TECO F510 Enhanced — Advanced Pump and Fan Control

Shared-cell notation: r2c3 means row 2, column 3 of the stated source table. Read the referenced parent cell; an unpopulated child is not zero.

Our F510 Enhanced drive helps control pumps, fans and building services around changing demand. With PID, multi-pump functions and building-automation communications, we can help configure a system for pressure control, HVAC, water management and other pump and fan duties.

Select the rating and enclosure

Our local page describes 3.7–600 kW with 400 V IP55 and IP00 configurations. The two-page Enhanced brochure gives a wider 0.75–600 kW headline and describes IP55/NEMA 4 through 45 kW and IP20/NEMA 1 through 600 kW. The manual instead pairs IP55 with NEMA 12. These source descriptions are not interchangeable enclosure approvals: confirm the exact supplied drive, nameplate and installation requirements.

The collected selection table has 20 rows and 20 linked PDF memberships. A separate 24-page Enhanced catalogue is a product-level attachment, not a twenty-first website model. All are retained with the 556-page manual and quick guide. We do not substitute the wider family schedules for an individual model's current rating.

F510 is described as normal duty, 120% overload for one minute. Size by motor current and duty, not kW alone. The manual distinguishes V/F, SLV and PMSLV modes and their output-frequency limits. Its headline 599 Hz is not available in every mode/capacity combination. Carrier-frequency derating and the motor's permissible speed remain part of selection.

Pump control that follows demand

Built-in PID and simple PLC support constant-pressure control. Multi-pump functions distribute operation across master and slave pumps; sleep mode can stop pumping at low demand, while blockage and dry-pump detection provide configured monitoring. These functions need the appropriate sensors, settings and system commissioning; they do not guarantee protection for every hydraulic installation.

Up to eight pumps requires the specified1-to-8 pump option card, identified in the Enhanced booklet as JN5-IO-8DO. Built-in multi-pump control and optional cascade-card operation are distinct arrangements. The detailed reference sections retain staging, alternation, pressure, timing, feedback, alarm and restart conditions.

Automatic Energy Saving adjusts voltage/current according to load. The booklet's25% illustration is a test at 20% load using a30 HP drive and equally rated motor; it is not a guaranteed site saving. Soft PWM is intended to reduce audible motor noise and interference. No unprinted energy, noise or efficiency value has been calculated.

Building controls and operator choices

The sources list Modbus, BACnet MS/TP and Metasys N2 for building automation through the specified RS-485 interface. Confirm the selected protocol, firmware and system integration. Additional communication cards have their own compatibility requirements; an RJ45 connector does not make the interface Ethernet.

Our short brochure describes an LCD keypad as standard, while the broader manual covers LED, LCD and optional HOA LCD operators. Hand/Auto/Off operation requires the suitable operator. RTC is described for the LCD keypad. Parameter copying, local/remote control, engineering-unit displays, fault history, operating-hour records and PTC motor input support commissioning and maintenance.

The catalogue's I/O card text conflicts: JN5-IO-2DO1AI is described with an analogue output on page 12 and an analogue input on page 21. Both CN2 and CN3 are labelled “Expansion Slot1”. Use the connector identity and confirmed accessory documentation; we do not resolve these differences by guessing from the part code.

Mounting, environment and filtering

IP00 units need an appropriate protective installation. The manual specifies indoor conditions protected from rain, moisture, direct sunlight, oil mist and corrosive gases. The page's outdoor-application wording does not override those restrictions. IP55 alone does not approve every outdoor or chemical environment.

The manual gives −10 to+40°C for IP20/IP21/IP55 and −10 to+50°C for the stated IP00/cover-removed arrangement, with a separate Enhanced frame 5 qualification. Higher temperatures up to 60°C and altitude above 1, 000 m require the stated current derating; the altitude limit is 3, 000 m. Use the full conditions rather than combining independent maxima.

Our local brochure describes built-in filtering through 45 kW. The manual distinguishes400 V IP20 through 75 HP and IP55 through 60 HP. These are edition/model statements; confirm the actual filter configuration and EMC installation. The dimension schedules separately retain filtered/unfiltered frames, installation kits, depth and weight. In the Enhanced catalogue, F510-4025-□3 is frame 3 while the F-suffix version is frame 4; frame 2 depths also differ. No outline is substituted on the basis of equal power alone.

Emergency operation, installation and service

The Enhanced booklet describes STO, but its system integration and supplied hardware require the applicable documentation. It is not electrical isolation or a general machine safety approval.

Fire override suppresses software protections and can continue until hardware protection operates or the drive is damaged. It overrides ordinary run/frequency commands and has firmware-specific conditions. Use it only within an engineered emergency system; it is not the normal operating mode. The source's reset and feedback-loss settings must be read with the entire procedure.

Qualified personnel should follow the complete manual for mounting clearances, earthing, supply/motor wiring, fuses, reactors, braking, commissioning, isolation and discharge verification. Parameter examples are not instructions for your particular motor. Maintenance and fault tables retain their context; no wiring topology or curve values have been inferred from figures.

Source differences to check before ordering

The quick guide is titled F510 Enhanced but its introduction says E510s. Its forward/stop–reverse/stop heading also differs from the RUN/STOP–REV/FWD diagram labels. These errors do not establish cross-product applicability. The Enhanced booklet gives0.1 Hz and 0.01 Hz lower frequency limits in different tables; the manual carrier footnote prints “2–8 Hz”, although surrounding carrier references use kHz. The original wording remains visible below pending confirmation.

The source tables and dimension data are retained with their edition and model labels. Blanks and unreadable fields remain unknown, not zero. The source software archive remains linked without having been executed. Share the motor current, supply, pump/fan duty, sensor arrangement, enclosure and control-system requirements so we can confirm the configuration with you.

Catalogue — TECO-F510.pdf PDF1 — page 1

TECO-F510.pdf · P002 · source page 1

TECO Variable Speed Drives Solutions

OPTIMISED CONTROL & EFFICIENCY

TECO manufactures and stocks a comprehensive range of LV Variable Speed Drives, designed to enhance motor control, improve energy efficiency, and optimise performance across various applications. Engineered with advanced technology, our drives deliver precision, reliability, and cost savings for your operations.

To find out more click the QR code.

electricmotors.teco.com.au

Catalogue — TECO-F510.pdf PDF2 — page 2

TECO-F510.pdf · P002 · source page 2

F510 Enhanced

Enhanced Fan and Pump Drive - 0.75kW to 600kW

IP55/NEMA 4 up to 45kW IP20/NEMA 1 up to 600kW FEATURES

BENEFITS

electricmotors.teco.com.au

Manual — TECO F510 Series Instruction Manual — page 1

Manual reference: physical PDF page 1. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

INSTRUCTION MANUAL

TECO INVERTER

F510 Series

Cover illustration does not establish operating settings or equipment ratings.

Manual — Table of contents I — page 2

I

Table of Contents

Preface ............................................................................................................................. 0-1

Chapter 1 Safety Precautions ........................................................................................ 1-1

1.1 Before Supplying Power to the Inverter ................................................................... 1-1

1.2 Wiring ...................................................................................................................... 1-1

1.3 Before Operation ..................................................................................................... 1-2

1.4 Parameters Setting .................................................................................................. 1-2

1.5 Operation ................................................................................................................. 1-2

1.6 Maintenance, Inspection and Replacement ............................................................. 1-3

1.7 Disposal of the Inverter ............................................................................................ 1-3

1.8 Guaranteed liability exemption ................................................................................ 1-3

Chapter 2 Model Description ......................................................................................... 2-1

2.1 Nameplate Data ...................................................................................................... 2-1

2.2 Model Identification ................................................................................................. 2-1

Chapter 3 Environment and Installation ....................................................................... 3-1

3.1 Environment ........................................................................................................... 3-1

3.2 Installation .............................................................................................................. 3-2

3.2.1 Installation Spaces ......................................................................................... 3-2

3.2.2 External View ................................................................................................. 3-3

3.2.2.1 External View (IP00/ IP20) ................................................................... 3-3

3.2.2.2 External View (IP55) ............................................................................ 3-6

3.2.3 Warning Labels ............................................................................................... 3-7

3.2.4 Removing the Front Cover and Keypad .......................................................... 3-8

3.2.4.1 Standard Type (IP00/IP20) ............................................................... 3-9

3.2.4.2 Built-in Filter Type (IP20/IP00) ........................................................... 3-16

3.2.4.3 Water proof Type (IP55) .................................................................... 3-18

3.3 Inverter Wiring ...................................................................................................... 3-20

3.3.1 Wire Gauges and Tightening Torque ............................................................. 3-20

3.3.2 Wiring Peripheral Power Devices .................................................................. 3-22

3.3.3 General Wiring Diagram ................................................................................ 3-24

3.3.3.1 General Wiring Diagram (For Standard H & C type) ......................... 3-24

3.3.3.2 General Wiring Diagram (For Enhanced E & G type) ........................ 3-25

3.3.4 Single/ Multi- Pump Dedicated Wiring Diagram ............................................. 3-26

3.3.4.1 For Standard H & C type.................................................................... 3-26

3.3.4.2 For Enhanced E & G type .................................................................. 3-29

3.3.5 Wiring for Control Circuit Terminals ............................................................... 3-32

3.3.5.1 Wiring for Control Circuit Terminals (For Standard H & C type) ........ 3-32

3.3.5.2 Wiring for Control Circuit Terminals (For Enhanced E & G type) ...... 3-35

3.3.6 Wiring for Main Circuit Terminals .................................................................. 3-38

3.3.6.1 Wiring for Main Circuit Terminals (For Standard H & C type) ............ 3-38

3.3.6.2 Wiring for Main Circuit Terminals (For Enhanced E & G type) .......... 3-43

3.3.7 Wiring Precautions ........................................................................................ 3-53

3.3.8 Input Power and Cable Length ...................................................................... 3-55

3.4 Inverter Specifications .......................................................................................... 3-56

3.5 Inverter De-rating Based on Carrier Frequency ................................................... 3-60

3.6 Inverter De-rating Based on Temperature ............................................................ 3-64

3.7 Inverter Dimensions .............................................................................................. 3-65

3.7.1 Standard Type (IP00/IP20) ........................................................................... 3-65

3.7.2 Standard Type with Built-in Filter (IP00/IP20) ............................................... 3-74

Manual — Table of contents II — page 3

II

3.7.3 Water proof Type (IP55) .............................................................................. 3-76

Chapter 4 Keypad and Programming Functions .......................................................... 4-1

4.1 LED Keypad ............................................................................................................ 4-1

4.1.1 Keypad Display and Keys ............................................................................... 4-1

4.1.2 Seven Segment Display Description ............................................................... 4-3

4.1.3 LED Indicator Description ............................................................................... 4-5

4.1.4 Power-up Monitor ........................................................................................... 4-7

4.1.5 Modifying Parameters/ Set Frequency Reference .......................................... 4-8

4.1.6 Operation Control ......................................................................................... 4-10

4.2 LCD keypad ........................................................................................................... 4-11

4.2.1 Keypad Display and Keys ............................................................................. 4-11

4.2.2 Keypad Menu Structure ............................................................................... 4-13

4.3 Parameters ............ ……………………………………………………………………..4-17

4.4 Description of Parameters .................................................................................... 4-70

4.5 Built-in PLC Function .......................................................................................... 4-308

4.5.1 Basic Command .......................................................................................... 4-308

4.5.2 Basic Command Function ............................................................................ 4-309

4.5.3 Application Functions ................................................................................... 4-310

4.6 Modbus Protocol Descriptions ........................................................................... 4-318

4.6.1 Communication Connection and Data Frame .............................................. 4-318

4.6.2 Register and Data Format ........................................................................... 4-322

4.7 BacNET Protocol Descriptions .......................................................................... 4-342

4.7.1 BACnet Services.......................................................................................... 4-342

4.7.2 BACnet Protocol Structure ........................................................................... 4-343

4.7.3 BACnet Specifications ................................................................................. 4-344

4.7.4 BACnet Object Properties ............................................................................ 4-345

4.8 MetaSys N2 Communication Protocol ............................................................... 4-348

4.8.1 Introduction and Setting ............................................................................... 4-348

4.8.2 MetaSys N2 Specification ............................................................................ 4-348

4.8.3 Definition of MetaSys N2 Communication Protocol ..................................... 4-349

4.8.4 MetaSys N2 Communication Protocol in F510 Model .................................. 4-350

Chapter 5 Check Motor Rotation and Direction ........................................................... 5-1

Chapter 6 Speed Reference Command Configuration ................................................ 6-1

6.1 Reference from Keypad .......................................................................................... 6-1

6.2 Reference from External Analog Signal (0-10V / 4-20mA) .................................... 6-2

6.3 Reference from Serial Communication RS485 (00-05=3) ....................................... 6-4

6.4 Reference from two Analog Inputs ......................................................................... 6-6

6.5 Change Frequency Unit from Hz to rpm ................................................................. 6-6

Chapter 7 Operation Method Configuration (Run / Stop) ........................................... 7-1

7.1 Run/Stop from the Keypad (00-02=0) – Default Setting ......................................... 7-1

7.2 Run/Stop from External Switch / Contact or Pushbutton (00-02=1) ........................ 7-2

7.3 Run/Stop from Serial Communication RS485 (00-02=3) ......................................... 7-3

Chapter 8 Motor and Application Specific Settings ..................................................... 8-1

8.1 Set Motor Nameplate Data (02-01, 02-05) ............................................................... 8-1

8.2 Acceleration and Deceleration Time (00-14, 00-15) ............................................... 8-2

Manual — Table of contents III — page 4

III

8.3 Torque Compensation Gain (01-10) ........................................................................ 8-3

8.4 Automatic Energy Savings Function (11-19) ........................................................... 8-4

8.5 Emergency Stop ...................................................................................................... 8-6

8.6 Direct / Unattended Startup .................................................................................... 8-7

8.7 Analog Output Setup ............................................................................................... 8-8

Chapter 9 Using PID Control for Constant Flow / Pressure Applications .................. 9-1

9.1 What is PID Control? ............................................................................................... 9-1

9.2 Connect Transducer Feedback Signal (10-01) ....................................................... 9-3

9.3 Engineering Units ................................................................................................... 9-4

9.4 Sleep / Wakeup Function ........................................................................................ 9-5

Chapter 10 Troubleshooting and Fault Diagnostics .................................................. 10-1

10.1 General .............................................................................................................. 10-1

10.2 Fault Detection Function .................................................................................... 10-1

10.3 Warning / Self-diagnosis Detection Function ..................................................... 10-7

10.4 Auto-tuning Error ............................................................................................. 10-15

10.5 PM Motor Auto-tuning Error .............................................................................. 10-16

10.6 General troubleshooting ................................................................................... 10-17

10.7 Troubleshooting of the Inverter ......................................................................... 10-18

10.7.1 Quick troubleshooting of the Inverter ........................................................ 10-18

10.7.2 Troubleshooting for OC, OL error displays ............................................... 10-20

10.7.3 Troubleshooting for OV, LV error .............................................................. 10-21

10.7.4 The motor can not run .............................................................................. 10-22

10.7.5 Motor Overheating .................................................................................... 10-23

10.7.6 Motor runs unbalanced ............................................................................. 10-24

10.8 Routine and periodic inspection ........................................................................ 10-25

10.9 Maintenance ..................................................................................................... 10-26

Chapter 11 Inverter Peripheral devices and Options ................................................. 11-1

11.1 Braking Resistors and Braking Units ................................................................. 11-1

11.2 AC Line Reactors................................................................................................ 11-5

11.3 Input Noise Filters .............................................................................................. 11-7

11.4 Input Current and Fuse Specifications ............................................................... 11-9

11.5 Other options ................................................................................................... 11-11

11.6 Communication options ................................................................................... 11-16

11.7 Others Options ................................................................................................. 11-17

11.8 NEMA1 Kit ........................................................................................................ 11-18

11.9 PROFIBUS high speed communication expansion card ................................... 11-19

11.9.1 Communication hardware and data structure ........................................... 11-19

11.9.2 Product specifications ............................................................................... 11-19

11.9.3 Installation instructions ............................................................................. 11-20

11.9.4 LED indicator descriptions ........................................................................ 11-21

11.9.5 Driver parameter setting descriptions ....................................................... 11-22

11.9.6 Connection instructions ............................................................................ 11-23

11.9.7 Meanings of each character ..................................................................... 11-24

11.9.8 PKW regional access parameters ............................................................. 11-25

11.9.9 Troubleshooting ........................................................................................ 11-27

11.9.10 GSD File ................................................................................................. 11-27

11.10 CANopen high speed communication expansion card ................................... 11-28

11.10.1 Communication hardware and data structure ......................................... 11-28

11.10.2 Product specifications ............................................................................. 11-28

Manual — Table of contents IV — page 5

IV

11.10.3 Installation instructions ........................................................................... 11-28

11.10.4 LED indicator descriptions ...................................................................... 11-30

11.10.5 Driver parameter setting descriptions ..................................................... 11-31

11.10.6 Connection instructions .......................................................................... 11-32

11.10.7 Object index list ...................................................................................... 11-34

11.10.8 Troubleshooting ...................................................................................... 11-40

11.10.9 EDS file ................................................................................................... 11-41

11.11 Introduction to the EtherCAT high speed communication expansion module . 11-42

11.11.1 Communication hardware and data structure ......................................... 11-42

11.11.2 Product specifications ............................................................................. 11-42

11.11.3 Installation instructions ........................................................................... 11-43

11.11.4 LED indicator descriptions ...................................................................... 11-44

11.11.5 Object index list ...................................................................................... 11-45

11.11.6 Troubleshooting ...................................................................................... 11-47

11.11.7 xml file .................................................................................................... 11-47

11.12 I/O expansion card .......................................................................................... 11-48

11.12.1 Hardware and data structure .................................................................. 11-48

11.12.2 Product specifications ............................................................................. 11-48

11.12.3 Installation instructions ........................................................................... 11-48

11.12.4 Driver parameter setting descriptions ..................................................... 11-49

11.13 DC reactor ...................................................................................................... 11-50

11.14 Sinusoidal output reactor ................................................................................ 11-52

11.15 DC24V power expansion card ........................................................................ 11-54

11.15.1 JN5-PS-DC24V Product specifications ................................................... 11-54

Appendix-A Instructions for UL .................................................................................... A-1

Manual — Preface and warning-symbol definitions — page 6

Preface

The F510 product is an inverter designed to control a three-phase induction motor. Please

read this manual carefully to ensure correct operation, safety and to become familiar with

the inverter functions.

The F510 inverter is an electrical / electronic product and must be installed and handled by

qualified service personnel.

Improper handling may result in incorrect operation, shorter life cycle, or failure of this

product as well as the motor.

All F510 documentation is subject to change without notice. Be sure to obtain the latest

editions for use or visit our website at http://industrialproducts.teco.com.tw/.

Available Documentation:

  1. F510 Start-up and Installation Manual

  2. F510 Instruction Manual

Read this instruction manual thoroughly before proceeding with installation, connections

(wiring), operation, or maintenance and inspection.

Ensure you have sound knowledge of the inverter and familiarize yourself with all safety

information and precautions before proceeding to operate the inverter.

Please pay close attention to the safety precautions indicated by the warning

and

caution

symbol.

Preface and warning-symbol definitions. Editorial column labels; all source rows retained including section headings. Do not silently correct supplier wording.

Preface and warning-symbol definitions. Editorial column labels; all source rows retained including section headings. Do not silently correct supplier wording. Row group: Warning-symbol definitions

Preface and warning-symbol definitions — PDF page 6

Source row Label (editorial) Source wording (editorial)
1 Warning Failure to ignore the information indicated by the warning symbol may result in death or serious injury.
2 Caution Failure to ignore the information indicated by the caution symbol may result in minor or moderate injury and/or substantial property damage.

Manual — Safety: before supplying power and wiring; continues on next page — page 7

Chapter 1 Safety Precautions

Users are advised to carefully read the safety precautions required in this chapter before

installing, testing and repairing the system. Any personnel injury and equipment loss

caused by illegal operation are irrelevant to the company and bear any responsibility.

1.1 Before Supplying Power to the Inverter

Warning

The main circuit must be correctly wired. For single phase supply use input terminals (R/L1,

T/L3) and for three phase supply use input terminals (R/L1, S/L2, T/L3). Terminals U/T1,

V/T2, W/T3 must only be used to connect the motor. Connecting the input supply to any of

the U/T1, V/T2 or W/T3 terminals will cause damage to the inverter.

Caution

To avoid the front cover from disengaging or other physical damage, do not carry the

inverter by its cover. Support the unit by its heat sink when transporting. Improper handling

can damage the inverter or injure personnel, and should be avoided.

To avoid the risk of fire, do not install the inverter on or near flammable objects. Install on

nonflammable objects such as metal surfaces.

If several inverters are placed inside the same control panel, provide adequate ventilation

to maintain the temperature below 40°C/104°F (50°C/122°F without a dust cover) to avoid

overheating or fire.

When removing or installing the digital operator, turn off the power first, and then follow the

instructions in this manual to avoid operator error or loss of display caused by faulty

connections.

This product is sold subject to IEC 61800-3. In a domestic environment this product may

cause radio interference in which case the user may need to apply corrective measures.

Over temperature protection function on motor is provided, please follow the description of

control circuit terminals, and refer to the parameter group 08.

1.2 Wiring

Always turn OFF the power supply before attempting inverter installation and wiring of the

user terminals.

Wiring must be performed by a qualified personnel / certified electrician.

Make sure the inverter is properly grounded. (200V Class: Grounding impedance shall be

less than 100Ω. 400V Class: Grounding impedance shall be less than 10Ω.) It is required

to disconnect the ground wire in the control board to avoid the sudden surge causing

damage on electronic parts if it is improperly grounded.

Please check and test emergency stop circuits after wiring. (Installer is responsible for the

correct wiring.)

Never touch any of the input or output power lines directly or allow any input or output

power lines to come in contact with the inverter case.

Do not perform a dielectric voltage withstand test (megger) on the inverter or this will result

in inverter damage to the semiconductor components.

The line voltage applied must comply with the inverter’s specified input voltage.

Connect braking resistor and braking unit to the designated terminals.

Do not connect a braking resistor directly to the DC terminals P(+) and N(-),otherwise fire

Manual — Safety: wiring continuation, before operation, parameter setting and operation — page 8

may result.

Use wire gauge recommendations and torque specifications.

Never connect input power to the inverter output terminals U/T1, V/T2, W/T3.

Do not connect a contactor or switch in series with the inverter and the motor.

Do not connect a power factor correction capacitor or surge suppressor to the inverter

output.

Ensure the interference generated by the inverter and motor does not affect peripheral

devices.

1.3 Before Operation

Warning

Make sure the inverter capacity matches the parameters 13-00 before supplying power.

Reduce the carrier frequency (parameter 11-01) If the cable from the inverter to the motor

is over 80 ft (25m). A high-frequency current can be generated by stray capacitance

between the cables and result in an overcurrent trip of the inverter, an increase in leakage

current, or an inaccurate current readout.

Be sure to install all covers before turning on power. Do not remove any of the covers while

power to the inverter is on, otherwise electric shock may occur.

Do not operate switches with wet hands, otherwise electric shock may result.

Do not touch inverter terminals when energized even if inverter has stopped, otherwise

electric shock may result.

1.4 Parameter Setting

Caution

Do not connect a load to the motor while performing an auto-tune.

Make sure the motor can freely run and there is sufficient space around the motor when

performing a rotational auto-tune.

1.5 Operation

Do not connect or disconnect the motor during operation. This will cause the inverter to trip

and may cause damage to the inverter.

Operations may start suddenly if an alarm or fault is reset with a run command active.

Confirm that no run command is active upon resetting the alarm or fault, otherwise

accidents may occur.

An external emergency stop switch is enabled when parameter 08-30 is set for the run

permissive function.

It provides an independent external hardware emergency switch, which emergently shuts

down the inverter output in the case of danger.

If automatic restart after power recovery (parameter 07-00) is enabled, the inverter will start

automatically after power is restored.

Make sure it is safe to operate the inverter and motor before performing a rotational

auto-tune.

Do not check signals on circuit boards while the inverter is running.

After the power is turned off, the cooling fan may continue to run for some time.

Do not touch heat-generating components such as heat sinks and braking resistors.

Manual — Safety: operation continuation, maintenance, disposal and liability wording — page 9

Carefully check the performance of motor or machine before operating at high speed,

otherwise Injury may result.

Note the parameter settings related to the braking unit when applicable.

Do not use the inverter braking function for mechanical holding, otherwise injury may result.

Do not check signals on circuit boards while the inverter is running.

1.6 Maintenance, Inspection and Replacement

Warning

Wait a minimum of 5 minutes after power has been turned OFF before starting an

inspection. Also confirm that the charge light is OFF and that the DC bus voltage has

dropped below 25Vdc. Wait a minimum of 15 minutes while inverter is over 20HP.

Never touch high voltage terminals in the inverter.

Make sure power to the inverter is disconnected before disassembling the inverter.

Only authorized personnel should perform maintenance, inspection, and replacement

operations. (Take off metal jewelry such as watches and rings and use insulated tools.)

Caution

The Inverter can be used in an environment with a temperature range from 14° -104°F

(-10-40°C) and relative humidity of 95% non-condensing.

The inverter must be operated in a dust, gas, mist and moisture free environment.

1.7 Disposal of the Inverter

Please dispose of this unit with care as an industrial waste and according to your required

local regulations.

The capacitors of inverter main circuit and printed circuit board are considered as

hazardous waste and must not be burned.

The Plastic enclosure and parts of the inverter such as the top cover board will release

harmful gases if burned.

Equipment containing electrical components may not be disposed of together with

domestic waste. It must be separately collected with electrical and electronic waste

according to local and currently valid legislation.

1.8 Guaranteed liability exemption

Loss of opportunity caused by the company's products, damage to customers of your

company or your company, damage to non-company products, or compensation for other

businesses, whether within the warranty period or not, is not covered by the company.

Manual — F510 nameplate example and model-code identification — page 10

P/N BARCODE

S/N BARCODE

Chapter 2 Model Description

2.1 Nameplate Data

It is essential to verify the F510 inverter nameplate and make sure that the F510 inverter has the

correct rating so it can be used in your application with the proper sized AC motor.

Unpack the F510 inverter and check the following:

(1) The F510 inverter and quick setting guide are contained in the package.

(2) The F510 inverter has not been damaged during transportation there should be no dents or

parts missing.

(3) The F510 inverter is the type you ordered. You can check the type and specifications on the

main nameplate.

(4) Check that the input voltage range meets the input power requirements.

(5) Ensure that the motor HP matches the motor rating of the inverter.

2.2 Model Identification

F510 - 4 010 – H 3 F N4

Inverter Model and Motor Rating

UL and CE Marks

Input Power Specifications

Output Power Specifications

Series No.

F510

Inverter

Series

Voltage Rating

2: 200V

4: 400V

Motor Rating

001: 1HP

002: 2HP

003: 3HP

005: 5HP

008:8HP

150: 150HP

175: 175HP

215: 215HP

535:535HP

800:800HP

Input

Blank: 1Ph/3Ph

3: 3Ph

Noise Filter

Blank: No RFI

F: RFI Filer

Operator Type

H: Standard Type (LED Keypad)

C: Standard Type (LCD Keypad)

E: Enhanced Type (LED Keypad)

G: Enhanced Type (LCD Keypad)

Protection Class

Blank: IP00/IP20

N4: IP55

Illustrative F510-4010-H3F nameplate: motor rating 7.5kW. Input AC 3PH 380–480V (+10%,-15%) 50/60Hz 18.2A. Output AC 3PH 380–480V 0–400Hz 17.5A. IP20/NEMA1. P/N BARCODE and S/N BARCODE are placeholders. TECO Electric & Machinery Co., Ltd.; CE and cULus LISTED marks, 16KJ IND. CONT. EQ. E177007. These are markings on this example, not proof of certification for every configuration.

F510 - 4 010 - H 3 F N4: F510 inverter series; voltage digit 2:200V,4:400V. Motor-rating examples printed:001:1HP,002:2HP,003:3HP,005:5HP,008:8HP,150:150HP,175:175HP,215:215HP,535:535HP,800:800HP. Operator H:standard LED keypad,C:standard LCD keypad,E:enhanced LED keypad,G:enhanced LCD keypad. Input blank:1Ph/3Ph,3:3Ph. Noise filter blank:No RFI,F:RFI Filer [printed spelling]. Protection blank:IP00/IP20,N4:IP55. Code legend is not a complete availability matrix.

Manual — 200V model table: 3ph 200–240V +10%/-15%, 50/60Hz — page 11

Inverter Models – Motor Power Rating:

200V Class

200V model table: 3ph 200–240V +10%/-15%, 50/60Hz. Preserve printed circle selection markers, blank cells, merged labels and exact model suffixes. Blank selection cells are not independently stated ratings. Page 10 code legend has a separate 008/8HP discrepancy.

200V model table: 3ph 200–240V +10%/-15%, 50/60Hz. Preserve printed circle selection markers, blank cells, merged labels and exact model suffixes. Blank selection cells are not independently stated ratings. Page 10 code legend has a separate 008/8HP discrepancy. Row group: 3ph

200~240V

+10%/-15%

50/60Hz

Shared source cells (coordinates refer to this table):

200V model table: 3ph 200–240V +10%/-15%, 50/60Hz — PDF page 11

Source row Voltage (Vac) & Frequency (Hz) F510 Model Motor Power (Hp) Applied Motor (kW) Filter — with Filter — without Protection Class (IP55)
1 3ph 200~240V +10%/-15% 50/60Hz F510-2001-□ 1 0.75 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ F510-2002-□ 2 1.5 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
3 ⟦null: no independent source value⟧ F510-2003-□ 3 2.2 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
4 ⟦null: no independent source value⟧ F510-2005-□ 5 3.7 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
5 ⟦null: no independent source value⟧ F510-2008-□ 7.5 5.5 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
6 ⟦null: no independent source value⟧ F510-2010-□ 10 7.5 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
7 ⟦null: no independent source value⟧ F510-2015-□ 15 11 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
8 ⟦null: no independent source value⟧ F510-2020-□ 20 15 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
9 ⟦null: no independent source value⟧ F510-2025-□ 25 18.5 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
10 ⟦null: no independent source value⟧ F510-2030-□ 30 22 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
11 ⟦null: no independent source value⟧ F510-2040-□ 40 30 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
12 ⟦null: no independent source value⟧ F510-2050-□ 50 37 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
13 ⟦null: no independent source value⟧ F510-2060-□ 60 45 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
14 ⟦null: no independent source value⟧ F510-2075-□ 75 55 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
15 ⟦null: no independent source value⟧ F510-2100-□ 100 75 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
16 ⟦null: no independent source value⟧ F510-2125-□ 125 94 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
17 ⟦null: no independent source value⟧ F510-2150-□ 150 112 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
18 ⟦null: no independent source value⟧ F510-2175-□ 175 130 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧

Manual — 400V model table: 3ph 380–480V +10%/-15%, 50/60Hz; continues on next page — page 12

400V Class

400V model table: 3ph 380–480V +10%/-15%, 50/60Hz; continues on next page. Preserve printed circle selection markers, blank cells, merged labels and exact model suffixes. Blank selection cells are not independently stated ratings. Page 10 code legend has a separate 008/8HP discrepancy.

400V model table: 3ph 380–480V +10%/-15%, 50/60Hz; continues on next page. Preserve printed circle selection markers, blank cells, merged labels and exact model suffixes. Blank selection cells are not independently stated ratings. Page 10 code legend has a separate 008/8HP discrepancy. Row group: 3ph

380~480V

+10%/-15%

50/60Hz

Shared source cells (coordinates refer to this table):

400V model table: 3ph 380–480V +10%/-15%, 50/60Hz; continues on next page — PDF page 12

Source row Voltage (Vac) & Frequency (Hz) F510 Model Motor Power (Hp) Applied Motor (kW) Filter — with Filter — without Protection Class (IP55)
1 3ph 380~480V +10%/-15% 50/60Hz F510-4001-□3 1 0.75 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ F510-4001-□3F 1 0.75 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
3 ⟦null: no independent source value⟧ F510-4001-C3FN4 1 0.75 ◎ ⟦blank source cell⟧ ◎
4 ⟦null: no independent source value⟧ F510-4002-□3 2 1.5 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
5 ⟦null: no independent source value⟧ F510-4002-□3F 2 1.5 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
6 ⟦null: no independent source value⟧ F510-4002-C3FN4 2 1.5 ◎ ⟦blank source cell⟧ ◎
7 ⟦null: no independent source value⟧ F510-4003-□3 3 2.2 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
8 ⟦null: no independent source value⟧ F510-4003-□3F 3 2.2 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
9 ⟦null: no independent source value⟧ F510-4003-C3FN4 3 2.2 ◎ ⟦blank source cell⟧ ◎
10 ⟦null: no independent source value⟧ F510-4005-□3 5 3.7 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
11 ⟦null: no independent source value⟧ F510-4005-□3F 5 3.7 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
12 ⟦null: no independent source value⟧ F510-4005-C3FN4 5 3.7 ◎ ⟦blank source cell⟧ ◎
13 ⟦null: no independent source value⟧ F510-4008-□3 7.5 5.5 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
14 ⟦null: no independent source value⟧ F510-4008-□3F 7.5 5.5 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦null: no independent source value⟧ F510-4008-C3FN4 7.5 5.5 ◎ ⟦blank source cell⟧ ◎
16 ⟦null: no independent source value⟧ F510-4010-□3 10 7.5 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
17 ⟦null: no independent source value⟧ F510-4010-□3F 10 7.5 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦null: no independent source value⟧ F510-4010-C3FN4 10 7.5 ◎ ⟦blank source cell⟧ ◎
19 ⟦null: no independent source value⟧ F510-4015-□3 15 11 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
20 ⟦null: no independent source value⟧ F510-4015-□3F 15 11 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦null: no independent source value⟧ F510-4015-C3FN4 15 11 ◎ ⟦blank source cell⟧ ◎
22 ⟦null: no independent source value⟧ F510-4020-□3 20 15 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
23 ⟦null: no independent source value⟧ F510-4020-□3F 20 15 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦null: no independent source value⟧ F510-4020-C3FN4 20 15 ◎ ⟦blank source cell⟧ ◎
25 ⟦null: no independent source value⟧ F510-4025-□3 25 18.5 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧

Manual — 400V model table continuation: 3ph 380–480V +10%/-15%, 50/60Hz — page 13

400V model table continuation: 3ph 380–480V +10%/-15%, 50/60Hz. Preserve printed circle selection markers, blank cells, merged labels and exact model suffixes. Blank selection cells are not independently stated ratings. Page 10 code legend has a separate 008/8HP discrepancy.

400V model table continuation: 3ph 380–480V +10%/-15%, 50/60Hz. Preserve printed circle selection markers, blank cells, merged labels and exact model suffixes. Blank selection cells are not independently stated ratings. Page 10 code legend has a separate 008/8HP discrepancy. Row group: 3ph

380~480V

+10%/-15%

50/60Hz

Shared source cells (coordinates refer to this table):

400V model table continuation: 3ph 380–480V +10%/-15%, 50/60Hz — PDF page 13

Source row Voltage (Vac) & Frequency (Hz) F510 Model Motor Power (Hp) Applied Motor (kW) Filter — with Filter — without Protection Class (IP55)
1 3ph 380~480V +10%/-15% 50/60Hz F510-4025-□3F 25 18.5 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ F510-4025-C3FN4 25 18.5 ◎ ⟦blank source cell⟧ ◎
3 ⟦null: no independent source value⟧ F510-4030-□3 30 22 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
4 ⟦null: no independent source value⟧ F510-4030-□3F 30 22 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
5 ⟦null: no independent source value⟧ F510-4030-C3FN4 30 22 ◎ ⟦blank source cell⟧ ◎
6 ⟦null: no independent source value⟧ F510-4040-□3 40 30 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
7 ⟦null: no independent source value⟧ F510-4040-□3F 40 30 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
8 ⟦null: no independent source value⟧ F510-4040-C3FN4 40 30 ◎ ⟦blank source cell⟧ ◎
9 ⟦null: no independent source value⟧ F510-4050-□3 50 37 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
10 ⟦null: no independent source value⟧ F510-4050-□3F 50 37 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
11 ⟦null: no independent source value⟧ F510-4050-C3FN4 50 37 ◎ ⟦blank source cell⟧ ◎
12 ⟦null: no independent source value⟧ F510-4060-□3 60 45 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
13 ⟦null: no independent source value⟧ F510-4060-□3F 60 45 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦null: no independent source value⟧ F510-4060-C3FN4 60 45 ◎ ⟦blank source cell⟧ ◎
15 ⟦null: no independent source value⟧ F510-4075-□3 75 55 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
16 ⟦null: no independent source value⟧ F510-4075-□3F 75 55 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦null: no independent source value⟧ F510-4075-C3N4 75 55 ⟦blank source cell⟧ ◎ ◎
18 ⟦null: no independent source value⟧ F510-4100-□3 100 75 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
19 ⟦null: no independent source value⟧ F510-4100-C3N4 100 75 ⟦blank source cell⟧ ◎ ◎
20 ⟦null: no independent source value⟧ F510-4125-□3 125 94 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
21 ⟦null: no independent source value⟧ F510-4150-□3 150 112 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
22 ⟦null: no independent source value⟧ F510-4175-□3 175 130 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
23 ⟦null: no independent source value⟧ F510-4215-□3 215 160 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
24 ⟦null: no independent source value⟧ F510-4250-□3 250 185 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
25 ⟦null: no independent source value⟧ F510-4300-□3 300 220 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
26 ⟦null: no independent source value⟧ F510-4375-□3 375 280 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
27 ⟦null: no independent source value⟧ F510-4425-□3 425 317 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
28 ⟦null: no independent source value⟧ F510-4535-□3 535 400 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
29 ⟦null: no independent source value⟧ F510-4670-□3 670 500 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧
30 ⟦null: no independent source value⟧ F510-4800-□3 800 600 ⟦blank source cell⟧ ◎ ⟦blank source cell⟧

Manual — Environment, protection and operating limits — page 14

Chapter 3 Environment and Installation

3.1 Environment

The environment will directly affect the proper operation and the life span of the inverter. To

ensure that the inverter will give maximum service life, please comply with the following

environmental conditions:

Environment, protection and operating limits. Editorial column labels; all source rows retained including section headings. Do not silently correct supplier wording.

Environment, protection and operating limits. Editorial column labels; all source rows retained including section headings. Do not silently correct supplier wording. Row group: Protection

Class

Environment, protection and operating limits. Editorial column labels; all source rows retained including section headings. Do not silently correct supplier wording. Row group: Ambient Environment

Environment, protection and operating limits. Editorial column labels; all source rows retained including section headings. Do not silently correct supplier wording. Row group: Operating

Temperature

Environment, protection and operating limits. Editorial column labels; all source rows retained including section headings. Do not silently correct supplier wording. Row group: Storage

Environment, protection and operating limits. Editorial column labels; all source rows retained including section headings. Do not silently correct supplier wording. Row group: Humidity

Environment, protection and operating limits. Editorial column labels; all source rows retained including section headings. Do not silently correct supplier wording. Row group: Altitude

Environment, protection and operating limits. Editorial column labels; all source rows retained including section headings. Do not silently correct supplier wording. Row group: Installation

Site

Environment, protection and operating limits. Editorial column labels; all source rows retained including section headings. Do not silently correct supplier wording. Row group: Shock

Shared source cells (coordinates refer to this table):

Environment, protection and operating limits — PDF page 14

Source row Label (editorial) Source wording (editorial)
1 Protection ⟦null: no independent source value⟧
2 Protection Class IP20/ IP21/ NEMA 1, IP00
3 ⟦null: no independent source value⟧ IP55/ NEMA 12
4 Ambient Environment ⟦null: no independent source value⟧
5 Operating Temperature IP20/IP21/IP55: -10°C - +40°C (14 -104 °F) IP00 (Without Cover): -10°C - +50°C (14-122 °F) Enhanced type frame 5 is 50°C without de-rating. The maximum operating temperature is 60°C, but it is required to derate 2% of current at each additional 1°C. If several inverters are placed in the same control panel, provide a heat removal means to maintain ambient temperatures
6 Storage Temperature -20°C - +70°C (-4 -158 °F)
7 Humidity 95% non-condensing Relative humidity 5% to 95%, free of moisture. (Follow IEC60068-2-78 standard)
8 Altitude Altitude: Below 1000 m (3281 ft.) It is required to derate 1% of current at each additional 100 m. The maximum altitude is 3000 m.
9 Installation Site Avoid direct sunlight.
10 ⟦null: no independent source value⟧ Avoid exposure to rain or moisture.
11 ⟦null: no independent source value⟧ Avoid oil mist and salinity.
12 ⟦null: no independent source value⟧ Avoid corrosive liquid and gas.
13 ⟦null: no independent source value⟧ Avoid dust, lint fibers, and small metal filings.
14 ⟦null: no independent source value⟧ Avoid electromagnetic interference (soldering machines, power machines).
15 ⟦null: no independent source value⟧ Keep away from radioactive and flammable materials.
16 ⟦null: no independent source value⟧ Avoid vibration (stamping, punching machines etc.). Add a vibration-proof pad if the situation cannot be avoided.
17 Shock Maximum acceleration: 1.2G (12m/s²), from 49.84 to 150 Hz Displacement amplitude : 0.3mm (peak value), from 10 to 49.84 Hz (Follow IEC60068-2-6 standard)

Manual — Installation clearances and heat dissipation — page 15

3.2 Installation

3.2.1 Installation Spaces

When installing the inverter, ensure that inverter is installed in upright position (vertical

direction) and there is adequate space around the unit to allow normal heat dissipation as per

the following Fig. 3.2.1

5.9in.

150mm

Air Flow

X

Fig 3.2.1: F510 Installation space

X = 1.18” (30mm) for inverter ratings up to 18.5kW

X = 1.96” (50mm) for inverter ratings 22kW or higher

Important Note: The inverter heatsink temperature can reach up to 90°C/ 194°F during

operation; make sure to use insulation material rated for this temperature.

Upright installation. Front and side drawings show 5.9in./150mm clearance above and below. X denotes horizontal clearance on each side:1.18in.(30mm) up to18.5kW;1.96in.(50mm)22kW or higher. Ambient temperature callout -10°C to +40°C. Air Flow arrow curves upward at lower side view. These clearances are diagram labels; do not derive dimensions by scaling.

Manual — IP00/IP20 external views: groups (a) and (b) — page 16

3.2.2 External View

3.2.2.1 External View (IP00/ IP20)

(a) 200V 1-7.5HP/ 400V 1-10HP

(Wall-mounted type, IEC IP00) (Wall-mounted type, IEC IP20, NEMA1)

(b) 200V 10-30HP/ 400V 15-40HP

(Wall-mounted type, IEC IP00) (Wall-mounted type, IEC IP20, NEMA1)

Left wall-mounted IEC IP00:front cover,digital operator,terminal cover,mounting hole,heat sink,nameplate and barcode. Right IEC IP20,NEMA1 additionally labels anti-dust cover.

Left wall-mounted IEC IP00:front cover,digital operator,terminal cover,mounting hole,nameplate and barcode. Right IEC IP20,NEMA1 also labels anti-dust cover.

Manual — IP00/IP20 external views: groups (c) and (d) — page 17

(c) 200V 40-50HP/ 400V 50-75HP

(Wall-mounted type, IEC IP20, NEMA1)

(d) 200V 60-125HP/ 400V 100-250HP

(Wall-mounted type, IEC IP00) (Wall-mounted type, IEC IP20, NEMA1)

Wall-mounted IEC IP20,NEMA1:front cover,digital operator,terminal cover,mounting hole,lifting lugs(4pcs),nameplate and barcode.

Left wall-mounted IEC IP00:front cover,digital operator,terminal cover,mounting hole,lifting lugs(4pcs),nameplate and barcode. Right IEC IP20,NEMA1 also labels anti-dust cover and wiring box.

Manual — IP00/IP20 external views: groups (e) and (f) — page 18

(e) 200V 150-175HP/ 400V 300-425HP

(Wall-mounted type, IEC IP00) (Wall-mounted type, IEC IP20)

(f) 400V 535-800HP

(Wall-mounted type, IEC IP00) (Wall-mounted type, IEC IP20)

Left IEC IP00 and right IEC IP20 wall-mounted:front cover,digital operator,terminal cover,mounting hole,lifting lugs(4pcs),nameplate and barcode. Right adds anti-dust cover and wiring box; neither caption states NEMA1.

Left IEC IP00 and right IEC IP20 wall-mounted:front cover,digital operator,terminal cover,mounting hole,lifting lugs(4pcs),nameplate and barcode. Right adds wiring box; no NEMA1 caption.

Manual — IP55 external views, 400V 1–25HP and 30–100HP — page 19

3.2.2.2 External View (IP55)

(a) 400V 1-25HP (b) 400V 30-100HP

(Wall-mounted type, IEC IP55) (Wall-mounted type, IEC IP55)

Wall-mounted IEC IP55:front cover,digital operator,mounting hole,nameplate and barcode.

Wall-mounted IEC IP55:front cover,digital operator,mounting hole,lifting lugs(4pcs),nameplate and barcode.

Manual — Warning labels by exact voltage, horsepower and IP enclosure — page 20

3.2.3 Warning Labels

Important:

Warning information located on the front cover must be read upon installation of

the inverter.

(a) 200V: 1-7.5HP/ 400V: 1-10HP (IP20)

(b) 200V: 10-15HP/ 400V: 15-20HP (IP20)

(c) 200V: 20-175HP/ 400V: 25-800HP(IP20)

(d) 400V:1-100HP (IP55)

WARNING:Risk of electrical shock. Shut off main power and wait for 5 minutes before servicing. Hot surface. Risk of burn. CAUTION:See manual before operation.

WARNING:Risk of electrical shock. Shut off main power and wait for 5 minutes before servicing. CAUTION:See manual before operation.

WARNING:Risk of electrical shock. Shut off main power and wait for 15 minutes before servicing. CAUTION:See manual before operation.

Manual — Front-cover and keypad removal: IP00/IP20 contrasted with IP55 — page 21

3.2.4 Removing the Front Cover and Keypad

Before making any wiring connections to the inverter, the front cover needs to be

removed.

IP00/ IP20 Type

Caution

It is not required to remove the digital operator before making any wiring connections.

Models 200V,1– 30 HP and 400V, 1 – 40 HP have a plastic cover. Loosen the screws

and remove the cover to gain access to the terminals and make wiring connections.

Place the plastic cover back and fasten screws when wiring connections have been

made.

Models 200V, 40 - 175HP and 400V, 50 - 800HP have a metal cover. Loosen the

screws and remove the cover to gain access to the terminals and make wiring

connections. Place the metal cover back and fasten screws when wiring connections

have been made.

IP55 Type

It is essential to remove the digital operator before making any wiring connections.

Model 400V, 1 – 25 HP has a plastic cover. Loosen the screws and remove the cover to

gain access to the terminals and make wiring connections. Place the plastic cover back

and fasten screws when wiring connections have been made, suggested screw locking

torque is 8 kgf-cm.

Models 400V, 30 - 100HP has a metal cover. Loosen the screws and remove the cover

to gain access to the terminals and make wiring connections. Place the metal cover

back and fasten screws when wiring connections have been made, suggested screw

locking torque is 8 kgf-cm.

Manual — IP00/IP20 removal: 200V 1–3HP /400V 1–3HP — page 22

3.2.4.1 IP00/ IP20 Type

(a) 200V 1-3HP/ 400V 1-3HP

Step 1: Unscrew Step 2: Remove whole top cover, and

unlock RJ45 connector

Step 3: Make wire connections, lock RJ45 Step 4: Fasten screw

connector and place top cover back

Four illustrated steps, read upper-left then upper-right then lower-left then lower-right. 1 Unscrew.2 Remove whole top cover and unlock RJ45 connector.3 Make wire connections,lock RJ45 connector and place top cover back.4 Fasten screw. Original figures govern screw locations and physical removal motion; no added torque or fastener specification.

Manual — IP00/IP20 removal: 200V 5–7 — page 23

(b) 200V 5-7.5HP(Standard Type) 5~10HP (Enhanced Type) /400V 5-10HP

Step 1: Unscrew Step 2: Remove cover

Step 3: Make wire connections and place cover back Step 4: Fasten screw

Four illustrated steps, read upper-left then upper-right then lower-left then lower-right. 1 Unscrew.2 Remove cover.3 Make wire connections and place cover back.4 Fasten screw. Original figures govern screw locations and physical removal motion; no added torque or fastener specification.

Manual — IP00/IP20 removal:200V 10–30HP /400V 15–40HP — page 24

(c) 200V 10-30HP/ 400V 15-40HP

Step 1: Unscrew Step 2: Remove cover

Step 3: Make wire connections and place cover back Step 4: Fasten screw

Four illustrated steps, read upper-left then upper-right then lower-left then lower-right. 1 Unscrew.2 Remove cover.3 Make wire connections and place cover back.4 Fasten screw. Original figures govern screw locations and physical removal motion; no added torque or fastener specification.

Manual — IP00/IP20 removal:200V 40–50HP /400V 50–75HP standard,50–100HP enhanced — page 25

(d) 200V 40-50HP/ 400V 50-75HP (Standard Type) 50~100HP (Enhanced Type)

Step 1: Unscrew cover Step 2: Remove cover

Step 3: Make wire connections and place cover back Step 4: Fasten screw

Four illustrated steps, read upper-left then upper-right then lower-left then lower-right. 1 Unscrew cover.2 Remove cover.3 Make wire connections and place cover back.4 Fasten screw. Original figures govern screw locations and physical removal motion; no added torque or fastener specification.

Manual — IP00/IP20 removal:200V 60–125HP /400V 100–250HP — page 26

(e) 200V 60-125HP/ 400V 100-250HP

Step 1: Unscrew cover Step 2: Remove cover

Step 3: Make wire connections and place cover back

Step 4: Fasten screw

Four illustrated steps, read upper-left then upper-right then lower-left then lower-right. 1 Unscrew cover.2 Remove cover.3 Make wire connections and place cover back.4 Fasten screw. Original figures govern screw locations and physical removal motion; no added torque or fastener specification.

Manual — IP00/IP20 removal:200V150–175HP /400V300–425HP — page 27

(f) 200V 150-175HP/ 400V 300-425HP

Step 1: Unscrew cover

Step 2: Remove cover

Step 3: Make wire connections and place cover back Step 4: Fasten screw

Four panels read left-to-right, top-to-bottom:1 Unscrew the cover;2 Remove the cover;3 Make wire connections and place the cover back;4 Fasten the screw. Arrows and geometry remain in the source figure; no torque inferred.

Manual — IP00/IP20 removal:400V535–800HP — page 28

(g) 400V 535-800HP

Step 1: Unscrew cover

Step 2: Remove cover

Step 3: Make wire connections and place cover back

Step 4: Fasten screw

Four panels read left-to-right, top-to-bottom:1 Unscrew the cover;2 Remove the cover;3 Make wire connections and place the cover back;4 Fasten the screw. Arrows and geometry remain in the source figure; no torque inferred.

Manual — Built-in filter IP20/IP00 removal:400V1–3HP — page 29

3.2.4.2 Built-in Filter Type (IP20/ IP00)

(a) 400V 1-3HP

Step 1: Unscrew cover Step 2: Remove whole top cover

Step 3: Unlock RJ45 connector, Unscrew filter section Step 4: Remove filter cover

Step 5: Make wire connections, lock RJ45 Step 6: Fasten screw

connector and place top cover back

Six ordered panels:1 Unscrew cover;2 Remove whole top cover;3 Unlock RJ45 connector and unscrew filter section;4 Remove filter cover;5 Make wire connections, lock RJ45 connector and place top cover back;6 Fasten screw. RJ45 connector detail belongs to panel3.

Manual — Built-in filter IP20/IP00 removal:400V5–75HP — page 30

(b) 400V 5-75HP

Step 1: Unscrew cover Step 2: Remove cover

Step 3: Unscrew filter section

Step 4: Remove filter cover

Step 5: Make connections and place filter cover back

Step 6: Fasten screw

Six ordered panels:1 Unscrew cover;2 Remove cover;3 Unscrew filter section;4 Remove filter cover;5 Make wire connections and place filter cover back;6 Fasten screw.

Manual — IP55 removal:400V1–25HP — page 31

3.2.4.3 Water proof Type (IP55)

(a) 400V 1-25HP

Step 1: Unscrew operator Step 2: Remove operator

Step 3: Pull out operator and remove power line Step 4: Unscrew cover

Step 5: Check the inside waterproof gasket is not pulled

away from cover while opening the cover

Waterproof gasket

Ordered panels:1 Unscrew operator;2 Remove operator;3 Pull out operator and remove power line;4 Unscrew cover;5 When opening the cover, check the inside waterproof gasket is not pulled away from the cover. Gasket callout identifies operator-frame gasket. The supplier wording power line is retained.

Manual — IP55 removal:400V30–100HP — page 32

(b) 400V 30-100HP

Step 1: Unscrew operator Step 2: Remove operator

Step 3: Pull out operator and unlock RJ45 connector Step4: Unscrew cover and remove it

Waterproof gasket

Ordered panels:1 Unscrew operator;2 Remove operator;3 Pull out operator and unlock RJ45 connector;4 Unscrew cover and remove it. Waterproof-gasket labels identify both the operator frame and the main cover; preserve both contexts.

Manual — Wire gauges, round crimp terminals, torque and tools — page 33

3.3 Inverter Wiring

3.3.1 Wire Gauges and Tightening Torque

To comply with UL standards, use UL approved copper wires (rated 75° C) and round crimp terminals

(UL Listed products) as shown in table below when connecting to the main circuit terminals. Teco

recommends using crimp terminals manufactured by NICHIFU Terminal Industry Co., Ltd and the

terminal crimping tool recommended by the manufacturer for crimping terminals and the insulating

sleeve.

Table 3.3.1.1 Wire gauges and tightening torque terminal screw size

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating.

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 0.75 (18)

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 1.25 (16)

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 2 (14)

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 3.5/5.5 (12/10)

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 8 (8)

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 14 (6)

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 22 (4)

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 30/38 (3 / 2)

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 50/ 60 (1/ 1/ 0)

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 70 (2/0)

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 80 (3/0)

Wire gauges, round crimp terminals, torque and tools. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 100 (4/0)

Shared source cells (coordinates refer to this table):

Wire gauges, round crimp terminals, torque and tools table1 — PDF page 33

Source row Wire size mm2 (AWG) Terminal Screw size Model of round crimp terminal Tightening torque kgf.cm (in.lbs) Model of insulating sleeve Model of crimp tool
1 0.75 (18) M3.5 R1.25-3.5 8.2 to 10 (7.1 to 8.7) TIC 1.25 NH 1
2 ⟦null: no independent source value⟧ M4 R1.25-4 12.2 to 14 (10.4 to 12.1) TIC 1.25 NH 1
3 1.25 (16) M3.5 R1.25-3.5 8.2 to 10 (7.1 to 8.7) TIC 1.25 NH 1
4 ⟦null: no independent source value⟧ M4 R1.25-4 12.2 to 14 (10.4 to 12.1) TIC 1.25 NH 1
5 2 (14) M3.5 R2-3.5 8.2 to 10 (7.1 to 8.7) TIC 2 NH 1 / 9
6 ⟦null: no independent source value⟧ M4 R2-4 12.2 to 14 (10.4 to 12.1) TIC 2 NH 1 / 9
7 ⟦null: no independent source value⟧ M5 R2-5 22.1 to 24 (17.7 to 20.8) TIC 2 NH 1 / 9
8 ⟦null: no independent source value⟧ M6 R2-6 25.5 to 30.0 (22.1 to 26.0) TIC 2 NH 1 / 9
9 3.5/5.5 (12/10) M4 R5.5-4 12.2 to 14 (10.4 to 12.1) TIC 3.5/5.5 NH 1 / 9
10 ⟦null: no independent source value⟧ M5 R5.5-5 20.4 to 24 (17.7 to 20.8) TIC 3.5/5.5 NH 1 / 9
11 ⟦null: no independent source value⟧ M6 R5.5-6 25.5 to 30.0 (22.1 to 26.0) TIC 3.5/5.5 NH 1 / 9
12 ⟦null: no independent source value⟧ M8 R5.5-8 61.2 to 66.0 (53.0 to 57.2) TIC 3.5/5.5 NH 1 / 9
13 8 (8) M4 R8-4 12.2 to 14 (10.4 to 12.1) TIC 8 NOP 60
14 ⟦null: no independent source value⟧ M5 R8-5 20.4 to 24 (17.7 to 20.8) TIC 8 NOP 60
15 ⟦null: no independent source value⟧ M6 R8-6 25.5 to 30.0 (22.1 to 26.0) TIC 8 NOP 60
16 ⟦null: no independent source value⟧ M8 R8-8 61.2 to 66.0 (53.0 to 57.2) TIC 8 NOP 60
17 14 (6) M4 R14-4 12.2 to 14 (10.4 to 12.1) TIC 14 NH 1 / 9
18 ⟦null: no independent source value⟧ M5 R14-5 20.4 to 24 (17.7 to 20.8) TIC 14 NH 1 / 9
19 ⟦null: no independent source value⟧ M6 R14-6 25.5 to 30.0 (22.1 to 26.0) TIC 14 NH 1 / 9
20 ⟦null: no independent source value⟧ M8 R14-8 61.2 to 66.0 (53.0 to 57.2) TIC 14 NH 1 / 9
21 22 (4) M6 R22-6 25.5 to 30.0 (22.1 to 26.0) TIC 22 NOP 60/ 150H
22 ⟦null: no independent source value⟧ M8 R22-8 61.2 to 66.0 (53.0 to 57.2) TIC 22 NOP 60/ 150H
23 30/38 (3 / 2) M6 R38-6 25.5 to 30.0 (22.1 to 26.0) TIC 38 NOP 60/ 150H
24 ⟦null: no independent source value⟧ M8 R38-8 61.2 to 66.0 (53.0 to 57.2) TIC 38 NOP 60/ 150H
25 50/ 60 (1/ 1/ 0) M8 R60-8 61.2 to 66.0 (53.0 to 57.2) TIC 60 NOP 60/ 150H
26 ⟦null: no independent source value⟧ M10 R60-10 102 to 120 (88.5 to 104) TIC 60 NOP 150H
27 70 (2/0) M8 R70-8 61.2 to 66.0 (53.0 to 57.2) TIC 60 NOP 150H
28 ⟦null: no independent source value⟧ M10 R70-10 102 to 120 (88.5 to 104) TIC 60 NOP 150H
29 80 (3/0) M10 R80-10 102 to 120 (88.5 to 104) TIC 80 NOP 150H
30 ⟦null: no independent source value⟧ M16 R80-16 255 to 280 (221 to 243) TIC 80 NOP 150H
31 100 (4/0) M10 R100-10 102 to 120 (88.5 to 104) TIC 100 NOP 150H
32 ⟦null: no independent source value⟧ M12 R100-12 143 to 157 (124 to 136) TIC 100 NOP 150H
33 ⟦null: no independent source value⟧ M16 R80-16 255 to 280 (221 to 243) TIC 80 NOP 150H

Manual — Drive-model closed-loop crimp terminal selection — page 34

Main Circuit Terminal Wiring

UL approval requires crimp terminals when wiring the drive’s main circuit terminals. Use

crimping tools as specified by the crimp terminal manufacturer. Teco recommends crimp

terminals made by NICHIFU for the insulation cap.

The table below matches drives models with crimp terminals and insulation caps.

Closed-Loop Crimp Terminal Size

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating.

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 2001/2002/

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 2005/2008

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 2010/2015

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 2030

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 2050

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 2075

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 2125

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 2175

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 4001/4002/

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 4005/4008/

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 4015/4020

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 4025/4030/

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 4050/4060/

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 4100/4125

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 4150/4175/

4215/4250

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 4300

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 4375/4425

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 4535/4670

Drive-model closed-loop crimp terminal selection. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 4800

Shared source cells (coordinates refer to this table):

Drive-model closed-loop crimp terminal selection table1 — PDF page 34

Source row Drive Model F510 Wire Gauge mm²(AWG):R/L1,S/L2,T/L3 Wire Gauge mm²(AWG):U/T1,V/T2,W/T3 Terminal screws Crimp Terminal model Tool machine Insulation Cap model
1 2001/2002/ 2003 2 (14) ⟦null: no independent source value⟧ M4 R2-4 Nichifu NH 1 / 9 TIC 2
2 ⟦null: no independent source value⟧ 3.5 (12) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ R5.5-4 ⟦null: no independent source value⟧ TIC 3.5
3 ⟦null: no independent source value⟧ 5.5 (10) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ TIC 5.5
4 2005/2008 5.5 (10) ⟦null: no independent source value⟧ M4 R5.5-4 Nichifu NH 1 / 9 TIC 5.5
5 2010/2015 14 (6) ⟦null: no independent source value⟧ M4 R14-6 Nichifu NOP 60 TIC 8
6 2030 38 (2) ⟦null: no independent source value⟧ M6 R38-6 Nichifu NOP 60 / 150H TIC 22
7 2050 80 (3/0) ⟦null: no independent source value⟧ M8 R80-8 Nichifu NOP 60 / 150H TIC 60
8 2075 150 (4/0) ⟦null: no independent source value⟧ M8 R150-8 Nichifu NOP 150H TIC 80
9 2125 300 (4/0)*2 ⟦null: no independent source value⟧ M10 R150-10 Nichifu NOP 150H TIC 100
10 2175 152 (300)*2 ⟦null: no independent source value⟧ M12 R150-12*2 Nichifu NOP 150H TIC 150
11 4001/4002/ 4003 2 (14) ⟦null: no independent source value⟧ M4 R2-4 Nichifu NH 1 / 9 TIC 2
12 ⟦null: no independent source value⟧ 3.5 (12) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ R5.5-4 ⟦null: no independent source value⟧ TIC 3.5
13 ⟦null: no independent source value⟧ 5.5 (10) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ TIC 5.5
14 4005/4008/ 4010 5.5 (10) ⟦null: no independent source value⟧ M4 R5.5-4 Nichifu NH 1 / 9 TIC 5.5
15 4015/4020 8 (8) ⟦null: no independent source value⟧ M6 R8-6 Nichifu NOP 60 TIC 8
16 4025/4030/ 4040 22 (6) ⟦null: no independent source value⟧ M6 R22-6 Nichifu NOP 60 / 150H TIC 14
17 4050/4060/ 4075 60 (2) ⟦null: no independent source value⟧ M8 R60-8 Nichifu NOP 60 / 150H TIC 38
18 4100/4125 150 (3/0) ⟦null: no independent source value⟧ M8 R150-8 Nichifu NOP 150H TIC 80
19 4150/4175/ 4215/4250 300 (4/0)*2 ⟦null: no independent source value⟧ M10 R150-10 Nichifu NOP 150H TIC 100
20 4300 203 (400)*2 ⟦null: no independent source value⟧ M12 R200-12S*2 Nichifu NOH 300K TIC 200
21 4375/4425 253 (500)*2 ⟦null: no independent source value⟧ M12 R325-12S*2 Nichifu NOH 300K TIC 325
22 4535/4670 152 (300)*4 ⟦null: no independent source value⟧ M10 R150-10*4 Nichifu NOP 150H TIC 150
23 4800 203 (400)*4 ⟦null: no independent source value⟧ M10 R200-10S *4 Nichifu NOH 300K TIC 200

Manual — Peripheral wiring precautions and voltage-drop formula — page 35

3.3.2 Wiring Peripheral Power Devices

Caution

After power is shut off to the inverter, the capacitors will slowly discharge. Do NOT touch the

inverter circuitry or replace any components until the “CHARGE” indicator is off.

Do NOT wire or connect/disconnect internal connectors of the inverter when the inverter is

powered up or when powered off and the “CHARGE”” indicator is on.

Do NOT connect inverter output U, V and W to the supply power. This will result in damage to

the inverter.

The inverter must be by properly grounded. Use terminal E to connect earth ground and

comply with local standards.

 It is required to disconnect the grounded wire in the control board when the inverter is not

grounded or floating ground power system.

Do NOT perform a dielectric voltage withstand test (megger) on the inverter this will result in

inverter damage to the semiconductor components.

Do NOT touch any of the components on the inverter control board to prevent damage to the

inverter by static electricity.

Refer to the recommended wire size table for the appropriate wire to use. The voltage

between the power supply and the input of the inverter may not exceed 2%.

Phase-to-phase voltage drop (V) = 3 ×resistance of wire (Ω/km) × length of line m) × current×10-3.

(km=3280 x feet) / (m=3.28 x feet )

Reduce the carrier frequency (parameter 11-01) If the cable from the inverter to the motor is

greater than 25m (82ft). A high-frequency current can be generated by stray capacitance

between the cables and result in an overcurrent trip of the inverter, an increase in leakage

current, or an inaccurate current readout.

To protect peripheral equipment, install fast acting fuses on the input side of the inverter. Refer

to section 11.4 for additional information.

Printed equation:Phase-to-phase voltage drop(V)=√3×resistance of wire(Ω/km)×length of line(m)×current×10^-3. Printed conversion line:(km=3280×feet)/(m=3.28×feet). This is a transcription, not an endorsed conversion or computed design result.

Manual — Peripheral device functions and conditional requirements — page 36

MCCB

Power supply:

Make sure the correct voltage is applied to avoid damaging the

inverter.

Molded-case circuit breaker (MCCB) or fused disconnect:

A molded-case circuit breaker or fused disconnect must be installed

between the AC source and the inverter that conforms to the rated

voltage and current of the inverter to control the power and protect

the inverter.

Do not use the circuit breaker as the run/stop switch for the

Ground fault detector / breaker:

Install a ground fault breaker to prevent problems caused by

current leakage and to protect personnel. Select current range up to

200mA, and action time up to 0.1 second to prevent high frequency

failure.

Magnetic contactor:

Normal operations do not need a magnetic contactor. When

performing functions such as external control and auto restart after

power failure, or when using a brake controller, install a magnetic

contactor.

Do not use the magnetic contactor as the run/stop switch for

AC line reactor for power quality:

When inverters are supplied by a high capacity power source (>

600KVA), an AC reactor can be connected to improve the power

factor.

Install Fast Acting Fuse:

To protect peripheral equipment, install fast acting fuses in

accordance with the specifications in section 11.4 for peripheral

devices.

Input Noise filter:

A filter must be installed when there are inductive loads affecting the

inverter. The inverter meets EN55011 Class A, category C3 when

the TECO special filter is used. See section 11.3 for peripheral

Inverter:

Output terminals T1, T2, and T3 are connected to U, V, and W

terminals of the motor. If the motor runs in reverse while the inverter

is set to run forward, swap any two terminals connections for T1, T2,

and T3.

To avoid damaging the inverter, do not connect the output

terminals T1, T2, and T3 to AC input power.

Connect the ground terminal properly. (200V series: Rg

<100; 400V series: Rg <10.)

Output Noise filter:

An output noise filter may reduce system interference and induced

noise.

Motor:

If the inverter drives multiple motors the output rated current of the

inverter must be greater than the total current of all the motors.

Top-to-bottom illustrated chain:Power Supply→MCCB→Magnetic Contactor→AC Reactor→Fast Acting Fuse→Input Noise Filter→F510→Output Noise Filter→Induction Motor. Ground symbols at drive and motor. This describes figure topology only; conditional component requirements are in adjacent source prose.

Manual — General wiring diagram for standard H and C types — page 37

3.3.3 General Wiring Diagram

3.3.3.1 General Wiring Diagram (For Standard H & C type)

The following is the standard wiring diagram for the F510 inverter (◎ indicates main circuit

terminals and ○ indicates control circuit terminals). Locations and symbols of the wiring terminal

block might be different due to different models of F510. The description of control circuit terminals

and main circuit terminals can be referred to Table 3.3.5.1, 3.3.6.1 and 3.3.6.2

InputR/L1,S/L2,T/L3 is shown through NFB,MC and fast-acting fuse; outputU/T1,V/T2,W/T3 goes to induction motor. B1/P andB2 connect optional braking resistor*1. E grounding label reads less than100Ω. S1 Forward/Stop,S2 Reverse/Stop,S3/S4/S5 multi-step speeds1/2/3,S6 Fault reset. SW3 selects Source(PNP) or Sink(NPN default).24V is PNP source supply;24VG is NPN common.

+10V analog supply20mA;AI1 diagram0–10V,20KΩ;AI2 diagram0–10V,200KΩ or4–20mA,250Ω selected bySW2(V/I,I default). MT is PTC input;GND analog common. F1/F2 run-permissive link is normally closed; opening stops operation. AO1/SW1 andAO2/SW6 select0–10V or4–20mA. PI pulse input32kHz maximum;PO/GND energy-meter pulse output. CN3 connectsJN5-IO-8DO. R1A/B/C,R2A/C,R3A/C relay outputs label250VAC/30VDC,under1A. CN6 RJ45 RS485,S+/S-,SW5 terminator. RJ45 pins1Data+,2Data-,3Data+,4Reserved,5Reserved,6Data-,7:5V,8GND.

Manual — General wiring diagram for enhanced E and G types — page 38

3.3.3.2 General Wiring Diagram (For Enhanced E & G type)

The following is the standard wiring diagram for the F510 inverter (◎ indicates main circuit

terminals and ○ indicates control circuit terminals). Locations and symbols of the wiring terminal

block might be different due to different models of F510. The description of control circuit terminals

and main circuit terminals can be referred to Table 3.3.5.1, 3.3.6.1 and 3.3.6.2

Remarks:

*1: Models IP20 200V 1~30HP, 400V 1~40HP have a built-in braking transistor so that the braking resistor can be connected between

terminal B1 and B2.

*2: The multi-function digital input terminals S1~S6 can be set to Source (PNP) or Sink (NPN) mode via SW6.

*3: Use SW3/SW4 to switch between voltage (0~10V) and current (4~20mA) input for Multi-function analog input 2 (AI2). Besides please

also check parameter 04-00 for proper setting.

*4: Run permissive input SF1 & SF2 is a normally closed input. This input should be closed to enable the inverter output. To activate this

input, open the link between SF1/ SF2 and SG.

*5: When using the open collector for pulse input, it doesn’t need resistance because of built-in pull-up resistance.

*6: AO1 / AO2 default setting is 0~+10V.

*7: It need turn on the switch for the terminal resistor RS485 in the last inverter when many inverters in parallel connection.

*8: Only the model 200V 5~50HP and 400V 5~100HP provide P1 terminal, for external DCL connected between P1 and P2, P1 and P2

are short-circuited before shipping out from the factory.

*9: Both 200V class 60HP~175HP and 400V class 125HP~425HP have built-in DC reactors.

InputR/L1,S/L2,T/L3 throughNFB/MC;outputU/T1,V/T2,W/T3 toIM. P1/P2/B1 link andB2 brake shown. S1–S6 functions match diagram labels Forward/Stop,Reverse/Stop,multi-step1/2/3,Fault reset. SW6 selectsPNP/NPN. SW1 selectsAO1,SW2 selectsAO2,SW3 selectsAI1,SW4 selectsAI2. AI1 diagram0–10V500KΩ or4–20mA500Ω;AI2 diagram0–10V90KΩ or4–20mA250Ω. SF1/SG/SF2 run-permissive:remove jumpersSF1–SG andSF2–SG for external use; normally closed. CN2 communication/I/O expansion;CN3JN5-IO-8DO orDC24V power option;SW5 is RS485 termination at last parallel unit. PI open-collector input has built-in pull-up; no additional resistor in stated arrangement.

Manual — Standard H/C voltage-type pressure sensor, single/multiple pumps — page 39

3.3.4 Single/ Multi- Pump Dedicated Wiring Diagram

3.3.4.1 Single/ Multi- Pump Dedicated Wiring Diagram (For Standard H & C type)

 PUMP Wiring Diagram for Pressure Sensor of Voltage Type

Single Pump:

Multi-Pump:

F510 Single Pump Operation

Operation Switch

Pressure

Converter

TM2

SW2

SW3

NPN

J

P

V

I

S(+) S(-)

S1

S3

S5

AI2

E

24VG

S2

S4

S6

F1

F2

PO

P I

24V

+10V

MT

GND

AI1

AO2

R1A

R1B

R1C

R2A

R2C

R3A

R3C

AO1

00-02 = 1 (Control Circuit Terminal)

04-00 = 0 (0~10V); 10-00=0 (Target Source: Keypad)

10-01 = 2 (Feedback Source: AI2)

10-03 = XXX1b( PID is enabled)

23-00 = 1 (Pump); 23-01 = 0 (Single Pump)

-

+

00-02=1(Control terminal);10-00=0(Keypad);10-01=2(AI2 PID feedback);10-03=XXX1b(PID mode);23-00=1(Pump). 04-00=0(AI2:0–10V); Single pump23-01=0. Multiple-pump illustrated assignments:Master23-01=1;Follower1=2;Follower2=3;Follower3=4. SW3=NPN;SW2=V. Four illustrated units are not evidence of a system maximum.

Blue RS485 network joins like S+ andS- terminals across illustrated drives. Red switch circuit usesS1 and24VG;24VG/GND common link is shown. Voltage pressure-converter terminals+,-,signal connect24V,GND,AI2 respectively. This is a figure transcription; consult original drawing for conductor routes and supplier installation requirements. Source terminal diagrams on this page labelF1/F2.

Manual — Standard H/C current-type pressure sensor, single/multiple pumps — page 40

 PUMP Wiring Diagram for Pressure Sensor of Current Type

Single Pump:

F510 Single Pump Operation

Operation Switch

Pressure

Converter

TM2

SW2

SW3

NPN

J

P

V

I

S(+)

S(-)

S1

S3

S5

AI2

E

24VG

S2

S4

S6

F1

F2

PO

P I

24V

+10V

MT

GND GND

AI1

AO2

R1A R1B

R1C

R2A

R2C

R3A

R3C

AO1

00-02=1 (Control Circuit Terminal)

04-00=1 (4mA~20mA); 10-00=0 (Target Source: Keypad)

10-01=2 (Feedback Source: AI2)

10-03=XXX1b (PID is enabled)

23-00=1(Pump); 23-01=0 (Single Pump)

Multi-Pump:

F510 Multi-Pump Operation: Master

F510 Multi-Pump Operation: Follower 1

F510 Multi-Pump Operation: Follower 2

F510 Multi-Pump Operation: Follower 3

Operation

Switch

CON2

A

B

24VG S2

24V +10V

R1A

R1B R1C

R3A R3C

MT GND GND

R1B

R1C R2A R2C

R1B R1C R2A

R2A R2C

00-02=1 (Control Circuit Terminal); 04-00=1 (4~20mA)

10-00=0 (Target Source: Keypad); 10-01=2 (Feedback Source: AI2)

10-03=XXX1b (PID is enabled); 23-00=1(Pump); 23-01=1 (Master)

00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V)

10-03=XXX1b (PID is enabled); 23-00=1(Pump); 23-01=2 (Follower 1)

10-03=XXX1b (PID is enabled); 23-00=1(Pump); 23-01=3 (Follower 2)

10-03=XXX1b (PID is enabled); 23-00=1(Pump); 23-01=4 (Follower 3)

Notes: 1. The position of dip switch requires being correct (SW2, SW3).

  1. It is required to reconnect after setting Master/ Slave.

  2. 24VG and GND require short circuit.

00-02=1(Control terminal);10-00=0(Keypad);10-01=2(AI2 PID feedback);10-03=XXX1b(PID mode);23-00=1(Pump). 04-00=1(AI2:4–20mA) for single pump and Master;multi-pump Followers1/2/3 print04-00=0(AI2:0–10V); Single pump23-01=0. Multiple-pump illustrated assignments:Master23-01=1;Follower1=2;Follower2=3;Follower3=4. SW3=NPN;SW2=I. Four illustrated units are not evidence of a system maximum.

Blue RS485 network joins like S+ andS- terminals across illustrated drives. Red switch circuit usesS1 and24VG;24VG/GND common link is shown. Two-wire current pressure converter uses24V andAI2;24VG/GND common link is shown. This is a figure transcription; consult original drawing for conductor routes and supplier installation requirements. Source terminal diagrams on this page labelF1/F2.

Manual — Standard H/C multiple-pump notes continued — page 41

  1. When the communication modes is selected to be multiple pumps in parallel connection (09-

01=3), the baud rate settings (09-02) of Master and Slave are required to be consistent. Refer

to parameter 23-31 for the actions in parallel connection modes.

  1. In the wiring of multi-pump current type pressure sensor, it is required to adjust Slave to be

04-07(AI2 Gain) =252.0% and 04-08(AI1 Bias) =25.0%.

  1. In multi-pump operation, if one of the inverter does not Power ON, the 24V of connection is

also need to dis-connect to avoid magnetoresistance effect.

Manual — Enhanced E/G voltage-type pressure sensor, single/multiple pumps — page 42

3.3.4.2 Single/ Multi- Pump Dedicated Wiring Diagram (For Enhanced E & G type)

 PUMP Wiring Diagram for Pressure Sensor of Voltage Type

Single Pump:

Multi-Pump: (For Enhanced type)

00-02=1(Control terminal);10-00=0(Keypad);10-01=2(AI2 PID feedback);10-03=XXX1b(PID mode);23-00=1(Pump). 04-00=0(AI2:0–10V); Single pump23-01=0. Multiple-pump illustrated assignments:Master23-01=1;Follower1=2;Follower2=3;Follower3=4. SW6=NPN;SW4=V. Four illustrated units are not evidence of a system maximum.

Blue RS485 network joins like S+ andS- terminals across illustrated drives. Red switch circuit usesS1 and24VG;24VG/GND common link is shown. Voltage pressure-converter terminals+,-,signal connect24V,GND,AI2 respectively. This is a figure transcription; consult original drawing for conductor routes and supplier installation requirements. Source terminal diagrams on this page labelF1/F2.

Manual — Enhanced E/G current-type pressure sensor, single/multiple pumps — page 43

 PUMP Wiring Diagram for Pressure Sensor of Current Type

Single Pump: (For Enhanced type)

F510 Single Pump Operation

Operation Switch

Pressure

Converter

TM2

SW2

SW3

NPN

J

P

V

I

S(+)

S(-)

S1

S3

S5

AI2

E

24VG

S2

S4

S6

F1

F2

PO

P I

24V

+10V

MT

GND GND

AI1

AO2

R1A R1B

R1C

R2A

R2C

R3A

R3C

AO1

00-02=1 (Control Circuit Terminal)

04-00=1 (4mA~20mA); 10-00=0 (Target Source: Keypad)

10-01=2 (Feedback Source: AI2)

10-03=XXX1b (PID is enabled)

23-00=1(Pump); 23-01=0 (Single Pump)

Multi-Pump: (For Enhanced type)

Notes: 1. The position of dip switch requires being correct (SW6, SW4).

  1. It is required to reconnect after setting Master/ Slave.

00-02=1(Control terminal);10-00=0(Keypad);10-01=2(AI2 PID feedback);10-03=XXX1b(PID mode);23-00=1(Pump). 04-00=1(AI2:4–20mA) for single pump and Master;multi-pump Followers1/2/3 print04-00=0(AI2:0–10V); Single pump23-01=0. Multiple-pump illustrated assignments:Master23-01=1;Follower1=2;Follower2=3;Follower3=4. drawingSW3=NPN;SW2=I;noteSW6/SW4. Four illustrated units are not evidence of a system maximum.

Blue RS485 network joins like S+ andS- terminals across illustrated drives. Red switch circuit usesS1 and24VG;24VG/GND common link is shown. Two-wire current pressure converter uses24V andAI2;24VG/GND common link is shown. This is a figure transcription; consult original drawing for conductor routes and supplier installation requirements. Source terminal diagrams on this page labelF1/F2.

Manual — Enhanced E/G multiple-pump notes continued — page 44

  1. 24VG and GND require short circuit.

  2. When the communication modes is selected to be multiple pumps in parallel connection (09-

01=3), the baud rate settings (09-02) of Master and Slave are required to be consistent. Refer

to parameter 23-31 for the actions in parallel connection modes.

  1. In the wiring of multi-pump current type pressure sensor, it is required to adjust Slave to be

04-07(AI2 Gain) =252.0% and 04-08(AI1 Bias) =25.0%.

  1. In multi-pump operation, if one of the inverter does not Power ON, the 24V of connection is

also need to dis-connect to avoid magnetoresistance effect.

Manual — Standard H/C control-terminal physical layout by model group — page 45

3.3.5 Wiring for Control Circuit Terminals

3.3.5.1 Wiring for Control Circuit Terminals (For Standard H & C type)

Control circuit terminals identification

 IP00/IP20 type

200V: 1-3HP,400V: 1-3HP

200V: 5HP~50HP,400V: 5HP~75HP

AI2

S(+)

S(-)

S1

S3

S5

24V

+10V

MT

GND

AI1

AO1

AO2

E

R1A

R1B

R1C

24VG

S2

S4

S6

F1

F2

PO

P I

R2A

R2C

R3A

R3C

 200V: 60HP~125HP,400V: 100HP~800HP

 IP55 type

400V: 1HP~100HP

R2A R2C

R3A R3C

R1A R1B R1C

S(+) S(-)

MT GND GND AI1

24VG S2

PI

AO1 AO2

Top control row readsS(+),S(-),S1,S3,S5,24V,+10V,MT,GND,GND,AI1,AI2. Bottom row readsE,24VG,S2,S4,S6,F1,F2,PO,PI,AO1,AO2,E. IP00/IP20 layouts separate200V1–3HP/400V1–3HP,200V5–50HP/400V5–75HP,and200V60–125HP/400V100–800HP;IP55 layout400V1–100HP. Relay groupsR1A/R1B/R1C,R2A/R2C,R3A/R3C have different physical positions between illustrations; consult image, not text order, for location.

Manual — Standard H/C control-terminal descriptions Table3 — page 46

Table 3.3.5.1 Description of control circuit terminals

Standard H/C control-terminal descriptions Table3.3.5.1. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating.

Standard H/C control-terminal descriptions Table3.3.5.1. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: Digital

input

signal

Standard H/C control-terminal descriptions Table3.3.5.1. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 24V

Power

supply

Standard H/C control-terminal descriptions Table3.3.5.1. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: Analog

output

Standard H/C control-terminal descriptions Table3.3.5.1. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: Pulse

Shared source cells (coordinates refer to this table):

Standard H/C control-terminal descriptions Table3.3.5.1 table1 — PDF page 46

Source row Type Terminal Terminal function Signal level/ information
1 Digital input signal S1 2-wire forward rotation/ stop command (default), multi- function input terminals * 1 Signal Level 24 VDC (opto-isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ
2 ⟦null: no independent source value⟧ S2 2-wire reversal rotation/ stop command (default), multi- function input terminals * 1 ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ S3 Multi-speed/ position setting command 1 (default), multi- function input terminals * 1 ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ S4 Multi-speed/ position setting command 2 (default), multi- function input terminals * 1 ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ S5 Multi-speed/ position setting command 3 (default), multi- function input terminal* 1 ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ S6 Fault reset (default), multi-function input terminal * 1 ⟦null: no independent source value⟧
7 24V Power supply 24V Digital signal SOURCE point (SW3 switched to SOURCE ) ±15%, Max. output current: 250mA (The sum of all loads connected)
8 ⟦null: no independent source value⟧ 24VG Common terminal of Digital signals Common point of digital signal SINK ( SW3 switched to SINK ) ⟦null: no independent source value⟧
9 Analog input signal +10V Power for external speed potentiometer ±5% (Max. current: 20mA )
10 ⟦null: no independent source value⟧ MT Motor temperature detector of externally connecting PTC Refer to group 08 setting
11 ⟦null: no independent source value⟧ AI1 Multi-function analog input for speed reference (0-10V input) From 0 to +10V Input impedance: 10KΩ Resolution: 12bit
12 ⟦null: no independent source value⟧ AI2 Multi-function analog input terminals *2, can use SW2 to switch voltage or current input (0~10V)/(4-20mA) From 0 to +10V Input impedance: 200KΩ From 4 to 20 mA Input impedance: 250Ω Resolution: 12bit
13 ⟦null: no independent source value⟧ GND Analog signal ground terminal ----
14 ⟦null: no independent source value⟧ E Shielding wire’s connecting terminal (Ground) ----
15 Analog output signal AO1 Multi-function analog output terminals *3 (0~10V/ 4-20mA output) From 0 to 10V Max. current: 2mA From 4 to 20 mA
16 ⟦null: no independent source value⟧ AO2 Multi-function analog output terminals *3 (0~10V/ 4-20mA output) ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ GND Analog signals ground terminal ⟦null: no independent source value⟧
18 Pulse output signal PO Pulse output, Band width 32KHz Max. Frequency: 32KHz Open Collector output Load: 2.2 KΩ
19 ⟦null: no independent source value⟧ GND Analog signals ground terminal ----
20 Pulse input signal PI Pulse command input, frequency width of 32KHz L: from 0.0 to 0.5V H: from 4.0 to 13.2V Max. Frequency: 0 - 32KHz Impedance: 3.89 KΩ
21 ⟦null: no independent source value⟧ GND Analog signals ground terminal ----

Manual — Standard H/C Table3 — page 47

Table 3.3.5.1 Description of control circuit terminals (Continued)

Notes:

*1: Multi-function digital input can be referred to in this manual.

*2: Multi-function analog input can be referred to in this manual.

*3: Multi-function analog output can be referred to in this manual.

Caution

 Maximum output current capacity for terminal 10V is 20mA.

 Multi-function analog output AO1 and AO2 are for use for an analog output meter. Do not

use these output for feedback control.

 Control board’s 24V and 10V are to be used for internal control only. Do not use the

internal power-supply to power external devices.

Standard H/C Table3.3.5.1 continued and cautions. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating.

