TECO Emotron F33 — Pump and Fan Drives

Our Emotron F33 range is designed around pumps, fans, compressors and blowers. We focus on maintaining flow and pressure, reducing unnecessary motor operation and making process control straightforward for the operator.

Control the process around demand

The source describes soft starting to reduce starting current and controlled stopping to help limit water hammer. Pressure-based sleep can pause the motor when demand falls, while a scheduled full-speed pump-clearing function can help manage sludge. Actual hydraulic performance depends on the installation and commissioning; these are not guarantees for every pump system.

The catalogue says one F33 can control up to seven units without an external control system. The manual's pump-control arrangements and I/O/option requirements define how those units are staged and alternated. This does not mean seven motors can simply be connected directly to the drive output. The reference sections keep the process, PID, pump-selection, runtime-balancing and alarm conditions together.

The website names JNFX and individual sheets commonly use FDU. The family catalogue also contains V33/JNVX/VFX material. We retain each source identity; shared performance or a common enclosure does not establish cross-family interchangeability. F33's motor-current setting[224] is 25–120% of I_NOM in its manual, distinct from V33's25–150% setting range.

Configuration records and one missing link

The collected website export contains 156 row associations across tables14 and 39, 78 rows each. There are 155 actual PDF memberships to 76 distinct technical PDFs. Table39, row56 contains #ERROR! and no download for its 630 kW/650 A listing. Table14, row56 has a collected sheet, but that does not repair or create a link for table39. We retain the missing association explicitly.

Every collected sheet is represented once with all its table/row associations. The shared28-page catalogue and 212-page F33 manual are retained separately. Broader source ranges, current duty, mounting and enclosure distinctions remain attached to their exact records rather than merged into a synthetic model list.

Ratings, enclosures and installation

The shared F33/V33 2.0 catalogue has a 0.55–3000 kW, 230–690 V cover headline. Its individual schedules and on-request ranges differ by family and voltage. A headline or requested larger size does not establish a model's current, dimensions or availability. The manual identifies48, 52 and 69 supply families with their own operating ranges; a motor-voltage parameter range is not the drive's input-voltage rating.

The catalogue's normal-duty columns are 120% for one minute every ten minutes and heavy-duty columns 150% for one minute every ten minutes, at the stated40°C reference ambient. Maximum-current entries have an additional limited-time/drive-temperature qualification. Preserve kW at 400/525/690 V separately from hp at 460/575 V. Select by actual motor current and overload duty, rather than combining similarly named rows.

The range page describes robust IP54 steel construction. The family documents also show larger IP20 modules and IP54 cabinet arrangements. Dimensions, weight and cooling airflow are frame-, enclosure- and voltage-specific. A shared frame number does not make two voltage classes dimensionally equivalent. Parenthesised heights and blank mounting values remain as printed; original drawings define geometry.

The catalogue's normal operating environment is 0–40°C, non-condensing and protected from conductive dust and corrosive cooling air. Higher-temperature derating differs by model group. Altitude guidance distinguishes480 V drives up to 4, 000m from 690 V drives up to 2, 000m, with current derating above 1, 000m and coating requirements at the stated elevations. The source does not explicitly establish the same limits for 525 V models. No combined temperature/altitude rating is calculated.

Interfaces, accessories and braking

The removable control panel supports parameter transfer and copying. Configure engineering units, motor data, command sources, protection and automatic restart for the actual process. Display illustrations, symbolic defaults and communication-register ranges remain references; they are not live settings or a motor performance envelope.

The shared catalogue supports three option boards plus one communication option. Safe Stop on B/C/D consumes one of those option positions. Options include I/O, encoder, PTC/PT100, fieldbus/serial interfaces and an external control panel. Model and software compatibility, occupied slots and factory-fit requirements remain part of selection. Coated boards and liquid cooling are separately described options; the heat exchanger is not included in the liquid-cooling option.

The catalogue describes Category C3 filtering as standard under its stated80m motor-cable condition. C2 and extended filters have separate frame, voltage and environment limits. Follow the complete EMC installation and cable/filter guide. The shared catalogue explicitly limits its sine-wave filter to F33; it is not a V33 option merely because the catalogue is shared.

A brake chopper is an optional factory-fitted item and the catalogue says it cannot be retrofitted; its resistor is external. Vector braking, a brake chopper/resistor and a mechanical holding brake are different functions. DC-link connections and overshoot clamps have their own prerequisites. Do not assume braking or Safe Stop replaces the machine's required safety/holding arrangement.

Commissioning, maintenance and source limits

Use qualified personnel and the complete manual for protective earthing, RCD selection, supply/motor connections, fuses, cables, cooling, commissioning and maintenance. Safe Stop is not electrical isolation. The manual distinguishes its normal discharge wait from a malfunction condition requiring DC-link verification or a longer wait; these have not been collapsed into one universal delay. Isolate before motor insulation testing and follow the prescribed procedure.

The detailed reference sections retain parameter sets, motor/process control, I/O, logic, timers, alarms, diagnostics, maintenance, options, wiring annotations and model-specific technical tables. Graphs and wiring geometry remain in the originals. Historical UL840, DNV, CE and safety-standard statements are preserved as source claims, not a current certificate or machine acceptance.

Several datasheets repeat VFX48-2K5-54 in a component-name field despite a different model in the title. They also label input power factor as percent while printing0.95, and pair a vibration value in g with oz. Some high-voltage sheets state400–690 V input but0–480 V output. These fields remain source-specific and flagged; we do not silently correct the model, scale, units or voltage.

Both manuals contain a derating example that states a68 A motor but selects a drive with a calculated32.4 A capability. That example is inconsistent and must not be used as approved selection guidance. Other menu indices, cross-references, merged cells and undefined boundaries retain their original values and local audit notes. We have not inferred missing defaults or corrected part numbers by pattern.

Confirm your configuration

Tell us the motor nameplate data, supply, duty cycle, driven load, speed and stopping requirements, site conditions and control-system interfaces. We can then confirm the correct model, enclosure, options and approved drawings.

Catalogue — Technical Catalogue AC Drives cover — page 1

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 1

TECO V33/F33 2.0; cover range0.55–3000kW,230–690V.

Context: Cover range not a per-model rating or source edition date. Small product photograph details are outside this text rendition.

Catalogue — V33 2.0 overview — page 2

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 2

TECO V33 2.0 / High dynamics for demanding applications

UL 840

GOST R

Main features

• Robust and certified IP54 metal construction as standard offers cost- efficient installation close to the application. • All drive sizes are delivered with a built-in Category C3 EMC-filter as standard. C3 requirements are fulfilled with 80 m motor cable. • Direct torque control reacts extremely quickly and eliminates disturbances due to abrupt load changes. • Soft starts minimize start currents and full motor overload capacity is available from standstill.

• UL (UL 840) and marine (DNV) approved standard drive. • Integrated vector braking ensures quick and controlled stops, increasing productivity and safety. • Speed controlled fans assures less noise, a more even drive temperature and higher drive efficiency.

• Module fuses included as standard for sizes above 300 A at 480 V and above 210 A at 690 V.

• Detachable multilingual control panel included as standard. Following languages are supported in the control panel: English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech and Turkish.

• Operation parameters can be set in your process units, for example m/sec, tons/h or cycles/min. • Removable control panel with own memory means it is easy to transfer or copy settings. • Liquid cooled version available for sizes above 90 A.

The TECO V33, 2.0 AC drive optimizes your process and prevents damage and downtime. The combination of direct torque control, accurate speed control and efficient vector braking makes it the ideal solution for all dynamic applications, such as cranes, crushers, mills, mixers and centrifuges.

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: UL 840, DNV, CE/GOST marks and EN-IEC 62061:2005 SIL2 / EN-ISO 13849-1:2006 are source claims only. No current approval, certification scope or engineered safety-system acceptance is asserted.

Context: Overview says above 90 A; detailed option includes E–K/F69–K69. Preserve both without resolving boundary eligibility for a 90 A model. Heat exchanger explicitly excluded; parallel-module dividing unit retained.

Context: StandardIP54 claim and frameI IP20 module photograph caption describe different presentation/configuration contexts. Do not turn the pictured IP20 module into a contradiction resolved by changing all ratings.

Catalogue — V33 typical power: 400/460 V — page 3

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 3

Sizes 900 kW - 2000 kW available on request

TECO V33, 2.0 Typical motor power at mains voltage 400 and 460 V

Note: calculate available 230 V motor power by multiplying the 400 V power value (kW) from table above with 0.575 or use motor rated current for drive selection. Example: JNVX48-046, 22 kW x 0.575 = 12.6 kW at 230 V

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: 400/460 V V33 table prints VJNVX48-046, whereas the example footnote uses JNVX48-046. Keep both literal identifiers; no silent model correction.

Context: Small-model V33 maximum-output-current values differ from F33 values. Separate families and source rows retained; do not deduplicate by equal normal/heavy-duty power.

Context: Normal 120% / heavy 150% duty is 1 minute every 10 minutes; maximum current has a limited-time/temperature condition; ratings are at 40 C. Preserve 400/525/690 V kW versus 460/575 V hp. On-request ranges do not supply specific extra models.

Context: These footnotes print 40 apostrophe-C in the text layer/typography rather than consistently using a degree symbol. Preserve literal prose; reviewed header context identifies the source ambient-temperature condition.

Table conditions: V33 only; mains 400/460 V. Normal duty 120% for 1 minute every 10 minutes; heavy duty 150% for 1 minute every 10 minutes. Maximum current is limited by time/drive temperature; rated data at 40 C ambient. Frame labels are printed merged source cells mapped to each model, not inferred. Power units vary by voltage and must not be interchanged.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. V33 400/460 V source headings, 120% normal/150% heavy for 1 minute each 10 minutes, 40°C rating footnote and limited maximum current, with reviewer merged-frame/unit instructions.

V33 typical motor power at 400/460 V — PDF page 3

Model Maximum output current A * Normal duty power 400 V kW Normal duty power 460 V hp Normal duty rated current A Heavy duty power 400 V kW Heavy duty power 460 V hp Heavy duty rated current A Frame size
JNVX48-003 3.8 0.75 1 2.5 0.55 1 2.0 B
JNVX48-004 6.0 1.5 2 4.0 1.1 1.5 3.2 B
JNVX48-006 9.0 2.2 3 6.0 1.5 2 4.8 B
JNVX48-008 11.3 3 3 7.5 2.2 3 6.0 B
JNVX48-010 14.3 4 5 9.5 3 3 7.6 B
JNVX48-013 19.5 5.5 7.5 13.0 4 5 10.4 B
JNVX48-018 27.0 7.5 10 18.0 5.5 7.5 14.4 B
JNVX48-026 39 11 15 26 7.5 10 21 C
JNVX48-031 46 15 20 31 11 15 25 C
JNVX48-037 55 18.5 25 37 15 20 29.6 C
VJNVX48-046 69 22 30 46 18.5 25 37 C
JNVX48-061 92 30 40 61 22 30 49 D
JNVX48-074 111 37 50 74 30 40 59 D
JNVX48-090 108 45 60 90 37 50 72 E
JNVX48-109 131 55 75 109 45 60 87 E
JNVX48-146 175 75 100 146 55 75 117 E
JNVX48-175 210 90 125 175 75 100 140 E
JNVX48-210 252 110 150 210 90 125 168 F
JNVX48-228 300 110 200 228 90 150 182 F
JNVX48-250 300 132 200 250 110 150 200 F
JNVX48-300 360 160 250 300 132 200 240 G
JNVX48-375 450 200 300 375 160 250 300 G
JNVX48-430 516 220 350 430 200 250 344 H
JNVX48-500 600 250 400 500 220 350 400 H
JNVX48-600 720 315 500 600 250 400 480 I
JNVX48-650 780 355 550 650 315 400 520 I
JNVX48-750 900 400 600 750 355 500 600 I
JNVX48-860 1032 450 700 860 400 550 688 J
JNVX48-1000 1200 500 800 1000 450 650 800 J
JNVX48-1200 1440 630 1000 1200 500 800 960 K
JNVX48-1500 1800 800 1250 1500 630 1000 1200 K

Catalogue — V33 typical power: 525 V — page 4

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 4

Sizes 710 kW - 2200 kW available on request

TECO V33, 2.0 Typical motor power at mains voltage 525 V

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: Small-model V33 maximum-output-current values differ from F33 values. Separate families and source rows retained; do not deduplicate by equal normal/heavy-duty power.

Context: Normal 120% / heavy 150% duty is 1 minute every 10 minutes; maximum current has a limited-time/temperature condition; ratings are at 40 C. Preserve 400/525/690 V kW versus 460/575 V hp. On-request ranges do not supply specific extra models.

Table conditions: V33 only; mains 525 V. Normal duty 120% for 1 minute every 10 minutes; heavy duty 150% for 1 minute every 10 minutes. Maximum current is limited by time/drive temperature; rated data at 40 C ambient. Frame labels are printed merged source cells mapped to each model, not inferred. Power units vary by voltage and must not be interchanged.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. V33 525 V source headings and duty/40°C conditions with reviewer merged-frame/unit instructions.

V33 typical motor power at 525 V — PDF page 4

Model Maximum output current A * Normal duty power 525 V kW Normal duty rated current A Heavy duty power 525 V kW Heavy duty rated current A Frame size
JNVX52-003 3.8 1.1 2.5 1.1 2.0 B
JNVX52-004 6.0 2.2 4.0 1.5 3.2 B
JNVX52-006 9.0 3 6.0 2.2 4.8 B
JNVX52-008 11.3 4 7.5 3 6.0 B
JNVX52-010 14.3 5.5 9.5 4 7.6 B
JNVX52-013 19.5 7.5 13.0 5.5 10.4 B
JNVX52-018 27.0 11 18.0 7.5 14.4 B
JNVX52-026 39 15 26 11 21 C
JNVX52-031 46 18.5 31 15 25 C
JNVX52-037 55 22 37 18.5 29.6 C
JNVX52-046 69 30 46 22 37 C
JNVX52-061 92 37 61 30 49 D
JNVX52-074 111 45 74 37 59 D
JNVX69-090 108 55 90 45 72 F69
JNVX69-109 131 75 109 55 87 F69
JNVX69-146 175 90 146 75 117 F69
JNVX69-175 210 110 175 90 140 F69
JNVX69-210 252 132 210 110 168 H69
JNVX69-250 300 160 250 132 200 H69
JNVX69-300 360 200 300 160 240 H69
JNVX69-375 450 250 375 200 300 H69
JNVX69-430 516 300 430 250 344 I69
JNVX69-500 600 315 500 300 400 I69
JNVX69-600 720 400 600 315 480 J69
JNVX69-650 780 450 650 355 520 J69
JNVX69-750 900 500 750 400 600 K69
JNVX69-860 1032 560 860 450 688 K69
JNVX69-1000 1200 630 1000 500 800 K69

Catalogue — V33 typical power: 575/690 V — page 5

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 5

Sizes 1100 kW - 3000 kW available on request

TECO V33, 2.0 Typical motor power at mains voltage 575 and 690 V

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: Normal 120% / heavy 150% duty is 1 minute every 10 minutes; maximum current has a limited-time/temperature condition; ratings are at 40 C. Preserve 400/525/690 V kW versus 460/575 V hp. On-request ranges do not supply specific extra models.

Table conditions: V33 only; mains 575/690 V. Normal duty 120% for 1 minute every 10 minutes; heavy duty 150% for 1 minute every 10 minutes. Maximum current is limited by time/drive temperature; rated data at 40 C ambient. Frame labels are printed merged source cells mapped to each model, not inferred. Power units vary by voltage and must not be interchanged.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. V33 575/690 V source headings and duty/40°C conditions with reviewer merged-frame/unit instructions.

V33 typical motor power at 575/690 V — PDF page 5

Model Maximum output current A * Normal duty power 575 V hp Normal duty power 690 V kW Normal duty rated current A Heavy duty power 575 V hp Heavy duty power 690 V kW Heavy duty rated current A Frame size
JNVX69-090 108 75 90 90 60 75 72 F69
JNVX69-109 131 100 110 109 75 90 87 F69
JNVX69-146 175 125 132 146 100 110 117 F69
JNVX69-175 210 150 160 175 125 132 140 F69
JNVX69-210 252 200 200 210 150 160 168 H69
JNVX69-250 300 250 250 250 200 200 200 H69
JNVX69-300 360 300 315 300 250 250 240 H69
JNVX69-375 450 350 355 375 300 315 300 H69
JNVX69-430 516 400 450 430 350 315 344 I69
JNVX69-500 600 500 500 500 400 355 400 I69
JNVX69-600 720 600 600 600 500 450 480 J69
JNVX69-650 780 650 630 650 550 500 520 J69
JNVX69-750 900 750 710 750 600 600 600 K69
JNVX69-860 1032 850 800 860 700 650 688 K69
JNVX69-900 1080 900 900 900 750 710 720 K69
JNVX69-1000 1200 1000 1000 1000 850 800 800 K69

Catalogue — V33 application challenges and solutions — page 6

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 6

The answer to a range of challenges Cranes

Crushers

Mixers

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Table conditions: Application-specific supplier challenge/solution/benefit claims. No independent quantified performance or safety validation.

V33 / Cranes — PDF page 6

Challenge TECO V33 solution Value
Starting with a heavy load is difficult and risky. Can lead to hoist load dips or jerks causing swinging load in travel motions Direct torque control, motor pre- magnetization and precise brake control gives instant yet soft start with heavy load. Shortened cycle times and increased safety. Less stress on equipment reduced maintenance costs and down time
Unsynchronized travel motions of a rail- mounted crane casus noisy operation and stress on wheels. Speed and position of wheels are fully synchronized. Crane rides parallel to the rail. Less maintenance and downtime. Less noise improves working conditions.
Crane is driven slowly when returning empty or with a light load. Valuable time is lost. Speed can be increased by operating the motor in the field weakening area. Reduced cycle times and optimized operation
Hoisting and grabbing cannot be controlled independently. Stress on ropes and longer cycle times. Hoisting and grabbing can be operated simultaneously. Grab can be opened/closed while being hoisted. Reduced cycle times. Hoisting while closing grab puts less stress on ropes. Reducing maintenance and downtime.
Braking with heavy load is difficult and risky. Can lead to jerks causing swinging load. Direct torque control and brake chopper smoothly reduce speed to zero before mechanical brake is activated. Increased safety. Less stress on equipment reduces maintenance and downtime
Operator starts braking earlier than necessary to stop the crane at end position. Increases cycle times and can lead to jerky movements. System automatically stops crane at end position. Operator can safely drive at full speed. Reduced cycle times and increased safety.

V33 / Crushers — PDF page 6

Challenge TECO V33 solution Value
High start currents require larger fuses and cables, or in mobile units larger generators. Causes stress on equipment and higher energy costs. Speed control reduces start current. Same fuses can be used as those required for the normal motor current, or a smaller generator. Lower investment and energy costs, extended equipment lifetime.
Abrupt load change or torque peak when starting heavily loaded crusher. Causes mechanical stress and false trips. Direct torque control adjusts the torque to handle load changes and overcome initial peak loads. Reliable operation without interruptions. Reduced mechanical stress and less downtime
Material that could cause damage gets into the crusher. Load curve protection function quickly detects deviation. Warning is sent or safety stop activated. Early warning allows preventive action before damage or breakdown.
Motor runs at same speed despite varying demand. Motor speed is continuously adapted to the amount and size of rock. Speed of feeder is adapted to load variations. Increased efficiency. Reduced maintenance cost.

V33 / Mixers — PDF page 6

Challenge TECO V33 solution Value
High start currents require larger fuses and cables, Causes stress on equipment and higher energy costs. Speed control reduces start current. Same fuses can be used as those required for the normal motor current, Lower investment and energy costs, extended equipment lifetime.
Difficult to determine when mixing process is ready Built-in shaft power monitor determines when viscosity is right. Optimized operation and higher product quality.
Motor runs at same speed despite varying demand. Speed is continuously adapted to viscosity level. Reduced mixing time and improved product quality. Reduced maintenance costs.
Process inefficiency due to e.g. a damaged or broken blade. Energy wasted, mechanical stress and risk of process failure Load curve protection function quickly detects deviation from normal load. Warning is sent or safety stop activated. Preventive action before damage or breakdown. No energy is lost and downtime is reduced.

Catalogue — F33 2.0 overview — page 7

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 7

TECO F33, 2.0 / Secure the flow and save energy

Main features

• Robust and certified IP54 metal construction as standard offers cost-efficient installation close to the application. • All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements are fulfilled with 80 m motor cable. • Soft starts minimize start currents and linear stops prevent water hammer. • One TECO F33 can control up to seven units without external control systems. • Energy saving function pauses the motor when it is not required to run to maintain pressure. • Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out sludge. • Speed controlled fans assures less noise, a more even drive temperature and higher efficiency. • Module fuses included as standard for sizes above 300 A at 480 V and above 210 A at 690 V. • Detachable multilingual control panel included as standard. Following languages are supported in the control panel: English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech and Turkish. • Operation parameters can be set in your process units, for example m3/min. and bar. • Removable control panel with own memory means it is easy to transfer or copy settings. • UL (UL 840) and marine (DNV) approved standard drive. • Liquid cooled version available for sizes above 90 A.

The TECO F33, 2.0 AC drive is specially developed for regulating flow and pressure. It continuously adapts motor speed to the level required, minimizing energy consumption and wear. A unique monitoring functionality protects your process from damage and unplanned downtime. Typical applications are pumps, fans, compressors and blowers.

UL 840

GOST R

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: UL 840, DNV, CE/GOST marks and EN-IEC 62061:2005 SIL2 / EN-ISO 13849-1:2006 are source claims only. No current approval, certification scope or engineered safety-system acceptance is asserted.

Context: Overview says above 90 A; detailed option includes E–K/F69–K69. Preserve both without resolving boundary eligibility for a 90 A model. Heat exchanger explicitly excluded; parallel-module dividing unit retained.

Context: StandardIP54 claim and frameI IP20 module photograph caption describe different presentation/configuration contexts. Do not turn the pictured IP20 module into a contradiction resolved by changing all ratings.

Catalogue — F33 typical power: 400/460 V — page 8

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 8

Sizes 900 - 2000 kW available on request

TECO F33, 2.0 Typical motor power at mains voltage 400 and 460 V

Note: calculate available 230 V motor power by multiplying the 400 V power value (kW) from table above with 0.575 or use motor rated current for drive selection. Example: JNFX48-046, 22 kW x 0.575 = 12.6 kW at 230 V

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: Small-model V33 maximum-output-current values differ from F33 values. Separate families and source rows retained; do not deduplicate by equal normal/heavy-duty power.

Context: Normal 120% / heavy 150% duty is 1 minute every 10 minutes; maximum current has a limited-time/temperature condition; ratings are at 40 C. Preserve 400/525/690 V kW versus 460/575 V hp. On-request ranges do not supply specific extra models.

Table conditions: F33 only; mains 400/460 V. Normal duty 120% for 1 minute every 10 minutes; heavy duty 150% for 1 minute every 10 minutes. Maximum current is limited by time/drive temperature; rated data at 40 C ambient. Frame labels are printed merged source cells mapped to each model, not inferred. Power units vary by voltage and must not be interchanged.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. F33 400/460 V source headings and duty/40°C conditions with reviewer merged-frame/unit instructions.

F33 typical motor power at 400/460 V — PDF page 8

Model Maximum output current A * Normal duty power 400 V kW Normal duty power 460 V hp Normal duty rated current A Heavy duty power 400 V kW Heavy duty power 460 V hp Heavy duty rated current A Frame size
JNFX48-003 3.0 0.75 1 2.5 0.55 1 2.0 B
JNFX48-004 4.8 1.5 2 4.0 1.1 1.5 3.2 B
JNFX48-006 7.2 2.2 3 6.0 1.5 2 4.8 B
JNFX48-008 9.0 3 3 7.5 2.2 3 6.0 B
JNFX48-010 11.4 4 5 9.5 3 3 7.6 B
JNFX48-013 15.6 5.5 7.5 13.0 4 5 10.4 B
JNFX48-018 21.6 7.5 10 18.0 5.5 7.5 14.4 B
JNFX48-026 31 11 15 26 7.5 10 21 C
JNFX48-031 37 15 20 31 11 15 25 C
JNFX48-037 44 18.5 25 37 15 20 29.6 C
JNFX48-046 55 22 30 46 18.5 25 37 C
JNFX48-061 73 30 40 61 22 30 49 D
JNFX48-074 89 37 50 74 30 40 59 D
JNFX48-090 108 45 60 90 37 50 72 E
JNFX48-109 131 55 75 109 45 60 87 E
JNFX48-146 175 75 100 146 55 75 117 E
JNFX48-175 210 90 125 175 75 100 140 E
JNFX48-210 252 110 150 210 90 125 168 F
JNFX48-228 300 110 200 228 90 150 182 F
JNFX48-250 300 132 200 250 110 150 200 F
JNFX48-300 360 160 250 300 132 200 240 G
JNFX48-375 450 200 300 375 160 250 300 G
JNFX48-430 516 220 350 430 200 250 344 H
JNFX48-500 600 250 400 500 220 350 400 H
JNFX48-600 720 315 500 600 250 400 480 I
JNFX48-650 780 355 550 650 315 400 520 I
JNFX48-750 900 400 600 750 355 500 600 I
JNFX48-860 1032 450 700 860 400 550 688 J
JNFX48-1000 1200 500 800 1000 450 650 800 J
JNFX48-1200 1440 630 1000 1200 500 800 960 K
JNFX48-1500 1800 800 1250 1500 630 1000 1200 K

Catalogue — F33 typical power: 525 V — page 9

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 9

Sizes 710 - 2200 kW available on request

TECO F33, 2.0 Typical motor power at mains voltage 525 V

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: Small-model V33 maximum-output-current values differ from F33 values. Separate families and source rows retained; do not deduplicate by equal normal/heavy-duty power.

Context: F33 525 V table includes JNFX52-019 in frame C in addition to JNFX52-018 in frame B. Retain both; do not infer a matching V33 row.

Context: Normal 120% / heavy 150% duty is 1 minute every 10 minutes; maximum current has a limited-time/temperature condition; ratings are at 40 C. Preserve 400/525/690 V kW versus 460/575 V hp. On-request ranges do not supply specific extra models.

Table conditions: F33 only; mains 525 V. Normal duty 120% for 1 minute every 10 minutes; heavy duty 150% for 1 minute every 10 minutes. Maximum current is limited by time/drive temperature; rated data at 40 C ambient. Frame labels are printed merged source cells mapped to each model, not inferred. Power units vary by voltage and must not be interchanged.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. F33 525 V source headings and duty/40°C conditions with reviewer merged-frame/unit instructions.

F33 typical motor power at 525 V — PDF page 9

Model Maximum output current A * Normal duty power 525 V kW Normal duty rated current A Heavy duty power 525 V kW Heavy duty rated current A Frame size
JNFX52-003 3.0 1.1 2.5 1.1 2.0 B
JNFX52-004 4.8 2.2 4.0 1.5 3.2 B
JNFX52-006 7.2 3 6.0 2.2 4.8 B
JNFX52-008 9.0 4 7.5 3 6.0 B
JNFX52-010 11.4 5.5 9.5 4 7.6 B
JNFX52-013 15.6 7.5 13.0 5.5 10.4 B
JNFX52-018 21.6 11 18.0 7.5 14.4 B
JNFX52-019 22 11 18 7.5 14.4 C
JNFX52-026 31 15 26 11 21 C
JNFX52-031 37 18.5 31 15 25 C
JNFX52-037 44 22 37 18.5 29.6 C
JNFX52-046 55 30 46 22 37 C
JNFX52-061 73 37 61 30 49 D
JNFX52-074 89 45 74 37 59 D
JNFX69-090 108 55 90 45 72 F69
JNFX69-109 131 75 109 55 87 F69
JNFX69-146 175 90 146 75 117 F69
JNFX69-175 210 110 175 90 140 F69
JNFX69-210 252 132 210 110 168 H69
JNFX69-250 300 160 250 132 200 H69
JNFX69-300 360 200 300 160 240 H69
JNFX69-375 450 250 375 200 300 H69
JNFX69-430 516 300 430 250 344 I69
JNFX69-500 600 315 500 300 400 I69
JNFX69-600 720 400 600 315 480 J69
JNFX69-650 780 450 650 355 520 J69
JNFX69-750 900 500 750 400 600 K69
JNFX69-860 1032 560 860 450 688 K69
JNFX69-1000 1200 630 1000 500 800 K69

Catalogue — F33 typical power: 575/690 V — page 10

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 10

Sizes 1100 - 3000 kW available on request

TECO F33 2.0 Typical motor power at mains voltage 575 and 690 V

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: Normal 120% / heavy 150% duty is 1 minute every 10 minutes; maximum current has a limited-time/temperature condition; ratings are at 40 C. Preserve 400/525/690 V kW versus 460/575 V hp. On-request ranges do not supply specific extra models.

Context: These footnotes print 40 apostrophe-C in the text layer/typography rather than consistently using a degree symbol. Preserve literal prose; reviewed header context identifies the source ambient-temperature condition.

Table conditions: F33 only; mains 575/690 V. Normal duty 120% for 1 minute every 10 minutes; heavy duty 150% for 1 minute every 10 minutes. Maximum current is limited by time/drive temperature; rated data at 40 C ambient. Frame labels are printed merged source cells mapped to each model, not inferred. Power units vary by voltage and must not be interchanged.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. F33 575/690 V source headings and duty/40°C conditions with reviewer merged-frame/unit instructions.

F33 typical motor power at 575/690 V — PDF page 10

Model Maximum output current A * Normal duty power 575 V hp Normal duty power 690 V kW Normal duty rated current A Heavy duty power 575 V hp Heavy duty power 690 V kW Heavy duty rated current A Frame size
JNFX69-090 108 75 90 90 60 75 72 F69
JNFX69-109 131 100 110 109 75 90 87 F69
JNFX69-146 175 125 132 146 100 110 117 F69
JNFX69-175 210 150 160 175 125 132 140 F69
JNFX69-210 252 200 200 210 150 160 168 H69
JNFX69-250 300 250 250 250 200 200 200 H69
JNFX69-300 360 300 315 300 250 250 240 H69
JNFX69-375 450 350 355 375 300 315 300 H69
JNFX69-430 516 400 450 430 350 315 344 I69
JNFX69-500 600 500 500 500 400 355 400 I69
JNFX69-600 720 600 600 600 500 450 480 J69
JNFX69-650 780 650 630 650 550 500 520 J69
JNFX69-750 900 750 710 750 600 600 600 K69
JNFX69-860 1032 850 800 860 700 650 688 K69
JNFX69-900 1080 900 900 900 750 710 720 K69
JNFX69-1000 1200 1000 1000 1000 850 800 800 K69

Catalogue — F33 application challenges and solutions — page 11

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 11

The answer to a range of challenges Common to Pumps / Fans / Compressors & Blowers

Pumps

Fans

Compressors

Blowers

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Table conditions: Application-specific supplier challenge/solution/benefit claims. No independent quantified performance or safety validation.

F33 / Common pumps/fans/compressors/blowers — PDF page 11

Challenge TECO F33 solution Value
High start currents require larger fuses and cables. Causing stress on equipment and higher energy costs Speed control reduces start current. Same fuses can be used as those required for the normal motor current. Lower investment and energy costs. Extended equipment lifetime
Motor runs at same speed despite varying demands in pressure and flow or when no air is compressed PID function continuously adapts speed to required level. Sleep function can be activated when the motor dose not need to run. Optimized energy consumption and increased efficiency. Reduced maintenance costs. Quicker set-up.
Process inefficiency due to e.g. A blocked pipe, a valve not fully opened or a worn impeller. A blocked filter, a damper not fully opened or a broken belt. The compressor idling Load curve protection function quickly detects deviation from normal load. Warning is sent or safety stop activated. Optimized operation. Preventive action before damage. No energy is lost and downtime is reduced.

F33 / Pumps — PDF page 11

Challenge TECO F33 solution Value
Sludge buildup on impeller when pump operates at low speed or on prolonged standby. Reduces pump efficiency Automatic pump rinsing: Pump can be set to run at full speed for a period of time before returning to normal operation. Higher process efficiency and reduced maintenance costs.
Prolonged Dry-running, cavitation and over heating damage the pump causing downtime Load curve protection function detects deviation. Sends warning or activates safety stop Preventive action before damage. Extended equipment lifetime and reduced downtime
Water hammer damages the pump when stopped. Mechanical stress on pipes, valves, gaskets and seals. Smooth linear stops protect the equipment. Eliminates need for costly motorized valves. Reduced maintenance costs and less downtime. Extended equipment lifetime. Lower installation costs.

F33 / Fans — PDF page 11

Challenge TECO F33 solution Value
Draught causes turned off fan t o rotate the wrong way. Starting causes high current peaks and mechanical stress. Dan result in blown fuses and breakdown. Spin start ensures that the motor is picked up at its present speed and direction, gradually slowed to zero speed and then started in the right direction. Reduced cycle times, extended equipment lifetime and less downtime.
Regulating pressure/flow with dampers causes high energy consumption and equipment wear. Automatic regulation of pressure/flow with motor speed gives a more exact control. Optimized energy consumption and minimized impact on equipment.

F33 / Compressors — PDF page 11

Challenge TECO F33 solution Value
Compressor is damaged when cooling agent enters the compressor screw. Overload situation is quickly detected and safety can be activated to avoid breakdown. Extended equipment lifetime, reduced maintenance costs and downtime
Pressure is higher than needed causing leaks, stress on the equipment and excessive air use. Load curve protection function detects deviation. Warning is sent or safety stop activated. Preventive action before damage or breakdown. No energy is lost and downtime is reduced.

F33 / Blowers — PDF page 11

Challenge TECO F33 solution Value
Difficult to compensate for pressure fluctuations. Energy wasted and risk of production stop. PID function continuously adapts pressure to the level required Reliable operation and no energy wasted. Always keeps the required pressure.

Catalogue — General specifications and enclosure dimensions — page 12

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 12

Cooling airflow table applies if mounted in cabinet. Models300–1500 consist of2,3,4 or6paralleled power modules(PEBB-s) in standard enclosure.

Context: Parenthesised heights retained without inferred meaning. Two dimension tables kept separate by source frame family; no invented individual models from ranges. Source wording FDU in switching-frequency line retained.

Table conditions: Mains footnotes TN/IT supply;* parameter-selected nominal voltage. Preserve voltage-specific tolerance and source FDU label.

Table conditions: Source upper table;dashes are printed absence markers, not zeros. IP20/IP54 weight order retained; cabinet airflow model split026–031/037–046 retained.

Table conditions: Source lower table; same model-range numbers in upper table do not establish same size/voltage variant. No inferred dimensions for dashes.

General specifications — PDF page 12

Parameter/source family Source value
Mains JNVX/JNFX48* 230–480V** +10%/-15%(-10% at230V)
Mains JNVX/JNFX52* 440–525V** +10%/-15%
Mains JNVX/JNFX69* 500–690V** +10%/-15%
Mains frequency 45–65Hz
Input total power factor 0.95
Output voltage 0–Mains supply voltage
Output frequency 0–400Hz
Output switching frequency 3kHz(FDU adjustable1.5–6kHz)
Efficiency at nominal load models003–018 97%
Efficiency at nominal load models026–1500 98%

Dimensions upper table framesB–K — PDF page 12

Models Frame size IP20 H x W x D mm IP54 H x W x D mm Weight IP20/IP54 kg Airflow m³/hour
003 to018 B – 350(416) x203 x200 –/12.5 75
026 to046 C – 440(512) x178 x292 –/24 026–031=120,037–046=170
061 to074 D - 545(590) x220 x295 -/32 175
90 to109 E – 950 x285 x314 –/56 510
146 to175 E – 950 x285 x314 –/60 510
210 to250 F – 950 x345 x314 –/74 800
300 to375 G(2xE) 1036 x500 x390 2250 x600 x600 140/350 1020
430 to500 H(2xF) 1036 x500 x450 2250 x600 x600 170/380 1600
600 to750 I(3xF) 1036 x730 x450 2250 x900 x600 248/506 2400
860 to1000 J(2xH) 1036 x1100 x450 2250 x1200 x600 340/697 3200
1200 to1500 K(2xI) 1036 x1560 x450 2250 x1800 x600 496/987 4800

Dimensions lower table framesF69–K69 — PDF page 12

Models Frame size IP20 H x W x D mm IP54 H x W x D mm Weight IP20/IP54 kg Airflow m³/hour
90 to175 F69 – 1090 x345 x314 –/77 800
210 to375 H69(2xF69) 1176 x500 x450 2250 x600 x600 176/399 1600
430 to500 I69(3xF69) 1176 x730 x450 2250 x900 x600 257/563 2400
600 to650 J69(2xH69) 1176 x1100 x450 2250 x1200 x600 352/773 3200
750 to1000 K69(2xI69) 1176 x1560 x450 2250 x1800 x600 514/1100 4800

Catalogue — Environmental limits derating and V33 speed — page 13

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 13

Most TECO AC drives designed for maximum40°C ambient; higher temperatures conditional on table derating.

V33 speed static graph labels: n actual/ref,±0,01% of nnom,t. Dynamic illustration: torque/speed,5%,80ms and(5 x0,08s)/2=0,2%s. These are illustration labels, not a digitized response curve.

Context: Derating model groups remain literal source groups, including** wildcard. No combined altitude/temperature derating calculated. Source classes are supplier statements, not independently verified conformity.

Table conditions: Voltage-family altitude boundaries and size-specific vibration condition retained as printed; no inferred applicability to525V models.

Table conditions: Storage only; separate fromnormaloperation.

Table conditions: Two-modelgroup merged source cells preserved within eachrow. Dashes not substituted with rated temperatures.

Table conditions: Source performance claims, not tested values. Chart geometry remains in PDF.

Environmental normal operation — PDF page 13

Parameter Normal operation
Nominal ambient temperature 0°C–40°C
Atmospheric pressure 86–106kPa
Relative humidity,non-condensing 0–90%
Contamination IEC60721-3-3 No electrically conductive dust; cooling air clean and free from corrosive materials. Chemical gases3C2(coated boards3C3);solid particles3S2.
Vibrations IEC60068-2-6 sinusoidal:10<f<57Hz,0.075mm;57<f<150Hz,1g. SizesB,C,D:IEC60721-3-3 3M4(2–9Hz,3.0mm;9–20Hz,acc.1g(10m/s²)).
Altitude 0–1000m.480V AC drives:1%/100m rated-current derating up to4000m.690V AC drives:1%/100m rated-current derating up to2000m. Coated boards required2000–4000m.

Storage conditions — PDF page 13

Parameter Storage condition
Temperature -20 to+60°C
Atmospheric pressure 86–106kPa
Relative humidity,non-condensing 0–90%

Table1 ambient derating400–690V types — PDF page 13

Source model group IP20 max temperature IP20 possible derating IP54 max temperature IP54 possible derating
JNVX-JNFX**-003 to JNVX-JNFX**-074 – – 40°C -2.5%/°C to max+10°C(50°C)
JNVX-JNFX48-090 to JNVX-JNFX48-250;JNVX-JNFX69-090 to JNVX-JNFX69-175 – – 40°C -2.5%/°C to max+5°C(45°C)
JNVX-JNFX48-300 to JNVX-JNFX48-1500;JNVX-JNFX69-210 to JNVX-JNFX69-1000 40°C -2.5%/°C to max+5°C(45°C) 40°C -2.5%/°C to max+5°C(45°C)

V33 2.0 speed control performance — PDF page 13

Metric Mode Source value
Static accuracy(linearity) Closed loop 0.01% of nnom
Static accuracy(linearity) Open loop 0.1% of nnom
Dynamic accuracy(impact drop) Closed loop 0.2%sec(100% load step)
Dynamic accuracy(impact drop) Open loop 0.4%sec(100% load step)

Catalogue — Control performance and basic I/O — page 14

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 14

Source limitation: Source comparator and fraction typography unresolved; no inferred numeric interpretation.

V33 torque illustration labels:actual/ref,±3% ofTnom,t;dynamic Tref/Tact,10%,90%,1ms. Geometry not reconstructed.

Source cross-reference says User interface data on page15 for connection/default settings; physicalPDF16 printed15 instead contains fuse/cable table. Preserve reference mismatch.

Context: Digital-input impedance comparator before second3.3VDC is malformed in source. Readable firstcondition<3.3VDC:4.7kΩ and second3.3VDC:3.6kΩ preserved; second comparator left unresolved. Do not infer equality boundary.

Context: Analogue input nonlinearity glyphs read11/2 LSB; fraction spacing unclear. Retained as printed, not converted to decimal. Output impedance has stray subscript n after10Ω; retained in note.

Table conditions: Source open-loop wording retained even where unitcontext differs; no engineering correction.

Table conditions: Four differential analogue inputs. Preserve printed fraction form; no decimal interpretation.

Table conditions: Malformed second impedance comparator retained as unresolved, not guessed.

Table conditions: Two analogue outputs; switched range, not software setting ofanalogueinputs. Source stray n retained.

Table conditions: Source merged label split into voltage andshort-circuit fields by two distinct valueblocks; shared100mA budgetretained.

Table conditions: Literal source current/maximum voltage statement; no switching category inferred.

Table conditions: Source+10VD label retained; no silent spelling correction. Digital-output shared-current condition preserved.

V33 torque and F33 V/Hz performance — PDF page 14

Family/metric Mode/condition Source value
V33 torque static(linearity) Closed loop <3% ofTnom
V33 torque static(linearity) Open loop <3% for speeds10–100% ofrated and<10% atzero speed(% ofnnom)
V33 torque dynamic Closed & open loop 100% torque step rise time1ms
F33 V/Hz speed accuracy Slip frequency Approx.1% ofnnom
F33 V/Hz torque accuracy 20–100% speed Approx.5% ofTnom

Analogue inputs differential4channels — PDF page 14

Parameter Source value
Voltage/current 0–±10V/0–20mA via software setting
Max input voltage +30V
Input impedance 20kΩ(voltage),250Ω(current)
Resolution 11bits+sign
Hardware accuracy 0.5% type+1 1/2 LSB fsd
Non-linearity 11/2 LSB(as printed,fraction typography unclear)

Digital inputs8channels — PDF page 14

Parameter Source value
Input voltage High>9VDC,Low<4VDC
Max input voltage +30VDC
Input impedance <3.3VDC:4.7kΩ / second condition[operator unclear]3.3VDC:3.6kΩ
Signal delay ≤8ms

Analogue outputs2channels — PDF page 14

Parameter Source value
Output voltage/current 0–10V/0–20mA via switch
Max output voltage +15V @5mA continuous
Short-circuit current(∞) +15mA(voltage),+140mA(current)
Output impedance 10Ω(voltage),stray source subscript n
Resolution 10bit
Maximum load impedance forcurrent 500Ω
Hardware accuracy 1.9% type fsd(voltage),2.4% type fsd(current)
Offset 3LSB
Non-linearity 2LSB

Digital outputs2channels — PDF page 14

Parameter Source value
Output voltage High>20VDC @50mA,>23VDC open / Low<1VDC @50mA
Short-circuit current(∞) 100mA max(together with+24VDC)

Relay contacts3pcs — PDF page 14

Parameter Source value
Contacts 0.1–2A/Umax250VAC or42VDC

Reference voltages — PDF page 14

Source label/context Source value
+10VD +10VDC @10mA,short-circuit current+30mA max
-10VDC -10VDC @10mA
+24VDC +24VDC,short-circuit current+100mA max(together withDigitalOutputs)

Catalogue — Photo gallery and model/frame captions — page 15

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 15

Photo gallery

VFX/FDU48/52: Model 003 - 018 (B) VFX/FDU48/52: Model 026 - 046 (C) VFX/FDU48/52: Model 061 - 074 (D)

JNVX/JNFX48: Model 090 – 175(E) JNVX/JNFX48:Model 210 – 250 (F) JNVX/JNFX: Model600 – 750 (I) IP20 (module) JNVX/JNFX 69: Model 090 – 175 (F69)

VFX/FDU48: Model 300 - 500 (G and H) VFX/FDU48: Model 600 - 750 (I) VFX/FDU69: Model 210 - 375 (H69) VFX/FDU69: Model 430 - 500 (I69)

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: Gallery and crane-option sections use VFX/FDU alongside JNVX/JNFX. Retain printed naming and frame associations without inventing a universal alias or claiming crane options for F33.

Context: StandardIP54 claim and frameI IP20 module photograph caption describe different presentation/configuration contexts. Do not turn the pictured IP20 module into a contradiction resolved by changing all ratings.

Catalogue — Fuses cable dimensions and glands IEC ratings — page 16

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 16

Use mains fuses typegL/gG conformingIEC269 or circuit breaker with similar characteristics. Checkequipment before installing glands; source says onlymetricglands will beused in due time.

Source defines Max.fuse as maximum fuse value still protecting ACdrive and upholding warranty. Fuse and cablecrosssection depend on application and must be determined in accordance with local regulations.

Power-terminal dimensions in models300–1500 can differ depending on customer specification.

Context: Printed model prefixes JNVX/JNFX and JVX/JNFX retained as printed; VFX/FDU cable cell wording preserved. No substituted model IDs. Source table is not a current installation design or warranty verification.

Table conditions: Expand only visible merged cells. Shared mains/motor gland cell duplicated into bothcolumns. Preserve printed prefixes,48/69 cable distinction and all dashes; no unprinted69cable for1200/1500. Application/local-regulation/customer-terminal qualifications remain essential.

Fuse cable and gland table — PDF page 16

Printed model Nominal input current A Maximum fuse A Maximum mains/motor cable cross-section supported mm² Mains gland/clamping mm Motor gland/clamping mm
JNVX/JNFX48-003 2.2 4 0.5–10 M32 opening M20+reducer(6–12) M32 opening M20+reducer(6–12)
JNVX/JNFX48-004 3.5 4 0.5–10 M32 opening M20+reducer(6–12) M32 opening M20+reducer(6–12)
JVX/JNFX48-006 5.2 6 0.5–10 M32 opening M20+reducer(6–12) M32 opening M20+reducer(6–12)
JVX/JNFX48-008 6.9 8 0.5–10 M32(12–20) M32 opening M25+reducer(10–14)
JNVX/JNFX48-010 8.7 10 0.5–10 M32(12–20) M32 opening M25+reducer(10–14)
JNVX/JNFX48-013 11.3 16 0.5–10 M32(16–25) M32(13–18)
JNVX/JNFX48-018 15.6 20 0.5–10 M32(16–25) M32(13–18)
JNVX/JNFX**-026 22 25 2.5–16 M32(15–21) M32(13–18)
JNVX/JNFX**-031 26 35 2.5–16 M32(15–21) M32(13–18)
JNVX/JNFX**-037 31 35 2.5–16 M40(19–28) M40(18–25)
JNVX/JNFX**-046 38 50 2.5–16 M40(19–28) M40(18–25)
JNVX/JNFX**-061 52 63 1–35 stranded wire;1–50 solid wire M50(27–35) M40(19–28)
JNVX/JNFX**-074 64 80 1–35 stranded wire;1–50 solid wire M50(27–35) M40(19–28)
JNVX/JNFX**-090 78 100 16–95 JNVXJNFX48:Ø17–42 cable flexible lead through orM50 opening;JNVXJNFX69:Ø23–55 cable flexible lead through M63 opening JNVXJNFX48:Ø17–42 cable flexible lead through orM50 opening;JNVXJNFX69:Ø23–55 cable flexible lead through M63 opening
JNVX/JNFX**-109 94 100 16–95 JNVXJNFX48:Ø17–42 cable flexible lead through orM50 opening;JNVXJNFX69:Ø23–55 cable flexible lead through M63 opening JNVXJNFX48:Ø17–42 cable flexible lead through orM50 opening;JNVXJNFX69:Ø23–55 cable flexible lead through M63 opening
JNVX/JNFX**-146 126 160 35–150 JNVXJNFX48:Ø17–42 cable flexible lead through orM50 opening;JNVXJNFX69:Ø23–55 cable flexible lead through M63 opening JNVXJNFX48:Ø17–42 cable flexible lead through orM50 opening;JNVXJNFX69:Ø23–55 cable flexible lead through M63 opening
JNVX/JNFX**-175 152 160 35–150 JNVXJNFX48:Ø17–42 cable flexible lead through orM50 opening;JNVXJNFX69:Ø23–55 cable flexible lead through M63 opening JNVXJNFX48:Ø17–42 cable flexible lead through orM50 opening;JNVXJNFX69:Ø23–55 cable flexible lead through M63 opening
JNVX/JNFX**-210 182 200 VFX/FDU48:35–240;VFX/FDU69:35–150 Ø23–55 cable flexible lead through orM63 opening Ø23–55 cable flexible lead through orM63 opening
JNVX/JNFX**-228 197 250 VFX/FDU48:35–240;VFX/FDU69:35–150 Ø23–55 cable flexible lead through orM63 opening Ø23–55 cable flexible lead through orM63 opening
JNVX/JNFX**-250 216 250 VFX/FDU48:35–240;VFX/FDU69:35–150 Ø23–55 cable flexible lead through orM63 opening Ø23–55 cable flexible lead through orM63 opening
JNVX/JNFX**-300 260 300 JNVX/JNFX48:(2x)35–240;JNVX/JNFX69:(2x)35–150 - -
JNVX/JNFX**-375 324 355 JNVX/JNFX48:(2x)35–240;JNVX/JNFX69:(2x)35–150 - -
JNVX/JNFX**-430 372 400 JNVX/JNFX48:(2x)35–240;JNVX/JNFX69:(3x)35–150 - -
JNVX/JNFX**-500 432 500 JNVX/JNFX48:(2x)35–240;JNVX/JNFX69:(3x)35–150 - -
JNVX/JNFX**-600 520 630 JNVX/JNFX48:(3x)35–240;JNVX/JNFX69:(4x)35–150 - -
JNVX/JNFX**-650 562 630 JNVX/JNFX48:(3x)35–240;JNVX/JNFX69:(4x)35–150 - -
JNVX/JNFX**-750 648 710 JNVX/JNFX48:(3x)35–240;JNVX/JNFX69:(6x)35–150
JNVX/JNFX**-860 744 800 JNVX/JNFX48:(4x)35–240;JNVX/JNFX69:(6x)35–150 - -
JNVX/JNFX**-900 795 900 JNVX/JNFX48:(4x)35–240;JNVX/JNFX69:(6x)35–150 - -
JNVX/JNFX**-1000 864 1000 JNVX/JNFX48:(4x)35–240;JNVX/JNFX69:(6x)35–150 - -
JNVX/JNFX**-1200 1037 1250 JNVX/JNFX48:(6x)35–240 - -
JNVX/JNFX**-1500 1296 1500 JNVX/JNFX48:(6x)35–240 - -

Catalogue — NEMA fuses and cable sizes — page 17

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 17

Fuses and cable dimensions according NEMA ratings

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: Merged cell spanning 146/175 contains AWG 1–AWG 3/0 and AWG 4/0–300 kcmil on separate lines without a physical row divider. Preserve shared cell context; do not infer which line belongs uniquely to one model.

Context: New NEMA UL Class J / part / AWG data must coexist with prior IEC metric data, not overwrite it. Printed rows are catalogue guidance, not verified site cable/fuse sizing.

Table conditions: Exact catalogue table, model/option and units as printed. Source blanks and dashes remain distinct; null marks a merged-cell placeholder, with separate source parent-cell context. Catalogue selection data is not a substitute for verified installation instructions. NEMA scope only; do not replace prior IEC fuse/cable tables. No AWG-to-metric conversion inferred.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. NEMA table source scope and AWG values combined with reviewer no-conversion/no-IEC-substitution rule.

NEMA fuses and cable sizes / table 1 — PDF page 17

Model Input current Arms Mains fuse UL Class J TD A Mains fuse Ferraz-Shawmut type Cable cross-section range: mains and motor
JNVX/JNFX48-003 2.2 6 AJT6 AWG 20 - AWG 6
JNVX/JNFX48-004 3.5 6 AJT6 None
JNVX/JNFX48-006 5.2 6 AJT6 None
JNVX/JNFX48-008 6.9 10 AJT10 None
JNVX/JNFX48-010 8.7 10 AJT10 None
JNVX/JNFX48-013 11.3 15 AJT15 None
JNVX/JNFX48-018 16 20 AJT20 AWG 12 – AWG 4
JNVX/JNFX48-026 22 25 AJT25 None
JNVX/JNFX48-031 26 30 AJT30 None
JNVX/JNFX48-037 31 35 AJT35 None
JNVX/JNFX48-046 38 45 AJT45 None
JNVX/JNFX48-061 52 60 AJT60 AWG 12 - AWG 4
JNVX/JNFX48-074 65 80 AJT80 AWG 10- AWG 0
JNVX/JNFX48-090 78 100 AJT100 AWG 4 – AWG 3/0
JNVX/JNFX48-109 94 110 AJT110 None
JNVX/JNFX48-146 126 150 AJT150 AWG 1 – AWG 3/0 AWG 4/0 – 300 kcmil
JNVX/JNFX48-175 152 175 AJT175 None
JNVX/JNFX48-210 182 200 AJT200 AWG 3/0 – 400 kcmil
JNVX/JNFX48-228 197 250 AJT250 None
JNVX/JNFX48-250 216 250 AJT250 None
JNVX/JNFX48-300 260 300 AJT300 2 x AWG 4/0 – 2 x 300 kcmil
JNVX/JNFX48-375 324 350 AJT350 None
JNVX/JNFX48-430 372 400 AJT400 2 x AWG 3/0 – 2 x 400 kcmil
JNVX/JNFX48-500 432 500 AJT500 None
JNVX/JNFX48-600 520 600 AJT600 3 x AWG 4/0 – 3 x 300 kcmil
JNVX/JNFX48-650 562 600 AJT600 None
JNVX/JNFX48-750 648 700 A4BQ700 None
JNVX/JNFX48-860 744 800 A4BQ800 4 x AWG 4/0 – 4 x 300 kcmil
JNVX/JNFX48-1000 864 1000 A4BQ1000 None
JNVX/JNFX48-1200 1037 1200 A4BQ1200 6 x AWG 4/0 – 6 x 300 kcmil
JNVX/JNFX48-1500 1296 1500 A4BQ1500 None

Catalogue — User interface terminals and default functions — page 18

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 18

4 -20 mA 0 -10 V

Comm.options

Fieldbus option or PC

X1

+10 VD AnIn 1 AnIn 2

AnIn 3 AnIn 4

-10 VDC Common

DigIn 1:RunL DigIn 2:RunR

DigIn3 +24 VDC Common DigIn 4 DigIn 5 DigIn 6 DigIn 7

DigIn8:Reset*

RFI- filter

Optional**

Relay 3

Relay 1

Relay 2

Optional

Common AnOut 1 AnOut 2 DigOut 1 DigOut 2

Other options

Option boards

X2

X3

Trip

Ready

Motor

User interface data * = Default selection ** = Optional terminals X1: 78 - 79 for connection of Motor-PTC on sizes B, C and D.

All inputs and outputs are programmable.

Illustrated power-terminal labels: L1, L2, L3, PE; U, V, W; optional DC+, R, DC-. The drawing also labels optional X1 terminals 78 and 79. These are source labels only; wiring topology remains in the original diagram.

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: All I/O is programmable. Keep X1/X2/X3 identities, default relay functions and N/C/N/O semantics. Motor-PTC 78–79 is optional only for B/C/D in this page; no wiring path reconstructed from artwork.

Context: Diagram text says +10 VD whereas terminal 1 table specifies +10 VDC. Both source statements retained; no new power-supply specification inferred.

Table conditions: Exact catalogue table, model/option and units as printed. Source blanks and dashes remain distinct; null marks a merged-cell placeholder, with separate source parent-cell context. Catalogue selection data is not a substitute for verified installation instructions. X1 terminals 1–22, X2 relays 31–43 and X3 relay51–52 retained. Functions are defaults and all I/O is programmable. Diagram topology is not reconstructed.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. Printed X1/default I/O and X2/X3 relay groups combined with reviewer topology boundary. X2 source groups are 31/32/33 and 41/42/43; shorthand 31–43 must not imply terminals 34–40. X1 78/79 are optional Motor-PTC on sizes B/C/D, not normal table rows.

User interface terminals and default functions / table 1 — PDF page 18

Terminal number Name Default function
1 +10 V +10 VDC Supply voltage
2 AnIn1 Speed reference
3 AnIn2 Not used
4 AnIn3 Not used
5 AnIn4 Not used
6 -10 V -10VDC Supply voltage
7 Common Signal ground
8 DigIn 1 RunL
9 DigIn 2 RunR
10 DigIn 3 Not used
11 +24 V +24VDC Supply voltage
12 Common Signal ground
13 AnOut 1 Min speed to max speed
14 AnOut 2 0 to max torque
15 Common Signal ground
16 DigIn 4 Not used
17 DigIn 5 Not used
18 DigIn 6 Not used
19 DigIn 7 Not used
20 DigOut 1 Ready
21 DigOut 2 Brake/No trip
22 DigIn 8 Reset
31 N/C 1 Relay 1 output=Trip Active when the AC drive is in a TRIP condition. N/C is opened when the relay is active (valid for all relays) N/O is closed when the relay is active (valid for all relays)
32 COM 1 None
33 N/O 1 None
41 N/C 2 Relay 2 Output=Ready Active when the AC drive is ready to start
42 COM 2 None
43 N/O 2 None
51 COM 3 Relay 3 Output=Not used
52 N/O 3 None

Catalogue — Standard option boards — page 19

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 19

Standard options for TECO F33/V33 2.0

Support for 3 option boards plus 1 communication option.

I/O board 3 extra relay outputs (230 VAC/5 A NO/NC). 3 extra 24 V /3.2 kO (AC or DC) differential digital inputs, all programmable. Inputs providing 50 Vac,dc isolation between channels. Maximum 3 I/O boards can be built -in per AC drive. Part no. 01-3876-01

Encoder board Differential encoder input suitable for 5 V (TTL) or 24 V (HTL) incremental encoders, range 5-16384 pulses/ revolution. Inputs min 9 kO. Max frequency = 100 kHz. For single ended or differential type of encoders (A/B, A’/B’). Selectable encoder supply voltage output 5 VDC or 24 VDC. Part no. 01-3876-03

PTC/PT100 board 1 PTC isolated input conforming DIN 44081/44082. Max 6 PTC thermistors can be connected in series to PTC input. Also including 3 PT100 inputs, 2/3/4-wire, conforming EN 60751. Part no. 01-3876-08

CRIO board (VFX) Crane option board to control hoist or travel motions. Inputs for joystick control: supporting 4-step, motor potentiometer or analog reference joystick types. Inputs for slow down and end limits switches (2+2). All 12 digital inputs 24 V/5 kΩ (8 - 24V) DC. 2 relay outputs 250 V/2AAC, for mechanical brake and load deviation protection. Load dependent field weakening operation of hoists also supported. Part no. 01-3876-07

Crane interface (VFX) Isolated I/O interface for control signals between (existing) crane controls and crane option board (CRIO). • Available for 230 V/27 kΩ (120 - 250V) AC or 24 V /2.7 kQ (15 - 36 V) DC input signals. • LED indications for all inputs and outputs. • For DIN-rail mounting. • HxWxD = 125 x 150 x 50 mm Part no. 590059 (230 VAC) 590060 (24 VDC)

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: Gallery and crane-option sections use VFX/FDU alongside JNVX/JNFX. Retain printed naming and frame associations without inventing a universal alias or claiming crane options for F33.

Context: I/O and encoder prose prints kO, and crane interface 24 V line prints kQ, while other lines use an omega symbol. Preserve source spellings and log ambiguity rather than silently rewriting resistance units.

Context: Source supports 3 option boards plus 1 communication option. Safe stop on B/C/D consumes 1 of 3 positions. Maximum 3 I/O boards does not override that occupied-slot condition.

Catalogue — Communication and coating options — page 20

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 20

Fieldbus - Profibus Fieldbus option module for Profibus DP or DP V1 communication. Use 9-pin D-sub connector. Baud rates: 9.6 kbits/s - 12 Mbits/s supported. Typical drive response time = 10 ms (not including any fieldbus delays). Part no. 01-3876-05

Fieldbus - DeviceNet Fieldbus option module for DeviceNet communication. Baud rates: 125 - 500 kbits/s supported. Typical drive response time = 10 ms (not including any fieldbus delays). Part no. 01-3876-06

Ethernet - Modbus/TCP Industrial Ethernet option module for Modbus/TCP protocol. RJ45 type connector. Baud rates: 10 or 100 Mbits/s supported. Typical drive response time = 10 ms (not including any fieldbus delays). Part no. 01-3876-09

RS232/RS485 isolated Isolated RS232/RS485 serial communication board. For Modbus/ RTU communication protocol. Baud rates: 2400 - 38400 bits/s supported. Typical drive response time = 10 ms (not including any fieldbus delays). Part no. 01-3876-04

Coated boards All drive boards are also available as coated, recommended e.g. for sewer pump applications (chlorine gases) or installations with occasional high humidity (if machine room installation or tropical climate). IEC60721-3-3 gases class 3C3, solid particles class 3S2.

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: 10 ms response excludes fieldbus delay; baud rates, old protocol/software and part numbers are catalogue statements, not current availability/software compatibility verification.

Catalogue — Panels, cable glands and software — page 21

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 21

Control panel kit, incl. blank panel External control panel IP54 suitable for mounting on a cabinet door. This option is to be used in combination with a AC drive module ordered with a built-in control panel. Part no. 01-3957-01

Control panel kit, incl. control panel External control panel IP54 suitable for mounting on a panel door. This option is to be used in combination with a AC drive module ordered with a blank control panel. Part no. 01-3957-00

Handheld Control Panel 2.0 Handheld Control Panel - HCP 2.0 is a complete control panel , easy to connect to the AC drive, for temporary use during e.g. commissioning and service. The HCP has full functionality. It is possible to set parameters, view actual values and fault logger. It is also possible to copy parameter data from one AC drive to the HCP and then load this data to other AC drives. Part no. 01-5039-00 Complete with cable.

EmoSoftCom Connect a PC with a standard RS232 cable under the control panel on the front. EmoSoftCom PC software makes it possible to perform signal recordings and save/load parameter backup data, for example during service & maintenance. .

Glands for frame sizes B, C and D Gland kits are available for size B, C and size D. Metal EMC glands are used for motor and brake resistor cables.

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: 10 ms response excludes fieldbus delay; baud rates, old protocol/software and part numbers are catalogue statements, not current availability/software compatibility verification.

Table conditions: Exact catalogue table, model/option and units as printed. Source blanks and dashes remain distinct; null marks a merged-cell placeholder, with separate source parent-cell context. Catalogue selection data is not a substitute for verified installation instructions.

Panels, cable glands and software / table 1 — PDF page 21

Part number Current and gland range Frame size
01-4601-21 3 - 6A (M16 - M20) B
01-4601-22 8 - 10A (M16 - M25) None
01-4601-23 13 - 18A (M16 - M32) None
01-4399-01 26 - 31A (M12 - M32) C
01-4399-00 37 - 46A (M12 - M40) None
01-4833-00 61 - 74A (M20 - M50) D

Catalogue — Factory-mounted options — page 22

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 22

Factory mounted options for TECO F33/V33, 2.0 Brake chopper All Teco V33/F33 drives can be fitted with an optional built-in brake chopper. Brake choppers are rated for continues braking at drive rated load. This option cannot be after mounted. The brake resistor must be mounted outside the AC drive (see page 23 for Brake resistor option).

DC+/DC- connection DC+/DC- terminals for external connection of the Teco V33/F33 drive DC link. This option is required if using the Overshoot clamp.

Standby power supply Built-in standby power supply board. To be connected to external 24 V AC/ DC supply voltage. If the main power is switched off, the control board, control panel and the connected options, for example fieldbus communication, will continue to operate. Part no: 01-3954-00

Safe stop Extra built-in inputs and outputs for emergency stop circuit conforming with the norms EN-IEC 62061:2005 SIL2 and EN-ISO 13849-1:2006. Safe stop for size B, C and D (uses 1 of the 3 option positions) Safe stop for size E and up

Blank control panel Blank panel instead of control panel (to maintain IP54). Indication LED’s for Power, Run and Trip available.

PTC Factory mounted, isolated motor PTC input conforming to DIN44081/ 44082, available with size B, C and D. Use PTC/PT100 option board if additional inputs are needed.

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: UL 840, DNV, CE/GOST marks and EN-IEC 62061:2005 SIL2 / EN-ISO 13849-1:2006 are source claims only. No current approval, certification scope or engineered safety-system acceptance is asserted.

Context: Source supports 3 option boards plus 1 communication option. Safe stop on B/C/D consumes 1 of 3 positions. Maximum 3 I/O boards does not override that occupied-slot condition.

Context: Brake chopper cannot be after-mounted and brake resistor is external. Overshoot clamp needs DC+/DC− connection; B to F(69) order condition retained. Do not present as universal retrofit availability.

Context: Brake text refers to page 23, but resistors are printed 25 / PDF 26. Choke/sine text refers to filter guide page 24, but the guide is printed 26 / PDF 27. Preserve original references and provide actual provenance.

Catalogue — EMC filters — page 23

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 23

EMC filter class C2 EMC filter according to EN61800- 3:2004 class C2 - 1st environment restricted distribution. For sizes B, C and D. Integrated inside the drive module. Note: EMC filter acc. to class C3 - 2nd environment included as standard in all drive units.

Extended options for TECO F33/V33 2.0

Extended EMC filter 90-650A EMC filter according to EN61800-3:2004 class C2 - 1st environment, restricted distribution. From frame size E. Rated voltage=480 V, 50/60 Hz. Max. 40 °C ambient temperature.

1=Screw terminal (protected) 2=Busbar terminals

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: JNVX/JNFX48-300 filter type is printed 3F480300.230 without the hyphen used in nearby types. Retain exact source code, no guessed replacement.

Context: IP20 superscript 1 and IP00 superscript 2 were parsed as IP201/IP002. Reviewed values explicitly separate footnote 1/2; raw originals and 12 before/after records retained. Footnote 1 = screw terminal (protected); 2 = busbar.

Table conditions: Exact catalogue table, model/option and units as printed. Source blanks and dashes remain distinct; null marks a merged-cell placeholder, with separate source parent-cell context. Catalogue selection data is not a substitute for verified installation instructions. External EMC filter: 480 V 50/60 Hz, maximum40 C, frame E upward, C2 first-environment restricted distribution. Superscripts1/2 are footnote markers, not IP201/IP002 classifications.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. Source external filter conditions 480 V/50–60 Hz/40°C/frame E upward/C2 restricted distribution with reviewer superscript interpretation; 1/2 are footnotes, not enclosure class digits.

EMC filters / table 1 — PDF page 23

Drive model Filter type Dimensions HxWxD mm Weight kg Enclosure with footnote marker
JNVX/JNFX48-090 3F480-100.230 325x150x107 7.1 IP20 [footnote 1]
JNVX/JNFX48-109 3F480-125.230 345x175x127 10 IP20 [footnote 1]
JNVX/JNFX48-146 3F480-150.230 375x175x135 10 IP20 [footnote 1]
JNVX/JNFX48-175 3F480-180.230 490x170x158 13.5 IP00 [footnote 2]
JNVX/JNFX48-210 3F480-220.230 490x170x158 13.5 IP00 [footnote 2]
JNVX/JNFX48-250 3F480-250.230 490x230x158 18.2 IP00 [footnote 2]
JNVX/JNFX48-300 3F480300.230 490x230x158 18.2 IP00 [footnote 2]
JNVX/JNFX48-375 3F480-400.230 580x230x158 22 IP00 [footnote 2]
JNVX/JNFX48-430 3F480-500.230 630x345x158 37.5 IP00 [footnote 2]
JNVX/JNFX48-500 3F480-500.230 630x345x158 37.5 IP00 [footnote 2]
JNVX/JNFX48-600 3F480-600.230 660x375x187 42 IP00 [footnote 2]
JNVX/JNFX48-650 3F480-700.230 865x345x157 42 IP00 [footnote 2]

Catalogue — Output chokes and overshoot clamp — page 24

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 24

Output choke (dU/dt) Output chokes (supplied separately) are recommended above app. 100 m cable length for all single drives. Consult your supplier in case of paralleled drives. Due to the switching of output voltage, high capacitive peak currents will run through the parasitic capacitances between the phases and to earth. Screened cables have more parasitic capacitances. Output chokes should be installed as close as possible to the drive output. Output chokes also limits voltage peaks at motor winding. Rated voltage = 800 V, IP00 units. Suitable for up to IP23 cabinet installation. Max. 40°C ambient temperature. Parallel connection of output coils possible if higher current rating required (e.g. one filter per PEBB). For further advice when to use output options see filter selection guide, page 24

Overshoot clamp Together with the output choke, the overshoot clamp restricts the voltage and the dV/dt on the motor winding. For rated voltages 380 - 690 V. H x W x D = 250 x 145 x 95 mm Part no. 052163 (size B–F) 052220 (size G–K) NOTE: AC drive, frame sizes B up to F(69), must be ordered including the option DC+/DC--connections.

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: Brake chopper cannot be after-mounted and brake resistor is external. Overshoot clamp needs DC+/DC− connection; B to F(69) order condition retained. Do not present as universal retrofit availability.

Context: Brake text refers to page 23, but resistors are printed 25 / PDF 26. Choke/sine text refers to filter guide page 24, but the guide is printed 26 / PDF 27. Preserve original references and provide actual provenance.

Table conditions: Exact catalogue table, model/option and units as printed. Source blanks and dashes remain distinct; null marks a merged-cell placeholder, with separate source parent-cell context. Catalogue selection data is not a substitute for verified installation instructions. Output choke nominal 800 V, IP00 unit, suitable up to IP23 cabinet installation, maximum40 C. Consult supplier for parallel drives.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. Source output choke 800 V/IP00/up to IP23 cabinet/40°C and parallel-drive referral, combined with extraction rules.

Output chokes and overshoot clamp / table 1 — PDF page 24

Nominal current IN A/phase Inductance L mH Weight kg Dimensions HxWxD mm Part number
2.8 1.5 0.6 60x78x95 473160 00
4.4 1 0.6 60x78x95 473161 00
6.6 0.65 0.6 60x78x95 473162 00
11 0.4 1 65x96x105 473163 00
14.3 0.3 1 65x96x105 473164 00
18.2 0.25 1.2 74x96x105 473165 00
26.4 0.175 1.2 74x96x105 473166 00
32 0.15 1.7 84x125x140 473167 00
65 0.1 4 105x155x205 473168 00
90 0.1 8.4 120x90x235 473169 00
146 0.05 10.2 140x190x260 473170 00
175 0.05 13.4 160x210x180 473171 00
275 0.032 18.4 170x230x200 473172 00
320 0.025 18.9 170x230x200 473173 00
410 0.021 22.6 180x240x210 473174 00

Catalogue — Sine-wave and common-mode filters — page 25

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 25

Sine wave filter Only for use with F33 drives. Rated voltage= 400 V ±25 %, 50/60 Hz (690 V on request). Max. 40 °C ambient temperature. IP20= with enclosure and screw terminals. IP00=no enclosure and busbar connections. Voltage drop approximately 25 V at rated current, 50 Hz. Overload: 110 % for 5 min, 150 % for 2 min or 200 % for 30 s. For further information see filter selection guide, page 24

Common mode filter Common mode filters are mainly used to reduce common mode currents in motors (typically used with motors >size 280). Common mode filters can prevent damage of motor bearings. All three motor phases are to be routed through common mode filter rings. These filter can also be used to reduce EMC emissions in supply cables. Part no. 052213 (size G - K69 require one Common mode filter per PEBB).

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: Brake text refers to page 23, but resistors are printed 25 / PDF 26. Choke/sine text refers to filter guide page 24, but the guide is printed 26 / PDF 27. Preserve original references and provide actual provenance.

Context: Sine-wave filters are expressly for F33 only, even though the brochure is shared with V33. Retain 400 V ±25%, 50/60 Hz, 690 V on request, 40 C maximum, overload conditions and voltage-drop statement.

Table conditions: Exact catalogue table, model/option and units as printed. Source blanks and dashes remain distinct; null marks a merged-cell placeholder, with separate source parent-cell context. Catalogue selection data is not a substitute for verified installation instructions. Sine-wave filters FOR F33 ONLY: 400 V ±25%,50/60 Hz;690 V on request;max40 C;110%5min/150%2min/200%30s. IP20 enclosure/screw terminals versus IP00 no enclosure/busbar.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. Source sine-wave filter is F33-only: 400 V ±25%, 50/60 Hz, 690 V on request, 40°C and three overload durations; enclosure distinctions retained. No extension to V33 or common-mode filter inferred.

Sine-wave and common-mode filters / table 1 — PDF page 25

Filter type suffix (prefix 3AFS400-) Protection class Power kW Nominal current IN A/phase Power loss W Weight kg Dimensions HxWxD mm
002.5 IP20 0.75 2.5 75 5 190x165x160
004 IP20 1.5 4 90 5 190x165x160
007 IP20 2.2 7 125 7 250x162x162
010 IP20 4 10 165 9 250x162x162
013 IP20 5.5 13 190 12 250x162x162
016 IP20 7.5 16 220 13 300x210x180
025 IP20 11 25 250 18 300x250x210
035 IP20 15 35 275 25 300x270x235
010 IP00 4 10 165 9 195x200x115
013 IP00 5.5 13 190 12 225x200x115
016 IP00 7.5 16 220 13 225x240x135
025 IP00 11 25 250 18 270x250x160
035 IP00 15 35 275 25 270x250x160
050 IP00 22 50 320 45 280x300x250
063 IP00 30 63 550 49 270x300x370
080 IP00 37 80 380 65 324x360x320
100 IP00 45 100 530 65 324x360x320
125 IP00 55 125 650 85 335x390x320
150 IP00 75 150 580 119 440x480x340
180 IP00 90 180 760 131 440x480x340
250 IP00 132 250 600 135 420x420x390
300 IP00 160 300 1000 140 420x420x390
400 IP00 200 400 1100 320 440x500x400
500 IP00 250 500 1250 335 470x500x400

Catalogue — Brake resistors and liquid cooling — page 26

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 26

Brake resistors

VPR= Compact – IP54 with 0.75 m shielded cable.

BEGT= Steel grid resistor – IP20 or IP23 with thermo contact.

For dynamic braking by connection to the drive brake chopper output (optional).

__R: resistance in ohm, example 26R=26 ohm R: resistance in ohm, example 6R5=6.5 ohm

Drive modules in frame sizes E - K and F69 – K69 are available in a liquid cooled versions. These units are designed for connection to a liquid cooling system, normally a heat exchanger of liquid – liquid or liquid - air type. Heat exchanger is not part of the liquid cooling option. Drive units with parallel power modules (frame size G – K69) are delivered with a dividing unit for connection of the cooling system. The drive units are equipped with rubber hoses with leak-proof quick couplings.

Liquid cooling

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: Overview says above 90 A; detailed option includes E–K/F69–K69. Preserve both without resolving boundary eligibility for a 90 A model. Heat exchanger explicitly excluded; parallel-module dividing unit retained.

Context: Brake text refers to page 23, but resistors are printed 25 / PDF 26. Choke/sine text refers to filter guide page 24, but the guide is printed 26 / PDF 27. Preserve original references and provide actual provenance.

Context: The first five VPR/DEGT rows do not supply 60% duty power values. Empty cells remain empty, never zero or interpolated. Dash in second dimensions column remains distinct.

Context: Single BEGT 47#120-R IP23 cell prints 301x483x736 versus IP20 1321x483x736 and the 2x version 2x(1481x483x736). Exact printed value retained; no inferred repair.

Context: Source # = 2 IP20 / # = 4 IP23 and __R/R ohmic placeholders with examples retained. Do not generate unprinted orderable resistance variants.

Table conditions: Exact catalogue table, model/option and units as printed. Source blanks and dashes remain distinct; null marks a merged-cell placeholder, with separate source parent-cell context. Catalogue selection data is not a substitute for verified installation instructions. First five VPR/DEGT rows use IP54 dimensions; following BEGT rows use IP20/IP23 columns. Duty columns are percentages, resistance placeholders require ohmic value; do not infer blank60% powers.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. Source first five VPR/DEGT IP54 rows versus BEGT IP20/IP23 dimensions with reviewer blank-duty/placeholder rules; no power inferred from blank 60% cells.

Brake resistors and liquid cooling / table 1 — PDF page 26

Type Power kW at 100% duty Power kW at 60% duty Power kW at 40% duty Power kW at 25% duty Power kW at 6% duty Dimensions HxWxD mm: IP54 for VPR/DEGT, IP20 for BEGT Dimensions HxWxD mm: dash for VPR/DEGT, IP23 for BEGT
VPR 200-__R 0.2 0.47 0.74 3.6 200x60x31 –
VPR 300-__R 0.3 0.705 1.11 5.4 250x60x31 –
VPR 400-__R 0.4 0.94 1.48 7.2 301x60x31 –
VPR 500-__R 0.5 1.175 1.85 9.0 370x60x31 –
DEGT1VPR1000S_R-S 1 2.0 3.7 13.0 542x98x170 –
BEGT 13#05-__R 2.5 3.25 4.25 6.25 21.0 301x483x326 500x483x326
BEGT 13#08-__R 4.0 5.2 6.8 10.0 34.0 301x483x326 500x483x326
BEGT 13#10-_R_ 5.0 6.5 8.5 12.5 42.5 301x483x326 500x483x326
BEGT 14#15-_R_ 7.5 9.8 12.7 18.7 64.0 301x483x426 500x483x426
BEGT 15#20-_R_ 10.0 13.0 17.0 25.0 85.0 301x483x526 500x483x526
BEGT 17#30-_R_ 15.0 19.5 25.5 37.5 127.0 301x483x740 500x483x740
BEGT 25#40-_R_ 20.0 26.0 34.0 50.0 170.0 601x484x526 800x484x526
BEGT 27#60-_R_ 30.0 39.0 51.0 75.0 255.0 601x484x736 800x484x736
BEGT 37#90-_R_ 40.0 52.0 68.0 100.0 340.0 1021x484x736 1181x484x736
BEGT 47#120-_R_ 50.0 65.0 85.0 125.0 425.0 1321x483x736 301x483x736
2xBEGT 27#60-_R_ 60.0 78.0 102.0 150.0 510.0 2x(601x484x736) 2x(800x484x736)
2xBEGT 37#78-_R_ 70.0 91.0 119.0 175.0 600.0 2x(1021x484x736) 2x(1181x484x736)
2xBEGT 37#90-_R_ 80.0 104.0 136.0 200.0 680.0 2x(1021x484x736) 2x(1181x484x736)
2xBEGT 47#120-_R_ 100.0 130.0 170.0 250.0 850.0 2x(1321x483x736) 2x(1481x483x736)

Catalogue — Filter selection guide — page 27

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 27

Filter selection guide

Recommendations with the different supply voltages up to and including 480 V

X = advised solution for this setup

Recommendations with the different supply voltages from 500 V - 690 V

Remarks

Cable lengths should always be as short as possible. The table is based on correct EMC wiring with shielded cable and proper EMC installation. For powers below 7.5 kW and long motor cables please contact Teco. Voltage drop over the complete system must be less than 10% of the main supply. Sine wave filters are only for use with Teco F33 range of drives. * Conducted interference limits on unshielded motor - lines according to EN61800-3, table 16. ** No marks in a row, means that there is no need to take precautions.

Context: No printed edition/date established; retain exact source hash and P034/P037 document associations.

Context: Brake text refers to page 23, but resistors are printed 25 / PDF 26. Choke/sine text refers to filter guide page 24, but the guide is printed 26 / PDF 27. Preserve original references and provide actual provenance.

Context: Sine-wave filters are expressly for F33 only, even though the brochure is shared with V33. Retain 400 V ±25%, 50/60 Hz, 690 V on request, 40 C maximum, overload conditions and voltage-drop statement.

Context: Keep ≤480 V and 500–690 V matrices separate. X is an advised solution; qualitative blank cells are not zero effect. The ** no-precaution statement is limited to the source row/conditions. Correct EMC installation, shielded cables, short cables, total drop <10%, below 7.5 kW long-cable referral and F33-only sine restriction remain attached.

Table conditions: Exact catalogue table, model/option and units as printed. Source blanks and dashes remain distinct; null marks a merged-cell placeholder, with separate source parent-cell context. Catalogue selection data is not a substitute for verified installation instructions. Qualitative effect matrix; empty cells are not inferred to mean ineffective. X means advised solution; ** no marks means no precautions in the stated source situation only. Correct EMC wiring,shielded cable,proper installation,total voltage drop<10%,F33-only sine filter restriction and below7.5kW/long-cable supplier referral remain attached.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. Source qualitative matrix and surrounding selection remarks with reviewer empty-cell rule. X/no-mark statements belong to the recommendation matrices and stated conditions, not automatic equivalence of every blank effect cell.

Table conditions: Exact catalogue table, model/option and units as printed. Source blanks and dashes remain distinct; null marks a merged-cell placeholder, with separate source parent-cell context. Catalogue selection data is not a substitute for verified installation instructions. Supply up to and including480 V. X means advised solution; ** no marks means no precautions in the stated source situation only. Correct EMC wiring,shielded cable,proper installation,total voltage drop<10%,F33-only sine filter restriction and below7.5kW/long-cable supplier referral remain attached.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. Source ≤480 V recommendation matrix and printed installation/voltage-drop/F33-only/referral conditions with reviewer preservation rules.

Table conditions: Exact catalogue table, model/option and units as printed. Source blanks and dashes remain distinct; null marks a merged-cell placeholder, with separate source parent-cell context. Catalogue selection data is not a substitute for verified installation instructions. Supply500–690 V. X means advised solution; ** no marks means no precautions in the stated source situation only. Correct EMC wiring,shielded cable,proper installation,total voltage drop<10%,F33-only sine filter restriction and below7.5kW/long-cable supplier referral remain attached.

Scope clarification: Reviewer-authored table context; not a literal supplier quotation. Source 500–690 V recommendation matrix and printed installation/voltage-drop/F33-only/referral conditions with reviewer preservation rules.

Filter selection guide / table 1 — PDF page 27

Phenomenon Common-mode filter Output choke Output choke and overshoot clamp Sine-wave filter All-pole sine-wave filter
Common mode currents Effective Limited effect Limited effect Effective Very effective
Bearing currents Effective Very effective
Voltage spikes U-V-W Limited effect Very effective Very effective Very effective
Voltage spikes U-PE Limited effect Effective Limited effect Very effective
dU/dt Effective Effective Very effective Very effective
Minimize motor audible noise Limited effect Limited effect Effective Effective
EMC conducted emission Limited effective Limited effect Limited effect Effective Very effective

Filter selection guide / table 2 — PDF page 27

Situation Cable-length qualification Common-mode filter Output choke Output choke and overshoot clamp Sine-wave filter All-pole sine-wave filter
Not rated, delicate or difficult positioned motors None X X
Motor in frame size >280 None X
IEC 60034-17 motor None X
IEC 60034-25 Curve A motor Cable lengths 0-100m**
None Cable lengths 100-200m X
None Cable lengths 200-500m X
Dynamic use with frequently raised DC voltage (braking) None X
Unshielded cables * None X

Filter selection guide / table 3 — PDF page 27

Situation Cable-length qualification Common-mode filter Output choke Output choke and overshoot clamp Sine-wave filter All-pole sine-wave filter
Not rated, delicate or difficult positioned motors None X X
Motor in frame size >280 None X
3 kV isolation windings ** None
IEC 60034-25 Curve B motor Cable lengths 0-100m**
None Cable lengths 100-200m X
None Cable lengths 200-500m X
Dynamic use with frequently raised DC voltage (braking) None X
Unshielded cables * None X

Catalogue — TECO back cover — page 28

TECO-F33-V33-CATALOGUE.pdf · P034, P037 · source page 28

TECO;www.teco.com.au.

Context: Website source reference only; no contact freshness or edition inferred.

Manual — TECO F33 AC drive — page 1

Manual reference: physical PDF page 1. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

TECO F33

AC drive

Instruction manual

English

Software version 4.3X

Cover product illustrations not numerical model ratings.

Manual — Edition r3, software4.3X publication identity. Collected P034 association; no extrapolation to other variants. — page 2

Manual reference: physical PDF page 2. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

F33

INSTRUCTION MANUAL - ENGLISH

Software version 4.3X

Document number:

Edition: r3

Date of release: 30-01-2011

© Copyright the manufacturer of F33 2005 - 2011

The manufacturer retains the right to change specifications and

illustrations in the text, without prior notification. The contents of

this document may not be copied without the explicit permission of

the manufacturer.

Manual — Blank page — page 3

Manual reference: physical PDF page 3. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Visually blank page.

Manual — Safety instructions. Collected P034 association; no extrapolation to other variants. — page 4

Manual reference: physical PDF page 4. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Safety Instructions

Instruction manual

Read this instruction manual before using the AC drive

(Frequency converter).

The following symbols can appear in this manual.

Always read these first before continuing:

Handling the AC drive

Installation, commissioning, demounting, taking

measurements, etc, of or on the AC drive may only be

carried out by personnel technically qualified for the

task. The installation must be carried out in accordance

with local standards.

