M. Internal circuit lines/symbols preserved by sourceimage; no inferred netlist or certification. DiagramS1/S2/SC labels differ423SF1/SF2/SG.

STO content retained as historical supplier instructions/claims, not safety-system design validation or current certification. Isolation, zero-voltage, risk assessment and stopping-time conditions retained with their context.

Manual — STO installation cautions and environmental conditions — page 425

Manual reference: physical PDF page 425. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

WARNING

The misuse of safety function leads to personal injury or death, property damage, or economic loss. To ensure that the system complies fully with requirement of safety, make a system-level risk assessment. TECO Electric Co. cannot assume responsibility for any system to comply with safety directive.

Installation and wiring

CAUTION

The following information is merely a guide for proper installation.

TECO Electric & Machinery Co. cannot assume responsibility for the compliance or the

noncompliance to any code, national, local or otherwise for the proper installation of this

equipment. A hazard of personal injury and/or equipment damage exists if codes are

ignored during installation.

CAUTION Ensure the safety relay unit and the 11-301 unit is mounted closely in open type and all interconnection wiring is short and protected against open and short circuit faults. Refer EN/ISO13849-1.

Installation

TECO 11-301 safety stop function should be used under following condition and environment.

Table.1 The condition and environment for using safety stop function

STO content retained as historical supplier instructions/claims, not safety-system design validation or current certification. Isolation, zero-voltage, risk assessment and stopping-time conditions retained with their context.

STO installation cautions and environmental conditions

Table 1 The condition and environment for using safety stop function — PDF page 425

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Item Item Condition
2 Temperature range Operation -10°C to +50°C inside distributor (without stick on type dust cover) -10°C to +40°C inside distributor (with stick on type dust cover)
3 Temperature range Storage -20°C to +60°C
4 Ambient humidity Ambient humidity 95%RH maximum (non-condensing)
5 Shock Shock 1G. (9.8m/s²) for 20Hz and below. 0.6G (5.88m/s²) from 20Hz to 50Hz (Compliance with IEC 60068-2-6)
6 Altitude Altitude maximum 1000m above sea level
7 Atmosphere Atmosphere Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
8 Over voltage category Over voltage category II or less
9 Pollution degree Pollution degree II or less
10 Mounting Mounting wall mounting / vertical orientation

Manual — Safety relay, discharge/test warnings and S1/S2/SC terminals — page 426

Manual reference: physical PDF page 426. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

CAUTION

In order to meet safety stop, an approved safety relay unit to ISO13849-1 safety category 3. In addition, all other components with in the safety stop loop shall be ‘safety approved’ types.

WARNING

To avoid an electric shock hazard, insert the magnetic contactor (MC) between power source and drive. Open the contact of MC and keep away from drive for discharging time (refer to your drive’s User Manual for information) before performing any work on the drive. And verify that the voltage on the bus capacitors has discharged before Measure the DC bus voltage at the P(+) and N(-) terminals or test points. (Refer to your drive’s User Manual for locations). The voltage must be zero.

CAUTION To avoid systematic faults, a test even for faulty demands of the safety function has to be performed in order to check the correct function of the monitor signal. This test shall be carried out at system installation, any software changes, parameterization changes, and/or at least once per year. Refer to “Chapter 5 Troubleshooting and Fault Diagnostics”.

Wiring

The safety related terminals are described in Table.2 and Table.3

Table.2 The safety related terminals

STO content retained as historical supplier instructions/claims, not safety-system design validation or current certification. Isolation, zero-voltage, risk assessment and stopping-time conditions retained with their context.

Safety relay, discharge/test warnings and S1/S2/SC terminals

Table 2 The safety related terminals — PDF page 426

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Terminal Symbol Description Rating
2 S1 The function status of S1-SC terminal. Open: In safety stop mode. Short: :Non-safety stop mode. Input resistance:4.22kΩ Input Current:5 to 6.5 mA Input Voltage:21.6 to 26.4 V
3 S2 For function status of S2-SC terminal. Open:In safety stop mode. Short:Non-safety stop mode. Input resistance:4.22kΩ Input Current:5 to 6.5 mA Input Voltage:21.6 to 26.4 V
4 SC Common terminal for S1, S2 terminals. ⟦blank source cell⟧

Manual — Safety input truth table, timings and terminal electric ratings — page 427

Manual reference: physical PDF page 427. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

  1. Safety Input Status

Table below shows the logic level status for external safety interface, internal circuit and drive

output.

Table.3 Truth table of Safety related signals

 The response time from safety stop signal input to drive shutoff is faster than 8ms.

 Hold the ON or OFF status for 1ms or longer to input signal to terminal S1 or S2.

 Signal input shorter than 1ms is not recognized.

Electric ratings of terminals

Truth-table shared ON power supply repeated from actual merged cell. Source marks Detected for all three ON-power states with either safety input OFF. Do not reinterpret these as engineering diagnosis.

Safety input truth table, timings and terminal electric ratings

Table 3 Truth table of Safety related signals — PDF page 427

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 +24VDC Power supply External Safety Input Status External Safety Input Status Internal safety circuit logic Internal safety circuit logic Internal safety circuit logic Internal safety circuit logic Safety Circuit Failure Drive Output Status OFF = Safe State ON= Enabled Motor status
2 +24VDC Power supply SF1-SG SF2-SG S1’ S2’ S1’’ S2’’ Safety Circuit Failure Drive Output Status OFF = Safe State ON= Enabled Motor status
3 OFF - - - - - - - OFF Stop
4 ON OFF OFF L L H H Detected OFF Stop
5 ON OFF ON L H H L Detected OFF Stop
6 ON ON OFF H L L H Detected OFF Stop
7 ON ON ON H H L L - ON Run

Electric ratings of terminals — PDF page 427

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 Model Horsepower Power Specification Voltage (Volt) Current (A)
2 Frame1 0.5/1 200V~240V 600 20
3 Frame1 1/2 380V~480V 600 20
4 Frame2 2/3/5 200V~240V 600 45
5 Frame2 3/5 380V~480V 600 45
6 Frame 3/4 7.5/10/15/20 200V~240V 600 100
7 Frame 3/4 7.5/10/15/20/25 380V~480V 600 165
8 Frame 5 25 200V~240V 600 100
9 Frame 5 30 380V~480V 600 75
10 Frame 6 30/40 200V~240V 600 175
11 Frame 6 40/50/60/75 380V~480V 600 175

Manual — Safety diagnostic, self-test and functionality test procedures — page 428

Manual reference: physical PDF page 428. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Source says Table.5 three times in functionality procedure; nearby PDF427 labels its truth table Table.3. Retain both literal references, with no assertion that Table3 is the intended replacement. 11-301 scope retained.

Diagnostic

Safety stop function protection mechanisms: Safety stop terminal (S1-S2-SC)contact short wire, Disable safety stop mode, Motor running; 1. When S1-SC open and S2-SC short, at this time, protection signal will cut off driver unit enable pin, IGBT none PWM signal, motor free run; 2. Otherwise, When S1-SC short and S2-SC open, at this time, protection signal will cut off driver unit input power, IGBT none PWM signal, motor free run;

  1. Safety stop terminal (S1-S2-SC)contact short wire, the motor running ,When photo-

coupler secondary side of the power supply V1 & V2 occurs suddenly OV or UV, CPU detected abnormal voltage state , sent “LO” signal to NAND logic gate cutting off gate drive enable signals, motor free run.

Self diagnostic test

11-301 does the self-diagnostic test on the power-ON.

If 11-301 output alarm at power-ON, please take the action described in

“Diagnostic” at above.

Test procedure for functionality

As depicted “ATTENTION” in above, the test for the

functionality is important. Please do the test following procedure.

(1) Please make each state of S1-SC and S2-SC depicted at Table.5.

(2) If there is any different state from Table.5, 11-301 has some malfunction.

(3) If there is no different state from Table.5, check the systematic performance,

such as, press the Emergency switch, press the start/restart button at the failure

detected (RUN-SE opened), and so on.

(4) Finally clear the error record of the 11-301 (see the user manual how to clear the

error record).

Functionality test refers Table5 absent in nearby appendix;427truth table is3. Correct intended reference unresolved.

Manual — 11-301 STO design requirements and reliability parameters — page 429

Manual reference: physical PDF page 429. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: PFHD abbreviation explicitly says Probability of Dangerous failure Per hour. Result table still lacks explicit unit columns/PFDAVG definition. Preserve exponents and separate target requirement0.5*10-6 from result1.18x10-8; do not infer PFDAVG meaning or certification.

  1. Safety design and specifications of 11-301

STO design main requirements

Abbreviations:

PFHD/PFDAVG parameter table units and PFDAVG definition not explicit; preserve raw values and PFHD per-hour abbreviation context without invented definitions.

STO content retained as historical supplier instructions/claims, not safety-system design validation or current certification. Isolation, zero-voltage, risk assessment and stopping-time conditions retained with their context.

Superscript exponents rendered -4/-8 preserved in linear strings2.58x10-4/1.18x10-8, not subtraction. RequirementPFHD0.5*10-6 andMTBF100000hours distinct from parameter results.

11-301 STO design requirements and reliability parameters

Safety Function Requirement Specification SIL2 — PDF page 429

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Safety Function Requirement Specification SIL2 Safety Function Requirement Specification SIL2
2 Initiating devices User connected sensor or other safety devices
3 Hazard Rotation of the motor (To be derived from hazard assessment)
4 Consequence Human harm or damage to machinery.
5 Safe State PWM removed, therefore No Voltage output from the drive.
6 Required Action Detect Safe input signals and remove PWM signal.
7 Response Time 8ms (from STO input signal detection to the final action of STO)
8 Target SIL SIL = 2, PL d, category 3
9 Demand Rate High demand rate
10 Mode of Operation Continuous
11 PFHD The PFHD of STO function shall be less than 0.5* 10-6
12 MTBF The MTBF of drive system shall be more than 100,000 hours
13 Trip Mode De-energize to trip
14 MTTR No more than 4 hours (No field repair, only change new board)

STO Parameter / Value — PDF page 429

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Parameter Value
2 PFDAVG 2.58x10-4
3 PFHD 1.18x10-8
4 PL d
5 MTBF 8,096 years
6 DCAVG 84%

Abbreviations — PDF page 429

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 SIL Safety Integrated Level
2 PFHD Probability of Dangerous failure Per hour
3 MTBF Mean Time Between Failures
4 MTTR Mean Time to Repair. ( hour)

Quick setup guide — E510s IP66

Source edition: TECO-E510s-IP66-Quick-Set-up-Guide.pdf. Source key: SRC-9d0c402713fca393. Collected product associations: P009. These attachments do not establish applicability of every model or instruction to every linked product.

Supplier source reference(s):

Use the instructions, warnings, model/voltage/duty conditions and safety requirements of this complete source edition together. Historical dates, contact information and certification statements are preserved as source claims, not confirmation of current validity. Diagram geometry remains in the original document; descriptions do not reconstruct wiring. Navigation headings may combine source words with organisational context and are not uniformly verbatim supplier quotations.