Standard H/C Table3.3.5.1 continued and cautions. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: Relay

output

Standard H/C Table3.3.5.1 continued and cautions. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: Safety input

Standard H/C Table3.3.5.1 continued and cautions. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: RS-485

port

Standard H/C Table3.3.5.1 continued and cautions. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: Grounding

Shared source cells (coordinates refer to this table):

Standard H/C Table3.3.5.1 continued and cautions table1 — PDF page 47

Source row Type Terminal Terminal function Signal level/ information
1 Relay output R1A- R1B- R1C Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) Relay contact common terminal, please refer to parameter group 03 in this manual for more functional descriptions. Rating: 250Vac: 10 mA ~ 1A 30Vdc: 10 mA ~ 1A
2 ⟦null: no independent source value⟧ R2A-R2C With the same functions as R1A/R1B/R1C Rating: 250Vac: 10 mA ~ 1A 30Vdc: 10 mA ~ 1A
3 ⟦null: no independent source value⟧ R3A-R3C With the same functions as R1A/R1B/R1C ⟦null: no independent source value⟧
4 Safety input F1 On: normal operation. Off: emergency stop. (Jumper wired has to be removed to use external safety function to stop.) 24Vdc, 8mA, pull-high
5 ⟦null: no independent source value⟧ F2 Safety command common terminal 24V Ground
6 RS-485 port S (+) RS485/MODBUS differential input and output
7 ⟦null: no independent source value⟧ S (-) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 Grounding E (G) Grounding to earth Shield the connecting terminal ----

Manual — Enhanced E/G control-terminal physical layout by model group — page 48

3.3.5.2 Wiring for Control Circuit Terminals (For Enhanced E & G type)

Control circuit terminals identification

IP00/IP20 type

200V: 1-3HP,400V: 1-3HP

200V: 5HP~50HP,400V: 5HP~75HP

 200V: 60HP~125HP,400V: 125HP~800HP

GND AI1

AI2

E

24VG

S2

S4

S6

SF1

SG

SF2

PO

PI

AO1 AO2

S(+)

S(-)

S1

S3

S5

24V +10V MT GND

R1A R1B R1C R2A R2C R3A R3C

RJ45

GND GND AI1

24V +10V MT

R1A R1B R1C

R2A R2C R3A R3C

24V +10V MT GND GND AI1

Top row:S(+),S(-),S1,S3,S5,24V,+10V,MT,GND,GND,AI1,AI2. Bottom row:E,24VG,S2,S4,S6,SF1,SG,SF2,PO,PI,AO1,AO2. Groups:200V1–3HP/400V1–3HP;200V5–50HP/400V5–75HP;200V60–125HP/400V125–800HP. Relay groupsR1A/R1B/R1C,R2A/R2C,R3A/R3C andRJ45 have figure-specific positions. No finalEterminal inferred at right end.

Manual — Enhanced E/G control-terminal descriptions Table3 — page 49

Table 3.3.5.2 Description of control circuit terminals

Enhanced E/G control-terminal descriptions Table3.3.5.2. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating.

Enhanced E/G control-terminal descriptions Table3.3.5.2. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: Digital

input

signal

Enhanced E/G control-terminal descriptions Table3.3.5.2. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 24V

Power

supply

Enhanced E/G control-terminal descriptions Table3.3.5.2. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: Analog

output

Enhanced E/G control-terminal descriptions Table3.3.5.2. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: Pulse

Shared source cells (coordinates refer to this table):

Enhanced E/G control-terminal descriptions Table3.3.5.2 table1 — PDF page 49

Source row Type Terminal Terminal function Signal level/ information
1 Digital input signal S1 2-wire forward rotation/ stop command (default), multi- function input terminals * 1 Signal Level 24 VDC (opto-isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ
2 ⟦null: no independent source value⟧ S2 2-wire reversal rotation/ stop command (default), multi- function input terminals * 1 ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ S3 Multi-speed/ position setting command 1 (default), multi- function input terminals * 1 ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ S4 Multi-speed/ position setting command 2 (default), multi- function input terminals * 1 ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ S5 Multi-speed/ position setting command 3 (default), multi- function input terminal* 1 ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ S6 Fault reset (default), multi-function input terminal * 1 ⟦null: no independent source value⟧
7 24V Power supply 24V Digital signal SOURCE point (SW6 switched to SOURCE ) ±15%, Max. output current: 250mA (The sum of all loads connected)
8 ⟦null: no independent source value⟧ 24VG Common terminal of Digital signals Common point of digital signal SINK ( SW6 switched to SINK ) ⟦null: no independent source value⟧
9 Analog input signal +10V Power for external speed potentiometer ±5% (Max. current: 20mA )
10 ⟦null: no independent source value⟧ MT Motor temperature detector of externally connecting PTC Refer to group 08 setting
11 ⟦null: no independent source value⟧ AI1 Multi-function analog input for speed reference, use SW3 to switch voltage and current input (0~10V) / (4-20mA) From 0 to +10V Input impedance: 500KΩ From 4 to 20 mA Input impedance: 500KΩ Resolution: 12bit
12 ⟦null: no independent source value⟧ AI2 Multi-function analog input terminals *2, can use SW4 to switch voltage or current input (0~10V)/(4-20mA) From 0 to +10V Input impedance: 900KΩ From 4 to 20 mA Input impedance: 250Ω Resolution: 12bit
13 ⟦null: no independent source value⟧ GND Analog signal ground terminal ----
14 ⟦null: no independent source value⟧ E Shielding wire’s connecting terminal (Ground) ----
15 Analog output signal AO1 Multi-function analog output terminals *3, use SW1 to switch voltage and current output (0~10V) / (4-20mA) From 0 to 10V Max. current: 2mA From 4 to 20 mA
16 ⟦null: no independent source value⟧ AO2 Multi-function analog output terminals *3, use SW2 to switch voltage and current output (0~10V) / (4-20mA) ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ GND Analog signals ground terminal ⟦null: no independent source value⟧
18 Pulse output signal PO Pulse output, Band width 32KHz Max. Frequency: 32KHz Open Collector output Load: 2.2 KΩ
19 ⟦null: no independent source value⟧ GND Analog signals ground terminal ----
20 Pulse input signal PI Pulse command input, frequency width of 32KHz L: from 0.0 to 0.5V H: from 4.0 to 13.2V Max. Frequency: 0 - 32KHz Impedance: 3.89 KΩ
21 ⟦null: no independent source value⟧ GND Analog signals ground terminal ----

Manual — Enhanced E/G Table3 — page 50

Table 3.3.5.2 Description of control circuit terminals (Continued)

Notes:

*1: Multi-function digital input can be referred to in this manual.

*2: Multi-function analog input can be referred to in this manual.

*3: Multi-function analog output can be referred to in this manual.

Caution

 Maximum output current capacity for terminal 10V is 20mA.

 Multi-function analog output AO1 and AO2 are for use for an analog output meter. Do not

use these output for feedback control.

 Control board’s 24V and 10V are to be used for internal control only. Do not use the

internal power-supply to power external devices.

Enhanced E/G Table3.3.5.2 continued and cautions. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating.

Enhanced E/G Table3.3.5.2 continued and cautions. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: Relay

output

Enhanced E/G Table3.3.5.2 continued and cautions. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: Safety input

Enhanced E/G Table3.3.5.2 continued and cautions. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: RS-485

port

Enhanced E/G Table3.3.5.2 continued and cautions. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: Grounding

Shared source cells (coordinates refer to this table):

Adjacent source context — repeated to preserve continuation:

Enhanced E/G Table3.3.5.2 continued and cautions table1 — PDF page 50

Source row Type Terminal Terminal function Signal level/ information
1 Relay output R1A- R1B- R1C Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) Relay contact common terminal, please refer to parameter group 03 in this manual for more functional descriptions. Rating: 250Vac: 10 mA ~ 1A 30Vdc: 10 mA ~ 1A
2 ⟦null: no independent source value⟧ R2A-R2C With the same functions as R1A/R1B/R1C Rating: 250Vac: 10 mA ~ 1A 30Vdc: 10 mA ~ 1A
3 ⟦null: no independent source value⟧ R3A-R3C With the same functions as R1A/R1B/R1C ⟦null: no independent source value⟧
4 Safety input F1 On: normal operation. Off: emergency stop. (Jumper wired has to be removed to use external safety function to stop.) 24Vdc, 8mA, pull-high
5 ⟦null: no independent source value⟧ F2 Safety command common terminal 24V Ground
6 RS-485 port S (+) RS485/MODBUS differential input and output
7 ⟦null: no independent source value⟧ S (-) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 Grounding E (G) Grounding to earth Shield the connecting terminal ----

Manual — Standard H/C main terminals IP00/IP20 andIP55 — page 51

3.3.6 Wiring for Main Circuit Terminals

3.3.6.1 Wiring for Main Circuit Terminals (For Standard H & C type)

Table 3.3.6.1.1 Description of main circuit terminals (IP00/IP20 Type)

Table 3.3.6.1.2 Description of main circuit terminals (IP55 Type)

*1. The model of 400V 25HP (18.5KW) or below is built-in braking transistor.

*2. Before connecting DC reactor, please remove short circuit between terminal ⊕1 and ⊕2.

IP00/IP20 smaller group200V1–30HP/400V1–40HP hasB1/P–B2 braking-resistor terminals;larger group200V40–175HP/400V50–800HP uses⊕–⊖ for braking module. InputR/L1,S/L2,T/L3 and outputU/T1,V/T2,W/T3 retain grouped/merged table cells. E is grounding. IP55 table400V1–100HP includesR/L1,S/L2,T/L3 input,U/T1,V/T2,W/T3 output,B1/B2 brake resistor 1,⊕1/⊕2 DC reactor 2,B1/B2/⊖ DC power/braking-module connections,earth symbol(PE)ground. 1 Built-in braking transistor400V25HP(18.5kW)or below. 2 Remove⊕1–⊕2 short before connecting DC reactor. Merged cells and dashes remain explicit in table evidence; no unprinted polarity assignment inferred.

Standard H/C main terminals IP00/IP20 andIP55. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating.

Standard H/C main terminals IP00/IP20 andIP55. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: R/L1

Standard H/C main terminals IP00/IP20 andIP55. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: S/L2

Standard H/C main terminals IP00/IP20 andIP55. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: T/L3

Standard H/C main terminals IP00/IP20 andIP55. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: B1/P

Standard H/C main terminals IP00/IP20 andIP55. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: B2

Standard H/C main terminals IP00/IP20 andIP55. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 

Standard H/C main terminals IP00/IP20 andIP55. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: 

Standard H/C main terminals IP00/IP20 andIP55. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: U/T1

Standard H/C main terminals IP00/IP20 andIP55. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: V/T2

Standard H/C main terminals IP00/IP20 andIP55. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: W/T3

Standard H/C main terminals IP00/IP20 andIP55. Exact row groups and merged headers govern applicability. Preserve all printed ratings,units,blanks,dashes and supplier discrepancies; no calculated or corrected rating. Row group: E

Shared source cells (coordinates refer to this table):

Standard H/C main terminals IP00/IP20 andIP55. IP55 Table3.3.6.1.2 only;built-in braking transistor limited by footnote to400V25HP(18.5kW)or below;remove short between⊕1and⊕2 before DC reactor.

Standard H/C main terminals IP00/IP20 andIP55. IP55 Table3.3.6.1.2 only;built-in braking transistor limited by footnote to400V25HP(18.5kW)or below;remove short between⊕1and⊕2 before DC reactor. Row group: R/L1,S/L2, T/L3

Standard H/C main terminals IP00/IP20 andIP55. IP55 Table3.3.6.1.2 only;built-in braking transistor limited by footnote to400V25HP(18.5kW)or below;remove short between⊕1and⊕2 before DC reactor. Row group: U/T1,V/T2, W/T3

Standard H/C main terminals IP00/IP20 andIP55. IP55 Table3.3.6.1.2 only;built-in braking transistor limited by footnote to400V25HP(18.5kW)or below;remove short between⊕1and⊕2 before DC reactor. Row group: B1, B2

Standard H/C main terminals IP00/IP20 andIP55. IP55 Table3.3.6.1.2 only;built-in braking transistor limited by footnote to400V25HP(18.5kW)or below;remove short between⊕1and⊕2 before DC reactor. Row group: ⊕1, ⊕2

Standard H/C main terminals IP00/IP20 andIP55. IP55 Table3.3.6.1.2 only;built-in braking transistor limited by footnote to400V25HP(18.5kW)or below;remove short between⊕1and⊕2 before DC reactor. Row group: B1, B2, 

Standard H/C main terminals IP00/IP20 andIP55. IP55 Table3.3.6.1.2 only;built-in braking transistor limited by footnote to400V25HP(18.5kW)or below;remove short between⊕1and⊕2 before DC reactor. Row group: ( PE)

Adjacent source context — repeated to preserve continuation:

Standard H/C main terminals IP00/IP20 andIP55 table1 — PDF page 51

Source row Terminal 200V : 1~30HP 400V : 1~40HP 200V : 40~175HP 400V : 50~800HP
1 R/L1 Input Power Supply ⟦null: no independent source value⟧
2 S/L2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 T/L3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 B1/P  B1/P-B2:External braking resistor -
5 B2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧   -:Connect braking module
7 - ⟦null: no independent source value⟧
8 U/T1 Inverter output ⟦null: no independent source value⟧
9 V/T2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 W/T3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 E Ground terminal ⟦null: no independent source value⟧

Standard H/C main terminals IP00/IP20 andIP55 table2 — PDF page 51

Source row Terminal 400V:1–100HP
1 R/L1,S/L2, T/L3 Input Power Supply
2 U/T1,V/T2, W/T3 Inverter output
3 B1, B2 Braking resistor connecting terminal *1
4 ⊕1, ⊕2 DC reactor connecting terminal*2
5 B1, B2,  DC power supply (DC+, DC-) Braking module connecting terminal
6 ( PE) Ground terminal

Manual — Standard H/C IP20 terminal identification:200V1–15HP/400V1–20HP — page 52

Main circuit terminals identification and screw size

 IP20 Type

˙200V : 1-3HP/ 400V: 1-3HP

˙200V: 5-7.5HP/ 400V: 5-10HP

˙200V: 10-15HP/ 400V: 15- 20HP

T

1–3HP200V/400V:strip labelsR/L1,S/L2,T/L3,B1/P,⊖,B2,U/T1,V/T2,W/T3;T and protective-earth screwsM4.200V5–7.5HP/400V5–10HP:Power InR/L1,S/L2,T/L3;⊖;Dynamic BrakeB1/P,B2;To MotorU/T1,V/T2,W/T3;CHARGE indicator. TheW/T3 label is drawn beneath the circular indicator region; consult figure for physical location.200V10–15HP/400V15–20HP addsE/earth at both ends and retains these named groups;allT/earth screwsM4. No torque inferred.

Standard H/C IP20 terminal identification:200V1–15HP/400V1–20HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V1–3HP/400V1–3HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C IP20 terminal identification:200V1–15HP/400V1–20HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V1–3HP/400V1–3HP. T/T1/T2 are figure callouts,not screw torque. Row group: M4

Standard H/C IP20 terminal identification:200V1–15HP/400V1–20HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V5–7.5HP/400V5–10HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C IP20 terminal identification:200V1–15HP/400V1–20HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V5–7.5HP/400V5–10HP. T/T1/T2 are figure callouts,not screw torque. Row group: M4

Standard H/C IP20 terminal identification:200V1–15HP/400V1–20HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V10–15HP/400V15–20HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C IP20 terminal identification:200V1–15HP/400V1–20HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V10–15HP/400V15–20HP. T/T1/T2 are figure callouts,not screw torque. Row group: M4

Standard H/C IP20 terminal identification:200V1–15HP/400V1–20HP table1 — PDF page 52

Source row T Protective earth symbol
1 M4 M4

Manual — Standard H/C terminal identification:200V20–125HP/400V25–250HP — page 53

˙200V: 20-30HP/ 400V: 25-40HP

˙200V: 40-50HP/ 400V: 50-75HP

˙200V: 60-75HP/ 400V: 100-125HP

˙200V: 100-125HP/ 400V: 150-250HP

T

200V20–30HP/400V25–40HP: R/L1,S/L2,T/L3,⊖,B1/P,B2,U/T1,V/T2,W/T3;screwsT/earthM6/M6.200V40–50HP/400V50–75HP: R/L1,S/L2,T/L3,⊖,⊕,U/T1,V/T2,W/T3;M8/M8.200V60–75HP/400V100–125HP same labels;400V100HP T/earthM8/M10;200V60–75HP and400V125HP M10/M10.200V100–125HP/400V150–250HP lugsP,N,R,S,T,U,V,W;M10/M10.

Standard H/C terminal identification:200V20–125HP/400V25–250HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V20–30HP/400V25–40HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C terminal identification:200V20–125HP/400V25–250HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V20–30HP/400V25–40HP. T/T1/T2 are figure callouts,not screw torque. Row group: M6

Standard H/C terminal identification:200V20–125HP/400V25–250HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V40–50HP/400V50–75HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C terminal identification:200V20–125HP/400V25–250HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V40–50HP/400V50–75HP. T/T1/T2 are figure callouts,not screw torque. Row group: M8

Standard H/C terminal identification:200V20–125HP/400V25–250HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V60–75HP/400V100–125HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C terminal identification:200V20–125HP/400V25–250HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V60–75HP/400V100–125HP. T/T1/T2 are figure callouts,not screw torque. Row group: 400V 100HP

Standard H/C terminal identification:200V20–125HP/400V25–250HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V60–75HP/400V100–125HP. T/T1/T2 are figure callouts,not screw torque. Row group: 200V 60-75HP/

400V 125HP

Standard H/C terminal identification:200V20–125HP/400V25–250HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V100–125HP/400V150–250HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C terminal identification:200V20–125HP/400V25–250HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V100–125HP/400V150–250HP. T/T1/T2 are figure callouts,not screw torque. Row group: M10

Standard H/C terminal identification:200V20–125HP/400V25–250HP table1 — PDF page 53

Source row T Protective earth symbol
1 M6 M6

Standard H/C terminal identification:200V20–125HP/400V25–250HP table2 — PDF page 53

Source row T Protective earth symbol
1 M8 M8

Standard H/C terminal identification:200V20–125HP/400V25–250HP table3 — PDF page 53

Source row Power supply T Protective earth symbol
1 400V 100HP M8 M10
2 200V 60-75HP/ 400V 125HP M10 M10

Standard H/C terminal identification:200V20–125HP/400V25–250HP table4 — PDF page 53

Source row T Protective earth symbol
1 M10 M10

Manual — Standard H/C large IP00/IP20 terminals and IP55 small terminals — page 54

˙200V: 150-175HP/ 400V: 300-425HP

˙400V: 535-800HP

Note: For 400V 535~800HP, the terminal separate to two, to share the current.

IP55 Type

˙400V: 1-7.5HP

˙400V: 10-15HP

200V150–175HP/400V300–425HP:P,N,R,S,T,U,V,W lugs;screwsT M12,earthM10.400V535–800HP:top paired groupsN,N;DCL⊖,DCL⊖;U,U;V,V;W,W;bottomP,P;DCL⊕,DCL⊕;R,R;S,S;T,T. Supplier states terminals are separated into two to share current;screwsT/earthM10/M10. IP55 400V1–7.5HP and10–15HP strips:earth,R/L1,S/L2,T/L3,⊖,⊕1,⊕2,B1,B2,U/T1,V/T2,W/T3,earth;T/earthM4/M4.

Standard H/C large IP00/IP20 terminals and IP55 small terminals. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP00/IP20:200V150–175HP/400V300–425HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C large IP00/IP20 terminals and IP55 small terminals. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP00/IP20:200V150–175HP/400V300–425HP. T/T1/T2 are figure callouts,not screw torque. Row group: M12

Standard H/C large IP00/IP20 terminals and IP55 small terminals. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP00/IP20:400V535–800HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C large IP00/IP20 terminals and IP55 small terminals. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP00/IP20:400V535–800HP. T/T1/T2 are figure callouts,not screw torque. Row group: M10

Standard H/C large IP00/IP20 terminals and IP55 small terminals. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP55:400V1–7.5HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C large IP00/IP20 terminals and IP55 small terminals. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP55:400V1–7.5HP. T/T1/T2 are figure callouts,not screw torque. Row group: M4

Standard H/C large IP00/IP20 terminals and IP55 small terminals. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP55:400V10–15HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C large IP00/IP20 terminals and IP55 small terminals. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP55:400V10–15HP. T/T1/T2 are figure callouts,not screw torque. Row group: M4

Standard H/C large IP00/IP20 terminals and IP55 small terminals table1 — PDF page 54

Source row T Protective earth symbol
1 M12 M10

Standard H/C large IP00/IP20 terminals and IP55 small terminals table2 — PDF page 54

Source row T Protective earth symbol
1 M10 M10

Standard H/C large IP00/IP20 terminals and IP55 small terminals table3 — PDF page 54

Source row T Protective earth symbol
1 M4 M4

Manual — Standard H/C IP55 terminals400V20–100HP — page 55

˙400V: 20-25HP

˙400V: 30-50HP

˙400V: 60-75HP

˙400V : 100HP

400V20–25HP strip:earth,R/L1,S/L2,T/L3,⊖,⊕1,⊕2,B1,B2,U/T1,V/T2,W/T3,earth;screwsT/earthM6/M6.400V30–50HP and60–75HP main rows:R/L1,S/L2,T/L3,⊖,⊕1,⊕2,U/T1,V/T2,W/T3;two separate protective-earth screws below.30–50HP T1/earthM6/M6;60–75HP M8/M8.400V100HP same labels:T1 brackets inputR/L1–T/L3 andoutputU/T1–W/T3,T2brackets⊖,⊕1,⊕2;sizesT1M8,T2M10,earthM8.

Standard H/C IP55 terminals400V20–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP55:400V20–25HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C IP55 terminals400V20–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP55:400V20–25HP. T/T1/T2 are figure callouts,not screw torque. Row group: M6

Standard H/C IP55 terminals400V20–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP55:400V30–50HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C IP55 terminals400V20–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP55:400V30–50HP. T/T1/T2 are figure callouts,not screw torque. Row group: M6

Standard H/C IP55 terminals400V20–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP55:400V60–75HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C IP55 terminals400V20–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP55:400V60–75HP. T/T1/T2 are figure callouts,not screw torque. Row group: M8

Standard H/C IP55 terminals400V20–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP55:400V100HP. T/T1/T2 are figure callouts,not screw torque.

Standard H/C IP55 terminals400V20–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:IP55:400V100HP. T/T1/T2 are figure callouts,not screw torque. Row group: M8

Standard H/C IP55 terminals400V20–100HP table1 — PDF page 55

Source row T Protective earth symbol
1 M6 M6

Standard H/C IP55 terminals400V20–100HP table2 — PDF page 55

Source row T1 Protective earth symbol
1 M6 M6

Standard H/C IP55 terminals400V20–100HP table3 — PDF page 55

Source row T1 Protective earth symbol
1 M8 M8

Standard H/C IP55 terminals400V20–100HP table4 — PDF page 55

Source row T1 T2 Protective earth symbol
1 M8 M10 M8

Manual — Enhanced E/G IP00/IP20 main terminal description — page 56

3.3.6.2 Wiring for Main Circuit Terminals (For Enhanced E & G type)

Table 3.3.6.2.1 Description of main circuit terminals (IP00/IP20 Type)

Table usesB1/P2 and⊕/P1 terminal labels;small group200V1–30HP/400V1–40HP describes external resistorB1/P–B2 andexternalDCL⊕/P1–B1/P2;largegroup200V40–175HP/400V50–800HP describes⊕–⊖braking module. InputR/L1,S/L2,T/L3;outputU/T1,V/T2,W/T3;Eground. Preserve merged spans and printed dash separately.

Enhanced E/G IP00/IP20 main terminal description. Exact source units/model/enclosure and qualifiers govern applicability; source claims only.

Enhanced E/G IP00/IP20 main terminal description. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: R/L1

Enhanced E/G IP00/IP20 main terminal description. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: S/L2

Enhanced E/G IP00/IP20 main terminal description. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: T/L3

Enhanced E/G IP00/IP20 main terminal description. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: B1/P2

Enhanced E/G IP00/IP20 main terminal description. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: B2

Enhanced E/G IP00/IP20 main terminal description. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: 

Enhanced E/G IP00/IP20 main terminal description. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: /P1

Enhanced E/G IP00/IP20 main terminal description. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: U/T1

Enhanced E/G IP00/IP20 main terminal description. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: V/T2

Enhanced E/G IP00/IP20 main terminal description. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: W/T3

Enhanced E/G IP00/IP20 main terminal description. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: E

Shared source cells (coordinates refer to this table):

Enhanced E/G IP00/IP20 main terminal description table1 — PDF page 56

Source row Terminal 200V : 1~30HP 400V : 1~40HP 200V : 40~175HP 400V : 50~800HP
1 R/L1 Input Power Supply ⟦null: no independent source value⟧
2 S/L2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 T/L3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 B1/P2  B1/P-B2:External braking resistor -
5 B2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧   -:Connect braking module
7 /P1  /P1-B1/P2:External DCL ⟦null: no independent source value⟧
8 U/T1 Inverter output ⟦null: no independent source value⟧
9 V/T2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 W/T3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 E Ground terminal ⟦null: no independent source value⟧

Manual — Enhanced E/G IP20 terminals200V1–30HP/400V1–40HP — page 57

Main circuit terminals identification and screw size (For Enhanced E & G

type)

 IP20 Type

˙200V : 1-3HP/ 400V: 1-3HP

˙200V: 5-15HP/ 400V: 5-25HP

˙200V: 20-30HP/ 400V: 30-40HP

T

200V/400V1–3HP:R/L1,S/L2,T/L3,B1/P,⊖,B2,U/T1,V/T2,W/T3;screwsT/earthM4/M4.200V5–15HP/400V5–25HP addsP1between⊖andB1/P2,withB2andU/T1,V/T2,W/T3;screwsM4/M4.200V20–30HP/400V30–40HP:R/L1,S/L2,T/L3,⊖,P1,B1/P2,B2,U/T1,V/T2,W/T3;screwsM6/M6. W/T3 label in middle illustration sits below circular indicator region as in standard illustration;physical geometry remains in source.

Enhanced E/G IP20 terminals200V1–30HP/400V1–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V1–3HP/400V1–3HP. T/T1/T2 are figure callouts,not screw torque.

Enhanced E/G IP20 terminals200V1–30HP/400V1–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V1–3HP/400V1–3HP. T/T1/T2 are figure callouts,not screw torque. Row group: M4

Enhanced E/G IP20 terminals200V1–30HP/400V1–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V5–15HP/400V5–25HP. T/T1/T2 are figure callouts,not screw torque.

Enhanced E/G IP20 terminals200V1–30HP/400V1–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V5–15HP/400V5–25HP. T/T1/T2 are figure callouts,not screw torque. Row group: M4

Enhanced E/G IP20 terminals200V1–30HP/400V1–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V20–30HP/400V30–40HP. T/T1/T2 are figure callouts,not screw torque.

Enhanced E/G IP20 terminals200V1–30HP/400V1–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V20–30HP/400V30–40HP. T/T1/T2 are figure callouts,not screw torque. Row group: M6

Enhanced E/G IP20 terminals200V1–30HP/400V1–40HP table1 — PDF page 57

Source row T Protective earth symbol
1 M4 M4

Enhanced E/G IP20 terminals200V1–30HP/400V1–40HP table3 — PDF page 57

Source row T Protective earth symbol
1 M6 M6

Manual — Enhanced E/G terminals200V40–175HP/400V50–425HP — page 58

˙200V: 40-50HP/ 400V: 50-75HP

˙200V: 60-75HP/ 400V: 100-125HP

˙200V: 100-125HP/ 400V: 150-250HP

˙200V: 150-175HP/ 400V: 300-425HP

T

200V40–50HP/400V50–75HP:R/L1,S/L2,T/L3,⊖,P1,P2,U/T1,V/T2,W/T3;screwsT/earthM8/M8.200V60–75HP/400V100–125HP:R/L1,S/L2,T/L3,⊖,⊕,U/T1,V/T2,W/T3;400V100HP M8/M10;200V60–75HP/400V125HP M10/M10.200V100–125HP/400V150–250HP:P,N,R,S,T,U,V,W lugs;M10/M10.200V150–175HP/400V300–425HP same named lugs;T M12,earthM10.

Enhanced E/G terminals200V40–175HP/400V50–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V40–50HP/400V50–75HP. T/T1/T2 are figure callouts,not screw torque.

Enhanced E/G terminals200V40–175HP/400V50–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V40–50HP/400V50–75HP. T/T1/T2 are figure callouts,not screw torque. Row group: M8

Enhanced E/G terminals200V40–175HP/400V50–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V60–75HP/400V100–125HP. T/T1/T2 are figure callouts,not screw torque.

Enhanced E/G terminals200V40–175HP/400V50–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V60–75HP/400V100–125HP. T/T1/T2 are figure callouts,not screw torque. Row group: 400V 100HP

Enhanced E/G terminals200V40–175HP/400V50–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V60–75HP/400V100–125HP. T/T1/T2 are figure callouts,not screw torque. Row group: 200V 60-75HP/

400V 125HP

Enhanced E/G terminals200V40–175HP/400V50–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V100–125HP/400V150–250HP. T/T1/T2 are figure callouts,not screw torque.

Enhanced E/G terminals200V40–175HP/400V50–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V100–125HP/400V150–250HP. T/T1/T2 are figure callouts,not screw torque. Row group: M10

Enhanced E/G terminals200V40–175HP/400V50–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V150–175HP/400V300–425HP. T/T1/T2 are figure callouts,not screw torque.

Enhanced E/G terminals200V40–175HP/400V50–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:200V150–175HP/400V300–425HP. T/T1/T2 are figure callouts,not screw torque. Row group: M12

Enhanced E/G terminals200V40–175HP/400V50–425HP table1 — PDF page 58

Source row T Protective earth symbol
1 M8 M8

Enhanced E/G terminals200V40–175HP/400V50–425HP table2 — PDF page 58

Source row Power supply T Protective earth symbol
1 400V 100HP M8 M10
2 200V 60-75HP/ 400V 125HP M10 M10

Enhanced E/G terminals200V40–175HP/400V50–425HP table3 — PDF page 58

Source row T Protective earth symbol
1 M10 M10

Enhanced E/G terminals200V40–175HP/400V50–425HP table4 — PDF page 58

Source row T Protective earth symbol
1 M12 M10

Manual — Enhanced E/G terminals400V535–800HP — page 59

˙400V: 535-800HP

Note: For 400V 535~800HP, the terminal separate to two, to share the current.

Paired terminal groups:topN/N,DCL⊖/DCL⊖,U/U,V/V,W/W;bottomP/P,DCL⊕/DCL⊕,R/R,S/S,T/T. Note states terminals separate into two to share current. T and protective-earth screw sizesM10. Keep original physical figure;do not infer conductor count or external reactor fitment from label alone.

Enhanced E/G terminals400V535–800HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:400V535–800HP. T/T1/T2 are figure callouts,not screw torque.

Enhanced E/G terminals400V535–800HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Figure group:400V535–800HP. T/T1/T2 are figure callouts,not screw torque. Row group: M10

Enhanced E/G terminals400V535–800HP table1 — PDF page 59

Source row T Protective earth symbol
1 M10 M10

Manual — Power-section reference diagrams IP00/IP20 groups1–6 — page 60

Input / Output Power Section Block Diagram

The following diagrams show the basic configuration of the power sections for the range of

horsepower and input voltages. This is shown for reference only and is not a detailed depiction.

(For Enhanced E & G type frame 2~5, which can connect option DC reactor, please refer to

General Wiring Diagram)

 IP00/IP20 Type

  1. IP20 200V: 1HP 400V: 1~2HP(Standard)

400V:1HP(Enhanced)

  1. IP20 200V: 2~30HP 400V: 3~40HP(Standard)

400V:2~40HP(Enhanced)

  1. IP20 200V: 40~50HP 400V: 50~75HP

  2. IP00/IP20 200V: 60~75HP 400V:

100~125HP

  1. IP00/IP20 200V: 100~125HP

  2. IP00/IP20 400V: 150~250HP

E

N

P

DCL

SPS

C/B

AC/DC

W/T3

R/L1

T/L3

S/L2

U/T1

V/T2

○

─

CONTROL

CIRCUITS

┼

B1/P

B2

Source diagram scoped to 1:IP20 200V1HP;400V1–2HP Standard,400V1HP Enhanced. InputR/L1,S/L2,T/L3;outputU/T1,V/T2,W/T3;Eearth. These are basic reference configurations,explicitly not detailed depictions. Retain illustrated SPS/control-board,DC bus,rectifier,capacitor,fan and reactor symbol relationships in the original figure;no inferred component ratings.

Source diagram scoped to 2:IP20 200V2–30HP;400V3–40HP Standard,400V2–40HP Enhanced. InputR/L1,S/L2,T/L3;outputU/T1,V/T2,W/T3;Eearth. These are basic reference configurations,explicitly not detailed depictions. Retain illustrated SPS/control-board,DC bus,rectifier,capacitor,fan and reactor symbol relationships in the original figure;no inferred component ratings.

Source diagram scoped to 3:IP20 200V40–50HP/400V50–75HP. InputR/L1,S/L2,T/L3;outputU/T1,V/T2,W/T3;Eearth. These are basic reference configurations,explicitly not detailed depictions. Retain illustrated SPS/control-board,DC bus,rectifier,capacitor,fan and reactor symbol relationships in the original figure;no inferred component ratings.

Source diagram scoped to 4:IP00/IP20 200V60–75HP/400V100–125HP. InputR/L1,S/L2,T/L3;outputU/T1,V/T2,W/T3;Eearth. These are basic reference configurations,explicitly not detailed depictions. Retain illustrated SPS/control-board,DC bus,rectifier,capacitor,fan and reactor symbol relationships in the original figure;no inferred component ratings.

Source diagram scoped to 5:IP00/IP20 200V100–125HP. InputR/L1,S/L2,T/L3;outputU/T1,V/T2,W/T3;Eearth. These are basic reference configurations,explicitly not detailed depictions. Retain illustrated SPS/control-board,DC bus,rectifier,capacitor,fan and reactor symbol relationships in the original figure;no inferred component ratings.

Source diagram scoped to 6:IP00/IP20 400V150–250HP. InputR/L1,S/L2,T/L3;outputU/T1,V/T2,W/T3;Eearth. These are basic reference configurations,explicitly not detailed depictions. Retain illustrated SPS/control-board,DC bus,rectifier,capacitor,fan and reactor symbol relationships in the original figure;no inferred component ratings.

Groups1/2 labelB1/P andB2 with braking transistor branch;group1showsSPS/control circuits without fan symbol,group2addsfan. Group3labels⊕/⊖andSPS/control circuits. Groups4–6labelDCL,P/N,SPS andC/B;group4hasadditionalSPS/fan branch;groups5/6showAC/DCfan block. EnhancedE/Gframe2–5 optionalDCreactor refers back to general wiring diagram,not an assertion that every drawing shows that option.

Manual — Power-section reference diagrams IP00/IP20 groups7–9 andIP55groups1–2 — page 61

  1. IP00/IP20 200V: 150~175HP

  2. IP00/IP20 400V: 300~425HP

  3. IP00/IP20 400V: 535~800HP

 IP55 Type

  1. IP55 400V: 1~15HP

  2. IP55 400V: 20~25HP

E

○

─

C/B

R/L1

S/L2

T/L3

U/T1

V/T2

W/T3

B1

SPS

B2

┼1

┼2

DCL

Filter

N

AC/DC

P

Source diagram scoped to 7:IP00/IP20 200V150–175HP. InputR/L1,S/L2,T/L3;outputU/T1,V/T2,W/T3;Eearth. These are basic reference configurations,explicitly not detailed depictions. Retain illustrated SPS/control-board,DC bus,rectifier,capacitor,fan and reactor symbol relationships in the original figure;no inferred component ratings.

Source diagram scoped to 8:IP00/IP20 400V300–425HP. InputR/L1,S/L2,T/L3;outputU/T1,V/T2,W/T3;Eearth. These are basic reference configurations,explicitly not detailed depictions. Retain illustrated SPS/control-board,DC bus,rectifier,capacitor,fan and reactor symbol relationships in the original figure;no inferred component ratings.

Source diagram scoped to 9:IP00/IP20 400V535–800HP. InputR/L1,S/L2,T/L3;outputU/T1,V/T2,W/T3;Eearth. These are basic reference configurations,explicitly not detailed depictions. Retain illustrated SPS/control-board,DC bus,rectifier,capacitor,fan and reactor symbol relationships in the original figure;no inferred component ratings.

Source diagram scoped to IP55group1:400V1–15HP. InputR/L1,S/L2,T/L3;outputU/T1,V/T2,W/T3;Eearth. These are basic reference configurations,explicitly not detailed depictions. Retain illustrated SPS/control-board,DC bus,rectifier,capacitor,fan and reactor symbol relationships in the original figure;no inferred component ratings.

Source diagram scoped to IP55group2:400V20–25HP. InputR/L1,S/L2,T/L3;outputU/T1,V/T2,W/T3;Eearth. These are basic reference configurations,explicitly not detailed depictions. Retain illustrated SPS/control-board,DC bus,rectifier,capacitor,fan and reactor symbol relationships in the original figure;no inferred component ratings.

Groups7/8showDCL andP/N,withSPS,C/B,AC/DCfan blocks. Group9has paired input/output terminal circles andP/N,noDCLlabel within its depicted power path. IP55groups1/2showFilter,DCL,⊕1,⊕2,⊖,B1,B2,SPS,C/B andfan. These graphic distinctions do not establish unshown component absence or compatibility.

Manual — IP55 power circuit diagram — page 62

Label inventory only. Circuit topology, symbols, connection geometry and electrical relationships remain in the original diagram; no installation instructions inferred. Right panel is blank.

Applicability is limited to this diagram caption, not the entire F510 range. Adjacent physical page 61 contains other distinct power circuits.

Literal labels and caption only. Circled plus/minus glyphs transcribed; no expanded acronyms or inferred ratings.

Printed circuit caption and labels — PDF page 62

Source row Source label/context Source value
1 Caption 3. IP55 400V: 30~100HP
2 DC-side terminal labels ⊕1; ⊕2; ⊖
3 Input terminal labels R/L1; S/L2; T/L3
4 Output terminal labels U/T1; V/T2; W/T3
5 Earth label E
6 Component labels DCL; Filter; SPS; C/B

Manual — 400V cooling-fan supply jumper selection — page 63

Cooling Fan Supply Voltage Selection (400V class)

The inverter input voltage range of the F510 400V class models ranges from 380 to 460Vac. In these

models the cooling fan is directly powered from the power supply. Inverter models F510-4150/ 4175/

4215/ 4250/ 4300/ 4375/ 4425/ 4535/ 4670/ 4800-H3 requires the user to select the correct jumper

position based on the inverter input voltage ("400V" is the default position for these models). Please

select the correct position according to the input voltage. If the voltage setting is too low, the cooling

fan will not provide adequate cooling for the inverter resulting in an over-heat error. If the input

voltage is greater than 460Vac, select the “460V” position.

(1) 400V: 150HP~250HP

(2) 400V:300HP~800HP

4KA69X613W01

DM1

25CN

36CN

32CN

31CN

33CN

34CN

35CN

FU1

220V

440V

S

R

TB3

+

26CN

TB4(220V)

380V

400/415

460V

SA4(220V)

TB2

JP1

JP2

JP3

JP4

4KA69X571W01

4P108C0010103 VER.04

Both boards showJP1=380V,JP2=400/415,JP3=440V,JP4=460V,with jumper-removal illustration.400V150–250HP boardlabels4KA69X571W01 and4P108C0010103VER.04;400V300–800HP board4KA69X613W01. Other visible labels:TB4(220V),DM1,26CN440V,25CN220V,36CN,32CN,31CN,33CN,34CN,35CN,FU1,SA4(220V),TB3,S,R;large boardalsoTB2. Preserve exact model list and400Vdefault position from surrounding prose;not independently endorsed voltage settings.

Manual — IP00/IP20 wiring instruments Table3 — page 64

Power Input Wire Size, NFB and MCB Part Numbers

The following table shows the recommended wire size, molded case circuit breakers and magnetic

contactors for each of the F510 models. It depends on the application whether or not to install a

circuit breaker. The NFB must be installed between the input power supply and the inverter input

(R/L1, S/L2, T/L3).

Note: When using a ground protection, make sure the current setting is above 200mA and trip delay time

is 0.1 sec of higher.

Table 3.3.6.3 Wiring Instrument for 200V/400V class (IP00/IP20 type)

IP00/IP20 wiring instruments Table3.3.6.3. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. IP00/IP20 only.

IP00/IP20 wiring instruments Table3.3.6.3. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. IP00/IP20 only. Row group: 200V

1 Ø/3Ø

3 Ø

IP00/IP20 wiring instruments Table3.3.6.3. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. IP00/IP20 only. Row group: 400V

Shared source cells (coordinates refer to this table):

IP00/IP20 wiring instruments Table3.3.6.3 table1 — PDF page 64

Source row Power supply Horse power(HP) Rated KVA Rated current(A) Main circuit(mm²)*1 GroundingE(G)(mm²) Control line(mm²)*2 NFB*3 MC*3
1 200V 1 Ø/3Ø 1HP 1.9 5 2~5.5 2~5.5 0.5~2 TO-50EC(15A) CU-11
2 ⟦null: no independent source value⟧ 2HP 2.9 7.5 2~5.5 3.5~5.5 0.5~2 TO-50EC(20A) CU-11
3 ⟦null: no independent source value⟧ 3HP 4.0 10.6 3.5~5.5 3.5~5.5 0.5~2 TO-50EC(30A) CU-11
4 200V 3 Ø 5HP 5.5 14.5 3.5~5.5 3.5~5.5 0.5~2 TO-50EC(30A) CU-16
5 ⟦null: no independent source value⟧ 7.5HP 8.0 22 5.5 5.5 0.5~2 TO-50EC(30A) CU-16
6 ⟦null: no independent source value⟧ 10HP 11.4 30 8 5.5~8 0.5~2 TO-100EC(50A) CU-18
7 ⟦null: no independent source value⟧ 15HP 15 42 8 5.5~8 0.5~2 TO-100EC(50A) CU-27
8 ⟦null: no independent source value⟧ 20HP 21 56 14 8 0.5~2 TO-100EC(100A) CU-50
9 ⟦null: no independent source value⟧ 25HP 26 69 22 8 0.5~2 TO-100EC(100A) CU-65
10 ⟦null: no independent source value⟧ 30HP 30 80 22 14 0.5~2 TO-225E(125A) CU-80
11 ⟦null: no independent source value⟧ 40HP 42 110 38 14 0.5~2 TO-225E(150A) CN-100R
12 ⟦null: no independent source value⟧ 50HP 53 138 60 22 0.5~2 TO-225E(175A) CN-125R
13 ⟦null: no independent source value⟧ 60HP 64 169 80 22 0.5~2 TO-225E(200A) CN-150
14 ⟦null: no independent source value⟧ 75HP 76 200 100 22 0.5~2 TO-225E(225A) CN-180
15 ⟦null: no independent source value⟧ 100HP 95 250 150 22 0.5~2 TO-400S(300A) CN-300
16 ⟦null: no independent source value⟧ 125HP 119 312 200 38 0.5~2 TO-400S(400A) CN-300
17 ⟦null: no independent source value⟧ 150HP 137 400 300 38 0.5~2 TO-600S(600A) CN-400
18 ⟦null: no independent source value⟧ 175HP 172 450 250*2P 50 0.5~2 TO-800S(800A) CN-630
19 400V 3 Ø 1HP 2.6 3.4 2~5.5 2~5.5 0.5~2 TO-50EC(15A) CU-11
20 ⟦null: no independent source value⟧ 2HP 3.1 4.1 2~5.5 3.5~5.5 0.5~2 TO-50EC(15A) CU-11
21 ⟦null: no independent source value⟧ 3HP 4.1 5.4 2~5.5 3.5~5.5 0.5~2 TO-50EC(15A) CU-11
22 ⟦null: no independent source value⟧ 5HP 7.0 9.2 2~5.5 3.5~5.5 0.5~2 TO-50EC(15A) CU-18
23 ⟦null: no independent source value⟧ 7.5HP 8.5 12.1 2~5.5 3.5~5.5 0.5~2 TO-50EC(15A) CU-18
24 ⟦null: no independent source value⟧ 10HP 13.3 17.5 3~5.5 3.5~5.5 0.5~2 TO-50EC(20A) CU-18
25 ⟦null: no independent source value⟧ 15HP 18 23 5.5 5.5 0.5~2 TO-50EC(30A) CU-25
26 ⟦null: no independent source value⟧ 20HP 24 31 8 8 0.5~2 TO-100EC(50A) CU-25
27 ⟦null: no independent source value⟧ 25HP 29 38 8 8 0.5~2 TO-100EC(50A) CU-35
28 ⟦null: no independent source value⟧ 30HP 34 44 8 8 0.5~2 TO-100EC(50A) CU-50
29 ⟦null: no independent source value⟧ 40HP 41 58 14 8 0.5~2 TO-100EC(75A) CU-50
30 ⟦null: no independent source value⟧ 50HP 55 73 22 8 0.5~2 TO-100EC(100A) CU-65
31 ⟦null: no independent source value⟧ 60HP 67 88 22 14 0.5~2 TO-100EC(100A) CN-80
32 ⟦null: no independent source value⟧ 75HP 79 103 38 14 0.5~2 TO-225E(150A) CN-100R
33 ⟦null: no independent source value⟧ 100HP 111 145 60 22 0.5~2 TO-225E(175A) CN-150
34 ⟦null: no independent source value⟧ 125HP 126 168 80 22 0.5~2 TO-225E(225A) CN-150
35 ⟦null: no independent source value⟧ 150HP 159 208 150 22 0.5~2 TO-400S(300A) CN-300
36 ⟦null: no independent source value⟧ 175HP 191 250 150 22 0.5~2 TO-400S(300A) CN-300
37 ⟦null: no independent source value⟧ 215HP 226 296 200 30 0.5~2 TO-400S(400A) CN-300
38 ⟦null: no independent source value⟧ 250HP 250 328 250 30 0.5~2 TO-400S(400A) CN-400
39 ⟦null: no independent source value⟧ 300HP 332 435 300 38 0.5~2 TO-600S(600A) CN-630
40 ⟦null: no independent source value⟧ 375HP 393 515 250*2P 50 0.5~2 TO-800S(800A) CN-630

Manual — IP00/IP20 wiring table continuation andIP55Table3 — page 65

*1. The main circuit terminals: R/L1, S/L2, T/L3 , U/T1, V/T2, W/T3, B1/P, B2, , .

*2. Control line is the terminal wire on the control board.

*3. The NFB and MCB listed in the table are of TECO product numbers, products with same rated specification

of other brands may be used. To reduce electrical noise interference, ensure that a RC surge absorber

(R: 10Ω/ 5W, C: 0.1μf/1000VDC) is added to both sides of MCB coil.

Table 3.3.6.4 Wiring Instrument for 400V class (IP55 type)

*1. The main circuit terminals: R(L1), S(L2), T(L3), , ⊕1, ⊕2, U(T1), V(T2), W(T3),B1, B2 (Polyethylene

power line of 600V is recommended to be used.)

*2. Control line is the terminal wire on the control board.

of other brands may be used. To reduce electrical noise interference, ensure that a RC surge absorber (R:

10Ω/ 5W, C: 0.1μf/1000VDC) is added to both sides of MCB coil.

IP00/IP20 wiring table continuation andIP55Table3.3.6.4. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Continuation of400V3phase group on precedingPDF64;blank power-supply cells retained.

IP00/IP20 wiring table continuation andIP55Table3.3.6.4. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Continuation of400V3phase group on precedingPDF64;blank power-supply cells retained. Row group:

Shared source cells (coordinates refer to this table):

IP00/IP20 wiring table continuation andIP55Table3.3.6.4. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. IP55 only.

IP00/IP20 wiring table continuation andIP55Table3.3.6.4. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. IP55 only. Row group: 400V

3 Ø

IP00/IP20 wiring table continuation andIP55Table3.3.6.4 table1 — PDF page 65

Source row Power supply Horse power(HP) Rated KVA Rated current(A) Main circuit(mm²)*1 GroundingE(G)(mm²) Control line(mm²)*2 NFB*3 MC*3
1 ⟦blank source cell⟧ 425HP 457 585 250*2P 50 0.5~2 TE-1000(1000A) CN-630
2 ⟦null: no independent source value⟧ 535HP 526 700 300*2P 50 0.5~2 TE-1000(1000A) 800
3 ⟦null: no independent source value⟧ 670HP 640 875 300*2P 50 0.5~2 TE-1200(1200A) 1000
4 ⟦null: no independent source value⟧ 800HP 732 960 300*2P 50 0.5~2 TE-1200(1200A) 1000

IP00/IP20 wiring table continuation andIP55Table3.3.6.4 table2 — PDF page 65

Source row Power supply Horse power(HP) Rated KVA Rated current(A) Main circuit(mm²)*1 GroundingE(G)(mm²) Control line(mm²)*2 NFB*3 MC*3
1 400V 3 Ø 1HP 2.6 3.4 2~5.5 2~5.5 0.5~2 TO-50EC(15A) CU-11
2 ⟦null: no independent source value⟧ 2HP 3.1 4.1 2~5.5 3.5~5.5 0.5~2 TO-50EC(15A) CU-11
3 ⟦null: no independent source value⟧ 3HP 4.1 5.4 2~5.5 3.5~5.5 0.5~2 TO-50EC(15A) CU-11
4 ⟦null: no independent source value⟧ 5HP 7.0 9.2 2~5.5 3.5~5.5 0.5~2 TO-50EC(15A) CU-18
5 ⟦null: no independent source value⟧ 7.5HP 8.5 12.1 2~5.5 3.5~5.5 0.5~2 TO-50EC(15A) CU-18
6 ⟦null: no independent source value⟧ 10HP 13.3 17.5 3~5.5 3.5~5.5 0.5~2 TO-50EC(20A) CU-18
7 ⟦null: no independent source value⟧ 15HP 18 23 5.5 5.5 0.5~2 TO-50EC(30A) CU-27
8 ⟦null: no independent source value⟧ 20HP 24 31 8 8 0.5~2 TO-100EC(50A) CU-27
9 ⟦null: no independent source value⟧ 25HP 29 38 8 8 0.5~2 TO-100EC(50A) CU-38
10 ⟦null: no independent source value⟧ 30HP 34 44 8 8 0.5~2 TO-100EC(50A) CU-50
11 ⟦null: no independent source value⟧ 40HP 41 58 14 8 0.5~2 TO-100EC(75A) CU-50
12 ⟦null: no independent source value⟧ 50HP 55 73 22 8 0.5~2 TO-100EC(100A) CU-65
13 ⟦null: no independent source value⟧ 60HP 67 88 22 14 0.5~2 TO-100EC(100A) CN-80
14 ⟦null: no independent source value⟧ 75HP 79 103 38 14 0.5~2 TO-225E(150A) CN-100R
15 ⟦null: no independent source value⟧ 100HP 111 145 60 22 0.5~2 TO-225E(175A) CN-150

Manual — Wiring precautions and shielded twisted-pair illustration — page 66

3.3.7 Wiring Precautions

!

 Do NOT remove any protective covers or attempt any wiring while input power is

applied. Connect all wiring before applying input power. When making wiring

changes after power up, remove input power and wait a minimum of five minutes

after power has been turned off before starting. Also confirm that the charge lamp

is off and that DC voltage between terminals B1/P or (+) and (-) does not exceed

25V, otherwise electric shock may result.

 Only authorized personnel should work on the equipment. (Take off metal jewelry

such as watches and rings and use insulated tools.), otherwise electric shock or

injury may result.

(A) Wiring for control circuit:

(1) Separate the wiring for control circuit terminals from main circuit wiring for terminals (R/L1,

S/L2, T/L3, U/T1, V/T2, and W/T3).

(2) Separate the wiring for control circuit terminals (R1A, R1B, R1C / R2A, R2C /R3A, R3C)

from wiring for terminals S1~S6, A01, A02, GND, +10V-, AI1, AI2, and GND wiring.

(3) Use shielded twisted-pair cables (#24 - #14 AWG / 0.5 -2 mm2) shown in Fig. 3.3.7.1 for

control circuits to minimize noise problems. The maximum wiring distance should not

exceed 50m (165 ft).

Figure 3.3.7.1 Shielded Twisted-Pair

(B) Wiring for main circuit:

(1) The Input power supply voltage can be connected in any phase sequence to power input

terminals R/L1, S/L2, or T/L3 on the terminal block.

(2) DO NOT connect the AC input power source to the output terminals U/T1, V/T2 and. W/T3.

(3) Connect the output terminals U/T1, V/T2, W/T3 to motor lead wires U/T1, V/T2, and W/T3,

respectively.

(4) Check that the motor rotates forward with the forward run source. If it does not, swap any 2

of the output cables to change motor direction.

(5) DO NOT connect phase correcting capacitors or LC/RC noise filter to the output circuit.

Figure callouts:Shield;Wrap with insulating Tape;Twisted Pair. Ground Shield at Inverter end ONLY(leftend). DO NOT Ground Shield at this end(rightend). No shield-ground connection inferred at remote end. Context:control cable#24–#14AWG/0.5–2mm²,max50m(165ft),source warning power off and voltage check.

Manual — Grounding requirements and loop illustrations — page 67

(C) Grounding:

(1) Connect the ground terminal (E) to ground having a resistance of less than 100Ω.

(2) Do not share the ground wire with other devices, such as welding machines or power tools.

(3) Always use a ground wire that complies with the local codes and standards for electrical

equipment and minimize the length of ground wire.

(4) When using more than one inverter, be careful not to loop the ground wire, as shown below

in Fig. 3.3.7.2.

Figure 3.3.7.2 F510 Inverter Grounding

Bluepanel a)Correct:threeF510ground conductors to a common earth point. Bluepanel b)Correct:linked chain ending at earth. Redpanel c)Incorrect:loop interconnection,explicit Loop label. Diagram statements are supplier labels;local-code requirements remain in prose.

Manual — Cable voltage drop,carrier-frequency table,AC reactor — page 68

3.3.8 Input Power and Cable Length

Cable size

The length of the cables between the input power source and /or the motor and inverter can

cause a significant phase to phase voltage reduction due to the voltage drop across the cables. The

wire size shown in Tables 3.3.6.3 & 3.3.6.4 is based on a maximum voltage drop of 2%. If this value

is exceeded, a wire size having larger diameter may be needed. To calculate phase tot phase voltage

drop, apply the following formula:

Phase-to-phase voltage drop (V) = 3 ×resistance of wire (Ω/km) × length of line m) × current×10-3.

(km=3280 x feet)

(m=3.28 x feet)

Cable length vs. Carrier frequency

The allowable setting of the PWM carrier frequency is also determined by motor cable length

and is specified in the following Table 3.3.8.1.

Table 3.3.8.1 Cable Length vs. Carrier Frequency

Installing an AC line reactor

If the inverter is connected to a large-capacity power source (600kVA or more), install an

optional AC reactor on the input side of the inverter. This also improves the power factor on the

power supply side.

Printed equation:phase-to-phase voltage drop(V)=√3×wire resistance(Ω/km)×line length(m)×current×10^-3. Printed conversions:(km=3280×feet),(m=3.28×feet). Cable table boundaries:<30m(100ft):16kHzmax;30–50m(100–165ft):10kHzmax;50–100m(166–328ft):5kHzmax;≥100m(329ft):2kHzmax,parameter11-01. Do not infer an unambiguous exact100m boundary or recalculate imperial endpoints.

Cable voltage drop,carrier-frequency table,AC reactor. Exact source units/model/enclosure and qualifiers govern applicability; source claims only.

Cable voltage drop,carrier-frequency table,AC reactor. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Recommended carrier

frequency allowed

Parameter 11-01

Cable voltage drop,carrier-frequency table,AC reactor table2 — PDF page 68

Source row Cable length between the inverter and Motor in m (ft.). < 30 (100) 30 – 50 (100 – 165) 50 – 100 (166 - 328) ≥ 100 (329)
1 Recommended carrier frequency allowed Parameter 11-01 16kHz (max) 10 kHz (max) 5 kHz (max) 2 kHz (max)

Manual — Basic specifications200V and400V classes — page 69

3.4 Inverter Specifications

Basic Specifications

(a) 200V class

(b) 400V class

Basic specifications200V and400V classes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Class:200V. Capacity column headers areHP. Footnotes onPDF70:standard4-pole induction motor basis;normal-duty120%/1min;carrier derating applies.

Basic specifications200V and400V classes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Class:200V. Capacity column headers areHP. Footnotes onPDF70:standard4-pole induction motor basis;normal-duty120%/1min;carrier derating applies. Row group: Output Rated

Basic specifications200V and400V classes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Class:200V. Capacity column headers areHP. Footnotes onPDF70:standard4-pole induction motor basis;normal-duty120%/1min;carrier derating applies. Row group: Power supply

Shared source cells (coordinates refer to this table):

Basic specifications200V and400V classes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Class:400V. Capacity column headers areHP. Footnotes onPDF70:standard4-pole induction motor basis;normal-duty120%/1min;carrier derating applies.

Basic specifications200V and400V classes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Class:400V. Capacity column headers areHP. Footnotes onPDF70:standard4-pole induction motor basis;normal-duty120%/1min;carrier derating applies. Row group: Output Rated

Basic specifications200V and400V classes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Class:400V. Capacity column headers areHP. Footnotes onPDF70:standard4-pole induction motor basis;normal-duty120%/1min;carrier derating applies. Row group: Power supply

Basic specifications200V and400V classes table1 — PDF page 69

Source row Source category Property 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 175
1 Output Rated Rated Output Capacity (KVA) 1.9 2.9 4.0 5.5 8 11.4 15.2 21.3 26.2 30 41.9 52.5 64.3 76.2 95.2 118.8 152.4 171.4
2 ⟦null: no independent source value⟧ Rated Output Current (A) 5.0 7.5 10.6 14.5 22 30 42 56 69 80 110 138 169 200 250 312 400 450
3 ⟦null: no independent source value⟧ Maximum Applicable Motor *1HP (KW) 1 (0.75) 2 (1.5) 3 (2.2) 5 (3.7) 7.5 (5.5) 10 (7.5) 15 (11) 20 (15) 25 (18.5) 30 (22) 40 (30) 50 (37) 60 (45) 75 (55) 100 (75) 125 (90) 150 (110) 175 (130)
4 ⟦null: no independent source value⟧ Maximum Output Voltage (V) 3-phase 200V~240V ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 Power supply Rated Voltage, Frequency 1-phase/ 3-phase ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3-phase 200V~240V, 50/60Hz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ Allowable Voltage Fluctuation -15% ~ +10% ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ Allowable Frequency Fluctuation ±5% ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Basic specifications200V and400V classes table2 — PDF page 69

Source row Source category Property 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 175 215 250 300 375
1 Output Rated Rated Output Capacity (KVA) 2.6 3.1 4.1 7.0 8.4 13.3 17.5 23.6 28.9 33.5 41.1 54.8 67 78.4 110 125 158 190 225 250 331 392
2 ⟦null: no independent source value⟧ Rated Output Current (A) 3.4 4.1 5.4 9.2 12.1 17.5 23 31 38 44 58 73 88 103 145 168 208 250 296 328 435 515
3 ⟦null: no independent source value⟧ Maximum Applicable Motor *1HP (KW) 1 (0.75) 2 (1.5) 3 (2.2) 5 (3.7) 7.5 (5.5) 10 (7.5) 15 (11) 20 (15) 25 (18.5) 30 (22) 40 (30) 50 (37) 60 (45) 75 (55) 100 (75) 125 (90) 150 (110) 175 (132) 215 (160) 250 (185) 300 (220) 375 (280)
4 ⟦null: no independent source value⟧ Maximum Output Voltage (V) 3-phase 380V~480V ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 Power supply Rated Voltage, Frequency 3-phase 380V ~ 480V, 50/60Hz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ Allowable Voltage Fluctuation -15% ~ +10% ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ Allowable Frequency Fluctuation ±5% ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Basic specifications200V and400V classes table3 — PDF page 69

Source row Source category Property 425 535 670 800
1 Output Rated Rated Output Capacity (KVA) 445 525 640 731
2 ⟦null: no independent source value⟧ Rated Output Current (A) 585 700 875 960
3 ⟦null: no independent source value⟧ Maximum Applicable Motor *1HP (KW) 425 (315) 535 (400) 670 (500) 800 (600)
4 ⟦null: no independent source value⟧ Maximum Output Voltage (V) 3-phase 380V~480V ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 Power supply Rated Voltage, Frequency 3-phase 380V ~ 480V, 50/60Hz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ Allowable Voltage Fluctuation -15% ~ +10% ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ Allowable Frequency Fluctuation ±5% ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Basic specification footnotes,carrier and control-mode limits — page 70

*1: Take standard 4-pole induction motor as the base.

*2: F510 model is designed to be used in normal duty (ND), whose overload capability is 120% for 1 min.

*3: If it is greater than default carrier frequency, you need to adjust the load current based on the de-rating

curve.

*4: If control mode is set to SLV mode and maximum frequency (01-02) is larger than 80 Hz, the carrier

frequency range is 2~8Hz.

The following table shows the maximum output frequency for each control mode.

Basic specification footnotes,carrier and control-mode limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only.

Basic specification footnotes,carrier and control-mode limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: 1~25HP

Basic specification footnotes,carrier and control-mode limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: 30HP

Basic specification footnotes,carrier and control-mode limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: 40~50HP

Basic specification footnotes,carrier and control-mode limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: 60~125HP

Basic specification footnotes,carrier and control-mode limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: -

Basic specification footnotes,carrier and control-mode limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: 150~175HP

Basic specification footnotes,carrier and control-mode limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: V/F

Basic specification footnotes,carrier and control-mode limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: SLV

Basic specification footnotes,carrier and control-mode limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: PMSLV

Shared source cells (coordinates refer to this table):

Basic specification footnotes,carrier and control-mode limits table1 — PDF page 70

Source row 200V class Carrier freq. default setting Carrier freq. range 400V class Carrier freq. default setting Carrier freq. range
1 1~25HP 2KHz 2~16KHz 1~30HP 4KHz 2~16KHz
2 30HP 2KHz 2~12KHz 40HP 2KHz 2~16KHz
3 40~50HP 2KHz 2~12KHz (*4) 50~60HP 4KHz 2~12KHz (*4)
4 60~125HP 2KHz 2~10KHz (*4) 75~215HP 4KHz 2~10KHz (*4)
5 - - - 250HP 2KHz 2~8KHz
6 150~175HP 2KHz 2~5KHz 300~375HP 4KHz 2~5KHz
7 - - - 425HP 2KHz 2~5KHz
8 - - - 535~800HP 4KHz 2~5KHz

Basic specification footnotes,carrier and control-mode limits table2 — PDF page 70

Source row Control mode Other settings Maximum output frequency
1 V/F Unlimited 599Hz
2 SLV 200V 1~15HP, 400V 1~20HP 150Hz
3 ⟦null: no independent source value⟧ 200V 20~30HP, 400V 25HP 110Hz
4 ⟦null: no independent source value⟧ 400V 30~40HP 100Hz
5 ⟦null: no independent source value⟧ 200V 40~125HP, 400V 50~215HP, carrier (11-01) is set as 8K or below 8K. 100Hz
6 ⟦null: no independent source value⟧ 200V 40~125HP, 400V 50~215HP, carrier (11-01) is set as above 8K. 80Hz
7 ⟦null: no independent source value⟧ 200V 150~175HP, 400V 250~800HP 100Hz
8 PMSLV Unlimited 599Hz

Manual — General specifications — page 71

Source limitation for this page: DC bus charge indicator comparison operator before50V absent/unreadable; no relation inferred.

General Specifications

General specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Footnotes continuePDF72; no current certification verification.

General specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Footnotes continuePDF72; no current certification verification. Row group: Control Characteristics

General specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Footnotes continuePDF72; no current certification verification. Row group: Protection Function

General specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Footnotes continuePDF72; no current certification verification. Row group: Environment Specifications

Shared source cells (coordinates refer to this table):

General specifications table1 — PDF page 71

Source row Category Property Supplier specification
1 Control Characteristics Operation Modes LED keypad with seven-segment display *5 and LCD keypad (Optional HOA LCD keypad); all LCD keypad with parameter copy function
2 ⟦null: no independent source value⟧ Control Modes V/F, SLV, PMSLV with space vector PWM mode
3 ⟦null: no independent source value⟧ Frequency Control Range 0.1Hz~599.0Hz
4 ⟦null: no independent source value⟧ Output Frequency Accuracy (Temperature change) Digital references: ±0.01%(-10 to +40℃), Analog references: ±0.1% (25℃±10℃)
5 ⟦null: no independent source value⟧ Speed Control Accuracy ±0.5% (Sensorless Vector Control Mode)*1
6 ⟦null: no independent source value⟧ Frequency Setting Resolution Digital references: 0.01Hz , Analog references: 0.06Hz/60Hz
7 ⟦null: no independent source value⟧ Output Frequency Resolution 0.01Hz
8 ⟦null: no independent source value⟧ Inverter Overload 120%/1 min
9 ⟦null: no independent source value⟧ Frequency Setting Signal DC 0~+10V / 0~20mA or 4~20mA
10 ⟦null: no independent source value⟧ Acceleration/ Deceleration Time 0.0~6000.0 seconds ( separately set acceleration and deceleration time )
11 ⟦null: no independent source value⟧ Voltage, Frequency Characteristics Custom V/F curve based on parameters
12 ⟦null: no independent source value⟧ Braking Torque About 20%
13 ⟦null: no independent source value⟧ Main Control Functions Auto tuning, Soft-PWM, Over voltage protection, Dynamic braking, Speed search, Restart upon momentary power loss, 2 sets of PID control, Slip Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch
14 ⟦null: no independent source value⟧ Other Functions Accumulated power-on/ run time, 30 sets of fault history records and latest fault record state, Energy-saving function setting, Phase loss protection, Smart braking, DC braking, Dwell,S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings
15 Protection Function Stall Prevention Current level can be setting (It can be set separately in acceleration or constant speed; it can be set with or without protection in deceleration)
16 ⟦null: no independent source value⟧ Instantaneous Over Current (OC) and Output Short- Circuit (SC) Protection Inverter stops when the output current exceeds 160% of the inverter rated current
17 ⟦null: no independent source value⟧ Inverter Overload Protection (OL2) If inverter rated current 120%/1min is exceeded, inverter stops. The factory default carrier frequency is 2~4KHZ*2
18 ⟦null: no independent source value⟧ Motor Overload Protection (OL1) Electrical overload protection curve
19 ⟦null: no independent source value⟧ Over voltage (OV) Protection If the main circuit DC voltage rises over 410V (200V class)/ 820V (400V class), the motor stops running.
20 ⟦null: no independent source value⟧ Under voltage (UV) Protection If the main circuit DC voltage falls below 190V (200V class) /380V (400V class), the motor stops running.
21 ⟦null: no independent source value⟧ Auto-Restart after Momentary Power Loss Power loss exceeds 15ms. Auto-restart function available after momentary power loss in 2 sec.;3HP below for 1sec
22 ⟦null: no independent source value⟧ Overheat(OH) Protection Use temperature sensor for protection.
23 ⟦null: no independent source value⟧ Ground Fault (GF) Protection Use current sensor for protection.
24 ⟦null: no independent source value⟧ DC Bus Charge Indicator When main circuit DC voltage [source relation unreadable] 50V, the CHARGE LED turns on.
25 ⟦null: no independent source value⟧ Input Phase Loss (IPL) Protection If the IPL is detected, the motor stops automatically.
26 ⟦null: no independent source value⟧ Output Phase Loss (OPL) Protection If the OPL is detected, the motor stops automatically.
27 ⟦null: no independent source value⟧ Short-circuit current rating (SCCR) Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes (rms) when protected by fuses given in the fuse table.
28 Environment Specifications Installation Location Indoor (protected from corrosive gases and dust)
29 ⟦null: no independent source value⟧ Ambient Temperature -10~+40℃(14℉~104℉) (IP20/NEMA1 or IP55/NEMA12), -10~+50℃(14℉~122℉) (IP00 or top anti-dust cover removed) without de-rating; with de-rating, its maximum operation temperature is 60℃(140℉). (Enhanced type frame 5 is 50°C without de-rating
30 ⟦null: no independent source value⟧ Storage Temperature -20~+70℃(-4℉~+158℉)
31 ⟦null: no independent source value⟧ Humidity 95%RH or less (no condensation)
32 ⟦null: no independent source value⟧ Altitude Altitude: Below 1000 m (3281 ft.), It is required to derate 1% of current at each additional 100 m, the maximum altitude is 3000 m.
33 ⟦null: no independent source value⟧ Vibration 9.8m/s2 (1.0G), meet IEC 60068-2-6
34 ⟦null: no independent source value⟧ Pollution Degree IP00/IP20/IP21 meet IEC 60721-3-3 Class 3C2, IP55 meet IEC 60721-3-3 Class 3C3

Manual — General specifications continuation,certification source claims — page 72

*1: Speed control accuracy will be different from the installation conditions and motor types.

*2: The factory default carrier frequency is different from models.

General specifications continuation,certification source claims. Exact source units/model/enclosure and qualifiers govern applicability; source claims only.

General specifications continuation,certification source claims. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Communication Function

General specifications continuation,certification source claims. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: PLC Function

General specifications continuation,certification source claims. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: EMI Protection

General specifications continuation,certification source claims. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: EMS Protection

General specifications continuation,certification source claims. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Safety

Certification

General specifications continuation,certification source claims. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Accessories

Shared source cells (coordinates refer to this table):

General specifications continuation,certification source claims table1 — PDF page 72

Source row Property/category Subproperty or merged cell Supplier specification
1 Communication Function ⟦null: no independent source value⟧ Built-in RS-485 as standard (Modbus protocol with RJ45/ BACnet/ Metasys N2)
2 PLC Function ⟦null: no independent source value⟧ Built-in
3 EMI Protection ⟦null: no independent source value⟧ The built-in noise filter complies with EN61800-3 available for inverters 400V 75HP or below (IP20) / 400V 60HP or below (IP55)
4 EMS Protection ⟦null: no independent source value⟧ in compliance with EN61800-3
5 Safety Certification CE Declaration in compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD, Low-Voltage Directive)
6 ⟦null: no independent source value⟧ UL Certification UL508C
7 Accessories ⟦null: no independent source value⟧ Please refer to chapter 11

Manual — Carrier-frequency derating200V models — page 73

3.5 Inverter De-rating Based on Carrier Frequency

Note: De-rating curve current of carrier frequency means inverter rated current.

(a) 200V Models

200V 1~25HP

100%

A

B

0 2KHz 8KHz 16KHz

Rated Current

Ratio

Carrier

Frequency (Fc)

200V 30~50HP

0 2KHz 6KHz 12KHz

200V 60~175HP

0 2KHz 5KHz 10KHz

Explicit plotted breakpoints:100%at2kHz;Aat8kHz;Bat16kHz. VerticalaxisRatedCurrentRatio;horizontalaxisCarrierFrequencyFc. A/Bvalues are model-specific in adjoining tables;do not interpolate unprinted values or infer frequencypermissionfromcurve.

Explicit plotted breakpoints:100%at2kHz;Aat6kHz;Bat12kHz. VerticalaxisRatedCurrentRatio;horizontalaxisCarrierFrequencyFc. A/Bvalues are model-specific in adjoining tables;do not interpolate unprinted values or infer frequencypermissionfromcurve.

Explicit plotted breakpoints:100%at2kHz;Aat5kHz;Bat10kHz. VerticalaxisRatedCurrentRatio;horizontalaxisCarrierFrequencyFc. A/Bvalues are model-specific in adjoining tables;do not interpolate unprinted values or infer frequencypermissionfromcurve.

Carrier-frequency derating200V models. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:200V1–25HP:Aat8kHz,Bat16kHz,100%at2kHz.

Carrier-frequency derating200V models. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:200V1–25HP:Aat8kHz,Bat16kHz,100%at2kHz. Row group: A

Carrier-frequency derating200V models. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:200V1–25HP:Aat8kHz,Bat16kHz,100%at2kHz. Row group: B

Carrier-frequency derating200V models. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:200V30–50HP:Aat6kHz,Bat12kHz,100%at2kHz.

Carrier-frequency derating200V models. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:200V30–50HP:Aat6kHz,Bat12kHz,100%at2kHz. Row group: A

Carrier-frequency derating200V models. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:200V30–50HP:Aat6kHz,Bat12kHz,100%at2kHz. Row group: B

Carrier-frequency derating200V models. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:200V60–175HP:Aat5kHz,Bat10kHz,100%at2kHz;conflicts withPDF70range for150–175HP retained.

Carrier-frequency derating200V models. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:200V60–175HP:Aat5kHz,Bat10kHz,100%at2kHz;conflicts withPDF70range for150–175HP retained. Row group: A

Carrier-frequency derating200V models. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:200V60–175HP:Aat5kHz,Bat10kHz,100%at2kHz;conflicts withPDF70range for150–175HP retained. Row group: B

Carrier-frequency derating200V models table2 — PDF page 73

Source row Model 2001 2002 2003 2005 2008
1 A 100% 67% 76% 76% 80%
2 B 80% 53% 60% 61% 68%

Carrier-frequency derating200V models table3 — PDF page 73

Source row Model 2010 2015 2020 2025
1 A 83% 79% 84% 87%
2 B 67% 67% 67% 70%

Carrier-frequency derating200V models table5 — PDF page 73

Source row Model 2030 2040 2050
1 A 92% 77% 83%
2 B 74% 62% 67%

Carrier-frequency derating200V models table7 — PDF page 73

Source row Model 2060 2075 2100
1 A 85% 90% 86%
2 B 68% 72% 69%

Carrier-frequency derating200V models table8 — PDF page 73

Source row Model 2125 2150 2175
1 A 91% 87% 92%
2 B 73% 78% 83%

Manual — Carrier-frequency derating400V1–60HP — page 74

400V 1~30HP

100%

A

B

0 4KHz 8KHz 16KHz

400V 40HP

78%

47%

0 2KHz 8KHz 16KHz

400V 50~60HP

0 4KHz 5KHz 12KHz

Carrier

Frequency (Fc)

(b) 400V Models

Rated Current

Ratio

Explicit plotted breakpoints:100%at4kHz;Aat8kHz;Bat16kHz. VerticalaxisRatedCurrentRatio;horizontalaxisCarrierFrequencyFc. A/Bvalues are model-specific in adjoining tables;do not interpolate unprinted values or infer frequencypermissionfromcurve.

Explicit plotted breakpoints:100%at2kHz;78%at8kHz;47%at16kHz. VerticalaxisRatedCurrentRatio;horizontalaxisCarrierFrequencyFc. A/Bvalues are model-specific in adjoining tables;do not interpolate unprinted values or infer frequencypermissionfromcurve.

Explicit plotted breakpoints:100%at4kHz;Aat5kHz;Bat12kHz. VerticalaxisRatedCurrentRatio;horizontalaxisCarrierFrequencyFc. A/Bvalues are model-specific in adjoining tables;do not interpolate unprinted values or infer frequencypermissionfromcurve.

Carrier-frequency derating400V1–60HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:400V1–30HP:Aat8kHz,Bat16kHz,100%at4kHz;IP55/IP20 suffixes retained.

Carrier-frequency derating400V1–60HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:400V1–30HP:Aat8kHz,Bat16kHz,100%at4kHz;IP55/IP20 suffixes retained. Row group: A

Carrier-frequency derating400V1–60HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:400V1–30HP:Aat8kHz,Bat16kHz,100%at4kHz;IP55/IP20 suffixes retained. Row group: B

Carrier-frequency derating400V1–60HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:400V50–60HP:Aat5kHz,Bat12kHz,100%at4kHz.

Carrier-frequency derating400V1–60HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:400V50–60HP:Aat5kHz,Bat12kHz,100%at4kHz. Row group: A

Carrier-frequency derating400V1–60HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:400V50–60HP:Aat5kHz,Bat12kHz,100%at4kHz. Row group: B

Carrier-frequency derating400V1–60HP table1 — PDF page 74

Source row Model 4001 (IP55) 4002 (IP55) 4003 (IP55)
1 A 100% 100% 100%
2 B 60% 60% 60%

Carrier-frequency derating400V1–60HP table3 — PDF page 74

Source row Model 4001 (IP20) 4002 (IP20) 4003 (IP20) 4005 4008
1 A 100% 83% 78% 100% 76%
2 B 60% 50% 47% 60% 46%

Carrier-frequency derating400V1–60HP table4 — PDF page 74

Source row Model 4010 4015 4020 4025 4030
1 A 85% 78% 77% 82% 89%
2 B 51% 47% 46% 49% 53%

Carrier-frequency derating400V1–60HP table7 — PDF page 74

Source row Model 4050 4060
1 A 83% 85%
2 B 66% 68%

Manual — Carrier-frequency derating400V75–375HP — page 75

400V 75~215HP

100%

A

B

0 4KHz 5KHz 10KHz

400V 250HP

88%

78%

0 2KHz 3KHz 5KHz

400V 300~375HP

0 4KHz 5KHz

Carrier

Frequency (Fc)

Rated Current

Ratio

Explicit plotted breakpoints:100%at4kHz;Aat5kHz;Bat10kHz. VerticalaxisRatedCurrentRatio;horizontalaxisCarrierFrequencyFc. A/Bvalues are model-specific in adjoining tables;do not interpolate unprinted values or infer frequencypermissionfromcurve.

Explicit plotted breakpoints:100%at2kHz;88%at3kHz;78%at5kHz. VerticalaxisRatedCurrentRatio;horizontalaxisCarrierFrequencyFc. A/Bvalues are model-specific in adjoining tables;do not interpolate unprinted values or infer frequencypermissionfromcurve.

Explicit plotted breakpoints:100%at4kHz;Aat5kHz. VerticalaxisRatedCurrentRatio;horizontalaxisCarrierFrequencyFc. A/Bvalues are model-specific in adjoining tables;do not interpolate unprinted values or infer frequencypermissionfromcurve.

Carrier-frequency derating400V75–375HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:400V75–215HP:Aat5kHz,Bat10kHz,100%at4kHz.

Carrier-frequency derating400V75–375HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:400V75–215HP:Aat5kHz,Bat10kHz,100%at4kHz. Row group: A

Carrier-frequency derating400V75–375HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:400V75–215HP:Aat5kHz,Bat10kHz,100%at4kHz. Row group: B

Carrier-frequency derating400V75–375HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:400V300–375HP:Aat5kHz,100%at4kHz.

Carrier-frequency derating400V75–375HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Curve associations:400V300–375HP:Aat5kHz,100%at4kHz. Row group: A

Carrier-frequency derating400V75–375HP table2 — PDF page 75

Source row Model 4075 4100 4125
1 A 88% 81% 89%
2 B 62% 57% 63%

Carrier-frequency derating400V75–375HP table3 — PDF page 75

Source row Model 4150 4175 4215
1 A 87% 86% 88%
2 B 61% 60% 61%

Carrier-frequency derating400V75–375HP table6 — PDF page 75

Source row Model 4300 4375
1 A 77% 79%

Manual — Carrier-frequency derating400V425–800HP — page 76

400V 425HP

100%

87%

78%

0 2KHz 3KHz 5KHz

Rated Current

Ratio

Carrier

Frequency (Fc)

400V 535~800HP

90%

80%

70%

0 2KHz 3KHz 4KHz 5KHz

Explicit plotted breakpoints:100%at2kHz;87%at3kHz;78%at5kHz. VerticalaxisRatedCurrentRatio;horizontalaxisCarrierFrequencyFc. A/Bvalues are model-specific in adjoining tables;do not interpolate unprinted values or infer frequencypermissionfromcurve.

Explicit plotted breakpoints:100%at2kHz;90%at3kHz;80%at4kHz;70%at5kHz. VerticalaxisRatedCurrentRatio;horizontalaxisCarrierFrequencyFc. A/Bvalues are model-specific in adjoining tables;do not interpolate unprinted values or infer frequencypermissionfromcurve.

Manual — Ambient derating,PMmotor notes andcapacitor reforming — page 77

3.6 Inverter De-rating Based on Temperature

Note: User needs to adjust the inverter rated current depending on ambient temperature to ensure

the appropriate industrial application.

◆ Notes for using the PM motor

  1. The inverter carry frequency (11-01) need to set upper than 6KHz.

  2. The rating current of the inverter at 6KHz carry frequency (11-01) (need refer to the

de-rating curve) must be bigger than the PM motor rating current.

◆ Capacitor reforming Guide after long storage

For correct performance of this product after long storage before use it is important that

Inverter Capacitors are reformed according to the guide below:

*1:Rated voltage: please connects rated voltage according to model label of inverter.

100%

60%

0 40℃ 60℃

Rated Current

Ratio

Temperature

Explicit curve:100%ratedcurrent through40°C;line descends to60%at60°C. No intermediate values computed. Applicability must retainPDF71differentIP00/open-cover andenhancedframe5temperature limits.

Ambient derating,PMmotor notes andcapacitor reforming. Exact source units/model/enclosure and qualifiers govern applicability; source claims only.

Ambient derating,PMmotor notes andcapacitor reforming. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: ≦1year

Ambient derating,PMmotor notes andcapacitor reforming. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Between

1-2 years

Ambient derating,PMmotor notes andcapacitor reforming. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: ≧2 years

Ambient derating,PMmotor notes andcapacitor reforming table1 — PDF page 77

Source row Storage time Procedure to re-apply voltage
1 ≦1year Apply rated voltage(*1) of inverter in the normal way
2 Between 1-2 years Apply 100% rated voltage of inverter to the product for one hour
3 ≧2 years Use a variable AC power supply to 1. Connecting 25% of inverter rated voltage for 30 minutes. 2. Connecting 50% of inverter rated voltage for 30 minutes. 3. Connecting 75% of inverter rated voltage for 30 minutes. 4. Connecting 100% of inverter rated voltage for 210 minutes. Once the procedures completed, inverter just can be used normally.

Manual — 3 — page 78

3-

3.7 Inverter Dimensions

3.7.1 Standard Type (IP00/IP20)

(a) 200V: 1-7.5HP(Standard H & C type) 1-10HP (Enhanced E & G type)/ 400V: 1-10HP

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is the short rear offset/thickness callout in the side view.

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2001-□

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2002-□

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2003-□

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2005-□3

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2008-□3

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2010-E3/G3

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4001- □3

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4002- □3

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4003- □3

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4005- □3

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4008- □3

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4010- □3

3.7.1 Standard IP00/IP20 dimensions:200V1–7.5HP standard or1–10HP enhanced;400V1–10HP table1 — PDF page 78

Source row Inverter Model W H D W1 H1 t d NW in kg(lbs)
1 F510-2001-□ 130 (5.12) 215 (8.46) 150 (5.91) 118 (4.65) 203 (7.99) 5 (0.20) M5 2.2 (4.9)
2 F510-2002-□ 130 (5.12) 215 (8.46) 150 (5.91) 118 (4.65) 203 (7.99) 5 (0.20) M5 2.2 (4.9)
3 F510-2003-□ 130 (5.12) 215 (8.46) 150 (5.91) 118 (4.65) 203 (7.99) 5 (0.20) M5 2.2 (4.9)
4 F510-2005-□3 140 (5.51) 279 (10.98) 177 (6.97) 122 (4.80) 267 (10.51) 7 (0.28) M6 3.8 (8.4)
5 F510-2008-□3 140 (5.51) 279 (10.98) 177 (6.97) 122 (4.80) 267 (10.51) 7 (0.28) M6 3.8 (8.4)
6 F510-2010-E3/G3 140 (5.51) 279 (10.98) 177 (6.97) 122 (4.80) 267 (10.51) 7 (0.28) M6 3.8 (8.4)
7 F510-4001- □3 130 (5.12) 215 (8.46) 150 (5.91 118 (4.65) 203 (7.99) 5 (0.20) M5 2.2 (4.9)
8 F510-4002- □3 130 (5.12) 215 (8.46) 150 (5.91 118 (4.65) 203 (7.99) 5 (0.20) M5 2.2 (4.9)
9 F510-4003- □3 130 (5.12) 215 (8.46) 150 (5.91 118 (4.65) 203 (7.99) 5 (0.20) M5 2.2 (4.9)
10 F510-4005- □3 140 (5.51) 279 (10.98) 177 (6.97) 122 (4.80) 267 (10.51) 7 (0.28) M6 3.8 (8.4)
11 F510-4008- □3 140 (5.51) 279 (10.98) 177 (6.97) 122 (4.80) 267 (10.51) 7 (0.28) M6 3.8 (8.4)
12 F510-4010- □3 140 (5.51) 279 (10.98) 177 (6.97) 122 (4.80) 267 (10.51) 7 (0.28) M6 3.8 (8.4)

Manual — Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP — page 79

3-

(b) 200V: 10-30HP(Standard H & C type) 15~30HP (Enhanced E & G type) / 400V: 15-

40HP

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is present in the source table; no additional unlabeled drawing location is inferred.

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2010-H3/C3

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2015-□3

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2020-□3

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2025-□3

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2030-□3

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4015-□3

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4020-□3

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4025-E3/G3

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4025-H3/C3

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4030-□3

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4040-□3

Standard IP00/IP20 dimensions:200V10–30HP standard or15–30HP enhanced;400V15–40HP table1 — PDF page 79

Source row Inverter Model W H D W1 H1 t d NW in kg(lbs)
1 F510-2010-H3/C3 210 (8.27) 300 (11.81) 215 (8.46) 192 (7.56) 286 (11.26) 1.6 (0.06) M6 6.2 (13.67)
2 F510-2015-□3 210 (8.27) 300 (11.81) 215 (8.46) 192 (7.56) 286 (11.26) 1.6 (0.06) M6 6.2 (13.67)
3 F510-2020-□3 265 (10.43) 360 (14.17) 225 (8.86) 245 (9.65) 340 (13.39) 1.6 (0.06) M8 10 (22.05)
4 F510-2025-□3 265 (10.43) 360 (14.17) 225 (8.86) 245 (9.65) 340 (13.39) 1.6 (0.06) M8 10 (22.05)
5 F510-2030-□3 265 (10.43) 360 (14.17) 225 (8.86) 245 (9.65) 340 (13.39) 1.6 (0.06) M8 10 (22.05)
6 F510-4015-□3 210 (8.27) 300 (11.81) 215 (8.46) 192 (7.56) 286 (11.26) 1.6 (0.06) M6 6.2 (13.67)
7 F510-4020-□3 210 (8.27) 300 (11.81) 215 (8.46) 192 (7.56) 286 (11.26) 1.6 (0.06) M6 6.2 (13.67)
8 F510-4025-E3/G3 210 (8.27) 300 (11.81) 215 (8.46) 192 (7.56) 286 (11.26) 1.6 (0.06) M6 6.2 (13.67)
9 F510-4025-H3/C3 265 (10.43) 360 (14.17) 225 (8.86) 245 (9.65) 340 (13.39) 1.6 (0.06) M8 10 (22.05)
10 F510-4030-□3 265 (10.43) 360 (14.17) 225 (8.86) 245 (9.65) 340 (13.39) 1.6 (0.06) M8 10 (22.05)
11 F510-4040-□3 265 (10.43) 360 (14.17) 225 (8.86) 245 (9.65) 340 (13.39) 1.6 (0.06) M8 10 (22.05)

Manual — Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced — page 80

3-

(c) 200V: 40-50HP/ 400V: 50-75HP (Standard H & C type) 50~100HP (Enhanced E & G

type)

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is present in the source table; no additional unlabeled drawing location is inferred.