Opening the AC drive

Always take adequate precautions before opening the

AC drive. Although the connections for the control sig-

nals and the switches are isolated from the main volt-

age, do not touch the control board when the AC drive is

switched on.

Precautions to be taken with a

connected motor

If work must be carried out on a connected motor or on

the driven machine, the mains voltage must always be

disconnected from the AC drive first. Wait at least 7

minutes before starting work.

Earthing

The AC drive must always be earthed via the mains

safety earth connection.

Earth leakage current

Residual current device (RCD)

compatibility

This product cause a DC current in the protective

conductor. Where a residual current device (RCD) is

used for protection in case of direct or indirect contact,

only a Type B RCD is allowed on the supply side of this

product. Use RCD of 300 mA minimum.

EMC Regulations

In order to comply with the EMC Directive, it is abso-

lutely necessary to follow the installation instructions.

All

installation descriptions in this manual follow the EMC

Directive.

Mains voltage selection

The AC drive may be ordered for use with the mains

voltage range listed below.

JNFX48: 230-480 V

JNFX52: 440-525 V

JNFX69: 500-690 V

Voltage tests (Megger)

Do not carry out voltage tests (Megger) on the motor,

before all the motor cables have been disconnected

from the AC drive.

NOTE: Additional information as an aid to avoid

problems.

CAUTION!

Failure to follow these instructions can result

in malfunction or damage to the AC drive.

WARNING!

in serious injury to the user in addition to

serious damage to the AC drive.

HOT SURFACE!

in injury to the user.

Always switch off the mains voltage before

opening the AC drive and wait at least

7minutes to allow the buffer capacitors to

discharge.

!

This AC drive has an earth leakage current

which does exceed 3.5 mA AC. Therefore the

minimum size of the protective earth

conductor must comply with the local safety regulations

for high leakage current equipment which means that

according the standard IEC61800-5-1 the protective

earth connection must be assured by one of following

conditions:

  1. Use a protective conductor with a cable cross-

section of at least 10 mm2 for copper (Cu) or 16 mm2

for aluminium (Al).

  1. Use an additional PE wire, with the same cable

cross-section as the used original PE and mains

supply wiring.

Manual — Safety instructions continued. Collected P034 association; no extrapolation to other variants. — page 5

Manual reference: physical PDF page 5. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Condensation

If the AC drive is moved from a cold (storage) room to a

room where it will be installed, condensation can occur.

This can result in sensitive components becoming

damp. Do not connect the mains voltage until all visible

dampness has evaporated.

Incorrect connection

The AC drive is not protected against incorrect connec-

tion of the mains voltage, and in particular against con-

nection of the mains voltage to the motor outlets U, V

and W. The AC drive can be damaged in this way.

Power factor capacitors for improving

cosϕ

Remove all capacitors from the motor and the motor

outlet.

Precautions during Autoreset

When the automatic reset is active, the motor will

restart automatically provided that the cause of the trip

has been removed. If necessary take the appropriate

precautions.

Transport

To avoid damage, keep the AC drive in its original

packaging during transport. This packaging is specially

designed to absorb shocks during transport.

IT Mains supply

The AC drives can be modified for an IT mains supply,

(non-earthed neutral), please contact your supplier for

details.

Heat warning

DC-link residual voltage

HOT SURFACE!

Be aware of specific parts on the AC drive

having high temperature.

WARNING!

After switching off the mains supply,

dangerous voltage can still be present in the

AC drive. When opening the AC drive for

installing and/or commissioning activities

wait at least 7 minutes. In case of malfunction a

qualified technician should check the DC-link or wait for

one hour before dismantling the AC drive for repair.

Manual — Contents printed page3. Collected P034 association; no extrapolation to other variants. — page 6

Manual reference: physical PDF page 6. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Contents

Safety Instructions ......................................... 1

Contents.......................................................... 3

1.

Introduction..................................................... 5

1.1

Delivery and unpacking ............................................ 5

1.2

Using of the instruction manual............................... 5

1.3

Type code number..................................................... 5

1.4

Standards .................................................................. 6

1.4.1

Product standard for EMC ........................................ 6

1.5

Dismantling and scrapping....................................... 7

1.5.1

Disposal of old electrical and electronic

equipment ................................................................. 7

1.6

Glossary ..................................................................... 8

1.6.1

Abbreviations and symbols....................................... 8

1.6.2

Definitions.................................................................. 8

2.

Mounting......................................................... 9

2.1

Lifting instructions..................................................... 9

2.2

Stand-alone units.................................................... 10

2.2.1

Cooling ..................................................................... 10

2.2.2

Mounting schemes.................................................. 10

2.3

Cabinet mounting.................................................... 13

2.3.1

Cooling ..................................................................... 13

2.3.2

Recommended free space in front of cabinet ...... 13

2.3.3

Mounting schemes.................................................. 14

3.

Installation................................................... 15

3.1

Before installation................................................... 15

3.2

Cable connections for model 003 to 074............. 15

3.2.1

Mains cables ........................................................... 15

3.2.2

Motor cables............................................................ 16

3.3

Connection of motor and mains cables for

model 090 and up .................................................. 18

3.3.1

Connection of mains and motor cables on IP20

modules ................................................................... 19

3.4

Cable specifications................................................ 20

3.5

Stripping lengths ..................................................... 20

3.5.1

Dimension of cables and fuses.............................. 21

3.5.2

Tightening torque for mains and motor cables..... 21

3.6

Thermal protection on the motor........................... 21

3.7

Motors in parallel .................................................... 21

4.

Control Connections.................................... 23

4.1

Control board........................................................... 23

4.2

Terminal connections ............................................. 24

4.3

Inputs configuration

with the switches..................................................... 24

4.4

Connection example ............................................... 25

4.5

Connecting the Control Signals.............................. 26

4.5.1

Cables ...................................................................... 26

4.5.2

Types of control signals .......................................... 27

4.5.3

Screening................................................................. 27

4.5.4

Single-ended or double-ended connection? ......... 27

4.5.5

Current signals ((0)4-20 mA).................................. 28

4.5.6

Twisted cables......................................................... 28

4.6

Connecting options ................................................. 28

5.

Getting Started............................................. 29

5.1

Connect the mains and motor cables ................... 29

5.1.1

Mains cables ........................................................... 29

5.1.2

Motor cables............................................................ 29

5.2

Using the function keys .......................................... 29

5.3

Remote control........................................................ 30

5.3.1

Connect control cables........................................... 30

5.3.2

Switch on the mains ............................................... 30

5.3.3

Set the Motor Data.................................................. 30

5.3.4

Run the AC drive...................................................... 30

5.4

Local control............................................................ 31

5.4.1

Switch on the mains ............................................... 31

5.4.2

Select manual control............................................. 31

5.4.3

Set the Motor Data.................................................. 31

5.4.4

Enter a Reference Value......................................... 31

5.4.5

Run the AC drive...................................................... 31

6.

Applications.................................................. 33

6.1

Application overview ............................................... 33

6.1.1

Pumps...................................................................... 33

6.1.2

Fans ......................................................................... 33

6.1.3

Compressors ........................................................... 34

6.1.4

Blowers .................................................................... 34

7.

Main Features .............................................. 35

7.1

Parameter sets........................................................ 35

7.1.1

One motor and one parameter set ........................ 36

7.1.2

One motor and two parameter sets....................... 36

7.1.3

Two motors and two parameter sets..................... 36

7.1.4

Autoreset at trip ...................................................... 36

7.1.5

Reference priority.................................................... 36

7.1.6

Preset references.................................................... 37

7.2

Remote control functions....................................... 37

7.3

Performing an Identification Run........................... 40

7.4

Using the Control Panel Memory............................ 40

7.5

Load Monitor and Process Protection [400]......... 40

7.5.1

Load Monitor [410]................................................. 40

7.6

Pump function......................................................... 42

7.6.1

Introduction ............................................................. 42

7.6.2

Fixed MASTER ......................................................... 43

7.6.3

Alternating MASTER................................................ 43

7.6.4

Feedback 'Status' input .......................................... 43

7.6.5

Fail safe operation .................................................. 44

7.6.6

PID control ............................................................... 45

7.6.7

Wiring Alternating Master....................................... 46

7.6.8

Checklist And Tips................................................... 47

7.6.9

Functional Examples of Start/Stop Transitions.... 48

8.

EMC and Machine Directive........................ 51

8.1

EMC standards........................................................ 51

8.2

Stop categories and emergency stop .................... 51

9.

Operation via the Control Panel.................. 53

Manual — Contents printed page4. Collected P034 association; no extrapolation to other variants. — page 7

Manual reference: physical PDF page 7. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

9.1

General .................................................................... 53

9.2

The control panel .................................................... 53

9.2.1

The display............................................................... 53

9.2.2

Indications on the display....................................... 54

9.2.3

LED indicators ......................................................... 54

9.2.4

Control keys............................................................. 54

9.2.5

The Toggle and Loc/Rem Key ................................ 54

9.2.6

Function keys .......................................................... 56

9.3

The menu structure................................................. 56

9.3.1

The main menu ....................................................... 56

9.4

Programming during operation .............................. 57

9.5

Editing values in a menu ........................................ 57

9.6

Copy current parameter to all sets ........................ 57

9.7

Programming example............................................ 58

10.

Serial communication ................................. 59

10.1

Modbus RTU ............................................................ 59

10.2

Parameter sets........................................................ 59

10.3

Motor data............................................................... 60

10.4

Start and stop commands...................................... 60

10.5

Reference signal ..................................................... 60

10.5.1

Process value .......................................................... 60

10.6

Description of the EInt formats.............................. 61

11.

Functional Description................................ 63

11.1

Preferred View [100]............................................... 63

11.1.1

1st Line [110].......................................................... 63

11.1.2

2nd Line [120] ........................................................ 64

11.2

Main Setup [200].................................................... 64

11.2.1

Operation [210]....................................................... 64

11.2.2

Remote Signal Level/Edge [21A]........................... 68

11.2.3

Mains supply voltage [21B].................................... 68

11.2.4

Motor Data [220] .................................................... 69

11.2.5

Motor Protection [230]........................................... 74

11.2.6

Parameter Set Handling [240]............................... 77

11.2.7

Trip Autoreset/Trip Conditions [250]..................... 80

11.2.8

Serial Communication [260].................................. 87

11.3

Process and Application Parameters [300] .......... 90

11.3.1

Set/View Reference Value [310] ........................... 90

11.3.2

Process Settings [320] ........................................... 91

11.3.3

Start/Stop settings [330] ....................................... 94

11.3.4

Mechanical brake control....................................... 98

11.3.5

Speed [340]........................................................... 101

11.3.6

Torques [350]........................................................ 104

11.3.7

Preset References [360] ...................................... 106

11.3.8

PID Process Control [380].................................... 107

11.3.9

Pump/Fan Control [390] ...................................... 111

11.4

Load Monitor and Process Protection [400]....... 117

11.4.1

Load Monitor [410]............................................... 117

11.4.2

Process Protection [420]...................................... 122

11.5

I/Os and Virtual Connections [500]..................... 123

11.5.1

Analogue Inputs [510].......................................... 123

11.5.2

Digital Inputs [520]............................................... 130

11.5.3

Analogue Outputs [530] ....................................... 132

11.5.4

Digital Outputs [540] ............................................ 136

11.5.5

Relays [550] .......................................................... 138

11.5.6

Virtual Connections [560]..................................... 139

11.6

Logical Functions and Timers [600].................... 140

11.6.1

Comparators [610] ............................................... 140

11.6.2

Logic Output Y [620]............................................. 151

11.6.3

Logic Output Z [630]............................................. 153

11.6.4

Timer1 [640] ......................................................... 154

11.6.5

Timer2 [650] ......................................................... 156

11.7

View Operation/Status [700] ............................... 157

11.7.1

Operation [710]..................................................... 157

11.7.2

Status [720] .......................................................... 160

11.7.3

Stored values [730] .............................................. 163

11.8

View Trip Log [800] ............................................... 164

11.8.1

Trip Message log [810]......................................... 164

11.8.2

Trip Messages [820] - [890] ................................ 165

11.8.3

Reset Trip Log [8A0] ............................................. 166

11.9

System Data [900]................................................ 166

11.9.1

VSD Data [920] ..................................................... 166

12.

Troubleshooting, Diagnoses and

Maintenance .............................................. 169

12.1

Trips, warnings and limits..................................... 169

12.2

Trip conditions, causes and remedial action ...... 170

12.2.1

Technically qualified personnel............................ 170

12.2.2

Opening the AC drive ............................................ 170

12.2.3

Precautions to take with a connected motor...... 170

12.2.4

Autoreset Trip........................................................ 170

12.3

Maintenance ......................................................... 174

13.

Options........................................................ 175

13.1

Options for the control panel................................ 175

13.2

Handheld Control Panel 2.0................................. 175

13.3

EmoSoftCom.......................................................... 175

13.4

Brake chopper....................................................... 176

13.5

I/O Board ............................................................... 177

13.6

Encoder.................................................................. 177

13.7

PTC/PT100............................................................ 177

13.8

Serial communication and fieldbus..................... 178

13.9

Standby supply board option................................ 178

13.10

Safe Stop option.................................................... 179

13.11

Output chokes....................................................... 181

13.12

Liquid cooling ........................................................ 181

14.

Technical Data ........................................... 183

14.1

Electrical specifications related to model ........... 183

14.2

General electrical specifications.......................... 187

14.3

Operation at higher temperatures ....................... 188

14.4

Operation at higher switching frequency............. 188

14.5

Dimensions and Weights...................................... 189

14.6

Environmental conditions..................................... 190

14.7

Fuses, cable cross-sections and glands.............. 191

14.7.1

According IEC ratings............................................ 191

14.7.2

Fuses and cable dimensions according to

NEMA ratings......................................................... 193

14.8

Control signals....................................................... 195

15.

Menu List.................................................... 197

Index ........................................................... 205

Manual — Introduction and type code positions1–10. Collected P034 association; no extrapolation to other variants. — page 8

Manual reference: physical PDF page 8. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

1.

Introduction

TECO F33 is used most commonly to control and pro-

tect pump and fan applications that put high demands

on flow control, process uptime and low maintenance

costs. It can also be used for e.g. compressors and

blowers. The used motor control method is V/Hz-con-

trol. Several options are available, listed in chapter 13.

page 175, that enable you to customize the AC drive for

your specific needs.

Users

This instruction manual is intended for:

• installation engineers

• maintenance engineers

• operators

• service engineers

Motors

The AC drive is suitable for use with standard 3-phase

asynchronous motors. Under certain conditions it is

possible to use other types of motors. Contact your sup-

plier for details.

1.1

Delivery and unpacking

Check for any visible signs of damage. Inform your sup-

plier immediately of any damage found. Do not install

the AC drive if damage is found.

The AC drives are delivered with a template for position-

ing the fixing holes on a flat surface. Check that all

items are present and that the type number is correct.

1.2

Using of the instruction

manual

Within this instruction manual the abbreviation “AC

drive” is used to indicate the complete variable speed

drive as a

single unit.

Check that the software version number on the first

page of this manual matches the software version in

the AC drive. See chapter 11.9 page 166

With help of the index and the table of contents it is

easy to track individual functions and to find out how to

use and set them.

The Quick Setup Card can be put in a cabinet door, so

that it is always easy to access in case of an emer-

gency.

1.3

Type code number

Fig. 1 gives an example of the type code numbering

used on all AC drives. With this code number the exact

type of the drive can be determined. This identification

will be required for type specific information when

mounting and installing. The code number is located on

the product label, on the front of the unit.

Fig. 1

NOTE: Read this instruction manual carefully before

starting installation, connection or working with the AC

drive.

JNFX48-0175-0054 C E – – – A – N N N N A N –

Position number:

5 6 7 8 9 10 11 12 13 14 15 16 17 18

Type code positions1–10. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation.

Type code positions1–10 — PDF page 8

Source row Position for 0003- 0074 Position for 0090- 1500 Configuration ⟦blank source cell⟧
1 1 1 AC drive type F33 V33
2 2 2 Supply voltage 48=400 V mains 52=525 V mains 69=690 V mains
3 3 3 Rated current (A) continuous -003=2.5 A - -1K5=1500 A
4 4 4 Protection class 20=IP20 54=IP54
5 5 5 Control panel –=Blank panel C=Standard panel
6 6 6 EMC option E=Standard EMC (Category C3) F=Extended EMC (Category C2) I=IT-Net
7 7 7 Brake chopper option –=No chopper B=Chopper built in D=DC+/- interface
8 8 8 Stand-by power supply option –=No SBS S=SBS included
9 - 9 Safe stop option (Only valid for 090-1500) –=No safe stop T=Safe stop incl.
10 9 10 Brand label ⟦blank source cell⟧
11 10 - Painted AC drive (Only valid for 003-074) A=Standard paint B=White paint RAL9010

Manual — Type code positions11–18 and EMC source claims. Collected P034 association; no extrapolation to other variants. — page 9

Manual reference: physical PDF page 9. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

1.4

Standards

The AC drives described in this instruction manual com-

ply with the standards listed in Table 1. For the declara-

tions of conformity and manufacturer’s certificate,

contact your

supplier for more information.

1.4.1Product standard for EMC

Product standard EN(IEC)61800-3, second edition of

2004 defines the:

First Environment (Extended EMC) as environment that

includes domestic premises. It also includes establish-

ments directly connected without intermediate trans-

formers to a low voltage power supply network that

supplies buildings used for domestic purposes.

Category C2: Power Drive System (PDS) of rated

voltage<1.000 V, which is neither a plug in device nor a

movable device and, when used in the first environ-

ment, is intended to be installed and commissioned

only by a

professional.

Second environment (Standard EMC) includes all other

establishments.

Category C3: PDS of rated voltage <1.000 V, intended

for use in the second environment and not intended for

use in the first environment.

Category C4: PDS or rated voltage equal or above

1.000 V, or rated current equal to or above 400 A, or

intended for use in complex systems in the second envi-

ronment.

The AC drive complies with the product standard

EN(IEC) 61800-3:2004 (Any kind of metal screened

cable may be used). The standard AC drive is designed

to meet the requirements according to category C3.

By using the optional “Extended EMC” filter the AC drive

fulfils requirements according to category C2,

WARNING!

In a domestic environment this product may

cause radio interference, in which case it

may be necessary to take adequate

additional measures.

The standard AC drive, complying with

category C3, is not intended to be used on a

low-voltage public network which supplies

domestic premises; radio interference is

expected if used in such a network. Contact

your supplier if you need additional

measures.

Type code positions11–18. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation.

Shared source cells (coordinates refer to this table):

Type code positions11–18 — PDF page 9

Source row Position for 0003- 0074 Position for 0090- 1500 Configuration ⟦blank source cell⟧
1 11 11 Coated boards, option - =Standard boards V=Coated boards
2 12 12 Option position 1 N=No option C=Crane I/O E=Encoder P=PTC/PT100 I=Extended I/O S=Safe Stop (only 003-074)
3 13 13 Option position 2 ⟦null: no independent source value⟧
4 14 14 Option position 3 ⟦null: no independent source value⟧
5 15 15 Option position, communication N=No option D=DeviceNet P=Profibus S=RS232/485 M=Modbus/TCP
6 16 16 Software type A=Standard
7 17 - Motor PTC. (Only valid for 003-074) N=No option P=PTC
8 18 - Gland kit. (Only valid for 003-074) –=Glands not included G=Gland kit included

Manual — Table1 source standards and disposal. Collected P034 association; no extrapolation to other variants. — page 10

Manual reference: physical PDF page 10. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

1.5

Dismantling and scrapping

The enclosures of the drives are made from recyclable

material as aluminium, iron and plastic. Each drive con-

tains a number of components demanding special

treatment, for example electrolytic capacitors. The cir-

cuit boards contain small amounts of tin and lead. Any

local or national

regulations in force for the disposal and recycling of

these materials must be complied with.

1.5.1Disposal of old electrical and

electronic equipment

This information is applicable in the European Union

and other European countries with separate collection

systems.

This symbol on the product or on its packaging indi-

cates that this product shall be taken to the applicable

collection point for the recycling of electrical and elec-

tronic

equipment. By ensuring this product is disposed of cor-

rectly, you will help prevent potentially negative conse-

quences for the environment and human health, which

could otherwise be caused by inappropriate waste han-

dling of this product. The recycling of materials will help

to conserve natural resources. For more detailed infor-

mation about recycling this product, please contact the

local distributor of the

product.

Table 1

Standards

Table1 Standards. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation.

Shared source cells (coordinates refer to this table):

Table1 Standards — PDF page 10

Source row Market Standard Description
1 European EMC Directive 2004/108/EEC
2 ⟦null: no independent source value⟧ Low Voltage Directive 2006/95/EC
3 ⟦null: no independent source value⟧ WEEE Directive 2002/96/EC
4 All EN 60204-1 Safety of machinery - Electrical equipment of machines Part 1: General requirements.
5 ⟦null: no independent source value⟧ EN(IEC)61800-3:2004 Adjustable speed electrical power drive systems Part 3: EMC requirements and specific test methods. EMC Directive: Declaration of Conformity and CE marking
6 ⟦null: no independent source value⟧ EN(IEC)61800-5-1 Ed. 2.0 Adjustable speed electrical power drive systems Part 5-1. Safety requirements - Electrical, thermal and energy. Low Voltage Directive: Declaration of Conformity and CE marking
7 ⟦null: no independent source value⟧ IEC 60721-3-3 Classification of environmental conditions. Air quality chemical vapours, unit in operation. Chemical gases 3C2, Solid particles 3S2. Optional with coated boards Unit in operation. Chemical gases Class 3C3, Solid particles 3S2.
8 ⟦null: no independent source value⟧ UL508C UL Safety standard for Power Conversion Equipment
9 USA ≥90 A only UL 840 UL Safety standard for Power Conversion Equipment power conversion equipment. Insulation coordination including clearances and creepage distances for electrical equipment.
10 Russian GOST R For all sizes

Manual — Glossary and definitions. Collected P034 association; no extrapolation to other variants. — page 11

Manual reference: physical PDF page 11. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

1.6

Glossary

1.6.1Abbreviations and symbols

In this manual the following abbreviations are used:

1.6.2Definitions

In this manual the following definitions for current,

torque and frequency are used:

Table 2

Abbreviations

Table 3

Definitions

Table3 Definitions. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation.

Table2 Abbreviations. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation.

Table3 Definitions — PDF page 11

Source row Name Description Quantity
1 I IN Nominal input current of AC drive A RMS
2 I NOM Nominal output current of AC drive A RMS
3 I MOT Nominal motor current A RMS
4 P NOM Nominal power of AC drive kW
5 P MOT Motor power kW
6 T NOM Nominal torque of motor Nm
7 T MOT Motor torque Nm
8 f OUT Output frequency of AC drive Hz
9 f MOT Nominal frequency of motor Hz
10 n MOT Nominal speed of motor rpm
11 I CL Maximum output current A RMS
12 Speed Actual motor speed rpm
13 Torque Actual motor torque Nm
14 Sync speed Synchronous speed of the motor rpm

Table2 Abbreviations — PDF page 11

Source row Abbreviation/ symbol Description
1 DSP Digital signals processor
2 AC drive Frequency converter
3 PEBB Power Electronic Building Block
4 IGBT Insulated Gate Bipolar Transistor
5 CP Control panel, the programming and presen- tation unit on the AC drive
6 EInt Communication format
7 UInt Communication format (Unsigned integer)
8 Int Communication format (Integer)
9 Long Communication format
10 [padlock symbol] The function cannot be changed in run mode

Manual — Mounting and lifting. Collected P034 association; no extrapolation to other variants. — page 12

Manual reference: physical PDF page 12. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Primary source finding: load-label final unit clipped at figure edge; native retained without full visual verification.

2.

Mounting

This chapter describes how to mount the AC drive.

Before mounting it is recommended that the installa-

tion is planned out first.

• Be sure that the AC drive suits the mounting loca-

tion.

• The mounting site must support the weight of the

AC drive.

• Will the AC drive continuously withstand vibrations

and/or shocks?

• Consider using a vibration damper.

• Check ambient conditions, ratings, required cooling

air flow, compatibility of the motor, etc.

• Know how the AC drive will be lifted and trans-

ported.

2.1

Lifting instructions

Recommended for AC drive models

-0090 to -0250

Fig. 2

Lifting AC drive model -0090 to -0250

-0300 to -1500

Fig. 3

Remove the roof unit and use the lifting eyes to lift

single unit 600mm and 900mm.

Single cabinet drives can be lifted/transported safely

using the eyebolts supplied and lifting cables/chains as

in illustration Fig. 3 above.

Depending on the cable/chain angle A (in Fig. 3),

following loads are permitted:

Regarding lifting instructions for other cabinet sizes,

please contact your supplier.

Note: To prevent personal risks and any damage to the

unit during lifting, it is advised that the lifting methods

described below are used.

Load: 56 to 74 kg

Lifting eyes

A°

Cable/chain angle A permitted load. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Single cabinet600mm/900mm with supplied eyebolts and cables/chains; othercabinet sizes contact supplier.

Cable/chain angle A permitted load — PDF page 12

Source row Cable/chain angle A Permitted load
1 45 ° 4 800 N
2 60 ° 6 400 N
3 90 ° 13 600N

Manual — Standalone mounting, cooling clearances, frameB. Collected P034 association; no extrapolation to other variants. — page 13

Manual reference: physical PDF page 13. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

2.2

Stand-alone units

The AC drive must be mounted in a vertical position

against a flat surface. Use the template (delivered

together with the AC drive) to mark out the position of

the fixing holes.

Fig. 4

AC drive mounting model 0003 to 1500

2.2.1 Cooling

Fig. 4 shows the minimum free space required around

the AC drive for the models 0003 to 1500 in order to

guarantee adequate cooling. Because the fans blow

the air from the bottom to the top it is advisable not to

position an air inlet immediately above an air outlet.

The following minimum separation between two AC

drives, or a AC drive and a non-dissipating wall must be

maintained. Valid if free space on opposite side.

2.2.2 Mounting schemes

Fig. 5

JNFX48/52: Model 0003 to 0018 (B)

Fig. 6

Cable interface for mains, motor and communica-

tion,JNFX48/52: Model 0003 to 0018 (B)

Fig. 7

JNFX48/52: Model 0003 to 0018 (B), with optional

gland plate

Table 4

Mounting and cooling

NOTE: When a 0300 to 1500 model is placed between

two walls, a minimum distance at each side of 200 mm

must be maintained.

128.5

Ø

13 (2x)

202.6

7 (4x)

Glands

M20

M32

Gland

M16

M25

Table4 Mounting and cooling. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Figure4 a=above,b=below,c=left,d=right. Opposite-side free space qualifies minimum separation. 0300–1500 between two walls requires200mm eachside.

Shared source cells (coordinates refer to this table):

Table4 Mounting and cooling — PDF page 13

Source row Mounting relationship (mm) Figure4 dimension 0003–0018 0026–0074 0090–0250 0300–1500 cabinet
1 F33-F33 (mm) a 200 200 200 100
2 ⟦null: no independent source value⟧ b 200 200 200 0
3 ⟦null: no independent source value⟧ c 0 0 0 0
4 ⟦null: no independent source value⟧ d 0 0 0 0
5 F33-wall, wall-one side (mm) a 100 100 100 100
6 ⟦null: no independent source value⟧ b 100 100 100 0
7 ⟦null: no independent source value⟧ c 0 0 0 0
8 ⟦null: no independent source value⟧ d 0 0 0 0

Manual — Mounting framesC andD. Collected P034 association; no extrapolation to other variants. — page 14

Manual reference: physical PDF page 14. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 8

JNFX48/52: Model 0026 to 0046 (C)

Fig. 9

Cable interface for mains, motor and communication,

Fig. 10 JNFX48/52: Model 0061 to 0074 (D)

Fig. 11 Cable interface for mains, motor and communication,

JNFX48/52: Model 0061 to 0074 (D).

292,1

128,5

24,8

Ø 7 (4x)

Ø 13 (2x)

Gland

M25 (026-031)

Glands

M20

M32 (026-031)

M32 (037-046)

M40 (037-046)

NOTE: Glands for size B, C and D are available as

option kit.

Ø 13 (2x)

Ø 7 (4x)

M50

M40

Manual — Mounting framesE,F,F69. Collected P034 association; no extrapolation to other variants. — page 15

Manual reference: physical PDF page 15. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 12 JNFX48: Model 0090 to 0175 (E) including cable

interface for mains, motor and communication

Fig. 13 JNFX48: Model 0210 to 0250 (F)

JNFX69: Model 0090 to 0175 (F69) including cable

Ø9(6x)

Ø16(3)

22.5

284.5

952.5

922.5

Cable glands M20

Cable flexible leadthrough

Ø17-42 /M50

Ø11-32 /M40

Ø9(x6)

344.5

A

B

C

Ø23-55 /M63

FrameF/F69 dimensions. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation.

FrameF/F69 dimensions — PDF page 15

Source row Frame JNFX model Dimension A (mm) Dimension B (mm) Dimension C (mm)
1 F 0210 - 0250 925 950 920
2 F69 0090 - 0175 1065 1090 1060

Manual — Cabinet cooling and service clearance. Collected P034 association; no extrapolation to other variants. — page 16

Manual reference: physical PDF page 16. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

2.3

Cabinet mounting

2.3.1 Cooling

If the variable speed drive is installed in a cabinet, the

rate of airflow supplied by the cooling fans must be tak-

en into consideration.

2.3.2 Recommended free space in

front of cabinet

All cabinet mounted AC drives are designed in modules,

so called PEBBs. These PEBBs can be folded out to be

replaced. To be able to remove a PEBB in the future, we

recommend 1.30 meter free space in front of the cabi-

net, see Fig. 14.

Fig. 14 Recommended free space in front of the cabinet

mounted AC drive

Table 5

Flow rates cooling fans

NOTE: For the models 0860 to 1500 the mentioned

amount of air flow should be divided equally over the two

cabinets.

RITTA L

NZM3

PN3

Table5 Flow rates cooling fans. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Flow m3/hour. Models0860–1500 flow divided equally between two cabinets. Merged flow cells retained.

Shared source cells (coordinates refer to this table):

Table5 Flow rates cooling fans — PDF page 16

Source row Frame JNFX Model Flow rate [m3/hour]
1 B 0003-0018 75
2 C 0026 – 0031 120
3 C 0037 - 0046 170
4 D 0061-0074 170
5 E 0090 - 0175 510
6 F 0210 - 0250 800
7 F69 0090 - 0175 ⟦null: no independent source value⟧
8 G 0300 - 0375 1020
9 H 0430 - 0500 1600
10 H69 0210 - 0375 ⟦null: no independent source value⟧
11 I 0600 - 0750 2400
12 I69 0430 - 0500 ⟦null: no independent source value⟧
13 J J69 0860 - 1000 0600 - 0650 3200
14 K 1200 - 1500 4800
15 K69 0750 - 1000 ⟦null: no independent source value⟧

Manual — Cabinet mounting G/H/H69,I/I69,J/J69,K/K69. Collected P034 association; no extrapolation to other variants. — page 17

Manual reference: physical PDF page 17. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

2.3.3 Mounting schemes

Fig. 15 JNFX48: Model 0300 to 0500 (G and H)

JNFX69: Model 0210 to 0375 (H69)

Fig. 16 JNFX48: Model 0600 to 0750 (I)

JNFX69: Model 0430 to 0500 (I69)

Fig. 17 JNFX48: Model 0860 to 1000 (J)

JNFX69: Model 0600 to 0650 (J69)

Fig. 18 JNFX48: Model 1200 to 1500 (K)

JNFX69: Model 0750 to 1000 (K69)

RITTAL

RITTA L

Manual — Installation and mains cable models0003–0074. Collected P034 association; no extrapolation to other variants. — page 18

Manual reference: physical PDF page 18. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.

Installation

The description of installation in this chapter complies

with the EMC standards and the Machine Directive.

Select cable type and screening according to the EMC

requirements valid for the environment where the AC

drive is installed.

3.1

Before installation

Read the following checklist and prepare for your

application before installation.

• Local or remote control.

• Long motor cables (>100m), refer to section Long

motor cables page 18.

• Motors in parallel, refer to menu [213] page 65.

• Functions used.

• Suitable AC drive size in proportion to the

motor/application.

If the AC drive is temporarily stored before being con-

nected, please check the technical data for environ-

mental conditions. If the AC drive is moved from a cold

storage room to the room where it is to be installed,

condensation can form on it. Allow the AC drive to

become fully acclimatised and wait until any visible

condensation has evaporated before connecting the

mains voltage.

3.2

Cable connections for

model 0003 to 0074

3.2.1 Mains cables

Dimension the mains and motor cables according to

local regulations. The cable must be able to carry the

AC drive load current.

Recommendations for selecting mains

cables

• To fulfil EMC purposes it is not necessary to use

screened mains cables.

• Use heat-resistant cables, +60°C or higher.

• Dimension the cables and fuses in accordance with

local regulations and the nominal current of the

motor. See table 49, page 191.

• The litz ground connection see fig. 23, is only neces-

sary if the mounting plate is painted. All the AC

drives have an unpainted back side and are there-

fore suitable for mounting on an unpainted mount-

ing plate.

Connect the mains cables according to fig. 19 or 20.

The AC drive has as standard a built-in RFI mains filter

that complies with category C3 which suits the Second

Environment standard.

Fig. 19 Mains and motor connections, model 0003-0018

Fig. 20 Mains and motor connections, 0026-0046

L1

L2

L3

DC-

DC+

R

U

V

W

Screen connection

of motor cables

PE

L1 L2 L3 DC-DC+ R

Manual — Motor cables and terminal connections. Collected P034 association; no extrapolation to other variants. — page 19

Manual reference: physical PDF page 19. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 21 Mains and motor connection, model 0061 - 0074

3.2.2 Motor cables

To comply with the EMC emission standards the AC

drive is provided with a RFI mains filter. The motor

cables must also be screened and connected on both

sides. In this way a so-called “Faraday cage” is created

around the AC drive, motor cables and motor. The RFI

currents are now fed back to their source (the IGBTs) so

the system stays within the emission levels.

Recommendations for selecting motor

cables

• Use screened cables according to specification in

table 7. Use symmetrical shielded cable; three

phase conductors and a concentric or otherwise

symmetrically constructed PE conductor, and a

shield.

• When the conductivity of the cable PE conductor is

<50% of the conductivity of the phase conductor, a

separate PE conductor is required.

• Use heat-resistant cables, +60°C or higher.

• Dimension the cables and fuses in accordance with

the nominal output current of the motor. See table

49, page 191.

• Keep the motor cable between AC drive and motor

as short as possible.

•

The screening must be connected with a large con-

tact surface of preferable 360° and always at both

ends, to the motor housing and the AC drive hous-

ing. When painted mounting plates are used, do not

be afraid to scrape away the paint to obtain as large

contact surface as possible at all mounting points

for items such as saddles and the bare cable

screening. Relying just on the connection made by

the screw thread is not sufficient.

• The litz ground connection, see fig. 23, is only nec-

essary if the mounting plate is painted. All the AC

drives have an unpainted back side and are there-

fore suitable for mounting on an unpainted mount-

ing plate.

Connect the motor cables according to U - U, V - V and

W - W, see Fig. 19, Fig. 20 and Fig. 21 .

Table 6

Mains and motor connections

NOTE: The Brake and DC-link Terminals are only fitted if

the DC+/DC- option or Brake Chopper Option is built-in.

WARNING!

The Brake Resistor must be connected

between terminals DC+ and R.

In order to work safely, the mains earth must

be connected to PE and the motor earth

to

.

DC- DC+ R

U

V

W

PE

L3

L2

L1

Screen connection

of motor cables

NOTE: It is important that the motor housing has the

same earth potential as the other parts of the machine.

NOTE: The terminals DC-, DC+ and R are options.

Motor earth is represented by an earth symbol in Table6 and in the warning; it is distinct from the PE mains earth label.

Table6 Mains and motor connections. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. First physicalrow contains L1,L2,L3→mains3phase and PE→safetyearth. Secondrow motor-earth symbol→motor earth and U,V,W→motor3phase. Motor-earth symbol is graphic, separately described. Brake/DC-link optional.

Table6 Mains and motor connections — PDF page 19

Source row Terminal/menu Description
1 L1,L2,L3 PE Mains supply, 3 -phase Safety earth (protected earth)
2 U, V, W Motor earth Motor output, 3-phase
3 DC-,DC+,R Brake resistor, DC-link connections (optional)

Manual — Cable screening and installation illustrations. Collected P034 association; no extrapolation to other variants. — page 20

Manual reference: physical PDF page 20. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Switches between the motor and the

AC drive

If the motor cables are to be interrupted by mainte-

nance switches, output coils, etc., it is necessary that

the screening is continued by using metal housing,

metal mounting plates, etc. as shown in the Fig. 23.

Fig. 22 Screen connection of cables.

Pay special attention to the following points:

• If paint must be removed, steps must be taken to

prevent subsequent corrosion. Repaint after making

connections!

• The fastening of the whole AC drive housing must be

electrically connected with the mounting plate over

an area which is as large as possible. For this pur-

pose the removal of paint is necessary. An alterna-

tive method is to connect the AC drive housing to

the mounting plate with as short a length of litz wire

as possible.

• Try to avoid interruptions in the screening wherever

possible.

• If the AC drive is mounted in a standard cabinet, the

internal wiring must comply with the EMC standard.

Fig. 23 shows an example of a AC drive built into a

cabinet.

Fig. 23 AC drive in a cabinet on a mounting plate

Fig. 24 shows an example when there is no metal

mounting plate used (e.g. if IP54 AC drives are used). It

is important to keep the “circuit” closed, by using metal

housing and cable glands.

Fig. 24 AC drive as stand alone

Screen connection

of signal cables

PE

Motor cable

shield connection

AC drive built into cabinet

RFI-Filter

(option)

Mains

Metal EMC cable glands

Output coil (option)

Screened cables

Unpainted mounting plate

Metal connector housing

Motor

Metal coupling

nut

Brake resistor

(L1,L2,L3,PE)

Litz

Metal EMC cable

glands

Metal housing

Brake

resistor

Output

coils

Metal cable gland

Manual — Motor cable installation and model0090up. Collected P034 association; no extrapolation to other variants. — page 21

Manual reference: physical PDF page 21. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Connect motor cables

  1. Remove the cable interface plate from the AC drive

housing.

  1. Put the cables through the glands.

  2. Strip the cable according to Table 8.

  3. Connect the stripped cables to the respective motor

terminal.

  1. Put the cable interface plate in place and secure

with the fixing screws.

  1. Tighten the EMC gland with good electrical contact

to the motor and brake chopper cable screens.

Placing of motor cables

Keep the motor cables as far away from other cables as

possible, especially from control signals. The minimum

distance between motor cables and control cables is

300 mm.

Avoid placing the motor cables in parallel with other

cables.

The power cables should cross other cables at an angle

of 90°.

Long motor cables

If the connection to the motor is longer than 100 m (40

m for models 0003-0018), it is possible that capacitive

current peaks will cause tripping at overcurrent. Using

output coils can prevent this. Contact the supplier for

appropriate coils.

Switching in motor cables

Switching in the motor connections is not advisable. In

the event that it cannot be avoided (e.g. emergency or

maintenance switches) only switch if the current is

zero. If this is not done, the AC drive can trip as a result

of current peaks.

3.3

Connection of motor and

mains cables for model

0090 and up

AC drive JNFX48-0090 and up, JNFX69-0090

and up

To simplify the connection of thick motor and mains

cables to the AC drive, the cable interface plate can be

removed.

Fig. 25 Connecting motor and mains cables

  1. Connect the stripped cables to the respective

mains/motor terminal.

  1. Fix the clamps on appropriate place and tighten the

cable in the clamp with good electrical contact to

the cable screen.

  1. Put the cable interface plate in place and secure

Cable interface

Clamps for screening

Mains cable

DC+, DC-, R (optional)

Motor cable

Manual — Model48-0300/69-0210up and IP20moduleG. Collected P034 association; no extrapolation to other variants. — page 22

Manual reference: physical PDF page 22. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AC drive model 0048-0300 & 0069-0210 and

up

Fig. 26 Connect motor cables and mains cables to the

terminals and earth/ground to the bus bar.

AC drive models 48-0300 & 0069-0210 and up are

supplied with power clamps for mains and motors, for

connection of PE and earth there is a bus bar.

For all type of wires to be connected the stripping

length should be 32 mm.

3.3.1 Connection of mains and

motor cables on IP20 modules

The IP 20 modules are delivered complete with factory

mounted cables for mains and motor. The length of the

cables are app. 1100 mm. The cables are marked L1,

L2, L3 for mains connection and U, V, W for motor con-

nection.

For detailed information about use of the IP20 mod-

ules, please contact your supplier.

Fig. 27 IP20 module size G, with qty 2 x 3 mains cables and

qty 2 x 3 motor cables.

Kabelabfangschiene Cable clamp rail

PEN-Schiene PEN-bus

sp eisung

Power supply

Q1

F1

T1

X3

3RV1021-4DA15

I

1 L 1

3 L 2

5 L 3

2 T1

4 T2

6 T3

2 0

2 5 A

2 3

-ÜÜÜÜÜ-

A2

A

A1

COIL

1 1

COM

NC

NO

1 2

1 4

K1

U

V

W

L1

L2

Motor connection

Mains Connection

L3

Ground / earth

connection

bus bar

PEBB 1

(Master)

PEBB 2

Mains cables

Motor cables

U, V, W

L1, L2, L3

Figure26 bottom labels: Kabelabfangschiene Cable clamp rail; PENSchiene PEN-bus. Internal terminal labels U,V,W;L1,L2,L2. External leader labels Motor connection U,V,W;Mains Connection L1,L2,L3;Ground/earth connection bus bar. Internal third mains terminal says L2 while its external leader says L3; no correction inferred.

Manual — IP20H/H69; cable specifications and stripping. Collected P034 association; no extrapolation to other variants. — page 23

Manual reference: physical PDF page 23. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 28 IP20 module size H/H69 with qty 3 x 3 Mains cables

and qty 3 x 3 motor cables.

3.4

Cable specifications

3.5

Stripping lengths

Fig. 29 indicates the recommended stripping lengths

for motor and mains cables.

Fig. 29 Stripping lengths for cables

PEBB 1

(Master)

PEBB 2

PEBB 3

Mains cables

Motor cables

L1, L2, L3

U, V, W

Table 7

Table 8

Stripping lengths for mains and motor cables

Mains cable

Motor cable

(06-F45-cables only)

Motor

Mains

Table7 Cable specifications. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation.

Table8 Stripping lengths for mains and motor cables. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation.

Table7 Cable specifications — PDF page 23

Source row Cable Cable specification
1 Mains Power cable suitable for fixed installation for the voltage used.
2 Motor Symmetrical three conductor cable with concentric protection (PE) wire or a four conductor cable with compact low-impedance concentric shield for the voltage used.
3 Control Control cable with low-impedance shield, screened.

Table8 Stripping lengths for mains and motor cables — PDF page 23

Source row Model Mains cable a (mm) Mains cable b (mm) Motor cable a (mm) Motor cable b (mm) Motor cable c (mm)
1 0003-0018 90 10 90 10 20
2 0026–0046 150 14 150 14 20
3 0061–0074 110 17 110 17 34
4 0090-0175 160 16 160 16 41
5 JNFX48- 0210–0250 JNFX69-0090- 0175 170 24 170 24 46

Manual — Terminal tightening torque; motor thermal protection and parallel motors. Collected P034 association; no extrapolation to other variants. — page 24

Manual reference: physical PDF page 24. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.5.1 Dimension of cables and fuses

Please refer to the chapter Technical data, section

14.7, page 191.

3.5.2 Tightening torque for mains

and motor cables

3.6

Thermal protection on the

motor

Standard motors are normally fitted with an internal

fan. The cooling capacity of this built-in fan is depend-

ent on the frequency of the motor. At low frequency, the

cooling capacity will be insufficient for nominal loads.

Please contact the motor supplier for the cooling char-

acteristics of the motor at lower frequency.

Motor thermistors offer better thermal protection for

the motor. Depending on the type of motor thermistor

fitted, the optional PTC input may be used. The motor

thermistor gives a thermal protection independent of

the speed of the motor, thus of the speed of the motor

fan. See the functions, Motor I2t type [231] and Motor

I2t current [232].

3.7

Motors in parallel

It is possible to have motors in parallel as long as the

total current does not exceed the nominal value of the

AC drive. The following has to be taken into account

when setting the motor data:

Table 9

Model JNFX48/52 0003 to 0046

Table 10

Model JNFX48/52 0061 to 0074

Table 11

Model JNFX48 0090 to 0109

Table 12

Model JNFX48 0146 to 0175

Table 13

Model JNFX48 0210 to 0250 and JNFX69 0090

to 0175

WARNING!

Depending on the cooling characteristics of

the motor, the application, the speed and the

load, it may be necessary to use forced

cooling on the motor.

Table9 JNFX48/52 0003–0046. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Printed Cable diameter unit mm2 retained literally; not corrected to mm. Thermal/parallel-motor conditions apply.

Table10 JNFX48/52 0061–0074. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Printed Cable diameter unit mm2 retained literally; not corrected to mm. Thermal/parallel-motor conditions apply.

Table11 JNFX48 0090–0109. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Printed Cable diameter unit mm2 retained literally; not corrected to mm. Thermal/parallel-motor conditions apply.

Table12 JNFX48 0146–0175. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Printed Cable diameter unit mm2 retained literally; not corrected to mm. Thermal/parallel-motor conditions apply.

Shared source cells (coordinates refer to this table):

Motors in parallel settings. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Printed Cable diameter unit mm2 retained literally; not corrected to mm. Thermal/parallel-motor conditions apply.

Table13 JNFX48 0210–0250 and JNFX69 0090–0175. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Printed Cable diameter unit mm2 retained literally; not corrected to mm. Thermal/parallel-motor conditions apply.

Table9 JNFX48/52 0003–0046 — PDF page 24

Source row ⟦blank source cell⟧ Brake chopper Mains/motor
1 Tightening torque, Nm 1.2-1.4 1.2-1.4

Table10 JNFX48/52 0061–0074 — PDF page 24

Source row ⟦blank source cell⟧ All cables 60 A All cables 73 A
1 Tightening torque, Nm 2.8 5.0

Table11 JNFX48 0090–0109 — PDF page 24

Source row ⟦blank source cell⟧ Brake chopper Mains/motor
1 Block, mm2 95 95
2 Cable diameter, mm2 16-95 16-95
3 Tightening torque, Nm 14 14

Table12 JNFX48 0146–0175 — PDF page 24

Source row Quantity Brake chopper Mains/motor Mains/motor
1 Block, mm2 95 150 ⟦null: no independent source value⟧
2 Cable diameter, mm2 16-95 35-95 120-150
3 Tightening torque, Nm 14 14 24

Motors in parallel settings — PDF page 24

Source row Terminal/menu Description
1 Menu [221] Motor Voltage: The motors in parallel must have the same motor voltage.
2 Menu [222] Motor Frequency: The motors in parallel must have the same motor frequency.
3 Menu [223] Motor Power: Add the motor power values for the motors in parallel.
4 Menu [224] Motor Current: Add the current for the motors in parallel.
5 Menu [225] Motor Speed: Set the average speed for the motors in parallel.
6 Menu [227] Motor Cos PHI: Set the average Cos PHI value for the motors in parallel.

Table13 JNFX48 0210–0250 and JNFX69 0090–0175 — PDF page 24

Source row Quantity Brake chopper Brake chopper Mains/motor Mains/motor
1 Block, mm2 150 ⟦null: no independent source value⟧ 240 ⟦null: no independent source value⟧
2 Cable diameter, mm2 35-95 120-150 35-70 95-240
3 Tightening torque, Nm 14 24 14 24

Manual — Installation — page 25

Manual reference: physical PDF page 25. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Visually footer-only; no engineering body content.

Manual — Control board layout. Collected P034 association; no extrapolation to other variants. — page 26

Manual reference: physical PDF page 26. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.

Control Connections

4.1

Control board

Fig. 30 shows the layout of the control board which is

where the parts most important to the user are located.

Although the control board is galvanically isolated from

the mains, for safety reasons do not make changes

while the mains supply is on!

Fig. 30 Control board layout

WARNING!

Always switch off the mains voltage and wait

at least 7 minutes to allow the DC capacitors

to discharge before connecting the control

signals or changing position of any switches. If the

option External supply is used, switch of the mains to

the option. This is done to prevent damage on the

control board.

X8

X2

X3

X1

S2

S1

S3

S4

X5

X4

X6

X7

U

I

AO1 AO2

DI4

DI5

DI6

DI7

DO1 DO2 DI8

+24V

DI3

DI2

DI1

-10V

AI4

AI3

AI2

AI1

+10V

NC

NO

C

R01

R02

R03

Relay outputs

Control

signals

Switches

Option

Panel

Communication

Figure30 X1 terminals1–11: +10V,AI1,AI2,AI3,AI4,-10V,ground,DI1,DI2,DI3,+24V. Upper12–22: ground,AO1,AO2,ground,DI4,DI5,DI6,DI7,DO1,DO2,DI8. R01 31NC32C33NO;R02 41NC42C43NO;R03 51NO52C. SwitchesS1–S4 depicted towardI;X4communicationC;X5/X6/X7option1/2/3;X8controlpanel.

Manual — Control terminals, defaults, analogue input switches. Collected P034 association; no extrapolation to other variants. — page 27

Manual reference: physical PDF page 27. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.2

Terminal connections

The terminal strip for connecting the control signals is

accessible after opening the front panel.

The table describes the default functions for the sig-

nals. The inputs and outputs are programmable for

other functions as described in chapter 11. page 63.

For signal specifications refer to chapter 14. page 183.

4.3

Inputs configuration

with the switches

The switches S1 to S4 are used to set the input configu-

ration for the 4 analogue inputs AnIn1, AnIn2, AnIn3

and AnIn4 as described in table 15. See Fig. 30 for the

location of the switches.

NOTE: The maximum total combined current for outputs

11, 20 and 21 is 100mA.

NOTE: It is possible to use external 24V if connection to

Common (15).

Table 14

Control signals

NOTE: N/C is opened when the relay is active and N/O is

closed when the relay is active.

Table 15

Switch settings

NOTE: Scaling and offset of AnIn1 - AnIn4 can be

configured using the software. See menus [512], [515],

[518] and [51B] in section 11.5, page 123.

NOTE: the 2 analogue outputs AnOut 1 and AnOut 2 can

be configured using the software. See menu [530]

section 11.5.3, page 132

Table15: AnIn1/S1,AnIn2/S2,AnIn3/S3,AnIn4/S4. For every switch, Voltage picture selects U (right);Current(default) picture selects I(left).

Table14 Relay outputs. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Defaults only, programmable; combinedoutputs11/20/21 maximum100mA; external24V referencesCommon15. Figure30 relay3 pins conflict retained in sourceflags.

Shared source cells (coordinates refer to this table):

Table14 Control signals. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Defaults only, programmable; combinedoutputs11/20/21 maximum100mA; external24V referencesCommon15. Figure30 relay3 pins conflict retained in sourceflags.

Table14 Control signals. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Defaults only, programmable; combinedoutputs11/20/21 maximum100mA; external24V referencesCommon15. Figure30 relay3 pins conflict retained in sourceflags. Row group: Outputs

Table14 Control signals. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Defaults only, programmable; combinedoutputs11/20/21 maximum100mA; external24V referencesCommon15. Figure30 relay3 pins conflict retained in sourceflags. Row group: Digital inputs

Table14 Control signals. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Defaults only, programmable; combinedoutputs11/20/21 maximum100mA; external24V referencesCommon15. Figure30 relay3 pins conflict retained in sourceflags. Row group: Digital outputs

Table14 Control signals. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Defaults only, programmable; combinedoutputs11/20/21 maximum100mA; external24V referencesCommon15. Figure30 relay3 pins conflict retained in sourceflags. Row group: Analogue inputs

Table14 Control signals. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Defaults only, programmable; combinedoutputs11/20/21 maximum100mA; external24V referencesCommon15. Figure30 relay3 pins conflict retained in sourceflags. Row group: Analogue outputs

Table14 Control signals. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Defaults only, programmable; combinedoutputs11/20/21 maximum100mA; external24V referencesCommon15. Figure30 relay3 pins conflict retained in sourceflags. Row group: Relay outputs

Table15 Switch settings. Source F33 manual software4.3X editionr3. Model and option restrictions apply; values as printed; no engineering or present certification validation. Defaults only, programmable; combinedoutputs11/20/21 maximum100mA; external24V referencesCommon15. Figure30 relay3 pins conflict retained in sourceflags.

Table14 Relay outputs — PDF page 27

Source row Terminal Name Function (Default)
1 31 N/C 1 Relay 1 output Trip, active when the AC drive is in a TRIP condition.
2 32 COM 1 ⟦null: no independent source value⟧
3 33 N/O 1 ⟦null: no independent source value⟧
4 41 N/C 2 Relay 2 output Run, active when the AC drive is started.
5 42 COM 2 ⟦null: no independent source value⟧
6 43 N/O 2 ⟦null: no independent source value⟧
7 51 COM 3 Relay 3 output Off
8 52 N/O 3 ⟦null: no independent source value⟧

Table14 Control signals — PDF page 27

Source row Terminal Name Function (Default)
1 Outputs ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 1 +10 V +10 VDC supply voltage
3 6 -10 V -10 VDC supply voltage
4 7 Common Signal ground
5 11 +24 V +24 VDC supply voltage
6 12 Common Signal ground
7 15 Common Signal ground
8 Digital inputs ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 8 DigIn 1 RunL (reverse)
10 9 DigIn 2 RunR (forward)
11 10 DigIn 3 Off
12 16 DigIn 4 Off
13 17 DigIn 5 Off
14 18 DigIn 6 Off
15 19 DigIn 7 Off
16 22 DigIn 8 RESET
17 Digital outputs ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 20 DigOut 1 Ready
19 21 DigOut 2 Brake
20 Analogue inputs ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 2 AnIn 1 Process Ref
22 3 AnIn 2 Off
23 4 AnIn 3 Off
24 5 AnIn 4 Off
25 Analogue outputs ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
26 13 AnOut 1 Min speed to max speed
27 14 AnOut 2 0 to max torque
28 Relay outputs ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Table15 Switch settings — PDF page 27

Source row Input Signal type Switch
1 AnIn1 Voltage S1 I U
2 ⟦null: no independent source value⟧ Current (default) S1 I U
3 AnIn2 Voltage S2 I U
4 ⟦null: no independent source value⟧ Current (default) S2 I U
5 AnIn3 Voltage S3 I U
6 ⟦null: no independent source value⟧ Current (default) S3 I U
7 AnIn4 Voltage S4 I U
8 ⟦null: no independent source value⟧ Current (default) S4 I U

Manual — Connection example. Collected P034 association; no extrapolation to other variants. — page 28

Manual reference: physical PDF page 28. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Small photographed control-panel key legends and LCD detail in Figure31 are blurred; surrounding connection labels and all tables/prose reviewed. No hidden-image key text inferred.

4.4

Connection example

Fig. 31 gives an overall view of a AC drive connection

example.

Fig. 31 Connection example

NG_06-F27

L1

L3

L2

PE

U

V

W

PREV

NEXT

ESC

ENTER

RESET

LOC/

REM

DC+

R

DC -

RFI-

filter

+10 VDC

AnIn 1: Reference

AnIn 2

AnIn 3

AnIn 4

-10 VDC

Common

DigIn 1:RunL*

DigIn 2:RunR*

DigIn3

+24 VDC

DigIn 4

DigIn 5

DigIn 6

DigIn 7

DigIn 8:Reset*

AnOut 1

AnOut 2

DigOut 1

DigOut 2

Motor

Fieldbus option

or PC

Option board

Other options

0 - 10 V

4 - 20 mA

Alternative for

potentiometer control**

Optional

Relay 1

Relay 2

Relay 3

** The switch S1 is set to U

Comm.options

Figure31 output associations:Common12,AnOut1 terminal13,AnOut2 terminal14,DigOut1 terminal20,DigOut2 terminal21. Relay1terminals31/32/33;Relay2 41/42/43;Relay3 51/52. Potentiometeralternative requiresS1setU;starredRunL/RunR/Reset are defaults.

Manual — Control cable installation by model. Collected P034 association; no extrapolation to other variants. — page 29

Manual reference: physical PDF page 29. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.5

Connecting the Control

Signals

4.5.1Cables

The standard control signal connections are suitable for

stranded flexible wire up to 1.5 mm2 and for solid wire

up to 2.5 mm2.

Fig. 32 Connecting the control signals, 0003 to 0018

Fig. 33 Connecting the control signals, 0026 to 0046

Fig. 34 Connecting the control signals, 0061 to 0074

Fig. 35 Connecting the control signals, 0090 to 0250

Control signals

DC-

DC+

R

U

V

PE

L3

L2

L1

Manual — Control cable screening and Table16 specifications. Collected P034 association; no extrapolation to other variants. — page 30

Manual reference: physical PDF page 30. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.5.2 Types of control signals

Always make a distinction between the different types

of signals. Because the different types of signals can

adversely affect each other, use a separate cable for

each type. This is often more practical because, for

example, the cable from a pressure sensor may be con-

nected directly to the AC drive.

We can distinguish between the following types of con-

trol signals:

Analogue inputs

Voltage or current signals, (0-10 V, 0/4-20 mA) nor-

mally used as control signals for speed, torque and PID

feedback signals.

Analogue outputs

Voltage or current signals, (0-10 V, 0/4-20 mA) which

change slowly or only occasionally in value. In general,

these are control or measurement signals.

Digital

Voltage or current signals (0-10 V, 0-24 V, 0/4-20 mA)

which can have only two values (high or low) and only o

ccasionally change in value.

Data

Usually voltage signals (0-5 V, 0-10 V) which change

rapidly and at a high frequency, generally data signals

such as RS232, RS485, Profibus, etc.

Relay

Relay contacts (0-250 VAC) can switch highly inductive

loads (auxiliary relay, lamp, valve, brake, etc.).

Example:

The relay output from a AC drive which controls an

auxiliary relay can, at the moment of switching, form a

source of interference (emission) for a measurement

signal from, for example, a pressure sensor. Therefore

it is advised to separate wiring and screening to reduce

disturbances.

4.5.3 Screening

For all signal cables the best results are obtained if the

screening is connected to both ends: the AC drive side

and the at the source (e.g. PLC, or computer). See Fig.

36.

It is strongly recommended that the signal cables be

allowed to cross mains and motor cables at a 90°

angle. Do not let the signal cable go in parallel with the

mains and motor cable.

4.5.4 Single-ended or double-ended

connection?

In principle, the same measures applied to motor

cables must be applied to all control signal cables, in

accordance with the EMC-Directives.

For all signal cables as mentioned in section 4.5.2 the

best results are obtained if the screening is connected

to both ends. See Fig. 36.

Fig. 36 Electro Magnetic (EM) screening of control signal

cables.

NOTE: The screening of control signal cables is

necessary to comply with the immunity levels given in

the EMC Directive (it reduces the noise level).

NOTE: Control cables must be separated from motor and

mains cables.

NOTE: Each installation must be examined carefully

before applying the proper EMC measurements.

Control board

Pressure

sensor

(example)

External control

(e.g. in metal housing)

Control consol

Table16 Control cable specifications. F33 manual software4.3X editionr3. Source claims and examples retained; no engineering, present certification or cross-product applicability inference. Shared wire-size and torque cells span all four signal types. Relay cable is explicitly Not screened. Signal voltage/current examples in adjacent prose remain source context.

Shared source cells (coordinates refer to this table):

Table16 Control cable specifications — PDF page 30

Source row Signal type Maximum wire size Tightening torque Cable type
1 Analogue Rigid cable: 0.14-2.5 mm2 Flexible cable: 0.14-1.5 mm2 Cable with ferrule: 0.25-1.5 mm2 0.5 Nm Screened
2 Digital ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Screened
3 Data ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Screened
4 Relay ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Not screened

Manual — Control signal types, twisting, option connections. Collected P034 association; no extrapolation to other variants. — page 31

Manual reference: physical PDF page 31. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.5.5 Current signals ((0)4-20 mA)

A current signal like (0)4-20 mA is less sensitive to

disturbances than a 0-10 V signal, because it is con-

nected to an input which has a lower impedance (250

Ω) than a voltage signal (20 kΩ). It is therefore strongly

advised to use current control signals if the cables are

longer than a few metres.

4.5.6 Twisted cables

Analogue and digital signals are less sensitive to inter-

ference if the cables carrying them are “twisted”. This is

certainly to be recommended if screening cannot be

used. By twisting the wires the exposed areas are mini-

mised. This means that in the current circuit for any

possible High Frequency (HF) interference fields, no

voltage can be induced. For a PLC it is therefore impor-

tant that the return wire remains in proximity to the sig-

nal wire. It is important that the pair of wires is fully

twisted over 360°.

4.6

Connecting options

The option cards are connected by the optional connec-

tors X4 or X5 on the control board see Fig. 30, page 23

and mounted above the control board. The inputs and

outputs of the option cards are connected in the same

way as other control signals.

Manual — Quick start mains/motor and function keys. Collected P034 association; no extrapolation to other variants. — page 32

Manual reference: physical PDF page 32. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.

Getting Started

This chapter is a step by step guide that will show you

the quickest way to get the motor shaft turning. We will

show you two examples, remote control and local con-

trol.

We assume that the AC drive is mounted on a wall or in

a cabinet as in the chapter 2. page 9.

First there is general information of how to connect

mains, motor and control cables. The next section

describes how to use the function keys on the control

panel. The subsequent examples covering remote con-

trol and local control describe how to program/set the

motor data and run the AC drive and motor.

5.1

Connect the mains and

motor cables

Dimension the mains and motor cables according to

local regulations. The cable must be able to carry the

AC drive load current.

5.1.1 Mains cables

  1. Connect the mains cables as in Fig. 37. The AC drive

has, as standard, a built-in RFI mains filter that com-

plies with category C3 which suits the Second Envi-

ronment standard.

5.1.2 Motor cables

  1. Connect the motor cables as in Fig. 37. To comply

with the EMC Directive you have to use screened

cables and the motor cable screen has to be con-

nected on both sides: to the housing of the motor

and the housing of the AC drive.

Fig. 37 Connection of mains and motor cables

5.2

Using the function keys

Fig. 38 Example of menu navigation when entering motor

voltage

AC drive

RFI-Filter

Mains

Metal EMC cable

glands

Screened cables

Metal housing

Brake

resistor

(option)

Output

coils

Metal connector housing

Motor

Metal cable gland

Table 16

Mains and motor connection

WARNING!

In order to work safely the mains earth must

be connected to PE and the motor earth to

.

step to lower menu level or confirm changed setting

step to higher menu level or ignore changed setting

step to next menu on the same level

step to previous menu on the same level

increase value or change selection

decrease value or change selection

PREV

ENTER

NEXT

ESC

ENTER: step to lower menu level or confirm changed setting; ESC: step to higher menu level or ignore changed setting; NEXT: next menu at same level; PREV: previous menu at same level; +: increase value or change selection; −: decrease value or change selection.

Second table row includes the motor-earth symbol before U,V,W; motor earth and motor3phase remain separate associations.

Mains and motor connections. F33 manual software4.3X editionr3. Source claims and examples retained; no engineering, present certification or cross-product applicability inference. First row L1,L2,L3→mains3phase and PE→safety earth. Second row graphic earth symbol→motor earth, U,V,W→motor3phase. Graphic symbol retained separately.

Mains and motor connections — PDF page 32

Source row Terminal Description
1 L1,L2,L3 PE Mains supply, 3 -phase Safety earth
2 U, V, W Motor earth Motor output, 3-phase

Manual — Remote-control startup example. Collected P034 association; no extrapolation to other variants. — page 33

Manual reference: physical PDF page 33. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.3

Remote control

In this example external signals are used to control the

AC drive/motor.

A standard 4-pole motor for 400 V, an external start

button and a reference value will also be used.

5.3.1 Connect control cables

Here you will make up the minimum wiring for starting.

In this example the motor/AC drive will run with right

rotation.

To comply with the EMC standard, use screened control

cables with plaited flexible wire up to 1.5 mm2 or solid

wire up to 2.5 mm2.

  1. Connect a reference value between terminals 7

(Common) and 2 (AnIn 1) as in Fig. 39.

  1. Connect an external start button between terminal

11 (+24 VDC) and 9 (DigIn2, RUNR) as in Fig. 39.

Fig. 39 Wiring

5.3.2 Switch on the mains

Close the door to the AC drive. Once the mains is

switched on, the internal fan in the AC drive will run for

5 seconds.

5.3.3 Set the Motor Data

Enter correct motor data for the connected motor. The

motor data is used in the calculation of complete oper-

ational data in the AC drive.

Change settings using the keys on the control panel.

For

further information about the control panel and menu

structure, see the chapter 9. page 53.

Menu [100], Preferred View is displayed when started.

  1. Press

to display menu [200], Main Setup.

  1. Press

and then

to display menu [220], Motor

Data.

  1. Press

to display menu [221] and set motor volt-

age.

  1. Change the value using the

and

keys. Con-

firm with

.

  1. Set motor frequency [222].

  2. Set motor power [223].

  3. Set motor current [224].

  4. Set motor speed [225].

  5. Set power factor (cos j) [227].

10.Select supply voltage level used [21B]

11.[229] Motor ID run: Choose Short, confirm with

and give start command

The AC drive will now measure some motor parame-

ters. The motor makes some beeping sounds but

the shaft does not rotate. When the ID run is fin-

ished after about one minute ("Test Run OK!" is dis-

played), press

to continue.

12.Use AnIn1 as input for the reference value. The

default range is 4-20 mA. If you need a 0-10 V refer-

ence value, change switch (S1) on control board

and set [512] Anln 1 Set-up to 0-10V.

13.Switch off power supply.

14.Connect digital and analogue inputs/outputs as in

Fig. 39.

15.Ready!

16.Switch on power supply.

5.3.4 Run the AC drive

Now the installation is finished, and you can press the

external start button to start the motor.

When the motor is running the main connections are

OK.

X2

X3

X1

Start

Reference

4-20 mA

+

0V

NEXT

ENTER

RESET

Source step1 NEXT; step2 ENTER then NEXT; step3 ENTER; step4 + and − then ENTER. Step11 Short motor-ID run confirmed ENTER, clockwise start icon; after TestRunOK press STOP/RESET. Source400V4-pole example and subsequent power-off/I/O/power-on sequence remain in native prose.

Manual — Local-control startup example. Collected P034 association; no extrapolation to other variants. — page 34

Manual reference: physical PDF page 34. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.4

Local control

Manual control via the control panel can be used to

carry out a test run.

Use a 400 V motor and the control panel.

5.4.1 Switch on the mains

Close the door to the AC drive. Once the mains is

switched on, the AC drive is started and the internal fan

will run for 5 seconds.

5.4.2 Select manual control

Menu [100], Preferred View is displayed when started.

  1. Press

to display menu [200], Main Setup.

  1. Press

to display menu [210], Operation.

  1. Press

to display menu [211], Language.

  1. Press

to display menu [214], Reference Control.

  1. Select Keyboard using the key

and press

to

confirm.

  1. Press

to get to menu [215], Run/Stop Control.

  1. Select Keyboard using the key

  2. Press

to get to previous menu level and then

to display menu [220], Motor Data.

5.4.3 Set the Motor Data

Enter correct motor data for the connected motor.

  1. Press

to display menu [221].

10.Change the value using the

and

keys. Con-

firm with

.

11.Press

to display menu [222].

12.Repeat step 9 and 10 until all motor data is entered.

13.Press

twice and then

to display menu [100],

Preferred View.

5.4.4 Enter a Reference Value

Enter a reference value.

14.Press

until menu [300], Process is displayed.

15.Press

to display menu [310], Set/View reference

value.

16.Use the

keys to enter, for example, 300

rpm. We select a low value to check the rotation

direction without damaging the application.

5.4.5 Run the AC drive

Press the

key on the control panel to run the motor

forward.

If the motor is running the main connections are OK.

NEXT

ENTER

ESC

PREV

Steps1 NEXT,2 ENTER,3 ENTER,4 NEXT,5 + then ENTER,6 NEXT,7 + then ENTER,8 ESC then NEXT. Steps9 ENTER,10 + and − then ENTER,11 NEXT,12 repeat9/10,13 ESC twice then PREV. Step14 NEXT until300,15 ENTER to310,16 + and − for example300rpm. Run key is clockwise rotation icon.

Manual — Getting Started — page 35

Manual reference: physical PDF page 35. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Visually footer-only; no engineering body content.

Manual — Pumps and fans application examples. Collected P034 association; no extrapolation to other variants. — page 36

Manual reference: physical PDF page 36. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.

Applications

This chapter contains tables giving an overview of many

different applications/duties in which it is suitable to

use the AC drives. Further on you will find application

examples of the most common applications and solu-

tions.

6.1

Application overview

6.1.1Pumps

6.1.2Fans

Pumps application examples. F33 manual software4.3X editionr3. Source claims and examples retained; no engineering, present certification or cross-product applicability inference.

Fans application examples. F33 manual software4.3X editionr3. Source claims and examples retained; no engineering, present certification or cross-product applicability inference.

Pumps application examples — PDF page 36

Source row Challenge TECO F33 solution Menu
1 Dry-running, cavitation and overheating damage the pump and cause downtime. Pump Curve Protection detects deviation. Sends warning or activates safety stop. 411–419, 41C1– 41C9
2 Sludge sticks to impeller when pump has been running at low speed or been stationary for a while. Reduces the pump’s efficiency. Automatic pump rinsing function: pump is set to run at full speed at certain intervals, then return to normal speed. 362–368, 560, 640
3 Motor runs at same speed despite varying demands in pressure/flow. Energy is lost and equipment stressed. PID continuously adapts pressure/flow to the level required. Sleep function activated when none is needed. 320, 380, 342, 354
4 Process inefficiency due to e.g. a blocked pipe, a valve not fully opened or a worn impeller. Pump Curve Protection detects deviation. Warning is sent or safety stop activated. 411–419, 41C1–41C9
5 Water hammer damages the pump when stopped. Mechanical stress on pipes, valves, gaskets, seals. Smooth linear stops protect the equipment. Eliminates need for costly motorized valves. 331–336

Fans application examples — PDF page 36

Source row Challenge TECO F33 solution Menu
1 Starting a fan rotating in the wrong direction can be critical, e.g. a tunnel fan in event of a fire. Fan is started at low speed to ensure correct direction and proper function. 219, 341
2 Draft causes turned off fan to rotate the wrong way. Starting causes high current peaks and mechanical stress. Motor is gradually slowed to complete stop before starting. Avoids blown fuses and breakdown. 219, 33A, 335
3 Regulating pressure/flow with dampers causes high energy consumption and equipment wear. Automatic regulation of pressure/flow with motor speed gives more exact control. 321, 354
4 Motor runs at same speed despite varying demands in pressure/flow. Energy is lost and equipment stressed. PID continuously adapts to the level required. Sleep function is activated when none is needed. 320, 380, 342, 354
5 Process inefficiency due to e.g. a blocked filter, a damper not fully opened or a worn belt. Load Curve Protection detects deviation. Warning is sent or safety stop activated. 411–419, 41C1–41C9

Manual — Compressors and blowers application examples. Collected P034 association; no extrapolation to other variants. — page 37

Manual reference: physical PDF page 37. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.1.3Compressors

6.1.4Blowers

Compressors application examples. F33 manual software4.3X editionr3. Source claims and examples retained; no engineering, present certification or cross-product applicability inference.

Blowers application examples. F33 manual software4.3X editionr3. Source claims and examples retained; no engineering, present certification or cross-product applicability inference.

Compressors application examples — PDF page 37

Source row Challenge TECO F33 solution Menu
1 Compressor is damaged when cooling media enters the compressor screw. Overload situation is quickly detected and safety stop can be activated to avoid breakdown. 411–41A
2 Pressure is higher than needed, causing leaks, stress on the equipment and excessive air use. Load Curve Protection function detects deviation. Warning is sent or safety stop activated. 411–419, 41C1–41C9
3 Motor runs at same speed when no air is compressed. Energy is lost and equipment stressed. PID continuously adapts to the level required. Sleep function activated when none is needed. 320, 380, 342, 354
4 Process inefficiency and energy wasted due to e.g. the compressor idling. Load Curve Protection quickly detects deviation. Warning is sent or safety stop activated. 411–419, 41C1–41C9

Blowers application examples — PDF page 37

Source row Challenge TECO F33 solution Menu
1 Difficult to compensate for pressure fluctuations. Wasted energy and risk of production stop. PID function continuously adapts pressure to the level required. 320, 380
2 Motor runs at same speed despite varying demands. Energy is lost and equipment stressed. PID continuously adapts air flow to level required. Sleep function activated when none is needed. 320, 380, 342, 354
3 Process inefficiency due to e.g. a broken damper, a valve not fully opened or a worn belt. Load Curve Protection quickly detects deviation. Warning is sent or safety stop activated. 411–419, 41C1–41C9

Manual — Parameter sets and digital selection. Collected P034 association; no extrapolation to other variants. — page 38

Manual reference: physical PDF page 38. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.

Main Features

This chapter contains descriptions of the main features

of the AC drive.

7.1

Parameter sets

Parameter sets are used if an application requires dif-

ferent settings for different modes. For example, a

machine can be used for producing different products

and thus requires two or more maximum speeds and

acceleration/deceleration times. With the four parame-

ter sets different control options can be configured with

respect to quickly changing the behaviour of the AC

drive. It is possible to adapt the AC drive online to

altered machine behaviour. This is based on the fact

that at any desired moment any one of the four param-

eter sets can be activated during Run or Stop, via the

digital inputs or the control panel and menu [241].

Each parameter set can be selected externally via a dig-

ital input. Parameter sets can be changed during opera-

tion and stored in the control panel.

Define parameter sets

When using parameter sets you first decide how to

select different parameter sets. The parameter sets

can be selected via the control panel, via digital inputs

or via serial communication. All digital inputs and vir-

tual inputs can be configured to select parameter set.

The function of the digital inputs is defined in the menu

[520].

Fig. 40 shows the way the parameter sets are activated

via any digital input configured to Set Ctrl 1 or Set Ctrl

2.

Fig. 40 Selecting the parameter sets

Select and copy parameter set

The parameter set selection is done in menu [241],

Select Set. First select the main set in menu [241], nor-

mally A. Adjust all settings for the application. Usually

most parameters are common and therefore it saves a

lot of work by copying set A>B in menu [242]. When

parameter set A is copied to set B you only change the

parameters in the set that need to be changed. Repeat

for C and D if used.

With menu [242], Copy Set, it is easy to copy the com-

plete contents of a single parameter set to another

parameter set. If, for example, the parameter sets are

selected via digital inputs, DigIn 3 is set to Set Ctrl 1 in

menu [523] and DigIn 4 is set to Set Ctrl 2 in menu

[524], they are activated as in Table 17.

Activate the parameter changes via digital input by set-

ting menu [241], Select Set to DigIn.

Examples

Different parameter sets can be used to easily change

the setup of a AC drive to adapt quickly to different

application requirements. For example when

• a process needs optimized settings in different

stages of the process, to

With these settings a large number of options are avail-

able. Some ideas are given here:

Multi frequency selection

Within a single parameter set the 7 preset references

can be selected via the digital inputs. In combination

with the parameter sets, 28 preset references can be

selected using all 4 digital inputs: DigIn1, 2 and 3 for

selecting preset reference within one parameter set

NOTE: The only data not included in the parameter set is

Motor data 1-4, (entered separately), language,

communication settings, selected set, local remote, and

keyboard locked.

{

(NG06-F03_1)

Run/Stop

-

Torques

Controllers

Limits/Prot.

-Max Alarm

Parameter Set A

Set B

Set C

Set D

Set Ctrl1

Set Ctrl2

+24 V

Table 17

Parameter set

NOTE: The selection via the digital inputs is immediately

activated. The new parameter settings will be activated

on-line, also during Run.

NOTE: The default parameter set is parameter set A.

Figure40 labels terminal11 +24V; terminal10 SetCtrl1; terminal16 SetCtrl2; stacked setsA,B,C,D. Source table separately gives A00,B10,C01,D11.

Table17 Parameter set selection. F33 manual software4.3X editionr3. Source claims and examples retained; no engineering, present certification or cross-product applicability inference. Digital selection requires SetCtrl1/SetCtrl2 functions; default A. Motor data, language and listed global selections are excluded from ordinary parameter sets.

Table17 Parameter set selection — PDF page 38

Source row Parameter set Set Ctrl 1 Set Ctrl 2
1 A 0 0
2 B 1 0
3 C 0 1
4 D 1 1

Manual — Parameter sets, motor selection, autoreset, reference priority. Collected P034 association; no extrapolation to other variants. — page 39

Manual reference: physical PDF page 39. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

and DigIn 4 and DigIn 5 for selecting the parameter

sets.

Bottling machine with 3 different products

Use 3 parameter sets for 3 different Jog reference

speeds when the machine needs to be set up. The 4th

parameter set can be used for “normal” remote control

when the machine is running at full production.

Manual - automatic control

If in an application something is filled up manually and

then the level is automatically controlled using PID reg-

ulation, this is solved using one parameter set for the

manual control and one for the automatic control.

7.1.1 One motor and one parameter

set

This is the most common application for pumps and

fans.

Once default motor M1 and parameter set A have been

selected:

  1. Enter the settings for motor data.

  2. Enter the settings for other parameters e.g. inputs

and outputs

7.1.2 One motor and two parameter

sets

This application is useful if you for example have a

machine running at two different speeds for different

products.

Once default motor M1 is selected:

  1. Select parameter set A in menu [241].

  2. Enter motor data in menu [220].

  3. Enter the settings for other parameters e.g. inputs

and outputs.

  1. If there are only minor differences between the set-

tings in the parameter sets, you can copy parameter

set A to parameter set B, menu [242].

  1. Enter the settings for parameters e.g. inputs and

outputs.

7.1.3 Two motors and two parameter

This is useful if you have a machine with two motors

that can not run at the same time, such as a cable

winding machine that lifts up the reel with one motor

and then turns the wheel with the other motor.

One motor must stop before changing to an other

motor.

  1. Select motor M1 in menu [212].

  2. Enter motor data and settings for other parameters

e.g. inputs and outputs.

  1. Select parameter set B in menu [241].

  2. Select M2 in menu [212].

  3. Enter motor data and settings for other parameters

7.1.4 Autoreset at trip

For several non-critical application-related failure

conditions, it is possible to automatically generate a

reset command to overcome the fault condition. The

selection can be made in menu [250]. In this menu the

maximum number of automatically generated restarts

allowed can be set, see menu [251], after this the AC

drive will stay in fault condition because external assist-

ance is required.

Example

The motor is protected by an internal protection for ther-

mal overload. When this protection is activated, the AC

drive should wait until the motor is cooled down enough

before resuming normal operation. When this problem

occurs three times in a short period of time, external

assistance is required.

The following settings should be applied:

• Insert maximum number of restarts; set menu [251]

to 3.

• Activate Motor I2t to be automatically reset; set

menu [25A] to 300 s.

• Set relay 1, menu [551] to AutoRst Trip; a signal will

be available when the maximum number of restarts

is reached and the AC drive stays in fault condition.

• The reset input must be constantly activated.

7.1.5 Reference priority

The active speed reference signal can be programmed

from several sources and functions. The table below

shows the priority of the different functions with

regards to the speed reference.

Note: Do not change motor data in parameter set B.

Table 18

Reference priority

Table18 Reference priority. F33 manual software4.3X editionr3. Source claims and examples retained; no engineering, present certification or cross-product applicability inference. Priority table: top source row has highest priority. On/Off means either state, not a blank.

Table18 Reference priority — PDF page 39

Source row Jog Mode Preset Reference Motor Pot Ref. Signal
1 On/Off On/Off On/Off Option cards
2 On On/Off On/Off Jog Ref
3 Off On On/Off Preset Ref
4 Off Off On Motor pot commands

Manual — Preset references and remote control. Collected P034 association; no extrapolation to other variants. — page 40

Manual reference: physical PDF page 40. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.1.6 Preset references

The AC drive is able to select fixed speeds via the con-

trol of digital inputs. This can be used for situations

where the required motor speed needs to be adapted

to fixed values, according to certain process conditions.

Up to 7 preset

references can be set for each parameter set, which

can be selected via all digital inputs that are set to Pre-

set Ctrl1,

Preset Ctrl2 or Preset Ctrl3. The amount digital inputs

used that are set to Preset Ctrl determines the number

of Preset References available; using 1 input gives 2

speeds, using 2 inputs gives 4 speeds and using 3

inputs gives 8 speeds.

Example

The use of four fixed speeds, at 50 / 100 / 300 / 800

rpm, requires the following settings:

• Set DigIn 5 as first selection input; set [525] to Pre-

set Ctrl1.

• Set DigIn 6 as second selection input; set [526] to

Preset Ctrl2.

• Set menu [341], Min Speed to 50 rpm.

• Set menu [362], Preset Ref 1 to 100 rpm.

• Set menu [363], Preset Ref 2 to 300 rpm.

• Set menu [364], Preset Ref 3 to 800 rpm.

With these settings, the AC drive switched on and a

RUN command given, the speed will be:

• 50 rpm, when both DigIn 5 and DigIn 6 are low.

• 100 rpm, when DigIn 5 is high and DigIn 6 is low.

• 300 rpm, when DigIn 5 is low and DigIn 6 is high.

• 800 rpm, when both DigIn 5 and DigIn 6 are high.

7.2

Remote control functions

Operation of the Run/Stop/Enable/Reset functions

As default, all the run/stop/reset related commands

are programmed for remote operation via the inputs on

the terminal strip (terminals 1-22) on the control board.

With the function Run/Stp Ctrl [215] and Reset Control

[216], this can be selected for keyboard or serial com-

munication control.

Default settings of the Run/Stop/

Enable/Reset functions

The default settings are shown in Fig. 41. In this exam-

ple the AC drive is started and stopped with DigIn 2 and

a reset after trip can be given with DigIn 8.

Fig. 41 Default setting Run/Reset commands

The inputs are default set for level-control. The rotation

is determined by the setting of the digital inputs.

NOTE: The examples in this paragraph do not cover all

possibilities. Only the most relevant combinations are

given. The starting point is always the default setting

(factory) of the AC drive.

X

X1

RunR

Reset

+24 V

Manual — Enable, stop and reset input behavior. Collected P034 association; no extrapolation to other variants. — page 41

Manual reference: physical PDF page 41. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Enable and Stop functions

Both functions can be used separately or simultane-

ously. The choice of which function is to be used

depends on the application and the control mode of the

inputs (Level/Edge [21A]).

Enable

Input must be active (HI) to allow any Run signal. If the

input is made LOW, the output of the AC drive is

immediately disabled and the motor will coast.

Stop

If the input is low then the AC drive will stop according

to the selected stop mode set in menu [33B] Stop

Mode. Fig. 42 shows the function of the Enable and the

Stop input and the Stop Mode=Decel [33B].

To run the input must be high.

Fig. 42 Functionality of the Stop and Enable input

Reset and Autoreset operation

If the AC drive is in Stop Mode due to a trip condition,

the AC drive can be remotely reset by a pulse (“low” to

“high” transition) on the Reset input, default on DigIn 8.

Depending on the selected control method, a restart

takes place as follows:

Level-control

If the Run inputs remain in their position the AC drive

will start immediately after the Reset command is

given.

Edge-control

After the Reset command is given a new Run command

must be applied to start the AC drive again.

Autoreset is enabled if the Reset input is continuously

active. The Autoreset functions are programmed in

menu Autoreset [250].

NOTE: In Edge mode, at least one digital input must be

programmed to “stop”, because the Run commands are

otherwise only able to start the AC drive.

CAUTION!

If the Enable function is not programmed to a

digital input, it is considered to be active

internally.

NOTE: Stop Mode=Coast [33B] will give the same

behaviour as the Enable input.

!

(06-F104_NG)

t

STOP

(STOP=DECEL)

OUTPUT

SPEED

ENABLE

(or if Spinstart is selected)

NOTE: If the control commands are programmed for

Keyboard control or Com, Autoreset is not possible.

Manual — Level/edge control and run examples. Collected P034 association; no extrapolation to other variants. — page 42

Manual reference: physical PDF page 42. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Run Inputs Level-controlled.

The inputs are set as default for level-control. This

means that an input is activated by making the input

continuously “High”. This method is commonly used if,

for example, PLCs are used to operate the AC drive.

The examples given in this and the following para-

graphs follow the input selection shown in Fig. 43.

Fig. 43 Example of wiring for Run/Stop/Enable/Reset inputs

The Enable input must be continuously active in order

to accept any run-right or run-left command. If both

RunR and RunL inputs are active, then the AC drive

stops according to the selected Stop Mode. Fig. 44

gives an example of a possible sequence.

Fig. 44 Input and output status for level-control

Run Inputs Edge-controlled

Menu [21A] Start signal Level/Edge must be set to

Edge to activate edge control. This means that an input

is activated by a “low” to “high” transition or vice versa.

See Fig. 43. The Enable and Stop input must be active

continuously in order to accept any run-right or run-left

command. The last edge (RunR or RunL) is valid. Fig.

45 gives an example of a possible sequence.