Editorial note: source prose, reviewed tables and bounded diagram-label descriptions are presented together, with their roles identified. Paragraph line wrapping and bullet formatting are normalized. Source wording, source contradictions and edition-specific contacts are retained. References are editorial and do not establish wiring topology.

TECO E510s IP66 - QUICK SET-UP GUIDE

This is a quick set-up guide for configuring the TECO E510s for either of the following control requirements:

Highlighted in the table below are the main parameter groups that are involved in this list of control requirements.

Source table (SRC-9d0c402713fca393-SS17-P1-T1). Generic column labels below are editorial; the first data row retains the supplier headings.

Short Press DSP/FUN to change to Parameter Group

Short press </RESET to move across, press ▲,▼ to change parameter

Short Press READ/ENTER

Source labels and bounded description (SRC-9d0c402713fca393-F0049; PDF 1):

Motor parameter group02: -01 Motor Rated Current(A); -03 Motor Rated Speed(RPM); -05 Motor Rated Power(kW); -06 Motor Rated Frequency(Hz). Short press DSP/FUN; </RESET cursor; short press READ/ENTER.

Original drawing geometry remains authoritative. This description does not reconstruct wiring connections.

Source labels and bounded description (SRC-9d0c402713fca393-F0050; PDF 1):

Group00 /00-02: Keypad0; External Switch1 (Default); Communication2. Short READ/ENTER.

For additional support, please contact us at:

TECO VSD Tech Support: 0433 215 642

Email Address: vsdsupport@teco.com.au

Page - 1

Applicable when

Source labels and bounded description (SRC-9d0c402713fca393-F0051; PDF 2):

Applicable when00-02=1.00-04=0: S1(FWD/STOP),S2(REV/STOP),+24V.00-04=1: S1(RUN/STOP),S2(REV/FWD),+24V.00-04=2: S1(RUN),S2(STOP),S3(FWD/REV),+24V. Three-wire prose requires S2 normally closed contact; original geometry authoritative.

Two external switches are required, one for forward direction and the other for reverse.

Switch type: two positions, maintained type.

Parameter Setup:

Wiring Diagram:

In this mode, two separated momentary push buttons are used for start and stop functions.

For S1 to initiate the Run command. Push button connected to S2 must be connected by a normally closed type contact (NC).

Parameter Setup

Short press </RESET to move across, press ▲,▼ to change parameter number.

Source labels and bounded description (SRC-9d0c402713fca393-F0052; PDF 2):

Group00 /00-05: Keypad(Default)=0; Potentiometer onKeypad=1; ExternalAVI=2. Short READ/ENTER.

Source labels and bounded description (SRC-9d0c402713fca393-F0053; PDF 2):

Frequencyreference; external speed potentiometer=10Kohm; +10V;AVI(0~10V);ACI(0~20mA/4~20mA);AGND. Original figure governs wiring.

Page - 2

The product photograph contains tiny label or nameplate text that has not been transcribed. The original PDF is preserved. Source wording and historical contacts are retained without a claim of current applicability or contact validity.

Parameter groups — PDF page 1

Source column 1 Source column 2
PARAMENTER GROUP No. Description
Group 00 Basic parameter
Group 01 V/F Control parameters
Group 02 IM Motor parameters
Group 03 External digital input and output parameters
Group 04 External analog input and output parameters
Group 05 Multi speed parameters
Group 06 Automatic program operation parameters
Group 07 Start/Stop parameters
Group 08 Protection parameters
Group 09 Communication parameters
Group 10 PID parameters
Group 11 Auxiliary parameters
Group 12 Monitoring parameters
Group 13 Maintenance parameters
Group 14 PLC parameters
Group 15 PLC monitoring parameters
Group 16 LCD parameters
Group 17 Autimatic tuning parameters
Group 18 Slip compensation parameters
Group 19 Speed control parameters
Group 20 Torque and position control parameters
Group 21 PM motor parameters
Group 22 Constant pressure PUMP parameters

Quick setup guide — E510s IP20

Source edition: TECO-E510s-IP20-Quick-Set-up-Guide.pdf. Source key: SRC-c3d8580ff1f1831d. Collected product associations: P009. These attachments do not establish applicability of every model or instruction to every linked product.

Supplier source reference(s):

Use the instructions, warnings, model/voltage/duty conditions and safety requirements of this complete source edition together. Historical dates, contact information and certification statements are preserved as source claims, not confirmation of current validity. Diagram geometry remains in the original document; descriptions do not reconstruct wiring. Navigation headings may combine source words with organisational context and are not uniformly verbatim supplier quotations.

Editorial note: source prose, reviewed tables and bounded diagram-label descriptions are presented together, with their roles identified. Paragraph line wrapping and bullet formatting are normalized. Source wording, source contradictions and edition-specific contacts are retained. References are editorial and do not establish wiring topology.

TECO E510s IP20 - QUICK SET-UP GUIDE

This is a quick set-up guide for configuring the TECO E510s for either of the following control requirements:

Highlighted in the table below are the main parameter groups that are involved in this list of control requirements.

Source table (SRC-c3d8580ff1f1831d-SS17-P1-T1). Generic column labels below are editorial; the first data row retains the supplier headings.

Short Press DSP/FUN to change to Parameter Group

Short press </RESET to move across, press ▲,▼ to change parameter

Short Press READ/ENTER

Source labels and bounded description (SRC-c3d8580ff1f1831d-F0049; PDF 1):

Motor parameter group02: -01 Motor Rated Current(A); -03 Motor Rated Speed(RPM); -05 Motor Rated Power(kW); -06 Motor Rated Frequency(Hz). Short press DSP/FUN; </RESET cursor; short press READ/ENTER.

Original drawing geometry remains authoritative. This description does not reconstruct wiring connections.

Source labels and bounded description (SRC-c3d8580ff1f1831d-F0050; PDF 1):

Group00 /00-02: Keypad0; External Switch1 (Default); Communication2. Short READ/ENTER.

For additional support, please contact us at:

TECO VSD Tech Support: 0433 215 642

Email Address: vsdsupport@teco.com.au

Page - 1

Applicable when

Source labels and bounded description (SRC-c3d8580ff1f1831d-F0051; PDF 2):

Applicable when00-02=1.00-04=0: S1(FWD/STOP),S2(REV/STOP),+24V.00-04=1: S1(RUN/STOP),S2(REV/FWD),+24V.00-04=2: S1(RUN),S2(STOP),S3(FWD/REV),+24V. Three-wire prose requires S2 normally closed contact; original geometry authoritative.

Two external switches are required, one for forward direction and the other for reverse.

Switch type: two positions, maintained type.

Parameter Setup:

Wiring Diagram:

In this mode, two separated momentary push buttons are used for start and stop functions.

For S1 to initiate the Run command. Push button connected to S2 must be connected by a normally closed type contact (NC).

Parameter Setup

Short press </RESET to move across, press ▲,▼ to change parameter number.

Source labels and bounded description (SRC-c3d8580ff1f1831d-F0052; PDF 2):

Group00 /00-05: Keypad(Default)=0; Potentiometer onKeypad=1; ExternalAVI=2. Short READ/ENTER.

Source labels and bounded description (SRC-c3d8580ff1f1831d-F0053; PDF 2):

Frequencyreference; external speed potentiometer=10Kohm; +10V;AVI(0~10V);ACI(0~20mA/4~20mA);AGND. Original figure governs wiring.

Page - 2

The product photograph contains tiny label or nameplate text that has not been transcribed. The original PDF is preserved. Source wording and historical contacts are retained without a claim of current applicability or contact validity.

Parameter groups — PDF page 1

Source column 1 Source column 2
PARAMENTER GROUP No. Description
Group 00 Basic parameter
Group 01 V/F Control parameters
Group 02 IM Motor parameters
Group 03 External digital input and output parameters
Group 04 External analog input and output parameters
Group 05 Multi speed parameters
Group 06 Automatic program operation parameter
Group 07 Start/Stop parameters
Group 08 Protection parameters
Group 09 Communication parameters
Group 10 PID parameters
Group 11 Auxiliary parameters
Group 12 Monitoring parameters
Group 13 Maintenance parameters
Group 14 PLC parameters
Group 15 PLC monitoring parameters
Group 16 LCD parameters
Group 17 Autimatic tuning parameters
Group 18 Slip compensation parameters
Group 19 Speed control parameters
Group 20 Torque and position control parameters
Group 21 PM motor parameters
Group 22 Constant pressure PUMP parameters

Technical source 001 — Variable speed drive E510-2P2-SH1F-IP20/ 0.4KW/ 0.5HP/ 200-240V

Source download: DataSheet_of_E510-2P2-SH1F-IP20.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-2P2-SH1F-IP20/ 0.4KW/ 0.5HP/ 200-240V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 1 / 1 Variable Torque (kW/A): 0.4 / 3.1; Supply: 200-240V 1PH; IP Rating: 20; kW Rating: 0.40 Datasheet PDF / DataSheet_of_E510-2P2-SH1F-IP20.pdf

P009 / Variable speed drive E510-2P2-SH1F-IP20/ 0.4KW/ 0.5HP/ 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 0.5 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 0.4 as printed in field/value —
Rated Output Current(A) 3.1 as printed in field/value —
Rated Capacity(KVA) 1.2 as printed in field/value —
Input Voltage Range(V) Single-phase 200~ 240V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~240V as printed in field/value —
Input current(A) 8.5 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ), as printed in field/value —
Main Control Features / Control 4 of S curve setting. as printed in field/value —

P009 / Variable speed drive E510-2P2-SH1F-IP20/ 0.4KW/ 0.5HP/ 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction Input 35 functions (refer to group3 in the manual). as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse, and etc. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Over Voltage 200V class :DC>410V, as printed in field/value —
Protective Functions / Under Voltage 200V class :DC<190V, as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Protective Functions / brake transistor Built in. as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), Acceleration : 2G (50Hz to 150Hz), (According to IEC60068-2-6 standard). as printed in field/value —
Environment / Enclosure IP20/NEMA1. as printed in field/value —

P009 / Variable speed drive E510-2P2-SH1F-IP20/ 0.4KW/ 0.5HP/ 200-240V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-2P2-SH1F-IP20/ 0.4KW/ 0.5HP/ 200-240V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 D E t Q Net Weight in kg/(lbs) Conditions
E510-2P2-SH1F 90.6 (3.57) mm (inch) 80.5 (3.17) mm (inch) 80.5 (3.17) mm (inch) 164 (6.46) mm (inch) 153 (6.02) mm (inch) 151.4 (5.96) mm (inch) 47 (1.85) mm (inch) 5 (0.19) mm (inch) M4 mm (inch) 1.7/(3.8) mm (inch) —

Technical source 002 — Variable speed drive E510-201-SH1F-IP20/ 0.75KW/ 1HP/ 200-240V

Source download: datasheet-38-1.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-201-SH1F-IP20/ 0.75KW/ 1HP/ 200-240V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 2 / 2 Variable Torque (kW/A): 0.75 / 4.5; Supply: 200-240V 1PH; IP Rating: 20; kW Rating: 0.75 Datasheet PDF / datasheet-38-1.pdf
90 / 2 / 2 Variable Torque (kW/A): 0.75 / 4.5; Supply: 200-240V 1PH; IP Rating: 20; kW Rating: 0.75 Drawings PDF / datasheet-38-1.pdf