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2040-H3/C3

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2050-H3/C3

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4050-H3/C3

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4060-H3/C3

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4075-H3/C3

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2040-E3/G3

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2050-E3/G3

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4050-E3/G3

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4060-E3/G3

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4075-E3/G3

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4100-E3/G3

Standard IP00/IP20 dimensions:200V40–50HP;400V50–75HP standard or50–100HP enhanced table1 — PDF page 80

Source row Inverter Model W H D W1 H1 t d NW in kg(lbs)
1 F510-2040-H3/C3 286.5 (11.28) 525 (20.67) 252 (9.92) 220 (8.66) 505 (19.88) 3.3 (0.13) M8 24 (52.91)
2 F510-2050-H3/C3 286.5 (11.28) 525 (20.67) 252 (9.92) 220 (8.66) 505 (19.88) 3.3 (0.13) M8 24 (52.91)
3 F510-4050-H3/C3 286.5 (11.28) 525 (20.67) 252 (9.92) 220 (8.66) 505 (19.88) 3.3 (0.13) M8 24 (52.91)
4 F510-4060-H3/C3 286.5 (11.28) 525 (20.67) 252 (9.92) 220 (8.66) 505 (19.88) 3.3 (0.13) M8 24 (52.91)
5 F510-4075-H3/C3 286.5 (11.28) 525 (20.67) 252 (9.92) 220 (8.66) 505 (19.88) 3.3 (0.13) M8 24 (52.91)
6 F510-2040-E3/G3 286.5 (11.28) 525 (20.67) 272 (10.71) 220 (8.66) 505 (19.88) 3.3 (0.13) M8 24 (52.91)
7 F510-2050-E3/G3 286.5 (11.28) 525 (20.67) 272 (10.71) 220 (8.66) 505 (19.88) 3.3 (0.13) M8 24 (52.91)
8 F510-4050-E3/G3 286.5 (11.28) 525 (20.67) 272 (10.71) 220 (8.66) 505 (19.88) 3.3 (0.13) M8 24 (52.91)
9 F510-4060-E3/G3 286.5 (11.28) 525 (20.67) 272 (10.71) 220 (8.66) 505 (19.88) 3.3 (0.13) M8 24 (52.91)
10 F510-4075-E3/G3 286.5 (11.28) 525 (20.67) 272 (10.71) 220 (8.66) 505 (19.88) 3.3 (0.13) M8 24 (52.91)
11 F510-4100-E3/G3 286.5 (11.28) 525 (20.67) 272 (10.71) 220 (8.66) 505 (19.88) 3.3 (0.13) M8 24 (52.91)

Manual — IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced — page 81

3-

(d) 200V: 60-125HP/ 400V: 100-250HP (Standard H & C type) 125~250HP (Enhanced E

& G type) (IP00)

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is present in the source table; no additional unlabeled drawing location is inferred.

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2060-□3

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2075-□3

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2100-□3

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2125-□3

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4100-H3/C3

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4125-□3

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4150-E3/G3

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4150-H3/C3

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4175-□3

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4215-□3

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4250-□3

IP00 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced table1 — PDF page 81

Source row Inverter Model W H D W1 H1 t d NW in kg(lbs)
1 F510-2060-□3 344 (13.54) 580 (22.83) 300 (11.81) 250 (9.84) 560 (22.05) 1.6 (0.06) M8 40 (88.18)
2 F510-2075-□3 344 (13.54) 580 (22.83) 300 (11.81) 250 (9.84) 560 (22.05) 1.6 (0.06) M8 40 (88.18)
3 F510-2100-□3 459 (18.07) 790 (31.10) 324.5 (12.78) 320 (12.60) 760 (29.92) 1.6 (0.06) M10 74 (163.14)
4 F510-2125-□3 459 (18.07) 790 (31.10) 324.5 (12.78) 320 (12.60) 760 (29.92) 1.6 (0.06) M10 74 (163.14)
5 F510-4100-H3/C3 344 (13.54) 580 (22.83) 300 (11.81) 250 (9.84) 560 (22.05) 1.6 (0.06) M8 40 (88.18)
6 F510-4125-□3 344 (13.54) 580 (22.83) 300 (11.81) 250 (9.84) 560 (22.05) 1.6 (0.06) M8 40 (88.18)
7 F510-4150-E3/G3 344 (13.54) 580 (22.83) 300 (11.81) 250 (9.84) 560 (22.05) 1.6 (0.06) M8 40 (88.18)
8 F510-4150-H3/C3 459 (18.07) 790 (31.10) 324.5 (12.78) 320 (12.60) 760 (29.92) 1.6 (0.06) M10 74 (163.14)
9 F510-4175-□3 459 (18.07) 790 (31.10) 324.5 (12.78) 320 (12.60) 760 (29.92) 1.6 (0.06) M10 74 (163.14)
10 F510-4215-□3 459 (18.07) 790 (31.10) 324.5 (12.78) 320 (12.60) 760 (29.92) 1.6 (0.06) M10 74 (163.14)
11 F510-4250-□3 459 (18.07) 790 (31.10) 324.5 (12.78) 320 (12.60) 760 (29.92) 1.6 (0.06) M10 74 (163.14)

Manual — IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced — page 82

3-

(e) 200V: 60-125HP/ 400V: 100-250HP (Standard H & C type) 125~250HP (Enhanced E

& G type) (IP20)

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is present in the source table; no additional unlabeled drawing location is inferred.

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2060-□3

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2075-□3

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2100-□3

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2125-□3

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4100-H3/C3

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4125-□3

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4150-E3/G3

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4150-H3/C3

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4175-□3

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4215-□3

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4250-□3

IP20 dimensions:200V60–125HP;400V100–250HP standard or125–250HP enhanced table1 — PDF page 82

Source row Inverter Model W H D W1 H1 t d NW in kg(lbs)
1 F510-2060-□3 348.5 (13.72) 740 (29.13) 300 (11.81) 250 (9.84) 560 (22.05) 1.6 (0.06) M8 44 (97.00)
2 F510-2075-□3 348.5 (13.72) 740 (29.13) 300 (11.81) 250 (9.84) 560 (22.05) 1.6 (0.06) M8 44 (97.00)
3 F510-2100-□3 463.5 (18.25) 1105 (43.50) 324.5 (12.78) 320 (12.60) 760 (29.92) 1.6 (0.06) M10 81 (178.57)
4 F510-2125-□3 463.5 (18.25) 1105 (43.50) 324.5 (12.78) 320 (12.60) 760 (29.92) 1.6 (0.06) M10 81 (178.57)
5 F510-4100-H3/C3 348.5 (13.72) 740 (29.13) 300 (11.81) 250 (9.84) 560 (22.05) 1.6 (0.06) M8 44 (97.00)
6 F510-4125-□3 348.5 (13.72) 740 (29.13) 300 (11.81) 250 (9.84) 560 (22.05) 1.6 (0.06) M8 44 (97.00)
7 F510-4150-E3/G3 348.5 (13.72) 740 (29.13) 300 (11.81) 250 (9.84) 560 (22.05) 1.6 (0.06) M8 44 (97.00)
8 F510-4150-H3/C3 463.5 (18.25) 1105 (43.50) 324.5 (12.78) 320 (12.60) 760 (29.92) 1.6 (0.06) M10 81 (178.57)
9 F510-4175-□3 463.5 (18.25) 1105 (43.50) 324.5 (12.78) 320 (12.60) 760 (29.92) 1.6 (0.06) M10 81 (178.57)
10 F510-4215-□3 463.5 (18.25) 1105 (43.50) 324.5 (12.78) 320 (12.60) 760 (29.92) 1.6 (0.06) M10 81 (178.57)
11 F510-4250-□3 463.5 (18.25) 1105 (43.50) 324.5 (12.78) 320 (12.60) 760 (29.92) 1.6 (0.06) M10 81 (178.57)

Manual — IP00 dimensions:200V150–175HP;400V300–425HP — page 83

3-

(f) 200V: 150-175HP/ 400V: 300-425HP (IP00)

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is present in the source table; no additional unlabeled drawing location is inferred. W2 is the horizontal span from the central mounting position to the right-hand mounting position.

IP00 dimensions:200V150–175HP;400V300–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.

IP00 dimensions:200V150–175HP;400V300–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2150-□3

IP00 dimensions:200V150–175HP;400V300–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2175-□3

IP00 dimensions:200V150–175HP;400V300–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4300-□3

IP00 dimensions:200V150–175HP;400V300–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4375-□3

IP00 dimensions:200V150–175HP;400V300–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4425-□3

IP00 dimensions:200V150–175HP;400V300–425HP table1 — PDF page 83

Source row Inverter Model W H D W1 W2 H1 t d NW in kg(lbs)
1 F510-2150-□3 692 (27.24) 1000 (39.37) 410 (16.14) 530 (20.87) 265 (10.43) 960 (37.80) 1.6 (0.06) M12 184 (405.65)
2 F510-2175-□3 690 (27.17) 1000 (39.37) 410 (16.14) 530 (20.87) 265 (10.43) 960 (37.80) 1.6 (0.06) M12 184 (405.65)
3 F510-4300-□3 690 (27.17) 1000 (39.37) 410 (16.14) 530 (20.87) 265 (10.43) 960 (37.80) 1.6 (0.06) M12 184 (405.65)
4 F510-4375-□3 690 (27.17) 1000 (39.37) 410 (16.14) 530 (20.87) 265 (10.43) 960 (37.80) 1.6 (0.06) M12 184 (405.65)
5 F510-4425-□3 690 (27.17) 1000 (39.37) 410 (16.14) 530 (20.87) 265 (10.43) 960 (37.80) 1.6 (0.06) M12 184 (405.65)

Manual — IP20 dimensions:200V150–175HP;400V300–425HP — page 84

3-

(g) 200V: 150-175HP/ 400V: 300-425HP (IP20)

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is present in the source table; no additional unlabeled drawing location is inferred. W2 is the horizontal span from the central mounting position to the right-hand mounting position.

IP20 dimensions:200V150–175HP;400V300–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.

IP20 dimensions:200V150–175HP;400V300–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2150-□3

IP20 dimensions:200V150–175HP;400V300–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-2175-□3

IP20 dimensions:200V150–175HP;400V300–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4300-□3

IP20 dimensions:200V150–175HP;400V300–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4375-□3

IP20 dimensions:200V150–175HP;400V300–425HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4425-□3

IP20 dimensions:200V150–175HP;400V300–425HP table1 — PDF page 84

Source row Inverter Model W H D W1 W2 H1 t d NW in kg(lbs)
1 F510-2150-□3 692 (27.24) 1313 (51.69) 410 (16.14) 530 (20.87) 265 (10.43) 960 (37.80) 1.6 (0.06) M12 194 (427.70)
2 F510-2175-□3 692 (27.24) 1313 (51.69) 410 (16.14) 530 (20.87) 265 (10.43) 960 (37.80) 1.6 (0.06) M12 194 (427.70)
3 F510-4300-□3 692 (27.24) 1313 (51.69) 410 (16.14) 530 (20.87) 265 (10.43) 960 (37.80) 1.6 (0.06) M12 194 (427.70)
4 F510-4375-□3 692 (27.24) 1313 (51.69) 410 (16.14) 530 (20.87) 265 (10.43) 960 (37.80) 1.6 (0.06) M12 194 (427.70)
5 F510-4425-□3 692 (27.24) 1313 (51.69) 410 (16.14) 530 (20.87) 265 (10.43) 960 (37.80) 1.6 (0.06) M12 194 (427.70)

Manual — IP00 dimensions:400V535–800HP — page 85

3-

(h) 400V: 535-800HP (IP00)

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is the short rear offset/thickness callout in the side view. W2 is the left bottom mounting offset; W3 is the bottom mounting span. H2 is the upper pair mounting vertical span; H3 is the bottom offset. These labels are distinct from H/H1.

IP00 dimensions:400V535–800HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.

IP00 dimensions:400V535–800HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4535-□3

IP00 dimensions:400V535–800HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4670-□3

IP00 dimensions:400V535–800HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4800-□3

IP00 dimensions:400V535–800HP table1 — PDF page 85

Source row Inverter Model W H D W1 W2 W3 H1 H2 H3 t d NW in kg(lbs)
1 F510-4535-□3 958 (37.72) 1356 (53.38) 507 (19.96) 916 (36.06) 158 (6.22) 600 (23.62) 1200 (47.24) 300 (11.81) 63.5 (2.50) 6.2 (0.24) M12 335 (739)
2 F510-4670-□3 958 (37.72) 1356 (53.38) 507 (19.96) 916 (36.06) 158 (6.22) 600 (23.62) 1200 (47.24) 300 (11.81) 63.5 (2.50) 6.2 (0.24) M12 335 (739)
3 F510-4800-□3 958 (37.72) 1356 (53.38) 507 (19.96) 916 (36.06) 158 (6.22) 600 (23.62) 1200 (47.24) 300 (11.81) 63.5 (2.50) 6.2 (0.24) M12 335 (739)

Manual — IP20 dimensions:400V535–800HP — page 86

3-

(i) 400V: 535-800HP (IP20)

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is the short rear offset/thickness callout in the side view. W2 is the left bottom mounting offset; W3 is the bottom mounting span. H2 is the upper pair mounting vertical span; H3 is the bottom offset. These labels are distinct from H/H1.

IP20 dimensions:400V535–800HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.

IP20 dimensions:400V535–800HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4535-□3

IP20 dimensions:400V535–800HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4670-□3

IP20 dimensions:400V535–800HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4800-□3

IP20 dimensions:400V535–800HP table1 — PDF page 86

Source row Inverter Model W H D W1 W2 W3 H1 H2 H3 t d NW in kg(lbs)
1 F510-4535-□3 958 (37.72) 1756 (69.13) 507 (19.96) 916 (36.06) 158 (6.22) 600 (23.62) 1200 (47.24) 300 (11.81) 63.5 (2.50) 6.2 (0.24) M12 350 (772)
2 F510-4670-□3 958 (37.72) 1756 (69.13) 507 (19.96) 916 (36.06) 158 (6.22) 600 (23.62) 1200 (47.24) 300 (11.81) 63.5 (2.50) 6.2 (0.24) M12 350 (772)
3 F510-4800-□3 958 (37.72) 1756 (69.13) 507 (19.96) 916 (36.06) 158 (6.22) 600 (23.62) 1200 (47.24) 300 (11.81) 63.5 (2.50) 6.2 (0.24) M12 350 (772)

Manual — 3 — page 87

3-

3.7.2 Standard Type with Built-in Filter (IP00/IP20)

(a) 400V: 1-10HP

(b) 400V: 15-40HP

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is the short rear offset/thickness callout in the side view. Filter drawings add H2 (body-height callout) separately from H (total with filter extension) and H1 (mounting span). PDF87 lower drawing for400V15–40HP belongs to PDF88 first table; PDF88 lower drawing/table covers400V50–75HP.

3.7.2 Standard with built-in filter IP00/IP20 dimensions:400V1–10HP;15–40HP drawing continuesPDF88. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.

3.7.2 Standard with built-in filter IP00/IP20 dimensions:400V1–10HP;15–40HP drawing continuesPDF88. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4001-□3F

3.7.2 Standard with built-in filter IP00/IP20 dimensions:400V1–10HP;15–40HP drawing continuesPDF88. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4002-□3F

3.7.2 Standard with built-in filter IP00/IP20 dimensions:400V1–10HP;15–40HP drawing continuesPDF88. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4003-□3F

3.7.2 Standard with built-in filter IP00/IP20 dimensions:400V1–10HP;15–40HP drawing continuesPDF88. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4005-□3F

3.7.2 Standard with built-in filter IP00/IP20 dimensions:400V1–10HP;15–40HP drawing continuesPDF88. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4008-□3F

3.7.2 Standard with built-in filter IP00/IP20 dimensions:400V1–10HP;15–40HP drawing continuesPDF88. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4010-□3F

3.7.2 Standard with built-in filter IP00/IP20 dimensions:400V1–10HP;15–40HP drawing continuesPDF88 table1 — PDF page 87

Source row Inverter Model W H D W1 H1 H2 t d NW in kg(lbs)
1 F510-4001-□3F 130 (5.12) 306 (12.05) 150 (5.91) 118 (4.65) 203 (7.99) 215 (8.46) 5 M5 3.5 (7.71)
2 F510-4002-□3F 130 (5.12) 306 (12.05) 150 (5.91) 118 (4.65) 203 (7.99) 215 (8.46) 5 M5 3.5 (7.71)
3 F510-4003-□3F 130 (5.12) 306 (12.05) 150 (5.91) 118 (4.65) 203 (7.99) 215 (8.46) 5 M5 3.5 (7.71)
4 F510-4005-□3F 140 (5.51) 400 (15.75) 177 (6.97) 122 (4.80) 267 (10.51) 279 (10.98) 7 (0.28) M6 5.5 (12.13)
5 F510-4008-□3F 140 (5.51) 400 (15.75) 177 (6.97) 122 (4.80) 267 (10.51) 279 (10.98) 7 (0.28) M6 5.5 (12.13)
6 F510-4010-□3F 140 (5.51) 400 (15.75) 177 (6.97) 122 (4.80) 267 (10.51) 279 (10.98) 7 (0.28) M6 5.5 (12.13)

Manual — Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP — page 88

3-

(c) 400V: 50-75HP

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is present in the source table; no additional unlabeled drawing location is inferred. Filter drawings add H2 (body-height callout) separately from H (total with filter extension) and H1 (mounting span). PDF87 lower drawing for400V15–40HP belongs to PDF88 first table; PDF88 lower drawing/table covers400V50–75HP.

Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. 400V15–40HP:diagram is onPDF87.

Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. 400V15–40HP:diagram is onPDF87. Row group: F510-4015-□3F

Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. 400V15–40HP:diagram is onPDF87. Row group: F510-4020-□3F

Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. 400V15–40HP:diagram is onPDF87. Row group: F510-4025-□3F

Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. 400V15–40HP:diagram is onPDF87. Row group: F510-4030-□3F

Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. 400V15–40HP:diagram is onPDF87. Row group: F510-4040-□3F

Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.400V50–75HP.

Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.400V50–75HP. Row group: F510-4050-□3F

Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.400V50–75HP. Row group: F510-4060-□3F

Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.400V50–75HP. Row group: F510-4075-□3F

Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP table1 — PDF page 88

Source row Inverter Model W H D W1 H1 H2 t d NW in kg(lbs)
1 F510-4015-□3F 210 (8.27) 416.5 (16.40) 215 (8.46) 192 (7.56) 286 (11.26) 300 (11.81) 1.6 (0.06) M6 8.0 (17.64)
2 F510-4020-□3F 210 (8.27) 416.5 (16.40) 215 (8.46) 192 (7.56) 286 (11.26) 300 (11.81) 1.6 (0.06) M6 8.0 (17.64)
3 F510-4025-□3F 265 (10.43) 500 (19.69) 225 (8.86) 245 (9.65) 340 (13.39) 360 (14.17) 1.6 (0.06) M8 12.5 (27.56)
4 F510-4030-□3F 265 (10.43) 500 (19.69) 225 (8.86) 245 (9.65) 340 (13.39) 360 (14.17) 1.6 (0.06) M8 12.5 (27.56)
5 F510-4040-□3F 265 (10.43) 500 (19.69) 225 (8.86) 245 (9.65) 340 (13.39) 360 (14.17) 1.6 (0.06) M8 12.5 (27.56)

Standard with built-in filter IP00/IP20 dimensions:400V15–40HP and50–75HP table2 — PDF page 88

Source row Inverter Model W H D W1 H1 H2 t d NW in kg(lbs)
1 F510-4050-□3F 286.5 (11.28) 679 (26.73) 252 (9.92) 220 (8.66) 505 (19.88) 525 (20.67) 3.3 (0.13) M8 29.5 (65.04)
2 F510-4060-□3F 286.5 (11.28) 679 (26.73) 252 (9.92) 220 (8.66) 505 (19.88) 525 (20.67) 3.3 (0.13) M8 29.5 (65.04)
3 F510-4075-□3F 286.5 (11.28) 679 (26.73) 252 (9.92) 220 (8.66) 505 (19.88) 525 (20.67) 3.3 (0.13) M8 29.5 (65.04)

Manual — 3 — page 89

3-

3.7.3 Water proof Type (IP55)

(a) 400V: 1-25HP

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is the short rear offset/thickness callout in the side view.

3.7.3 Waterproof IP55 dimensions:400V1–25HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.

3.7.3 Waterproof IP55 dimensions:400V1–25HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4001-C3FN4

3.7.3 Waterproof IP55 dimensions:400V1–25HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4002-C3FN4

3.7.3 Waterproof IP55 dimensions:400V1–25HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4003-C3FN4

3.7.3 Waterproof IP55 dimensions:400V1–25HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4005-C3FN4

3.7.3 Waterproof IP55 dimensions:400V1–25HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4008-C3FN4

3.7.3 Waterproof IP55 dimensions:400V1–25HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4010-C3FN4

3.7.3 Waterproof IP55 dimensions:400V1–25HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4015-C3FN4

3.7.3 Waterproof IP55 dimensions:400V1–25HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4020-C3FN4

3.7.3 Waterproof IP55 dimensions:400V1–25HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4025-C3FN4

3.7.3 Waterproof IP55 dimensions:400V1–25HP table1 — PDF page 89

Source row Inverter Model W H D W1 H1 t d NW in kg(lbs)
1 F510-4001-C3FN4 189 (7.44) 284 (11.18) 186 (7.32) 171 (6.73) 266 (10.47) 1.2 (0.05) M5 5.1 (11.3)
2 F510-4002-C3FN4 189 (7.44) 284 (11.18) 186 (7.32) 171 (6.73) 266 (10.47) 1.2 (0.05) M5 5.1 (11.24)
3 F510-4003-C3FN4 189 (7.44) 284 (11.18) 186 (7.32) 171 (6.73) 266 (10.47) 1.2 (0.05) M5 5.1 (11.3)
4 F510-4005-C3FN4 189 (7.44) 284 (11.18) 186 (7.32) 171 (6.73) 266 (10.47) 1.2 (0.05) M5 5.1 (11.3)
5 F510-4008-C3FN4 189 (7.44) 284 (11.18) 186 (7.32) 171 (6.73) 266 (10.47) 1.2 (0.05) M5 5.1 (11.3)
6 F510-4010-C3FN4 230 (9.06) 320 (12.60) 210 (8.27) 210 (8.27) 305 (12.01) 2 (0.08) M5 8.6 (19.0)
7 F510-4015-C3FN4 230 (9.06) 320 (12.60) 210 (8.27) 210 (8.27) 305 (12.01) 2 (0.08) M5 8.6 (19.0)
8 F510-4020-C3FN4 265 (10.43) 396 (15.59) 227 (8.94) 249 (9.80) 380 (14.96) 2 (0.08) M5 17 (37.5)
9 F510-4025-C3FN4 265 (10.43) 396 (15.59) 227 (8.94) 249 (9.80) 380 (14.96) 2 (0.08) M5 17 (37.5)

Manual — Waterproof IP55 dimensions:400V30–100HP — page 90

3-

(b) 400V: 30-100HP

Front view: W is overall width, W1 is the mounting horizontal span; H is overall height, H1 is the mounting vertical span. Side view: D is overall depth. d identifies mounting-hole/slot fastener callout; the table retains M designations. Geometric interpretation must use the original drawing. t is the short rear offset/thickness callout in the side view.

Waterproof IP55 dimensions:400V30–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion.

Waterproof IP55 dimensions:400V30–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4030-C3FN4

Waterproof IP55 dimensions:400V30–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4040-C3FN4

Waterproof IP55 dimensions:400V30–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4050-C3FN4

Waterproof IP55 dimensions:400V30–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4060-C3FN4

Waterproof IP55 dimensions:400V30–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4075-C3N4

Waterproof IP55 dimensions:400V30–100HP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Dimensions in mm(inch);NW in kg(lbs). d is a source fastener designation (M5/M6/M8/M10/M12),not a scalar dimension or torque. The source square placeholder is retained literally; no variant expansion. Row group: F510-4100-C3N4

Waterproof IP55 dimensions:400V30–100HP table1 — PDF page 90

Source row Inverter Model W H D W1 H1 t d NW in kg(lbs)
1 F510-4030-C3FN4 224 (8.82) 527 (20.75) 311 (12.24) 180 (7.09) 505 (19.88) 2 (0.08) M10 32.5 (71.7)
2 F510-4040-C3FN4 224 (8.82) 527 (20.75) 311 (12.24) 180 (7.09) 505 (19.88) 2 (0.08) M10 32.5 (71.7)
3 F510-4050-C3FN4 224 (8.82) 527 (20.75) 311 (12.24) 180 (7.09) 505 (19.88) 2 (0.08) M10 32.5 (71.7)
4 F510-4060-C3FN4 326 (12.83) 695 (27.36) 343 (13.50) 276 (10.87) 671 (26.42) 2.3 (0.09) M10 55 (121.3)
5 F510-4075-C3N4 326 (12.83) 695 (27.36) 343 (13.50) 276 (10.87) 671 (26.42) 2.3 (0.09) M10 55 (121.3)
6 F510-4100-C3N4 326 (12.83) 695 (27.36) 343 (13.50) 276 (10.87) 671 (26.42) 2.3 (0.09) M10 55 (121.3)

Manual — 4 — page 91

Chapter 4 Keypad and Programming Functions

4.1 LED Keypad

4.1.1 Keypad Display and Keys

Top indicators left to right:FAULT,FWD,REV,SEQ,REF. REMOTE bracket groupsSEQ/REF; arrows distinguish external sequenceSEQ and external referenceREF. RUN button is green with run-status indicator;STOP button red with stop-status indicator. Eight membrane keys:LOC/REM,▲,DSP/FUN,◄/RESET,▼,READ/ENTER,RUN,STOP. The central display is5digit7segmentLED.

4.1 LED keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only.

4.1 LED keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: 5 Digit LED Display

4.1 LED keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: LED INDICATORS

4.1 LED keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: FAULT

4.1 LED keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: FWD

4.1 LED keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: REV

4.1 LED keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: SEQ

4.1 LED keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: REF

Shared source cells (coordinates refer to this table):

4.1 LED keypad display and indicators table1 — PDF page 91

Source row DISPLAY Description
1 5 Digit LED Display Monitor inverter signals, view / edit parameters, fault / alarm display.
2 LED INDICATORS ⟦null: no independent source value⟧
3 FAULT LED ON when a fault or alarm is active.
4 FWD LED ON when inverter is running in forward direction, flashing when stopping.
5 REV LED On when inverter is running in reverse direction, flashing when stopping.
6 SEQ LED ON when RUN command is from the external control terminals or from serial communication.
7 REF LED ON when Frequency Reference command is from the external control terminals or from serial communication.

Manual — LED keypad eight keys and local/remote operation — page 92

Auto-Repeat Keys

Holding the ▲UP or ▼DOWN key for a longer period of time will initiate the auto-repeat function

resulting in the value of the selected digit to automatically increase or decrease.

LED keypad eight keys and local/remote operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only.

LED keypad eight keys and local/remote operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: RUN

LED keypad eight keys and local/remote operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: STOP

LED keypad eight keys and local/remote operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: ▲

LED keypad eight keys and local/remote operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: ▼

LED keypad eight keys and local/remote operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: LOC/REM

LED keypad eight keys and local/remote operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: DSP/FUN

LED keypad eight keys and local/remote operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: ◄ / RESET

LED keypad eight keys and local/remote operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: READ / ENTER

LED keypad eight keys and local/remote operation table1 — PDF page 92

Source row KEYS (8) Description
1 RUN RUN inverter
2 STOP STOP inverter
3 ▲ Parameter navigation Up, Increase parameter or reference value
4 ▼ Parameter navigation down, decrease parameter or reference value
5 LOC/REM Used to switch between Local Mode and Remote Mode REMOTE Mode: Set by parameters, controlled by control circuit terminals, communication or other ways. LOCAL Mode: Controlled by operator. It displays REMOTE Mode at power-up. Users can switch between LOCAL and REMOTE Mode if they press LOC/ REM keys when the inverter stops. Parameter of 23-41 can determine if LOC/REM keys are enabled or not.
6 DSP/FUN Used to scroll to next screen Frequency screenFunction selectionMonitor parameter
7 ◄ / RESET Selects active seven segment digit for editing with the ▲▼ keys Used to reset fault condition.
8 READ / ENTER Used to read and save the value of the active parameter.

Manual — Seven-segment character correspondence and frequency-reference editing — page 93

4.1.2 Seven Segment Display Description

Display output frequency

Frequency Reference

Set Frequency Reference

At power-up, the display will show the frequency reference setting and all LEDs are flashing. Press

the ▲ (UP) or ▼ (DOWN) key to enter the frequency reference edit mode, use the ◄/RESET key

to select which digit to edit (flashing). Use the ▲ (UP) or ▼ (DOWN) key to modify the value and

press the READ / ENTER key to save the frequency reference and switch back to the frequency

reference display mode.

During run operation, the display will show the output frequency.

Note: When in edit mode and the READ / ENTER is not pressed within 5 sec, the inverter will switch

back to the frequency reference display mode.

Source Actual character '0' corresponds to seven-segment image: 0. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'A' corresponds to seven-segment image: A. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'L' corresponds to seven-segment image: L. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'Y' corresponds to seven-segment image: lowercase y. Glyph description is visual transcription,not a new parameter value.

Source Actual character '1' corresponds to seven-segment image: 1. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'B' corresponds to seven-segment image: lowercase b. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'n' corresponds to seven-segment image: lowercase n. Glyph description is visual transcription,not a new parameter value.

Source Actual character '-' corresponds to seven-segment image: middle horizontal bar. Glyph description is visual transcription,not a new parameter value.

Source Actual character '2' corresponds to seven-segment image: 2. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'C' corresponds to seven-segment image: C. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'o' corresponds to seven-segment image: 0-like full-height loop. Glyph description is visual transcription,not a new parameter value.

Source Actual character '°' corresponds to seven-segment image: small upper loop. Glyph description is visual transcription,not a new parameter value.

Source Actual character '3' corresponds to seven-segment image: 3. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'D' corresponds to seven-segment image: lowercase d. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'P' corresponds to seven-segment image: P. Glyph description is visual transcription,not a new parameter value.

Source Actual character '_' corresponds to seven-segment image: bottom horizontal bar. Glyph description is visual transcription,not a new parameter value.

Source Actual character '4' corresponds to seven-segment image: 4. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'E' corresponds to seven-segment image: E. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'q' corresponds to seven-segment image: q-like upper loop and right leg. Glyph description is visual transcription,not a new parameter value.

Source Actual character '.' corresponds to seven-segment image: decimal point. Glyph description is visual transcription,not a new parameter value.

Source Actual character '5' corresponds to seven-segment image: 5. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'F' corresponds to seven-segment image: F. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'r' corresponds to seven-segment image: lowercase r. Glyph description is visual transcription,not a new parameter value.

Source Actual character '6' corresponds to seven-segment image: 6. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'G' corresponds to seven-segment image: open-right G-like shape (top,left,bottom and lower-right segments). Glyph description is visual transcription,not a new parameter value.

Source Actual character 'S' corresponds to seven-segment image: 5-like. Glyph description is visual transcription,not a new parameter value.

Source Actual character '7' corresponds to seven-segment image: 7. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'H' corresponds to seven-segment image: H. Glyph description is visual transcription,not a new parameter value.

Source Actual character 't' corresponds to seven-segment image: lowercase t. Glyph description is visual transcription,not a new parameter value.

Source Actual character '8' corresponds to seven-segment image: 8. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'I' corresponds to seven-segment image: 1-like vertical strokes. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'u' corresponds to seven-segment image: lowercase u. Glyph description is visual transcription,not a new parameter value.

Source Actual character '9' corresponds to seven-segment image: 9. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'J' corresponds to seven-segment image: J. Glyph description is visual transcription,not a new parameter value.

Source Actual character 'V' corresponds to seven-segment image: full-height U-like. Glyph description is visual transcription,not a new parameter value.

Display output frequency:example005.00;steady illuminated LEDs. Flashing is indicated by black rays.

Frequency Reference:example005.00;all digits flashing. Flashing is indicated by black rays.

Set Frequency Reference:example005.00;only active digit flashing. Flashing is indicated by black rays.

Seven-segment character correspondence and frequency-reference editing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information.

Seven-segment character correspondence and frequency-reference editing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: 0

Seven-segment character correspondence and frequency-reference editing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: 1

Seven-segment character correspondence and frequency-reference editing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: 2

Seven-segment character correspondence and frequency-reference editing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: 3

Seven-segment character correspondence and frequency-reference editing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: 4

Seven-segment character correspondence and frequency-reference editing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: 5

Seven-segment character correspondence and frequency-reference editing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: 6

Seven-segment character correspondence and frequency-reference editing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: 7

Seven-segment character correspondence and frequency-reference editing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: 8

Seven-segment character correspondence and frequency-reference editing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: 9

Seven-segment character correspondence and frequency-reference editing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group:

Seven-segment character correspondence and frequency-reference editing table1 — PDF page 93

Source row Actual LED Display Actual LED Display Actual LED Display Actual LED Display
1 0 ⟦blank source cell⟧ A ⟦blank source cell⟧ L ⟦blank source cell⟧ Y ⟦blank source cell⟧
2 1 ⟦blank source cell⟧ B ⟦blank source cell⟧ n ⟦blank source cell⟧ - ⟦blank source cell⟧
3 2 ⟦blank source cell⟧ C ⟦blank source cell⟧ o ⟦blank source cell⟧ ° ⟦blank source cell⟧
4 3 ⟦blank source cell⟧ D ⟦blank source cell⟧ P ⟦blank source cell⟧ _ ⟦blank source cell⟧
5 4 ⟦blank source cell⟧ E ⟦blank source cell⟧ q ⟦blank source cell⟧ . ⟦blank source cell⟧
6 5 ⟦blank source cell⟧ F ⟦blank source cell⟧ r ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
7 6 ⟦blank source cell⟧ G ⟦blank source cell⟧ S ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
8 7 ⟦blank source cell⟧ H ⟦blank source cell⟧ t ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
9 8 ⟦blank source cell⟧ I ⟦blank source cell⟧ u ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
10 9 ⟦blank source cell⟧ J ⟦blank source cell⟧ V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Seven-segment character correspondence and frequency-reference editing table2 — PDF page 93

Source row LED lights on LED flashes Flashing digit
1 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Seven-segment display examples and descriptions — page 94

LED Display Examples

Illustrative display glyphs:005.00. Meaning:frequency reference at power-up/output frequency running. Example only,not a rating,limit or default. Upper/lowercaseU/u approximate the seven-segment voltage glyph; original image retained.

Illustrative display glyphs:00-01. Meaning:parameter code. Example only,not a rating,limit or default. Upper/lowercaseU/u approximate the seven-segment voltage glyph; original image retained.

Illustrative display glyphs:00000. Meaning:parameter setting. Example only,not a rating,limit or default. Upper/lowercaseU/u approximate the seven-segment voltage glyph; original image retained.

Illustrative display glyphs:220u. Meaning:input voltage. Example only,not a rating,limit or default. Upper/lowercaseU/u approximate the seven-segment voltage glyph; original image retained.

Illustrative display glyphs:001.1A. Meaning:inverter current. Example only,not a rating,limit or default. Upper/lowercaseU/u approximate the seven-segment voltage glyph; original image retained.

Illustrative display glyphs:0310U. Meaning:DC bus voltage. Example only,not a rating,limit or default. Upper/lowercaseU/u approximate the seven-segment voltage glyph; original image retained.

Illustrative display glyphs:024°C. Meaning:temperature. Example only,not a rating,limit or default. Upper/lowercaseU/u approximate the seven-segment voltage glyph; original image retained.

Illustrative display glyphs:00000. Meaning:PIDfeedback;digits controlled by12-01. Example only,not a rating,limit or default. Upper/lowercaseU/u approximate the seven-segment voltage glyph; original image retained.

Illustrative display glyphs:Err1. Meaning:error example;see chapter5. Example only,not a rating,limit or default. Upper/lowercaseU/u approximate the seven-segment voltage glyph; original image retained.

Illustrative display glyphs: 000P. Meaning:AI1/AI2input0–100%. Example only,not a rating,limit or default. Upper/lowercaseU/u approximate the seven-segment voltage glyph; original image retained.

Seven-segment display examples and descriptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information.

Seven-segment display examples and descriptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group:

Seven-segment display examples and descriptions table1 — PDF page 94

Source row Seven Segment Display Description
1 ⟦blank source cell⟧ 1. Displays the frequency reference at power-up. 2. Displays the actual output frequency during run operation.
2 ⟦blank source cell⟧ Displays parameter code.
3 ⟦blank source cell⟧ Displays the setting value of parameter.
4 ⟦blank source cell⟧ Displays input voltage.
5 ⟦blank source cell⟧ Displays inverter current.
6 ⟦blank source cell⟧ Displays DC Bus Voltage.
7 ⟦blank source cell⟧ Displays temperature.
8 ⟦blank source cell⟧ Displays PID feedback value; The displayed digit is set by 12-01.
9 ⟦blank source cell⟧ Error display; refer to chapter 5 Troubleshooting and Maintenance.
10 ⟦blank source cell⟧ Displays AI1/ AI2 input (0~100%)

Manual — FAULT/FWD/REV/RUN indication states — page 95

4.1.3 LED Indicator Description

Fault LED

Forward LED

Reverse LED

RUN LED

FAULT LED image for stateOff: gray oval/off. Meaning:No Fault Active

FAULT LED image for stateIlluminated: solid red oval/illuminated. Meaning:Fault Active

FWD LED image for stateOff: gray oval/off. Meaning:Inverter in reverse direction

FWD LED image for stateIlluminated: solid red oval/illuminated. Meaning:Inverter is running in forward direction

FWD LED image for stateFlashing: red oval with rays/flashing. Meaning:Forward direction active, no run command

REV LED image for stateOff: gray oval/off. Meaning:Inverter in forward direction

REV LED image for stateIlluminated: solid red oval/illuminated. Meaning:Inverter is running in reverse direction

REV LED image for stateFlashing: red oval with rays/flashing. Meaning:Reverse direction active, no run command

RUN LED image for stateOff: gray oval/off. Meaning:Inverter stopped

RUN LED image for stateIlluminated: solid red oval/illuminated. Meaning:Inverter running

RUN LED image for stateFlashing: red oval with rays/flashing. Meaning:Inverter stopped or stopping

FAULT/FWD/REV/RUN indication states. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information.

FAULT/FWD/REV/RUN indication states. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: Off

FAULT/FWD/REV/RUN indication states. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: Illuminated

FAULT/FWD/REV/RUN indication states. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: Flashing

FAULT/FWD/REV/RUN indication states table1 — PDF page 95

Source row State Description FAULT LED
1 Off No Fault Active ⟦blank source cell⟧
2 Illuminated Fault Active ⟦blank source cell⟧

FAULT/FWD/REV/RUN indication states table2 — PDF page 95

Source row State Description FWD LED
1 Off Inverter in reverse direction ⟦blank source cell⟧
2 Illuminated Inverter is running in forward direction ⟦blank source cell⟧
3 Flashing Forward direction active, no run command ⟦blank source cell⟧

FAULT/FWD/REV/RUN indication states table3 — PDF page 95

Source row State Description REV LED
1 Off Inverter in forward direction ⟦blank source cell⟧
2 Illuminated Inverter is running in reverse direction ⟦blank source cell⟧
3 Flashing Reverse direction active, no run command ⟦blank source cell⟧

FAULT/FWD/REV/RUN indication states table4 — PDF page 95

Source row State Description RUN LED
1 Off Inverter stopped ⟦blank source cell⟧
2 Illuminated Inverter running ⟦blank source cell⟧
3 Flashing Inverter stopped or stopping ⟦blank source cell⟧

Manual — SEQ/REF states and RUN/STOP timeline — page 96

SEQ LED

REF LED

Run / Stop Status Indicators

SEQ LED image for stateOff: gray oval/off. Meaning:Sequence controlled from keypad

SEQ LED image for stateIlluminated: solid red oval/illuminated. Meaning:Sequence set from external source

REF LED image for stateOff: gray oval/off. Meaning:Frequency reference set from keypad

REF LED image for stateIlluminated: solid red oval/illuminated. Meaning:Frequency reference set from external source

Source timeline left to right: initiallySTOP,output frequency0,RUNindicatorOFF/STOPindicatorON;RUNcommand before frequency setting,RUNON/STOPflashing;after frequency setting and through acceleration/steady output,RUNON/STOPOFF;STOPcommand through deceleration,RUNflashing/STOPON;at zero output,RUNOFF/STOPON. Legend:redON,red with raysFlashing,pinkOFF. No numeric timing interval is printed.

SEQ/REF states and RUN/STOP timeline. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information.

SEQ/REF states and RUN/STOP timeline. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: Off

SEQ/REF states and RUN/STOP timeline. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Image-only glyph/state cells are retained as raw empty native strings,with visual correspondence in separate evidence;these are not absent source information. Row group: Illuminated

SEQ/REF states and RUN/STOP timeline table1 — PDF page 96

Source row State Description SEQ LED
1 Off Sequence controlled from keypad ⟦blank source cell⟧
2 Illuminated Sequence set from external source ⟦blank source cell⟧

SEQ/REF states and RUN/STOP timeline table2 — PDF page 96

Source row State Description REF LED
1 Off Frequency reference set from keypad ⟦blank source cell⟧
2 Illuminated Frequency reference set from external source ⟦blank source cell⟧

Manual — Display selection parameter12-00 and basic mode flow — page 97

4.1.4 Power-up Monitor

Power-up

Changing Monitor at Power-up

Example: 12- 00=【10000】

At power-up voltage-class illustration220u flashes;after3sec frequency reference005.00 flashes. DSP/FUN switches to parameter selection00-01 and back. Example12-00=10000:after3sec voltage-class display switches to output current;DSP/FUN cycles output current→frequency reference→parameter selection→output current. Values are illustrative.

Display selection parameter12-00 and basic mode flow. Exact source units/model/enclosure and qualifiers govern applicability; source claims only.

Display selection parameter12-00 and basic mode flow. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Range

Display selection parameter12-00 and basic mode flow table1 — PDF page 97

Source row 12- 00 Display Selection
1 Range Highest bit -> 0 0 0 0 0 <- Lowest bit The setting range for each bit is 0 ~ 7 from the highest bit to the lowest bit. 0: No display 4: Temperature 1: Output current 5: PID feedback 2: Output voltage 6: AI1 value 3: DC voltage 7: AI2 value

Manual — 12-00 expanded monitor selection and parameter-edit flow — page 98

Example: 12- 00=【12345】

4.1.5 Modifying Parameters/ Set Frequency Reference

Example: Modifying Parameters

After3sec voltage-class display220u switches to OutputCurrent<1>. DSP/FUN cycle:OutputCurrent<1>→FrequencyReference005.00→ParameterSelection00-01→OutputVoltage<2>→DCVoltage<3>→HeatsinkTemperature<4>→PIDFeedback<5>→OutputCurrent<1>. Each arrow isDSP/FUN;values are illustrative.

Example:FrequencyReference005.00→DSP/FUN→00-01;◄/RESETtwice cycles selected digit;▲changes code to00-02;READ/ENTERopens00001;▲changes value to00002;READ/ENTERsaves,display-End-flashes3sec,then00002;DSP/FUNreturns code00-02. This is source example,not a required configuration/default.

Manual — Frequency-reference editing while stopped/running — page 99

Example: Set Frequency Reference

Inverter stopped:

Inverter is running:

Note: When upper or lower limit is reached during editing of the frequency reference, the edit value will

automatically rollover from the lower limit to the upper limit or from the upper limit to the lower limit.

Stopped example:voltage class220u flashes3sec→reference005.00. ◄/RESETselects0.01Hz digit;further◄/RESETselects0.1Hz then1Hz. ▲at1Hzchanges005.00to006.00;READ/ENTERcompletes reference006.00. Side branch shows▲1xfrom005.00to005.01 and then▲1xback to005.00;this inconsistent source arrow is retained and flagged,not silently changed to▼.

Running example:power-up220u3sec→reference005.00;RUN1x→output005.00. ◄/RESET1xenters reference editing;subsequent◄/RESETselects0.1Hz then1Hz. ▲1xchanges005.00to006.00;READ/ENTER1x→output006.00. Diagram says automatically returns to output-frequency display if no modifications within5sec. Note says upper/lower edit limits wrap to opposite boundary.

Manual — 4.1.6 Operation Control — page 100

Qualitative diagram only; output-frequency geometry, duration, command edges and vertical boundaries remain original-only visual information. No numeric timing or frequency inferred.

Eight left-to-right indicator intervals, not one row per command. Literal red/grey/ray glyphs; no on/off/flashing interpretation added.

Source case retained; illustrative state diagram, not prescribed settings.

Glyph inventory only. Last two intervals are distinct; do not replace this four-indicator/eight-interval source with E510s two-LED/seven-interval diagram.

Adjacent source context — repeated to preserve continuation:

Diagram labels — PDF page 100

Source row Source label/context Source value
1 Status regions Stopped; Running; Stopping; Stopped
2 Trace Output Frequency
3 Command arrows left-to-right Power on; REV command; FWD command; RUN command; REV command; FWD command; Stop command
4 Indicator rows FWD Indicator; REV Indicator; RUN Indicator; STOP Indicator

Visible indicator glyphs by displayed interval — PDF page 100

Source row Interval left-to-right FWD glyph REV glyph RUN glyph STOP glyph
1 1 Red with rays Grey Grey Red
2 2 Grey Red with rays Grey Red
3 3 Red with rays Grey Grey Red
4 4 Red Grey Red Grey
5 5 Grey Red Red Grey
6 6 Red Grey Red Grey
7 7 Red Grey Red with rays Red
8 8 Red with rays Grey Grey Red

Manual — 4 — page 101

4.2 LCD keypad

4.2.1 Keypad Display and Keys

Top indicators left to right:FAULT,FWD,REV,SEQ,REF. REMOTE bracket groupsSEQ/REF; arrows distinguish external sequenceSEQ and external referenceREF. RUN button is green with run-status indicator;STOP button red with stop-status indicator. Eight membrane keys:LOC/REM,▲,DSP/FUN,◄/RESET,▼,READ/ENTER,RUN,STOP. The central display isLCD; this separate source page is retained.

4.2 LCD keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only.

4.2 LCD keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: LCD Display

4.2 LCD keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: LED INDICATORS

4.2 LCD keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: FAULT

4.2 LCD keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: FWD

4.2 LCD keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: REV

4.2 LCD keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: SEQ

4.2 LCD keypad display and indicators. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: REF

Shared source cells (coordinates refer to this table):

Adjacent source context — repeated to preserve continuation:

4.2 LCD keypad display and indicators table1 — PDF page 101

Source row DISPLAY Description
1 LCD Display Monitor inverter signals, view / edit parameters, fault / alarm display.
2 LED INDICATORS ⟦null: no independent source value⟧
3 FAULT LED ON when a fault or alarm is active.
4 FWD LED ON when inverter is running in forward direction, flashing when stopping.
5 REV LED On when inverter is running in reverse direction, flashing when stopping.
6 SEQ LED ON when RUN command is from the external control terminals or from serial communication.
7 REF LED ON when Frequency Reference command is from the external control terminals or from serial communication.

Manual — LCD keypad eight keys and optional HOA note — page 102

Auto-Repeat Keys

Holding the ▲UP or ▼DOWN key for a longer period of time will initiate the auto-repeat function

resulting in the value of the selected digit to automatically increase or decrease.

Note: HOA LCD keypad is available with an optional accessory.

LCD keypad eight keys and optional HOA note. Exact source units/model/enclosure and qualifiers govern applicability; source claims only.

LCD keypad eight keys and optional HOA note. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: RUN

LCD keypad eight keys and optional HOA note. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: STOP

LCD keypad eight keys and optional HOA note. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: ▲

LCD keypad eight keys and optional HOA note. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: ▼

LCD keypad eight keys and optional HOA note. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: LOC/REM

LCD keypad eight keys and optional HOA note. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: DSP/FUN

LCD keypad eight keys and optional HOA note. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: ◄ / RESET

LCD keypad eight keys and optional HOA note. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: READ / ENTER

LCD keypad eight keys and optional HOA note table1 — PDF page 102

Source row KEYS (8) Description
1 RUN RUN inverter
2 STOP STOP inverter
3 ▲ Parameter navigation Up, Increase parameter or reference value
4 ▼ Parameter navigation down, decrease parameter or reference value
5 LOC/REM Used to switch between Local Mode and Remote Mode REMOTE Mode: Set by parameters, controlled by control circuit terminals, communication or other ways. LOCAL Mode: Controlled by operator. It displays REMOTE Mode at power-up. Users can switch between LOCAL and REMOTE Mode if they press LOC/ REM keys when the inverter stops. Parameter of 23-41 can determine if LOC/REM keys are enabled or not.
6 DSP/FUN Used to scroll to next screen Frequence screenFunction selectionMonitor parameter
7 ◄ / RESET Selects active seven segment digit for editing with the ▲▼ keys Used to reset fault condition.
8 READ / ENTER Used to read and save the value of the active parameter.

Manual — LCD monitor/parameter/autotune modes and navigation — page 103

4.2.2 Keypad Menu Structure

Main Menu

The F510 inverter main menu consists of two main groups (modes). The DSP/FUN key is

used to switch between the monitor mode and the parameter group mode. Refer to Figure 4.2.2.1.

All the available parameter groups are listed in the Parameter Group Mode. Use the up and

down keys to select a group and press READ/ ENTER to access its parameters.

Fig. 4.2.2.1 Parameter Group Structure

Notes:

flux vector). Auto-tuning mode will not be displayed when the inverter is running or when a fault is active.

key.

Parameter Group Mode

Parameter Mode

Parameter Edit Mode

DSP

FUN

RUN

READ

ENTER

Auto-Tune Mode

Select parameter

Change parameter setting

Auto-tune motor

Select parameter group

PowerOn→Power-up→MonitorMode. DSP/FUN togglesMonitorMode↔ParameterGroupMode. Lower flow:ParameterGroupMode(select group)→READ/ENTER→ParameterMode(select parameter)→READ/ENTER→ParameterEditMode(change setting)→RUN→Auto-TuneMode(auto-tune motor);DSP/FUNreturns one level at each step. Source notes require auto-tune beforevectorcontrol and hideauto-tunemodewhile running/faulted;these remain source claims,not engineering approval.

LCD monitor/parameter/autotune modes and navigation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only.

LCD monitor/parameter/autotune modes and navigation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Monitor Mode

LCD monitor/parameter/autotune modes and navigation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Parameter Group Mode

LCD monitor/parameter/autotune modes and navigation table1 — PDF page 103

Source row Mode Description
1 Monitor Mode View inverter status, signals and fault data.
2 Parameter Group Mode Access to available parameter groups.

Manual — LCD monitor-mode navigation — page 104

Power ON

Monitor

Freq Ref

12-17=000.00Hz

12-18=0000.0A

12-16=005.00Hz

Flt Freq Ref

12-15=000.00Hz

Flt DC Voltage

00 Basic Func.

01 V/F Pattern.

02 Motor Parameter

Group

DSP

FUN

12-14=0000.0V

Monitor Mode

Parameter Group

Selection Mode

In monitor mode inverter signals can be monitored such as output frequency, output current

and output voltage, etc…) as well as fault information and fault trace. See Fig 4.2.2.2 for keypad

navigation.

Fig 4.2.2.2 Monitor Mode

Fig4.2.2.2:PowerONentersMonitorMode. Down-arrow cyclesFreqRef12-16=005.00Hz→FltFreqRef12-15=000.00Hz→FltDCVoltage12-14=0000.0V;up-arrow reverses. Each screen also shows12-17=000.00Hz and12-18=0000.0A below a dashed divider. DSP/FUNfrom each monitor screen opensParameterGroupSelection,showing00BasicFunc.,01V/FPattern.,02MotorParameter;DSP/FUNreturns toMonitorMode. Values are source display examples,not parameter defaults.

Manual — LCD programming-mode navigation — page 105

Programming Mode

In programming mode inverter parameters can be read or changed. See Fig 4.2.2.3 for

keypad navigation.

Power ON

DSP

FUN

READ

ENT ER

As the above

parameter setting

Monitor

Freq Ref

12-17=000.00Hz

12-18=0000.0A

12-16=005.00Hz

Control Method

Edit 00-00

0 V/F

(0~4)

<0>

Motor Direction

0 Forward

(0~1)

Run Source

0 Digital Op

<1>

Edit 00-01

Edit 00-02

Group

01 V/F Pattern

02 Motor Parameter

00 Basic Func.

00 Basic Fun.

PARA 00

-00 Control Method

-01 Motor Direction

-02 Run Source

Parameter Group

Selection Mode

Parameter

Group Mode

Edit Mode

Press▼ / ▲ to

edit the setting

value or

READ/ENTER

to save the

changes.

Monitor Mode

Fig 4.2.2.3 Programming Mode

Notes:

and < / RESET shift key.

DSP/FUN key.

DSP/FUN in the parameter edit mode, it will return to the previous screen of parameter group mode;

when pressing DSP/FUN in the parameter group mode, it will return to the previous screen of

parameter group selection mode.

Fig4.2.2.3:Monitor→DSP/FUN→ParameterGroupSelection. ▲/▼select00BasicFunc./01V/FPattern/02MotorParameter. READ/ENTERopensParameterGroupMode;▲/▼select00-00ControlMethod,00-01MotorDirection,00-02RunSource. READ/ENTERopensEditMode;▲/▼and◄/RESETedit;READ/ENTERsaves. DSP/FUNreturnsEdit→GroupMode→GroupSelection→Monitor. Example00-00displays0V/F,(0~4),<0>;00-01displays0Forward,(0~1),<0>;00-02displays0DigitalOp,(0~4),<1>. Refersection4.4forparameterdetails. Display range0~4for00-00conflicts withsummaryoption5;retained as illustration.

Manual — LCD parameter-group screen labels — page 106

Language

Parameter Code

Setting Value

Parameter Group

Selection Mode

Group G01-01

Parameter Name

0 English

(0~0)

<0>

Setting Range

Default Value

Fig 4.2.2.4 Parameter Group Selection Mode Screen

Fig4.2.2.4:top-leftGroup is ParameterGroupSelectionMode;top-rightG01-01 is ParameterCode;Language is ParameterName;0English isSettingValue;(0~0)isSettingRange;<0>isDefaultValue. This source screen illustration differs from00-04LanguageSelectionrange0–3inPDF108;neither is silently rewritten.

Manual — Parameter groups00–24 and attribute/version legend — page 107

4.3 Parameters

Parameter-group list runs00through24,including19Reserved. Right-hand Note1–Note9version legend is one separate merged cell,not a row-by-row pairing with left-hand 1– 10attributes. Note9V1.58is blue. All attributes and version notes are explicitly attached to subsequent table contexts;O/X/dash remain source marks,not inferred certification.

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only.

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 00

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 01

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 02

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 03

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 04

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 05

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 06

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 07

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 08

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 09

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 10

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 11

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 12

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 13

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 14

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 15

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 16

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 17

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 18

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 19

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 20

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 21

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 22

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 23

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: Group 24

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: *1

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: *2

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: *3

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: *4

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: *5

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: 6 7

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: *8

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: *9

Parameter groups00–24 and attribute/version legend. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Row group: *10

Shared source cells (coordinates refer to this table):

Parameter groups00–24 and attribute/version legend table1 — PDF page 107

Source row Parameter Group Name
1 Group 00 Basic Parameters
2 Group 01 V/F Control Parameters
3 Group 02 IM Motor Parameters
4 Group 03 External Digital Input and Output Parameters
5 Group 04 External Analog Input and Output Parameters
6 Group 05 Multi-Speed Parameters
7 Group 06 Automatic Program Operation Parameters
8 Group 07 Start/ Stop Parameters
9 Group 08 Protection Parameters
10 Group 09 Communication Parameters
11 Group 10 PID Parameters
12 Group 11 Auxiliary Parameters
13 Group 12 Monitoring Parameters
14 Group 13 Maintenance Parameters
15 Group 14 PLC Setting Parameters
16 Group 15 PLC Monitoring Parameters
17 Group 16 LCD Parameters
18 Group 17 IM Motor Automatic Tuning Parameters
19 Group 18 Slip Compensation Parameters
20 Group 19 Reserved
21 Group 20 Speed Control Parameters
22 Group 21 Torque Control Parameters
23 Group 22 PM Motor Parameters
24 Group 23 Pump & HVAC
25 Group 24 1 to 8 Pump Card Function Group

Parameter groups00–24 and attribute/version legend table2 — PDF page 107

Source row Attribute symbol Meaning Software-version notes (merged independent list)
1 *1 Parameters can be changed during run operation Note1: New added or modified parameters in V1.41 Note2: New added or modified parameters in V1.43 Note3: New added or modified parameters in V1.50 Note4: New added or modified parameters in V1.51 Note5: New added or modified parameters in V1.52 Note6: New added or modified parameters in V1.53 Note7: Parameter edit available for V1.53 above Note8: New added or modified parameters in V1.55 Note9: New added or modified parameters in V1.58
2 *2 Read-only parameters for communication ⟦null: no independent source value⟧
3 *3 Parameter will not reset to default during a factory reset ⟦null: no independent source value⟧
4 *4 Read-only parameter ⟦null: no independent source value⟧
5 *5 Only displayed in using LED keypad ⟦null: no independent source value⟧
6 *6 *7 Modified(*6) and New added (*7) parameters in software V1.4 ⟦null: no independent source value⟧
7 *8 The value will be modified depend on the setting of 13-08 ⟦null: no independent source value⟧
8 *9 For enhanced E type & G type only ⟦null: no independent source value⟧
9 *10 Only available after I/O expansion card installed ⟦null: no independent source value⟧

Manual — Parameter summary:group00 — page 108

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-00

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-01

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-02

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-03

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-04

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-05

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-06

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-07

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-08

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-09

Shared source cells (coordinates refer to this table):

Parameter summary:group00 table1 — PDF page 108

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 00-00 Control Mode Selection 0: V/F 0 - O O O *3
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: SLV ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3~4: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: PM SLV ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 00-01 Motor’s Rotation Direction 0: Forward 0 - O O O *1
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Reverse ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 00-02 Main Run Command Source Selection 0: Keypad 1 - O O O ⟦blank source cell⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: External Terminal (Control Circuit) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Communication Control (RS-485) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: PLC ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: RTC ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 00-03 Alternative Run Command Source Selection 0: Keypad 0 - O O O ⟦blank source cell⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: External Terminal (Control Circuit) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Communication Control (RS-485) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: PLC ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: RTC ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 00-04 Language Selection (for LCD only) 0: English 0 - O O O ⟦blank source cell⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Simple Chinese ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Traditional Chinese ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Turkish ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 00-05 Main Frequency Command Source Selection 0: Keypad 1 - O O O ⟦blank source cell⟧
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: External Terminal (Analog AI1) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
24 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Terminal Command UP/ DOWN ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Communication Control (RS-485) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
28 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: RTC ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
29 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7. AI2 Auxiliary Frequency *7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
30 00-06 Alternative Frequency Command Source Selection 0: Keypad 0 - O O O ⟦blank source cell⟧
31 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: External Terminal (Analog) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
32 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Terminal Command UP/ DOWN ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
33 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Communication Control (RS-485) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
34 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
35 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
36 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: RTC ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
37 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7. AI2 Auxiliary Frequency *7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
38 00-07 Main and Alternative Frequency Command Modes 0: Main Frequency 0 - O O O ⟦blank source cell⟧
39 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Main Frequency + Alternative Frequency ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
40 00-08 Communication Frequency Command Range 0.00-599.00 (Note8) 0.00 Hz O O O ⟦blank source cell⟧
41 00-09 Communication Frequency Command Memory Selection 0: Do not save when power is off. 0 - O O O ⟦blank source cell⟧
42 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Save when power is off. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Parameter summary:group00 — page 109

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-10

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-11

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-12

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-13

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-14

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-15

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-16

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-17

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-18

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-19

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-20

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-21

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-22

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-23

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-24

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-25

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-26

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-27

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-28

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-29

~

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-32

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-33

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-34

Shared source cells (coordinates refer to this table):

Parameter summary:group00 table1 — PDF page 109

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 00-10 Minimum frequency detection 0: Show warning if lower than minimum frequency 1: Run as minimum frequency if lower than minimum frequency 0 - O O O Note2
2 00-11 Selection of PID Lower Limit Frequency 0: PID is bound to lower limit frequency when inverter sleeps. 0 - O O O Note1
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: PID is bound to 0Hz when inverter sleeps. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 00-12 Upper Limit Frequency 0.1~109.0 100.0 % O O O ⟦blank source cell⟧
5 00-13 Lower Limit Frequency 0.0~109.0 0.0 % O O O ⟦blank source cell⟧
6 00-14 Acceleration Time 1 0.1~6000.0 - s O O O *1
7 00-15 Deceleration Time 1 0.1~6000.0 - s O O O *1
8 00-16 Acceleration Time 2 0.1~6000.0 - s O O O *1
9 00-17 Deceleration Time 2 0.1~6000.0 - s O O O *1
10 00-18 Jog Frequency 0.00~599.00 (Note8) 6.00 Hz O O O *1
11 00-19 Jog Acceleration Time 0.1~0600.0 - s O O O *1
12 00-20 Jog Deceleration Time 0.1~0600.0 - s O O O *1
13 00-21 Acceleration Time 3 0.1~6000.0 - s O O O *1
14 00-22 Deceleration Time 3 0.1~6000.0 - s O O O *1
15 00-23 Acceleration Time 4 0.1~6000.0 - s O O O *1
16 00-24 Deceleration Time 4 0.1~6000.0 - s O O O *1
17 00-25 Switch-Over Frequency of Acc/Dec Time 1 and Time 4 0.0~599.00 (Note8) 0.0 Hz O O O ⟦blank source cell⟧
18 00-26 Emergency Stop Time 0.1~6000.0 5.0 s O O O ⟦blank source cell⟧
19 00-27 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 00-28 Main Frequency Command Characteristic Selection 0: Positive Characteristic (0~10V/4~20mA is corresponding to 0~100%) 0 - O O O ⟦blank source cell⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Negative Characteristic (0~10V/4~20mA is corresponding to 100~0%) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 00-29 ~ 00-31 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 00-32 Application Selection Presets 0: General 0 - O O O ⟦blank source cell⟧
24 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Water Supply Pump ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Conveyor *7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Exhaust fan ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: HVAC ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
28 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: Compressor *7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
29 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
30 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
31 00-33 Modified Parameters (only for LCD) 0: Enable 0 - O O O ⟦blank source cell⟧
32 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Disable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
33 00-34 ~ 00-40 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Parameter summary:group00/01 — page 110

00-41through00-56share instructionSet13-06=1,enablerange00-01~24-17except00-41~00-56andgroup17,LCDonly. Group01keeps200V/400Vrowsseparate;50.0/60.0defaults and*8dependenceon13-08remainliteral. V/F,SLV,PMSLVcolumnsretainownO/Xmarks.

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-41

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-42

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-43

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-44

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-45

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-46

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-47

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-48

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-49

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-50

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-51

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-52

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-53

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-54

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-55

Group 00 Basic Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 00-56

Shared source cells (coordinates refer to this table):

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-00

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-01

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-02

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-03

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-04

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-05

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-06

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-07

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-08

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-09

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-10

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-11

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-12

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-13

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-14

Group 01 V/F Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 01-15

Parameter summary:group00/01 table1 — PDF page 110

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 00-41 User Parameter 0 Set 13-06 = 1, and enable user parameter. Setting Range: 00-01 ~24-17, but except 00-41~00-56 and group 17 (only used in LCD keypad) - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
2 00-42 User Parameter 1 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
3 00-43 User Parameter 2 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
4 00-44 User Parameter 3 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
5 00-45 User Parameter 4 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
6 00-46 User Parameter 5 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
7 00-47 User Parameter 6 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
8 00-48 User Parameter 7 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
9 00-49 User Parameter 8 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
10 00-50 User Parameter 9 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
11 00-51 User Parameter 10 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
12 00-52 User Parameter 11 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
13 00-53 User Parameter 12 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
14 00-54 User Parameter 13 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
15 00-55 User Parameter 14 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧
16 00-56 User Parameter 15 ⟦null: no independent source value⟧ - ⟦blank source cell⟧ O O O ⟦blank source cell⟧

Parameter summary:group00/01 table2 — PDF page 110

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 01-00 V/F Curve Selection 0~FF F - O X X *3
2 01-01 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 01-02 Maximum Output Frequency 4.8~599.00 (Note8) 50.0/ 60.0 Hz O O O *6*8
4 01-03 Maximum Output Voltage 200V: 0.1~255.0 - V O X X *8
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 0.2~510.0 - ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 01-04 Middle Output Frequency 2 0.0~599.00 (Note8) 0.0 Hz O X X ⟦blank source cell⟧
7 01-05 Middle Output Voltage 2 200V: 0.0~255.0 0.0 V O X X *8
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 0.0~510.0 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 01-06 Middle Output Frequency 1 0.0~599.00 (Note8) 30.0 Hz O X X ⟦blank source cell⟧
10 01-07 Middle Output Voltage 1 200V: 0.0~255.0 38.5 V O X X *8
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 0.0~510.0 77.0 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 01-08 Minimum Output Frequency 0.0~599.00 (Note8) 1.5 Hz O O O ⟦blank source cell⟧
13 01-09 Minimum Output Voltage 200V: 0.0~255.0 6.6 V O X X *8
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 0.0~510.0 13.2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 01-10 Torque Compensation Gain 0.0~2.0 0.5 - O X X *1
16 01-11 Selection of Torque Compensation Mode 0: Torque Compensation Mode 0 0 - O X X Note1
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Torque Compensation Mode 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 01-12 Base Frequency 4.8~599.00 (Note8) 50.0/ 60.0 Hz O O O *8
19 01-13 Base Output Voltage 200V: 0.0~255.0 - V O X X *8
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 0.0~510.0 - ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 01-14 Input Voltage Setting 200V: 155.0~255.0 - V O O O *8
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 310.0~510.0 - ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 01-15 Torque Compensation Time 0~10000 200 ms O X X ⟦blank source cell⟧

Manual — Parameter summary:group02/03 — page 111

Left-hand parameter entries:S1=03-00/default0;S2=03-01/default1;S3=03-02/default2;S4=03-03/default3;S5=03-04/default4;S6=03-05/default17onPDF112. Separate setting-option column begins0Forward2-wire,1Reverse2-wireandcontinues through69onPDF113. This preserves source layout;do notbindoptionstoonecodebynearesttext.

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-00

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-01

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-02

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-03

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-04

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-05

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-06

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-07

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-08

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-09

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-10

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-11

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-12

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-13

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-14

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-15

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-19

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-20

~

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-33

Group 02 IM Motor Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 02-34

Shared source cells (coordinates refer to this table):

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations.

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. Row group: Parallel DI columns:code/default per merged span;shared optionlistPDF111–113;no exclusive nearest-row binding

Parameter summary:group02/03 table1 — PDF page 111

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 02-00 No-Load Current 0.01~600.00 KVA A O X X ⟦blank source cell⟧
2 02-01 Rated Current 25%~200% of inverter’s rated current. KVA A O O X ⟦blank source cell⟧
3 02-02 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 02-03 Rated Rotation Speed 0~60000 KVA Rpm O O X ⟦blank source cell⟧
5 02-04 Rated Voltage 200V: 50.0~240.0 - V O O X *8
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 100.0~480.0 - ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 02-05 Rated Power 0.01~600.00 KVA kW O O X ⟦blank source cell⟧
8 02-06 Rated Frequency 4.8~599.00 (Note8) 50.0/ 60.0 Hz O O X *8
9 02-07 Poles 2~16 (Even) 4 pole- O O X *6
10 02-08 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 02-09 Excitation Current 15.0~70.0 KVA % X O X ⟦blank source cell⟧
12 02-10 Core Saturation Coefficient 1 1~100 KVA % X O X ⟦blank source cell⟧
13 02-11 Core Saturation Coefficient 2 1~100 KVA % X O X ⟦blank source cell⟧
14 02-12 Core Saturation Coefficient 3 80~300 KVA % X O X ⟦blank source cell⟧
15 02-13 Core Loss 0.0~15.0 KVA % O X X ⟦blank source cell⟧
16 02-14 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 02-15 Resistance between Wires 0.001~60.000 KVA Ω O O X ⟦blank source cell⟧
18 02-19 No-Load Voltage 200V: 50~240 KVA V X O X ⟦blank source cell⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 100~480 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 02-20 ~ 02-32 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 02-33 Leakage Inductance Ratio 0.1~15.0 KVA % X O X ⟦blank source cell⟧
22 02-34 Slip Frequency 0.10~20.00 KVA Hz X O X ⟦blank source cell⟧

Parameter summary:group02/03 table2 — PDF page 111

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 03-00 Multi-function Terminal Function Setting-S1 0: 2-Wire Sequence (ON: Forward Run Command) 0 - O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: 2-Wire Sequence (ON: Reverse Run Command) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
3 03-01 Multi-function Terminal Function Setting-S2 2: Multi-Speed Setting Command 1 1 ⟦null: no independent source value⟧ O O O ⟦blank source cell⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Multi-Speed Setting Command 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Multi-Speed Setting Command 3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
6 03-02 Multi-function Terminal Function Setting-S3 5: Multi-Speed Setting Command 4 2 ⟦null: no independent source value⟧ O O O *6
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: Forward Jog Run Command ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
8 03-03 Multi-function Terminal Function Setting-S4 7: Reverse Jog Run Command 3 ⟦null: no independent source value⟧ O O O *6
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8: UP Frequency Increasing Command ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
10 03-04 Multi-function Terminal Function Setting-S5 9: DOWN Frequency Decreasing Command 4 ⟦null: no independent source value⟧ O O O *6
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10: Acceleration/ Deceleration Setting Command 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 11: Acceleration/ Deceleration Inhibition Command ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧

Manual — Parameter summary:group03 — page 112

PDF112continuesDIsettingoptions12through64fromPDF111. S6/03-05/default17spansleftcolumns;default17appears twiceinsourcewithinthatspan. Control-mode O/X/-marks belong to corresponding optionrow;reservedrangesremainliteral. Option65/66~67/68/69continuePDF113.

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations.

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. Row group: Parallel DI columns:code/default per merged span;shared optionlistPDF111–113;no exclusive nearest-row binding

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c5, r2c5, r3c5, r4c5, r5c5, r6c5. A header spans across these blank regions in the native text; no header value is propagated into them.

Parameter summary:group03 table1 — PDF page 112

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 03-05 Multi-function Terminal Function Setting-S6 12: Main/Alternative Run command Switching 17 ⟦null: no independent source value⟧ O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 13: Main/Alternative Frequency Command Switching ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 14: Emergency Stop (Decelerate to Zero and Stop) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 15: External Base block Command (Rotation freely to Stop) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 16: PID Control Disable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 17: Fault Reset (RESET) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 18: Reserved ⟦null: no independent source value⟧ - - - - ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 19: Speed Search 1(from the maximum frequency) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O X ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 20: Manual Energy Saving Function 17 ⟦null: no independent source value⟧ O X X ⟦blank source cell⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 21: PID Integral Reset ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 22~23: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 24: PLC Input ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 25: External Fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 26: 3-Wire Sequence (Forward/ Reverse Command) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 27: Local/ Remote Selection ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 28: Remote Mode Selection ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 29: Jog Frequency Selection ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 30: Acceleration/ Deceleration Setting Command 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 31: Inverter Overheating Warning ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 32: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 33: DC Braking ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O X X ⟦null: no independent source value⟧
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 34: Speed Search 2 (from Frequency Command) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O X O ⟦null: no independent source value⟧
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 35: Timing Function Input ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
24 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 36: PID Soft Start Disable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 37~40: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 41: PID Sleep ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 42~46: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
28 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 47: Fire Mode (Forced to Run Mode) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
29 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 48: KEB Acceleration ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O X X ⟦null: no independent source value⟧
30 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 49: Parameters Writing Allowable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
31 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 50: Unattended Start Protection (USP) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
32 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 51~52: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
33 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 53: 2-Wire Self Holding Mode (Stop Command) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
34 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 54: Switch PID1 and PID2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
35 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 55: RTC Time Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
36 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 56: RTC Offset Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
37 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 57: Forced Frequency Run ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
38 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 58: Run Permissive Function ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
39 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 63: switch to Tolerance Range of Constant Pressure 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
40 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 64: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦blank source cell⟧

Manual — Parameter summary:group03 — page 113

Firstfour rows65,66~67Reserved,68Ext.Fault2(Note6),69Ext.Overload(Note6)continueDIoptionlist.03-06/03-07Reservedthen03-08scanselection4/8ms(default1),03-09S1–S4contactbits,03-10S5–S6bits. Relayleftcodes03-11R1default1and03-12R2default0areseparatefromsharedoptionlist0through31continuing32through59onPDF114.03-13±03-14andcomparatorspreservedexactly.

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. Firstfour rows continueDI03-00–03-05optionlist fromPDF111–112;code/default blank continuations are not new parameters.

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. Firstfour rows continueDI03-00–03-05optionlist fromPDF111–112;code/default blank continuations are not new parameters. Row group: Parallel DI columns:code/default per merged span;shared optionlistPDF111–113;no exclusive nearest-row binding

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. Firstfour rows continueDI03-00–03-05optionlist fromPDF111–112;code/default blank continuations are not new parameters. Row group: 03-06

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. Firstfour rows continueDI03-00–03-05optionlist fromPDF111–112;code/default blank continuations are not new parameters. Row group: 03-08

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. Firstfour rows continueDI03-00–03-05optionlist fromPDF111–112;code/default blank continuations are not new parameters. Row group: 03-09

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. Firstfour rows continueDI03-00–03-05optionlist fromPDF111–112;code/default blank continuations are not new parameters. Row group: 03-10

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. Firstfour rows continueDI03-00–03-05optionlist fromPDF111–112;code/default blank continuations are not new parameters. Row group: Parallel relay columns:code/default per merged span;shared optionlistPDF113–114;no exclusive nearest-row binding

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c1, r1c2, r1c4, r1c5, r2c1, r2c2, r2c4, r2c5, r3c1, r3c2, r3c4, r4c1, r4c2, r4c4. A header spans across these blank regions in the native text; no header value is propagated into them.

Parameter summary:group03 table1 — PDF page 113

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 65: Short-circuit braking ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X X O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 66~67: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦blank source cell⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 68: Ext. Fault 2 (Note6) ⟦null: no independent source value⟧ ⟦blank source cell⟧ O O O ⟦blank source cell⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 69: Ext. Overload (Note6) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦blank source cell⟧
5 03-06 03-07 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 03-08 (S1~S6) DI Scan Time 0: Scan Time 4ms 1: Scan Time 8ms 1 - O O O ⟦blank source cell⟧
7 03-09 Multi-Function Terminal (S1-S4 Selection) xxx0b:S1 A Contact xxx1b:S1 B Contact 0000b - O O O ⟦blank source cell⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx0xb:S2 A Contact xx1xb:S2 B Contact ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x0xxb:S3 A Contact x1xxb:S3 B Contact ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0xxxb:S4 A Contact 1xxxb:S4 B Contact ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 03-10 Multi-Function Terminal (S5-S6 Selection) xxx0b:S5 A Contact xxx1b:S5 B Contact 0000b - O O O ⟦blank source cell⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx0xb:S6 A Contact xx1xb:S6 B Contact ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x0xxb: Reserved x1xxb: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0xxxb: Reserved 1xxxb: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 03-11 Relay (R1A-R1C) Output 0: During Running 1 - O O O *6
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Fault Contact Output ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Frequency Agree ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 03-12 Relay (R2A-R2C) Output 3: Setting Frequency Agree (03-13 ± 03-14) 0 - O O O *6
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Frequency Detection 1 (≧03-13+03-14) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: Frequency Detection 2 (<03-13+03-14) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: Automatic Restart ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7~8: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9: Baseblock ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
24 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10~11: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 12: Over-Torque Detection ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 13: Current Agree *7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 14: Mechanical Brake Control (03-17~18)Note1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
28 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 15~17: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
29 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 18: PLC Status ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
30 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 19: PLC Control ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
31 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 20: Zero Speed ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
32 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 21: Inverter Ready ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
33 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 22: Undervoltage Detection ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
34 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 23: Source of Operation Command ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
35 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 24: Source of Frequency Command ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
36 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 25: Low Torque Detection ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
37 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 26: Frequency Reference Missing ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
38 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 27: Timing Function Output ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
39 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 28~31: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧

Manual — Parameter summary:group03 — page 114

Topoptions32–59continue03-11/03-12listfromPDF113;blankleft/defaultcellsarenewpagecontinuations,notunknownnewparameters.03-19contactbitlabelsR1/R2/R3/R4withR4 10.03-20R4default2and03-21DO2-DOGdefault3eachuse03-11/03-12rangeand 10.03-39onPDF115R3default20explicitlyusessamerange.

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. First23option rows continue relayoutput03-11/03-12list fromPDF113;code/default blank continuations are not new parameters.

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. First23option rows continue relayoutput03-11/03-12list fromPDF113;code/default blank continuations are not new parameters. Row group: Parallel relay columns:code/default per merged span;shared optionlistPDF113–114;no exclusive nearest-row binding

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. First23option rows continue relayoutput03-11/03-12list fromPDF113;code/default blank continuations are not new parameters. Row group: 03-13

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. First23option rows continue relayoutput03-11/03-12list fromPDF113;code/default blank continuations are not new parameters. Row group: 03-14

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. First23option rows continue relayoutput03-11/03-12list fromPDF113;code/default blank continuations are not new parameters. Row group: 03-15

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. First23option rows continue relayoutput03-11/03-12list fromPDF113;code/default blank continuations are not new parameters. Row group: 03-16

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. First23option rows continue relayoutput03-11/03-12list fromPDF113;code/default blank continuations are not new parameters. Row group: 03-17

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. First23option rows continue relayoutput03-11/03-12list fromPDF113;code/default blank continuations are not new parameters. Row group: 03-18

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. First23option rows continue relayoutput03-11/03-12list fromPDF113;code/default blank continuations are not new parameters. Row group: 03-19

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. First23option rows continue relayoutput03-11/03-12list fromPDF113;code/default blank continuations are not new parameters. Row group: 03-20

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Shared setting-option columns and parameter-code/default columns have independent vertical spans. Do not interpret one visual row as exclusive option applicability to adjacent code. DIoptionlist acrossPDF111–113;relayoutputoptionlist acrossPDF113–114. See explicit visual associations. First23option rows continue relayoutput03-11/03-12list fromPDF113;code/default blank continuations are not new parameters. Row group: 03-21

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c1, r1c2, r1c4, r1c5, r1c9, r2c1, r2c2, r2c4, r2c5, r2c9, r3c1, r3c2, r3c4, r3c5, r3c9, r4c1, r4c2, r4c4, r4c5, r4c9, r5c1, r5c2, r5c4, r5c5, r5c9, r6c1, r6c2, r6c4, r6c5, r6c9, r7c1, r7c2, r7c4, r7c5, r7c9, r8c1, r8c2, r8c4, r8c5, r8c9, r9c1, r9c2, r9c4, r9c5, r9c9, r10c1, r10c2, r10c4, r10c5, r10c9, r11c1, r11c2, r11c4, r11c5, r11c9, r12c1, r12c2, r12c4, r12c5, r12c9, r13c1, r13c2, r13c4, r13c5, r13c9, r14c1, r14c2, r14c4, r14c5, r14c9, r15c1, r15c2, r15c4, r15c5, r15c9, r16c1, r16c2, r16c4, r16c5, r16c9, r17c1, r17c2, r17c4, r17c5, r17c9, r18c1, r18c2, r18c4, r18c5, r18c9, r19c1, r19c2, r19c4, r19c5, r19c9, r20c1, r20c2, r20c4, r20c5, r20c9, r21c1, r21c2, r21c4, r21c5, r21c9, r22c1, r22c2, r22c4, r22c5, r22c9, r23c1, r23c2, r23c4, r23c5, r23c9. A header spans across these blank regions in the native text; no header value is propagated into them.

Parameter summary:group03 table1 — PDF page 114

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 32: Communication Control Contacts ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 33: RTC Timer 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 34: RTC Timer 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 35: RTC Timer 3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 36: RTC Timer 4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 37: Detection Output of PID Feedback Loss *7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 38: Brake Release *7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X O X ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 42: Over-High Pressure Note1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O X X ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 43: Over-Low Pressure Note1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O X X ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 44: Loss of Pressure Detection Note1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O X X ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 45: PID Sleep Note1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 46: Over-High Flow Note1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 47: Over-Low Flow Note1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 48: Shortage of Low Suction Note1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 49: Communication Error Note2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 50: Frequency Detection 3 Note2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 51: Frequency Detection 4 Note2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 52: Frequency Detection 5 Note2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 53: Frequency Detection 6 Note2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 54: Turn on short-circuit braking Note2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X X O ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 57: Low Current Detection Note3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 58: Frequency Deceleration DetectionNote5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 59: Over Temperature Detection Note6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
24 03-13 Frequency Detection Level 0.0~599.00 (Note8) 0.0 Hz O O O ⟦blank source cell⟧
25 03-14 Frequency Detection Width 0.1~25.5 2.0 Hz O O O ⟦blank source cell⟧
26 03-15 Current Agree Level 0.1~999.9 0.1 A O O O *7
27 03-16 Delay Time of Current Agree Detection 0.1~10.0 0.1 s X O X *7
28 03-17 Setting of Mechanical Brake Release LevelNote1 0.00~599.00 (Note8) 0.00 Hz O O O ⟦blank source cell⟧
29 03-18 Setting of Mechanical Brake Operation LevelNote1 0.00~599.00 (Note8) 0.00 Hz O O O ⟦blank source cell⟧
30 03-19 Relay(R1A-R3C)Type xxx0b: R1 A Contact xxx1b: R1 B Contact 0000b - O O O ⟦blank source cell⟧
31 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx0xb: R2 A Contact xx1xb: R2 B Contact ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
32 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x0xxb: R3 A Contact x1xxb: R3 B Contact ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
33 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0xxxb: R4 A Contact 1xxxb: R4 B Contact ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ *10
34 03-20 Relay (R4A-R4C) Output Range and definition are the same as those of 03-11, 03-12 2 - O O O *10
35 03-21 Photo-coupler Output Selection (DO2-DOG) Range and definition are the same as those of 03-11, 03-12 3 - O O O *10

Manual — Parameter summary:group03 — page 115

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-22

~

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-27

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-28

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-29

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-30

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-31

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-32

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-33

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-34

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-35

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-37

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-38

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-39

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-40

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-41

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-42

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-43

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-44

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-45

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-46

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-47

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-48

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-49

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-50

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-51

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-52

Group 03 External Digital Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 03-53

Shared source cells (coordinates refer to this table):

Parameter summary:group03 table1 — PDF page 115

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 03-22 ~ 03-26 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 03-27 UP/DOWN Frequency Hold/ Adjust Selection 0: Keep UP/DOWN frequency when stopping. 0 - O O O ⟦blank source cell⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Clear UP/DOWN frequency when stopping. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Allow frequency UP/DOWN when stopping. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Refresh frequency at acceleration. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 03-28 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 03-29 Photo-coupler Output Selection (DO2-DOG) xx0xb: Photo-coupler 2 A Contact xx1xb: Photo-coupler 2 B Contact 0000b - O O O *10
8 03-30 Pulse Input Selection 0: Common Pulse Input 0 - O O O *7
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: PWM (Pulse Width Modulation) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 03-31 Pulse Input Scaling 50~32000 1000 Hz O O O *1
11 03-32 Pulse input gain 0.0~1000.0 100 % O O O *1
12 03-33 Pulse input bias -100.0~100.0 0.0 % O O O *1
13 03-34 Pulse input filter time 0.00~2.00 0.1 Sec O O O *1
14 03-35 03-36 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 03-37 Timer ON Delay (DI/DO) 0.0~6000.0 0.0 s O O O ⟦blank source cell⟧
16 03-38 Timer OFF Delay (DI/DO) 0.0~6000.0 0.0 s O O O ⟦blank source cell⟧
17 03-39 Relay (R3A-R3C) Output Setting range and definition are the same as those of 03-11 and 03-12. 20 - O O O ⟦blank source cell⟧
18 03-40 Up/down Frequency Width Setting 0.00~5.00 0.00 Hz O O O *7
19 03-41 Torque Detection Level 0~150 10 % X O X *7
20 03-42 Delay Time of Braking Action 0.00~65.00 0.00 s X O X *7
21 03-43 UP/DOWN Acceleration/ Deceleration Selection 0: Acceleration/ Deceleration Time 1 0 - O O O Note1
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Acceleration/ Deceleration Time 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 03-44 Frequency Detection Level 2 0.0~599.00 (Note8) 0.0 Hz O O O Note2
24 03-45 Frequency Detection Width 2 0.1~25.5 2.0 Hz O O O Note2
25 03-46 Frequency Detection Level 3 0.0~599.00 (Note8) 0.0 Hz O O O Note2
26 03-47 Frequency Detection Width 3 0.1~25.5 2.0 Hz O O O Note2
27 03-48 Low Current Detection Level 0.0~999.9 0.1 A O O O Note3
28 03-49 Low Current Detection Delay Time 0.00~655.34 (Note6) 0.01 Sec O O O Note3
29 03-50 Frequency Detection Level 4 0.0~599.00 (Note8) 0.0 Hz O O O Note4
30 03-51 Frequency Detection Level 5 0.0~599.00 (Note8) 0.0 Hz O O O Note4
31 03-52 Frequency Detection Level 6 0.0~599.00 (Note8) 0.0 Hz O O O Note4
32 03-53 Current Agree Level 2 0.0~999.9 0.0 A O O O Note6

Manual — Parameter summary:group04 — page 116

04-00choices0,1,4,5specifydistinctAI1/AI2voltage/currentcombinations;2/3reserved. Options4and5onlycarry 9.04-05AI2functionoptionshaveindividualV/F/SLV/PMSLVmarks;04-10AI3functionpointsbackto04-05butretainsdefault10and 10.