Fig. 45 Input and output status for edge-control

CAUTION!

Level-controlled inputs DO NOT comply with the

Machine Directive, if the inputs are directly

used to start and stop the machine.

!

X1

Stop

Reset

+24 V

RunL

RunR

Enable

(06-F103new_1)

INPUTS

OUTPUT

STATUS

ENABLE

STOP

RUN R

RUN L

Right rotation

Left rotation

Standstill

NOTE: Edge-controlled inputs comply with the Machine

Directive (see chapter EMC and Machine Directive), if

the inputs are directly used for starting and stopping the

machine.

(06-F94new_1)

Source wiring example: Stop to17; RunL to8; RunR to9; Enable to10; Reset to22; +24V to11. These are example figure associations, not a new wiring instruction.

Manual — Motor identification, parameter copying and load monitor. Collected P034 association; no extrapolation to other variants. — page 43

Manual reference: physical PDF page 43. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Figure46 embedded control-panel LCD and tiny key legends are not fully readable; no reconstruction from another page.

7.3

Performing an

Identification Run

To get the optimum performance out of your AC drive/

motor combination, the AC drive must measure the

electrical parameters (resistance of stator winding,

etc.) of the connected motor. See menu [229], Motor

ID-Run.

7.4

Using the Control Panel

Memory

Data can be copied from the AC drive to the memory in

the control panel and vice versa. To copy all data

(including parameter set A-D and motor data) from the

AC drive to the control panel, select Copy to CP[244],

Copy to CP.

To copy data from the control panel to the AC drive,

enter the menu [245], Load from CP and select what

you want to copy.

The memory in the control panel is useful in applica-

tions with VSDs without a control panel and in applica-

tions where several AC drives have the same setup. It

can also be used for temporary storage of settings. Use

a control panel to upload the settings from one AC drive

and then move the control panel to another AC drive

and download the settings.

Fig. 46 Copy and load parameters between AC drive and

control panel

7.5

Load Monitor and Process

Protection [400]

7.5.1

Load Monitor [410]

The monitor functions enable the AC drive to be used

as a load monitor. Load monitors are used to protect

machines and processes against mechanical overload

and underload, such as a conveyer belt or screw con-

veyer jamming, belt failure on a fan or a pump dry run-

ning. The load is measured in the AC drive by the

calculated motor shaft torque. There is an overload

alarm (Max Alarm and Max Pre-Alarm) and an under-

load alarm (Min Alarm and Min Pre-Alarm).

The Basic Monitor type uses fixed levels for overload

and underload (pre-)alarms over the whole speed

range. This function can be used in constant load appli-

cations where the torque is not dependent on the

speed, e.g. conveyor belt, displacement pump, screw

pump, etc.

For applications with a torque that is dependent on the

speed, the Load Curve monitor type is preferred. By

measuring the actual load curve of the process,

characteristically over the range of minimum speed to

maximum speed, an accurate protection at any speed

can be established.

The max and min alarm can be set for a trip condition.

The pre-alarms act as a warning condition. All the

alarms can be monitored on the digital or relay outputs.

The autoset function automatically sets the 4 alarm lev-

els whilst running: maximum alarm, maximum pre-

alarm, minimum alarm and minimum pre-alarm.

Fig. 7.6 gives an example of the monitor functions for

constant torque applications

NOTE: Load from and copy to the AC drive is only

possible when the AC drive is in stop mode.

AC drive

Manual — Load monitor graphical overview. Collected P034 association; no extrapolation to other variants. — page 44

Manual reference: physical PDF page 44. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

.

Ramp-down phase

Stationary phase

Ramp-up phase

[413] Ramp Alarm=On

[411] Alarm Select=Max or Max0Min

[413] Ramp Alarm=On or Off

Must be <t (or t´) otherwise no (pre)alarm

[4192] MinAlarmDel (0.1s)

[4172] MaxPreAlDel (0.1s)

[414] Start Delay (0.2s)

[4161] MaxAlarmMar (15%)

[4171] MaxPreAlMar (10%)

100%

Default: TNOM or

Autoset: TMOMENTARY

[4191] MinAlarmMar (15%)

[4181] MinPreAlMar (10%)

Must be elapsed before first (pre)alarm

Max Alarm

Max PreAlarm

Min Alarm

Min PreAlarm

[4162] MaxAlarmDel (0.1s)

[4182] MinPreAlDel (0.1s)

Torque [%]

t [s]

[41B]

Four phases left to right: ramp-up; stationary; stationary; ramp-down. 413RampAlarmOn in ramp phases and On or Off stationary;411AlarmSelect reads Max or Max0Min. Baseline41B100% is Default TNOM or Autoset TMOMENTARY. Margins4161MaxAlarmMar15%,4171MaxPreAlMar10%,4181MinPreAlMar10%,4191MinAlarmMar15%; plotted upper margins above and lower margins below baseline.414StartDelay0.2s must elapse before first(pre)alarm.4162MaxAlarmDel0.1s,4172MaxPreAlDel0.1s,4182MinPreAlDel0.1s,4192MinAlarmDel0.1s. Durations t and t′ govern whether alarms occur, without numerical duration inferred. Lower output-row names conflict with adjacent delay names, explicitly flagged.

Manual — Pump control system principles. Collected P034 association; no extrapolation to other variants. — page 45

Manual reference: physical PDF page 45. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.6

Pump function

7.6.1 Introduction

A maximum of 4 pumps can be controlled with the

standard F33 AC drive.

If I/O Board options are installed, a maximum of 7

pumps can be controlled. The I/O Board can also be

used as a general extended I/O.

The Pump Control function is used to control a number

of drives (pumps, fans, etc., with a maximum of 3 addi-

tional drives per I/O-board connected) of which one is

always driven by the F33. Other names for this kind of

controllers are 'Cascade controller' or 'Hydrophore con-

troller'.

Depending on the flow, pressure or temperature, addi-

tional pumps can be activated via the appropriate sig-

nals by the output relays of the F33 and/or the I/O

Board. The system is developed in such a way that one

F33 will be the master of the system.

Select relay on the control board or on an option board.

The relays are set to functions for controlling pumps. In

the pictures in this section, the relays are named

R:Function, e.g. R:SlavePump1, which means a relay on

the control board or on a option board set to function

SlavePump1.

Fig. 47 Flow control with pump control option

All additional pumps can be activated via an AC drive,

soft starter, Y/

or D.O.L. switches.

Fig. 48 Pressure control with pump control option

Pumps in parallel will operate as a flow controller, See

Fig. 47.

Pumps in series will operate as a pressure controller

see Fig. 48. The basic control principle is shown in Fig.

42.

Fig. 49 Basic Control principle

R:SlavePump3

R:SlavePump1

R:SlavePump2

R:SlavePump4

F33

MASTER

P1

P2

P3

P4

P5

P6

AnIn

Set FLOW

Feedback

FLOW

PM

PI D

R:SlavePump5

R:SlavePump6

Pr essur e

Flow

Power

(50-PC-1_1)

NOTE: Read this instruction manual carefully before

commencing installation, connecting or working with

the AC drive with Pump Control option.

Δ

Set

PRESSURE

(50-PC-2_1)

FLOW /

Add pump

FREQUENCY (master pump P)

Stop pump

P1=on

P2=on

P3=on

P4=on P5=on P6=on

P=on

TIM E

(50-PC-3_1)

Manual — Fixed and alternating master pump control. Collected P034 association; no extrapolation to other variants. — page 46

Manual reference: physical PDF page 46. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.6.2 Fixed MASTER

This is the default setting of the Pump Control. The F33

controls the Master pump which is always running. The

relay outputs start and stop the other pumps P1 to P6,

depending on flow/pressure. In this configuration a

maximum of 7 pumps can be controlled, see Fig. 43. To

equalize the lifetime of the additional pumps it is possi-

ble to select the pumps depending on the run time his-

tory of each pump.

Fig. 50 Fixed MASTER control

7.6.3 Alternating MASTER

With this function the Master pump is not fixed to the

F33 all the time. After the AC drive is powered up or

started again after a stop or sleep mode the Master

pump is selected via the relay set to function Master

Pump. section 7.6.7 on page 44 shows a detailed wir-

ing diagram with 3 pumps. The purpose of this function

is that all pumps are used equally, so the lifetime of all

pumps, including the Master pump, will be equalized.

Maximum 6 pumps can be controlled with this function.

Fig. 51 Alternating MASTER Control

7.6.4 Feedback 'Status' input

In this example the additional pumps are controlled by

an other kind of drive (e.g. soft starter, frequency

inverter, etc.). The digital inputs on the I/O Board can

be programmed as a "Error" input for each pump. If a

drive fails the digital input will monitor this and the

PUMP CONTROL option will not use that particular drive

anymore and automatically switch to another drive.

This means that the control continues without using

this (faulty) drive. This function can also be used to

manually stop a particular pump for maintenance pur-

poses, without shutting down the whole pump system.

Of course the maximum flow/pressure is then limited to

the maximum pump power of the remaining pumps.

NOTE: The pumps MAY have different powers, however

the MASTER pump MUST always be the largest.

P1

P2

P3

P4

P5

P6

PM

F33

MASTER

R:SlavePump6

R:SlavePump5

R:SlavePump4

R:SlavePump3

R:SlavePump2

R:SlavePump1

(NG_50-PC-4_1)

See menu:

[393] Select Drive

[39H] to [39N] Run Time 1 - 6, Pump

[554] to [55C] Relays

NOTE: The pumps MUST have all the same power.

R: SlavePump6

R: SlavePump5

R: SlavePump4

R: SlavePump3

R: SlavePump2

R: SlavePump1

(NG_50-PC-5_1)

R: MasterPump1

R: MasterPump2

R: MasterPump3

R: MasterPump4

R: MasterPump5

R: MasterPump6

[393] to [396]

[553] to [55C]

Manual — Drive feedback and fail-safe example. Collected P034 association; no extrapolation to other variants. — page 47

Manual reference: physical PDF page 47. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 52 Feedback "Status" input

7.6.5 Fail safe operation

Some pump systems must always have a minimum flow

or pressure level, even if the frequency inverter is

tripped or damaged. So at least 1 or 2 (or maybe all)

additional pumps must keep running after the inverter

is powered down or tripped. This kind of "safe" pump

operation can be obtained by using the NC contacts of

the pump control relays. These can be programmed for

each individual additional pump. In this example

pumps P5 and P6 will run at maximum power if the

inverter fails or is powered down.

Fig. 53 Example of "Fail safe" operation

P1

P2

P3

PM

F33

MASTER

R:SlavePump3

R:SlavePump2

R:SlavePump1

DI:Pump1Feedb

DI:Pump2Feedb

DI:Pump3Feedb

other

drive

feedback

inputs

(NG_50-PC-6_1)

See menu:

[529] to [52H] Digital Input

[554] to [55C] Relay

P4

P5

P6

R:SlavePump6

R:SlavePump5

R:SlavePump4

(50-PC-7_1)

[554] to [55C] Relays

[55D4] to [55DC] Mode

Manual — PID pump control and reference. Collected P034 association; no extrapolation to other variants. — page 48

Manual reference: physical PDF page 48. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.6.6 PID control

When using the Pump Control option it is mandatory to

activate the PID controller function. Analogue inputs

AnIn1 to AnIn4 can be set as functions for PID set val-

ues and/or feedback values.

Fig. 54 PID control

P1

P2

P3

P4

P5

P6

PM

F33

MASTER

R:SlavePump6

R:SlavePump5

R:SlavePump4

R:SlavePump3

R:SlavePump2

R:SlavePump1

AnIn

PID

(NG_50-PC-8_1)

See menu:

[381] to [385]

[553] to [55C]

[411] to [41C]

Set

Value

Feedback

Flow/Pressure

measurement

Manual — Alternating-master wiring and interlocks. Collected P034 association; no extrapolation to other variants. — page 49

Manual reference: physical PDF page 49. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.6.7 Wiring Alternating Master

Fig. 48 and Fig. 49 show the relay functions

MasterPump1-6 and SlavePump1-6. The Master and

Additional contactors also interlock with each other to

prevent dual powering of the pump and damage to the

inverter. (K1M/K1S, K2M/K2S, K3M/K3S). Before run-

ning, the F33 will select a pump to be Master, depend-

ing on the pump run times.

Fig. 55 Power connections for Alternating MASTER circuit

with 3 pumps

Fig. 56 Control connections for Alternating MASTER circuit

CAUTION!

The wiring for the Alternating Master control

needs special attention and should be wired

exactly as described here, to avoid

destructive short circuit at the output of the

inverter.

!

P1

3~

P2

P3

PE L1 L2 L3

U V W

F33

PE

L1

L2

L3

K1S

K1M

K2M

K2S

K3S

K3M

(NG_50-PC-10_1)

B2:R1

Slave

Pump1

B1:R1

Master

~

N

(NG_50-PC-11_3)

B1:R2

Pump2

B2:R2

B1:R3

Pump3

B2:R3

Six relay boxes: B1:R1 MasterPump1; B2:R1 SlavePump1; B1:R2 MasterPump2; B2:R2 SlavePump2; B1:R3 MasterPump3; B2:R3 SlavePump3. Corresponding lower coils K1M,K1S,K2M,K2S,K3M,K3S; opposite interlock contacts labelled K1S,K1M,K2S,K2M,K3S,K3M. Source rails marked AC symbol and N; original diagram governs topology.

Manual — Pump-control checklist sections1–7. Collected P034 association; no extrapolation to other variants. — page 50

Manual reference: physical PDF page 50. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.6.8 Checklist And Tips

  1. Main Functions

Start by choosing which of the two main functions to use:

In this case the “Master” pump can be alternated, although this function needs slightly more complicated wiring than the

“Fixed MASTER” function described below. The I/O Board option is necessary.

One pump is always the master, only the additional pumps alternate.

Notice that there is a big difference in the wiring of the system between these main functions, so it not possible to switch

between these 2 functions later on. For further information see section 7.6.2, page 41.

  1. Number of pumps/drives

If the system consists of 2 or 3 pumps the I/O Board option is not needed. However, this does mean that the following

functions are not then possible:

With the I/O Board option installed, the maximum number of pumps is:

The sizes of the pumps must be equal.

The pumps may have different power sizes, but the master pump (F33) must always have the greatest power.

  1. Programming the Digital inputs

If the digital inputs are used, the digital input function must be set to Drive feedback.

  1. Programming the Relay outputs

After the Pump controller is switched on in menu [391] the number of drives (pumps, fans, etc.) must be set in menu [392]

(Number of Drives). The relays themselves must be set to the function SlavePump1-6 and if Alternate master is used,

MasterPump1-6 as well.

  1. Equal Pumps

If all pumps are equal in power size it is likely that the Upper band is much smaller than the Lower band, because the

maximum pump discharge of the master pump is the same if the pump is connected to the mains (50Hz). This can give a

very narrow hysteresis causing an unstable control area in the flow/pressure. By setting the maximum frequency of the

inverter only slightly above 50Hz it means that the master pump has a slightly bigger pump discharge than the pump on

the mains. Of course caution is essential in order to prevent the master pump running at a higher frequency for a longer

period of time, which in turn prevents the master pump from overloading.

  1. Minimum Speed

With pumps and fans it is normal to use a minimum speed, because at lower speed the discharge of the pump or fan will

be low until 30-50% of the nominal speed (depending on size, power, pump properties, etc.). When using a minimum

speed, a much smoother and better control range of the whole system will be achieved.

Adjacent source context — repeated to preserve continuation:

Manual — Starting an additional pump. Collected P034 association; no extrapolation to other variants. — page 51

Manual reference: physical PDF page 51. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.6.9 Functional Examples of Start/

Stop Transitions

Starting an additional pump

This figure shows a possible sequence with all levels

and functions involved when a additional pump is

started by means of the pump control relays. The start-

ing of the second pump is controlled by one of the relay

outputs. The relay in this example starts the pump

directly on line. Of course other start/stop equipment

like a soft starter could be controlled by the relay out-

put.

Fig. 57 Time sequence starting an additional pump

Flow

Set view ref. [310]

Feedback Flow

time

Master pump

Max speed

Speed

Transition Speed Start

Min speed

Lower band

Upper band

Start delay [399]

Settle time start [39D]

Start ramp depends

on start method

Start command

2nd pump

[39E]

[343]

[341]

Adjacent source context — repeated to preserve continuation:

Manual — Stopping an additional pump. Collected P034 association; no extrapolation to other variants. — page 52

Manual reference: physical PDF page 52. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Stopping an additional pump

This figure shows a possible sequence with all levels

and functions involved when an additional pump is

stopped by means of the pump control relays. The stop-

ping of the second pump is controlled by one of the

relay outputs. The relay in this example stops the pump

directly on line. Of course other start/stop equipment

like a soft starter could be controlled by the relay out-

put.

Fig. 58 Time sequence stopping an additional pump

(NG_50-PC-20_1)

Set view ref. [310]

Feedback Flow

time

Master pump

Max speed

Speed

Transition Speed Stop

Min speed

Lower band

Upper band

Stop delay [39A]

Settle time stop [39F]

Stop ramp depends

on start method

Stop command

2nd pump

[39G]

[343]

[341]

Manual — Main Features — page 53

Manual reference: physical PDF page 53. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Visually footer-only; no engineering body content.

Manual — Historical EMC and machine standards source claims. Collected P034 association; no extrapolation to other variants. — page 54

Manual reference: physical PDF page 54. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.

EMC and Machine Directive

8.1

EMC standards

The AC drive complies with the following standards:

EN(IEC)61800-3:2004 Adjustable speed electronic

power drive systems, part 3, EMC product standards:

Standard: category C3, for systems of rated supply

voltage< 1000 VAC, intended for use in the second

environment.

Optional:

Category C2, for systems of rated supply

voltage <1.000 V, which is neither a plug in device nor

a movable device and, when used in the first environ-

ment, is intended to be installed and commissioned

only by experienced person with the necessary skills in

installing and/or commissioning AC drives including

their EMC aspects.

8.2

Stop categories and

emergency stop

The following information is important if emergency

stop circuits are used or needed in the installation

where a AC drive is used. EN 60204-1 defines 3 stop

categories:

Category 0: Uncontrolled STOP:

Stopping by switching off the supply voltage. A mechan-

ical stop must be activated. This STOP may not be

implemented with the help of a AC drive or its input/

output signals.

Category 1: Controlled STOP:

Stopping until the motor has come to rest, after which

the mains supply is switched off. This STOP may not be

Category 2: Controlled STOP:

Stopping while the supply voltage is still present. This

STOP can be implemented with each of the AC drives

STOP command.

WARNING!

EN 60204-1 specifies that every machine

must be provided with a category 0 stop. If

the application prevents this from being

implemented, this must be explicitly stated.

Furthermore, every machine must be provided with an

Emergency Stop function. This emergency stop must

ensure that the voltage at the machine contacts, which

could be dangerous, is removed as quickly as possible,

without resulting in any other danger. In such an

Emergency Stop situation, a category 0 or 1 stop may be

used. The choice will be decided on the basis of the

possible risks to the machine.

NOTE: With option Safe Stop, a “Safe Torque Off (STO)”

stop according EN-IEC 62061:2005 SIL 2 & EN-ISO

13849-1:2006, can be achieved.

See chapter 13.10 page 179

Manual — EMC and Machine Directive — page 55

Manual reference: physical PDF page 55. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Visually footer-only; no engineering body content.

Manual — Control panel display areas and status indicators. Collected P034 association; no extrapolation to other variants. — page 56

Manual reference: physical PDF page 56. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

9.

Operation via the Control Panel

This chapter describes how to use the control panel.

The AC drive can be delivered with a control panel or a

blank panel.

9.1

General

The control panel displays the status of the AC drive

and is used to set all the parameters. It is also possible

to control the motor directly from the control panel. The

control panel can be built-in or located externally via

serial communication. The AC drive can be ordered

without the control panel. Instead of the control panel

there will be a blank panel.

9.2

The control panel

Fig. 59 Control panel

9.2.1The display

The display is back lit and consists of 2 rows, each with

space for 16 characters. The display is divided into six

areas.

The different areas in the display are described below:

Fig. 60 The display

Area A:

Shows the actual menu number (3 or 4

digits).

Area B

Shows if the menu is in the toggle loop or

the AC drive is set for Local operation.

Area C:

Shows the heading of the active menu.

Area D:

Shows the status of the AC drive (3 digits).

The following status indications are possi-

ble:

Acc : Acceleration

Dec : Deceleration

I2t

: Active I2t protection

Run : Motor runs

Trp

: Tripped

Stp

: Motor is stopped

VL

: Operating at Voltage limit

SL

: Operating at Speed limit

CL

: Operating at Current limit

TL

: Operating at Torque limit

OT

: Operating at Temperature Limit

LV

: Operating at Low Voltage

Sby : Operating from Standby power supply

SST : Operating Safe Stop, is flashing when

activated

LCL : Operating with low cooling liquid level

Area E:

Shows active parameter set and if it is a

motor parameter.

Area F:

Shows the setting or selection in the active

menu.This area is empty at the 1st level and

2nd level menu. This area also shows warn-

ings and alarm messages. In some situa-

tions this area could

indicate +++ or - - - please see further

information in chapter 9.2.2 page 54

NOTE: The AC drive can run without the control panel

being connected. However the settings must be such

that all control signals are set for external use.

LC Display

LEDs

Control Keys

Toggle Key

Function Keys

Motor Volt

M1:

400V

T

A

C

D

F

B

E

Figure59 includes PREV,NEXT,ESC,−,+,ENTER function keys; STOP/RESET central control key, opposing rotation icons and LOC/REM toggle. Figure60 LCD example:221T Motor Volt / Stp A M1:400V; areasA menu,Btoggle/local,Cheading,Dstatus,Eparameter/motor set,Fvalue. LCD labels and400V are illustrative.

Manual — Display examples, range indications and LED states. Collected P034 association; no extrapolation to other variants. — page 57

Manual reference: physical PDF page 57. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 61 Example 1st level menu

Fig. 62 Example 2nd level menu

Fig. 63 Example 3d level menu

Fig. 64 Example 4th level menu

9.2.2 Indications on the display

The display can indicate +++ or - - - if a parameter is out

of range. In the AC drive there are parameters which

are dependent on other parameters. For example, if the

speed reference is 500 and the maximum speed value

is set to a value below 500, this will be indicated with

+++ on the display. If the minimum speed value is set

over 500, - - - is displayed.

9.2.3 LED indicators

The symbols on the control panel have the following

functions:

Fig. 65 LED indications

Table 19

LED indication

300 Process Appl

StpA

220 Motor Data

221 Motor Volt

Stp

M1:

400V

A

4161 Max Alarm

0.1s

Run

Green

Trip

Red

Power

NOTE: If the control panel is built in, the back light of the

display has the same function as the Power LED in Table

19 (Blank panel LEDs).

Table19 rows use ON,FLASHING,OFF in that order. Fig65 symbols: curved rotation arrow Run green; triangle Trip red; lightning Power green. Fig64 LCD reads4161MaxAlarm / StpA0.1s.

Table19 RUN continuation. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. ON/FLASHING/OFF column association continues from left lower table to right upper RUN row.

Table19 LED states. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. ON/FLASHING/OFF column association continues from left lower table to right upper RUN row.

Table19 RUN continuation — PDF page 57

Source row Symbol ON FLASHING OFF
1 RUN (green) Motor shaft rotates Motor speed increase/ decrease Motor stopped

Table19 LED states — PDF page 57

Source row Symbol ON FLASHING OFF
1 POWER (green) Power on ---------------- Power off
2 TRIP (red) AC drive tripped Warning/Limit No trip

Manual — Control keys and toggle operation. Collected P034 association; no extrapolation to other variants. — page 58

Manual reference: physical PDF page 58. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

9.2.4 Control keys

The control keys are used to give the Run, Stop or Reset

commands directly. As default these keys are disabled,

set for remote control. Activate the control keys by

selecting Keyboard in the menus Ref Control [214] and

Reset Ctrl [216].

If the Enable function is programmed on one of the dig-

ital inputs, this input must be active to allow Run/Stop

commands from the control panel.

9.2.5 The Toggle and Loc/Rem Key

This key has two functions: Toggle and

switching between Loc/Rem function.

Press one second to use the toggle func-

tion

Press and hold the toggle key for more than five sec-

onds to switch between Local and Remote function,

depending on the settings in [2171] and [2172].

When editing values, the toggle key can be used to

change the sign of the value, see section 9.5, page 57.

Toggle function

Using the toggle function makes it possible to easily

step through selected menus in a loop. The toggle loop

can contain a maximum of ten menus. As default the

toggle loop contains the menus needed for Quick

Setup. You can use the toggle loop to create a quick-

menu for the parameters that are most importance to

your specific application.

Add a menu to the toggle loop

  1. Go to the menu you want to add to the loop.

  2. Press the Toggle key and keep it pressed while

pressing the + key.

Delete a menu from the toggle loop

  1. Go to the menu you want to delete using the toggle

key.

pressing the - key.

Delete all menus from the toggle loop

  1. Press the Toggle key and keep it pressed while

pressing the Esc key.

  1. Confirm with Enter. The menu Preferred view [100]

is displayed.

Default toggle loop

Fig. 66 shows the default toggle loop. This loop con-

tains the necessary menus that need to be set before

starting. Press Toggle to enter menu [211] then use the

Next key to enter the sub menus [212] to [21A] and

enter the parameters. When you press the Toggle key

again, menu [221] is

displayed.

Fig. 66 Default toggle loop

Indication of menus in toggle loop

Menus included in the toggle loop are indicated with a

in area B in the display.

Table 20

Control keys

NOTE: It is not possible to simultaneously activate the

Run/Stop commands from the keyboard and remotely

from the terminal strip (terminals 1-22).

NOTE: Do not keep the Toggle key pressed for more than

five seconds without pressing either the +, - or Esc key,

as this may activate the Loc/Rem function of this key

instead. See menu [217].

LOC/

REM

NEXT

Toggle loop

Sub menus

T

Control-key graphic rows: counterclockwise RUNL; central STOP/RESETtriangle; clockwise RUNR. Defaulttoggleloop100→211→221→331→341→511→100, withNEXTsubmenus212,213… and222…228. Blank boxes represent unspecified menus, not missing values.

Table20 Control keys. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Table20 Control keys — PDF page 58

Source row Graphic/native key label Key Function
1 ⟦blank source cell⟧ RUN L: gives a start with left rotation
2 RESET STOP/RESET: stops the motor or resets the AC drive after a trip
3 ⟦blank source cell⟧ RUN R: gives a start with right rotation

Manual — Local/remote modes and function keys. Collected P034 association; no extrapolation to other variants. — page 59

Manual reference: physical PDF page 59. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Loc/Rem function

The Loc/Rem function of this key is disabled as default.

Enable the function in menu [2171] and/or [2172].

With the function Loc/Rem you can change between

local and remote control of the AC drive from the con-

trol panel. The function Loc/Rem can also be changed

via the DigIn, see menu Digital inputs [520]

Change control mode

  1. Press the Loc/Rem key for five seconds, until Local?

or Remote? is displayed.

  1. Confirm with Enter.

  2. Cancel with Esc.

Local mode

Local mode is used for temporary operation. When

switched to LOCAL operation, the AC drive is controlled

via the defined Local operation mode, i.e. [2171] and

[2172]. The actual status of the AC drive will not

change, e.g. Run/Stop conditions and the actual speed

will remain exactly the same. When the AC drive is set

to Local operation, the display will show

in area B in

the display.

The AC drive will be started and stopped using the keys

on the control panel. The reference signal can be con-

trolled using the + and - keys on the keyboard, when in

the menu [310] according to the selection in Keyboard

Reference menu [369].

Remote mode

When the AC drive is switched to REMOTE operation,

the AC drive will be controlled according to selected

control methods in the menu’s Reference Control

[214], Run/Stop Control [215] and Reset Control [216].

The actual operation status of the AC drive will reflect

the status and settings of the programmed control

selections, e.g. Start/Stop status and settings of the

programmed control selections, acceleration or decel-

eration speed according to the selected reference value

in the menu Acceleration Time [331] / Deceleration

Time [332].

To monitor the actual Local or Remote status of the AC

drive control, a “Loc/Rem” function is available on the

Digital Outputs or Relays. When the AC drive is set to

Local, the signal on the DigOut or Relay will be active

high, in Remote the signal will be inactive low. See

menu Digital Outputs [540] and Relays [550].

9.2.6 Function keys

The function keys operate the menus and are also used

for programming and read-outs of all the menu set-

tings.

Fig. 67 Menu structure

9.3

The menu structure

The menu structure consists of 4 levels:

This structure is consequently independent of the

number of menus per level.

For instance, a menu can have one selectable menu

(Set/View Reference Value [310]), or it can have 17

selectable menus (menu Speeds [340]).

L

Table 21

Function keys

NOTE: If there are more than 10 menus within one level,

the numbering continues in alphabetic order.

Table21 graphic keys in source order ENTER bentreturnarrow,ESC upwardarrow,PREV leftarrow,NEXT rightarrow,minus,plus. Menu levels correspond first/second/third/fourth character.

Table21 Function keys. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Menu hierarchy. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Table21 Function keys — PDF page 59

Source row Graphic/native key label Key Function
1 ENTER ENTER key: - step to a lower menu level - confirm a changed setting
2 ESC ESCAPE key: - step to a higher menu level - ignore a changed setting, without confirming
3 PREV PREVIOUS key: - step to a previous menu within the same level - go to more significant digit in edit mode
4 NEXT NEXT key: - step to a next menu within the same level - go to less significant digit in edit mode
5 ⟦blank source cell⟧ - key: - decrease a value - change a selection
6 ⟦blank source cell⟧ + key: - increase a value - change a selection

Menu hierarchy — PDF page 59

Source row Menu level Meaning
1 Main Menu 1st level The first character in the menu number.
2 2nd level The second character in the menu number.
3 3rd level The third character in the menu number.
4 4th level The fourth character in the menu number.

Manual — Menu structure and editing values. Collected P034 association; no extrapolation to other variants. — page 60

Manual reference: physical PDF page 60. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 68 Menu structure

9.3.1The main menu

This section gives you a short description of the func-

tions in the Main Menu.

Preferred View

Displayed at power-up. It displays the actual process

value as default. Programmable for many other read-

outs.

Main Setup

Main settings to get the AC drive operable. The motor

data settings are the most important. Also option utility

and settings.

Process and Application Parameters

Settings more relevant to the application such as Refer-

ence Speed, torque limitations, PID control settings,

etc.

Shaft Power Monitor and Process

Protection

The monitor function enables the AC drive to be used

as a load monitor to protect machines and processes

against mechanical overload and underload.

Inputs/Outputs and Virtual

Connections

All settings for inputs and outputs are entered here.

Logical Functions and Timers

All settings for conditional signals are entered here.

View Operation and Status

Viewing all the operational data like frequency, load,

power, current, etc.

View Trip Log

Viewing the last 10 trips in the trip memory.

Service Information and AC drive Data

Electronic type label for viewing the software version

and AC drive type.

9.4

Programming during

operation

Most of the parameters can be changed during opera-

tion without stopping the AC drive. Parameters that can

not be changed are marked with a lock symbol in the

display.

9.5

Editing values in a menu

Most values in the second row in a menu can be

changed in two different ways. Enumerated values like

the baud rate can only be changed with alternative 1.

Alternative 1

When you press the + or - keys to change a value, the

cursor is flashing to the left in the display and the value

is increased or decreased when you press the appropri-

ate key. If you keep the + or - keys pressed, the value

will increase or decrease continuously. When you keep

the key pressed the change speed will increase. The

Toggle key is used to change the sign of the entered

value. The sign of the value will also change when zero

is passed. Press Enter to confirm the value.

NG_06-F28

NOTE: If you try to change a function during operation

that only can be changed when the motor is stopped, the

message “Stop First” is displayed.

Baudrate

Stp

Acc Time

2.00s

A

Flashing

Figure68 mainmenus100through900;submenu410/420;under410units411–417;under416examples4161/4162. NEXT/PREV horizontallevel andENTER/ESC verticallevel arrows. No unseen menu numbers filled.

Manual — Editing/copying parameters and programming example. Collected P034 association; no extrapolation to other variants. — page 61

Manual reference: physical PDF page 61. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Alternative 2

Press the + or - key to enter edit mode. Then press the

Prev or Next key to move the cursor to the right most

position of the value that should be changed. The cur-

sor will make the selected character flashes. Move the

cursor using the Prev or Next keys. When you press the

increase or decrease. This alternative is suitable when

you want to make large changes, i.e. from 2 s to 400 s.

To change the sign of the value, press the toggle key.

This makes it possible to enter negative values.

Example: When you press Next the 4 will flash.

Press Enter to save the setting and Esc to leave the edit

mode.

9.6

Copy current parameter to

all sets

When a parameter is displayed, press the Enter key for

5 seconds. Now the text To all sets? is displayed. Press

Enter to copy the setting for current parameter to all

sets.

9.7

Programming example

This example shows how to program a change of the

Acc. Time set from 2.0 s to 4.0 s.

The flashing cursor indicates that a change has taken

place but is not saved yet. If at this moment, the power

fails, the change will not be saved.

Use the ESC, Prev, Next or the Toggle keys to proceed

and to go to other menus.

Fig. 69 Programming example

Acc Time

Stp

4.00s

A

Flashing

Menu 100 appears

after power-up.

Press Next for menu

[200].

[300].

Press Enter for menu

[310].

Press Next two times

for menu [330].

[331].

Keep

key pressed

until desired value has

been reached.

Save the changed

value by pressing

Enter.

0rpm

0.0A

NEXT

MAIN SETUP

StpA

Process

ENTER

310 Set/View Ref

Run/Stop

2.00s

Figure69 graphical keysequence NEXT100→200,NEXT→300,ENTER→310,NEXTtwice→330,ENTER→331,holdplus tochange2.00s,ENTERtosave4.00s. Exampleonly.

Manual — Serial communication interface and parameter sets. Collected P034 association; no extrapolation to other variants. — page 62

Manual reference: physical PDF page 62. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

10.

Serial communication

The AC drive provides possibility for different types of

serial communication.

• Modbus RTU via RS232/485

• Fieldbuses as Profibus DP and DeviceNet

• Industrial Ethernet as Modbus/TCP

10.1 Modbus RTU

The AC drive has an asynchronous serial communica-

tion interface behind the control panel. It is also possi-

ble to use the isolated RS232/485 option board (if

installed).

The protocol used for data exchange is based on the

Modbus RTU protocol, originally developed by Modicon.

The physical connection is RS232. The AC drive acts as

a slave with address 1 in a master-slave configuration.

The communication is half-duplex. It has a standard

non return zero (NRZ) format.

The baud rate is fixed to 9600 (Control panel RS232

port).

The character frame format (always 11 bits) has:

• one start bit

• eight data bits

• two stop bits

• no parity

It is possible to temporarily connect a personal compu-

ter with for example the software EmoSoftCom (pro-

gramming and monitoring software) to the RS232

connector on the control panel. This can be useful

when copying parameters between AC drives etc. For

permanent connection of a personal computer you

have to use one of the communication option boards.

Fig. 70 RS232 connector behind the control panel

10.2 Parameter sets

Communication information for the different parameter

sets.

The different parameter sets in the AC drive have the

following DeviceNet instance numbers and Profibus

slot/index numbers:

Parameter set A contains parameters 43001 to 43556.

The parameter sets B, C and D contains the same type

of information. For example parameter 43123 in

parameter set A contain the same type of information

as 44123 in parameter set B.

A DeviceNet instance number can easily be converted

into a Profibus slot/index number according to descrip-

tion in section section 11.8.2, page 165.

NOTE: This RS232 port is not isolated.

WARNING!

Correct and safe use of a RS232 connection

depends on the ground pins of both ports

being the same potential. Problems can

occur when connecting two ports of e.g. machinery and

computers where both ground pins are not the same

potential. This may cause hazardous ground loops that

can destroy the RS232 ports.

The control panel RS232 connection is not galvanically

isolated.

The RS232/485 option board is galvanically isolated.

Note that the control panel RS232 connection can

safely be used in combination with commercial available

isolated USB to RS232 converters.

Parameter-set communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Parameter-set communication — PDF page 62

Source row Parameter set Modbus/DeviceNet Instance number Profibus Slot/Index
1 A 43001–43556 168/160 to 170/205
2 B 44001–44529 172/140 to 174/185
3 C 45001–45529 176/120 to 178/165
4 D 46001–46529 180/100 to 182/145

Manual — Motor data and communication commands/reference/process value. Collected P034 association; no extrapolation to other variants. — page 63

Manual reference: physical PDF page 63. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

10.3 Motor data

Communication information for the different motors.

M1 contains parameters 43041 to 43048. The M2,

M3, and M4 contains the same type of information. For

example parameter 43043 in motor M1 contain the

same type of information as 44043 in M2.

A DeviceNet instance number can easily be converted

into a Profibus slot/index number according to descrip-

tion in section section 11.8.2, page 165.

10.4 Start and stop commands

Set start and stop commands via serial communica-

tion.

10.5 Reference signal

When menu Reference Control [214] is set to “Com”

the following parameter data should be used:

10.5.1 Process value

It is also possible to send the Process value feedback

signalover a bus (e.g. from a process or temperature

sensor) for use with PID Process controller [380].

Set menu Process Source [321] to F(Bus). Use following

parameter data for the process value:

Example:

(See the Fielbus manual for detalied information)

We would like to control the AC drive over a bus system

using the first two bytes of the Basic Control Message

by setting menu [2661] FB Signal 1 to 49972. Further,

we also want to transmit a 16 bit signed reference and

a 16 bit process value. This is done by setting menu

[2662] FB Signal 2 to 42905 and menu [2663] FB Sig-

nal 3 to 42906.

Note! Bipolar reference mode is activated if both RunR

and RunL is active.

Communication information

NOTE! It is possible to view the transmitted process

value in control panel menu Operation [710]. The

presented value is depending on settings in menus

Process Min [324] and Process Max [325].

Motor-set communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. M2 source Profibus range172/180 to174/187 retained literally, even though other motor ranges remain in one slot.

Reference42905 range. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Reference42905 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Start/stop commands. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Process42906 range. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Process42906 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Motor-set communication — PDF page 63

Source row Motor Modbus/DeviceNet Instance number Profibus Slot/Index
1 M1 43041–43048 168/200 to 168/207
2 M2 44041–44048 172/180 to 174/187
3 M3 45041–45048 176/160 to 176/167
4 M4 46041–46048 180/140 to 180/147

Reference42905 range — PDF page 63

Source row Property Value
1 Default 0
2 Range -32768 to 32767
3 Corresponding to -100% to 100% ref

Reference42905 communication — PDF page 63

Source row Property Value
1 Modbus /DeviceNet Instance number 42905
2 Profibus slot /Index 168/64
3 Fieldbus format Int
4 Modbus format Int

Start/stop commands — PDF page 63

Source row Modbus/DeviceNet Instance number Function
1 42901 Reset
2 42902 Run, active together with either RunR or RunL to perform start.
3 42903 RunR
4 42904 RunL

Process42906 communication — PDF page 63

Source row Property Value
1 Modbus /DeviceNet Instance number 42906
2 Profibus slot /Index 168/65
3 Fieldbus format Int
4 Modbus format Int

Manual — EInt encoding description and bit examples. Collected P034 association; no extrapolation to other variants. — page 64

Manual reference: physical PDF page 64. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

10.6 Description of the EInt

formats

A parameter with Eint format can be represented in two

different formats (F). Either as a 15 bit unsigned integer

format (F= 0) or a Floating point format (F=1). The most

significant bit (B15) indicates the format used. See

detailed description below.

All parameters written to a register may be rounded to

the number of significant digits used in the internal sys-

tem.

The matrix below describes the contents of the 16-bit

word for the two different EInt formats:

If the format bit (B15) is 0, then all bits may be treated

as a standard unsigned integer (UInt)

If the format bit is 1, then is the number interpreted as

this:

Value = M * 10^E, where M=m10..m0 represents a

two- complement signed mantissa and E= e3..e0 repre-

sents a two- complement signed exponent.

Example, resolution

If you write the value 1004 to a register and this regis-

ter has 3 significant digits, it will be stored as 1000.

In the Floating point format (F=1), one 16-bit word is

used to represent large (or very small numbers) with 3

significant digits.

If data is read or written as a fixed point (i.e. no deci-

mals) number between 0-32767, the 15 bit Unsigned

integer format (F=0) may be used.

Detailed description of Floating point format

A signed number should be represented as a two

omplement binary number, like below:

Value Binary

The value represented by the Floating point format is

m·10e.

To convert a value from the Floating point format to a

floating point value, use the formula above.

To convert a floating point value to the Floating point

format, see the C-code example below.

Example, Floating point format

The number 1.23 would be represented by this in Float-

ing point format,

The value is then 123x10-2 = 1.23

Example 15bit unsigned int format

The value 72.0 can be represented as the fixed point

number 72. It is within the range 0-32767, which

means that the 15-bit fixed point format may be used.

The value will then be represented as:

Where bit 15 indicates that we are using the fixed point

format (F=0).

NOTE: Parameters with EInt format may return values

both as 15 bit unsigned int (F=0) or in Floating point

(F=1).

e3-e0 4-bit signed exponent. Gives a value

range:

-8..+7 (binary 1000 .. 0111)

m10-m0 11-bit signed mantissa.Gives a value

-1024..+1023 (binary

10000000000..01111111111)

B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0

F=1 e3 e2 e1 e0 m10 m9 m8 m7 m6 m5 m4 m3 m2 m1 m0

F=0 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0

-8 1000

-7 1001

..

-2 1110

-1 1111

0 0000

1 0001

2 0010

6 0110

7 0111

F EEEE MMMMMMMMMMM

1 1110 00001111011

F=1 -> floating point format used

E=-2

M=123

0 0 0 0 0 0 0 0 0 1 0 0 1 0 0 0

EIntformatB15=F;F1 usesB14…B11=e3…e0 andB10…B0=m10…m0. F0usesB14…B0unsigned.1.23example F1,E1110=−2,M00001111011=123.72examplebinary0000000001001000. Source2-complement rangesexponent−8…7,mantissa−1024…1023.

Manual — Supplier programming example code. Collected P034 association; no extrapolation to other variants. — page 65

Manual reference: physical PDF page 65. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Programming example:

typedef struct

{

int m:11; // mantissa, -1024..1023

int e: 4; // exponent -8..7

unsigned int f: 1; // format, 1->special emoint format

}

eint16;

//---------------------------------------------------------------------------

unsigned short int float_to_eint16(float value)

eint16 etmp;

int dec=0;

while (floor(value) != value && dec<16)

dec++; value*=10;

if (value>=0 && value<=32767 && dec==0)

(short int )&etmp=(short int)value;

else if (value>=-1000 && value<0 && dec==0)

etmp.e=0;

etmp.f=1;

etmp.m=(short int)value;

else

etmp.m=0;

etmp.e=-dec;

if (value>=0)

etmp.m=1; // Set sign

etmp.m=-1; // Set sign

value=fabs(value);

while (value>1000)

etmp.e++; // increase exponent

value=value/10;

value+=0.5; // round

etmp.m=etmp.m*value; // make signed

return ((unsigned short int )&etmp);

float eint16_to_float(unsigned short int value)

float f;

eint16 evalue;

evalue=(eint16 )&value;

if (evalue.f)

if (evalue.e>=0)

f=(int)evalue.m*pow10(evalue.e);

f=(int)evalue.m/pow10(abs(evalue.e));

f=value;

return f;

Manual — Functional-description table conventions and display110. Collected P034 association; no extrapolation to other variants. — page 66

Manual reference: physical PDF page 66. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.

Functional Description

This chapter describes the menus and parameters in

the software. You will find a short description of each

function and information about default values, ranges,

etc. There are also tables containing communication

information. You will find the Modbus, DeviceNet and

Fieldbus address for each parameter as well as the

enumeration for the data.

Description of table layout

Resolution of settings

The resolution for all range settings described in this

chapter is 3 significant digits. Exceptions are speed val-

ues which are presented with 4 significant digits. Table

22 shows the resolutions for 3 significant digits.

11.1 Preferred View [100]

This menu is displayed at every power-up. During

operation, the menu [100] will automatically be dis-

played when the keyboard is not operated for 5 min-

utes. The automatic return function will be switched off

when the Toggle and Stop key is pressed simultane-

ously. As default it displays the actual current.

Menu [100], Preferred View displays the settings made

in menu [110], 1st line, and [120], 2nd line. See Fig.

71.

Fig. 71 Display functions

11.1.1 1st Line [110]

Sets the content of the upper row in the menu

[100] Preferred View.”

*

The “Motor temp” is only visible if you have the

option PTC/PT100 card installed and a PT100

input is selected in menu[ 236].

NOTE: Functions marked with the sign

cannot be

changed during Run Mode.

Table 22

0rpm

Stp

0.0A

A

(1st Line)

(2nd Line)

Padlocksymbol identifiesfunctionsnotchangeableRun. Display110MotorTempoptionconditional. TablelayoutLCDmenuandstatusareschemaexample,notrealparameterrow.

Parameter-table schema. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Shared source cells (coordinates refer to this table):

110 First line selections. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Table22 resolution. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Parameter-table schema — PDF page 66

Source row Selection/property Enumeration or merged span Description/value
1 Menu no. Menu name Status Selected value ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 Default: ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 Selection or range Integer value of selection Description

110 First line selections — PDF page 66

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Process Val
2 Dependent on menu ⟦null: no independent source value⟧ ⟦blank source cell⟧
3 Process Val 0 Process value
4 Speed 1 Speed
5 Torque 2 Torque
6 Process Ref 3 Process reference
7 Shaft Power 4 Shaft power
8 El Power 5 Electrical power
9 Current 6 Current
10 Output volt 7 Output voltage
11 Frequency 8 Frequency
12 DC Voltage 9 DC voltage
13 Heatsink Tmp 10 Heatsink temperature
14 Motor Temp * 11 Motor temperature
15 AC drive Sta- tus 12 AC drive status
16 Run Time 13 Run Time
17 Energy 14 Energy
18 Mains Time 15 Mains time

Table22 resolution — PDF page 66

Source row 3 Digit Resolution
1 0.01-9.99 0.01
2 10.0-99.9 0.1
3 100-999 1
4 1000-9990 10
5 10000-99900 100

Manual — Communication110, display120 and language211. Collected P034 association; no extrapolation to other variants. — page 67

Manual reference: physical PDF page 67. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Communication information

11.1.2 2nd Line [120]

Sets the content of the lower row in the menu

[100] Preferred View. Same selection as in menu [110].

11.2 Main Setup [200]

The Main Setup menu contains the most important set-

tings to get the AC drive operational and set up for the

application. It includes different sub menus concerning

the control of the unit, motor data and protection, utili-

ties and automatic resetting of faults. This menu will

instantaneously be adapted to build in options and

show the required settings.

11.2.1 Operation [210]

Selections concerning the used motor, AC drive mode,

control signals and serial communication are described

in this submenu and is used to set the AC drive up for

the application.

Language [211]

Select the language used on the LC Display. Once the

language is set, this selection will not be affected by the

Load Default command.

110 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

120 Second line default. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

211 Language. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Shared source cells (coordinates refer to this table):

211 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

110 communication — PDF page 67

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43001
2 Profibus slot/index 168/160
3 Fieldbus format UInt
4 Modbus format UInt

120 Second line default — PDF page 67

Source row Property Value
1 Default: Current

211 Language — PDF page 67

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ English
2 English 0 English selected
3 Svenska 1 Swedish selected
4 Nederlands 2 Dutch selected
5 Deutsch 3 German selected
6 Français 4 French selected
7 Español 5 Spanish selected
8 Руccкий 6 Russian selected
9 Italiano 7 Italian selected
10 Česky 8 Czech selected
11 Turkish 9 Turkish selected

211 communication — PDF page 67

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43011
2 Profibus slot/index 168/170
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Motor212,drive mode213,reference214. Collected P034 association; no extrapolation to other variants. — page 68

Manual reference: physical PDF page 68. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Select Motor [212]

This menu is used if you have more than one motor in

your application. Select the motor to define. It is possi-

ble to define up to four different motors, M1 to M4, in

the AC drive.

Communication information

Drive Mode [213]

This menu is used to set the control mode for the

motor. Settings for the reference signals and read-outs

is made in menu Process source, [321].

• V/Hz Mode (output speed [712] in rpm) .

Reference control [214]

To control the speed of the motor, the AC drive needs a

reference signal. This reference signal can be con-

trolled by a remote source from the installation, the key-

board of the AC drive, or by serial or fieldbus

communication. Select the required reference control

for the application in this menu.

NOTE: If the reference is switched from Remote to

Keyboard, the last remote reference value will be the

default value for the control panel.

212 SelectMotor. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Shared source cells (coordinates refer to this table):

214 ReferenceControl. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

212 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

213 DriveMode. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

214 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

213 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

212 SelectMotor — PDF page 68

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ M1
2 M1 0 Motor Data is connected to selected motor.
3 M2 1 ⟦null: no independent source value⟧
4 M3 2 ⟦null: no independent source value⟧
5 M4 3 ⟦null: no independent source value⟧

214 ReferenceControl — PDF page 68

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Remote
2 Remote 0 The reference signal comes from the analogue inputs of the terminal strip (terminals 1-22).
3 Keyboard 1 Reference is set with the + and - keys on the Control Panel. Can only be done in menu Set/View reference [310].
4 Com 2 The reference is set via the serial communication (RS 485, Fieldbus.) See section section 10.5 for further information.
5 Option 3 The reference is set via an option. Only available if the option can control the reference value.

212 communication — PDF page 68

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43012
2 Profibus slot/index 168/171
3 Fieldbus format UInt
4 Modbus format UInt

213 DriveMode — PDF page 68

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ V/Hz
2 V/Hz 2 All control loops are related to frequency control. In this mode multi-motor applica- tions are possible. NOTE: All the functions and menu read-outs with regard to speed and rpm (e.g. Max Speed = 1500 rpm, Min Speed=0 rpm, etc.) remain speed and rpm, although they represent the output frequency.

214 communication — PDF page 68

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43014
2 Profibus slot/index 168/173
3 Fieldbus format UInt
4 Modbus format UInt

213 communication — PDF page 68

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43013
2 Profibus slot/index 168/172
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Run/stop215 and reset216. Collected P034 association; no extrapolation to other variants. — page 69

Manual reference: physical PDF page 69. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Run/Stop Control [215]

This function is used to select the source for run and

stop commands. Start/stop via analogue signals can

be achieved by combining a few functions. This is

described in the Chapter 7.2 page 37.

Communication information

Reset Control [216]

When the AC drive is stopped due to a failure, a reset

command is required to make it possible to restart the

AC drive. Use this function to select the source of the

reset signal.

215 RunStopControl. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Shared source cells (coordinates refer to this table):

216 ResetControl. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

215 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

216 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

215 RunStopControl — PDF page 69

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Remote
2 Remote 0 The start/stop signal comes from the digital inputs of the terminal strip (terminals 1-22). For settings, see menu group [330] and [520].
3 Keyboard 1 Start and stop is set on the Control Panel.
4 Com 2 The start/stop is set via the serial communication (RS 485, Fieldbus.) See Fieldbus or RS232/485 option manual for details.
5 Option 3 The start/stop is set via an option.

216 ResetControl — PDF page 69

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Remote
2 Remote 0 The command comes from the inputs of the terminal strip (terminals 1-22).
3 Keyboard 1 The command comes from the command keys of the Control Panel.
4 Com 2 The command comes from the serial communication (RS 485, Fieldbus).
5 Remote + Keyb 3 The command comes from the inputs of the terminal strip (terminals 1-22) or the keyboard.
6 Com + Keyb 4 The command comes from the serial communication (RS485, Fieldbus) or the keyboard.
7 Rem+Keyb +Com 5 The command comes from the inputs of the terminal strip (terminals 1-22), the keyboard or the serial communication (RS485, Fieldbus).
8 Option 6 The command comes from an option. Only available if the option can control the reset command.

215 communication — PDF page 69

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43015
2 Profibus slot/index 168/174
3 Fieldbus format UInt
4 Modbus format UInt

216 communication — PDF page 69

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43016
2 Profibus slot/index 168/175
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Local control2171/2172,lock218 and rotation219. Collected P034 association; no extrapolation to other variants. — page 70

Manual reference: physical PDF page 70. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Local/Remote key function [217]

The Toggle key on the keyboard, see section 9.2.5,

page 54, has two functions and is activated in this

menu. As default the key is just set to operate as a Tog-

gle key that moves you easily through the menus in the

toggle loop. The second function of the key allows you

to easily swap between Local and normal operation (set

up via [214] and [215]) of the AC drive. Local mode can

also be activated via a digital input. If both [2171] and

[2172] is set to Standard, the function is disabled.

Communication information

Lock Code [218]

To prevent the keyboard being used or to change the

setup of the AC drive and/or process control, the key-

board can be locked with a password. This menu, Lock

Code [218], is used to lock and unlock the keyboard.

Enter the password “291” to lock/unlock the keyboard

operation. If the keyboard is not locked (default) the

selection “Lock Code?” will appear. If the keyboard is

already locked, the selection “Unlock Code?” will

appear.

When the keyboard is locked, parameters can be

viewed but not changed. The reference value can be

changed and the AC drive can be started, stopped and

reversed if these functions are set to be controlled from

the keyboard.

Rotation [219]

Overall limitation of motor rotation direction

This function limits the overall rotation, either to left or

right or both directions. This limit is prior to all other

selections, e.g.: if the rotation is limited to right, a Run-

Left command will be ignored. To define left and right

rotation we assume that the motor is connected U-U, V-

V and W-W.

Speed Direction and Rotation

The speed direction can be controlled by:

• RunR/RunL commands on the control panel.

• RunR/RunL commands on the terminal strip

(terminals 1-22).

• Via the serial interface options.

•

The parameter sets.

Fig. 72 Rotation

Right

Left

2171 LocalReference. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Shared source cells (coordinates refer to this table):

218 LockCode. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

2171 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

2172 LocalRun. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

2172 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

2171 LocalReference — PDF page 70

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Standard
2 Standard 0 Local reference control set via [214]
3 Remote 1 Local reference control via remote
4 Keyboard 2 Local reference control via keyboard
5 Com 3 Local reference control via communication

218 LockCode — PDF page 70

Source row Property Value
1 Default: 0
2 Range: 0–9999

2171 communication — PDF page 70

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43009
2 Profibus slot/index 168/168
3 Fieldbus format UInt
4 Modbus format UInt

2172 LocalRun — PDF page 70

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Standard
2 Standard 0 Local Run/Stop control set via [215]
3 Remote 1 Local Run/Stop control via remote
4 Keyboard 2 Local Run/Stop control via keyboard
5 Com 3 Local Run/Stop control via communication

2172 communication — PDF page 70

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43010
2 Profibus slot/index 168/169
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Rotation219,remote edge21A,supply21B. Collected P034 association; no extrapolation to other variants. — page 71

Manual reference: physical PDF page 71. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

In this menu you set the general rotation for the motor.

Communication information

11.2.2 Remote Signal Level/Edge

[21A]

In this menu you select the way to control the inputs for

RunR, RunL and Reset that are operated via the digital

inputs on the terminal strip. The inputs are default set

for level-control, and will be active as long as the input

is made and kept high. When edge-control is selected,

the input will be activated by the low to high transition

of the input. See Chapter 7.2 page 37 for more informa-

tion.

11.2.3 Mains supply voltage [21B]

In this menu the nominal mains supply voltage con-

nected to the AC drive can be selected. The setting will

be valid for all parameter sets. The default setting, Not

defined, is never selectable and is only visible until a

new value is selected.

Once the supply voltage is set, this selection will not be

affected by the Load Default command [243].

Brake chopper activation level is adjusted using the set-

ting of [21B].

CAUTION!

Level controlled inputs DO NOT comply with the

Machine Directive if the inputs are directly

used to start and stop the machine.

!

NOTE: Edge controlled inputs can comply with the

Machine Directive (see the Chapter 8. page 51) if the

inputs are directly used to start and stop the machine.

WARNING!

This menu must be set according to the AC

drive product lable and the supply voltage

used. Wrong setting might damage the AC

drive or brake resistor.

NOTE: The setting is affected by the Load from CP

command [245] and if loading parameter file via

EmoSoftCom.

219 Rotation. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Shared source cells (coordinates refer to this table):

219 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

21B SupplyVoltage. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

21A LevelEdge. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

21B communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

21A communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

219 Rotation — PDF page 71

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ R + L
2 R 1 Speed direction is limited to right rotation. The input and key RunL are disabled.
3 L 2 Speed direction is limited to left rotation. The input and key RunR are disabled.
4 R+L 3 Both speed directions allowed.

219 communication — PDF page 71

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43019
2 Profibus slot/index 168/178
3 Fieldbus format UInt
4 Modbus format UInt

21B SupplyVoltage — PDF page 71

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Not defined
2 Not Defined 0 Inverter default value used. Only valid if this parameter is never set.
3 220-240 V 1 Only valid for JNFX48
4 380-415 V 3 Only valid for JNFX48/52
5 440-480 V 4 Only valid for JNFX48/52
6 500-525 V 5 Only valid for JNFX52/69
7 550-600 V 6 Only valid for JNFX69
8 660-690 V 7 Only valid for JNFX69

21A LevelEdge — PDF page 71

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Level
2 Level 0 The inputs are activated or deactivated by a continuous high or low signal. Is commonly used if, for example, a PLC is used to operate the AC drive.
3 Edge 1 The inputs are activated by a transition; for Run and Reset from “low” to “high” and for Stop from "high" to "low".

21B communication — PDF page 71

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43381
2 Profibus slot/index 170/30
3 Fieldbus format UInt
4 Modbus format UInt

21A communication — PDF page 71

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43020
2 Profibus slot/index 168/179
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Motor voltage221,frequency222,power223. Collected P034 association; no extrapolation to other variants. — page 72

Manual reference: physical PDF page 72. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

The default settings are for a standard 4-pole motor according to the nominal power of the AC drive.

Referenced Note 2 provides context; no additional numeric defaults are inferred.

11.2.4 Motor Data [220]

In this menu you enter the motor data to adapt the AC

drive to the connected motor. This will increase the con-

trol accuracy as well as different read-outs and ana-

logue output signals.

Motor M1 is selected as default and motor data

entered will be valid for motor M1. If you have more

than one motor you need to select the correct motor in

menu [212] before entering motor data.

Motor Voltage [221]

Set the nominal motor voltage.

Communication information

Motor Frequency [222]

Set the nominal motor frequency.

Motor Power [223]

Set the nominal motor power. If paralell motors, set the

value as sum of motors power.

PNOM is the nominal AC drive power.

NOTE 1: The parameters for motor data cannot be

changed during run mode.

NOTE 2: The default settings are for a standard 4-pole

motor according to the nominal power of the AC drive.

NOTE 3: Parameter set cannot be changed during run if

the sets is set for different motors.

NOTE 4: Motor Data in the different sets M1 to M4 can

be revert to default setting in menu [243], Default>Set.

WARNING!

Enter the correct motor data to prevent

dangerous situations and assure correct

control.

NOTE: The Motor Volts value will always be stored as a 3

digit value with a resolution of 1 V.

NOTE: The Motor Power value will always be stored as a

3 digit value in W up to 999 W and in kW for all higher

powers.

Padlocks shown for221MotorVolts,222MotorFreq,223MotorPower; motor data cannot change duringRun. HeaderPNOM subscript representsnominaldrivepower; values remain literal.

222 MotorFrequency. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Default motor values depend on inverter family; motor data cannot change in run; parallel-motor power is summed.

222 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Default motor values depend on inverter family; motor data cannot change in run; parallel-motor power is summed.

223 MotorPower. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Default motor values depend on inverter family; motor data cannot change in run; parallel-motor power is summed.

221 MotorVoltage. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Default motor values depend on inverter family; motor data cannot change in run; parallel-motor power is summed.

223 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Default motor values depend on inverter family; motor data cannot change in run; parallel-motor power is summed.

221 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Default motor values depend on inverter family; motor data cannot change in run; parallel-motor power is summed.

222 MotorFrequency — PDF page 72

Source row Property Value
1 Default: 50 Hz
2 Range: 24-300 Hz
3 Resolution 1 Hz

222 communication — PDF page 72

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43042
2 Profibus slot/index 168/201
3 Fieldbus format Long, 1=1 Hz
4 Modbus format EInt

223 MotorPower — PDF page 72

Source row Property Value
1 Default: P VSD NOM
2 Range: 1W-120% x P NOM
3 Resolution 3 significant digits

221 MotorVoltage — PDF page 72

Source row Property Value
1 Default: 400 V for JNFX48 500 V for JNFX52 690 V for JNFX69
2 Range: 100-700 V
3 Resolution 1 V

223 communication — PDF page 72

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43043
2 Profibus slot/index 168/202
3 Fieldbus format Long, 1=1 W
4 Modbus format EInt

221 communication — PDF page 72

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43041
2 Profibus slot/index 168/200
3 Fieldbus format Long, 1=0.1 V
4 Modbus format EInt

Manual — Motor data [224]–[227] — page 73

Manual reference: physical PDF page 73. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

[224] Set the nominal motor current. If paralell motors, set the value as sum of motors current.

[224] NOTE: The default settings are for a standard 4-pole motor according to the nominal power of the AC drive.

[225] Set the nominal asynchronous motor speed.

[225] WARNING! Do NOT enter a synchronous (no-load) motor speed.

[225] NOTE: Maximum speed [343] is not automatically changed when the motor speed is changed.

[225] NOTE: Entering a wrong, too low value can cause a dangerous situation for the driven application due to high speeds.

[226] When the nominal speed of the motor is ≤500 rpm, the additional menu for entering the number of poles, [226], appears automatically. In this menu the actual pole number can be set which will increase the control accuracy of the AC drive.

[227] Set the nominal Motor cosphi (power factor).

Two columns read separately. F33 [224] range25–120% is source-specific; do not replace with V33 25–150%.

Subscripts flattened as I_MOT, I_NOM, n_MOT, Cosφ_NOM. Defaults symbolic, not numeric model ratings.

LCD illustrations retain source display values, not measured outputs. Padlock symbols shown; no lock behaviour inferred.

Referenced Note 2 on printed page 69 is on physical page 72; read it with these defaults.

F33 nominal current setting. Symbolic default and standard4-pole note retained.

Source F33 menu-specific communication table; no other family or adjacent menu values substituted.

Nominal asynchronous motor speed setting; preserve prohibition on synchronous no-load speed and other source warnings.

Additional menu appears when nominal motor speed ≤500rpm; this condition is not a drive maximum-speed rating.

Nominal motor power-factor setting. Symbolic default retained.

Motor Current [224] — PDF page 73

Source row Printed label Source value
1 Default I_MOT (see Note 2 page 69)
2 Range 25 - 120% x I_NOM
3 LCD illustration 224 Motor Curr; Stp A M1: (I_MOT)A

[224] communication information — PDF page 73

Source row Printed label Source value
1 Modbus Instance no/DeviceNet no 43044
2 Profibus slot/index 168/203
3 Fieldbus format Long, 1=0.1 A
4 Modbus format EInt

Motor Speed [225] — PDF page 73

Source row Printed label Source value
1 Default n_MOT (see Note 2 page 69)
2 Range 50 - 18000 rpm
3 Resolution 1 rpm, 4 sign digits
4 LCD illustration 225 Motor Speed; Stp A M1: (n_MOT)rpm

[225] communication information — PDF page 73

Source row Printed label Source value
1 Modbus Instance no/DeviceNet no 43045
2 Profibus slot/index 168/204
3 Fieldbus format UInt; 1=1 rpm
4 Modbus format UInt

Motor Poles [226] — PDF page 73

Source row Printed label Source value
1 Default 4
2 Range 2-144
3 LCD illustration 226 Motor Poles; Stp A M1: 4

[226] communication information — PDF page 73

Source row Printed label Source value
1 Modbus Instance no/DeviceNet no 43046
2 Profibus slot/index 168/205
3 Fieldbus format Long, 1=1 pole
4 Modbus format EInt

Motor Cos φ [227] — PDF page 73

Source row Printed label Source value
1 Default Cosφ_NOM (see Note 2 page 69)
2 Range 0.50 - 1.00
3 LCD illustration 227 Motor Cosφ; Stp A M1: Cosφ_NOM

[227] communication information — PDF page 73

Source row Printed label Source value
1 Modbus Instance no/DeviceNet no 43047
2 Profibus slot/index 168/206
3 Fieldbus format Long, 1=0.01
4 Modbus format EInt

Manual — Motor ventilation228 and ID run229. Collected P034 association; no extrapolation to other variants. — page 74

Manual reference: physical PDF page 74. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Motor ventilation [228]

Parameter for setting the type of motor ventilation.

Affects the characteristics of the I2t motor protection by

lowering the actual overload current at lower speeds.

Communication information

When the motor has no cooling fan, None is selected

and the current level is limited to 55% of rated motor

current.

With a motor with a shaft mounted fan, Self is selected

and the current for overload is limited to 87% from 20%

of synchronous speed. At lower speed, the overload cur-

rent allowed will be smaller.

When the motor has an external cooling fan, Forced is

selected and the overload current allowed starts at

90% from rated motor current at zero speed, up to

nominal motor current at 70% of synchronous speed.

Fig. 73 shows the characteristics with respect for Nomi-

nal Current and Speed in relation to the motor ventila-

tion type selected.

Fig. 73 I2t curves

Motor Identification Run [229]

This function is used when the AC drive is put into

operation for the first time. To achieve an optimal con-

trol performance, fine tuning of the motor parameters

using a motor ID run is needed. During the test run the

display shows “Test Run” flashing.

To activate the Motor ID run, select “Short” and press

Enter. Then press RunL or RunR on the control panel to

start the ID run. If menu

[219] Rotation is set to L the RunR key is inactive and

vice versa. The ID run can be aborted by giving a Stop

command via the control panel or Enable input. The

parameter will automatically return to OFF when the

test is completed. The message “Test Run OK!” is dis-

played. Before the AC drive can be operated normally

again, press the STOP/RESET key on the control panel.

During the Short ID run the motor shaft does not rotate.

The AC drive measures the rotor and stator resistance.

.

1.00

0.90

0.87

0.55

0.20

0.70

2.00

xSync Speed

xInom for I2t

Forced

Self

None

NOTE: To run the AC drive it is not mandatory for the ID

RUN to be executed, but without it the performance will

not be optimal.

NOTE: If the ID Run is aborted or not completed the

message “Interrupted!” will be displayed. The previous

data do not need to be changed in this case. Check that

the motor data are correct.

Figure73verticalaxis xInomforI2t:1.00,0.90,0.87,0.55;horizontal xSyncSpeed0.20,0.70,2.00. Forced/Self/Nonecurvesillustrative; no additionalpointsinterpolated.228and229havepadlocksymbols.

228 MotorVentilation. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Shared source cells (coordinates refer to this table):

228 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

229 MotorIDRun. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

229 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

228 MotorVentilation — PDF page 74

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Self
2 None 0 Limited I2t overload curve.
3 Self 1 Normal I2t overload curve. Means that the motor stands lower current at low speed.
4 Forced 2 Expanded I2t overload curve. Means that the motor stands almost the whole current also at lower speed.

228 communication — PDF page 74

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43048
2 Profibus slot/index 168/207
3 Fieldbus format UInt
4 Modbus format UInt

229 MotorIDRun — PDF page 74

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off, see Note
2 Off 0 Not active
3 Short 1 Parameters are measured with injected DC current. No rotation of the shaft will occur.

229 communication — PDF page 74

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43049
2 Profibus slot/index 168/208
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Motor sound [22A] and encoder parameters [22B]–[22D] — page 75

Manual reference: physical PDF page 75. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

[22A] Sets the sound characteristic of the AC drive output stage by changing the switching frequency and/or pattern. Generally the motor noise will go down at higher switching frequencies.

[22A] NOTE: At switching frequencies >3 kHz derating may become necessary. If the heat sink temperature gets too high the switching frequency is decreased to avoid tripping. This is done automatically in the AC drive. The default switching frequency is 3 kHz.

[22B] Only visible if the Encoder option board is installed. This parameter enables or disables the encoder feedback from the motor to the AC drive.

[22C] Only visible if the Encoder option board is installed. This parameter describes the number of pulses per rotation for your encoder, i.e. it is encoder specific. For more information please see the encoder manual.

[22D] Only visible if the Encoder option board is installed. This parameter shows the measured motor speed. To check if the encoder is correctly installed, set Encoder Feedback [22B] to Off, run the AC drive at any speed and compare with the value in this menu. The value in this menu [22D] should be about the same as the motor speed [712]. If you get the wrong sign for the value, swap encoder input A and B.

[22C] prose continues from bottom of left column to top of right on the same page; associate all its rows and context with22C.

LCD values are source illustrations; option board not presumed included.

[22D] Resolution is literally descriptive, not numerical.

[22A] Advanced choice references22E; its detailed setup is outside this page review and not inferred.

Switching-frequency choices with source derating condition.

Preserve source codes and ±750Hz. Derating may be required above3kHz; source temperature-dependent frequency reduction retained.

Source F33 menu-specific communication table; no other family or adjacent menu values substituted.

Only visible if Encoder option board installed.

Encoder option board required.

Encoder-specific pulses per rotation; encoder manual reference and option-board condition retained.

Monitoring parameter; option-board condition retained; no numeric resolution inferred.

Motor Sound [22A] — PDF page 75

Source row Printed label Source value
1 Default F
2 LCD illustration 22A Motor Sound; Stp A M1: F

[22A] choices — PDF page 75

Source row Choice Code Source description
1 E 0 Switching frequency 1.5 kHz
2 F 1 Switching frequency 3 kHz
3 G 2 Switching frequency 6 kHz
4 H 3 Switching frequency 6 kHz, random frequency (±750 Hz)
5 Advanced 4 Switching frequency and PWM mode setup via [22E]

[22A] communication information — PDF page 75

Source row Printed label Source value
1 Modbus Instance no/DeviceNet no 43050
2 Profibus slot/index 168/209
3 Fieldbus format UInt
4 Modbus format UInt

Encoder Feedback [22B] — PDF page 75

Source row Printed label Source value
1 Default Off
2 LCD illustration 22B Encoder; Stp A M1: Off

[22B] choices — PDF page 75

Source row Choice Code Source description
1 Off 0 Encoder feedback disabled
2 On 1 Encoder feedback enabled

[22B] communication information — PDF page 75

Source row Printed label Source value
1 Modbus Instance no/DeviceNet no 43051
2 Profibus slot/index 168/210
3 Fieldbus format UInt
4 Modbus format UInt

Encoder Pulses [22C] — PDF page 75

Source row Printed label Source value
1 Default 1024
2 Range 5–16384
3 LCD illustration 22C Enc Pulses; Stp A M1: 1024

[22C] communication information — PDF page 75

Source row Printed label Source value
1 Modbus Instance no/DeviceNet no 43052
2 Profibus slot/index 168/211
3 Fieldbus format Long, 1=1 pulse
4 Modbus format EInt

Encoder Speed [22D] — PDF page 75

Source row Printed label Source value
1 Unit rpm
2 Resolution speed measured via the encoder
3 LCD illustration 22D Enc Speed; Stp A M1: XXrpm

[22D] communication information — PDF page 75

Source row Printed label Source value
1 Modbus Instance no/DeviceNet no 42911
2 Profibus slot/index 168/70
3 Fieldbus format Int
4 Modbus format Int

Manual — PWM22E1–3 and encoder22F. Collected P034 association; no extrapolation to other variants. — page 76

Manual reference: physical PDF page 76. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Motor PWM [22E]

Menus for advanced setup of motor modulation proper-

ties PWM = Pulse Width Modulation).

PWM Fswitch [22E1]

Set the PWM switching frequency of the AC drive

Communication information

PWM Mode [22E2]

PWM Random [22E3]

Encoder Pulse counter [22F]

Only visible if the Encoder option is installed. Added

menu/parameter for accumulated QEP (Quadrature

Encoder Pulse) encoder pulses. Can be preset to any

value within bus format used (Int = 2 byte, Long = 4

byte).

NOTE: Switching frequency is fixed when “Sine Filt” is

selected. This means that it is not possible to control the

switching frequency based on temperature.

Note! For a 1024 pulse encoder [22F] will count

1024 * 4= 4096 pulses per turn.

22E3 PWMRandom. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Encoder counter visible only with fitted encoder option; PWMRandom source references E22E1 literally.

Shared source cells (coordinates refer to this table):

22E1 SwitchingFrequency. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Encoder counter visible only with fitted encoder option; PWMRandom source references E22E1 literally.

22E3 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Encoder counter visible only with fitted encoder option; PWMRandom source references E22E1 literally.

22E1 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Encoder counter visible only with fitted encoder option; PWMRandom source references E22E1 literally.

22E2 PWMMode. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Encoder counter visible only with fitted encoder option; PWMRandom source references E22E1 literally.

22F EncoderPulse. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Encoder counter visible only with fitted encoder option; PWMRandom source references E22E1 literally.

22F communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Encoder counter visible only with fitted encoder option; PWMRandom source references E22E1 literally.

22E2 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Encoder counter visible only with fitted encoder option; PWMRandom source references E22E1 literally.

22E3 PWMRandom — PDF page 76

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Random modulation is Off.
3 On 1 Random modulation is active. Random fre- quency variation range is ± 1/8 of level set in [E22E1].

22E1 SwitchingFrequency — PDF page 76

Source row Property Value
1 Default: 3.00 kHz
2 Range 1.50 - 6.00kHz
3 Resolution 0.01kHz

22E3 communication — PDF page 76

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43055
2 Profibus slot/index 168/214
3 Fieldbus format UInt
4 Modbus format UInt

22E1 communication — PDF page 76

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43053
2 Profibus slot/index 168/212
3 Fieldbus format Long, 1=1Hz
4 Modbus format EInt

22E2 PWMMode — PDF page 76

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Standard
2 Standard 0 Standard
3 Sine Filt 1 Sine Filter mode for use with output Sine Filters

22F EncoderPulse — PDF page 76

Source row Property Value
1 Default: 0
2 Resolutione 1

22F communication — PDF page 76

Source row Property Value
1 Modbus Instance no/DeviceNet no: 42912
2 Profibus slot/index 168/71
3 Fieldbus format Long, 1=1 quad encoder pulse
4 Modbus format Int

22E2 communication — PDF page 76

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43054
2 Profibus slot/index 168/213
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Motor I2t protection231–233. Collected P034 association; no extrapolation to other variants. — page 77

Manual reference: physical PDF page 77. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.2.5 Motor Protection [230]

This function protects the motor against overload

based on the standard IEC 60947-4-2.

Motor I2t Type [231]

The motor protection function makes it possible to pro-

tect the motor from overload as published in the stand-

ard IEC 60947-4-2. It does this using Motor I2t Current,

[232] as a reference. The Motor I2t Time [233] is used

to define the time behaviour of the function. The cur-

rent set in [232] can be delivered infinite in time. If for

instance in [233] a time of 1000 s is chosen the upper

curve of Fig. 74 is valid. The value on the x-axis is the

multiple of the current chosen in [232]. The time [233]

is the time that an overloaded motor is switched off or

is reduced in power at 1.2 times the current set in

[232].

Communication information

Motor I2t Current [232]

Sets the current limit for the motor I2t protection.

Motor I2t Time [233]

Sets the time of the I2t function. After this time the limit

for the I2t is reached if operating with 120% of the I2t

current value. Valid when start from 0 rpm.

NOTE: When Mot I2t Type=Limit, the AC drive can control

the speed < MinSpeed to reduce the motor current.

NOTE: When the selection Limit is set in menu [231], the

value must be above the no-load current of the motor.

NOTE: Not the time constant of the motor.

232 I2tCurrent. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

232 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

231 I2tType. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Shared source cells (coordinates refer to this table):

233 I2tTime. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

231 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

233 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

232 I2tCurrent — PDF page 77

Source row Property Value
1 Default: 100% of I MOT
2 Range: 0–150% of I MOT

232 communication — PDF page 77

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43062
2 Profibus slot/index 168/221
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

231 I2tType — PDF page 77

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Trip
2 Off 0 I2t motor protection is not active.
3 Trip 1 When the I2t time is exceeded, the AC drive will trip on “Motor I2t”.
4 Limit 2 This mode helps to keep the inverter run- ning when the Motor I2t function is just before tripping the AC drive. The trip is replaced by current limiting with a maxi- mum current level set by the value out of the menu [232]. In this way, if the reduced current can drive the load, the AC drive continues running.

233 I2tTime — PDF page 77

Source row Property Value
1 Default: 60 s
2 Range: 60–1200 s

231 communication — PDF page 77

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43061
2 Profibus slot/index 168/220
3 Fieldbus format UInt
4 Modbus format UInt

233 communication — PDF page 77

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43063
2 Profibus slot/index 168/222
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

Manual — I2t plot and thermal protection234. Collected P034 association; no extrapolation to other variants. — page 78

Manual reference: physical PDF page 78. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 74 I2t function

Fig. 74 shows how the function integrates the square of

the motor current according to the Mot I2t Curr [232]

and the Mot I2t Time [233].

When the selection Trip is set in menu [231] the AC

drive trips if this limit is exceeded.

When the selection Limit is set in menu [231] the AC

drive reduces the torque if the integrated value is 95%

or closer to the limit, so that the limit cannot be

exceeded.

Example

In Fig. 74 the thick grey line shows the following exam-

ple.

• Menu [232] Mot I2t Curr is set to 100%.

1.2 x 100% = 120%

• Menu [233] Mot I2t Time is set to 1000 s.

This means that the AC drive will trip or reduce after

1000 s if the current is 1.2 times of 100% nominal

motor current.

Thermal Protection [234]

Only visible if the PTC/PT100 option board is installed.

Set the PTC input for thermal protection of the motor.

The motor thermistors (PTC) must comply with DIN

44081/44082. Please refer to the manual for the PTC/

PT100 option board.

Menu [234] PTC contains functions to enable or disa-

ble the PTC input. Here you can select and activate PTC

and/or PT100.

Communication information

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9

t [s]

i / I2t-current

60 s (120%)

120 s (120%)

240 s (120%)

480 s (120%)

1000 s (120%)

Actual output current/ I2t-current

NOTE: If it is not possible to reduce the current, the AC

drive will trip after exceeding 110% of the limit.

NOTE: PTC option and PT100 selections can only be

selected in menu [234] if the option board is mounted.

Figure74 logtimeaxis10,100,1000,10000,100000s andcurrentratio1.0–2.0 in0.1steps. Labelledcurves60,120,240,480,1000s at120%;thickexampleat1.2ratioand1000s.

234 ThermalProtection. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. PTC/PT100 option fitted and selections enabled govern applicability; not current certification validation.

Shared source cells (coordinates refer to this table):

234 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. PTC/PT100 option fitted and selections enabled govern applicability; not current certification validation.

234 ThermalProtection — PDF page 78

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 PTC and PT100 motor protection are disabled.
3 PTC 1 Enables the PTC protection of the motor via the insulated option board.
4 PT100 2 Enables the PT100 protection for the motor via the insulated option board.
5 PTC+PT100 3 Enables the PTC protection as well as the PT100 protection for the motor via the insulated option board.

234 communication — PDF page 78

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43064
2 Profibus slot/index 168/223
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Motor class235 and PT100inputs236. Collected P034 association; no extrapolation to other variants. — page 79

Manual reference: physical PDF page 79. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Motor Class [235]

Only visible if the PTC/PT100 option board is installed.

Set the class of motor used. The trip levels for the

PT100 sensor will automatically be set according to the

setting in this menu.

Communication information

PT100 Inputs [236]

Sets which of PT100 inputs that should be used for

thermal protection. Deselecting not used PT100 inputs

on the PTC/PT100 option board in order to ignore those

inputs, i.e. extra external wiring is not needed if port is

not used.

NOTE: If you select the PTC option, the PT100 inputs are

ignored.

NOTE: This menu is only valid for PT 100.

NOTE: This menu is only valid for PT 100 thermal

protection if PT100 is enabled in menu [234].

236 PT100Inputs. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. PTC/PT100 option fitted and selections enabled govern applicability; not current certification validation.

Shared source cells (coordinates refer to this table):

235 MotorClass. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. PTC/PT100 option fitted and selections enabled govern applicability; not current certification validation.

235 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. PTC/PT100 option fitted and selections enabled govern applicability; not current certification validation.

236 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. PTC/PT100 option fitted and selections enabled govern applicability; not current certification validation.

236 PT100Inputs — PDF page 79

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ PT100 1+2+3
2 Selection: ⟦blank source cell⟧ PT100 1, PT100 2, PT100 1+2, PT100 3, PT100 1+3, PT100 2+3, PT100 1+2+3
3 PT100 1 1 Channel 1 used for PT100 protection
4 PT100 2 2 Channel 2 used for PT100 protection
5 PT100 1+2 3 Channel 1+2 used for PT100 protection
6 PT100 3 4 Channel 3 used for PT100 protection
7 PT100 1+3 5 Channel 1+3 used for PT100 protection
8 PT100 2+3 6 Channel 2+3 used for PT100 protection
9 PT100 1+2+3 7 Channel 1+2+3 used for PT100 protec- tion

235 MotorClass — PDF page 79

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ F 140°C
2 A 100°C 0 ⟦blank source cell⟧
3 E 115°C 1 ⟦blank source cell⟧
4 B 120°C 2 ⟦blank source cell⟧
5 F 140°C 3 ⟦blank source cell⟧
6 F Nema 145°C 4 ⟦blank source cell⟧
7 H 165°C 5 ⟦blank source cell⟧

235 communication — PDF page 79

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43065
2 Profibus slot/index 168/224
3 Fieldbus format UInt
4 Modbus format UInt

236 communication — PDF page 79

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43066
2 Profibus slot/index 168/225
3 Fieldbus format UInt
4 Modbus format UInt

Manual — MotorPTC237 and set selection241. Collected P034 association; no extrapolation to other variants. — page 80

Manual reference: physical PDF page 80. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Motor PTC [237]

In this menu the internal motor PTC hardware option is

enabled. This PTC input complies with DIN 44081/

  1. Please refer to the manual for the PTC/PT100

option board for electrical specification.

This menu is only visible if a PTC (or resistor <2 kOhm)

is connected to terminals X1: 78–79.

To enable the function:

  1. Connect the thermistor wires to X1: 78–79 or for

testing the input, connect a resistor to the terminals.

Use resistor value between 50 and 2000 ohm.

Menu [237] will now appear.

  1. Enable input by setting menu [237] Motor PTC=On.

If enabled and <50 ohm a sensor error trip will occur.

The message “Motor PTC” is shown.

If the function is disabled and the PTC or resistor is

removed, the menu will disappear after the next power

up

Communication information

11.2.6 Parameter Set Handling [240]

There are four different parameter sets available in the

AC drive. These parameter sets can be used to set the

AC drive up for different processes or applications such

as different motors used and connected, activated PID

controller, different ramp time settings, etc.

A parameter set consists of all parameters with the

exception of the Global parameters . The Global param-

eters are only able to have one value for all parameter

sets.

Following parameters are Global: [211] Language,

[217] Local Remote, [218] Lock Code, [220] Motor

Data, [241] Select Set, [260] Serial Communication

and [21B]Mains Supply Voltage .

Select Set [241]

Here you select the parameter set. Every menu

included in the parameter sets is designated A, B, C or

D depending on the active parameter set. Parameter

sets can be selected from the keyboard, via the pro-

grammable digital inputs or via serial communication.

Parameter sets can be changed during the run. If the

sets are using different motors (M1 to M4) the set will

be changed when the motor is stopped.

NOTE: This option is available only for (size B to D)

JNFX48/52-0003-0074.

NOTE: Actual timers are common for all sets. When a set

is changed the timer functionality will change according

to the new set, but the timer value will stay unchanged.

237 MotorPTC. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. InternalPTC onlysizeB–D JNFX48/52-0003–0074;motor-changing parameter sets require stop.

Shared source cells (coordinates refer to this table):

241 SelectSet. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. InternalPTC onlysizeB–D JNFX48/52-0003–0074;motor-changing parameter sets require stop.

237 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. InternalPTC onlysizeB–D JNFX48/52-0003–0074;motor-changing parameter sets require stop.

241 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. InternalPTC onlysizeB–D JNFX48/52-0003–0074;motor-changing parameter sets require stop.

237 MotorPTC — PDF page 80

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Motor PTC protection is disabled
3 On 1 Motor PTC protection is enabled

241 SelectSet — PDF page 80

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ A
2 Selection: ⟦blank source cell⟧ A, B, C, D, DigIn, Com, Option
3 A 0 Fixed selection of one of the 4 parameter sets A, B, C or D.
4 B 1 ⟦null: no independent source value⟧
5 C 2 ⟦null: no independent source value⟧
6 D 3 ⟦null: no independent source value⟧
7 DigIn 4 Parameter set is selected via a digital input. Define which digital input in menu [520], Digital inputs.
8 Com 5 Parameter set is selected via serial communication.
9 Option 6 The parameter set is set via an option. Only available if the option can control the selection.

237 communication — PDF page 80

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43067
2 Profibus slot/index 168/226
3 Fieldbus format UInt
4 Modbus format UInt

241 communication — PDF page 80

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43022
2 Profibus slot/index 168/181
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Copy set242 and default set243. Collected P034 association; no extrapolation to other variants. — page 81

Manual reference: physical PDF page 81. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

The active set can be viewed with function [721] FI sta-

tus.