P009 / Variable speed drive E510-201-SH1F-IP20/ 0.75KW/ 1HP/ 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 1 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 0.75 as printed in field/value —
Rated Output Current(A) 4.5 as printed in field/value —
Rated Capacity(KVA) 1.7 as printed in field/value —
Input Voltage Range(V) Single-phase 200~ 240V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~240V as printed in field/value —
Input current(A) 12 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ), as printed in field/value —
Main Control Features / Control 4 of S curve setting. as printed in field/value —

P009 / Variable speed drive E510-201-SH1F-IP20/ 0.75KW/ 1HP/ 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction Input 35 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Relay Output 22 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual). as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse, and etc. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Over Voltage 200V class :DC>410V, as printed in field/value —
Protective Functions / Under Voltage 200V class :DC<190V, as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Protective Functions / brake transistor Built in. as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), Acceleration : 2G (50Hz to 150Hz), (According to IEC60068-2-6 standard). as printed in field/value —
Environment / Enclosure IP20/NEMA1. as printed in field/value —

P009 / Variable speed drive E510-201-SH1F-IP20/ 0.75KW/ 1HP/ 200-240V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-201-SH1F-IP20/ 0.75KW/ 1HP/ 200-240V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 D E t Q Net Weight in kg/(lbs) Conditions
E510-201-SH1F 90.6 (3.57) mm (inch) 80.5 (3.17) mm (inch) 80.5 (3.17) mm (inch) 164 (6.46) mm (inch) 153 (6.02) mm (inch) 151.4 (5.96) mm (inch) 47 (1.85) mm (inch) 5 (0.19) mm (inch) M4 mm (inch) 1.7/(3.8) mm (inch) —

Technical source 003 — Variable speed drive E510-202-SH1F-IP20/ 1.5KW/ 2HP/ 200-240V

Source download: datasheet-39-1.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-202-SH1F-IP20/ 1.5KW/ 2HP/ 200-240V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 3 / 3 Variable Torque (kW/A): 1.5 / 7.5; Supply: 200-240V 1PH; IP Rating: 20; kW Rating: 1.50 Datasheet PDF / datasheet-39-1.pdf
90 / 3 / 3 Variable Torque (kW/A): 1.5 / 7.5; Supply: 200-240V 1PH; IP Rating: 20; kW Rating: 1.50 Drawings PDF / datasheet-39-1.pdf

P009 / Variable speed drive E510-202-SH1F-IP20/ 1.5KW/ 2HP/ 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 2 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 1.5 as printed in field/value —
Rated Output Current(A) 7.5 as printed in field/value —
Rated Capacity(KVA) 2.9 as printed in field/value —
Input Voltage Range(V) Single-phase 200~ 240V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~240V as printed in field/value —
Input current(A) 16 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ), as printed in field/value —
Main Control Features / Control 4 of S curve setting. as printed in field/value —

P009 / Variable speed drive E510-202-SH1F-IP20/ 1.5KW/ 2HP/ 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction Input 35 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Relay Output 22 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual). as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse, and etc. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Over Voltage 200V class :DC>410V, as printed in field/value —
Protective Functions / Under Voltage 200V class :DC<190V, as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Protective Functions / brake transistor Built in. as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), Acceleration : 2G (50Hz to 150Hz), (According to IEC60068-2-6 standard). as printed in field/value —
Environment / Enclosure IP20/NEMA1. as printed in field/value —

P009 / Variable speed drive E510-202-SH1F-IP20/ 1.5KW/ 2HP/ 200-240V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-202-SH1F-IP20/ 1.5KW/ 2HP/ 200-240V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 D D1 E t Q Net Weight in kg/(lbs) Conditions
E510-202-SH1F 128.7 (5.07) mm (inch) 118 (4.65) mm (inch) 118 (4.65) mm (inch) 187.6 (7.39) mm (inch) 177.6 (6.99) mm (inch) 197.5 (7.78) mm (inch) 152.4 (6) mm (inch) 147.4 (5.8) mm (inch) 48.2 (1.9) mm (inch) 5 (0.19) mm (inch) M4 mm (inch) 2.5/ (5.51) mm (inch) —

Technical source 004 — Variable speed drive E510-203-SH1F-IP20/ 2.2KW/ 3HP/ 200-240V

Source download: datasheet-40-1.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-203-SH1F-IP20/ 2.2KW/ 3HP/ 200-240V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 4 / 4 Variable Torque (kW/A): 2.2 / 10.5; Supply: 200-240V 1PH; IP Rating: 20; kW Rating: 2.20 Datasheet PDF / datasheet-40-1.pdf
90 / 4 / 4 Variable Torque (kW/A): 2.2 / 10.5; Supply: 200-240V 1PH; IP Rating: 20; kW Rating: 2.20 Drawings PDF / datasheet-40-1.pdf

P009 / Variable speed drive E510-203-SH1F-IP20/ 2.2KW/ 3HP/ 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 3 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 2.2 as printed in field/value —
Rated Output Current(A) 10.5 as printed in field/value —
Rated Capacity(KVA) 4.0 as printed in field/value —
Input Voltage Range(V) Single-phase 200~ 240V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~240V as printed in field/value —
Input current(A) 23.9 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ), as printed in field/value —
Main Control Features / Control 4 of S curve setting. as printed in field/value —

P009 / Variable speed drive E510-203-SH1F-IP20/ 2.2KW/ 3HP/ 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction Input 35 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Relay Output 22 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual). as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse, and etc. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Over Voltage 200V class :DC>410V, as printed in field/value —
Protective Functions / Under Voltage 200V class :DC<190V, as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Protective Functions / brake transistor Built in. as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), Acceleration : 2G (50Hz to 150Hz), (According to IEC60068-2-6 standard). as printed in field/value —
Environment / Enclosure IP20/NEMA1. as printed in field/value —

P009 / Variable speed drive E510-203-SH1F-IP20/ 2.2KW/ 3HP/ 200-240V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-203-SH1F-IP20/ 2.2KW/ 3HP/ 200-240V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 D D1 E t Q Net Weight in kg/(lbs) Conditions
E510-203-SH1F 128.7 (5.07) mm (inch) 118 (4.65) mm (inch) 118 (4.65) mm (inch) 187.6 (7.39) mm (inch) 177.6 (6.99) mm (inch) 197.5 (7.78) mm (inch) 152.4 (6) mm (inch) 147.4 (5.8) mm (inch) 48.2 (1.9) mm (inch) 5 (0.19) mm (inch) M4 mm (inch) 2.5/ (5.51) mm (inch) —

Technical source 005 — Variable speed drive E510-201-H1FN4S-IP66/NEMA 4X, 0.75KW, 1HP, 200-240V

Source download: DataSheet_of_E510-201-H1FN4S.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Wiring diagram: use the original source page, including its notes. Text order does not establish electrical connections.

Dimensions by printed model — P009, Variable speed drive E510-201-H1FN4S-IP66/NEMA 4X, 0.75KW, 1HP, 200-240V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 5 / 5 Variable Torque (kW/A): 0.75 / 7.5; Supply: 200-240V 1PH; IP Rating: 66; kW Rating: 0.75 Datasheet PDF / DataSheet_of_E510-201-H1FN4S.pdf

P009 / Variable speed drive E510-201-H1FN4S-IP66/NEMA 4X, 0.75KW, 1HP, 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510 as printed in field/value —
Horse Power(HP) 1 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 0.75 as printed in field/value —
Rated Output Current(A) 4.5 as printed in field/value —
Rated Capacity(KVA) 1.7 as printed in field/value —
Input Voltage Range(V) Single-phase 200~ 240V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~240V as printed in field/value —
Input current(A) 12 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 66/NEMA 4X as printed in field/value —
Control Mode V/F Control, Vector Control as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F),150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the keypad External Input Terminals: AI1(0/2~10V), AI2(0/4~20mA)input Multifunction input up/down function(Group3) Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad run, stop button External terminals: Multi- operation-mode(2 or3 wire selection) Jog operation Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 18 fixed curves and one customized curve as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting(0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ) as printed in field/value —
Main Control Features / Control 4 sections of S curve setting as printed in field/value —
Main Control Features / Multifunction Input 29 functions (refer to group3 in the manual) as printed in field/value —

P009 / Variable speed drive E510-201-H1FN4S-IP66/NEMA 4X, 0.75KW, 1HP, 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction / Output 21 functions (refer to group3 in the manual) as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual) as printed in field/value —
Main Features Overload Detection,16 preset speeds, Auto-run, Acc/Dec Switch (2 Stages),Main/Alt run Command select, Main/Alt Frequency Command select, PID control, Torque boost, V/F start Frequency, Slip frequency, Fault reset as printed in field/value —
Display / LED Display :parameter / parameter value / frequency / line speed / DC voltage / output voltage / output current / PID feedback / input and output terminal status / Heat sink temperature / Program Version / Fault Log as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse ,and etc. as printed in field/value —
Protective Functions / Overload Protection The relays to protect the motor and the inverter. (150%/1min) as printed in field/value —
Protective Functions / Over Voltage 200V class :>410V , 400V class:>820V as printed in field/value —
Protective Functions / Under Voltage 200V class :<190V , 400V class:<380V as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, The carrier frequency decreasing with the temperature function, fault output, reverse prohibit, prohibit for direct start after power up and error recovery ,parameter lock up as printed in field/value —
Protective Functions / brake transistor Built in as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) (Compliance with IEC 60068 -2-78) as printed in field/value —
Environment / Shock 20Hz or less 1G(9.8m/s²)20~50Hz 0.6G(5.88m/s²) (Compliance with IEC 60068 -2-6) as printed in field/value —
Environment / Enclosure IP20/NEMA1 and IP66/NEMA4X as printed in field/value —

P009 / Variable speed drive E510-201-H1FN4S-IP66/NEMA 4X, 0.75KW, 1HP, 200-240V — source page 5 — PDF page 5

Configuration / printed row W W1 H H1 H2 D NW in kg Conditions
E510-201-H1FN4S 150.8 (5.94) mm (inch) 133.3 (5.25) mm (inch) 248.7 (9.79) mm (inch) 230.2 (9.06) mm (inch) 214.2 (8.43) mm (inch) 183 (7.20) mm (inch) 2.9 kg —

Technical source 006 — Variable speed drive E510-202-H1FN4S-IP66/NEMA 4X, 1.5KW, 2HP, 200-240V

Source download: DataSheet_of_E510-202-H1FN4S.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Wiring diagram: use the original source page, including its notes. Text order does not establish electrical connections.