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-00

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-01

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-02

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-03

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-04

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-05

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-06

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-07

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-08

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-09

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-10

Shared source cells (coordinates refer to this table):

Parameter summary:group04 table1 — PDF page 116

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 04-00 AI Input Signal Type 0: AI1: 0~10V AI2: 0~10V 1 - O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: AI1: 0~10V AI2: 4~20mA ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: AI1: 4~20mA AI2: 0~10V ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ *9
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: AI1: 4~20mA AI2: 4~20mA ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ *9
7 04-01 AI1 Signal Scanning and Filtering Time 0.00~2.00 0.03 s O O O ⟦blank source cell⟧
8 04-02 AI1 Gain 0.0~1000.0 100.0 % O O O *1
9 04-03 AI1 Bias -100.0~100.0 0 % O O O *1
10 04-04 Negative AI 0: Disable 0 - O O O Note6
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 04-05 AI2 Function Setting 0: Auxiliary Frequency 0 - O O O ⟦blank source cell⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Frequency Reference Gain ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Frequency Reference Bias ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Output Voltage Bias ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O X O ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Coefficient of Acceleration and Deceleration Reduction ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: DC Braking Current ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O X ⟦null: no independent source value⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: Over-Torque Detection Level ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7: Stall Prevention Level During Running ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O X X ⟦null: no independent source value⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8: Frequency Lower Limit ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9: Jump Frequency 4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10: Added to AI1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 11: Positive Torque Limit ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X O O ⟦null: no independent source value⟧
24 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 12: Negative Torque Limit ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X O O ⟦null: no independent source value⟧
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 13: Regenerative Torque Limit ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X O O ⟦null: no independent source value⟧
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 14: Positive / Negative Torque Limit ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X O O ⟦null: no independent source value⟧
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 15: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
28 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 16: Torque Compensation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X O X ⟦null: no independent source value⟧
29 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 17: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
30 04-06 AI2 Signal Scanning and Filtering Time 0.00~2.00 0.03 s O O O ⟦blank source cell⟧
31 04-07 AI2 Gain 0.0~1000.0 100.0 % O O O *1
32 04-08 AI2 Bias -100.0~100.0 0 % O O O *1
33 04-09 AI Input Signal Type of I/O card 0: AI3:0~10V 1: AI3:-10~10V 2: AI3:4~20mA 0 - O O O *10
34 04-10 AI3 Function Setting Range and definition are the same as those of 04-05 10 - O O O *10

Manual — Parameter summary:group04 — page 117

04-11AO1functionoptions0–28retainreservedrangesandoption-specificcontrol-modecells.04-16AO2uses04-11rangebutdefault3insteadAO1default0.04-19fourAO1/AO2voltage/currentcombinationsareseparate;AI3scan/gain/bias04-21–23retain*10.

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-11

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-12

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-13

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-14

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-16

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-17

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-18

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-19

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-20

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-21

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-22

Group 04 External Analog Input and Output Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 04-23

Shared source cells (coordinates refer to this table):

Parameter summary:group04 table1 — PDF page 117

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 04-11 AO1 Function Setting 0: Output Frequency 0 - O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Frequency Command ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Output Voltage ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: DC Voltage ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Output Current ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: Output Power ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: Motor Speed ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7: Output Power Factor ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8: AI1 Input ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9: AI2 Input ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10: Torque Command ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X O O ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 11: q-axis Current ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X O O ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 12: d-axis Current ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X O O ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 13: Speed deviation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X X O ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 14: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 15: ASR Output ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X X O ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 16: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 17: q-axis Voltage ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X O O ⟦null: no independent source value⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 18: d-axis Voltage ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ X O O ⟦null: no independent source value⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 19~20: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 21: PID Input ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 22: PID Output ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 23: PID Target Value ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
24 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 24: PID Feedback Value ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 25: Output Frequency of the Soft Starter ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 26~27: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - ⟦null: no independent source value⟧
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 28: Communication Control *6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
28 04-12 AO1 Gain 0.0~1000.0 100.0 % O O O *1
29 04-13 AO1 Bias -100.0~100.0 0 % O O O *1
30 04-14 04-15 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
31 04-16 AO2 Function Setting Setting range and definition are the same as 04-11 3 - O O O ⟦blank source cell⟧
32 04-17 AO2 Gain 0.0~1000.0 100.0 % O O O *1
33 04-18 AO2 Bias -100.0~100.0 0 % O O O *1
34 04-19 AO Output Signal Type 0: AO1:0~10V AO2:0~10V 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
35 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: AO1:0~10V AO2:4~20mA ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
36 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: AO1:4~20mA AO2:0~10V ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
37 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: AO1:4~20mA AO2: 4~20mA ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
38 04-20 Filter Time of AO Signal Scan 0.00~0.50 0.00 s O O O *1 *7
39 04-21 AI3 Signal Scanning and Filtering Time 0.00~2.00 0.03 s O O O *10
40 04-22 AI3 Gain 0.0~1000.0 100.0 % O O O *10
41 04-23 AI3 Bias -100.0~100.0 0 % O O O *10

Manual — Parameter summary:group05 — page 118

05-00selectsacceleration/decelerationfrom00-14~00-24or05-17~05-48.05-01–05-16arefrequencysettingsforstages0–15withdistinctdefaults.05-17–05-48pairedacceleration/decelerationsettingscoverstages0–15acrossPDF118–120,eachrange0.1~6000.0s/default10.0. No stage omitted orcollapsed.

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-00

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-01

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-02

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-03

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-04

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-05

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-06

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-07

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-08

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-09

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-10

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-11

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-12

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-13

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-14

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-15

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-16

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-17

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-18

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-19

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-20

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-21

Shared source cells (coordinates refer to this table):

Parameter summary:group05 table1 — PDF page 118

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 05-00 Acceleration and Deceleration Selection of Multi-Speed 0: Acceleration and deceleration time are set by 00-14 ~ 00-24 0 - O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Acceleration and Deceleration Time are set by 05-17 ~ 05-48 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 05-01 Frequency Setting of Speed-Stage 0 0.00~599.00 (Note8) 5.00 Hz O O O *1
4 05-02 Frequency Setting of Speed- Stage 1 0.00~599.00 (Note8) 5.00 Hz O O O *7
5 05-03 Frequency Setting of Speed- Stage 2 0.00~599.00 (Note8) 10.00 Hz O O O *7
6 05-04 Frequency Setting of Speed- Stage 3 0.00~599.00 (Note8) 20.00 Hz O O O *7
7 05-05 Frequency Setting of Speed- Stage 4 0.00~599.00 (Note8) 30.00 Hz O O O *7
8 05-06 Frequency Setting of Speed- Stage 5 0.00~599.00 (Note8) 40.00 Hz O O O *7
9 05-07 Frequency Setting of Speed- Stage 6 0.00~599.00 (Note8) 50.00 Hz O O O *7
10 05-08 Frequency Setting of Speed- Stage 7 0.00~599.00 (Note8) 50.00 Hz O O O *7
11 05-09 Frequency Setting of Speed- Stage 8 0.00~599.00 (Note8) 5.00 Hz O O O *7
12 05-10 Frequency Setting of Speed- Stage 9 0.00~599.00 (Note8) 5.00 Hz O O O *7
13 05-11 Frequency Setting of Speed- Stage 10 0.00~599.00 (Note8) 5.00 Hz O O O *7
14 05-12 Frequency Setting of Speed- Stage 11 0.00~599.00 (Note8) 5.00 Hz O O O *7
15 05-13 Frequency Setting of Speed- Stage 12 0.00~599.00 (Note8) 5.00 Hz O O O *7
16 05-14 Frequency Setting of Speed- Stage 13 0.00~599.00 (Note8) 5.00 Hz O O O *7
17 05-15 Frequency Setting of Speed- Stage 14 0.00~599.00 (Note8) 5.00 Hz O O O *7
18 05-16 Frequency Setting of Speed- Stage 15 0.00~599.00 (Note8) 5.00 Hz O O O *7
19 05-17 Acceleration Time Setting of Multi Speed 0 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
20 05-18 Deceleration Time Setting of Multi Speed 0 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
21 05-19 Acceleration Time Setting of Multi Speed 1 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
22 05-20 Deceleration Time Setting of Multi Speed 1 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
23 05-21 Acceleration Time Setting of Multi Speed 2 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧

Manual — Parameter summary:group05 — page 119

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-22

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-23

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-24

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-25

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-26

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-27

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-28

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-29

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-30

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-31

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-32

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-33

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-34

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-35

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-36

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-37

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-38

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-39

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-40

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-41

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-42

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-43

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-44

Parameter summary:group05 table1 — PDF page 119

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 05-22 Deceleration Time Setting of Multi Speed 2 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
2 05-23 Acceleration Time Setting of Multi Speed 3 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
3 05-24 Deceleration Time Setting of Multi Speed 3 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
4 05-25 Acceleration Time Setting of Multi Speed 4 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
5 05-26 Deceleration Time Setting of Multi Speed 4 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
6 05-27 Acceleration Time Setting of Multi Speed 5 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
7 05-28 Deceleration Time Setting of Multi Speed 5 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
8 05-29 Acceleration Time Setting of Multi Speed 6 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
9 05-30 Deceleration Time Setting of Multi Speed 6 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
10 05-31 Acceleration Time Setting of Multi Speed 7 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
11 05-32 Deceleration Time Setting of Multi Speed 7 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
12 05-33 Acceleration Time Setting of Multi Speed 8 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
13 05-34 Deceleration Time Setting of Multi Speed 8 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
14 05-35 Acceleration Time Setting of Multi Speed 9 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
15 05-36 Deceleration Time Setting of Multi Speed 9 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
16 05-37 Acceleration Time Setting of Multi Speed 10 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
17 05-38 Deceleration Time Setting of Multi Speed 10 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
18 05-39 Acceleration Time Setting of Multi Speed 11 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
19 05-40 Deceleration Time Setting of Multi Speed 11 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
20 05-41 Acceleration Time Setting of Multi Speed 12 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
21 05-42 Deceleration Time Setting of Multi Speed 12 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
22 05-43 Acceleration Time Setting of Multi Speed 13 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
23 05-44 Deceleration Time Setting of Multi Speed 13 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧

Manual — Parameter summary:group05/06 — page 120

05-45–05-48finishmultispeedstage14/15acceleration/deceleration. Group06startsat06-00withchoices0–6;V/FandSLVmarkedO,PMSLVX.06-01–15frequencysettingsareoperationstages1–15;06-16–31timesand06-32–47directionscoverstages0–15. Sourceindexdifferencepreservedwithoutinventingfrequency-stage0parameter.

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-45

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-46

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-47

Group 05 Multi-Speed Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 05-48

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-00

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-01

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-02

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-03

Shared source cells (coordinates refer to this table):

Parameter summary:group05/06 table1 — PDF page 120

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 05-45 Acceleration Time Setting of Multi Speed 14 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
2 05-46 Deceleration Time Setting of Multi Speed 14 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
3 05-47 Acceleration Time Setting of Multi Speed 15 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧
4 05-48 Deceleration Time Setting of Multi Speed 15 0.1~6000.0 10.0 s O O O ⟦blank source cell⟧

Parameter summary:group05/06 table2 — PDF page 120

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 06-00 Automatic Operation Mode Selection 0: Disable 0 - O O X ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Execute a single cycle operation mode. Restart speed is based on the previous stopped speed. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Execute continuous cycle operation mode. Restart speed is based on the previous stopped speed. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: After the completion of a single cycle, the on-going operation speed is based on the speed of the last stage. Restart speed is based on the previous stopped speed. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Execute a single cycle operation mode. Restart speed will be based on the speed of stage 1. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: Execute continuous cycle operation mode. Restart speed will be based on the speed of stage 1. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: After the completion of a single cycle, the on-going operation speed is based on the speed of the last stage. Restart speed is based on the previous stopped speed. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 06-01 Frequency Setting of Operation-Stage 1 0.00~599.00 (Note8) 5.00 Hz O O X *1
9 06-02 Frequency Setting of Operation -Stage 2 0.00~599.00 (Note8) 10.00 Hz O O X *1
10 06-03 Frequency Setting of Operation -Stage 3 0.00~599.00 (Note8) 20.00 Hz O O X *1

Manual — Parameter summary:group06 — page 121

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-04

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-05

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-06

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-07

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-08

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-09

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-10

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-11

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-12

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-13

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-14

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-15

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-16

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-17

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-18

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-19

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-20

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-21

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-22

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-23

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-24

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-25

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-26

Parameter summary:group06 table1 — PDF page 121

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 06-04 Frequency Setting of Operation -Stage 4 0.00~599.00 (Note8) 30.00 Hz O O X *1
2 06-05 Frequency Setting of Operation -Stage 5 0.00~599.00 (Note8) 40.00 Hz O O X *1
3 06-06 Frequency Setting of Operation -Stage 6 0.00~599.00 (Note8) 50.00 Hz O O X *1
4 06-07 Frequency Setting of Operation -Stage 7 0.00~599.00 (Note8) 50.00 Hz O O X *1
5 06-08 Frequency Setting of Operation -Stage 8 0.00~599.00 (Note8) 5.00 Hz O O X *1
6 06-09 Frequency Setting of Operation -Stage 9 0.00~599.00 (Note8) 5.00 Hz O O X *1
7 06-10 Frequency Setting of Operation -Stage 10 0.00~599.00 (Note8) 5.00 Hz O O X *1
8 06-11 Frequency Setting of Operation -Stage 11 0.00~599.00 (Note8) 5.00 Hz O O X *1
9 06-12 Frequency Setting of Operation -Stage 12 0.00~599.00 (Note8) 5.00 Hz O O X *1
10 06-13 Frequency Setting of Operation -Stage 13 0.00~599.00 (Note8) 5.00 Hz O O X *1
11 06-14 Frequency Setting of Operation -Stage 14 0.00~599.00 (Note8) 5.00 Hz O O X *1
12 06-15 Frequency Setting of Operation -Stage 15 0.00~599.00 (Note8) 5.00 Hz O O X *1
13 06-16 Time Setting of Operation -Stage 0 0.0~6000.0 0.0 s O O X *1
14 06-17 Time Setting of Operation -Stage 1 0.0~6000.0 0.0 s O O X *1
15 06-18 Time Setting of Operation -Stage 2 0.0~6000.0 0.0 s O O X *1
16 06-19 Time Setting of Operation -Stage 3 0.0~6000.0 0.0 s O O X *1
17 06-20 Time Setting of Operation -Stage 4 0.0~6000.0 0.0 s O O X *1
18 06-21 Time Setting of Operation -Stage 5 0.0~6000.0 0.0 s O O X *1
19 06-22 Time Setting of Operation -Stage 6 0.0~6000.0 0.0 s O O X *1
20 06-23 Time Setting of Operation -Stage 7 0.0~6000.0 0.0 s O O X *1
21 06-24 Time Setting of Operation -Stage 8 0.0~6000.0 0.0 s O O X *1
22 06-25 Time Setting of Operation -Stage 9 0.0~6000.0 0.0 s O O X *1
23 06-26 Time Setting of Operation -Stage 10 0.0~6000.0 0.0 s O O X *1

Manual — Parameter summary:group06 — page 122

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-27

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-28

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-29

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-30

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-31

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-32

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-33

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-34

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-35

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-36

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-37

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-38

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-39

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-40

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-41

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-42

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-43

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-44

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-45

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-46

Group 06 Automatic Program Operation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 06-47

Parameter summary:group06 table1 — PDF page 122

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 06-27 Time Setting of Operation -Stage 11 0.0~6000.0 0.0 s O O X *1
2 06-28 Time Setting of Operation -Stage 12 0.0~6000.0 0.0 s O O X *1
3 06-29 Time Setting of Operation -Stage 13 0.0~6000.0 0.0 s O O X *1
4 06-30 Time Setting of Operation -Stage 14 0.0~6000.0 0.0 s O O X *1
5 06-31 Time Setting of Operation -Stage 15 0.0~6000.0 0.0 s O O X *1
6 06-32 Direction Selection of Operation -Stage 0 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
7 06-33 Direction Selection of Operation -Stage 1 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
8 06-34 Direction Selection of Operation -Stage 2 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
9 06-35 Direction Selection of Operation -Stage 3 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
10 06-36 Direction Selection of Operation -Stage 4 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
11 06-37 Direction Selection of Operation -Stage 5 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
12 06-38 Direction Selection of Operation -Stage 6 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
13 06-39 Direction Selection of Operation -Stage 7 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
14 06-40 Direction Selection of Operation -Stage 8 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
15 06-41 Direction Selection of Operation -Stage 9 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
16 06-42 Direction Selection of Operation -Stage 10 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
17 06-43 Direction Selection of Operation -Stage 11 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
18 06-44 Direction Selection of Operation -Stage 12 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
19 06-45 Direction Selection of Operation -Stage 13 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
20 06-46 Direction Selection of Operation -Stage 14 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧
21 06-47 Direction Selection of Operation -Stage 15 0: Stop 1: Forward 2: Reverse 0 - O O X ⟦blank source cell⟧

Manual — Parameter summary:group07 — page 123

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-00

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-01

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-02

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-03

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-04

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-05

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-06

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-07

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-08

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-09

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-10

~

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-13

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-14

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-15

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-16

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-17

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-18

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-19

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-20

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-21

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-22

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-23

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-24

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-25

Shared source cells (coordinates refer to this table):

Parameter summary:group07 table1 — PDF page 123

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 07-00 Momentary Power Loss/ Fault Restart Selection 0: Disable 0 - O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 07-01 Fault Auto-Restart Time 0~7200 0 s O O O ⟦blank source cell⟧
4 07-02 Number of Fault Auto-Restart Attempts 0~10 0 - O O O ⟦blank source cell⟧
5 07-03 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 07-04 Direct Start at Power on 0: When the external run command is enabled, direct start at power up 1 - O O O ⟦blank source cell⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: When the external run command is enabled, unable to direct start at power-up. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 07-05 Automatic start delay at power up 1.0~300.0 3.5 Sec O O O ⟦blank source cell⟧
9 07-06 DC Injection Braking Start Frequency 0.0~10.0 0.5 Hz O O O ⟦blank source cell⟧
10 07-07 DC Injection Braking Current 0~100 50 % O O O ⟦blank source cell⟧
11 07-08 DC Injection Braking Time at Stop 0.00~10.00 0.50 s O O O ⟦blank source cell⟧
12 07-09 Stop Mode Selection 0: Deceleration to Stop 0 - O O O ⟦blank source cell⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Coast to Stop ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: DC Braking Stop ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O X ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Coast to Stop with Timer ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ O O O ⟦null: no independent source value⟧
16 07-10 ~ 07-12 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 07-13 Low Voltage Detection Level 200V: 150~300 190 V O O O ⟦blank source cell⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 300~600 380 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 07-14 Pre-excitation Time 0.00~10.00 2.00 s X O X ⟦blank source cell⟧
20 07-15 Pre-excitation Level 50~200 100 % X O X *6
21 07-16 DC Injection Braking Time at Start 0.00~100.00 0.00 s O O O ⟦blank source cell⟧
22 07-17 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 07-18 Minimum Base block Time 0.1~5.0 - Sec O O O ⟦blank source cell⟧
24 07-19 Direction-Detection Speed Search Operating Current 0~100 50 % O O X ⟦blank source cell⟧
25 07-20 Speed Search Operating Current 0~100 20 % O O X ⟦blank source cell⟧
26 07-21 Integral Time of Speed Searching 0.1~10.0 2.0 Sec O O X ⟦blank source cell⟧
27 07-22 Delay Time of Speed Searching 0.0~20.0 0.2 Sec O O X ⟦blank source cell⟧
28 07-23 Voltage Recovery Time 0.1~5.0 2.0 Sec O O X ⟦blank source cell⟧
29 07-24 Direction-Detection Speed Search Selection 0: Disable 1 - O O X ⟦blank source cell⟧
30 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
31 07-25 Low voltage Detection Time 0.00~1.00 0.02 Sec O O O ⟦blank source cell⟧

Manual — Parameter summary:group07 — page 124

07-34/35/36short-circuitbrakingand07-43/44PMspeedsearchbrakingarePMSLV-onlysourceOmarks.07-47PMSpeedSwitchingFrequencyModeisblue,choices0Disabled/1Mode1/2Mode2,default0,PMSLVO,V/FandSLVX,Note9V1.58. Sourcefirmwarequalifierretained.

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-26

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-27

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-28

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-29

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-30

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-32

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-33

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-34

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-35

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-36

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-42

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-43

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-44

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-45

Group 07: Start /Stop Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 07-47

Shared source cells (coordinates refer to this table):

Parameter summary:group07 table1 — PDF page 124

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 07-26 SLV Speed Search Function 0: Enable 0 - X O X ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Disable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 07-27 Start Selection after Fault during SLV Mode 0: Speed search start 0 - X O X ⟦blank source cell⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Normal Start ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 07-28 Start Selection after External Base Block 0: Speed search start 0 - X O X ⟦blank source cell⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Normal Start ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 07-29 Run Command Available during DC Braking 0: Disable (Run command isn’t available until the DC braking is completely done) 0 - O X X Note1
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 07-30 07-31 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 07-32 Speed Search Mode Selection 0: Disable 1: Mode1: Start a Speed Search at Power on 2: Mode 2: Start Speed Search upon the Motor Run 0 ⟦blank source cell⟧ O O O Note2
11 07-33 Start Frequency of Speed Search Selection 0: Maximum Output Frequency of Motor 1: Frequency Command 0 ⟦blank source cell⟧ O O X Note2
12 07-34 Short-circuit Braking Time at Start 0.00~100.00 0 Sec X X O Note2
13 07-35 Short-circuit Braking Time at Stop 0.00~100.00 0.5 Sec X X O Note2
14 07-36 Short-circuit Braking Current Limited Level 0.0~200.0 100 % X X O Note2
15 07-42 Voltage limit gain 0.0~50.0 0 % X O X Note3
16 07-43 Short-circuit Braking Time of PM Motor Speed Search 0.00~100.00 0.00 Sec X X O Note4
17 07-44 DC Braking Time of PM Motor Speed Search 0.00~100.00 0.00 Sec X X O Note4
18 07-45 STP2 Function Selection 0:STP2 Enable 0 - O O O Note6
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1:STP2 Disable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 07-47 PM Speed Switching Frequency Mode 0: Disabled 0 - X X O Note9
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Mode 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Mode 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Parameter summary:group08 — page 125

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-00

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-01

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-02

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-03

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-04

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-05

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-06

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-07

Shared source cells (coordinates refer to this table):

Parameter summary:group08 table1 — PDF page 125

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 08-00 Stall Prevention Function xxx0b: Stall prevention is enabled in acceleration. 0000b - O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xxx1b: Stall prevention is disabled in acceleration. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx0xb: Stall prevention is enabled in deceleration. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx1xb: Stall prevention is disabled in deceleration. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x0xxb: Stall prevention is enabled in operation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x1xxb: Stall prevention is disabled in operation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0xxxb: Stall prevention in operation decelerates based on deceleration time 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1xxxb: Stall prevention in operation decelerates based on deceleration time 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 08-01 Stall Prevention Level in Acceleration 20~200 120 % O O O ⟦blank source cell⟧
10 08-02 Stall Prevention Level in Deceleration 200V: 330~410 385 V O O O ⟦blank source cell⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 660~820 770 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 08-03 Stall Prevention Level in Operation 30~200 120 % O X X ⟦blank source cell⟧
13 08-04 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 08-05 Selection for Motor Overload Protection (OL1) xxx0b: Motor Overload Protection is disabled 0001b - O O O ⟦blank source cell⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xxx1b: Motor Overload Protection is enabled ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx0xb: Cold Start of Motor Overload ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx1xb: Hot Start of Motor Overload ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x0xxb: Standard Motor ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x1xxb: Special motor ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0xxxb: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1xxxb: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 08-06 Start-up Mode of Overload Protection Operation (OL1) 0: Stop Output after Overload Protection 0 - O O O ⟦blank source cell⟧
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Continuous Operation after Overload Protection. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
24 08-07 Motor Overload (OL1) Protection Level 0: Motor overload (OL1) Protection 0 0 - O O O Note3
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Motor overload (OL1) Protection 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Motor overload (OL1) Protection 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Parameter summary:group08 — page 126

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-08

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-09

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-10

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-11

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-13

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-14

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-15

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-16

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-17

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-18

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-19

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-20

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-21

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-22

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-23

Shared source cells (coordinates refer to this table):

Parameter summary:group08 table1 — PDF page 126

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 08-08 Automatic Voltage Regulation (AVR) 0: Enable 0 - O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Disable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 08-09 Selection of Input Phase Loss Protection 0: Disable 0 - O O O ⟦blank source cell⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 08-10 Selection of Output Phase Loss Protection 0: Disable 0 - O O O ⟦blank source cell⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 08-11 08-12 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 08-13 Selection of Over-Torque Detection 0: Over-Torque Detection is Disabled. 0 - O O O ⟦blank source cell⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Start to Detect when Reaching the Set Frequency. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Start to Detect when the Operation is Begun. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 08-14 Selection of Over-Torque Operation 0: Deceleration to Stop when Over- Torque is Detected. 0 - O O O ⟦blank source cell⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Display Warning when Over- Torque is Detected. Go on Operation. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Coast to Stop when Over Torque is Detected ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 08-15 Level of Over-Torque Detection 0~300 150 % O O O ⟦blank source cell⟧
15 08-16 Time of Over-Torque Detection 0.0~10.0 0.1 Sec O O O ⟦blank source cell⟧
16 08-17 Selection of Low-Torque Detection 0: Low-Torque Detection is Disabled. 0 - O O O ⟦blank source cell⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Start to Detect when Reaching the Set Frequency. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Start to Detect when the Operation is Begun. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 08-18 Selection of Low-Torque Operation 0: Deceleration to Stop when Low- Torque is Detected. 0 - O O O ⟦blank source cell⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Display Warning when Low- Torque is Detected. Go on Operation. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Coast to Stop when Low-Torque is Detected ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 08-19 Level of Low-Torque Detection 0~300 30 % O O O ⟦blank source cell⟧
23 08-20 Time of Low-Torque Detection 0.0~10.0 0.1 Sec O O O ⟦blank source cell⟧
24 08-21 Limit of Stall Prevention in Acc over Base Speed 1~100 50 % O O O ⟦blank source cell⟧
25 08-22 Stall Prevention Detection Time in Operation 2~100 100 ms O O O ⟦blank source cell⟧
26 08-23 Ground Fault (GF) Selection 0: Disable 0 - O O O ⟦blank source cell⟧
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Parameter summary:group08 — page 127

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-24

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-25

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-26

~

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-30

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-31

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-35

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-36

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-37

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-38

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-39

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-42

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-43

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-45

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-46

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-47

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-48

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-49

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-50

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-51

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-52

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-53

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-54

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 08-55

Shared source cells (coordinates refer to this table):

Parameter summary:group08 table1 — PDF page 127

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 08-24 Operation Selection of External Fault 0: Deceleration to Stop 0 - O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Coast to Stop ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Continuous Operation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 08-25 Detection selection of External Fault 0: Immediately Detect when the Power is Supplied. 0 - O O O ⟦blank source cell⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Start to Detect during Operation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 08-26 ~ 08-29 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 08-30 Selection of Run Permissive Function 0: Deceleration to Stop 0 - O O O ⟦blank source cell⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Coast to Stop ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 08-31 ~ 08-34 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 08-35 Fault Selection of Motor Overheat 0: Disable 0 - O O O ⟦blank source cell⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Deceleration to Stop ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Coast to Stop ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 08-36 Time Coefficient of PTC Input Filter 0.00 ~ 5.00 2 Sec O O O ⟦blank source cell⟧
14 08-37 Fan Control Function (Note) 0: Start at Operation 0 - O O O ⟦blank source cell⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Permanent Start ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Start at High Temperature ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 08-38 Delay Time of Fan Off 0~600 60 Sec O O O ⟦blank source cell⟧
18 08-39 Delay Time of Motor Overheat Protection 1~300 60 Sec O O O ⟦blank source cell⟧
19 08-42 PTC Trip Level 0.1~10.0 0.7 V O O O Note1
20 08-43 PTC Reset Level 0.1~10.0 0.3 V O O O Note1
21 08-45 PTC Disconnection Detection 0: Disable 0 - O O O Note3
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Warning ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
24 08-46 Temperature Agree Level 0~254°C 0 °C O O O Note6
25 08-47 Temperature Reset Level 0~254°C 0 °C O O O Note6
26 08-48 Selection of Fire Mode 0: Disable 1: Enable 0 - O O O Note6
27 08-49 Multi-Function Input Terminal Status of Fire Mode 0:Reset after Power Off 1:Reset after Terminal Removed 0 - O O O Note6
28 08-50 Multi-Function Terminal Status of Fire Mode XXX0b: S6 A contact XXX1b: S6 B contact 0000b - O O O Note6
29 08-51 Motor Speed Setting Source of Fire Mode 0:Fire Mode Speed(08-52) 1:PID Control 2:AI2 0 - O O O Note6
30 08-52 Motor Speed of Fire Mode 0.00~100.00 100.00 % O O O Note6
31 08-53 PID Detection Level of Fire Mode 0~100 0 % O O O Note6
32 08-54 Delay Time of Fire Mode PID Loss 0.0~10.0 1.0 s O O O Note6
33 08-55 PID Feedback Loss Detection 0:Keep Running 1 - O O O Note6

Manual — Parameter summary:group08/09 — page 128

Note: 1. Standard H & C type, IP20 frame 6~9 do not have 08-37 function.

  1. Enhanced E & G type, IP20 frame 6~8 do not have “Start at High Temperature” function.(08-37=2)

  2. Enhanced E & G type, IP20 frame 9 do not have 08-37 function.

Firstrowcontinues08-55PIDFeedbackLossDetectionSelectionofFireModefromPDF127:0KeepRunningthere;1FireModeSpeed(08-52),2MaximumOutputFrequency(01-02)here. Default1/unitdash/controlO/Note6remainatPDF127,notblanknewvalues.08-37fanrestrictionnotesapplybacktoPDF127;hardwareexceptionsarepreservedverbatiminprose.

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Firstrow continues08-55onPDF127;fan-function restrictions below this table apply08-37onPDF127.

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Firstrow continues08-55onPDF127;fan-function restrictions below this table apply08-37onPDF127. Row group: 08-55 continuation fromPDF127;previouspageprovidescode/default/units/modes/attribute

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Firstrow continues08-55onPDF127;fan-function restrictions below this table apply08-37onPDF127. Row group: 08-56

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Firstrow continues08-55onPDF127;fan-function restrictions below this table apply08-37onPDF127. Row group: 08-57

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Firstrow continues08-55onPDF127;fan-function restrictions below this table apply08-37onPDF127. Row group: 08-58

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Firstrow continues08-55onPDF127;fan-function restrictions below this table apply08-37onPDF127. Row group: 08-59

Group 08 Protection Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Firstrow continues08-55onPDF127;fan-function restrictions below this table apply08-37onPDF127. Row group: 08-60

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Final09-07row is incomplete at page boundary;continuationPDF129remains pending outside this part. Do not use partial option text as complete definition.

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Final09-07row is incomplete at page boundary;continuationPDF129remains pending outside this part. Do not use partial option text as complete definition. Row group: 09-00

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Final09-07row is incomplete at page boundary;continuationPDF129remains pending outside this part. Do not use partial option text as complete definition. Row group: 09-01

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Final09-07row is incomplete at page boundary;continuationPDF129remains pending outside this part. Do not use partial option text as complete definition. Row group: 09-02

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Final09-07row is incomplete at page boundary;continuationPDF129remains pending outside this part. Do not use partial option text as complete definition. Row group: 09-03

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Final09-07row is incomplete at page boundary;continuationPDF129remains pending outside this part. Do not use partial option text as complete definition. Row group: 09-04

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Final09-07row is incomplete at page boundary;continuationPDF129remains pending outside this part. Do not use partial option text as complete definition. Row group: 09-05

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Final09-07row is incomplete at page boundary;continuationPDF129remains pending outside this part. Do not use partial option text as complete definition. Row group: 09-06

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Final09-07row is incomplete at page boundary;continuationPDF129remains pending outside this part. Do not use partial option text as complete definition. Row group: 09-07

Shared source cells (coordinates refer to this table):

Parameter summary:group08/09 table1 — PDF page 128

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 ⟦blank source cell⟧ Selection of Fire Mode 1:Fire Mode Speed (08-52) 2:Maximum Output Frequency (01-02) ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 08-56 Detection Level of Fire Mode AI2 Signal 0.0~100 80.0 % O O O Note6
3 08-57 Delay Time of Fire Mode AI2 Signal Loss 0.0~10.0 1.0 s O O O Note6
4 08-58 Selection of Fire Mode AI2 Signal Loss 0:Keep Running 1:Fire Mode Speed (08-52) 2:Maximum Output Frequency (01-02) 1 - O O O Note6
5 08-59 Fire Mode Motor Direction 0:Forward 1:Reverse 0 - O O O Note6
6 08-60 Fire Mode Password 00000~65534 0 - O O O Note6

Parameter summary:group08/09 table2 — PDF page 128

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 09-00 INV Communication Station Address 1~31 1 - O O O *2
2 09-01 Communication Mode Selection 0: MODBUS 0 - O O O ⟦blank source cell⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: BACNET ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: METASYS ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: PUMP in Parallel Connection ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 09-02 Baud Rate Setting (bps) 0:1200 4 - O O O *2 *6
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1:2400 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2:4800 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3:9600 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4:19200 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5:38400 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 09-03 Stop Bit Selection 0:1 Stop Bit 0 - O O O *2
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: 2 Stop Bit ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 09-04 Parity Selection 0: No Parity 0 - O O O *2
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Even Bit ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Odd Bit ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 09-05 Communications Data Bits Selection 0: 8 bits data 0 - O O O Note1
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: 7 bits data ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 09-06 Communication Error Detection Time 0.0~25.5 0.0 S O O O ⟦blank source cell⟧
20 09-07 Fault Stop Selection 0: Deceleration to Stop Based on 3 - O O O ⟦blank source cell⟧

Manual — Parameter summary:Group 09,Group 10 — page 129

Note: Parameters in group 09 are not affected by parameter 13-08 (initialization).

First five range rows complete09-07 Fault Stop Selection begun onPDF128: option0 Deceleration to Stop Based on Deceleration Time1 when Communication Fault Occurs;1 Coast to Stop when Communication Fault Occurs;2 Deceleration to Stop Based on Deceleration Time2 when Communication Fault Occurs;3 Keep Operating when Communication Fault Occurs;4 Run the Frequency Command given by AI2. Code/default/unit/mode/attribute cells on this page are blank continuation areas, not new parameters. Group09 is not affected by initialization13-08.10-03 final1xxxb option continues the words Frequency Command ontoPDF130.

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters.

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 09-07 continuation fromPDF128

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 09-08

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 09-09

Group 09: Communication Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 09-10

Shared source cells (coordinates refer to this table):

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters.

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-00

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-01

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-02

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-03

Parameter summary:Group 09,Group 10 table1 — PDF page 129

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 ⟦blank source cell⟧ ⟦blank source cell⟧ Deceleration Time 1 when Communication Fault Occurs. ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Coast to Stop when Communication Fault Occurs. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Deceleration to Stop Based on Deceleration Time 2 when Communication Fault Occurs. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Keep Operating when Communication Fault Occurs. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4. Run the Frequency Command given by AI2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 09-08 Comm. Fault Tolerance Count 1~20 1 - O O O ⟦blank source cell⟧
7 09-09 Waiting Time 5~65 5 ms O O O ⟦blank source cell⟧
8 09-10 Device Instance Number 1 ~ 254 1 - O O O ⟦blank source cell⟧

Parameter summary:Group 09,Group 10 table2 — PDF page 129

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 10-00 PID Target Value Source Setting 0: PUMP or HVAC function given (refer to group 23) 1 - O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: AI1 Given ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: AI2 Given ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: 10-02 Given ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: Reserved Note ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: Frequency Command (00-05) Note ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7: Multi-speed Frequency Command Note4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 10-01 PID Feedback Value Source Setting 1: AI1 Given 2 - O O O ⟦blank source cell⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: AI2 Given ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: AI1 - AI2 Given ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 10-02 PID Target Value 0.0~100.0 0.0 % O O O ⟦blank source cell⟧
14 10-03 PID Control Mode xxx0b: PID Disable 0000b - O O O ⟦blank source cell⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xxx1b: PID Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx0xb: PID Positive Characteristic ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx1xb: PID Negative Characteristic ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x0xxb: PID Error Value of D Control ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x1xxb: PID Feedback Value of D Control ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0xxxb: PID Output ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1xxxb: PID Output + Frequency ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Parameter summary:Group 10 — page 130

First range cell Command completes10-03 option1xxxb PID Output + Frequency Command onPDF129.10-35 PID Unit begins0:% here and continues options1–24 onPDF131. Do not bind the continuation to10-36. Reserved10-08,10-15/16,10-21,10-28 retained. Frequencies withNote8 retain their firmware qualification.

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters.

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-03 continuation fromPDF129

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-04

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-05

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-06

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-07

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-08

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-09

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-10

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-11

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-12

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-13

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-14

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-15

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-17

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-18

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-19

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-20

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-21

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-22

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-23

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-24

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-25

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-26

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-27

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-28

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-29

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-30

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-31

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-32

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-33

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-34

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-35

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c1, r1c2, r1c4, r1c5, r1c9. A header spans across these blank regions in the native text; no header value is propagated into them.

Parameter summary:Group 10 table1 — PDF page 130

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Command ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧
2 10-04 Feedback Gain 0.01~10.00 1.00 - O O O *1
3 10-05 Proportional Gain (P) 0.00~10.00 3.00 - O O O *1
4 10-06 Integral Time (I) 0.00~100.00 0.50 s O O O *1
5 10-07 Differential Time (D) 0.00~10.00 0.00 s O O O *1
6 10-08 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 10-09 PID Bias -100.0~100.0 0 % O O O *1
8 10-10 PID Primary Delay Time 0.00~10.00 0.00 s O O O *1
9 10-11 PID Feedback Loss Detection Selection 0: Disable 0 - O O O ⟦blank source cell⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Warning ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 10-12 PID Feedback Loss Detection Level 0~100 0 % O O O ⟦blank source cell⟧
13 10-13 PID Feedback Loss Detection Time 0.0~10.0 1.0 s O O O ⟦blank source cell⟧
14 10-14 PID Integral Limit 0.0~100.0 100.0 % O O O *1
15 10-15 10-16 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 10-17 Start Frequency of PID Sleep 0.00~599.00 (Note8) 30.00 Hz O O O ⟦blank source cell⟧
17 10-18 Delay Time of PID Sleep 0.0~255.5 0.0 s O O O ⟦blank source cell⟧
18 10-19 Frequency of PID Waking up 0.00~599.00 (Note8) 0.00 Hz O O O ⟦blank source cell⟧
19 10-20 Delay Time of PID Waking up 0.0~255.5 0.0 s O O O ⟦blank source cell⟧
20 10-21 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 10-22 Start Level of PID Enable 0.00~599.00 (Note8) 0.00 Hz O O O Note2
22 10-23 PID Limit 0.00~100.0 100.0 % O O O *1
23 10-24 PID Output Gain 0.0~25.0 1.0 - O O O ⟦blank source cell⟧
24 10-25 PID Reversal Output Selection 0: Do not Allow Reversal Output 0 - O O O ⟦blank source cell⟧
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Allow Reversal Output ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
26 10-26 PID Target Acceleration/ Deceleration Time 0.0~25.5 0.0 s O O O ⟦blank source cell⟧
27 10-27 PID Feedback Display Bias 0~9999 0 - O O O ⟦blank source cell⟧
28 10-28 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
29 10-29 PID Sleep Selection 0: Disable 1 - O O O ⟦blank source cell⟧
30 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
31 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Set by DI ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
32 10-30 Upper Limit of PID Target 0.0 ~ 100.0 100.0 % O O O ⟦blank source cell⟧
33 10-31 Lower Limit of PID Target 0.0 ~ 100.0 0.0 % O O O ⟦blank source cell⟧
34 10-32 PID Switching Function 0: PID1 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
35 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: PID2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
36 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Set by DI ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
37 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Switch to PID2 when RTC Timer Enables ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
38 10-33 PID Maximum Feedback Value 1~10000 999 - O O O ⟦blank source cell⟧
39 10-34 PID Decimal Width 0~4 1 - O O O ⟦blank source cell⟧
40 10-35 PID Unit 0: % 0 - O O O *6

Manual — Parameter summary:Group 10 — page 131

First24 range rows belong to10-35 fromPDF130:1FPM,2CFM,3PSI,4GPH,5GPM,6IN,7FT,8/s,9/m,10/h,11°F,12inW,13HP,14m/s,15MPM,16CMM,17W,18KW,19m,20°C,21RPM,22Bar,23Pa,24KPa(Note4). The blank continuation defaults/modes are not missing values to fill from a neighbouring parameter.

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters.

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-35 continuation fromPDF130

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-36

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-37

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-38

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-39

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-40

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-41

~

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-44

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-45

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-46

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-47

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-48

Group 10: PID Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 10-49

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c1, r1c2, r1c4, r1c5, r1c9, r2c1, r2c2, r2c4, r2c5, r2c9, r3c1, r3c2, r3c4, r3c5, r3c9, r4c1, r4c2, r4c4, r4c5, r4c9, r5c1, r5c2, r5c4, r5c5, r5c9, r6c1, r6c2, r6c4, r6c5, r6c9, r7c1, r7c2, r7c4, r7c5, r7c9, r8c1, r8c2, r8c4, r8c5, r8c9, r9c1, r9c2, r9c4, r9c5, r9c9, r10c1, r10c2, r10c4, r10c5, r10c9, r11c1, r11c2, r11c4, r11c5, r11c9, r12c1, r12c2, r12c4, r12c5, r12c9, r13c1, r13c2, r13c4, r13c5, r13c9, r14c1, r14c2, r14c4, r14c5, r14c9, r15c1, r15c2, r15c4, r15c5, r15c9, r16c1, r16c2, r16c4, r16c5, r16c9, r17c1, r17c2, r17c4, r17c5, r17c9, r18c1, r18c2, r18c4, r18c5, r18c9, r19c1, r19c2, r19c4, r19c5, r19c9, r20c1, r20c2, r20c4, r20c5, r20c9, r21c1, r21c2, r21c4, r21c5, r21c9, r22c1, r22c2, r22c4, r22c5, r22c9, r23c1, r23c2, r23c4, r23c5, r23c9, r24c1, r24c2, r24c4, r24c5, r24c9. A header spans across these blank regions in the native text; no header value is propagated into them.

Parameter summary:Group 10 table1 — PDF page 131

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: FPM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: CFM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: PSI ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: GPH ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: GPM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: IN ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7: FT ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8: /s ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9: /m ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10: /h ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 11: °F ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 12: inW ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 13: HP ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 14: m/s ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 15: MPM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 16: CMM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 17: W ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 18: KW ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 19: m ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 20: °C ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 21: RPM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 22: Bar ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 23: Pa ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
24 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 24: KPa Note4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
25 10-36 PID2 Proportional Gain (P) 0.00~10.00 3.00 - O O O *1
26 10-37 PID2 Integral Time (I) 0.0~100.0 0.50 s O O O *1
27 10-38 PID2 Differential Time (D) 0.00~10.00 0.00 s O O O *1
28 10-39 PID Output Frequency Setting during disconnection 00.00~599.00 (Note8) 30.00 Hz O O O *6
29 10-40 Compensation Frequency Selection of PID Sleep 0: Disable 0 - O O O Note1
30 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
31 10-41 ~ 10-43 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
32 10-44 Precharge Frequency 0.0~120.0 0 Hz O O O Note3
33 10-45 Precharge Time 0~250 0 Sec O O O Note3
34 10-46 Precharge Target Level 0~10000 0 - O O O Note3
35 10-47 Proportional Gain 3(P) 0.00~10.00 3.00 ⟦blank source cell⟧ O O O Note6
36 10-48 Integral Time 3(I) 0.00~100.00 0.50 Sec O O O Note6
37 10-49 Differential Time 3(D) 0.00~10.00 0.00 Sec O O O Note6

Manual — Parameter summary:Group 11 — page 132

11-02 default is1 forV/f and0 forSLV/PMSLV;not one universal value.11-01 and11-24 printKVA*a as a capacity-dependent default placeholder, defined onPDF135. V/F-only energy-saving parameters keep individualO/X marks.

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-00

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-01

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-02

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-03

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-04

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-05

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-06

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-07

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-08

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-09

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-10

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-11

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-12

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-13

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-14

~

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-18

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-19

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-20

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-21

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-22

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-23

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-24

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-25

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-28

Shared source cells (coordinates refer to this table):

Parameter summary:Group 11 table1 — PDF page 132

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 11-00 Direction Lock Selection 0: Allow Forward and Reverse Rotation 1 - O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Only Allow Forward Rotation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Only Allow Reverse Rotation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 11-01 Carrier Frequency 0: Carrier Output Frequency Tuning KVA*a - O O O ⟦blank source cell⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: 1~16: 1~16KHz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 11-02 Soft PWM Function Selection 0: Disable 1(V/f) 0(SLV& PMSLV) - O O O ⟦blank source cell⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Soft PWM Function 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Soft PWM Function 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 11-03 Automatic carrier lowering selection 0: Disable 0 - O X X ⟦blank source cell⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 11-04 S-curve Time Setting at the Start of Acceleration 0.00~2.50 0.20 s O O O ⟦blank source cell⟧
12 11-05 S-curve Time Setting at the End of Acceleration 0.00~2.50 0.20 s O O O ⟦blank source cell⟧
13 11-06 S-curve Time Setting at the Start of Deceleration 0.00~2.50 0.20 s O O O ⟦blank source cell⟧
14 11-07 S-curve Time Setting at the End of Deceleration 0.00~2.50 0.20 s O O O ⟦blank source cell⟧
15 11-08 Jump Frequency 1 0.0~599.00 (Note8) 0.0 Hz O O O ⟦blank source cell⟧
16 11-09 Jump Frequency 2 0.0~599.00 (Note8) 0.0 Hz O O O ⟦blank source cell⟧
17 11-10 Jump Frequency 3 0.0~599.00 (Note8) 0.0 Hz O O O ⟦blank source cell⟧
18 11-11 Jump Frequency Width 0.0~25.5 1.0 Hz O O O ⟦blank source cell⟧
19 11-12 Manual Energy Saving Gain 0~100 80 % O X X ⟦blank source cell⟧
20 11-13 Automatic Return Time 0~120 60 Sec O O O *6
21 11-14 ~ 11-17 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 11-18 Manual Energy Saving Frequency 0.00~599.00 (Note8) 0.00 Hz O X X ⟦blank source cell⟧
23 11-19 Automatic Energy Saving Function 0: Disabled 0 - O X X ⟦blank source cell⟧
24 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enabled ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
25 11-20 Filter Time of Automatic Energy Saving 0~200 140 ms O X X ⟦blank source cell⟧
26 11-21 Voltage Upper Limit of Energy Saving Tuning 0~100 100 % O X X ⟦blank source cell⟧
27 11-22 Adjustment Time of Automatic Energy Saving 0~5000 20 ms O X X *1
28 11-23 Detection Level of Automatic Energy Saving 0~100 10 % O X X ⟦blank source cell⟧
29 11-24 Coefficient of Automatic Energy Saving 0.00~655.34 KVA*a - O X X ⟦blank source cell⟧
30 11-25 ~ 11-27 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
31 11-28 Frequency Gain of Overvoltage Prevention 2 1~200 100 % O X X Note4

Manual — Parameter summary:Group 11 — page 133

11-38 range200V:200–400V,400V:400–800V;default200V:300,400V:700.11-39 range200V:300–400V,400V:600–800V but default labels are220V:350 and440V:750. This source label difference is retained.11-48 range200V:190–210,400V:380–420;default paired200/400. No inferred class relabelling.

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-29

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-30

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-31

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-32

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-33

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-34

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-35

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-36

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-37

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-38

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-39

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-40

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-41

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-42

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-43

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-44

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-45

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-46

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-47

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-48

Shared source cells (coordinates refer to this table):

Parameter summary:Group 11 table1 — PDF page 133

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 11-29 Auto De-rating Selection 0: Disable 0 - O X X ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 11-30 Variable Carrier Frequency Max. Limit 2~16 KVA*a KHz O X X ⟦blank source cell⟧
4 11-31 Variable Carrier Frequency Min. Limit 1~16 KVA*a KHz O X X ⟦blank source cell⟧
5 11-32 Variable Carrier Frequency Proportional Gain 00~99 00 - O X X ⟦blank source cell⟧
6 11-33 Rise Amount of DC Voltage Filter 0.1~10.0 0.1 Vdc O X X Note4 *1
7 11-34 Fall Amount of DC Voltage Filter 0.1~10.0 5.0 Vdc O X X Note4 *1
8 11-35 Dead band Level of DC Voltage Filter 0.0~99.0 10.0 Vdc O X X Note4 *1
9 11-36 Frequency Gain of OV Prevention 0.000~1.000 0.050 - O X X Note2 *1
10 11-37 Frequency Limit of OV Prevention 0.00~599.00 (Note8) 5.00 Hz O X X Note2
11 11-38 Deceleration Start Voltage of OV Prevention 200V: 200~400V 400V: 400~800V 200V: 300 400V: 700 V O X X Note2
12 11-39 Deceleration Stop Voltage of OV Prevention 200V: 300~400V 400V: 600~800V 220V: 350 440V: 750 V O X X Note2
13 11-40 OV Prevention Selection 0: Disable 1: OV Prevention Mode 1 2: OV Prevention Mode 2 3: OV Prevention Mode 3 0 - O X X Note2
14 11-41 Reference Frequency Loss Detection 0: Deceleration to Stop when Reference Frequency Disappears 0 - O O O ⟦blank source cell⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Operation is Set by 11-42 when Reference Frequency Disappears ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 11-42 Reference Frequency Loss Level 0.0~100.0 80.0 % O O O ⟦blank source cell⟧
17 11-43 Hold Frequency at Start 0.0~599.00 (Note8) 0.0 Hz O O O ⟦blank source cell⟧
18 11-44 Frequency Hold Time at Start 0.0~10.0 0.0 s O O O ⟦blank source cell⟧
19 11-45 Hold Frequency at Stop 0.0~599.00 (Note8) 0.0 Hz O O O ⟦blank source cell⟧
20 11-46 Frequency Hold Time at Stop 0.0~10.0 0.0 s O O O ⟦blank source cell⟧
21 11-47 EB Deceleration Time 0.0~25.5 0.0 s O X X *1
22 11-48 KEB Detection Level 200V: 190~210 200 V O X X ⟦blank source cell⟧
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 380~420 400 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Parameter summary:Group 11 — page 134

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-49

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-51

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-52

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-54

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-55

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-56

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-57

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-58

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-59

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-60

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-61

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-62

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-63

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-64

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-65

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-66

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-67

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-68

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-69

Shared source cells (coordinates refer to this table):

Parameter summary:Group 11 table1 — PDF page 134

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 11-49 11-50 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 11-51 Braking Selection of Zero Speed 0: Disable 0 - O X X ⟦blank source cell⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 11-52 11-53 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 11-54 Initialization of Cumulative Energy 0: Do not Clear Cumulative Energy 0 - O O O *1
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Clear Cumulative Energy ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 11-55 STOP Key Selection 0: Stop Key is Disabled when the Operation Command is not Provided by Keypad. 1 - O O O ⟦blank source cell⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Stop Key is Enabled when the Operation Command is not Provided by Keypad. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 11-56 UP/DOWN Selection 0: When UP/DOWN in Keypad is Disabled, it will be Enabled if Pressing ENTER after Frequency Modification. 0 - O O O ⟦blank source cell⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: When UP/DOWN in Keypad is Enabled, it will be Enabled upon Frequency Modification. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 11-57 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 11-58 Record Reference Frequency 0: Disable 0 - O O O *1
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 11-59 Gain of Preventing Oscillation 0.00~2.50 0.01 ⟦blank source cell⟧ O X X *7
15 11-60 Upper Limit of Preventing Oscillation 0~100 30 % O X X *7
16 11-61 Time Parameter of Preventing Oscillation 0~100 0 ⟦blank source cell⟧ O X X *7
17 11-62 Prevention of Oscillation Selection 0: Mode 1 1: Mode 2 2: Mode 3 1 ⟦blank source cell⟧ O X X *7
18 11-63 Flux-Strengthening Selection 0: Disable 1 ⟦blank source cell⟧ X O X Note1
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 11-64 Acceleration Speed Gain Adjustment 0.1~10.0 1.0 - O X X Note3
21 11-65 Target Main Circuit Voltage 200V: 200V~400V 370 - O X X Note3
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 400V~800V 740 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 11-66 2 Phase/ 3 Phase PWM Switch Frequency 6.00~60.00 20 Hz O O O Note3
24 11-67 Detection Range at Soft PWM Function 2 0~12000 0 Hz X O O Note3
25 11-68 Detecting Start Frequency at Soft PWM Function 2 6.00~60.00 20 Hz X O O Note3
26 11-69 Gain of Preventing Oscillation 3 0.00~200.00 5.00 % O X X Note2

Manual — Parameter summary:Group 11 — page 135

*a: KVA means the default value of this parameter will be changed by different capacities of inverter.

*a explicitly saysKVA means the default value changes with different inverter capacities. Preserve literalKVA placeholders and their unit columns; no numeric defaults inferred.

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-70

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-71

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-72

Group 11: Auxiliary Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 11-73

Parameter summary:Group 11 table1 — PDF page 135

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 11-70 Upper Limit of Preventing Oscillation 3 0.01~100.00 5.00 % O X X Note2
2 11-71 Time Parameter of Preventing Oscillation 3 0~30000 100 ms O X X Note2
3 11-72 Switch Frequency 1 for Preventing Oscillation Gain 0.01~300.00 30.00 Hz O X X Note2
4 11-73 Switch Frequency 2 for Preventing Oscillation Gain 0.01~300.00 50.00 Hz O X X Note2

Manual — Parameter summary:Group 12 — page 136

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags.

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-00

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-01

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-02

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-03

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-04

Shared source cells (coordinates refer to this table):

Parameter summary:Group 12 table1 — PDF page 136

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 12-00 Display Screen Selection (LED) 00000~77777 From the leftmost bit, it displays the screen when press DSP key in order. 0: No display 1: Output Current 2: Output Voltage 3: DC Bus Voltage 4: Heatsink Temperature 5: PID Feedback 6: AI1 Value 7: AI2 Value 00321 - O O O *1 *5
2 12-01 PID Feedback Display Mode (LED) 0: Display the Feedback Value by Integer (xxx) 0 ⟦blank source cell⟧ O O O *5
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Display the Feedback Value by the Value with First Decimal Place (xx.x) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Display the Feedback Value by the Value with Second Decimal Place (x.xx) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 12-02 PID Feedback Display Unit Setting (LED) 0: xxxxx (no unit) 0 ⟦blank source cell⟧ O O O *5
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: xxxPb (pressure) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: xxxFL (flow) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 12-03 Line Speed Display (LED) 0~60000 1500/ 1800 RP M O O O *5
9 12-04 Line Speed Display Mode (LED) 0: Display Inverter Output Frequency 0 ⟦blank source cell⟧ O O O *1 *5
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Line Speed Display at Integer.(xxxxx) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Line Speed Display at One Decimal Place. (xxxx.x) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Line Speed Display at Two Decimal Places. (xxx.xx) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Line Speed Display at Three Decimal Places. (xx.xxx) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Parameter summary:Group 12 — page 137

LED no-input example has five horizontal dash segments. Input indicator segments proceed left-to-right S1,S2,S3,S4,S5,S6 across the first three display digits; separate relay glyph positions left-to-right R1,R2,R3. LCD nine positions left-to-right areR1,R2,R3,S1,S2,S3,S4,S5,S6;0:OPEN,1:CLOSE. The name says digital input terminal while the illustration also includes relay outputs; both preserved.

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags.

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-05

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-06

~

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-11

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-12

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-13

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-14

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-15

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-16

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-17

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-18

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-19

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-20

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-21

Shared source cells (coordinates refer to this table):

Parameter summary:Group 12 table1 — PDF page 137

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 12-05 Status display of digital input terminal (LED / LCD) LED display is shown as below no input correspondences to input and output LCD display is shown as below 0:OPEN 0 0 0 0 0 0 0 0 0 1:CLOSE Input Terminal(S6) Input Terminal(S5) Input Terminal(S4) Input Terminal(S3) Input Terminal(S2) Input Terminal(S1) Output Terminal(R3) Output Terminal(R2) Output Terminal(R1) - - O O O ⟦blank source cell⟧
2 12-06 ~ 12-10 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 12-11 Output Current of Current Fault Display the output current of current fault - A O O O ⟦blank source cell⟧
4 12-12 Output Voltage of Current Fault Display the output voltage of current fault - V O O O ⟦blank source cell⟧
5 12-13 Output Frequency of Current Fault Display the output frequency of current fault - Hz O O O ⟦blank source cell⟧
6 12-14 DC Voltage of Current Fault Display the DC voltage of current fault - V O O O ⟦blank source cell⟧
7 12-15 Frequency Command of Current Fault Display the frequency command of current fault - Hz O O O ⟦blank source cell⟧
8 12-16 Frequency Command If LED enters this parameter, it only allows monitoring frequency command. - Hz O O O ⟦blank source cell⟧
9 12-17 Output Frequency Display the current output frequency - Hz O O O ⟦blank source cell⟧
10 12-18 Output Current Display the current output current - A O O O ⟦blank source cell⟧
11 12-19 Output Voltage Display the current output voltage - V O O O ⟦blank source cell⟧
12 12-20 DC Voltage Display the current DC voltage - V O O O ⟦blank source cell⟧
13 12-21 Output Power Display the current output power - kW O O O ⟦blank source cell⟧

Manual — Parameter summary:Group 12 — page 138

12-22 literally states rotation speed = output power ×(120/motor pole number), refers toPG/SV feedback-frequency calculation, and gives maximum65535. Neither the dimensional wording nor PG/SV mention is converted into a validated formula or inferred extra supported mode. PDF141 separately states maximum65534; both claims retained.

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags.

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-22

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-23

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-24

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-25

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-26

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-27

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-28

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-29

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-30

~

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-36

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-37

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-38

Shared source cells (coordinates refer to this table):

Parameter summary:Group 12 table1 — PDF page 138

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 12-22 Motor’s Rotation Speed Display motor’s current rotation speed in VF/SLV mode Motor’s rotation speed = output power x(120/motor’s pole number) In PG/SV mode, motor’s rotation speed is calculated by feedback frequency. Max limit is 65535 - rpm O O O ⟦blank source cell⟧
2 12-23 Output Power Factor Display the current output power factor - - O O O ⟦blank source cell⟧
3 12-24 Control Mode Display control mode 0 : VF 2 : SLV 5 : PM SLV - - O O O ⟦blank source cell⟧
4 12-25 AI1 Input Display the current Al1 input (0V corresponds to 0%, 10V corresponds to 100%,) - % O O O ⟦blank source cell⟧
5 12-26 AI2 Input Display the current Al2 input (0V or 4mA corresponds to 0%, 10V or 20mA corresponds to 100%) - % O O O ⟦blank source cell⟧
6 12-27 Motor Torque Display the current torque command (100% corresponds to motor torque ) - % X O O ⟦blank source cell⟧
7 12-28 Motor Torque Current (Iq) Display the current q-axis current - % X O O ⟦blank source cell⟧
8 12-29 Motor Excitation Current (Id) Display the current d-axis current - % X O O ⟦blank source cell⟧
9 12-30 ~ 12-35 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 12-36 PID Input Display input error of the PID controller (PID target value - PID feedback) (100% corresponds to the maximum frequency set by 01-02 or 01-16) - % O O O ⟦blank source cell⟧
11 12-37 PID Output Display output of the PID controller (100% corresponds to the maximum frequency set by 01-02 or 01-16) - % O O O ⟦blank source cell⟧
12 12-38 PID Setting Display the target value of the PID controller (100% corresponds to the maximum frequency set by 01-02 or 01-16) - % O O O ⟦blank source cell⟧

Manual — Parameter summary:Group 12 — page 139

LCD eight positions right-to-left:CRC Error,Data length Error,Data Function Error,Parity Error,Overrun Error,Framing Error,Time Out Error,Reserved. Error positions display1. LED no-error example has five horizontal dashes. LED error-segment callouts proceed left-to-right:CRC,Data length,Data Function,Parity,Overrun,Framing,Time out,Reserved. Preserve display geometry; no inferred bit-register encoding beyond source labels.

LCD rightmost positions respectivelyInverter ready,During running,During zero speed,During speed agree,During fault detection(minor fault),During fault detection(major fault);leftmost two bracketedReserved. LED status values:Inverter ready1,Running2,Zero Speed4,Frequency Agree8,Warning16,Error32. Source says display sums values and example6 means running in zero speed. Default cell101B preserved as printed.

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags.

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-39

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-40

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-41

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-42

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-43

Shared source cells (coordinates refer to this table):

Parameter summary:Group 12 table1 — PDF page 139

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 12-39 PID Feedback Display the feedback value of the PID controller (100% corresponds to the maximum frequency set by 01-02 or 01-16) - % O O O ⟦blank source cell⟧
2 12-40 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 12-41 Heatsink Temperature Display the heatsink temperature of IGBT temperature. - ℃ O O O ⟦blank source cell⟧
4 12-42 RS-485 Error Code LCD Display: 0 0 0 0 0 0 0 0 1: C R C E rror 1: D ata length E rror 1: D ata F unction E rror 1: P arity E rror 1: O verrun E rror 1: F ram ing E rror 1: T im e O ut E rror R eserved LED Display: (without any error) LED Display: (with certain error) 1: CRC Error 1: Data length Error 1: Data Function Error 1: Parity Error 1: Framing Error 1: Time out Error Reserved 1: Overrun Error - - O O O *7
5 12-43 Inverter Status LCD Display: 0 0 0 0 0 0 0 0 1: Inverter ready 1: During running 1: During zero speed 1: During speed agree 1: During fault detection (minor fault) 1: During fault detection (major fault) Reserved LED Display: Inverter ready 1 Running 2 Zero Speed 4 Frequency Agree 8 Warning 16 Error 32 Inverter status display is the summed up value. Ex: Display of the value 6 means the inverter is running in zero speed. 101B - O O O ⟦blank source cell⟧

Manual — Parameter summary:Group 12 — page 140

Current fault:12-53 isdays and12-52 remaininghours. Last fault:12-62 isdays and12-61 remaininghours.12-50/59 DI/O references12-05;12-51/60 inverterstatus references12-43.12-67kWHr and12-68MWHr have blank default cells, not zero defaults.

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags.

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-44

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-45

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-46

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-47

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-48

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-49

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-50

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-51

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-52

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-53

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-54

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-55

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-56

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-57

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-58

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-59

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-60

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-61

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-62

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-63

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-64

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-65

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-67

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-68

Shared source cells (coordinates refer to this table):

Parameter summary:Group 12 table1 — PDF page 140

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 12-44 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 12-45 Recent Fault Message Display current fault message - - O O O ⟦blank source cell⟧
3 12-46 Previous Fault Message Display previous fault message - - O O O ⟦blank source cell⟧
4 12-47 Previous Two Fault Messages Display previous two fault messages - - O O O ⟦blank source cell⟧
5 12-48 Previous Three Fault Messages Display previous three fault messages - - O O O ⟦blank source cell⟧
6 12-49 Previous Four Fault Messages Display previous four fault messages - - O O O ⟦blank source cell⟧
7 12-50 DIO Status of Current Fault Display the DI/DO status of current fault Description is similar to 12-05 - - O O O ⟦blank source cell⟧
8 12-51 Inverter Status of Current Fault Display the inverter status of current fault Description is similar to 12-43 - - O O O ⟦blank source cell⟧
9 12-52 Trip Time 1 of Current Fault Display the operation time of current fault, 12-53 is the days, while 12-52 is the remaining hours. - Hr O O O ⟦blank source cell⟧
10 12-53 Trip Time 2 of Current Fault ⟦null: no independent source value⟧ - day O O O ⟦blank source cell⟧
11 12-54 Frequency Command of Previous Fault Display frequency command of previous fault - Hz O O O ⟦blank source cell⟧
12 12-55 Output Frequency of Previous Fault Display output frequency of previous fault - Hz O O O ⟦blank source cell⟧
13 12-56 Output Current of Previous Fault Display output current of previous fault - A O O O ⟦blank source cell⟧
14 12-57 Output Voltage of Previous Fault Display output voltage of previous fault - V O O O ⟦blank source cell⟧
15 12-58 DC Voltage of Previous Fault Display DC voltage of previous fault - V O O O ⟦blank source cell⟧
16 12-59 DIO Status of Previous Fault Display DI/DO status of previous fault Description is similar to 12-05 - - O O O ⟦blank source cell⟧
17 12-60 Inverter Status of Previous Fault Display inverter status of previous fault Description is similar to 12-43 - - O O O ⟦blank source cell⟧
18 12-61 Trip time 1 of last fault Display the operation time of last time’s fault, 12-62 is the days, while 12-61 is the remaining hours. - Hr O O O ⟦blank source cell⟧
19 12-62 Trip time 2 of last fault ⟦null: no independent source value⟧ - day O O O ⟦blank source cell⟧
20 12-63 Recent warning messages Display the recent warning messages - - O O O ⟦blank source cell⟧
21 12-64 Previous warning message Display the previous warning messages - - O O O ⟦blank source cell⟧
22 12-65 12-66 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 12-67 Accumulative Energy (kWHr) 0.0 ~ 999.9 ⟦blank source cell⟧ kWH r O O O ⟦blank source cell⟧
24 12-68 Accumulative Energy (MWHr) 0 ~ 60000 ⟦blank source cell⟧ MW Hr O O O ⟦blank source cell⟧

Manual — Parameter summary:Group 12,Group 13 Maintenance Function Group — page 141

IP20 enclosure do not support functions of heatsink temperature display. All models in IP55 enclosure

support functions of heatsink temperature display.

The note saysIP20 models at/above200V60HP(including60HP) and400V100HP(including100HP) do not support heatsink temperature display; allIP55 models support it. This qualifies12-41 onPDF139 and other heatsink display references. Same note gives12-22 maximum65534, conflicting with65535 onPDF138.12-85AI3 input remains*10 I/O expansion-card dependent. Codes12-80,12-83,12-84 are unprinted, not silently invented.

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags.

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-69

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-70

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-71

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-72

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-73

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-74

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-75

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-76

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-77

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-78

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-79

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-81

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-82

Group 12: Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 12-85

Shared source cells (coordinates refer to this table):

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags.

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 13-00

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 13-01

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 13-02

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 13-03

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 13-04

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 13-05

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Heatsink-display hardware restrictions and12-22speed-limit conflict appear onPDF141;see source flags. Row group: 13-06

Parameter summary:Group 12,Group 13 Maintenance Function Group table1 — PDF page 141

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 12-69 Accumulative Electricity Price ($) 0 ~ 9999 ⟦blank source cell⟧ $ O O O ⟦blank source cell⟧
2 12-70 Accumulative Electricity Price (10000$) 0 ~ 60000 ⟦blank source cell⟧ $ O O O ⟦blank source cell⟧
3 12-71 Flow Meter Feedback 1 ~ 50000 ⟦blank source cell⟧ GP M O O O ⟦blank source cell⟧
4 12-72 RTC Date 12.01.01 ~ 99.12.31 12.01.0 1 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
5 12-73 RTC Time 00:00 ~ 23:59 00:00 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
6 12-74 Operating Pressure Setting 0.01 ~ 25.50 2.00 PSI O X X ⟦blank source cell⟧
7 12-75 Pressure Feedback Value 0.01 ~ 25.50 - PSI O X X ⟦blank source cell⟧
8 12-76 Non-Load Voltage 0.0 ~ 600.0 - V X O X ⟦blank source cell⟧
9 12-77 Flow Meter Target Setting 1 ~ 50000 - GP M O O O *7
10 12-78 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 12-79 Pulse Input Percentage 0.0~100.0 - % O O O *7
12 12-81 Relay Card Display ON: LCD display is 1 OFF: LCD display is 0 - - O O O Note5
13 12-82 Motor Load 0 ~ 200.0 - % O O O Note6
14 12-85 AI3 Input Display the current Al3 input (-10V corresponds to -100%, 10V corresponds to 100%) - % O O O *10

Parameter summary:Group 12,Group 13 Maintenance Function Group table2 — PDF page 141

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 13-00 Inverter Rating Selection 00H~FFH - - O O O *4
2 13-01 Software Version 0.00-9.99 - - O O O *4
3 13-02 Clear Cumulative Operation Hours Function 0: Disable to Clear Cumulative Operation Hours 1: Clear Cumulative Operation Hours 0 ⟦blank source cell⟧ O O O *1
4 13-03 Cumulative Operation Hours 1 0~23 - hr O O O *4
5 13-04 Cumulative Operation Hours 2 0~65534 - day O O O *4
6 13-05 Selection of Accumulative Operation Time 0: Accumulative time in power on 0 ⟦blank source cell⟧ O O O *1
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Accumulative time in operation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 13-06 Parameters Locked 0: Only parameter 13-06 and frequency setting parameters in main screen are writable 2 ⟦blank source cell⟧ O O O *1
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Only user parameter is enabled. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: All parameters are writable. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Parameter summary:Group 13 Maintenance Function Group — page 142

13-08 choices retain both wire count and voltage/frequency pair:2/3=2/3wire220/440V60Hz;4/5=230/415V50Hz;6/7=200/380V50Hz;8PLC initialization;9/10=230/460V60Hz;11/12=230/400V60Hz;13/14=230/400V50Hz;15/16=220/380V50Hz Note4. Choice0 no initialization;choice1 not printed.13-07 password default00000 is literal, not reformatted. Group09 initialization exception onPDF129 remains applicable.

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-07

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-08

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-09

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-10

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-11

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-12

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-13

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-14

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-15

~

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-21

Shared source cells (coordinates refer to this table):

Parameter summary:Group 13 Maintenance Function Group table1 — PDF page 142

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 13-07 Parameter Password Function 00000~65534 00000 - O O O ⟦blank source cell⟧
2 13-08 Restore Factory Setting 0: No Initialization 0 - O O O ⟦blank source cell⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: 2 wire Initialization (220/440V, 60Hz) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: 3 wire Initialization (220/440V, 60Hz) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: 2 wire Initialization (230/415V, 50Hz) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: 3 wire Initialization (230/415V, 50Hz) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: 2 wire Initialization (200/380V, 50Hz) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7: 3 wire Initialization (200/380V, 50Hz) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8: PLC Initialization ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9: 2 Wire Initialization (230V/460V, 60Hz) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10: 3 Wire Initialization (230V/460V, 60Hz) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 11: 2 wire Initialization, 230V/400V, 60Hz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 12: 3 wire Initialization, 230V/400V, 60Hz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 13: 2 wire Initialization, 230V/400V, 50Hz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 14: 3 wire Initialization, 230V/400V, 50Hz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 15: 2 wire Initialization, (220/380V, 50Hz) Note4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 16: 3 wire Initialization (220/380V, 50Hz) Note4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 13-09 Fault History Clearance Function 0: Do not Clear Fault History 0 - O O O *1
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Clear Fault History ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 13-10 Parameter Password Function 2 0 ~ 9999 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
21 13-11 C/B CPLD Ver. 0.00~9.99 - ⟦blank source cell⟧ O O O *7
22 13-12 Option Card Id 0~255 0 ⟦blank source cell⟧ O O O *7
23 13-13 Option Card CPLD Ver. 0.00~9.99 - ⟦blank source cell⟧ O O O *7
24 13-14 Fault Storage Selection 0: Auto Restart Fault Messages are not saved in fault history. 1 ⟦blank source cell⟧ O O O Note1
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Auto Restart Fault Messages are saved in fault history. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
26 13-15 ~ 13-20 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
27 13-21 Previous Fault Message Display Previous Fault Message - - O O O Note2

Manual — Parameter summary:Group 13 Maintenance Function Group — page 143

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-22

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-23

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-24

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-25

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-26

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-27

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-28

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-29

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-30

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-31

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-32

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-33

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-34

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-35

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-36

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-37

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-38

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-39

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-40

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-41

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-42

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-43

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-44

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-45

Parameter summary:Group 13 Maintenance Function Group table1 — PDF page 143

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 13-22 Previous Two Fault Message Display Previous Two Fault Message - - O O O Note2
2 13-23 Previous Three Fault Message Display Previous Three Fault Message - - O O O Note2
3 13-24 Previous Four Fault Message Display Previous Four Fault Message - - O O O Note2
4 13-25 Previous Five Fault Message Display Previous Five Fault Message - - O O O Note2
5 13-26 Previous Six Fault Message Display Previous Six Fault Message - - O O O Note2
6 13-27 Previous Seven Fault Message Display Previous Seven Fault Message - - O O O Note2
7 13-28 Previous Eight Fault Message Display Previous Eight Fault Message - - O O O Note2
8 13-29 Previous Nine Fault Message Display Previous Nine Fault Message - - O O O Note2
9 13-30 Previous Ten Fault Message Display Previous Ten Fault Message - - O O O Note2
10 13-31 Previous Eleven Fault Message Display Previous Eleven Fault Message - - O O O Note2
11 13-32 Previous Twelve Fault Message Display Previous Twelve Fault Message - - O O O Note2
12 13-33 Previous Thirteen Fault Message Display Previous Thirteen Fault Message - - O O O Note2
13 13-34 Previous Fourteen Fault Message Display Previous Fourteen Fault Message - - O O O Note2
14 13-35 Previous Fifteen Fault Message Display Previous Fifteen Fault Message - - O O O Note2
15 13-36 Previous Sixteen Fault Message Display Previous Sixteen Fault Message - - O O O Note2
16 13-37 Previous Seventeen Fault Message Display Previous Seventeen Fault Message - - O O O Note2
17 13-38 Previous Eighteen Fault Message Display Previous Eighteen Fault Message - - O O O Note2
18 13-39 Previous Nineteen Fault Message Display Previous Nineteen Fault Message - - O O O Note2
19 13-40 Previous Twenty Fault Message Display Previous Twenty Fault Message - - O O O Note2
20 13-41 Previous Twenty One Fault Message Display Previous Twenty One Fault Message - - O O O Note2
21 13-42 Previous Twenty Two Fault Message Display Previous Twenty Two Fault Message - - O O O Note2
22 13-43 Previous Twenty Three Fault Message Display Previous Twenty Three Fault Message - - O O O Note2
23 13-44 Previous Twenty Four Fault Message Display Previous Twenty Four Fault Message - - O O O Note2
24 13-45 Previous Twenty Five Fault Message Display Previous Twenty Five Fault Message - - O O O Note2

Manual — Parameter summary:Group 13 Maintenance Function Group,Group 14 — page 144

13-21through13-50 are30 distinct previous-fault messages acrossPDF142–144, allNote2,not repeated copies to deduplicate. Group14 PLC setting values carryNote7 editableV1.53above;T1–T8 each haveValue1 andValue2(Mode7). Counter and arithmetic fields retain individual identifiers.

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-46

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-47

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-48

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-49

Group 13 Maintenance Function Group. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 13-50

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-00

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-01

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-02

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-03

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-04

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-05

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-06

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-07

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-08

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-09

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-10

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-11

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-12

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-13

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-14

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-15

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-16

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-17

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-18

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-19

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-20

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-21

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-22

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-23

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-24

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-25

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-26

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-27

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-28

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-29

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-30

Parameter summary:Group 13 Maintenance Function Group,Group 14 table1 — PDF page 144

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 13-46 Previous Twenty Six Fault Message Display Previous Twenty Six Fault Message - - O O O Note2
2 13-47 Previous Twenty Seven Fault Message Display Previous Twenty Seven Fault Message - - O O O Note2
3 13-48 Previous Twenty Eight Fault Message Display Previous Twenty Eight Fault Message - - O O O Note2
4 13-49 Previous Twenty Nine Fault Message Display Previous Twenty Nine Fault Message - - O O O Note2
5 13-50 Previous Thirty Fault Message Display Previous Thirty Fault Message - - O O O Note2

Parameter summary:Group 13 Maintenance Function Group,Group 14 table2 — PDF page 144

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 14-00 T1 Set Value 1 0~9999 0 - O O O Note7
2 14-01 T1 Set Value 2(Mode 7) 0~9999 0 - O O O Note7
3 14-02 T2 Set Value 1 0~9999 0 - O O O Note7
4 14-03 T2 Set Value 2(Mode 7) 0~9999 0 - O O O Note7
5 14-04 T3 Set Value 1 0~9999 0 - O O O Note7
6 14-05 T3 Set Value 2(Mode 7) 0~9999 0 - O O O Note7
7 14-06 T4 Set Value 1 0~9999 0 - O O O Note7
8 14-07 T4 Set Value 2(Mode 7) 0~9999 0 - O O O Note7
9 14-08 T5 Set Value 1 0~9999 0 - O O O Note7
10 14-09 T5 Set Value 2(Mode 7) 0~9999 0 - O O O Note7
11 14-10 T6 Set Value 1 0~9999 0 - O O O Note7
12 14-11 T6 Set Value 2(Mode 7) 0~9999 0 - O O O Note7
13 14-12 T7 Set Value 1 0~9999 0 - O O O Note7
14 14-13 T7 Set Value 2(Mode 7) 0~9999 0 - O O O Note7
15 14-14 T8 Set Value 1 0~9999 0 - O O O Note7
16 14-15 T8 Set Value 2(Mode 7) 0~9999 0 - O O O Note7
17 14-16 C1 Set Value 0~65534 0 - O O O Note7
18 14-17 C2 Set Value 0~65534 0 - O O O Note7
19 14-18 C3 Set Value 0~65534 0 - O O O Note7
20 14-19 C4 Set Value 0~65534 0 - O O O Note7
21 14-20 C5 Set Value 0~65534 0 - O O O Note7
22 14-21 C6 Set Value 0~65534 0 - O O O Note7
23 14-22 C7 Set Value 0~65534 0 - O O O Note7
24 14-23 C8 Set Value 0~65534 0 - O O O Note7
25 14-24 AS1 Set Value 1 0~65534 0 - O O O Note7
26 14-25 AS1 Set Value 2 0~65534 0 - O O O Note7
27 14-26 AS1 Set Value 3 0~65534 0 - O O O Note7
28 14-27 AS2 Set Value 1 0~65534 0 - O O O Note7
29 14-28 AS2 Set Value 2 0~65534 0 - O O O Note7
30 14-29 AS2 Set Value 3 0~65534 0 - O O O Note7
31 14-30 AS3 Set Value 1 0~65534 0 - O O O Note7

Manual — Parameter summary:Group 14,Group 15 — page 145

Group14 AS set-value defaults0;MD1–MD4 set-value defaults1. Group15 current-value/monitor rows have their own codes and defaults0;do not deduplicate against similarly named setting rows. Continuation15-23through15-32 onPDF146.

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-31

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-32

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-33

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-34

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-35

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-36

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-37

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-38

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-39

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-40

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-41

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-42

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-43

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-44

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-45

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-46

Group 14: PLC Setting Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 14-47

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-00

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-01

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-02

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-03

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-04

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-05

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-06

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-07

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-08

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-09

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-10

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-11

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-12

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-13

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-14

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-15

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-16

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-17

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-18

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-19

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-20

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-21

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-22

Parameter summary:Group 14,Group 15 table1 — PDF page 145

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 14-31 AS3 Set Value 2 0~65534 0 - O O O Note7
2 14-32 AS3 Set Value 3 0~65534 0 - O O O Note7
3 14-33 AS4 Set Value 1 0~65534 0 - O O O Note7
4 14-34 AS4 Set Value 2 0~65534 0 - O O O Note7
5 14-35 AS4 Set Value 3 0~65534 0 - O O O Note7
6 14-36 MD1 Set Value 1 0~65534 1 - O O O Note7
7 14-37 MD1 Set Value 2 0~65534 1 - O O O Note7
8 14-38 MD1 Set Value 3 0~65534 1 - O O O Note7
9 14-39 MD2 Set Value 1 0~65534 1 - O O O Note7
10 14-40 MD2 Set Value 2 0~65534 1 - O O O Note7
11 14-41 MD2 Set Value 3 0~65534 1 - O O O Note7
12 14-42 MD3 Set Value 1 0~65534 1 - O O O Note7
13 14-43 MD3 Set Value 2 0~65534 1 - O O O Note7
14 14-44 MD3 Set Value 3 0~65534 1 - O O O Note7
15 14-45 MD4 Set Value 1 0~65534 1 - O O O Note7
16 14-46 MD4 Set Value 2 0~65534 1 - O O O Note7
17 14-47 MD4 Set Value 3 0~65534 1 - O O O Note7

Parameter summary:Group 14,Group 15 table2 — PDF page 145

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 15-00 T1 Current Value 1 0~9999 0 - O O O ⟦blank source cell⟧
2 15-01 T1 Current Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
3 15-02 T2 Current Value 1 0~9999 0 - O O O ⟦blank source cell⟧
4 15-03 T2 Current Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
5 15-04 T3 Current Value 1 0~9999 0 - O O O ⟦blank source cell⟧
6 15-05 T3 Current Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
7 15-06 T4 Current Value 1 0~9999 0 - O O O ⟦blank source cell⟧
8 15-07 T4 Current Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
9 15-08 T5 Current Value 1 0~9999 0 - O O O ⟦blank source cell⟧
10 15-09 T5 Current Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
11 15-10 T6 Current Value 1 0~9999 0 - O O O ⟦blank source cell⟧
12 15-11 T6 Current Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
13 15-12 T7 Current Value 1 0~9999 0 - O O O ⟦blank source cell⟧
14 15-13 T7 Current Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
15 15-14 T8 Current Value 1 0~9999 0 - O O O ⟦blank source cell⟧
16 15-15 T8 Current Value 2 (Mode 7) 0~9999 0 - O O O ⟦blank source cell⟧
17 15-16 C1 Current Value 0~65534 0 - O O O ⟦blank source cell⟧
18 15-17 C2 Current Value 0~65534 0 - O O O ⟦blank source cell⟧
19 15-18 C3 Current Value 0~65534 0 - O O O ⟦blank source cell⟧
20 15-19 C4 Current Value 0~65534 0 - O O O ⟦blank source cell⟧
21 15-20 C5 Current Value 0~65534 0 - O O O ⟦blank source cell⟧
22 15-21 C6 Current Value 0~65534 0 - O O O ⟦blank source cell⟧
23 15-22 C7 Current Value 0~65534 0 - O O O ⟦blank source cell⟧

Manual — Parameter summary:Group 15 — page 146

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-23

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-24

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-25

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-26

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-27

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-28

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-29

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-30

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-31

Group 15: PLC Monitoring Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 15-32

Parameter summary:Group 15 table1 — PDF page 146

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 15-23 C8 Current Value 0~65534 0 - O O O ⟦blank source cell⟧
2 15-24 AS1 Results 0~65534 0 - O O O ⟦blank source cell⟧
3 15-25 AS2 Results 0~65534 0 - O O O ⟦blank source cell⟧
4 15-26 AS3 Results 0~65534 0 - O O O ⟦blank source cell⟧
5 15-27 AS4 Results 0~65534 0 - O O O ⟦blank source cell⟧
6 15-28 MD1 Results 0~65534 0 - O O O ⟦blank source cell⟧
7 15-29 MD2 Results 0~65534 0 - O O O ⟦blank source cell⟧
8 15-30 MD3 Results 0~65534 0 - O O O ⟦blank source cell⟧
9 15-31 MD4 Results 0~65534 0 - O O O ⟦blank source cell⟧
10 15-32 TD Current Value 0~65534 0 - O O O ⟦blank source cell⟧

Manual — Parameter summary:Group 16 — page 147

16-00/01/02 monitor range5–82 means12-05–12-82, defaults16/17/18 selectingfrequencycommand/outputfrequency/outputcurrent.16-03 decimal format ranges preserve gaps9999→10001,19999→20001,29999→30001;do not invent values10000/20000/30000.16-04 unit list starts0NoUnit through9/m and continues10–24 onPDF148.

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 16-00

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 16-01

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 16-02

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 16-03

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 16-04

Shared source cells (coordinates refer to this table):

Parameter summary:Group 16 table1 — PDF page 147

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 16-00 Main Screen Monitoring 5~82 (Parameter 12-05~12-82) When using LCD to operate, the monitored item displays in the first line. (default is frequency command) 16 - O O O *1 *6
2 16-01 Sub-Screen Monitoring 1 5~82 (Parameter 12-05~12-82) When using LCD to operate, the monitored item displays in the second line. (default is output frequency) 17 - O O O *1 *6
3 16-02 Sub-Screen Monitoring 2 5~82(Parameter 12-05~12-82) when using LCD to operate, the monitored item displays in the third line. (default is output current) 18 - O O O *1 *6
4 16-03 Selection of Display Unit 0~39999: Determine the display way and unit of frequency command 0 - O O O ⟦blank source cell⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0: Frequency display unit is 0.01Hz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Frequency display unit 0.01% ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Rpm display; motor rotation speed is set by the control modes to select IM (02-07)/ PM (22-03) motor poles to calculate. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3~39: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 40~9999: Users specify the format, Input 0XXXX represents the display of XXXX at 100%. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10001~19999: Users specify the format; Input 1XXXX represents the display of XXX.X at 100%. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 20001~29999: Users specify the format, Input 2XXXX represents the display of XX.XX at 100%. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 30001~39999: Users specify the format, Input 3XXXX represents the display of X.XXX at 100%. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 16-04 Selection of Engineering Unit 0: No Unit 0 - O O O *6
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: FPM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: CFM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: PSI ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: GPH ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: GPM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: IN ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7: FT ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8: /s ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9: /m ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Parameter summary:Group 16 — page 148

First15 rows continue16-04 unit choices10–24.16-16/17 P1 weekday range begins1Mon,2Tue,3Wed,4Thu,5Fri,6Sat here and7Sun continues below header onPDF149.16-07 copy options distinguish read inverter→operator,write operator→inverter,and compare.16-09 removed-LCD choice0 keep operating versus1fault stop retained.

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters.