Copy Set [242]

This function copies the content of a parameter set into

another parameter set.

Communication information

A>B means that the content of parameter set A is cop-

ied into parameter set B.

Load Default Values Into Set [243]

With this function three different levels (factory set-

tings) can be selected for the four parameter sets.

When loading the default settings, all changes made in

the software are set to factory settings. This function

also includes selections for loading default settings to

the four different Motor Data Sets.

NOTE: Parameter set cannot be changed during run if

this also would imply a change of the motor set (M2-

M4).

NOTE: The actual value of menu [310] will not be copied

into the other set.

NOTE: Trip log hour counter and other VIEW ONLY menus

are not regarded as settings and will be unaffected.

NOTE: If “Factory” is selected, the message “Sure?” is

displayed. Press the + key to display “Yes” and then

Enter to confirm.

NOTE: The parameters in menu [220], Motor data, are

not affected by loading defaults when restoring

parameter sets A–D.

243 DefaultSet. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Shared source cells (coordinates refer to this table):

242 CopySet. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

243 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

242 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

243 DefaultSet — PDF page 81

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ A
2 A 0 Only the selected parameter set will revert to its default settings.
3 B 1 ⟦null: no independent source value⟧
4 C 2 ⟦null: no independent source value⟧
5 D 3 ⟦null: no independent source value⟧
6 ABCD 4 All four parameter sets will revert to the default settings.
7 Factory 5 All settings, except [211], [221]-[22D], [261] and [923], will revert to the default settings.
8 M1 6 Only the selected motor set will revert to its default settings.
9 M2 7 ⟦null: no independent source value⟧
10 M3 8 ⟦null: no independent source value⟧
11 M4 9 ⟦null: no independent source value⟧
12 M1234 10 All four motor sets will revert to default settings.

242 CopySet — PDF page 81

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ A>B
2 A>B 0 Copy set A to set B
3 A>C 1 Copy set A to set C
4 A>D 2 Copy set A to set D
5 B>A 3 Copy set B to set A
6 B>C 4 Copy set B to set C
7 B>D 5 Copy set B to set D
8 C>A 6 Copy set C to set A
9 C>B 7 Copy set C to set B
10 C>D 8 Copy set C to set D
11 D>A 9 Copy set D to set A
12 D>B 10 Copy set D to set B
13 D>C 11 Copy set D to set C

243 communication — PDF page 81

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43023
2 Profibus slot/index 168/182
3 Fieldbus format UInt
4 Modbus format UInt

242 communication — PDF page 81

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43021
2 Profibus slot/index 168/180
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Control-panel copy244/load245. Collected P034 association; no extrapolation to other variants. — page 82

Manual reference: physical PDF page 82. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Copy All Settings to Control Panel [244]

All the settings can be copied into the control panel

including the motor data. Start commands will be

ignored during copying.

Communication information

Load Settings from Control Panel [245]

This function can load all four parameter sets from the

control panel to the AC drive. Parameter sets from the

source AC drive are copied to all parameter sets in the

target AC drive, i.e. A to A, B to B, C to C and D to D.

Start commands will be ignored during loading.

NOTE: The actual value of menu [310] will not be copied

into control panel memory set.

NOTE: Loading from the control panel will not affect the

value in menu [310].

Padlocksymbols for244CopytoCP and245LoadfromCP: unavailableduringRun; noengineeringpermission inferred.

244 CopyToCP. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Shared source cells (coordinates refer to this table):

245 LoadFromCP. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

244 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

245 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

244 CopyToCP — PDF page 82

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ No Copy
2 No Copy 0 Nothing will be copied
3 Copy 1 Copy all settings

245 LoadFromCP — PDF page 82

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ No Copy
2 No Copy 0 Nothing will be loaded.
3 A 1 Data from parameter set A is loaded.
4 B 2 Data from parameter set B is loaded.
5 C 3 Data from parameter set C is loaded.
6 D 4 Data from parameter set D is loaded.
7 ABCD 5 Data from parameter sets A, B, C and D are loaded.
8 A+Mot 6 Parameter set A and Motor data are loaded.
9 B+Mot 7 Parameter set B and Motor data are loaded.
10 C+Mot 8 Parameter set C and Motor data are loaded.
11 D+Mot 9 Parameter set D and Motor data are loaded.
12 ABCD+Mot 10 Parameter sets A, B, C, D and Motor data are loaded.
13 M1 11 Data from motor 1 is loaded.
14 M2 12 Data from motor 2 is loaded.
15 M3 13 Data from motor 3 is loaded.
16 M4 14 Data from motor 4 is loaded.
17 M1M2M3 M4 15 Data from motor 1, 2, 3 and 4 are loaded.
18 All 16 All data is loaded from the control panel.

244 communication — PDF page 82

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43024
2 Profibus slot/index 168/183
3 Fieldbus format UInt
4 Modbus format UInt

245 communication — PDF page 82

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43025
2 Profibus slot/index 168/184
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Autoreset251 and overtemperature252. Collected P034 association; no extrapolation to other variants. — page 83

Manual reference: physical PDF page 83. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.2.7 Trip Autoreset/Trip Conditions

[250]

The benefit of this feature is that occasional trips that

do not affect the process will be automatically reset.

Only when the failure keeps on coming back, recurring

at defined times and therefore cannot be solved by the

AC drive, will the unit give an alarm to inform the opera-

tor that attention is required.

For all trip functions that can be activated by the user

you can select to control the motor down to zero speed

according to set deceleration ramp to avoid water ham-

mer.

Also see section 12.2, page 170.

Autoreset example:

In an application it is known that the main supply volt-

age sometimes disappears for a very short time, a so-

called “dip”. That will cause the AC drive to trip an “Und-

ervoltage alarm”. Using the Autoreset function, this trip

will be acknowledged automatically.

• Enable the Autoreset function by making the reset

input continuously high.

• Activate the Autoreset function in the menu [251],

Number of trips.

• Select in menus [252] to [25N] the Trip condition

that are allowed to be automatically reset by the

Autoreset function after the set delay time has

expired.

Number of Trips [251]

Any number set above 0 activates the Autoreset. This

means that after a trip, the AC drive will restart auto-

matically according to the number of attempts

selected. No restart attempts will take place unless all

conditions are normal.

If the Autoreset counter (not visible) contains more trips

than the selected number of attempts, the Autoreset

cycle will be interrupted. No Autoreset will then take

place.

If there are no trips for more than 10 minutes, the

Autoreset counter decreases by one.

If the maximum number of trips has been reached, the

trip message hour counter is marked with an “A”.

If the Autoreset is full then the AC drive must be reset

by a normal Reset.

Example:

• Autoreset = 5

• Within 10 minutes 6 trips occur

• At the 6th trip there is no Autoreset, because the

Autoreset trip log contains 5 trips already.

•

To reset, apply a normal reset: set the reset input

high to low and high again to maintain the Autoreset

function. The counter is reset.

Communication information

Over temperature [252]

Delay time starts counting when the fault is gone.

When the time delay has elapsed, the alarm will be

reset if the function is active.

NOTE: An auto reset is delayed by the remaining ramp

time.

251 NumberTrips. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

251 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

252 Overtemperature. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

Shared source cells (coordinates refer to this table):

252 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent.

251 NumberTrips — PDF page 83

Source row Property Value
1 Default: 0 (no Autoreset)
2 Range: 0–10 attempts

251 communication — PDF page 83

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43071
2 Profibus slot/index 168/230
3 Fieldbus format UInt
4 Modbus format UInt

252 Overtemperature — PDF page 83

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off
3 1–3600 1–3600 1–3600 s

252 communication — PDF page 83

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43072
2 Profibus slot/index 168/231
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

Manual — Autoreset delay/trip settings. Collected P034 association; no extrapolation to other variants. — page 84

Manual reference: physical PDF page 84. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Overvolt D [253]

Delay time starts counting when the fault is gone.

When the time delay has elapsed, the alarm will be

reset if the function is active.

Communication information

Overvolt G [254]

Delay time starts counting when the fault is gone When

the time delay has elapsed, the alarm will be reset if

the function is active.

Overvolt [255]

Motor Lost [256]

NOTE: An auto reset is delayed by the remaining ramp

time.

NOTE: Only visible when Motor Lost is selected in menu

[423].

253 Overvolt D. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

Shared source cells (coordinates refer to this table):

255 Overvolt. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

253 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

255 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

256 Motor Lost. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

254 Overvolt G. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

254 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

256 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

253 Overvolt D — PDF page 84

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off
3 1–3600 1–3600 1–3600 s

253 communication — PDF page 84

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43075
2 Profibus slot/index 168/234
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

255 communication — PDF page 84

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43077
2 Profibus slot/index 168/236
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

254 communication — PDF page 84

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43076
2 Profibus slot/index 168/235
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

256 communication — PDF page 84

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43083
2 Profibus slot/index 168/242
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

Manual — Autoreset delay/trip settings. Collected P034 association; no extrapolation to other variants. — page 85

Manual reference: physical PDF page 85. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Locked Rotor [257]

Delay time starts counting when the fault is gone.

When the time delay has elapsed, the alarm will be

reset if the function is active.

Communication information

Power Fault [258]

Undervoltage [259]

Motor I2t [25A]

Motor I2t Trip Type [25B]

Select the preferred way to react to a Motor I2t trip.

PT100 [25C]

25C PT100

Stp

Off

A

259 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

257 Locked Rotor. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

Shared source cells (coordinates refer to this table):

257 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25A communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

258 Power Fault. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

258 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25B communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

259 Undervoltage. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

259 communication — PDF page 85

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43088
2 Profibus slot/index 168/247
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

257 Locked Rotor — PDF page 85

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off
3 1–3600 1–3600 1–3600 s

257 communication — PDF page 85

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43086
2 Profibus slot/index 168/245
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

25A communication — PDF page 85

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43073
2 Profibus slot/index 168/232
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

2 — PDF page 85

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Trip
2 Trip 0 The motor will trip
3 Deceleration 1 The motor will decelerate

258 communication — PDF page 85

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43087
2 Profibus slot/index 168/246
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

25B communication — PDF page 85

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43074
2 Profibus slot/index 168/233
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Autoreset delay/trip settings. Collected P034 association; no extrapolation to other variants. — page 86

Manual reference: physical PDF page 86. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Communication information

PT100 Trip Type [25D]

Delay time starts counting when the fault is gone.

When the time delay has elapsed, the alarm will be

reset if the function is active.

PTC [25E]

PTC Trip Type [25F]

Select the preferred way to react to a PTC trip.

External Trip [25G]

25C PT100 continuation from PDF85. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

Shared source cells (coordinates refer to this table):

25F PTC TT. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25C communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25F communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25D PT100 TT. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25G Ext Trip. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25D communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25G communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25E PTC. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25E communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25C PT100 continuation from PDF85 — PDF page 86

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off
3 1–3600 1–3600 1–3600 s

25F PTC TT — PDF page 86

Source row Property Value
1 Default: Trip
2 Selection: Same as menu [25B]

25C communication — PDF page 86

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43078
2 Profibus slot/index 168/237
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

25F communication — PDF page 86

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43085
2 Profibus slot/index 168/244
3 Fieldbus format UInt
4 Modbus format UInt

25D communication — PDF page 86

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43079
2 Profibus slot/index 168/238
3 Fieldbus format Uint
4 Modbus format UInt

25G communication — PDF page 86

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43080
2 Profibus slot/index 168/239
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

25E communication — PDF page 86

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43084
2 Profibus slot/index 168/243
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

Manual — Autoreset delay/trip settings. Collected P034 association; no extrapolation to other variants. — page 87

Manual reference: physical PDF page 87. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

External Trip Type [25H]

Select the preferred way to react to an alarm trip.

Communication information

Communication Error [25I]

Delay time starts counting when the fault is gone.

When the time delay has elapsed, the alarm will be

reset if the function is active.

Communication Error Trip Type [25J]

Select the preferred way to react to a communication

trip.

Min Alarm [25K]

Min Alarm Trip Type [25L]

Select the preferred way to react to a min alarm trip.

25H Ext Trip TT. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25J Com Error TT. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25H communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25J communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25I Com Error. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

Shared source cells (coordinates refer to this table):

25K Min Alarm. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25I communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25K communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25L Min Alarm TT. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25L communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25H Ext Trip TT — PDF page 87

Source row Property Value
1 Default: Trip
2 Selection: Same as menu [25B]

25H communication — PDF page 87

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43081
2 Profibus slot/index 168/240
3 Fieldbus format UInt
4 Modbus format UInt

25J communication — PDF page 87

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43090
2 Profibus slot/index 168/249
3 Fieldbus format UInt
4 Modbus format UInt

25I Com Error — PDF page 87

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off
3 1–3600 1–3600 1–3600 s

25I communication — PDF page 87

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43089
2 Profibus slot/index 168/248
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

25K communication — PDF page 87

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43091
2 Profibus slot/index 168/250
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

25L communication — PDF page 87

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43092
2 Profibus slot/index 168/251
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Autoreset delay/trip settings. Collected P034 association; no extrapolation to other variants. — page 88

Manual reference: physical PDF page 88. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Max Alarm [25M]

Delay time starts counting when the fault is gone.

When the time delay has elapsed, the alarm will be

reset if the function is active.

Communication information

Max Alarm Trip Type [25N]

Select the preferred way to react to a max alarm trip.

Over current F [25O]

Pump [25P]

Over Speed [25Q]

25O communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25M Max Alarm. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

Shared source cells (coordinates refer to this table):

25P Pump. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25M communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25P communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25N Max Alarm TT. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25N communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25Q Over speed. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25O Over curr F. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25Q communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25O communication — PDF page 88

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43082
2 Profibus slot/index 168/241
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

25M Max Alarm — PDF page 88

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off
3 1–3600 1–3600 1–3600 s

25M communication — PDF page 88

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43093
2 Profibus slot/index 168/252
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

25P communication — PDF page 88

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43095
2 Profibus slot/index 168/254
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

25N Max Alarm TT — PDF page 88

Source row Property Value
1 Default: Trip
2 Selection: Same as menu [25B]

25N communication — PDF page 88

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43094
2 Profibus slot/index 168/253
3 Fieldbus format UInt
4 Modbus format UInt

25Q communication — PDF page 88

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43096
2 Profibus slot/index 169/0
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

Manual — Autoreset delay/trip settings. Collected P034 association; no extrapolation to other variants. — page 89

Manual reference: physical PDF page 89. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

External Motor Temperature [25R]

Delay time starts counting when the fault disappears.

When the time delay has elapsed, the alarm will be

reset if the function is active.

Communication information

External Motor Trip Type [25S]

Select the preferred way to react to an alarm trip.

Liquid cooling low level [25T]

Liquid Cooling Low level Trip Type [25U]

Brake Fault [25V]

Select the preferred way to react to an alarm trip, acti-

vate auto reset and specify delay time.

25T communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25R Ext Mot Temp. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

Shared source cells (coordinates refer to this table):

25U LC Level TT. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25R communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25U communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25S Ext Mot TT. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25V Brk Fault. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25S communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25V communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25T LC Level. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Autoreset delays count after fault clears plus remaining ramp time; Off and trip type refer to this named fault only.

25T communication — PDF page 89

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43099
2 Profibus slot/index 169/3
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

25R Ext Mot Temp — PDF page 89

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off
3 1–3600 1–3600 1–3600 s

25U LC Level TT — PDF page 89

Source row Property Value
1 Default: Trip
2 Selection: Same as menu [25B]

25R communication — PDF page 89

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43097
2 Profibus slot/index 168/239
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

25U communication — PDF page 89

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43100
2 Profibus slot/index 169/4
3 Fieldbus format UInt
4 Modbus format UInt

25V Brk Fault — PDF page 89

Source row Selection/property Enumeration or merged span Description/value
1 Default ⟦null: no independent source value⟧ Off
2 Off 0 Autoreset not activated.
3 1 - 3600s 1 - 3600s Brake fault auto reset delay time.

25S communication — PDF page 89

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43098
2 Profibus slot/index 168/240
3 Fieldbus format UInt
4 Modbus format UInt

25V communication — PDF page 89

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43070
2 Profibus slot/index 168/229
3 Fieldbus format Long, 1=1s
4 Modbus format EInt

Manual — Communications and fieldbus. Collected P034 association; no extrapolation to other variants. — page 90

Manual reference: physical PDF page 90. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.2.8 Serial Communication [260]

This function is to define the communication parame-

ters for serial communication. There are two types of

options available for serial communication, RS232/

485 (Modbus/RTU) and fieldbus modules (Profibus,

DeviceNet and Ethernet).

For more information see chapter Serial communica-

tion and respective option manual.

Comm Type [261]

Select RS232/485 [262] or Fieldbus [263].

RS232/485 [262]

Press Enter to set up the parameters for RS232/485

(Modbus/RTU) communication.

Baud rate [2621]

Set the baud rate for the communication.

Address [2622]

Enter the unit address for the AC drive.

Fieldbus [263]

Press Enter to set up the parameters for fieldbus

communication.

Address [2631]

Enter the unit address of the AC drive.

Process Data Mode [2632]

Enter the mode of process data (cyclic data). For fur-

ther information, see the Fieldbus option manual.

NOTE: Toggling the setting in this menu will perform a

soft reset (re-boot) of the Fieldbus module.

NOTE: This baud rate is only used for the isolated

RS232/485 option.

262 RS232/485

Stp

NOTE: This address is only used for the isolated RS232/

485 option.

263 Fieldbus

StpA

Padlock next to261 indicates unavailable duringRun. ParentLCD262RS232/485 and263Fieldbus carry no independent numericdefault.

2622 Address. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

261 Com Type. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

Shared source cells (coordinates refer to this table):

2631 Address. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2632 PrData Mode. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2621 Baudrate. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2621 Baudrate; default9600. Individual source rows2400→0,4800→1,9600→2,19200→3,38400→4. IsolatedRS232/485 option only.

2622 Address — PDF page 90

Source row Property Value
1 Default: 1
2 Selection: 1–247

261 Com Type — PDF page 90

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ RS232/485
2 RS232/485 0 RS232/485 selected
3 Fieldbus 1 Fieldbus selected (Profibus, DeviceNet or Modbus/TCP)

2631 Address — PDF page 90

Source row Property Value
1 Default: 62
2 Range: Profibus 0–126, DeviceNet 0–63
3 Node address valid for Profibus and DeviceNet ⟦null: no independent source value⟧

2632 PrData Mode — PDF page 90

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ Basic
2 None 0 Control/status information is not used.
3 Basic 4 4 byte process data control/status information is used.
4 Extended 8 4 byte process data (same as Basic setting) + additional proprietary protocol for advanced users is used.

2621 Baudrate — PDF page 90

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ 9600
2 2400 0 Selected baud rate
3 4800 1 ⟦null: no independent source value⟧
4 9600 2 ⟦null: no independent source value⟧
5 19200 3 ⟦null: no independent source value⟧
6 38400 4 ⟦null: no independent source value⟧

Manual — Communications and fieldbus. Collected P034 association; no extrapolation to other variants. — page 91

Manual reference: physical PDF page 91. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Read/Write [2633]

Select read/write to control the inverter over a fieldbus

network. For further information, see the Fieldbus

option manual.

Additional Process Values [2634]

Define the number of additional process values sent in

cyclic messages.

Communication Fault [264]

Main menu for communication fault/warning settings.

For further details please see the Fieldbus option man-

ual.

Communication Fault Mode [2641]]

Selects action if a communication fault is detected.

Communication information

NOTE: Menu [214] and/or [215] must be set to COM to

activate the communication fault function.

2633 Read/Write. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

Shared source cells (coordinates refer to this table):

2641 ComFlt Mode. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2634 AddPrValues. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2641 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2633 Read/Write — PDF page 91

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ RW
2 RW 0 ⟦blank source cell⟧
3 Read 1 ⟦blank source cell⟧
4 Valid for process data. Select R (read only) for logging process without writing process data. Select RW in normal cases to control inverter. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

2641 ComFlt Mode — PDF page 91

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 No communication supervision.
3 Trip 1 RS232/485 selected: The AC drive will trip if there is no communication for time set in parameter [2642]. Fieldbus selected: The AC drive will trip if: 1. The internal communication between the control board and fieldbus option is lost for time set in parameter [2642]. 2. If a serious network error has occurred.
4 Warning 2 RS232/485 selected: The AC drive will give a warning if there is no communication for time set in parameter [2642]. Fieldbus selected: The AC drive will give a warning if: 1. The internal communication between the control board and fieldbus option is lost for time set in parameter [2642]. 2. If a serious network error has occurred.

2634 AddPrValues — PDF page 91

Source row Property Value
1 Default: 0
2 Range: 0-8

2641 communication — PDF page 91

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43037
2 Profibus slot/index 168/196
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Communications and fieldbus. Collected P034 association; no extrapolation to other variants. — page 92

Manual reference: physical PDF page 92. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Communication Fault Time [2642]]

Defines the delay time for the trip/warning.

Communication information

Ethernet [265]

Settings for Ethernet module (Modbus/TCP). For further

information, see the Fieldbus option manual.

IP Address [2651]

MAC Address [2652]

Subnet Mask [2653]

Gateway [2654]

DHCP [2655]

Fieldbus Signals [266]

Defines modbus mapping for additional process values.

For further information, see the Fieldbus option man-

ual.

FB Signal 1 - 16 [2661]-[266G]

Used to create a block of parameters which are read/

written via communication. 1 to 8 read + 1 to 8 write

parameters possible.

FB Status [269]

Sub menus showing status of fieldbus parameters.

Please see the Fieldbus manual for detailed informa-

tion.

NOTE: The Ethernet module must be re-booted to

activate the below settings. For example by toggling

parameter [261]. Non-initialized settings indicated by

flashing display text.

269 FB Status

Stp

LCDIP2651,Subnet2653,Gateway2654 show four spaced0 groups separated by dots; nativehiddenpaddingzeros preserved in sourceheader. MACdisplayexample is zeros; default expressly unique Ethernetmodule number.

2654 Gateway. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2642 ComFlt Time. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2655 DHCP. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2642 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2661 FB Signal 1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2651 IP Address. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2661–266G communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2652 MAC Address. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2653 Subnet Mask. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Communication-board type and selected process-data mode govern availability; display addresses may be examples.

2654 Gateway — PDF page 92

Source row Property Value
1 Default: 0.0.0.0

2642 ComFlt Time — PDF page 92

Source row Property Value
1 Default: 0.5 s
2 Range: 0.1-15 s

2655 DHCP — PDF page 92

Source row Property Value
1 Default: Off
2 Selection: On/Off

2642 communication — PDF page 92

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43038
2 Profibus slot/index 168/197
3 Fieldbus format Long, 1=0.1 s
4 Modbus format EInt

2661 FB Signal 1 — PDF page 92

Source row Property Value
1 Default: 0
2 Range: 0-65535

2661–266G communication — PDF page 92

Source row Property Value
1 Modbus Instance no/DeviceNet no: 42801-42816
2 Profibus slot/index 167/215-167/230
3 Fieldbus format UInt
4 Modbus format UInt

2652 MAC Address — PDF page 92

Source row Property Value
1 Default: An unique number for the Ethernet module.

Manual — Process reference, units and scaling. Collected P034 association; no extrapolation to other variants. — page 93

Manual reference: physical PDF page 93. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.3 Process and Application

Parameters [300]

These parameters are mainly adjusted to obtain opti-

mum process or machine performance.

The read-out, references and actual values depends on

selected process source, [321}:

11.3.1 Set/View Reference Value

[310]

View reference value

As default the menu [310] is in view operation. The

value of the active reference signal is displayed. The

value is displayed according to selected process

source, [321] or the process unit selected in menu

[322].

Set reference value

If the function Reference Control [214] is set to

“Keyboard”, the reference value can be set in menu

Set/View Reference [310] or as a motor potentiometer

with the + and - keys (default) on the control panel.

Selection is made with parameter Keyboard Reference

Mode in menu [369]. The ramp times used when set-

ting the reference value with MotPot function selected

in [369] are according to menus Acc MotPot [333] and

Dec MotPot [334].

The ramp times used for the reference value when Nor-

mal function is selected in menu [369], are according

to Acc Time [331] and Dec Time [332].

Menu [310] displays on-line the actual reference value

according to the Mode Settings in Table 23.

Communication information

Table 23

NOTE: The actual value in menu [310] is not copied, or

loaded from the control panel memory when Copy Set

[242], Copy to CP [244] or Load from CP [245] is

performed.

NOTE: If the MotPot function is used, the reference value

ramp times are according to the Acc MotPot [333] and

Dec MotPot [334] settings. Actual speed ramp will be

limited according to Acc Time [331] and Dec Time [332].

NOTE: Write access to this parameter is only allowed

when menu “Ref Control [214] is set to Keyboard. When

Reference control is used, see section “10.5 Reference

signal” on page 60

310 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

Table23 Process-source unit and resolution. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

310 Set/View ref. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

310 communication — PDF page 93

Source row Property Value
1 Modbus Instance no/DeviceNet no: 42991
2 Profibus slot/index 168/150
3 Fieldbus format Long
4 Modbus format EInt

Table23 Process-source unit and resolution — PDF page 93

Source row Selected process source Unit for reference and actual value Resolution
1 Speed rpm 4 digits
2 Torque % 3 digits
3 PT100 °C 3 digits
4 Frequency Hz 3 digits

310 Set/View ref — PDF page 93

Source row Property Value
1 Default: 0 rpm
2 Dependent on: Process Source [321] and Process Unit [322]
3 Speed mode 0 - max speed [343]
4 Torque mode 0 - max torque [351]
5 Other modes Min according to menu [324] - max accord- ing to menu [325]

Manual — Process reference, units and scaling. Collected P034 association; no extrapolation to other variants. — page 94

Manual reference: physical PDF page 94. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.3.2 Process Settings [320]

With these functions, the AC drive can be set up to fit

the application. The menus [110], [120], [310], [362]-

[368] and [711] use the process unit selected in [321]

and [322] for the application, e.g. rpm, bar or m3/h.

This makes it possible to easily set up the AC drive for

the required process requirements, as well as for copy-

ing the range of a feedback sensor to set up the Proc-

ess Value Minimum and Maximum in order to establish

accurate actual process information.

Process Source [321]

Select the signal source for the process value that con-

trols the motor. The Process Source can be set to act as

a function of the process signal on AnIn F(AnIn), a func-

tion of the motor speed F(Speed), a function of the

shaft torque F(Torque) or as a function of a process

value from serial communication F(Bus). The right func-

tion to select depends on the characteristics and

behaviour of the process. If the selection Speed, Torque

or Frequency is set, the AC drive will use speed, torque

or frequency as reference value.

Example

An axial fan is speed-controlled and there is no feed-

back signal available. The process needs to be control-

led within fixed process values in “m3/hr” and a

process read-out of the air flow is needed. The charac-

teristic of this fan is that the air flow is linearly related

to the actual speed. So by selecting F(Speed) as the

Process Source, the process can easily be controlled.

The selection F(xx) indicates that a process unit and

scaling is needed, set in menus [322]-[328]. This

makes it possible to e.g. use pressure sensors to meas-

ure flow etc. If F(AnIn) is selected, the source is auto-

matically connected to the AnIn which has Process

Value as selected.

  1. Only when Drive mode [213] is set to Speed or V/Hz.

Communication information

Process Unit [322]

NOTE: When PT100 is selected, use PT100 channel 1 on

the PTC/PT100 option board.

NOTE: If Speed, Torque or Frequency is chosen in menu

[321] Proc Source, menus [322] - [328] are hidden.

NOTE: The motor control method depends on the

selection of drive mode [213], regardless of selected

process source, [321].

NOTE: If F (Bus) is chosen in menu [321]see section

10.5.1 Process value.

321 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

322 Proc Unit. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

Shared source cells (coordinates refer to this table):

321 Proc Source. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

322 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

321 communication — PDF page 94

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43302
2 Profibus slot/index 169/206
3 Fieldbus format UInt
4 Modbus format UInt

322 Proc Unit — PDF page 94

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ rpm
2 Off 0 No unit selection
3 % 1 Percent
4 °C 2 Degrees Centigrade
5 °F 3 Degrees Fahrenheit
6 bar 4 bar
7 Pa 5 Pascal
8 Nm 6 Torque
9 Hz 7 Frequency
10 rpm 8 Revolutions per minute
11 m3/h 9 Cubic meters per hour
12 gal/h 10 Gallons per hour
13 ft3/h 11 Cubic feet per hour
14 User 12 User defined unit

321 Proc Source — PDF page 94

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Speed
2 F(AnIn) 0 Function of analogue input. E.g. via PID control, [330].
3 Speed 1 Speed as process reference1.
4 PT100 3 Temperature as process reference.
5 F(Speed) 4 Function of speed
6 F(Bus) 6 Function of communication reference
7 Frequency 7 Frequency as process reference1.

322 communication — PDF page 94

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43303
2 Profibus slot/index 169/207
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Process reference, units and scaling. Collected P034 association; no extrapolation to other variants. — page 95

Manual reference: physical PDF page 95. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

User-defined Unit [323]

This menu is only displayed if User is selected in menu

[322]. The function enables the user to define a unit

with six symbols. Use the Prev and Next key to move the

cursor to required position. Then use the + and - keys to

scroll down the character list. Confirm the character by

moving the cursor to the next position by pressing the

Next key.

Example:

Create a user unit named kPa.

  1. When in the menu [323] press Next to move the cur-

sor to the right most position.

  1. Press the + key until the character k is displayed.

  2. Press Next.

  3. Then press the + key until P is displayed and con-

firm with Next.

  1. Repeat until you have entered kPa.

Communication information

When sending a unit name you send one character at a

time starting at the right most position.

Character table physicalpairs continue fromlefttableSpace0 throughé47 andm58 through<96 to righttableê48 throughl57 and=97 throughsuperscript³105. Rightlastrow pairedrightcharacter/code cells are printedempty; do not infer106. Superscript²=104,³=105.

323 User Unit character-code table continuation. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

323 User Unit character-code table. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

323 User Unit. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

323 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

323 User Unit character-code table continuation — PDF page 95

Source row Character No. for serial comm. Character No. for serial comm.
1 ê 48 = 97
2 ë 49 > 98
3 f 50 ? 99
4 g 51 @ 100
5 h 52 ^ 101
6 i 53 _ 102
7 í 54 ° 103
8 j 55 2 104
9 k 56 3 105
10 l 57 ⟦blank source cell⟧ ⟦blank source cell⟧

323 User Unit character-code table — PDF page 95

Source row Character No. for serial comm. Character No. for serial comm.
1 Space 0 m 58
2 0–9 1–10 n 59
3 A 11 ñ 60
4 B 12 o 61
5 C 13 ó 62
6 D 14 ô 63
7 E 15 p 64
8 F 16 q 65
9 G 17 r 66
10 H 18 s 67
11 I 19 t 68
12 J 20 u 69
13 K 21 ü 70
14 L 22 v 71
15 M 23 w 72
16 N 24 x 73
17 O 25 y 74
18 P 26 z 75
19 Q 27 å 76
20 R 28 ä 77
21 S 29 ö 78
22 T 30 ! 79
23 U 31 ¨ 80
24 Ü 32 # 81
25 V 33 $ 82
26 W 34 % 83
27 X 35 & 84
28 Y 36 · 85
29 Z 37 ( 86
30 Å 38 ) 87
31 Ä 39 * 88
32 Ö 40 + 89
33 a 41 , 90
34 á 42 - 91
35 b 43 . 92
36 c 44 / 93
37 d 45 : 94
38 e 46 ; 95
39 é 47 < 96

323 User Unit — PDF page 95

Source row Property Value
1 Default: No characters shown

323 communication — PDF page 95

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43304 43305 43306 43307 43308 43309
2 Profibus slot/index 169/208 169/209 169/210 169/211 169/212 169/213
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Process reference, units and scaling. Collected P034 association; no extrapolation to other variants. — page 96

Manual reference: physical PDF page 96. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Process Min [324]

This function sets the minimum process value allowed.

Communication information

Process Max [325]

This menu is not visible when speed, torque or fre-

quency is selected. The function sets the value of the

maximum process value allowed.

Ratio [326]

This menu is not visible when speed, frequency or

torque is selected. The function sets the ratio between

the actual process value and the motor speed so that it

has an accurate process value when no feedback sig-

nal is used. See Fig. 75.

Fig. 75 Ratio

F(Value), Process Min [327]

This function is used for scaling if no sensor is used. It

offers you the possibility of increasing the process

accuracy by scaling the process values. The process

values are scaled by linking them to known data in the

AC drive. With F(Value), Proc Min [327] the precise

value at which the entered

Process Min [324] is valid can be entered.

NOTE: If Speed, Torque or Frequency is chosen in menu

[321] Proc Source, menus [322]- [328] are hidden.

Ratio=Linear

Ratio=Quadratic

Process

Min

Max

unit

[325]

[324]

Speed

[341]

[343]

Figure75 processunit verticalProcessMin324/ProcessMax325 and speedhorizontalMin341/Max343; LinearstraightandQuadraticcurved lines share endpoints; no new intermediatevalues.

326 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

324 Process Min. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

324 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

325 Process Max. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

325 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

327 F(Val) PrMin. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

Shared source cells (coordinates refer to this table):

326 Ratio. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

327 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

326 communication — PDF page 96

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43312
2 Profibus slot/index 169/216
3 Fieldbus format UInt
4 Modbus format UInt

324 Process Min — PDF page 96

Source row Property Value
1 Default: 0
2 Range: 0.000-10000 (Speed, Torque, F(Speed), F(Torque)) -10000– +10000 (F(AnIn, PT100, F(Bus))

324 communication — PDF page 96

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43310
2 Profibus slot/index 169/214
3 Fieldbus format Long, 1=0.001
4 Modbus format EInt

325 Process Max — PDF page 96

Source row Property Value
1 Default: 0
2 Range: 0.000-10000

325 communication — PDF page 96

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43311
2 Profibus slot/index 169/215
3 Fieldbus format Long, 1=0.001
4 Modbus format EInt

327 F(Val) PrMin — PDF page 96

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Min
2 Min -1 According to Min Speed setting in [341].
3 Max -2 According to Max Speed setting in [343].
4 0.000-10000 0-10000 0.000-10000

326 Ratio — PDF page 96

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Linear
2 Linear 0 Process is linear related to speed/torque
3 Quadratic 1 Process is quadratic related to speed/ torque

327 communication — PDF page 96

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43313
2 Profibus slot/index 169/217
3 Fieldbus format Long, 1=1 rpm
4 Modbus format EInt

Manual — Process reference, units and scaling. Collected P034 association; no extrapolation to other variants. — page 97

Manual reference: physical PDF page 97. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

F(Value), Process Max [328]

This function is used for scaling if no sensor is used. It

offers you the possibility of increasing the process

accuracy by scaling the process values. The process

values are scaled by linking them to known data in the

AC drive. With F(Value), Proc Max the precise value at

which the entered Process Max [525] is valid can be

entered.

Communication information

Example

A conveyor belt is used to transport bottles. The

required bottle speed needs to be within 10 to 100 bot-

tles/s. Process characteristics:

10 bottles/s = 150 rpm

100 bottles/s = 1500 rpm

The amount of bottles is linearly related to the speed of

the conveyor belt.

Set-up:

Process Min [324] = 10

Process Max [325] = 100

Ratio [326] = linear

F(Value), ProcMin [327] = 150

F(Value), ProcMax [328] = 1500

With this set-up, the process data is scaled and linked

to known values which results in an accurate control.

Fig. 76

11.3.3 Start/Stop settings [330]

Submenu with all the functions for acceleration,

deceleration, starting, stopping, etc.

Acceleration Time [331]

The acceleration time is defined as the time it takes for

the motor to accelerate from 0 rpm to nominal motor

speed.

Fig. 77 shows the relationship between nominal motor

speed/max speed and the acceleration time. The same

is valid for the deceleration time.

NOTE: If Speed, Torque or Frequency is chosen in menu

[321] Proc Source, menus [322]- [328] are hidden.

NOTE: If the Acc Time is too short, the motor is

accelerated according to the Torque Limit. The actual

Acceleration Time may then be longer than the value

set.

F(Value)

PrMax

[328]

F(Value

PrMin

[327]

Process Min [324]

Process Max [325]

Linear

Bottles/s

Figure76 illustrative bottleconversion: horizontalBottles/s10ProcessMin324 to100ProcessMax325; vertical150FValueProcMin327 to1500FValueProcMax328;Linear.

328 F(Val) PrMax. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

Shared source cells (coordinates refer to this table):

328 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

331 Acc Time. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

331 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Process source selection governs menu visibility, units and scaling. Source omissions and numbering conflicts remain unresolved.

328 F(Val) PrMax — PDF page 97

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Max
2 Min -1 Min
3 Max -2 Max
4 0.000- 10000 0-10000 0.000-10000

328 communication — PDF page 97

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43314
2 Profibus slot/index 169/218
3 Fieldbus format Long, 1=1 rpm
4 Modbus format EInt

331 Acc Time — PDF page 97

Source row Property Value
1 Default: 10.0 s
2 Range: 0.50–3600 s

331 communication — PDF page 97

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43101
2 Profibus slot/index 169/5
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

Manual — Acceleration, braking, speed and torque. Collected P034 association; no extrapolation to other variants. — page 98

Manual reference: physical PDF page 98. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 77 Acceleration time and maximum speed

Fig. 78 shows the settings of the acceleration and

deceleration times with respect to the nominal motor

speed.

Fig. 78 Acceleration and deceleration times

Deceleration Time [332]

The deceleration time is defined as the time it takes for

the motor to decelerate from nominal motor speed to 0

rpm.

Communication information

Acceleration Time Motor Potentiometer

[333]

It is possible to control the speed of the AC drive using

the motor potentiometer function. This function con-

trols the speed with separate up and down commands,

over remote signals. The MotPot function has separate

ramps settings which can be set in Acc MotPot [333]

and Dec MotPot [334].

If the MotPot function is selected, this is the accelera-

tion time for the MotPot up command. The acceleration

time is defined as the time it takes for the motor poten-

tiometer value to increase from 0 rpm to nominal

Deceleration Time Motor Potentiometer

[334]

If the MotPot function is selected, this is the decelera-

tion time for the MotPot down command. The decelera-

tion time is defined as the time it takes for the motor

potentiometer value to decrease from nominal speed to

0 rpm.

Nominal

Speed

Max Speed

rpm

t

10s

8s

(06-F12)

100% nMOT

80% nMOT

(NG_06-F11)

Nom. Speed

Acc Time [331]

Dec Time [332]

NOTE: If the Dec Time is too short and the generator

energy cannot be dissipated in a brake resistor, the

motor is decelerated according to the overvoltage limit.

The actual deceleration time may be longer than the

value set.

Figure77 accelerationexample nominal100% nMOTat10s andmaximum80% nMOTat8s. Figure78 speedvs time labelsNom.Speed,AccTime331,DecTime332; no numericalplateauduration.

333 Acc MotPot. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

333 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

332 Dec Time. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

334 Dec MotPot. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

332 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

334 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

333 Acc MotPot — PDF page 98

Source row Property Value
1 Default: 16.0 s
2 Range: 0.50–3600 s

333 communication — PDF page 98

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43103
2 Profibus slot/index 169/7
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

332 Dec Time — PDF page 98

Source row Property Value
1 Default: 10.0 s
2 Range: 0.50–3600 s

332 communication — PDF page 98

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43102
2 Profibus slot/index 169/6
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

334 communication — PDF page 98

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43104
2 Profibus slot/index 169/8
3 Fieldbus format Long, 1=0.01
4 Modbus format EInt

Manual — Acceleration, braking, speed and torque. Collected P034 association; no extrapolation to other variants. — page 99

Manual reference: physical PDF page 99. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Acceleration Time to Minimum Speed

[335]

If minimum speed, [341]>0 rpm, is used in an applica-

tion, the AC drive uses separate ramp times below this

level. With Acc>MinSpeed [335] and Dec<MinSpeed

[336] you can set the required ramp times. Short times

can be used to prevent damage and excessive pump

wear due too little lubrication at lower speeds. Longer

times can be used to fill up a system smoothly and pre-

vent water hammer due to rapidly exhausting air from

the pipe system.

If a Minimum speed is programmed, this parameter will

be used to set the acceleration time to the minimum

speed at a run command. The ramp time is defined as

the time it takes for the motor to accelerate from 0 rpm

to nominal motor speed.

Communication information

Fig. 79

Deceleration Time from Minimum

Speed [336]

If a minimum speed is programmed, this parameter will

be used to set the deceleration time from the minimum

speed to 0 rpm at a stop command. The ramp time is

defined as the time it takes for the motor to decelerate

from the nominal motor speed to 0 rpm.

Acceleration Ramp Type [337]

Sets the type of all the acceleration ramps in a parame-

ter set. See Fig. 80. Depending on the acceleration and

deceleration requirements for the application, the

shape of both the ramps can be selected. For applica-

tions where speed changes need to be started and

stopped smoothly, such as a conveyor belt with materi-

als that can drop following a quick speed change, the

ramp shape can be adapted to a S-shape and

prevent speed change shocks. For applications that are

not critical in this, the speed change can be fully linear

over the complete range.

time

rpm

Nom.Speed

Max speed

Min speed

[331]

[332]

[336]

[341]

[343]

[225]

NOTE: For S-curve ramps the ramp times, [331] and

[332], defines the maximum acceleration and

deceleration rated, i.e. linear part of S-curve, just as for

the linear ramps. The S-curves are implemented so that

for a speed step below sync speed the ramps are fully

S-shaped while for larger steps the middle part will be

linear. Therefore will a S-curve ramp from 0 –sync speed

take 2 x Time while a step from 0–2 x sync speed will

take 3 x Time (middle part 0.5sync speed – 1.5sync

speed linear). Also valid for menu [337], D.eceleration

ramp type.

Figure79 verticalrpmlevelsNom.Speed225,MaxSpeed343,MinSpeed341; ascendinglower335/upper331 anddescendingupper332/lower336.337S-curvetime qualifiers retained inadjacent sourceprose.

336 Dec<Min Spd. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

336 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

335 Acc>Min Spd. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

335 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

337 Acc Rmp. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

Shared source cells (coordinates refer to this table):

336 Dec<Min Spd — PDF page 99

Source row Property Value
1 Default: 10.0 s
2 Range: 0.50-3600 s

336 communication — PDF page 99

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43106
2 Profibus slot/index 169/10
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

335 communication — PDF page 99

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43105
2 Profibus slot/index 169/9
3 Fieldbus format Long, 1=0.01
4 Modbus format EInt

337 Acc Rmp — PDF page 99

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Linear
2 Linear 0 Linear acceleration ramp.
3 S-Curve 1 S-shape acceleration ramp.

Manual — Acceleration, braking, speed and torque. Collected P034 association; no extrapolation to other variants. — page 100

Manual reference: physical PDF page 100. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Communication information

Fig. 80 Shape of acceleration ramp

Deceleration Ramp Type [338]

Sets the ramp type of all deceleration parameters in a

parameter set Fig. 81.

Fig. 81 Shape of deceleration ramp

Start Mode [339]

Sets the way of starting the motor when a run com-

mand is given.

Spinstart [33A]

The spinstart will smoothly start a motor which is

already rotating by catching the motor at the actual

speed and control it to the desired speed. If in an appli-

cation, such as an exhausting fan, the motor shaft is

already rotating due to external conditions, a smooth

start of the application is required to prevent excessive

wear. With the spinstart=on, the actual control of the

motor is delayed due to detecting the actual speed and

rotation direction, which depend on motor size, running

conditions of the motor before the Spinstart, inertia of

the application, etc. Depending on the motor electrical

time constant and the size of the motor, it can take

maximum a couple of minutes before the motor is

caught.

rpm

t

Linear

S-curve

Figure80 acceleration andFigure81 deceleration showLinear/S-curve onrpm/time axes; no numericalpoints.339LCDhasliteralast whileDefaultFastfixed isreadable.

337 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

339 Start Mode. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

Shared source cells (coordinates refer to this table):

339 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

338 Dec Rmp. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33A Spinstart. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

338 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

Adjacent source context — repeated to preserve continuation:

337 communication — PDF page 100

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43107
2 Profibus slot/index 169/11
3 Fieldbus format UInt
4 Modbus format UInt

339 Start Mode — PDF page 100

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Fast (fixed)
2 Fast 0 The motor flux increases gradually. The motor shaft starts rotating immediately once the Run command is given.

339 communication — PDF page 100

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43109
2 Profibus slot/index 169/13
3 Fieldbus format UInt
4 Modbus format UInt

338 Dec Rmp — PDF page 100

Source row Property Value
1 Default: Linear
2 Selection: Same as menu [337]

33A Spinstart — PDF page 100

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 No spinstart. If the motor is already running the AC drive can trip or will start with high current.
3 On 1 Spinstart will allow the start of a running motor without tripping or high inrush currents.

338 communication — PDF page 100

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43108
2 Profibus slot/index 169/12
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Acceleration, braking, speed and torque. Collected P034 association; no extrapolation to other variants. — page 101

Manual reference: physical PDF page 101. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Communication information

Stop Mode [33B]

When the AC drive is stopped, different methods to

come to a standstill can be selected in order to opti-

mize the stop and prevent unnecessary wear, like water

hammer. Stop Mode sets the way of stopping the motor

when a Stop command is given.

11.3.4 Mechanical brake control

The four brake-related menus [33C] to [33F] can be

used to control mechanical brakes.

Support is included for a Brake Acknowledge signal via

a digital input. It is monitored using a brake fault time

parameter. Additional output and trip/warning signals

are also included. The acknowledge signal is either con-

nected from the brake contactor or from a proximity

switch on the brake.

The brake acknowledge signal can also be used to

improve safety by preventing hoist falling load in case

the brake is not engaged when stopping.

Brake not released - Brake Fault trip

During start and running the brake acknowledge signal

is compared to the actual brake output signal and if no

acknowledge, i.e. brake not released, while brake out-

put is high for the Brake Fault time [33H], then a Brake

trip is generated.

Brake not engaged - Brake Warning and

continued operation (keep torque)

The brake acknowledge signal is compared to the

actual brake output signal at stop. If acknowledge is

still active, i.e. brake not engaged, while brake output is

low for the Brake Engage time [33E] then a Brake warn-

ing is generated and the torque is kept, i.e. prolonging

normal brake engage mode, until brake closes or an

emergency action is needed by the operator, such as

setting down the load.

Brake Release Time [33C]

The Brake Release Time sets the time the AC drive

delays before ramping up to whatever final reference

value is selected. During this time a predefined speed

can be generated to hold the load where after the

mechanical brake finally releases. This speed can be

selected at Release Speed, [33D]. Immediate after the

brake release time expiration the brake lift signal is set.

The user can set a digital output or relay to the function

Brake. This output or relay can control the mechanical

brake.

Fig. 82 shows the relation between the four Brake func-

tions.

• Brake Release Time [33C]

• Start Speed [33D]

• Brake Engage Time [33E]

• Brake Wait Time [33F]

The correct time setting depends on the maximum load

and the properties of the mechanical brake. During the

brake release time it is possible to apply extra holding

torque by setting a start speed reference with the func-

tion start speed [33D]

33A communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33B Stop Mode. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

Shared source cells (coordinates refer to this table):

33C Brk Release. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33B communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33C communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

Adjacent source context — repeated to preserve continuation:

33A communication — PDF page 101

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43110
2 Profibus slot/index 169/14
3 Fieldbus format UInt
4 Modbus format UInt

33B Stop Mode — PDF page 101

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Decel
2 Decel 0 The motor decelerates to 0 rpm according to the set deceleration time.
3 Coast 1 The motor freewheels naturally to 0 rpm.

33C Brk Release — PDF page 101

Source row Property Value
1 Default: 0.00 s
2 Range: 0.00–3.00 s

33B communication — PDF page 101

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43111
2 Profibus slot/index 169/15
3 Fieldbus format UInt
4 Modbus format UInt

33C communication — PDF page 101

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43112
2 Profibus slot/index 169/16
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

Manual — Acceleration, braking, speed and torque. Collected P034 association; no extrapolation to other variants. — page 102

Manual reference: physical PDF page 102. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

.

Fig. 82 Brake Output functions

Release Speed [33D]

The release speed only operates with the brake func-

tion: brake release [33C]. The release speed is the ini-

tial speed reference during the brake release time.

Communication information

Brake Engage Time [33E]

The brake engage time is the time the load is held to

engage a mechanical brake.

NOTE: This function is designed to operate a mechanical

brake via the digital outputs or relays (set to brake

function) controlling a mechanical brake.

Mechanical

Brake

Brake Relay

Output

Action must take place within

Brake release

time [33C]

Brake engage

time [33E]

Brake wait

time [33F]

Closed

On

Off

Open

Start

hse time intervals

Figure82 labelsStart,ReleaseSpeed33D,BrakeReleaseTime33C,BrakeWaitTime33F,BrakeEngageTime33E,MechanicalBrakeOpen/Closed,BrakeRelayOutputOn/Off; arrows identifyactionintervals without numericdurations. Originalplotrequired for waveforms.

33E Brk Engage. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33D Release Spd. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33E communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33D communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33E Brk Engage — PDF page 102

Source row Property Value
1 Default: 0.00 s
2 Range: 0.00–3.00 s

33D Release Spd — PDF page 102

Source row Property Value
1 Default: 0 rpm
2 Range: - 4x Sync. Speed to 4x Sync.
3 Depend on: 4xmotor sync speed, 1500 rpm for 1470 rpm motor.

33E communication — PDF page 102

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43114
2 Profibus slot/index 169/18
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

33D communication — PDF page 102

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43113
2 Profibus slot/index 169/17
3 Fieldbus format Int, 1=1 rpm
4 Modbus format Int, 1=1 rpm

Manual — Acceleration, braking, speed and torque. Collected P034 association; no extrapolation to other variants. — page 103

Manual reference: physical PDF page 103. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Wait Before Brake Time [33F]

The brake wait time is the time to keep brake open and

to hold the load, either in order to be able to speed up

immediately, or to stop and engage the brake.

Communication information

Vector Brake [33G]

Braking by increasing the internal electrical losses in

the motor.

Brake Fault trip time [33H]

The “Brake Fault trip time” for “Brake not released”

function is specified in this menu.

The “Brake not engaged” warning is using the setting of

parameter “Brake Engaged time [33E]”.

Following Figure shows principle of brake operation for

fault during run (left) and during stop (right).

Release torque [33I]

The Brake Release Time [33C] sets the time the VSD

delays before ramping up to whatever final speed refer-

ence value is selected, to allow the brake to be fully

opened. During this time a holding torque to prevent

roll-back of the load can be activated. The parameter

Release Torque [33I] is used for this purpose.

The release torque initiates the torque reference from

the speed controller during the Brake Release Time

[33C]. The release torque defines a minimum level of

release (holding) torque. The set release torque is inter-

nally overruled if the actual required holding torque

measured at the previous closing of brake is higher.

The release torque is set with sign in order to define the

holding torque direction.

Note: The Brake Fault trip time should be set to longer

time than the Brake release time[33C].

Note! Function is deactivated if set to 0%.

Note! Release Torque [33I] has priority over torque

reference initialization by Release Speed [33D].

33H communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33F Brk Wait. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33F communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33G Vector Brake. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

Shared source cells (coordinates refer to this table):

33I Release Trq. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33G communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33I communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33H Brk Fault. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

33H communication — PDF page 103

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43117
2 Profibus slot/index 169/21
3 Fieldbus format Long, 1=0.1s
4 Modbus format EInt

33F Brk Wait — PDF page 103

Source row Property Value
1 Default: 0.00 s
2 Range: 0.00–30.0 s

33F communication — PDF page 103

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43115
2 Profibus slot/index 169/19
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

33G Vector Brake — PDF page 103

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Vector brake switched off. AC drive brakes normal with voltage limit on the DC link.
3 On 1 Maximum AC drive current (I ) is available CL for braking.

33I Release Trq — PDF page 103

Source row Selection/property Enumeration or merged span Description/value
1 Default: 0% ⟦null: no independent source value⟧
2 Range -400% to 400% ⟦null: no independent source value⟧

33G communication — PDF page 103

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43116
2 Profibus slot/index 169/20
3 Fieldbus format UInt
4 Modbus format UInt

33I communication — PDF page 103

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43118
2 Profibus slot/index 169/22
3 Fieldbus format Long, 1=1H%
4 Modbus format EInt

33H Brk Fault — PDF page 103

Source row Property Value
1 Default: 1.00s
2 Range 0.00 - 5.00s

Manual — Acceleration, braking, speed and torque. Collected P034 association; no extrapolation to other variants. — page 104

Manual reference: physical PDF page 104. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 83 Principle of Brake operation for fault during run and during stop

11.3.5 Speed [340]

Menu with all parameters for settings regarding to

speeds, such as Min/Max speeds, Jog speeds, Skip

speeds.

Minimum Speed [341]

Sets the minimum speed. The minimum speed will

operate as an absolute lower limit. Used to ensure the

motor does not run below a certain speed and to main-

tain a certain performance.

Communication information

Stop/Sleep when less than Minimum

Speed [342]

With this function it is possible to put the AC drive in

“sleep mode” when it is running at minimum speed for

the length of time set, due to process value feedback or

a reference value that corresponds to a speed lower

than the min speed set. The AC drive will go into sleep

mode after programmed time. When the reference sig-

nal or process value feedback raises the required

speed value above the min speed value, the AC drive

will automatically wake up and ramp up to the required

speed.

Brake warning

Brake Trip

Brake acknowledge

Brake relay

Speed>0

Torque

Running

Start

During run

During stop

Brake

<33H

33H

Brake wait

time

Brake engage

33F

33E

33C

release time

Brake Fault trip time

*

**

** Time for operator to set down the load.

NOTE: A lower speed value than the set minimum speed

can be shown in the display due to motor slip.

NOTE: Menu [386] has higher priority than menu [342].

Figure83 duringrun/duringstop tracksStart,Running,Torque,Speed>0,BrakeRelay,BrakeAcknowledge,BrakeTrip,BrakeWarning.33Crelease,33Fwait,33Eengage;33Hfaulttrip and<33H markers. memorizedloadtorque if33Iactive; *operator time tosetdownload.

341 Min Speed. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

342 Stp<MinSpd. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

Shared source cells (coordinates refer to this table):

341 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

342 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

341 Min Speed — PDF page 104

Source row Property Value
1 Default: 0 rpm
2 Range: 0 - Max Speed
3 Dependent on: Set/View ref [310]

342 Stp<MinSpd — PDF page 104

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off
3 1–3600 1–3600 1–3600 s

341 communication — PDF page 104

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43121
2 Profibus slot/index 169/25
3 Fieldbus format Int, 1=1 rpm
4 Modbus format Int, 1=1 rpm

342 communication — PDF page 104

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43122
2 Profibus slot/index 169/26
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

Manual — Acceleration, braking, speed and torque. Collected P034 association; no extrapolation to other variants. — page 105

Manual reference: physical PDF page 105. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 84

Maximum Speed [343]

Sets the maximum speed. The maximum speed will

operate as an absolute maximum limit. This parameter

is used to prevent damage due to high speed.

The synchronous speed (Sync-spd) is determined by the

parameter motor speed [225]..

Communication information

Skip Speed 1 Low [344]

Within the Skip Speed range High to Low, the speed

cannot be constant in order to avoid mechanical reso-

nance in the AC drive system.

When Skip Speed Low £ Ref Speed £ Skip Speed High,

then Output Speed=Skip Speed HI during deceleration

and Output Speed=Skip Speed LO during acceleration.

Fig. 85 shows the function of skip speed hi and low.

Between Skip Speed HI and LO, the speed changes

with the set acceleration and deceleration times.

Skipspd1 LO sets the lower value for the 1st skip range.

Fig. 85 Skip Speed

NOTE: It is not possible to set the maximum speed lower

than the minimum speed.

Note: Maximum speed [343] has priority over Min Speed

[341], i.e. if [343] is set below [341] then the drive will

run at [343] Max Speed with acceleration times given by

[335] and [336] respectively.

PID ref

Min

PID out

PID fb

[342]

speed

NOTE: The two Skip Speed ranges may be overlapped.

(NG_06-F17)

n

Skip Speed HI

Skip Speed LO

Speed Reference

Figure84 PIDref/PIDfb/PIDout andMinspeed,bracket342 sleeptime;Figure85SkipSpeedHI/LO againstSpeedReference showsdifferentup/down paths. No interpolatedspeeds.

344 SkipSpd 1 Lo. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

343 Max Speed. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

344 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

343 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

344 SkipSpd 1 Lo — PDF page 105

Source row Property Value
1 Default: 0 rpm
2 Range: 0 - 4 x Motor Sync Speed

343 Max Speed — PDF page 105

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ Sync Speed
2 Sync Speed 0 Synchronous speed, i.e. no load speed, at nominal frequency.
3 1-24000rpm 1- 24000 Min Speed - 4 x Motor Sync Speed

344 communication — PDF page 105

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43124
2 Profibus slot/index 169/28
3 Fieldbus format Int
4 Modbus format Int

343 communication — PDF page 105

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43123
2 Profibus slot/index 169/27
3 Fieldbus format Int, 1=1 rpm
4 Modbus format UInt

Manual — Acceleration, braking, speed and torque. Collected P034 association; no extrapolation to other variants. — page 106

Manual reference: physical PDF page 106. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Skip Speed 1 High [345]

Skipspd1 HI sets the higher value for the 1st skip

range.

Communication information

Skip Speed 2 Low [346]

The same function as menu [344] for the 2nd skip

Skip Speed 2 High [347]

The same function as menu [345] for the 2nd skip

Jog Speed [348]

The Jog Speed function is activated by one of the digital

inputs. The digital input must be set to the Jog function

[520]. The Jog command/function will automatically

generate a run command as long as the Jog command/

function is active. The rotation is determined by the

polarity of the set Jog Speed.

Example

If Jog Speed = -10, this will give a Run Left command at

10 rpm regardless of RunL or RunR commands. Fig. 86

shows the function of the Jog command/function.

Fig. 86 Jog command

t

f

(NG_06-F18)

Jog

Freq

com-

mand

Figure86 JogFreq andJogcommand alignedontimeaxes; no numericalspeed/durationlabels.

345 SkipSpd 1 Hi. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

345 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

348 Jog Speed. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

346 SkipSpd 2 Lo. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

348 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

346 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

347 SkipSpd 2 Hi. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

347 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

345 SkipSpd 1 Hi — PDF page 106

Source row Property Value
1 Default: 0 rpm
2 Range: 0 – 4 x Sync Speed

345 communication — PDF page 106

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43125
2 Profibus slot/index 169/29
3 Fieldbus format Int
4 Modbus format Int

348 Jog Speed — PDF page 106

Source row Property Value
1 Default: 50 rpm
2 Range: -4 x motor sync speed to +4 x motor sync speed
3 Dependent on: Defined motor sync speed. Max = 400%, nor- mally max=AC drive I /motor I x 100%. max nom

346 SkipSpd 2 Lo — PDF page 106

Source row Property Value
1 Default: 0 rpm
2 Range: 0 – 4 x Motor Sync Speed

348 communication — PDF page 106

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43128
2 Profibus slot/index 169/32
3 Fieldbus format Int
4 Modbus format Int

346 communication — PDF page 106

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43126
2 Profibus slot/index 169/30
3 Fieldbus format Int, 1=1 rpm
4 Modbus format Int, 1=1 rpm

347 communication — PDF page 106

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43127
2 Profibus slot/index 169/31
3 Fieldbus format Int, 1=1 rpm
4 Modbus format Int, 1=1 rpm

Manual — Acceleration, braking, speed and torque. Collected P034 association; no extrapolation to other variants. — page 107

Manual reference: physical PDF page 107. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.3.6 Torques [350]

Menu with all parameters for torque settings.

Maximum Torque [351]

Sets the maximum torque. This Maximum Torque oper-

ates as an upper torque limit. A Speed Reference is

always necessary to run the motor.

Communication information

IxR Compensation [352]

This function compensates for the drop in voltage over

different resistances such as (very) long motor cables,

chokes and motor stator by increasing the output volt-

age at a constant frequency. IxR Compensation is most

important at low frequencies and is used to obtain a

higher starting torque. The maximum voltage increase

is 25% of the nominal output voltage. See Fig. 87.

Selecting “Automatic” will use the optimal value accord-

ing to the internal model of motor. “User-Defined” can

be selected when the start conditions of the application

do not change and a high starting torque is always

required. A fixed IxR Compensation value can be set in

the menu [353].

Fig. 87 IxR Comp at Linear V/Hz curve

IxR Comp_user [353]

Only visible if User-Defined is selected in previous

menu.

NOTE: The Max Torque parameter will limit the maxmum

output current of the AC drive following the relation:

100% Tmot corresponds to 100% Imot.

The maximum possible setting for parameter 351 is

limited by Inom/Imot x 120%, but not higher than 400%.

NOTE: The power loss in the motor will increase by the

square of the torque when operating above 100%. 400%

torque will result in 1600% power loss, which will

increase the motor temperature very quickly.

TMOT Nm

(

)

PMOT kw

)x9550

nMOT rpm


=

NOTE: A too high level of IxR Compensation could cause

motor saturation. This can cause a “Power Fault” trip.

The effect of IxR Compensation is stronger with higher

power motors.

50 Hz

f

%

U

IxR Comp=25%

IxR Com=0%

Torque formulaT_MOT(Nm)=P_MOT(kW)×9550/n_MOT(rpm), transcribed fromprinted fraction. Figure87 U%vs fHz labels100/25 and10,20,30,40,50; curvesIxRComp25%/IxRCom0%,illustrative.

352 IxR Comp. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

352 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

351 Max Torque. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

351 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

353 IxR CompUsr. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

353 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

352 IxR Comp — PDF page 107

Source row Selection/property and printed enumeration Description/value
1 Default: Off
2 Off 0 Function disabled
3 Automatic 1 Automatic compensation
4 User Defined 2 User defined value in percent.

352 communication — PDF page 107

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43142
2 Profibus slot/index 169/46
3 Fieldbus format UInt
4 Modbus format UInt

351 Max Torque — PDF page 107

Source row Property Value
1 Default: 120% calculated from the motor data
2 Range: 0–400%

351 communication — PDF page 107

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43141
2 Profibus slot/index 169/45
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

353 IxR CompUsr — PDF page 107

Source row Property Value
1 Default: 0.0%
2 Range: 0-25% x UNOM (0.1% of resolution)

353 communication — PDF page 107

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43143
2 Profibus slot/index 169/47
3 Fieldbus format Long
4 Modbus format EInt

Manual — Acceleration, braking, speed and torque. Collected P034 association; no extrapolation to other variants. — page 108

Manual reference: physical PDF page 108. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Flux Optimization [354]

Flux Optimization reduces the energy consumption and

the motor noise, at low or no load conditions.

Flux Optimization automatically decreases the V/Hz

ratio, depending on the actual load of the motor when

the process is in a steady situation. Fig. 88 shows the

area within which the Flux Optimization is active.

Communication information

Fig. 88 Flux Optimizing

Maximum power [355]

Sets maximum power. Can be used for limiting motor

power in field weakening operation. This function oper-

ates as an upper power limit and internally limits the

parameter Max Torque [351] according to :

Tlimit = Plimit[%] / (Actual Speed / Sync Speed)

NOTE: The motor may be overheated at low speed.

Therefore it is important that the Motor I2t Current [232]

is set correctly.

NOTE: Flux optimization works best at stable situations

in slow changing processes.

50 Hz

f

%

U

Flux optimizing

area

NOTE: The maximum possible setting for parameter 355

is limited by INOM/IMOT x 120%, but not higher than

400%.

Figure88 U%vertical100 andfrequencyhorizontal50Hz; shadedFluxoptimizingarea. No lowercurve numericpoints inferred.

355 Max Power. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

Shared source cells (coordinates refer to this table):

354 Flux optim. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

355 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

354 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Motor nominal/synchronous speed, selected control mode and mechanical-brake setup govern applicability; parameter claims are not validated installation advice.

355 Max Power — PDF page 108

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off. No power limit
3 1 - 400 1 - 400 1 - 400% of motor nominal power

354 Flux optim — PDF page 108

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Function disabled
3 On 1 Function enabled

355 communication — PDF page 108

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43145
2 Profibus slot/index 169/49
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

354 communication — PDF page 108

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43144
2 Profibus slot/index 169/48
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Preset references andPIDcontrol. Collected P034 association; no extrapolation to other variants. — page 109

Manual reference: physical PDF page 109. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.3.7 Preset References [360]

Motor Potentiometer [361]

Sets the properties of the motor potentiometer func-

tion. See the parameter DigIn1 [521] for the selection

of the motor potentiometer function.

Communication information

Fig. 89 MotPot function

Preset Ref 1 [362] to Preset Ref 7

[368]

Preset speeds have priority over the analogue inputs.

Preset speeds are activated by the digital inputs. The

digital inputs must be set to the function Pres. Ref 1,

Pres. Ref 2 or Pres. Ref 4.

Depending on the number of digital inputs used, up to

7 preset speeds can be activated per parameter set.

Using all the parameter sets, up to 28 preset speeds

are possible.

The same settings are valid for the menus:

[363] Preset Ref 2, with default 250 rpm

[364] Preset Ref 3, with default 500 rpm

[365] Preset Ref 4, with default 750 rpm

[366] Preset Ref 5, with default 1000 rpm

[367] Preset Ref 6, with default 1250 rpm

[368] Preset Ref 7, with default 1500 rpm

The selection of the presets is as in Table 24.

1)= selected if only one preset reference is active

1 = active input

0 = non active input

t

n

Motpot

UP

DOWN

Table 24

NOTE: If only Preset Ctrl3 is active, then the Preset Ref 4

can be selected. If Presets Ctrl2 and 3 are active, then

the Preset Ref 2, 4 and 6 can be selected.

Table24 ordered bit columns Ctrl3, Ctrl2, Ctrl1:000 Analogreference;001 Preset1;010 Preset2;011 Preset3;100 Preset4;101 Preset5;110 Preset6;111 Preset7. Footnote1 singleselectedinput activatesPreset1,2or4. No new bit combinations inferred. Figure89 shows speed n againsttime t, linked MotpotUP andMotpotDOWN pulses with aligned verticalguides; no numeric speed/time values.

362 Preset Ref 1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

361 Motor Pot. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

Shared source cells (coordinates refer to this table):

362–368 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

361 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

Table24 presetcontrol bit selection. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

362 Preset Ref 1 — PDF page 109

Source row Property Value
1 Default: Speed, 0 rpm
2 Dependent on: Process Source [321] and Process Unit [322]
3 Speed mode 0 - max speed [343]
4 Torque mode 0 - max torque [351]
5 Other modes Min according to menu [324] - max according to menu [325]

361 Motor Pot — PDF page 109

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Non Volatile
2 Volatile 0 After a stop, trip or power down, the AC drive will start always from zero speed (or minimum speed, if selected).
3 Non volatile 1 Non Volatile. After a stop, trip or power down of the AC drive, the reference value at the moment of the stop will be memorized. After a new start command the output speed will resume to this saved value.

362–368 communication — PDF page 109

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43132–43138
2 Profibus slot/index 169/36–169/42
3 Fieldbus format Long
4 Modbus format EInt

361 communication — PDF page 109

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43131
2 Profibus slot/index 169/35
3 Fieldbus format UInt
4 Modbus format UInt

Table24 presetcontrol bit selection — PDF page 109

Source row Preset Ctrl3 Preset Ctrl2 Preset Ctrl1 Output Speed
1 0 0 0 Analogue reference
2 0 0 11) Preset Ref 1
3 0 11) 0 Preset Ref 2
4 0 1 1 Preset Ref 3
5 11) 0 0 Preset Ref 4
6 1 0 1 Preset Ref 5
7 1 1 0 Preset Ref 6
8 1 1 1 Preset Ref 7

Manual — Preset references andPIDcontrol. Collected P034 association; no extrapolation to other variants. — page 110

Manual reference: physical PDF page 110. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Keyboard reference mode [369]

This parameter sets how the reference value [310] is

edited.

Communication information

11.3.8 PID Process Control [380]

The PID controller is used to control an external process

via a feedback signal. The reference value can be set

via analogue input AnIn1, at the Control Panel [310] by

using a Preset Reference, or via serial communication.

The feedback signal (actual value) must be connected

to an analogue input that is set to the function Process

Value.

Process PID Control [381]

This function enables the PID controller and defines the

response to a changed feedback signal.

PID P Gain [383]

Setting the P gain for the PID controller.

NOTE: When Key Ref Mode is set to MotPot, the

reference value ramp times are according to the Acc

MotPot [333] and Dec MotPot [334] settings. Actual

speed ramp will be limited according to Acc Time [331]

and Dec Time [332].

369 keyboard reference mode is a parameter table with Normal0 andMotPot1. Its note distinguishes reference ramps333/334 from actualspeed ramps331/332. The motor-potentiometer figure89 is on preceding PDF109, not thispage.

369 Key Ref Mode. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

Shared source cells (coordinates refer to this table):

381 PID Control. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

369 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

381 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

383 PID P Gain. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

383 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

369 Key Ref Mode — PDF page 110

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ MotPot
2 Normal 0 The reference value is edited as a normal parameter (the new reference value is activated when Enter is pressed after the value has been changed). The Acc Time [331] and Dec Time [332] are used.
3 MotPot 1 The reference value is edited using the motor potentiometer function (the new reference value is activated directly when the key + or - is pressed). The Acc MotPot [333] and Dec MotPot [334] are used.

381 PID Control — PDF page 110

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 PID control deactivated.
3 On 1 The speed increases when the feedback value decreases. PID settings according to menus [381] to [385].
4 Invert 2 The speed decreases when the feedback value decreases. PID settings according to menus [383] to [385].

369 communication — PDF page 110

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43139
2 Profibus slot/index 169/43
3 Fieldbus format UInt
4 Modbus format UInt

381 communication — PDF page 110

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43154
2 Profibus slot/index 169/58
3 Fieldbus format UInt
4 Modbus format UInt

383 PID P Gain — PDF page 110

Source row Property Value
1 Default: 1.0
2 Range: 0.0–30.0

383 communication — PDF page 110

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43156
2 Profibus slot/index 169/60
3 Fieldbus format Long, 1=0.1
4 Modbus format EInt

Manual — Preset references andPIDcontrol. Collected P034 association; no extrapolation to other variants. — page 111

Manual reference: physical PDF page 111. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 90 Closed loop PID control

PID I Time [384]

Setting the integration time for the PID controller.

Communication information

Process PID D Time [385]

Setting the differentiation time for the PID controller.

PID sleep functionality

This function is controlled via a wait delay and a sepa-

rate wake-up margin condition. With this function it is

possible to put the AC drive in “sleep mode” when the

process value is at it’s set point and the motor is run-

ning at minimum speed for the length of the time set in

[386]. By going into sleep mode, the by the application

consumed energy is reduced to a minimum. When the

process feedback value goes below the set margin on

the process reference as set in [387], the AC drive will

wake up automatically and normal PID operation con-

tinues, see examples.

PID sleep when less than minimum

speed [386]

If the PID output is equal to or less than minimum

speed for given delay time, the AC drive will go to sleep.

PID Activation Margin [387]

The PID activation (wake-up) margin is related to the

process reference and sets the limit when the AC drive

should wake-up/start again.

+

M

-

06-F95

Process

reference

feedback

PID

AC drive

NOTE: Menu [386] has higher priority than menu [342].

NOTE: The margin is always a positive value.

Figure90 closed-loop process control: Process reference andprocess feedback through ProcessPID to ACdrive, motorM andProcess, thenfeedbackloop. Diagram arrows are functional associations,not wiring instructions.

384 PID I Time. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

386 PID<MinSpd. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

384 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

386 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

385 PID D Time. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

387 PID Act Marg. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

385 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

387 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

384 PID I Time — PDF page 111

Source row Property Value
1 Default: 1.00 s
2 Range: 0.01–300 s

386 PID<MinSpd — PDF page 111

Source row Property Value
1 Default: Off
2 Range: Off, 0.01 –3600 s

384 communication — PDF page 111

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43157
2 Profibus slot/index 169/61
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

386 communication — PDF page 111

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43371
2 Profibus slot/index 170/20
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

385 PID D Time — PDF page 111

Source row Property Value
1 Default: 0.00 s
2 Range: 0.00–30 s

387 PID Act Marg — PDF page 111

Source row Property Value
1 Default: 0
2 Range: 0 –10000 in Process unit

385 communication — PDF page 111

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43158
2 Profibus slot/index 169/62
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

387 communication — PDF page 111

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43372
2 Profibus slot/index 170/21
3 Fieldbus format Long
4 Modbus format EInt

Manual — Preset references andPIDcontrol. Collected P034 association; no extrapolation to other variants. — page 112

Manual reference: physical PDF page 112. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example 1 PID control = normal (flow or

pressure control)

[321] = F (AnIn)

[322] = Bar

[310] = 20 Bar

[342] = 2 s (inactive since [386] is activated and have

higher priority)

[381]= On

[386] = 10 s

[387] = 1 Bar

The AC drive will stop/sleep when the speed (PID out-

put) is below or equal to Min Speed for 10 seconds. The

AC drive will activate/wake up when the “Process

value” goes below the PID Activation Margin which is

related to the process reference, i.e. goes below (20-1)

Bar. See Fig. 91.

Fig. 91 PID Stop/sleep with normal PID

Example 2 PID control = inverted (tank level

control)

[322] = m

[310] = 7 m

[381]= Inverted

[386] = 30 s

[387] = 1 m

put) is below or equal to Min Speed for 30 seconds. The

value” goes above the PID Activation Margin which is

related to the process reference, i.e. goes above (7+1)

m. See Fig. 92.

Fig. 92 PID Stop/sleep with inverted PID

PID Steady State Test [388]

In application situations where the feedback can

become independent of the motor speed, this PID

Steady Test function can be used to overrule the PID

operation and force the AC drive to go in sleep mode i.e.

the AC drive automatically reduces the output speed

while at the same time ensures the process value.

Example: pressure controlled pump systems with low/

no flow operation and where the process pressure has

become independent of the pump speed, e.g. due to

slowly closed valves. By going into Sleep mode, heating

of the pump and motor will be avoided and no energy is

spilled.

PID Steady state test delay.

Communication information

PID Steady State Margin [389]

PID steady state margin defines a margin band around

the reference that defines “steady state operation”.

During the steady state test the PID operation is over-

ruled and the AC drive is decreasing the speed as long

as the PID error is within the steady state margin. If the

PID error goes outside the steady state margin the test

failed and normal PID operation continues, see exam-

ple.

[711] Process Value

[387]

[712] Speed

[341] Min Speed

[386]

Stop/Sleep

[310] Process Ref

Activate/Wake up

NOTE: It is important that the system has reached a

stable situation before the Steady State Test is initiated.

Figures91/92 normal andinvertedPID examples show reference+/-wakeupmargin,PIDfeedback andPIDoutput vsMinSpeed341;386sleeptimer precedesstop;normaldecrease orinvertincrease crosseswake threshold. Values only as adjacentexamples.

388 PID Stdy Tst. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

388 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

389 PID Stdy Mar. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

389 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Source PID/preset values depend on processsource321/units322 andactiveinputs; examples not universaldefaults.

388 PID Stdy Tst — PDF page 112

Source row Property Value
1 Default: Off
2 Range: Off, 0.01–3600 s

388 communication — PDF page 112

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43373
2 Profibus slot/index 170/22
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

389 PID Stdy Mar — PDF page 112

Source row Property Value
1 Default: 0
2 Range: 0–10000 in process unit

389 communication — PDF page 112

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43374
2 Profibus slot/index 170/23
3 Fieldbus format Long, 1=0.01 s
4 Modbus format EInt

Manual — Preset references andPIDcontrol. Collected P034 association; no extrapolation to other variants. — page 113

Manual reference: physical PDF page 113. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example: The PID Steady Test starts when the process

value [711] is within the margin and Steady State Test

Wait Delay has expired. The PID output will decrease

speed with a step value which corresponds to the mar-

gin as long as the Process value [711] stays within

steady state margin. When Min Speed [341] is reached

the steady state test was successful and stop/sleep is

commanded if PID sleep function [386]and [387] is

activated. If the Process value [711] goes outside the

set steady state margins then the test

failed and normal PID operation will continue, see Fig.

.

Fig. 93 Steady state test

time

[711] Process Value

[310] Process Ref

[387]

[712] Speed

[388]

Stop/Sleep

[389]

[341] Min Speed

[386] PID<Min Spd

Normal PID

Stop steady

Start steady

Steady state

test

state test

Figure93 labels PIDfeedback711, PIDreference310, steady-state margin389 aroundreference; steadytest388; wakeupmargin387; sleep386; output712 andminspeed341. Duringtest speeddecreases; leaves389band => returntonormal, otherwise reachesmin then sleepsafter386. No intermediate slopes converted to numerical data.

Manual — Pumpandfancontrol. Collected P034 association; no extrapolation to other variants. — page 114

Manual reference: physical PDF page 114. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.3.9 Pump/Fan Control [390]

The Pump Control functions are in menu [390]. The

function is used to control a number of drives (pumps,

fans, etc.) of which one is always driven by the AC drive.

Pump enable [391]

This function will enable the pump control to set all rel-

evant pump control functions.

Communication information

Number of Drives [392]

Sets the total number of drives which are used, includ-

ing the Master AC drive. The setting here depends on

the parameter Select Drive [393]. After the number of

drives is chosen it is important to set the relays for the

pump control. If the digital inputs are also used for sta-

tus feedback, these must be set for the pump control

according to; Pump 1 OK– Pump6 OK in menu [520].

Select Drive [393]

Sets the main operation of the pump system.

'Sequence' and 'Runtime' are Fixed MASTER operation.

'All' means Alternating MASTER operation.

NOTE: Used relays must be defined as Slave Pump or

Master Pump. Used digital inputs must be defined as

Pump Feedback.

NOTE: This menu will NOT be active if less than 3 drives

are selected.

392 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

391 Pump enable. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

Shared source cells (coordinates refer to this table):

393 Select Drive. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

391 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

392 No of Drives. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

393 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

392 communication — PDF page 114

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43162
2 Profibus slot/index 169/66
3 Fieldbus format UInt
4 Modbus format UInt

391 Pump enable — PDF page 114

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Pump control is switched off.
3 On 1 Pump control is on: - Pump control parameters [392] to [39G] appear and are activated according to default settings. - View functions [39H] to [39M] are added in the menu structure.

393 Select Drive — PDF page 114

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ Sequence
2 Sequence 0 Fixed MASTER operation: - The additional drives will be selected in sequence, i.e. first pump 1 then pump 2 etc. - A maximum of 7 drives can be used.
3 Run Time 1 Fixed MASTER operation: - The additional drives will be selected depending on the Run Time. So the drive with the lowest Run Time will be selected first. The Run Time is monitored in menus [39H] to [39M] in sequence. For each drive the Run Time can be reset. - When drives are stopped, the drive with the longest Run Time will be stopped first. - Maximum 7 drives can be used.
4 All 2 Alternating MASTER operation: - When the drive is powered up, one drive is selected as the Master drive. The selection criteria depends on the Change Condition [394]. The drive will be selected according to the Run Time. So the drive with the lowest Run Time will be selected first. The Run Time is monitored in menus [39H] to [39M] in sequence. For each drive the Run Time can be reset. - A maximum of 6 drives can be used.

391 communication — PDF page 114

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43161
2 Profibus slot/index 169/65
3 Fieldbus format UInt
4 Modbus format UInt

392 No of Drives — PDF page 114

Source row Property Value
1 Default: 1
2 1-3 Number of drives if I/O Board is not used.
3 1-6 Number of drives if 'Alternating MASTER' is used, see Select Drive [393]. (I/O Board is used.)
4 1-7 Number of drives if 'Fixed MASTER' is used, see Select Drive [393]. (I/O Board is used.)

393 communication — PDF page 114

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43163
2 Profibus slot/index 169/67
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Pumpandfancontrol. Collected P034 association; no extrapolation to other variants. — page 115

Manual reference: physical PDF page 115. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Change Condition [394]

This parameter determines the criteria for changing the

master. This menu only appears if Alternating MASTER

operation is selected. The elapsed run time of each

drive is monitored. The elapsed run time always deter-

mines which drive will be the 'new' master drive.

This function is only active if the parameter Select Drive

[393]=All.

Communication information

Change Timer [395]

When the time set here is elapsed, the master drive will

be changed. This function is only active if Select Drive

[393]=All and Change Cond [394]= Timer/ Both.

Drives on Change [396]

If a master drive is changed according to the timer func-

tion (Change Condition=Timer/Both [394]), it is possi-

ble to leave additional pumps running during the

change operation. With this function the change opera-

tion will be as smooth as possible. The maximum

number to be programmed in this menu depends on

the number of additional drives.

Example:

If the number of drives is set to 6, the maximum value

will be 4. This function is only active if Select Drive

NOTE: If the Status feedback inputs (DigIn 9 to Digin 14)

are used, the master drive will be changed immediately

if the feedback generates an 'Error'.

395 Change Timer. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

394 Change Cond. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

395 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

396 Drives on Ch. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

394 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

396 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

395 Change Timer — PDF page 115

Source row Property Value
1 Default: 50 h
2 Range: 1-3000 h

394 Change Cond — PDF page 115

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ Both
2 Stop 0 The Runtime of the master drive determines when a master drive has to be changed. The change will only take place after a: - Power Up - Stop - Standby condition - Trip condition.
3 Timer 1 The master drive will be changed if the timer setting in Change Timer [395] has elapsed. The change will take place immediately. So during operation the additional pumps will be stopped temporarily, the 'new' master will be selected according to the Run Time and the additional pumps will be started again. It is possible to leave 2 pumps running during the change operation. This can be set with Drives on Change [396].
4 Both 2 The master drive will be changed if the timer setting in Change Timer [395] has elapsed. The 'new' master will be selected according to the elapsed Run Time. The change will only take place after a: - Power Up - Stop - Standby condition. - Trip condition.

395 communication — PDF page 115

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43165
2 Profibus slot/index 169/69
3 Fieldbus format UInt, 1=1 h
4 Modbus format UInt, 1=1 h

396 Drives on Ch — PDF page 115

Source row Property Value
1 Default: 0
2 Range: 0 to (the number of drives - 2)

394 communication — PDF page 115

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43164
2 Profibus slot/index 169/68
3 Fieldbus format UInt
4 Modbus format UInt

396 communication — PDF page 115

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43166
2 Profibus slot/index 169/70
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Pumpandfancontrol. Collected P034 association; no extrapolation to other variants. — page 116

Manual reference: physical PDF page 116. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Upper Band [397]

If the speed of the master drive comes into the upper

band, an additional drive will be added after a delay

time that is set in start delay [399].

Communication information

Example:

Max Speed = 1500 rpm

Min Speed = 300 rpm

Upper Band = 10%

Start delay will be activated:

Range = Max Speed to Min Speed = 1500–300 = 1200

rpm

10% of 1200 rpm = 120 rpm

Start level = 1500–120 = 1380 rpm

Fig. 94 Upper band

Lower Band [398]

If the speed of the master drive comes into the lower

band an additional drive will be stopped after a delay

time. This delay time is set in the parameter Stop Delay

[39A].

Lower Band = 10%

Stop delay will be activated:

Range = Max Speed - Min Speed = 1500–300 = 1200 rpm

Start level = 300 + 120 = 420 rpm

Fig. 95 Lower band

Start Delay [399]

This delay time must have elapsed before the next

pump is started. A delay time prevents the nervous

switching of pumps.

(NG_50-PC-12_1)

Flow/Pressure

Speed

Max

Min

Upper band

next pump starts

(NG_50-PC-13_1)

“top” pump stops

Lower band

Stop Delay [39A]

Figures94/95 show verticalSpeed withMax/Min andhorizontalFlow/Pressure. Upper/lowerbands andStartDelay399/StopDelay39A are annotated; nextpump starts andtop pump stops. Threshold ordering retained without inferring durations.

398 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

397 Upper Band. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

397 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

399 Start Delay. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

399 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

398 Lower Band. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

398 communication — PDF page 116

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43168
2 Profibus slot/index 169/72
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

397 Upper Band — PDF page 116

Source row Property Value
1 Default: 10%
2 Range: 0-100% of total min speed to max speed

397 communication — PDF page 116

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43167
2 Profibus slot/index 169/71
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

399 Start Delay — PDF page 116

Source row Property Value
1 Default: 0 s
2 Range: 0-999 s

399 communication — PDF page 116

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43169
2 Profibus slot/index 169/73
3 Fieldbus format Long, 1=1s
4 Modbus format EInt

Manual — Pumpandfancontrol. Collected P034 association; no extrapolation to other variants. — page 117

Manual reference: physical PDF page 117. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Stop Delay [39A]

This delay time must have elapsed before the 'top'

pump is stopped. A delay time prevents the nervous

switching of pumps.

Communication information

Upper Band Limit [39B]

If the speed of the pump reaches the upper band limit,

the next pump is started immediately without delay. If a

start delay is used this delay will be ignored. Range is

between 0%, equalling max speed, and the set percent-

age for the UpperBand [397].