Dimensions by printed model — P009, Variable speed drive E510-202-H1FN4S-IP66/NEMA 4X, 1.5KW, 2HP, 200-240V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 6 / 6 Variable Torque (kW/A): 1.5 / 7.5; Supply: 200-240V 1PH; IP Rating: 66; kW Rating: 1.50 Datasheet PDF / DataSheet_of_E510-202-H1FN4S.pdf

P009 / Variable speed drive E510-202-H1FN4S-IP66/NEMA 4X, 1.5KW, 2HP, 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510 as printed in field/value —
Horse Power(HP) 2 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 1.5 as printed in field/value —
Rated Output Current(A) 7.5 as printed in field/value —
Rated Capacity(KVA) 2.9 as printed in field/value —
Input Voltage Range(V) Single-phase 200~ 240V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~240V as printed in field/value —
Input current(A) 16 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 66/NEMA 4X as printed in field/value —
Control Mode V/F Control, Vector Control as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F),150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the keypad External Input Terminals: AI1(0/2~10V), AI2(0/4~20mA)input Multifunction input up/down function(Group3) Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad run, stop button External terminals: Multi- operation-mode(2 or3 wire selection) Jog operation Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 18 fixed curves and one customized curve as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting(0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ) as printed in field/value —
Main Control Features / Control 4 sections of S curve setting as printed in field/value —
Main Control Features / Multifunction Input 29 functions (refer to group3 in the manual) as printed in field/value —

P009 / Variable speed drive E510-202-H1FN4S-IP66/NEMA 4X, 1.5KW, 2HP, 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction / Output 21 functions (refer to group3 in the manual) as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual) as printed in field/value —
Main Features Overload Detection,16 preset speeds, Auto-run, Acc/Dec Switch (2 Stages),Main/Alt run Command select, Main/Alt Frequency Command select, PID control, Torque boost, V/F start Frequency, Slip frequency, Fault reset as printed in field/value —
Display / LED Display :parameter / parameter value / frequency / line speed / DC voltage / output voltage / output current / PID feedback / input and output terminal status / Heat sink temperature / Program Version / Fault Log as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse ,and etc. as printed in field/value —
Protective Functions / Overload Protection The relays to protect the motor and the inverter. (150%/1min) as printed in field/value —
Protective Functions / Over Voltage 200V class :>410V , 400V class:>820V as printed in field/value —
Protective Functions / Under Voltage 200V class :<190V , 400V class:<380V as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, The carrier frequency decreasing with the temperature function, fault output, reverse prohibit, prohibit for direct start after power up and error recovery ,parameter lock up as printed in field/value —
Protective Functions / brake transistor Built in as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) (Compliance with IEC 60068 -2-78) as printed in field/value —
Environment / Shock 20Hz or less 1G(9.8m/s²)20~50Hz 0.6G(5.88m/s²) (Compliance with IEC 60068 -2-6) as printed in field/value —
Environment / Enclosure IP20/NEMA1 and IP66/NEMA4X as printed in field/value —

P009 / Variable speed drive E510-202-H1FN4S-IP66/NEMA 4X, 1.5KW, 2HP, 200-240V — source page 5 — PDF page 5

Configuration / printed row W W1 H H1 H2 D NW in kg Conditions
E510-202-H1FN4S 198 (7.80) mm (inch) 115 (4.53) mm (inch) 335 (13.19) mm (inch) 315 (12.40) mm (inch) 337.9 (13.30) mm (inch) 218.4 (8.60) mm (inch) 5.98 kg —

Technical source 007 — Variable speed drive E510-401-SH3F-IP20/ 0.75KW/ 1HP/ 380-480V

Source download: datasheet-41-2.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-401-SH3F-IP20/ 0.75KW/ 1HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 7 / 7 Variable Torque (kW/A): 0.75 / 2.5; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 0.75 Datasheet PDF / datasheet-41-2.pdf
90 / 7 / 7 Variable Torque (kW/A): 0.75 / 2.5; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 0.75 Drawings PDF / datasheet-41-2.pdf

P009 / Variable speed drive E510-401-SH3F-IP20/ 0.75KW/ 1HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 1 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 0.75 as printed in field/value —
Rated Output Current(A) 2.5 as printed in field/value —
Rated Capacity(KVA) 1.7 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 4.2 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ), as printed in field/value —
Main Control Features / Control 4 of S curve setting. as printed in field/value —

P009 / Variable speed drive E510-401-SH3F-IP20/ 0.75KW/ 1HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction Input 35 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Relay Output 22 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual). as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse, and etc. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Over Voltage 400V class :DC>820V, as printed in field/value —
Protective Functions / Under Voltage 400V class :DC<380V as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Protective Functions / brake transistor Built in. as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), Acceleration : 2G (50Hz to 150Hz), (According to IEC60068-2-6 standard). as printed in field/value —
Environment / Enclosure IP20/NEMA1. as printed in field/value —

P009 / Variable speed drive E510-401-SH3F-IP20/ 0.75KW/ 1HP/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-401-SH3F-IP20/ 0.75KW/ 1HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 D E t Q Net Weight in kg/(lbs) Conditions
E510-401-SH3F 90.6 (3.57) mm (inch) 80.5 (3.17) mm (inch) 80.5 (3.17) mm (inch) 164 (6.46) mm (inch) 153 (6.02) mm (inch) 151.4 (5.96) mm (inch) 47 (1.85) mm (inch) 5 (0.19) mm (inch) M4 mm (inch) 1.7/(3.8) mm (inch) —

Technical source 008 — Variable speed drive E510-402-SH3F-IP20/ 1.5KW/ 2HP/ 380-480V

Source download: datasheet-42-2.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-402-SH3F-IP20/ 1.5KW/ 2HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 8 / 8 Variable Torque (kW/A): 1.5 / 3.8; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 1.50 Datasheet PDF / datasheet-42-2.pdf
90 / 8 / 8 Variable Torque (kW/A): 1.5 / 3.8; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 1.50 Drawings PDF / datasheet-42-2.pdf

P009 / Variable speed drive E510-402-SH3F-IP20/ 1.5KW/ 2HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 2 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 1.5 as printed in field/value —
Rated Output Current(A) 3.8 as printed in field/value —
Rated Capacity(KVA) 2.9 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 5.6 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ), as printed in field/value —
Main Control Features / Control 4 of S curve setting. as printed in field/value —

P009 / Variable speed drive E510-402-SH3F-IP20/ 1.5KW/ 2HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction Input 35 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Relay Output 22 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual). as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse, and etc. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Over Voltage 400V class :DC>820V, as printed in field/value —
Protective Functions / Under Voltage 400V class :DC<380V, as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Protective Functions / brake transistor Built in. as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), Acceleration : 2G (50Hz to 150Hz), (According to IEC60068-2-6 standard). as printed in field/value —
Environment / Enclosure IP20/NEMA1. as printed in field/value —

P009 / Variable speed drive E510-402-SH3F-IP20/ 1.5KW/ 2HP/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-402-SH3F-IP20/ 1.5KW/ 2HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 D E t Q Net Weight in kg/(lbs) Conditions
E510-402-SH3F 90.6 (3.57) mm (inch) 80.5 (3.17) mm (inch) 80.5 (3.17) mm (inch) 164 (6.46) mm (inch) 153 (6.02) mm (inch) 151.4 (5.96) mm (inch) 47 (1.85) mm (inch) 5 (0.19) mm (inch) M4 mm (inch) 1.7/(3.8) mm (inch) —

Technical source 009 — Variable speed drive E510-403-SH3F-IP20/ 2.2KW/ 3HP/ 380-480V

Source download: datasheet-43-2.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-403-SH3F-IP20/ 2.2KW/ 3HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 9 / 9 Variable Torque (kW/A): 2.2 / 5.3; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 2.20 Datasheet PDF / datasheet-43-2.pdf
90 / 9 / 9 Variable Torque (kW/A): 2.2 / 5.3; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 2.20 Drawings PDF / datasheet-43-2.pdf

P009 / Variable speed drive E510-403-SH3F-IP20/ 2.2KW/ 3HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 3 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 2.2 as printed in field/value —
Rated Output Current(A) 5.3 as printed in field/value —
Rated Capacity(KVA) 4.0 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 7.3 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ), as printed in field/value —
Main Control Features / Control 4 of S curve setting. as printed in field/value —

P009 / Variable speed drive E510-403-SH3F-IP20/ 2.2KW/ 3HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction Input 35 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Relay Output 22 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual). as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse, and etc. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Over Voltage 400V class :DC>820V, as printed in field/value —
Protective Functions / Under Voltage 400V class :DC<380V, as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Protective Functions / brake transistor Built in. as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), Acceleration : 2G (50Hz to 150Hz), (According to IEC60068-2-6 standard). as printed in field/value —
Environment / Enclosure IP20/NEMA1. as printed in field/value —

P009 / Variable speed drive E510-403-SH3F-IP20/ 2.2KW/ 3HP/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-403-SH3F-IP20/ 2.2KW/ 3HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 D D1 E t Q Net Weight in kg/(lbs) Conditions
E510-403-SH3F 128.7 (5.07) mm (inch) 118 (4.65) mm (inch) 118 (4.65) mm (inch) 187.6 (7.39) mm (inch) 177.6 (6.99) mm (inch) 197.5 (7.78) mm (inch) 152.4 (6) mm (inch) 147.4 (5.8) mm (inch) 48.2 (1.9) mm (inch) 5 (0.19) mm (inch) M4 mm (inch) 2.5/ (5.51) mm (inch) —

Technical source 010 — Variable speed drive E510-405-SH3F-IP20/ 4KW/ 5HP/ 380-480V

Source download: datasheet-44-2.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-405-SH3F-IP20/ 4KW/ 5HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 10 / 10 Variable Torque (kW/A): 4.0 / 9.2; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 4.00 Datasheet PDF / datasheet-44-2.pdf
90 / 10 / 10 Variable Torque (kW/A): 4.0 / 9.2; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 4.00 Drawings PDF / datasheet-44-2.pdf

P009 / Variable speed drive E510-405-SH3F-IP20/ 4KW/ 5HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 5 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 4.0 as printed in field/value —
Rated Output Current(A) 9.2 as printed in field/value —
Rated Capacity(KVA) 6.7 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 11.6 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ), as printed in field/value —
Main Control Features / Control 4 of S curve setting. as printed in field/value —

P009 / Variable speed drive E510-405-SH3F-IP20/ 4KW/ 5HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction Input 35 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Relay Output 22 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual). as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse, and etc. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Over Voltage 400V class :DC>820V, as printed in field/value —
Protective Functions / Under Voltage 400V class :DC<380V, as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Protective Functions / brake transistor Built in. as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), Acceleration : 2G (50Hz to 150Hz), (According to IEC60068-2-6 standard). as printed in field/value —
Environment / Enclosure IP20/NEMA1. as printed in field/value —

P009 / Variable speed drive E510-405-SH3F-IP20/ 4KW/ 5HP/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-405-SH3F-IP20/ 4KW/ 5HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 D D1 E t Q Net Weight in kg/(lbs) Conditions
E510-405-SH3F 128.7 (5.07) mm (inch) 118 (4.65) mm (inch) 118 (4.65) mm (inch) 187.6 (7.39) mm (inch) 177.6 (6.99) mm (inch) 197.5 (7.78) mm (inch) 152.4 (6) mm (inch) 147.4 (5.8) mm (inch) 48.2 (1.9) mm (inch) 5 (0.19) mm (inch) M4 mm (inch) 2.5/ (5.51) mm (inch) —