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-04 continuation fromPDF147

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-05

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-06

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-07

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-08

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-09

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-10

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-11

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-12

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-13

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-14

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-15

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-16

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-17

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c1, r1c2, r1c4, r1c5, r1c9, r2c1, r2c2, r2c4, r2c5, r2c9, r3c1, r3c2, r3c4, r3c5, r3c9, r4c1, r4c2, r4c4, r4c5, r4c9, r5c1, r5c2, r5c4, r5c5, r5c9, r6c1, r6c2, r6c4, r6c5, r6c9, r7c1, r7c2, r7c4, r7c5, r7c9, r8c1, r8c2, r8c4, r8c5, r8c9, r9c1, r9c2, r9c4, r9c5, r9c9, r10c1, r10c2, r10c4, r10c5, r10c9, r11c1, r11c2, r11c4, r11c5, r11c9, r12c1, r12c2, r12c4, r12c5, r12c9, r13c1, r13c2, r13c4, r13c5, r13c9, r14c1, r14c2, r14c4, r14c5, r14c9, r15c1, r15c2, r15c4, r15c5, r15c9. A header spans across these blank regions in the native text; no header value is propagated into them.

Parameter summary:Group 16 table1 — PDF page 148

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10: /h ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 11: °F ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 12: inW ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 13: HP ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 14: m/s ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 15: MPM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 16: CMM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 17: W ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 18: KW ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 19: m ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 20: °C ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 21: RPM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 22: Bar ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 23: Pa ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 24: KPa Note4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 16-05 LCD Backlight 0~7 5 - O O O *1
17 16-06 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 16-07 Copy Function Selection 0: Do not copy parameters 0 - O O O ⟦blank source cell⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Read inverter parameters and save to the operator. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Write the operator parameters to inverter. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Compare parameters of inverter and operator. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 16-08 Selection of Allowing Reading 0: Do not allow to read inverter parameters and save it to the operator. 0 - O O O ⟦blank source cell⟧
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Allow to read inverter parameters and save it to the operator. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
24 16-09 Selection of Operator Removed (LCD) 0: Keep operating when LCD operator is removed. 0 - O O O *1
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Display fault to stop when LCD operator is removed ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
26 16-10 RTC Time Display Setting 0: Hide 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Display ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
28 16-11 RTC Date Setting 12.01.01 ~ 99.12.31 12.01.0 1 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
29 16-12 RTC Time Setting 00:00 ~ 23:59 00:00 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
30 16-13 RTC Timer Function 0: Disable 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
31 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
32 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Set by DI ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
33 16-14 P1 Start Time 00:00 ~ 23:59 08:00 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
34 16-15 P1 Stop Time 00:00 ~ 23:59 18:00 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
35 16-16 P1 Start Date 1:Mon, 2:Tue, 3:Wed, 4:Thu,:5:Fri,:6:Sat, 1 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
36 16-17 P1 Stop Date ⟦null: no independent source value⟧ 5 ⟦blank source cell⟧ O O O ⟦blank source cell⟧

Manual — Parameter summary:Group 16 — page 149

7:Sun at page top is body continuation for16-16/16-17 fromPDF148, visually below header though native parser merged it into header.16-32/33/34/35 default1/2/4/8 respectively;all share the single range0–31 representingP1/P2/P3/P4andOff combinations. Shared range spans all four code rows; no exclusive nearest-row option assignment. P2/P3/P4 start08:00/stop18:00,startweekday1/stopweekday5 retained.

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters.

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-16/16-17 continuation fromPDF148

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-18

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-19

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-20

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-21

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-22

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-23

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-24

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-25

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-26

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-27

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-28

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-29

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-30

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: 16-31

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Cross-page continuation scope is preserved in row group metadata and visual association records;blank code/default cells are not new parameters. Row group: Shared timer source options16-32–16-35;code/default spans independent

r1c3: Source continuation context: 7:Sun. 16-16/16-17 weekday continuation fromPDF148

Shared source cells (coordinates refer to this table):

Parameter summary:Group 16 table1 — PDF page 149

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 16-18 P2 Start Time 00:00 ~ 23:59 08:00 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
3 16-19 P2 Stop Time 00:00 ~ 23:59 18:00 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
4 16-20 P2 Start Date 1:Mon,2:Tue,3:Wed, 4:Thu,:5:Fri,:6:Sat,7:Sun 1 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
5 16-21 P2 Stop Date ⟦null: no independent source value⟧ 5 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
6 16-22 P3 Start Time 00:00 ~ 23:59 08:00 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
7 16-23 P3 Stop Time 00:00 ~ 23:59 18:00 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
8 16-24 P3 Start Date 1:Mon,2:Tue,3:Wed, 4:Thu,:5:Fri,:6:Sat, 7:Sun 1 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
9 16-25 P3 Stop Date ⟦null: no independent source value⟧ 5 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
10 16-26 P4 Start Time 00:00 ~ 23:59 08:00 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
11 16-27 P4 Stop Time 00:00 ~ 23:59 18:00 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
12 16-28 P4 Start Date 1:Mon, 2:Tue, 3:Wed, 4:Thu, 5:Fri, 6:Sat, 7:Sun 1 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
13 16-29 P4 Stop Date ⟦null: no independent source value⟧ 5 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
14 16-30 Selection of RTC Offset 0: Disable 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Set by DI ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 16-31 RTC Offset Time Setting 00:00 ~ 23:59 00:00 - O O O ⟦blank source cell⟧
18 16-32 Source of Timer 1 0: None, 1:P1, 2: P2, 3:P1+P2 4: P3, 5:P1+P3, 6: P2+P3, 7:P1+P2+P3, 8: P4, 9:P1+P4, 10: P2+P4, 11: P1+P2+P4 12: P3+P4 13: P1+P3+P4, 14: P2+P3+P4 15: P1+P2+P3+P4, 16: Off, 17:Off+P1 18: Off+P2, 19: Off+P1+P2 20: Off+P3, 21: Off+P1+P3 22: Off+P2+P3 23: Off+P1+P2+P3 24: Off+P4 25: Off+P1+P4 26: Off+P2+P4 27: Off+P1+P2+P4 28: Off+P3+P4 29: Off+P1+P3+P4 30: Off+P2+P3+P4 31: Off+P1+P2+P3+P4 1 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
19 16-33 Source of Timer 2 ⟦null: no independent source value⟧ 2 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
20 16-34 Source of Timer 3 ⟦null: no independent source value⟧ 4 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
21 16-35 Source of Timer 4 ⟦null: no independent source value⟧ 8 ⟦blank source cell⟧ O O O ⟦blank source cell⟧

Manual — Parameter summary:Group 16,Group 17 — page 150

16-37 four bits independently controlRun1–Run4:0forward/1reverse withRun1 rightmost andRun4 leftmost,default0000b.17-00 IM auto-tuning defaultVF:2,SLV:6;PMSLVX. Choice5combines4+2+0;choice6combines4+2+1;both carryun-numberedNote.17-04 default50.0/60.0 retained without selecting one.

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 16-36

Group 16: LCD Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 16-37

Shared source cells (coordinates refer to this table):

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-00

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-01

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-02

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-03

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-04

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-05

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-06

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-07

Adjacent source context — repeated to preserve continuation:

Parameter summary:Group 16,Group 17 table1 — PDF page 150

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 16-36 Selection of RTC Speed 0: Off 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: By Timer 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: By Timer 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: By Timer 3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: By Timer 4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: By Timer 1+2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 16-37 Selection of RTC Rotation Direction xxx0b: RTC Run1 Forward Rotation 0000b ⟦blank source cell⟧ O O O ⟦blank source cell⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xxx1b: RTC Run1 Reverse Rotation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx0xb: RTC Run2 Forward Rotation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx1xb: RTC Run2 Reverse Rotation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x0xxb: RTC Run3 Forward Rotation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x1xxb: RTC Run3 Reverse Rotation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0xxxb: RTC Run4 Forward Rotation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1xxxb: RTC Run4 Reverse Rotation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Parameter summary:Group 16,Group 17 table2 — PDF page 150

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 17-00 Mode Selection of Automatic Tuning 0: Rotational Auto-tuning VF:2 SLV:6 - O O X ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Static Auto-tuning ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Stator Resistance Measurement ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Loop Tuning ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: Rotational Auto-tuning Combination (Item: 4+2+0) Note ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: Static Auto-tuning Combination (Item: 4+2+1) Note ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 17-01 Motor Rated Output Power 0.00~600.00 - KW O O X ⟦blank source cell⟧
9 17-02 Motor Rated Current 0.1~1200.0 - A O O X ⟦blank source cell⟧
10 17-03 Motor Rated Voltage 200V: 50.0~240.0 - V O O X ⟦blank source cell⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V:100.0~480.0 - ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 17-04 Motor Rated Frequency 4.8~599.00 (Note8) 50.0/ 60.0 Hz O O X ⟦blank source cell⟧
13 17-05 Motor Rated Speed 0~24000 KVA*a rpm O O X ⟦blank source cell⟧
14 17-06 Pole Number of Motor 2~16 (Even) 4 Pole O O X *6
15 17-07 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Parameter summary:Group 17,Group 18 — page 151

*a: KVA means the default value of this parameter will be changed by different capacities of inverter.

■1: It can be set when 17-00=1, 2, 6.

Group 19 Reserved

17-09 symbol■1 means it can be set when17-00=1,2,6. KVA*a defaults change with invertercapacity.18-00 low-speed slip compensation defaultVF0.00 versusSLV1.00;18-02/03/04V/F-only;18-05/06SLV-only. Group19 explicitlyReserved. No new parameter records invented for it.

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-08

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-09

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-10

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-11

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-12

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-13

Group 17: IM Motor Automatic Tuning Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 17-14

Shared source cells (coordinates refer to this table):

Group 18: Slip Compensation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 18: Slip Compensation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 18-00

Group 18: Slip Compensation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 18-01

Group 18: Slip Compensation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 18-02

Group 18: Slip Compensation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 18-03

Group 18: Slip Compensation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 18-04

Group 18: Slip Compensation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 18-05

Group 18: Slip Compensation Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 18-06

Adjacent source context — repeated to preserve continuation:

Parameter summary:Group 17,Group 18 table1 — PDF page 151

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 17-08 Motor No-load Voltage 200V: 50~240 KVA*a V O O X ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 400V: 100~480 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 17-09 Motor Excitation Current 0.01~600.00 (15%~70% motor rated current) KVA*a A O O X ■1
4 17-10 Automatic Tuning Start 0: Disable 0 - O O X ⟦blank source cell⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 17-11 Error History of Automatic Tuning 0: No Error 0 - O O X ⟦blank source cell⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Motor Data Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Stator Resistance Tuning Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Leakage Induction Tuning Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Rotor Resistance Tuning Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: Mutual Induction Tuning Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7: DT Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8: Motor Acceleration Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9: Warning ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 17-12 Leakage Inductance Ratio 0.1 ~ 15.0 3.4 % X O X ⟦blank source cell⟧
17 17-13 Slip Frequency 0.10 ~ 20.00 1.00 Hz X O X ⟦blank source cell⟧
18 17-14 Rotational Tuning Mode Selection 0: VF Mode 1: Vector Mode 0 - O O X Note1

Parameter summary:Group 17,Group 18 table2 — PDF page 151

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 18-00 Slip Compensation Gain at Low Speed 0.00~2.50 VF: 0.00 - O O X *1
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ SLV: 1.00 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 18-01 Slip Compensation Gain at High Speed -1.00~1.00 0.0 - O O X *1
4 18-02 Slip Compensation Limit 0~250 200 % O X X ⟦blank source cell⟧
5 18-03 Slip Compensation Filter Time 0.0~10.0 1.0 Sec O X X ⟦blank source cell⟧
6 18-04 Regenerative Slip Compensation Selection 0: Disable 0 - O X X ⟦blank source cell⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 18-05 FOC Delay Time 1~1000 100 ms X O X ⟦blank source cell⟧
9 18-06 FOC Gain 0.00~2.00 0.1 - X O X ⟦blank source cell⟧

Manual — Parameter summary:Group 20 Speed Control Parameters* — page 152

*: This parameter group is enabled in SLV and PMSLV modes.

Group20 general note says enabled inSLV andPMSLV, but individual rows retainPMSLVX where printed.20-01/03 defaultsSLV0.500sec/PMSLV0.08sec;20-10and20-12 differ0.05/0.06sec;no normalization. Group note never overrides individual mode cells.

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-00

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-01

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-02

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-03

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-04

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-05

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-07

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-08

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-09

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-10

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-11

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-12

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-13

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-14

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-15

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-16

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-17

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-18

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-19

~

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-33

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-34

Group 20 Speed Control Parameters . Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly;*10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 20-35

Shared source cells (coordinates refer to this table):

Parameter summary:Group 20 Speed Control Parameters* table1 — PDF page 152

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 20-00 ASR Gain 1 0.00~250.00 3.00 - X O O *1
2 20-01 ASR Integral Time 1 0.001~10.000 SLV: 0.500 PMSLV :0.08, Sec X O O *1
3 20-02 ASR Gain 2 0.00~250.00 3.00 - X O O *1
4 20-03 ASR Integral Time 2 0.001~10.000 SLV: 0.500 PMSLV :0.08, Sec X O O *1
5 20-04 ASR Integral Time Limit 0~300 200 % X O O ⟦blank source cell⟧
6 20-05 20-06 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 20-07 Selection of Acceleration and Deceleration of P/PI 0: PI speed control will be enabled only in constant speed. For accel/ decel, only use P control. 1 - X O X ⟦blank source cell⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Speed control is enabled either in constant speed or accel/ decel. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 20-08 ASR Delay Time 0.000~0.500 0.004 Sec X O O ⟦blank source cell⟧
10 20-09 Speed Observer Proportional (P) Gain 1 0.00~2.55 0.61 - X O X *1
11 20-10 Speed Observer Integral(I) Time 1 0.01~10.00 0.05 Sec X O X *1
12 20-11 Speed Observer Proportional (P) Gain 2 0.00~2.55 0.61 - X O X *1
13 20-12 Speed Observer Integral(I) Time 2 0.01~10.00 0.06 Sec X O X *1
14 20-13 Low-pass Filter Time Constant of Speed Feedback 1 1~1000 4 ms X O X ⟦blank source cell⟧
15 20-14 Low-pass Filter Time Constant of Speed Feedback 2 1~1000 30 ms X O X ⟦blank source cell⟧
16 20-15 ASR Gain Change Frequency 1 0.0~599.00 (Note8) 4.0 Hz X O O ⟦blank source cell⟧
17 20-16 ASR Gain Change Frequency 2 0.0~599.00 (Note8) 8.0 Hz X O O ⟦blank source cell⟧
18 20-17 Torque Compensation Gain at Low Speed 0.00~2.50 1.00 - X O X *1
19 20-18 Torque Compensation Gain at High Speed -10~10 0 % X O X *1
20 20-19 ~ 20-32 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 20-33 Constant Speed Detection Level 0.1~5.0 1.0 ⟦blank source cell⟧ X O O *7
22 20-34 Derating of Compensation Gain 0~25600 0 % X O X *7
23 20-35 Derating of Compensation Time 0~30000 100 ms X O X *7

Manual — Parameter summary:Group 21 Torque Control Parameters,Group 22 — page 153

Group21 torque limits21-05..08 default160%,V/F X andSLV/PMSLV O. Group22 availableonlywhenPMControlMode selected;individualX/X/O marks retained.22-04 says onlyone of22-04or22-06 needssetting,theprogramcalculatesother.22-21 lastrow begins0Disable;remaining definition continuesPDF154outside this part,so do not treat this partial optionlist as complete.

Group 21 Torque Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.

Group 21 Torque Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 21-00

~

Group 21 Torque Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 21-05

Group 21 Torque Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 21-06

Group 21 Torque Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 21-07

Group 21 Torque Control Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. Row group: 21-08

Shared source cells (coordinates refer to this table):

Group 22: PM Motor Parameters-

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only.

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-00

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-01

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-02

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-03

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-04

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-05

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-06

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-07

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-08

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-10

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-11

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-12

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-14

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-15

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-16

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-17

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-18

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-19

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation.22-21definition continuesPDF154outside thispart;partial optionlist only. Row group: 22-21

Parameter summary:Group 21 Torque Control Parameters,Group 22 table1 — PDF page 153

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 21-00 ~ 21-04 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 21-05 Positive Torque Limit 0~160 160 % X O O ⟦blank source cell⟧
3 21-06 Negative Torque Limit 0~160 160 % X O O ⟦blank source cell⟧
4 21-07 Forward Regenerative Torque Limit 0~160 160 % X O O ⟦blank source cell⟧
5 21-08 Reversal Regenerative Torque Limit 0~160 160 % X O O ⟦blank source cell⟧

Parameter summary:Group 21 Torque Control Parameters,Group 22 table2 — PDF page 153

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 22-00 Rated Power of PM Motor 0.00~600.00 KVA kW X X O ⟦blank source cell⟧
2 22-01 PM Motor Rated Voltage 200V: 50.0~240.0 400V: 100.0~480.0 220.0 440.0 V X X O Note8
3 22-02 Rated Current of PM Motor 0.1~999.9 KVA A X X O ⟦blank source cell⟧
4 22-03 Pole Number of PM Motor 2~96 6 pole s X X O ⟦blank source cell⟧
5 22-04 Rated Rotation Speed of PM Motor 6~60000 (22-04, 22-06, only need to set one of them, the program will calculate the other.) 1500 rpm X X O ⟦blank source cell⟧
6 22-05 Maximum Rotation Speed of PM Motor 6~60000 1500 rpm X X O ⟦blank source cell⟧
7 22-06 PM Motor Rated Frequency 4.8~599.00 (Note8) 75.0 Hz X X O ⟦blank source cell⟧
8 22-07 PM Type Selection 0:SPM 1:IPM 0 ⟦blank source cell⟧ X X O Note8
9 22-08 ~ 22-09 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 22-10 PM SLV Start Current 20 ~ 200% Motor Rated Current 80 % X X O ⟦blank source cell⟧
11 22-11 I/F Mode Start Frequency Switching Point 10 ~ 100% 10.0 % X X O Note2
12 22-12 22-13 Reserved (Note6) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 22-14 PM Motor Armature Resistance 0.001 ~ 30.000 1.000 Ω X X O ⟦blank source cell⟧
14 22-15 PM Motor D-axis Inductance 0.01 ~ 300.00 10.00 mH X X O ⟦blank source cell⟧
15 22-16 PM Motor Q-axis Inductance 0.01 ~ 300.00 10.00 mH X X O ⟦blank source cell⟧
16 22-17 PM No-Load Voltage 200V: 0~250 400V: 0~500 150 300 V X X O Note8
17 22-18 Flux-Weakening Control 0~120 90 % X X O Note1
18 22-19 22-20 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 22-21 SLV PM Motor Tuning 0: Disable 0 - X X O ⟦blank source cell⟧

Manual — PM and Pump/HVAC summary — page 154

First row 1:Enable completes22-21 onPDF153.22-22 retains reserved error options and named errors;22-25 default2 Note8;22-27/28 conditional on22-25=2 or22-26=1. PM X/X/O mode marks retained.23-00 choices0Disable,1Pump,2HVAC,3Compressor*7;23-01 single/master/slave1/slave2/slave3 distinct.

Group 22: PM Motor Parameters-

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 22-21 continuation fromPDF153

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 22-22

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 22-25

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 22-26

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 22-27

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 22-28

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 22-29

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 22-30

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 22-31

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 22-32

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 22-33

only available when PM Control Mode is selected. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 22-34

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c1, r1c2, r1c4, r1c5, r1c9. A header spans across these blank regions in the native text; no header value is propagated into them.

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-00

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-01

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-02

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-03

PM and Pump/HVAC summary table1 — PDF page 154

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧
2 22-22 Fault History of SLV PM Motor Tuning 0. No Error 0 -- X X O *4
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1~4: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: Circuit tuning time out. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7: Other motor tuning errors ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9: Current Abnormity Occurs while Loop Adjustment. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 11: Stator Resistance Measurement Timeout ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 12: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 22-25 Detection Mode Selection of Default Magnetic Pole 0: Angle before Stop 2 (Note8) -- X X O Note4
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Mode 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Mode 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 22-26 Estimator Mode 0~1 (in PMSLV mode) 0 - X X O Note6
16 22-27 Mode 2 Voltage Command 5~120 (Note8) (22-25=2 or 22-26=1is enabled) 50 % X X O Note4
17 22-28 Mode 2 Frequency Division Ratio 0~8 (Note8) (22-25=2 or 22-26=1is enabled) 2 ⟦blank source cell⟧ X X O Note4
18 22-29 Field-Weakening Voltage Control 80~110 (Note8) 100 % X X O Note4
19 22-30 SPM Speed Estimation Gain 1~150 85 % X X O Note6
20 22-31 SPM Speed Estimation Filter Value 1~2000 60 HZ X X O Note6
21 22-32 MTPA Selection 0: Disable 0 - X X O Note8
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Mode 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 22-33 MTPA Gain 0~400% 200 % X X O Note8
24 22-34 IPM Estimator Gain 1~300 180 - X X O Note8

PM and Pump/HVAC summary table2 — PDF page 154

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 23-00 Function Selection 0: Disable 0 - O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Pump ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: HVAC ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Compressor *7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 23-01 Setting of Single & Multiple Pumps and Master & Slave Machines 0: Single Pump 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Master ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Slave 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Slave 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Slave 3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 23-02 Operation Pressure Setting 0.10 ~ 650.00 4.00 PSI O O O *6
11 23-03 Maximum Pressure of Pressure Transmitter 0.10 ~ 650.00 10.00 PSI O O O *6

Manual — Pump/HVAC summary — page 155

23-09/12/15/24 ranges explicitly depend on23-20=0 pressure versus1 percentage. Literal unit column %/PSI retained without implying ordering.23-26/27 KVA defaults are capacity dependent.23-29 default3 Hr/min selection depends on23-72,not one inferred unit.

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-04

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-05

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-06

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-07

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-08

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-09

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-10

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-11

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-12

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-13

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-14

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-15

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-16

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-17

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-18

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-19

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-20

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-21

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-22

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-23

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-24

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-25

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-26

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-27

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-28

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-29

Shared source cells (coordinates refer to this table):

Pump/HVAC summary table1 — PDF page 155

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 23-04 Pump Pressure Command Source 0: Set by 23-02 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Set by AI ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 23-05 Display Mode Selection 0: Display of Target and Pressure Feedback * 0 % O O O ⟦blank source cell⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Only Display Target Pressure ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Only Display Feedback Pressure ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 23-06 Proportion Gain (P) 0.00~10.00 3.00 - O O O ⟦blank source cell⟧
7 23-07 Integral Time (I) 0.0~100.0 0.5 Sec O O O ⟦blank source cell⟧
8 23-08 Differential Time (D) 0.00~10.00 0.00 Sec O O O ⟦blank source cell⟧
9 23-09 Tolerance Range of Constant Pressure 23-20=0 : 0.01 ~ 650.00 23-20=1 : 1~100 5 %/ PSI O O O *6
10 23-10 Sleep Frequency of Constant Pressure 0.00 ~ 599.00 (Note8) 30.00 Hz O O O ⟦blank source cell⟧
11 23-11 Sleep Time of Constant Pressure 0.0 ~ 255.5 0.0 Sec O O O ⟦blank source cell⟧
12 23-12 Maximum Pressure Limit 23-20=0 : 0.00 ~ 650.00 23-20=1 : 0~100 50 %/ PSI O O O *6
13 23-13 Warning Time of High Pressure 0.0 ~ 600.0 10.0 Sec O O O ⟦blank source cell⟧
14 23-14 Stop Time of High Pressure 0.0 ~ 600.0 20.0 Sec O O O ⟦blank source cell⟧
15 23-15 Minimum Pressure Limit 23-20=0 : 0.00 ~ 650.00 23-20=1 : 0~100 5 %/ PSI O O O *6
16 23-16 Warning Time of Low Pressure 0.0 ~ 600.0 0.0 Sec O O O ⟦blank source cell⟧
17 23-17 Fault Stop Time of Low Pressure 0.0 ~ 600.0 0.0 Sec O O O ⟦blank source cell⟧
18 23-18 Time of Loss Pressure Detection 0.0 ~ 600.0 0.0 Sec O O O ⟦blank source cell⟧
19 23-19 Proportion of Loss Pressure Detection 0 ~ 100 0 % O O O ⟦blank source cell⟧
20 23-20 Switching of Pressure and Percentage 0:Pressure 1 - O O O Note4
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1:Percentage ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 23-21 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 23-22 Slave Trip Frequency 0.00 ~ 599.00 (Note8) 45.00 Hz O O O Note2
24 23-23 Direction of Water Pressure Detection 0: Upward Detection 1 - O O O ⟦blank source cell⟧
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Downward Detection ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
26 23-24 Range of Water Pressure Detection 23-20=0 : 0.00 ~ 65.00 23-20=1 : 0~10 1 %/ PSI O O O *6
27 23-25 Period of Water Pressure Detection 0.0 ~ 200.0 30.0 Sec O O O ⟦blank source cell⟧
28 23-26 Acceleration Time of Water Pressure Detection 0.1 ~ 6000.0 KVA Sec O O O ⟦blank source cell⟧
29 23-27 Deceleration Time of Water Pressure Detection 0.1 ~ 6000.0 KVA Sec O O O ⟦blank source cell⟧
30 23-28 Forced Run Command 0.00 ~ 599.00 (Note8) 0.00 Hz O O O ⟦blank source cell⟧
31 23-29 Switching Time of Multiple Pumps in Parallel 0 ~ 240 3 Hr/ min O O O ⟦blank source cell⟧

Manual — Pump/HVAC summary — page 156

23-35 choices0–4 remain distinct.23-36 pressure units PSI/inW/Bar/Pa.23-44 pulse options0Disable,1:0.1kWh,2:1kWh,3:10kWh,4:100kWh,5:1000kWh.23-46 maximum flow default10000GPM and23-47 target5000GPM are separate parameters.

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-30

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-31

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-32

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-34

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-35

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-36

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-37

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-38

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-39

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-40

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-41

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-42

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-43

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-44

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-45

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-46

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-47

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-48

Shared source cells (coordinates refer to this table):

Pump/HVAC summary table1 — PDF page 156

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 23-30 Detection Time of Multiple Pumps in Parallel Running Start 0.0 ~ 30.0 0.0 Sec O O O ⟦blank source cell⟧
2 23-31 Synchronous Selection of Multiple Pumps in Parallel 0: Disable 1 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Pressure Setting and Run/Stop ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Pressure Setting ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Run/Stop ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 23-32 23-33 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 23-34 Tolerance Range of Constant Pressure 2 23-20=0 : 0.01 ~ 650.00 23-20=1 : 1~100 5 %/ PSI O O O Note1
8 23-35 Selection of Multiple Pumps Shift Operation 0: No function 1: Timer Alternately Selection 2: Sleep Stop Alternately Selection 3: Timer and Sleep Stop Alternately Selection 4: Multiple Pumps Test Mode 1 ⟦blank source cell⟧ O O O Note2
9 23-36 PUMP Unit Display 0:PSI 0 ⟦blank source cell⟧ O O O Note4
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1:inW ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2:Bar ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3:Pa ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 23-37 Leakage Detection Time 0.0~100.0 0.0 Sec O O O *7
14 23-38 Pressure Variation of Leakage Detection Restart 23-20=0 : 0.01 ~ 65.00 23-20=1 : 1~10 1 %/ PSI O O O *7
15 23-39 Pressure Tolerance Range of Leakage Detection Restart 23-20=0 : 0.01 ~ 650.00 23-20=1 : 1~100 5 %/ PSI O O O *7
16 23-40 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 23-41 Local/ Remote Key 0: Disable 1 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 23-42 Energy Recalculating 0: Disable (Energy Accumulating) 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 23-43 Electricity Price per kWh 0.000 ~ 5.000 0.000 $ O O O ⟦blank source cell⟧
22 23-44 Selection of Accumulative Electricity Pulse Output Unit 0: Disable 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Unit for 0.1kWh ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
24 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Unit for 1kWh ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Unit for 10kWh ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Unit for 100kWh ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: Unit for 1000kWh ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
28 23-45 Given Modes of Flow Meters Feedback 0: Disable 1 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
29 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Analog Input ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
30 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Pulse Input ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
31 23-46 Maximum Value of Flow Meters 1 ~ 50000 10000 GPM O O O ⟦blank source cell⟧
32 23-47 Target Value of Flow Meters 1 ~ 50000 5000 GPM O O O ⟦blank source cell⟧
33 23-48 Maximum Flow Value of Feedback 0.01 ~ 99.00 80.00 % O O O ⟦blank source cell⟧

Manual — Pump/HVAC summary — page 157

23-60 HVAC units GPM/FPM/CFM/GPH. Unprinted23-61–65 not invented.23-66–70 carry V/F-only O/X/X.23-72 selects hours0/minutes1 with default0.23-76 option2 continues ontoPDF158.

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-49

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-50

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-51

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-52

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-53

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-54

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-55

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-56

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-57

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-58

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-59

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-60

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-66

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-67

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-68

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-69

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-70

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-71

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-72

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-73

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-74

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-75

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-76

Shared source cells (coordinates refer to this table):

Pump/HVAC summary table1 — PDF page 157

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 23-49 Maximum Flow Warning Time of Feedback 0.0 ~ 255.0 3.0 Sec O O O ⟦blank source cell⟧
2 23-50 Maximum Flow Stop Time of Feedback 0.0 ~ 255.0 6.0 Sec O O O ⟦blank source cell⟧
3 23-51 Minimum Flow Value of Feedback 0.01 ~ 99.00 10.00 % O O O ⟦blank source cell⟧
4 23-52 Minimum Flow Warning Time of Feedback 0.0 ~ 255.0 3.0 Sec O O O ⟦blank source cell⟧
5 23-53 Minimum Flow Stop Time of Feedback 0.0 ~ 255.0 6.0 Sec O O O ⟦blank source cell⟧
6 23-54 Detection Function of Low Suction 0: Disable 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: PID Error Value ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Current ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Current and PID Error Value ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 23-55 Detection Time of Low Suction 0 ~ 30.0 10.0 Sec O O O ⟦blank source cell⟧
11 23-56 PID Error Level of Low Suction 0 ~ 30 10 % O O O ⟦blank source cell⟧
12 23-57 Current Level of Low Suction(Motor Rated Current) 0 ~ 100 10 % O O O ⟦blank source cell⟧
13 23-58 Reaction of Low Suction 0: Disable 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Warning ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Fault & Restart ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 23-59 Source of HVAC Pressure Command 0: Set by 23-47 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Set by AI ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 23-60 HVAC Unit Display 0: GPM 0 ⟦blank source cell⟧ O O O Note4
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: FPM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: CFM ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: GPH ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 23-66 Derating of Current Level 10~200 110 % O X X ⟦blank source cell⟧
24 23-67 Derating of Delay Time 1.0~20.0 10.0 Sec O X X ⟦blank source cell⟧
25 23-68 Derating of Frequency Gain 1~100 90 % O X X ⟦blank source cell⟧
26 23-69 OL4 Current Level 10~200 120 % O X X ⟦blank source cell⟧
27 23-70 OL4 Delay Time 0~20.0 5.0 Sec O X X ⟦blank source cell⟧
28 23-71 Maximum Pressure Setting 0.10~650.00 10.00 PSI O O O Note3
29 23-72 Switching Time of Alternation in Parallel 0: Hour 0 ⟦blank source cell⟧ O O O Note4
30 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Minute ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
31 23-73 Slave Wake-up Selection 0: Disable 0 ⟦blank source cell⟧ O O O Note4
32 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
33 23-74 High Pressure Setting 0: Disable 2 ⟦blank source cell⟧ O O O Note5
34 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: High Pressure Warning ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
35 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: High Pressure Warning or Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
36 23-75 Low Pressure Setting 0: Disable 0 ⟦blank source cell⟧ O O O Note5
37 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Low Pressure Warning ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
38 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Low Pressure Warning or Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
39 23-76 High Flow Setting 0: Disable 2 ⟦blank source cell⟧ O O O Note5
40 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: High Flow Warning ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Pump/HVAC and pump-control summary — page 158

First row2:High Flow Warning or Error completes23-76 fromPDF157.23-77 default2 low-flow protection;23-78 option2 literally says Low Pressure Error despite Loss of Pressure Detection name.24-00 modes0–9 distinguish pump-card one-to-eight and built-in one-to-three operations.24-01 first rows start rightmost reserved bit,Relay2,then Relay3;continuesPDF159.

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-76 continuation fromPDF157

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-77

Group 23 Pump & HVAC Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-78

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c1, r1c2, r1c4, r1c5, r1c9. A header spans across these blank regions in the native text; no header value is propagated into them.

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-00

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-01

Pump/HVAC and pump-control summary table1 — PDF page 158

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: High Flow Warning or Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧
2 23-77 Low Flow Setting 0: Disable 2 ⟦blank source cell⟧ O O O Note5
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Low Flow Warning ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Low Flow Warning or Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 23-78 Selection of Loss Pressure Detection 0: Disable 0 ⟦blank source cell⟧ O O O Note5
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Loss Pressure Warning ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Low Pressure Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Pump/HVAC and pump-control summary table2 — PDF page 158

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 24-00 Selection of Pump Control Function 0: Function of 1 to 8 Pump Card is Disabled 0 - O O O ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Fixed Modes of Inverter Pump: First on and Last off; then Stop All. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2: Fixed Modes of Inverter Pump: Only Stop Inverter Pump. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3: Fixed Modes of Inverter Pump: First on and First Off; then Stop All. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4: Cycle Modes of Inverter Pump: First on and First Off; then Stop All. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5: Cycle Modes of Inverter Pump: Only Stop Inverter Pump. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6: 1 to 3 Relay of Cycle Modes of Inverter Pump: First on and First off; then Stop All ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7: Cycle Modes of Inverter Pump: First on and First Off; then Stop All. And First Boot Relay in Cycling.Note1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8: Cycle Modes of Inverter Pump 1 to 3 Relay: First on and First Off; then Stop All. And First Boot Relay in Cycling.Note1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9: Cycle Modes of Inverter Pump 1 to 3 Relay: Only Stop Inverter Pump. And First Boot Relay in Cycling.Note3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 24-01 Selection of Relay 2-4 Function xxx0b: Reserved 0000b ⟦blank source cell⟧ O O O ⟦blank source cell⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xxx1b: Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx0xb: Relay 2 Disable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx1xb: Relay 2 Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x0xxb: Relay 3 Disable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Pump-control summary — page 159

First three rows complete24-01: x1xxb Relay3 enabled;0xxxb Relay4 disabled;1xxxb Relay4 enabled.24-02 maps Relay5–8 bits with0000b default.24-07 source0 pump-card one-to-eight,1 built-in one-to-three;24-08 literal Hr/min.24-17 toggles PID during pump increase/decrease.

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-01 continuation fromPDF158

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-02

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-03

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-04

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-05

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-06

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-07

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-08

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-09

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-10

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-11

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-12

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-13

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-14

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-15

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-16

Group 24 Pump Control Function Parameters. Source parameter summary;raw O/X/dash/blank preserved. Attributes fromPDF107: 1change during run; 2read-only for communication; 3not reset by factory reset; 4read-only; 5LEDkeypadonly; 6modified and 7new inV1.4; 8dependent on13-08; 9enhancedE/Gonly; 10I/Oexpansioncardrequired. Note1V1.41;Note2V1.43;Note3V1.50;Note4V1.51;Note5V1.52;Note6V1.53;Note7editableV1.53above;Note8V1.55;Note9V1.58. No inferred installation approval or configuration recommendation. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 24-17

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c1, r1c2, r1c4, r1c5, r1c9, r2c1, r2c2, r2c4, r2c5, r2c9, r3c1, r3c2, r3c4, r3c5, r3c9. A header spans across these blank regions in the native text; no header value is propagated into them.

Pump-control summary table1 — PDF page 159

Source row Code Parameter Name Setting Range Default Unit Control Mode:V/F Control Mode:SLV Control Mode:PM SLV Attribute
1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x1xxb: Relay 3 Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0xxxb: Relay 4 Disable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1xxxb: Relay 4 Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 24-02 Selection of Relay 5-8 Function xxx0b: Relay 5 Disable 0000b ⟦blank source cell⟧ O O O ⟦blank source cell⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xxx1b: Relay 5 Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx0xb: Relay 6 Disable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ xx1xb: Relay 6 Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x0xxb: Relay 7 Disable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ x1xxb: Relay 7 Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0xxxb: Relay 8 Disable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1xxxb: Relay 8 Enable ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 24-03 Duration of Upper Limit Frequency 1.0 ~ 600.0 300.0 Sec O O O *1
13 24-04 Duration of Lower Limit Frequency 1.0 ~ 600.0 300.0 Sec O O O *1
14 24-05 Switching Time of Magnetic Contactor 0.1 ~ 20.0 1.00 Sec O O O *1
15 24-06 Allowable Bias of Pump Switch 0.0 ~ 20.0 0.0 % O O O *1
16 24-07 Pump Control Source Selection 0: 1 to 8 pump card 0 ⟦blank source cell⟧ O O O ⟦blank source cell⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: Built-in 1 to 3 control mode ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 24-08 Relay Switching Time 0~240 1 Hr/ min O O O Note1
19 24-09 Frequency/ Target Switch 0: Disable 1: Enable 0 ⟦blank source cell⟧ O O O Note3
20 24-10 Stop Mode Selection on Mode 6/7/9 0: Disable 1: Enable 0 ⟦blank source cell⟧ O O O Note3
21 24-11 High Pressure Limit Level 0~10000 500 - O O O Note4
22 24-12 Delay Time of High Pressure Warning 0.0 ~ 600.0 10.0 Sec O O O Note4
23 24-13 Delay Time of High Pressure Error 0.0 ~ 600.0 20.0 Sec O O O Note4
24 24-14 Low Pressure Limit Level 0~10000 0 - O O O Note4
25 24-15 Delay Time of Low Pressure Warning 0.0 ~ 600.0 0.0 Sec O O O Note4
26 24-16 Delay Time of Low Pressure Error 0.0 ~ 600.0 0.0 Sec O O O Note4
27 24-17 PID Control during Increasing/ Decreasing pumps 0: PID Control is disabled during increasing/ decreasing pumps 0 - O O O Note6
28 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1: PID Control is enabled during increasing/ decreasing pumps ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Basic control modes and run sources — page 160

4.4 Description of Parameters

Group 00-Basic Parameters

The inverter offers the following control modes:

00-00=0: V/F Mode

Select the required V/F curve (01-00) based on your motor and application.

Perform a stationary auto-tune (17-00=2). If the motor cable length is longer than 50m (165ft), see

parameter 17-00 for details.

00-00=2: Sensorless Vector Control

Verify the inverter rating matches the motor rating. Perform rotational auto-tune to measure and store

motor parameters for higher performance operation. Perform non-rotational auto-tune if it’s not possible to

rotate the motor during auto-tune. Refer to parameter group 17 for details on auto-tuning.

00-00=5: PM Sensorless Vector Control

Verify the inverter rating matches the motor rating. Set PM motor data in parameters 22-00 to 22-06. Refer

to parameter 22-21 for details on PM Motor tuning. A braking resistor is recommended to be used to

prevent drive from getting regenerative energy. A braking module is required for Inverters ratings 200V

30HP, 400V/40HP or greater.

Note: Parameter 00-00 is excluded from initialization.

Use the FWD/REV key to change motor direction when Run Command Selection (00-02 = 0) is set to

keypad control. In keypad control operation the direction is stored in 00-01. Direction of this function will be

limited to the motor direction lock selection of parameter 11-00.

00-02=0: Keypad Control

Use the keypad to start and stop the inverter and set direction with the forward / reverse key. Refer to

section 4-1 for details on the keypad.

00-02=1: External Terminal Control

External terminals are used to start and stop the inverter and select motor direction.

The inverter can be operated in 2-wire and 3-wire mode.

00-00 choices0V/F,2SLV,5PMSLV;1/3/4 reserved. V/F stationary tuning17-00=2 and >50m(165ft) cable note;SLV rotational or nonrotational tuning per source. PM uses22-00–06 and22-21. Braking resistor recommended;source says module required at200V30HP or400V40HP and above.00-00 excluded from initialization.00-01 applies only keypad run00-02=0;11-00 direction lock. These are supplier operating instructions,not installation approval.

Basic control modes and run sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Basic control modes and run sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 00; explicit source label 00- 00

Basic control modes and run sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 00; explicit source label Range

Basic control modes and run sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 01; explicit source label 00- 01

Basic control modes and run sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 01; explicit source label Range

Basic control modes and run sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 02; explicit source label 00- 02

Basic control modes and run sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 02; explicit source label Range

Basic control modes and run sources table1 — PDF page 160

Source row Parameter or range label Source name or range value
1 00- 00 Control Mode Selection
2 Range 【0】: V/F 【1】: Reserved 【2】: SLV 【3】: Reserved 【4】: Reserved 【5】: PMSLV

Basic control modes and run sources table2 — PDF page 160

Source row Parameter or range label Source name or range value
1 00- 01 Motor’s Rotation Direction
2 Range 【0】: Forward 【1】: Reverse

Basic control modes and run sources table3 — PDF page 160

Source row Parameter or range label Source name or range value
1 00- 02 Main Run Command Source Selection
2 Range 【0】: Keypad control 【1】: External terminal control 【2】: Communication control 【3】: PLC 【4】: RTC

Manual — Alternative run source and two-wire operation — page 161

00-03=0: Keypad Control

Use the keys (Stop/ Run or FWD/ REV) in the keypad via the setting of 00-03=0 to run the inverter (please

refer to section 4.1 for details on the keypad).

00-03=1: External Terminal Control

External terminals are used to start and stop the inverter and select motor direction via the setting of

00-03=1.

Note: Assign the function of one of DI (S1 to S6) to be “Run Command Switch Over” (03-00~03-05=12),

then the run command source can be switched over between the setting of main (00-02) and alternative

(00-03).

■ 2-wire operation

For 2-wire operation, set 03-00 (S1 terminal selection) to 0 and 03-01 (S2 terminal selection) to 1.

Parameter 13-08 to 2, 4 or 6 for 2-wire program initialization, multi-function input terminal S1 is set to

forward , operation/ stop, and S2 is set for reverse, operation / stop.

Figure 4.4.1 Wiring example of 2-wire

DI03-00–05=12 switches main00-02/alternative00-03. Figure4.4.1: S1 forward command, S2 reverse command, return24VG. Two-wire table open/openStop,closed/openForward,open/closedReverse only11-00=0,closed/closedStop withEF9 after500ms.13-08 options2/4/6 are the particular examples given,not an exhaustive initialization list.

Alternative run source and two-wire operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Alternative run source and two-wire operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 03; explicit source label 00- 03

Alternative run source and two-wire operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 03; explicit source label Range

Alternative run source and two-wire operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Open

Alternative run source and two-wire operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Closed

Alternative run source and two-wire operation table1 — PDF page 161

Source row Parameter or range label Source name or range value
1 00- 03 Alternative Run Command Source Selection
2 Range 【0】: Keypad control 【1】: External terminal control 【2】: Communication control 【3】: PLC 【4】: RTC

Alternative run source and two-wire operation table2 — PDF page 161

Source row Terminal S1 Terminal S2 Operation
1 Open Open Stop Inverter
2 Closed Open Run Forward
3 Open Closed Run Reverse (Only at 11-00=0)
4 Closed Closed Stop Inverter, Display EF9 Alarm after 500ms

Manual — Three-wire operation and timing — page 162

■ 3-wire operation

For 3-wire operation set any of parameters 03-02 to 03-05 (terminal S3 ~ S6) to 26 to enable 3-wire

operation in combination with S1 and S2 terminals set to operation command and stop command.

Parameter 13-08 for 3-wire program initialization, multi-function input terminal S1 is set to run operation,

S2 for stop operation and S5 for forward/reverse command. (Additionally must be 00-02=1, 11-00=0)

Note: Terminal S1 must be closed for a minimum of 50ms to activate operation.

Figure 4.4.2 Wiring example of 3-wire

Figure 4.4.3 Timing chart of 3-wire operation

Set one03-02–05(S3–S6)=26;S1run,S2stop;initialization usesS5direction and requires00-02=1,11-00=0. Fig4.4.2 stop normally closed momentary,operation normally open momentary. S1 On:Run;S2 Off:Stop;S5direction;24VG common. Fig4.4.3 run pulse >=50ms;direction Off:forward/On:reverse;stop Off:Stop. Sequence stop→forward→reverse→stop→forward. No inferred electrical values from geometry.

Manual — Two-wire latching and communication/PLC/RTC — page 163

■ 2-wire self holding (latching) operation

Set one of parameters, 03-00 to 03-05 (terminal S1 ~ S6), to 53 in order to enable 2-wire self holding

operation. After this mode is enabled, set terminal S1 (03-00=0) to forward and S2 (03-01=1) to reverse

run command.

S1

S2

S5 Stop (On: Stop)

24VG

Momentary switches

(Push buttons)

Reverse Run Command

(On: Run Reverse)

Forward Run Command

(On: Run Forward)

Note: Terminal S1, S2 and S5 must be closed for a minimum of 50ms to activate operation. The inverter

will display SE2 error when input terminals S1-S6 is set to 53 and 26 simultaneously.

00-02=2: Communication control

The inverter is controlled by the RS-485 port. Refer to parameter group 9 for communication setup.

00-02=3: PLC control

The inverter is controlled by the inverter built-in PLC logic. Refer to section 4.4.

00-02=4: RTC control

The inverter is controlled by RTC timer when run command is set to RTC. Refer to function group 16.

Set one03-00–05=53,S1/03-00=0 forward,S2/03-01=1 reverse,S5stop. Momentary buttons use24VG common. S1 On RunForward,S2 On RunReverse,S5 On Stop. Prose minimum50ms versus timing labels >50ms retained distinctly. Setting53 and26 simultaneously givesSE2. Timing sequence stop→forward→reverse→stop→forward. Communication usesRS485;PLC built-in;RTC group16.

Manual — Language and frequency sources — page 164

It is only for LCD keypad to select. This parameter is not allowed to be modified when 13-08 (restore

factory setting) is active but it is still initialized in inverter software V1.3).

00-04 = 0: English Display

00-04 = 1: Simple Chinese Display

00-04 = 2: Traditional Chinese Display

00-04 = 3: Turkish Display

00-05/00-06= 0: Keypad

Use the keypad to enter the frequency reference or by setting parameter 05-01 (frequency reference 1).

Note that once the frequency command is switched to alternative one, and 00-06=0, the frequency just can

be adjusted via parameter 05-01. Refer to section 4.1.4 for details.

00-05/00-06= 1: External control (Analog Input)

When 04-05=0, give frequency reference command from control circuit terminal AI1 (voltage input). If

auxiliary frequency is used, refer to the descriptions of multi-speed functions in parameter 03-00~05.

When frequency reference command is control by either AI1 or AI2, please regard the following setting:

 00-05/ 00-06 are set individually to be 1 and 7.

 Set AI2 signal type in 04-00 (AI1 is always 0~10V).

 Set 04-05=0 (Auxiliary frequency setting).

 Set multi-function terminal function of 03-00~05 to be 13, then frequency reference command can be

switched to AI1 control or AI2 control.

When 04-05=1, give frequency reference command from control circuit terminal AI1 (voltage input) or AI2

(current input, set by 04-00).

Use AI1 terminal when voltage input signal is the main frequency reference command.

Use AI2 terminal when current input signal (4-20mA) is the main frequency reference command.

Use analog reference from analog input AI1 or AI2 to set the frequency reference (as shown in Figure

4.4.4). Refer to parameter 04-00 to select the signal type.

00-04 LCD languages English,SimpleChinese,TraditionalChinese,Turkish;not reset by13-08 except softwareV1.3 still initialized.00-05/06 options retain reserved4/5. Alternative keypad00-06=0 frequency adjusted only via05-01. AI1 described always0–10V here;04-00 AI2type,04-05=0 auxiliary andDI13 switching. Hardware-specific enhanced analog options elsewhere are not erased.

Language and frequency sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Language and frequency sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 04; explicit source label 00- 04

Language and frequency sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 04; explicit source label Range

Language and frequency sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 05; explicit source label 00- 05

Language and frequency sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 06; explicit source label 00- 06

Language and frequency sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 06; explicit source label Range

Language and frequency sources table1 — PDF page 164

Source row Parameter or range label Source name or range value
1 00- 04 Language Selection (for LCD only)
2 Range 【0】: English 【1】: Simple Chinese 【2】: Traditional Chinese 【3】: Turkish

Language and frequency sources table2 — PDF page 164

Source row Parameter or range label Source name or range value
1 00- 05 Main Frequency Command Source Selection
2 00- 06 Alternative Frequency Source Selection
3 Range 【0】: Keypad 【1】: External control (analog AI1) 【2】: Terminal UP / DOWN 【3】: Communication control 【4】: Reserved 【5】: Reserved 【6】: RTC 【7】: AI2 Auxiliary frequency

Manual — Analog input and frequency sources — page 165

Note: Set parameter 04-05 to 10 to add frequency reference AI2 to AI1.

Figure 4.4.4 Analog input as main frequency reference command (For Enhanced E&G type)

00-05/00-06= 2: Terminal UP / DOWN

The inverter accelerates with the UP command closed and decelerates with the DOWN command closed.

Please refer to parameter 03-00 ~ 03-05 for additional information.

Note: To use this function both the UP and DOWN command have to be selected to any of the input

terminals.

00-05/00-06= 3: Communication Control

The frequency reference command is set via the RS-485 communication port using the MODBUS RTU/

BacNet/ MetaSys protocol.

Refer to parameter group 9 for additional information.

00-05/00-06= 6: RTC

Enables RTC control, reference frequency is controlled by the RTC function, Refer to parameter group 16

for RTC setup.

00-05/00-06=7: AI2 Auxiliary frequency*1

When 04-05 is set to 0 (auxiliary frequency), frequency command is set by multi-function analog input AI2.

Maximum output frequency (01-02, Fmax) =100%; if 04-05 is not set to 0, the frequency is 0. Refer to the

parmeters of 03-00~03-07 for descriptions of multi-speed functions.

Table uses SW2 for AI2 voltage/current:AI1 0–10V,current dash;AI2 0–10V with04-00=0/SW2V or4–20mA with04-00=1/SW2I.04-05=10 addsAI2 reference toAI1. Fig4.4.4 enhancedE&G drawing labels AI1 SW3,AI2 SW4;2kΩ potentiometer between+10V/GND,wiperAI1;AI2 current input. Table/drawing switch names differ. Both UP/DOWN must be assigned. RS485 protocols MODBUS RTU/BacNet/MetaSys. AI2aux needs04-05=0 else reference0;100%=01-02 Fmax.

Analog input and frequency sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Analog input and frequency sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: AI1 – Analog

Input 1

Analog input and frequency sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: AI2 – Analog

Input 2

Shared source cells (coordinates refer to this table):

Analog input and frequency sources table1 — PDF page 165

Source row ⟦blank source cell⟧ Voltage input Current input 04-00 Setting (Default = 1) Dipswitch SW2 (Default ‘V’) Remark Default 04-05=”10”
1 AI1 – Analog Input 1 0 ~ 10V ------ ------ ------ ------
2 AI2 – Analog Input 2 0 ~ 10V ------ 0: AI2 0~10V Set to ‘V’ Set 04-05=”10” (Note)
3 ⟦null: no independent source value⟧ ------- 4 ~ 20mA 1: AI2 4~20mA Set to “I” ⟦null: no independent source value⟧

Manual — Frequency modes/minimum/PID limits — page 166

When set to 0, the reference frequency is set by the main reference frequency selection of parameter

00-05. When set to 1, the reference frequency is sum of the main reference frequency (00-05) and

alternative frequency (00-06).

Note: The inverter will display the SE01 error when 00-07 = 1 and parameter 00-05 and 00-06 are set to

the same selection.

When parameter 00-06 is set to 0 (Keypad) the alternative frequency reference is set by parameter 05-01

(Frequency setting of speed-stage 0).

Display the frequency reference when 00-05 or 00-06 is set to communication control (3).

Note: This parameter is only effective in communication mode.

00-10=0:

When frequency command is lower than 01-08 (Minimum Output Frequency of Motor 1), it shows STP0

warning.

00-10=1:

When frequency command is lower than 01-08 (Minimum Output Frequency of Motor 1), inverter runs as

minimum output frequency of motor 1.

When inverter gets to sleep,

00-11=0: PID is bound to lower limit frequency (00-13).

00-11=1: PID is bound to 0 Hz.

Note: Refer to descriptions of parameters 10-17~10-20 for details when inverter gets to sleep.

00-07=1 sums00-05/06;equal source selections produceSE01.00-06=0 uses05-01 speed-stage0.00-08 read-only communication reference;00-09 memory only communication mode.00-10 selectsSTP0 warning or minimum01-08 operation.00-11 PID sleep lower bound00-13 or0Hz;refer10-17–20.

Frequency modes/minimum/PID limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Frequency modes/minimum/PID limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 07; explicit source label 00- 07

Frequency modes/minimum/PID limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 07; explicit source label Range

Frequency modes/minimum/PID limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 08; explicit source label 00- 08

Frequency modes/minimum/PID limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 08; explicit source label Range

Frequency modes/minimum/PID limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 09; explicit source label 00- 09

Frequency modes/minimum/PID limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 09; explicit source label Range

Frequency modes/minimum/PID limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-10; explicit source label 00-10

Frequency modes/minimum/PID limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-10; explicit source label Range

Frequency modes/minimum/PID limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 11; explicit source label 00- 11

Frequency modes/minimum/PID limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 11; explicit source label Range

Frequency modes/minimum/PID limits table1 — PDF page 166

Source row Parameter or range label Source name or range value
1 00- 07 Main and Alternative Frequency Command Modes
2 Range 【0】: Main reference frequency 【1】: Main frequency + alternative frequency

Frequency modes/minimum/PID limits table2 — PDF page 166

Source row Parameter or range label Source name or range value
1 00- 08 Communication Frequency Command – READ ONLY
2 Range 【0.00~599.00】Hz

Frequency modes/minimum/PID limits table3 — PDF page 166

Source row Parameter or range label Source name or range value
1 00- 09 Communication Frequency Command Memory
2 Range 【0】: Do not store the communication frequency command at power down 【1】: Store communication frequency reference at power down

Frequency modes/minimum/PID limits table4 — PDF page 166

Source row Parameter or range label Source name or range value
1 00-10 Minimum frequency detection
2 Range 【0】:Show warning if lower than minimum frequency 【1】:Run as minimum frequency if lower than minimum frequency

Frequency modes/minimum/PID limits table5 — PDF page 166

Source row Parameter or range label Source name or range value
1 00- 11 Selection of PID Lower Limit Frequency
2 Range 【0】: PID is bound to lower limit frequency when inverter sleeps. 【1】: PID is bound to 0Hz when inverter sleeps.

Manual — Frequency limits and ramps — page 167

Set the minimum frequency reference as a percentage of the maximum output frequency. Maximum

output frequency depends on frequency parameter 01-02.

Notes:

-

When the frequency lower limit is set to a value greater than 0 and the inverter is started the output

frequency will accelerate to the frequency lower limit with a minimum frequency defined by parameter

01-08.

Frequency upper limit has to greater or equal to the frequency lower limit otherwise the inverter will

display a SE01 (Set range error).

Frequency upper and lower limit is active for all frequency reference modes.

Figure 4.4.5 Frequency reference upper and lower limits

Note: The maximum frequency setting in the keypad is according to parameter 01-02 (Maximum Output

Frequency) and 00-12 (Upper Frequency limit). The upper frequency limit is not over than 599Hz and

maximum limit for AI frequency is 100% to parameter 01-02.

Figure4.4.5 output lower plateau00-13→linear rise→upper plateau00-12 against reference;100% related01-02. Upper must >=lower elseSE01;all reference modes. Upper limit <=599Hz;AI maximum100% of01-02. Ramp pairs1:00-14/15,2:16/17,3:21/22,4:23/24;0.1–6000s.00-25 change frequency0–599Hz.

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-12; explicit source label 00-12

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-12; explicit source label Range

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-13; explicit source label 00-13

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-13; explicit source label Range

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-14; explicit source label 00-14

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-14; explicit source label Range

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-15; explicit source label 00-15

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-15; explicit source label Range

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-16; explicit source label 00-16

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-16; explicit source label Range

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-17; explicit source label 00-17

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-17; explicit source label Range

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-21; explicit source label 00-21

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-21; explicit source label Range

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-22; explicit source label 00-22

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-22; explicit source label Range

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-23; explicit source label 00-23

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-23; explicit source label Range

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-24; explicit source label 00-24

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-24; explicit source label Range

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-25; explicit source label 00-25

Frequency limits and ramps. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-25; explicit source label Range

Frequency limits and ramps table1 — PDF page 167

Source row Parameter or range label Source name or range value
1 00-12 Upper Limit Frequency
2 Range 【0.1~109.0】%
3 00-13 Lower Limit Frequency
4 Range 【0.0~109.0】%

Frequency limits and ramps table2 — PDF page 167

Source row Parameter or range label Source name or range value
1 00-14 Acceleration Time 1
2 Range 【0.1~6000.0】 Sec
3 00-15 Deceleration Time 1
4 Range 【0.1~6000.0】 Sec
5 00-16 Acceleration Time 2
6 Range 【0.1~6000.0】 Sec
7 00-17 Deceleration Time 2
8 Range 【0.1~6000.0】 Sec
9 00-21 Acceleration Time 3
10 Range 【0.1~6000.0】 Sec
11 00-22 Deceleration Time 3
12 Range 【0.1~6000.0】 Sec
13 00-23 Acceleration Time 4
14 Range 【0.1~6000.0】 Sec
15 00-24 Deceleration Time 4
16 Range 【0.1~6000.0】 Sec
17 00-25 Switching Frequency of Acceleration and Deceleration
18 Range 【0.00~599.00】Hz

Manual — Ramp size defaults and selection — page 168

time

Output

Frequency

Digital Input

Terminal S5

( 03 -

04= 10 )

Tacc1

Rate

Tacc2

Tdec1

Tdec2

Acceleration time is the time required to accelerate from 0 to 100% of maximum output frequency.

Deceleration time is the time required to decelerate from 100 to 0% of maximum output frequency.

Motor 1: Maximum frequency is set by parameter 01-02 and Motor 2 Maximum frequency is set by

parameter 01-16.

Note: Actual acceleration and deceleration times can be affected by the inverter driven load.

The default values for the acceleration, deceleration times are dependent on the inverter size.

A: Select acceleration and deceleration time via the digital input terminals

The following table shows the acceleration / deceleration selected when the digital input function

Accel/Decel time 1 (#10) and Accel/Decel time 2 1(#30) are used.

Table 4.4.1 Acceleration / deceleration time selection

0: OFF, 1: ON

Figure 4.4.6: Terminal S5 switch between Tacc1/Tacc2 and Tdec1/Tdec2

B. Automatically acceleration / deceleration time switch-over based on output frequency

Set acceleration / deceleration switch over frequency parameter 00-25 to a value greater than 0 to

automatically switch between Tacc1 (00-14) / Tdec1 (00-23) and Tacc4 (00-24) / Tdec4 (00-15).

Tacc1 (00-14) / Tdec1 (00-23) are active when the output frequency < 00-25 and Tacc4 (00-24) / Tdec4

(00-15) are active when the output frequency >= 00-25. Refer to the Figure 4.4.7 for details.

Defaults paired200V/400V:1–15HP/1–20HP=10s;20–30/25–40=15s;40–175/50–800=20s. Acc/dec0↔100%max01-02 motor1/01-16 motor2;actual load can affect. Digital input#30,#10 states00→pair1,01→pair2,10→pair3,11→pair4. Fig4.4.6 S5/03-04=10 low selectsTacc1/Tdec1,highTacc2/Tdec2. ParagraphB printsTdec1(00-23),Tacc4(00-24),Tdec4(00-15),contradicting table andPDF169 figure;all source text retained.

Ramp size defaults and selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Ramp size defaults and selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 1~15HP

Ramp size defaults and selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 20~30HP

Ramp size defaults and selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 40~175HP

Ramp size defaults and selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 0

Ramp size defaults and selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 1

Ramp size defaults and selection table1 — PDF page 168

Source row 200V Class 400V Class Acceleration/Deceleration default value
1 1~15HP 1~20HP 10s
2 20~30HP 25~40HP 15s
3 40~175HP 50~800HP 20s

Ramp size defaults and selection table2 — PDF page 168

Source row Accel/decel time 2 (Set 03-00 ~ 03-05 = 30) Accel/decel time 1 (Set 03-00 to 03-05 = 10) Acceleration time Deceleration time
1 0 0 Taccc1 (00-14) Tdec1 (00-15)
2 0 1 Taccc2 (00-16) Tdec2 (00-17)
3 1 0 Taccc3 (00-21) Tdec3 (00-22)
4 1 1 Taccc4 (00-23) Tdec4 (00-24)

Manual — Ramp switching,jog and emergency stop — page 169

Note: Multi-function input function #10 (Accel/Decel time 1) and #30 (Accel/Decel time 2) have a higher

priority than switch over frequency parameter 00-25.

Figure 4.4.7 Automatic acceleration / deceleration time switch-over based on output

frequency

Jog acceleration time (00-19) is the time required to accelerate from 0 to 100% of maximum output

frequency. Jog deceleration time (00-20) is the time required to decelerate from 100 to 0% of maximum

output frequency. Motor 1: Maximum frequency is set by parameter 01-02 and Motor 2 Maximum

frequency is set by parameter 01-16.

When run command selection is external terminal control (00-02=1) and the inverter uses the jog

frequency (00-18, default 6.0 Hz) as its frequency reference with 03-00~03-07=6 or 7(6: Forward jog run

command 7: Reverse jog run command).The motor will run by the setting.

The emergency stop time is used in combination with multi-function digital input function #14 (Emergency

stop). When emergency stop input is activated the inverter will decelerate to a stop using the Emergency

stop time (00-26) and display the [EM STOP] condition on the keypad.

Note: To cancel the emergency stop condition the run command has to be removed and emergency stop

input deactivated.

Multi-function digital input terminals (03-00 ~ 03-05) are set to 14: When the emergency stop input is

activated the inverter will decelerate to a stop using the time set in parameter 00-26.

Note: After an emergency stop command the run command and emergency stop command have to be

removed before the inverter can be restarted. Please refer to Figure 4.4.8. The emergency stop function

can be used to stop inverter in case of an external event.

Multi-function digital input terminals (03-00 ~ 03-05) set to 15: When the base block input is activated the

inverter output will turn off and the motor will coast to a stop.

DI#10/#30 priority over00-25. Fig4.4.7 lower frequency Tacc1(00-14)/Tdec1(00-15),higher Tacc4(00-23)/Tdec4(00-24). Jog default6Hz,functions6forward/7reverse. EmergencyDI14 decelerates using00-26 and displaysEMSTOP;run andemergency must both be removed before restart. DI15 baseblock turns output off and coasts,distinct from emergency deceleration.

Ramp switching,jog and emergency stop. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Ramp switching,jog and emergency stop. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-18; explicit source label 00-18

Ramp switching,jog and emergency stop. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-18; explicit source label Range

Ramp switching,jog and emergency stop. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-19; explicit source label 00-19

Ramp switching,jog and emergency stop. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-19; explicit source label Range

Ramp switching,jog and emergency stop. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-20; explicit source label 00-20

Ramp switching,jog and emergency stop. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00-20; explicit source label Range

Ramp switching,jog and emergency stop. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 26; explicit source label 00- 26

Ramp switching,jog and emergency stop. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 26; explicit source label Range

Ramp switching,jog and emergency stop table1 — PDF page 169

Source row Parameter or range label Source name or range value
1 00-18 Jog Frequency
2 Range 【0.00~599.00】Hz
3 00-19 Jog Acceleration Time
4 Range 【0.1~0600.0】Sec
5 00-20 Jog Deceleration Time
6 Range 【0.1~0600.0】Sec

Ramp switching,jog and emergency stop table2 — PDF page 169

Source row Parameter or range label Source name or range value
1 00- 26 Emergency Stop Time
2 Range 【0.0~6000.0】 Sec

Manual — Emergency stop,analog characteristic and presets — page 170

time

Emergency stop

command

S 5 ( 03 - 04=14 )

Run

Output

Frequency

ON

OFF

Emergency stop deceleration

100%

-10V

10V

(20 mA)

0V

(4 mA)

Analog input

signal

( % )

(a) Forward Characteristics

(b) Reverse Characteristics

Figure 4.4.8 Emergency stop example

00-28= 0: Positive reference curve, 0 – 10V / 4 – 20mA = 0 – 100% main frequency reference.

00-28= 1: Negative reference curve, 0 – 10V / 4 – 20mA = 100 – 0% main frequency reference.

Note: Selection applies to analog input AI1 and AI2.

Note: AI2 will be useful for analog input frequency command when 04-05=0.

Figure 4.4.9 Positive/negative analog input as main frequency reference command.

Note: If set 00-32 back to 0, 2 wire initialization (60Hz)(230/400V) setting (13-08=11) will be executed.

Note: Before setting up 00-32 Application, it should do initialized setting (parameter 13-08) first.

Warning: When setting 00-32, the I/O port function changed automatically. To avoid accident,be sure to

confirm the I/O port signal of inverter and external terminal control

Fig4.4.8 emergencyS5/03-04=14 graph labels low ON and high OFF;frequency decelerates during high segment,so source polarity is ambiguous against activation prose. Fig4.4.9 positive0–10V/4–20mA→0–100%,inverse→100–0%;AI2 effective when04-05=0.00-32 presets changeI/O automatically;source requires confirming inverter/externalterminal signals and initializing13-08 first. Returning00-32 to0 executes13-08=11 two-wire60Hz230/400V initialization.

Emergency stop,analog characteristic and presets. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Emergency stop,analog characteristic and presets. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 28; explicit source label 00- 28

Emergency stop,analog characteristic and presets. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 28; explicit source label Range

Emergency stop,analog characteristic and presets. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 32; explicit source label 00- 32

Emergency stop,analog characteristic and presets. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 32; explicit source label Range

Emergency stop,analog characteristic and presets table2 — PDF page 170

Source row Parameter or range label Source name or range value
1 00- 28 Selection of Main Frequency Command Characteristic
2 Range 【0】: Positive characteristic (0~10V/4~20mA = 0~100%) 【1】: Negative / inverse characteristic (0~10V/4~20mA = 100~0%)

Emergency stop,analog characteristic and presets table3 — PDF page 170

Source row Parameter or range label Source name or range value
1 00- 32 Application
2 Range 【0】: General 【1】: Water supply pump 【2】: Conveyor 【3】: Exhaust fan 【4】: HVAC 【5】: Compressor 【6】: Reserved 【7】: Reserved

Manual — Water pump/conveyor/exhaust fan presets — page 171

(1) Water supply pump

(2) Conveyor

(3) Exhaust fan

Three independent tables:00-32=1 Water supply pump14rows;=2 Conveyor5rows;=3 Exhaust fan6rows. Preset values are not universal factory defaults. Water ramps2s/15s andPID settings;conveyor3s/3s;exhaust speedsearch07-32=1 versus0 in water/conveyor. All table cells retained.

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-00

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-14

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-15

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 11-00

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 01-00

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 07-00

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 07-32

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 08-00

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-00

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-06

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-07

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-26

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-27

Water supply pump (00-32=1) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 10-03

Conveyor (00-32=2) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Conveyor (00-32=2) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-00

Conveyor (00-32=2) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-14

Conveyor (00-32=2) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-15

Conveyor (00-32=2) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 07-32

Conveyor (00-32=2) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 08-00

Exhaust fan (00-32=3) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Exhaust fan (00-32=3) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-00

Exhaust fan (00-32=3) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 11-00

Exhaust fan (00-32=3) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 01-00

Exhaust fan (00-32=3) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 07-00

Exhaust fan (00-32=3) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 07-32

Exhaust fan (00-32=3) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 08-00

Water supply pump (00-32=1) — PDF page 171

Source row Parameter Name Value
1 00-00 Control mode selection 0 : V/F
2 00-14 Acceleration Time 1 2.0 sec
3 00-15 Deceleration Time 1 15.0 sec
4 11-00 Direction lock selection 1 : Forward direction only
5 01-00 V/F curve selection F
6 07-00 Momentary power loss/ fault restart selection 1 : Enable
7 07-32 Speed Search Mode Selection 0 : Disable
8 08-00 Stall prevention function xx0xb : Stall prevention is enabled in deceleration
9 23-00 Function Selection 1: Pump
10 23-06 Proportion Gain (P) 2.00
11 23-07 Integral Time (I) 3.00 sec
12 23-26 Acceleration Time of Water Pressure Detection 3.0 sec
13 23-27 Deceleration Time of Water Pressure Detection 3.0 sec
14 10-03 PID Control Mode xxx1b: PID Enable

Conveyor (00-32=2) — PDF page 171

Source row Parameter Name Value
1 00-00 Control mode selection 0: V/F
2 00-14 Acceleration time 1 3.0 sec
3 00-15 Deceleration time 1 3.0 sec
4 07-32 Speed Search Mode Selection 0 : Disable
5 08-00 Stall prevention function xx0xb: Stall prevention is enabled in deceleration

Exhaust fan (00-32=3) — PDF page 171

Source row Parameter Name Value
1 00-00 Control mode selection 0 : V/F
2 11-00 Direction lock selection 1 : Forward direction only
3 01-00 V/F curve selection F
4 07-00 Momentary power loss/ fault restart selection 1 : Enable
5 07-32 Speed Search Mode Selection 1 : Enable
6 08-00 Stall prevention function xx0xb : Stall prevention is enabled in deceleration

Manual — HVAC/compressor presets — page 172

(4) HVAC

(5) Compressor

Note: 01-00 (V/F pattern) will hidden automatically.

(6) Reserved

(7) Reserved

00-32=4 HVAC9rows:carrier8kHz,automatic reduction11-03=1.00-32=5 Compressor12rows:externalrun/AI1,ramp5s/5s,01-06halfmaximumfrequency,01-07halfmaximumvoltage,01-00 hidden automatically. Choices6/7 reserved. Preset values are conditional and distinct from main parameter defaults.

HVAC (00-32=4) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

HVAC (00-32=4) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-00

HVAC (00-32=4) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 11-00

HVAC (00-32=4) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 11-01

HVAC (00-32=4) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 07-00

HVAC (00-32=4) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 07-32

HVAC (00-32=4) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 10-03

HVAC (00-32=4) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 11-03

HVAC (00-32=4) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 01-00

HVAC (00-32=4) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-00

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-00

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-02

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-05

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 11-00

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-14

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 00-15

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 01-06

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 01-07

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 07-00

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 07-32

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 08-00

Compressor (00-32=5) application preset. These values apply when this preset is selected; not universal defaults. See PDF170 automatic I/O and initialization warning. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: 23-00

HVAC (00-32=4) — PDF page 172

Source row Parameter Name Value
1 00-00 Control mode selection 0 : V/F
2 11-00 Direction lock selection 1 : Forward direction only
3 11-01 Carrier frequency 8.0kHz
4 07-00 Momentary power loss/ fault restart selection 1 : Enable
5 07-32 Speed Search Mode Selection 0 : Disable
6 10-03 PID Control Mode xxx1b: PID Enable
7 11-03 Automatic carrier frequency reduction 1 : Enable
8 01-00 V/F curve selection F
9 23-00 Function Selection 2: HVAC

Compressor (00-32=5) — PDF page 172

Source row Parameter Name Value
1 00-00 Control mode selection 0: V/F
2 00-02 Main Run Command Source Selection 1: External Terminal (Control Circuit)
3 00-05 Main Frequency Command Source Selection 1: External Terminal (Analog AI1)
4 11-00 Direction lock selection 1: Forward direction only
5 00-14 Acceleration time 1 5.0 sec
6 00-15 Deceleration time 1 5.0 sec
7 01-06 Middle Output Frequency 1 Half of the maximum frequency
8 01-07 Middle Output Voltage 1 Half of the maximum voltage
9 07-00 Momentary power loss/ fault restart selection 1: Enable
10 07-32 Speed Search Mode Selection 0: Disable
11 08-00 Stall prevention function xx0xb: Stall prevention is enabled in deceleration
12 23-00 Function Selection 3: Compressor

Manual — Modified-parameter LCD example — page 173

Note: only for LCD keypad.

This parameter automatically lists all the adjusted parameters. When the default value is adjusted and

00-33=1, it will list all the parameters different from default values in the advanced modes and these

parameters can be edited directly. The adjusted parameters list displays only when 00-33 is set from 0 to 1

or 00-33=1 at start up.

If user wants to restore to the original editing interface, it is only required to set parameter 00-33=0.

This function can display 250 adjusted parameters. If they are more than 250 parameters, it will list the

adjusted parameters before 250.

Example: set 00-03 (Alternative Run Command Source Selection) to be different default value.

00-33 LCD-only lists up to250 changed parameters;enable displays and permitsediting,disable returnsnormal. Six steps:group00→00-03→edit→00-33→enable1→modifiedlist. Step3 screen saysEdit00-00 while titleSub RUN Source and example00-03;retain mismatch. Physical table subdivisions inside LCD screens are not extra numbered steps.

Modified-parameter LCD example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

Modified-parameter LCD example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 33; explicit source label 00- 33

Modified-parameter LCD example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 33; explicit source label Range

Modified-parameter LCD example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 1; LCD internal subdivisions belong to same numbered step

Modified-parameter LCD example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 2; LCD internal subdivisions belong to same numbered step

Modified-parameter LCD example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 3; LCD internal subdivisions belong to same numbered step

Modified-parameter LCD example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 4; LCD internal subdivisions belong to same numbered step

Modified-parameter LCD example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 5; LCD internal subdivisions belong to same numbered step

Modified-parameter LCD example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 6; LCD internal subdivisions belong to same numbered step

Shared source cells (coordinates refer to this table):

Modified-parameter LCD example table1 — PDF page 173

Source row Parameter or range label Source name or range value
1 00- 33 Modified Parameters
2 Range 【0】: Disable 【1】: Enable

Modified-parameter LCD example table2 — PDF page 173

Source row Steps LCD Display Descriptions
1 1 Group 00 Basic Func. 01 V/F Pattern 02 Motor Parameter The starting parameter group (00) in the setting modes of ▲ (Up)/ ▼ (Down) selection groups.
2 2 PARA 00 -01. Motor Direction -02. RUN Source -03. Sub RUN Source Press READ/ ENTER key and ▲ (Up)/ ▼ (Down) to select alternative run command source (00-03).
3 3 Edit 00-00 Sub RUN Source Press READ/ ENTER key and adjust the value. The selected setting value will flash.
4 ⟦null: no independent source value⟧ 1 Terminal (0 ~4) <2> ⟦null: no independent source value⟧
5 4 PARA 00 -33. Modify parameter -41. User P1 -42. User P2 Press DSP/ FUN to the menu of modified parameters (00-33).
6 ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧
7 5 Edit 00-33 Modify parameter Press READ/ ENTER key to adjust the value to 1 (The modified parameter is enabled.) The selected setting value will flash.
8 ⟦null: no independent source value⟧ 1 Enable (0 ~1) <0> ⟦null: no independent source value⟧
9 6 Modify 00 00-03. Sub RUN Source 00-33. Modify parameter Press DSP/ FUN back to the advanced modes.
10 ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧

Manual — User parameter definitions — page 174

 User Parameter Setting (00-41 ~ 00-56) (only for LCD )

‧

User parameter (00-41 ~ 00-56) can select 16 sets of parameters (group 00 ~ 24, but except 00-00/

00-41~00-56/ group 17) and put them into the list to do the fast access setting.

When the access setting of parameter 13-06 is set to 1, user parameter 00-41 ~ 00-56 can be

displayed and changed.

User parameter 00-41 ~ 00-56 can be changed in the advanced modes, exclusive of being in

operation.

Set value in the parameter of 00-41 ~ 00-56 and set 13-06 to 1.

When 13-06=1, only parameter of 00-00 ~ 00-56 can be set or read in the advanced modes. 13-06=1

is enabled in the parameter setting of 00-41~00-56.

When user would like to leave the screen of user parameters, press RESET key and then DSP/FUN

key to select parameter Group 13.

Sixteen user slots00-41–56,User0–15. Source prints00-48 twice forUser7/User8,omits00-49;not silently corrected. Groups00–24 except00-00,00-41–56,group17.13-06=1 permitsuserlevel. Nochange while operating. ExitRESETthenDSP/FUNgroup13. All scope wording retained.

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 41; explicit source label 00- 41

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 42; explicit source label 00- 42

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 43; explicit source label 00- 43

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 44; explicit source label 00- 44

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 45; explicit source label 00- 45

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 46; explicit source label 00- 46

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 47; explicit source label 00- 47

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 48; explicit source label 00- 48

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 50; explicit source label 00- 50

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 51; explicit source label 00- 51

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 52; explicit source label 00- 52

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 53; explicit source label 00- 53

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 54; explicit source label 00- 54

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 55; explicit source label 00- 55

User parameter definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 00- 56; explicit source label 00- 56

User parameter definitions table1 — PDF page 174

Source row Parameter or range label Source name or range value
1 00- 41 User Parameter 0 Function Setting
2 00- 42 User Parameter 1 Function Setting
3 00- 43 User Parameter 2 Function Setting
4 00- 44 User Parameter 3 Function Setting
5 00- 45 User Parameter 4 Function Setting
6 00- 46 User Parameter 5 Function Setting
7 00- 47 User Parameter 6 Function Setting
8 00- 48 User Parameter 7 Function Setting
9 00- 48 User Parameter 8 Function Setting
10 00- 50 User Parameter 9 Function Setting
11 00- 51 User Parameter 10 Function Setting
12 00- 52 User Parameter 11 Function Setting
13 00- 53 User Parameter 12 Function Setting
14 00- 54 User Parameter 13 Function Setting
15 00- 55 User Parameter 14 Function Setting
16 00- 56 User Parameter 15 Function Setting

Manual — User parameter example1 — page 175

Example 1: Set 03-00 (Multi-function terminal Function Setting-S1) to user parameter 0 (00-41)

Six steps bind03-00 S1 function to00-41 UserP0:selectgroup00,slot00-41,read/edit,choose03-00,save,returnmonitor. LCD examples show range00-01–24-07 despite summary24-17. Timeout prose cites16-06 although summary calls16-06 Reserved;retain reference with flag. Monitor values are screen examples,not product operating measurements.

User parameter example1. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

User parameter example1. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 1; LCD internal subdivisions belong to same numbered step

User parameter example1. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 2; LCD internal subdivisions belong to same numbered step

User parameter example1. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 3; LCD internal subdivisions belong to same numbered step

User parameter example1. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 4; LCD internal subdivisions belong to same numbered step

User parameter example1. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 5; LCD internal subdivisions belong to same numbered step

User parameter example1. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 6; LCD internal subdivisions belong to same numbered step

Shared source cells (coordinates refer to this table):

User parameter example1 table1 — PDF page 175

Source row Steps LCD Display Descriptions
1 1 Group 00 Basic Func. 01 V/F Pattern 02 Motor Parameter Select the start parameter group (00) in the advanced modes.
2 2 PARA 00 -41. User P0 -42. User P1 -43. User P2 Press (READ/ ENTER) key and ▲ (Up) / ▼ (Down) to select user parameter 0 (00-41).
3 3 Edit 00-41 User P0=00-41 Press (READ/ ENTER) key to the screen of data setting/ read. * The selected setting value will flash.
4 ⟦null: no independent source value⟧ 00-41 User P0 <00-01 - 24-07> ⟦null: no independent source value⟧
5 4 Edit 00-41 User P0=00-41 Press ◄ (Left) / ► (Right) and ▲ (Up) / ▼ (Down) key to set the value to 03-00 ( Multi-function terminal Function Setting-S1)
6 ⟦null: no independent source value⟧ 03-00 S1 Function Sel <00-01 - 24-07> ⟦null: no independent source value⟧
7 5 Edit 00-41 User P0= 03-00 Press (READ/ ENTER) key to save 03-00 and the digit stops flashing and the screen displays User P0 = 03-00; 03-00 (Multi-function terminal Function Setting-S1) has been defined as 00-41. Few seconds later, the selected digit will flash again.
8 ⟦null: no independent source value⟧ 03-00 S1 Function Sel <00-01 - 24-07> ⟦null: no independent source value⟧
9 6 Monitor Freq Ref Press (DSP/ FUN) key to the display of main screen. * If users do not press BACK key in one minute, the screen will automatically display the monitor mode shown as the left figure. The automatically return time can be set via 16-06.
10 ⟦null: no independent source value⟧ 12-16=000.00Hz --------------------------------------- 12-17=000.00Hz ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ 12-18=0000.0A ⟦null: no independent source value⟧

Manual — User parameter example2 — page 176

.

Example 2: After one or more parameters in 00-41 ~ 00-56 are set, user parameters settings

are as follows.

Steps1–10 configure13-06=1,returnUserFunction andedit00-41. Step1 prosegroup03 versus screen13;step4 prose save03-00 and screenG01-02 despite access13-06. Userlevel requires at leastone assigned userparameter. Hotkeys onlysoftwareV1.4. Step10 illustrated range00–57 remains an example,not replacement for broaderDI table.

User parameter example2. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

User parameter example2. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 1; LCD internal subdivisions belong to same numbered step

User parameter example2. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 2; LCD internal subdivisions belong to same numbered step

User parameter example2. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 3; LCD internal subdivisions belong to same numbered step

User parameter example2. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 4; LCD internal subdivisions belong to same numbered step

User parameter example2. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 5; LCD internal subdivisions belong to same numbered step

User parameter example2. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 6; LCD internal subdivisions belong to same numbered step

User parameter example2. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 7; LCD internal subdivisions belong to same numbered step

User parameter example2. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 8; LCD internal subdivisions belong to same numbered step

User parameter example2. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 9; LCD internal subdivisions belong to same numbered step

User parameter example2. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 10; LCD internal subdivisions belong to same numbered step

Shared source cells (coordinates refer to this table):

User parameter example2 table1 — PDF page 176

Source row Step LCD Display Descriptions
1 1 Group 13 Driver Status 14 PLC Setting 15 PLC Monitor Select the start parameter group (03) in the advanced modes.
2 2 PARA 13 -06. Access Level -07. Password 1 -08. Initialize Press (READ/ ENTER) and ▲ (Up) / ▼ (Down) key to enter the access level of parameter (13-06).
3 3 Edit 13-06 Access Level Press (READ/ ENTER) key to enter the screen of the data setting/ read. * The selected setting value will flash.
4 ⟦null: no independent source value⟧ --------------------------------------- 1 User Level (0~2) ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ < 2 > ⟦null: no independent source value⟧
6 4 ─ADV─ G01-02 Access Level Press ▲ (Up) / ▼ (Down) key to change setting value to 1 (13-06=1, user level) and Press (READ/ ENTER) key to save the setting value (03-00). Then, the digit stops flashing and the screen displays the setting value. Few seconds later, the selected digit will flash again. User level (13-06=1) can be set by one or more parameters in the user parameters of 00-41 ~ 00-56. If users do not set user parameters, 13-06 will not be set in the user level (setting value=1).
7 ⟦null: no independent source value⟧ 1 User Level (0-2) < 2 > ⟦null: no independent source value⟧
8 5 PARA 13 -06. Access Level Press (DSP/FUN) key to the display of subdirectory.
9 6 Group 00.User Function Press (DSP/FUN) key to the display of group directory. It is required to press ▲ (Up) key to select Group 00 User Function.
10 7 Monitor Freq Ref 12-16=000.00Hz --------------------------------------- 12-17=000.00Hz 12-18=0000.0A Press (DSP/ FUN) key to enter the main screen. If user would like to leave the screen of user parameters, press RESET key and then DSP/FUN key to select parameter Group 13. Hotkeys are only enabled in inverter software V1.4.
11 8 Group 00. User Function00 User 13.Driver Status 13-06 can be selected to be adjusted so leave parameters or enter parameter group 00 to edit user parameters is allowable.
12 9 PARA 00 -41. S1 Function Sel Press (READ/ ENTER) key and ▲ (Up) / ▼ (Down) key to select user parameter 0 (00-41) display.
13 10 Edit 00-41 S1 Function Sel Press (READ/ ENTER) key to enter the screen of data setting/ read. *The selected setting value will flash. In this example, 03-00 (Multi-function terminal Function Setting-S1) has been defined as user parameters (00-41). The right bottom location displays the original parameter group.
14 ⟦null: no independent source value⟧ 00 2-Wire (FWD-RUN) (00~57) < 00 > < 03-00 > ⟦null: no independent source value⟧

Manual — User parameter continuation and menu flow — page 177

01 V/F Pattern

00 Basic Func.

Group

[ Main Screen ]

[ Main Menu]

[ Subdirectroy]

[ READ/ ENTER ]

ENTER

Monitor

Freq Ref

12 – 16 = 000 . 00Hz


12-17 = 000.00Hz

12-18 = 0000.0A

DSP

FUN

02 Motor Parameter

READ

PARA 00

-41 User P0

-42 User P1

-43 User P2

-54 User P13

-55 User P14

-56 User P15

Edit 00-41

User P0


01-00 V/F Pattern. Sel

(01-00–24-06)

-00 Control Method

-01 Motor Direction

-02 RUN Source

User Parameter Run Mode Structures

A.

Define Parameter Group 0~24 as user parameters except parameter 00-00 and 00-41~00-56.

Note: User level (13-06=1) can be set by one or more parameters in the user parameters of 00-41 ~

00-56.

Steps11/12 continuePDF176. Step11 prose sayschange2 whileLCD06FJOG;save to00-41 and03-00 simultaneously. Timeout again16-06. Navigation diagram mainmonitor↔group viaDSP/FUN;READ/ENTER tosubdirectory;up/down cyclesnormalparameters anduser00-41..56;READ/ENTER editUserP0,shown01-00 V/F Pattern withrange01-00–24-06;DSP/FUN returns. Thispage omitsgroup17 exclusion statedPDF174;do not inferpermissionoverride. Examples are not authoritative new parameter ranges.

User parameter continuation and menu flow. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

User parameter continuation and menu flow. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 11; LCD internal subdivisions belong to same numbered step

User parameter continuation and menu flow. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Illustrated example step 12; LCD internal subdivisions belong to same numbered step

Shared source cells (coordinates refer to this table):

User parameter continuation and menu flow table1 — PDF page 177

Source row Step LCD Display Descriptions
1 11 Edit 00-41 S1 Function Sel Press ▲ (Up) / ▼ (Down) key to change the setting value to 2. Use (READ/ ENTER) key to save the setting value. When the selected setting value does not flash again, the setting value will be saved to 00-41 and 03-00 simultaneously.
2 ⟦null: no independent source value⟧ 06 FJOG (00~57) < 00 > < 03-00 > ⟦null: no independent source value⟧
3 12 Monitor Freq Ref 12-16=000.00Hz --------------------------------------- 12-17=000.00Hz 12-18=0000.0A Press (DSP/FUN) key to the display of main screen. * If users do not press (DSP/ FUN) key in one minute, the screen will automatically display the monitor mode shown as the left figure. The automatically return time can be set via 16-06.