Fig. 96 Upper band limit

Lower Band Limit [39C]

If the speed of the pump reaches the lower band limit,

the 'top' pump is stopped immediately without delay. If

a stop delay is used this delay will be ignored. Range is

from 0%, equalling min speed, to the set percentage for

the Lower Band [398].

Fig. 97 Lower band limit

Settle Time Start [39D]

The settle start allows the process to settle after a

pump is switched on before the pump control contin-

ues. If an additional pump is started D.O.L. (Direct On

Line) or Y/

, the flow or pressure can still fluctuate

due to the 'rough' start/stop method. This could cause

unnecessary starting and stopping of additional

pumps.

During the Settle start:

• PID controller is off.

• The speed is kept at a fixed level after adding a

pump.

(NG_50-PC-14_2)

Speed

Max

Min

Upper band

Start Delay [399]

limit [39B]

next pump starts

immediately

Flow/Pressure

(NG_50-PC-15_2)

Lower band

limit [39C]

“top” pump stops

Δ

Figures96/97 upperfastlimit39B andlowerfastlimit39C alongsidebands397/398 anddelays399/39A; fastlimit bypassesdelay. 39Dsettle conditions appear in prose; Figure98 is on PDF118. No plot values added.

39A Stop Delay. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39C Low Band Lim. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39A communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39C communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39B Upp Band Lim. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39B communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39D Settle Start. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

Shared source cells (coordinates refer to this table):

39A Stop Delay — PDF page 117

Source row Property Value
1 Default: 0 s
2 Range: 0-999 s

39C Low Band Lim — PDF page 117

Source row Property Value
1 Default: 0%
2 Range: 0 to Lower Band level. 0% (=min speed) means that he Limit function is switched off.

39A communication — PDF page 117

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43170
2 Profibus slot/index 169/74
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

39C communication — PDF page 117

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43172
2 Profibus slot/index 169/76
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

39B Upp Band Lim — PDF page 117

Source row Property Value
1 Default: 0%
2 Range: 0 to Upper Band level. 0% (=max speed) means that the Limit function is switched off.

39B communication — PDF page 117

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43171
2 Profibus slot/index 169/75
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

39D Settle Start — PDF page 117

Source row Property Value
1 Default: 0 s ⟦null: no independent source value⟧
2 Range: 0-999 s

Manual — Pumpandfancontrol. Collected P034 association; no extrapolation to other variants. — page 118

Manual reference: physical PDF page 118. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Communication information

Transition Speed Start [39E]

The transition speed start is used to minimize a flow/

pressure overshoot when adding another pump. When

an additional pump needs to be switched on, the mas-

ter pump will slow down to the set transition speed

start value, before the additional pump is started. The

setting depends on the dynamics of both the master

drive and the additional drives.

The transition speed is best set by trial and error.

In general:

• If the additional pump has 'slow' start/stop dynam-

ics, then a higher transition speed should be used.

•

If the additional pump has 'fast' start/stop dynam-

ics, then a lower transition speed should be used.

Example

Max Speed = 1500 rpm

Min Speed = 200 rpm

TransS Start = 60%

When an additional pump is needed, the speed will be

controlled down to min speed + (60% x (1500 rpm -

200 rpm)) = 200 rpm + 780 rpm = 980 rpm. When this

speed is reached, the additional pump with the lowest

run time hours will be switched on.

Fig. 98 Transition speed start

Fig. 99 Effect of transition speed

Settle Time Stop [39F]

The settle stop allows the process to settle after a

pump is switched off before the pump control contin-

ues. If an additional pump is stopped D.O.L. (Direct On

Line) or Y/

, the flow or pressure can still fluctuate

due to the 'rough' start/stop method. This could cause

unnecessary starting and stopping of additional

pumps.

During the Settle stop:

• PID controller is off.

the speed is kept at a fixed level after stopping a

pump

(NG_50-PC-16_1)

Speed

Actual

Trans

Min

Switch on

procedure starts

Additional pump

Master pump

Flow/Pressure

Actual start

command of next

pump (RELAY)

Transition speed

decreases overshoot

Time

Δ

Figure98 transitionstart showsSpeed againstFlow/Pressure, Actual/Trans/Min, switchonprocedurestart, master/additionalpump andrelaystartcommand. Figure99 Flow/Pressure againstTime showsreducedovershoot withtransitionspeed. Adjacent39Eprose selectslowest-runtimepump;1500max200min60%=980rpm is supplierexample.

39D communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39E TransS Start. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39E communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39F Settle Stop. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39F communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39D communication — PDF page 118

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43173
2 Profibus slot/index 169/77
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

39E TransS Start — PDF page 118

Source row Property Value
1 Default: 60%
2 Range: 0-100% of total min speed to max speed

39E communication — PDF page 118

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43174
2 Profibus slot/index 169/78
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

39F Settle Stop — PDF page 118

Source row Property Value
1 Default: 0 s
2 Range: 0–999 s

39F communication — PDF page 118

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43175
2 Profibus slot/index 169/79
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

Manual — Pumpandfancontrol. Collected P034 association; no extrapolation to other variants. — page 119

Manual reference: physical PDF page 119. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Transition Speed Stop [39G]

The transition speed stop is used to minimize a flow/

pressure overshoot when shutting down an additional

pump. The setting depends on the dynamics of both

the master drive and the additional drives.

In general:

• If the additional pump has 'slow' start/stop dynam-

ics, then a higher transition speed should be used.

•

If the additional pump has 'fast' start/stop dynam-

ics, then a lower transition speed should be used.

Communication information

Example

Max Speed = 1500 rpm

Min Speed = 200 rpm

TransS Start = 60%

When less additional pumps are needed, the speed will

be controlled up to min speed + (60% x (1500 rpm -

200 rpm)) = 200 rpm + 780 rpm = 980 rpm. When this

speed is reached, the additional pump with the highest

run time hours will be switched off.

Fig. 100 Transition speed stop

Run Times 1-6 [39H] to [39M]

Reset Run Times 1-6 [39H1] to [39M1]

Speed

Max

Trans

Actual

Min

Actual shut down of pump

Master pump

Switch off procedure starts

Additional pump

Flow/Pressure

Figure100 transitionstop showsSpeed againstFlow/Pressure, Max/Trans/Actual/Min, master/additionalpump, switchoffprocedurestart andactualshutdownofpump. The39Gprose sayshighest-runtimepumpstops; figure doesnotprint39G/39Flabels. ExampleliteralTransS Start retained despite stopheading.

39H Run Time 1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39H–39M communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39G TransS Stop. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39G communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39H1 Rst Run Tm1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

Shared source cells (coordinates refer to this table):

39H1–39M1 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39H Run Time 1 — PDF page 119

Source row Property Value
1 Unit: h:mm:ss (hours:minutes:seconds)
2 Range: 0:00:00–262143:59:59

39H–39M communication — PDF page 119

Source row Property Value
1 Modbus Instance no/ DeviceNet no: 31051 : 31052 : 31053(hr:min:sec) 31054 : 31055: 31056(hr:min:sec) 31057 : 31058: 31059(hr:min:sec) 31060 : 31061: 31062(hr:min:sec) 31063 : 31064: 31065(hr:min:sec) 31066 : 31067: 31068(hr:min:sec)
2 Profibus slot/index 121/195, 121/196, 121/197, 121/198, 121/199, 121/200, 121/201, 121/202, 121/203, 121/204, 121/205, 121/206, 121/207, 121/208, 121/209, 121/210, 121/211, 121/212
3 Fieldbus format Long, 1=1h/m/s
4 Modbus format EInt, 1=1h/m/s

39G TransS Stop — PDF page 119

Source row Property Value
1 Default: 60%
2 Range: 0-100% of total min speed to max speed

39G communication — PDF page 119

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43176
2 Profibus slot/index 169/80
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

39H1 Rst Run Tm1 — PDF page 119

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ No
2 No 0 ⟦blank source cell⟧
3 Yes 1 ⟦blank source cell⟧

39H1–39M1 communication — PDF page 119

Source row Property Value
1 Modbus Instance no/DeviceNet no: 38–43, pump 1 -6
2 Profibus slot/index 0/37–0/42
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Pumpandfancontrol. Collected P034 association; no extrapolation to other variants. — page 120

Manual reference: physical PDF page 120. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Pump Status [39N]

Number backup/reserve [39P]

Sets the number of pumps used for backup/reserve

which in normal conditions can not be selected. This

function can be used for increasing redundancy in the

pump system by having pumps in reserve that can be

activated when some pumps indicate fault or are shut

off for maintenance.

Communication information

11.4 Load Monitor and Process

Protection [400]

11.4.1 Load Monitor [410]

The monitor functions enable the AC drive to be used

as a load monitor. Load monitors are used to protect

machines and processes against mechanical overload

and underload, e.g. a conveyer belt or screw conveyer

jamming, belt failure on a fan and a pump dry running.

See explanation in section 7.5, page 40.

Alarm Select [411]

Selects the types of alarms that are active.

Alarm Trip [412]

Selects which alarm must cause a trip to the AC drive.

39N Pump 123456

Stp

OCD

A

39N pumpstatus indications. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

411 Alarm Select. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

Shared source cells (coordinates refer to this table):

39P No of Backup. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39P communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

411 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

412 Alarm trip. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

412 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Fixed versus alternatingmaster andoptionalI/Oboard govern drive counts/menus; sourceformula/example claims retained without engineering validation.

39N pumpstatus indications — PDF page 120

Source row Indication Description
1 C Control, master pump, only when alternating master is used
2 D Direct control
3 O Pump is off
4 E Pump error

411 Alarm Select — PDF page 120

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 No alarm functions active.
3 Min 1 Min Alarm active. The alarm output func- tions as an underload alarm.
4 Max 2 Max Alarm active. The alarm output func- tions as an overload alarm.
5 Max+Min 3 Both Max and Min alarm are active. The alarm outputs function as overload and underload alarms.

39P No of Backup — PDF page 120

Source row Property Value
1 Default: 0
2 Range: 0-3

39P communication — PDF page 120

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43177
2 Profibus slot/index 169/81
3 Fieldbus format UInt
4 Modbus format UInt

411 communication — PDF page 120

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43321
2 Profibus slot/index 169/225
3 Fieldbus format UInt
4 Modbus format UInt

412 Alarm trip — PDF page 120

Source row Property Value
1 Default: Off
2 Selection: Same as in menu [411]

412 communication — PDF page 120

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43322
2 Profibus slot/index 169/226
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Loadmonitor andprocessprotection. Collected P034 association; no extrapolation to other variants. — page 121

Manual reference: physical PDF page 121. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Ramp Alarm [413]

This function inhibits the (pre) alarm signals during

acceleration/deceleration of the motor to avoid false

alarms.

Communication information

Alarm Start Delay [414]

This parameter is used if, for example, you want to over-

ride an alarm during the start-up procedure.

Sets the delay time after a run command, after which

the alarm may be given.

• If Ramp Alarm=On. The start delay begins after a

RUN command.

•

If Ramp Alarm=Off. The start delay begins after the

acceleration ramp.

Load Type [415]

In this menu you select monitor type according to the

load characteristic of your application. By selecting the

required monitor type, the overload and underload

alarm function can be optimized according to the load

characteristic.

When the application has a constant load over the

whole speed range, i.e. extruder or screw compressor,

the load type can be set to basic. This type uses a sin-

gle value as a reference for the nominal load. This value

is used for the complete speed range of the AC drive.

The value can be set or automatically measured. See

Autoset Alarm [41A] and Normal Load [41B] about set-

ting the nominal load reference.

The load curve mode uses an interpolated curve with 9

load values at 8 equal speed intervals. This curve is

populated by a test run with a real load. This can be

used with any smooth load curve including constant

load.

Fig. 101

Basic

Load curve

Load

Speed

Max Alarm

Min Alarm

Figure101 load monitor graph: Loadvertical/Speedhorizontal, Basicconstant middlelinewithMax/MinAlarmbounds andcurvedLoadcurve; no numericalsamples asserted.

413 Ramp Alarm. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

Shared source cells (coordinates refer to this table):

413 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

414 Start Delay. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

415 Load Type. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

414 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

415 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

413 Ramp Alarm — PDF page 121

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 (Pre) alarms are inhibited during accelera- tion/deceleration.
3 On 1 (Pre) alarms active during acceleration/ deceleration.

413 communication — PDF page 121

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43323
2 Profibus slot/index 169/227
3 Fieldbus format UInt
4 Modbus format UInt

414 Start Delay — PDF page 121

Source row Property Value
1 Default: 2 s
2 Range: 0-3600 s

415 Load Type — PDF page 121

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Basic
2 Basic 0 Uses a fixed maximum and minimum load level over the full speed range. Can be used in situations where the torque is independ- ent of the speed.
3 Load Curve 1 Uses the measured actual load characteristic of the process over the speed range.

414 communication — PDF page 121

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43324
2 Profibus slot/index 169/228
3 Fieldbus format Long, 1=1 s
4 Modbus format EInt

415 communication — PDF page 121

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43325
2 Profibus slot/index 169/229
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Loadmonitor andprocessprotection. Collected P034 association; no extrapolation to other variants. — page 122

Manual reference: physical PDF page 122. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Max Alarm [416]

Max Alarm Margin [4161]

With load type Basic, [415], used the Max Alarm Margin

sets the band above the Normal Load, [41B], menu that

does not generate an alarm. With load type Load Curve,

[415], used the Max Alarm Margin sets the band above

the Load Curve, [41C], that does not generate an

alarm. The Max Alarm Margin is a percentage of nomi-

nal motor torque.

Communication information

Max Alarm delay [4162]

Sets the delay time between the first occurrence of max

alarm condition and after when the alarm is given.

Max Pre Alarm [417]

Max Pre AlarmMargin [4171]

With load type Basic, [415], used the Max Pre-Alarm

Margin sets the band above the Normal Load, [41B],

menu that does not generate a pre-alarm. With load

type Load Curve, [415], used the Max Pre-Alarm Margin

sets the band above the Load Curve, [41C], that does

not generate a pre-alarm. The Max Pre-Alarm Margin is

a percentage of nominal motor torque.

Max Pre Alarm delay [4172]

pre alarm condition and after when the alarm is given.

Min Pre Alarm [418]

Min Pre Alarm Margin [4181]

With load type Basic, [415], used the Min Pre-Alarm

Margin sets the band under the Normal Load, [41B],

type Load Curve, [415], used the Min Pre-Alarm Margin

sets the band under the Load Curve, [41C], that does

not generate a pre-alarm. The Min Pre-Alarm Margin is

4171 MaxPreAlMar

Stp

10%

A

4171 MaxPreAlarmMargin continuation from leftcolumn. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4171 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4161 MaxAlarmMar. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4172 MaxPreAlDel. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4161 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4172 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4162 MaxAlarmDel. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4162 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4181 MinPreAlMar. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4181 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4171 MaxPreAlarmMargin continuation from leftcolumn — PDF page 122

Source row Property Value
1 Default: 10%
2 Range: 0–400%

4171 communication — PDF page 122

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43327
2 Profibus slot/index 169/231
3 Fieldbus format Long, 1=0.1%
4 Modbus format EInt

4161 MaxAlarmMar — PDF page 122

Source row Property Value
1 Default: 15%
2 Range: 0–400%

4172 MaxPreAlDel — PDF page 122

Source row Property Value
1 Default: 0.1 s
2 Range: 0–90 s

4161 communication — PDF page 122

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43326
2 Profibus slot/index 169/230
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

4172 communication — PDF page 122

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43331
2 Profibus slot/index 169/235
3 Fieldbus format Long, 1=0.1 s
4 Modbus format EInt

4162 MaxAlarmDel — PDF page 122

Source row Property Value
1 Default: 0.1 s
2 Range: 0-90 s

4162 communication — PDF page 122

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43330
2 Profibus slot/index 169/234
3 Fieldbus format Long, 1=0.1 s
4 Modbus format EInt

4181 MinPreAlMar — PDF page 122

Source row Property Value
1 Default: 10%
2 Range: 0-400%

4181 communication — PDF page 122

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43328
2 Profibus slot/index 169/232
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

Manual — Loadmonitor andprocessprotection. Collected P034 association; no extrapolation to other variants. — page 123

Manual reference: physical PDF page 123. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Min Pre Alarm Response delay [4182]

Sets the delay time between the first occurrence of min

pre alarm condition and after when the alarm is given.

Communication information

Min Alarm [419]

Min Alarm Margin [4191]

With load type Basic, [415], used the Min Alarm Margin

sets the band under the Normal Load, [41B], menu that

does not generate an alarm. With load type Load Curve,

[415], used the Min Alarm Margin sets the band under

the Load Curve, [41C], that does not generate an

alarm. The Max Alarm Margin is a percentage of nomi-

nal motor torque.

Min Alarm Response delay [4192]

alarm condition and after when the alarm is given.

Autoset Alarm [41A]

The Autoset Alarm function can measure the nominal

load that is used as reference for the alarm levels. If the

selected Load Type [415] is Basic it copies the load the

motor is running with to the menu Normal Load [41B].

The motor must run on the speed that generates the

load that needs to be recorded. If the selected Load

Type [415] is Load Curve it performs a test-run and pop-

ulates the Load Curve [41C] with the found load values.

WARNING!

When autoset does a test run the motor and

application/machine will ramp up to

maximum speed.

NOTE: The motor must be running for the Autoset Alarm

function to succeed. A not running motor generates a

“Failed!” message.

4182 MinPreAlDel. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4192 MinAlarmDel. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4182 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4192 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4191 MinAlarmMar. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4191 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

41A AutoSet Alrm. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

Shared source cells (coordinates refer to this table):

41A communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

4182 MinPreAlDel — PDF page 123

Source row Property Value
1 Default: 0.1 s
2 Range: 0-90 s

4182 communication — PDF page 123

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43332
2 Profibus slot/index 169/236
3 Fieldbus format Long, 1=0.1 s
4 Modbus format EInt

4192 communication — PDF page 123

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43333
2 Profibus slot/index 169/237
3 Fieldbus format Long, 1=0.1 s
4 Modbus format EInt

4191 MinAlarmMar — PDF page 123

Source row Property Value
1 Default: 15%
2 Range: 0-400%

4191 communication — PDF page 123

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43329
2 Profibus slot/index 169/233
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

41A AutoSet Alrm — PDF page 123

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ No
2 No 0 ⟦blank source cell⟧
3 Yes 1 ⟦blank source cell⟧

41A communication — PDF page 123

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43334
2 Profibus slot/index 169/238
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Loadmonitor andprocessprotection. Collected P034 association; no extrapolation to other variants. — page 124

Manual reference: physical PDF page 124. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

The default set levels for the (pre)alarms are:

These default set levels can be manually changed in

menus [416] to [419]. After execution the message

“Autoset OK!” is displayed for 1s and the selection

reverts to “No”.

Normal Load [41B]

Set the level of the normal load. The alarm or pre alarm

will be activated when the load is above/under normal

load ± margin.

Communication information

Load Curve [41C]

The load curve function can be used with any smooth

load curve. The curve can be populated with a test-run

or the values can be entered or changed manually.

Load Curve 1-9 [41C1]-[41C9]

The measured load curve is based on 9 stored sam-

ples. The curve starts at minimum speed and ends at

maximum speed, the range in between is divided into 8

equal steps. The measured values of each sample are

displayed in [41C1] to [41C9] and can be adapted man-

ually. The value of the 1st sampled value on the load

curve is displayed.

Fig. 102

NOTE: 100% Torque means: INOM= IMOT. The maximum

depends on the motor current and AC drive max current

settings, but the absolute maximum adjustment is

400%.

NOTE: The speed values depend on the Min- and Max

Speed values. they are read only and cannot be

changed.

0.2

0.4

0.6

0.8

0.5

Min Speed

Speed

Max Speed

Min-Max alarm tolerance band graph

Measured load samples

Min-max tolerance band

Max alarm limit

Min alarm limit

Figure102 nine measuredloadsamples onSpeed0–1 plot withmin/maxspeed endpoints, min-max tolerancebars, dashedMaxAlarmandMinAlarmlimits. Axislabels0,0.2,0.4,0.6,0.8,1 andload0,0.5,1 are illustrative; no reconstructedengineeringcurve.

41A autoset alarm formula relationships. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

Shared source cells (coordinates refer to this table):

41C1–41C9 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

41B Normal Load. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

41B communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

41C1 Load Curve1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

41A autoset alarm formula relationships — PDF page 124

Source row Selection/property Enumeration or merged span Description/value
1 Overload Max Alarm menu [4161] + [41B]
2 ⟦null: no independent source value⟧ Max Pre Alarm menu [4171] + [41B]
3 Underload Min Pre Alarm menu [41B] - [4181]
4 ⟦null: no independent source value⟧ Min Alarm menu [41B] - [4191]

41C1–41C9 communication — PDF page 124

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43336%, 43337 rpm, 43338%, 43339 rpm, 43340%, 43341 rpm, 43342%, 43343 rpm, 43344%, 43345 rpm, 43346%, 43347 rpm, 43348%, 43349 rpm, 43350%, 43351 rpm, 43352%, 43353 rpm
2 Profibus slot/index 169/240, 169/242, 169/244, 169/246, 169/248, 169/250, 169/252, 169/254, 170/1
3 Fieldbus format Long
4 Modbus format EInt

41B Normal Load — PDF page 124

Source row Property Value
1 Default: 100%
2 Range: 0-400% of max torque

41B communication — PDF page 124

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43335
2 Profibus slot/index 169/239
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

41C1 Load Curve1 — PDF page 124

Source row Property Value
1 Default: 100%
2 Range: 0–400% of max torque

Manual — Loadmonitor andprocessprotection. Collected P034 association; no extrapolation to other variants. — page 125

Manual reference: physical PDF page 125. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.4.2 Process Protection [420]

Submenu with settings regarding protection functions

for the AC drive and the motor.

Low Voltage Override [421]

If a dip in the mains supply occurs and the low voltage

override function is enabled, the AC drive will automati-

cally decrease the motor speed to keep control of the

application and prevent an under voltage trip until the

input voltage rises again. Therefore the rotating energy

in the motor/load is used to keep the DC link voltage

level at the override level, for as long as possible or

until the motor comes to a standstill. This is dependent

on the inertia of the motor/load combination and the

load of the motor at the time the dip occurs, see Fig.

103.

Communication information

Fig. 103 Low voltage override

Rotor locked [422]

With the rotor locked function enabled, the AC drive will

protect the motor and application when this is stalled

whilst increasing the motor speed from standstill. This

protection will coast the motor to stop and indicate a

fault when the Torque Limit has been active at very low

speed for more than 5 seconds.

Motor lost [423]

With the motor lost function enabled, the AC drive is

able to detect a fault in the motor circuit: motor, motor

cable, thermal relay or output filter. Motor lost will

cause a trip, and the motor will coast to standstill, when

a missing motor phase is detected during a period of 5

s.

NOTE: During the low voltage override the LED trip/limit

blinks.

t

(06-F60new)

Override

level

Low Volt.

Speed

DC link voltage

Figure103 DC-linkvoltage dropsbetweenOverridelevelandLowVoltlevel; speedreductioncurve alignedontimeaxis. No numericvoltage ordeceltime stated.

422 Rotor locked. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

Shared source cells (coordinates refer to this table):

421 Low Volt OR. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

422 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

421 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

423 Motor lost. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

423 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Loadtype415 andnormal/loadcurve41B/41C govern alarmdefinitions; warnings and runstate conditions retained.

422 Rotor locked — PDF page 125

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 No detection
3 On 1 AC drive will trip when locked rotor is detected. Trip message “Locked Rotor”.

421 Low Volt OR — PDF page 125

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ On
2 Off 0 At a voltage dip the low voltage trip will protect.
3 On 1 At mains dip, AC drive ramps down until voltage rises.

422 communication — PDF page 125

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43362
2 Profibus slot/index 170/11
3 Fieldbus format UInt
4 Modbus format UInt

421 communication — PDF page 125

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43361
2 Profibus slot/index 170/10
3 Fieldbus format UInt
4 Modbus format UInt

423 Motor lost — PDF page 125

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Function switched off to be used if no motor or very small motor connected.
3 Trip 1 AC drive will trip when the motor is disconnected. Trip message “Motor Lost”.

423 communication — PDF page 125

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43363
2 Profibus slot/index 170/12
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Analogueanddigitalinputcontrols. Collected P034 association; no extrapolation to other variants. — page 126

Manual reference: physical PDF page 126. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Overvolt control [424]

Used to switch off the overvoltage control function

when only braking by brake chopper and resistor is

required. The overvoltage control function, limits the

braking torque so that the DC link voltage level is con-

trolled at a high, but safe, level. This is achieved by lim-

iting the actual deceleration rate during stopping. In

case of a defect at the brake chopper or the brake

resistor the AC drive will trip for “Overvoltage” to avoid a

fall of the load e.g. in crane applications.

Communication information

11.5 I/Os and Virtual

Connections [500]

Main menu with all the settings of the standard inputs

and outputs of the AC drive.

11.5.1 Analogue Inputs [510]

Submenu with all settings for the analogue inputs.

AnIn1 Function [511]

Sets the function for Analogue input 1. Scale and range

are defined by AnIn1 Advanced settings [513].

Adding analogue inputs

If more then one analogue input is set to the same

function, the values of the inputs can be added

together. In the following examples we assume that

Process Source [321] is set to Speed.

Example 1: Add signals with different weight (fine tun-

ing).

Signal on AnIn1 = 10 mA

Signal on AnIn2 = 5 mA

[511] AnIn1 Function = Process Ref.

[512] AnIn1 Setup = 4-20 mA

[5134] AnIn1 Function Min = Min (0 rpm)

[5136] AnIn1 Function Max = Max (1500 rpm)

[5138] AnIn1 Operation = Add+

[514] AnIn2 Function = Process Ref.

NOTE: Overvoltage control should not be activated if

brake chopper is used.

NOTE: When AnInX Func=Off, the connected signal will

still be available for Comparators [610].

424 Over Volt Ctl. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

Shared source cells (coordinates refer to this table):

511 AnIn1 Fc. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

424 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

511 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

424 Over Volt Ctl — PDF page 126

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ On
2 On 0 Overvoltage control activated
3 Off 1 Overvoltage control off

511 AnIn1 Fc — PDF page 126

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Process Ref
2 Off 0 Input is not active
3 Max Speed 1 The input acts as an upper speed limit.
4 Max Torque 2 The input acts as an upper torque limit.
5 Process Val 3 The input value equals the actual process value (feedback) and is compared to the reference signal (set point) by the PID controller, or can be used to display and view the actual process value.
6 Process Ref 4 Reference value is set for control in process units, see Process Source [321] and Process Unit [322].

424 communication — PDF page 126

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43364
2 Profibus slot/index 170/13
3 Fieldbus format UInt
4 Modbus format UInt

511 communication — PDF page 126

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43201
2 Profibus slot/index 169/105
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Analogueanddigitalinputcontrols. Collected P034 association; no extrapolation to other variants. — page 127

Manual reference: physical PDF page 127. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

[515] AnIn2 Setup = 4-20 mA

[5164] AnIn2 Function Min = Min (0 rpm)

[5166] AnIn2 Function Max = User defined

[5167] AnIn2 Value Max = 300 rpm

[5168] AnIn2 Operation = Add+

Calculation:

AnIn1 = (10-4) / (20-4) x (1500-0) + 0 = 562.5 rpm

AnIn2 = (5-4) / (20-4) x (300-0) + 0 = 18.75 rpm

The actual process reference will be:

+562.5 + 18.75 = 581 rpm

Analogue Input Selection via Digital Inputs:

When two different external Reference signals are

used, e.g. 4-20mA signal from control centre and a 0-

10 V locally mounted potentiometer, it is possible to

switch between these two different analogue input sig-

nals via a Digital Input set to “AnIn Select”.

AnIn1 is 4-20 mA

AnIn2 is 0-10 V

DigIn3 is controlling the AnIn selection; HIGH is 4-20

mA, LOW is 0-10 V

[511] AnIn1 Fc = Process Ref;

set AnIn1 as reference signal input

[512] AnIn1 Setup = 4-20mA;

set AnIn1 for a current reference signal

[513A] AnIn1 Enable = DigIn;

set AnIn1 to be active when DigIn3 is HIGH

[514] AnIn2 Fc = Process Ref;

set AnIn2 as reference signal input

[515] AnIn2 Setup = 0-10V;

set AnIn2 for a voltage reference signal

[516A] AnIn2 Enabl = !DigIn;

set AnIn2 to be active when DigIn3 is LOW

[523] DigIn3=AnIn;

set DIgIn3 as input fot selection of AI reference

Subtracting analogue inputs

Example 2: Subtract two signals

Signal on AnIn1 = 8 V

Signal on AnIn2 = 4 V

[511] AnIn1 Function = Process Ref.

[512] AnIn1 Setup = 0-10 V

[5134] AnIn1 Function Min = Min (0 rpm)

[5136] AnIn1 Function Max = Max (1500 rpm)

[5138] AnIn1 Operation = Add+

[514] AnIn2 Function = Process Ref.

[515] AnIn2 Setup = 0-10 V

[5166] AnIn2 Function Max = Max (1500 rpm)

[5168] AnIn2 Operation = Sub-

AnIn1 = (8-0) / (10-0) x (1500-0) + 0 = 1200 rpm

AnIn2 = (4-0) / (10-0) x (1500-0) + 0 = 600 rpm

+1200 - 600 = 600 rpm

AnIn1 Setup [512]

The analogue input setup is used to configure the ana-

logue input in accordance with the signal used that will

be connected to the analogue input. With this selection

the input can be determined as current (4-20 mA) or

voltage (0-10 V) controlled input. Other selections are

available for using a threshold (live zero), a bipolar

input function, or a user defined input range. With a

bipolar input reference signal, it is possible to control

the motor in two directions. See Fig. 104.

NOTE: The selection of voltage or current input is done

with S1. When the switch is in voltage mode only the

voltage menu items are selectable. With the switch in

current mode only the current menu items are

selectable.

NOTE: For bipol function, input RunR and RunL needs to

be active and Rotation, [219] must be set to “R+L”.

512 AnIn1 Setup. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

Shared source cells (coordinates refer to this table):

512 AnIn1 Setup — PDF page 127

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ 4-20 mA
2 Dependent on ⟦null: no independent source value⟧ Setting of switch S1
3 4–20mA 0 The current input has a fixed threshold (Live Zero) of 4 mA and controls the full range for the input signal. See Fig. 106.
4 0–20mA 1 Normal full current scale configuration of the input that controls the full range for the input signal. See Fig. 105.
5 User mA 2 The scale of the current controlled input, that controls the full range for the input sig- nal. Can be defined by the advanced AnIn Min and AnIn Max menus.
6 User Bipol mA 3 Sets the input for a bipolar current input, where the scale controls the range for the input signal. Scale can be defined in advanced menu AnIn Bipol.
7 0–10V 4 Normal full voltage scale configuration of the input that controls the full range for the input signal. See Fig. 105.
8 2–10V 5 The voltage input has a fixed threshold (Live Zero) of 2 V and controls the full range for the input signal. See Fig. 106.
9 User V 6 The scale of the voltage controlled input, that controls the full range for the input sig- nal. Can be defined by the advanced AnIn Min and AnIn Max menus.
10 User Bipol V 7 Sets the input for a bipolar voltage input, where the scale controls the range for the input signal. Scale can be defined in advanced menu AnIn Bipol.

Manual — Analogueanddigitalinputcontrols. Collected P034 association; no extrapolation to other variants. — page 128

Manual reference: physical PDF page 128. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Communication information

Fig. 104

Fig. 105 Normal full-scale configuration

Fig. 106 2–10 V/4–20 mA (Live Zero)

AnIn1 Advanced [513]

AnIn1 Min [5131]

Parameter to set the minimum value of the external

reference signal. Only visible if [512] = User mA/V.

AnIn1 Max [5132]

Parameter to set the maximum value of the external

Special function: Inverted reference signal

If the AnIn minimum value is higher than the AnIn

maximum value, the input will act as an inverted refer-

ence input, see Fig. 107.

NOTE: Always check the needed set up when the setting

of S1 is changed; selection will not adapt automatically.

20 mA

100 %

n

(NG_06-F21)

10 V

-10 V

Speed

20mA

%

Ref

0–10 V

0–20 mA

0mA

4mA

2 V

2–10 V

4–20 mA

NOTE: The different menus will automatically be set to

either “mA” or “V”, based on the selection in AnIn 1

Setup [512].

513 AnIn1 Advan

Stp A

Figure104 bipolarreference graph spansnegativevoltage/current topositive;Figure105fullscale0–10V/0–20mA reaches100%;Figure106livezero2V/4mA to10V/20mA reaches100%. No interpretationas faultthresholdbeyond source.

512 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5131 AnIn1 Min. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5131 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5132 AnIn1 Max. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5132 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

512 communication — PDF page 128

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43202
2 Profibus slot/index 169/106
3 Fieldbus format UInt
4 Modbus format UInt

5131 AnIn1 Min — PDF page 128

Source row Property Value
1 Default: 0 V/4.00 mA
2 Range: 0.00–20.00 mA 0–10.00 V

5131 communication — PDF page 128

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43203
2 Profibus slot/index 169/107
3 Fieldbus format Long
4 Modbus format EInt

5132 AnIn1 Max — PDF page 128

Source row Property Value
1 Default: 10.00 V/20.00 mA
2 Range: 0.00–20.00 mA 0–10.00 V

5132 communication — PDF page 128

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43204
2 Profibus slot/index 169/108
3 Fieldbus format Long
4 Modbus format EInt

Manual — Analogueanddigitalinputcontrols. Collected P034 association; no extrapolation to other variants. — page 129

Manual reference: physical PDF page 129. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 107 Inverted reference

AnIn1 Bipol [5133]

This menu is automatically displayed if AnIn1 Setup is

set to User Bipol mA or User Bipol V. The window will

automatically show mA or V range according to selected

function. The range is set by changing the positive

maximum value; the negative value is automatically

adapted accordingly. Only visible if [512] = User Bipol

mA/V. The inputs RunR and RunL input need to be

active, and Rotation, [219], must be set to “R+L”, to

operate the bipolar function on the analogue input.

Communication information

AnIn1 Function Min [5134]

With AnIn1 Function Min the physical minimum value is

scaled to selected process unit. The default scaling is

dependent of the selected function of AnIn1 [511].

Table 25 shows corresponding values for the min and

max selections depending on the function of the ana-

logue input [511].

AnIn1 Function Value Min [5135]

With AnIn1 Function ValMin you define a user-defined

value for the signal. Only visible when user-defined is

selected in menu [5134].

1 0 V

%

n

(NG_06-F25)

Invert

Ref

AnIn Min >

AnIn Max

Table 25

Figure107 invertedreference decreasesfrom100%to0asreferenceincreaseswhenAnInMin>AnInMax; no extra endpoints beyond visibleaxes.

5134 AnIn1 FcMin. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

Shared source cells (coordinates refer to this table):

Table25 function-specific Min andMax selections. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5133 AnIn1 Bipol. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5134 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5133 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5135 AnIn1 VaMin. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5135 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5134 AnIn1 FcMin — PDF page 129

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Min
2 Min 0 Min value
3 Max 1 Max value
4 User- defined 2 Define user value in menu [5135]

Table25 function-specific Min andMax selections — PDF page 129

Source row AnIn Function Min Max
1 Speed Min Speed [341] Max Speed [343]
2 Torque 0% Max Torque [351]
3 Process Ref Process Min [324] Process Max [325]
4 Process Value Process Min [324] Process Max [325]

5133 AnIn1 Bipol — PDF page 129

Source row Property Value
1 Default: 10.00 V/20.00 mA
2 Range: 0.0–20.0 mA, 0.00–10.00 V

5134 communication — PDF page 129

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43206
2 Profibus slot/index 169/110
3 Fieldbus format UInt
4 Modbus format UInt

5133 communication — PDF page 129

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43205
2 Profibus slot/index 169/109
3 Fieldbus format Long
4 Modbus format EInt

5135 AnIn1 VaMin — PDF page 129

Source row Property Value
1 Default: 0.000
2 Range: -10000.000 – 10000.000

5135 communication — PDF page 129

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43541
2 Profibus slot/index 170/190
3 Fieldbus format Long, Speed 1=1 rpm Torque 1=1% Process val 1=0.001
4 Modbus format EInt

Manual — Analogueanddigitalinputcontrols. Collected P034 association; no extrapolation to other variants. — page 130

Manual reference: physical PDF page 130. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AnIn1 Function Max [5136]

With AnIn1 Function Max the physical maximum value

is scaled to selected process unit. The default scaling is

dependent of the selected function of AnIn1 [511]. See

Table 25.

Communication information

AnIn1 Function Value Max [5137]

With AnIn1 Function VaMax you define a user-defined

value for the signal. Only visible when user-defined is

selected in menu [5136].

Example:

Process sensor is a sensor with the following specifica-

tion:

Range:

0–3 bar

Output:

2–10 mA

Analogue input should be set up according to:

[512] AnIn1 Setup = User mA

[5131] AnIn1 Min = 2 mA

[5132] AnIn1 Max = 10 mA

[5134] AnIn1 Function Min = User-defined

[5135] AnIn1 VaMin = 0.000 bar

[5136] AnIn 1 Function Max = User-defined

[5137] AnIn1 VaMax = 3.000 bar

AnIn1 Operation [5138]

AnIn1 Filter [5139]

If the input signal is unstable (e.g. fluctuation reference

value), the filter can be used to stabilize the signal. A

change of the input signal will reach 63% on AnIn1

within the set AnIn1 Filter time. After 5 times the set

time, AnIn1 will have reached 100% of the input

change. See Fig. 108.

NOTE: With AnIn Min, AnIn Max, AnIn Function Min and

AnIn Function Max settings, loss of feedback signals

(e.g. voltage drop due to long sensor wiring) can be

compensated to ensure an accurate process control.

5136 AnIn1 FcMax. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

Shared source cells (coordinates refer to this table):

5136 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5138 AnIn1 Oper. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5138 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5137 AnIn1 VaMax. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5137 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5139 AnIn1 Filt. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5139 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

5136 AnIn1 FcMax — PDF page 130

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Max
2 Min 0 Min value
3 Max 1 Max value
4 User-defined 2 Define user value in menu [5137]

5136 communication — PDF page 130

Source row Property Value
1 Modbus Instance no/ DeviceNet no: 43207
2 Profibus slot/index 169/111
3 Fieldbus format Long, Speed/Torque 1=1 rpm or %. Other 1= 0.001
4 Modbus format EInt

5138 AnIn1 Oper — PDF page 130

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Add+
2 Add+ 0 Analogue signal is added to selected function in menu [511].
3 Sub- 1 Analogue signal is subtracted from selected function in menu [511].

5138 communication — PDF page 130

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43208
2 Profibus slot/index 169/112
3 Fieldbus format UInt
4 Modbus format UInt

5137 AnIn1 VaMax — PDF page 130

Source row Property Value
1 Default: 0.000
2 Range: -10000.000 – 10000.000

5137 communication — PDF page 130

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43551
2 Profibus slot/index 170/200
3 Fieldbus format Long, Speed 1=1 rpm Torque 1=1% Process val 1=0.001
4 Modbus format EInt

5139 AnIn1 Filt — PDF page 130

Source row Property Value
1 Default: 0.1 s
2 Range: 0.001 – 10.0 s

5139 communication — PDF page 130

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43209
2 Profibus slot/index 169/113
3 Fieldbus format Long, 1=0.001 s
4 Modbus format EInt

Manual — Analogueanddigitalinputcontrols. Collected P034 association; no extrapolation to other variants. — page 131

Manual reference: physical PDF page 131. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 108

AnIn1 Enable [513A]

Parameter for enable/disable analogue input selection

via digital inputs (DigIn set to function AnIn Select).

Communication information

AnIn2 Function [514]

Parameter for setting the function of Analogue Input 2.

Same function as AnIn1 Func [511].

AnIn2 Setup [515]

Same functions as AnIn1 Setup [512].

AnIn2 Advanced [516]

Same functions and submenus as under AnIn1

Advanced [513].

AnIn3 Function [517]

Parameter for setting the function of Analogue Input 3.

AnIn change

100%

63%

Original input signal

Filtered AnIn signal

T

5 X T

516 AnIn2 Advan

Stp A

Figure108 originalinputstep100%, filteredresponse63%atTandapproaching100%at5xT. T is5139timeconstant. Graph qualitative; noexactintermediatevalues.

515 AnIn2 Setup. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

515 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

513A AnIn1 Enabl. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

Shared source cells (coordinates refer to this table):

516 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

513A communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

514 AnIn2 Fc. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

517 AnIn3 Fc. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

514 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

517 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

515 AnIn2 Setup — PDF page 131

Source row Property Value
1 Default: 4 – 20 mA
2 Dependent on Setting of switch S2
3 Selection: Same as in menu [512].

515 communication — PDF page 131

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43212
2 Profibus slot/index 169/116
3 Fieldbus format UInt
4 Modbus format UInt

513A AnIn1 Enabl — PDF page 131

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ On
2 On 0 AnIn1 is always active
3 !DigIn 1 AnIn1 is only active if the digital input is low.
4 DigIn 2 AnIn1 is only active if the digital input is high.

516 communication — PDF page 131

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43213–43220 43542 43552
2 Profibus slot/index 169/117–124 170/191 170/201

513A communication — PDF page 131

Source row Property Value
1 Modbus Instance no/DeviceNet no: AnIn1 43210
2 Profibus slot/index AnIn1 169/114
3 Fieldbus format UInt
4 Modbus format UInt

514 AnIn2 Fc — PDF page 131

Source row Property Value
1 Default: Off
2 Selection: Same as in menu [511]

514 communication — PDF page 131

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43211
2 Profibus slot/index 169/115
3 Fieldbus format UInt
4 Modbus format UInt

517 communication — PDF page 131

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43221
2 Profibus slot/index 169/125
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Analogueanddigitalinputcontrols. Collected P034 association; no extrapolation to other variants. — page 132

Manual reference: physical PDF page 132. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AnIn3 Setup [518]

Same functions as AnIn1 Setup [512].

Communication information

AnIn3 Advanced [519]

Same functions and submenus as under AnIn1

Advanced [513].

AnIn4 Function [51A]

Parameter for setting the function of Analogue Input 4.

Same function as AnIn1 Func [511].

AnIn4 Set-up [51B]

AnIn4 Advanced [51C]

519 AnIn3 Advan

StpA

51C AnIn4 Advan

518 AnIn3 Setup. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

51B AnIn4 Setup. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

518 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

51B communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

519 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

51C communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

51A AnIn4 Fc. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

51A communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

518 AnIn3 Setup — PDF page 132

Source row Property Value
1 Default: 4–20 mA
2 Dependent on Setting of switch S3
3 Selection: Same as in menu [512].

51B AnIn4 Setup — PDF page 132

Source row Property Value
1 Default: 4-20 mA
2 Dependent on Setting of switch S4
3 Selection: Same as in menu [512].

518 communication — PDF page 132

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43222
2 Profibus slot/index 169/126
3 Fieldbus format UInt
4 Modbus format UInt

51B communication — PDF page 132

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43232
2 Profibus slot/index 169/136
3 Fieldbus format UInt
4 Modbus format UInt

519 communication — PDF page 132

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43223–43230 43543 43553
2 Profibus slot/index 169/127–169/134 170/192 170/202

51C communication — PDF page 132

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43233–43240 43544 43554
2 Profibus slot/index 169/137–144 170/193 170/203

51A AnIn4 Fc — PDF page 132

Source row Property Value
1 Default: Off
2 Selection: Same as in menu [511]

51A communication — PDF page 132

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43231
2 Profibus slot/index 169/135
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Analogueanddigitalinputcontrols. Collected P034 association; no extrapolation to other variants. — page 133

Manual reference: physical PDF page 133. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.5.2 Digital Inputs [520]

Submenu with all the settings for the digital inputs.

Digital Input 1 [521]

To select the function of the digital input.

On the standard control board there are eight digital

inputs.

If the same function is programmed for more than one

input that function will be activated according to “OR”

logic if nothing else is stated.

Communication information

NOTE: Additional inputs will become available when the

I/O option boards are connected.

NOTE: For bipol function, input RunR and RunL needs to

be active and Rotation, [219] must be set to “R+L”.

521 digitalinputselection continuation from leftcolumn. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

521 DigIn 1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

Shared source cells (coordinates refer to this table):

521 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Inputfunction/switchselection andoptionboard govern applicability. Source enumeration gaps are not filled; crosspagecontinuation retained.

521 digitalinputselection continuation from leftcolumn — PDF page 133

Source row Selection/property Enumeration or merged span Description/value
1 Pump1 Feedb 15 Feedback input pump1 for Pump/Fan control and informs about the status of the auxiliary connected pump/fan.
2 Pump2 Feedb 16 Feedback input pump 2 for Pump/Fan control and informs about the status of the auxiliary connected pump/fan.
3 Pump3 Feedb 17 Feedback input pump3 for Pump/Fan control and informs about the status of the auxiliary connected pump/fan.
4 Pump4 Feedb 18 Feedback input pump 4 for Pump/Fan control and informs about the status of the auxiliary connected pump/fan.
5 Pump5 Feedb 19 Feedback input pump5 for Pump/Fan control and informs about the status of the auxiliary connected pump/fan.
6 Pump6 Feedb 20 Feedback input pump 6 for Pump/Fan control and informs about the status of the auxiliary connected pump/fan.
7 Timer 1 21 Timer 1 Delay [643] will be activated on the rising edge of this signal.
8 Timer 2 22 Timer 2 Delay [653] will be activated on the rising edge of this signal.
9 Set Ctrl 1 23 Activates other parameter set. See Table 26 for selection possibilities.
10 Set Ctrl 2 24 Activates other parameter set. See Table 26 for selection possibilities.
11 Mot PreMag 25 Pre-magnetises the motor. Used for faster motor start.
12 Jog 26 To activate the Jog function. Gives a Run command with the set Jog speed and Direction, page 103.
13 Ext Mot Temp 27 Be aware that if there is nothing connected to the input, the AC drive will trip at “External Motor Temp” immediately. NOTE: The External Motor Temp is active low.
14 Loc/Rem 28 Activate local mode defined in [2171] and [2172].
15 AnIn select 29 Activate/deactivate analogue inputs defined in [513A], [516A], [519A] and [51CA]
16 LC Level 30 Liquid cooling low level signal. NOTE: The Liquid Cooling Level is active low.
17 Brk Ackn 31 Brake acknowledge input for Brake Fault control. Function is activated via this selec- tion see menu [33H] page 100

521 DigIn 1 — PDF page 133

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ RunL
2 Off 0 The input is not active.
3 Ext. Trip 3 Be aware that if there is nothing connected to the input, the AC drive will trip at “Exter- nal trip” immediately. NOTE: The External Trip is active low. NOTE: Activated according to “AND” logic.
4 Stop 4 Stop command according to the selected Stop mode in menu [33B]. NOTE: The Stop command is active low. NOTE: Activated according to “AND” logic.
5 Enable 5 Enable command. General start condition to run the AC drive. If made low during running the output of the AC drive is cut off immediately, causing the motor to coast to zero speed. NOTE: If none of the digital inputs are programmed to “Enable”, the internal enable signal is active. NOTE: Activated according to “AND” logic.
6 RunR 6 Run Right command (positive speed). The output of the AC drive will be a clockwise rotary field.
7 RunL 7 Run Left command (negative speed). The output of the AC drive will be a counter-clockwise rotary field.
8 Reset 9 Reset command. To reset a Trip condition and to enable the Autoreset function.
9 Preset Ctrl1 10 To select the Preset Reference.
10 Preset Ctrl2 11 To select the Preset Reference.
11 Preset Ctrl3 12 To select the Preset Reference.
12 MotPot Up 13 Increases the internal reference value according to the set AccMotPot time [333]. Has the same function as a “real” motor potentiometer, see Fig. 89.
13 MotPot Down 14 Decreases the internal reference value according to the set DecMotPot time [334]. See MotPot Up.

521 communication — PDF page 133

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43241
2 Profibus slot/index 169/145

Manual — Digital inputs andanalogueoutputs. Collected P034 association; no extrapolation to other variants. — page 134

Manual reference: physical PDF page 134. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Digital Input 2 [522] to Digital Input 8

[528]

Same function as DigIn 1 [521]. Default function for

DigIn 8 is Reset. For DigIn 3 to 7 the default function is

Off.

Communication information

Additional digital inputs [529] to [52H]

Additional digital inputs with I/O option board installed,

B1 DigIn 1 [529] - B3 DigIn 3 [52H]. B stands for board

and 1 to 3 is the number of the board which is related

to the position of the I/O option board on the option

mounting plate. The functions and selections are the

same as DigIn 1 [521].

Table 26

NOTE: To activate the parameter set selection, menu

241 must be set to DigIn.

521 communication continuation from PDF133. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Table26 parameter set control bits. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

529–52H communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

522 DigIn 2. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

522–528 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

521 communication continuation from PDF133 — PDF page 134

Source row Property Value
1 Fieldbus format UInt
2 Modbus format UInt

Table26 parameter set control bits — PDF page 134

Source row Parameter Set Set Ctrl 1 Set Ctrl 2
1 A 0 0
2 B 1 0
3 C 0 1
4 D 1 1

529–52H communication — PDF page 134

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43501–43509
2 Profibus slot/index 170/150–170/158
3 Fieldbus format Int
4 Modbus format Int

522 DigIn 2 — PDF page 134

Source row Property Value
1 Default: RunR
2 Selection: Same as in menu [521]

522–528 communication — PDF page 134

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43241–43248
2 Profibus slot/index 169/146–169/152
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Digital inputs andanalogueoutputs. Collected P034 association; no extrapolation to other variants. — page 135

Manual reference: physical PDF page 135. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.5.3 Analogue Outputs [530]

Submenu with all settings for the analogue outputs.

Selections can be made from application and AC drive

values, in order to visualize actual status. Analogue out-

puts can also be used as a mirror of the analogue

input. Such a signal can be used as:

• a reference signal for the next AC drive in a Master/

Slave configuration (see Fig. 109).

• a feedback acknowledgement of the received ana-

logue reference value.

AnOut1 Function [531]

Sets the function for the Analogue Output 1. Scale and

range are defined by AnOut1 Advanced settings [533].

Communication information

AnOut 1 Setup [532]

Preset scaling and offset of the output configuration.

NOTE: When selections AnIn1, AnIn2 …. AnIn4 is

selected, the setup of the AnOut (menu [532] or [535])

has to be set to 0-10V or 0-20mA. When the AnOut Setup

is set to e.g. 4-20mA, the mirroring is not working

correct.

531 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

532 AnOut1 Setup. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

531 AnOut1 Fc. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

532 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

531 communication — PDF page 135

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43251
2 Profibus slot/index 169/155
3 Fieldbus format UInt
4 Modbus format UInt

532 AnOut1 Setup — PDF page 135

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ 4-20mA
2 4–20mA 0 The current output has a fixed threshold (Live Zero) of 4 mA and controls the full range for the output signal. See Fig. 106.
3 0–20mA 1 Normal full current scale configuration of the output that controls the full range for the output signal. See Fig. 105.
4 User mA 2 The scale of the current controlled output that controls the full range for the output signal. Can be defined by the advanced AnOut Min and AnOut Max menus.
5 User Bipol mA 3 Sets the output for a bipolar current output, where the scale controls the range for the output signal. Scale can be defined in advanced menu AnOut Bipol.
6 0-10V 4 Normal full voltage scale configuration of the output that controls the full range for the output signal. See Fig. 105.
7 2–10V 5 The voltage output has a fixed threshold (Live Zero) of 2 V and controls the full range for the output signal. See Fig. 106.
8 User V 6 The scale of the voltage controlled output that controls the full range for the output signal. Can be defined by the advanced AnOut Min and AnOut Max menus.
9 User Bipol V 7 Sets the output for a bipolar voltage output, where the scale controls the range for the output signal. Scale can be defined in advanced menu AnOut Bipol.

531 AnOut1 Fc — PDF page 135

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Speed
2 Process Val 0 Actual process value according to Process feedback signal.
3 Speed 1 Actual speed.
4 Torque 2 Actual torque.
5 Process Ref 3 Actual process reference value.
6 Shaft Power 4 Actual shaft power.
7 Frequency 5 Actual frequency.
8 Current 6 Actual current.
9 El power 7 Actual electrical power.
10 Output volt 8 Actual output voltage.
11 DC-voltage 9 Actual DC link voltage.
12 AnIn1 10 Mirror of received signal value on AnIn1.
13 AnIn2 11 Mirror of received signal value on AnIn2.
14 AnIn3 12 Mirror of received signal value on AnIn3.
15 AnIn4 13 Mirror of received signal value on AnIn4.
16 Speed Ref 14 Actual internal speed reference Value after ramp and V/Hz.
17 Torque Ref 15 Actual torque reference value (=0 in V/Hz mode)

532 communication — PDF page 135

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43252
2 Profibus slot/index 169/156
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Digital inputs andanalogueoutputs. Collected P034 association; no extrapolation to other variants. — page 136

Manual reference: physical PDF page 136. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 109

AnOut1 Advanced [533]

With the functions in the AnOut1 Advanced menu, the

output can be completely defined according to the

application needs. The menus will automatically be

adapted to “mA” or “V”, according to the selection in

AnOut1 Setup [532].

AnOut1 Min [5331]

This parameter is automatically displayed if User mA or

User V is selected in menu AnOut 1 Setup [532]. The

menu will automatically adapt to current or voltage set-

ting according to the selected setup. Only visible if

[532] = User mA/V.

Communication information

AnOut1 Max [5332]

User V is selected in menu AnOut1 Setup [532]. The

AnOut1 Bipol [5333]

Automatically displayed if User Bipol mA or User Bipol V

is selected in menu AnOut1 Setup. The menu will

automatically show mA or V range according to the

selected function. The range is set by changing the pos-

itive maximum value; the negative value is automati-

cally adapted accordingly. Only visible if [512] = User

Bipol mA/V.

AC drive 1

Master

AC drive 2

Slave

Ref.

AnOut

533 AnOut 1 Adv

Stp A

Figure109 shows Ref. into ACdrive1 Master; AnOut frommaster feeds Ref. input ofACdrive2 Slave. This is a functional master/slave example; terminal wiring geometry remains inPDF.

5332 AnOut 1 Max. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5332 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5331 AnOut 1 Min. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5333 AnOut1Bipol. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5331 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5333 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5332 AnOut 1 Max — PDF page 136

Source row Property Value
1 Default: 20.00 mA
2 Range: 0.00–20.00 mA, 0–10.00 V

5332 communication — PDF page 136

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43254
2 Profibus slot/index 169/158
3 Fieldbus format Long, 1=0.01
4 Modbus format EInt

5331 AnOut 1 Min — PDF page 136

Source row Property Value
1 Default: 4 mA
2 Range: 0.00 – 20.00 mA, 0 – 10.00 V

5333 AnOut1Bipol — PDF page 136

Source row Property Value
1 Default: -10.00–10.00 V
2 Range: -10.00–10.00 V, -20.0–20.0 mA

5331 communication — PDF page 136

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43253
2 Profibus slot/index 169/157
3 Fieldbus format Long, 1=0.01
4 Modbus format EInt

5333 communication — PDF page 136

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43255
2 Profibus slot/index 169/159
3 Fieldbus format Long, 1=0.01
4 Modbus format EInt

Manual — Digital inputs andanalogueoutputs. Collected P034 association; no extrapolation to other variants. — page 137

Manual reference: physical PDF page 137. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AnOut1 Function Min [5334]

With AnOut1 Function Min the physical minimum value

is scaled to selected presentation. The default scaling

is dependent of the selected function of AnOut1 [531].

Table 27 shows corresponding values for the min and

max selections depending on the function of the ana-

logue output [531].

*) Fmin is dependent on the set value in menu

“Minimum Speed [341]”.

Communication information

Example

Set the AnOut function for Motorfrequency to 0Hz, set

AnOut functionMin [5334] to “User-defined” and

AnOut1 VaMin[5335] = 0.0. This results in an anlogue

output signal from 0/4 mA to 20mA:: 0Hz to Fmot.

This principle is valid for all Min to Max settings.

AnOut1 Function Value Min [5335]

With AnOut1 Function VaMin you define a user-defined

value for the signal. Only visible when user-defined is

selected in menu [5334].

AnOut1 Function Max [5336]

is dependent on the selected function of AnOut1 [531].

See Table 27.

Table 27

NOTE: It is possible to set AnOut1 up as an inverted

output signal by setting AnOut1 Min > AnOut1 Max. See

Fig. 107.

5334 AnOut1FCMin. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

5335 AnOut1VaMin. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Table27 AnOut function scaling. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5335 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5336 AnOut1FCMax. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5334 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5336 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5334 AnOut1FCMin — PDF page 137

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Min
2 Min 0 Min value
3 Max 1 Max value
4 User-defined 2 Define user value in menu [5335]

5335 AnOut1VaMin — PDF page 137

Source row Property Value
1 Default: 0.000
2 Range: -10000.000–10000.000

Table27 AnOut function scaling — PDF page 137

Source row AnOut Function Min Value Max Value
1 Process Value Process Min [324] Process Max [325]
2 Speed Min Speed [341] Max Speed [343]
3 Torque 0% Max Torque [351]
4 Process Ref Process Min [324] Process Max [325]
5 Shaft Power 0% Motor Power [223]
6 Frequency Fmin * Motor Frequency [222]
7 Current 0 A Motor Current [224]
8 El Power 0 W Motor Power [223]
9 Output Voltage 0 V Motor Voltage [221]
10 DC voltage 0 V 1000 V
11 AnIn1 AnIn1 Function Min AnIn1 Function Max
12 AnIn2 AnIn2 Function Min AnIn2 Function Max
13 AnIn3 AnIn3 Function Min AnIn3 Function Max
14 AnIn4 AnIn4 Function Min AnIn4 Function Max

5335 communication — PDF page 137

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43545
2 Profibus slot/index 170/194
3 Fieldbus format Long, Speed 1=1 rpm Torque 1=1% Process val 1=0.001
4 Modbus format EInt

5336 AnOut1FCMax — PDF page 137

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Max
2 Min 0 Min value
3 Max 1 Max value
4 User defined 2 Define user value in menu [5337]

5334 communication — PDF page 137

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43256
2 Profibus slot/index 169/160
3 Fieldbus format Long, 1=0.1 W, 0.1 Hz, 0.1 A, 0.1 V or 0.001
4 Modbus format EInt

5336 communication — PDF page 137

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43257
2 Profibus slot/index 169/161
3 Fieldbus format Long, 0.001
4 Modbus format EInt

Manual — Digital inputs andanalogueoutputs. Collected P034 association; no extrapolation to other variants. — page 138

Manual reference: physical PDF page 138. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AnOut1 Function Value Max [5337]

With AnOut1 Function VaMax you define a user-defined

value for the signal. Only visible when user-defined is

selected in menu [5334].

Communication information

AnOut2 Function [534]

Sets the function for the Analogue Output 2.

AnOut2 Setup [535]

Preset scaling and offset of the output configuration for

analogue output 2.

AnOut2 Advanced [536]

Same functions and submenus as under AnOut1

Advanced [533].

536 AnOut2 Advan

Stp A

535 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5337 AnOut1VaMax. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

5337 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

536 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

534 AnOut2 Fc. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

534 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

535 AnOut2 Setup. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digital inputs andanalogueoutputs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

535 communication — PDF page 138

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43262
2 Profibus slot/index 169/166
3 Fieldbus format UInt
4 Modbus format UInt

5337 AnOut1VaMax — PDF page 138

Source row Property Value
1 Default: 0.000
2 Range: -10000.000–10000.000

5337 communication — PDF page 138

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43555
2 Profibus slot/index 170/204
3 Fieldbus format Long, Speed 1=1 rpm Torque 1=1% Process val 1=0.001
4 Modbus format EInt

536 communication — PDF page 138

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43263–43267 43546 43556
2 Profibus slot/index 169/167–169/171 170/195 170/205

534 AnOut2 Fc — PDF page 138

Source row Property Value
1 Default: Torque
2 Selection: Same as in menu [531]

534 communication — PDF page 138

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43261
2 Profibus slot/index 169/165
3 Fieldbus format UInt
4 Modbus format UInt

535 AnOut2 Setup — PDF page 138

Source row Property Value
1 Default: 4-20mA
2 Selection: Same as in menu [532]

Manual — Digitaloutputs,relays andvirtualconnections. Collected P034 association; no extrapolation to other variants. — page 139

Manual reference: physical PDF page 139. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.5.4 Digital Outputs [540]

Submenu with all the settings for the digital outputs.

Digital Out 1 [541]

Sets the function for the digital output 1.

NOTE: The definitions described here are valid for the

active output condition.

541 digitaloutput options20–59 continuation. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

541 DigOut 1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

541 digitaloutput options20–59 continuation — PDF page 139

Source row Selection/property Enumeration or merged span Description/value
1 Max Alarm 20 The max alarm level has been reached.
2 Max PreAlarm 21 The max pre alarm level has been reached.
3 Min Alarm 22 The min alarm level has been reached.
4 Min PreAlarm 23 The min pre alarm Level has been reached.
5 LY 24 Logic output Y.
6 !LY 25 Logic output Y inverted.
7 LZ 26 Logic output Z.
8 !LZ 27 Logic output Z inverted.
9 CA 1 28 Analogue comparator 1 output.
10 !A1 29 Analogue comp 1 inverted output.
11 CA 2 30 Analogue comparator 2 output.
12 !A2 31 Analogue comp 2 inverted output.
13 CD 1 32 Digital comparator 1 output.
14 !D1 33 Digital comp 1 inverted output.
15 CD 2 34 Digital comparator 2 output.
16 !D2 35 Digital comp 2 inverted output.
17 Operation 36 Run command is active or AC drive running. The signal can be used to control the mains contactor if the AC drive is equipped with Standby supply option.
18 T1Q 37 Timer1 output
19 !T1Q 38 Timer1 inverted output
20 T2Q 39 Timer2 output
21 !T2Q 40 Timer2 inverted output
22 Sleeping 41 Sleeping function activated
23 PumpSlave1 43 Activate pump slave 1
24 PumpSlave2 44 Activate pump slave 2
25 PumpSlave3 45 Activate pump slave 3
26 PumpSlave4 46 Activate pump slave 4
27 PumpSlave5 47 Activate pump slave 5
28 PumpSlave6 48 Activate pump slave 6
29 PumpMaster1 49 Activate pump master 1
30 PumpMaster2 50 Activate pump master 2
31 PumpMaster3 51 Activate pump master 3
32 PumpMaster4 52 Activate pump master 4
33 PumpMaster5 53 Activate pump master 5
34 PumpMaster6 54 Activate pump master 6
35 All Pumps 55 All pumps are running
36 Only Master 56 Only the master is running
37 Loc/Rem 57 Local/Rem function is active
38 Standby 58 Standby supply option is active
39 PTC Trip 59 Trip when function is active

541 DigOut 1 — PDF page 139

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Ready
2 Off 0 Output is not active and constantly low.
3 On 1 Output is made constantly high, i.e. for checking circuits and trouble shooting.
4 Run 2 Running. The AC drive output is active = produces current for the motor.
5 Stop 3 The AC drive output is not active.
6 0Hz 4 The output frequency=0±0.1Hz when in Run condition.
7 Acc/Dec 5 The speed is increasing or decreasing along the acc. ramp dec. ramp.
8 At Process 6 The output = Reference.
9 At Max spd 7 The frequency is limited by the Maximum Speed.
10 No Trip 8 No Trip condition active.
11 Trip 9 A Trip condition is active.
12 AutoRst Trip 10 Autoreset trip condition active.
13 Limit 11 A Limit condition is active.
14 Warning 12 A Warning condition is active.
15 Ready 13 The AC drive is ready for operation and to accept a start command. This means that the AC drive is powered up and healthy.
16 T= T lim 14 The torque is limited by the torque limit function.
17 I>I nom 15 The output current is higher than the motor nominal current [224], reduced according to Motor ventilation [228], see Fig. 73.
18 Brake 16 The output is used to control a mechanical brake.
19 Sgnl<Offset 17 One of the AnIn input signals is lower than 75% of the threshold level.
20 Alarm 18 The max or min alarm level has been reached.
21 Pre-Alarm 19 The max or min pre alarm level has been reached.

Manual — Digitaloutputs,relays andvirtualconnections. Collected P034 association; no extrapolation to other variants. — page 140

Manual reference: physical PDF page 140. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Communication information

541 digitaloutput options60–97 continuation. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

541 digitaloutput option98 continuation. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

541 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

541 digitaloutput options60–97 continuation — PDF page 140

Source row Selection/property Enumeration or merged span Description/value
1 PT100 Trip 60 Trip when function is active
2 Overvolt 61 Overvoltage due to high main voltage
3 Overvolt G 62 Overvoltage due to generation mode
4 Overvolt D 63 Overvoltage due to deceleration
5 Acc 64 Acceleration along the acc. ramp
6 Dec 65 Deceleration along the dec. ramp
7 I2t 66 I2t limit protection active
8 V-Limit 67 Overvoltage limit function active
9 C-Limit 68 Overcurrent limit function active
10 Overtemp 69 Over temperature warning
11 Low voltage 70 Low voltage warning
12 DigIn 1 71 Digital input 1
13 DigIn 2 72 Digital input 2
14 DigIn 3 73 Digital input 3
15 DigIn 4 74 Digital input 4
16 DigIn 5 75 Digital input 5
17 DigIn 6 76 Digital input 6
18 DigIn 7 77 Digital input 7
19 DigIn 8 78 Digital input 8
20 ManRst Trip 79 Active trip that needs to be manually reset
21 Com Error 80 Serial communication lost
22 External Fan 81 The AC drive requires external cooling. Internal fans are active.
23 LC Pump 82 Activate liquid cooling pump
24 LC HE Fan 83 Activate liquid cooling heat exchanger fan
25 LC Level 84 Liquid cooling low level signal active
26 Run Right 85 Positive speed (>0.5%), i.e. forward/ clockwise direction.
27 Run Left 86 Negative speed (≤0.5%), i.e. reverse counter clockwise direction.
28 Com Active 87 Fieldbus communication active.
29 Brk Fault 88 Tripped on brake fault (not released)
30 BrkNotEngage 89 Warning and continued operation (keep torque) due to Brake not engaged during stop.
31 Option 90 Failure occured in built-in option board.
32 CA3 91 Analogue comparator 3 output
33 !A3 92 Analogue comparator 3 inverted output
34 CA4 93 Analogue comparator 4 output
35 !A4 94 Analogue comparator 4 inverted output
36 CD3 95 Digital comparator 3 output
37 !D3 96 Digital comparator 3 inverted output
38 CD4 97 Digital comparator 4 output

541 digitaloutput option98 continuation — PDF page 140

Source row Selection/property Enumeration or merged span Description/value
1 !D4 98 Digital comparator 4 inverted output

541 communication — PDF page 140

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43271
2 Profibus slot/index 169/175
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Digitaloutputs,relays andvirtualconnections. Collected P034 association; no extrapolation to other variants. — page 141

Manual reference: physical PDF page 141. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Digital Out 2 [542]

Sets the function for the digital output 2.

Communication information

11.5.5 Relays [550]

Submenu with all the settings for the relay outputs. The

relay mode selection makes it possible to establish a

“fail safe” relay operation by using the normal closed

contact to function as the normal open contact.

Relay 1 [551]

Sets the function for the relay output 1. Same function

as digital output 1 [541] can be selected.

Relay 2 [552]

Sets the function for the relay output 2.

Relay 3 [553]

Sets the function for the relay output 3.

Board Relay [554] to [55C]

These additional relays are only visible if an I/O option

board is fitted in slot 1, 2, or 3. The outputs are named

B1 Relay 1–3, B2 Relay 1–3 and B3 Relay 1–3. B

stands for board and 1–3 is the number of the board

which is related to the position of the I/O option board

on the option mounting plate.

NOTE: The definitions described here are valid for the

active output condition.

NOTE: Additional relays will become available when I/O

option boards are connected. Maximum 3 boards with 3

relays each.

NOTE: Visible only if optional board is detected or if any

input/output is activated.

542 DigOut2. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

552 Relay 2. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

542 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

552 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

553 Relay 3. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

553 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

551 Relay 1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

551 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

542 DigOut2 — PDF page 141

Source row Property Value
1 Default: Brake
2 Selection: Same as in menu [541]

552 Relay 2 — PDF page 141

Source row Property Value
1 Default: Run
2 Selection: Same as in menu [541]

542 communication — PDF page 141

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43272
2 Profibus slot/index 169/176
3 Fieldbus format UInt
4 Modbus format UInt

552 communication — PDF page 141

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43274
2 Profibus slot/index 169/178
3 Fieldbus format UInt
4 Modbus format UInt

553 Relay 3 — PDF page 141

Source row Property Value
1 Default: Off
2 Selection: Same as in menu [541]

553 communication — PDF page 141

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43275
2 Profibus slot/index 169/179
3 Fieldbus format UInt
4 Modbus format UInt

551 Relay 1 — PDF page 141

Source row Property Value
1 Default: Trip
2 Selection: Same as in menu [541]

551 communication — PDF page 141

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43273
2 Profibus slot/index 169/177
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Digitaloutputs,relays andvirtualconnections. Collected P034 association; no extrapolation to other variants. — page 142

Manual reference: physical PDF page 142. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Communication information

Relay Advanced [55D]

This function makes it possible to ensure that the relay

will also be closed when the AC drive is malfunctioning

or powered down.

Example

A process always requires a certain minimum flow. To

control the required number of pumps by the relay

mode NC, the e.g. the pumps can be controlled nor-

mally by the pump control, but are also activated when

the AC drive is tripped or powered down.

Relay 1 Mode [55D1]

Relay Modes [55D2] to [55DC]

Same function as for relay 1 mode [55D1].

11.5.6 Virtual Connections [560]

Functions to enable eight internal connections of

comparator, timer and digital signals, without occupy-

ing physical digital in/outputs. Virtual connections are

used to wireless connection of a digital output function

to a digital input function. Available signals and control

functions can be used to create your own specific func-

tions.

Example of start delay

The motor will start in RunR 10 seconds after DigIn1

gets high. DigIn1 has a time delay of 10 s.

Virtual Connection 1 Destination [561]

With this function the destination of the virtual connec-

tion is established. When a function can be controlled

by several sources, e.g. VC destination or Digital Input,

the function will be controlled in conformity with “OR

logic”. See DigIn for descriptions of the different selec-

55D Relay Adv

StpA

NOTE: When a digital input and a virtual destination are

set to the same function, this function will act as an OR

logic function.

554–55C communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Virtualconnection startdelay example. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

55D1 Relay Mode. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

561 VIO 1 Dest. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

55D1 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

561 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

55D2–55DC communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

554–55C communication — PDF page 142

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43511–43519
2 Profibus slot/index 170/160–170/168
3 Fieldbus format UInt
4 Modbus format UInt

Virtualconnection startdelay example — PDF page 142

Source row Menu Parameter Setting
1 [521] DigIn1 Timer 1
2 [561] VIO 1 Dest RunR
3 [562] VIO 1 Source T1Q
4 [641] Timer1 Trig DigIn 1
5 [642] Timer1 Mode Delay
6 [643] Timer1 Delay 0:00:10

55D1 Relay Mode — PDF page 142

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ N.O
2 N.O 0 The normal open contact of the relay will be activated when the function is active.
3 N.C 1 The normally closed contact of the relay will act as a normal open contact. The contact will be opened when function is not active and closed when function is active.

561 VIO 1 Dest — PDF page 142

Source row Property Value
1 Default: Off
2 Selection: Same selections as for Digital Input 1, menu [521].

55D1 communication — PDF page 142

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43276
2 Profibus slot/index 169/180
3 Fieldbus format UInt
4 Modbus format UInt

561 communication — PDF page 142

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43281
2 Profibus slot/index 169/185
3 Fieldbus format UInt
4 Modbus format UInt

55D2–55DC communication — PDF page 142

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43277–43278, 43521–43529
2 Profibus slot/index 169/181–169/182, 170/170–170/178
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Digitaloutputs,relays andvirtualconnections. Collected P034 association; no extrapolation to other variants. — page 143

Manual reference: physical PDF page 143. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Virtual Connection 1 Source [562]

With this function the source of the virtual connection

is defined. See DigOut 1 for description of the different

selections.

Communication information

Virtual Connections 2-8 [563] to [56G]

Same function as virtual connection 1 [561] and [562].

Communication information for virtual connections 2-8

Destination.

Source.

11.6 Logical Functions and

Timers [600]

With the Comparators, Logic Functions and Timers,

conditional signals can be programmed for control or

signalling features. This gives you the ability to compare

different signals and values in order to generate moni-

toring/controlling features.

11.6.1 Comparators [610]

The comparators available make it possible to monitor

different internal signals and values, and visualize via

digital relay outputs, when a specific value or status is

reached or established.

Analogue comparators [611] - [614]

There are 4 analogue comparators that compare any

available analogue value (including the analogue refer-

ence inputs) with two adjustable levels. The two levels

available are Level HI and Level LO. There are two ana-

logue comparator types selectable, an analogue com-

parator with hysteresis and an analogue window

comparator.

The analogue hysteresis type comparator uses the two

available levels to create a hysteresis for the compara-

tor between setting and resetting the output. This func-

tion gives a clear difference in switching levels, which

lets the process adapt until a certain action is started.

With such a hysteresis, even an unstable analogue sig-

nal can be monitored without getting a nervous compa-

rator output signal. Another feature is the possibility to

get a fixed indication that a certain level has been

passed. The comparator can latch by setting Level LO to

a higher value than Level HI.

The analogue window comparator uses the two availa-

ble levels to define the window in which the analogue

value should be within for setting the comparator out-

put.

The input analogue value of the comparator can also

be selected as bipolar, i.e. treated as signed value or

unipolar, i.e. treated as absolute value.

Refer to Fig. 114, page 145 where these functions are

illustrated.

Digital comparators [615]

There are 4 digital comparators that compare any avail-

able digital signal.

The output signals of these comparators can be logi-

cally tied together to yield a logical output signal.

All the output signals can be programmed to the digital

or relay outputs or used as a source for the virtual con-

nections [560].

562 VIO 1 Source. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

562 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

563–56F destinations communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

564–56G sources communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Digitaloutputs,relays andvirtualconnections. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

562 VIO 1 Source — PDF page 143

Source row Property Value
1 Default: Off
2 Selection: Same as for menu [541].

562 communication — PDF page 143

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43282
2 Profibus slot/index 169/186
3 Fieldbus format UInt
4 Modbus format UInt

563–56F destinations communication — PDF page 143

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43283, 43285, 43287, 43289, 43291, 43293, 43295
2 Profibus slot/index 169/ 187, 189, 191, 193, 195, 197, 199
3 Fieldbus format UInt
4 Modbus format UInt

564–56G sources communication — PDF page 143

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43284, 43286, 43288, 43290, 43292, 43294, 43296
2 Profibus slot/index 169/ 188, 190, 192, 194, 196, 198, 200
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Analogueanddigitalcomparators. Collected P034 association; no extrapolation to other variants. — page 144

Manual reference: physical PDF page 144. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

CA1 Setup [611]

Analogue comparator 1, parameter group.

Analogue Comparator 1, Value [6111]

Selection of the analogue value for Analogue Compara-

tor 1 (CA1).

Analogue comparator 1 compares the selectable ana-

logue value in menu [6111] with the constant Level HI

in menu [6112] and constant Level LO in menu [6113].

If Bipolar type[6115] input signal is selected then the

comparison is made with sign otherwise if unipolar

selected then comparison is made with absolute val-

ues.

For Hysteresis comparator type [6114], when the value

exceeds the upper limit level high, the output signal

CA1 is set high and !A1 low, see Fig. 110. When the

value decreases below the lower limit, the output signal

CA1 is set low and !A1 high.

Fig. 110 Analogue comparator type Hysteresiss

For Window comparator type [6114], when the value is

between the lower and upper levels, the output signal

value CA1 is set high and !A1 low, see Fig 113. When

the value is outside the band of lower and upper levels,

the output CA1 is set low and !A1 high.

Fig. 111 Analogue comparator type “Window”

The output signal can be programmed as a virtual

connection source and to the digital or relay outputs.

Communication information

(NG_06-F125)

Signal:CA1

Analogue value:

Menu [6111]

Adjustable Level HI.

Menu [6112]

Adjustable Level LO.

Menu [6113]

Level High [6112]

An Value [6111]

Level Low [6113]

AND

Signal

CA1

Figure110 Analogvalue6111 andadjustableHI6112/LO6113 feedhysteresiscomparator, SignalCA1. Figure111 uses two comparators fromLevelHigh6112,AnValue6111,LevelLow6113 combinedAND toSignalCA1. Literalplotlabels,notanindependentcircuitdesign.

6111 CA1 Value. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

6111 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6111 CA1 Value — PDF page 144

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Speed
2 Process Val 0 Set by Process settings [321] and [322]
3 Speed 1 rpm
4 Torque 2 %
5 Shaft Power 3 kW
6 El Power 4 kW
7 Current 5 A
8 Output Volt 6 V
9 Frequency 7 Hz
10 DC Voltage 8 V
11 Heatsink Tmp 9 °C
12 PT100_1 10 °C
13 PT100_2 11 °C
14 PT100_3 12 °C
15 Energy 13 kWh
16 Run Time 14 h
17 Mains Time 15 h
18 AnIn1 16 %
19 AnIn2 17 %
20 AnIn3 18 %
21 AnIn4 19 %
22 Process Ref 20 Set by Process settings [321] and [322]
23 Process Err 21 ⟦null: no independent source value⟧

6111 communication — PDF page 144

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43401
2 Profibus slot/index 170/50
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Analogueanddigitalcomparators. Collected P034 association; no extrapolation to other variants. — page 145

Manual reference: physical PDF page 145. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example

Create automatic RUN/STOP signal via the analogue

reference signal. Analogue current reference signal, 4-

20 mA, is connected to Analogue Input 1. AnIn1 Setup,

menu [512] = 4-20 mA and the threshold is 4 mA. Full

scale (100%) input signal on AnIn 1 = 20 mA. When the

reference signal on AnIn1 increases 80% of the thresh-

old (4 mA x 0.8 = 3.2 mA), the AC drive will be set in

RUN mode. When the signal on AnIn1 goes below 60%

of the threshold (4 mA x 0.6 = 2.4 mA) the AC drive is

set to STOP mode. The output of CA1 is used as a vir-

tual connection source that controls the virtual connec-

tion destination RUN.

Fig. 112

1 2

20 mA

4 mA

3.2 mA

2.4 mA

CA1 Level HI = 16%

CA1 Level LO = 12%

Max speed

Reference signal AnIn1

CA1

Mode

RUN

STOP

T

t

Figure112 referenceAnIn1 plotmark20mA/4mA/3.2mA/2.4mA,CA1HI16%,LO12%;belowareCA1andModeRUN/STOP traces,events1,2,3,T,4,5,6. Modeplotrisesat2,fallsat6; event1tabletextmodeRUN conflictswithlowplot. No extraeventtimes inferred.

Comparator runstop example settings. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Figure112 event descriptions. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Comparator runstop example settings — PDF page 145

Source row Menu Function Setting
1 511 AnIn1 Function Process reference
2 512 AnIn1 Set-up 4-20 mA, threshold is 4 mA
3 341 Min Speed 0
4 343 Max Speed 1500
5 6111 CA1 Value AnIn1
6 6112 CA1 Level HI 16% (3.2mA/20mA x 100%)
7 6113 CA1 Level LO 12% (2.4mA/20mA x 100%)
8 6114 CA1 Type Hysteresis
9 561 VIO 1 Dest RunR
10 562 VIO 1 Source CA1
11 215 Run/Stp Ctrl Remote

Figure112 event descriptions — PDF page 145

Source row No. Description
1 1 The reference signal passes the Level LO value from below (positive edge), the comparator CA1 output stays low, mode=RUN.
2 2 The reference signal passes the Level HI value from below (positive edge), the comparator CA1 output is set high, mode=RUN.
3 3 The reference signal passes the threshold level of 4 mA, the motor speed will now follow the reference signal.
4 T During this period the motor speed will follow the reference signal.
5 4 The reference signal reaches the threshold level, motor speed is 0 rpm, mode = RUN.
6 5 The reference signal passes the Level HI value from above (negative edge), the comparator CA1 output stays high, mode =RUN.
7 6 The reference signal passes the Level LO value from above (negative edge), the comparator CA1 out- put=STOP.

Manual — Analogueanddigitalcomparators. Collected P034 association; no extrapolation to other variants. — page 146

Manual reference: physical PDF page 146. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Analogue Comparator 1,

Level High [6112]

Sets the analogue comparator high level, with range

according to the selected value in menu [6111].

Min/Max setting range for menu [6112]

Communication information

NOTE: If Bipolar selected [6115] then Min value is equal

to -Max in the table.

6112 CA1 Level HI. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6112 mode-dependent MinMax range. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

6112 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6112 CA1 Level HI — PDF page 146

Source row Property Value
1 Default: 300 rpm
2 Range: See min/max in table below.

6112 mode-dependent MinMax range — PDF page 146

Source row Mode Min Max Decimals
1 Process Val Set by Process settings [321] and [322] ⟦null: no independent source value⟧ 3
2 Speed, rpm 0 Max speed 0
3 Torque, % 0 Max torque 0
4 Shaft Power, kW 0 Motor P x4 n 0
5 El Power, kW 0 Motor P x4 n 0
6 Current, A 0 Motor I x4 n 1
7 Output volt, V 0 1000 1
8 Frequency, Hz 0 400 1
9 DC voltage, V 0 1250 1
10 Heatsink temp, °C 0 100 1
11 PT 100_1_2_3, °C -100 300 1
12 Energy, kWh 0 1000000 0
13 Run time, h 0 65535 0
14 Mains time, h 0 65535 0
15 AnIn 1-4% 0 100 0
16 Process Ref Set by Process settings [321] and [322] ⟦null: no independent source value⟧ 3
17 Process Err Set by Process settings [321] and [322] ⟦null: no independent source value⟧ 3

6112 communication — PDF page 146

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43402
2 Profibus slot/index 170/51
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

Manual — Analogueanddigitalcomparators. Collected P034 association; no extrapolation to other variants. — page 147

Manual reference: physical PDF page 147. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example

This example describes, both for hysteresis and window

type comparator, the normal use of the constant level

high and low.

Fig. 113

t

MAX

speed

[343]

CA1 Level HI [6112]

CA1 Level LO [6113]

Hysteresis

Output

CA1

High

Low

[6114] Hysteresis

[6114] Window

,

Figure113 exampleHI300rpm/LO200rpm,maxspeed343=1500insettings. Hysteresisoutputhighafter2until4andafter6until8;Windowoutputhighbetween1–2,3–4,5–6,7–8. Eventtablearrowsequencepreservedincells. Figureaxisbreakdoesnotprovideadditionalnumericpointvalues.

Figure113 events and hysteresis/window state changes. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Comparator example settings. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Figure113 events and hysteresis/window state changes — PDF page 147

Source row No. Description Hysteresis Window
1 1 The reference signal passes the Level LO value from below (positive edge), the comparator CA1 does not change, output stays low. — ↑
2 2 The reference signal passes the Level HI value from below (positive edge), the comparator CA1 output is set high. ↑ ↓
3 3 The reference signal passes the Level HI value from above (negative edge), the comparator CA1 does not change, output stays high. — ↑
4 4 The reference signal passes the Level LO value from above (negative edge), the comparator CA1 is reset, output is set low. ↓ ↓
5 5 The reference signal passes the Level LO value from below (positive edge), the comparator CA1 does not change, output stays low. — ↑
6 6 The reference signal passes the Level HI value from below (positive edge), the comparator CA1 output is set high. ↑ ↓
7 7 The reference signal passes the Level HI value from above (negative edge), the comparator CA1 does not change, output stays high. — ↑
8 8 The reference signal passes the Level LO value from above (negative edge), the comparator CA1 is reset, output is set low. ↓ ↓

Comparator example settings — PDF page 147

Source row Menu Function Setting
1 343 Max Speed 1500
2 6111 CA1 Value Speed
3 6112 CA1 Level HI 300 rpm
4 6113 CA1 Level LO 200 rpm
5 6114 CA1 Type Hysteresis
6 561 VC1 Dest Timer 1
7 562 VC1 Source CA1

Manual — Analogueanddigitalcomparators. Collected P034 association; no extrapolation to other variants. — page 148

Manual reference: physical PDF page 148. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Analogue Comparator 1,

Level Low [6113]

Sets the analogue comparator low level, with unit and

range according to the selected value in menu [6111]. .

Communication information

Analogue Comparator 1, Type [6114]

Selects the analogue comparator type, i.e. Hysteresis or

Window type. See Fig. 114 and Fig. 115.

Analogue Comparator 1, Polarity [6115]

Selects how the selected value in [6111] should be

handled prior to the the analogue comparator , i.e. as

absolute value or handled with sign. See Fig. 114

Example

See Fig. 114 and Fig. 115 for different principle

functionality of comparator features 6114 and 6115.