Technical source 011 — Variable speed drive E510-408-SH3F-IP20/ 5.5KW/ 7.5HP/ 380-480V

Source download: datasheet-45-2.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-408-SH3F-IP20/ 5.5KW/ 7.5HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 11 / 11 Variable Torque (kW/A): 5.5 / 13; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 5.50 Datasheet PDF / datasheet-45-2.pdf
90 / 11 / 11 Variable Torque (kW/A): 5.5 / 13; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 5.50 Drawings PDF / datasheet-45-2.pdf

P009 / Variable speed drive E510-408-SH3F-IP20/ 5.5KW/ 7.5HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 7.5 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 5.5 as printed in field/value —
Rated Output Current(A) 13 as printed in field/value —
Rated Capacity(KVA) 9.9 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 17 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —

P009 / Variable speed drive E510-408-SH3F-IP20/ 5.5KW/ 7.5HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Deceleration Sec ), as printed in field/value —
Control 4 of S curve setting. as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), as printed in field/value —

P009 / Variable speed drive E510-408-SH3F-IP20/ 5.5KW/ 7.5HP/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-408-SH3F-IP20/ 5.5KW/ 7.5HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 D D1 E t Q Net Weight in kg/(lbs) Conditions
E510-408-SH3F 186.9 (7.36) mm (inch) 175 (6.89) mm (inch) 176 (6.93) mm (inch) 260.9 (10.27) mm (inch) 249.8 (9.83) mm (inch) 273 (10.75) mm (inch) 202.6 (7.98) mm (inch) 197.6 (7.78) mm (inch) 76.7 (3.02) mm (inch) 6.5 (0.26) mm (inch) M4 mm (inch) 6.7/ (14.8) mm (inch) —

Technical source 012 — Variable speed drive E510-410-SH3F-IP20/ 7.5KW/ 10HP/ 380-480V

Source download: datasheet-46-2.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-410-SH3F-IP20/ 7.5KW/ 10HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 12 / 12 Variable Torque (kW/A): 7.5 / 17.5; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 7.50 Datasheet PDF / datasheet-46-2.pdf
90 / 12 / 12 Variable Torque (kW/A): 7.5 / 17.5; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 7.50 Drawings PDF / datasheet-46-2.pdf

P009 / Variable speed drive E510-410-SH3F-IP20/ 7.5KW/ 10HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 10 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 7.5 as printed in field/value —
Rated Output Current(A) 17.5 as printed in field/value —
Rated Capacity(KVA) 13.3 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 23 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —

P009 / Variable speed drive E510-410-SH3F-IP20/ 7.5KW/ 10HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Deceleration Sec ), as printed in field/value —
Control 4 of S curve setting. as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), as printed in field/value —

P009 / Variable speed drive E510-410-SH3F-IP20/ 7.5KW/ 10HP/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-410-SH3F-IP20/ 7.5KW/ 10HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 D D1 E t Q Net Weight in kg/(lbs) Conditions
E510-410-SH3F 186.9 (7.36) mm (inch) 175 (6.89) mm (inch) 176 (6.93) mm (inch) 260.9 (10.27) mm (inch) 249.8 (9.83) mm (inch) 273 (10.75) mm (inch) 202.6 (7.98) mm (inch) 197.6 (7.78) mm (inch) 76.7 (3.02) mm (inch) 6.5 (0.26) mm (inch) M4 mm (inch) 6.7/ (14.8) mm (inch) —

Technical source 013 — Variable speed drive E510-415-SH3F-IP20/ 11KW/ 15HP/ 380-480V

Source download: datasheet-47-2.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-415-SH3F-IP20/ 11KW/ 15HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 13 / 13 Variable Torque (kW/A): 11 / 24; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 11.00 Datasheet PDF / datasheet-47-2.pdf
90 / 13 / 13 Variable Torque (kW/A): 11 / 24; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 11.00 Drawings PDF / datasheet-47-2.pdf

P009 / Variable speed drive E510-415-SH3F-IP20/ 11KW/ 15HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 15 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 11 as printed in field/value —
Rated Output Current(A) 24 as printed in field/value —
Rated Capacity(KVA) 19.1 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 31 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ), as printed in field/value —
Main Control Features / Control 4 of S curve setting. as printed in field/value —

P009 / Variable speed drive E510-415-SH3F-IP20/ 11KW/ 15HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction Input 35 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Relay Output 22 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual). as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse, and etc. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Over Voltage 400V class :DC>820V, as printed in field/value —
Protective Functions / Under Voltage 400V class :DC<380V, as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Protective Functions / brake transistor Built in. as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), Acceleration : 2G (50Hz to 150Hz), (According to IEC60068-2-6 standard). as printed in field/value —
Environment / Enclosure IP20/NEMA1. as printed in field/value —

P009 / Variable speed drive E510-415-SH3F-IP20/ 11KW/ 15HP/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-415-SH3F-IP20/ 11KW/ 15HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 D D1 E t Q Net Weight in kg/(lbs) Conditions
E510-415-SH3F 186.9 (7.36) mm (inch) 175 (6.89) mm (inch) 176 (6.93) mm (inch) 260.9 (10.27) mm (inch) 249.8 (9.83) mm (inch) 273 (10.75) mm (inch) 202.6 (7.98) mm (inch) 197.6 (7.78) mm (inch) 76.7 (3.02) mm (inch) 6.5 (0.26) mm (inch) M4 mm (inch) 6.7/ (14.8) mm (inch) —

Technical source 014 — Variable speed drive E510-420-SH3F-IP20/ 15KW/ 20HP/ 380-480V

Source download: datasheet-48-2.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-420-SH3F-IP20/ 15KW/ 20HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 14 / 14 Variable Torque (kW/A): 15 / 32; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 15.00 Datasheet PDF / datasheet-48-2.pdf
90 / 14 / 14 Variable Torque (kW/A): 15 / 32; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 15.00 Drawings PDF / datasheet-48-2.pdf

P009 / Variable speed drive E510-420-SH3F-IP20/ 15KW/ 20HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 20 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 15 as printed in field/value —
Rated Output Current(A) 32 as printed in field/value —
Rated Capacity(KVA) 24 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 38 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ), as printed in field/value —
Main Control Features / Control 4 of S curve setting. as printed in field/value —

P009 / Variable speed drive E510-420-SH3F-IP20/ 15KW/ 20HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction Input 35 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Relay Output 22 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual). as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse, and etc. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Over Voltage 400V class :DC>820V, as printed in field/value —
Protective Functions / Under Voltage 400V class :DC<380V, as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Protective Functions / brake transistor Built in. as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), Acceleration : 2G (50Hz to 150Hz), (According to IEC60068-2-6 standard). as printed in field/value —
Environment / Enclosure IP20/NEMA1. as printed in field/value —

P009 / Variable speed drive E510-420-SH3F-IP20/ 15KW/ 20HP/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-420-SH3F-IP20/ 15KW/ 20HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 D D1 E t Q Net Weight in kg/(lbs) Conditions
E510-420-SH3F 224.6 (8.84) mm (inch) 207 (8.15) mm (inch) 207 (8.15) mm (inch) 321.6 (12.66) mm (inch) 303.5 (11.95) mm (inch) 330.9 (13.03) mm (inch) 206.1 (8.11) mm (inch) 201.1 (7.92) mm (inch) 94 (3.7) mm (inch) 8 (0.31) mm (inch) M4 mm (inch) 10.5/ (23.2) mm (inch) —

Technical source 015 — Variable speed drive E510-425-SH3F-IP20/ 18.5KW/ 25HP/ 380-480V

Source download: datasheet-49-2.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-425-SH3F-IP20/ 18.5KW/ 25HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 15 / 15 Variable Torque (kW/A): 18.5 / 40; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 18.50 Datasheet PDF / datasheet-49-2.pdf
90 / 15 / 15 Variable Torque (kW/A): 18.5 / 40; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 18.50 Drawings PDF / datasheet-49-2.pdf

P009 / Variable speed drive E510-425-SH3F-IP20/ 18.5KW/ 25HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 25 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 18.5 as printed in field/value —
Rated Output Current(A) 40 as printed in field/value —
Rated Capacity(KVA) 30.5 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 48 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ), as printed in field/value —
Main Control Features / Control 4 of S curve setting. as printed in field/value —

P009 / Variable speed drive E510-425-SH3F-IP20/ 18.5KW/ 25HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction Input 35 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Relay Output 22 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual). as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse, and etc. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Over Voltage 400V class :DC>820V, as printed in field/value —
Protective Functions / Under Voltage 400V class :DC<380V, as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Protective Functions / brake transistor Built in. as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), Acceleration : 2G (50Hz to 150Hz), (According to IEC60068-2-6 standard). as printed in field/value —
Environment / Enclosure IP20/NEMA1. as printed in field/value —

P009 / Variable speed drive E510-425-SH3F-IP20/ 18.5KW/ 25HP/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-425-SH3F-IP20/ 18.5KW/ 25HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 D D1 E t Q Net Weight in kg/(lbs) Conditions
E510-425-SH3F 224.6 (8.84) mm (inch) 207 (8.15) mm (inch) 207 (8.15) mm (inch) 321.6 (12.66) mm (inch) 303.5 (11.95) mm (inch) 330.9 (13.03) mm (inch) 206.1 (8.11) mm (inch) 201.1 (7.92) mm (inch) 94 (3.7) mm (inch) 8 (0.31) mm (inch) M4 mm (inch) 10.5/ (23.2) mm (inch) —

Technical source 016 — Variable speed drive E510-430-SH3F-IP20/ 22KW/ 30HP/ 380-480V

Source download: datasheet-50-2.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P009, Variable speed drive E510-430-SH3F-IP20/ 22KW/ 30HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 16 / 16 Constant Torque (kW/A): 22 / 45; Variable Torque (kW/A): 30 / 58; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 22.00 Datasheet PDF / datasheet-50-2.pdf
90 / 16 / 16 Constant Torque (kW/A): 22 / 45; Variable Torque (kW/A): 30 / 58; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 22.00 Drawings PDF / datasheet-50-2.pdf

P009 / Variable speed drive E510-430-SH3F-IP20/ 22KW/ 30HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 30 as printed in field/value —
Suitable Motor Capacity Capacity(KW) (HD)22/(ND)30 as printed in field/value —
Rated Output Current(A) (HD)45/(ND)58 as printed in field/value —
Rated Capacity(KVA) (HD)34.3/(ND)44.2 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) (HD)48.9/(ND)63 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External input terminals: AI÷AI2 (0/2-10V, 0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —
Main Control Features / Acceleration and 2 sections of acceleration /deceleration time setting (0.1~ 3600.0 as printed in field/value —
Main Control Features / Deceleration Sec ), as printed in field/value —
Main Control Features / Control 4 of S curve setting. as printed in field/value —
Main Control Features / Multifunction Input 35 functions (refer to group3 in the manual). as printed in field/value —