Manual — User parameter run-mode menu diagram — page 178

Screen examples only; shown numerical display values are not recommended settings or independently established defaults. Branch geometry and numbered continuation arrows1/2 retained in original.

Read adjacent physical page 177 user-parameter instructions. This page prints S1 Function Sel at 00-41; do not reconcile it by substituting neighbouring-page labels.

Menu diagram text; main-screen values are examples only.

Group and suffix combined only as explicit screen associations; example menu content, not a complete parameter list.

The angle-bracket value is retained literally without inferring its meaning. Navigation arrows retained in source.

Main screen and main menu — PDF page 178

Source row Source label/context Source value
1 Headings Main Screen; Main Menu; Subdirectory; READ/ENTER
2 Main screen title Monitor / Freq Ref
3 Monitor12-16 display 000.00Hz
4 Monitor12-17 display 000.00Hz
5 Monitor12-18 display 0000.0A
6 Group13 Driver Status
7 Group14 PLC Setting
8 Group15 PLC Monitor
9 Group00 User Function

Displayed parameter labels — PDF page 178

Source row Parameter group Displayed suffix Displayed label
1 13 -00 KVA Sel
2 13 -01 S/W Version 1
3 13 -02 Elapsed Time1
4 13 -06 Access Level
5 13 -07 Password 1
6 13 -08 Initialize
7 00 -41 S1 Function Sel

Access-level edit example and key labels — PDF page 178

Source row Source label/context Source value
1 Edit parameter 13-06
2 Edit label Access Level
3 Displayed selection 1 User Level
4 Displayed range (0~2)
5 Angle-bracket value <2>
6 Keys shown DSP/FUN; READ/ENTER; ▲; ▼; </RESET + DSP/FUN

Manual — V/F curve selection — page 179

Group 01-V/F Control Parameters

*When restore factory setting (13-08), this parameter will not be changed.

The V/F curve selection is enabled for V/F mode. Make sure to set the inverter input voltage parameter

01-14.

There are three ways to set V/F curve:

(1) 01-00 = 0 to E: choose any of the 15 predefined curves (0 to E).

(2) 01-00 = 0F, use 01-02~01-09 and 01-12 ~ 01-13, with voltage limit.

(3) 01-00 = FF: use 01-02~01-09 and 01-12 ~ 01-13, without voltage limit.

The default parameters (01-02 ~ 01-09 and 01-12 ~ 01-13) are the same when 01-00 is set to F (default)

and 01-00 is set to 1.

Parameters 01-02 ~ 01-13 are automatically set when any of the predefined V/F curves are selected.

This parameter will be affected to reset by the initialization parameter (13-08).

Consider the following items as the conditions for selecting a V/F pattern.

(1) The voltage and frequency characteristic of motor.

(2) The maximum speed of motor.

01-00 range0–FF. Topnote says13-08 factoryreset doesnotchange it;body says affected by13-08 reset. Both retained unresolved. V/F only,set01-14 inputvoltage.0–E fifteen predefinedcurves;0F customwithvoltagelimit;FF without;uses01-02..09/01-12..13. Fdefault samevalues as1. Predefinedcurve sets01-02..13 automatically per source.

V/F curve selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected.

V/F curve selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 01- 00; explicit source label 01- 00

V/F curve selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. See page-specific visual associations and source flags; no supplier contradiction silently corrected. Row group: Parameter 01- 00; explicit source label Range

V/F curve selection table1 — PDF page 179

Source row Parameter or range label Source name or range value
1 01- 00 V/F Curve Selection
2 Range 【0~FF】

Manual — 1–30HP V/F curves — page 180

Table 4.4.2 1 - 30HP V/F curve selection

*1. Values shown are for 200V class inverters; double values for 400V class inverters.

‡: Select high starting torque only for the following conditions.

(1) The power cable length is > 50m (492ft).

(2) Voltage drop at startup is high.

(3) An AC reactor is used on the input side or output side of the inverter.

(4) Motor power is lower than the inverter rated power.

Table4.4.2 applies1–30HP. Graph voltages are for200V class;source saysdouble for400V,no calculated values substituted.0/F50Hz:7.5V at1.3Hz,14V at2.5Hz,200V at50Hz.1/F60Hz:7.5V at1.5Hz,14V at3Hz,200V at60Hz;curve2 reaches200V at50Hz.3 extends to72Hz after200V at60Hz. Variable4/5 at50Hz:1.3Hz points6.6/7.5V,25Hz points38.5/55V,respectively;both200V at50Hz.6/7 analogous1.5Hz and30Hz,200V at60Hz;4 default50Hz,6 default60Hz.8/9 high-start50Hz low/high torque respectively:1.3Hz7.6/7.7V,2.5Hz14.6/15.2V,50Hz200V. A/B analogous60Hz with1.5Hz/3Hz. C/D/E reach200V at60Hz and extend90/120/180Hz respectively,lower points7.5V at1.5Hz/14V at3Hz. Separate ratedhorsepower180Hz row saysF whilegraphlabel(E) and220V;retain contradiction. High-start conditions include source50m(492ft) cable claim,high startup voltage drop,ACreactor or motor smaller thaninverter.

1–30HP V/F curves. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table4.4.2 applies1–30HP. Graph voltages are for200V class;source saysdouble for400V,no calculated values substituted.0/F50Hz:7.5V at1.3Hz,14V at2.5Hz,200V at50Hz.1/F60Hz:7.5V at1.5Hz,14V at3Hz,200V at60Hz;curve2 reaches200V at50Hz.3 extends to72Hz after200V at60Hz. Variable4/5 at50Hz:1.3Hz points6.6/7.5V,25Hz points38.5/55V,respectively;both200V at50Hz.6/7 analogous1.5Hz and30Hz,200V at60Hz;4 default50Hz,6 default60Hz.8/9 high-start50Hz low/high torque respectively:1.3Hz7.6/7.7V,2.5Hz14.6/15.2V,50Hz200V. A/B analogous60Hz with1.5Hz/3Hz. C/D/E reach200V at60Hz and extend90/120/180Hz respectively,lower points7.5V at1.5Hz/14V at3Hz. Separate ratedhorsepower180Hz row saysF whilegraphlabel(E) and220V;retain contradiction. High-start conditions include source50m(492ft) cable claim,high startup voltage drop,ACreactor or motor smaller thaninverter. Page-specific source conflicts and diagram associations retained;not engineering approval.

1–30HP V/F curves. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table4.4.2 applies1–30HP. Graph voltages are for200V class;source saysdouble for400V,no calculated values substituted.0/F50Hz:7.5V at1.3Hz,14V at2.5Hz,200V at50Hz.1/F60Hz:7.5V at1.5Hz,14V at3Hz,200V at60Hz;curve2 reaches200V at50Hz.3 extends to72Hz after200V at60Hz. Variable4/5 at50Hz:1.3Hz points6.6/7.5V,25Hz points38.5/55V,respectively;both200V at50Hz.6/7 analogous1.5Hz and30Hz,200V at60Hz;4 default50Hz,6 default60Hz.8/9 high-start50Hz low/high torque respectively:1.3Hz7.6/7.7V,2.5Hz14.6/15.2V,50Hz200V. A/B analogous60Hz with1.5Hz/3Hz. C/D/E reach200V at60Hz and extend90/120/180Hz respectively,lower points7.5V at1.5Hz/14V at3Hz. Separate ratedhorsepower180Hz row saysF whilegraphlabel(E) and220V;retain contradiction. High-start conditions include source50m(492ft) cable claim,high startup voltage drop,ACreactor or motor smaller thaninverter. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: General purpose

1–30HP V/F curves. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table4.4.2 applies1–30HP. Graph voltages are for200V class;source saysdouble for400V,no calculated values substituted.0/F50Hz:7.5V at1.3Hz,14V at2.5Hz,200V at50Hz.1/F60Hz:7.5V at1.5Hz,14V at3Hz,200V at60Hz;curve2 reaches200V at50Hz.3 extends to72Hz after200V at60Hz. Variable4/5 at50Hz:1.3Hz points6.6/7.5V,25Hz points38.5/55V,respectively;both200V at50Hz.6/7 analogous1.5Hz and30Hz,200V at60Hz;4 default50Hz,6 default60Hz.8/9 high-start50Hz low/high torque respectively:1.3Hz7.6/7.7V,2.5Hz14.6/15.2V,50Hz200V. A/B analogous60Hz with1.5Hz/3Hz. C/D/E reach200V at60Hz and extend90/120/180Hz respectively,lower points7.5V at1.5Hz/14V at3Hz. Separate ratedhorsepower180Hz row saysF whilegraphlabel(E) and220V;retain contradiction. High-start conditions include source50m(492ft) cable claim,high startup voltage drop,ACreactor or motor smaller thaninverter. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Variable Torque Characteristic

Shared source cells (coordinates refer to this table):

1–30HP V/F curves. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table4.4.2 applies1–30HP. Graph voltages are for200V class;source saysdouble for400V,no calculated values substituted.0/F50Hz:7.5V at1.3Hz,14V at2.5Hz,200V at50Hz.1/F60Hz:7.5V at1.5Hz,14V at3Hz,200V at60Hz;curve2 reaches200V at50Hz.3 extends to72Hz after200V at60Hz. Variable4/5 at50Hz:1.3Hz points6.6/7.5V,25Hz points38.5/55V,respectively;both200V at50Hz.6/7 analogous1.5Hz and30Hz,200V at60Hz;4 default50Hz,6 default60Hz.8/9 high-start50Hz low/high torque respectively:1.3Hz7.6/7.7V,2.5Hz14.6/15.2V,50Hz200V. A/B analogous60Hz with1.5Hz/3Hz. C/D/E reach200V at60Hz and extend90/120/180Hz respectively,lower points7.5V at1.5Hz/14V at3Hz. Separate ratedhorsepower180Hz row saysF whilegraphlabel(E) and220V;retain contradiction. High-start conditions include source50m(492ft) cable claim,high startup voltage drop,ACreactor or motor smaller thaninverter. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Rated

Horsepower

Torque

(Reducer)

1–30HP V/F curves table1 — PDF page 180

Source row Left type Left frequency specification Left saturation/torque specification Left01-00 Left V/F curve Right type Right frequency specification Right starting torque specification Right01-00 Right V/F curve
1 General purpose 50Hz ⟦null: no independent source value⟧ 0 (V) 200 (0) 14 7.5 0 1.32.5 50 (Hz) High Staring Torque‡ 50Hz Low Starting Torque 8 (V) 200 (9) 15.2 (8) 14.6 7.7 7.6 0 1.3 2.5 50(Hz)
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ F ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ High Starting Torque 9 ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ 60Hz 60Hz Saturation 1 (V) 200 (2) (1),(F) 14 7.5 0 1.5 3 50 60(Hz ⟦null: no independent source value⟧ 60Hz Low Starting Torque A (V) 200 (B) 15.2 (A) 14.6 7.7 7.6 0 1.5 3 60(Hz)
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ F (Def. Value) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 50Hz Saturation 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ High Starting Torque B ⟦null: no independent source value⟧
6 Variable Torque Characteristic 72Hz ⟦null: no independent source value⟧ 3 (V) 200 (3) 14 7.5 01.5 3 6072(Hz) Constant-power torque(Reducer) 90Hz ⟦null: no independent source value⟧ C (V) 200 (C) 14 7.5 0 1.5 3 60 90 (Hz)
7 ⟦null: no independent source value⟧ 50Hz Variable Torque 1 4 (Def. Value for 50Hz) (V) 200 (5) 55 38.5 (4) 7.5 6.6 01.3 25 50 (Hz) ⟦null: no independent source value⟧ 120Hz ⟦null: no independent source value⟧ D (V) 200 (D) 14 7.5 01.53 60120(Hz)
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Variable Torque 2 5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ 60Hz Variable Torque 3 6 (Def. Value for 60Hz) (V) 200 (7) 55 38.5 (6) 7.5 6.6 (Hz) 01.5 30 60 ⟦null: no independent source value⟧ 180Hz ⟦null: no independent source value⟧ E (V) 200 (E) 14 7.5 01.5 3 60180(Hz)
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Variable Torque 4 7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

1–30HP V/F curves table2 — PDF page 180

Source row Type Specification 01-00 V/F curve*1
1 Rated Horsepower Torque (Reducer) 180Hz F (V) 220 (E) 14 7.5 01.53 60180(Hz)

Manual — 40HP and above V/F curves — page 181

Table 4.4.3 40HP and above V/F curve selection

*1. Values shown are for 200V class inverters; double values for 400V class inverters.

‡: Select high starting torque only for the following conditions.

(1) The power cable length is > 50m (492ft).

(2) Voltage drop at startup is high.

(3) An AC reactor is used on the input side or output side of the inverter.

(4) Motor power lower than the inverter rated power.

Table4.4.3 applies40HPandabove;200V shown,source saysdouble for400V. General0/F50Hz points8.5V at1.3Hz,15V at2.5Hz,200V at50Hz.1/F60Hz lower8.5V at1.5Hz,15V at3Hz,200V60Hz;2 saturates50Hz.3 extends72Hz after200V60Hz.4/5variable50Hz both8.5V at1.3Hz;25Hz40/57.5V respectively;200V50Hz.6/7 samevalues at1.5/30/60Hz;4default50Hz,6default60Hz.8/9 high-start50Hz low/high:8.5/9V at1.3Hz,15.3/16V at2.5Hz,200V50Hz. A/B analogous60Hz1.5/3Hz. C/D/E lower8.5V at1.5Hz/15V at3Hz,200V60Hz andextend90/120/180Hz. Source again50m(492ft);no corrected conversion inserted.

40HP and above V/F curves. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table4.4.3 applies40HPandabove;200V shown,source saysdouble for400V. General0/F50Hz points8.5V at1.3Hz,15V at2.5Hz,200V at50Hz.1/F60Hz lower8.5V at1.5Hz,15V at3Hz,200V60Hz;2 saturates50Hz.3 extends72Hz after200V60Hz.4/5variable50Hz both8.5V at1.3Hz;25Hz40/57.5V respectively;200V50Hz.6/7 samevalues at1.5/30/60Hz;4default50Hz,6default60Hz.8/9 high-start50Hz low/high:8.5/9V at1.3Hz,15.3/16V at2.5Hz,200V50Hz. A/B analogous60Hz1.5/3Hz. C/D/E lower8.5V at1.5Hz/15V at3Hz,200V60Hz andextend90/120/180Hz. Source again50m(492ft);no corrected conversion inserted. Page-specific source conflicts and diagram associations retained;not engineering approval.

40HP and above V/F curves. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table4.4.3 applies40HPandabove;200V shown,source saysdouble for400V. General0/F50Hz points8.5V at1.3Hz,15V at2.5Hz,200V at50Hz.1/F60Hz lower8.5V at1.5Hz,15V at3Hz,200V60Hz;2 saturates50Hz.3 extends72Hz after200V60Hz.4/5variable50Hz both8.5V at1.3Hz;25Hz40/57.5V respectively;200V50Hz.6/7 samevalues at1.5/30/60Hz;4default50Hz,6default60Hz.8/9 high-start50Hz low/high:8.5/9V at1.3Hz,15.3/16V at2.5Hz,200V50Hz. A/B analogous60Hz1.5/3Hz. C/D/E lower8.5V at1.5Hz/15V at3Hz,200V60Hz andextend90/120/180Hz. Source again50m(492ft);no corrected conversion inserted. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: General purpose

40HP and above V/F curves. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table4.4.3 applies40HPandabove;200V shown,source saysdouble for400V. General0/F50Hz points8.5V at1.3Hz,15V at2.5Hz,200V at50Hz.1/F60Hz lower8.5V at1.5Hz,15V at3Hz,200V60Hz;2 saturates50Hz.3 extends72Hz after200V60Hz.4/5variable50Hz both8.5V at1.3Hz;25Hz40/57.5V respectively;200V50Hz.6/7 samevalues at1.5/30/60Hz;4default50Hz,6default60Hz.8/9 high-start50Hz low/high:8.5/9V at1.3Hz,15.3/16V at2.5Hz,200V50Hz. A/B analogous60Hz1.5/3Hz. C/D/E lower8.5V at1.5Hz/15V at3Hz,200V60Hz andextend90/120/180Hz. Source again50m(492ft);no corrected conversion inserted. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Variable Torque Characteristic

Shared source cells (coordinates refer to this table):

40HP and above V/F curves table1 — PDF page 181

Source row Left type Left frequency specification Left saturation/torque specification Left01-00 Left V/F curve Right type Right frequency specification Right starting torque specification Right01-00 Right V/F curve
1 General purpose 50Hz ⟦null: no independent source value⟧ 0 (V) 200 (0) 15 8.5 0 1.32.5 50 (Hz) High Staring Torque‡ 50Hz Low Starting Torque 8 (V) 200 (9) 16.0 (8) 15.3 9.0 8.5 0 1.3 2.5 50(Hz
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ F ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ High Starting Torque 9 ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ 60Hz 60Hz Saturation 1 (V) 200 (2) 15 (1),(F) 8.5 0 5060(Hz) 1.53 ⟦null: no independent source value⟧ 60Hz Low Starting Torque A (V) 200 (B) 16.0 (A) 15.3 9.0 8.5 0 1.5 3 60(Hz
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ F (Def. Value) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 50Hz Saturation 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ High Starting Torque B ⟦null: no independent source value⟧
6 Variable Torque Characteristic 72Hz ⟦null: no independent source value⟧ 3 (V) 200 (3) 15 8.5 01.5 3 6072(Hz) Constant-power torque(Reducer) 90Hz ⟦null: no independent source value⟧ C (V) 200 (C) 15 8.5 0 1.5 3 6090(Hz)
7 ⟦null: no independent source value⟧ 50Hz Variable Torque 1 4 (Def. Value for 50Hz ) (V) 200 57.5 (5) 40 (4) 8.5 (Hz) 01.3 25 50 ⟦null: no independent source value⟧ 120Hz ⟦null: no independent source value⟧ D (V) 200 (D) 15 8.5 01.53 60120(Hz)
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Variable Torque 2 5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ 60Hz Variable Torque 3 6 (Def. Value for 60Hz ) (V) 200 57.5 (7) 40 (6) 8.5 (Hz) 01.5 30 60 ⟦null: no independent source value⟧ 180Hz ⟦null: no independent source value⟧ E (V) 200 (E) 15 8.5 01.53 60180(Hz)
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Variable Torque 4 7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Custom V/F parameter ranges — page 182

V/F curve setting (01-02 ~ 01-09 and 01-12 ~ 01-13)

Select any of the predefined V/F curves setting ‘0’ to ‘E’ that best matches your application and the load

characteristic of your motor, choose a custom curve setting ‘F’ or ‘FF’ to set a custom curve.

Important:

Improper V/F curve selection can result in low motor torque or increased current due to excitation.

For low torque or high speed applications, the motor may overheat. Make sure to provide adequate cooling

when operating the motor under these conditions for a longer period of time.

If the automatic torque boost function is enabled (parameter 01-10), the applied motor voltage will

automatically change to provide adequate motor torque during start or operating at low frequency.

Custom V/F Curve Setting:

A custom curve selection allows users to set parameters 01-02 ~ 01-13 whereas a predefined curve

selection does not.

01-02/12 range4.8–599Hz;01-03 minimum200Vclass0.1V versus400Vclass0.2V retained. Othermid/min voltagesstart0. Source cautions lowtorque/highspeed overheating andadequatecooling;incorrectcurves canincreasecurrent. CustomF/FFpermits01-02..13;sourceonly,not configuration approval.

Custom V/F parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Custom V/F parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01- 02

Custom V/F parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01- 03

Custom V/F parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01- 04

Custom V/F parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01- 05

Custom V/F parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01- 06

Custom V/F parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01- 07

Custom V/F parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01- 08

Custom V/F parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01- 09

Custom V/F parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01- 12

Custom V/F parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01- 13

Custom V/F parameter ranges table1 — PDF page 182

Source row Parameter or range label Source name or range value
1 01- 02 Maximum Output Frequency
2 Range 【4.8~599.0】Hz
3 01- 03 Maximum Output Voltage
4 Range 200V:【0.1~255.0】V 400V:【0.2~510.0】V
5 01- 04 Middle output frequency 2
6 Range 【0.0~599.0】Hz
7 01- 05 Middle Output Voltage 2
8 Range 200V:【0.0~255.0】V 400V:【0.0~510.0】V
9 01- 06 Middle Output Frequency 1
10 Range 【0.0~599.0】Hz
11 01- 07 Middle Output Voltage 1
12 Range 200V:【0.0~255.0】V 400V:【0.0~510.0】V
13 01- 08 Minimum Output Frequency
14 Range 【0.0~599.0】Hz
15 01- 09 Minimum Output Voltage
16 Range 200V:【0.0~255.0】V 400V:【0.0~510.0】V
17 01- 12 Base Frequency
18 Range 【4.8~599.0】Hz
19 01- 13 Base Output Voltage
20 Range 200V:【0.0~255.0】V 400V:【0.0~510.0】V

Manual — Custom V/F diagram and SLV tuning — page 183

Figure 4.4.10 Custom V/F curve

When setting the frequency related parameters for a custom V/F curve values make sure that:

Fmax ≧ Fbase > Fmid2 > Fmid1 >Fmin

(01-02) (01-12) (01-04) (01-06) (01-08)

The ‘SE03’ V/F curve tuning error is displayed when the frequency values are set incorrectly.

When 01-04 and 01-05 (or 01-18 and 01-09) are set to 0, the inverter ignores the set values of Fmid2 and

Vmid2.

When the control mode is changed parameter 00-00, 01-08 (Fmin) and 01-09 (Vmin) will automatically be

changed to the default setting of the selected control mode.

SLV (Sensorless vector control)

Enter the motor data in parameter group 17 for SV and SLV control mode (00-00) and perform auto-tuning.

In the SLV mode the V/F curve normally does not have to be re-adjusted after a successful auto-tune.

The maximum output frequency setting 01-02 (Fmax), base frequency 01-12 (Fbase) or minimum output

frequency 01-08 (Fmin) can be adjusted but the voltage is automatically adjusted by the internal current

controller.

Set the base frequency (01-12, Fbase) to the motor rated frequency on the motor nameplate.

Perform the auto-tuning procedure after adjusting parameters 02-19 or 17-04 to reduce the voltage at

no-load operation.

Motor jitter can be reduced by lowering the no-load voltage. Please note that lowering the no-load voltage

increases the current at no-load.

Output Voltage

(V)

(

Fmin

( 01- 08)

Fmid

( 01- 06)

(01- 04)

Fbase

(01- 12)

Fmax

(01- 02)

Output

Frequency

(Hz)

Figure4.4.10:minimum(Fmin01-08,Vmin01-09),mid1(Fmid1 01-06,Vmid1 01-07),mid2(Fmid2 01-04,Vmid2 01-05),base(Fbase01-12,Vbase01-13),maximum(Fmax01-02,Vmax01-03). Printedinequality Fmax>=Fbase>Fmid2>Fmid1>Fmin;SE03 ifincorrect. Prosezero condition says01-04/01-05 or01-18/01-09;01-18 keptliteral.00-00change resets01-08/09. SLV prose mentionsSV too and17-04 forvoltage thoughsummary17-04frequency;do not inferextra mode orcorrectcode.

Manual — Torque compensation gain and mode — page 184

In V/F mode the inverter automatically adjusts the output voltage to adjust the output torque during start or

during load changes based on the calculated loss of motor voltage.

The rate of adjustment can be changed with the torque compensation gain parameter.

Refer to the torque compensation gain adjustment shown in Figure 4.4.11.

Figure 4.4.11 Torque compensation gain to increase/decrease output torque

Increase value when:

The wiring between the inverter and the motor is too long

The motor size is smaller than the inverter size

Note: Gradually increase the torque compensation value and make sure the output current does not

exceed inverter rated current.

Reduce value when:

When experiencing motor vibration

Important:

Confirm that the output current at low speed does not exceed the rated output current of the inverter.

01-11=0: General torque compensation mode.

01-11=1: High-speed torque compensation mode (120~160Hz).

Compensation amount decreases as the frequency increases. Compensation in 0~120Hz is the same as

that in torque compensation mode 0.

Fig4.4.11 raising curve atgivenbasefrequency increasesoutputvoltage/torque;lowering decreases;100%top. Gain0–2. Longwire/smallmotor increase gradually whilecurrent<=inverterrating;vibration reduce.01-11=0general;1highspeed120–160Hz,compensation decreaseswithfrequency and0–120Hzsameasmode0. Supplierconditions retained.

Torque compensation gain and mode. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Torque compensation gain and mode. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01-10

Torque compensation gain and mode. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01-11

Torque compensation gain and mode table1 — PDF page 184

Source row Parameter or range label Source name or range value
1 01-10 Torque Compensation Gain
2 Range 【0.0~2.0】

Torque compensation gain and mode table2 — PDF page 184

Source row Parameter or range label Source name or range value
1 01-11 Selection of Torque Compensation Mode
2 Range 0: Torque Compensation Mode 0 1: Torque Compensation Mode 1

Manual — Input voltage and torque compensation time — page 185

The minimum input voltage of inverter is 0.1V.

Set the inverter input voltage (E.g. 200V / 208V / 230V / 240V or 380V / 415V / 440V / 460V / 480V).

This parameter is used as a reference for predefined V/F curve calculation (01-00 = 0 to E), over-voltage

protection level, stall prevention, etc…

Note: It will depend on restore factory setting (13-08) to set the value of voltage

Set the torque compensation delay time in milliseconds.

Only adjust in the following situations:

Increase value when:

When experiencing motor vibration

Decrease value when:

When motor torque response is too slow

01-14 range200V155–255V,400V310–510V;prose saysminimum inputvoltage0.1V;retain literal claimwithflag. Itisreferenceforcurve/protection anddepends13-08.01-15 range0–10000ms;increaseforvibration,decreasefortoo-slow torque response.

Input voltage and torque compensation time. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Input voltage and torque compensation time. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01-14

Input voltage and torque compensation time. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 01-15

Input voltage and torque compensation time table1 — PDF page 185

Source row Parameter or range label Source name or range value
1 01-14 Input Voltage Setting
2 Range 200V:【155.0~255.0】V 400V:【310.0~510.0】V

Input voltage and torque compensation time table2 — PDF page 185

Source row Parameter or range label Source name or range value
1 01-15 Torque Compensation Time
2 Range 【0~10000】ms

Manual — IM motor parameter ranges — page 186

Group 02-IM Motor Parameter

In most case no adjustment is required after performing an auto-tune except when using the inverter in

special applications (e.g. machine tool, positioning, etc…).

Please refer to parameter group 22 for permanent magnet motor parameters.

(1) Number of motor poles (02-07)

Set the number of motor pole according to the motor nameplate.

(2) Motor rated power (02-05)

Set the motor power according to the motor nameplate.

(3) Motor rated current (02-01)

Set the motor rated current according to the motor nameplate.

Group02 IMparameters;PMrefergroup22.02-01 rating25–200%ofinverterratedcurrent;02-07 evenpoles2–16;02-03 rpm0–60000. <1>on02-09/10/11/12/33/34 meansrenewedafterautotune perPDF188. Nameplateconditions retained. No invented02-02 orotherunprintedrows.

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02- 00

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02- 01

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02-03

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02- 04

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02- 05

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02-06

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02-07

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02-09

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02-10

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02-11

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02-12

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02-13

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02-15

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02-19

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02-33

IM motor parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 02-34

IM motor parameter ranges table1 — PDF page 186

Source row Parameter or range label Source name or range value
1 02- 00 No-load Current
2 Range 【0.01~600.00】A
3 02- 01 Rated Current
4 Range 25%~200% of inverter’s rated current.
5 02-03 Rated Rotation Speed
6 Range 【0~60000】rpm
7 02- 04 Rated Voltage
8 Range 200V:【50.0~240.0】V 400V: 【100.0~480.0】V
9 02- 05 Rated Power
10 Range 【0.01~600.00】KW
11 02-06 Rated Frequency
12 Range 【4.8~599.0】Hz
13 02-07 Poles
14 Range 【2~16】(Even)
15 02-09 Excitation Current <1>
16 Range 【15.0~70.0】%
17 02-10 Core Saturation Coefficient 1 <1>
18 Range 【0~100】%
19 02-11 Core Saturation Coefficient 2 <1>
20 Range 【0~100】%
21 02-12 Core Saturation Coefficient 3 <1>
22 Range 【80~300】%
23 02-13 Core Loss
24 Range 【0.0~15.0】%
25 02-15 Resistance between Wires
26 Range 【0.001~60.000】Ω
27 02-19 No-Load Voltage
28 Range 200V:【50~240】V 400V:【100~480】V
29 02-33 Leakage Inductance Ratio <1>
30 Range 【0.1~15.0】%
31 02-34 Slip Frequency <1>
32 Range 【0.1~20.0】Hz

Manual — IM nameplate and saturation formulae — page 187

(4) Motor rated voltage (02-04)

Set the motor rated voltage according to the motor nameplate.

(5) Rated frequency of motor (02-06)

Set the motor rated frequency according to the motor nameplate.

(6) Rated rotation speed of motor (02-03)

Set the motor rpm according to the motor nameplate.

(7) No-load motor voltage (02-19)

Parameter determines the rated flux during motor’s rated rotation in SLV control mode. Set the value of

this parameter to the same value as parameter 17-08 (02-19 for motor 2). A value of 10~50V below the

input voltage level ensures that the motor is capable of providing adequate torque performance when

operating at nominal speed (or higher speed). Setting the value to small can result in a reduction in

no-load current, weakened motor flux and an increase in motor current while the motor is loaded.

(8) Motor excitation current (02-09)

This parameter is automatically set via auto-tuning. It required manual adjustment without

auto-tuning.

Start tunig from 33% when doing manual adjustment. If the output value of no-load voltage (12-67)

is higher than the setting value of no-load voltage (17-08), the motor excitation current is adjusted

downward; if the value (12-67) is lower than the value (17-08), the motor excitation current is

adjusted upward.

Adjust the value of motor excitation current (02-09) will change the value of the motor leakage

inductance (02-17) and motor mutual inductance (02-18).

(9) Setting of motor core saturation coefficients 1, 2 and 3 (02-10, 02-11, 02-12)

These parameters are automatically set during auto-tune. No adjustment required. Parameters are set

to 50% for 02-10, 75% for 02-11 and 137.5% for 02-12 to reduce the impact of core saturation. The

motor core’s saturation coefficient is defined as a percentage of the motor excitation current. When the

motor flux reaches 137.5% level, the core’s saturation coefficient shall be greater than 137.5%. When

the motor flux is 50% or 75%, the core’s saturation coefficient is required to be less than 50% and 75%.

(10) Motor core loss (02-13)

Set motor core loss as the percentage of the motor rated power.

3 × Motor core loss (watt)

Motor rated power (watts, 02-05)

Note: In V/F mode motor core loss (02-13) is used to for torque compensation.

(11) Motor line to line resistance (02-15)

% Wcore (02-13) =

× 100%

Im: 02-09 Motor Excitation Current

Ks1: 02-10 Motor Core Saturation Coefficients 1

Ks2: 02-11 Motor Core Saturation Coefficients 2

Ks3: 02-12 Motor Core Saturation Coefficients 3

Coregraph:flux50%,75%,100%,137.5% correspondKs1 Im,Ks2 Im,Im,Ks3*Im. Im02-09;Ks1 02-10,Ks2 02-11,Ks3 02-12. Sourceformula %Wcore(02-13)=[3×motorcoreloss(watt)/motorratedpower(watts,02-05)]×100%. NativeunitskW elsewhere not silently substituted. No-load voltage02-19 paragraphrefers17-08 andmotor2;excitationprocedure33%start refersno-loadvoltage12-67 althoughsummary12-67kWHr. Preserveuncertainreferences. Section11line-to-lineresistance isheadingonly,thenPDF188starts12;no missingprocedure invented.

Manual — Induction motor model and slip formulae — page 188

(12) Motor no-load current (02-00).

Value is calculated based on the motor rated frequency (17-05) and motor rated current (17-03).

In V / F control mode, the output current is greater than the no-load current with slip compensation is

enabled.

Note: The value of 02-01 needs to be greater than the value set in parameter 02-00, otherwise warning

message "SE01" out of range error will be displayed.

Figure 4.4.12 Y-equivalent model of an induction motor

(13) Motor Leakage Inductance Ratio (02-33)

This parameter is set by the conversion of manual adjustment function. This adjustment does not

have the magnetic function. Normally, it does not require adjustment.

Definition of leakage inductance ratio is the ratio of leakage inductance to rotor inductance. If

default setting is 3.4%, adjust this ratio changes the parameter of motor leakage inductance. The

formula of this ratio is as follows:

Lr

LlKg

When the ratio of leakage inductance is too high or too low, it may cause the motor jittering with

different sound and without operation. The general setting range is 3.0%~5.0% and 4.0% is the

relatively common value for motor operation normally. The ratio of leakage inductance is adjusted

depending on different motor types.

(14) Motor Slip Frequency (02-34)

The default setting is 1Hz and the value of motor slip frequency is obtained from motor nameplate.

Take 4-pole motor with 60Hz for example,

Synchronous speed is

Pole

Frequence

N

rpm and the rated speed in the

motor nameplate is 1700 rpm, then

Hz

Slip

.

Note: Adjusting the motor slip frequency changes the parameter of rotor resistance and the value of slip

frequency is adjusted depending on different motor types.

Note: After executing auto-tuning, parameters which marked <1> will renew the value. Please refer Group

17: Automatic Tuning Parameters for more detail.

Fig4.4.12 Y-equivalent:seriesR1andLlkg feedparallelmagnetizingLm(Idbranch) andR2/s(Iqbranch);s:slip. Leakageformula ξ=LlKg/Lr;sourcegeneral3–5%,common4%,exampledefault3.4%;not model-verified defaults. Synchronousspeed N=120×Frequency/Pole=120×60/4=1800rpm. Sourceexample Slip=(1800−1700)/60=1.67Hz retainedexactly,not endorsed/corrected engineeringformula.02-01 mustexceed02-00 elseSE01. Prose saysratedfrequency17-05/ratedcurrent17-03,where summary17-05speed;flag. <1>valuesrenewedautotune.

Manual — External digital input function list — page 189

Group 03- External Digital Input and Output Parameters

03-00..05 correspondS1..S6;single sharedRange appliesall sixcodes,not only03-05. Choices0–53continuePDF190. PreserveReservedgroups and*1 on15/19/33/34.

External digital input function list. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

External digital input function list. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Shared03-00–03-05(S1–S6) range;continuesPDF190

External digital input function list table1 — PDF page 189

Source row Parameter or range label Source name or range value
1 03- 00 Multi-function terminal function setting – S1
2 03- 01 Multi-function terminal function setting – S2
3 03- 02 Multi-function terminal function setting – S3
4 03- 03 Multi-function terminal function setting – S4
5 03- 04 Multi-function terminal function setting – S5
6 03- 05 Multi-function terminal function setting – S6
7 Range 【0】: 2-Wire Sequence (ON: Forward Run Command) 【1】: 2-Wire Sequence (ON: Reverse Run Command) 【2】: Multi-Speed Setting Command 1 【3】: Multi-Speed Setting Command 2 【4】: Multi-Speed Setting Command 3 【5】: Multi-Speed Setting Command 4 【6】: Forward Jog Run Command 【7】: Reverse Jog Run Command 【8】: UP Frequency Increasing Command 【9】: DOWN Frequency Decreasing Command 【10】: Acceleration/ Deceleration Setting Command 1 【11】: Acceleration/ Deceleration Inhibition Command 【12】: Main/Alternative Run command Switching 【13】: Main/Alternative Frequency Command Switching 【14】: Emergency Stop (Decelerate to Zero and Stop) 【15】: External Baseblock Command (Rotation freely to Stop)*1 【16】: PID Control Disable 【17】: Fault Reset (RESET) 【18】: Reserved 【19】: Speed Search 1(from the maximum frequency)*1 【20】: Manual Energy Saving Function 【21】: PID Integral Reset 【22】~【23】: Reserved 【24】: PLC Input 【25】: External Fault 【26】: 3-Wire Sequence (Forward/ Reverse Command) 【27】: Local/ Remote Selection 【28】: Remote Mode Selection 【29】: Jog Frequency Selection 【30】: Acceleration/ Deceleration Setting Command 2 【31】: Inverter Overheating Warning 【32】: Reserved 【33】: DC Braking*1 【34】: Speed Search 2 (from Frequency Command)*1 【35】: Timing Function Input 【36】: PID Soft Start Disable 【37】~【40】: Reserved 【41】: PID Sleep 【42】~【46】: Reserved 【47】: Fire Mode (Forced to Run Mode) 【48】: KEB Acceleration 【49】: Parameters Writing Allowable 【50】: Unattended Start Protection (USP) 【51】~【52】: Reserved 【53】: 2-Wire Self Holding Mode (Stop Command)

Manual — Input list continuation and terminal map — page 190

S1

S2

S3

S4

S5

S6

Related Parameters

24VG

*1: It can not be selected on the items 15, 19, 33, and 34 while using the permanent magnetic (PM)

motor.

Refer to the multi-function digital input and related parameters in the following Fig. 4.4.13

Figure 4.4.13 Multi-function digital input and related parameters

Choices54–58,63–69continue shared03-00..05 rangefromPDF189;59–62unprinted. *1 statescannotselect15,19,33,34whenusingPMmotor. Fig4.4.13 S1→03-00,S2→03-01,S3→03-02,S4→03-03,S5→03-04,S6→03-05,common24VG. No inferredotherterminal.

Input list continuation and terminal map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Input list continuation and terminal map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Shared03-00–03-05 range continuationfromPDF189

Input list continuation and terminal map table1 — PDF page 190

Source row Parameter or range label Source name or range value
1 ⟦blank source cell⟧ 【54】: Switch PID1 and PID2 【55】: RTC Time Enable 【56】: RTC Offset Enable 【57】: Forcing Frequency Run 【58】: Run Permissive Function 【63】: Switch to Tolerance Range of Constant Pressure 2 【64】: Reserved 【65】: Short-circuit braking 【66】: Reserved 【67】: Reserved 【68】: External Fault 2 【69】: External Overload

Manual — Input functions0–19 mode table — page 191

Table 4.4.4 Multi-function digital input setting (03-00 ~ 03-05) (“O”: Enable, “X”: Disable)

Oenabled,Xdisabled,dashreserved. Function15ExternalBaseblock PMcolumnO conflictsPDF190 cannotselect15PM. Function19PMX. Rowpairs2/3 and4/5 share descriptioncells;retainmergedparents. Everyfunction/name/LCD/description/mode separatelyretained.

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 0

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 1

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 2

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 3

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 4

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 5

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 6

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 7

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 8

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 9

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 10

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 11

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 12

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 13

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 14

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 15

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 16

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 17

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 18

Input functions0–19 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 19

Input functions0–19 mode table table1 — PDF page 191

Source row Value Function name LCD display Description V/F SLV PM SLV
1 0 2-wire type (Forward operation) 2-Wire (FWD-RUN) 2- wire (ON : Forward operation command). O O O
2 1 2-wire type (Reverse operation) 2-Wire (REV-RUN) 2- wire (ON : Reverse operation command). O O O
3 2 Multi-Speed Setting Command 1 Muti-Spd Ref 1 Multi-Speed Reference 1 O O O
4 3 Multi-Speed Setting Command 2 Muti-Spd Ref 2 Multi-Speed Reference 2 O O O
5 4 Multi-Speed Setting Command 3 Muti-Spd Ref 3 Multi-speed Reference 3 O O O
6 5 Multi-Speed Setting Command 4 Muti-Spd Ref 4 Multi-speed Reference 4 O O O
7 6 Forward Jog Run Command FJOG ON: Forward operation in jog mode (00-18) O O O
8 7 Reverse Jog Run Command RJOG ON: Reverse operation in jog mode (00-18) O O O
9 8 UP Frequency Increasing Command UP command ON: Command of output frequency increasing (only used by support of DOWN command). O O O
10 9 DOWN Frequency Decreasing Command DOWN command ON: Command of output frequency decreasing (only used by support of UP command). O O O
11 10 Acceleration/ Deceleration Setting Command 1 Acc/Decel Time Selection 1 Acceleration/deceleration time selection command1 O O O
12 11 Acceleration/ Deceleration Inhibition Command ACC/DEC Inhibit ON: Acceleration/deceleration prohibition O O O
13 12 Main/Alternative Run command Switching Run Change Sel Run command source is set by alternative run command (00-03). O O O
14 13 Main/Alternative Frequency Command Switching Freq Change Sel Frequency command source is set by alternative frequency command (00- 06). O O O
15 14 Emergency Stop (Decelerate to Zero and Stop) E-Stop ON: Emergency stop input O O O
16 15 External Baseblock Command (Rotation freely to Stop) Ext. Baseblock ON: Inverter base interdiction O O O
17 16 PID Control Disable PID Disable ON: PID control disable O O O
18 17 Fault Reset Fault Reset Fault reset O O O
19 18 Reserved Reserved Reserved - - -
20 19 Speed Search 1(from the maximum frequency) Speed Search 1 ON: Search the speed from the maximum output frequency O O X

Manual — Input functions20–49 mode table — page 192

Function20/48VFonly;33DCbrakingVFonly;34speedsearch2 modeO/X/O conflictsPDF190 PMprohibition.26descriptionomitssecondterminalidentifier afterS1;PDF200explicitS1/S2separatelyretained.47FireMode saysstopsforOC,SC,CUV,FUL,STO,contrastsPDF201SC-onlyprotectionexception.49OFFprotectsall exceptreference00-05;PDF201simplifiedtabledoesnoteraseexception.

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 20

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 21

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 22~23

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 24

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 25

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 26

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 27

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 28

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 29

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 30

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 31

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 32

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 33

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 34

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 35

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 36

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 37~40

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 41

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 42~46

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 47

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 48

Input functions20–49 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 49

Input functions20–49 mode table table1 — PDF page 192

Source row Value Function name LCD display Description V/F SLV PM SLV
1 20 Manual Energy Saving Function Energy saving ON: Manual energy saving control is based on the settings of 11-12 and 11-18. O X X
2 21 PID Integral Reset PID I-Reset ON: PID integral value reset O O O
3 22~23 Reserved Reserved Reserved - - -
4 24 PLC input PLC Input ON: Digital PLC input O O O
5 25 External fault Ext. Fault ON: External fault alarm O O O
6 26 3-Wire Sequence (Forward/ Reverse Command) 3-Wire (FWD/REV) 3-wire control (forward/reverse command). ON: Reverse; OFF: Forward. When the parameter is set to 26,terminal S1 and terminal will become operation command and stop command respectively, and their original functions will be closed. O O O
7 27 Local/ Remote Selection Local/Remote ON: Local mode (via the digital operator) OFF: Frequency command and operation command will be determined according to the setting of parameter (00-02 and 00-05) O O O
8 28 Remote Mode Selection Remote Mode Sel ON: RS-485 communication OFF: Control circuit terminal O O O
9 29 Jog Frequency Selection JOG Freq Ref ON: Selection jog frequency command O O O
10 30 Acceleration/ Deceleration Setting Command 2 Acc/Decel Time Selection 2 Acceleration/deceleration time selection command2 O O O
11 31 Inverter Overheating Warning (OH2) Overheat Alarm ON: Inverter overheat alarm (OH2) input( will display OH2) O O O
12 32 Reserved Reserved Reserved - - -
13 33 DC Braking DC Brake Command ON: Perform DC braking O X X
14 34 Speed Search 2 (from Frequency Command) Speed Search 2 ON: Search speed from set frequency O X O
15 35 Timing Function Input Timer Input .Set the time function at 03-37, 03-38 .Set the time function output at 03-11, 03-12 O O O
16 36 PID Soft Start Disable PID SFS Disable ON: PID slow-start off O O O
17 37~40 Reserved Reserved Reserved - - -
18 41 PID Sleep PID Sleep ON: PID Sleep O O O
19 42~46 Reserved Reserved Reserved - - -
20 47 Fire Mode (Forced to Run Mode) Fire Mode ON: Inverter runs in the max. frequency of motor 1 (parameter 01-02). Note: If fault message of OC, SC, CUV, FUL, STO occur, function of fire mode will stop. O O O
21 48 KEB Acceleration KEB Accel. ON: KEB acceleration start O X X
22 49 Parameters Write-in Allowed Write Enabled ON: All parameters are writable. OFF: Except reference frequency (00-05) all parameters are write-protected. O O O

Manual — Input functions50–69 mode table — page 193

03-0X =00: 2-wire control: forward operation

03-0X =01: 2-wire control: reverse operation. Refer to the 2-wire operation mode in Figure 4.3.1.

03-0X =02: Multi-speed setting command 1.

03-0X =03: Multi-speed setting command 2.

03-0X =04: Multi-speed setting command 3.

03-0X =05: Multi-speed setting command 4.

03-0X =29: Jog frequency selection (setting =29).

Select frequency reference using the multi-function digital input.

54description ON:PID1/OFF:PID2 whileLCDPID2Enable andPDF202saysswitchPID1toPID2whenPID2ON;polaritynotresolved.65short-circuitbrakingX/X/O.58ONstopsaccording08-30.63ONpressure2(23-34),OFFpressure1(23-09)PUMPmode.59–62unprinted,notinvented.69ExternalOverload hasS5/fireconditiononPDF203.

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 50

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 51~52

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 53

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 54

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 55

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 56

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 57

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 58

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 63

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 64

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 65

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 66

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 67

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 68

Input functions50–69 mode table. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 69

Input functions50–69 mode table table1 — PDF page 193

Source row Value Function name LCD display Description V/F SLV PM SLV
1 50 Unattended Start Protection (USP) USP ON: After power is input,the inverter ignores the operation command OFF: After power is input,the inverter will return the operation status before power is cut off. O O O
2 51~52 Reserved Reserved Reserved - - -
3 53 2-Wire Self Holding Mode (Stop Command) 2-Wire (STOP) 2-Wire Self Holding Mode (ON: Stop Command). O O O
4 54 Switch PID1 and PID2 PID 2 Enable ON: PID1 enabled OFF: PID2 enabled O O O
5 55 RTC Time Enable RTC Timer Switch ON:RTC Time Function Enabled O O O
6 56 RTC Offset Enable Offset Time Switch ON:RTC Offset Enabled O O O
7 57 Forcing Frequency Run Force Freq Cmd ON: Run on Forcing Frequency (23-28) OFF: Determine frequency reference and run command depending on the setting of parameter (00-02 and 00-05) O O O
8 58 Run Permissive Function Safety Function ON: Stop on the setting of 08-30 O O O
9 63 Switch to Tolerance Range of Constant Pressure 2 Switch Const.P. Range 2 ON: Use tolerance range of constant pressure 2 (23-34) for PUMP mode OFF: Use tolerance range of constant pressure 1 (23-09) for PUMP mode O O O
10 64 Reserved Reserved Reserved - - -
11 65 Short-circuit braking SC Brk ON: Excute short-circuit braking X X O
12 66 Reserved Reserved Reserved - - -
13 67 Reserved Reserved Reserved - - -
14 68 External Fault 2 Ext. Fault 2 ON: the alarm of external Fault O O O
15 69 External Overload Ext. Overload ON: the input of external overload O O O

Manual — Multispeed operation selection — page 194

Table 4.4.5 Multi-speed operation selection

0: OFF, 1: ON, ─: Ignore

*1. Jog frequency terminal has a higher priority than multi-speed reference 1 to 4.

*2. When parameter 00-05=0 (frequency reference input = digital operator), multi-speed frequency 1 will be

set by 05-01 frequency reference setting1). When parameter 00-05=1 (frequency reference input=control

circuit terminal), multi-speed frequency command 1 is input through analog command terminal AI1 or

AI2.

*3. 05-02 is used for auxiliary speed frequency of AI2 as default setting. It is necessary to set 04-05≠0 to

switch 05-02 to be for Frequency command 1. When PID control mode is enabled (10-03= xxx1b),

Frequency of Speed - Stage 1 can not switch auxiliary speed frequency even though Multi-function

Terminal Function Setting (03-00~03-05)=16 (PID control disable).

Wiring Example: Fig. 4.4.14 and 4.4.15 show an example of a 9-speed operation selection.

Figure 4.4.14 Control Terminal Wiring Example

17rows:16binaryspeedcombinationsplusjogoverride. InputcolumnsJog,Ref4,Ref3,Ref2,Ref1.0OFF1ON,dashIgnore. Joghigherpriority. Row1uses05-01ormain;row2AI2auxif04-05=0 else05-02;PID10-03xxx1brestrictsauxswitch evenDI16. Fig4.4.14 S1forward03-00=0,S2reverse03-01=1,S3ref1 03-02=2,S4ref2 03-03=3,S5ref3 03-04=4,S6jog03-05=29,common24VG.

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 1

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 2

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 3

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 4

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 5

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 6

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 7

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 8

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 9

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 10

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 11

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 12

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 13

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 14

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 15

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 16

Multispeed operation selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 17

Multispeed operation selection table1 — PDF page 194

Source row Speed Jog frequency reference Multispeed frequency4 Multispeed frequency3 Multispeed frequency2 Multispeed frequency1 Frequency selection
1 1 0 0 0 0 0 Frequency command 0 ( 05-01) or main speed frequency*2
2 2 0 0 0 0 1 (04-05=0) Auxiliary speed frequency or (04-05≠0) Frequency command 1 (05-02) *3
3 3 0 0 0 1 0 Frequency command 2 (05-03)
4 4 0 0 0 1 1 Frequency command 3 (05-04)
5 5 0 0 1 0 0 Frequency command 4 (05-05)
6 6 0 0 1 0 1 Frequency command 5 (05-06)
7 7 0 0 1 1 0 Frequency command 6 (05-07)
8 8 0 0 1 1 1 Frequency command 7 (05-08)
9 9 0 1 0 0 0 Frequency command 8 (05-09)
10 10 0 1 0 0 1 Frequency command 9 (05-10)
11 11 0 1 0 1 0 Frequency command 10 (05-11)
12 12 0 1 0 1 1 Frequency command 11 (05-12)
13 13 0 1 1 0 0 Frequency command 12 (05-13)
14 14 0 1 1 0 1 Frequency command 13 (05-14)
15 15 0 1 1 1 0 Frequency command 14 (05-15)
16 16 0 1 1 1 1 Frequency command 15 (05-16)
17 17 1*1 ─ ─ ─ ─ Jog frequency command (00-18)

Manual — Nine-speed timing and jog control — page 195

Termina

l

(S1)

(S5)

(S6)

(S7)

(S8)

Forward RUN

Multi- step

speed Ref1

speed Ref2

speed Ref3

JOG Frequency

Ref

speed

*1

master

ref

*2

aux.

t

Frequency

Reference

(05-01)

(00-18)

(05-02)

(05-03)

(05-04)

(05-05)

(05-06)

(05-07)

(05-08)

Figure 4.4.15 9-speed timing diagram

*1. When 00-05=1, multi-speed frequency reference is set by analog input AI1 or AI2.

03-0X =06: Forward jog run command, uses jog frequency parameter 00-18.

03-0X =07: Reverse jog run command, uses jog frequency parameter 00-18.

Notes:

-

To excute the Forward jog or Reverse jog command need to set 00-02=1 at first.

Jog command has a higher priority than other frequency reference commands.

Jog command uses stop mode set in parameter 07-09 when Jog command is active > 500ms.

When 11-00 (Direction Lock Selection) set to 1 (Only Allow Forward Rotation), if there is a motor

reverse command, the “RUNER” warning will display.

When 11-00 (Direction Lock Selection) set to 2 (Only Allow Reverse Rotation), if there is a motor

forward command, the “RUNER” warning will display.

03-0X =08: UP frequency accelerating command; set parameter 00-05 Frequency command to 2 to

activate.

03-0X =09: Down frequency decelerating command; set parameter 00-05 Frequency command to 2 to

Note:

The inverter operates the variation of increasing/ decreasing output frequency via keypad (refer

to parameter 11-56) / external multi-function digital input (terminal S1to S6) when the motor is

running.

Fig4.4.15 forwardS1 ONthroughspeed1–9. TiminglabelsRef1(S5),Ref2(S6),Ref3(S7),Jog(S8) differPDF194wiringS3/S4/S5/S6. Ref3/2/1 combinationsspeeds1–8:000,001,010,011,100,101,110,111;speed9jogON,allrefs0. Frequencystages05-01..08then00-18. Master 1/aux 2 retainPDF194notes. Jogneeds00-02=1,higherpriority,07-09stopmodewhenactive>500ms;11-00directionlockgivesRUNER. UP/DOWNneeds00-05=2.

Manual — UP/DOWN operation and timing — page 196

command via the external multi-function digital input terminal and 00-02=1 (external terminals) &

00-05=2 (terminal command UP/DOWN) & 03-00~03-05=8 (UP command)/ 9 (DOWN

command).

deceleration time.

.

Note: SE02 DI terminal Error will be displayed when:

-

Only the UP or DOWN command function is set.

Both UP command and Inhibit Acceleration/deceleration command are activated simultaneously.

Both DOWN command and Inhibit Acceleration/deceleration command are activated

simultaneously.

For the examples of UP/DOWN control wiring and operation, please refer to Figure 4.4.16 and 4.4.17.

Figure 4.4.16 UP/DOWN wiring and operation example

Figure 4.4.17 Up / Down command timing diagram

UP / DOWN Command Operation

When the Forward Run command is active and the UP or Down command is momentarily activated the

inverter will accelerate the motor up to the lower limit of the frequency reference (00-13).

When using the UP / Down command, the output frequency is limited to the upper limit of frequency

reference (00-12) and the lower limit of frequency reference (00-13).

The UP / DOWN command uses acceleration 1 or 2 / deceleration time 1 or 2 for normal operation Tacc1 /

Tdec1 (00-14, 00-15) or Tacc2 / Tdec 2 (00-16, 00-17).

Fig4.4.16 S1forward03-00=0,S5UP03-04=8,S6DOWN03-05=9/common24VG. UP/DOWN states10accelerate,01decelerate,00hold,11hold. Requiresbothterminals,00-02=1,00-05=2;SE02ifonlyone orUP/DOWNwithinhibit. Fig4.4.17 frequencyrisesbetween00-13lower/00-12upper,holdswhenbothorneither,andstopswhenrunremoved;afterpowerrestore 1storedreferenceif11-58=1, 2lowerlimitif0 perPDF197.

UP/DOWN operation and timing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

UP/DOWN operation and timing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: UP Command

(Terminal S5)

UP/DOWN operation and timing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Down Command

(Terminal S6)

UP/DOWN operation and timing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Operation

UP/DOWN operation and timing table1 — PDF page 196

Source row Command or operation State1 State2 State3 State4
1 UP Command (Terminal S5) 1 0 0 1
2 Down Command (Terminal S6) 0 1 0 1
3 Operation Accel (UP) Decel (DWN) Hold Hold

Manual — Frequency memory and inhibition — page 197

Hold

Fref 1

Fref

*1

*2

Power

Supply

Forward

Run

Inhibit

ACC / DEC

Command

Frequency

Reference

Output

ON

OFF

t

Refer to 03-40 UP/ DOWN frequency width setting for using other functions of UP/ DOWN. (It is enabled in

inverter software V1.4)

Frequency reference retention is active when parameter 11-58 is set to 1 and the frequency reference is

saved when power is lost and retrieved when power is restored.

*1: When 11-58 = 1 and the operation command is active, the output frequency will accelerate to the

previously stored frequency command.

*2: When 11-58 = 0 and the operation command is active, the output frequency will accelerate to the lower

limit of frequency reference (00-13).

03-0X =10: Acceleration/deceleration 1 selection

03-0X =30: Acceleration/deceleration 2 selection

Refer to the "multi-function digital input terminals select acceleration/ deceleration time” in Table 4.4.1 and

Figure 4.4.6.

03-0X =11: Acceleration/deceleration inhibition command (hold command)

When activated suspends the acceleration / deceleration operation and maintains the output frequency at

current level.

If 11-58 = 1, the frequency reference value is saved when the acceleration/deceleration inhibition

command is active. Deactivating the acceleration / deceleration inhibition command resumes acceleration

/ deceleration.

command is active and even when powering down the inverter.

Refer to Fig.4.4.18. for an example.

Figure 4.4.18 Acceleration / deceleration inhibition command operation

*1. When 11-58 = 1, and acceleration / deceleration inhibit command is activated, the frequency reference

is stored even when powering down the inverter. When a run command is given (e.g. run forward) and the

acceleration / deceleration inhibit command is active, the inverter will accelerate to the previously stored

frequency reference.

03-40additionalUP/DOWN functionV1.4.11-58=1saveonpowerloss;0restartlowerlimit. Inhibitfunction11holdsoutput;resumeaccdecwhenreleased. Fig4.4.18 separateholdperiods whileaccelerating/decelerating;Fref1→Fref2;powerlossoutput0;return 1storedfrequencywhen11-58=1,continuation 2onPDF198zeroif11-58=0andrun/inhibitactive.

Manual — Main/alternative switching and baseblock — page 198

t

Run

Command

External

Baseblock

Output

Frequency

(Speed search)

Coast to

stop

*2. When 11-58 = 0, and a run command is given and the acceleration / deceleration inhibit command is

active, the frequency reference and output frequency will remain at zero.

03-0X =12: Main/Alternative Run command Switching

Run command source is set by alternative run command (00-03) when function terminal is active. When

function terminal is set to 27 (Local/ Remote control selection), the priority will higher than the switch of

main/ alternative run command.

03-0X =13: Main/Alternative Frequency Command Switching

Frequency command source is set by alternative frequency command (00- 06) when function terminal is

active. When function terminal is set to 27 (Local/ Remote control selection), the priority will higher than the

switch of main/ alternative frequency command.

03-0X =14: Emergency stop (decelerate to zero and stop)

Refer to the "deceleration time of emergency stop" of parameter 00-26.

03-0X =15: External Baseblock Command (coast to stop)

Execute the base block command by the use of ON / OFF way of multi-function digital input terminal, and

prohibit the inverter output.

During run: When an external base block command is activated, the keypad displays "BBn BaseBlock

(Sn)", indicating the inverter output is turned off (n indicates the digital input number 1 – 6). Upon removing

the base block signal, the motor will run at the frequency reference. If speed seach from frequency

reference is active the inverter output frequency starts from the frequency reference and searches for the

coasting motor speed and continue to operate. If speed search is not active the output frequency starts at

0Hz.

During deceleration: When an external base block command is activated, the keypad displays "BBn

BaseBlock (Sn)", indicating the inverter output is turned off (n indicates the digital input number 1 – 6).

Upon removing the base block signal, the motor is stopped or will coast to a stop and the inverter will

remains in the stop condition.

During acceleration: When an external base block command is activated, the keypad displays "BBn

Upon removing the base block signal, the motor will run at the frequency reference. If speed seach from

frequency reference is active the inverter output frequency starts from the frequency reference and

searches for the coasting motor speed and continue to operate. If speed search is not active the output

frequency starts at 0Hz.

Figure 4.4.19 External base block operation

First*2completesPDF197figure. Local/remote27higherprioritythan12run/13frequency main-alt switches. Baseblock15duringrun/acceleration removal resumesreferencewithspeedsearchor0Hzwithout;duringdecelerationremainsstop. Fig4.4.19 firstbaseblockduringruncoasts,releaseSpeedSearchresumes;secondafterrunoffcoaststop. BFnnotinferred;sourceBBnBaseBlock(Sn),n1–6 retained.

Manual — Fault reset and local/remote control — page 199

03-0X =16: PID control disable.

Note: The frequency will depend on parameter 00-05 (reference frequency) to determine the source of

frequency input. Refer to the descriptions of parameter 00-05 and 00-06 for details.

03-0X =17: Fault reset

The output becomes active when the inverter trips on a fault. Upon an inverter fault the inverter output will

turn off (base block) and the keypad displays the dedicated fault message.

When fault occurs, the following actions can be used to reset the fault:

  1. Program one of the multi-function digital inputs (03-00 to 03-05) to 17 (reset fault) and active input.*

  2. Press the reset key of the digital operator (RESET).*

  3. Recycle power to the inverter. Important Note: If a run command is active during power-up, the

inverter will start running automatically.

03-0X =19: Speed Search 1 (from the maximum frequency).

03-0X =34: Speed Search 2 (from the frequency command).

Refer to the "speed search" function in the parameter group 7 (start/ stop control function).

03-0X =20: Energy saving enabled

Manual energy savings function is set with parameters 11-12 and 11-18.

For the manual energy saving operation refer to Figure 4.3.78.

03-0X =21: PID integral reset

03-0X =25: External fault

Activating the external fault input will turn off the inverter output and the motor will coast to a stop. The

keypad displays the external fault message “EFn Ext. Fault (Sn)”, where n is the input terminal number.

03-0X =27: Local / Remote selection.

Switch the inverter frequency reference source between Local (keypad) or Remote (control circuit

terminals or RS485). Use parameter 00-05 (Main frequency command source selection) and 00-02 (Run

command selection) to select the input source. When PID is enabled (10-03=XXX1), parameter 10-00

(target value source) is performed. If 23-00=1, make sure the setting value of parameter 23-04. If 23-00=2,

make sure the setting value of parameter 23-59 and 00-02.

Note: In 3-wire operation terminal S1 and S2 are reserved for run/stop operation and the Local / Remote

function can only be set to digital input terminals S3 to S6 (03-02 to 03-05).

Note: To switch between local and remote the inverter has to be stopped.

FaultresetDI17,keyRESETorpowercycle. SourcewarnsactiveRUNduringpowerupstartsautomatically;activefaultresetrequiresRUNremoved. Externalfault25coaststoStopEFn(Sn). Local27ONkeypad/SEQREFoff;OFFremote00-05/00-02SEQREFon. PIDtargetbranches10-00,23-04pumpor23-59HVACretained. ThreewireS1/S2reserved,localremoteonlyS3–6;switchonlystopped.

Fault reset and local/remote control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Fault reset and local/remote control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: ON

Fault reset and local/remote control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: OFF

Fault reset and local/remote control table1 — PDF page 199

Source row Input Mode Frequency Reference / Run/Stop Command Source
1 ON Local - Frequency reference and Run-Stop from keypad. - LEDs SEQ and REF are off. - When PID is enabled, REF indicator OFF presents PID target value is set by the keypad.
2 OFF Remote - Frequency reference source selected by parameter 00-05 and Run-Stop source selected by parameter 00-02. - LEDs SEQ and REF are on. - When PID is enabled, REF indicator ON presents PID target value is set by the control terminal AI1.

Manual — Remote source selection — page 200

LCD Digital

Operator

Frequency Reference

and

Run Command

RS – 422 /485

communications

Control circuit

terminals

ON

OFF

(

)

( Local Mode )

( Remote Mode )

Set one of 03-00 to 03-05 = 28

Set one of 03-00 to 03-05 = 27

10-03=xxx1B

Target Reference

10-03=xxx0B

03-0X =28: Remote mode selection

Switch between terminal source and communication (RS-422/RS-485) source for frequency reference and

operation command.

In Remote mode, indicators of SEQ and REF are on; you can use terminals AI1 and AI2 to control the

frequency command, and use terminals S1, S2 or communication terminal RS-485 to control the operation

command.

Figure 4.4.20 Remote mode operation selection

To switch the frequency reference and operation command input between communication RS-485 and

control terminals the following parameters have to be set:

  1. 00-05=1 (use control terminal AI1 or AI2 as reference frequency source)

  2. 00-02=1 (use control terminal S1 or S2 for operation command)

  3. Set one of the digital input terminals (03-02 to 03-05) to 28 (Operation selection of remote mode)

03-0X =24: PLC Input

It is required to match Drive Link program. Ladder diagram is edited in the PLC program. When the

message output is conducted, this message will be sent to the inverter.

03-0X =26: 3-Wire Sequence (Forward/ Reverse Command)

When the digital input terminals (S3~S6) is set to 26, terminal S1 and S2 will become the run command

and stop command. Refer to Fig.4.4.2.

03-0X =29: Jog Frequency Selection

When 00-18 (Jog Frequency) is set up, the inverter depends on this frequency for command when it is ON.

Fig4.4.20 DI27ONlocalLCD,OFFremotebranch;DI28ONRS422/485,OFFcontrolterminals.10-03xxx0Bfrequencyreference/run;xxx1Btargetreference/run. Remoteconditions00-05=1,00-02=1,one03-02..05=28. Diagram says03-00..05=28;retainbroaderdiagramandnarrowertextwithoutinference. PLC24requiresDriveLink;3wire26onS3–6makesS1run/S2stop;Jog29uses00-18.

Remote source selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Remote source selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: ON

Remote source selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: OFF

Adjacent source context — repeated to preserve continuation:

Remote source selection table1 — PDF page 200

Source row Input Mode Frequency Reference / Run/Stop Command Source
1 ON Communication - Frequency reference and run/stop command control via communication (RS-422/RS-485).
2 OFF Terminal - Frequency reference source from AI1 / AI2 input (00-05=1) and Run-Stop command from terminals S1 / S2 (00-02=1).

Manual — Braking/fire/write-enable functions — page 201

DC

injection

Brake

t

(Fmin)

The larger of 01-08

or 07-06

Run

Command

DC injection

Braking

Output

Frequency

(or Jog command)

OFF

ON

03-0X =30: Acceleration/ Deceleration Setting Command 2

When it is ON, the inverter will be active depends on the acceleration time 2 of 00-16 and deceleration time

2 of 00-17.

03-0X =31: Inverter overheat warning

When input is active the inverter displays warning message "OH2" and continues operation. Deactivating

the input reverts back to the original display. Warning message does not require resetting the inverter.

03-0X =33: DC braking

When input is active DC-Injection braking is enabled during start and stopping of the inverter.

DC Injection braking is disabled when a run or jog command is active.

Note: Either short-circuits braking command or DC braking command is selected. If these two modes are

both selected, SE02 error (DI Terminal Error) will occur.

Refer to the DC braking time diagram in Fig.4.4.21.

Figure 4.4.21 DC braking timing diagram

03-0X =35: Timing function

Refer to the "time function" parameter 03-37 and 03-38.

03-0X =36: PID Soft start disable

Refer to the "PID Control" function of PID function parameter group 10.

03-0X =47: Fire mode (Foreced to operation mode)

When input is active disables all inverter warning and hardware (exclusive of SC) protections. This function

is commonly used in commercial applications where the inverter controls an exhaust fan and needs run to

destruction in case of a fire.

03-0X =48: KEB acceleration

When input is active enables KEB (Kinetic Energy Braking) during acceleration. Refer to the parameter

description of 11-47 and 11-48. Note: To enable set parameter 11-47 to a value greater than 0.

03-0X =49: Parameters write-in allowed

When input is active allows parameter to be changed.

Note: When none of the digital input terminals are set to function 49, parameter write-in protection is

controlled by parameter 13-06.

Fig4.4.21 DCinjectiononlybeforestart/afterstopwhilebrakeinputON;run/jogoverrides. Startthreshold01-08Fmin,stoplarger01-08or07-06. CannotselectDCandshortcircuitbrakingsimultaneously(SE02). Function30textuses00-16/17 thoughfullselectiontableincludespair3/4;retaincontexts. Fire47prosesaysallwarning/hardwareprotectionsdisabledexceptSC,contradictsPDF192OC/SC/CUV/FUL/STOstoplist. Supplierclaimnot safetyapproval.49writeenable ON;OFFprotected;13-06governswhennoDI49.

Braking/fire/write-enable functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Braking/fire/write-enable functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter ON

Braking/fire/write-enable functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter OFF

Adjacent source context — repeated to preserve continuation:

Braking/fire/write-enable functions table2 — PDF page 201

Source row Parameter or range label Source name or range value
1 ON Parameters Write Enabled
2 OFF Parameters Write Protected

Manual — USP and PID/RTC/forced frequency functions — page 202

03-0X =50: Unattended Start Protection (USP)

When input is active prevents inverter from starting automatically when a run command is present at time

of power-up. Please refer to Fig.4.4.21a for more details.

Figure 4.4.21a Unattended Start Protection

03-0X =53: 2-Wire Self Holding Mode (Stop Command).

Refer to the “2-wire operation with hold function” of parameter 00-02.

03-0X =54: Switch PID1 and PID2

It will switch PID1 to PID2 when PID2 is ON.

03-0X =55: RTC Time Enable

When 16-13 (RTC timer function) = 2 (DI setting) and RTC Time Enable is ON, RTC timer function is

enabled.

03-0X =56: RTC Offset Enable

When 16-30 (Selection of RTC Offset) = 2 (DI setting) and RTC Offset Enable is ON, the inverter will run

depending on RTC offset time setting (16-31).

03-0X =57: Forced Frequency Run

This function enables with the corresponding of parameter of 23-28 and the source of frequency command

of parameter 00-05 set to the value of 5 (PID given, namely the parameter of10-03 needs to be active).

When any one of the multi-function digital input terminal (S1~S6) is set to the value of 16 (the interdiction

of PID function), pump will not depend on feedback to do any PID output adjustment; simultaneously

another one is set to the value of 57 (forced frequency run) and inverter will have the frequency run setting

depending on the parameter of 23-28. Inverter will stop output when digital input terminals (S1~S6) are

removed.

This function is applied to inverter output being controlled by external pressure sensor (eg. differential

pressure switch) when pressure sensor disconnects.

03-0X =58: Run Permissive Function

When digital input terminal enables, inverter will stop via the set of parameter 08-30 after Run Permissive

Function function is active.

Fig4.4.21a USPpreventsstartifRUNpresentpowerup;firstwarningclearswhenRUNoff;clearingalarmwhileRUNactiveautomaticallyrestarts;RUNalreadyOFFpowerupnormalnextstart. CaptiontexttypoUPSretained.54PIDswitchpolarityconflictPDF193.55requires16-13=2;56requires16-30=2and16-31offset.57forced23-28withDI16/57andPIDactive;prosesays00-05=5PIDthoughrange5ReservedPDF164;retain.58ONstopvia08-30.

Manual — Short-circuit braking and external faults — page 203

03-0X =63: Switch to Tolerance Range of Constant Pressure 2

When using in PUMP mode (23-00=1), the tolerance range of constant pressure (23-09) will be used for

waking up the inverter. When digital input terminal enables, the tolerance range of constant pressure 2

(23-34) will be used.

03-0X =65: Short-circuit breaking

To stop inverter by turning on Short-circuit breaking with setting terminal. If executing run command or jog

command, short-circuit breaking command will erased and start to run. The following picture is short-circuit

breaking time process.

Note: Either short-circuits braking command or DC braking command is selected. If these two modes are

both selected, SE02 error (DI Terminal Error) will occur.

03-0X =68: External Fault 2

‧ When an external fault occurs, the external fault 2 input terminal is turned on, the inverter will be turned

off and the motor will free run to stop.

‧ If external input terminal S3 is set (03-02 = 68) as external fault, the message “EF3 Ext. Fault (S3)”

(EF3) will be displayed.

‧ All six input terminals (S1 to S6) can be designated as external fault input.

03-0X =69: External Overload, Input Terminal is Normally Closed Switch.

‧ When external overload occurs, the external overload input terminal closed, the inverter will be turned

off and the motor will decelerate to stop.

‧ If the external input terminal S5 is set (03-04 = 69) to external overload, “TOL Ext. OverLoad” message

will be displayed.

‧ To enable the external overload function, the fire mode must be enabled first (08-48 =1), only the

external input terminal S5 can be designated as External Overload Input.

‧ Setting the external input terminal as External Overload will set the input terminal as the normally

closed, therefore, before setting the external overload function, do not set the operation command from

the external terminal, otherwise, it will cause unnecessary damage.

Set the digital input CPU scan time. The digital input signal needs to be present for the minimum scan time

to qualify as an enabled command.

Note: For noisy environments select scan time of 8ms (results in a slower response time).

Shortcircuit65run/jogoverridesbrake;diagramstart01-08Fmin,stoplarger01-08or07-06;DCandsccannotbothselectedSE02.68externalfaultallS1–6coast;S3example03-02=68EF3.69externaloverloadonlyS5,03-04=69,TOL,requiresfire08-48=1;normallyclosedassignmentandbefore-terminalRUNwarningretained. Textsaysclosedwhenfaultdespitenormallycloseddescription;no inferredpolarityfix.03-08scan0:4ms,1:8ms;minsignalpresentforscantime;8msnoisyenvironment/slowerresponse.

Short-circuit braking and external faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Short-circuit braking and external faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 03- 08

Short-circuit braking and external faults table1 — PDF page 203

Source row Parameter or range label Source name or range value
1 03- 08 (S1~S6) DI Scan Time
2 Range 【0】 Scan Time 4ms 【1】 Scan Time 8ms

Manual — Input contact polarity and relay output choices — page 204

Parameter 03-09 and 03-10 selects the digital input type between a normally open and a normally closed

switch/contact.

Each bit of 03-09/03-10 presents an input:

03-09= 0 0 0 0 0:normally open switch

s4 s3 s2 s1 1:normally closed switch

03-10= x x 0 0 0:normally open switch

s6 s5 1:normally closed switch

Example: S1 and S2 wired to a normally closed contact / switch set 03-09=0011.

Do not set the operation command parameter 00-02 to terminal control before setting the digital

input type. Failure to comply may cause death or serious injury.

03-09bitsleft→rightS4,S3,S2,S1;03-10xxS6S5;0normallyopenAcontact,1normallyclosedBcontact. S1/S2NCexample0011. Sourcewarnssetinputtypebefore00-02terminalcontrol. Outputchoicesapply03-11R1,03-12R2,03-20R4 1,03-21DO2-DOG 1,03-39R3;sharedlist0–31continuesPDF205outsidepart,including*1qualification. No complete relaydefinition claimed.

Input contact polarity and relay output choices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Input contact polarity and relay output choices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 03- 09

Input contact polarity and relay output choices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 03- 10

Input contact polarity and relay output choices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Shared03-11/12/20/21/39 relay-outputrange;partialcontinuesPDF205

Input contact polarity and relay output choices table1 — PDF page 204

Source row Parameter or range label Source name or range value
1 03- 09 Multi-function Terminal S1-S4 Type Selection
2 Range 【xxx0b】:S1 A contact 【xxx1b】:S1 B contact 【xx0xb】:S2 A contact 【xx1xb】:S2 B contact 【x0xxb】:S3 A contact 【x1xxb】:S3 B contact 【0xxxb】:S4 A contact 【1xxxb】:S4 B contact

Input contact polarity and relay output choices table2 — PDF page 204

Source row Parameter or range label Source name or range value
1 03- 10 Multi-function Terminal S5-S6 Type Selection
2 Range 【xxx0b】:S5 A contact 【xxx1b】:S5 B contact 【xx0xb】:S6 A contact 【xx1xb】:S6 B contact

Input contact polarity and relay output choices table3 — PDF page 204

Source row Parameter or range label Source name or range value
1 03-11 Relay (R1A-R1C) Output
2 03-12 Relay (R2A-R2C) Output
3 03-20 Relay(R4A-R4C) Output *1
4 03-21 Photo-coupler(DO2-DOG) Output *1
5 03-39 Relay (R3A-R3C) Output
6 Range 【0】: During Running 【1】: Fault Contact Output 【2】: Frequency Agree 【3】: Setting Frequency Agree (03-13±03-14) 【4】: Frequency Detection 1 (≧ 03-13 + 03-14) 【5】: Frequency Detection 2 (< 03-13) 【6】: Automatic Restart 【7】~【8】: Reserved 【9】: Baseblock 【10】~【11】:Reserved 【12】: Over-Torque Detection 【13】: Current Agree 【14】: Mechanical Brake Control (03-17~18) 【15】~【17】: Reserved 【18】: PLC Status 【19】: PLC Control 【20】: Zero Speed 【21】: Inverter Ready 【22】: Undervoltage Detection 【23】: Source of Operation Command 【24】:Source of Frequency Command 【25】: Low Torque Detection 【26】: Frequency Reference Missing 【27】: Timing Function Output 【28】~【31】: Reserved

Manual — Relay choices continuation and output functions0–5 — page 205

*1: The parameters are available when the I/O expansion card installed.

Default function

Related parameter

During

Running

Fault signal

R1B

R1C

R2A

R2C

R1A

R3A

R3C

Zero

Speed

Figure 4.4.22 Multi-function digital output and related parameters

Table 4.4.6 Description of multi-function digital output

Continues PDF204 shared range for03-11/12/20/21/39. Choices32–59 printed with39–41 and55–56 unprinted,not invented. *1 applies only with I/O expansion card installed. Figure4.4.22: R1A/R1B/R1C changeover fault signal03-11; R2A/R2C during-running03-12; R3A/R3C zero-speed03-39. Table4.4.6 function0 run ON;1 fault exceptCF00/CF01;2 frequency agree width03-14;3 band03-13±03-14;4 ON at output>=03-13+03-14;5 OFF at output>=03-13+03-14. Preserve inequality and mode columns.

Relay choices continuation and output functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Relay choices continuation and output functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 03-11/12/20/21/39 continuationfromPDF204

Relay choices continuation and output functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 0

Relay choices continuation and output functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 1

Relay choices continuation and output functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 2

Relay choices continuation and output functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 3

Relay choices continuation and output functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 4

Relay choices continuation and output functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 5

Relay choices continuation and output functions0–5 table1 — PDF page 205

Source row Source row label Source value or description
1 ⟦blank source cell⟧ 【32】: Communication Control Contacts 【33】: RTC Timer 1 【34】: RTC Timer 2 【35】: RTC Timer 3 【36】: RTC Timer 4 【37】: Detection Output of PID Feedback Loss 【38】: Brake Release 【42】: Over-High Pressure 【43】: Over-Low Pressure 【44】: Loss of Pressure Detection 【45】: PID Sleep 【46】: Over-High Flow 【47】: Over-Low Flow 【48】: Shortage of Low Suction 【49】: Communication Error 【50】: Frequency Detection 3 (≧ 03-44+03-45) 【51】: Frequency Detection 4 (< 03-44) 【52】: Frequency Detection 5 (≧ 03-46+03-47) 【53】: Frequency Detection 6 (< 03-46) 【54】: Turn on short-circuit braking 【57】: Low Current Detection 【58】: Frequency Deceleration Detection 【59】: Overheat Detection

Relay choices continuation and output functions0–5 table3 — PDF page 205

Source row Value Function name LCD display Description V/F SLV PM SLV
1 0 During Running Running ON: During running (Run Command is ON) O O O
2 1 Fault Contact Output Fault ON: Fault contact output (except CF00 and CF01 ) O O O
3 2 Frequency Agree Freq. Agree ON: Frequency agree (frequency agree width detection is set by 03-14 ) O O O
4 3 Setting Frequency Agree Setting Freq Agree ON: Output frequency = allowed frequency detection level (03-13) ± frequency bandwidth (03-14) O O O
5 4 Frequency Detection 1 Freq. Detect 1 ON: Output frequency ≧ 03-13 + 03-14 O O O
6 5 Frequency Detection 2 Freq. Detect 2 OFF: Output frequency ≧ 03-13 + 03-14 O O O

Manual — Output functions6–37 — page 206

Functions6–37 retained including reserved7–8,10–11,15–17,28–31 with dash modes. Mechanical brake14 ON release/OFF operation;20 zero speed ON output<Fmin;22 DC bus=<07-13;27 timer03-37/38,input03-00..05;33–36 RTC16-36 and respective source16-32/33/34/35 active together. All printed available functions O/O/O; no reserved capability inferred.

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 6

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 7~8

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 9

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 10~11

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 12

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 13

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 14

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 15~17

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 18

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 19

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 20

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 21

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 22

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 23

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 24

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 25

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 26

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 27

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 28~31

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 32

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 33

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 34

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 35

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 36

Output functions6–37. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 37

Output functions6–37 table1 — PDF page 206

Source row Value Function name LCD display Description V/F SLV PM SLV
1 6 Automatic Restart Auto Restart ON: the period of automatic restart O O O
2 7~8 Reserved Reserved Reserved - - -
3 9 Baseblock Baseblock ON: During baseblock O O O
4 10~11 Reserved Reserved Reserved - - -
5 12 Over-Torque Detection Over Torque ON: Over torque detection is ON O O O
6 13 Current Agree Current Agree ON: Output current > 03-15 O O O
7 14 Mechanical Brake Control (03-17~03-18) Mechanical Brake Control ON: Mechanical brake release frequency OFF: Mechanical brake operation frequency O O O
8 15~17 Reserved Reserved Reserved - - -
9 18 PLC Status PLC statement ON: when 00-02 is set to 3 (PLC operation command source) O O O
10 19 PLC Control Control From PLC ON: Control from PLC O O O
11 20 Zero Speed Zero Speed ON: Output frequency < Minimum output frequency (Fmin) O O O
12 21 Inverter Ready Ready ON: Inverter ready (after power on, no faults) O O O
13 22 Undervoltage Detection Low Volt Detected ON: DC bus voltage = < Low-voltage warning detection level (07-13) O O O
14 23 Source of Operation Command Run Cmd Status ON: Operation command from LED digital operator (local mode) O O O
15 24 Source of Frequency Command Freq Ref Status ON: Reference frequency from LED digital operator (local mode) O O O
16 25 Low Torque Detection Under Torque ON: Low-torque detection is ON O O O
17 26 Frequency Reference Missing Ref. Loss. ON: Reference frequency loss O O O
18 27 Timing Function Output Timer Output Set time function parameter to 03-37 and 03-38,and the time function input is set by parameter from 03-00 and 03-05 O O O
19 28~31 Reserved Reserved Reserved - - -
20 32 Communication Control Contacts Control From Comm ON: DO is set by communication control. O O O
21 33 RTC Timer 1 RTC Timer 1 ON: 16-36 (RTC Speed Selection) selects Timer 1 and 16-32 (Source of Timer 1) is active in the set time. O O O
22 34 RTC Timer 2 RTC Timer 2 ON: 16-36 (RTC Speed Selection) selects Timer 2 and 16-33 (Source of Timer 2) is active in the set time. O O O
23 35 RTC Timer 3 RTC Timer 3 ON: 16-36 (RTC Speed Selection) selects Timer 3 and 16-34 (Source of Timer 3) is active in the set time. O O O
24 36 RTC Timer 4 RTC Timer 4 ON: 16-36 (RTC Speed Selection) selects Timer 4 and 16-35 (Source of Timer 4) is active in the set time. O O O
25 37 Detection Output of PID Feedback Loss PID Fbk Loss ON: PID Feedback Loss O O O

Manual — Output functions38–59 and running/fault status — page 207

03-1X=0: During Running

03-1X=1: Fault contact output

Output is active during fault condition.

Note: Communication error (CF00, CF01) do not activate the fault contact.

03-1X=2: Frequency Agree

Output is active when the output frequency falls within the frequency reference minus the frequency

detection width (03-14).

38 brake release X/O/X.42–44 pressure O/X/X.45–53 O/O/O.54 short-circuit brake X/X/O.57–59 O/O/O. Running OFF only RUN off and stopped;ON if RUN on or output>0. Fault CF00/01 excluded. 50/52 wording uses output>level and separate hysteresis,where PDF205 uses>=level+width;both retained.

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 38

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 42

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 43

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 44

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 45

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 46

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 47

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 48

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 49

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 50

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 51

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 52

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 53

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 54

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 57

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 58

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 59

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context OFF

Output functions38–59 and running/fault status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context ON

Output functions38–59 and running/fault status table1 — PDF page 207

Source row Value Function name LCD display Description V/F SLV PM SLV
1 38 Brake Release Brake Relase ON: Brake Release X O X
2 42 Over-High Pressure High PSI ON:High PSI Warning/Fault O X X
3 43 Over-Low Pressure Low PSI ON: Low PSI Warning/Fault O X X
4 44 Loss of Pressure Detection Fb PSI ON: Fb PSI Fault O X X
5 45 PID Sleep PID Sleep ON: During PID Sleep O O O
6 46 Over-High Flow Over GPM ON: Over GPM Warning/Fault O O O
7 47 Over-Low Flow Low GPM ON: Low GPM Warning/Fault O O O
8 48 Shortage of Low Suction Low Suction ON: Low Suction Warning/Fault O O O
9 49 Communication Error RS-485 Err. ON: Communication Error Warning O O O
10 50 Frequency Detection 3 Freq. Detect 3 ON: output frequency > 03-44,Hysteresis range :03-45 O O O
11 51 Frequency Detection 4 Freq. Detect 4 OFF: output frequency > 03-44,Hysteresis range :03-45 O O O
12 52 Frequency Detection 5 Freq. Detect 5 ON: output frequency > 03-46,Hysteresis range :03-47 O O O
13 53 Frequency Detection 6 Freq. Detect 6 OFF: output frequency > 03-46,Hysteresis range :03-47 O O O
14 54 Turn on short-circuit braking SC Brk ON: Turn on short-circuit breaking X X O
15 57 Low Current Detection Low Current Detect ON: Output Current ≦ 03-48 Low current detection level O O O
16 58 Frequency Deceleration Detection Freq. Decel to ON: Output Frequency < Frequency Command – parameter 03-14 in deceleration O O O
17 59 OH Detection OH Detect ON: Heat Sink Fin Temperature >08-46, hysteresis Zone 08-47 O O O

Output functions38–59 and running/fault status table2 — PDF page 207

Source row Source row label Source value or description
1 OFF Run command is OFF and the inverter is stopped.
2 ON Run command is ON or output frequency is greater than 0.

Manual — Frequency/current/zero-speed output explanations — page 208

03-1X=3: Setting Frequency Agree

Output is active when the output frequency falls within the frequency detection width (03-14) of the set

frequency detection level (03-13).

03-1X=4: Frequency detected 1

Output is active when the output frequency rises above the frequency detection level (03-13) + frequency

detection width (o3-14) and deactivates when the output frequency falls below frequency detection level

(o3-13).

03-1X=5: Frequency detected 2

Output is active when the output frequency is below the frequency detection level (03-13) + frequency

detection width (03-14) and turns off when the output frequency falls below frequency detection level.

Refer to parameter group 03 for frequency detection function.

03-1X=6: Automatic restart.

Output is active during an auto-restart operation.

03-1X=9: Baseblock (B.B.)

Output is active when the inverter output is turned off during a Baseblock command.

03-1X=12: Over torque detected (Normally Open)

Output is active during an over torque detection see parameters 08-13 ~ 08-16.

03-1X=25: Low torque detected (Normally Open)

Output is active during low torque detection see parameters 08-17 ~ 08-20.