Fig. 114 Principle functionality of comparator features for

“Type [6114] = Hysteresis ” and “Polar [6115]”.

Type [6114]= Hysteresis

[6115] Unipolar

[6115] Bipolar

[6112] HI > 0

[6113] LO > 0

[6113] LO < 0

[6112] HI < 0

An.Value

[6111]

CA1

Figure114 Type6114Hysteresis usesfour signcases:UnipolarHI>0LO>0;BipolarHI>0LO>0;BipolarHI>0LO<0;BipolarHI<0LO<0. AxesCA1andAn.Value6111; thresholdsmarkedHI/LOandnegativecounterpartswherevisible. No missingthresholdvalues inferred.

6115 CA1 Polar. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6113 CA1 Level LO. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6113 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6115 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6114 CA1 Type. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6114 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6115 CA1 Polar — PDF page 148

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ Unipolar
2 Unipolar 0 Absolute value of [6111] used
3 Bipolar 1 Signed value of [6111] used

6113 CA1 Level LO — PDF page 148

Source row Property Value
1 Default: 200 rpm
2 Range: Range as [6112].

6113 communication — PDF page 148

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43403
2 Profibus slot/index 170/52
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

6115 communication — PDF page 148

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43486
2 Profibus slot/index 170/135
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

6114 CA1 Type — PDF page 148

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ Hysteresis
2 Hysteresis 0 Hysteresis type comparator
3 Window 1 Window type comparator

6114 communication — PDF page 148

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43481
2 Profibus slot/index 170/130
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

Manual — Analogueanddigitalcomparators. Collected P034 association; no extrapolation to other variants. — page 149

Manual reference: physical PDF page 149. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 115 Principle functionality of comparator features for

“Type [6114] =Window ” and “Polar [6115]”.

CA2 Setup [612]

Analogue comparator 2, parameter group.

Analogue Comparator 2, Value [6121]

Function is identical to analogue comparator 1,

value [6111].

Communication information

Analogue Comparator 2,

Level High [6122]

level high [6112].

Level Low [6123]

level low [6113].

NOTE: When “Unipolar “ is selected, absolute value of

signal is used.

NOTE: When “Bipolar” is selected in [6115] then:

  1. Functionality is not symmetrical and

  2. Ranges for high/low are bipolar

Type [6114] = Window

[6115] Unipolar

[6115] Bipolar

[6112] HI > 0

[6113] LO > 0

[6113] LO < 0

[6112] HI < 0

An.Value

[6111]

CA1

Figure115 Type6114Window shows samefour signcases asFigure114, withdifferentwindowstatecurves. Unipolarsymmetricalabsolutevalue behaviour andbipolarsignednon-symmetry remainas sourceprose; no interpolated threshold values.

6122 CA2 Level HI. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6122 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6123 CA2 Level LO. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6121 CA2 Value. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6123 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6121 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6122 CA2 Level HI — PDF page 149

Source row Property Value
1 Default: 20%
2 Range: Enter a value for the high level.

6122 communication — PDF page 149

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43405
2 Profibus slot/index 170/54
3 Fieldbus format Long 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

6123 CA2 Level LO — PDF page 149

Source row Property Value
1 Default: 10%
2 Range: Enter a value for the low level.

6121 CA2 Value — PDF page 149

Source row Property Value
1 Default: Torque
2 Selections: Same as in menu [6111]

6123 communication — PDF page 149

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43406
2 Profibus slot/index 170/55
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

6121 communication — PDF page 149

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43404
2 Profibus slot/index 170/53
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Analogueanddigitalcomparators. Collected P034 association; no extrapolation to other variants. — page 150

Manual reference: physical PDF page 150. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Analogue Comparator 2, Type [6124]

Function is identical to analogue comparator 1,

Type [6114].

Communication information

Analogue Comparator 2, Polar [6125]

Polar [6115].

CA3 Setup [613]

Analogue comparators 3, parameter group.

Analogue Comparator 3, Value [6131]

value [6111]

Analogue Comparator 3,

Level High [6132]

level high [6112].

6124 CA2 Type. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6131 CA3 Value. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6124 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6131 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6125 CA2 Polar. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6132 CA3 Level HI. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6132 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6125 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Adjacent source context — repeated to preserve continuation:

6124 CA2 Type — PDF page 150

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ Hysteresis
2 Hysteresis 0 Hysteresis type comparator
3 Window 1 Window type comparator

6131 CA3 Value — PDF page 150

Source row Property Value
1 Default: Process Value
2 Selections: Same as in menu [6111]

6124 communication — PDF page 150

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43482
2 Profibus slot/index 170/131
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

6131 communication — PDF page 150

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43471
2 Profibus slot/index 170/120
3 Fieldbus format UInt
4 Modbus format UInt

6125 CA2 Polar — PDF page 150

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ Unipolar
2 Unipolar 0 Absolute value of [6111] used
3 Bipolar 1 Signed value of [6111] used

6132 CA3 Level HI — PDF page 150

Source row Property Value
1 Default: 300rpm
2 Range: Enter a value for the high level.

6132 communication — PDF page 150

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43472
2 Profibus slot/index 170/121
3 Fieldbus format Long 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

6125 communication — PDF page 150

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43487
2 Profibus slot/index 170/136
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

Manual — Analogueanddigitalcomparators. Collected P034 association; no extrapolation to other variants. — page 151

Manual reference: physical PDF page 151. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Analogue Comparator 3,

Level Low [6133]

Function is identical to analogue comparator 1,

level low [6113].

Communication information

Analogue Comparator, 3 Type [6134]

Function is identical to analogue comparator 1, level

Type [6114]

Analogue Comparator 3, Polar [6135]

Polar [6115].

CA4 Setup [614]

Analogue comparators 4, parameter group.

Analogue Comparator 4, Value [6141]

value [6111].

6135 CA3 Polar. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6133 CA3 Level LO. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6133 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6135 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6134 CA3 Type. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6141 CA4 Value. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6134 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6141 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Adjacent source context — repeated to preserve continuation:

6135 CA3 Polar — PDF page 151

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ Unipolar
2 Unipolar 0 Absolute value of [6111] used
3 Bipolar 1 Signed value of [6111] used

6133 CA3 Level LO — PDF page 151

Source row Property Value
1 Default: 200 rpm
2 Range: Enter a value for the low level.

6133 communication — PDF page 151

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43473
2 Profibus slot/index 170/122
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

6135 communication — PDF page 151

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43488
2 Profibus slot/index 170/137
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

6134 CA3 Type — PDF page 151

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ Hysteresis
2 Hysteresis 0 Hysteresis type comparator
3 Window 1 Window type comparator

6141 CA4 Value — PDF page 151

Source row Property Value
1 Default: Process Error
2 Selections: Same as in menu [6111]

6134 communication — PDF page 151

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43483
2 Profibus slot/index 170/132
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

6141 communication — PDF page 151

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43474
2 Profibus slot/index 170/123
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Analogueanddigitalcomparators. Collected P034 association; no extrapolation to other variants. — page 152

Manual reference: physical PDF page 152. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Analogue Comparator 4, Level High

[6142]

Function is identical to analogue comparator 1 level

high [6112].

Communication information

Analogue Comparator 4,

Level Low [6143]

Function is identical to analogue comparator 1, level

low [6113].

Analogue Comparator 4, Type [6144]

Type [6114]

Analogue Comparator 4, Polar [6145]

Function is identical to analogue comparator 1,

Polar [6115]

6144 CA4 Type. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6142 CA4 Level HI. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6142 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6144 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6145 CA4 Polar. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6143 CA4 Level LO. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6145 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6143 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6144 CA4 Type — PDF page 152

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ Window
2 Hysteresis 0 Hysteresis type comparator
3 Window 1 Window type comparator

6142 CA4 Level HI — PDF page 152

Source row Property Value
1 Default: 100rpm
2 Range: Enter a value for the high level.

6142 communication — PDF page 152

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43475
2 Profibus slot/index 170/124
3 Fieldbus format Long 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

6144 communication — PDF page 152

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43484
2 Profibus slot/index 170/133
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

6145 CA4 Polar — PDF page 152

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦blank source cell⟧ Bipolar
2 Unipolar 0 Absolute value of [6111] used
3 Bipolar 1 Signed value of [6111] used

6143 CA4 Level LO — PDF page 152

Source row Property Value
1 Default: -100 rpm
2 Range: Enter a value for the low level.

6145 communication — PDF page 152

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43489
2 Profibus slot/index 170/138
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

6143 communication — PDF page 152

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43476
2 Profibus slot/index 170/125
3 Fieldbus format Long, 1=1 W, 0.1 A, 0.1 V, 0.1 Hz, 0.1°C, 1 kWh, 1H, 1%, 1 rpm or 0.001 via process value
4 Modbus format EInt

Manual — Analogueanddigitalcomparators. Collected P034 association; no extrapolation to other variants. — page 153

Manual reference: physical PDF page 153. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Digital comparator Setup [615]

Digital comparators, parameter group.

Digital Comparator 1 [6151]

Selection of the input signal for digital comparator 1

(CD1).

The output signal CD1 is set high if the selected input

signal is active. See Fig. 116.

The output signal can be programmed to the digital or

relay outputs or used as a source for the virtual connec-

tions [560].

Fig. 116 Digital comparator

Communication information

Digital Comparator 2 [6152]

Function is identical to digital comparator 1 [6151].

Digital Comparator 3 [6153]

Digital Comparator 4 [6154]

+

-

(NG_06-F126)

Signal: CD1

Digital signal:

Menu [6151]

DComp 1

Figure116 digitalsignal menu6151 feedsDComp1 andSignalCD1; plus/minus signs are comparatorgraphiclabels, notseparatelywiredterminalnumbers.

6153 CD 3. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6153 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6154 CD 4. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6151 CD1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6154 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6151 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6152 CD 2. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6152 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Analogueanddigitalcomparators. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

6153 CD 3 — PDF page 153

Source row Property Value
1 Default: Trip
2 Selection: Same selections as for DigOut 1 [541].

6153 communication — PDF page 153

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43477
2 Profibus slot/index 170/126
3 Fieldbus format UInt
4 Modbus format UInt

6154 CD 4 — PDF page 153

Source row Property Value
1 Default: Ready
2 Selection: Same selections as for DigOut 1 [541].

6151 CD1 — PDF page 153

Source row Property Value
1 Default: Run
2 Selection: Same selections as for DigOut 1 [541].

6154 communication — PDF page 153

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43478
2 Profibus slot/index 170/127
3 Fieldbus format UInt
4 Modbus format UInt

6151 communication — PDF page 153

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43407
2 Profibus slot/index 170/56
3 Fieldbus format UInt
4 Modbus format UInt

6152 CD 2 — PDF page 153

Source row Property Value
1 Default: DigIn 1
2 Selection: Same selections as for DigOut 1 [541].

6152 communication — PDF page 153

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43408
2 Profibus slot/index 170/57
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Logicoutputs andtimers. Collected P034 association; no extrapolation to other variants. — page 154

Manual reference: physical PDF page 154. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.6.2 Logic Output Y [620]

By means of an expression editor, the comparator sig-

nals can be logically combined into the Logic Y function.

The expression editor has the following features:

• The following signals can be used:

CA1, CA2, CD1, CD2 or LZ (or LY)

• The following signals can be inverted:

!A1, !A2, !D1, !D2, or !LZ (or !LY)

• The following logical operators are available:

"+" : OR operator

"&" : AND operator

"^" : EXOR operator

Expressions according to the following truth table can

be made:

The output signal can be programmed to the digital or

relay outputs or used as a Virtual Connection Source

[560].

Communication information

The expression must be programmed by means of the

menus [621] to [625].

Example:

Broken belt detection for Logic Y

This example describes the programming for a so-

called “broken belt detection” for fan applications.

The comparator CA1 is set for frequency>10Hz.

The comparator !A2 is set for load < 20%.

The comparator CD1 is set for Run.

The 3 comparators are all AND-ed, given the “broken

belt detection”.

In menus [621]-[625] expression entered for Logic Y is

visible.

Set menu [621] to CA1

Set menu [622] to &

Set menu [623] to !A2

Set menu [624] to &

Set menu [625] to CD1

Menu [620] now holds the expression for Logic Y:

CA1&!A2&CD1

which is to be read as:

(CA1&!A2)&CD1

620 LOGIC Y

Stp

NOTE: Set menu [624] to "." to finish the expression

when only two comparators are required for Logic Y.

Logic operator truth table. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

620 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Logic operator truth table — PDF page 154

Source row A B & (AND) + (OR) ^(EXOR)
1 0 0 0 0 0
2 0 1 0 1 1
3 1 0 0 1 1
4 1 1 1 1 0

620 communication — PDF page 154

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31035
2 Profibus slot/index 121/179
3 Fieldbus format Long
4 Modbus format Text

Manual — Logicoutputs andtimers. Collected P034 association; no extrapolation to other variants. — page 155

Manual reference: physical PDF page 155. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Y Comp 1 [621]

Selects the first comparator for the logic Y function.

Communication information

Y Operator 1 [622]

Selects the first operator for the logic Y function.

Y Comp 2 [623]

Selects the second comparator for the logic Y function.

621 Y Comp 1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

622 Y Operator 1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

622 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

623 Y Comp 2. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

623 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

621 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

621 Y Comp 1 — PDF page 155

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ CA1
2 CA1 0 ⟦blank source cell⟧
3 !A1 1 ⟦blank source cell⟧
4 CA2 2 ⟦blank source cell⟧
5 !A2 3 ⟦blank source cell⟧
6 CD1 4 ⟦blank source cell⟧
7 !D1 5 ⟦blank source cell⟧
8 CD2 6 ⟦blank source cell⟧
9 !D2 7 ⟦blank source cell⟧
10 LZ/LY 8 ⟦blank source cell⟧
11 !LZ/!LY 9 ⟦blank source cell⟧
12 T1 10 ⟦blank source cell⟧
13 !T1 11 ⟦blank source cell⟧
14 T2 12 ⟦blank source cell⟧
15 !T2 13 ⟦blank source cell⟧
16 CA3 14 ⟦blank source cell⟧
17 !A3 15 ⟦blank source cell⟧
18 CA4 16 ⟦blank source cell⟧
19 !A4 17 ⟦blank source cell⟧
20 CD3 18 ⟦blank source cell⟧
21 !D3 19 ⟦blank source cell⟧
22 CD4 20 ⟦blank source cell⟧
23 !D4 21 ⟦blank source cell⟧

622 Y Operator 1 — PDF page 155

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ &
2 & 1 &=AND
3 + 2 +=OR
4 ^ 3 ^=EXOR

622 communication — PDF page 155

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43412
2 Profibus slot/index 170/61
3 Fieldbus format UInt
4 Modbus format UInt

623 Y Comp 2 — PDF page 155

Source row Property Value
1 Default: !A2
2 Selection: Same as menu [621]

623 communication — PDF page 155

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43413
2 Profibus slot/index 170/62
3 Fieldbus format UInt
4 Modbus format UInt

621 communication — PDF page 155

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43411
2 Profibus slot/index 170/60
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Logicoutputs andtimers. Collected P034 association; no extrapolation to other variants. — page 156

Manual reference: physical PDF page 156. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Y Operator 2 [624]

Selects the second operator for the logic Y function.

Communication information

Y Comp 3 [625]

Selects the third comparator for the logic Y function.

11.6.3 Logic Output Z [630]

The expression must be programmed by means of the

menus [631] to [635].

Z Comp 1 [631]

Selects the first comparator for the logic Z function.

Z Operator 1 [632]

Selects the first operator for the logic Z function.

630 LOGIC Z

Stp

CA1&!A2&CD1

A

624 Y Operator 2. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

631 Z Comp 1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

624 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

631 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

625 Y Comp 3. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

632 Z Operator 1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

625 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

632 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

624 Y Operator 2 — PDF page 156

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ &
2 . 0 When · (dot) is selected, the Logic Y expression is finished (when only two expressions are tied together).
3 & 1 &=AND
4 + 2 +=OR
5 ^ 3 ^=EXOR

631 Z Comp 1 — PDF page 156

Source row Property Value
1 Default: CA1
2 Selection: Same as menu [621]

624 communication — PDF page 156

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43414
2 Profibus slot/index 170/63
3 Fieldbus format UInt
4 Modbus format UInt

631 communication — PDF page 156

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43421
2 Profibus slot/index 170/70
3 Fieldbus format UInt
4 Modbus format UInt

625 Y Comp 3 — PDF page 156

Source row Property Value
1 Default: CD1
2 Selection: Same as menu [621]

632 Z Operator 1 — PDF page 156

Source row Property Value
1 Default: &
2 Selection: Same as menu [622]

625 communication — PDF page 156

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43415
2 Profibus slot/index 170/64
3 Fieldbus format UInt
4 Modbus format UInt

632 communication — PDF page 156

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43422
2 Profibus slot/index 170/71
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Logicoutputs andtimers. Collected P034 association; no extrapolation to other variants. — page 157

Manual reference: physical PDF page 157. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Z Comp 2 [633]

Selects the second comparator for the logic Z function.

Communication information

Z Operator 2 [634]

Selects the second operator for the logic Z function.

Z Comp 3 [635]

Selects the third comparator for the logic Z function.

11.6.4 Timer1 [640]

The Timer functions can be used as a delay timer or as

an interval with separate On and Off times (alternate

mode). In delay mode, the output signal T1Q becomes

high if the set delay time is expired. See Fig. 117.

Fig. 117

In alternate mode, the output signal T1Q will switch

automatically from high to low etc. according to the set

interval times. See Fig. 118.

The output signal can be programmed to the digital or

relay outputs used in logic functions [620] and [630],

or as a virtual connection source [560].

Fig. 118

Timer 1 Trig [641]

NOTE: The actual timers are common for all parameter

sets. If the actual set is changed, the timer functionality

[641] to [645] will change according set settings but the

timer value will stay unchanged. So initialization of the

timer might differ for a set change compared to normal

triggering of a timer.

Timer1 Trig

T1Q

Timer1 delay

T1

T2

Figure117 Timer1Trig risingedge thenT1QafterTimer1delay; bothfallwhen triggerfalls. Figure118 Timer1TrighighenablesalternatingT1QwithintervalsT1,T2,T1,T2. PrintedfirstT1spanliesunderlowT1Q;158prose callsT1uptime. No numericaldelayorpolarityrepairinferred.

633 Z Comp 2. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

633 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

634 Z Operator 2. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

634 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

635 Z Comp 3. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

641 Timer1 Trig. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

635 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

641 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

633 Z Comp 2 — PDF page 157

Source row Property Value
1 Default: !A2
2 Selection: Same as menu [621]

633 communication — PDF page 157

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43423
2 Profibus slot/index 170/72
3 Fieldbus format UInt
4 Modbus format UInt

634 Z Operator 2 — PDF page 157

Source row Property Value
1 Default: &
2 Selection: Same as menu [624]

634 communication — PDF page 157

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43424
2 Profibus slot/index 170/73
3 Fieldbus format UInt
4 Modbus format UInt

635 Z Comp 3 — PDF page 157

Source row Property Value
1 Default: CD1
2 Selection: Same as menu [621]

641 Timer1 Trig — PDF page 157

Source row Property Value
1 Default: Off
2 Selection: Same selections as Digital Output 1 menu [541].

635 communication — PDF page 157

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43425
2 Profibus slot/index 170/74
3 Fieldbus format UInt
4 Modbus format UInt

641 communication — PDF page 157

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43431
2 Profibus slot/index 170/80
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Logicoutputs andtimers. Collected P034 association; no extrapolation to other variants. — page 158

Manual reference: physical PDF page 158. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Timer 1 Mode [642]

Communication information

Timer 1 Delay [643]

This menu is only visible when timer mode is set to

delay.

This menu can only be edited as in alternative 2, see

section 9.5, page 57.

Timer 1 delay sets the time that will be used by the first

timer after it is activated. Timer 1 can be activated by a

high signal on a DigIn that is set to Timer 1 or via a vir-

tual destination [560].

Timer 1 T1 [644]

When timer mode is set to Alternate and Timer 1 is ena-

bled, this timer will automatically keep on switching

according to the independently programmable up and

down times. The Timer 1 in Alternate mode can be ena-

bled by a digital input or via a virtual connection. See

Fig. 118. Timer 1 T1 sets the up time in the alternate

mode.

Timer 1 T2 [645]

Timer 1 T2 sets the down time in the alternate mode.

NOTE: Timer 1 T1 [644] and Timer 2 T1 [654] are only

visible when Timer Mode is set to Alternate.

642 Timer1 Mode. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

644 Timer 1 T1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

642 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

644 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

645 Timer1 T2. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

643 Timer1Delay. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

645 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

643 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Logicoutputs andtimers. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

642 Timer1 Mode — PDF page 158

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 ⟦blank source cell⟧
3 Delay 1 ⟦blank source cell⟧
4 Alternate 2 ⟦blank source cell⟧

644 Timer 1 T1 — PDF page 158

Source row Property Value
1 Default: 0:00:00 (hr:min:sec)
2 Range: 0:00:00–9:59:59

642 communication — PDF page 158

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43432
2 Profibus slot/index 170/81
3 Fieldbus format UInt
4 Modbus format UInt

644 communication — PDF page 158

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43436 hours 43437 minutes 43438 seconds
2 Profibus slot/index 170/85, 170/86, 170/87
3 Fieldbus format UInt
4 Modbus format UInt

645 Timer1 T2 — PDF page 158

Source row Property Value
1 Default: 0:00:00, hr:min:sec
2 Range: 0:00:00–9:59:59

645 communication — PDF page 158

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43439 hours 43440 minutes 43441 seconds
2 Profibus slot/index 170/88, 170/89, 170/90
3 Fieldbus format UInt
4 Modbus format UInt

643 communication — PDF page 158

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43433 hours 43434 minutes 43435 seconds
2 Profibus slot/index 170/82, 170/83, 170/84
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Timers and operating status. Collected P034 association; no extrapolation to other variants. — page 159

Manual reference: physical PDF page 159. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Timer 1 Value [649]

Timer 1 Value shows actual value of the timer.

Communication information

11.6.5 Timer2 [650]

Refer to the descriptions for Timer1.

Timer 2 Trig [651]

Timer 2 Mode [652]

Timer 2 Delay [653]

Timer 2 T1 [654]

652 Timer2 Mode. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

649 Timer1 Value. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

652 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

649 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

653 Timer2Delay. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

651 Timer2 Trig. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

653 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

651 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

654 Timer 2 T1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

654 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

652 Timer2 Mode — PDF page 159

Source row Property Value
1 Default: Off
2 Selection: Same as in menu [642]

649 Timer1 Value — PDF page 159

Source row Property Value
1 Default: 0:00:00, hr:min:sec
2 Range: 0:00:00–9:59:59

652 communication — PDF page 159

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43452
2 Profibus slot/index 170/101
3 Fieldbus format UInt
4 Modbus format UInt

649 communication — PDF page 159

Source row Property Value
1 Modbus Instance no/DeviceNet no: 42921 hours 42922 minutes 42923 seconds
2 Profibus slot/index 168/80, 168/81, 168/82
3 Fieldbus format UInt
4 Modbus format UInt

651 Timer2 Trig — PDF page 159

Source row Property Value
1 Default: Off
2 Selection: Same selections as Digital Output 1 menu [541].

653 communication — PDF page 159

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43453 hours 43454 minutes 43455 seconds
2 Profibus slot/index 170/102, 170/103, 170/104
3 Fieldbus format UInt
4 Modbus format UInt

651 communication — PDF page 159

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43451
2 Profibus slot/index 170/100
3 Fieldbus format UInt
4 Modbus format UInt

654 communication — PDF page 159

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43456 hours 43457 minutes 43458 seconds
2 Profibus slot/index 170/105, 170/106, 170/107
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Timers and operating status. Collected P034 association; no extrapolation to other variants. — page 160

Manual reference: physical PDF page 160. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Timer 2 T2 [655]

Communication information

Timer 2 Value [659]

Timer 2 Value shows actual value of the timer.

11.7 View Operation/Status

[700]

Menu with parameters for viewing all actual operational

data, such as speed, torque, power, etc.

11.7.1 Operation [710]

Process Value [711]

The process value is showing the process actual value,

depending on selection done in chapter Process Source

[321].

Speed [712]

Displays the actual shaft speed.

655 Timer 2 T2. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

655 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

711 Process Val. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

659 Timer2 Value. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

711 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

659 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

712 Speed. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

712 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

655 Timer 2 T2 — PDF page 160

Source row Property Value
1 Default: 0:00:00, hr:min:sec
2 Range: 0:00:00–9:59:59

655 communication — PDF page 160

Source row Property Value
1 Modbus Instance no/DeviceNet no: 43459 hours 43460 minutes 43461 seconds
2 Profibus slot/index 170/108, 170/109, 170/110
3 Fieldbus format UInt
4 Modbus format UInt

711 Process Val — PDF page 160

Source row Property Value
1 Unit Depends on selected Pocess source [321] and Process Unit [322].
2 Resolution Speed: 1 rpm, 4 digits Other units: 3 digits

711 communication — PDF page 160

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31001
2 Profibus slot/index 121/145
3 Fieldbus format Long, 1=0.001
4 Modbus format EInt

659 communication — PDF page 160

Source row Property Value
1 Modbus Instance no/DeviceNet no: 42924 hours 42925 minutes 42926 seconds
2 Profibus slot/index 168/83, 168/84, 168/84
3 Fieldbus format UInt
4 Modbus format UInt

712 Speed — PDF page 160

Source row Property Value
1 Unit: rpm
2 Resolution: 1 rpm, 4 digits

712 communication — PDF page 160

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31002
2 Profibus slot/index 121/146
3 Fieldbus format Int, 1=1 rpm
4 Modbus format Int, 1=1 rpm

Manual — Timers and operating status. Collected P034 association; no extrapolation to other variants. — page 161

Manual reference: physical PDF page 161. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Torque [713]

Displays the actual shaft torque.

Communication information

Shaft power [714]

Displays the actual shaft power.

Electrical Power [715]

Displays the actual electrical output power.

Current [716]

Displays the actual output current.

Output Voltage [717]

Displays the actual output voltage.

715 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

713 Torque. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

713 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

716 Current. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

716 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

714 Shaft Power. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

717 Output Volt. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

714 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

717 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

715 El Power. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

715 communication — PDF page 161

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31006
2 Profibus slot/index 121/150
3 Fieldbus format Long, 1=1W
4 Modbus format EInt

713 Torque — PDF page 161

Source row Property Value
1 Unit: %, Nm
2 Resolution: 1 %, 0.1 Nm

713 communication — PDF page 161

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31003 Nm 31004 %
2 Profibus slot/index 121/147 121/148
3 Fieldbus format Long, 1=0.1 Nm Long, 1=1 %
4 Modbus format EInt

716 Current — PDF page 161

Source row Property Value
1 Unit: A
2 Resolution: 0.1 A

716 communication — PDF page 161

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31007
2 Profibus slot/index 121/151
3 Fieldbus format Long, 1=0.1 A
4 Modbus format EInt

714 Shaft Power — PDF page 161

Source row Property Value
1 Unit: W
2 Resolution: 1W

717 Output Volt — PDF page 161

Source row Property Value
1 Unit: V
2 Resolution: 0.1 V

714 communication — PDF page 161

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31005
2 Profibus slot/index 121/149
3 Fieldbus format Long, 1=1W
4 Modbus format EInt

717 communication — PDF page 161

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31008
2 Profibus slot/index 121/152
3 Fieldbus format Long, 1=0.1 V
4 Modbus format EInt

715 El Power — PDF page 161

Source row Property Value
1 Unit: kW
2 Resolution: 1 W

Manual — Timers and operating status. Collected P034 association; no extrapolation to other variants. — page 162

Manual reference: physical PDF page 162. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Frequency [718]

Displays the actual output frequency.

Communication information

DC Link Voltage [719]

Displays the actual DC link voltage.

Heatsink Temperature [71A]

Displays the actual heatsink temperature, measured.

The signal is generated by a sensor in the IGBT module.

PT100_1_2_3 Temp [71B]

Displays the actual PT100 temperature.

718 Frequency. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

71B PT100 1,2,3. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

718 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

71B communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

719 DC Voltage. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

719 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

71A Heatsink Tmp. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

71A communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

718 Frequency — PDF page 162

Source row Property Value
1 Unit: Hz
2 Resolution: 0.1 Hz

71B PT100 1,2,3 — PDF page 162

Source row Property Value
1 Unit: °C
2 Resolution: 1°C

718 communication — PDF page 162

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31009
2 Profibus slot/index 121/153
3 Fieldbus format Long, 1=0.1 Hz
4 Modbus format EInt

71B communication — PDF page 162

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31012, 31013, 31014
2 Profibus slot/index 121/156 121/157 121/158
3 Fieldbus format Long, 1=1 °C
4 Modbus format EInt

719 DC Voltage — PDF page 162

Source row Property Value
1 Unit: V
2 Resolution: 0.1 V

719 communication — PDF page 162

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31010
2 Profibus slot/index 121/154
3 Fieldbus format Long, 1=0.1 V
4 Modbus format EInt

71A Heatsink Tmp — PDF page 162

Source row Property Value
1 Unit: °C
2 Resolution: 0.1°C

71A communication — PDF page 162

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31011
2 Profibus slot/index 121/155
3 Fieldbus format Long, 1=0.1°C
4 Modbus format EInt

Manual — Timers and operating status. Collected P034 association; no extrapolation to other variants. — page 163

Manual reference: physical PDF page 163. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.7.2 Status [720]

VSD Status [721]

Indicates the overall status of the AC drive.

Fig. 119 AC drive status

Example: “A/Key/Rem/TL”

This means:

A:

Parameter Set A is active.

Key:

Reference value comes from the keyboard (CP).

Rem:

Run/Stop commands come from terminals 1-22.

TL:

Torque Limit active.

Warning [722]

Display the actual or last warning condition. A warning

occurs if the AC drive is close to a trip condition but still

in operation. During a warning condition the red trip

LED will start to blink as long as the warning is active.

The active warning message is displayed in menu

[722]. If no warning is active the message “No Error” is

displayed.

The following warnings are possible:

Communication information

See also the Chapter 12. page 169.

721 VSD Status

Stp 1/222/333/44

Warnings

Stp

warn.msg

722 warning enumeration. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

721 VSD status positions. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

722 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

722 warning enumeration — PDF page 163

Source row Fieldbus integer value Warning message
1 0 No Error
2 1 Motor I²t
3 2 PTC
4 3 Motor lost
5 4 Locked rotor
6 5 Ext trip
7 6 Mon MaxAlarm
8 7 Mon MinAlarm
9 8 Comm error
10 9 PT100
11 11 Pump
12 12 Ext Mot Temp
13 13 LC Level
14 14 Brake
15 15 Option
16 16 Over temp
17 17 Over curr F
18 18 Over volt D
19 19 Over volt G
20 20 Over volt M
21 21 Over speed
22 22 Under voltage
23 23 Power fault
24 24 Desat
25 25 DClink error
26 26 Int error
27 27 Ovolt m cut
28 28 Over voltage
29 29 Not used
30 30 Not used
31 31 Not used

721 VSD status positions — PDF page 163

Source row Display position Status Value
1 1 Parameter Set A,B,C,D
2 222 Source of reference value -Key (keyboard) -Rem (remote) -Com (Serial comm.) -Opt (option)
3 333 Source of Run/ Stop/Reset com- mand -Key (keyboard) -Rem (remote) -Com (Serial comm.) -Opt (option)
4 44 Limit functions -TL (Torque Limit) -SL (Speed Limit) -CL (Current Limit) -VL (Voltage Limit) - - - -No limit active

722 communication — PDF page 163

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31016
2 Profibus slot/index 121/160
3 Fieldbus format Long
4 Modbus format UInt

Manual — Timers and operating status. Collected P034 association; no extrapolation to other variants. — page 164

Manual reference: physical PDF page 164. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Digital Input Status [723]

Indicates the status of the digital inputs. See Fig. 120.

DigIn 1

DigIn 2

DigIn 3

DigIn 4

DigIn 5

DigIn 6

DigIn 7

DigIn 8

The positions one to eight (read from left to right) indi-

cate the status of the associated input:

High

Low

The example in Fig. 120 indicates that DigIn 1,

DigIn 3 and DigIn 6 are active at this moment.

Fig. 120 Digital input status example

Communication information

Digital Output Status [724]

Indicates the status of the digital outputs and relays.

See Fig. 121.

RE indicate the status of the relays on position:

Relay1

Relay2

Relay3

DO indicate the status of the digital outputs on position:

DigOut1

DigOut2

The status of the associated output is shown.

The example in Fig. 121 indicates that DigOut1 is active

and Digital Out 2 is not active. Relay 1 is active, relay 2

and 3 are not active.

Fig. 121 Digital output status example

Analogue Input Status [725]

Indicates the status of the analogue inputs 1 and 2.

Fig. 122 Analogue input status

The first row indicates the analogue inputs.

AnIn 1

AnIn 2

Reading downwards from the first row to the second

row the status of the belonging input is shown in %:

-100% AnIn1 has a negative 100% input value

65%

AnIn2 has a 65% input value

So the example in Fig. 122 indicates that both the Ana-

logue inputs are active.

Analogue Input Status [726]

Indicates the status of the analogue inputs 3 and 4.

Fig. 123 Analogue input status

723 DigIn Status

Stp

1010 0100

724 DigOutStatus

Stp RE 100 DO 10

NOTE: The shown percentages are absolute values

based on the full range/scale of the in- our output; so

related to either 0–10 V or 0–20 mA.

725 AnIn 1

-100% 65%

726 AnIn 3

Figures120–123 example labels:723 DigInStatus1010 0100 (DigIn1,3,6 active);724 RE100 DO10;725 AnIn1/2 −100%/65%;726 AnIn3/4 −100%/65%. These are example states, not defaults.

724 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

725 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

723 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

724 communication — PDF page 164

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31018
2 Profibus slot/index 121/162
3 Fieldbus format UInt, bit 0=DigOut1, bit 1=DigOut2 bit 8=Relay1 bit 9=Relay2 bit 10=Relay3
4 Modbus format ⟦null: no independent source value⟧

725 communication — PDF page 164

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31019, 31020
2 Profibus slot/index 121/163, 121/164
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

723 communication — PDF page 164

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31017
2 Profibus slot/index 121/161
3 Fieldbus format UInt, bit 0=DigIn1, bit 8=DigIn8
4 Modbus format ⟦null: no independent source value⟧

Manual — Timers and operating status. Collected P034 association; no extrapolation to other variants. — page 165

Manual reference: physical PDF page 165. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Communication information

Analogue Output Status [727]

Indicates the status of the analogue outputs. Fig. 120.

E.g. if 4-20 mA output is used, the value 20% equals to

4 mA.

Fig. 124 Analogue output status

The first row indicates the Analogue outputs.

AnOut 1

AnOut 2

Reading downwards from the first row to the second

row the status of the belonging output is shown in %:

-100%AnOut1 has a negative 100% output value

65%AnOut2 has a 65% output value

The example in Fig. 120 indicates that both the Ana-

logue outputs are active.

I/O board Status [728] - [72A]

Indicates the status for the additional I/O on option

boards 1 (B1), 2 (B2) and 3 (B3).

NOTE: The shown percentages are absolute values

based on the full range/scale of the in- our output; so

related to either 0–10 V or 0–20 mA.

727 AnOut 1

Stp

-100% 65%

728 IO B1

RE000 DI10

Figure124 example727 AnOut1/2 −100%/65%;728 IOB1 display RE000 DI10. The latter image shows two input digits while communication describes three option inputs; preserve literal image, not an invented third digit.

726 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

728–72A communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

727 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Timers and operating status. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

726 communication — PDF page 165

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31021, 31022
2 Profibus slot/index 121/165, 121/166
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

728–72A communication — PDF page 165

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31025 - 31027
2 Profibus slot/index 121/170 - 172
3 Fieldbus format UInt, bit 0=DigIn1 bit 1=DigIn2 bit 2=DigIn3 bit 8=Relay1 bit 9=Relay2 bit 10=Relay3
4 Modbus format ⟦null: no independent source value⟧

727 communication — PDF page 165

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31023, 31024
2 Profibus slot/index 121/167, 121/168
3 Fieldbus format Long, 1=1%
4 Modbus format EInt

Manual — Stored values and trip logs. Collected P034 association; no extrapolation to other variants. — page 166

Manual reference: physical PDF page 166. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.7.3 Stored values [730]

The shown values are the actual values built up over

time. Values are stored at power down and updated

again at power up.

Run Time [731]

Displays the total time that the AC drive has been in the

Run Mode.

Communication information

Reset Run Time [7311]

Reset the run time counter. The stored information will

be erased and a new registration period will start.

Mains time [732]

Displays the total time that the AC drive has been con-

nected to the mains supply. This timer cannot be reset.

Energy [733]

Displays the total energy consumption since the last

energy reset [7331] took place.

NOTE: After reset the setting automatically reverts to

“No”.

732 Mains Time. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

731 Run Time. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

732 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

731 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

733 Energy. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

7311 Reset RunTm. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

733 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

7311 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

732 Mains Time — PDF page 166

Source row Property Value
1 Unit: h: mm:ss (hours: minutes: seconds)
2 Range: 00: 00: 00–262143: 59: 59

732 communication — PDF page 166

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31031:31032:31033 (hr:min:sec)
2 Profibus slot/index 121/175:121/176: 121/177
3 Fieldbus format UInt, 1=1h/m/s
4 Modbus format UInt, 1=1h/m/s

731 communication — PDF page 166

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31028:31029:31030 (hr:min:sec)
2 Profibus slot/index 121/172:121/173: 121/174
3 Fieldbus format UInt, 1=1h/m/s
4 Modbus format UInt, 1=1h/m/s

733 Energy — PDF page 166

Source row Property Value
1 Unit: Wh (shows Wh, kWh, MWh or GWh)
2 Range: 0.0–999999GWh

7311 Reset RunTm — PDF page 166

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ No
2 No 0 ⟦blank source cell⟧
3 Yes 1 ⟦blank source cell⟧

733 communication — PDF page 166

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31034
2 Profibus slot/index 121/178
3 Fieldbus format Long, 1=1 W
4 Modbus format EInt

7311 communication — PDF page 166

Source row Property Value
1 Modbus Instance no/DeviceNet no: 7
2 Profibus slot/index 0/6
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Stored values and trip logs. Collected P034 association; no extrapolation to other variants. — page 167

Manual reference: physical PDF page 167. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Reset Energy [7331]

Resets the energy counter. The stored information will

be erased and a new registration period will start.

Communication information

11.8 View Trip Log [800]

Main menu with parameters for viewing all the logged

trip data. In total the AC drive saves the last 10 trips in

the trip memory. The trip memory refreshes on the FIFO

principle (First In, First Out). Every trip in the memory is

logged on the time of the Run Time [731] counter. At

every trip, the actual values of several parameter are

stored and available for troubleshooting.

11.8.1 Trip Message log [810]

Display the cause of the trip and what time that it

occurred. When a trip occurs the status menus are cop-

ied to the trip message log. There are nine trip message

logs [810]–[890]. When the tenth trip occurs the oldest

trip will disappear.

For fieldbus integer value of trip message, see mes-

sage table for warnings, [722].

NOTE: After reset the setting automatically goes back to

“No”.

NOTE: Bits 0–5 used for trip message value. Bits 6–15

for internal use.

810 Ext Trip

Stp

132:12:14

7331 Rst Energy. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

7331 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

8x0 Trip message. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

810 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

7331 Rst Energy — PDF page 167

Source row Property Value
1 Default: No
2 Selection: No, Yes

7331 communication — PDF page 167

Source row Property Value
1 Modbus Instance no/DeviceNet no: 6
2 Profibus slot/index 0/5
3 Fieldbus format UInt
4 Modbus format UInt

8x0 Trip message — PDF page 167

Source row Property Value
1 Unit: h: m (hours: minutes)
2 Range: 0h: 0m–65355h: 59m

810 communication — PDF page 167

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31101
2 Profibus slot/index 121/245
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Stored values and trip logs. Collected P034 association; no extrapolation to other variants. — page 168

Manual reference: physical PDF page 168. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Trip message [811]-[81N]

The information from the status menus are copied to

the trip message log when a trip occurs.

Communication information

Example:

Fig. 121 shows the third trip memory menu [830]: Over

temperature trip occurred after 1396 hours and 13

minutes in Run time.

Fig. 125 Trip 3

11.8.2 Trip Messages [820] - [890]

Same information as for menu [810].

All nine alarm lists contain the same type of data. For

example DeviceNet parameter 31101 in alarm list 1

contains the same data information as 31151 in alarm

list 2. It is possible to read all parameters in alarm lists

2–9 by recalculating the DeviceNet instance number

into a Profibus slot/index number. This is done in the

following way:

slot no = abs((dev instance no-1)/255)

index no = (dev instance no-1) modulo 255

dev instance no = slot nox255+index no+1

Example: We want to read out the process value out

from alarm list 9. In alarm list 1 process value has the

DeviceNet instance number 31102. In alarm list 9 it

has DeviceNet instance no 31502 (see table 2 above).

The corresponding slot/index no is then:

slot no = abs((31502-1)/255)=123

index no (modulo)= the remainder of the division above

= 136, calculated as: (31502-1)-123x255=136

830 Over temp

Stp

1396h:13m

Figure125 example830 Overtemp Stp1396h:13m is third-trip history illustration; body refersFig121. It is not a product performance limit.

Trip status copy map. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

820–890 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

811–81O communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Trip status copy map — PDF page 168

Source row Trip menu Copied from Description
1 811 711 Process Value
2 812 712 Speed
3 813 712 Torque
4 814 714 Shaft Power
5 815 715 Electrical Power
6 816 716 Current
7 817 717 Output voltage
8 818 718 Frequency
9 819 719 DC Link voltage
10 81A 71A Heatsink Temperature
11 81B 71B PT100_1, 2, 3
12 81C 721 AC drive Status
13 81D 723 Digital input status
14 81E 724 Digital output status
15 81F 725 Analogue input status 1-2
16 81G 726 Analogue input status 3-4
17 81H 727 Analogue output status 1-2
18 81I 728 I/O status option board 1
19 81J 729 I/O status option board 2
20 81K 72A I/O status option board 3
21 81L 731 Run Time
22 81M 732 Mains Time
23 81N 733 Energy
24 81O 310 Process reference

820–890 communication — PDF page 168

Source row Selection/property Enumeration or merged span Description/value
1 Modbus Instance no/ DeviceNet no: 31151–31185 31201–31235 31251–31285 31301–31335 31351–31385 31401–31435 31451–31485 31501–31535 Trip log list 2 3 4 5 6 7 8 9
2 Profibus slot/index 122/40–122/74 122/90–122/124 122/140–122/174 122/190–122/224 122/240–123/18 123/35 - 123/68 123/85–123/118 123/135–123/168 Trip log list 2 3 4 5 6 7 8 9
3 Fieldbus format Depends on parameter, see respec- tive parameter. ⟦null: no independent source value⟧
4 Modbus format Depends on parameter, see respec- tive parameter. ⟦null: no independent source value⟧

811–81O communication — PDF page 168

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31102 - 31135
2 Profibus slot/index 121/246 - 254, 122/0 - 24
3 Fieldbus format Depends on parameter, see respective parame- ter.
4 Modbus format Depends on parameter, see respective parame- ter.

Manual — Stored values and trip logs. Collected P034 association; no extrapolation to other variants. — page 169

Manual reference: physical PDF page 169. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.8.3 Reset Trip Log [8A0]

Resets the content of the 10 trip memories.

Communication information

11.9

System Data [900]

Main menu for viewing all the AC drive system data.

11.9.1

VSD Data [920]

VSD Type [921]

Shows the AC drive type according to the type number.

The options are indicated on the type plate of the AC

drive.

Example of type

Examples:

JNFX48-046AC drive-series suited for 380-480 volt

mains supply, and a rated output current of 46 A.

Software [922]

Shows the software version number of the AC drive.

Fig. 126 gives an example of the version number.

Fig. 126 Example of software version

NOTE: After the reset the setting goes automatically

back to “NO”. The message “OK” is displayed for 2 sec.

NOTE: If the control board is not configured, then type

type shown is JNFX40-XXXX.

JNFX2.0

Stp

JNFX48-0046

922 Software

V 4.30

8A0 Reset Trip. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Shared source cells (coordinates refer to this table):

8A0 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

921 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

922 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

8A0 Reset Trip — PDF page 169

Source row Selection/property Enumeration or merged span Description/value
1 Default: ⟦null: no independent source value⟧ No
2 No 0 ⟦blank source cell⟧
3 Yes 1 ⟦blank source cell⟧

8A0 communication — PDF page 169

Source row Property Value
1 Modbus Instance no/DeviceNet no: 8
2 Profibus slot/index 0/7
3 Fieldbus format UInt
4 Modbus format UInt

921 communication — PDF page 169

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31037
2 Profibus slot/index 121/181
3 Fieldbus format Long
4 Modbus format Text

922 communication — PDF page 169

Source row Property Value
1 Modbus Instance no/DeviceNet no: 31038 software version 31039 option version
2 Profibus slot/index 121/182-183
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Stored values and trip logs. Collected P034 association; no extrapolation to other variants. — page 170

Manual reference: physical PDF page 170. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

V 4.30 = Version of the Software

Unit name [923]

Option to enter a name of the unit for service use or

customer identity. The function enables the user to

define a name with 12 symbols. Use the Prev and Next

key to move the cursor to the required position. Then

use the + and - keys to scroll in the character list. Con-

firm the character by moving the cursor to the next posi-

tion by pressing the Next key. See section User-defined

Unit [323].

Example

Create user name USER 15.

  1. When in the menu [923] press Next to move the cur-

sor to the right most position.

  1. Press the + key until the character U is displayed.

  2. Press Next.

  3. Then press the + key until S is displayed and con-

firm with Next.

  1. Repeat until you have entered USER15.

Communication information

When sending a unit name you send one character at a

time starting at the right most position.

Table 28

Information for Modbus and Profibus number,

software version

Table 29

option version

NOTE: It is important that the software version displayed

in menu [922] is the same software version number as

the software version number written on the title page of

this instruction manual. If not, the functionality as

described in this manual may differ from the

functionality of the AC drive.

Table28 software version bit fields. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Table29 option version bit fields. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

923 Unit Name. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

923 communication. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Stored values and trip logs. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference.

Table28 software version bit fields — PDF page 170

Source row Bit Description
1 7–0 minor
2 13–8 major
3 15–14 release 00: V, release version 01: P, pre-release version 10: β, Beta version 11: α, Alpha version

Table29 option version bit fields — PDF page 170

Source row Bit Description
1 7–0 minor
2 15–8 major

923 Unit Name — PDF page 170

Source row Property Value
1 Default: No characters shown

923 communication — PDF page 170

Source row Property Value
1 Modbus Instance no/DeviceNet no: 42301–42312
2 Profibus slot/index 165/225–236
3 Fieldbus format UInt
4 Modbus format UInt

Manual — Functional Description — page 171

Manual reference: physical PDF page 171. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Visually footer-only; no engineering body content.

Manual — Troubleshooting and maintenance. Collected P034 association; no extrapolation to other variants. — page 172

Manual reference: physical PDF page 172. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

12.

Troubleshooting, Diagnoses and Maintenance

12.1 Trips, warnings and limits

In order to protect the AC drive the principal operating

variables are continuously monitored by the system. If

one of these variables exceeds the safety limit an error/

warning message is displayed. In order to avoid any

possibly dangerous situations, the inverter sets itself

into a stop Mode called Trip and the cause of the trip is

shown in the display.

Trips will always stop the AC drive. Trips can be divided

into normal and soft trips, depending on the setup Trip

Type, see menu [250] Autoreset. Normal trips are

default. For normal trips the AC drive stops immedi-

ately, i.e. the motor coasts naturally to a standstill. For

soft trips the AC drive stops by ramping down the

speed, i.e. the motor decelerates to a standstill.

“Normal Trip”

• The AC drive stops immediately, the motor coasts to

naturally to a standstill.

• The Trip relay or output is active (if selected).

• The Trip LED is on.

• The accompanying trip message is displayed.

• The “TRP” status indication is displayed (area D of

the display).

“Soft Trip”

• the AC drive stops by decelerating to a standstill.

During the deceleration.

• The accompanying trip message is displayed,

including an additional soft trip indicator “S” before

the trip time.

• The Trip LED is flashing.

• The Warning relay or output is active (if selected).

After standstill is reached.

Apart from the TRIP indicators there are two more

indicators to show that the inverter is in an “abnormal”

situation.

“Warning”

• The inverter is close to a trip limit.

• The accompanying warning message is displayed in

window [722] Warning.

• One of the warning indications is displayed (area F

of the display).

“Limits”

• The inverter is limiting torque and/or frequency to

avoid a trip.

• The Limit relay or output is active (if selected).

•

One of the Limit status indications is displayed (area

D of the display).

*)

Refer to table Table 31regarding which Desat or

Power Fault is triggered.

Table 30

List of trips and warnings

Table30 trips warnings and limits. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Troubleshooting and maintenance. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Table30 trips warnings and limits — PDF page 172

Source row Trip/Warning messages Selections Trip (Normal/ Soft) Warning indicators (Area D)
1 Motor I2t Trip/Off/Limit Normal/Soft I2t
2 PTC Trip/Off Normal/Soft ⟦blank source cell⟧
3 Motor PTC On Normal ⟦blank source cell⟧
4 PT100 Trip/Off Normal/Soft ⟦blank source cell⟧
5 Motor lost Trip/Off Normal ⟦blank source cell⟧
6 Locked rotor Trip/Off Normal ⟦blank source cell⟧
7 Ext trip Via DigIn Normal/Soft ⟦blank source cell⟧
8 Ext Mot Temp Via DigIn Normal/Soft ⟦blank source cell⟧
9 Mon MaxAlarm Trip/Off/Warn Normal/Soft ⟦blank source cell⟧
10 Mon MinAlarm Trip/Off/Warn Normal/Soft ⟦blank source cell⟧
11 Comm error Trip/Off/Warn Normal/Soft ⟦blank source cell⟧
12 Pump Via Option Normal ⟦blank source cell⟧
13 Over temp On Normal OT
14 Over curr F On Normal ⟦blank source cell⟧
15 Over volt D On Normal ⟦blank source cell⟧
16 Over volt G On Normal ⟦blank source cell⟧
17 Over volt On Normal ⟦blank source cell⟧
18 Under voltage On Normal LV
19 LC Level Trip/Off/Warn Via DigIn Normal/Soft LCL
20 Desat ### * On Normal ⟦blank source cell⟧
21 DClink error On Normal ⟦blank source cell⟧
22 Power Fault PF #### * On Normal ⟦blank source cell⟧
23 Ovolt m cut On Normal ⟦blank source cell⟧
24 Over voltage Warning ⟦blank source cell⟧ VL
25 Safe stop Warning ⟦blank source cell⟧ SST
26 Brake Trip/Off/Warn Normal ⟦blank source cell⟧
27 OPTION On Normal ⟦blank source cell⟧

Manual — Troubleshooting and maintenance. Collected P034 association; no extrapolation to other variants. — page 173

Manual reference: physical PDF page 173. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

12.2 Trip conditions, causes and

remedial action

The table later on in this section must be seen as a

basic aid to find the cause of a system failure and to

how to solve any problems that arise. An AC drive is

mostly just a small part of a complete AC drive system.

Sometimes it is

difficult to determine the cause of the failure, although

the AC drive gives a certain trip message it is not always

easy to find the right cause of the failure. Good knowl-

edge of the complete drive system is therefore

necessary. Contact your supplier if you have any ques-

tions.

The AC drive is designed in such a way that it tries to

avoid trips by limiting torque, overvolt etc.

Failures occurring during commissioning or shortly

after commissioning are most likely to be caused by

incorrect settings or even bad connections.

Failures or problems occurring after a reasonable

period of failure-free operation can be caused by

changes in the system or in its environment (e.g. wear).

Failures that occur regularly for no obvious reasons are

generally caused by Electro Magnetic Interference. Be

sure that the installation fulfils the demands for instal-

lation stipulated in the EMC directives. See chapter 8.

page 51.

Sometimes the so-called “Trial and error” method is a

quicker way to determine the cause of the failure. This

can be done at any level, from changing settings and

functions to disconnecting single control cables or

replacing entire drives.

The Trip Log can be useful for determining whether cer-

tain trips occur at certain moments. The Trip Log also

records the time of the trip in relation to the run time

counter.

12.2.1 Technically qualified personnel

Installation, commissioning, demounting, making

measurements, etc., of or at the AC drive may only be

carried out by personnel technically qualified for the

task.

12.2.2 Opening the AC drive

The connections for the control signals and the

switches are isolated from the mains voltage. Always

take adequate precautions before opening the AC drive.

12.2.3 Precautions to take with a

connected motor

If work must be carried out on a connected motor or on

the driven machine, the mains voltage must always first

be disconnected from the AC drive. Wait at least 7 min-

utes before continuing.

12.2.4 Autoreset Trip

If the maximum number of Trips during Autoreset has

been reached, the trip message hour counter is marked

with an “A”.

Fig. 127 Autoreset trip

Fig. 127 shows the 3rd trip memory menu [830]:

Overvoltage G trip after the maximum Autoreset

attempts took place after 345 hours, 45 minutes and

12 seconds of run time.

WARNING!

If it is necessary to open the AC drive or any

part of the system (motor cable housing,

conduits, electrical panels, cabinets, etc.) to

inspect or take measure-ments as suggested in this

instruction manual, it is absolutely necessary to read

and follow the safety instructions in the manual.

Always switch the mains voltage off if it is

necessary to open the AC drive and wait at

least 7 minutes to allow the capacitors to

discharge.

In case of malfunctioning always check the

DC-link voltage, or wait one hour after the

mains voltage has been switched off, before

dismantling the AC drive for repair.

830 OVERVOLT G

Trp A 345:45:12

Figure127 example830 OVERVOLT G Trp A345:45:12; A marks maximum autoreset attempts reached. Trip time reflectsRunTimecounter, not wall-clock time.

Manual — Troubleshooting and maintenance. Collected P034 association; no extrapolation to other variants. — page 174

Manual reference: physical PDF page 174. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 31

Trip condition, their possible causes and remedial action

Table31 trip causes remedies part1. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Troubleshooting and maintenance. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Table31 trip causes remedies part1 — PDF page 174

Source row Trip condition Possible Cause Remedy Size**
1 Motor I2t “I2t” I2t value is exceeded. - Overload on the motor according to the programmed I2t settings. - Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.) - Change the Motor I2t Current setting in menu group [230] ⟦blank source cell⟧
2 PTC Motor thermistor (PTC) exceeds maximum level. NOTE: Only valid if option board PTC/ PT100 is used. - Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.) - Check the motor cooling system. - Self-cooled motor at low speed, too high load. - Set PTC, menu [234] to OFF ⟦blank source cell⟧
3 Motor PTC Motor thermistor (PTC) exceeds maximum level. NOTE: Only valid if [237] is enabled. - Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.) - Check the motor cooling system. - Self-cooled motor at low speed, too high load. - Set PTC, menu [237] to OFF B,C,D
4 PT100 Motor PT100 elements exceeds maximum level. NOTE: Only valid if option board PTC/ PT100 is used. - Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.) - Check the motor cooling system. - Self-cooled motor at low speed, too high load. - Set PT100 to OFF, menu [234] ⟦blank source cell⟧
5 Motor lost Phase loss or too great imbalance on the motor phases - Check the motor voltage on all phases. - Check for loose or poor motor cable connections - If all connections are OK, contact your supplier - Set motor lost alarm to OFF. ⟦blank source cell⟧
6 Locked rotor Torque limit at motor standstill: - Mechanical blocking of the rotor. - Check for mechanical problems at the motor or the machinery connected to the motor - Set locked rotor alarm to OFF. ⟦blank source cell⟧
7 Ext trip External input (DigIn 1-8) active: - active low function on the input. - Check the equipment that initiates the external input - Check the programming of the digital inputs DigIn 1-8 ⟦blank source cell⟧
8 Ext Mot Temp External input (DigIn 1-8) active: - active low function on the input. - Check the equipment that initiates the external input - Check the programming of the digital inputs DigIn 1-8 ⟦blank source cell⟧
9 Mon MaxAlarm Max alarm level (overload) has been reached. - Check the load condition of the machine - Check the monitor setting in section 11.6, page 140. ⟦blank source cell⟧
10 Mon MinAlarm Min alarm level (underload) has been reached. - Check the load condition of the machine - Check the monitor setting in section 11.6, page 140. ⟦blank source cell⟧

Manual — Troubleshooting and maintenance. Collected P034 association; no extrapolation to other variants. — page 175

Manual reference: physical PDF page 175. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 31

Trip condition, their possible causes and remedial action

Table31 trip causes remedies part2. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Troubleshooting and maintenance. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Shared source cells (coordinates refer to this table):

Table31 trip causes remedies part2 — PDF page 175

Source row Trip condition Possible Cause Remedy Size**
1 Comm error Error on serial communication (option) - Check cables and connection of the serial communication. - Check all settings with regard to the serial communication - Restart the equipment including the AC drive ⟦blank source cell⟧
2 Pump No master pump can be selected due to error in feedback signalling. NOTE: Only used in Pump Control. - Check cables and wiring for Pump feedback signals - Check settings with regard to the pump feedback digital inputs ⟦blank source cell⟧
3 Over temp Heatsink temperature too high: - Too high ambient temperature of the AC drive - Insufficient cooling - Too high current - Blocked or stuffed fans - Check the cooling of the AC drive cabinet. - Check the functionality of the built-in fans. The fans must switch on automatically if the heatsink temperature gets too high. At power up the fans are briefly switched on. - Check AC drive and motor rating - Clean fans ⟦blank source cell⟧
4 Over curr F Motor current exceeds the peak AC drive current: - Too short acceleration time. - Too high motor load - Excessive load change - Soft short-circuit between phases or phase to earth - Poor or loose motor cable connections - Too high IxR Compensation level - Check the acceleration time settings and make them longer if necessary. - Check the motor load. - Check on bad motor cable connections - Check on bad earth cable connection - Check on water or moisture in the motor housing and cable connections. - Lower the level of IxR Compensation [352] ⟦blank source cell⟧
5 Over volt D(eceleration) Too high DC Link voltage: - Too short deceleration time with respect to motor/machine inertia. - Too small brake resistor malfunctioning Brake chopper - Check the deceleration time settings and make them longer if necessary. - Check the dimensions of the brake resistor and the functionality of the Brake chopper (if used) ⟦blank source cell⟧
6 Over volt G(eneration) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
7 Over volt (Mains) Too high DC Link voltage, due to too high mains voltage - Check the main supply voltage - Try to take away the interference cause or use other main supply lines. ⟦blank source cell⟧
8 O(ver) volt M(ains) cut ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
9 Under voltage Too low DC Link voltage: - Too low or no supply voltage - Mains voltage dip due to starting other major power consuming machines on the same line. - Make sure all three phases are properly connected and that the terminal screws are tightened. - Check that the mains supply voltage is within the limits of the AC drive. - Try to use other mains supply lines if dip is caused by other machinery - Use the function low voltage override [421] ⟦blank source cell⟧
10 LC Level Low liquid cooling level in external reservoir. External input (DigIn 1-8) active: - active low function on the input. NOTE: Only valid for AC drive types with Liq- uid Cooling option. - Check liquid cooling - Check the equipment and wiring that initiates the external input - Check the programming of the digital inputs DigIn 1-8 ⟦blank source cell⟧
11 OPTION If an Option specific trip occurs Check the description of the specific option ⟦blank source cell⟧

Manual — Troubleshooting and maintenance. Collected P034 association; no extrapolation to other variants. — page 176

Manual reference: physical PDF page 176. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

** = If no size is mentioned in this column, the information is valid for all sizes.

Table 31

Trip condition, their possible causes and remedial action

Table31 trip causes remedies part3. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Troubleshooting and maintenance. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Shared source cells (coordinates refer to this table):

Table31 trip causes remedies part3 — PDF page 176

Source row Trip condition Possible Cause Remedy Size**
1 Desat Failure in output stage, - desaturation of IGBTs - Hard short circuit between phases or phase to earth - Earth fault - For size B - D also the Brake IGBT - Check on bad motor cable connections - Check on bad earth cable connections - Check on water and moisture in the motor housing and cable connections - Check that the rating plate data of the motor is correctly entered. - Check the brake resistor, brake IGBT and wiring. B - D
2 Desat U+ * ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ E & Up
3 Desat U- * ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 Desat V+ * ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 Desat V- * ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 Desat W+ * ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 Desat W- * ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 Desat BCC * ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 DC link error DC link voltage ripple exceeds maximum level - Make sure all three phases are properly connected and that the terminal screws are tight- ened. - Check that the mains supply voltage is within the limits of the AC drive. - Try to use other mains supply lines if dip is caused by other machinery. ⟦blank source cell⟧
10 Power Fault One of the 10 PF (Power Fault) trips below has occured, but could not be determined. - Check the PF errors and try to determine the cause. The trip history can be helpful. ⟦blank source cell⟧
11 PF Fan Err * Error in fan module - Check for clogged air inlet filters in panel door and blocking material in fan module. E & Up
12 PF HCB Err* Error in controlled rectifier module (HCB) - Check mains supply voltage D & Up
13 PF Curr Err * Error in current balancing: - between different modules. - between two phases within one module. - Check motor. - Check fuses and line connections - Check the individual motor current leads with an clamp on amp meter. G& Up
14 PF Overvolt * Error in voltage balancing, overvoltage detected in one of the power modules (PEBB) - Check motor. - Check fuses and line connections. G& Up
15 PF Comm Err * Internal communication error Contact service ⟦blank source cell⟧
16 PF Int Temp * Internal temperature too high Check internal fans ⟦blank source cell⟧
17 PF Temp Err * Malfunction in temperature sensor Contact service ⟦blank source cell⟧
18 PF DC Err * DC-link error and mains supply fault - Check mains supply voltage - Check fuses and line connections. D & Up
19 PF Sup Err * Mains supply fault - Check mains supply voltage - Check fuses and line connections. ⟦blank source cell⟧
20 Brake Brake tripped on brake fault (not released) or Brake not engaged during stop. - Check Brake acknowledge signal wiring to selected digital input. - Check programming of digital input DigIn 1-8, [520]. - Check circuit breaker feeding mechanical brake circuit. - Check mechanical brake if acknowledge signal is wired from brake limit switch. - Check brake contactor. - Check settings [33C], [33D], [33E], [33F]. ⟦blank source cell⟧

Manual — Troubleshooting and maintenance. Collected P034 association; no extrapolation to other variants. — page 177

Manual reference: physical PDF page 177. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

12.3 Maintenance

The AC drive is designed not to require any servicing or

maintenance. There are however some things which

must be checked regularly.

All AC drives have built-in fan which is speed controlled

using heatsink temperature feedback. This means that

the fans are only running if the AC drive is running and

loaded. The design of the heatsinks is such that the fan

does not blow the cooling air through the interior of the

AC drive, but only across the outer surface of the heat-

sink. However, running fans will always attract dust.

Depending on the environment the fan and the heat-

sink will collect dust. Check this and clean the heatsink

and the fans when necessary.

If AC drives are built into cabinets, also check and clean

the dust filters of the cabinets regularly.

Check external wiring, connections and control signals.

Tighten terminal screws if necessary.

Manual — Optional accessories and source safety claims. Collected P034 association; no extrapolation to other variants. — page 178

Manual reference: physical PDF page 178. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

13.

Options

The standard options available are described here

briefly. Some of the options have their own instruction

or installation manual. For more information please

contact your supplier.

13.1

Options for the control

panel

Mounting cassette, blank panel and straight RS232-

cable are available as options for the control panel.

These options may be useful, for example for mounting

a control panel in a cabinet door.

Fig. 128 Control panel in mounting cassette

13.2

Handheld

Control Panel 2.0

The Handheld Control Panel - HCP 2.0 is a complete

control panel, easy to connect to the AC drive, for

temporary use when e.g. commissioning, servicing and

so on.

The HCP has full functionality including memory. It is

possible to set parameters, view signals, actual values,

fault logger information and so on. It is also possible to

use the memory to copy all data (such as parameter set

data and motor data) from one AC drive to the HCP and

then load this data to other AC drives

13.3

EmoSoftCom

EmoSoftCom is an optional software that runs on a per-

sonal computer. It can also be used to load parameter

settings from the AC drive to the PC for backup and

printing. Recording can be made in oscilloscope mode.

Please contact your supplier for further information.

Figure128 mounting cassette and handheldpanel illustration preserve product appearance only; tinybuttonicons are not an additional functional specification.

Handheld control panel2.0 part. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Optional accessories and source safety claims. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Control panel mounting kits. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Optional accessories and source safety claims. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Handheld control panel2.0 part — PDF page 178

Source row Part number Description
1 01-5039-00 Handheld Control Panel 2.0 complete for F33/V33 2.0 or CDU/CDX 2.0

Control panel mounting kits — PDF page 178

Source row Part number Description
1 01-3957-00 Panel kit complete including panel
2 01-3957-01 Panel kit complete including blank panel

Manual — Optional accessories and source safety claims. Collected P034 association; no extrapolation to other variants. — page 179

Manual reference: physical PDF page 179. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

13.4

Brake chopper

All AC drive sizes can be fitted with an optional built-in

brake chopper. The brake resistor must be mounted

outside the AC drive. The choice of the resistor depends

on the application switch-on duration and duty-cycle.

This option can not be after mounted.

The following formula can be used to define the power

of the connected brake resistor:

Where:

Presistor

required power of brake

resistor

Brake level VDCDC brake voltage level (see Table 32)

Rmin

minimum allowable brake resistor

(see Table 33, Table 34 and Table 35

ED

effective braking period. Defined as:

tbr

Active braking time at nominal braking

power during a 2 minute operation

cycle.

Maximum value of ED = 1, meaning continuous braking.

WARNING!

The table gives the minimum values of the

brake resistors. Do not use resistors lower

than this value. The AC drive can trip or even

be damaged due to high braking currents.

Table 32

Presistor =

(Brake level VDC)2

x ED

ED =

120 [s]

Table 33

Brake resistor JNFX48 type

Printed brake formula: P_resistor = ((Brake level V_DC)^2 / R_min) × ED; ED = t_br / 120[s]. P_resistor required brake-resistor power, R_min minimum allowable resistance, t_br effective braking time at nominal braking power in a2minutecycle; maximumED=1continuousbraking. No design calculation performed.

Table33 brake resistor JNFX48. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Optional accessories and source safety claims. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Table32 supply voltage and brake level. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Optional accessories and source safety claims. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Table33 brake resistor JNFX48 — PDF page 179

Source row Type Rmin [ohm] if supply 380–415 V AC Rmin [ohm] if supply 440–480 V AC
1 JNFX48- 0003 43 50
2 -0004 43 50
3 -0006 43 50
4 -0008 43 50
5 -0010 43 50
6 -0013 43 50
7 -0018 43 50
8 -0026 26 30
9 -0031 26 30
10 -0037 17 20
11 -046 17 20
12 -0061 10 12
13 -0074 10 12
14 -0090 3.8 4.4
15 -0109 3.8 4.4
16 -0146 3.8 4.4
17 -0175 3.8 4.4
18 -0210 2.7 3.1
19 -0250 2.7 3.1
20 -0300 2 x 3.8 2 x 4.4
21 -0375 2 x 3.8 2 x 4.4
22 -0430 2 x 2.7 2 x 3.1
23 -0500 2 x 2.7 2 x 3.1
24 -0600 3 x 2.7 3 x 3.1
25 -0650 3 x 2.7 3 x 3.1
26 -0750 3 x 2.7 3 x 3.1
27 -0860 4 x 2.7 4 x 3.1
28 -1000 4 x 2.7 4 x 3.1
29 -1200 6 x 2.7 6 x 3.1
30 -1500 6 x 2.7 6 x 3.1

Table32 supply voltage and brake level — PDF page 179

Source row Supply voltage (V ) AC (set in menu [21B] Brake level (V ) DC
1 220–240 380
2 380–415 660
3 440–480 780
4 500–525 860
5 550–600 1000
6 660–690 1150

Manual — Optional accessories and source safety claims. Collected P034 association; no extrapolation to other variants. — page 180

Manual reference: physical PDF page 180. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

The brake chopper option is built-in by the manufacturer

and must be specified when the AC drive is ordered.

13.5

I/O Board

Each I/O option board 2.0 provides three extra relay

outputs and three extra digital inputs (24V). The I/O

Board works in combination with the Pump/Fan Con-

trol, but can also be used as a separate option. Maxi-

mum 3 I/O boards possible. This option is described in

a separate manual.

13.6

Encoder

The Encoder 2.0 option board, used for connection of

feedback signal of the actual motor speed via an incre-

mental encoder is described in a separate manual.

13.7

PTC/PT100

The PTC/PT100 2.0 option board for connecting motor

thermistors and max 3 PT100 elements to the AC drive

is described in a separate manual.

Table 34

Brake resistors JNFX52 V types

Table 35

Brake resistors JNFX69 V types

NOTE: Although the AC drive will detect a failure in the

brake electronics, the use of resistors with a thermal

overload which will cut off the power at overload is

strongly recommended.

Table34 brake resistor JNFX52. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Optional accessories and source safety claims. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

I/O board option. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Optional accessories and source safety claims. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Encoder option. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Optional accessories and source safety claims. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Table35 brake resistor JNFX69. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Optional accessories and source safety claims. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

PTC/PT100 option. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Optional accessories and source safety claims. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Table34 brake resistor JNFX52 — PDF page 180

Source row Type Rmin [ohm] if supply 440–480 V AC Rmin [ohm] if supply 500–525 V AC
1 JNFX52- 0003 50 55
2 -0004 50 55
3 -0006 50 55
4 -0008 50 55
5 -0010 50 55
6 -0013 50 55
7 -0018 50 55
8 -0026 30 32
9 -0031 30 32
10 -0037 20 22
11 -0046 20 22
12 -0061 12 14
13 -0074 12 14

I/O board option — PDF page 180

Source row Part number Description
1 01-3876-01 I/O option board 2.0

Encoder option — PDF page 180

Source row Part number Description
1 01-3876-03 Encoder 2.0 option board

Table35 brake resistor JNFX69 — PDF page 180

Source row Type Rmin [ohm] if supply 500–525 V AC Rmin [ohm] if supply 550–600 V AC Rmin [ohm] if supply 660–690 V AC
1 JNFX69- 0090 4.9 5.7 6.5
2 -0109 4.9 5.7 6.5
3 -0146 4.9 5.7 6.5
4 -0175 4.9 5.7 6.5
5 -0210 2 x 4.9 2 x 5.7 2 x 6.5
6 -0250 2 x 4.9 2 x 5.7 2 x 6.5
7 -0300 2 x 4.9 2 x 5.7 2 x 6.5
8 -0375 2 x 4.9 2 x 5.7 2 x 6.5
9 -0430 3 x 4.9 3 x 5.7 3 x 6.5
10 -0500 3 x 4.9 3 x 5.7 3 x 6.5
11 -0600 4 x 4.9 4 x 5.7 4 x 6.5
12 -0650 4 x 4.9 4 x 5.7 4 x 6.5
13 -0750 6 x 4.9 6 x 5.7 6 x 6.5
14 -0860 6 x 4.9 6 x 5.7 6 x 6.5
15 -0900 6 x 4.9 6 x 5.7 6 x 6.5
16 -1000 6 x 4.9 6 x 5.7 6 x 6.5

PTC/PT100 option — PDF page 180

Source row Part number Description
1 01-3876-08 PTC/PT100 2.0 option board

Manual — Optional accessories and source safety claims. Collected P034 association; no extrapolation to other variants. — page 181

Manual reference: physical PDF page 181. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

13.8

Serial communication

and fieldbus

For communication with the AC drive there are several

option boards for communication. There are different

options for Fieldbus communication and one serial

communication option with RS232 or RS485 interface

which has galvanic isolation.

13.9

Standby supply board

option

The standby supply board option provides the possibil-

ity of keeping the communication system up and run-

ning without having the 3-phase mains connected. One

advantage is that the system can be set up without

mains power. The option will also give backup for com-

munication failure if main power is lost.

The standby supply board option is supplied with exter-

nal ±10% 24 VDC protected by a 2 A slow acting fuse,

from a double isolated transformer. The terminals X1:1,

X1:2 (on size B,C and E to F) are voltage polarity inde-

pendant.

The terminals A and B (on size D) are voltage polarity

dependent.

Fig. 129 Connection of standby supply option on size B,C and

E-F

Fig. 130 Connection of standby supply option on size D

~

Must be

double

isolated

X1:1 Left terminal

X1:2 Right terminal

X1

Connect the

power supply

board to the

two blue

terminals

marked

A- and B+

=

0V to A-

24V to B+

Figure129 B/C/E–F showsX1:1left/X1:2right anddoubleisolation. Figure130 sizeD identifiestwo blue terminalsA−/B+,0VtoA−and24VtoB+. Polarity conditions are source-specific; original wiring geometry retained inPDF.

Serial communication option boards. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Optional accessories and source safety claims. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Standby power supply kit. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Optional accessories and source safety claims. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Standby X1 sizeB C E F; source literal wording including main power dependent/independent retained. Merged function/specification applies across two rows by physical bounds. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Shared source cells (coordinates refer to this table):

Standby sizeD A B; source literal wording including main power dependent/independent retained. Merged function/specification applies across two rows by physical bounds. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Serial communication option boards — PDF page 181

Source row Part number Description
1 01-3876-04 RS232/485
2 01-3876-05 Profibus DP
3 01-3876-06 DeviceNet
4 01-3876-09 Modbus/TCP, Ethernet

Standby power supply kit — PDF page 181

Source row Part number Description
1 01-3954-00 Standby power supply kit for after mounting

Standby X1 sizeB C E F — PDF page 181

Source row X1 terminal Name Function Specification
1 1 Ext. supply 1 External, AC drive main power inde- pendent, supply voltage for control and communica- tion circuits 24 VDC ±10% Double iso- lated
2 2 Ext. supply 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Standby sizeD A B — PDF page 181

Source row Terminal Name Function Specification
1 A - 0V External, AC drive main power depend- ent, supply voltage for control and communi- cation circuits 24 VDC ±10% Double isolated
2 B + +24V ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Optional accessories and source safety claims. Collected P034 association; no extrapolation to other variants. — page 182

Manual reference: physical PDF page 182. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

13.10 Safe Stop option

To realize a Safe Stop configuration in accordance with

Safe Torque Off (STO) EN-IEC 62061:2005 SIL 2 & EN-

ISO 13849-1:2006, the following three parts need to

be attended to:

  1. Inhibit trigger signals with safety relay K1 (via Safe

Stop option board).

  1. Enable input and control of AC drive (via normal I/O

control signals of AC drive).

  1. Power conductor stage (checking status and feed-

back of driver circuits and IGBT’s).

To enable the AC drive to operate and run the motor,

the following signals should be active:

• "Inhibit" input, terminals 1 (DC+) and 2 (DC-) on the

Safe Stop option board should be made active by

connecting 24 VDC to secure the supply voltage for

the driver circuits of the power conductors via safety

relay K1. See also Fig. 133.

• High signal on the digital input, e.g. terminal 10 in

Fig. 133, which is set to "Enable". For setting the dig-

ital input please refer to section 11.5.2, page 130.

These two signals need to be combined and used to

enable the output of the AC drive and make it possible

to activate a Safe Stop condition.

When the "Safe Stop" condition is achieved by using

these two different methods, which are independently

controlled, this safety circuit ensures that the motor will

not start running because:

• The 24VDC signal is disconnected from the "Inhibit"

input, terminals 1 and 2, the safety relay K1 is

switched off.

The supply voltage to the driver circuits of the power

conductors is switched off. This will inhibit the trig-

ger pulses to the power conductors.

• The trigger pulses from the control board are shut

down.

The Enable signal is monitored by the controller cir-

cuit which will forward the information to the PWM

part on the Control board.

To make sure that the safety relay K1 has been

switched off, this should be guarded externally to

ensure that this relay did not refuse to act. The Safe

Stop option board offers a

feedback signal for this via a second forced switched

safety relay K2 which is switched on when a detection

circuit has confirmed that the supply voltage to the

driver circuits is shut down. See Table 36 for the con-

tacts connections.

To monitor the "Enable" function, the selection "RUN"

on a digital output can be used. For setting a digital out-

put, e.g. terminal 20 in the example Fig. 133, please

refer to section 11.5.4, page 136 [540].

When the "Inhibit" input is de-activated, the AC drive

display will show a flashing "SST" indication in section D

(bottom left corner) and the red Trip LED on the Control

panel will be flashing.

To resume normal operation, the following steps have

to be taken:

• Release "Inhibit" input; 24VDC (High) to terminal 1

and 2.

• Give a STOP signal to the AC drive, according to the

set Run/Stop Control in menu [215].

•

Give a new Run command, according to the set Run/

Stop Control in menu [215].

Fig. 131 Connection of safe stop option in size B - D.

NOTE: The "Safe Stop" condition according to EN-IEC

62061:2005 SIL 2 & EN-ISO 13849-1:2006, can only be

realized by de-activating both the "Inhibit" and "Enable"

inputs.

NOTE: The method of generating a STOP command is

dependent on the selections made in Start Signal Level/

Edge [21A] and the use of a separate Stop input via

digital input.

WARNING!

The safe stop function can never be used for

electrical maintenance. For electrical

maintenance the AC drive should always be

disconnected from the supply voltage.

Figure131 safe-stop boardconnector positions1–6 forsizeB–D. Componentimage is not independent installationverification.

Manual — Optional accessories and source safety claims. Collected P034 association; no extrapolation to other variants. — page 183

Manual reference: physical PDF page 183. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 132 Connection of safe stop option in size E and up.

Fig. 133

2 3

Table 36

Specification of Safe Stop option board

Safe Stop

+5V

+24 VDC

K1

K2

Power board

PWM

Controller

DigIn

DigOut

Enable

Stop

NC

Figure132 sizeEandup shows paired1/2,3/4,5/6connections. Figure133sourceexample labelsX1pins1–6,NC,K1,K2,+24VDC,+5V,Powerboard,U/V/W,Controller,PWM;EnabletoDigIn10 andStopfromDigOut20. These are the supplier diagram associations, not reconstructed wiring instructions.

Table36 safe stop option X1 terminals. F33 software4.3X editionr3; units/default/range/enumeration and communication formats are source-specific. Source header LCD is an example, not an additional universal rating. Native nulls are merged cells; do not infer their value without recorded parent. Optional accessories and source safety claims. Exact menu, optionboard and signalfunction scope retained; repeated mode formats and contradictory references are supplier source claims, not resolved by inference. Supplier manual instructions/claims only; prior PDF173 isolation and qualified-personnel warnings apply. No independent safety or certification validation.

Shared source cells (coordinates refer to this table):

Table36 safe stop option X1 terminals — PDF page 183

Source row X1 pin Name Function Specification
1 1 Inhibit + Inhibit driver circuits of power conductors DC 24 V (20–30 V)
2 2 Inhibit - ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 3 NO contact relay K2 Feedback; confirmation of activated inhibit 48 V / DC 30 V /2 A AC
4 4 P contact relay K2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 5 GND Supply ground ⟦blank source cell⟧
6 6 +24 VDC Supply Voltage for oper- ating Inhibit input only. +24 V , DC 50 mA

Manual — Optional accessories and source safety claims. Collected P034 association; no extrapolation to other variants. — page 184

Manual reference: physical PDF page 184. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

13.11 Output chokes

Output chokes, which are supplied separately, are rec-

ommended for lengths of screened motor cable longer

than 100 m. Because of the fast switching of the motor

voltage and the capacitance of the motor cable (both

line to line and line to earth screen), large switching

currents can be generated with long lengths of motor

cable. Output chokes prevent the AC drive from tripping

and should be installed as closely as possible to the AC

drive.

13.12 Liquid cooling

AC drive modules in frame sizes E - K and F69 - K69 are

available in a liquid cooled version. These units are

designed for connection to a liquid cooling system, nor-

mally a heat exchanger of liquid-liquid or liquid-air type.

Heat exchanger is not part of the liquid cooling option.

Drive units with parallel power modules (frame size

G - K69) are delivered with a dividing unit for connec-

tion of the cooling liquid. The drive units are equipped

with rubber hoses with leak-proof quick couplings.

The Liquid cooling option is described in a separate

manual

Manual — Options — page 185

Manual reference: physical PDF page 185. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Visually footer-only; no engineering body content.

Manual — Technical specifications and model-specific limits. P034 association only. — page 186

Manual reference: physical PDF page 186. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

14.

Technical Data

14.1 Electrical specifications related to model

Table 37

Typical motor power at mains voltage 400 V

Table37 typical motor power400V. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Maximumcurrent footnote: availablelimitedtimeandonlyasdrive temperature allows;normal120% andheavy150% for1minevery10min.

Shared source cells (coordinates refer to this table):

Table37 typical motor power400V — PDF page 186

Source row Model Maximum output current[A]* Normal duty120%1min/10min power@400V[kW] Normal duty rated current[A] Heavy duty150%1min/10min power@400V[kW] Heavy duty rated current[A] Frame size
1 JNFX48-0003 3.0 0.75 2.5 0.55 2.0 B
2 JNFX48-0004 4.8 1.5 4.0 1.1 3.2 ⟦null: no independent source value⟧
3 JNFX48-0006 7.2 2.2 6.0 1.5 4.8 ⟦null: no independent source value⟧
4 JNFX48-0008 9.0 3 7.5 2.2 6.0 ⟦null: no independent source value⟧
5 JNFX48-0010 11.4 4 9.5 3 7.6 ⟦null: no independent source value⟧
6 JNFX48-0013 15.6 5.5 13.0 4 10.4 ⟦null: no independent source value⟧
7 JNFX48-0018 21.6 7.5 18.0 5.5 14.4 ⟦null: no independent source value⟧
8 JNFX48-0026 31 11 26 7.5 21 C
9 JNFX48-0031 37 15 31 11 25 ⟦null: no independent source value⟧
10 JNFX48-0037 44 18.5 37 15 29.6 ⟦null: no independent source value⟧
11 JNFX48-0046 55 22 46 18.5 37 ⟦null: no independent source value⟧
12 JNFX48-0061 73 30 61 22 49 D
13 JNFX48-0074 89 37 74 30 59 ⟦null: no independent source value⟧
14 JNFX48-0090 108 45 90 37 72 E
15 JNFX48-0109 131 55 109 45 87 ⟦null: no independent source value⟧
16 JNFX48-0146 175 75 146 55 117 ⟦null: no independent source value⟧
17 JNFX48-0175 210 90 175 75 140 ⟦null: no independent source value⟧
18 JNFX48-0210 252 110 210 90 168 F
19 JNFX48-0228 300 110 228 90 182 ⟦null: no independent source value⟧
20 JNFX48-0250 300 132 250 110 200 ⟦null: no independent source value⟧
21 JNFX48-0300 360 160 300 132 240 G
22 JNFX48-0375 450 200 375 160 300 ⟦null: no independent source value⟧
23 JNFX48-0430 516 220 430 200 344 H
24 JNFX48-0500 600 250 500 220 400 ⟦null: no independent source value⟧
25 JNFX48-0600 720 315 600 250 480 I
26 JNFX48-0650 780 355 650 315 520 ⟦null: no independent source value⟧
27 JNFX48-0750 900 400 750 355 600 ⟦null: no independent source value⟧
28 JNFX48-0860 1032 450 860 400 688 J
29 JNFX48-1000 1200 500 1000 450 800 ⟦null: no independent source value⟧
30 JNFX48-1200 1440 630 1200 500 960 K
31 JNFX48-1500 1800 800 1500 630 1200 ⟦null: no independent source value⟧

Manual — Technical specifications and model-specific limits. P034 association only. — page 187

Manual reference: physical PDF page 187. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 38

Typical motor power at mains voltage 460 V

Table38 typical motor power460V. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Maximumcurrent footnote: availablelimitedtimeandonlyasdrive temperature allows;normal120% andheavy150% for1minevery10min.