P009 / Variable speed drive E510-430-SH3F-IP20/ 22KW/ 30HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction / Relay Output 22 functions (refer to group3 in the manual). as printed in field/value —
Multifunction / Analog Output 5 functions (refer to group4 in the manual). as printed in field/value —
Main Features Overload detection, 16 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset, Fire mode, Multi-Pump function. as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse, and etc. as printed in field/value —
Protective Functions / Overload Protection OL1 Electrical overload protection curve, OL2 HD 150% for 60s, ND 120% for 30s. as printed in field/value —
Protective Functions / Over Voltage 400V class :DC>820V, as printed in field/value —
Protective Functions / Under Voltage 400V class :DC<380V, as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Protection for overheating of heat sink, Fault output, Reverse prohibit, Prohibit for direct start after power up and error recovery, Parameter lock up, STO (Safety Torque Off). Built-in RS485 communication for one to one or one to many. Built-in BACnet communication for building control. (Ex:Fire protection system, Air conditioning system, Monitoring system and Access control system). as printed in field/value —
Protective Functions / brake transistor Built in. as printed in field/value —
Environment / Operating temperature IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type : -10~50℃ as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Shock Frequency : 10Hz to 150Hz and return to 10Hz, Amplitude : 0.3mm (10Hz to 50Hz), Acceleration : 2G (50Hz to 150Hz), (According to IEC60068-2-6 standard). as printed in field/value —
Environment / Enclosure IP20/NEMA1. as printed in field/value —
Environment / Altitude It is required to derate 1% of output current at each additional 100m, the maximum altitude is 2000m. as printed in field/value —

P009 / Variable speed drive E510-430-SH3F-IP20/ 22KW/ 30HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 D D1 E t Q Net Weight in kg/(lbs) Conditions
E510-430-SH3F 265 (10.43) mm (inch) 245 (9.65) mm (inch) 245 (9.65) mm (inch) 360 (14.17) mm (inch) 340 (13.39) mm (inch) 238.2 (9.38) mm (inch) 233.2 (9.18) mm (inch) NA mm (inch) 1.6 (0.06) mm (inch) M8 mm (inch) 10/ (22.1) mm (inch) —

Technical source 017 — Variable speed drive E510-401-SH3FN4S-IP66/NEMA 4X, 0.75KW, 1HP, 380-460V

Source download: DataSheet_of_E510-401-SH3FN4S_E510s_IP66.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Dimensions by printed model — P009, Variable speed drive E510-401-SH3FN4S-IP66/NEMA 4X, 0.75KW, 1HP, 380-460V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 17 / 17 Variable Torque (kW/A): 0.75 / 2.5; Supply: 380-480V 3PH; IP Rating: 66; kW Rating: 0.75 Datasheet PDF / DataSheet_of_E510-401-SH3FN4S_E510s_IP66.pdf

P009 / Variable speed drive E510-401-SH3FN4S-IP66/NEMA 4X, 0.75KW, 1HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 1 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 0.75 as printed in field/value —
Rated Output Current(A) 2.5 as printed in field/value —
Rated Capacity(KVA) 1.7 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 4.2 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 66/NEMA 4X as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/F) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Frequency Digital input: 0.01Hz as printed in field/value —
Frequency / Resolution Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Frequency Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External Input Terminals: AI1(0~10V/2-20mA), AI2(0~10V/2-20mA) Multifunction input UP/DOWN (Group3) RS485 Communication Setting frequency by communication method as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings as printed in field/value —
Run / Operation Set Keypad Run/Stop buttons External terminals:  Multi- operation-mode (2 or 3 wire selection)  Jog operation RS485 Communication Run signal by communication method as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and one customized curve as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —

P009 / Variable speed drive E510-401-SH3FN4S-IP66/NEMA 4X, 0.75KW, 1HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Main Control Features / Acceleration and 2 sections of Acceleration /Deceleration time setting (0.1~ 6000.0 as printed in field/value —
Main Control Features / Deceleration Sec), 4 sections of S Curve setting as printed in field/value —
Main Control Features / Main Features Overload detection, 16 preset speeds, Auto-run, Acc/Dec curves setting, Main/Alternative run command select, Main/Alternative frequency command select, PID control, Torque boost, Auto restart, Speed search start, Fire mode, Constant-Pressure Pump control as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list as printed in field/value —
Display / LED Status Indicador Run / Stop, Forward / Reverse, Frequency screen, Parameter screen as printed in field/value —
Protective Functions / Overload Protection Electrical overload protection curves selectable as printed in field/value —
Protective Functions / Over Voltage 200V class :>410V, 400V class:>820V as printed in field/value —
Protective Functions / Under Voltage 200V class :<190V, 400V class:<380V as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection as printed in field/value —
Protective Functions / Other Protection Functions Heat sink over temperature, Reverse prohibit, Parameter lock up, Safety Torque Off (STO, SIL2), motor PTC feedback, phase loss detection, communication error detection as printed in field/value —
Protective Functions / Brake transistor Built in as printed in field/value —
Environment IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type: -10~40℃ -20~ 60℃ 95% RH or less (no condensation) (Compliance with IEC 60068 -2-78) 1G. (9.8m/s²) for < 20Hz. 0.6G (5.88m/s²) 20Hz~50Hz (Follow IEC60068-2-6 standard) IP20/NEMA 1 and IP66/NEMA 4X as printed in field/value —

P009 / Variable speed drive E510-401-SH3FN4S-IP66/NEMA 4X, 0.75KW, 1HP, 380-460V — source page 5 — PDF page 5

Specification Value Unit / basis Conditions
Dimensions / D2 82.1 (3.23) mm (inch) C1
Dimensions / Ø column (as printed) M6 printed designation C2
Dimension figure / Frame 1 inverter frame C1

P009 / Variable speed drive E510-401-SH3FN4S-IP66/NEMA 4X, 0.75KW, 1HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W W1 H H1 D D1 NW in kg Conditions
E510-401-SH3FN4S 229 (9.01) mm (inch) 211 (8.30) mm (inch) 298 (11.73) mm (inch) 269 (10.59) mm (inch) 202.6 (7.97) mm (inch) 122.1 (4.80) mm (inch) 3.0 kg —

Technical source 018 — Variable speed drive E510-402-SH3FN4S-IP66/NEMA 4X, 1.5KW, 2HP, 380-460V

Source download: DataSheet_of_E510-402-SH3FN4S_E510s_IP66.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Dimensions by printed model — P009, Variable speed drive E510-402-SH3FN4S-IP66/NEMA 4X, 1.5KW, 2HP, 380-460V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 18 / 18 Variable Torque (kW/A): 1.5 / 3.8; Supply: 380-480V 3PH; IP Rating: 66; kW Rating: 1.50 Datasheet PDF / DataSheet_of_E510-402-SH3FN4S_E510s_IP66.pdf

P009 / Variable speed drive E510-402-SH3FN4S-IP66/NEMA 4X, 1.5KW, 2HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 2 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 1.5 as printed in field/value —
Rated Output Current(A) 3.8 as printed in field/value —
Rated Capacity(KVA) 2.9 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 5.6 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 66/NEMA 4X as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/F) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Frequency Digital input: 0.01Hz as printed in field/value —
Frequency / Resolution Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Frequency Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External Input Terminals: AI1(0~10V/2-20mA), AI2(0~10V/2-20mA) Multifunction input UP/DOWN (Group3) RS485 Communication Setting frequency by communication method as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings as printed in field/value —
Run / Operation Set Keypad Run/Stop buttons External terminals:  Multi- operation-mode (2 or 3 wire selection)  Jog operation RS485 Communication Run signal by communication method as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and one customized curve as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —

P009 / Variable speed drive E510-402-SH3FN4S-IP66/NEMA 4X, 1.5KW, 2HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Main Control Features / Acceleration and 2 sections of Acceleration /Deceleration time setting (0.1~ 6000.0 as printed in field/value —
Main Control Features / Deceleration Sec), 4 sections of S Curve setting as printed in field/value —
Main Control Features / Main Features Overload detection, 16 preset speeds, Auto-run, Acc/Dec curves setting, Main/Alternative run command select, Main/Alternative frequency command select, PID control, Torque boost, Auto restart, Speed search start, Fire mode, Constant-Pressure Pump control as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list as printed in field/value —
Display / LED Status Indicador Run / Stop, Forward / Reverse, Frequency screen, Parameter screen as printed in field/value —
Protective Functions / Overload Protection Electrical overload protection curves selectable as printed in field/value —
Protective Functions / Over Voltage 200V class :>410V, 400V class:>820V as printed in field/value —
Protective Functions / Under Voltage 200V class :<190V, 400V class:<380V as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection as printed in field/value —
Protective Functions / Other Protection Functions Heat sink over temperature, Reverse prohibit, Parameter lock up, Safety Torque Off (STO, SIL2), motor PTC feedback, phase loss detection, communication error detection as printed in field/value —
Protective Functions / Brake transistor Built in as printed in field/value —
Environment IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type: -10~40℃ -20~ 60℃ 95% RH or less (no condensation) (Compliance with IEC 60068 -2-78) 1G. (9.8m/s²) for < 20Hz. 0.6G (5.88m/s²) 20Hz~50Hz (Follow IEC60068-2-6 standard) IP20/NEMA 1 and IP66/NEMA 4X as printed in field/value —

P009 / Variable speed drive E510-402-SH3FN4S-IP66/NEMA 4X, 1.5KW, 2HP, 380-460V — source page 5 — PDF page 5

Specification Value Unit / basis Conditions
Dimensions / D2 82.1 (3.23) mm (inch) C1
Dimensions / Ø column (as printed) M6 printed designation C2
Dimension figure / Frame 1 inverter frame C1

P009 / Variable speed drive E510-402-SH3FN4S-IP66/NEMA 4X, 1.5KW, 2HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W W1 H H1 D D1 NW in kg Conditions
E510-402-SH3FN4S 229 (9.01) mm (inch) 211 (8.30) mm (inch) 298 (11.73) mm (inch) 269 (10.59) mm (inch) 202.6 (7.97) mm (inch) 122.1 (4.80) mm (inch) 3.0 kg —

Technical source 019 — Variable speed drive E510-403-SH3FN4S-IP66/NEMA 4X, 2.2KW, 3HP, 380-460V

Source download: DataSheet_of_E510-403-SH3FN4S_E510s_IP66.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Dimensions by printed model — P009, Variable speed drive E510-403-SH3FN4S-IP66/NEMA 4X, 2.2KW, 3HP, 380-460V, page 5

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 19 / 19 Variable Torque (kW/A): 2.2 / 5.3; Supply: 380-480V 3PH; IP Rating: 66; kW Rating: 2.20 Datasheet PDF / DataSheet_of_E510-403-SH3FN4S_E510s_IP66.pdf