03-1X=13: Current Agree

When the output current is larger than that in 03-15 and its duration is higher than that in 03-16, this

function will be ON.

03-1X=18: PLC status (setting =18)

Output is active when operation command parameter (00-02) is set to 3: PLC Control.

03-1X=19: PLC control contact

Output is controlled by the PLC logic

03-1X=20: Zero-speed

Output is active during zero-speed

Function5 prose says active below03-13+03-14 and turns OFF when falling below03-13;contradicts complementary diagram on212. Zero-speed table Active output>=01-08 Fmin,Off output<=minimum overlaps equality and opposes PDF206 ON<Fmin/PDF209 diagram. Current agree requires current>03-15 longer than03-16. Preserve table and prose without choosing engineering behaviour.

Frequency/current/zero-speed output explanations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Frequency/current/zero-speed output explanations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context Active

Frequency/current/zero-speed output explanations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context Off

Frequency/current/zero-speed output explanations table1 — PDF page 208

Source row Source row label Source value or description
1 Active Output frequency >=minimum output frequency (01-08, Fmin)
2 Off Output frequency is <=the minimum output frequency

Manual — Zero-speed diagram and local/remote output status — page 209

Figure 4.4.23 Zero-speed operation

03-1X=21: Inverter Ready

Output is active when no faults are active and the inverter is ready for operation.

03-1X=22: Undervoltage Detection

Output is active when the DC bus voltage falls below the low voltage detection level (07-13).

03-1X=23: Source of operation command

Output is active in local operation command.

03-1X=24: Source of frequency command

Output is active in local frequency command.

03-1X=26: Frequency reference missing

Output is active when the frequency reference is lost. When parameter 11-41 is set to 0 the inverter will

decelerate to a stop. When parameter 11-41 is set to 1 operation will continue at the value of parameter

11-42 times the last know frequency reference.

03-1X=27: Time function output

Output is controlled by timer function see parameter 03-37 and 03-38.

Figure4.4.23 output decelerates; zero-speed signal OFF above01-08 Fmin,ON on crossing down through Fmin. Command local/remote tables cite DI function5;earlier digital input list says27. Run remote00-02=1or2 andSEQ LED ON,local0 andSEQ OFF;frequency remote00-05=1or2 andREF ON,local0 andREF OFF. Frequency loss11-41=0 decelerate stop;1 continue at11-42 times last reference. No automatic correction of function number.

Zero-speed diagram and local/remote output status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Zero-speed diagram and local/remote output status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context OFF

Zero-speed diagram and local/remote output status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context ON

Zero-speed diagram and local/remote output status table1 — PDF page 209

Source row Source row label Source value or description
1 OFF Remote mode: 00-02 = 1 or 2, or any one of the multi-function digital input terminals (S1 to S6) set to function 5 (LOCAL / REMOTE control) is OFF. SEQ LED of the keypad is ON.
2 ON Local mode: 00-02 = 0, or any one of the multi-function digital input terminals (S1 to S6) set to function 5 (LOCAL / REMOTE control) is active. SEQ LED of the keypad is OFF.

Zero-speed diagram and local/remote output status table2 — PDF page 209

Source row Source row label Source value or description
1 OFF Remote mode: 00-05 = 1 or 2, or any one of the multi-function digital input terminals (S1 to S6) set to function 5 (LOCAL / REMOTE control) is OFF. REF LED of the keypad is ON.
2 ON Local mode: 00-05 = 0, or any one of the multi-function digital input terminals (S1 to S6) set to function 5 (LOCAL / REMOTE control) is active. REF LED of the keypad is OFF.

Manual — Relay functions and frequency level parameters — page 210

03-1X=32: Communication control contacts

Output is active when communication control is active.

03-1X=37: Detection Output of PID Feedback Loss

When PID feedback loss occurs (refer to parameters setting 10-11~10-13), this function will be ON.

03-1X=38: Brake Release

When this function is ON, Break release is enabled. Refer to parameters descriptions of 03-41~03-42.

03-1X=42: Over-High Pressure

Refer to the setting of parameters 23-12~23-14 for the warning / fault.

03-1X=43: Over-Low Pressure

Refer to the setting of parameters 23-15~23-17 for the warning / fault.

03-1X=44: Loss of Pressure Detection

Refer to the setting of parameters 23-18~23-19 for the warning / fault.

03-1X=45: PID Sleep

PID sleep will be informed.

03-1X=46: Over-High Flow

Refer to the setting of parameters 23-48~23-50 for the warning / fault.

03-1X=47: Over-Low Flow

Refer to the setting of parameters 23-51~23-53 for the warning / fault.

03-1X=48: Shortage of Low Suction

Refer to the setting of parameters 23-54~23-58 for the warning / fault.

03-1X=49: RS-485 communication error

When RS-485 communication error, the output terminal is closed, please refer to the description of

09-06~09-07.

03-1X=54: Turn on short-circuit braking

Output terminal is closed when Turning on short-circuit braking

03-1X=57: Low Current Detection

When output current ≦ 03-48, the relay is active.

03-1X=58: Frequency Deceleration Detection

When output frequency < frequency command- 03-14 in deceleration, the relay is active.

03-1X=59: Over Temperature Detection

The Heat Sink Temperature > 08-46, the relay is active, the Magnetic Hysteresis Zone is set by 08-47.

03-44 Frequency Detection Level2 heading continues with first Range onPDF211. Frequency level03-13 0–599Hz,width03-14 .1–25.5Hz. Source references PID10-11..13,brake03-41..42,pressure23-12..14/15..17/18..19,flow23-48..50/51..53,low suction23-54..58,communication09-06..07. Low-current <=03-48 and overtemperature>08-46 with08-47 hysteresis retained.

Relay functions and frequency level parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Relay functions and frequency level parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-13

Relay functions and frequency level parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-14

Relay functions and frequency level parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-44

Relay functions and frequency level parameters table1 — PDF page 210

Source row Source row label Source value or description
1 03-13 Frequency Detection Level
2 Range 【0.0~599.0】 Hz
3 03-14 Frequency Detection Width
4 Range 【0.1~25.5】 Hz
5 03-44 Frequency Detection Level 2

Manual — Frequency levels continuation and agreement diagrams — page 211

Frequency Detection Level: set the multi-function output terminals R1A-R1C, R2A-R2C or R3A-R3C

(03-11, 03-12 or 03-39) to the output frequency detection signal. Set frequency and output frequency

detection 1 and 2.

The time charts for the Frequency Agree Detection operation are shown in the following Table 4.4.7.

Table 4.4.7 Frequency Detection Operation

First range0–599Hz belongs03-44 fromPDF210. Width2/3 .1–25.5Hz;levels3/4/5/6 0–599Hz. Table4.4.7 semantic columns Function/Diagram/Description;parser splits diagram into three physical columns,retained explicitly. Function2 ON during reference−03-14 band in FWD/REV. Function3 ON in03-13±03-14 band;function58 ON while decelerating outside reference−03-14 band. Diagram lines do not define new table columns or independent settings.

Frequency levels continuation and agreement diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Frequency levels continuation and agreement diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-44 continuationfromPDF210

Frequency levels continuation and agreement diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-45

Frequency levels continuation and agreement diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-46

Frequency levels continuation and agreement diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-47

Frequency levels continuation and agreement diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-50

Frequency levels continuation and agreement diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-51

Frequency levels continuation and agreement diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-52

Frequency levels continuation and agreement diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Frequency

agree

Frequency levels continuation and agreement diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Set frequency

Deceleration

Detection

Shared source cells (coordinates refer to this table):

Frequency levels continuation and agreement diagrams table1 — PDF page 211

Source row Source row label Source value or description
1 Range 【0.0~599.0】 Hz
2 03-45 Frequency Detection Width 2
3 Range 【0.1~25.5】 Hz
4 03-46 Frequency Detection Level 3
5 Range 【0.0~599.0】 Hz
6 03-47 Frequency Detection Width 3
7 Range 【0.1~25.5】 Hz
8 03-50 Frequency Detection Level 4
9 Range 【0.0~599.0】 Hz
10 03-51 Frequency Detection Level 5
11 Range 【0.0~599.0】 Hz
12 03-52 Frequency Detection Level 6
13 Range 【0.0~599.0】 Hz

Frequency levels continuation and agreement diagrams table2 — PDF page 211

Source row Function Diagram segment1 Diagram segment2 Diagram segment3 Description
1 Frequency agree ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Output is active when the output  frequency falls within the frequency reference minus the frequency detection width (03-14). Any of the digital outputs function  (03-11, 03-12 or 03-39) can be set to 2 (Frequency agree).
2 Set frequency agree ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ Output is active when the output  frequency falls within the frequency detection width (03-14) of the set frequency detection level (03-13). Any of the digital outputs function  (03-11, 03-12 or 03-39) can be set to 3 (Set frequency agree)
3 Frequency Deceleration Detection Output Frequency Frequency Decelerate Singal Freq Reference 03-14 FWD time REV 03-14 Freq Reference OFF ON OFF ON time ⟦null: no independent source value⟧ Signal of frequency deceleration  is ON when output frequency is out of the range between frequency reference minus frequency detection width (03-14) Any of the digital outputs function  (03-11, 03-12 or 03-39) can be set to 58 (Frequency Deceleration Detection)

Manual — Frequency detection1–4 diagrams — page 212

Detection1/function4 acc ON above03-13+03-14,decel OFF text at03-50(level4),diagram at03-13. Detection2/function5 complementary OFF onacc/ON ondecel;again text03-50 versusdiagram03-13. Detection3/function50 acc ON above03-44+03-45,decel OFF text03-51(level5),diagram03-44. Detection4/function51 complementary OFF onacc/ON ondecel;text03-51 versusdiagram03-44. Both FWD/REV directions plotted. No unified threshold substituted.

Frequency detection1–4 diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Frequency detection1–4 diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Output

frequency

detection 1

detection 2

detection 3

detection 4

Frequency detection1–4 diagrams table1 — PDF page 212

Source row Function Diagram Description
1 Output frequency detection 1 ⟦blank source cell⟧ Output frequency detection 1  signal is ON in acceleration when the output frequency rises above the frequency detection level (03-13) + frequency detection width (03-14). Output frequency detection 1  signal is OFF in deceleration when the output frequency declines to the frequency detection level 4 (03-50). Any of the digital outputs function  (03-11, 03-12 or 03-39) can be set to 4 (Output frequency detection 1).
2 Output frequency detection 2 ⟦blank source cell⟧ Output frequency detection 2  signal is OFF in acceleration when the output frequency rises above the frequency detection level (03-13) + frequency detection width (03-14). Output frequency detection 2  signal is ON in deceleration when the output frequency declines to the frequency detection level 4 (03-50). Any of the digital outputs function  (03-11, 03-12 or 03-39) can be set to 5 (Output frequency detection 2).
3 Output frequency detection 3 ⟦blank source cell⟧ Output frequency detection 3  signal is ON in acceleration when the output frequency rises above the frequency detection level 2 (03-44) + frequency detection width 2 (03-45). Output frequency detection 3  signal is OFF in deceleration when the output frequency declines to the frequency detection level 5 (03-51). Any of the digital outputs function  (03-11, 03-12 or 03-39) can be set to 50 (Output frequency detection 3).
4 Output frequency detection 4 ⟦blank source cell⟧ Output frequency detection 4  signal is OFF in acceleration when the output frequency rises above the frequency detection level 2 (03-44) + frequency detection width 2 (03-45). Output frequency detection 4  signal is ON in deceleration when the output frequency declines to the frequency detection level 5 (03-51). Any of the digital outputs function  (03-11, 03-12 or 03-39) can be set to 51 (Output frequency detection 4).

Manual — Frequency detection5–6 diagrams — page 213

Detection5/function52 acc ON above03-46+03-47,decel OFF text03-52(level6);positive diagram decel arrow says03-47,negative arrow03-46. Detection6/function53 complementary OFF onacc/ON ondecel;text03-52 versusdiagram03-46. Source labels and directional distinctions retained.

Frequency detection5–6 diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Frequency detection5–6 diagrams. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Output

frequency

detection 5

detection 6

Frequency detection5–6 diagrams table1 — PDF page 213

Source row Function Diagram Description
1 Output frequency detection 5 ⟦blank source cell⟧ Output frequency detection 5  signal is ON in acceleration when the output frequency rises above the frequency detection level 3 (03-46) + frequency detection width 3 (03-47). Output frequency detection 5  signal is OFF in deceleration when the output frequency declines to the frequency detection level 6 (03-52). Any of the digital outputs function  (03-11, 03-12 or 03-39) can be set to 52 (Output frequency detection 5).
2 Output frequency detection 6 ⟦blank source cell⟧ Output frequency detection 6  signal is OFF in acceleration when the output frequency rises above the frequency detection level 3 (03-46) + frequency detection width 3 (03-47). Output frequency detection 6  signal is ON in deceleration when the output frequency declines to the frequency detection level 6 (03-52). Any of the digital outputs function  (03-11, 03-12 or 03-39) can be set to 53 (Output frequency detection 6).

Manual — Current agreement and low-current parameters — page 214

Note: The Maximum Value of 03-53 will be limited by Setting Value of 03-15

03-11=13: Relay is active when output current is larger than that in 03-15.

03-15: The suggested setting value is 0.1~ the motor rated current.

03-16: The unit of the setting value (0.1~10.0) is second. In addition, when the Output Current is ≤

03-53, the delay time of relay signal from ON to OFF is 100ms (constant).

Timing Diagram:

03-11 =57: Relay is active when output current is lower than that in 03-48.

03-48: Setting value: 0.1~999.9; when it is 0.0, function of low current detection is disabled.

03-49: Setting value: 0.00~655.35 (unit: sec); when the current is continuously lower than the setted

value of parameter 03-48 within the setted time of parameter 03-49, the relay is enabled. The delay

time of relay signal from ON to OFF is 100ms (constant).

03-15 .1–999.9A;03-16 .1–10s;03-53 0–999.9A,max limited03-15. Current-agree relay ON after above03-15 for03-16,OFF after<=03-53 for fixed100ms. Diagram axis100% despite tabular amperes,no conversion inferred. Low-current03-48 .1–999.9A;prose0disables.03-49 table0–655.34s versusprose0–655.35s. Low-current prose strictly below48 whereasPDF207/210<=48. Relay ON onlycontinuouslowfor49;OFFdelay100ms.

Current agreement and low-current parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Current agreement and low-current parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-15

Current agreement and low-current parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-16

Current agreement and low-current parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-53

Current agreement and low-current parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-48

Current agreement and low-current parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-49

Current agreement and low-current parameters table1 — PDF page 214

Source row Source row label Source value or description
1 03-15 Current Agree Level
2 Range 【0.1~999.9】 A
3 03-16 Delay Time of Current Agree Detection
4 Range 【0.1~10.0】 Sec
5 03-53 Current Agree Level 2
6 Range 【0.0~999.9】A

Current agreement and low-current parameters table2 — PDF page 214

Source row Source row label Source value or description
1 03-48 Low Current Detection Level
2 Range 【0.1~999.9】 A
3 03-49 Low current Detection Delay Time
4 Range 【0.00~655.34】 Sec

Manual — Low-current timing and brake frequency parameters — page 215

Timing Diagram:

Constant

100msec

Relay

ON

I Load Current

100%

T

Operation

Command

The continuous time set

by parameter 03-49 is not

reached, the relay is

disabled.

When 03-11=14,

Relay output starts at acceleration if the output frequency reaches the mechanical brake release level

(03-17).

Relay output stops at deceleration if the output frequency reaches the mechanical brake operation level

(03-18).

When 03-17≤03-18, timing diagram is as follows:

03-11=14

Hz

OFF

RUN

STOP

Low-current diagram: run command ON;after03-49 continuousbelow03-48 relay ON;current rises above threshold relay OFF after100ms;later below-threshold interval shorter03-49 doesnotreactivate. Mechanical03-17 release/03-18 operation both0–599Hz;03-11=14. Prose ON accelerating at17,OFF decelerating at18. Diagram17<=18: ON at lower17,OFF at higher18;preserve separate next-page case.

Low-current timing and brake frequency parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Low-current timing and brake frequency parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-17

Low-current timing and brake frequency parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-18

Low-current timing and brake frequency parameters table2 — PDF page 215

Source row Source row label Source value or description
1 03-17 Setting of Mechanical Brake Release Level
2 Range 0.00~599.00 Hz
3 03-18 Setting of Mechanical Brake Operation Level
4 Range 0.00~599.00 Hz

Manual — Mechanical brake timing and output polarity — page 216

When 03-17≥03-18, timing diagram is as follows:

Operation

03-11=14

Hz

T

ON

OFF

RUN

STOP

*1: The parameters are available when the I/O expansion card installed.

Parameter 03-19 selects the digital output type between a normally open and a normally closed contact.

Each bit of 03-19 presents an output:

03-19= 0 0 0 0 0: normally open contact

R3 R2 R1 1: normally close contact

Example: R1 normally closed and R2 normally open contact set 03-19=x001b.

03-27=0: When the run command is removed the UP/DOWN frequency reference before deceleration is

stored. The next time the run command is applied the output frequency will ramp up to the previously stored

frequency reference.

03-27=1: When the run command is removed the UP/DOWN frequency reference command is cleared (set

to 0). The next time the run command is applied the output frequency will start at 0.

03-27=2: UP/DOWN command is active when run command is not active.

03-27=3: Keep the state of frequency command not to be cleared. When Run Command re-sends, press

UP/DOWN key before the run frequency reaches the frequency command, press UP/ DOWN key, then:

of 03-40.

Diagram17>=18 visibly aligns ON with lower03-18 and OFF with03-18,unlike preceding prose ON17.03-19 table R1xxx0/xxx1,R2xx0/xx1,R3x0xx/x1xx,R4alsox0xx/x1xx. Bit diagram0000 labels rightmostR1,nextR2,nextR3,leftmostunlabelled. Examplex001 R1NC/R2NO. R4 and03-29 DO2 require expansioncard.03-27 options0retainstopref,1clear0,2allowadjuststopped,3refreshonaccel;03-40=0 usescurrentrunfreq,nonzero usesrunfreqpluswidth.

Mechanical brake timing and output polarity. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Mechanical brake timing and output polarity. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03- 19

Mechanical brake timing and output polarity. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03- 29

Mechanical brake timing and output polarity. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03- 27

Mechanical brake timing and output polarity table2 — PDF page 216

Source row Source row label Source value or description
1 03- 19 Relay (R1A-R3C) Type
2 Range 【xxx0b】: R1A normally open 【xxx1b】: R1A normally close 【xx0xb】: R2A normally open 【xx1xb】: R2A normally close 【x0xxb】: R3A normally open 【x1xxb】: R3A normally close 【x0xxb】: R4A normally open 【x1xxb】: R4A normally close *1
3 03- 29 Photo-coupler Output Selection (DO2-DOG) *1
4 Range 【xx0xb】: Photo-coupler 2 A Contact 【xx1xb】: Photo-coupler 2 B Contact

Mechanical brake timing and output polarity table3 — PDF page 216

Source row Source row label Source value or description
1 03- 27 UP/DOWN Frequency Hold/ Adjust Selection
2 Range 【0】: Keep UP/DOWN frequency when stopping. 【1】: Clear UP/DOWN frequency when stopping. 【2】: Allow frequency UP/DOWN when stopping. 【3】: Refresh frequency at acceleration.

Manual — Pulse input type and PWM scaling — page 217

*1: It is new added in inverter software V1.4.

There are two modes in pulse input selection:

03-30=0: Common Pulse Input

Pulse Input (PI) = the selected frequency divided by pulse input scaling (set by 03-31), corresponding to

the maximum output frequency of motor 1 (01-02).

Note: Monitor parameter 12-79 (pulse input percentage) displays the proportional relationship between

input signal and 03-31 (pulse input scaling).

03-30=1: PWM (Pulse Width Modulation)

It is required to input the correct frequency.

PWM= posedge pulse time divided by previous pulse time period, corresponding to the maximum output

frequency of motor 1 (01-02).

the positive edge of input signal and time period.

Note: Tolerance range of pulse time period in PWM modes is ±12.5%. If it is over than the range, it is

inactive.

Diagram of pulse input selection:

03-30 newV1.4. Mode0 normal: frequency=1/T;command=(frequency/scaling03-31)×100%(01-02). Mode1 PWM: command=(T1/T)×100%(01-02),T1 high pulse duration,T wholeperiod. Monitor12-79 percentage. Period tolerance±12.5%;outside range inactive. Formulae source claims,not independentlyvalidated control configuration.

Pulse input type and PWM scaling. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Pulse input type and PWM scaling. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03- 30

Pulse input type and PWM scaling table1 — PDF page 217

Source row Source row label Source value or description
1 03- 30 Pulse Input Selection *1
2 Range 【0】: Common Pulse Input 【1】: PWM (Pulse Width Modulation)

Manual — Pulse input scaling and PID feedback — page 218

Pulse input scaling, 100% = Maximum pulse frequency.

Target value (03-03) in % = Pulse input frequency scaled to 100% based on maximum pulse frequency

(03-31) times the gain (03-32) + bias (03-33).

Figure 4.4.24 Pulse input adjustment

Set Pulse Input Setup as Flow Meters Input

Set parameter 23-45 (Given Modes of Flow Meters Feedback) to 2 (Pulse Input) to use the pulse input

terminal PI as the flow meters input. Refer to the description of parameter group 23 for details. Next set the

pulse input scaling (03-31), enter the pulse input frequency to match the maximum output frequency.

Adjust the pulse input filter time (03-34) in case interference or noise is encountered.

03-31 50–32000Hz;100%=maximum pulsefrequency.03-32 gain0–1000%,03-33 bias−100..100%,03-34filter0–2s. Figure4.4.24 Pulse→PI→1/(1+sT),T03-34→1/K,K03-31→gain03-32/bias03-33→23-45=2→PIDfeedback. Prose target03-03 conflicts earlierS4assignment;retain. Flowmeter input23-45=2,scale03-31 to maximumoutputfrequency,filternoise03-34.

Pulse input scaling and PID feedback. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Pulse input scaling and PID feedback. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-31

Pulse input scaling and PID feedback. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03- 32

Pulse input scaling and PID feedback. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-33

Pulse input scaling and PID feedback. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-34

Pulse input scaling and PID feedback table1 — PDF page 218

Source row Source row label Source value or description
1 03-31 Pulse Input Scaling
2 Range 【50~32000】Hz

Pulse input scaling and PID feedback table2 — PDF page 218

Source row Source row label Source value or description
1 03- 32 Pulse Input Gain
2 Range 【0.0~1000.0】%

Pulse input scaling and PID feedback table3 — PDF page 218

Source row Source row label Source value or description
1 03-33 Pulse Input Bias
2 Range 【-100.0~100.0】%

Pulse input scaling and PID feedback table4 — PDF page 218

Source row Source row label Source value or description
1 03-34 Pulse Input Filter Time
2 Range 【0.00~2.00】Sec

Manual — Delay timer and UP/DOWN step width — page 219

Enable the timer function be setting one of multi-function input parameters 03-00~03-05 (S1 to S6) to 35

(timer function input) and one of multi-function output parameters 03-11, 03-12, 03-39 (R1A-R1C to R3A-

R3C) to 27 (timer function output).

The timer function can be used to implement a timer relay. Use timing parameter 03-37 and 03-38 to set

the timer ON / OFF delay.

Timer output is turned ON when the multi-function timer input is ON for the time specified in parameter

03-37.

Timer output is turned OFF after the multi-function timer input is OFF for the time specified in parameter

03-38.

Timing example:

ON

Timer input function

Timer output function

*1: It is new added in inverter software V1.4.

For example: Set terminal S1: 03- 00=【8】(Up Frequency Increasing Command), S2:03- 01=【9】(DOWN

Frequency Decreasing Command) and 03- 40=【△】Hz.

Mode1: When 03-40 is set to 0Hz, it will maintain the original up/down function, shown as Fig. 4.4.20.

Mode2: When 03-40 is not set to 0Hz and terminal conduction time is lower than 2 sec, conducting one

time leading to frequency variation △Hz (setting frequency by 03-40)。

DIfunction35 on03-00..05 and DO27 on03-11/12/39;03-37 ONdelay and03-38 OFFdelay each0–6000s. ContinuousON37 activates;continuousOFF38 deactivates;shortinitialpulses cannotactivate,shortOFFpulses afteractivation resetOFFdelay.03-40 width0–5Hz,newV1.4. ExampleS1function8 UP/S2function9 DOWN. Width0originalbehaviour;nonzero conduct<2s one ΔHz step. Exact2s boundary unspecified;PDF220 says>2s forramp.

Delay timer and UP/DOWN step width. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Delay timer and UP/DOWN step width. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03- 37

Delay timer and UP/DOWN step width. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-38

Delay timer and UP/DOWN step width. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03- 40

Delay timer and UP/DOWN step width table1 — PDF page 219

Source row Source row label Source value or description
1 03- 37 Timer ON Delay (DI/DO)
2 Range 【0.0~6000.0】Sec
3 03-38 Timer OFF Delay (DI/DO)
4 Range 【0.0~6000.0】Sec

Delay timer and UP/DOWN step width table3 — PDF page 219

Source row Source row label Source value or description
1 03- 40 Up/down Frequency Width Setting *1
2 Range 【0.00~5.00】Hz

Manual — UP/DOWN duration and ramp examples — page 220

Terminal S1

Terminal S2

ON

Hz

T

△Hz

Real Output

Frequency

Lower limit

of frequency

reference

Upper limit

Mode3: When 03-40 is not set to 0Hz and terminal conduction time is larger than 2 sec, frequency

variation depends on acceleration/ deceleration.

2Sec

OFF

Setting Frequency

(Hz)

△ H1

t1

△ H2

t2

Notes:

△H1: setting frequency increment in acceleration, t1: terminal conduction time in acceleration,

△H2: setting frequency increment in deceleration, t2: terminal conduction time in deceleration.

(t1)

Time

Conduction

Terminal

on

Accelerati

Limit

Upper

H

(t2)

Decelerati

Topgraph threeS1pulses eachupΔHz toUpperLimit,threeS2pulses eachdownΔHz toLowerLimit. Mode3 nonzero width and conduct>2s: first2s initialstep,then ramp duringt1/t2. Printed ΔH1=(UpperLimitFrequency/AccelerationTime2)×t1;ΔH2=(UpperLimitFrequency/DecelerationTime2)×t2. t1/t2 terminalconduction times afterinitial2s in shown diagram;do not invent numericalramp.

Manual — Brake release and UP/DOWN ramp selection — page 221

*1: It is new added in inverter software V1.4.

Function of Brake Release:

It requires function of frquecny agree to use, shown as the following figure.

When output frequency is larger than frequency detection level (03-13) and output torque is larger than

torque detection level (03-41) during Inverter operation, it will delay braking action delay time (03-42) and

then release brake.

It is also recommended to be with the use of start and stop frequency locked function (11-43~11-46),

shown as the following figure:

Calculate the acceleration/ deceleration time of frequency command by switch the function of UP/DOWN

from parameter 03-43. Ex: ᇞH1 (set frequency increment at acceleration) and ᇞH2 (set frequency

increment at deceleration).

03-41 torque0–150%;03-42 delay0–65s,newV1.4. Function38:freq>03-13 ANDtorque>03-41 then delay03-42 activates;freq<13 ORtorque<41 then delay03-42 deactivates. Firstdiagram DO03-11/12/28;second03-11/12/39. Recommendedstartlock11-43frequency/44time andstoplock11-45frequency/46time remain sourceclaims.03-43=0 Time1,=1 Time2 forUP/DOWN commandramp.

Brake release and UP/DOWN ramp selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Brake release and UP/DOWN ramp selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03- 41

Brake release and UP/DOWN ramp selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-42

Brake release and UP/DOWN ramp selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 03-43

Brake release and UP/DOWN ramp selection table1 — PDF page 221

Source row Source row label Source value or description
1 03- 41 Torque Detection Level *1
2 Range 【0~150】%
3 03-42 Delay Time of Braking Action *1
4 Range 【0.00~65.00】Sec

Brake release and UP/DOWN ramp selection table2 — PDF page 221

Source row Source row label Source value or description
1 03-43 UP/DOWN Acceleration/ Deceleration Selection
2 Range 【0】: Acceleration/Deceleration Time 1 【1】: Acceleration/Deceleration Time 2

Manual — UP/DOWN example1 ramp timing — page 222

Ex 1:

 03-43=1(Acceleration/ Deceleration Time 2)

 Acceleration/ Deceleration Time 1 > Acceleration/ Deceleration Time 2

Terminal S1

Terminal S2

Lasting ON

2Sec

OFF

t1

t4

△ H2

△Hz

△ H4

UP/DOWN

Command Slope

Frequency

Output

Upper Limit of

Reference

Lower Limit of

△ H3

△ H1

t3

t2

Notes:

ᇞH1: Frequency augmentation setting in acceleration, t1: Terminal conduction time in acceleration

ᇞH2: Frequency augmentation setting in deceleration, t2: Terminal conduction time in deceleration

t3: Acceleration time in output

ᇞH3: Output frequency augmentation in acceleration, t4: Deceleration time in output

ᇞH4: Output frequency augmentation in deceleration

Time

on

Decelerati

limit

Upper

Accelerati

t

H

Time1

Limit

Example1 03-43=1,Time1>Time2. Command rampsfasterthanactualoutput:initial2s step,commandaccelt1 versusoutputt3;commanddecelt2 versusoutputt4. Formulae ΔH1=Upper/AccTime2×t1;ΔH2=Upper/DecTime2×t2;ΔH3=Upper/AccTime1×t3;ΔH4=Upper/DecTime1×t4. Firstpaircommand increments,secondpairoutputincrements. Originalgeometry andlabels retained.

Manual — UP/DOWN example2 ramp timing — page 223

Ex2:

 03-43=1(Acceleration/ Deceleration Time 2)

 Acceleration/ Deceleration Time 1 < Acceleration/ Deceleration Time 2

Terminal S1

Terminal S2

Lasting ON

2Sec

OFF

t1

t2

△ H2

△Hz

△H4

UP/DOWN

Command Slope

Frequency

Upper Limit

reference

Lower Limit

△ H3

△ H1

t3

t4

Output

Notes:

ᇞH1: Frequency augmentation setting in acceleration t1: Terminal conduction time in acceleration

ᇞH2: Frequency augmentation setting in deceleration t2: Terminal conduction time in deceleration

t3: Acceleration time in output

ᇞH3: Output frequency augmentation in acceleration, t4: Deceleration time in output

ᇞH4: Output frequency augmentation in deceleration

Time

on

Decelerati

limit

Upper

Accelerati

t

H

Time1

Limit

Example2 03-43=1,Time1<Time2. Output initialstep rampsduringt3/t4 then holdsuntil2s and followscommandramps t1/t2. Samefourprintedformulae asPDF222. DiagramΔH3 arrow spansfrominitialplateau toupperlimit whereas t3marksinitialstep duration;source geometry notreconciled into alternateformula. ΔH4 top stepdrop andt4align. No inferred configuration.

Manual — Analog input parameter ranges — page 224

Group 04 External Analog Input and Output Parameters

04-00 pairs:0 AI1/AI2 both0–10V;1 AI1 0–10V/AI2 4–20mA;2/3Reserved;4 AI1 4–20mA/AI2 0–10V;5 both4–20mA.04-09 expansionAI3:0 0–10V,1−10..10V,2 4–20mA.04-05AI2 and04-10AI3 share function0–17Range. AI filters0–2s,gains0–1000%,bias−100..100%.04-22gain headingcontinuesPDF225. Function15Reserved hereversusTorqueLimitwithX/X/X on228. DCBrakingCurrentasterisk hasno matchingstandalone explanationonpage.

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 00

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 09

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 01

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 02

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 03

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 04

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 05

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 10

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Shared04-05AI2/04-10AI3functionrange

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 06

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 07

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 08

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 21

Analog input parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 22

Analog input parameter ranges table1 — PDF page 224

Source row Source row label Source value or description
1 04- 00 AI Input Signal Type
2 Range 【0】: AI1 0~10V AI2 0~10V 【1】: AI1 0~10V AI2 4~20mA 【2】: Reserved 【3】: Reserved 【4】: AI1 4~20mA AI2 0~10V 【5】: AI1 4~20mA AI2 4~20mA
3 04- 09 AI Input Signal Type on I/O expansion card *1
4 Range 【0】: AI3 0~10V 【1】: AI3 -10~10V 【2】: AI3 4~20mA
5 04- 01 AI1 Signal Scanning and Filtering Time
6 Range 【0.00~2.00】Sec
7 04- 02 AI1 Gain
8 Range 【0.0~1000.0】%
9 04- 03 AI1 Bias
10 Range 【-100~100.0】%
11 04- 04 AI negative Characteristics
12 Range 【0】:Disable 【1】:Enable
13 04- 05 AI2 Function Setting
14 04- 10 AI3 Function Setting *1
15 Range 【0】: Auxiliary Frequency 【1】: Frequency Reference Gain 【2】: Frequency Reference Bias 【3】: Output Voltage Bias 【4】: Coefficient of Acceleration and Deceleration Reduction 【5】: DC Braking Current* 【6】: Over-Torque Detection Level 【7】: Stall Prevention Level During Running 【8】: Frequency Lower Limit 【9】: Jump Frequency 4 【10】: Added to AI1 【11】: Positive Torque Limit 【12】: Negative Torque Limit 【13】: Regenerative Torque Limit 【14】: Positive / Negative Torque Limit 【15】: Reserved 【16】: Torque Compensation 【17】: Reserved
16 04- 06 AI2 Signal Scanning and Filtering Time
17 Range 【0.00~2.00】Sec
18 04- 07 AI2 Gain
19 Range 【0.0~1000.0】%
20 04- 08 AI2 Bias
21 Range 【-100.0~100.0】%
22 04- 21 AI3 Signal Scanning and Filtering Time *1
23 Range 【0.00~2.00】Sec
24 04- 22 AI3 Gain *1

Manual — Analog ranges continuation and hardware signal selection — page 225

*1: The parameters are available when the I/O expansion card installed.

For Standard H & C type:

Refer to the followings for the details of parameter 04-00 (AI input signal type)

AI2=0~10V, Set 04-00=0, tune SW2 on the control board ro V.

AI2=0~20mA, Set 04-00=0, tune SW2 on the control board to I.

AI2=4~20mA, Set 04-00=1, tune SW2 on the control board to I.

AI2=2~10V, Set 04-00=1, tune SW2 on the control board to V.

For Enhanced E & G type:

AI1=0~10V, Set 04-00=0 or 1, tune SW3 on the control board to V.

AI1=4~20mA, Set 04-00=4 or 5, tune SW3 on the control board to I.

AI2=0~10V, Set 04-00=0 or 2 or 4, tune SW4 on the control board to V

AI2=4~20mA, Set 04-00=1 or 3 or 5, tune SW4 on the control board to I.

For I/O expansion card:

Refer to the followings for the details of parameter 04-09 (AI input signal type)

AI3=0~10V, Set 04-09=0, tune SW7 on the I/O expansion card to V.

AI3=-10~10V, Set 04-09=1, tune SW7 on the I/O expansion card to V.

AI3=4~20mA, Set 04-09=2, tune SW7 on the I/O expansion card to I.

(1) Analog Input Level Adjustment AI1, AI2, AI3 (04-02, 04-03, 04-04, 04-07, 04-08, 04-22, 04-23)

Each analog input AI1and AI2 has a separate gain and bias parameter associated with it.

Analog input signal AI1 can be adjusted with parameter 04-02 and 04-03; Analog input signal AI2 can

be adjusted with parameter 04-07 and 04-08, Analog input signal AI3 can be adjusted with parameter

04-22 and 04-23. Refer to Fig.4.4.25.

Figure 4.4.25 Analog inputs and related parameters (For Standard H & C type)

Gain setting: Sets the level in % that corresponds to a 10V or 20mA signal at the analog input.

Bias setting: Sets the level in % that corresponds to a 0V or 4mA signal at the analog input.

Use both gain and bias setting to scale the input signal.

FirstRange0–1000% belongs04-22 from224.04-23bias−100..100%;*1expansioncardonly. StandardH/C:SW2V for0–10V04-00=0 or2–10V=1;SW2I for0–20mA=0 or4–20mA=1. EnhancedE/G:AI1 SW3V04-00=0or1,I=4or5;AI2 SW4V=0or2or4,I=1or3or5. Values2/3 conflictReservedin224;retainhardwarecontexts. AI3 SW7V04-09=0/1,I=2. Fig4.4.25 StandardH/C AI1gain04-02/bias03;AI2type00,function05,gain07,bias08;commonGND. Gain endpoint10V/20mA,bias0V/4mA.

Analog ranges continuation and hardware signal selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Analog ranges continuation and hardware signal selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04-22 continuationfromPDF224

Analog ranges continuation and hardware signal selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Source row context 04- 23

Analog ranges continuation and hardware signal selection table1 — PDF page 225

Source row Source row label Source value or description
1 Range 【0.0~1000.0】%
2 04- 23 AI3 Bias *1
3 Range 【-100.0~100.0】%

Manual — Analog gain/bias and negative characteristics — page 226

Gain: 200%

Gain: 100%

200%

100%

10V

(20mA)

0V

(4mA)

-200%

-10V

Terminal

AI1,AI2

analog input

Frequency

Reference

+100%

-

Bias = positive

Bias = 0%

Bias = Negative

(a)

Gain

(b)

Bias

Figure 4.4.26 Gain and bias operations (for frequency reference signal)

04-04 (AI negative characteristics)

Through the following figure negative characteristics diagram find out the AI Input 10V, -10V, or 20mA

input relative frequency reference to be used for the ratio of maximum output frequency (set the maximum

output frequency 01-02 to 100%), the ratio will be presented in reverse.

0% 0V

Figure4.4.26 gain100% maps0V(4mA)→0%,10V(20mA)→100%;gain200% dashed to200%but solidclamped100%. Biaspositive/zero/negative parallelshift;negative-axis100%label lacksminus in source. 04-04negativecharacteristic triangulargraph:100% at0V(4mA),0% at−10V and+10V(20mA);prosesays0/20mA whilegraph4/20mA. Keeprawlabelsnot correctedmapping.

Manual — Analog filtering and functions0–5 — page 227

(1) AI1 signal filtering time (04-01)

(2) AI2 signal filtering time (04-06)

(3) AI3 signal filtering time (04-21)

All analog inputs (AI1, AI2, AI3) have a 1st order programmable input filter that can be adjusted when noise

is present on each of the incoming analog signal to prevent erratic drive control.

The filter time constant (range: 0.00 to 2.00 seconds) is defined as the time that the input step signal

reaches 63% of its final value.

Note: Increasing the filter time causes the drive operation to become more stable but less responsive to

change to the analog input.

Figure 4.4.27 Filter time constant

(4) AI2 function setting (04-05/04-10)

AI2 is multi-function analog input terminal function selection. Refer to Table 4.4.8 for function overview

Table 4.4.8 Multi-function analog input list (04-05/04-10 setting)

AI1/2/3 firstorder filters04-01/06/21 time0–2s is63%stepresponse;largertime morestablelessresponsive. Fig4.4.27 unfiltered100%step,filtered63%atoneconstant→100%. Function0aux100%=Fmax01-02.1 gainproduct04-02×FGAIN.2 biastableproduct04-03×FBIAS differsPDF229sum.3voltagebiasV/F+VBIAS O/X/O;others0–5O/O/O.5 DCcurrent0–100%,100%=inverterratedcurrent and07-07disabled.

Analog filtering and functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Analog filtering and functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 0

Analog filtering and functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 1

Analog filtering and functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 2

Analog filtering and functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 3

Analog filtering and functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 4

Analog filtering and functions0–5. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 5

Analog filtering and functions0–5 table1 — PDF page 227

Source row Value Function name LCD display Description V/F SLV PM SLV
1 0 Auxiliary Frequency AUX.Freq Ref Max Output Frequency (01-02, Fmax) =100% O O O
2 1 Frequency Reference Gain (FGAIN) Freq Ref Gain Aggregated gain= AI1 = 04-02 * FGAIN O O O
3 2 Frequency Reference Bias (FBIAS) Freq Ref Bias Aggregated bias= AI1 = 04-03 * FBIAS O O O
4 3 Output Voltage Bias (VBIAS) Output Volt Bias Aggregate output voltage =V/F curve voltage + VBIAS O X O
5 4 Coefficient of Acceleration and Deceleration Reduction (K) Tacc/Tdec Scaling Actual acceleration and deceleration time = accel. and decal. time / K O O O
6 5 DC Braking Current DC Inj Current Adjust the DC braking current (0 ~ 100%) based on analog input. When the inverter rated current = 100%, DC braking current 07-07 is disabled. O O O

Manual — Analog functions6–17 and gain — page 228

Note: When the setting of AI2 and AI3 are the same, use AI2 signal only.

04-05=0: Auxiliary frequency

When parameter 00-05 = 1 (main frequency from external control) the auxiliary speed reference frequency

can be activated via the multi-speed input commands (see table 4.4.5). The auxiliary frequency command

can be set via AI2/AI3. The maximum output frequency is set by 01-02, Fmax =100%.

04-05/04-10=1: Frequency Reference Gain (FGAIN)

Multi-function analog input AI2/AI3 can be used to adjust the frequency reference gain of analog input AI1.

The total frequency reference gain of terminal AI1 is the internal gain set by parameter 04-02 times FGAIN.

The maximum frequency reference for AI1 is 100%.

Figure 4.4.28 Frequency gain adjustment

Modes11–14 X/O/O,15TorqueLimitX/X/X,16compensationX/O/X,17ReservedO/O/O retained.7stall30–200%ratedcurrent O/X/O;8lowerlimitgreaterof00-13andanalog,100%=Fmax.6overtorque replaces08-15. SameAI2/AI3functions useAI2only. Aux04-05=0 with00-05=1 usesmultispeed;Fmax01-02. Gain04-02×FGAIN maxreference100%;Fig4.4.28 AI2 0V(4mA)→0%,10V(20mA)→100%.

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 6

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 7

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 8

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 9

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 10

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 11

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 12

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 13

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 14

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 15

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 16

Analog functions6–17 and gain. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 17

Analog functions6–17 and gain table1 — PDF page 228

Source row Value Function name LCD display Description V/F SLV PM SLV
1 6 Over-Torque Detection Level Over Tq Level Change over-torque detection level based on over-torque detection level, at this time, 08-15 is disabled. O O O
2 7 Stall Prevention Level During Running Run Stall Level Adjust the action level (30% ~ 200%) of stall prevention in operation based on analog input. The inverter rated current =100% O X O
3 8 Frequency Lower Limit Ref. Low Bound Adjust the lower limit (0 ~ 100%) of frequency command based on analog input, the maximum output = 100%. The lower limit of frequency command is the greater one of the actual frequency command’s lower limit 00-13 or the multi-function analog input. O O O
4 9 Jump Frequency 4 Jump Freq 4 Jump frequency 4. 100% = maximum output frequency O O O
5 10 Added to AI1 Add to AI1 Added to AI1. 100% = maximum output frequency O O O
6 11 Positive Torque Limit Positive Tq Limit 100% = Motor’s rated torque X O O
7 12 Negative Torque Limit Negative Tq Limit 100% = Motor’s rated torque X O O
8 13 Regenerative Torque Limit Regen. Tq Limit 100% = Motor’s rated torque X O O
9 14 Positive / Negative Torque Limit +/- Tq Limit 100% = Motor’s rated torque X O O
10 15 Torque Limit Tq Limit 100% = Motor’s rated torque X X X
11 16 Torque Compensation Tq Compensation 100% = Motor’s rated torque X O X
12 17 Reserved No Function Reserved O O O

Manual — Analog gain/bias examples and voltage bias — page 229

Example:

When the internal gain of AI1 (04-02) is set to 100% and AI2 to 5V (for example FGAIN = 50%), the

reference frequency of terminal AI1 will be 50%, as shown in Fig. 4.4.29.

Figure 4.4.29 Frequency reference gain adjustment (example)

04-05/04-10=2: Frequency Reference bias (FBIAS)

Multi-function analog input terminal AI2 can be used to adjust the frequency reference bias of AI1.

The total frequency reference bias of terminal AI1 is the sum of internal bias set by parameter 04-03 and

FBIAS. The maximum frequency reference for AI1 is 100%.

Figure 4.4.30 Bias adjustment

Terminal AI1 input is 0V, 04-02 = 100% (AI1 gain), 04-03 = 0% (AI1 bias) and terminal AI2 input is 3V. The

reference frequency will be 30% as shown in Fig.4.4.31.

Figure 4.4.31 Frequency Reference bias adjustment (example)

04-05/04-10=3: Output Voltage Bias (VBIAS)

Multi-function analog input AI2/AI3 can be used to adjust the output voltage. The total output voltage of

inverter is the sum of output voltage based on the selected V/F curve (01-00=F) and VBIAS.

The maximum output voltage will be limited by 01-03, Vmax = 100%

Fig4.4.29 sourceexample04-02=100%,AI2=5V FGAIN50%,AI1at10V gives50%reference;original100%slopeand50%scaledslopeshown. Biasprose total=04-03+FBIAS contradictsPDF227product. Fig4.4.30 0V(4mA)0%,10V(20mA)100%,−100%axisunconnectedline. Fig4.4.31 exampleAI1=0V,gain100%,bias0%,AI2=3V→30%reference;30%intercept and100%upperlimit. OutputVBIAS for04-05/10=3:totalV/Fcurve01-00=F plusVBIAS,limited01-03 Vmax100%;furtherdetailcontinuesnextpart230.

Manual — Analog voltage bias,ramp coefficient and DC current — page 230

Figure 4.4.32 Bias adjustment

04-05/04-10=4: Acceleration and deceleration coefficient (K)

Multi-function analog input AI2/AI3 can be used to adjust the acceleration and deceleration time coefficient.

The actual acceleration and deceleration time is calculated as follows:

Acceleration / Deceleration time (00-14 ~ 00-17, 00-21~ 00-24)

Actual accel /decel time =

K

Acceleration/ Deceleration time setting is 100% (00-14~00-17, 00-21~00-24).

Figure 4.4.33 Acceleration / deceleration time reduction coefficient

04-05/04-10=5: DC braking current

Multi-function analog input AI2/AI3 can be used to adjust the DC Injection braking current.

DC braking current parameter 07-07 setting should be set to 0% to use this function.

The inverter rated current = 100%

Note: When using the permanent magnet (PM) motor, there will be no options of setting 5.

Figure4.4.32 completesPDF229 VBIAS:AI2 0V(4mA)→0%,10V(20mA)→100%;−10V axis only. Function4 actualaccel/decel time=(00-14..17,00-21..24 time)/K. Figure4.4.33 K=1at0–1V thenrises to10at10V;time100%initial then decreases inversely;no inferred intermediate values. Function5 DCcurrent controlrequires07-07=0%,100%=inverterratedcurrent;PMmotorcannotselect5 conflictsPDF227PMO.

Manual — DC current,overtorque and stall analog control — page 231

Figure 4.4.34 DC braking current adjustment

04-05/04-10=6: Over-torque detection level

Multi-function analog input AI2/AI3 can be used to adjust the over-torque detection level.

100% of inverter rated current (V/F control mode)

100% motor rated torque (SLV control mode)

If the multi-function analog input is used to adjust the over-torque level, the internal over-torque detection

level (08-15) is disabled.

Figure 4.4.35 Over-torque/less torque detection level adjustment

4-05/04-10=7: Stall prevention level during running

Multi-function analog input AI2/AI3 can be used to adjust the stall prevention level during operation.

Inverter rated current = 100%. When AI2 is set to control stall prevention level (04-05 = 7) or AI3 is set to

control stall prevention level (04-10 = 7) and parameter 08-03 (Stall prevention level during operation) is

used, then the lesser of the two value becomes the active stall prevention level during operation.

Example: If the motor power is less than that of the inverter, the operation and the stall prevention of the

motor will be based on the factory settings, multi-function analog input AI2/AI3 can be used to reduce the

stall prevention level during operation.

Figure4.4.34 DCcurrent0V(4mA)0%,10V(20mA)100%. Function6 overtorque100%=inverterratedcurrent inV/F, motorratedtorque inSLV;usinganalogdisables08-15. Figure4.4.35same0–100%scale;captionalso saysless torque. Function7 stall useslesserofanalogAI2/AI3 and08-03;100%=inverterratedcurrent. Smaller-motorexample isnotdefaultorengineeringapproval.

Manual — Stall and frequency lower-limit diagrams — page 232

Figure 4.4.36 Stall prevention level adjustment during operation

04-05/04-10=8: Frequency lower limit

Multi-function analog input AI2/AI3 can be used to adjust the lower limit of frequency reference.

Maximum output frequency (Fmax, 01-02) = 100%. The actual lower limit is determined by the maximum

value of 00-13 (frequency lower limit) and level of the multi-function analog input AI2/AI3.

Figure 4.4.37 Adjustment of lower limit of frequency reference

Figure4.4.36 stallminimum30%from0V(4mA)to1.5V(6.4mA),rising to200%at10V(20mA). Function8 lowerlimit max(00-13,analogAI2/AI3),100%=Fmax01-02. Figure4.4.37 0V(4mA)0%,10V(20mA)100%;−10Vaxisunconnected. Sourcevaluesretained.

Manual — Jump frequency,bias addition and torque limits — page 233

04-05/04-10=9: Jump frequency 4

Multi-function analog input AI2/AI3 can be used to adjust Jump frequency 4.

Maximum output frequency (01-02, Fmax) = 100%. Setting 11-08 ~ 11-10 to 0.0Hz turns of the Jump

frequency function.

Figure 4.4.38 Jump frequency 4 setting operation

04-05=10 or 04-10=10: Added to AI1

Multi-function analog input AI2/AI3 can be used as a bias level for analog input AI1.

Figure 4.4.39 Added to Al1 as a bias operation

Example:

04-02 (AI1 gain) = 100%, 04-03 (AI2 gain) = 0%, and terminal AI2 level is 2V. If input terminal AI1 is 0V,

the internal reference frequency of terminal AI1 will be 20 %

04-05=11: Positive torque limit

Multi-function analog input AI2 can be used to adjust the positive torque limit.

04-05=12: Negative torque limit

Multi-function analog input AI2 can be used to adjust the negative torque limit.

04-05=13: Regenerative torque limit

Multi-function analog input AI2 can be used to adjust the regenerative torque limit.

Function9 jump4 usinganalogAI2/3,100%=Fmax01-02;11-08..10zero disablesjumpfunction perprose. Figure4.4.38 jump4analog,jump3=11-10,jump2=11-09,jump1=11-08,drawnascendinghierarchy;notnewfixedfrequencies. Figure4.4.39 function10addedbias0V4mA→0%,10V20mA→100%,negativeaxis−100%. Example04-02AI1gain100%,04-03labelledAI2gain0%,AI2=2V/AI1=0V→20%;04-03labelconflictsAI1biaselsewhere. Functions11/12/13 positive/negative/regenerative torquelimit,AI2 asprinted.

Manual — Torque compensation and analog output parameters — page 234

04-05=14: Positive / negative torque limits

Multi-function analog input AI2 can be used to adjust both the positive and negative torque limit.

For more details on torque limits, please refer to parameter group 21 - torque control group.

04-05=15: Reserved

04-05=16: Torque compensation of speed control

Multi-function analog input AI2 can be used to adjust the torque compensation in closed loop vector mode.

For more details on the torque control functions, please refer to parameter group 21 - torque control group.

Function14 bothpositive/negative torque;15Reserved;16 torquecompensation textclosed-loopvector andgroup21references,withoutinferringclosedloopF510capability. AO1function04-11options0–28;AO2function04-16explicitlyinherits04-11range. Gains04-12/17 0–1000%;biases04-13/18−100..100%.04-19heading continues235. Option15ASRlistedbutallmodeXon236;retainrestriction.

Torque compensation and analog output parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Torque compensation and analog output parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 04-11

Torque compensation and analog output parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 04-12

Torque compensation and analog output parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 04-13

Torque compensation and analog output parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 04-16

Torque compensation and analog output parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 04-17

Torque compensation and analog output parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 04-18

Torque compensation and analog output parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 04-19

Torque compensation and analog output parameters table1 — PDF page 234

Source row Source row label Source value or description
1 04-11 AO1 Function Setting
2 Range 【0】: Output Frequency 【1】: Frequency Command 【2】: Output Voltage 【3】: DC Voltage 【4】: Output Current 【5】: Output Power 【6】: Motor Speed 【7】: Output Power Factor 【8】: AI1 Input 【9】: AI2 Input 【10】: Torque Command 【11】: q-axis Current 【12】: d-axis Current 【13】: Speed Deviation 【14】: Reserved 【15】: ASR Output 【16】: Reserved 【17】: q-axis Voltage 【18】: d-axis Voltage 【19】~【20】: Reserved 【21】: PID Input 【22】: PID Output 【23】: PID Target Value 【24】: PID Feedback Value 【25】: Output Frequency of the Soft Starter 【26】: Reserved 【27】: Reserved 【28】: Communication Control
3 04-12 AO1 Gain
4 Range 【0.0~1000.0】%
5 04-13 AO1 Bias
6 Range 【-100.0~100.0】%
7 04-16 AO2 Function Setting
8 Range Setting range and definition are the same as those of 04-11.
9 04-17 AO2 Gain
10 Range 【0.0~1000.0】%
11 04-18 AO2 Bias
12 Range 【-100.0~100.0】%
13 04-19 AO Output Signal Type

Manual — Analog output signal and gain/bias adjustment — page 235

For the analog output and related parameters, refer to Fig.4.4.40.

Figure 4.4.40 Analog outputs and related parameters

Analog output AO1 and AO2 adjustment (04-12, 04-13 and 04-17, 04-18)

Signal: Use parameter 04-11 to select the analog output signal for AO1 and parameter 04-16 to select the

analog output signal for AO2.

Gain: Use parameter 04-12 to adjust the gain for AO1 and parameter 04-17 to adjust the gain for AO2.

Adjust the gain so that the analog output (10V/20mA) matches 100% of the selected analog output signal

(04-11 for AO1 and 04-16 for AO2).

Bias: Use parameter 04-13 to adjust the bias for AO1 and parameter 04-18 to adjust the bias for AO2.

Adjust the bias so that the analog output (0V/4mA) matches 0% of the selected analog output signal

Figure 4.4.41 Analog output level adjustment

04-19rangefrom234:0bothAO0–10V;1AO1voltage/AO2current;2AO1current/AO2voltage;3both4–20mA. Figure4.4.40 AO1function04-11,gain12,bias13;AO2function16,gain17,bias18. Gain10V/20mA maps100%,bias0V/4mA maps0%. Figure4.4.41 showsoffset/slopesandclippingat10V(20mA),negativeaxis−10V and−10V×gain;do not infernegativecurrentcapability.

Analog output signal and gain/bias adjustment. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Analog output signal and gain/bias adjustment. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 04-19 continuationfromPDF234

Analog output signal and gain/bias adjustment table1 — PDF page 235

Source row Source row label Source value or description
1 Range 【0】: AO1 0~10V AO2 0~10V 【1】: AO1 0~10V AO2 4~20mA 【2】: AO1 4~20mA AO2 0~10V 【3】: AO1 4~20mA AO2 4~20mA

Manual — Analog output functions and filtering — page 236

Table 4.4.9 Selection of analog output terminals function (04-11 and 04-16)

*1: It is new added in inverter software V1.4.

This function is used for filtering out momentary change of analog output signal.

Note: When this function is added, it will decrease the system reaction but increase interference

protection.

Table4.4.9 separate04-11/16function,Group12monitor,modes.0–9 and21–25/28 O/O/O.10–13 and17–18 X/O/O.14–16,19–20,26–27 X/X/X. Monitoringdashisabsentparameter,notzero. ASR15monitor12-32 stillallX.04-20AOscanfilter0–.5s,newV1.4,increasedinterferenceprotectionbutslowerresponse.

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 0

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 1

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 2

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 3

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 4

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 5

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 6

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 7

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 8

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 9

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 10

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 11

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 12

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 13

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 14

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 15

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 16

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 17

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 18

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 19~20

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 21

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 22

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 23

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 24

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 25

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 26~27

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 28

Analog output functions and filtering. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 04-20

Analog output functions and filtering table1 — PDF page 236

Source row 04-11/04-16 setting Function keypad display Monitoring parameter Group12 V/F SLV PM SLV
1 0 Output Freq 12-17 O O O
2 1 Freq Ref 12-16 O O O
3 2 Output Voltage 12-19 O O O
4 3 DC Voltage 12-20 O O O
5 4 Output Current 12-18 O O O
6 5 Output KW 12-21 O O O
7 6 Motor Speed 12-22 O O O
8 7 Output PF 12-23 O O O
9 8 AI1 Input 12-25 O O O
10 9 AI2 Input 12-26 O O O
11 10 Torque Ref 12-27 X O O
12 11 Current Iq 12-28 X O O
13 12 Current Id 12-29 X O O
14 13 Speed Deviation 12-30 X O O
15 14 Reserved - X X X
16 15 ASR Output 12-32 X X X
17 16 Reserved - X X X
18 17 Voltage Ref Vq - X O O
19 18 Voltage Ref Vd - X O O
20 19~20 Reserved - X X X
21 21 PID Input 12-36 O O O
22 22 PID Output 12-37 O O O
23 23 PID Setpoint 12-38 O O O
24 24 PID Feedback 12-39 O O O
25 25 Output Freq (SFS) - O O O
26 26~27 Reserved - X X X
27 28 Comm Control - O O O

Analog output functions and filtering table2 — PDF page 236

Source row Source row label Source value or description
1 04-20 Filter Time of AO Signal Scan *1
2 Range 【0.00~0.50】Sec

Manual — Multi-speed ramp selection and formulas — page 237

Group 05 Multi-Speed Parameters

05-00=0: Standard Acceleration and deceleration times parameters 00-14 ~ 00-17 / 00-21 ~ 00-24 are

used for multi-speed 0 ~ 15.

05-00=1: Each multi-speed uses a dedicated acceleration and deceleration time parameters 05-17 ~

05-48. There are two different modes for acceleration / deceleration timing when 05-00 is set to 1, see time

example on the next page.

Acceleration time calculation formula

Acceleration time x (set frequency - output frequency)

Time it takes to reach set frequency =

Maximum output frequency

Deceleration time calculation formula

Deceleration time x (output frequency - set frequency)

Maximum output frequency: Parameter 01-00=F, maximum output frequency set by 01-02, 01-00 ≠ F,

maximum output frequency determined by V/F curve selected (50.0 / 60.0 / 90.0 / 120.0 / 180.0).

Example:01-00=01 (50Hz (maximum output frequency), 05-02=10 Hz (multi-step speed 0), 05-17=5.0s

(Acceleration time), 05-18=20.0 sec. (Deceleration time).

5.0 x 10 Hz

= 1.0 sec.

50 Hz

20.0 x 10 Hz

= 4.0 sec.

Example: Acceleration / deceleration timing when 05-00 is set to 1. In this example the following

parameters are set:

00-02=1 (External Terminal Operation)

03-00=0 (Terminal S1: Forward /Stop)

03-01=1 (Terminal S2: Reversal /Stop)

03-02=2 (Terminal S3: Speed 1)

03-03=3 (Terminal S4: Speed 2)

03-03=4 (Terminal S5: Speed 3)

*Speed 1 is required to confirm if AI2 function setting (04-05) is set to 0 (Auxiliary frequency). If 04-05=0, it

will make the frequency of speed 1 set to AI2 auxiliary frequency and the value is determined by AI2. If

function of speed 1 is generally used, set AI2 to other functions except 0 (the recommended value: set 10

ADD to AI1.)

05-00=0 standard00-14..17/00-21..24;tablebroader00-14..24 retained.1dedicated05-17..48. Acceltime=AccSetting×(setfreq−outputfreq)/Fmax;deceltime=DecSetting×(outputfreq−setfreq)/Fmax. Fmax01-02if01-00=F elsecurve. Sourceexample01-00=01labelled50Hz,05-02labelledstage0=10Hz,05-17=5s,05-18=20s;results5×10/50=1s,20×10/50=4s. Curve01earlier60Hz andstage0elsewhere05-01. ExampleterminalS4andS5both03-03with3and4;rawduplicatepreserved. AI2aux04-05=0overridesstage1;source recommendsnonzeroe.g10forgeneralstagefrequency.

Multi-speed ramp selection and formulas. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Multi-speed ramp selection and formulas. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05- 00

Multi-speed ramp selection and formulas table1 — PDF page 237

Source row Source row label Source value or description
1 05- 00 Acceleration and Deceleration Selection of Multi-Speed
2 Range 【0】:Acceleration and deceleration time are set by 00-14 ~ 00-24 【1】:Acceleration and Deceleration Time are set by 05-17 ~ 05-48

Manual — Multi-speed calculation mode1 — page 238

Acceleration / Deceleration Calculation Mode 1:

If the run command is cycled on and off, acceleration and deceleration time (a ~ f) is calculated based on

the active speed command as follows:

Terminal S1

Terminal S2

Terminal S3

Terminal S4

Run

Stop

Off

On

a

b

c

d

e

f

Speed

Command 0

Command 1

Command 2

T

Hz

in sec.

(05-17) x (05-01)

(05-18) x (05-01)

(05-19) x (05-02)

(01-02)

a =

b =

c =

(05-20) x (05-02)

(05-21) x (05-03)

(05-22) x (05-03)

d =

e =

f =

RUNcycledbetweenstages0/1/2;S1RUN,S2OFF,S3ONonlystage1,S4ONonlystage2. Speeds05-01/02/03. Sixdurations a=05-17×05-01/01-02;b=05-18×05-01/01-02;c=05-19×05-02/01-02;d=05-20×05-02/01-02;e=05-21×05-03/01-02;f=05-22×05-03/01-02,allseconds. Diagramsnotparsedasnumericaltables.

Manual — Multi-speed calculation mode2 and stage frequencies — page 239

Acceleration / Deceleration Calculation Mode 2:

If the run command is remains on, acceleration and deceleration time (a ~ f) is calculated based on the

active speed command as follows:

Terminal S1

Terminal S2

Terminal S3

Terminal S4

On

17/18

Stop

Off

a

b

c

d

e

f

Speed

Command 0

Command 1

T

Hz

g

h

i

Command 2

Command 3

Command 4

Command 5

Terminal S5

19/20

21/22

23/24

25/26

27/28

in sec.

(05-17) x (05-01) (05-19) x [(05-02)-(05-01)] (05-21) x [(05-03) – (05-02)]

(01-02)

a =

b =

c =

(05-24) x [(05-03) – (05-04)]

(05-26) x (05-04)

(05-25) x (05-05)

d =

e =

f =

(05-27) x (05-05)

(05-27) x (05-06)

(05-19) x (05-06)

g =

h =

i =

RUNmaintainedacrossstages0→1→2→3FWD→4REV→5FWD→stop. Sourceformulas a=05-17×05-01/01-02;b=05-19×(05-02−05-01)/01-02;c=05-21×(05-03−05-02)/01-02;d=05-24×(05-03−05-04)/01-02;e=05-26×05-04/01-02;f=05-25×05-05/01-02;g=05-27×05-05/01-02;h=05-27×05-06/01-02;i=05-19×05-06/01-02. Allseconds. iisdecelerationsegmentbut05-19acceltimeprinted. S3/S4/S5binarysequences000,100,010,110,001,101,100;undergraphpairs17/18,19/20,21/22,23/24,25/26,27/28,19/20.05-01..04stage0..3 range0–599Hz;footnotescontinue240.

Multi-speed calculation mode2 and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Multi-speed calculation mode2 and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05- 01

Multi-speed calculation mode2 and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-02

Multi-speed calculation mode2 and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-03

Multi-speed calculation mode2 and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-04

Multi-speed calculation mode2 and stage frequencies table2 — PDF page 239

Source row Source row label Source value or description
1 05- 01 *Frequency Setting of Speed-Stage 0
2 Range 【0.0~599.00】 Hz

Multi-speed calculation mode2 and stage frequencies table3 — PDF page 239

Source row Source row label Source value or description
1 05-02 *Frequency Setting of Speed- Stage 1 *1
2 Range 【0.0~599.00】 Hz

Multi-speed calculation mode2 and stage frequencies table4 — PDF page 239

Source row Source row label Source value or description
1 05-03 *Frequency Setting of Speed- Stage 2 *1
2 Range 【0.0~599.00】 Hz

Multi-speed calculation mode2 and stage frequencies table5 — PDF page 239

Source row Source row label Source value or description
1 05-04 *Frequency Setting of Speed- Stage 3 *1
2 Range 【0.0~599.00】 Hz

Manual — Stage frequencies and ramp times — page 240

*: (When the motor’s maximum output frequency is over than 300Hz, the frequency resolution is

0.1Hz.)

*1: It isnew added in inverter software V1.4. Parameters 05-02~05-16 is required to set the

frequency in parameters 06-01~06-15 in inverter software V1.3.

05-05..16 mapstage4..15,each0–599Hz;05-17/18stage0accel/decel .1–6000s. frequencyresolution .1Hz whenmotor maximumoutputfrequency>300Hz,notallsettingsunconditionally. 1 05-02..16newV1.4;V1.3uses06-01..15formultispeed. Preserveedition/softwaredistinctionratherthanmergingparameterIDs.

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-05

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-06

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-07

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-08

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-09

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-10

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-11

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-12

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-13

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-14

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-15

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-16

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-17

Stage frequencies and ramp times. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-18

Stage frequencies and ramp times table1 — PDF page 240

Source row Source row label Source value or description
1 05-05 *Frequency Setting of Speed- Stage 4 *1
2 Range 【0.0~599.00】 Hz

Stage frequencies and ramp times table2 — PDF page 240

Source row Source row label Source value or description
1 05-06 *Frequency Setting of Speed- Stage 5 *1
2 Range 【0.0~599.00】 Hz

Stage frequencies and ramp times table3 — PDF page 240

Source row Source row label Source value or description
1 05-07 *Frequency Setting of Speed- Stage 6 *1
2 Range 【0.0~599.00】 Hz

Stage frequencies and ramp times table4 — PDF page 240

Source row Source row label Source value or description
1 05-08 *Frequency Setting of Speed- Stage 7 *1
2 Range 【0.0~599.00】 Hz

Stage frequencies and ramp times table5 — PDF page 240

Source row Source row label Source value or description
1 05-09 *Frequency Setting of Speed- Stage 8 *1
2 Range 【0.0~599.00】 Hz

Stage frequencies and ramp times table6 — PDF page 240

Source row Source row label Source value or description
1 05-10 *Frequency Setting of Speed- Stage 9 *1
2 Range 【0.0~599.00】 Hz

Stage frequencies and ramp times table7 — PDF page 240

Source row Source row label Source value or description
1 05-11 *Frequency Setting of Speed- Stage 10 *1
2 Range 【0.0~599.00】 Hz

Stage frequencies and ramp times table8 — PDF page 240

Source row Source row label Source value or description
1 05-12 *Frequency Setting of Speed- Stage 11 *1
2 Range 【0.0~599.00】 Hz

Stage frequencies and ramp times table9 — PDF page 240

Source row Source row label Source value or description
1 05-13 *Frequency Setting of Speed- Stage 12 *1
2 Range 【0.0~599.00】 Hz

Stage frequencies and ramp times table10 — PDF page 240

Source row Source row label Source value or description
1 05-14 *Frequency Setting of Speed- Stage 13 *1
2 Range 【0.0~599.00】 Hz

Stage frequencies and ramp times table11 — PDF page 240

Source row Source row label Source value or description
1 05-15 *Frequency Setting of Speed- Stage 14 *1
2 Range 【0.0~599.00】 Hz

Stage frequencies and ramp times table12 — PDF page 240

Source row Source row label Source value or description
1 05-16 *Frequency Setting of Speed- Stage 15 *1
2 Range 【0.0~599.00】 Hz

Stage frequencies and ramp times table13 — PDF page 240

Source row Source row label Source value or description
1 05-17 Acceleration time setting for multi speed 0
2 Range 【0.1~6000.0】 Sec

Stage frequencies and ramp times table14 — PDF page 240

Source row Source row label Source value or description
1 05-18 Deceleration time setting for multi speed 0
2 Range 【0.1~6000.0】 Sec

Manual — Multi-speed ramp times stages1–9 — page 241

05-19/20stage1,21/22stage2,23/24stage3,25/26stage4,27/28stage5,29/30stage6,31/32stage7,33/34stage8 areaccel/decelpairs.05-35stage9accel;deceleration05-36continueson242. Everyrange .1–6000s retainedseparately.

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-19

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-20

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-21

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-22

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-23

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-24

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-25

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-26

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-27

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-28

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-29

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-30

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-31

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-32

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-33

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-34

Multi-speed ramp times stages1–9. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-35

Multi-speed ramp times stages1–9 table1 — PDF page 241

Source row Source row label Source value or description
1 05-19 Acceleration time setting for multi speed 1
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table2 — PDF page 241

Source row Source row label Source value or description
1 05-20 Deceleration time setting for multi speed 1
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table3 — PDF page 241

Source row Source row label Source value or description
1 05-21 Acceleration time setting for multi speed 2
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table4 — PDF page 241

Source row Source row label Source value or description
1 05-22 Deceleration time setting for multi speed 2
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table5 — PDF page 241

Source row Source row label Source value or description
1 05-23 Acceleration time setting for multi speed 3
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table6 — PDF page 241

Source row Source row label Source value or description
1 05-24 Deceleration time setting for multi speed 3
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table7 — PDF page 241

Source row Source row label Source value or description
1 05-25 Acceleration time setting for multi speed 4
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table8 — PDF page 241

Source row Source row label Source value or description
1 05-26 Deceleration time setting for multi speed 4
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table9 — PDF page 241

Source row Source row label Source value or description
1 05-27 Acceleration time setting for multi speed 5
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table10 — PDF page 241

Source row Source row label Source value or description
1 05-28 Deceleration time setting for multi speed 5
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table11 — PDF page 241

Source row Source row label Source value or description
1 05-29 Acceleration time setting for multi speed 6
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table12 — PDF page 241

Source row Source row label Source value or description
1 05-30 Deceleration time setting for multi speed 6
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table13 — PDF page 241

Source row Source row label Source value or description
1 05-31 Acceleration time setting for multi speed 7
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table14 — PDF page 241

Source row Source row label Source value or description
1 05-32 Deceleration time setting for multi speed 7
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table15 — PDF page 241

Source row Source row label Source value or description
1 05-33 Acceleration time setting for multi speed 8
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table16 — PDF page 241

Source row Source row label Source value or description
1 05-34 Deceleration time setting for multi speed 8
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages1–9 table17 — PDF page 241

Source row Source row label Source value or description
1 05-35 Acceleration time setting for multi speed 9
2 Range 【0.1~6000.0】 Sec

Manual — Multi-speed ramp times stages9–15 — page 242

05-36stage9decel;37/38stage10,39/40stage11,41/42stage12,43/44stage13,45/46stage14,47/48stage15accel/decelpairs. All .1–6000s. Full05-17..48setcovers16stagepairswithpreviouspages;noskippedIDs.

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-36

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-37

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-38

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-39

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-40

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-41

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-42

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-43

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-44

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-45

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-46

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-47

Multi-speed ramp times stages9–15. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 05-48

Multi-speed ramp times stages9–15 table1 — PDF page 242

Source row Source row label Source value or description
1 05-36 Deceleration time setting for multi speed 9
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages9–15 table2 — PDF page 242

Source row Source row label Source value or description
1 05-37 Acceleration time setting for multi speed 10
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages9–15 table3 — PDF page 242

Source row Source row label Source value or description
1 05-38 Deceleration time setting for multi speed 10
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages9–15 table4 — PDF page 242

Source row Source row label Source value or description
1 05-39 Acceleration time setting for multi speed 11
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages9–15 table5 — PDF page 242

Source row Source row label Source value or description
1 05-40 Deceleration time setting for multi speed 11
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages9–15 table6 — PDF page 242

Source row Source row label Source value or description
1 05-41 Acceleration time setting for multi speed 12
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages9–15 table7 — PDF page 242

Source row Source row label Source value or description
1 05-42 Deceleration time setting for multi speed 12
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages9–15 table8 — PDF page 242

Source row Source row label Source value or description
1 05-43 Acceleration time setting for multi speed 13
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages9–15 table9 — PDF page 242

Source row Source row label Source value or description
1 05-44 Deceleration time setting for multi speed 13
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages9–15 table10 — PDF page 242

Source row Source row label Source value or description
1 05-45 Acceleration time setting for multi speed 14
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages9–15 table11 — PDF page 242

Source row Source row label Source value or description
1 05-46 Deceleration time setting for multi speed 14
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages9–15 table12 — PDF page 242

Source row Source row label Source value or description
1 05-47 Acceleration time setting for multi speed 15
2 Range 【0.1~6000.0】 Sec

Multi-speed ramp times stages9–15 table13 — PDF page 242

Source row Source row label Source value or description
1 05-48 Deceleration time setting for multi speed 15
2 Range 【0.1~6000.0】 Sec

Manual — Automatic program mode and stage frequencies — page 243

Group 06 Automatic Program Operation Parameters

Automatic operation mode uses frequency reference parameters 05-01, 06-01~06-15, operation time

parameters 06-16 ~ 06-31 and direction of operation parameters 06-32~06-47.

Note: The automatic operation mode is disabled when any of the following functions are enabled:

Notes:

(03-00~03-07=2~5) is disabled.

*1: It is operation frequency in inverter software V1.4.

*: (When the motor’s maximum output frequency is over than 300Hz, the frequency resolution is

0.1Hz.)

06-00=0disabled;1/4singlecycle;2/5continuous;3/6singlethenlastspeed. Restartgroup1–3unfinishedstep,4–6firststep;rangeinitialrestartwording retained. Uses05-01stage0,06-01..15stages1..15;shared0–599Hzrangeappliesall15. V1.4operationfrequencydistinction;resolution .1Hzifmax>300Hz. Disabledwithfrequencywobble,PID,ortimes06-16..31zero. Multi-stepDI03-00..07=2..5disabledasprinted;earlierterminalrange00..05,nobroaderhardwareinference. Autoramps00-14/15.

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06- 00

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-01

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-02

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-03

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-04

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-05

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-06

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-07

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-08

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-09

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-10

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-11

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-12

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-13

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-14

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-15

Automatic program mode and stage frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Shared06-01..06-15 frequencyrange,all15stages

Automatic program mode and stage frequencies table1 — PDF page 243

Source row Source row label Source value or description
1 06- 00 Automatic Operation Mode Selection
2 Range 【0】: Disable 【1, 4】: Execute a single cycle operation. Restart speed is based on the previous stopped speed. 【2, 5】: Execute continuous cycle operation. Restart speed is based on the previous cycle stop speed. 【3, 6】: After completion of a single cycle, the on-going operation speed is based on the speed of the last stage. Restart speed is based on the previous stopped speed 1 to 3: After a stop the inverter will start with the incomplete step when the run command is re-applied. 4 to 6: After a stop the inverter will start with the first step of the cycle when the run command is re-applied.

Automatic program mode and stage frequencies table2 — PDF page 243

Source row Source row label Source value or description
1 06-01 *Frequency Setting of Operation -Stage 1 *1
2 06-02 *Frequency Setting of Operation -Stage 2 *1
3 06-03 *Frequency Setting of Operation -Stage 3 *1
4 06-04 *Frequency Setting of Operation -Stage 4 *1
5 06-05 *Frequency Setting of Operation -Stage 5 *1
6 06-06 *Frequency Setting of Operation -Stage 6 *1
7 06-07 *Frequency Setting of Operation -Stage 7 *1
8 06-08 *Frequency Setting of Operation -Stage 8 *1
9 06-09 *Frequency Setting of Operation -Stage 9 *1
10 06-10 *Frequency Setting of Operation -Stage 10 *1
11 06-11 *Frequency Setting of Operation -Stage 11 *1
12 06-12 *Frequency Setting of Operation -Stage 12 *1
13 06-13 *Frequency Setting of Operation -Stage 13 *1
14 06-14 *Frequency Setting of Operation -Stage 14 *1
15 06-15 *Frequency Setting of Operation -Stage 15 *1
16 Range 0.00~599.00 Hz

Manual — Automatic program times and directions — page 244

Example 1: Automatic operation mode – Single cycle

In this example the inverter executes a single cycle and then stops.

06-16..31timesstages0..15share0–6000s.06-32..47directionsstages0..15share0Stop/1Forward/2Reversal. Sharedrangesapplyalllistedrows,notonlylastparameter. Example1singlecycleintroduced;settingson245.

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-16

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-17

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-18

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-19

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-20

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-21

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-22

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-23

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-24

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-25

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-26

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-27

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-28

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-29

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-30

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-31

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Shared06-16..31times,all16stages

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-32

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-33

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-34

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-35

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-36

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-37

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-38

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-39

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-40

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-41

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-42

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-43

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-44

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-45

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-46

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 06-47

Automatic program times and directions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Shared06-32..47directions,all16stages

Automatic program times and directions table1 — PDF page 244

Source row Source row label Source value or description
1 06-16 Time Setting of Operation -Stage 0
2 06-17 Time Setting of Operation -Stage 1
3 06-18 Time Setting of Operation -Stage 2
4 06-19 Time Setting of Operation -Stage 3
5 06-20 Time Setting of Operation -Stage 4
6 06-21 Time Setting of Operation -Stage 5
7 06-22 Time Setting of Operation -Stage 6
8 06-23 Time Setting of Operation -Stage 7
9 06-24 Time Setting of Operation -Stage 8
10 06-25 Time Setting of Operation -Stage 9
11 06-26 Time Setting of Operation -Stage 10
12 06-27 Time Setting of Operation -Stage 11
13 06-28 Time Setting of Operation -Stage 12
14 06-29 Time Setting of Operation -Stage 13
15 06-30 Time Setting of Operation -Stage 14
16 06-31 Time Setting of Operation -Stage 15
17 Range 0.0~6000.0 Sec

Automatic program times and directions table2 — PDF page 244

Source row Source row label Source value or description
1 06-32 Direction Selection of Operation -Stage 0
2 06-33 Direction Selection of Operation -Stage 1
3 06-34 Direction Selection of Operation -Stage 2
4 06-35 Direction Selection of Operation -Stage 3
5 06-36 Direction Selection of Operation -Stage 4
6 06-37 Direction Selection of Operation -Stage 5
7 06-38 Direction Selection of Operation -Stage 6
8 06-39 Direction Selection of Operation -Stage 7
9 06-40 Direction Selection of Operation -Stage 8
10 06-41 Direction Selection of Operation -Stage 9
11 06-42 Direction Selection of Operation -Stage 10
12 06-43 Direction Selection of Operation -Stage 11
13 06-44 Direction Selection of Operation -Stage 12
14 06-45 Direction Selection of Operation -Stage 13
15 06-46 Direction Selection of Operation -Stage 14
16 06-47 Direction Selection of Operation -Stage 15
17 Range 0: Stop, 1: Forward, 2: Reversal

Manual — Single-cycle and continuous-cycle examples — page 245

Parameter Settings:

06-00 = 1 (Single cycle operation)

06-32~06-34 = 1 (Forward for operation stage 0 - 2)

06-47 = 2 (Reversal for operation stage 15)

06-35~06-46 = 0 (Stop for operation frequency stage 3 - 14)

05-01 = 15 Hz (Operation frequency stage 0: 15 Hz)

06-01 = 30 Hz (Operation frequency stage 1: 30 Hz)

06-02 = 50 Hz (Operation frequency stage 2: 50 Hz)

06-15 = 20 Hz (Operation frequency stage 15: 20 Hz)

06-16 = 20 sec (Operation time stage 0: 20 sec)

06-17 = 25 sec (Operation time stage 1: 25 sec)

06-18 = 30 sec (Operation time stage 2: 30 sec)

06-31 = 40 sec (Operation time stage 15 :40 sec)

Freq.

50 Hz

30 Hz

15 Hz

20 Hz

20s

25s

30s

40s

Figure 4.4.42 Single cycle automatic operation (stop)

Example 2: Automatic operation mode – Continuous cycle

In this example the inverter repeats the same cycle.

06-00 =

2 or 5 (Continuous cycle operation)

06-01~06-47= Enter same setting as that of Example 1.

Example1:06-00=1;06-32..34=1FWDstages0–2;06-47=2REVstage15;06-35..46=0stages3–14.05-01=15Hz,06-01=30Hz,06-02=50Hz,06-15=20Hz;06-16=20s,17=25s,18=30s,31=40s. Fig4.4.42 intervalsincludeaccelerationanddirectiontransitionasdrawn,thenstopafterreverse20Hz. Example2=06-00 2or5,other06-01..47sameexample1;notproductiondefaults.

Manual — Continuous and last-speed program behaviour — page 246

Figure 4.4.43 Periodic automatic operation

Example 3: Automatic operation mode – Single cycle and continue running at last speed of the cycle

In this example the inverter executes a single cycle and continue running at last speed of the cycle.

Figure 4.4.44 Single cycle automatic operation (continuous)

06-00= 1 to 3:

After a stop the inverter will start with the incomplete step when the run command is re-applied.

06-00= 4 to 6:

After a stop the inverter will start with the first step of the cycle when the run command is re-applied.

Notes:

Figure4.4.43continuousgraph15Hz20s/30Hz25s/50Hz30s/reverse20Hz40srepeat;reverse labels06-03and06-19 differexample1reuse06-15/31. Figure4.4.44singlethenlast reverse20Hzcontinuesafter40s;labels06-15/31. Restart1–3 resumesincompletestep;4–6newcyclefromfirst. Accel/decel00-14/15;06-16..31zero meansinactive. Keepdiagramvariantlabelsandproseindependently.

Manual — Power-loss and fault autorestart parameters — page 247

Group 07: Start /Stop Parameters

07-00=0: Inverter trips on “UV” fault if power loss time is greater than 8ms.

07-00=1: Inverter restarts after restarting the power at the momentary power loss.

Note: When 07-00=1, inverter restore automatically the motor rotation after restarting the power even if

momentary power loss occurs.

07-01 = 0 sec.:

Automatic restart time interval is set by minimum baseblock time (07-18).

07-01 <07-18:

07-01> 07-18:

Automatic restart time interval is set by fault reset time (07-01).

Note:

Automatic restart time interval is time of 07-18 plus 07-01 and delay time of peed search (07-22).

Refer to Fig.4.4.45 for setting automatic restart interval.

Figure 4.4.45 Automatic restart operation

When the automatic restart function is enabled the internal automatic restart attempt counter is reset

based on the following actions:

a) No fault occurs in 10 minutes or longer after the automatic restart

b) Reset command to clear fault via input terminal or using the keypad (ex: press reset/  key)

c) Power to the inverter is turned off and back on again

Multi-function digital output R1A-R1C, R2A-R2C, R3A-R3C can be programmed to activate during an

automatic reset attempt, refer to parameter 03-11, 03-12 and 03-39.

Automatic restart operation:

a) Fault is detected. The inverter turn off the output, displays the fault on the keypad and waits for the

minimum baseblock time parameter 07-18 to expire before accepting another run / automatic restart

command.

b) After the minimum baseblock time (07-18) has expired, the active fault is reset and a speed search

operation is performed. The time between each fault restart attempt is set by parameter 07-01.

c) When the total numbers of restart attempts exceed the number of automatic restart attempts set in

parameter 07-02, the inverter will turn off the output and the fault contact is activated.

07-00=0UVtripifpowerloss>8ms;1automaticrotationrestoreafterpowerreturns.07-01 0–7200s;0or<07-18usesminimum07-18,>07-18uses07-01;notealso saysintervalsum07-18+07-01+07-22,conflictretained. Fig4.4.45 tenpulses1–10bound07-02andspacing07-01.07-02range0–10;counterresetafter10minnofault,resetcommand,orpowercycle. Outputs03-11/12/39canactivateautorestart. Faultoff→wait07-18→reset/speedsearch;exceedcountoutputoff/faultcontact.

Power-loss and fault autorestart parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Power-loss and fault autorestart parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 00

Power-loss and fault autorestart parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 01

Power-loss and fault autorestart parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 02

Power-loss and fault autorestart parameters table1 — PDF page 247

Source row Source row label Source value or description
1 07- 00 Momentary Power Loss/Fault Restart Selection
2 Range 【0】:Disable 【1】:Enable

Power-loss and fault autorestart parameters table2 — PDF page 247

Source row Source row label Source value or description
1 07- 01 Fault Auto-Restart Time
2 Range 【0~7200】 Sec

Power-loss and fault autorestart parameters table3 — PDF page 247

Source row Source row label Source value or description
1 07- 02 Number of Fault Auto-Restart Attempts
2 Range 【0~10】

Manual — Restart fault scope and power-up selection — page 248

Please refer to Figure 4.4.46 for the automatic restart operation.

Figure 4.4.46 Auto-restart operation

The automatic restart function is active for the following faults. Please note that when the fault is not listed

in the table the inverter will not attempt an automatic restart.

Notes:

1.

Fault restart function contains momentary power loss restart and auto reset restart.

2.

Refer to chapter 10 for the details of troubleshooting and fault diagnostics.

3.

Refer to speed search function (07-19~07-24) for the selection of speed search modes.

Note:

Automatic restart function is only active in the state of no harm to the safety or to the application devices.

Warning - Excessively use of the automatic restart function will damage the inverter.

07- 04 = 0:

If the running switch is in conducting state when power supply is on, the inverter will start automatically.

07- 04 =1:

If the running switch is not in conducting state when power supply is on , the inverter will not start

automatically and STP1 will flash. It is required to switch off the running switch and make it be in

conducting state so as to start the inverter.

Fig4.4.46 firsttwoaxesunnamed;synchronouspulsesduring07-18,secondcalloutfaultcontactactive07-00=1;thirdtracezero duringintervalthenrecovervia dip. No inferredaxisidentities. FaulttableUV/07-00Unlimited;07-01/02dependentcount07-02forOC,OCA,OCC,OCd,OL1,UT,IPL,GF,OV,OL2,OT,OPL,CF07,CF08. Unlistedfaultsnoautorestart. Sourcewarningexcessiveautorestartdamagesdrive andsafeapplicationconditionretained.07-04=0autoifexternalRUN;1noauto. Prose1saysRUNnotconductingyetrequireoff/on/STP1,polaritywordingflagged.