Shared source cells (coordinates refer to this table):

Table38 typical motor power460V — PDF page 187

Source row Model Maximum output current[A]* Normal duty120%1min/10min power@460V[hp] Normal duty rated current[A] Heavy duty150%1min/10min power@460V[hp] Heavy duty rated current[A] Frame size
1 JNFX48-0003 3.0 1 2.5 1 2.0 B
2 JNFX48-0004 4.8 2 4.0 1.5 3.2 ⟦null: no independent source value⟧
3 JNFX48-0006 7.2 3 6.0 2 4.8 ⟦null: no independent source value⟧
4 JNFX48-0008 9.0 3 7.5 3 6.0 ⟦null: no independent source value⟧
5 JNFX48-0010 11.4 5 9.5 3 7.6 ⟦null: no independent source value⟧
6 JNFX48-0013 15.6 7.5 13.0 5 10.4 ⟦null: no independent source value⟧
7 JNFX48-0018 21.6 10 18.0 7.5 14.4 ⟦null: no independent source value⟧
8 JNFX48-0026 31 15 26 10 21 C
9 JNFX48-0031 37 20 31 15 25 ⟦null: no independent source value⟧
10 JNFX48-0037 44 25 37 20 29.6 ⟦null: no independent source value⟧
11 JNFX48-0046 55 30 46 25 37 ⟦null: no independent source value⟧
12 JNFX48-0061 73 40 61 30 49 D
13 JNFX48-0074 89 50 74 40 59 ⟦null: no independent source value⟧
14 JNFX48-0090 108 60 90 50 72 E
15 JNFX48-0109 131 75 109 60 87 ⟦null: no independent source value⟧
16 JNFX48-0146 175 100 146 75 117 ⟦null: no independent source value⟧
17 JNFX48-0175 210 125 175 100 140 ⟦null: no independent source value⟧
18 JNFX48-0210 252 150 210 125 168 F
19 JNFX48-0228 300 200 228 150 182 ⟦null: no independent source value⟧
20 JNFX48-0250 300 200 250 150 200 ⟦null: no independent source value⟧
21 JNFX48-0300 360 250 300 200 240 G
22 JNFX48-0375 450 300 375 250 300 ⟦null: no independent source value⟧
23 JNFX48-0430 516 350 430 250 344 H
24 JNFX48-0500 600 400 500 350 400 ⟦null: no independent source value⟧
25 JNFX48-0600 720 500 600 400 480 I
26 JNFX48-0650 780 550 650 400 520 ⟦null: no independent source value⟧
27 JNFX48-0750 900 600 750 500 600 ⟦null: no independent source value⟧
28 JNFX48-0860 1032 700 860 550 688 J
29 JNFX48-1000 1200 800 1000 650 800 ⟦null: no independent source value⟧
30 JNFX48-1200 1440 1000 1200 800 960 K
31 JNFX48-1500 1800 1250 1500 1000 1200 ⟦null: no independent source value⟧

Manual — Technical specifications and model-specific limits. P034 association only. — page 188

Manual reference: physical PDF page 188. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 39

Typical motor power at mains voltage 525 V

Table39 typical motor power525V. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Maximumcurrent footnote: availablelimitedtimeandonlyasdrive temperature allows;normal120% andheavy150% for1minevery10min.

Shared source cells (coordinates refer to this table):

Table39 typical motor power525V — PDF page 188

Source row Model Maximum output current[A]* Normal duty120%1min/10min power@525V[kW] Normal duty rated current[A] Heavy duty150%1min/10min power@525V[kW] Heavy duty rated current[A] Frame size
1 JNFX52-0003 3.0 1.1 2.5 1.1 2.0 B
2 JNFX52-0004 4.8 2.2 4.0 1.5 3.2 ⟦null: no independent source value⟧
3 JNFX52-0006 7.2 3 6.0 2.2 4.8 ⟦null: no independent source value⟧
4 JNFX52-0008 9.0 4 7.5 3 6.0 ⟦null: no independent source value⟧
5 JNFX52-0010 11.4 5.5 9.5 4 7.6 ⟦null: no independent source value⟧
6 JNFX52-0013 15.6 7.5 13.0 5.5 10.4 ⟦null: no independent source value⟧
7 JNFX52-0018 21.6 11 18.0 7.5 14.4 ⟦null: no independent source value⟧
8 JNFX52-0026 31 15 26 11 21 C
9 JNFX52-0031 37 18.5 31 15 25 ⟦null: no independent source value⟧
10 JNFX52-0037 44 22 37 18.5 29.6 ⟦null: no independent source value⟧
11 JNFX52-0046 55 30 46 22 37 ⟦null: no independent source value⟧
12 JNFX52-0061 73 37 61 30 49 D
13 JNFX52-0074 89 45 74 37 59 ⟦null: no independent source value⟧
14 JNFX69-0090 108 55 90 45 72 F69
15 JNFX69-0109 131 75 109 55 87 ⟦null: no independent source value⟧
16 JNFX69-0146 175 90 146 75 117 ⟦null: no independent source value⟧
17 JNFX69-0175 210 110 175 90 140 ⟦null: no independent source value⟧
18 JNFX69-0210 252 132 210 110 168 H69
19 JNFX69-0250 300 160 250 132 200 ⟦null: no independent source value⟧
20 JNFX69-0300 360 200 300 160 240 ⟦null: no independent source value⟧
21 JNFX69-0375 450 250 375 200 300 ⟦null: no independent source value⟧
22 JNFX69-0430 516 300 430 250 344 I69
23 JNFX69-0500 600 315 500 300 400 ⟦null: no independent source value⟧
24 JNFX69-0600 720 400 600 315 480 J69
25 JNFX690-650 780 450 650 355 520 ⟦null: no independent source value⟧
26 JNFX69-0750 900 500 750 400 600 K69
27 JNFX69-0860 1032 560 860 450 688 ⟦null: no independent source value⟧
28 JNFX69-1000 1200 630 1000 500 800 ⟦null: no independent source value⟧

Manual — Technical specifications and model-specific limits. P034 association only. — page 189

Manual reference: physical PDF page 189. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 40

Typical motor power at mains voltage 575 V

Table 41

Typical motor power at mains voltage 690 V

Table40 typical motor power575V. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Maximumcurrent footnote: availablelimitedtimeandonlyasdrive temperature allows;normal120% andheavy150% for1minevery10min.

Shared source cells (coordinates refer to this table):

Table41 typical motor power690V. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Maximumcurrent footnote: availablelimitedtimeandonlyasdrive temperature allows;normal120% andheavy150% for1minevery10min.

Table40 typical motor power575V — PDF page 189

Source row Model Maximum output current[A]* Normal duty120%1min/10min power@575V[hp] Normal duty rated current[A] Heavy duty150%1min/10min power@575V[hp] Heavy duty rated current[A] Frame size
1 JNFX69-0090 108 75 90 60 72 F69
2 JNFX69-0109 131 100 109 75 87 ⟦null: no independent source value⟧
3 JNFX69-0146 175 125 146 100 117 ⟦null: no independent source value⟧
4 JNFX69-0175 210 150 175 125 140 ⟦null: no independent source value⟧
5 JNFX69-0210 252 200 210 150 168 H69
6 JNFX69-0250 300 250 250 200 200 ⟦null: no independent source value⟧
7 JNFX69-0300 360 300 300 250 240 ⟦null: no independent source value⟧
8 JNFX69-0375 450 350 375 300 300 ⟦null: no independent source value⟧
9 JNFX69-0430 516 400 430 350 344 I69
10 JNFX69-0500 600 500 500 400 400 ⟦null: no independent source value⟧
11 JNFX69-0600 720 600 600 500 480 J69
12 JNFX69-0650 780 650 650 550 520 ⟦null: no independent source value⟧
13 JNFX69-0750 900 750 750 600 600 K69
14 JNFX69-0860 1032 850 860 700 688 ⟦null: no independent source value⟧
15 JNFX69-1000 1200 1000 1000 850 800 ⟦null: no independent source value⟧

Table41 typical motor power690V — PDF page 189

Source row Model Maximum output current[A]* Normal duty120%1min/10min power@690V[kW] Normal duty rated current[A] Heavy duty150%1min/10min power@690V[kW] Heavy duty rated current[A] Frame size
1 JNFX69-0090 108 90 90 75 72 F69
2 JNFX69-0109 131 110 109 90 87 ⟦null: no independent source value⟧
3 JNFX69-0146 175 132 146 110 117 ⟦null: no independent source value⟧
4 JNFX69-0175 210 160 175 132 140 ⟦null: no independent source value⟧
5 JNFX69-0210 252 200 210 160 168 H69
6 JNFX69-0250 300 250 250 200 200 ⟦null: no independent source value⟧
7 JNFX69-0300 360 315 300 250 240 ⟦null: no independent source value⟧
8 JNFX69-0375 450 355 375 315 300 ⟦null: no independent source value⟧
9 JNFX69-0430 516 450 430 315 344 I69
10 JNFX69-0500 600 500 500 355 400 ⟦null: no independent source value⟧
11 JNFX69-0600 720 600 600 450 480 J69
12 JNFX69-0650 780 630 650 500 520 ⟦null: no independent source value⟧
13 JNFX69-0750 900 710 750 600 600 K69
14 JNFX69-0860 1032 800 860 650 688 ⟦null: no independent source value⟧
15 JNFX69-0900 1080 900 900 710 720 ⟦null: no independent source value⟧
16 JNFX69-1000 1200 1000 1000 800 800 ⟦null: no independent source value⟧

Manual — Technical specifications and model-specific limits. P034 association only. — page 190

Manual reference: physical PDF page 190. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

14.2 General electrical specifications

Table 42

General electrical specifications

General

Control signal inputs:

Analogue (differential)

Digital:

Control signal outputs

Analogue

Digital

Relays

References

Table42 physical association: General mains voltage JNFX48=230–480V +10%/−15%(−10% at230V), JNFX52=440–525V +10%/−15%, JNFX69=500–690V +10%/−15%; mains frequency45–65Hz; input power factor0.95; output voltage0–mains supply; outputfrequency0–400Hz; switching3kHz adjustable1.5–6kHz; nominal efficiency97% models0003–0018,98%0026–1500. Analogue input: voltage/current0–±10V/0–20mA via switch; maximum+30V/30mA; impedance20kΩ voltage/250Ω current; resolution11bits+sign; accuracy1%type+1½LSBfsd; nonlinearity1½LSB. Digitalinput: High>9VDC Low<4VDC; max+30VDC; impedance<3.3VDC4.7kΩ and≥3.3VDC3.6kΩ; delay≤8ms. Analogueoutput:0–10V/0–20mA software; max+15V@5mAcontinuous; shortcurrent+15mA(voltage)/+140mA(current); impedance10Ω(voltage);10bit; maxcurrentload500Ω; accuracy1.9%fsd(voltage)/2.4%fsd(current); offset3LSB; nonlinearity2LSB. Digitaloutput:High>20VDC@50mA/>23VDCopen,Low<1VDC@50mA; short100mA shared+24VDC. Relay contacts0.1–2A/Umax250VACor42VDC. References+10VDC@10mA(short+30mAmax),−10VDC@10mA,+24VDC(short+100mAmax sharedDigitalOutputs). These associations transcribe this edition, not validated design limits.

General. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Analogue differential inputs. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Digital inputs. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Analogue outputs. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Digital outputs. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Relay contacts. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Reference supplies. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

General — PDF page 190

Source row Property list in source order Corresponding value list in source order
1 Mains voltage: JNFX48 JNFX52 JNFX69 Mains frequency: Input power factor: Output voltage: Output frequency: Output switching frequency: Efficiency at nominal load: 230-480V +10%/-15% (-10% at 230 V) 440-525 V +10 %/-15 % 500-690V +10%/-15% 45 to 65 Hz 0.95 0–Mains supply voltage: 0–400 Hz 3 kHz (adjustable 1,5-6 kHz) 97% for models 0003 to 0018 98% for models 0026 to 1500

Analogue differential inputs — PDF page 190

Source row Property list in source order Corresponding value list in source order
1 Analogue Voltage/current: Max. input voltage: Input impedance: Resolution: Hardware accuracy: Non-linearity 0-±10 V/0-20 mA via switch +30 V/30 mA 20 kΩ (voltage) 250 Ω (current) 11 bits + sign 1% type + 1 ½ LSB fsd 1½ LSB

Digital inputs — PDF page 190

Source row Property list in source order Corresponding value list in source order
1 Input voltage: Max. input voltage: Input impedance: Signal delay: High: >9 VDC, Low: <4 VDC +30 VDC <3.3 VDC: 4.7 kΩ ≥3.3 VDC: 3.6 kΩ ≤8 ms

Analogue outputs — PDF page 190

Source row Property list in source order Corresponding value list in source order
1 Output voltage/current: Max. output voltage: Short-circuit current (∞): Output impedance: Resolution: Maximum load impedance for current Hardware accuracy: Offset: Non-linearity: 0-10 V/0-20 mA via software setting +15 V @5 mA cont. +15 mA (voltage), +140 mA (current) 10 Ω (voltage) 10 bit 500 Ω 1.9% type fsd (voltage), 2.4% type fsd (current) 3 LSB 2 LSB

Digital outputs — PDF page 190

Source row Property list in source order Corresponding value list in source order
1 Output voltage: Shortcircuit current(∞): High: >20 VDC @50 mA, >23 VDC open Low: <1 VDC @50 mA 100 mA max (together with +24 VDC)

Relay contacts — PDF page 190

Source row Property list in source order Corresponding value list in source order
1 Contacts 0.1 – 2 A/U 250 VAC or 42 VDC max

Reference supplies — PDF page 190

Source row Property list in source order Corresponding value list in source order
1 +10VDC -10VDC +24VDC +10 V @10 mA Short-circuit current +30 mA max DC -10 V @10 mA DC +24 V Short-circuit current +100 mA max (together with Digital Outputs) DC

Manual — Technical specifications and model-specific limits. P034 association only. — page 191

Manual reference: physical PDF page 191. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

14.3 Operation at higher

temperatures

Most AC drives are made for operation at maximum of

40°C ambient temperature. However, for most models,

it is possible to use the AC drive at higher temperatures

with little loss in performance. Table 43 shows ambient

temperatures as well as derating for higher tempera-

tures.

Example

In this example we have a motor with the following data

that we want to run at the ambient temperature of

45°C:

Voltage

400 V

Current

68 A

Power

37 kW

Select AC drive

The ambient temperature is 5 °C higher than the maxi-

mum ambient temperature. The following calculation is

made to select the correct AC drive model.

Derating is possible with loss in performance of 2.5%/

°C.

Derating will be: 5 X 2.5% = 12.5%

Calculation for model JNFX48-0031

31 A - (12.5% x 31) = 27.1 A; this is not enough.

Calculation for model JNFX48-0037

37 A - (12.5% x 37) = 32.4 A

In this example we select the JNFX48-0037.

14.4 Operation at higher

switching frequency

Table 44 shows the switching frequency for the differ-

ent AC drive models. With the possibility of running at

higher switching frequency you can reduce the noise

level from the motor. The switching frequency is set in

menu [22A], Motor sound, see section section 11.2.3,

page 68. At switching frequencies >3 kHz derating

might be needed.

Table 43

Ambient temperature and derating 400–690 V types

Table 44

Switching frequency

Table43 ambient temperature and derating400–690V. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Table44 switching frequency. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Table43 ambient temperature and derating400–690V — PDF page 191

Source row Model IP20 maximum temperature IP20 derating possible IP54 maximum temperature IP54 derating possible
1 JNFX**-0003 to JNFX**-0074 – – 40°C -2.5%/°C to max +10°C
2 JNFX48-0090 to JNFX48-0250 JNFX69-0090 to JNFX69-0175 – – 40°C -2.5%/°C to max +5°C
3 JNFX48-0300 to JNFX48-1500 JNFX69-0210 to JNFX69-1000 40°C -2.5%/°C to max +5°C 40°C -2.5%/°C to max +5°C

Table44 switching frequency — PDF page 191

Source row Models Standard Switching frequency Range
1 JNFX**-0003 to JNFX**-0074 3 kHz 1.5–6 kHz
2 JNFX**-0090 to JNFX**-1500 3 kHz 1.5–6 kHz

Manual — Technical specifications and model-specific limits. P034 association only. — page 192

Manual reference: physical PDF page 192. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

14.5 Dimensions and Weights

The table below gives an overview of the dimensions

and weights. The models 003 to 250 is available in

IP54 as wall mounted modules. The models 300 to

1500 consist of 2, 3, 4 or 6 paralleled power electonic

building block (PEBB) available in IP20 as wall mounted

modules and in IP54 mounted standard cabinet

Protection class IP54 is according to the EN 60529

standard.

Table 45

Mechanical specifications, JNFX48, JNFX52

Table 46

Mechanical specifications, JNFX69

Table45 JNFX48/JNFX52 mechanical. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Table46 JNFX69 mechanical. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Table45 JNFX48/JNFX52 mechanical — PDF page 192

Source row Models Frame size Dim. H x W x D [mm] IP20 Dim. H x W x D [mm] IP54 Weight IP20 [kg] Weight IP54 [kg]
1 0003 to 0018 B – 350(416)x 203 x 200 – 12.5
2 0026 to 0046 C – 440(512) x 178 x 292 – 24
3 0061 to 0074 D – 545(590) x 220 x 295 – 32
4 0090 to 0109 E – 950 x 285 x 314 – 56
5 0146 to 0175 E – 950 x 285 x 314 – 60
6 0210 to 0250 F – 950 x 345 x 314 – 74
7 0300 to 0375 G 1036 x 500 x 390 2330 x 600 x 500 140 270
8 0430 to 0500 H 1036 x 500 x 450 2330 x 600 x 600 170 305
9 0600 to 0750 I 1036 x 730 x 450 2330 x 1000 x 600 248 440
10 0860 to 1000 J 1036 x 1100 x 450 2330 x 1200 x 600 340 580
11 1200 to 1500 K 1036 x 1560 x 450 2330 x 2000 x 600 496 860

Table46 JNFX69 mechanical — PDF page 192

Source row Models Frame size Dim. H x W x D [mm] IP20 Dim. H x W x D [mm] IP54 Weight IP20 [kg] Weight IP54 [kg]
1 0090 to 0175 F69 – 1090 x 345 x 314 – 77
2 0210 to 0375 H69 1176 x 500 x 450 2330 x 600 x 600 176 311
3 0430 to 0500 I69 1176 x 730 x 450 2330 x 1000 x 600 257 449
4 0600 to 0650 J69 1176 x 1100 x 450 2330 x 1200 x 600 352 592
5 0750 to 1000 K69 1176 x 1560 x 450 2330 x 2000 x 600 514 878

Manual — Technical specifications and model-specific limits. P034 association only. — page 193

Manual reference: physical PDF page 193. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

14.6 Environmental conditions

Table 47

Operation

Table 48

Storage

Table47 normal operation. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Table48 storage. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Table47 normal operation — PDF page 193

Source row Parameter Normal operation
1 Nominal ambient temperature 0°C–40°C See table, see Table 43 for different conditions
2 Atmospheric pressure 86–106 kPa
3 Relative humidity, non-condensing 0–90%
4 Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corro- sive materials. Chemical gases, class 3C2. Solid particles, class 3S2.
5 Vibrations According to IEC 600068-2-6, Sinusodial vibrations: 10<f<57 Hz, 0.075 mm 57<f<150 Hz, 1g
6 Altitude 0–1000 m 480V AC drives, with derating 1%/100 m of rated current up to 4000 m 690V AC drives, with derating 1%/100 m of rated current up to 2000 m

Table48 storage — PDF page 193

Source row Parameter Storage condition
1 Temperature -20 to +60 °C
2 Atmospheric pressure 86–106 kPa
3 Relative humidity, non-condensing 0– 90%

Manual — Technical specifications and model-specific limits. P034 association only. — page 194

Manual reference: physical PDF page 194. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

14.7 Fuses, cable cross-

sections and glands

14.7.1 According IEC ratings

Use mains fuses of the type gL/gG conforming to IEC

269 or installation cut-outs with similar characteristics.

Check the equipment first before installing the glands.

Max. Fuse = maximum fuse value that still protects the

AC drive and upholds warranty.

NOTE: The dimensions of fuse and cable cross-section

are dependent on the application and must be

determined in accordance with local regulations.

NOTE: The dimensions of the power terminals used in the

models 300 to 1500 can differ depending on customer

specification.

Table 49

Fuses, cable cross-sections and glands

Table49 first merged-model block, literal model → nominal input A → maximum fuse A: JNFX**-0003→2.2→4;0004→3.5→4;0006→5.2→6;0008→6.9→8;0010→8.7→10;0013→11.3→16;0018→15.6→20. All seven share mains/motor0.5–10mm², brake0.5–10mm², PE1.5–16mm². Gland first0003/0004/0006 group: mainsM32opening/M20+reducer(6–12),brakeM25opening/M20+reducer(6–12).0008/0010 mainsM32(12–20)/M32opening/M25+reducer(10–14);0013/0018 mainsM32(16–25)/M32(13–18);brakeM25(10–14) shared0008 through0018.0228/0250 share216Ainput/250Afuse. Remaining physically merged cable ranges andsuperscript1 retain table parent evidence; no generalized cable-sizing recommendation.

Table49 IEC fuses cables glands. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Source cable/fuse tables depend application/localregulations; brakechopperfootnotes and IEC/NEMA scope remain distinct.

Shared source cells (coordinates refer to this table):

Table49 IEC fuses cables glands — PDF page 194

Source row Model Nominal input current[A] Maximum fuse[A] Mains/motor connector[mm²] Brake connector[mm²] PE connector[mm²] Mains/motor gland clamping[mm] Brake gland clamping[mm]
1 JNFX**-0003 JNFX**-0004 JNFX**-0006 JNFX**-0008 JNFX**-0010 JNFX**-0013 JNFX**-0018 2.2 3.5 5.2 4 4 6 0.5–10 0.5–10 1.5–16 M32 opening M20 + reducer (6–12) M25 opening M20 + reducer (6–12)
2 ⟦null: no independent source value⟧ 6.9 8.7 8 10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ M32 (12–20)/ M32 opening M25+reducer (10-14) M25 (10–14)
3 ⟦null: no independent source value⟧ 11.3 15.6 16 20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ M32 (16–25)/ M32 (13–18) ⟦null: no independent source value⟧
4 JNFX**-0026 22 25 2.5 - 16 stranded wire 2.5 - 25 solid wire ⟦null: no independent source value⟧ 6 - 35 M32 (15–21) M25
5 JNFX**-0031 26 35 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 JNFX**-0037 31 35 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ M40 (19–28) M32
7 JNFX**-0046 38 50 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 JNFX**-0061 52 63 1 - 35 stranded wire 1 - 50 solid wire ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ M50 (27 - 35) M40 (19 - 28)
9 JNFX**-0074 65 80 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 JNFX**-0090 78 100 16 - 95 16 - 95 16-95 (16-70)¹ JNFX48: Ø17- 42 cable flexi- ble leadthrough or M50 opening. JNFX69: Ø23- 55 Cable flexi- ble leadthrough or M63 opening. JNFX48: Ø11- 32 Cable flexi- ble leadthrough or M40 opening. JNFX69: Ø17- 42 Cable flexi- ble leadthrough or M50 opening.
11 JNFX**-0109 94 100 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 JNFX**-0146 126 160 35 - 150 16 - 95 35-150 (16-70)¹ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 JNFX**-0175 152 160 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 JNFX**-0210 182 200 JNFX48: 35-250 JNFX69: 35-150 JNFX48: 35- 150 JNFX69: 16-95 JNFX48: 35-250 (95-185)¹ JNFX69: 35-150 (16-70)¹ Ø23-55 cable flexible leadthrough or M63 opening. Ø17-42 cable flexible leadthrough or M50 opening.
15 JNFX**-0228 216 250 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 JNFX**-0250 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 JNFX**-0300 260 300 JNFX48: (2x)35-240 JNFX69: (2x)35-150 ⟦null: no independent source value⟧ frame --- --
18 JNFX**-0375 324 355 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 JNFX**-0430 372 400 JNFX48: (2x)35-240 JNFX69: (3x)35-150 ⟦null: no independent source value⟧ frame -- --
20 JNFX**-0500 432 500 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 JNFX**-0600 520 630 JNFX48: (3x)35-240 JNFX69: (4x)35-150 ⟦null: no independent source value⟧ frame -- --
22 JNFX**-0650 562 630 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Technical specifications and model-specific limits. P034 association only. — page 195

Manual reference: physical PDF page 195. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note: For models 0003 to 0074 cable glands are

optional.

  1. Values are valid when brake chopper electronics are built in.

Table 49

Fuses, cable cross-sections and glands

Table49 IEC fuses cables glands continued. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Source cable/fuse tables depend application/localregulations; brakechopperfootnotes and IEC/NEMA scope remain distinct.

Shared source cells (coordinates refer to this table):

Table49 IEC fuses cables glands continued — PDF page 195

Source row Model Nominal input current[A] Maximum fuse[A] Mains/motor connector[mm²] Brake connector[mm²] PE connector[mm²] Mains/motor gland clamping[mm] Brake gland clamping[mm]
1 JNFX**-0750 648 710 JNFX48: (3x)35-240 JNFX69: (6x)35-150 ⟦null: no independent source value⟧ frame -- --
2 JNFX**-0860 744 800 JNFX48: (4x)35-240 JNFX69: (6x)35-150 ⟦null: no independent source value⟧ frame -- --
3 JNFX**-0900 795 900 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 JNFX**-1000 864 1000 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 JNFX**-1200 1037 1250 JNFX48: (6x)35-240 ⟦null: no independent source value⟧ frame -- --
6 JNFX**-1500 1296 1500 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Technical specifications and model-specific limits. P034 association only. — page 196

Manual reference: physical PDF page 196. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

14.7.2 Fuses and cable dimensions

according to NEMA ratings

Table 50

Types and fuses

Table50 NEMA types and fuses. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Source cable/fuse tables depend application/localregulations; brakechopperfootnotes and IEC/NEMA scope remain distinct.

Table50 NEMA types and fuses — PDF page 196

Source row Model Input current[Arms] UL ClassJ TD fuse[A] Ferraz-Shawmut type
1 JNFX48-0003 2,2 6 AJT6
2 JNFX48-0004 3,5 6 AJT6
3 JNFX48-0006 5,2 6 AJT6
4 JNFX48-0008 6,9 10 AJT10
5 JNFX48-0010 8,7 10 AJT10
6 JNFX48-0013 11,3 15 AJT15
7 JNFX48-0018 15,6 20 AJT20
8 JNFX48-0026 22 25 AJT25
9 JNFX48-0031 26 30 AJT30
10 JNFX48-0037 31 35 AJT35
11 JNFX48-0046 38 45 AJT45
12 JNFX48-0061 52 60 AJT60
13 JNFX48-0074 65 80 AJT80
14 JNFX48-0090 78 100 AJT100
15 JNFX48-0109 94 110 AJT110
16 JNFX48-0146 126 150 AJT150
17 JNFX48-0175 152 175 AJT175
18 JNFX48-0210 182 200 AJT200
19 JNFX48-0228 216 250 AJT250
20 JNFX48-0250 216 250 AJT250
21 JNFX48-0300 260 300 AJT300
22 JNFX48-0375 324 350 AJT350
23 JNFX48-0430 372 400 AJT400
24 JNFX48-0500 432 500 AJT500
25 JNFX48-0600 520 600 AJT600
26 JNFX48-0650 562 600 AJT600
27 JNFX48-0750 648 700 A4BQ700
28 JNFX48-0860 744 800 A4BQ800
29 JNFX48-1000 864 1000 A4BQ1000
30 JNFX48-1200 1037 1200 A4BQ1200
31 JNFX48-1500 1296 1500 A4BQ1500

Manual — Technical specifications and model-specific limits. P034 association only. — page 197

Manual reference: physical PDF page 197. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 51

Type cables cross-sections and glands

Table51 NEMA cables part1. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Source cable/fuse tables depend application/localregulations; brakechopperfootnotes and IEC/NEMA scope remain distinct.

Shared source cells (coordinates refer to this table):

Table51 NEMA cables part1 — PDF page 197

Source row Model Mains/motor range Mains/motor torque[Nm/ftlbf] Brake range Brake torque[Nm/ftlbf] PE range PE torque[Nm/ftlbf] Cable type
1 JNFX48- 0003 AWG 20 - AWG 6 1.3 / 1 AWG 20 - AWG 6 1.3 / 1 AWG 14 - AWG 6 2.6/2 Copper (Cu) 60°C
2 JNFX48- 0004 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 JNFX48- 0006 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 JNFX48- 0008 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 JNFX48- 0010 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 JNFX48- 0013 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 JNFX48- 0018 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 JNFX48- 0019 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 JNFX48- 0026 AWG 12 - AWG 4 1.3 / 1 AWG 12 - AWG 4 1.3 / 1 AWG 8 - AWG 2 2.6 / 2 output current <44A: Copper (Cu) 60°C output current >44A: Copper (Cu) 75°C
10 JNFX48- 0031 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 JNFX48- 0037 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 JNFX48- 0046 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Technical specifications and model-specific limits. P034 association only. — page 198

Manual reference: physical PDF page 198. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

  1. Values are valid when brake chopper electronics are

built in.

Table 51

Type cables cross-sections and glands

Table51 NEMA cables part2. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Source cable/fuse tables depend application/localregulations; brakechopperfootnotes and IEC/NEMA scope remain distinct.

Shared source cells (coordinates refer to this table):

Table51 NEMA cables part2 — PDF page 198

Source row Model Mains/motor range Mains/motor torque[Nm/ftlbf] Brake range Brake torque[Nm/ftlbf] PE range PE torque[Nm/ftlbf] Cable type
1 JNFX48- 0061 AWG 12–AWG 4 1.6/1.2 AWG 12–AWG 4 1.6/1.2 AWG 12–AWG 4 1.6/1.2 Copper (Cu) 75°C
2 JNFX48- 0074 AWG 10-AWG 0 2.8/3.0 AWG 10-AWG 0 2.8/3.0 AWG 10-AWG 0 2.8/3.0 ⟦null: no independent source value⟧
3 JNFX48- 0090 AWG 4 - AWG 3/0 14 / 10.5 AWG 4 - AWG 3/0 14 / 10.5 AWG 4 - AWG 3/0 (AWG 4 - AWG 2/0)¹ 14 / 10.5 (10 / 7.5)¹ ⟦null: no independent source value⟧
4 JNFX48- 0109 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 JNFX48- 0146 AWG 1 - AWG 3/0 AWG 4/0 - 300 kcmil 14 / 10.5 24 / 18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ AWG 1 - AWG 3/0 (AWG 4 - AWG 2/0)¹ 14 / 10.5 (10 / 7.5)¹ ⟦null: no independent source value⟧
6 JNFX48- 0175 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 JNFX48- 0210 AWG 3/0 - 400 kcmil 24 / 18 AWG 1 - AWG 3/0 AWG 4/0 - 300 kcmil 14 / 10.5 24 / 18 AWG 3/0 - 400 kcmil (AWG 4/0 - 400 kcmil)¹ 24 / 18 (10 / 7.5)¹ ⟦null: no independent source value⟧
8 JNFX48- 0228 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 JNFX48- 0250 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 JNFX48- 0300 2 x AWG 4/0 - 2 x 300 kcmil 24 / 18 2 x AWG 3/0 - 2 x 400 kcmil 24 / 18 frame - ⟦null: no independent source value⟧
11 JNFX48- 0375 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 JNFX48- 0430 2 x AWG 3/0 - 2 x 400 kcmil 24 / 18 2 x AWG 3/0 - 2 x 400 kcmil 24 / 18 frame - ⟦null: no independent source value⟧
13 JNFX48- 0500 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 JNFX48- 0600 3 x AWG 4/0 - 3 x 300 kcmil 24 / 18 2 x AWG 3/0 - 2 x 400 kcmil 24 / 18 frame - ⟦null: no independent source value⟧
15 JNFX48- 0650 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 JNFX48- 0750 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 JNFX48- 0860 4 x AWG 4/0 - 4 x 300 kcmil 24 / 18 3 x AWG 3/0 - 3 x 400 kcmil 24 / 18 frame - ⟦null: no independent source value⟧
18 JNFX48- 1000 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 JNFX48- 1200 6 x AWG 4/0 - 6 x 300 kcmil 24 / 18 6 x AWG 3/0 - 6 x 400 kcmil 24 / 18 frame - ⟦null: no independent source value⟧
20 JNFX48- 1500 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Technical specifications and model-specific limits. P034 association only. — page 199

Manual reference: physical PDF page 199. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

14.8 Control signals

Table 52

Terminal groups in Table52: X1 rows1–22; X2 rows31–33(relay1 trip),41–43(relay2run); X3 rows51–52(relay3Off). Terminal group header cells span full table width and must not be interpreted as individual terminal values. Relay potentials are source change-over contact ratings0.1–2A/Umax250VACor42VDC.

Table52 control signals. F33 software4.3X editionr3. Technical specifications and model-specific limits. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability.

Shared source cells (coordinates refer to this table):

Table52 control signals — PDF page 199

Source row Terminal X1 Name: Function (Default): Signal: Type:
1 1 +10 V +10 VDC Supply voltage +10 VDC, max 10 mA output
2 2 AnIn1 Process reference 0 -10 VDC or 0/4–20 mA bipolar: -10 - +10 VDC or -20 - +20 mA analogue input
3 3 AnIn2 Off 0 -10 VDC or 0/4–20 mA bipolar: -10 - +10 VDC or -20 - +20 mA analogue input
4 4 AnIn3 Off 0 -10 VDC or 0/4–20 mA bipolar: -10 - +10 VDC or -20 - +20 mA analogue input
5 5 AnIn4 Off 0 -10 VDC or 0/4–20 mA bipolar: -10 - +10 VDC or -20 - +20 mA analogue input
6 6 -10 V -10VDC Supply voltage -10 VDC, max 10 mA output
7 7 Common Signal ground 0V output
8 8 DigIn 1 RunL 0-8/24 VDC digital input
9 9 DigIn 2 RunR 0-8/24 VDC digital input
10 10 DigIn 3 Off 0-8/24 VDC digital input
11 11 +24 V +24VDC Supply voltage +24 VDC, 100 mA output
12 12 Common Signal ground 0 V output
13 13 AnOut 1 Min speed to max speed 0 ±10 VDC or 0/4– +20 mA analogue output
14 14 AnOut 2 0 to max torque 0 ±10 VDC or 0/4– +20 mA analogue output
15 15 Common Signal ground 0 V output
16 16 DigIn 4 Off 0-8/24 VDC digital input
17 17 DigIn 5 Off 0-8/24 VDC digital input
18 18 DigIn 6 Off 0-8/24 VDC digital input
19 19 DigIn 7 Off 0-8/24 VDC digital input
20 20 DigOut 1 Ready 24 VDC, 100 mA digital output
21 21 DigOut 2 No trip 24 VDC, 100 mA digital output
22 22 DigIn 8 RESET 0-8/24 VDC digital input
23 Terminal X2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
24 31 N/C 1 Relay 1 output Trip, active when the AC drive is in a TRIP condition N/C is opened when the relay is active (valid for all relays) N/O is closed when the relay is active (valid for all relays) potential free change over 0.1 – 2 A/U 250 VAC or 42 VDC max relay output
25 32 COM 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
26 33 N/O 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
27 41 N/C 2 Relay 2 Output Run, active when the AC drive is started potential free change over 0.1 – 2 A/U 250 VAC or 42 VDC max relay output
28 42 COM 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
29 43 N/O 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
30 Terminal X3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
31 51 COM 3 Relay 3 Output Off potential free change over 0.1 – 2 A/U 250 VAC or 42 VDC max relay output
32 52 N/O 3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Menu summary default/custom columns. P034 association only. — page 200

Manual reference: physical PDF page 200. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

15.

Menu List

Menu list physical panel1. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Menu list physical panel2. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Adjacent source context — repeated to preserve continuation:

Menu list physical panel1 — PDF page 200

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 250 Autoreset ⟦blank source cell⟧ ⟦blank source cell⟧
2 251 No of Trips 0 ⟦blank source cell⟧
3 252 Overtemp Off ⟦blank source cell⟧
4 253 Overvolt D Off ⟦blank source cell⟧
5 254 Overvolt G Off ⟦blank source cell⟧
6 255 Overvolt Off ⟦blank source cell⟧
7 256 Motor Lost Off ⟦blank source cell⟧
8 257 Locked Rotor Off ⟦blank source cell⟧
9 258 Power Fault Off ⟦blank source cell⟧
10 259 Undervoltage Off ⟦blank source cell⟧
11 25A Motor I2t Off ⟦blank source cell⟧
12 25B Motor I2t TT Trip ⟦blank source cell⟧
13 25C PT100 Off ⟦blank source cell⟧
14 25D PT100 TT Trip ⟦blank source cell⟧
15 25E PTC Off ⟦blank source cell⟧
16 25F PTC TT Trip ⟦blank source cell⟧
17 25G Ext Trip Off ⟦blank source cell⟧
18 25H Ext Trip TT Trip ⟦blank source cell⟧
19 25I Com Error Off ⟦blank source cell⟧
20 25J Com Error TT Trip ⟦blank source cell⟧
21 25K Min Alarm Off ⟦blank source cell⟧
22 25L Min Alarm TT Trip ⟦blank source cell⟧
23 25M Max Alarm Off ⟦blank source cell⟧
24 25N Max Alarm TT Trip ⟦blank source cell⟧
25 25O Over curr F Off ⟦blank source cell⟧
26 25P Pump Off ⟦blank source cell⟧
27 25Q Over speed Off ⟦blank source cell⟧
28 25R Ext Mot Temp Off ⟦blank source cell⟧
29 25S Ext Mot TT Trip ⟦blank source cell⟧
30 25T LC Level Off ⟦blank source cell⟧
31 25U LC Level TT Trip ⟦blank source cell⟧
32 25V Brk Fault Off ⟦blank source cell⟧
33 260 Serial Com ⟦blank source cell⟧ ⟦blank source cell⟧
34 261 Com Type RS232/485 ⟦blank source cell⟧
35 262 RS232/485 ⟦blank source cell⟧ ⟦blank source cell⟧
36 2621 Baudrate 9600 ⟦blank source cell⟧
37 2622 Address 1 ⟦blank source cell⟧
38 263 Fieldbus ⟦blank source cell⟧ ⟦blank source cell⟧
39 2631 Address 62 ⟦blank source cell⟧
40 2632 PrData Mode Basic ⟦blank source cell⟧
41 2633 Read/Write RW ⟦blank source cell⟧
42 2634 AddPrValue 0 ⟦blank source cell⟧
43 264 Comm Fault ⟦blank source cell⟧ ⟦blank source cell⟧
44 2641 ComFlt Mode Off ⟦blank source cell⟧
45 2642 ComFlt Time 0.5 s ⟦blank source cell⟧
46 265 Ethernet ⟦blank source cell⟧ ⟦blank source cell⟧
47 2651 IP Address 0.0.0.0 ⟦blank source cell⟧
48 2652 MAC Address 000000000000 ⟦blank source cell⟧
49 2653 Subnet Mask 0.0.0.0 ⟦blank source cell⟧
50 2654 Gateway 0.0.0.0 ⟦blank source cell⟧
51 2655 DHCP Off ⟦blank source cell⟧
52 266 FB Signal ⟦blank source cell⟧ ⟦blank source cell⟧
53 2661 FB Signal 1 0 ⟦blank source cell⟧
54 2662 FB Signal 2 0 ⟦blank source cell⟧

Menu list physical panel2 — PDF page 200

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 100 Preferred View ⟦blank source cell⟧ ⟦blank source cell⟧
2 110 1st Line Process Val ⟦blank source cell⟧
3 120 2nd Line Current ⟦blank source cell⟧
4 200 Main Setup ⟦blank source cell⟧ ⟦blank source cell⟧
5 210 Operation ⟦blank source cell⟧ ⟦blank source cell⟧
6 211 Language English ⟦blank source cell⟧
7 212 Select Motor M1 ⟦blank source cell⟧
8 213 Drive Mode V/Hz ⟦blank source cell⟧
9 214 Ref Control Remote ⟦blank source cell⟧
10 215 Run/Stp Ctrl Remote ⟦blank source cell⟧
11 216 Reset Ctrl Remote ⟦blank source cell⟧
12 217 Local/Rem ⟦blank source cell⟧ ⟦blank source cell⟧
13 2171 LocRefCtrl Standard ⟦blank source cell⟧
14 2172 LocRunCtrl Standard ⟦blank source cell⟧
15 218 Lock Code? 0 ⟦blank source cell⟧
16 219 Rotation R+L ⟦blank source cell⟧
17 21A Level/Edge Level ⟦blank source cell⟧
18 21B Supply Volts Not Defined ⟦blank source cell⟧
19 220 Motor Data ⟦blank source cell⟧ ⟦blank source cell⟧
20 221 Motor Volts UNOM V ⟦blank source cell⟧
21 222 Motor Freq 50Hz ⟦blank source cell⟧
22 223 Motor Power (PNOM) W ⟦blank source cell⟧
23 224 Motor Curr (IMOT) A ⟦blank source cell⟧
24 225 Motor Speed (nMOT) rpm ⟦blank source cell⟧
25 226 Motor Poles 4 ⟦blank source cell⟧
26 227 Motor Cosϕ CosφNOM ⟦blank source cell⟧
27 228 Motor Vent Self ⟦blank source cell⟧
28 229 Motor ID-Run Off ⟦blank source cell⟧
29 22A Motor Sound F ⟦blank source cell⟧
30 22B Encoder Off ⟦blank source cell⟧
31 22C Enc Pulses 1024 ⟦blank source cell⟧
32 22D Enc Speed 0rpm ⟦blank source cell⟧
33 22E Motor PWM ⟦blank source cell⟧ ⟦blank source cell⟧
34 22E1 PWM Fswitch 3.00 kHz ⟦blank source cell⟧
35 22E2 PWM Mode Standard ⟦blank source cell⟧
36 22E3 PWM Random Off ⟦blank source cell⟧
37 22F Enc Puls Ctr 0 ⟦blank source cell⟧
38 230 Mot Protect ⟦blank source cell⟧ ⟦blank source cell⟧
39 231 Mot I2t Type Trip ⟦blank source cell⟧
40 232 Mot I2t Curr 100% ⟦blank source cell⟧
41 233 Mot I2t Time 60s ⟦blank source cell⟧
42 234 Thermal Prot Off ⟦blank source cell⟧
43 235 Motor Class F 140°C ⟦blank source cell⟧
44 236 PT100 Inputs PT100 1+2+3 ⟦blank source cell⟧
45 237 Motor PTC Off ⟦blank source cell⟧
46 240 Set Handling ⟦blank source cell⟧ ⟦blank source cell⟧
47 241 Select Set A ⟦blank source cell⟧
48 242 Copy Set A>B ⟦blank source cell⟧
49 243 Default>Set A ⟦blank source cell⟧
50 244 Copy to CP No Copy ⟦blank source cell⟧
51 245 Load from CP No Copy ⟦blank source cell⟧

Manual — Menu summary default/custom columns. P034 association only. — page 201

Manual reference: physical PDF page 201. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Menu list physical panel1. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Menu list physical panel2. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Adjacent source context — repeated to preserve continuation:

Menu list physical panel1 — PDF page 201

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 2663 FB Signal 3 0 ⟦blank source cell⟧
2 2664 FB Signal 4 0 ⟦blank source cell⟧
3 2665 FB Signal 5 0 ⟦blank source cell⟧
4 2666 FB Signal 6 0 ⟦blank source cell⟧
5 2667 FB Signal 7 0 ⟦blank source cell⟧
6 2668 FB Signal 8 0 ⟦blank source cell⟧
7 2669 FB Signal 9 0 ⟦blank source cell⟧
8 266A FB Signal 10 0 ⟦blank source cell⟧
9 266B FB Signal 11 0 ⟦blank source cell⟧
10 266C FB Signal 12 0 ⟦blank source cell⟧
11 266D FB Signal 13 0 ⟦blank source cell⟧
12 266E FB Signal 14 0 ⟦blank source cell⟧
13 266F FB Signal 15 0 ⟦blank source cell⟧
14 266G FB Signal 16 0 ⟦blank source cell⟧
15 269 FB Status ⟦blank source cell⟧ ⟦blank source cell⟧
16 300 Process ⟦blank source cell⟧ ⟦blank source cell⟧
17 310 Set/View ref 0rpm ⟦blank source cell⟧
18 320 Proc Setting ⟦blank source cell⟧ ⟦blank source cell⟧
19 321 Proc Source Speed ⟦blank source cell⟧
20 322 Proc Unit rpm ⟦blank source cell⟧
21 323 User Unit 0 ⟦blank source cell⟧
22 324 Process Min 0 ⟦blank source cell⟧
23 325 Process Max 0 ⟦blank source cell⟧
24 326 Ratio Linear ⟦blank source cell⟧
25 327 F(Val) PrMin Min ⟦blank source cell⟧
26 328 F(Val) PrMax Max ⟦blank source cell⟧
27 330 Start/Stop ⟦blank source cell⟧ ⟦blank source cell⟧
28 331 Acc Time 10.00s ⟦blank source cell⟧
29 332 Dec Time 10.00s ⟦blank source cell⟧
30 333 Acc MotPot 16.00s ⟦blank source cell⟧
31 334 Dec MotPot 16.00s ⟦blank source cell⟧
32 335 Acc>Min Spd 10.00s ⟦blank source cell⟧
33 336 Dec<Min Spd 10.00s ⟦blank source cell⟧
34 337 Acc Rmp Linear ⟦blank source cell⟧
35 338 Dec Rmp Linear ⟦blank source cell⟧
36 339 Start Mode Fast ⟦blank source cell⟧
37 33A Spinstart Off ⟦blank source cell⟧
38 33B Stop Mode Decel ⟦blank source cell⟧
39 33C Brk Release 0.00s ⟦blank source cell⟧
40 33D Release Spd 0rpm ⟦blank source cell⟧
41 33E Brk Engage 0.00s ⟦blank source cell⟧
42 33F Brk Wait 0.00s ⟦blank source cell⟧
43 33G Vector Brake Off ⟦blank source cell⟧
44 33H Brk Fault 1.00s ⟦blank source cell⟧
45 33I Release Torque 0% ⟦blank source cell⟧
46 340 Speed ⟦blank source cell⟧ ⟦blank source cell⟧
47 341 Min Speed 0rpm ⟦blank source cell⟧
48 342 Stp<MinSpd Off ⟦blank source cell⟧
49 343 Max Speed Sync Speed ⟦blank source cell⟧
50 344 SkipSpd 1 Lo 0rpm ⟦blank source cell⟧
51 345 SkipSpd 1 Hi 0rpm ⟦blank source cell⟧
52 346 SkipSpd 2 Lo 0rpm ⟦blank source cell⟧
53 347 SkipSpd 2 Hi 0rpm ⟦blank source cell⟧
54 348 Jog Speed 50rpm ⟦blank source cell⟧

Menu list physical panel2 — PDF page 201

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 350 Torques ⟦blank source cell⟧ ⟦blank source cell⟧
2 351 Max Torque 120% ⟦blank source cell⟧
3 352 IxR Comp Off ⟦blank source cell⟧
4 353 IxR CompUsr 0% ⟦blank source cell⟧
5 354 Flux optim Off ⟦blank source cell⟧
6 355 Max Power Off ⟦blank source cell⟧
7 360 Preset Ref ⟦blank source cell⟧ ⟦blank source cell⟧
8 361 Motor Pot Non Volatile ⟦blank source cell⟧
9 362 Preset Ref 1 0 rpm ⟦blank source cell⟧
10 363 Preset Ref 2 250 rpm ⟦blank source cell⟧
11 364 Preset Ref 3 500 rpm ⟦blank source cell⟧
12 365 Preset Ref 4 750 rpm ⟦blank source cell⟧
13 366 Preset Ref 5 1000 rpm ⟦blank source cell⟧
14 367 Preset Ref 6 1250 rpm ⟦blank source cell⟧
15 368 Preset Ref 7 1500 rpm ⟦blank source cell⟧
16 369 Keyb Ref Mot Pot ⟦blank source cell⟧
17 380 ProcCtrlPID ⟦blank source cell⟧ ⟦blank source cell⟧
18 381 PID Control Off ⟦blank source cell⟧
19 383 PID P Gain 1.0 ⟦blank source cell⟧
20 384 PID I Time 1.00s ⟦blank source cell⟧
21 385 PID D Time 0.00s ⟦blank source cell⟧
22 386 PID<MinSpd Off ⟦blank source cell⟧
23 387 PID Act Marg 0 ⟦blank source cell⟧
24 388 PID Stdy Tst Off ⟦blank source cell⟧
25 389 PID Stdy Mar 0 ⟦blank source cell⟧
26 390 Pump/Fan Ctrl ⟦blank source cell⟧ ⟦blank source cell⟧
27 391 Pump enable Off ⟦blank source cell⟧
28 392 No of Drives 2 ⟦blank source cell⟧
29 393 Select Drive Sequence ⟦blank source cell⟧
30 394 Change Cond Both ⟦blank source cell⟧
31 395 Change Timer 50h ⟦blank source cell⟧
32 396 Drives on Ch 0 ⟦blank source cell⟧
33 397 Upper Band 10% ⟦blank source cell⟧
34 398 Lower Band 10% ⟦blank source cell⟧
35 399 Start Delay 0s ⟦blank source cell⟧
36 39A Stop Delay 0s ⟦blank source cell⟧
37 39B Upp Band Lim 0% ⟦blank source cell⟧
38 39C Low Band Lim 0% ⟦blank source cell⟧
39 39D Settle Start 0s ⟦blank source cell⟧
40 39E TransS Start 60% ⟦blank source cell⟧
41 39F Settle Stop 0s ⟦blank source cell⟧
42 39G TransS Stop 60% ⟦blank source cell⟧
43 39H Run Time 1 00:00:00 ⟦blank source cell⟧
44 39H1 Rst Run Tm1 No ⟦blank source cell⟧
45 39I Run Time 2 00:00:00 ⟦blank source cell⟧
46 39I1 Rst Run Tm2 No ⟦blank source cell⟧
47 39J Run Time 3 00:00:00 ⟦blank source cell⟧
48 39J1 Rst Run Tm3 No ⟦blank source cell⟧
49 39K Run Time 4 00:00:00 ⟦blank source cell⟧
50 39K1 Rst Run Tm4 No ⟦blank source cell⟧
51 39L Run Time05 00:00:00 ⟦blank source cell⟧
52 39L1 Rst Run Tm5 No ⟦blank source cell⟧
53 39M Run Time 6 00:00:00 ⟦blank source cell⟧
54 39M1 Rst Run Tm6 No ⟦blank source cell⟧

Manual — Menu summary default/custom columns. P034 association only. — page 202

Manual reference: physical PDF page 202. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Menu list physical panel1. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Menu list physical panel2. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Menu list physical panel1 — PDF page 202

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 39N Pump 123456 ⟦blank source cell⟧ ⟦blank source cell⟧
2 39P No of Backup 0 ⟦blank source cell⟧
3 400 Monitor/Prot ⟦blank source cell⟧ ⟦blank source cell⟧
4 410 Load Monitor ⟦blank source cell⟧ ⟦blank source cell⟧
5 411 Alarm Select Off ⟦blank source cell⟧
6 412 Alarm trip Off ⟦blank source cell⟧
7 413 Ramp Alarm Off ⟦blank source cell⟧
8 414 Start Delay 2s ⟦blank source cell⟧
9 415 Load Type Basic ⟦blank source cell⟧
10 416 Max Alarm ⟦blank source cell⟧ ⟦blank source cell⟧
11 4161 MaxAlarmMar 15% ⟦blank source cell⟧
12 4162 MaxAlarmDel 0.1s ⟦blank source cell⟧
13 417 Max Pre alarm ⟦blank source cell⟧ ⟦blank source cell⟧
14 4171 MaxPreAlMar 10% ⟦blank source cell⟧
15 4172 MaxPreAlDel 0.1s ⟦blank source cell⟧
16 418 Min Pre Alarm ⟦blank source cell⟧ ⟦blank source cell⟧
17 4181 MinPreAlMar 10% ⟦blank source cell⟧
18 4182 MinPreAlDel 0.1s ⟦blank source cell⟧
19 419 Min Alarm ⟦blank source cell⟧ ⟦blank source cell⟧
20 4191 MinAlarmMar 15% ⟦blank source cell⟧
21 4192 MinAlarmDel 0.1s ⟦blank source cell⟧
22 41A Autoset Alrm No ⟦blank source cell⟧
23 41B Normal Load 100% ⟦blank source cell⟧
24 41C Load Curve ⟦blank source cell⟧ ⟦blank source cell⟧
25 41C1 Load Curve 1 100% ⟦blank source cell⟧
26 41C2 Load Curve 2 100% ⟦blank source cell⟧
27 41C3 Load Curve 3 100% ⟦blank source cell⟧
28 41C4 Load Curve 4 100% ⟦blank source cell⟧
29 41C5 Load Curve 5 100% ⟦blank source cell⟧
30 41C6 Load Curve 6 100% ⟦blank source cell⟧
31 41C7 Load Curve 7 100% ⟦blank source cell⟧
32 41C8 Load Curve 8 100% ⟦blank source cell⟧
33 41C9 Load Curve 9 100% ⟦blank source cell⟧
34 420 Process Prot ⟦blank source cell⟧ ⟦blank source cell⟧
35 421 Low Volt OR On ⟦blank source cell⟧
36 422 Rotor Locked Off ⟦blank source cell⟧
37 423 Motor lost Off ⟦blank source cell⟧
38 424 Overvolt Ctrl On ⟦blank source cell⟧
39 500 I/Os ⟦blank source cell⟧ ⟦blank source cell⟧
40 510 An Inputs ⟦blank source cell⟧ ⟦blank source cell⟧
41 511 AnIn1 Fc Process Ref ⟦blank source cell⟧
42 512 AnIn1 Setup 4-20mA ⟦blank source cell⟧
43 513 AnIn1 Advn ⟦blank source cell⟧ ⟦blank source cell⟧
44 5131 AnIn1 Min 4mA ⟦blank source cell⟧
45 5132 AnIn1 Max 10.00V/ 20.00mA ⟦blank source cell⟧
46 5133 AnIn1 Bipol 10.00V/ 20.00mA ⟦blank source cell⟧
47 5134 AnIn1 FcMin Min ⟦blank source cell⟧
48 5135 AnIn1 ValMin 0 ⟦blank source cell⟧
49 5136 AnIn1 FcMax Max ⟦blank source cell⟧
50 5137 AnIn1 ValMax 0 ⟦blank source cell⟧
51 5138 AnIn1 Oper Add+ ⟦blank source cell⟧
52 5139 AnIn1 Filt 0.1s ⟦blank source cell⟧
53 513A AnIn1 Enabl On ⟦blank source cell⟧

Menu list physical panel2 — PDF page 202

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 514 AnIn2 Fc Off ⟦blank source cell⟧
2 515 AnIn2 Setup 4-20mA ⟦blank source cell⟧
3 516 AnIn2 Advan ⟦blank source cell⟧ ⟦blank source cell⟧
4 5161 AnIn2 Min 4mA ⟦blank source cell⟧
5 5162 AnIn2 Max 20.00mA ⟦blank source cell⟧
6 5163 AnIn2 Bipol 20.00mA ⟦blank source cell⟧
7 5164 AnIn2 FcMin Min ⟦blank source cell⟧
8 5165 AnIn2 ValMin 0 ⟦blank source cell⟧
9 5166 AnIn2 FcMax Max ⟦blank source cell⟧
10 5167 AnIn2 ValMax 0 ⟦blank source cell⟧
11 5168 AnIn2 Oper Add+ ⟦blank source cell⟧
12 5169 AnIn2 Filt 0.1s ⟦blank source cell⟧
13 516A AnIn2 Enabl On ⟦blank source cell⟧
14 517 AnIn3 Fc Off ⟦blank source cell⟧
15 518 AnIn3 Setup 4-20mA ⟦blank source cell⟧
16 519 AnIn3 Advan ⟦blank source cell⟧ ⟦blank source cell⟧
17 5191 AnIn3 Min 4mA ⟦blank source cell⟧
18 5192 AnIn3 Max 20.00mA ⟦blank source cell⟧
19 5193 AnIn3 Bipol 20.00mA ⟦blank source cell⟧
20 5194 AnIn3 FcMin Min ⟦blank source cell⟧
21 5195 AnIn3 ValMin 0 ⟦blank source cell⟧
22 5196 AnIn3 FcMax Max ⟦blank source cell⟧
23 5197 AnIn3 ValMax 0 ⟦blank source cell⟧
24 5198 AnIn3 Oper Add+ ⟦blank source cell⟧
25 5199 AnIn3 Filt 0.1s ⟦blank source cell⟧
26 519A AnIn3 Enabl On ⟦blank source cell⟧
27 51A AnIn4 Fc Off ⟦blank source cell⟧
28 51B AnIn4 Setup 4-20mA ⟦blank source cell⟧
29 51C AnIn4 Advan ⟦blank source cell⟧ ⟦blank source cell⟧
30 51C1 AnIn4 Min 4mA ⟦blank source cell⟧
31 51C2 AnIn4 Max 20.00mA ⟦blank source cell⟧
32 51C3 AnIn4 Bipol 20.00mA ⟦blank source cell⟧
33 51C4 AnIn4 FcMin Min ⟦blank source cell⟧
34 51C5 AnIn4 ValMin 0 ⟦blank source cell⟧
35 51C6 AnIn4 FcMax Max ⟦blank source cell⟧
36 51C7 AnIn4 ValMax 0 ⟦blank source cell⟧
37 51C8 AnIn4 Oper Add+ ⟦blank source cell⟧
38 51C9 AnIn4 Filt 0.1s ⟦blank source cell⟧
39 51CA AnIn4 Enabl On ⟦blank source cell⟧
40 520 Dig Inputs ⟦blank source cell⟧ ⟦blank source cell⟧
41 521 DigIn 1 RunL ⟦blank source cell⟧
42 522 DigIn 2 RunR ⟦blank source cell⟧
43 523 DigIn 3 Off ⟦blank source cell⟧
44 524 DigIn 4 Off ⟦blank source cell⟧
45 525 DigIn 5 Off ⟦blank source cell⟧
46 526 DigIn 6 Off ⟦blank source cell⟧
47 527 DigIn 7 Off ⟦blank source cell⟧
48 528 DigIn 8 Reset ⟦blank source cell⟧
49 529 B(oard)1 DigIn 1 Off ⟦blank source cell⟧
50 52A B(oard)1 DigIn 2 Off ⟦blank source cell⟧
51 52B B(oard)1 DigIn 3 Off ⟦blank source cell⟧
52 52C B(oard)2 DigIn 1 Off ⟦blank source cell⟧
53 52D B(oard)2 DigIn 2 Off ⟦blank source cell⟧
54 52E B(oard)2 DigIn 3 Off ⟦blank source cell⟧

Manual — Menu summary default/custom columns. P034 association only. — page 203

Manual reference: physical PDF page 203. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Menu list physical panel1. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Menu list physical panel2. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Menu list physical panel1 — PDF page 203

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 52F B(oard)3 DigIn 1 Off ⟦blank source cell⟧
2 52G B(oard)3 DigIn 2 Off ⟦blank source cell⟧
3 52H B(oard)3 DigIn 3 Off ⟦blank source cell⟧
4 530 An Outputs ⟦blank source cell⟧ ⟦blank source cell⟧
5 531 AnOut1 Fc Speed ⟦blank source cell⟧
6 532 AnOut1 Setup 4-20mA ⟦blank source cell⟧
7 533 AnOut1 Adv ⟦blank source cell⟧ ⟦blank source cell⟧
8 5331 AnOut 1 Min 4mA ⟦blank source cell⟧
9 5332 AnOut 1 Max 20.0mA ⟦blank source cell⟧
10 5333 AnOut1Bipol -10.00-10.00 V ⟦blank source cell⟧
11 5334 AnOut1 FcMin Min ⟦blank source cell⟧
12 5335 AnOut1 VlMin 0 ⟦blank source cell⟧
13 5336 AnOut1 FcMax Max ⟦blank source cell⟧
14 5337 AnOut1 VlMax 0 ⟦blank source cell⟧
15 534 AnOut2 FC Torque ⟦blank source cell⟧
16 535 AnOut2 Setup 4-20mA ⟦blank source cell⟧
17 536 AnOut2 Advan ⟦blank source cell⟧ ⟦blank source cell⟧
18 5361 AnOut 2 Min 4mA ⟦blank source cell⟧
19 5362 AnOut 2 Max 20.0mA ⟦blank source cell⟧
20 5363 AnOut2Bipol -10.00-10.00 V ⟦blank source cell⟧
21 5364 AnOut2 FcMin Min ⟦blank source cell⟧
22 5365 AnOut2 VlMin 0 ⟦blank source cell⟧
23 5366 AnOut2 FcMax Max ⟦blank source cell⟧
24 5367 AnOut2 VlMax 0 ⟦blank source cell⟧
25 540 Dig Outputs ⟦blank source cell⟧ ⟦blank source cell⟧
26 541 DigOut 1 Ready ⟦blank source cell⟧
27 542 DigOut 2 Brake ⟦blank source cell⟧
28 550 Relays ⟦blank source cell⟧ ⟦blank source cell⟧
29 551 Relay 1 Trip ⟦blank source cell⟧
30 552 Relay 2 Run ⟦blank source cell⟧
31 553 Relay 3 Off ⟦blank source cell⟧
32 554 B(oard)1 Relay 1 Off ⟦blank source cell⟧
33 555 B(oard)1 Relay 2 Off ⟦blank source cell⟧
34 556 B(oard)1 Relay 3 Off ⟦blank source cell⟧
35 557 B(oard)2 Relay 1 Off ⟦blank source cell⟧
36 558 B(oard)2 Relay 2 Off ⟦blank source cell⟧
37 559 B(oard)2 Relay 3 Off ⟦blank source cell⟧
38 55A B(oard)3 Relay 1 Off ⟦blank source cell⟧
39 55B B(oard)3 Relay 2 Off ⟦blank source cell⟧
40 55C B(oard)3 Relay 3 Off ⟦blank source cell⟧
41 55D Relay Adv ⟦blank source cell⟧ ⟦blank source cell⟧
42 55D1 Relay 1 Mode N.O ⟦blank source cell⟧
43 55D2 Relay 2 Mode N.O ⟦blank source cell⟧
44 55D3 Relay 3 Mode N.O ⟦blank source cell⟧
45 55D4 B1R1 Mode N.O ⟦blank source cell⟧
46 55D5 B1R2 Mode N.O ⟦blank source cell⟧
47 55D6 B1R3 Mode N.O ⟦blank source cell⟧
48 55D7 B2R1 Mode N.O ⟦blank source cell⟧
49 55D8 B2R2 Mode N.O ⟦blank source cell⟧
50 55D9 B2R3 Mode N.O ⟦blank source cell⟧
51 55DA B3R1 Mode N.O ⟦blank source cell⟧
52 55DB B3R2 Mode N.O ⟦blank source cell⟧
53 55DC B3R3 Mode N.O ⟦blank source cell⟧
54 560 Virtual I/Os ⟦blank source cell⟧ ⟦blank source cell⟧

Menu list physical panel2 — PDF page 203

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 561 VIO 1 Dest Off ⟦blank source cell⟧
2 562 VIO 1 Source Off ⟦blank source cell⟧
3 563 VIO 2 Dest Off ⟦blank source cell⟧
4 564 VIO 2 Source Off ⟦blank source cell⟧
5 565 VIO 3 Dest Off ⟦blank source cell⟧
6 566 VIO 3 Source Off ⟦blank source cell⟧
7 567 VIO 4 Dest Off ⟦blank source cell⟧
8 568 VIO 4 Source Off ⟦blank source cell⟧
9 569 VIO 5 Dest Off ⟦blank source cell⟧
10 56A VIO 5 Source Off ⟦blank source cell⟧
11 56B VIO 6 Dest Off ⟦blank source cell⟧
12 56C VIO 6 Source Off ⟦blank source cell⟧
13 56D VIO 7 Dest Off ⟦blank source cell⟧
14 56E VIO 7 Source Off ⟦blank source cell⟧
15 56F VIO 8 Dest Off ⟦blank source cell⟧
16 56G VIO 8 Source Off ⟦blank source cell⟧
17 600 Logical&Timers ⟦blank source cell⟧ ⟦blank source cell⟧
18 610 Comparators ⟦blank source cell⟧ ⟦blank source cell⟧
19 611 CA1 Setup ⟦blank source cell⟧ ⟦blank source cell⟧
20 6111 CA1 Value Speed ⟦blank source cell⟧
21 6112 CA1 Level HI 300rpm ⟦blank source cell⟧
22 6113 CA1 Level LO 200rpm ⟦blank source cell⟧
23 6114 CA1 Type Hysteresis ⟦blank source cell⟧
24 6115 CA1 Bipolar Unipolar ⟦blank source cell⟧
25 612 CA2 Setup ⟦blank source cell⟧ ⟦blank source cell⟧
26 6121 CA2 Value Torque ⟦blank source cell⟧
27 6122 CA2 Level HI 20% ⟦blank source cell⟧
28 6123 CA2 Level LO 10% ⟦blank source cell⟧
29 6124 CA2 Type Hysteresis ⟦blank source cell⟧
30 6125 CA2 Bipolar Unipolar ⟦blank source cell⟧
31 613 CA3 Setup ⟦blank source cell⟧ ⟦blank source cell⟧
32 6131 CA3 Value Process Val ⟦blank source cell⟧
33 6132 CA3 Level HI 300rpm ⟦blank source cell⟧
34 6133 CA3 Level LO 200rpm ⟦blank source cell⟧
35 6134 CA3 Type Hysteresis ⟦blank source cell⟧
36 6135 CA3 Bipolar Unipolar ⟦blank source cell⟧
37 614 CA4 Setup ⟦blank source cell⟧ ⟦blank source cell⟧
38 6141 CA4 Value Process Err ⟦blank source cell⟧
39 6142 CA4 Level HI 100 rpm ⟦blank source cell⟧
40 6143 CA4 Level LO - 100 rpm ⟦blank source cell⟧
41 6144 CA4 Type Window ⟦blank source cell⟧
42 6145 CA4 Bipolar Bipolar ⟦blank source cell⟧
43 615 CD Setup ⟦blank source cell⟧ ⟦blank source cell⟧
44 6151 CD1 Run ⟦blank source cell⟧
45 6152 CD2 DigIn 1 ⟦blank source cell⟧
46 6153 CD3 Trip ⟦blank source cell⟧
47 6154 CD4 Ready ⟦blank source cell⟧
48 620 Logic Output Y ⟦blank source cell⟧ ⟦blank source cell⟧
49 621 Y Comp 1 CA1 ⟦blank source cell⟧
50 622 Y Operator 1 & ⟦blank source cell⟧
51 623 Y Comp 2 !A2 ⟦blank source cell⟧
52 624 Y Operator 2 & ⟦blank source cell⟧
53 625 Y Comp 3 CD1 ⟦blank source cell⟧
54 630 Logic Z ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Menu summary default/custom columns. P034 association only. — page 204

Manual reference: physical PDF page 204. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Menu list physical panel1. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Menu list physical panel2. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Menu list physical panel1 — PDF page 204

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 631 Z Comp 1 CA1 ⟦blank source cell⟧
2 632 Z Operator 1 & ⟦blank source cell⟧
3 633 Z Comp2 !A2 ⟦blank source cell⟧
4 634 Z Operator 2 & ⟦blank source cell⟧
5 635 Z Comp 3 CD1 ⟦blank source cell⟧
6 640 Timer1 ⟦blank source cell⟧ ⟦blank source cell⟧
7 641 Timer1 Trig Off ⟦blank source cell⟧
8 642 Timer1 Mode Off ⟦blank source cell⟧
9 643 Timer1 Delay 0:00:00 ⟦blank source cell⟧
10 644 Timer 1 T1 0:00:00 ⟦blank source cell⟧
11 645 Timer1 T2 0:00:00 ⟦blank source cell⟧
12 649 Timer1 Value 0:00:00 ⟦blank source cell⟧
13 650 Timer2 ⟦blank source cell⟧ ⟦blank source cell⟧
14 651 Timer2 Trig Off ⟦blank source cell⟧
15 652 Timer2 Mode Off ⟦blank source cell⟧
16 653 Timer2 Delay 0:00:00 ⟦blank source cell⟧
17 654 Timer 2 T1 0:00:00 ⟦blank source cell⟧
18 655 Timer2 T2 0:00:00 ⟦blank source cell⟧
19 659 Tmer2 Value 0:00:00 ⟦blank source cell⟧
20 700 Oper/Status ⟦blank source cell⟧ ⟦blank source cell⟧
21 710 Operation ⟦blank source cell⟧ ⟦blank source cell⟧
22 711 Process Val ⟦blank source cell⟧ ⟦blank source cell⟧
23 712 Speed ⟦blank source cell⟧ ⟦blank source cell⟧
24 713 Torque ⟦blank source cell⟧ ⟦blank source cell⟧
25 714 Shaft Power ⟦blank source cell⟧ ⟦blank source cell⟧
26 715 Electrical Power ⟦blank source cell⟧ ⟦blank source cell⟧
27 716 Current ⟦blank source cell⟧ ⟦blank source cell⟧
28 717 Output volt ⟦blank source cell⟧ ⟦blank source cell⟧
29 718 Frequency ⟦blank source cell⟧ ⟦blank source cell⟧
30 719 DC Voltage ⟦blank source cell⟧ ⟦blank source cell⟧
31 71A Heatsink Tmp ⟦blank source cell⟧ ⟦blank source cell⟧
32 71B PT100_1_2_3 ⟦blank source cell⟧ ⟦blank source cell⟧
33 720 Status ⟦blank source cell⟧ ⟦blank source cell⟧
34 721 AC drive Status ⟦blank source cell⟧ ⟦blank source cell⟧
35 722 Warning ⟦blank source cell⟧ ⟦blank source cell⟧
36 723 DigIn Status ⟦blank source cell⟧ ⟦blank source cell⟧
37 724 DigOut Status ⟦blank source cell⟧ ⟦blank source cell⟧
38 725 AnIn Status 1-2 ⟦blank source cell⟧ ⟦blank source cell⟧
39 726 AnIn Status 3-4 ⟦blank source cell⟧ ⟦blank source cell⟧
40 727 AnOut Status 1-2 ⟦blank source cell⟧ ⟦blank source cell⟧
41 728 IO Status B1 ⟦blank source cell⟧ ⟦blank source cell⟧
42 729 IO Status B2 ⟦blank source cell⟧ ⟦blank source cell⟧
43 72A IO Status B3 ⟦blank source cell⟧ ⟦blank source cell⟧
44 730 Stored Val ⟦blank source cell⟧ ⟦blank source cell⟧
45 731 Run Time 00:00:00 ⟦blank source cell⟧
46 7311 Reset RunTm No ⟦blank source cell⟧
47 732 Mains Time 00:00:00 ⟦blank source cell⟧
48 733 Energy kWh ⟦blank source cell⟧
49 7331 Rst Energy No ⟦blank source cell⟧
50 800 View TripLog ⟦blank source cell⟧ ⟦blank source cell⟧
51 810 Trip Message ⟦blank source cell⟧ ⟦blank source cell⟧
52 811 Process Value ⟦blank source cell⟧ ⟦blank source cell⟧
53 812 Speed ⟦blank source cell⟧ ⟦blank source cell⟧
54 813 Torque ⟦blank source cell⟧ ⟦blank source cell⟧

Menu list physical panel2 — PDF page 204

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 814 Shaft Power ⟦blank source cell⟧ ⟦blank source cell⟧
2 815 Electrical Power ⟦blank source cell⟧ ⟦blank source cell⟧
3 816 Current ⟦blank source cell⟧ ⟦blank source cell⟧
4 817 Output voltage ⟦blank source cell⟧ ⟦blank source cell⟧
5 818 Frequency ⟦blank source cell⟧ ⟦blank source cell⟧
6 819 DC Link voltage ⟦blank source cell⟧ ⟦blank source cell⟧
7 81A Heatsink Tmp ⟦blank source cell⟧ ⟦blank source cell⟧
8 81B PT100_1, 2, 3 ⟦blank source cell⟧ ⟦blank source cell⟧
9 81C AC drive Status ⟦blank source cell⟧ ⟦blank source cell⟧
10 81D DigIn status ⟦blank source cell⟧ ⟦blank source cell⟧
11 81E DigOut status ⟦blank source cell⟧ ⟦blank source cell⟧
12 81F AnIn status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
13 81G AnIn status 3 4 ⟦blank source cell⟧ ⟦blank source cell⟧
14 81H AnOut status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
15 81I IO Status B1 ⟦blank source cell⟧ ⟦blank source cell⟧
16 81J IO Status B2 ⟦blank source cell⟧ ⟦blank source cell⟧
17 81K IO Status B3 ⟦blank source cell⟧ ⟦blank source cell⟧
18 81L Run Time ⟦blank source cell⟧ ⟦blank source cell⟧
19 81M Mains Time ⟦blank source cell⟧ ⟦blank source cell⟧
20 81N Energy ⟦blank source cell⟧ ⟦blank source cell⟧
21 820 Trip Message ⟦blank source cell⟧ ⟦blank source cell⟧
22 821 Process Value ⟦blank source cell⟧ ⟦blank source cell⟧
23 822 Speed ⟦blank source cell⟧ ⟦blank source cell⟧
24 823 Torque ⟦blank source cell⟧ ⟦blank source cell⟧
25 824 Shaft Power ⟦blank source cell⟧ ⟦blank source cell⟧
26 825 Electrical Power ⟦blank source cell⟧ ⟦blank source cell⟧
27 826 Current ⟦blank source cell⟧ ⟦blank source cell⟧
28 827 Output voltage ⟦blank source cell⟧ ⟦blank source cell⟧
29 828 Frequency ⟦blank source cell⟧ ⟦blank source cell⟧
30 829 DC Link voltage ⟦blank source cell⟧ ⟦blank source cell⟧
31 82A Heatsink Tmp ⟦blank source cell⟧ ⟦blank source cell⟧
32 82B PT100_1, 2, 3 ⟦blank source cell⟧ ⟦blank source cell⟧
33 82C AC drive Status ⟦blank source cell⟧ ⟦blank source cell⟧
34 82D DigIn status ⟦blank source cell⟧ ⟦blank source cell⟧
35 82E DigOut status ⟦blank source cell⟧ ⟦blank source cell⟧
36 82F AnIn status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
37 82G AnIn status 3 4 ⟦blank source cell⟧ ⟦blank source cell⟧
38 82H AnOut status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
39 82I IO Status B1 ⟦blank source cell⟧ ⟦blank source cell⟧
40 82J IO Status B2 ⟦blank source cell⟧ ⟦blank source cell⟧
41 82K IO Status B3 ⟦blank source cell⟧ ⟦blank source cell⟧
42 82L Run Time ⟦blank source cell⟧ ⟦blank source cell⟧
43 82M Mains Time ⟦blank source cell⟧ ⟦blank source cell⟧
44 82N Energy ⟦blank source cell⟧ ⟦blank source cell⟧
45 830 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
46 831 Process Value ⟦blank source cell⟧ ⟦blank source cell⟧
47 832 Speed ⟦blank source cell⟧ ⟦blank source cell⟧
48 833 Torque ⟦blank source cell⟧ ⟦blank source cell⟧
49 834 Shaft Power ⟦blank source cell⟧ ⟦blank source cell⟧
50 835 Electrical Power ⟦blank source cell⟧ ⟦blank source cell⟧
51 836 Current ⟦blank source cell⟧ ⟦blank source cell⟧
52 837 Output voltage ⟦blank source cell⟧ ⟦blank source cell⟧
53 838 Frequency ⟦blank source cell⟧ ⟦blank source cell⟧
54 839 DC Link voltage ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Menu summary default/custom columns. P034 association only. — page 205

Manual reference: physical PDF page 205. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Menu list physical panel1. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Menu list physical panel2. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Menu list physical panel1 — PDF page 205

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 83A Heatsink Temperature ⟦blank source cell⟧ ⟦blank source cell⟧
2 83B PT100_1, 2, 3 ⟦blank source cell⟧ ⟦blank source cell⟧
3 83C AC drive Status ⟦blank source cell⟧ ⟦blank source cell⟧
4 83D DigIn status ⟦blank source cell⟧ ⟦blank source cell⟧
5 83E DigOut status ⟦blank source cell⟧ ⟦blank source cell⟧
6 83F AnIn status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
7 83G AIn status 3 4 ⟦blank source cell⟧ ⟦blank source cell⟧
8 83H AnOut status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
9 83I IO Status B1 ⟦blank source cell⟧ ⟦blank source cell⟧
10 83J IO Status B2 ⟦blank source cell⟧ ⟦blank source cell⟧
11 83K IO Status B3 ⟦blank source cell⟧ ⟦blank source cell⟧
12 83L Run Time ⟦blank source cell⟧ ⟦blank source cell⟧
13 83M Mains Time ⟦blank source cell⟧ ⟦blank source cell⟧
14 83N Energy ⟦blank source cell⟧ ⟦blank source cell⟧
15 840 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
16 841 Process Value ⟦blank source cell⟧ ⟦blank source cell⟧
17 842 Speed ⟦blank source cell⟧ ⟦blank source cell⟧
18 843 Torque ⟦blank source cell⟧ ⟦blank source cell⟧
19 844 Shaft Power ⟦blank source cell⟧ ⟦blank source cell⟧
20 845 Electrical Power ⟦blank source cell⟧ ⟦blank source cell⟧
21 846 Current ⟦blank source cell⟧ ⟦blank source cell⟧
22 847 Output voltage ⟦blank source cell⟧ ⟦blank source cell⟧
23 848 Frequency ⟦blank source cell⟧ ⟦blank source cell⟧
24 849 DC Link voltage ⟦blank source cell⟧ ⟦blank source cell⟧
25 84A Heatsink Tmp ⟦blank source cell⟧ ⟦blank source cell⟧
26 84B PT100_1, 2, 3 ⟦blank source cell⟧ ⟦blank source cell⟧
27 84C AC drive Status ⟦blank source cell⟧ ⟦blank source cell⟧
28 84D DigIn status ⟦blank source cell⟧ ⟦blank source cell⟧
29 84E DigOut status ⟦blank source cell⟧ ⟦blank source cell⟧
30 84F AnIn status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
31 84G AnIn status 3 4 ⟦blank source cell⟧ ⟦blank source cell⟧
32 84H AnOut status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
33 84I IO Status B1 ⟦blank source cell⟧ ⟦blank source cell⟧
34 84J IO Status B2 ⟦blank source cell⟧ ⟦blank source cell⟧
35 84K IO Status B3 ⟦blank source cell⟧ ⟦blank source cell⟧
36 84L Run Time ⟦blank source cell⟧ ⟦blank source cell⟧
37 84M Mains Time ⟦blank source cell⟧ ⟦blank source cell⟧
38 84N Energy ⟦blank source cell⟧ ⟦blank source cell⟧
39 850 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
40 851 Process Value ⟦blank source cell⟧ ⟦blank source cell⟧
41 852 Speed ⟦blank source cell⟧ ⟦blank source cell⟧
42 853 Torque ⟦blank source cell⟧ ⟦blank source cell⟧
43 854 Shaft Power ⟦blank source cell⟧ ⟦blank source cell⟧
44 855 Electrical Power ⟦blank source cell⟧ ⟦blank source cell⟧
45 856 Current ⟦blank source cell⟧ ⟦blank source cell⟧
46 857 Output voltage ⟦blank source cell⟧ ⟦blank source cell⟧
47 858 Frequency ⟦blank source cell⟧ ⟦blank source cell⟧
48 859 DC Link voltage ⟦blank source cell⟧ ⟦blank source cell⟧
49 85A Heatsink Tmp ⟦blank source cell⟧ ⟦blank source cell⟧
50 85B PT100_1, 2, 3 ⟦blank source cell⟧ ⟦blank source cell⟧
51 85C AC drive Status ⟦blank source cell⟧ ⟦blank source cell⟧
52 85D DigIn status ⟦blank source cell⟧ ⟦blank source cell⟧
53 85E DigOut status ⟦blank source cell⟧ ⟦blank source cell⟧
54 85F AnIn 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧

Menu list physical panel2 — PDF page 205

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 85G AnIn 3 4 ⟦blank source cell⟧ ⟦blank source cell⟧
2 85H AnIOut 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
3 85I IO Status B1 ⟦blank source cell⟧ ⟦blank source cell⟧
4 85J IO Status B2 ⟦blank source cell⟧ ⟦blank source cell⟧
5 85K IO Status B3 ⟦blank source cell⟧ ⟦blank source cell⟧
6 85L Run Time ⟦blank source cell⟧ ⟦blank source cell⟧
7 85M Mains Time ⟦blank source cell⟧ ⟦blank source cell⟧
8 85N Energy ⟦blank source cell⟧ ⟦blank source cell⟧
9 860 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
10 861 Process Value ⟦blank source cell⟧ ⟦blank source cell⟧
11 862 Speed ⟦blank source cell⟧ ⟦blank source cell⟧
12 863 Torque ⟦blank source cell⟧ ⟦blank source cell⟧
13 864 Shaft Power ⟦blank source cell⟧ ⟦blank source cell⟧
14 865 Electrical Power ⟦blank source cell⟧ ⟦blank source cell⟧
15 866 Current ⟦blank source cell⟧ ⟦blank source cell⟧
16 867 Output voltage ⟦blank source cell⟧ ⟦blank source cell⟧
17 868 Frequency ⟦blank source cell⟧ ⟦blank source cell⟧
18 869 DC Link voltage ⟦blank source cell⟧ ⟦blank source cell⟧
19 86A Heatsink Tmp ⟦blank source cell⟧ ⟦blank source cell⟧
20 86B PT100_1, 2, 3 ⟦blank source cell⟧ ⟦blank source cell⟧
21 86C AC drive Status ⟦blank source cell⟧ ⟦blank source cell⟧
22 86D DigIn status ⟦blank source cell⟧ ⟦blank source cell⟧
23 86E DigOut status ⟦blank source cell⟧ ⟦blank source cell⟧
24 86F AnIn 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
25 86G AnIn 3 4 ⟦blank source cell⟧ ⟦blank source cell⟧
26 86H AnOut 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
27 86I IO Status B1 ⟦blank source cell⟧ ⟦blank source cell⟧
28 86J IO Status B 2 ⟦blank source cell⟧ ⟦blank source cell⟧
29 86K IO Status B3 ⟦blank source cell⟧ ⟦blank source cell⟧
30 86L Run Time ⟦blank source cell⟧ ⟦blank source cell⟧
31 86M Mains Time ⟦blank source cell⟧ ⟦blank source cell⟧
32 86N Energy ⟦blank source cell⟧ ⟦blank source cell⟧
33 870 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
34 871 Process Value ⟦blank source cell⟧ ⟦blank source cell⟧
35 872 Speed ⟦blank source cell⟧ ⟦blank source cell⟧
36 873 Torque ⟦blank source cell⟧ ⟦blank source cell⟧
37 874 Shaft Power ⟦blank source cell⟧ ⟦blank source cell⟧
38 875 Electrical Power ⟦blank source cell⟧ ⟦blank source cell⟧
39 876 Current ⟦blank source cell⟧ ⟦blank source cell⟧
40 877 Output voltage ⟦blank source cell⟧ ⟦blank source cell⟧
41 878 Frequency ⟦blank source cell⟧ ⟦blank source cell⟧
42 879 DC Link voltage ⟦blank source cell⟧ ⟦blank source cell⟧
43 87A Heatsink Tmpe ⟦blank source cell⟧ ⟦blank source cell⟧
44 87B PT100_1, 2, 3 ⟦blank source cell⟧ ⟦blank source cell⟧
45 87C AC drive Status ⟦blank source cell⟧ ⟦blank source cell⟧
46 87D DigIn status ⟦blank source cell⟧ ⟦blank source cell⟧
47 87E DigOut status ⟦blank source cell⟧ ⟦blank source cell⟧
48 87F AnIn status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
49 87G AnIn status 3 4 ⟦blank source cell⟧ ⟦blank source cell⟧
50 87H AnOut status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
51 87I IO Status B1 ⟦blank source cell⟧ ⟦blank source cell⟧
52 87J IO Status B2 ⟦blank source cell⟧ ⟦blank source cell⟧
53 87K IO Status B3 ⟦blank source cell⟧ ⟦blank source cell⟧
54 87L Run Time ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Menu summary default/custom columns. P034 association only. — page 206

Manual reference: physical PDF page 206. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Menu list physical panel1. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Menu list physical panel2. F33 software4.3X editionr3. Menu summary default/custom columns. Native nulls denote merged cell spans; preserve physical parent evidence. No inferred unit/rating/applicability. Menu summary may differ from detailed parameter pages; source differences retained, customcolumn is userform not configured customerdata. Printed DEFAULT/CUSTOM headings govern final2columns; blank custom fields represent unfilled source form.