P009 / Variable speed drive E510-403-SH3FN4S-IP66/NEMA 4X, 2.2KW, 3HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 3 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 2.2 as printed in field/value —
Rated Output Current(A) 5.3 as printed in field/value —
Rated Capacity(KVA) 4.0 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 7.3 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 66/NEMA 4X as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/F) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Frequency Digital input: 0.01Hz as printed in field/value —
Frequency / Resolution Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Frequency Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External Input Terminals: AI1(0~10V/2-20mA), AI2(0~10V/2-20mA) Multifunction input UP/DOWN (Group3) RS485 Communication Setting frequency by communication method as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings as printed in field/value —
Run / Operation Set Keypad Run/Stop buttons External terminals:  Multi- operation-mode (2 or 3 wire selection)  Jog operation RS485 Communication Run signal by communication method as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and one customized curve as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —

P009 / Variable speed drive E510-403-SH3FN4S-IP66/NEMA 4X, 2.2KW, 3HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Main Control Features / Acceleration and 2 sections of Acceleration /Deceleration time setting (0.1~ 6000.0 as printed in field/value —
Main Control Features / Deceleration Sec), 4 sections of S Curve setting as printed in field/value —
Main Control Features / Main Features Overload detection, 16 preset speeds, Auto-run, Acc/Dec curves setting, Main/Alternative run command select, Main/Alternative frequency command select, PID control, Torque boost, Auto restart, Speed search start, Fire mode, Constant-Pressure Pump control as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list as printed in field/value —
Display / LED Status Indicador Run / Stop, Forward / Reverse, Frequency screen, Parameter screen as printed in field/value —
Protective Functions / Overload Protection Electrical overload protection curves selectable as printed in field/value —
Protective Functions / Over Voltage 200V class :>410V, 400V class:>820V as printed in field/value —
Protective Functions / Under Voltage 200V class :<190V, 400V class:<380V as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection as printed in field/value —
Protective Functions / Other Protection Functions Heat sink over temperature, Reverse prohibit, Parameter lock up, Safety Torque Off (STO, SIL2), motor PTC feedback, phase loss detection, communication error detection as printed in field/value —
Protective Functions / Brake transistor Built in as printed in field/value —
Environment IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type: -10~40℃ -20~ 60℃ 95% RH or less (no condensation) (Compliance with IEC 60068 -2-78) 1G. (9.8m/s²) for < 20Hz. 0.6G (5.88m/s²) 20Hz~50Hz (Follow IEC60068-2-6 standard) IP20/NEMA 1 and IP66/NEMA 4X as printed in field/value —

P009 / Variable speed drive E510-403-SH3FN4S-IP66/NEMA 4X, 2.2KW, 3HP, 380-460V — source page 5 — PDF page 5

Specification Value Unit / basis Conditions
Dimensions / D2 113.6 (5.53) mm (inch) C1
Dimensions / Ø column (as printed) M6 printed designation C2
Dimension figure / Frame 2 inverter frame C1

P009 / Variable speed drive E510-403-SH3FN4S-IP66/NEMA 4X, 2.2KW, 3HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W W1 H H1 D D1 NW in kg Conditions
E510-403-SH3FN4S 198 (9.63) mm (inch) 115 (5.59) mm (inch) 335 (16.30) mm (inch) 315 (15.33) mm (inch) 235.3 (11.45) mm (inch) 153.6 (7.47) mm (inch) 5.9/(13.0) kg (column header); parenthetical unit not stated —, C1

Technical source 020 — Variable speed drive E510-405-SH3FN4S-IP66/NEMA 4X, 4KW, 5HP, 380-460V

Source download: DataSheet_of_E510-405-SH3FN4S_E510s_IP66.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Dimensions by printed model — P009, Variable speed drive E510-405-SH3FN4S-IP66/NEMA 4X, 4KW, 5HP, 380-460V, page 5

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 20 / 20 Variable Torque (kW/A): 4.0 / 9.2; Supply: 380-480V 3PH; IP Rating: 66; kW Rating: 4.00 Datasheet PDF / DataSheet_of_E510-405-SH3FN4S_E510s_IP66.pdf

P009 / Variable speed drive E510-405-SH3FN4S-IP66/NEMA 4X, 4KW, 5HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 5 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 4.0 as printed in field/value —
Rated Output Current(A) 9.2 as printed in field/value —
Rated Capacity(KVA) 6.7 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 11.6 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 66/NEMA 4X as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/F) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Frequency Digital input: 0.01Hz as printed in field/value —
Frequency / Resolution Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Frequency Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External Input Terminals: AI1(0~10V/2-20mA), AI2(0~10V/2-20mA) Multifunction input UP/DOWN (Group3) RS485 Communication Setting frequency by communication method as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings as printed in field/value —
Run / Operation Set Keypad Run/Stop buttons External terminals:  Multi- operation-mode (2 or 3 wire selection)  Jog operation RS485 Communication Run signal by communication method as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and one customized curve as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —

P009 / Variable speed drive E510-405-SH3FN4S-IP66/NEMA 4X, 4KW, 5HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Main Control Features / Acceleration and 2 sections of Acceleration /Deceleration time setting (0.1~ 6000.0 as printed in field/value —
Main Control Features / Deceleration Sec), 4 sections of S Curve setting as printed in field/value —
Main Control Features / Main Features Overload detection, 16 preset speeds, Auto-run, Acc/Dec curves setting, Main/Alternative run command select, Main/Alternative frequency command select, PID control, Torque boost, Auto restart, Speed search start, Fire mode, Constant-Pressure Pump control as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list as printed in field/value —
Display / LED Status Indicador Run / Stop, Forward / Reverse, Frequency screen, Parameter screen as printed in field/value —
Protective Functions / Overload Protection Electrical overload protection curves selectable as printed in field/value —
Protective Functions / Over Voltage 200V class :>410V, 400V class:>820V as printed in field/value —
Protective Functions / Under Voltage 200V class :<190V, 400V class:<380V as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection as printed in field/value —
Protective Functions / Other Protection Functions Heat sink over temperature, Reverse prohibit, Parameter lock up, Safety Torque Off (STO, SIL2), motor PTC feedback, phase loss detection, communication error detection as printed in field/value —
Protective Functions / Brake transistor Built in as printed in field/value —
Environment IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type: -10~40℃ -20~ 60℃ 95% RH or less (no condensation) (Compliance with IEC 60068 -2-78) 1G. (9.8m/s²) for < 20Hz. 0.6G (5.88m/s²) 20Hz~50Hz (Follow IEC60068-2-6 standard) IP20/NEMA 1 and IP66/NEMA 4X as printed in field/value —

P009 / Variable speed drive E510-405-SH3FN4S-IP66/NEMA 4X, 4KW, 5HP, 380-460V — source page 5 — PDF page 5

Specification Value Unit / basis Conditions
Dimensions / D2 113.6 (5.53) mm (inch) C1
Dimensions / Ø column (as printed) M6 printed designation C2
Dimension figure / Frame 2 inverter frame C1

P009 / Variable speed drive E510-405-SH3FN4S-IP66/NEMA 4X, 4KW, 5HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W W1 H H1 D D1 NW in kg Conditions
E510-405-SH3FN4S 198 (9.63) mm (inch) 115 (5.59) mm (inch) 335 (16.30) mm (inch) 315 (15.33) mm (inch) 235.3 (11.45) mm (inch) 153.6 (7.47) mm (inch) 5.9/(13.0) kg (column header); parenthetical unit not stated —, C1

Technical source 021 — Variable speed drive E510-408-SH3FN4S-IP66/NEMA 4X, 5.5KW, 7.5HP, 380-460V

Source download: DataSheet_of_E510-408-SH3FN4S_E510s_IP66.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Dimensions by printed model — P009, Variable speed drive E510-408-SH3FN4S-IP66/NEMA 4X, 5.5KW, 7.5HP, 380-460V, page 5

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 21 / 21 Variable Torque (kW/A): 5.5/13; Supply: 380-480V 3PH; IP Rating: 66; kW Rating: 5.50 Datasheet PDF / DataSheet_of_E510-408-SH3FN4S_E510s_IP66.pdf

P009 / Variable speed drive E510-408-SH3FN4S-IP66/NEMA 4X, 5.5KW, 7.5HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 7.5 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 5.5 as printed in field/value —
Rated Output Current(A) 13.0 as printed in field/value —
Rated Capacity(KVA) 9.9 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 17.0 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 66/NEMA 4X as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/F) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Frequency Digital input: 0.01Hz as printed in field/value —
Frequency / Resolution Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Frequency Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External Input Terminals: AI1(0~10V/2-20mA), AI2(0~10V/2-20mA) Multifunction input UP/DOWN (Group3) RS485 Communication Setting frequency by communication method as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings as printed in field/value —
Run / Operation Set Keypad Run/Stop buttons External terminals:  Multi- operation-mode (2 or 3 wire selection)  Jog operation RS485 Communication Run signal by communication method as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and one customized curve as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —

P009 / Variable speed drive E510-408-SH3FN4S-IP66/NEMA 4X, 5.5KW, 7.5HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Main Control Features / Acceleration and 2 sections of Acceleration /Deceleration time setting (0.1~ 6000.0 as printed in field/value —
Main Control Features / Deceleration Sec), 4 sections of S Curve setting as printed in field/value —
Main Control Features / Main Features Overload detection, 16 preset speeds, Auto-run, Acc/Dec curves setting, Main/Alternative run command select, Main/Alternative frequency command select, PID control, Torque boost, Auto restart, Speed search start, Fire mode, Constant-Pressure Pump control as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list as printed in field/value —
Display / LED Status Indicador Run / Stop, Forward / Reverse, Frequency screen, Parameter screen as printed in field/value —
Protective Functions / Overload Protection Electrical overload protection curves selectable as printed in field/value —
Protective Functions / Over Voltage 200V class :>410V, 400V class:>820V as printed in field/value —
Protective Functions / Under Voltage 200V class :<190V, 400V class:<380V as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection as printed in field/value —
Protective Functions / Other Protection Functions Heat sink over temperature, Reverse prohibit, Parameter lock up, Safety Torque Off (STO, SIL2), motor PTC feedback, phase loss detection, communication error detection as printed in field/value —
Protective Functions / Brake transistor Built in as printed in field/value —
Environment IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type: -10~40℃ -20~ 60℃ 95% RH or less (no condensation) (Compliance with IEC 60068 -2-78) 1G. (9.8m/s²) for < 20Hz. 0.6G (5.88m/s²) 20Hz~50Hz (Follow IEC60068-2-6 standard) IP20/NEMA 1 and IP66/NEMA 4X as printed in field/value —

P009 / Variable speed drive E510-408-SH3FN4S-IP66/NEMA 4X, 5.5KW, 7.5HP, 380-460V — source page 5 — PDF page 5

Specification Value Unit / basis Conditions
Dimensions / D2 130 (6.32) mm (inch) C1
Dimensions / Ø column (as printed) M6 printed designation C2
Dimension figure / Frame 3 inverter frame C1

P009 / Variable speed drive E510-408-SH3FN4S-IP66/NEMA 4X, 5.5KW, 7.5HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W W1 H H1 D D1 NW in kg Conditions
E510-408-SH3FN4S 223 (10.58) mm (inch) 140 (6.81) mm (inch) 460 (22.39) mm (inch) 440 (21.42) mm (inch) 263.5 (12.82) mm (inch) 180 (8.76) mm (inch) 13.0/(28.6) kg (column header); parenthetical unit not stated —, C1