Menu list physical panel1 — PDF page 206

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 87M Mains Time ⟦blank source cell⟧ ⟦blank source cell⟧
2 87N Energy ⟦blank source cell⟧ ⟦blank source cell⟧
3 880 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
4 881 Process Value ⟦blank source cell⟧ ⟦blank source cell⟧
5 882 Speed ⟦blank source cell⟧ ⟦blank source cell⟧
6 818 Torque ⟦blank source cell⟧ ⟦blank source cell⟧
7 884 Shaft Power ⟦blank source cell⟧ ⟦blank source cell⟧
8 885 Electrical Power ⟦blank source cell⟧ ⟦blank source cell⟧
9 886 Current ⟦blank source cell⟧ ⟦blank source cell⟧
10 887 Output voltage ⟦blank source cell⟧ ⟦blank source cell⟧
11 888 Frequency ⟦blank source cell⟧ ⟦blank source cell⟧
12 889 DC Link voltage ⟦blank source cell⟧ ⟦blank source cell⟧
13 88A Heatsink Tmp ⟦blank source cell⟧ ⟦blank source cell⟧
14 88B PT100_1, 2, 3 ⟦blank source cell⟧ ⟦blank source cell⟧
15 88C AC drive Status ⟦blank source cell⟧ ⟦blank source cell⟧
16 88D DigIn status ⟦blank source cell⟧ ⟦blank source cell⟧
17 88E DigOut status ⟦blank source cell⟧ ⟦blank source cell⟧
18 88F AnIn status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
19 88G AnIn status 3 4 ⟦blank source cell⟧ ⟦blank source cell⟧
20 88H AnOut status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
21 88I IO Status B1 ⟦blank source cell⟧ ⟦blank source cell⟧
22 88J IO Status B2 ⟦blank source cell⟧ ⟦blank source cell⟧
23 88K IO Status B3 ⟦blank source cell⟧ ⟦blank source cell⟧
24 88L Run Time ⟦blank source cell⟧ ⟦blank source cell⟧
25 88M Mains Time ⟦blank source cell⟧ ⟦blank source cell⟧
26 88N Energy ⟦blank source cell⟧ ⟦blank source cell⟧
27 890 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
28 891 Process Value ⟦blank source cell⟧ ⟦blank source cell⟧
29 892 Speed ⟦blank source cell⟧ ⟦blank source cell⟧
30 893 Torque ⟦blank source cell⟧ ⟦blank source cell⟧
31 894 Shaft Power ⟦blank source cell⟧ ⟦blank source cell⟧
32 895 Electrical Power ⟦blank source cell⟧ ⟦blank source cell⟧
33 896 Current ⟦blank source cell⟧ ⟦blank source cell⟧
34 897 Output voltage ⟦blank source cell⟧ ⟦blank source cell⟧
35 898 Frequency ⟦blank source cell⟧ ⟦blank source cell⟧
36 899 DC Link voltage ⟦blank source cell⟧ ⟦blank source cell⟧
37 89A Heatsink Tmp ⟦blank source cell⟧ ⟦blank source cell⟧
38 89B PT100_1, 2, 3 ⟦blank source cell⟧ ⟦blank source cell⟧
39 89C AC drive Status ⟦blank source cell⟧ ⟦blank source cell⟧
40 89D DigIn status ⟦blank source cell⟧ ⟦blank source cell⟧
41 89E DigOut status ⟦blank source cell⟧ ⟦blank source cell⟧
42 89F AnIn status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
43 89G AnIn status 3 4 ⟦blank source cell⟧ ⟦blank source cell⟧
44 89H AnOut status 1 2 ⟦blank source cell⟧ ⟦blank source cell⟧
45 89I IO Status B1 ⟦blank source cell⟧ ⟦blank source cell⟧
46 89J IO Status B2 ⟦blank source cell⟧ ⟦blank source cell⟧
47 89K IO Status B3 ⟦blank source cell⟧ ⟦blank source cell⟧
48 89L Run Time ⟦blank source cell⟧ ⟦blank source cell⟧
49 89M Mains Time ⟦blank source cell⟧ ⟦blank source cell⟧
50 89N Energy ⟦blank source cell⟧ ⟦blank source cell⟧
51 8A0 Reset Trip No ⟦blank source cell⟧
52 900 System Data ⟦blank source cell⟧ ⟦blank source cell⟧
53 920 AC drive Data ⟦blank source cell⟧ ⟦blank source cell⟧
54 921 AC drive Type ⟦blank source cell⟧ ⟦blank source cell⟧

Menu list physical panel2 — PDF page 206

Source row Menu/group identifier Name Default (source summary) Custom (blank form)
1 922 Software ⟦blank source cell⟧ ⟦blank source cell⟧
2 923 Unit name 0 ⟦blank source cell⟧

Manual — Menu List — page 207

Manual reference: physical PDF page 207. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Visually footer-only; no engineering body content.

Manual — Printed index navigation references. P034 association only. — page 208

Manual reference: physical PDF page 208. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Index

Symbols

+10VDC Supply voltage ..............196

+24VDC Supply voltage ..............196

Numerics

-10VDC Supply voltage ...............196

Menu

73, 86, 89, 104, 106, 119, 122

4-20mA ........................................125

............................123, 125, 126

A

Abbreviations ...................................8

Acceleration ............................94, 96

Acceleration ramp ................. 96

Acceleration time ................... 94

Ramp type .............................. 96

Alarm trip ..................................... 117

Alternating MASTER 43, 46, 47, 111

Ambient temperature and derating ..

Analogue comparators ...............140

Analogue input ............................123

AnIn1 ....................................123

AnIn2 ...........................128, 129

Offset ...........................124, 132

Analogue Output .......132, 135, 196

AnOut 1 .......................132, 135

Output configuration ..132, 135

AND operator .............................. 151

AnIn2 ...........................................128

AnIn3 ...........................................129

AnIn4 ...........................................129

Autoreset ................... 2, 38, 80, 170

B

Baudrate .......................... 57, 87, 88

Brake chopper ............................ 176

Brake function ....................... 98, 99

Bake release time ................. 98

Brake ...................................... 99

Brake Engage Time ............... 99

Brake wait time ....................100

Release speed ....................... 99

Vector Brake ........................100

Brake functions

Frequency ............................123

Brake resistors ............................ 176

C

Cable cross-section ....................191

Cable specifications ..................... 20

Cascade controller ........................ 42

CE-marking .......................................7

Change Condition .......................112

Change Timer ..............................112

Checklist ........................................ 47

Clockwise rotary field ..................130

Com Type .......................................87

Comparators ................................140

Connecting control signals ...........26

Connections

Brake chopper connections ..16

Control signal connections ....26

Mains supply ................... 16, 29

Motor earth ..................... 16, 29

Motor output ................... 16, 29

Safety earth ..................... 16, 29

Control panel .................................53

Control Panel memory ..................40

Copy all settings to Control Panel

.................................................79

Frequency .............................123

Control signal connections ...........26

Control signals ........................24, 27

Edge-controlled ............... 39, 68

Level-controlled ............... 39, 68

Counter-clockwise rotary field ....130

ctrical ...........................................158

Current ...........................................24

Current control (0-20mA) .............28

D

DC-link residual voltage .................. 2

Deceleration ..................................95

Deceleration time ..................95

Ramp type .............................. 97

Declaration of Conformity .............. 7

Default ...........................................78

Definitions ....................................... 8

Derating .......................................188

Digital comparators ....................140

Digital inputs

Board Relay ..........................138

DigIn 1 ..................................130

DigIn 2 ..................................131

DigIn 3 ..................................131

Dismantling and scrapping ............ 7

Display ...........................................53

Double-ended connection ............27

Drive mode ....................................65

Drives on Change ........................112

E

ECP ...............................................175

Edge control ........................... 39, 68

Electrical specification ................187

EMC ................................................16

Current control (0-20mA) ......28

Double-ended connection .....27

RFI mains filter .......................16

Single-ended connection .......27

Twisted cables ........................28

Emergency stop .............................51

EN60204-1 ......................................7

EN61800-3 ......................................7

EN61800-5-1 ..................................7

Enable ............................37, 55, 130

EXOR operator .............................151

Expression ...................................151

External Control Panel ............... 175

F

Factory settings .............................78

Fail safe .........................................44

Fans ............................................. 111

Feedback 'Status' input ................43

Fieldbus ................................87, 178

Fixed MASTER .......................47, 111

Flux optimization ........................ 105

Frequency

Frequency priority ..................36

Jog Frequency ..................... 103

Maximum Frequency ..101, 102

Minimum Frequency ........... 101

Preset Frequency ................ 106

Skip Frequency ........... 102, 103

Frequency priority ..........................36

Fuses, cable cross-sections and

glands .......................................... 191

G

General electrical specifications 187

Global parameters ........................77

H

Hydrophore controller ...................42

I

I/O Board .....................................177

I/O board option ............................42

I2t protection

Motor I2t Current .............74, 76

Motor I2t Type ........................74

ID run .............................................71

Identification Run ................... 40, 71

IEC269 ........................................ 191

Interrupt ..................................88, 89

IT Mains supply ................................2

IxR Compensation ...................... 104

J

Jog Frequency ............................. 103

K

Keyboard reference ....................107

Keys ................................................55

Manual — Printed index navigation references. P034 association only. — page 209

Manual reference: physical PDF page 209. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Control keys ........................... 55

ENTER key .............................. 56

ESCAPE key ............................ 56

Function keys ......................... 56

NEXT key ................................ 56

PREVIOUS key ........................ 56

RUN L ..................................... 55

RUN R ..................................... 55

STOP/RESET .......................... 55

Toggle Key .............................. 55

L

LCD display ................................... 53

Level control ........................... 39, 68

Load default .................................. 78

Load monitor ........................ 40, 117

Local/Remote ............................... 67

Lock code ...................................... 67

Long motor cables ........................ 18

Low Voltage Directive ......................7

Lower Band .................................113

Lower Band Limit ........................114

M

Machine Directive ............................7

Main menu .................................... 57

Mains supply ....................16, 23, 29

Maintenance ................................174

Manis cables ................................. 15

Max Frequency ..................... 94, 102

Memory ......................................... 40

Menu

(110) ...................................... 63

(120) ...................................... 64

(210) ...................................... 64

(211) ...................................... 64

(212) ...................................... 65

(213) ...................................... 65

(214) ...................................... 65

(215) ...................................... 66

(216) ...................................... 66

(217) ...................................... 67

(218) ...................................... 67

(219) ...................................... 67

(21A) ....................................... 68

(21B) ...................................... 68

(220) ...................................... 69

(221) ...................................... 69

(222) ...................................... 69

(223) ...................................... 69

(224) ...................................... 70

(225) ...................................... 70

(226) ...................................... 70

(227) ...................................... 70

(228) .......................................71

(229) .......................................71

(22A) ....................................... 72

(22B) ...................................... 72

(22C) .......................................72

(22D) .......................................72

(230) ....................................... 74

(231) ....................................... 74

(232) ....................................... 74

(233) ....................................... 74

(234) .......................................75

(235) ....................................... 76

(236) ....................................... 76

(237) .......................................77

(240) .......................................77

(241) .......................................77

(242) .......................................78

(243) .......................................78

(244) .......................................79

(245) .......................................79

(250) .......................................80

(251) .......................................80

(252) .......................................80

(253) .......................................81

(254) .......................................81

(255) .......................................81

(256) .......................................81

(257) .......................................82

(258) .......................................82

(259) .......................................82

(25A) .......................................82

(25B) .......................................82

(25C) .......................................82

(25D) .......................................83

(25E) .......................................83

(25F) .......................................83

(25G) .......................................83

(25H) .......................................84

(25I) ........................................84

(25J) ........................................84

(25K) .......................................84

(25L) .......................................84

(25M) ......................................85

(25N) ................................ 80, 85

(25O) .......................................85

(25P) .......................................85

(25Q) .......................................85

(25R) .......................................86

(25S) .......................................86

(25T) .......................................86

(25U) .......................................86

(260) .......................................87

(261) .......................................87

(262) .......................................87

(2621) ....................................87

(2622) ....................................87

(263) .......................................87

(2631) ....................................87

(2632) ....................................87

(2633) ....................................88

(2634) ....................................88

(264) .......................................88

(265) .......................................89

(269) .......................................89

(310) .......................................90

(320) .......................................91

(321) .......................................91

(322) .......................................91

(323) .......................................92

(324) .......................................93

(325) .......................................93

(326) .......................................93

(327) .......................................93

(328) .......................................94

(331) .......................................94

(332) .......................................95

(333) .......................................95

(334) .......................................95

(335) .......................................96

(336) .......................................96

(337) .......................................96

(338) .......................................97

(339) .......................................97

(33A) .......................................97

(33B) .......................................98

(33C) .......................................98

(33D) .......................................99

(33E) .......................................99

(33F) .................................... 100

(33G) .................................... 100

(33H1) .................................. 100

(341) .................................... 101

(342) .................................... 101

(343) .................................... 102

(344) .................................... 102

(345) .................................... 103

(346) .................................... 103

(347) .................................... 103

(348) .................................... 103

(351) .................................... 104

(354) .................................... 105

(361) .................................... 106

(362) .................................... 106

(363) .................................... 106

(364) .................................... 106

(365) .................................... 106

(366) .................................... 106

(367) .................................... 106

(368) .................................... 106

(369) .....................................107

(380) .....................................107

(381) .....................................107

(383) .....................................107

(384) .................................... 108

(385) .................................... 108

(386) .................................... 108

(387) .................................... 108

(388) .................................... 109

(389) .................................... 109

(391) .................................... 111

(392) .................................... 111

(393) .................................... 111

(394) .................................... 112

(395) .................................... 112

Manual — Printed index navigation references. P034 association only. — page 210

Manual reference: physical PDF page 210. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(396) ....................................112

(398) ....................................113

(399) ....................................113

(39A) .....................................114

(39B) ....................................114

(39C) .....................................114

(39D) ....................................114

(39E) .....................................115

(39F) .....................................115

(39G) ....................................116

(39H-39M) ...........................116

(410) .................................... 117

(411) .................................... 117

(412) .................................... 117

(413) ....................................118

(414) ....................................118

(415) ....................................118

(416) ....................................119

(4162) ..................................119

(417) ....................................119

(4171) ..................................119

(4172) ..................................119

(418) ....................................119

(4181) ..................................119

(4182) ..................................120

(419) ....................................120

(4191) ..................................120

(4192) ..................................120

(41A) .....................................120

(41B) ....................................121

(41C) .....................................121

(421) ....................................122

(422) ....................................122

(423) ....................................122

(424) ....................................123

(511) ....................................123

(512) ....................................124

(513) ....................................125

(514) ....................................128

(515) ....................................128

(516) ....................................128

(517) ....................................128

(518) ....................................129

(519) ....................................129

(51A) .....................................129

(51B) ....................................129

(51C) .....................................129

(521) ...........................100, 130

(522) ....................................131

(529-52H) ............................131

(531) ....................................132

(532) ....................................132

(533) ....................................133

(534) ....................................135

(535) ....................................135

(536) ....................................135

(541) ....................................136

(542) ....................................138

(551) ....................................138

(552) ....................................138

(553) .....................................138

(55D) .....................................139

(561) .....................................139

(562) .....................................140

(563-56G) .............................140

(610) .....................................140

(6111) ..................................141

(6112) ..................................143

(6113) ..................................145

(6114) ..................................145

(6115) ..................................145

(6121) ..................................146

(6122) ..................................146

(6123) ..................................146

(6124) ..................................147

(6125) ..................................147

(6131) ..................................147

(6132) ..................................147

(6133) ..................................148

(6134) ..................................148

(6135) ..................................148

(6141) ..................................148

(6142) ..................................149

(6143) ..................................149

(6144) ..................................149

(6145) ..................................149

(6151) ..................................150

(6152) ..................................150

(6153) ..................................150

(6154) ..................................150

(620) .....................................151

(621) ............................151, 152

(622) ............................151, 152

(623) ............................151, 152

(624) .....................................151

(625) .....................................151

(630) .....................................153

(631) .....................................153

(632) .....................................153

(633) .....................................154

(634) .....................................154

(635) .....................................154

(640) .....................................154

(641) .....................................154

(642) .....................................155

(643) .....................................155

(644) .....................................155

(645) .....................................155

(649) .....................................156

(650) .....................................156

(651) .....................................156

(652) .....................................156

(653) .....................................156

(654) .....................................156

(655) .....................................157

(659) .....................................157

(711) .....................................157

(712) .....................................157

(713) .....................................158

(714) .....................................158

(715) .................................... 158

(716) .................................... 158

(717) .................................... 158

(718) .................................... 159

(719) .................................... 159

(71A) .................................... 159

(71B) .................................... 159

(720) .................................... 160

(721) .................................... 160

(722) .................................... 160

(723) .....................................161

(724) .....................................161

(725) .....................................161

(726) .....................................161

(727) .................................... 162

(728-72A) ............................ 162

(730) .................................... 163

(731) .................................... 163

(7311) .................................. 163

(732) .................................... 163

(733) .................................... 163

(7331) .................................. 164

(800) .................................... 164

(810) .................................... 164

(811-81N) ............................ 165

(820) .................................... 165

(830) .................................... 165

(8A0) .................................... 166

(900) .................................... 166

(920) .................................... 166

(922) .................................... 166

33F ....................................... 100

616 ...................................... 146

Minimum Frequency .....................96

Monitor function

Alarm Select ........................ 121

Delay time ............................ 118

Max Alarm .............................117

Overload ........................40, 117

Response delay .......... 119, 121

Start delay ........................... 118

Motor cables ..................................16

Motor cos phi (power factor) ........70

Motor data .....................................69

Motor frequency ............................70

Motor I2t Current .........................171

Motor identification run ................71

Motor Lost ......................................81

Motor lost .................................... 122

Motor Potentiometer ......... 106, 130

Motor potentiometer .................. 130

Motor ventilation ...........................71

Motors ..............................................5

Motors in parallel ..........................21

MotPot ............................................95

Multi-motor application .................65

N

Nominal motor frequency .......... 102

Number of drives ........................ 111

Manual — Printed index navigation references. P034 association only. — page 211

Manual reference: physical PDF page 211. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

O

Operation ....................................... 64

Options ................................. 28, 175

Brake chopper ..................... 176

External Control Panel (ECP) .....

I/O Board ............................. 177

Output coils ..........................178

Protection class IP23 and IP54 .

Serial communication, fieldbus .

OR operator ................................. 151

Output coils ................................. 178

Output Voltage ............................158

Overload ............................... 40, 117

Overload alarm ............................. 40

P

Parameter sets

Load default values ............... 78

Load parameter sets from Con-

trol Panel ................................ 79

Parameter Set Selection ....... 35

Select a Parameter set ......... 77

PID control ..................................... 45

PID Controller .............................. 107

Closed loop PID control .......108

Feedback signal .................. 107

PID D Time ...........................108

PID I Time .............................108

PID P Gain ............................ 107

Power LED ..................................... 54

Priority ........................................... 36

Process Protection ......................122

Process Value .............................157

Product standard, EMC ...................6

Programming ................................ 57

Protection class IP23 and IP54 . 175

PT100 Inputs ..........................76, 77

PTC input ....................................... 75

Pump size ...................................... 47

Pump/Fan Control ......................111

Q

Quick Setup Card .............................5

R

Reference

Frequency ............................122

Motor potentiometer ...........130

Reference signal ............. 65, 90

Set reference value ............... 90

Torque ..................................122

View reference value ............. 90

Reference control ......................... 65

Reference signal .................... 65, 66

Relay output ................................138

Relay 1 .................................138

Relay 2 .................................138

Relay 3 ..................................138

Release speed ..............................99

Remote control ..............................37

Reset command ..........................130

Reset control .................................66

Resolution .....................................63

RFI mains filter ..............................16

Rotation .........................................67

RS232/485 ...................................87

RUN ................................................54

Run command ...............................55

Run Left command .....................130

Run Right command ...................130

Running motor .............................. 97

S

Select Drive .................................111

Settle Time ..................................114

Setup menu ...................................57

Menu structure ......................56

Shaft power .................................158

Signal ground ..............................196

Single-ended connection ..............27

Software ......................................166

Sound characteristic .....................72

Speed ...........................................157

Spinstart ........................................ 97

Standards ........................................ 6

Start Delay ...................................113

Start/Stop settings .......................94

Status indications .........................53

Stop categories ............................. 51

Stop command ............................130

Stop Delay ...................................114

Stripping lengths ...........................20

Switches ........................................24

Switching frequency ......................72

Switching in motor cables ............18

T

Technical Data ............................183

Terminal connections ...................24

Test Run ........................................ 71

Timer ............................................112

Torque ..........................................104

Transition Frequency ..................115

Trip .................................................54

Trip causes and remidial action .170

Trip Message log .........................164

Trips, warnings and limits ...........169

Twisted cables ...............................28

Type code number .......................... 5

U

Underload ......................................40

Underload alarm .........................117

Unlock Code ..................................67

Upper Band .................................113

Menu

(397) 113

Upper Band Limit ....................... 114

V

V/Hz Mode .....................................65

Vector Brake ............................... 100

Ventilation ......................................71

View reference value .....................90

Voltage ...........................................24

VSD Data ..................................... 166

W

Wiring .............................................46

Manual — Publisher imprint and edition. P034 association only. — page 212

Manual reference: physical PDF page 212. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

TECO Electric & Machinery Co.,Ltd.

10F, No.3-1,Yuancyu St., Nangang District, Taipei City 115, Taiwan

Tel: +886-2-6615-9111, Fax: +886-2-6615-0933

Internet: www.teco.com.tw

Ver.03 2011.6

Back-cover imprint reads TECO Electric & Machinery Co.,Ltd.;10F,No.3-1,Yuancyu St.,Nangang District,Taipei City115,Taiwan;Tel.+886-2-6615-9111,Fax.+886-2-6615-0933;Internetwww.teco.com.tw;Ver.03 2011.6. Historical supplier imprint only, not current-contact verification.

Technical source 001 — Variable speed drive FDU48-003-54/ 0.75KW/ 380-480V

Source download: Datasheet3078.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-003-54/ 0.75KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 1 / 1 Variable Torque (kW/A): 0.75 / 2.5; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3078.pdf
39 / 1 / 1 Variable Torque (kW/A): 0.75 / 2.5; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3078.pdf

P034 / Variable speed drive FDU48-003-54/ 0.75KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-003-54/ 0.75KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-003-54/ 0.75KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-003-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 0.75 as printed in field/value C2
General specification / Rated Output Current(A) 2.5 as printed in field/value C2
General specification / Maximum Output Current(A) 3 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-003-54/ 0.75KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-003-54/ 0.75KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 416x 203x 203 (mm). mm C3

Technical source 002 — Variable speed drive FDU48-004-54/ 1.5KW/ 380-480V

Source download: Datasheet3079.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-004-54/ 1.5KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 2 / 2 Variable Torque (kW/A): 1.5 / 4; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3079.pdf
39 / 2 / 2 Variable Torque (kW/A): 1.5 / 4; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3079.pdf

P034 / Variable speed drive FDU48-004-54/ 1.5KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-004-54/ 1.5KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-004-54/ 1.5KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-004-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 1.5 as printed in field/value C2
General specification / Rated Output Current(A) 4 as printed in field/value C2
General specification / Maximum Output Current(A) 4.8 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-004-54/ 1.5KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-004-54/ 1.5KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 416x 203x 203 (mm). mm C3

Technical source 003 — Variable speed drive FDU69-002-54/ 1.5KW/ 400-690V

Source download: Datasheet3080.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-002-54/ 1.5KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 3 / 3 Variable Torque (kW/A): 1.5 / 2; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3080.pdf
39 / 3 / 3 Variable Torque (kW/A): 1.5 / 2; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3080.pdf

P034 / Variable speed drive FDU69-002-54/ 1.5KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-002-54/ 1.5KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-002-54/ 1.5KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-002-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 1.5 as printed in field/value C2
General specification / Rated Output Current(A) 2 as printed in field/value C2
General specification / Maximum Output Current(A) 3.2 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-002-54/ 1.5KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-002-54/ 1.5KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 314 (mm). mm C3

Technical source 004 — Variable speed drive FDU69-003-54/ 2.2KW/ 400-690V

Source download: Datasheet3081.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-003-54/ 2.2KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 4 / 4 Variable Torque (kW/A): 2.2 / 3; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3081.pdf
39 / 4 / 4 Variable Torque (kW/A): 2.2 / 3; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3081.pdf

P034 / Variable speed drive FDU69-003-54/ 2.2KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-003-54/ 2.2KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-003-54/ 2.2KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-003-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 2.2 as printed in field/value C2
General specification / Rated Output Current(A) 3 as printed in field/value C2
General specification / Maximum Output Current(A) 4.8 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-003-54/ 2.2KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-003-54/ 2.2KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 314 (mm). mm C3

Technical source 005 — Variable speed drive FDU48-006-54/ 2.2KW/ 380-480V

Source download: Datasheet3082.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-006-54/ 2.2KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 5 / 5 Variable Torque (kW/A): 2.2 / 6; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3082.pdf
39 / 5 / 5 Variable Torque (kW/A): 2.2 / 6; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3082.pdf

P034 / Variable speed drive FDU48-006-54/ 2.2KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-006-54/ 2.2KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-006-54/ 2.2KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-006-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 2.2 as printed in field/value C2
General specification / Rated Output Current(A) 6 as printed in field/value C2
General specification / Maximum Output Current(A) 7.2 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-006-54/ 2.2KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-006-54/ 2.2KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 416x 203x 203 (mm). mm C3

Technical source 006 — Variable speed drive FDU48-008-54/ 3KW/ 380-480V

Source download: Datasheet3083.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-008-54/ 3KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 6 / 6 Variable Torque (kW/A): 3 / 7.5; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3083.pdf
39 / 6 / 6 Variable Torque (kW/A): 3 / 7.5; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3083.pdf

P034 / Variable speed drive FDU48-008-54/ 3KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-008-54/ 3KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-008-54/ 3KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-008-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 3 as printed in field/value C2
General specification / Rated Output Current(A) 7.5 as printed in field/value C2
General specification / Maximum Output Current(A) 9 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-008-54/ 3KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-008-54/ 3KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 416x 203x 203 (mm). mm C3

Technical source 007 — Variable speed drive FDU69-004-54/ 3KW/ 400-690V

Source download: Datasheet3084.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-004-54/ 3KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 7 / 7 Variable Torque (kW/A): 3 / 4; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3084.pdf
39 / 7 / 7 Variable Torque (kW/A): 3 / 4; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3084.pdf

P034 / Variable speed drive FDU69-004-54/ 3KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-004-54/ 3KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-004-54/ 3KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-004-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 3 as printed in field/value C2
General specification / Rated Output Current(A) 4 as printed in field/value C2
General specification / Maximum Output Current(A) 6.4 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-004-54/ 3KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-004-54/ 3KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 314 (mm). mm C3

Technical source 008 — Variable speed drive FDU69-006-54/ 4KW/ 400-690V

Source download: Datasheet3085.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-006-54/ 4KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 8 / 8 Variable Torque (kW/A): 4 / 6; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3085.pdf
39 / 8 / 8 Variable Torque (kW/A): 4 / 6; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3085.pdf

P034 / Variable speed drive FDU69-006-54/ 4KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-006-54/ 4KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-006-54/ 4KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-006-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 4 as printed in field/value C2
General specification / Rated Output Current(A) 6 as printed in field/value C2
General specification / Maximum Output Current(A) 9.6 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-006-54/ 4KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-006-54/ 4KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 314 (mm). mm C3

Technical source 009 — Variable speed drive FDU48-010-54/ 4KW/ 380-480V

Source download: Datasheet3086.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-010-54/ 4KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 9 / 9 Variable Torque (kW/A): 4 / 9.5; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3086.pdf
39 / 9 / 9 Variable Torque (kW/A): 4 / 9.5; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3086.pdf

P034 / Variable speed drive FDU48-010-54/ 4KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-010-54/ 4KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-010-54/ 4KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-010-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 4 as printed in field/value C2
General specification / Rated Output Current(A) 9.5 as printed in field/value C2
General specification / Maximum Output Current(A) 11.4 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-010-54/ 4KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-010-54/ 4KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 416x 203x 203 (mm). mm C3

Technical source 010 — Variable speed drive FDU48-013-54/ 5.5KW/ 380-480V

Source download: Datasheet3087.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-013-54/ 5.5KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 10 / 10 Variable Torque (kW/A): 5.5 / 13; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3087.pdf
39 / 10 / 10 Variable Torque (kW/A): 5.5 / 13; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3087.pdf

P034 / Variable speed drive FDU48-013-54/ 5.5KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-013-54/ 5.5KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-013-54/ 5.5KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-013-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 5.5 as printed in field/value C2
General specification / Rated Output Current(A) 13 as printed in field/value C2
General specification / Maximum Output Current(A) 15.6 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-013-54/ 5.5KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-013-54/ 5.5KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 416x 203x 203 (mm). mm C3

Technical source 011 — Variable speed drive FDU69-008-54/ 5.5KW/ 400-690V

Source download: Datasheet3088.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-008-54/ 5.5KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 11 / 11 Variable Torque (kW/A): 5.5 / 8; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3088.pdf
39 / 11 / 11 Variable Torque (kW/A): 5.5 / 8; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3088.pdf

P034 / Variable speed drive FDU69-008-54/ 5.5KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-008-54/ 5.5KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-008-54/ 5.5KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-008-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 5.5 as printed in field/value C2
General specification / Rated Output Current(A) 8 as printed in field/value C2
General specification / Maximum Output Current(A) 12.8 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-008-54/ 5.5KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-008-54/ 5.5KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 314 (mm). mm C3

Technical source 012 — Variable speed drive FDU69-010-54/ 7.5KW/ 400-690V

Source download: Datasheet3089.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-010-54/ 7.5KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 12 / 12 Variable Torque (kW/A): 7.5 / 10; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3089.pdf
39 / 12 / 12 Variable Torque (kW/A): 7.5 / 10; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3089.pdf

P034 / Variable speed drive FDU69-010-54/ 7.5KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-010-54/ 7.5KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-010-54/ 7.5KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-010-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 7.5 as printed in field/value C2
General specification / Rated Output Current(A) 10 as printed in field/value C2
General specification / Maximum Output Current(A) 16 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-010-54/ 7.5KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-010-54/ 7.5KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 314 (mm). mm C3

Technical source 013 — Variable speed drive FDU48-018-54/ 7.5KW/ 380-480V

Source download: Datasheet3090.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-018-54/ 7.5KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 13 / 13 Variable Torque (kW/A): 7.5 / 18; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3090.pdf
39 / 13 / 13 Variable Torque (kW/A): 7.5 / 18; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3090.pdf

P034 / Variable speed drive FDU48-018-54/ 7.5KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-018-54/ 7.5KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-018-54/ 7.5KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-018-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 7.5 as printed in field/value C2
General specification / Rated Output Current(A) 18 as printed in field/value C2
General specification / Maximum Output Current(A) 21.6 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-018-54/ 7.5KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-018-54/ 7.5KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 416x 203x 203 (mm). mm C3

Technical source 014 — Variable speed drive FDU48-026-54/ 11KW/ 380-480V

Source download: Datasheet3091.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-026-54/ 11KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 14 / 14 Variable Torque (kW/A): 11.0 / 26; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3091.pdf
39 / 14 / 14 Variable Torque (kW/A): 11.0 / 26; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3091.pdf

P034 / Variable speed drive FDU48-026-54/ 11KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-026-54/ 11KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-026-54/ 11KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-026-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 11 as printed in field/value C2
General specification / Rated Output Current(A) 26 as printed in field/value C2
General specification / Maximum Output Current(A) 31 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-026-54/ 11KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-026-54/ 11KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 292 (mm). mm C3

Technical source 015 — Variable speed drive FDU69-013-54/ 11KW/ 400-690V

Source download: Datasheet3092.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-013-54/ 11KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 15 / 15 Variable Torque (kW/A): 11 / 13; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3092.pdf
39 / 15 / 15 Variable Torque (kW/A): 11 / 13; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3092.pdf

P034 / Variable speed drive FDU69-013-54/ 11KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-013-54/ 11KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-013-54/ 11KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-013-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 11 as printed in field/value C2
General specification / Rated Output Current(A) 13 as printed in field/value C2
General specification / Maximum Output Current(A) 20.8 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-013-54/ 11KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-013-54/ 11KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 314 (mm). mm C3

Technical source 016 — Variable speed drive FDU69-018-54/ 15KW/ 400-690V

Source download: Datasheet3093.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-018-54/ 15KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 16 / 16 Variable Torque (kW/A): 15 / 18; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3093.pdf
39 / 16 / 16 Variable Torque (kW/A): 15 / 18; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3093.pdf

P034 / Variable speed drive FDU69-018-54/ 15KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-018-54/ 15KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-018-54/ 15KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-018-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 15 as printed in field/value C2
General specification / Rated Output Current(A) 18 as printed in field/value C2
General specification / Maximum Output Current(A) 29 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-018-54/ 15KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-018-54/ 15KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 314 (mm). mm C3

Technical source 017 — Variable speed drive FDU48-031-54/ 15KW/ 380-480V

Source download: Datasheet3094.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-031-54/ 15KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 17 / 17 Variable Torque (kW/A): 15 / 31; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3094.pdf
39 / 17 / 17 Variable Torque (kW/A): 15 / 31; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3094.pdf

P034 / Variable speed drive FDU48-031-54/ 15KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-031-54/ 15KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-031-54/ 15KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-031-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 15 as printed in field/value C2
General specification / Rated Output Current(A) 31 as printed in field/value C2
General specification / Maximum Output Current(A) 37 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-031-54/ 15KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-031-54/ 15KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 292 (mm). mm C3

Technical source 018 — Variable speed drive FDU48-037-54/ 18.5KW/ 380-480V

Source download: Datasheet3095.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-037-54/ 18.5KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 18 / 18 Variable Torque (kW/A): 18.5 / 37; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3095.pdf
39 / 18 / 18 Variable Torque (kW/A): 18.5 / 37; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3095.pdf

P034 / Variable speed drive FDU48-037-54/ 18.5KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-037-54/ 18.5KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-037-54/ 18.5KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-037-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 18.5 as printed in field/value C2
General specification / Rated Output Current(A) 37 as printed in field/value C2
General specification / Maximum Output Current(A) 44 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-037-54/ 18.5KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-037-54/ 18.5KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 292 (mm). mm C3

Technical source 019 — Variable speed drive FDU69-021-54/ 18.5KW/ 400-690V

Source download: Datasheet3096.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-021-54/ 18.5KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 19 / 19 Variable Torque (kW/A): 18.5 / 21; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3096.pdf
39 / 19 / 19 Variable Torque (kW/A): 18.5 / 21; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3096.pdf

P034 / Variable speed drive FDU69-021-54/ 18.5KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-021-54/ 18.5KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-021-54/ 18.5KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-021-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 18.5 as printed in field/value C2
General specification / Rated Output Current(A) 21 as printed in field/value C2
General specification / Maximum Output Current(A) 34 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-021-54/ 18.5KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-021-54/ 18.5KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 314 (mm). mm C3

Technical source 020 — Variable speed drive FDU69-025-54/ 22KW/ 400-690V

Source download: Datasheet3097.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-025-54/ 22KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 20 / 20 Variable Torque (kW/A): 22 / 25; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3097.pdf
39 / 20 / 20 Variable Torque (kW/A): 22 / 25; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3097.pdf

P034 / Variable speed drive FDU69-025-54/ 22KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-025-54/ 22KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-025-54/ 22KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-025-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 22 as printed in field/value C2
General specification / Rated Output Current(A) 25 as printed in field/value C2
General specification / Maximum Output Current(A) 40 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-025-54/ 22KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-025-54/ 22KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 314 (mm). mm C3

Technical source 021 — Variable speed drive FDU48-046-54/ 22KW/ 380-480V

Source download: Datasheet3098.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-046-54/ 22KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 21 / 21 Variable Torque (kW/A): 22 / 46; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3098.pdf
39 / 21 / 21 Variable Torque (kW/A): 22 / 46; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3098.pdf

P034 / Variable speed drive FDU48-046-54/ 22KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-046-54/ 22KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-046-54/ 22KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-046-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 22 as printed in field/value C2
General specification / Rated Output Current(A) 46 as printed in field/value C2
General specification / Maximum Output Current(A) 55 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-046-54/ 22KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-046-54/ 22KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 512x 178x 292 (mm). mm C3

Technical source 022 — Variable speed drive FDU48-061-54/ 30KW/ 380-480V

Source download: Datasheet3099.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-061-54/ 30KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 22 / 22 Variable Torque (kW/A): 30 / 61; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3099.pdf
39 / 22 / 22 Variable Torque (kW/A): 30 / 61; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3099.pdf

P034 / Variable speed drive FDU48-061-54/ 30KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-061-54/ 30KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-061-54/ 30KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-061-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 30 as printed in field/value C2
General specification / Rated Output Current(A) 61 as printed in field/value C2
General specification / Maximum Output Current(A) 73 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-061-54/ 30KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-061-54/ 30KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 590x 220x 295 (mm). mm C3

Technical source 023 — Variable speed drive FDU69-033-54/ 30KW/ 400-690V

Source download: Datasheet3100.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-033-54/ 30KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 23 / 23 Variable Torque (kW/A): 30 / 33; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3100.pdf
39 / 23 / 23 Variable Torque (kW/A): 30 / 33; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3100.pdf

P034 / Variable speed drive FDU69-033-54/ 30KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-033-54/ 30KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-033-54/ 30KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-033-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 30 as printed in field/value C2
General specification / Rated Output Current(A) 33 as printed in field/value C2
General specification / Maximum Output Current(A) 53 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-033-54/ 30KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-033-54/ 30KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 590x 220x 295 (mm). mm C3

Technical source 024 — Variable speed drive FDU69-042-54/ 37KW/ 400-690V

Source download: Datasheet3101.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-042-54/ 37KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 24 / 24 Variable Torque (kW/A): 37 / 42; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3101.pdf
39 / 24 / 24 Variable Torque (kW/A): 37 / 42; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3101.pdf

P034 / Variable speed drive FDU69-042-54/ 37KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-042-54/ 37KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-042-54/ 37KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-042-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 37 as printed in field/value C2
General specification / Rated Output Current(A) 42 as printed in field/value C2
General specification / Maximum Output Current(A) 67 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-042-54/ 37KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-042-54/ 37KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 590x 220x 295 (mm). mm C3

Technical source 025 — Variable speed drive FDU48-074-54/ 37KW/ 380-480V

Source download: Datasheet3102.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-074-54/ 37KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 25 / 25 Variable Torque (kW/A): 37 / 74; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3102.pdf
39 / 25 / 25 Variable Torque (kW/A): 37 / 74; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3102.pdf

P034 / Variable speed drive FDU48-074-54/ 37KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-074-54/ 37KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-074-54/ 37KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-074-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 37 as printed in field/value C2
General specification / Rated Output Current(A) 74 as printed in field/value C2
General specification / Maximum Output Current(A) 89 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-074-54/ 37KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-074-54/ 37KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 590x 220x 295 (mm). mm C3

Technical source 026 — Variable speed drive FDU48-090-54/ 45KW/ 380-480V

Source download: Datasheet3103.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-090-54/ 45KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 26 / 26 Variable Torque (kW/A): 45 / 90; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3103.pdf
39 / 26 / 26 Variable Torque (kW/A): 45 / 90; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3103.pdf

P034 / Variable speed drive FDU48-090-54/ 45KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-090-54/ 45KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-090-54/ 45KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-090-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 45 as printed in field/value C2
General specification / Rated Output Current(A) 90 as printed in field/value C2
General specification / Maximum Output Current(A) 108 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-090-54/ 45KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-090-54/ 45KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 950x 285x 314 (mm). mm C3

Technical source 027 — Variable speed drive FDU69-050-54/ 45KW/ 400-690V

Source download: Datasheet3104.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-050-54/ 45KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 27 / 27 Variable Torque (kW/A): 45 / 50; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3104.pdf
39 / 27 / 27 Variable Torque (kW/A): 45 / 50; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3104.pdf

P034 / Variable speed drive FDU69-050-54/ 45KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-050-54/ 45KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-050-54/ 45KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-050-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 45 as printed in field/value C2
General specification / Rated Output Current(A) 50 as printed in field/value C2
General specification / Maximum Output Current(A) 80 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-050-54/ 45KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-050-54/ 45KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 590x 220x 295 (mm). mm C3

Technical source 028 — Variable speed drive FDU69-058-54/ 55KW/ 400-690V

Source download: Datasheet3105.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-058-54/ 55KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 28 / 28 Variable Torque (kW/A): 55 / 58; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3105.pdf
39 / 28 / 28 Variable Torque (kW/A): 55 / 58; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3105.pdf

P034 / Variable speed drive FDU69-058-54/ 55KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-058-54/ 55KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-058-54/ 55KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-058-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 55 as printed in field/value C2
General specification / Rated Output Current(A) 58 as printed in field/value C2
General specification / Maximum Output Current(A) 93 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-058-54/ 55KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-058-54/ 55KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 590x 220x 295 (mm). mm C3

Technical source 029 — Variable speed drive FDU48-109-54/ 55KW/ 380-480V

Source download: Datasheet3106.pdf.

Source download: Datasheet3112.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-109-54/ 55KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 29 / 29 Variable Torque (kW/A): 55 / 109; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3106.pdf
14 / 35 / 35 Variable Torque (kW/A): 110 / 109; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3112.pdf
39 / 29 / 29 Variable Torque (kW/A): 55 / 109; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3106.pdf
39 / 35 / 35 Variable Torque (kW/A): 110 / 109; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3112.pdf

P034 / Variable speed drive FDU48-109-54/ 55KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-109-54/ 55KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-109-54/ 55KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-109-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 55 as printed in field/value C2
General specification / Rated Output Current(A) 109 as printed in field/value C2
General specification / Maximum Output Current(A) 131 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-109-54/ 55KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-109-54/ 55KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 950x 285x 314 (mm). mm C3

Technical source 030 — Variable speed drive FDU48-146-54/ 75KW/ 380-480V

Source download: Datasheet3107.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-146-54/ 75KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 30 / 30 Variable Torque (kW/A): 75 / 146; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3107.pdf
39 / 30 / 30 Variable Torque (kW/A): 75 / 146; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3107.pdf

P034 / Variable speed drive FDU48-146-54/ 75KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-146-54/ 75KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-146-54/ 75KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-146-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 75 as printed in field/value C2
General specification / Rated Output Current(A) 146 as printed in field/value C2
General specification / Maximum Output Current(A) 175 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-146-54/ 75KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-146-54/ 75KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 950x 285x 314 (mm). mm C3

Technical source 031 — Variable speed drive FDU69-082-54/ 75KW/ 400-690V

Source download: Datasheet3108.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-082-54/ 75KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 31 / 31 Variable Torque (kW/A): 75 / 82; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3108.pdf
39 / 31 / 31 Variable Torque (kW/A): 75 / 82; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3108.pdf

P034 / Variable speed drive FDU69-082-54/ 75KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-082-54/ 75KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-082-54/ 75KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-082-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 75 as printed in field/value C2
General specification / Rated Output Current(A) 82 as printed in field/value C2
General specification / Maximum Output Current(A) 98 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-082-54/ 75KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-082-54/ 75KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 1090x 345x 314 (mm). mm C3

Technical source 032 — Variable speed drive FDU69-090-54/ 90KW/ 400-690V

Source download: Datasheet3109.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-090-54/ 90KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 32 / 32 Variable Torque (kW/A): 90 / 90; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3109.pdf
39 / 32 / 32 Variable Torque (kW/A): 90 / 90; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3109.pdf

P034 / Variable speed drive FDU69-090-54/ 90KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-090-54/ 90KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-090-54/ 90KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-090-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 90 as printed in field/value C2
General specification / Rated Output Current(A) 90 as printed in field/value C2
General specification / Maximum Output Current(A) 108 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-090-54/ 90KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-090-54/ 90KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 1090x 345x 314 (mm). mm C3

Technical source 033 — Variable speed drive FDU48-175-54/ 90KW/ 380-480V

Source download: Datasheet3110.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-175-54/ 90KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 33 / 33 Variable Torque (kW/A): 90 / 175; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3110.pdf
39 / 33 / 33 Variable Torque (kW/A): 90 / 175; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3110.pdf

P034 / Variable speed drive FDU48-175-54/ 90KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-175-54/ 90KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-175-54/ 90KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-175-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 90 as printed in field/value C2
General specification / Rated Output Current(A) 175 as printed in field/value C2
General specification / Maximum Output Current(A) 210 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-175-54/ 90KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-175-54/ 90KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 950x 285x 314 (mm). mm C3

Technical source 034 — Variable speed drive FDU48-210-54/ 110KW/ 380-480V

Source download: Datasheet3111.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-210-54/ 110KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 34 / 34 Variable Torque (kW/A): 110 / 210; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3111.pdf
39 / 34 / 34 Variable Torque (kW/A): 110 / 210; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3111.pdf

P034 / Variable speed drive FDU48-210-54/ 110KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-210-54/ 110KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-210-54/ 110KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-210-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 110 as printed in field/value C2
General specification / Rated Output Current(A) 210 as printed in field/value C2
General specification / Maximum Output Current(A) 252 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-210-54/ 110KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-210-54/ 110KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 950x 345x 314 (mm). mm C3

Technical source 035 — Variable speed drive FDU69-146-54/ 132KW/ 400-690V

Source download: Datasheet3113.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-146-54/ 132KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 36 / 36 Variable Torque (kW/A): 132 / 146; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3113.pdf
39 / 36 / 36 Variable Torque (kW/A): 132 / 146; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3113.pdf

P034 / Variable speed drive FDU69-146-54/ 132KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-146-54/ 132KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-146-54/ 132KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-146-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 132 as printed in field/value C2
General specification / Rated Output Current(A) 146 as printed in field/value C2
General specification / Maximum Output Current(A) 175 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-146-54/ 132KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-146-54/ 132KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 1090x 345x 314 (mm). mm C3

Technical source 036 — Variable speed drive FDU48-250-54/ 132KW/ 380-480V

Source download: Datasheet3114.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-250-54/ 132KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 37 / 37 Variable Torque (kW/A): 132 / 250; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3114.pdf
39 / 37 / 37 Variable Torque (kW/A): 132 / 250; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3114.pdf

P034 / Variable speed drive FDU48-250-54/ 132KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-250-54/ 132KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-250-54/ 132KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-250-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 132 as printed in field/value C2
General specification / Rated Output Current(A) 250 as printed in field/value C2
General specification / Maximum Output Current(A) 300 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-250-54/ 132KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-250-54/ 132KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 950x 345x 314 (mm). mm C3

Technical source 037 — Variable speed drive FDU48-295-54/ 160KW/ 380-480V

Source download: Datasheet3115.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-295-54/ 160KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 38 / 38 Variable Torque (kW/A): 160 / 295; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3115.pdf
39 / 38 / 38 Variable Torque (kW/A): 160 / 295; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3115.pdf

P034 / Variable speed drive FDU48-295-54/ 160KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-295-54/ 160KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-295-54/ 160KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-295-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 160 as printed in field/value C2
General specification / Rated Output Current(A) 295 as printed in field/value C2
General specification / Maximum Output Current(A) 354 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-295-54/ 160KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-295-54/ 160KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 950x 345x 314 (mm). mm C3

Technical source 038 — Variable speed drive FDU69-175-54/ 160KW/ 400-690V

Source download: Datasheet3116.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-175-54/ 160KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 39 / 39 Variable Torque (kW/A): 160 / 175; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3116.pdf
39 / 39 / 39 Variable Torque (kW/A): 160 / 175; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3116.pdf

P034 / Variable speed drive FDU69-175-54/ 160KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-175-54/ 160KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-175-54/ 160KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-175-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 160 as printed in field/value C2
General specification / Rated Output Current(A) 175 as printed in field/value C2
General specification / Maximum Output Current(A) 210 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-175-54/ 160KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-175-54/ 160KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 1090x 345x 314 (mm). mm C3

Technical source 039 — Variable speed drive FDU69-200-54/ 200KW/ 400-690V

Source download: Datasheet3117.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-200-54/ 200KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 40 / 40 Variable Torque (kW/A): 200 / 200; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3117.pdf
39 / 40 / 40 Variable Torque (kW/A): 200 / 200; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3117.pdf

P034 / Variable speed drive FDU69-200-54/ 200KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-200-54/ 200KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-200-54/ 200KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-200-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 200 as printed in field/value C2
General specification / Rated Output Current(A) 200 as printed in field/value C2
General specification / Maximum Output Current(A) 240 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-200-54/ 200KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-200-54/ 200KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 1090x 345x 314 (mm). mm C3

Technical source 040 — Variable speed drive FDU48-365-54/ 200KW/ 380-480V

Source download: Datasheet3118.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-365-54/ 200KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 41 / 41 Variable Torque (kW/A): 200 / 365; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3118.pdf
39 / 41 / 41 Variable Torque (kW/A): 200 / 365; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3118.pdf

P034 / Variable speed drive FDU48-365-54/ 200KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-365-54/ 200KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-365-54/ 200KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-365-54 as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 200 as printed in field/value C2
General specification / Rated Output Current(A) 365 as printed in field/value C2
General specification / Maximum Output Current(A) 438 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-365-54/ 200KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-365-54/ 200KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 1395x 345x 365 (mm). mm C3

Technical source 041 — Variable speed drive FDU48-430-IP/ 220KW/ 380-480V

Source download: Datasheet3119.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-430-IP/ 220KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 42 / 42 Variable Torque (kW/A): 220 / 430; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3119.pdf
39 / 42 / 42 Variable Torque (kW/A): 220 / 430; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3119.pdf

P034 / Variable speed drive FDU48-430-IP/ 220KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-430-IP/ 220KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-430-IP/ 220KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-430-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 220 as printed in field/value C2
General specification / Rated Output Current(A) 430 as printed in field/value C2
General specification / Maximum Output Current(A) 516 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-430-IP/ 220KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-430-IP/ 220KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 600x 600 (mm). mm C3

Technical source 042 — Variable speed drive FDU48-500-IP/ 250KW/ 380-480V

Source download: Datasheet3120.pdf.

Source download: Datasheet3130.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-500-IP/ 250KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 43 / 43 Variable Torque (kW/A): 250 / 500; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3120.pdf
14 / 53 / 53 Variable Torque (kW/A): 500 / 500; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3130.pdf
39 / 43 / 43 Variable Torque (kW/A): 250 / 500; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3120.pdf
39 / 53 / 53 Variable Torque (kW/A): 500 / 500; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3130.pdf

P034 / Variable speed drive FDU48-500-IP/ 250KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-500-IP/ 250KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-500-IP/ 250KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-500-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 250 as printed in field/value C2
General specification / Rated Output Current(A) 500 as printed in field/value C2
General specification / Maximum Output Current(A) 600 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-500-IP/ 250KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-500-IP/ 250KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 600x 600 (mm). mm C3

Technical source 043 — Variable speed drive FDU69-250-IP/ 250KW/ 400-690V

Source download: Datasheet3121.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-250-IP/ 250KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 44 / 44 Variable Torque (kW/A): 250 / 250; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3121.pdf
39 / 44 / 44 Variable Torque (kW/A): 250 / 250; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3121.pdf

P034 / Variable speed drive FDU69-250-IP/ 250KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-250-IP/ 250KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-250-IP/ 250KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-250-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 250 as printed in field/value C2
General specification / Rated Output Current(A) 250 as printed in field/value C2
General specification / Maximum Output Current(A) 300 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-250-IP/ 250KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-250-IP/ 250KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 600x 600 (mm). mm C3

Technical source 044 — Variable speed drive FDU69-300-IP/ 315KW/ 400-690V

Source download: Datasheet3122.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-300-IP/ 315KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 45 / 45 Variable Torque (kW/A): 315 / 300; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3122.pdf
39 / 45 / 45 Variable Torque (kW/A): 315 / 300; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3122.pdf

P034 / Variable speed drive FDU69-300-IP/ 315KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-300-IP/ 315KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-300-IP/ 315KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-300-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 315 as printed in field/value C2
General specification / Rated Output Current(A) 300 as printed in field/value C2
General specification / Maximum Output Current(A) 360 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-300-IP/ 315KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-300-IP/ 315KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 600x 600 (mm). mm C3

Technical source 045 — Variable speed drive FDU48-600-IP/ 315KW/ 380-480V

Source download: Datasheet3123.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-600-IP/ 315KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 46 / 46 Variable Torque (kW/A): 315 / 600; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3123.pdf
39 / 46 / 46 Variable Torque (kW/A): 315 / 600; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3123.pdf

P034 / Variable speed drive FDU48-600-IP/ 315KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-600-IP/ 315KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-600-IP/ 315KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-600-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 315 as printed in field/value C2
General specification / Rated Output Current(A) 600 as printed in field/value C2
General specification / Maximum Output Current(A) 720 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-600-IP/ 315KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-600-IP/ 315KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 900x 600 (mm). mm C3

Technical source 046 — Variable speed drive FDU48-650-IP/ 355KW/ 380-480V

Source download: Datasheet3124.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-650-IP/ 355KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 47 / 47 Variable Torque (kW/A): 355 / 650; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3124.pdf
39 / 47 / 47 Variable Torque (kW/A): 355 / 650; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3124.pdf

P034 / Variable speed drive FDU48-650-IP/ 355KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-650-IP/ 355KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-650-IP/ 355KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-650-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 355 as printed in field/value C2
General specification / Rated Output Current(A) 650 as printed in field/value C2
General specification / Maximum Output Current(A) 780 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-650-IP/ 355KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-650-IP/ 355KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 900x 600 (mm). mm C3

Technical source 047 — Variable speed drive FDU69-375-IP/ 355KW/ 400-690V

Source download: Datasheet3125.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-375-IP/ 355KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 48 / 48 Variable Torque (kW/A): 355 / 375; Supply: 690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3125.pdf
39 / 48 / 48 Variable Torque (kW/A): 355 / 375; Supply: 690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3125.pdf

P034 / Variable speed drive FDU69-375-IP/ 355KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-375-IP/ 355KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-375-IP/ 355KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-375-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 355 as printed in field/value C2
General specification / Rated Output Current(A) 375 as printed in field/value C2
General specification / Maximum Output Current(A) 450 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-375-IP/ 355KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-375-IP/ 355KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 600x 600 (mm). mm C3

Technical source 048 — Variable speed drive FDU69-400-IP/ 400KW/ 400-690V

Source download: Datasheet3126.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-400-IP/ 400KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 49 / 49 Variable Torque (kW/A): 400 / 400; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3126.pdf
39 / 49 / 49 Variable Torque (kW/A): 400 / 400; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3126.pdf

P034 / Variable speed drive FDU69-400-IP/ 400KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-400-IP/ 400KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-400-IP/ 400KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-400-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 400 as printed in field/value C2
General specification / Rated Output Current(A) 400 as printed in field/value C2
General specification / Maximum Output Current(A) 480 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-400-IP/ 400KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-400-IP/ 400KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 600x 600 (mm). mm C3

Technical source 049 — Variable speed drive FDU48-750-IP/ 400KW/ 380-480V

Source download: Datasheet3127.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-750-IP/ 400KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 50 / 50 Variable Torque (kW/A): 400 / 750; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3127.pdf
39 / 50 / 50 Variable Torque (kW/A): 400 / 750; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3127.pdf

P034 / Variable speed drive FDU48-750-IP/ 400KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-750-IP/ 400KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-750-IP/ 400KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-750-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 400 as printed in field/value C2
General specification / Rated Output Current(A) 750 as printed in field/value C2
General specification / Maximum Output Current(A) 900 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-750-IP/ 400KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-750-IP/ 400KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 900x 600 (mm). mm C3

Technical source 050 — Variable speed drive FDU48-1K0-IP/ 450KW/ 380-480V

Source download: Datasheet3128.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-1K0-IP/ 450KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 51 / 51 Variable Torque (kW/A): 450 / 860; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3128.pdf
39 / 51 / 51 Variable Torque (kW/A): 450 / 860; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3128.pdf

P034 / Variable speed drive FDU48-1K0-IP/ 450KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-1K0-IP/ 450KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-1K0-IP/ 450KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-860-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 450 as printed in field/value C2
General specification / Rated Output Current(A) 860 as printed in field/value C2
General specification / Maximum Output Current(A) 1032 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-1K0-IP/ 450KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-1K0-IP/ 450KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 1200x 600 (mm). mm C3

Technical source 051 — Variable speed drive FDU69-430-IP/ 450KW/ 400-690V

Source download: Datasheet3129.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-430-IP/ 450KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 52 / 52 Variable Torque (kW/A): 450 / 430; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3129.pdf
39 / 52 / 52 Variable Torque (kW/A): 450 / 430; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3129.pdf

P034 / Variable speed drive FDU69-430-IP/ 450KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-430-IP/ 450KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-430-IP/ 450KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-430-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 450 as printed in field/value C2
General specification / Rated Output Current(A) 430 as printed in field/value C2
General specification / Maximum Output Current(A) 516 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-430-IP/ 450KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-430-IP/ 450KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 900x 600 (mm). mm C3

Technical source 052 — Variable speed drive FDU48-1K0-IP/ 560KW/ 380-480V

Source download: Datasheet3131.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-1K0-IP/ 560KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 54 / 54 Variable Torque (kW/A): 560 / 1000; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3131.pdf
39 / 54 / 54 Variable Torque (kW/A): 560 / 1000; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3131.pdf

P034 / Variable speed drive FDU48-1K0-IP/ 560KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-1K0-IP/ 560KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-1K0-IP/ 560KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-1K0-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 560 as printed in field/value C2
General specification / Rated Output Current(A) 1000 as printed in field/value C2
General specification / Maximum Output Current(A) 1200 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-1K0-IP/ 560KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-1K0-IP/ 560KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 1200x 600 (mm). mm C3

Technical source 053 — Variable speed drive FDU69-595-IP/ 600KW/ 400-690V

Source download: Datasheet3132.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-595-IP/ 600KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 55 / 55 Variable Torque (kW/A): 600 / 600; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3132.pdf
39 / 55 / 55 Variable Torque (kW/A): 600 / 600; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3132.pdf

P034 / Variable speed drive FDU69-595-IP/ 600KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-595-IP/ 600KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-595-IP/ 600KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-595-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 600 as printed in field/value C2
General specification / Rated Output Current(A) 600 as printed in field/value C2
General specification / Maximum Output Current(A) 720 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-595-IP/ 600KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-595-IP/ 600KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 900x 600 (mm). mm C3

Technical source 054 — Variable speed drive FDU69-650-IP/ 630KW/ 400-690V

Source download: Datasheet3133.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-650-IP/ 630KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 56 / 56 Variable Torque (kW/A): 630 / 650; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3133.pdf

P034 / Variable speed drive FDU69-650-IP/ 630KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-650-IP/ 630KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-650-IP/ 630KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-650-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 630 as printed in field/value C2
General specification / Rated Output Current(A) 650 as printed in field/value C2
General specification / Maximum Output Current(A) 780 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-650-IP/ 630KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-650-IP/ 630KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 1200x 600 (mm). mm C3

Technical source 055 — Variable speed drive FDU48-1K15-IP/ 630KW/ 380-480V

Source download: Datasheet3134.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-1K15-IP/ 630KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 57 / 57 Variable Torque (kW/A): 630 / 1150; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3134.pdf
39 / 57 / 57 Variable Torque (kW/A): 630 / 1150; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3134.pdf

P034 / Variable speed drive FDU48-1K15-IP/ 630KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-1K15-IP/ 630KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-1K15-IP/ 630KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-1K15-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 630 as printed in field/value C2
General specification / Rated Output Current(A) 1150 as printed in field/value C2
General specification / Maximum Output Current(A) 1380 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-1K15-IP/ 630KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-1K15-IP/ 630KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 1500x 600 (mm). mm C3

Technical source 056 — Variable speed drive FDU48-1K25-IP/ 710KW/ 380-480V

Source download: Datasheet3135.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-1K25-IP/ 710KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 58 / 58 Variable Torque (kW/A): 710 / 1250; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3135.pdf
39 / 58 / 58 Variable Torque (kW/A): 710 / 1250; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3135.pdf

P034 / Variable speed drive FDU48-1K25-IP/ 710KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-1K25-IP/ 710KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-1K25-IP/ 710KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-1K25-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 710 as printed in field/value C2
General specification / Rated Output Current(A) 1250 as printed in field/value C2
General specification / Maximum Output Current(A) 1500 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-1K25-IP/ 710KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-1K25-IP/ 710KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 1500x 600 (mm). mm C3

Technical source 057 — Variable speed drive FDU48-1K35-IP/ 710KW/ 380-480V

Source download: Datasheet3136.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-1K35-IP/ 710KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 59 / 59 Variable Torque (kW/A): 710 / 1350; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3136.pdf
39 / 59 / 59 Variable Torque (kW/A): 710 / 1350; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3136.pdf

P034 / Variable speed drive FDU48-1K35-IP/ 710KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-1K35-IP/ 710KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-1K35-IP/ 710KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-1K35-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 710 as printed in field/value C2
General specification / Rated Output Current(A) 1350 as printed in field/value C2
General specification / Maximum Output Current(A) 1620 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-1K35-IP/ 710KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-1K35-IP/ 710KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 1800x 600 (mm). mm C3

Technical source 058 — Variable speed drive FDU69-720-IP/ 710KW/ 400-690V

Source download: Datasheet3137.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-720-IP/ 710KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 60 / 60 Variable Torque (kW/A): 710 / 720; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3137.pdf
39 / 60 / 60 Variable Torque (kW/A): 710 / 720; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3137.pdf

P034 / Variable speed drive FDU69-720-IP/ 710KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-720-IP/ 710KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-720-IP/ 710KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-720-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 710 as printed in field/value C2
General specification / Rated Output Current(A) 720 as printed in field/value C2
General specification / Maximum Output Current(A) 864 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-720-IP/ 710KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-720-IP/ 710KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 1200x 600 (mm). mm C3

Technical source 059 — Variable speed drive FDU69-800-IP/ 800KW/ 400-690V

Source download: Datasheet3138.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-800-IP/ 800KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 61 / 61 Variable Torque (kW/A): 800 / 800; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3138.pdf
39 / 61 / 61 Variable Torque (kW/A): 800 / 800; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3138.pdf

P034 / Variable speed drive FDU69-800-IP/ 800KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-800-IP/ 800KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-800-IP/ 800KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-800-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 800 as printed in field/value C2
General specification / Rated Output Current(A) 800 as printed in field/value C2
General specification / Maximum Output Current(A) 960 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-800-IP/ 800KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-800-IP/ 800KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 1200x 600 (mm). mm C3

Technical source 060 — Variable speed drive FDU48-1K5-IP/ 800KW/ 380-480V

Source download: Datasheet3139.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-1K5-IP/ 800KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 62 / 62 Variable Torque (kW/A): 800 / 1500; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3139.pdf
39 / 62 / 62 Variable Torque (kW/A): 800 / 1500; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3139.pdf

P034 / Variable speed drive FDU48-1K5-IP/ 800KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-1K5-IP/ 800KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-1K5-IP/ 800KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-1K5-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 800 as printed in field/value C2
General specification / Rated Output Current(A) 1500 as printed in field/value C2
General specification / Maximum Output Current(A) 1800 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-1K5-IP/ 800KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-1K5-IP/ 800KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 1800x 600 (mm). mm C3

Technical source 061 — Variable speed drive FDU48-1K75-IP/ 900KW/ 380-480V

Source download: Datasheet3140.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-1K75-IP/ 900KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 63 / 63 Variable Torque (kW/A): 900 / 1750; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3140.pdf
39 / 63 / 63 Variable Torque (kW/A): 900 / 1750; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3140.pdf

P034 / Variable speed drive FDU48-1K75-IP/ 900KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-1K75-IP/ 900KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-1K75-IP/ 900KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-1K75-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 900 as printed in field/value C2
General specification / Rated Output Current(A) 1750 as printed in field/value C2
General specification / Maximum Output Current(A) 2100 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-1K75-IP/ 900KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-1K75-IP/ 900KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 2100x 600 (mm). mm C3

Technical source 062 — Variable speed drive FDU69-905-IP/ 900KW/ 400-690V

Source download: Datasheet3141.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-905-IP/ 900KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 64 / 64 Variable Torque (kW/A): 900 / 900; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3141.pdf
39 / 64 / 64 Variable Torque (kW/A): 900 / 900; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3141.pdf

P034 / Variable speed drive FDU69-905-IP/ 900KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-905-IP/ 900KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-905-IP/ 900KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-905-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 900 as printed in field/value C2
General specification / Rated Output Current(A) 900 as printed in field/value C2
General specification / Maximum Output Current(A) 1080 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-905-IP/ 900KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-905-IP/ 900KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 1500x 600 (mm). mm C3

Technical source 063 — Variable speed drive FDU69-995-IP/ 1000KW/ 400-690V

Source download: Datasheet3142.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-995-IP/ 1000KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 65 / 65 Variable Torque (kW/A): 1000 / 1000; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3142.pdf
39 / 65 / 65 Variable Torque (kW/A): 1000 / 1000; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3142.pdf

P034 / Variable speed drive FDU69-995-IP/ 1000KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-995-IP/ 1000KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-995-IP/ 1000KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-995-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 1000 as printed in field/value C2
General specification / Rated Output Current(A) 1000 as printed in field/value C2
General specification / Maximum Output Current(A) 1200 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-995-IP/ 1000KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-995-IP/ 1000KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 1500x 600 (mm). mm C3

Technical source 064 — Variable speed drive FDU48-2K0-IP/ 1120KW/ 380-480V

Source download: Datasheet3143.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-2K0-IP/ 1120KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 66 / 66 Variable Torque (kW/A): 1120 / 2000; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3143.pdf
39 / 66 / 66 Variable Torque (kW/A): 1120 / 2000; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3143.pdf

P034 / Variable speed drive FDU48-2K0-IP/ 1120KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-2K0-IP/ 1120KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-2K0-IP/ 1120KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-2K0-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 1120 as printed in field/value C2
General specification / Rated Output Current(A) 2000 as printed in field/value C2
General specification / Maximum Output Current(A) 2400 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-2K0-IP/ 1120KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-2K0-IP/ 1120KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 2400x 600 (mm). mm C3

Technical source 065 — Variable speed drive FDU69-1K2-IP/ 1200KW/ 400-690V

Source download: Datasheet3144.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-1K2-IP/ 1200KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 67 / 67 Variable Torque (kW/A): 1200 / 1200; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3144.pdf
39 / 67 / 67 Variable Torque (kW/A): 1200 / 1200; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3144.pdf

P034 / Variable speed drive FDU69-1K2-IP/ 1200KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-1K2-IP/ 1200KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-1K2-IP/ 1200KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-1K2-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 1200 as printed in field/value C2
General specification / Rated Output Current(A) 1200 as printed in field/value C2
General specification / Maximum Output Current(A) 1440 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-1K2-IP/ 1200KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-1K2-IP/ 1200KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 1800x 600 (mm). mm C3

Technical source 066 — Variable speed drive FDU48-2K25-IP/ 1250KW/ 380-480V

Source download: Datasheet3145.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-2K25-IP/ 1250KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 68 / 68 Variable Torque (kW/A): 1250 / 2250; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3145.pdf
39 / 68 / 68 Variable Torque (kW/A): 1250 / 2250; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3145.pdf

P034 / Variable speed drive FDU48-2K25-IP/ 1250KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-2K25-IP/ 1250KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-2K25-IP/ 1250KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-2K25-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 1250 as printed in field/value C2
General specification / Rated Output Current(A) 2250 as printed in field/value C2
General specification / Maximum Output Current(A) 2700 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-2K25-IP/ 1250KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-2K25-IP/ 1250KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 2700x 600 (mm). mm C3

Technical source 067 — Variable speed drive FDU48-2K5-IP/ 1400KW/ 380-480V

Source download: Datasheet3146.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU48-2K5-IP/ 1400KW/ 380-480V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 69 / 69 Variable Torque (kW/A): 1400 / 2500; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3146.pdf
39 / 69 / 69 Variable Torque (kW/A): 1400 / 2500; Supply: 380-480V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3146.pdf

P034 / Variable speed drive FDU48-2K5-IP/ 1400KW/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU48-2K5-IP/ 1400KW/ 380-480V as printed in field/value C1

P034 / Variable speed drive FDU48-2K5-IP/ 1400KW/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU48-2K5-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 1400 as printed in field/value C2
General specification / Rated Output Current(A) 2500 as printed in field/value C2
General specification / Maximum Output Current(A) 3000 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 230~ 480V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU48-2K5-IP/ 1400KW/ 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU48-2K5-IP/ 1400KW/ 380-480V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 3000x 600 (mm). mm C3

Technical source 068 — Variable speed drive FDU69-1K4-IP/ 1400KW/ 400-690V

Source download: Datasheet3147.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-1K4-IP/ 1400KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 70 / 70 Variable Torque (kW/A): 1400 / 1400; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3147.pdf
39 / 70 / 70 Variable Torque (kW/A): 1400 / 1400; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3147.pdf

P034 / Variable speed drive FDU69-1K4-IP/ 1400KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-1K4-IP/ 1400KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-1K4-IP/ 1400KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-1K4-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 1400 as printed in field/value C2
General specification / Rated Output Current(A) 1400 as printed in field/value C2
General specification / Maximum Output Current(A) 1680 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-1K4-IP/ 1400KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-1K4-IP/ 1400KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 2100x 600 (mm). mm C3

Technical source 069 — Variable speed drive FDU69-1K6-IP/ 1600KW/ 400-690V

Source download: Datasheet3148.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-1K6-IP/ 1600KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 71 / 71 Variable Torque (kW/A): 1600 / 1600; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3148.pdf
39 / 71 / 71 Variable Torque (kW/A): 1600 / 1600; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3148.pdf

P034 / Variable speed drive FDU69-1K6-IP/ 1600KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-1K6-IP/ 1600KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-1K6-IP/ 1600KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-1K6-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 1600 as printed in field/value C2
General specification / Rated Output Current(A) 1600 as printed in field/value C2
General specification / Maximum Output Current(A) 1920 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-1K6-IP/ 1600KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-1K6-IP/ 1600KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 2400x 600 (mm). mm C3

Technical source 070 — Variable speed drive FDU69-1K8-IP/ 1800KW/ 400-690V

Source download: Datasheet3149.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-1K8-IP/ 1800KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 72 / 72 Variable Torque (kW/A): 1800 / 1800; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3149.pdf
39 / 72 / 72 Variable Torque (kW/A): 1800 / 1800; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3149.pdf

P034 / Variable speed drive FDU69-1K8-IP/ 1800KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-1K8-IP/ 1800KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-1K8-IP/ 1800KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-1K8-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 1800 as printed in field/value C2
General specification / Rated Output Current(A) 1800 as printed in field/value C2
General specification / Maximum Output Current(A) 2160 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-1K8-IP/ 1800KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-1K8-IP/ 1800KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 2700x 600 (mm). mm C3

Technical source 071 — Variable speed drive FDU69-2K0-IP/ 2000KW/ 400-690V

Source download: Datasheet3150.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-2K0-IP/ 2000KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 73 / 73 Variable Torque (kW/A): 2000 / 2000; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3150.pdf
39 / 73 / 73 Variable Torque (kW/A): 2000 / 2000; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3150.pdf

P034 / Variable speed drive FDU69-2K0-IP/ 2000KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-2K0-IP/ 2000KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-2K0-IP/ 2000KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-2K0-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 2000 as printed in field/value C2
General specification / Rated Output Current(A) 2000 as printed in field/value C2
General specification / Maximum Output Current(A) 2400 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-2K0-IP/ 2000KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-2K0-IP/ 2000KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 3000x 600 (mm). mm C3

Technical source 072 — Variable speed drive FDU69-2K2-IP/ 2200KW/ 400-690V

Source download: Datasheet3151.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-2K2-IP/ 2200KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 74 / 74 Variable Torque (kW/A): 2200 / 2200; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3151.pdf
39 / 74 / 74 Variable Torque (kW/A): 2200 / 2200; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3151.pdf

P034 / Variable speed drive FDU69-2K2-IP/ 2200KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-2K2-IP/ 2200KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-2K2-IP/ 2200KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-2K2-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 2200 as printed in field/value C2
General specification / Rated Output Current(A) 2200 as printed in field/value C2
General specification / Maximum Output Current(A) 2640 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-2K2-IP/ 2200KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-2K2-IP/ 2200KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 3300x 600 (mm). mm C3

Technical source 073 — Variable speed drive FDU69-2K4-IP/ 2400KW/ 400-690V

Source download: Datasheet3152.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-2K4-IP/ 2400KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 75 / 75 Variable Torque (kW/A): 2400 / 2400; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3152.pdf
39 / 75 / 75 Variable Torque (kW/A): 2400 / 2400; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3152.pdf

P034 / Variable speed drive FDU69-2K4-IP/ 2400KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-2K4-IP/ 2400KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-2K4-IP/ 2400KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-2K4-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 2400 as printed in field/value C2
General specification / Rated Output Current(A) 2400 as printed in field/value C2
General specification / Maximum Output Current(A) 2880 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-2K4-IP/ 2400KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-2K4-IP/ 2400KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 3600x 600 (mm). mm C3

Technical source 074 — Variable speed drive FDU69-2K6-IP/ 2400KW/ 400-690V

Source download: Datasheet3153.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-2K6-IP/ 2400KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 76 / 76 Variable Torque (kW/A): 2600 / 2600; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3153.pdf
39 / 76 / 76 Variable Torque (kW/A): 2600 / 2600; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3153.pdf

P034 / Variable speed drive FDU69-2K6-IP/ 2400KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-2K6-IP/ 2400KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-2K6-IP/ 2400KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-2K6-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 2600 as printed in field/value C2
General specification / Rated Output Current(A) 2600 as printed in field/value C2
General specification / Maximum Output Current(A) 3120 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-2K6-IP/ 2400KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-2K6-IP/ 2400KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 3900x 600 (mm). mm C3

Technical source 075 — Variable speed drive FDU69-2K8-IP/ 2800KW/ 400-690V

Source download: Datasheet3154.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-2K8-IP/ 2800KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 77 / 77 Variable Torque (kW/A): 2800 / 2800; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3154.pdf
39 / 77 / 77 Variable Torque (kW/A): 2800 / 2800; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3154.pdf

P034 / Variable speed drive FDU69-2K8-IP/ 2800KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-2K8-IP/ 2800KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-2K8-IP/ 2800KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-2K8-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 2800 as printed in field/value C2
General specification / Rated Output Current(A) 2800 as printed in field/value C2
General specification / Maximum Output Current(A) 3360 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-2K8-IP/ 2800KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-2K8-IP/ 2800KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 4200x 600 (mm). mm C3

Technical source 076 — Variable speed drive FDU69-3K0-IP/ 3000KW/ 400-690V

Source download: Datasheet3155.pdf.

Source differences and limitations

Conditions for this section:

Printed section / Main features — P034, Variable speed drive FDU69-3K0-IP/ 3000KW/ 400-690V, page 1

Conditions for this section:

• NEW - Control panel with Real time clock. Optional Bluetooth communication.
• Available as robust and certified IP54 metal construction or IP20/21 version.
• All drive sizes are delivered with built-in Category C3 EMC-filter as standard. C3 requirements
are fulfilled with 80 m motor cable (IP2Y= 25m).
• Soft starts minimize start currents and linear stops prevent water hammer.
• One Emotron FDU can control up to seven pumps/fans without external control systems.
• Energy saving function pauses the motor when it is not required to run to maintain pressure.
• Efficiency is increased by setting the pump to run at full speed at certain intervals to rinse out
sludge.
• Temp/Speed controlled fans assures less noise, a more even drive temperature and higher
efficiency.
• Load monitor function included as standard.
• Detachable multi-language control panel included as standard. Following languages are
supported in the control panel:
English, Swedish, Dutch, German, French, Spanish, Russian, Italian, Czech, Turkish and Polish.
• Operation parameters can be set in your process units, for example m3/min. and bar.
• Removable control panel with own memory means it is easy to transfer or copy settings.
• UL (UL 840) approved version available (not IP2Y).
• Marine (DNV-GL & BV) approved version available (not IP2Y, IP2x).
• Liquid cooled version available for sizes above 90 A

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
14 / 78 / 78 Variable Torque (kW/A): 3000 / 3000; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3155.pdf
39 / 78 / 78 Variable Torque (kW/A): 3000 / 3000; Supply: 400-690V 3PH; IP Rating: 54 Drawing/Datasheet PDF / Datasheet3155.pdf

P034 / Variable speed drive FDU69-3K0-IP/ 3000KW/ 400-690V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Source heading Variable speed drive FDU69-3K0-IP/ 3000KW/ 400-690V as printed in field/value C1

P034 / Variable speed drive FDU69-3K0-IP/ 3000KW/ 400-690V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
General specification / Component name FDU69-3K0-IP as printed in field/value C1
General specification / Suitable Motor Capacity Capacity(KW) 3000 as printed in field/value C2
General specification / Rated Output Current(A) 3000 as printed in field/value C2
General specification / Maximum Output Current(A) 3600 as printed in field/value C2
General specification / Input Voltage Range(V) Three-phase 400~ 690V, 50/60Hz as printed in field/value C2
General specification / Allowable Voltage Fluctuation -15%~ +10% as printed in field/value C2
General specification / Output Voltage range(V) Three-phase 0~480V as printed in field/value C2
General specification / Mains Frequency (Hz) 45 to 65 as printed in field/value C2
General specification / Output Switching Frequency (kHz) 3 as printed in field/value C2
General specification / Input Power Factor (%) 0.95 as printed in field/value C3
Environmental conditions / Nominal ambient temperature 0°C - 40°C (32°F- 104°F) as printed in field/value C2
Environmental conditions / Atmospheric pressure 86–106 kPa ( 12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Relative humidity according to IEC 60721-3-3 Class 3K4, 5...95% and no condensing as printed in field/value C2
Environmental conditions / Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materi­als. Chemical gases, class 3C2 (coated boards 3C3). Solid particles, class 3S2. as printed in field/value C2
Environmental conditions / Component name VFX48-2K5-54 as printed in field/value C1
Environmental conditions / Vibrations According to IEC 60068-2-6, Sinusoidal vibrations: 10<f<57 Hz, 0.075 mm (0.00295 ft) 57<f<150 Hz, 1g (0,035 oz) as printed in field/value C4
Environmental conditions / Altitude 0–1000 m (0 - 3280 ft) with derating 1%/100 m (328 ft) of rated current as printed in field/value C2
Environmental conditions / Storage temperature -20 to +60 °C (-4 to + 140 °F) as printed in field/value C2
Environmental conditions / Storage atmospheric pressure 86–106 kPa (12.5 - 15.4 PSI) as printed in field/value C2
Environmental conditions / Storage relative humidity according to IEC60721-3-1 Class 1K4, max. 95% and no condensing and no formation of ice. as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Analogue voltage/current 0-±10 V/0-20 mA via switch as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Max. input voltage +30 V as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Input impedance 20 kΩ (voltage), 250 Ω (current) as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Resolution 11 bits + sign as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Hardware accuracy 0.5% type + 1 ½ LSB fsd as printed in field/value C2
Control signal inputs: Analogue (differential), 4 channels / Non-linearity 1½ LSB as printed in field/value C2
Digital inputs: 8 channels / Input voltage High >9 VDC, Low<4 VDC as printed in field/value C2
Digital inputs: 8 channels / Max. input voltage +30 VDC as printed in field/value C2
Digital inputs: 8 channels / Input impedance <3.3 VDC: 4.7 kΩ , ≥3.3 VDC: 3.6 kΩ as printed in field/value C2

P034 / Variable speed drive FDU69-3K0-IP/ 3000KW/ 400-690V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Digital inputs: 8 channels / Signal delay ≤8 ms as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output voltage/current 0-10 V/0-20 mA via software setting as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Max. output voltage +15 V @5 mA cont. as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Short-circuit current (∞) +15 mA (voltage) +140 mA (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Output impedance 10 Ω (voltage) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Resolution 10 bit as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Maximum load impedance for current 500 Ω as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Hardware accuracy 1.9% type fsd (voltage), 2.4% type fsd (current) as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Offset 3 LSB as printed in field/value C1
Control signal outputs: Analogue, 2 channels / Non-linearity 2 LSB as printed in field/value C1
Digital outputs: 2 channels / Output voltage High>20 VDC @50 mA, >23 VDC open Low<1 VDC @50 mA as printed in field/value C1
Digital outputs: 2 channels / Short-circuit current (∞) 100 mA max (together with +24 VDC) as printed in field/value C1
Relays, 3pcs / Contacts 0.1 – 2 A/Umax 250 VAC or 42 VDC as printed in field/value C1
Reference voltages / +10 VDC +10 VDC @10 mA short-circuit current +30 mA max as printed in field/value C1
Reference voltages / -10 VDC -10 VDC @10 mA as printed in field/value C1
Reference voltages / +24 VDC +24 VDC short-circuit current +100 mA max (together with Digital Outputs) as printed in field/value C1

P034 / Variable speed drive FDU69-3K0-IP/ 3000KW/ 400-690V — source page 6 — PDF page 6

Specification Value Unit / basis Conditions
Terminal X1 / 1 / Name +10V as printed in field/value C1
Terminal X1 / 1 / Default function +10 VDC Supply voltage as printed in field/value C1
Terminal X1 / 2 / Name AnIn 1 as printed in field/value C1
Terminal X1 / 2 / Default function Speed reference as printed in field/value C1
Terminal X1 / 3 / Name AnIn 2 as printed in field/value C1
Terminal X1 / 3 / Default function Not Used as printed in field/value C1
Terminal X1 / 4 / Name AnIn 3 as printed in field/value C1
Terminal X1 / 4 / Default function Not Used as printed in field/value C1
Terminal X1 / 5 / Name AnIn 4 as printed in field/value C1
Terminal X1 / 5 / Default function Not Used as printed in field/value C1
Terminal X1 / 6 / Name -10V as printed in field/value C1
Terminal X1 / 6 / Default function -10VDC Supply voltage as printed in field/value C1
Terminal X1 / 7 / Name Common as printed in field/value C1
Terminal X1 / 7 / Default function Signal ground as printed in field/value C1
Terminal X1 / 8 / Name DigIn 1 as printed in field/value C1
Terminal X1 / 8 / Default function RunL as printed in field/value C1
Terminal X1 / 9 / Name DigIn 2 as printed in field/value C1
Terminal X1 / 9 / Default function RunR as printed in field/value C1
Terminal X1 / 10 / Name DigIn 3 as printed in field/value C1
Terminal X1 / 10 / Default function Not Used as printed in field/value C1
Terminal X1 / 11 / Name +24VDC as printed in field/value C1
Terminal X1 / 11 / Default function +24VDC Supply voltage as printed in field/value C1
Terminal X1 / 12 / Name Common as printed in field/value C1
Terminal X1 / 12 / Default function Signal ground as printed in field/value C1
Terminal X1 / 13 / Name AnOut 1 as printed in field/value C1
Terminal X1 / 13 / Default function Min speed to max speed as printed in field/value C1
Terminal X1 / 14 / Name AnOut 2 as printed in field/value C1
Terminal X1 / 14 / Default function 0 to max torque as printed in field/value C1
Terminal X1 / 15 / Name Common as printed in field/value C1
Terminal X1 / 15 / Default function Signal ground as printed in field/value C1
Terminal X1 / 16 / Name DigIn 4 as printed in field/value C1
Terminal X1 / 16 / Default function Not Used as printed in field/value C1
Terminal X1 / 17 / Name DigIn 5 as printed in field/value C1
Terminal X1 / 17 / Default function Not Used as printed in field/value C1
Terminal X1 / 18 / Name DigIn 6 as printed in field/value C1
Terminal X1 / 18 / Default function Not Used as printed in field/value C1
Terminal X1 / 19 / Name DigIn 7 as printed in field/value C1
Terminal X1 / 19 / Default function Not Used as printed in field/value C1
Terminal X1 / 20 / Name DigOut 1 as printed in field/value C1
Terminal X1 / 20 / Default function Ready as printed in field/value C1
Terminal X1 / 21 / Name DigOut 2 as printed in field/value C1
Terminal X1 / 21 / Default function Brake/No trip as printed in field/value C1
Terminal X1 / 22 / Name DigIn 8 as printed in field/value C1
Terminal X1 / 22 / Default function Reset as printed in field/value C1
Terminal X2 / 31 / Name N/C 1 as printed in field/value C1
Terminal X2 / 31,32,33 / Shared relay function Relay 1 Output= Trip. Active when the AC drive is in a Trip condition. The N/C is opened when the relay is active (valid for all relays). The N/O is closed when the relay is active (valid for all relays). as printed in field/value C2
Terminal X2 / 32 / Name COM 1 as printed in field/value C1
Terminal X2 / 33 / Name N/O 1 as printed in field/value C1
Terminal X2 / 41 / Name N/C 2 as printed in field/value C1
Terminal X2 / 41,42,43 / Shared relay function Relay 2 Output= Ready. Active when the AC drive is ready to start. as printed in field/value C2
Terminal X2 / 42 / Name COM 2 as printed in field/value C1
Terminal X2 / 43 / Name N/O 2 as printed in field/value C1
Terminal X3 / 51 / Name COM 3 as printed in field/value C1
Terminal X3 / 51,52 / Shared relay function Relay 3 Output= Not used. as printed in field/value C2
Terminal X3 / 52 / Name N/O 3 as printed in field/value C1
Drive dimensions H x W x D (Hx Wx D): preliminary 2250x 4500x 600 (mm). mm C3

Selection checks and source differences

Each website row is keyed by table ID plus row ID. Repeated row numbers in separate tables are distinct associations, not a single78-row inventory.

Individual sheet component names repeat VFX48-2K5-54 despite distinct title models; power-factor percent/0.95 and g/oz vibration units are literal conflicts. High-voltage input/output scope is not reconciled by inference.

F33 and V33 maximum-current, parameter-current and family-specific option data differ. The shared sine-wave filter is F33-only. Safe Stop and braking equipment remain conditional options.

The manual derating example states68A motor current but selects32.4A capability. It is retained as a source contradiction, not a recommended selection.

Catalogue/manually printed model spelling, code gaps, voltage-specific rows and graphical comparator ambiguity are preserved. Historical compliance/approval statements are not independently verified current certificates.

Table39 row56 is #ERROR! with no source PDF; table14 row56 is separate and has a source.155 memberships across156 website rows retained. Do not report all156 rows as acquired downloads.

Product documents

Our company certificates and conditions of sale remain separate from the selected product’s ratings and approvals.

Talk to our team about your application, supply, motor rating and configuration.