Technical source 022 — Variable speed drive E510-410-SH3FN4S-IP66/NEMA 4X, 7.5KW, 10HP, 380-460V

Source download: DataSheet_of_E510-410-SH3FN4S_E510s_IP66.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Dimensions by printed model — P009, Variable speed drive E510-410-SH3FN4S-IP66/NEMA 4X, 7.5KW, 10HP, 380-460V, page 5

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 22 / 22 Variable Torque (kW/A): 7.5/17.5; Supply: 380-480V 3PH; IP Rating: 66; kW Rating: 7.50 Datasheet PDF / DataSheet_of_E510-410-SH3FN4S_E510s_IP66.pdf

P009 / Variable speed drive E510-410-SH3FN4S-IP66/NEMA 4X, 7.5KW, 10HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 10 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 7.5 as printed in field/value —
Rated Output Current(A) 17.5 as printed in field/value —
Rated Capacity(KVA) 13.3 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 23.0 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 66/NEMA 4X as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/F) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Frequency Digital input: 0.01Hz as printed in field/value —
Frequency / Resolution Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Frequency Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External Input Terminals: AI1(0~10V/2-20mA), AI2(0~10V/2-20mA) Multifunction input UP/DOWN (Group3) RS485 Communication Setting frequency by communication method as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings as printed in field/value —
Run / Operation Set Keypad Run/Stop buttons External terminals:  Multi- operation-mode (2 or 3 wire selection)  Jog operation RS485 Communication Run signal by communication method as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and one customized curve as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —

P009 / Variable speed drive E510-410-SH3FN4S-IP66/NEMA 4X, 7.5KW, 10HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Main Control Features / Acceleration and 2 sections of Acceleration /Deceleration time setting (0.1~ 6000.0 as printed in field/value —
Main Control Features / Deceleration Sec), 4 sections of S Curve setting as printed in field/value —
Main Control Features / Main Features Overload detection, 16 preset speeds, Auto-run, Acc/Dec curves setting, Main/Alternative run command select, Main/Alternative frequency command select, PID control, Torque boost, Auto restart, Speed search start, Fire mode, Constant-Pressure Pump control as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list as printed in field/value —
Display / LED Status Indicador Run / Stop, Forward / Reverse, Frequency screen, Parameter screen as printed in field/value —
Protective Functions / Overload Protection Electrical overload protection curves selectable as printed in field/value —
Protective Functions / Over Voltage 200V class :>410V, 400V class:>820V as printed in field/value —
Protective Functions / Under Voltage 200V class :<190V, 400V class:<380V as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection as printed in field/value —
Protective Functions / Other Protection Functions Heat sink over temperature, Reverse prohibit, Parameter lock up, Safety Torque Off (STO, SIL2), motor PTC feedback, phase loss detection, communication error detection as printed in field/value —
Protective Functions / Brake transistor Built in as printed in field/value —
Environment IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type: -10~40℃ -20~ 60℃ 95% RH or less (no condensation) (Compliance with IEC 60068 -2-78) 1G. (9.8m/s²) for < 20Hz. 0.6G (5.88m/s²) 20Hz~50Hz (Follow IEC60068-2-6 standard) IP20/NEMA 1 and IP66/NEMA 4X as printed in field/value —

P009 / Variable speed drive E510-410-SH3FN4S-IP66/NEMA 4X, 7.5KW, 10HP, 380-460V — source page 5 — PDF page 5

Specification Value Unit / basis Conditions
Dimensions / D2 130 (6.32) mm (inch) C1
Dimensions / Ø column (as printed) M6 printed designation C2
Dimension figure / Frame 3 inverter frame C1

P009 / Variable speed drive E510-410-SH3FN4S-IP66/NEMA 4X, 7.5KW, 10HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W W1 H H1 D D1 NW in kg Conditions
E510-410-SH3FN4S 223 (10.58) mm (inch) 140 (6.81) mm (inch) 460 (22.39) mm (inch) 440 (21.42) mm (inch) 263.5 (12.82) mm (inch) 180 (8.76) mm (inch) 13.0/(28.6) kg (column header); parenthetical unit not stated —, C1

Technical source 023 — Variable speed drive E515-415-SH3FN4S-IP66/NEMA 4X, 11KW, 15HP, 380-460V

Source download: DataSheet_of_E510-415-SH3FN4S_E510s_IP66-v1-1.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
90 / 23 / 23 Variable Torque (kW/A): 11/24; Supply: 380-480V 3PH; IP Rating: 66; kW Rating: 11.00 Datasheet PDF / DataSheet_of_E510-415-SH3FN4S_E510s_IP66-v1-1.pdf

P009 / Variable speed drive E515-415-SH3FN4S-IP66/NEMA 4X, 11KW, 15HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E510s as printed in field/value —
Horse Power(HP) 15 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 11 as printed in field/value —
Rated Output Current(A) 24.0 as printed in field/value —
Rated Capacity(KVA) 19.1 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 31.0 as printed in field/value —
Allowable Momentary Power Loss / Time(Sec.) 2.0 as printed in field/value —
Enclosure IP 66/NEMA 4X as printed in field/value —
Control Mode V/F, SLV, PMSLV as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/F) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Speed Control Ratio 1:50 as printed in field/value —
Frequency / Frequency Digital input: 0.01Hz as printed in field/value —
Frequency / Resolution Analog input:0.06Hz/60Hz as printed in field/value —
Frequency / Frequency Setting Keypad: Set directly with▲▼ keys or the VR on the Keypad External Input Terminals: AI1(0~10V/2-20mA), AI2(0~10V/2-20mA) Multifunction input UP/DOWN (Group3) RS485 Communication Setting frequency by communication method as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings as printed in field/value —
Operation Set Keypad Run/Stop buttons External terminals: as printed in field/value —
Run / Operation Set  Multi- operation-mode (2 or 3 wire selection)  Jog operation as printed in field/value —
Operation Set RS485 Communication Run signal by communication method as printed in field/value —
Main Control Features / V/F Curve Setting 15 fixed curves and one customized curve as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz as printed in field/value —

P009 / Variable speed drive E515-415-SH3FN4S-IP66/NEMA 4X, 11KW, 15HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Main Control Features / Acceleration and 2 sections of Acceleration /Deceleration time setting (0.1~ 6000.0 as printed in field/value —
Main Control Features / Deceleration Sec), 4 sections of S Curve setting as printed in field/value —
Main Control Features / Multifunction Digital Input 42 functions (refer to group3 in the manual) as printed in field/value —
Main Control Features / Multifunction / Relay Output 27 functions (refer to group3 in the manual) as printed in field/value —
Main Control Features / Multifunction Analog Output 5 functions (refer to group4 in the manual) as printed in field/value —
Main Control Features / Main Features Overload detection, 16 preset speeds, Auto-run, Acc/Dec curves setting, Main/Alternative run command select, Main/Alternative frequency command select, PID control, Torque boost, Auto restart, Speed search start, Fire mode, Constant-Pressure Pump control as printed in field/value —
Display / LED Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list as printed in field/value —
LED Status Indicador Run / Stop, Forward / Reverse, Frequency screen, Parameter screen as printed in field/value —
Protective Functions / Overload Protection Electrical overload protection curves selectable as printed in field/value —
Protective Functions / Over Voltage 200V class :>410V, 400V class:>820V as printed in field/value —
Protective Functions / Under Voltage 200V class :<190V, 400V class:<380V as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter can be set to restart automatically as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection as printed in field/value —
Protective Functions / Other Protection Heat sink over temperature, Reverse prohibit, Parameter lock up, as printed in field/value —
Protective Functions / Other Protection / Functions Safety Torque Off (STO, SIL2), motor PTC feedback, phase loss as printed in field/value —
Protective Functions / Functions detection, communication error detection as printed in field/value —
Protective Functions / Brake transistor Built in as printed in field/value —
Environment IP20/NEMA 1 Type: –10 ~ 50℃ (without stick on type dust cover.) –10 ~ 40℃ (with stick on type dust cover.) IP66/NEMA 4X Type: -10~40℃ -20~ 60℃ 95% RH or less (no condensation) (Compliance with IEC 60068 -2-78) 1G. (9.8m/s²) for < 20Hz. 0.6G (5.88m/s²) 20Hz~50Hz (Follow IEC60068-2-6 standard) IP20/NEMA 1 and IP66/NEMA 4X as printed in field/value —

Selection checks and source differences

Range scopes differ: page0.4–2.2kW single-phase/0.75–18.5kW three-phase; collected22kWHD/30kWND row; short brochure0.75–2.2kW single-phase,IP2055kW/IP6611kW; broader manual schedules retained separately. No stock extension inferred.

0.75kW IP66 website row5 lists7.5A while its E510-201-H1FN4S PDF states4.5A. Preserve both associations; do not use the website current as a corrected sheet value.

ND overload is120%/60s in the catalogue and manual but120%/30s in several individual IP20 sheets. Confirm the selected unit; retain both.

0.4kW sheet identifies2P2 while catalogue/manual use2P5. The11kW IP66 source title prints E515-415, while filename and component refer toE510/E510s. Several IP66 titles state380–460V but their input rows state380–480V. These are supplier-source differences, not corrected order codes.

The catalogue400V heading says Single/Three phase but its input specification says three-phase380–480V. No400V single-phase product is inferred.

Manual IP66200V product-identification table has model-code versus horsepower/kW mismatches. Brochure FigureK dimension metric/inch pairs are inconsistent. Preserve literal rows; do not calculate replacements or select by those inconsistencies.

Older E510 IP66 sheets and E510s sheets differ in control modes, V/F curve counts, terminal-function counts and acceleration ranges. Quick guides label PM Group21/pump Group22 whereas full manual uses PM Group22. These are not merged into a single firmware specification.

Manual fire-mode page241 says08-40 for disabling fire mode, whereas page240/parameter table identify08-48. Page241 also mixes08-51/08-55 references and stop/keep-running descriptions. Source references retained; no corrected commissioning procedure inferred.

STO applies to built-in EMC-filter models per manual page103. Its appendix mixes E510s SF1/SF2/SG labels with11-301 S1/S2/SC and has visibly clipped shock/atmosphere rows on page418. Page425 is separately scoped and is not substituted. Historical category/reliability claims are not current certification proof.

Manual temperature/current/altitude conditions and STO limits differ. General safety text includes inconsistent Celsius/Fahrenheit wording and discharge thresholds/waits. Follow the complete applicable procedure, model and safety requirements; no universal threshold synthesized.

LCD marketing, LED display code, optional LCD operator and N4/N4S hardware scopes remain distinct. Supplier NEMA4 versusNEMA4X wording is retained without equating enclosure certifications.

All locally collected PDF associations and archive members reconcile. Fresh static-page refresh found no new main PDFs; this is not a new exhaustive live pagination crawl. Drawing geometry, unreadable labels and unresolved source anomalies remain in the original PDFs and local audit.

Product documents

Our company certificates and conditions of sale remain separate from the selected product’s ratings and approvals.

Talk to our team about your application, supply, motor rating and configuration.