Restart fault scope and power-up selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Restart fault scope and power-up selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 07-00

Restart fault scope and power-up selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: 07-01

Shared source cells (coordinates refer to this table):

Restart fault scope and power-up selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 04

Restart fault scope and power-up selection table1 — PDF page 248

Source row Parameter Faults left column Faults right column Number of restarts
1 07-00 UV (under voltage) ⟦null: no independent source value⟧ Unlimited
2 07-01 07-02 OC (over current) OCA (over current in ACC.) OCC (over current in constant speed) OCd (over current in DEC) OL1 (motor overload) UT (Under torque detection) IPL (input phase loss) GF (ground failure) OV (overvoltage) OL2 (Inverter overload) OT (Over-torque detection) OPL (Output phase loss) CF07 (SLV motor control setting fault) CF08 (PMSLV motor control setting fault) Depend on parameter 07-02

Restart fault scope and power-up selection table2 — PDF page 248

Source row Source row label Source value or description
1 07- 04 Automatic start at power up
2 Range 【0】: Automatic start at power up when external run command is enabled 【1】: Without automatic start at power up when external run command is enabled

Manual — Automatic start delay and braking modes — page 249

When 07- 04 = 0, if power supply is on, the inverter automatically start at power up and it will count the

delay time set by 07–05. The inverter starts running only when the delay time ends.

!Warning:

When 07- 04 = 0 and run command source is set to external control (00- 02/00- 03 = 1), if

running switch is in conducting state and the inverter starts automatically when power supply is

on, customers are suggested to switch off the power supply and running switch at power loss to

prevent from the damage to the inverter and user when reconnecting.

When 07- 04 = 1 and run command source is set to external control (00- 02/00- 03 = 1), if

running switch is not in conducting state when power supply is on, the inverter will not start

automatically and STP1 will flash. It is required to switch off the running switch and then make it

be in conducting state and start the inverter after the delay time of automatic start at power up

ends.

The braking opearion is controlled by the different control modes (00-00), please refer to the following

descriptions:

  1. Control mode: VF, SLV (00-00 = 0,2)

When the inverter runs, DC injection braking is enabled by the time of parameter 07-16. Deceleration

to stop is according to 07-06 and 07-08. When output frequency is lower than 07-06 in deceleration

time, it starts DC injection braking by the time of 07-08.

07 - 16

07 - 08

07 - 06 (Braking start

frequency)

Or 01 - 08 (Fmin)

DC

injection

braking

Output

frequency

Time

Figure 4.4.47a VF、VF+PG、SLV and SLV2 DC injection braking

Note: When 07-06<01-08, It start DC injection braking by the setting frequency (01-08)

  1. Control mode: PMSLV (00-00=5)

Set short-circuit breaking time at start by 07-34 and DC braking time by 07-16. Braking action at

start runs by the setting time of 07-34 (short-circuit braking) and then by that of 07-16 (DC

braking).

Deceleration to stop is set by 07-35 (short-circuit braking) and 07-08 (DC braking). When output

frequency is lower than 07-06 in deceleration, braking action runs by the setting time of 07-35

(short-circuit braking) and then by that of 07-08 (DC braking).

Note: If 07-06 < 01-08, braking function starts at the setting frequency of 01-08. Refer to the following

figure 4.4.47b.

Set DC braking current level by 07-07 on the base of the inverter rated current being 100%. If the

setting value of 07-07 is higher than the motor rated current, DC braking current level is limited

to the motor rated value.

Set short-circuit braking current level by 07-36 on the base of the motor rated current being

100%.

07-05delay1–300swith07-04=0;external00-02/03=1sourcewarningspreserved.07-06DCstart0–10Hz. V/F/SLV00-00=0/2:startupDCtime07-16,stop07-08 atlarger07-06or01-08. Figure4.4.47acaptionadditionallyVF+PG/SLV2notinprose;nocapabilityinferred. PMSLV00-00=5:startupSC07-34thenDC07-16;stopSC07-35thenDC07-08.07-07DC100%=inverterratedcurrent,limitedtomotorratedcurrent;07-36SC100%=motorratedcurrent.

Automatic start delay and braking modes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Automatic start delay and braking modes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 05

Automatic start delay and braking modes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07-06

Automatic start delay and braking modes table1 — PDF page 249

Source row Source row label Source value or description
1 07- 05 Automatic start delay at power up
2 Range 【1.0~300.0】 Sec

Automatic start delay and braking modes table2 — PDF page 249

Source row Source row label Source value or description
1 07-06 DC injection braking starting frequency
2 Range 0.0~10.0 Hz

Manual — PMSLV and DC injection braking — page 250

07 - 06 (Braking Start Frequency)

or 01 - 08 (Fmin)

SC

Braking

Output

frequency

Time

DC

07-34 07-16

07-35 07-08

Figure 4.4.47b PMSLV braking action

DC Injection braking current as percentage of the inverter rated current. Increasing this level will increase

the amount of heat generated by the motor windings. Do not set this parameter higher than the level

necessary to hold the motor shaft.

Duration of DC injection braking is during a stop operation. DC injection braking at stop is disabled when

parameter 07-08 is set to 0 sec.

Duration of DC injection braking is during a start operation. DC injection braking at start is disabled when

parameter 07-16 is set to 0 sec.

DC Injection Braking Operation

When DC Injection braking is active DC voltage is applied to the motor, increasing the braking current and

resulting in an increase in the strength of the magnetic field trying to lock the motor shaft.

To enable DC injection braking during a start operation set the DC injection braking current (07-07) and

the DC injection braking time (07-16) at start to a value greater than 0. DC injection braking at start can be

used to prevent “wind milling effect” in fan applications.

To enable DC injection braking during a stop operation set the DC injection braking current (07-07) and the

DC injection braking time at stop (07-08) to a value greater than 0.

Notes:

output frequency.

braking is activated when the output frequency reaches the minimum output frequency level.

Figure4.4.47b sequenceSC07-34→DC07-16→run→atlarger07-06/01-08SC07-35→DC07-08.07-07DCcurrent0–100%inverterrating;heatwarningnotexceednecessaryshaft-holdlevel.07-08stop0–10s,07-16start0–100s;0disablesrespectivephase. Startrequirescurrentandtime>0;windmillingexample.07-16zero startsminimumfreq. Increasingtime/currentcanreducestoptime sourceclaimnotengineeringguarantee.

PMSLV and DC injection braking. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

PMSLV and DC injection braking. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 07

PMSLV and DC injection braking. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 08

PMSLV and DC injection braking. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 16

Adjacent source context — repeated to preserve continuation:

PMSLV and DC injection braking table2 — PDF page 250

Source row Source row label Source value or description
1 07- 07 DC Injection Braking Current
2 Range 【0~100】%

PMSLV and DC injection braking table3 — PDF page 250

Source row Source row label Source value or description
1 07- 08 DC Injection Braking Time at Stop
2 Range 【0.00~10.00】Sec

PMSLV and DC injection braking table4 — PDF page 250

Source row Source row label Source value or description
1 07- 16 DC Injection Braking Time at Start
2 Range 【0.00~100.00】Sec

Manual — Short-circuit braking and stop modes — page 251

Figure 4.4.47c DC braking operation

DC braking operation can be controlled via any one of the multi-function input terminals (03-00 to 05)

function 33. Refer to Fig. 4.4.47 for DC braking operation.

DC braking current can be controlled via the multi-function analog input (04-05 or 04-10) function 5. Refer

to Fig. 4.4.34.

PMSLV control mode is available for short-circuit braking. Short-circuit braking is the way to switch IGBT to

produce braking torque. Setting value of 07-06, 07-34, 07-35 and 07-36 can adjust the braking action

process.

If 07-35=0, Inverter starts from the minimum frequency.

The setting value of 07-36 depends on the motor rated current being 100%. (ex. motor rated current is 5A,

07-36=100% is 5A)

03-00~03-07=65, it can control Short-circuit braking action.

When a stop command is issued the inverter stops according to the stop mode selected. There are four

types of stop modes,

Note: When using the permanent magnet motor, only the option of deceleration to stop mode is available.

07-09=0: Deceleration to stop

When a stop command is issued, the motor will decelerate to the minimum output frequency (01-08) Fmin

and then stop. Deceleration rate depends on the deceleration time (factory default: 00-15).

Figure4.4.47c RUNON→07-16delayatFmin→motorspeedrise;RUNOFF→decel→larger01-08/07-06→07-08braking. DI33on03-00..05 controlsDC;analog04-05/10=5current.07-34/35SCstart/stop0–100s,07-36limit0–200%motorratedcurrent;example5Arating100%=5A. Prose07-35=0startatminimumfreq conflictsstopname;retain. DI03-00..07=65 broaderthanterminaltable.07-09options0decel,1coast,2DC,3timedcoast;PMonly0allowed. Mode0deceltoFmin01-08,defaulttime00-15.

Short-circuit braking and stop modes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Short-circuit braking and stop modes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 34

Short-circuit braking and stop modes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 35

Short-circuit braking and stop modes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 36

Short-circuit braking and stop modes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 09

Adjacent source context — repeated to preserve continuation:

Short-circuit braking and stop modes table1 — PDF page 251

Source row Source row label Source value or description
1 07- 34 Short-circuit braking time at Start
2 Range 【0.00~100.00】Sec
3 07- 35 Short-circuit braking time at Stop
4 Range 【0.00~100.00】Sec
5 07- 36 Short-circuit braking current limited level
6 Range 【0.0~200.0】%

Short-circuit braking and stop modes table2 — PDF page 251

Source row Source row label Source value or description
1 07- 09 Stop Mode Selection
2 Range 【0】:Deceleration to Stop 【1】:Coast to Stop 【2】:DC Braking Stop 【3】:Coast to Stop with Timer

Manual — Deceleration and coast stop — page 252

Source limitation for this page: Figure4.4.48 left-side labels are clipped in both source renders; only visible fragments retained, no expansion inferred.

When the output frequency reaches the DC braking stop frequency (07-06) or the minimum output

frequency (01-08), DC injection braking is activated and the motor stops.

Output frequency when stop command is issued

Deceleration time = × deceleration time setting

Maximum output frequency Fmax (01-02)

Note: S curve setting will add to the overall stop time

Figure 4.4.48 Deceleration to stop

07-09=1: Coast to stop

When a stop command is issued, the motor will coast to a stop. Stop time depends on motor load and

friction of the system.

The inverter waits for the time set in the minimum baseblock time (07-18) before accepting the next run

command.

In SLV mode (00-00=2) the speed search function is automatically enabled upon the next run command.

Note: When using a mechanical brake set parameter 07-26 to 1.

Figure 4.4.49 Coast to stop

Deceltime=(outputfrequencyatSTOP/Fmax01-02)×decelsetting;S-curveaddsstopduration. Fig4.4.48 RUNOFF→ramp→07-06→DCduration07-08. Leftlabelsvisiblycropped(insource),notreconstructedasnewfacts. Mode1coaststop dependsload/friction;wait07-18beforenextRUN;SLV00-00=2speedsearchnextRUN;mechanicalbrake07-26=1sourceinstruction. Fig4.4.49 RUNcomesbeforebaseblockexpires,butoutputrampwaitsuntil07-18elapsed.

Manual — DC braking stop and timed coast — page 253

07-09=2: DC braking to stop

When a stop command is issued, the inverter will turn off the output (Baseblock) and after the minimum

Baseblock time (07-18) has expired activate DC braking (07-07). Refer to Fig.4.4.50.

The DC braking time (tDCDB) of Figure 4.4.50 is determined by the value of 07-08 (DC Braking start time)

and the output frequency at the time the stop command was issued.

(07-08) x 10 x output frequency

tDCDB =

Fmax (01-02)

Note: Increase the minimum Baseblock time (07-18) in case an Overcurrent trip occurs during the DC

braking.

Figure 4.4.50 DC braking to stop

07-09=3: Coast to stop with timer

When a stop command is issued the motor will coast to a stop after the minimum Baseblock time (07-18)

has expired. The inverter ignores the run command until the total time of the timer has expired.

The total time of the timer is determined by the deceleration time (00-15, 17, 22 or 24) and the output

frequency upon stop. Refer to Fig.4.4.51

Figure 4.4.51 Coast to stop with timer

Mode2stopturnsoffoutput,wait07-18thenDC07-07. Source tDCDB=(07-08×10×outputfreq)/Fmax01-02. Graphminimum07-08×1up to10%Fmax thenrises to07-08×10at100%;formulaalonewouldbelowminimum,retainboth. Textcalls07-08DCstarttimewheretable250callsstop. Increase07-18ifOCduringDC. Mode3coastwithtimer ignoresRUNuntilT1;diagramoutputoffimmediatelyatSTOPthoughprosesayscoastafterbaseblock. T1depends00-15/17/22/24andfrequency,graphfloor07-18thenrise todecelsetting100%;RUNwithinT1ignored.

Manual — Low-voltage detection and pre-excitation — page 254

Adjust the 07-13 voltage level from 150 to 300 Vdc (200V class) or from 300 to 600 Vdc (400V class).

When the AC input voltage is lower than the 07-13 value (07-13/ 1.414 = AC voltage detection level) for

the time specified in 07-25 the low-voltage error "UV" will displayed. If 07-25 = 0.00 sec., the UV error will

be displayed immediately.

Set preventive measures:

-

The inverter input voltage will limit the output voltage. If the input voltage drops excessively, or if the

load is too big, the motor may stall.

If the input voltage drops below the value set in 07-13 then the output is turned off momentarily. The

inverter will not automatically start when power is restored.

If a high starting torque is required for the application, especially for a large horsepower motors, the

pre-excitation operation can be used to pre-flux (magnetize) the motor.

07-14: Pre-excitation time

When an operation command (forward or reverse) is activated, the inverter will automatically start

pre-excitation based on the time set in parameter 07-14.

The time for the flux to reach 100% is a function value of motor’s electrical time constant (See figure

4.4.52).

Electrical time constant (quadratic by-pass circuit time constant) is suggested to set 2.00~4.00 Sec.

07-15: Pre-excitation initial level

Use the pre-excitation initial level (07-15) to provide a higher excitation current during the pre-excitation

time (07-14), which will increase the speed and stability for motors.

In order to quickly magnetize the motor, reduce the pre-excitation time (07-14) and set the pre-excitation

level (07-15) to a high level.

If 07-15 is set greater than 100%, providing a high excitation current during the pre-excitation time (07-14),

motor’s magnetization time is shorted. When the setting reaches 200%, magnetization is reduced by

roughly half.

A high pre-excitation level (07-15) might result in excessive motor sound during pre-excitation.

When the flux reaches 100%, pre-excitation current reverts back to 100% and pre-excitation is completed.

07-13table200V150–300V/400V300–600V,proseVdc;ACdetection07-13/1.414.07-25delay0–1s,0immediateUV. Prosesayspowerrestorewillnotautomaticstart,unqualifiedversus07-00=1on247.07-14preexcitation0–10s;07-15level50–200%;electricaltimeconstantrecommended2–4s sourceclaim. Flux100%complete/revertcurrent100%;200%levelroughlyhalvesmagnetizationtime,mayincreasenoise. Figure4.4.52referencedbutcontinues255outsidepart;no fullprocedurecompletionclaim.

Low-voltage detection and pre-excitation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval.

Low-voltage detection and pre-excitation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 13

Low-voltage detection and pre-excitation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 25

Low-voltage detection and pre-excitation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 14

Low-voltage detection and pre-excitation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained;not engineering approval. Row group: Parameter 07- 15

Low-voltage detection and pre-excitation table1 — PDF page 254

Source row Source row label Source value or description
1 07- 13 Low Voltage Detection Level
2 Range 【200V】: 150~300V 【400V】: 300~600V
3 07- 25 Low voltage Detection Time
4 Range 【0.00~1.00】Sec

Low-voltage detection and pre-excitation table2 — PDF page 254

Source row Source row label Source value or description
1 07- 14 Pre-excitation Time
2 Range 【0.00~10.00】Sec
3 07- 15 Pre-excitation Level
4 Range 【50~200】%

Manual — Pre-excitation and minimum baseblock — page 255

Figure 4.4.52 Pre-excitation operation

In case of a momentary power failure, the inverter continues to operate after the power has been restored

when parameter 07-00 is set to 1. Once the momentary power failure is detected; the inverter will

automatically shut down the output and maintain B.B for a set time (07-18).

It is expected that after the minimum base block time has expired the residual voltage to be almost zero.

When the momentary power failure time exceeds the minimum base block time (07-18), the inverter will

automatically perform a speed search upon return of power. Refer to the following figure 4.4.53.

Figure 4.4.53 Minimum B.B time and momentary power loss time

Minimum base block time (07-18) is also used to for the DC braking function in combination with speed

search as follows:

Figure 4.4.52 completes PDF254: RUN ON starts pre-excitation 07-14; current at initial level 07-15 while magnetic flux rises to100%; current returns100% and motor accelerates after 07-14. 07-18 minimum block .1–5s. Figure4.4.53a: when block longer than power loss wait until block expires; b: when power loss longer wait until power restored. Residual voltage almost zero is an expectation in source, not a verified guarantee. Used also with DC braking/speed search; increase block if OC occurs.

Pre-excitation and minimum baseblock. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Pre-excitation and minimum baseblock. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 18

Pre-excitation and minimum baseblock table1 — PDF page 255

Source row Source row label Source value or description
1 07- 18 Minimum Base block Time
2 Range 【0.1~5.0】Sec

Manual — Speed-search parameter ranges — page 256

Speed search function is used to find the speed of a coasting motor and continue operation from that point.

The speed search function is active after a momentary power loss.

Speed Search from Multi-function digital inputs

Set the multi-function digital input to external speed search command 1 or 2. External speed search

command 1 (value = 19) and 2 (value = 34) cannot be set at the same time, otherwise "SE02" (digital input

terminal error) warning occurs.

Speed search function must be enabled before applying the run command to ensure proper operation.

See relay logic in Fig. 4.4.54.

Figure 4.4.54 Speed search and operation commands

07-19/20 currents0–100%; 07-21 .1–10s;07-22 0–20s;07-23 .1–5s. 07-24=0disable/1enable direction detection;07-26 opposite polarity0enable/1disable SLV search. 07-27/28=0search/1normal. 07-32=0disabled,1power-on,2eachrun;07-33=0maxmotorfrequency,1command. DI19 and34 cannot both be assigned or SE02. Fig4.4.54 speed-search command relay Ry1 precedes RUN relay Ry2; intervening contact printed Rv1, not silently changed to Ry1.

Speed-search parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Speed-search parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 19

Speed-search parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 20

Speed-search parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 21

Speed-search parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 22

Speed-search parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07-23

Speed-search parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 24

Speed-search parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 26

Speed-search parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 27

Speed-search parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 28

Speed-search parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 32

Speed-search parameter ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 33

Speed-search parameter ranges table1 — PDF page 256

Source row Source row label Source value or description
1 07- 19 Direction-Detection Speed Search Operating Current
2 Range 【0~100】%
3 07- 20 Speed Search Operating Current
4 Range 【0~100】%
5 07- 21 Integral Time of Speed Searching
6 Range 【0.1~10.0】Sec
7 07- 22 Delay Time of Speed Search
8 Range 【0.0~20.0】Sec
9 07-23 Voltage Recovery Time
10 Range 【0.1~5.0】Sec
11 07- 24 Direction-Detection Speed Search Selection
12 Range 【0】: Disable 【1】: Enable
13 07- 26 SLV Speed Search Function
14 Range 【0】: Enable 【1】: Disable
15 07- 27 Start Selection after Fault during SLV Mode
16 Range 【0】: Speed search start 【1】: Normal Start
17 07- 28 Start after External Base Block
18 Range 【0】: Speed search start 【1】: Normal Start
19 07- 32 Speed Search Mode Selection
20 Range 【0】: Disable 【1】: Mode1: Start a Speed Search at Power on 【2】: Mode2: Start Speed Search upon the Motor Run
21 07- 33 Start Frequency of Speed Search Selection
22 Range 【0】: Maximum Output Frequency of Motor 【1】: Frequency Command

Manual — Speed-search restrictions and currents — page 257

Notes: Speed Search Operation

inverter currently used.

auto-tune.

rotational auto-tune. Perform a static auto-tune when using long motor leads.

Speed search uses current detecting. Use parameter 07-24 to select detection direction.

07-19: Speed Direction Search Operating Current

Note: If value is too high may cause DC braking effect.

07-20: Speed Search Operating Current

the no-load current is unknown it is recommended to set value at 20%.

block time (07-18) in case of an over-current condition.

07-21: Integral time of speed searching

start is required

07-22: Delay time of speed search

07-23: Voltage recovery time

search function is completed.

07-24: Direction-Detection Speed Search Selection

07-24=0: Disable Direction-Detection Speed Search

Speed search is executed using speed search operating current defined in parameter 07-20. In case

speed search is not successful (e.g. motor speed is too low) a speed search time-out warning is displayed.

Unavailable when motor rated power exceeds inverter, is two inverter sizes smaller, or motor is high-speed. V/F requires static autotune;SLV rotational autotune;long leads static autotune. 07-19 bidirectional only (07-24=1), increase if failure at low speeds above5Hz; excess causes DC braking. 07-20 both directions: below excitation current02-09 and equal no-load current; if unknown source recommends20%, not a universal default. 07-21 increase after OV for longer search;07-22 output-contactor delay,0disabled;07-23 voltage restoration from0V to specified V/F. 07-24=0 paragraph continues258.

Manual — Search modes and PM applicability — page 258

Set 07-19 to value greater than 0 to enable DC braking at speed search if a time-out occurs frequently.

07-24=1: Enable Direction-Detection Speed Search

At start the current controller will send a step current to the motor (07-19) to determine the motor direction.

Once direction is determined the current controller will perform a speed search using speed search

operating current defined in parameter 07-20. Speed search is executed after a momentary power loss

(external speed search command 2, 03-00 to 03-05 = 34) or from max. frequency (external speed search

command 1, 03-00 to 03-05 = 19). Speed search direction will follow the speed command.

07-26: SLV Speed Search Function

timer (07-09 = 3). After a stop command is issued (coast to stop or coast to stop with times) the speed

search function is automatically activated for the next start.

07-26=0: Enable (No mechanical brake is installed)

07-26=1: Disable (Mechanical brake is installed)

07-27: Start Selection after fault during SLV mode

07-27=0: Speed search start: Speed search is executed after a fault in SLV mode.

07-27=1: Normal start: Speed search is not enabled.

Note: Set the parameter to 1 (normal start) after a fault has occurred and a mechanical brake is used to

stop the motor.

07-28: Start after external Baseblock

07-28=0: Speed search start: Speed search is executed after base block is removed.

07-28=1: Normal start: Speed search is not enabled.

07-32: Speed Search Mode Selection

0: Disable: The inverter start to run from the lowest output frequency but it won’t limit the other functions of

trigger speed search.

1: Execute a Speed Search at Power On: The inverter executes a speed search at power on when

entering first run command. It start the motor from found frequency.

2: The inverter will start speed search upon the motor run to find the exact frequency.

07-33: Start Frequency of Speed Search Selection

0: Maximum Output Frequency of Motor: The inverter start speed search from the maximum output

frequency of motor.

1: Frequency Command: The inverter start speed search from setting frequency command.

Notes:

-

Set parameter to 1 for the control mode of SLV mode (00-00 = 2) when the external base block

Unidirectional paragraph from257 continues with07-19>0 for DC braking on frequent timeout, despite previous bidirectional-only restriction. Bidirectional07-24=1 uses07-19 to detect direction then07-20 search; DI34 command2 after power loss, DI19 command1 from maximum frequency. SLV00-00=2 and coast07-09=1/3 activate search next start;07-26=1 for mechanical brake. 07-27=1 normal start after fault recommended with mechanical brake.07-28=1 normal after external block.07-32=0 does not disable other search triggers. Last note says set parameter to1 for external baseblock but unnamed parameter under07-33; continuation259 retained without assigning to07-28.

Manual — Start and power-loss search diagrams — page 259

active time is longer than the time the motor needs to come to a complete stop. After the external

base block command is removed the inverter will accelerate from min. frequency.

-

The inverter has no choices but can only normally start when using permanent magnetic motor.

■ Speed search based on current detection

(a) Speed search at starting

Figure 4.4.55 Speed search at starting

(b) Speed search in recovery period of momentary power failure

Figure 4.4.56 Speed search in recovery period of momentary power failure

Notes:

search starts operation after the minimum base block time (07-18).

after power has been restored.

Continuation258: external baseblock longer than time to stop then accelerate from minimum after removal; PM motor only normal start stated here. Fig4.4.55 search command precedes RUN; wait07-18, frequency falls during search07-21 then rises to command; voltage follows V/F and recovers via07-23; operating current07-20. Fig4.4.56 power-loss recovery with RUN/search held: output blocked until later of power restoration and07-18 expiration, then same search sequence. PM only-normal statement is retained alongside PM searched-frequency behaviour on260.

Manual — Braking and PM speed switching — page 260

After DC braking action starts, if run command selection is set to 0, it will not run until DC braking action

ends.

If run command selection is set to 1, it is not required to wait for the ending of DC braking action. It can run

during DC braking action process.

When output voltage saturation happen, and the motor running is not normal, increase this parameter to

limit the output voltage.

But when this parameter is too big, the output torque maybe not enough,please decrease this parameter.

If the motor is in a rotating state due to inertia and the rotation speed is far below the minimum speed

control range, parameters 07-43 and 07-44 are available to perform braking action to let the motor stop

and then restart.

If the motor is in a rotating state due to inertia and the rotation speed is higher than the minimum speed

control range, the motor starts in a certain searched frequency regardless of the setting value of parameter

07-43 or 07-44.

If parameters 07-43 and 07-44 are set to 0, the motor starts in a certain searched frequency after motor’s

speed search stops regardless of motor’s rotarion speed.

.

 If STP2 is enabled, when 00-02=1 and external operation signal is tripped, keypad will display

“Terminal STOP” error when stop command comes from keypad.

 If STP2 is disabled, when 00-02=1 and external operation signal is tripped, keypad will not display

If switch the three-speed speed switching according to the following figure, use the 00-25

(acceleration/deceleration switching frequency) ≠0 and 22-11 (I/f mode starting frequency switching point)

parameters for frequency switching acceleration and deceleration:

Invalid: Please refer to the 00-25 parameter frequency for speed switching.

Mode 1: After the power is turned on, the speed can be switched, and the speed is switched according to

the following figure.

Mode 2: The speed switching of the following figure can be realized only for the first operation, but the

22-11 switching will be invalid when decelerating.

07-29=0 wait until DC braking finished before RUN,1can run during braking.07-42 voltage-limit gain0–50%; excess reduces torque.07-43/44 PM short-circuit/DC braking times0–100s: far below min speed range brake then restart; above min range use searched frequency irrespective times; both0 search then start at found frequency.07-45 STP2=0enabled/1disabled for keypad stop with external00-02=1.07-47=0disabled,1mode1,2mode2;00-25 must nonzero with22-11 switching point. Mode2 first operation only and22-11 switching invalid on deceleration; figure continues261.

Braking and PM speed switching. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Braking and PM speed switching. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 29

Braking and PM speed switching. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 42

Braking and PM speed switching. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 43

Braking and PM speed switching. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 44

Braking and PM speed switching. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 45

Braking and PM speed switching. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 07- 47

Braking and PM speed switching table1 — PDF page 260

Source row Source row label Source value or description
1 07- 29 Run Command Available during DC Braking
2 Range 【0】: Disable (Run command isn’t available until the DC braking is completely done) 【1】: Enable

Braking and PM speed switching table2 — PDF page 260

Source row Source row label Source value or description
1 07- 42 Voltage Limit Gain
2 Range 【0.0~ 50.0】%

Braking and PM speed switching table3 — PDF page 260

Source row Source row label Source value or description
1 07- 43 Short-circuit Braking Time of PM Motor Speed Search
2 Range 【0.00~100.00】Sec
3 07- 44 DC Braking Time of PM Motor Speed Search
4 Range 【0.00~100.00】Sec

Braking and PM speed switching table4 — PDF page 260

Source row Source row label Source value or description
1 07- 45 STP2 Function Selection
2 Range 【0】:STP2 is enabled 【1】:STP2 is disabled

Braking and PM speed switching table5 — PDF page 260

Source row Source row label Source value or description
1 07- 47 PM Speed Switching Frequency Mode
2 Range 【0】: Disabled 【1】: Mode 1 【2】: Mode 2

Manual — PM switching timing — page 261

time

Output

Frequency

Tacc4

Rate

(00-23)

Tacc1

(00-14)

Tacc3

(00-21)

Tdec3

(00-22)

Tdec1

(00-15)

(00-25)

Note: When 00-25≠0, the switching frequency can't be less than the 22-11 parameter frequency setting,

and this parameter is enabled only in PMSLV mode.

PMSLV only. Switching frequency00-25 nonzero cannot be below22-11. Acceleration low-to-high segments: Tacc3 Rate00-21 up to22-11;Tacc1 Rate00-14 up to00-25;Tacc4 Rate00-23 to top. Deceleration high-to-low segments labelled Tacc4 Rate00-25 to00-25 threshold, Tdec1 Rate00-15 to22-11, Tdec3 Rate00-22 to0. First deceleration label Tacc4/00-25 conflicts acceleration name and00-25 frequency role; preserved without changing to00-24.

Manual — Stall prevention parameters — page 262

Group 08 Protection Parameters

Note: Stall prevention function only can be set in V/F control mode.

Stall prevention during acceleration (08-00=xxx0b)

(1) Prevents the inverter from faulting (Overcurrent, Motor overload, Inverter overload) when accelerating

with heavy loads.

(2) When the inverter output current reaches the level set in parameter 08-01 minus 15% the acceleration

rate starts to decrease. When the inverter output current reaches the level set in parameter 08-01 the

motor stops accelerating.

(3) Reduce stall prevention level during acceleration (08-01) in case the motor stalls (when the motor

power is smaller than the inverter rating.

Prevents the inverter from faulting (Overcurrent, Motor overload, Inverter overload) when accelerating with

heavy loads.

When the inverter output current reaches the level set in parameter 08-01 minus 15% the acceleration rate

starts to decrease. When the inverter output current reaches the level set in parameter 08-01 the motor

stops accelerating. Refer to Fig.4.4.57 for more information.

Notes:

is smaller than the inverter rating.

Only V/F control.08-00 bits xxx0b acceleration enabled,xx0xb decel enabled,x0xxb run enabled;corresponding1 disables;0xxx b time1/1xxx b time2.08-01 20–200%;08-02 200V330–410V and400V660–820V;08-03 30–200%;08-21 1–100%;08-22 2–100ms. Acceleration rate reduces at08-01 minus15%, stops accelerating at08-01; source repeats explanatory paragraph.100%=inverter rated current; smaller motor may require reduction, source condition preserved.

Stall prevention parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Stall prevention parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 00

Stall prevention parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 01

Stall prevention parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 02

Stall prevention parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 03

Stall prevention parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 21

Stall prevention parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 22

Stall prevention parameters table1 — PDF page 262

Source row Source row label Source value or description
1 08- 00 Stall Prevention Function
2 Range 【xxx0b】: Stall prevention is enabled in acceleration. 【xxx1b】: Stall prevention is disabled in acceleration. 【xx0xb】: Stall prevention is enabled in deceleration. 【xx1xb】: Stall prevention is disabled in deceleration. 【x0xxb】: Stall prevention is enabled in operation. 【x1xxb】: Stall prevention is disabled in operation. 【0xxxb】: Stall prevention in operation decelerates based on deceleration time 1 【1xxxb】: Stall prevention in operation decelerates based on deceleration time 2
3 08- 01 Stall Prevention Level in Acceleration
4 Range 【20~200】%
5 08- 02 Stall Prevention Level in Deceleration
6 Range 【330~410】V : 200V 【660~820】V : 400V
7 08- 03 Stall Prevention Level in Operation
8 Range 【30~200】%
9 08- 21 Limit of Stall Prevention in Acc over Base Speed
10 Range 【1~100】%
11 08- 22 Stall Prevention Detection Time in Operation
12 Range 【2~100】msec

Manual — Acceleration and deceleration stall curves — page 263

Figure 4.4.57 Stall prevention during acceleration

If the motor is used in the constant power (CH) region, the stall prevention level (08-01) is automatically

reduced to prevent the stall.

Stall prevention level during acceleration (Constant horsepower)

Stall Prev. Lev. Acceleration (CH) = Stall prevention level in acceleration (08-01) x Fbase (01-12)

Output frequency

Parameter 08-21 is the stall prevention limit value in Constant Horsepower region. Refer to Fig.4.4.58.

Figure 4.4.58 Stall prevention level and limit in acceleration

Stall prevention selection during deceleration (08-00=xx0xb)

Stall prevention during deceleration automatically increases the deceleration time according based on the

DC-bus voltage to prevent over-voltage during deceleration. Refer to Fig.4.4.59 for stall prevention during

deceleration

When the DC-bus voltage exceeds the stall prevention level deceleration will stop and the inverter will wait

for the DC-bus voltage to fall below the stall prevention level before continuing deceleration. Stall

prevention level can be set by 08-02, see Table 4.4.10.

Fig4.4.57 acceleration pauses after08-01 and resumes after lower15% hysteresis boundary. Constant horsepower stall level=(08-01×Fbase01-12)/output frequency. Fig4.4.58 flat08-01 in constant torque then falling in constant horsepower, clipped at lower08-21; dashed below-limit continuation is illustrative. Deceleration08-00=xx0xb pauses when DC bus exceeds08-02 until voltage falls below level. Full deceleration illustration on264.

Manual — Stall defaults and running prevention — page 264

Table 4.4.10 Stall prevention level

Note: When using external braking (braking resistor or braking module) disable stall prevention during

deceleration (08-00 to xx1xb).

Figure 4.4.59 Stall prevention selection in deceleration

Stall prevention selection during run (08-00=x0xxb)

Stall prevention during run can only be used in V/F control mode for induction motor.

This function prevents the motor from stalling by automatically reducing the output frequency during run.

If the inverter output current rises above the level set in parameter 08-03 for the time specified in

parameter 08-22, the inverter output frequency is automatically decreased following deceleration time 1

(00-15) or deceleration time 2 (00-17).

When the inverter output current falls below the level set in parameter (08-03) minus 2%, normal operation

continues and the output frequency increases to the frequency reference using the acceleration time 1 or

acceleration time 2. Refer to the following Fig.4.4.60.

Note: The stall prevention level during run can be set by using multi-function analog input AI2 (04-05=7) or

AI3(04-10=7).

Table4.4.10 200V class385VDC/400V class770VDC defaults08-02. External braking resistor/module requires disabling decel stall08-00=xx1xb per source. Fig4.4.59 stepwise paused deceleration extends stop time, dotted nominal deceleration. Run stall only V/F induction motor; current above08-03 for08-22 causes frequency decrease using00-15 or00-17; resume below08-03 minus2%, ramp via acceleration1/2. AI2=04-05=7 or AI3=04-10=7 can set running stall level.

Stall defaults and running prevention. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Stall defaults and running prevention. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: 200V class

Stall defaults and running prevention. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: 400V class

Stall defaults and running prevention table1 — PDF page 264

Source row Inverter model 08-02 default value
1 200V class 385VDC
2 400V class 770VDC

Manual — Motor overload settings and running stall — page 265

Figure 4.4.60 Stall prevention selection in operation

The motor overload protection function estimates the motor overload level based on the output current,

output frequency, motor characteristics and time. The motor overload trip time depends on the motor rated

current when the output frequency is higher than 60Hz.

On inverter power-up the motor overload protection internal thermal accumulation register is automatically

reset.

To use the built-in motor overload protection function parameter 02-01 (motor rated current) has to match

the motor rated current on the motor nameplate.

Turn off the motor overload protection when using two or more motors connected to the inverter (set 08-05

= xxx0b), and provide external overload protection for each motor (e.g. thermal overload switch).

With cold start enabled (08-05 = xx0xb), motor overload protection occurs in 5 and a half minutes when

operating the motor at 150% of the motor rated current at an output frequency greater than 60Hz.

Fig4.4.60 load rises; current crosses08-03, waits08-22 then frequency falls along Tdec1(00-15) orTdec2(00-17), recovers after current crosses threshold minus2%.08-05 bits:xxx1b protection enabled,xx0xb cold/xx1xb hot,x0xxb standard/x1xxb special;top bit reserved.08-07 levels0/1/2 distinct curves. Thermal register resets on power-up;02-01 must match nameplate current. For multiple motors disable internal protection and provide individual external protection, source instruction retained. Cold at150% and>60Hz says5.5min; separate curve examples nextpages not overwritten.

Motor overload settings and running stall. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Motor overload settings and running stall. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 05

Motor overload settings and running stall. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08-07

Motor overload settings and running stall table1 — PDF page 265

Source row Source row label Source value or description
1 08- 05 Selection for Motor Overload Protection (OL1)
2 Range 【xxx0b】:Motor Overload Protection is disabled. 【xxx1b】:Motor Overload Protection is enabled. 【xx0xb】:Cold Start of Motor Overload 【xx1xb】:Hot Start of Motor Overload 【x0xxb】:Standard Motor 【x1xxb】:Special motor 【0xxxb】:Reserved 【1xxxb】:Reserved
3 08-07 Motor Overload (OL1) Protection Level
4 Range 【0】:Motor Overload (OL1) Protection 0 【1】:Motor Overload (OL1) Protection 1 【2】:Motor Overload (OL1) Protection 2

Manual — Motor overload curves levels0 and1 — page 266

With hot start enabled (08-05 = xx1xb), motor overload protection occurs in 3 and a half minutes when

operating the motor at 150% of the motor rated current at an output frequency greater than 60Hz.

Refer to the following Fig.4.4.61 for an example of motor overload protection standard curve.

And refer to the setting of 08-07 (Motor overload (OL1) protection level), the overload curve will be

different.

08-07=0:

Low Speed

(1.5 Hz)

Hot Start

100%

150%

200%

Motor Load Current (%)

(02-01 = 100%)

Overload Protect Time (min)

1.5

2.9

7.9

Cold Start

2.4

4.5

12.4

08-07=1:

Fig4.4.61 standard-motor examples. Each listed trip time in minutes pairs with motor-load current%;02-01=100%. Level08-07=0 low1.5Hz hot:100%=7.9,150%=2.9,200%=1.5; cold:100%=12.4,150%=4.5,200%=2.4. Level0 high60Hz hot:116%=28.8,150%=3.9,200%=1.7; cold:116%=45.2,150%=6.1,200%=2.7. Level1 low1.5Hz hot:100%=8.9,150%=3.2,200%=1.7; cold:100%=14.9,150%=5.3,200%=2.8. Level1 high60Hz hot:116%=30.9,150%=4.2,200%=1.9; cold:116%=51.6,150%=7.1,200%=3.2.116% labelled start-activated point at high speed. Prose hot150%/>60Hz3.5min retained separately; no interpolation or curve fitting.

Manual — Overload level2 and motor derating — page 267

08-07=2:

Figure 4.4.61 Motor overload protection curve (example: standard motor)

When using force cooled motors (Special inverter motor), thermal characteristics are independent of the

motor speed, set 08-05 = x1xxb.

When 08-05 = x1xxb, overload protection function is based on motor rated current for output frequencies

between 6 and 60Hz. If the output frequency is lower than 1Hz, the overload protection function uses 83%

of the motor rated current to determine an overload condition.

When 08-05 = x0xxb, overload protection function is based on 70% of the motor rated current for an output

frequency of 20Hz. If the output frequency is lower than 1Hz, the overload protection function uses 40% of

the motor rated current to determine an overload condition.

Refer to Fig.4.4.62 for motor overload rating at different output frequencies.

Figure 4.4.62 Motor overload rating at different output frequencies

Fig4.4.61 level08-07=2,standard motor: low1.5Hz hot100%=9.9min,150%=3.5,200%=1.9; cold100%=17.8,150%=6.3,200%=3.4. High60Hz hot116%=34.4,150%=4.7,200%=2.1; cold116%=61.9,150%=8.5,200%=3.8. High116% start-activated point. Fig4.4.62 special motor08-05=x1xxb dashed curve, prose100% rated current6–60Hz and83% below1Hz; standardx0xxb solid40% below1Hz,70% at20Hz,100% at60Hz. Do not derive exact unlabelled special-curve breakpoint from graph; plotted rise not a new frequency value.

Manual — OL1 AVR and phase-loss protections — page 268

08-06=0: When the inverter detects a motor overload the inverter output is turned off and the OL1 fault

message will display on the keypad. Press RESET button on the keypad or activate the reset function

through the multi-function inputs to reset the OL1 fault.

08-06=1: When the inverter detects a motor overload the inverter will continue running and the OL1 alarm

message will flash on the keypad until the motor current falls within the normal operating range.

Automatic voltage regulation stabilizes the motor voltage independent of fluctuation to the input voltage.

08-08=0: Automatic voltage regulation is active. It will limit the maximum output voltage. When input

three-phase voltage fluctuates and the voltage is smaller than the value of 01-14, the output voltage will

fluctuate with the fluctuation of input voltage.

08-08=1: Automatic voltage regulation is not active, motor voltage follows the input voltage fluctuation.

When input three-phase voltage fluctuates, the output voltage won’t fluctuate with the fluctuation of input

voltage.

08-09=0: Input phase loss detection is disabled.

08-09=1: Input phase loss detection is enabled. Keypad shows "IPL input Phase Loss" (IPL), when an

input phase loss is detected the inverter output is turned off and the fault contact is activated.

Note: The input phase loss detection is disabled when the output current is less than 30% of the inverter

rated current.

08-10=0: Output phase loss detection is disabled.

08-10=1: Output phase loss detection is enabled. Keypad shows "OPL Output Phase Loss" (OPL), when

an output phase loss is detected and the inverter output is turned off and the fault contact is activated.

Note: The output phase loss detection is disabled when the output current is less than 10% of the inverter

08-06=0 OL1 fault/output off/reset required,1continue/alarm until normalcurrent.08-08=0AVR enabled,1disabled. Disabled prose first says voltage follows input fluctuation then says will not fluctuate; source contradiction retained.08-09input phase loss0disabled1enabled; detection disabled below30% inverter rated current.08-10output phase loss0disabled1enabled; disabled below10%. Enabled loss triggers outputoff/faultcontact IPL orOPL respectively.

OL1 AVR and phase-loss protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

OL1 AVR and phase-loss protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 06

OL1 AVR and phase-loss protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 08

OL1 AVR and phase-loss protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 09

OL1 AVR and phase-loss protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 10

OL1 AVR and phase-loss protections table1 — PDF page 268

Source row Source row label Source value or description
1 08- 06 Start-up mode of overload protection operation (OL1)
2 Range 【0】:Stop Output after Overload Protection 【1】:Continuous Operation after Overload Protection.

OL1 AVR and phase-loss protections table2 — PDF page 268

Source row Source row label Source value or description
1 08- 08 Automatic Voltage Regulation (AVR)
2 Range 【0】:AVR is enabled 【1】:AVR is disabled

OL1 AVR and phase-loss protections table3 — PDF page 268

Source row Source row label Source value or description
1 08- 09 Selection of Input Phase Loss Protection
2 Range 【0】:Disable 【1】:Enable

OL1 AVR and phase-loss protections table4 — PDF page 268

Source row Source row label Source value or description
1 08- 10 Selection of Output Phase Loss Protection
2 Range 【0】:Disable 【1】:Enable

Manual — Overtorque and undertorque parameters — page 269

The over torque detection function monitor the inverter output current or motor torque and can be used to

detect increase in inverter current or motor torque (e.g. heavy load).

The low torque detection function monitor the inverter output current or motor torque and can be used to

detect a decrease in inverter current or motor torque (e.g. belt break).

The torque detection levels (08-15, 08-19) are based on the inverter rated output current (100% = inverter

rated output current) when operating the inverter in V/F control mode and motor output torque (100% =

motor rated torque) when operating the inverter in SLV control mode.

Over-torque detection

Parameter 08-13 selects over-torque detection function. An over-torque condition is detected when the

output current / torque rises above the level set in parameter 08-15 (Over-torque detection level) for the

time specified in parameter 08-06 (Over-torque detection time).

08-13=0: Over-torque detection is disabled.

08-13=1: Over-torque detection is enabled when the output frequency reaches the set frequency.

08-13=2: Over-torque detection is enabled during running.

Parameter 08-14 selects the way the inverter acts when an over-torque condition is detected.

08-14=0: When an over-torque condition is detected the inverter displays and over-torque detection fault

and the motor decelerates to a stop.

08-14=1: When an over-torque condition is detected the inverter displays an over-torque detection alarm

and continues to run.

08-14=2: When an over-torque condition is detected the inverter displays and over-torque detection fault

and the motor coasts to a stop.

08-13/17 over/low detection0off,1atsetfrequency,2duringrun.08-14/18 action0decelstop,1alarmcontinue,2coaststop.08-15/19 level0–300%;08-16/20 time0–10s.100%=inverter rated current V/F, motor rated torque SLV; no PM inference. Over-torque prose wrongly names08-06 detection time versus08-16 table/nextfigure; retain original. No merging overtorque and lowtorque parameter identities.

Overtorque and undertorque parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Overtorque and undertorque parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 13

Overtorque and undertorque parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 14

Overtorque and undertorque parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 15

Overtorque and undertorque parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 16

Overtorque and undertorque parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 17

Overtorque and undertorque parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 18

Overtorque and undertorque parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 19

Overtorque and undertorque parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 20

Overtorque and undertorque parameters table1 — PDF page 269

Source row Source row label Source value or description
1 08- 13 Selection of Over-Torque Detection
2 Range 【0】: Over-Torque Detection is Disabled. 【1】: Start to Detect when Reaching the Set Frequency. 【2】: Start to Detect when the Operation is Begun.
3 08- 14 Selection of Over-Torque Operation
4 Range 【0】: Deceleration to Stop when Over- Torque is Detected. 【1】: Display Warning when Over- Torque is Detected. Go on Operation. 【2】: Coast to Stop when Over Torque is Detected.
5 08- 15 Level of Over-Torque Detection
6 Range 【0~300】%
7 08- 16 Time of Over-Torque Detection
8 Range 【0.0~10.0】Sec
9 08- 17 Selection of Low-Torque Detection
10 Range 【0】: Low-Torque Detection is Disabled. 【1】: Start to Detect when Reaching the Set Frequency. 【2】: Start to Detect when the Operation is Begun.
11 08- 18 Selection of Low-Torque Operation
12 Range 【0】: Deceleration to Stop when Low- Torque is Detected. 【1】: Display Warning when Low- Torque is Detected. Go on Operation. 【2】: Coast to Stop when Low-Torque is Detected.
13 08- 19 Level of Low-Torque Detection
14 Range 【0~300】%
15 08- 20 Time of Low-Torque Detection
16 Range 【0.0~10.0】Sec

Manual — Overtorque and undertorque timing — page 270

Figure 4.4.63 Over-torque detection operation

Low-torque detection

Parameter 08-18 selects low-torque detection function. An low-torque condition is detected when the

output current / torque falls below the level set in parameter 08-19 (low-torque detection level) for the time

specified in parameter 08-20 (Low-torque detection time).

08-17=0: Low-torque detection is disabled.

08-17=1: Low-torque detection is enabled when the output frequency reaches the set frequency.

08-17=2: Low-torque detection is enabled during running.

Parameter 08-18 selects the way the inverter acts when an over-torque condition is detected.

08-18=0: When a low-torque condition is detected the inverter displays and low-torque detection fault and

the motor decelerates to a stop.

08-18=1: When a low-torque condition is detected the inverter displays a low-torque detection alarm and

continues to run.

08-18=2: When a low-torque condition is detected the inverter displays and low-torque detection fault and

the motor coasts to a stop.

Figure 4.4.64 Low torque detection operation

Over and low torque detection condition can be output to the multi-function digital outputs (R1A-R1C,

R2A-R2C, R3A-R3C) by setting parameters 03-11, 03-12 and 03-39 to 12 or 25. Refer to Fig. 4.4.65 for

more information.

Fig4.4.63 current/torque above08-15 for08-16 activates signal, reset at10% lower hysteresis. Fig4.4.64 below08-19 for08-20 activates lowtorque signal, reset at10% upper hysteresis. Lowtorque introductory prose says08-18 selects detection but explicit values use08-17; later08-18 sentence calls overtorque although lowtorque actions follow. Relay outputs03-11/12/39 set12 or25, terminalsR1A–R1C/R2A–R2C/R3A–R3C;diagram271.

Manual — Relay map and ground/external/safety faults — page 271

R1A

R1B

R1C

R2A

R2C

}

R3A

R3C }

Figure 4.4.65 Over-torque / low torque detection multi-function digital output terminal

If the inverter leakage current is greater than 50% of inverter rated current and the ground fault function is

enabled (08-23), the keypad will display a "GF Ground Fault" (GF), motor will coast to a stop and fault

contact is activated.

When multi-function digital input terminal is set to 25 (the external fault) and this terminal signal is triggered

off, parameter 08-24 (Operation Selection of External Fault) can be selected to stop it. The selection of

stop modes is the same as 07-09.

The reason for the detection of external faults is determined by parameter 08-25.

When 08-25=0, faults are immediately detected at power up.

When 08-25=1, faults are detected when the inverter is running.

If multi-function digital input terminal is set to 58 (Safety Function), inverter will stop via the set of 08-30

when this function is enabled.

Fig4.4.65 R1 A/B/C tied03-11: A contact shownopen, B closed, C common;R2 A/C03-12 andR3 A/C03-39 opencontacts.08-23GF if leakage>50%inverterratedcurrent andenabled:coaststop/faultcontact.08-24 external fault0decel1coast2continue,DI25triggeredoff asprinted;prose says sameas07-09 although07-09=2DCbrake.08-25=0detectpowerup,1duringrun.08-30 safety DI58 selects0decel1coast; no certification/performance level inferred.

Relay map and ground/external/safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Relay map and ground/external/safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 23

Relay map and ground/external/safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 24

Relay map and ground/external/safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 25

Relay map and ground/external/safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 30

Relay map and ground/external/safety faults table2 — PDF page 271

Source row Source row label Source value or description
1 08- 23 Ground Fault (GF) Selection
2 Range 【0】: Disable 【1】: Enable

Relay map and ground/external/safety faults table3 — PDF page 271

Source row Source row label Source value or description
1 08- 24 Operation Selection of External Fault
2 Range 【0】: Deceleration to Stop 【1】: Coast to Stop 【2】: Continuous Operation

Relay map and ground/external/safety faults table4 — PDF page 271

Source row Source row label Source value or description
1 08- 25 Detection selection of External Fault
2 Range 【0】: Immediately Detect when the Power is Supplied 【1】: Start to Detect during Operation

Relay map and ground/external/safety faults table5 — PDF page 271

Source row Source row label Source value or description
1 08- 30 Selection of Safety Function
2 Range 【0】: Deceleration to Stop 【1】: Coast to Stop

Manual — Fan and motor-temperature protection — page 272

08-37=0: Start at Operation

Fan starts while inverter is running.

If the inverter stops over the delay time of fan off (08-38), fan is off.

08-37=1: Permanent Start

When the inverter is at power on, fan will start permanently.

08-37=2: Start at High Temperature

When the temperature of heatsink is higher than that of internal setting, fan immediately starts.

If the temperature is lower than internal setting value or the delay time of fan off (08-38) is due, fan will be

off.

Note: Function of fans on is disabled for the models of 60HP or the above (200V) and 100HP or the above

(400V) in IP20 series and is enabled for all the models in IP55 series.

Protection of motor overheating is enabled via the sensor of motor fan with the temperature impedance

chacteristics of positive temperature coefficient (PTC).

Thermistor of PTC connects with terminals MT and GND. If motor is overheating, the keypad displays the

error code of OH4.

08-35=0: Fault selection of motor overheating is disabled.

08-35=1, 2: Motor stop running while fault of motor overheating occurs.

Protection of motor overheating is enabled when the motor temperature rises, and the MT voltage level is

higher than 08-42 PTC trip level and the reach of delay time set by 08-39. The keypad will display an “OH4

Motor overheat” and fault output is active.

When the motor temperature falls, and the MT voltage level is lower than 08-43 PTC reset level, it can

08-37fan0operation,1permanent,2high-temperature;08-38offdelay0–600s. Source wording fan-on function disabled IP20 models≥60HP200V/≥100HP400V; enabled allIP55, not evidence fans physically absent.08-35overheat0disabled1decel2coast;08-36filter .00–5.00 no printed unit;08-39delay1–300s;08-42/43trip/reset .1–10V;08-45disconnect0off1warning2fault. MT–GND PTC;OH4 whenMT voltage>08-42 for08-39;resetwhen<08-43 continuation273.

Fan and motor-temperature protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Fan and motor-temperature protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 37

Fan and motor-temperature protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 38

Fan and motor-temperature protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 35

Fan and motor-temperature protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 36

Fan and motor-temperature protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 39

Fan and motor-temperature protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 42

Fan and motor-temperature protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 43

Fan and motor-temperature protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08- 45

Fan and motor-temperature protection table1 — PDF page 272

Source row Source row label Source value or description
1 08- 37 Fan Control Function
2 Range 【0】: Start at Operation 【1】: Permanent Start 【2】: Start at High Temperature
3 08- 38 Delay Time of Fan Off
4 Range 【0~600】Sec

Fan and motor-temperature protection table2 — PDF page 272

Source row Source row label Source value or description
1 08- 35 Fault Selection of Motor Overheat
2 Range 【0】: Disable 【1】: Deceleration to Stop 【2】: Coast to Stop
3 08- 36 Time Coefficient of PTC Input Filter
4 Range 【0.00 ~ 5.00】
5 08- 39 Delay Time of Motor Overheat Protection
6 Range 【1 ~ 300】Sec
7 08 - 42 PTC Trip Level
8 Range 【0.1~10】V
9 08 - 43 PTC Reset Level
10 Range 【0.1~10】V
11 08- 45 PTC Disconnection Detection
12 Range 【0】: Disable 【1】: Warning 【2】: Fault

Manual — PTC formula and connection — page 273

reset ‘’OH4 Motor overheat.’’

Note: The stop mode of the inverter fault is set by 08-35.

08-35=1: Deceleration to stop when the inverter fault occurs.

08-35=2: Coast to stop when the inverter fault occurs

Notes:

overheat.”

When Tr is 150℃ in class F and 180℃ in class H,

a. Tr- 5℃: RPTC ≦ 550Ω, use RPTC value to formula (1), the V value can be set to 08-43 PTC

reset level.

b. Tr+ 5℃: RPTC≧1330Ω, use RPTC value to formula (1), the V value can be set to 08-42 PTC trip

level

  1. If the specification of PTC is different, please follow formula 1 to calculate the value of 8-42 and 8-43.

K

R

V

PTC

//

Formula (1)

  1. It can be calculated via formula (1) if it is in an empty connection or disconnection state when the

voltage value is between 3.3~4V. if empty connection or disconnection occurs, the inverter trips to

PTCLS warning or fault signal. Set fault signal by parameter 08-45. There will be ten seconds to detect

once disconnection occurs. If it reconnects withinthe time, PTC signal will not be tripped and it will be

recounting on redisconnection.

  1. When measuring the voltage-across from MT and GND terminals, the measured voltage is not equal

to the input level one. The level one is calculated by formula (1).

Refer to Fig. 4.4.66 for the connecting between the corresponding temperature of thermistor of PTC and

terminals.

Figure 4.4.66 (a) PTC Themistor Characteristics (b) PTC Themistor Connections

Completes272 OH4 resetbelow08-43. Source claims British National Standard without identifier;Tr150°CclassF/180°CclassH. Tr−5°C:RPTC≤550Ω resetlevel;Tr+5°C:RPTC≥1330Ω trip. Formula1 V=(1/2)×10V×[(RPTC//20K)/(10K+(RPTC//20K))]. // retained as printed parallel notation. Disconnect calculated3.3–4V,PTCLS via08-45 after10s; reconnectwithin intervalavoids trip andtimerrecounts onnewdisconnect. MeasuredMT–GND voltage not equal calculated inputlevel. Fig4.4.66 curves550/1330Ω aroundTr andTrprime;classF/H temperature context;PTCbetweenMT/GND internal+10V resistor network,uncalledresistancevaluesnotinferred.

Manual — Temperature relay and fire-mode parameters — page 274

Note: 08-47 maximum value will be limited by 08-46 set value

The inverter temperature agree and reset level selection

03-11 set to【59】:

‧ 08-46: The inverter temperature is > 08-46, the relay operates.

‧ 08-47: When the output current is ≤ 08-47, the relay signal from ON to OFF.

Down time frequency diagram:

繼電器

ON

變頻器溫度

T(°C)

Time

Inverter temperature agree and reset detection

 When 08-48=0, Fire Mode is disabled.

Frequency Converter Temperature

Relay

08-46/47temperature0–254°C;reset47limitedby46.03-11=59:graph ONwhenT>46/OFFwhenT≤47. Prose calls resetquantityoutputcurrent despite°C axes;native hidden Chinese diagram text not a separate visible value.08-48=0off1on;49reset0poweroff1terminalremoved;50xxx0bS6Acontact/xxx1bS6Bcontact;51source0speed52,1PID,2AI2;52speed0–100%;59direction0forward1reverse;60password00000–65534. Detailscontinue275.

Temperature relay and fire-mode parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Temperature relay and fire-mode parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 46

Temperature relay and fire-mode parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 47

Temperature relay and fire-mode parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 48

Temperature relay and fire-mode parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 49

Temperature relay and fire-mode parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 50

Temperature relay and fire-mode parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 51

Temperature relay and fire-mode parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 52

Temperature relay and fire-mode parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 59

Temperature relay and fire-mode parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 60

Temperature relay and fire-mode parameters table1 — PDF page 274

Source row Source row label Source value or description
1 08 - 46 Temperature agree level
2 Range 【0 ~ 254】°C
3 08 - 47 Temperature reset level
4 Range 【0 ~ 254】°C

Temperature relay and fire-mode parameters table3 — PDF page 274

Source row Source row label Source value or description
1 08 - 48 Selection of Fire Mode
2 Range 【0】: Disable 【1】: Enable
3 08 - 49 Multi-Function Input Terminal Status of Fire Mode
4 Range 【0】: Reset after Power Off 【1】: Reset after Terminal Removed
5 08 - 50 Multi-Function Terminal Status of Fire Mode
6 Range 【xxx0b】: S6 A Contact 【xxx1b】: S6 B Contact
7 08 - 51 Motor Speed Setting Source of Fire Mode
8 Range 【0】:Fire Mode Speed (08-52) 【1】:PID Control 【2】:AI2
9 08 - 52 Fire Mode Motor Speed
10 Range 【0.00~100.00】%
11 08 - 59 Fire Mode Motor Direction
12 Range 【0】: Forward 【1】: Reverse
13 08 - 60 Fire Mode Password
14 Range 【00000 ~ 65534】

Manual — Fire-mode operation and suppressed protections — page 275

When 08-48=1, Fire Mode is enabled.

 When fire mode is enabled, S6 will be defined to digital input of fire mode (03-0X=47).

When fire mode is enabled, inverter will become to fire mode. No matter inverter is running or

stopping, run and frequency command source will be covered by the setting of fire mode, keypad

display will show “ FIRE ”, some of protect functions will be ignored, please refer the table 4.3.35,

inverter will not stop.

When fire mode (03-0X=47) and outour overload (03-0X=68) function is triggered, the other

digital inputs will be ignored, the parameters just can be read by communication or keypad

display.

 When 08-49=0, pelase disconnect the power first, remove external trigger signal and then

connect the power.

 When 08-49=1, no need to disconnect the power, inverter will become to normal mode, run

and frequency will reture to original setting.

Note: Only Version V1.53 and above will meet the above functions.

Table 4.3.35 These functions will be ignoed when fire mode is triggered

!Danger:

Fire mode:

The drive will run at full speed either in forward or reverse direction and ignore all software

protections until any one of the hardware protection is triggered or drive is damaged to achieve

the requirement of smoke extraction and reduce the hazard to humans.

Each bit of 08-50 presents an input:

08-50= 0 0 0 0 0

: Normal open

s6 1

: Normal close

Notes:

Please set 08-48=0 (fire mode disabled) before setting normal open or normal close contact.

Failure to comply may cause death or serious injury.

 When 08-51=0, motor speed setting will follow 08-52. If the value of 08-52 is 100%, inverter

output frequency will follow the value of 01-02.

 When 08-51=1, motor speed setting will follow PID control; when fire mode is enabled, PID

control will base on 10-47/10-48/10-49 (please refer the setting value of group 10)

 When 08-51=2, frequency reference will become to 4-20mA (default setting of 04-00)

V1.53 andabove source qualification. Fire setsS6DI47; overridesRUN/frequency source and displaysFIRE; whenfire/DI68overloadtriggered otherDIsignored,parametersread-only.49=0poweroff,removeexternaltrigger,repower;1returnnormalafterterminalremoved. Table4.3.35 ignoredfaults hexregister0x2521H codes4OH1,5OL1,6OL2,7OT,25FB,26keypadremoved,28CE,46OH4,49MtrSw,58PF. Source danger statement says fullspeed/ignoreallsoftwareuntilhardwaretripordrive damage, versus selectable51/52 source/settings andlistedfaults; both retained, no safety approval.50bitdiagram shows sixzerosfornormalopen ands6=1normallyclosed; aligns S6 text butbitposition unclear. Disable08-48beforecontactchanges,source death/seriousinjurywarning retained.51=1 PID10-47/48/49;51=2 4–20mA calls04-00defaultthough AI2 usual04-05;flag.

Fire-mode operation and suppressed protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Fire-mode operation and suppressed protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: 4

Fire-mode operation and suppressed protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: 5

Fire-mode operation and suppressed protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: 6

Fire-mode operation and suppressed protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: 7

Fire-mode operation and suppressed protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: 25

Fire-mode operation and suppressed protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: 26

Fire-mode operation and suppressed protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: 28

Fire-mode operation and suppressed protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: 46

Fire-mode operation and suppressed protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: 49

Fire-mode operation and suppressed protections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: 58

Fire-mode operation and suppressed protections table1 — PDF page 275

Source row 0x2521H Fault Description
1 4 OH1 (Heat sink over heat)
2 5 OL1 (Motor overload)
3 6 OL2 (Inverter overload)
4 7 OT (Over torque)
5 25 FB (PID feedback signal error)
6 26 Keypad Removed
7 28 CE (Communication error)
8 46 OH4 (Motor over heat)
9 49 MtrSw (DI Motor Switch Fault)
10 58 PF(Protection error)

Manual — Fire-mode PID loss — page 276

08 – 59: Fire Mode Motor Direction

 When fire mode is enabled, motor direction will base on the setting of 08-59.

08 – 60: Fire Mode Password

 When fire mode is enabled, use can set password in parameter 08-60, please refer the

process of parameter 13-07.

 In order to prevent the parameters of fire mode being modified, keypad display will just show

the related parameters of fire mode when fire mode is enabled. (Parameter 08-48~08-60 will

be read only).

 Parameter 08-60(password of fire mode) and 13-07(parameter password), only one

parameter can be allowed to set at the same time.

 When 08-51=1, PID feedback loss detection function will be opened automatically.

 When fire mode is enabled, if 08-51=1 and then PID feedback, inverter will be stopped after

the setting value of 08-54.

08 - 55 PID Feedback Loss Detection Selection of Fire Mode

 When 08-55=0, output frequency will be fixed on current frequency.

 When 08-55=1, output frequency will be based on the setting value of parameter 08-52.

 When 08-55=2, output frequency will be based on the setting value of parameter 01-02.

When PID feedback value less than 08-53 and then longer than 08-54, inverter will keep running,

but the frequency reference will be switched to 08-55, output frequency will not less than the

setting value of 08-52.

t

t1

FBL

偵測

回授值

PID feedback loss detection

Notes:

If there is no any feedback signal and then feedback loss level also be set to 0%, feedback loss detection

function will not be triggered.

Feedback value

FBL detection

08-60 and13-07password cannotbothset;08-48..60readonlyinfire.08-53level0–100%;54delay0–10s;55loss0holdcurrentfrequency1speed52,2max01-02.08-51=1enablesPIDloss. Onebullet saysinverterstopsafter54;laterparagraph sayskeep running andfrequencyselected55withfloor52. Figfeedbackdip<t54 doesnottrigger,continuousbelow53fort54 triggersFBL. No feedback pluslosslevel0% doesnottrigger. Sourcecontradictionspreserved.

Fire-mode PID loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Fire-mode PID loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 53

Fire-mode PID loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 54

Fire-mode PID loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 55

Fire-mode PID loss table1 — PDF page 276

Source row Source row label Source value or description
1 08 - 53 PID Detection Level of Fire Mode
2 Range 【0~100】%
3 08 - 54 Delay Time of Fire Mode PID Loss
4 Range 【0.0~10.0】Sec
5 08 - 55 PID Feedback Loss Detection Selection of Fire Mode
6 Range 【0】:Keep Running 【1】:Fire Mode Speed(08-52) 【2】:Max. Output Frequency of Motor 1 (01-02)

Manual — Fire-mode AI2 loss — page 277

 When 08-51=2 (AI2), inverter will trigger AI2 feedback loss detection function automatically.

Selection of Fire Mode AI2 Signal Loss (08-58):

 When 08-58=0, output frequency will be fixed on current frequency.

 When 08-58=1, output frequency will be based on the setting value of parameter 08-52.

 When 08-58=2, output frequency will be based on the setting value of parameter 01-02.

If AI2 signal is less than the setting value of 08-56 in 360ms, and the time longer than setting value of

08-57, the frequency reference will be considered to loss.

Analog signal will compare with the previous value at 360ms, if inverter ensure the frequency reference

already loss, frequency reference will base on the value of 08-58.

Following is the description of the Frequency Loss Function:

When the inverter is in operation and the selected analog command source AI2 disappears, the command

will operate according to the setting ratio of 08-58.

The following figure is the operating diagram of analog frequency instruction AI2 when the frequency

Instruction is lost.

t

By 08-58

Setting

360ms

Frequency

Command

AI2 Loss Detection

By AI2

Fig 4.3.76 AI2 frequency reference loss

08-56threshold0–100%;57delay0–10s;58loss0holdcurrentfrequency1speed52,2max01-02. Enabled08-51=2. Fig4.3.76 frequencycommandfallsbelow56,360ms interval tolowplateau,then57delay,lossoutputONandfrequencyramps to58selectedvalue. Textreferencescomparisonwithpreviousvalueat360ms;timingretainedwithout changingtoconventionaltimeout. Captionnumber4.3.76notcorrectedto4.4.

Fire-mode AI2 loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Fire-mode AI2 loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 – 56

Fire-mode AI2 loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 57

Fire-mode AI2 loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 08 - 58

Fire-mode AI2 loss table1 — PDF page 277

Source row Source row label Source value or description
1 08 – 56 Detection Level of Fire Mode AI2 Signal
2 Range 【0~100】%
3 08 - 57 Delay Time of Fire Mode AI2 Signal Loss
4 Range 【0.0~10.0】Sec
5 08 - 58 Selection of Fire Mode AI2 Signal Loss
6 Range 【0】:Keep Running 【1】:Fire Mode Speed(08-52) 【2】:Max. Output Frequency of Motor 1 (01-02)

Manual — Communication parameters — page 278

Group 09: Communication Parameters

The Modbus communication port RJ45 (S+, S-) can be used to monitor, control, program and

trouble-shoot the inverter. The built-in RS-485 can support the following communication protocol:

Modbus communication protocol

BacNet communication protocol (Refer to section 4.7 for more details)

MetaSys communication protocol (Refer to section 4.8 for more details)

Pump in Parallel Connection (Refer to parameter group 23 for more details)

Modbus communication can perform the following operations, independent of the frequency command

selection (00-05) setting and operation command selection (00-02) setting:

09-00station1–31;09-01modes0MODBUS1BacNET2MetaSys3parallelpump.09-02codes0..5=1200/2400/4800/9600/19200/38400bps;03stop0one1two;04parity0none1even2odd;05data0eight1seven.06error0–25.5s;07fault0decel1,1coast,2decel2,3keep,4AI2;08tolerance1–20;09wait5–65ms;10instance1–254. RJ45S+/S−RS485. Operations independent00-05frequency/00-02RUN selection continue279.

Communication parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

Communication parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 09- 00

Communication parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 09- 01

Communication parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 09- 02

Communication parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 09- 03

Communication parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 09- 04

Communication parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 09-05

Communication parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 09- 06

Communication parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 09- 07

Communication parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 09- 08

Communication parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 09- 09

Communication parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Parameter 09- 10

Communication parameters table1 — PDF page 278

Source row Source row label Source value or description
1 09- 00 INV Communication Station Address
2 Range 【1~31】
3 09- 01 Communication Mode Selection
4 Range 【0】: MODBUS 【1】: BacNET 【2】: MetaSys 【3】: PUMP in Parallel Connection
5 09- 02 Baud Rate Setting (bps)
6 Range 【0】: 1200 【1】: 2400 【2】: 4800 【3】: 9600 【4】: 19200 【5】: 38400
7 09- 03 Stop Bit Selection
8 Range 【0】: 1 Stop Bit 【1】: 2 Stop Bits
9 09- 04 Parity Selection
10 Range 【0】: No Parity 【1】: Even Bit 【2】: Odd Bit
11 09-05 Communications Data Bits Selection
12 Range 【0】: 8 bits data 【1】: 7 bits data
13 09- 06 Communication Error Detection Time
14 Range 【0.0~25.5】Sec
15 09- 07 Fault Stop Selection
16 Range 【0】:Deceleration to Stop Based on Deceleration Time 1 【1】:Coast to Stop when Communication Fault Occurs. 【2】:Deceleration to Stop Based on Deceleration Time 2 【3】:Keep Operating when Communication Fault Occurs. 【4】:Run the Frequency Command given by AI2
17 09- 08 Comm. Fault Tolerance Count
18 Range 【1~20】
19 09- 09 Waiting Time
20 Range 【5~65】msec
21 09- 10 Device Instance Number
22 Range 1~254

Manual — RS485 specification and setup — page 279

Monitor inverter signals

Read and write parameters.

Reset fault

Control multi-function inputs

Modbus (RS-485) communication specification:

Communication wiring and setup

(1) Turn off power to the inverter.

(2) Connect communication lines of the controller to the inverter (RJ45).

(3) Turn power on.

(4) Set the required communication parameters via the keypad.

(5) Press DSP/FUN key to go back to the main menu.

(6) If it is over the automatic return time (11-13) and DSP/FUN key is not pressed, reset the parameter

and press DSP/FUN key to go back to the main menu. Or reconnect the inverter.

(7) Start communication between controller and inverter.

Modbus (485) communication architecture

(1) Modbus communication configuration uses a master controller (PC, PLC), communicating to a

maximum of 31 inverters.

(2) The master controller is directly connected to the inverter via the RS-485 interface. If the master

controller has a RS-232, a converter must be installed to convert signals to RS-485 to connect the master

controller to the inverter.

(3) A maximum 31 inverters can be connected to a network, following the Modbus communication

standard.

Communication Parameters:

09-00: Inverter station addresses: Range 1-31

09-02: RS-485 communication baud rate setting

= 0: 1200 bps (bits / second)

= 1: 2400 bps

= 2: 4800 bps

= 3: 9600 bps

= 4: 19200 bps

= 5: 38400 bps

09-03: Stop bit selection

= 0: 1 stop bit

= 1: 2 stop bits

09-04: Parity selection of RS-485 communication

= 0: No parity.

= 1: even parity.

= 2: odd parity.

Continuation278 operations monitor,read/writeparameters,resetfault,controlDIs. Modbus RS485 async,start-stop;table1200–38400bps,sixrates,8datafixed,paritynone/even/odd,even/oddstopfixed1;RTU/ASCII,max31units.8fixedconflicts09-05sevenchoice278. Setup poweroff→connectRJ45→poweron→setkeypadcomms→DSP/FUNtomain→if11-13automaticreturnbeforeDSP/FUNresetparametersandreturnorreconnect→startcomms. MasterPC/PLC;RS232needsconverter.09-00/02/03/04repeatvaluesexactly. Further09-05/protocolprocedures beyond279 remainpending,notwholecommunicationsectioncomplete.

RS485 specification and setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval.

RS485 specification and setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Interface

RS485 specification and setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Communication type

RS485 specification and setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Communication parameters

RS485 specification and setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Communication protocol

RS485 specification and setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and diagram associations retained; not engineering approval. Row group: Number of inverters

RS485 specification and setup table1 — PDF page 279

Source row Items Specification
1 Interface RS-485
2 Communication type Asynchronous (start - stop synchronization)
3 Communication parameters Baud rate: 1200, 2400, 4800, 9600, 19200 and 38400 bps Data Length: 8 bits (Fixed) Parity: options of none, even and odd bit. For even and odd selection stop bit is fixed at 1 bit.
4 Communication protocol Modbus RTU / ASCII
5 Number of inverters Maximum 31 units

Manual — Communication continuation and PID target — page 280

09-05: Communications Data Bits Selection

= 0: 8 bits data

= 1: 7 bits data

09-06: RS-485 communication error detection time

09-07: Stop selection of RS-485 communication failure

= 0: Deceleration to stop by deceleration time 00-15

= 1: Coast to stop

= 2: Deceleration to stop using the deceleration time of 00-26 (emergency stop time)

= 3: Continue to operate (only shows a warning message, press the stop button to stop operation)

= 4: Run the frequency command given by AI2 (After setting the Communication Error Detection Time

(09-06), when RS-485 communication error, the warning message will display, and run the

frequency given by AI2, when stop key is pressed, the inverter stops)

09-08: Comm. fault tolerance count

When the number of communication errors exceeds the value set in parameter 09-08 the inverter will

display the comm. Fault alarm.

09-09: Wait time of inverter transmission

Sets the inverter response delay time. This is the time between the controller message and the start of the

inverter response message. Refer to Fig. 4.4.67. Set the controller receive time-out to a greater value than

the wait time parameter (09-09).

Figure 4.4.67 Communication Message Timing

Group 10: PID Parameters

Operation Pressure Setting (23-02) or Target Value of Flow Meters (PUMP or HVAC function selection)

can be set as PID’s target value only when 10-00=0 and 23-00=1 or 2.

When 10-00=1 or 2, signal source proportional is corresponding to PID target via analog input terminal.

For example, 0~10V is corresponding to the target of 0~100% so given 2V is equivalent with the target

value of 20%.

Completes PDF279:09-05=0eight/1seven bits.09-07=0decel00-15,1coast,2decel00-26emergency,3continuewarning,4AI2after09-06;stopkey applies3/4.09-08 error count exceeds threshold. Fig4.4.67 command end→24-bit interval→09-09 interval→response;prose describes gap09-09.10-00target0keypadPUMP/HVAC requiring23-00=1/2,1AI1,2AI2,3reserved,4parameter10-02,5reserved,6frequency00-05,7multispeed.0–10V=0–100%;2V20%.

Communication continuation and PID target. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

Communication continuation and PID target. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 00

Communication continuation and PID target table1 — PDF page 280

Source row Source row label Source value or description
1 10- 00 PID Target Value Source Setting
2 Range 【0】: Keypad Given (for PUMP or HVAC mode) 【1】: AI1 Given 【2】: AI2 Given 【3】: Reserved 【4】: 10-02 Given 【5】: Reserved 【6】: Frequency Command (00-05) 【7】: Multi-speed Frequency Command

Manual — PID target feedback and enable settings — page 281

For normal use of PID, set 10-00 to 4 and set PID target value in parameter 10-02.

When 10-00=4, in addtition to the percentage setting of 10-02 (PID target value), it allows PID setting

(12-38) in the main screen monitor. The maximum target value is set via parameter 10-33 (PID maximum

feedback value), the decimals are set via parameter 10-34 (PID decimal width) and the unit is set via

parameter 10-35 (PID unit). For example:

When 10-33 = 999, 10-34 = 1, 10-35 = 3 and 10-02 = 10%, then 12-38 = 9.9 PSI displayed in the main

screen monitor. User can also modify the value of 12-38 in the main screen monitor but the maximum

calue is 99.9 PSI (depending on the setting value of 10-33).

10-00=6 (from frequency command), it means the setpoint is the perecnetage of frequency reference

corresponding to the rated frequency. (ie: setpoint = 50 %, if the frequency reference is 30Hz and the rated

frequency is 60Hz). And this frequency source refers to the setting of 00-05.

When 10-00=7, DI multi-speed frequency command (refer to the setting description of parameter group 3)

is proportionally corresponding to PID target via multi-speed stage frequenfy setting of 05-01~05-16.

Note: Speed-stage 1 cannot set PID target value by switching auxiliary frequency via 04-05=0 or 4-10=0.

Note: Parameter 10-00 and 10-01 cannot be set to the same source. If both parameters are set to the

same source the keypad will show a SE05 alarm.

Note: When AI1 - AI2 is minus, it will be set to zero.

PID target value source setting(10-00) / PID feedback value source setting(10-01)

Please confirm parameter 04-00 conform the need (0V~10 V or 4mA~20 mА) if AI2 as PID target or PID

feedback. And check the dip switch from control board to the input type (V or I), please refer to wiring

diagram for more detail.

When 10-03 is set to xxx0b, PID will is disabled; if it is set to xxx1b, PID is enabled.

Note:

-

LCD keypad will be switched automatically (16-00).

Main Screen Monitoring will be changed to PID Setting (12-38).

10-00=4recommendednormalPID;12-38target editable;10-33max/34decimal/35unit. Example33=999,34=1,35=3,02=10% displays9.9PSI max99.9PSI. Source6frequency30Hz/60Hz=50%;7uses05-01..16,stage1cannot switch auxiliary04-05=0or04-10=0.10-01feedback1AI1,2AI2,3reserved,4AI1−AI2;negative differenceclamped0;same inputtarget/feedbackSE05.10-03bit0enable,bit1polarity,bit2derivative error/feedback,bit3PID/addfreq. AI2voltage/currentcheck04-00andDIP;LCD16-00automatic and12-38main.

PID target feedback and enable settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

PID target feedback and enable settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 01

PID target feedback and enable settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 02

PID target feedback and enable settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 03

PID target feedback and enable settings table1 — PDF page 281

Source row Source row label Source value or description
1 10- 01 PID Feedback Value Source Setting
2 Range 【1】:AI1 Given 【2】:AI2 Given 【3】:Reserved 【4】:AI1 - AI2 Given

PID target feedback and enable settings table2 — PDF page 281

Source row Source row label Source value or description
1 10- 02 PID Target Value
2 Range 【0.0~100.0】%
3 10- 03 PID Control Mode
4 Range 【xxx0b】:PID Disable 【xxx1b】:PID Enable 【xx0xb】:PID Positive Characteristic 【xx1xb】:PID Negative Characteristic 【x0xxb】:PID Error Value of D Control 【x1xxb】:PID Feedback Value of D Cotrol 【0xxxb】:PID Output 【1xxxb】:PID Output + Frequency Command

Manual — PID modes and gains — page 282

-

Sub-Screen Monitoring 1 will be changed to PID Feedback (12-39).

Sub-Screen Monitoring 2 will be changed to Output Frequency (12-17).

At this time, if the setting is disabled, it will be switched automatically back to frequency command as the

main page. When switching to PID setting in the LED keypad, it displays the modes selection of parameter

23-05.

Note: when 23-05=0, set the value in the conditions of 10-33 < 1000 and 10-34=1, or the inverter will

display the signal of PID setting error (SE05).

When 10-03 is set to xx0xb, PID output occurs forward;

When 10-03= xx1xb: PID output is reverse. PID output is chosen to reverse, If PID input is negative, the

output frequency of PID will gain. On the contrary,

When 10-03 is set to x1xxb, PID control for feedback differential value is enabled; if it is set to x0xxb, basic

PID control is enabled. Refer to Fig.4.4.69 and Fig.4.4.70.

When 10-03 is set to 0xxxb, PID output is enabled and it is corresponding to the frequency of 01-02 at

100%.

When 10-03 is set to 1xxxb, PID output and frequency command are enabled. The output percentage of

frequency command (corresponding to the selected main frequency command of 00-05/ 00-06) will be

cumulated when the inverter starts to run, and PID control starts.

PID Adjustments

Gain control: The error signal (deviation) between the input command (set value) and the actual control

value (feedback). This error signal or deviation is amplified by the proportional gain (P) to control the offset

between the set value and the feedback value.

Subscreens12-39feedback/12-17output;LED23-05=0requires10-33<1000 and34=1orSE05.10-03xx0xbforward,xx1xbreverse;x1xxbDfeedback,x0xxbbasic;0xxxbPID100%=01-02,1xxxbaddfreq00-05/06.10-10primarydelay range0–10% printed with percent despite time name.10-25reverse0no/1yes;all other ranges retained in cells.

PID modes and gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

PID modes and gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 04

PID modes and gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 05

PID modes and gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 06

PID modes and gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 07

PID modes and gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 09

PID modes and gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 10

PID modes and gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-14

PID modes and gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-23

PID modes and gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-24

PID modes and gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-25

PID modes and gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-26

PID modes and gains table1 — PDF page 282

Source row Source row label Source value or description
1 10- 04 Feedback Gain
2 Range 【0.01~10.00】
3 10- 05 Proportional Gain (P)
4 Range 【0.00~10.00】
5 10- 06 Integral Time (I)
6 Range 【0.0~100.0】Sec
7 10- 07 Differential Time (D)
8 Range 【0.00~10.00】Sec
9 10- 09 PID Bias
10 Range 【-100~100】%
11 10- 10 PID Primary Delay Time
12 Range 【0.00~10.00】%
13 10-14 PID Integral Limit
14 Range 【0.0~100.0】%
15 10-23 PID Limit
16 Range 【0.00~100.0】%
17 10-24 PID Output Gain
18 Range 【0.0~25.0】
19 10-25 PID Reversal Output Selection
20 Range 【0】: Do not Allow Reversal Output 【1】: Allow Reversal Output
21 10-26 PID Target Acceleration/ Deceleration Time
22 Range 【0.0~25.5】Sec

Manual — Integral differential and PID feedback — page 283

Integral control: The output of this control is the integral of the error signal (difference between set value

and feedback value) and is used to minimize the offset signal that is left over from the gain control. When

the integral time (I) is increased, the system response becomes slower.

Differential control: This control is the inverse from integral control and tries to guess the behavior of the

error signal by multiplying the error with the differential time. The result is added to the PID input.

Differential control slows down the PID controller response and may reduce system oscillation.

Note: Most applications that PID control (fan and pump) do not require differential control.

Refer to Fig. 4.4.68 for PID control operation

Figure 4.4.68 PID Control

PID Control Type

The inverter offers two types of PID control:

(a) PID control with differential feedback: (10-03 = x1xxb)

Make sure to adjust the PID parameters without causing system instability. Refer to Fig. 4.4.69 for PID

control for feedback value differential.

Figure 4.4.69 PID control for feedback differential value

(b) Basic PID control: (10-03 = x0xxb)

This is the basic type of PID control. Refer to the Fig. 4.4.70.

Higher integral time gives slower response. Fig4.4.68 step error: P horizontal,I linear rise,D decays,PID initial fall then rise;no unlabelled numeric timing inferred. Fig4.4.69 x1xxb:target minus (feedback plus derivative of feedback)→P;P branches directly and viaI to positive sum→control→feedback. Derivative feedback is added before subtraction;do not rearrange to basic PID. Basic mode continues284.

Manual — Basic PID and input-source diagrams — page 284

Figure 4.4.70 Basic PID control

PID Setup

Enable PID control by setting parameter 10-03, PID target value (10-00) and PID feedback value (10-01).

10-00: PID target value

= 0: keypad given

= 1: analog AI1 given (default)

= 2: analog AI2 given

= 3: Reserved

= 4:10-02

10-01: PID feedback value

= 1: Analog AI1 given

= 2: Analog AI2 given

Figure 4.4.71 PID input selection

Fig4.4.70 x0xxb:target minus feedback→P;P branches direct/I/D,all positive sum→control. Setup shortlist10-00only0–4 and10-01only1–3 is incomplete relative earlier options. Fig4.4.71 targetPUMP/HVAC0,AI1=1,AI2=2,10-02=4,freq00-05=6→10-26SFS;7multispeed omitted. FeedbackAI1=1,AI2=2,AI1−AI2=4;display10-27/33 conversion distinct from raw feedback.

Manual — Full PID block diagram and tuning — page 285

PID Control Setting

PID control block diagram.

The following figure shows the PID control block diagram.

Figure 4.4.72 PID control block diagram

PID Tuning

Use the following procedures to start PID control,

(1) Enable PID control (set 10-03 to a value greater than "xxx0b").

(2) Increase the proportional gain (10-05) to the highest value possible without causing the system to

become unstable.

(3) Decrease the integral time (10-06) to the lowest value possible without causing the system to become

unstable.

(4) Increase the differential time (10-07) to the highest value possible without causing the system to

The PID control serves to maintain a given process within certain limits whether it is pressure, flow etc. To

do this the feedback signal is compared to the set value and the difference becomes the error signal for

the PID control.

The PID control then responds by trying to minimize this error. The error is multiplied times the value of the

proportional gain set by parameter 10-05. An increased gain value results in a larger error. However, in

any system as the gain is increased there is a point that the system will become unstable (oscillate).

To correct this instability, the response time of the system may be slowed down by increasing the Integral

time set by parameter 10-06. However slowing the system down too much may be unsatisfactory for the

process.

The end result is that these two parameters in conjunction with the acceleration time (01-14) and

deceleration (01-15) times require to be adjusted to achieve optimum performance for a particular

application.

PID output polarity can be selected with parameter 10-03 (setting = xx0xb: PID output forward, setting =

Fig4.4.72 target selector→subtract feedback→P10-05. Feedback gain10-04 then direct x0xxb or feedback+D10-07 x1xxb. P→I10-06→Ilimit10-14 (both ends printed100%)→resetDI switch→sum;P derivative10-07 selected x0xxb,zero x1xxb. Sum→limit10-23 ±100%→delay10-10→polarity +1xx0xb/−1xx1xb→addbias10-09→gain10-24→±200%limit→addfreq00-05if1xxxb→10-25reverse switch0range0..+109%,1range−109..+109% as printed→PIDON. PIDOFF bypassfreq,caption10-03=0,JOG,DI03-00..03-07=29. Tuning raisesP/lowersI/raisesD until stable;prose acceleration01-14/deceleration01-15 retained as reference discrepancy.

Manual — PID limits and fine tuning — page 286

xx1xb: PID output reversal). When the PID output is set for reverse operation the output frequency

decreased when the PID target value increases.

PID feedback value can be adjusted using parameter 10-04 (PID feedback gain) as well as with the analog

input gain and bias for terminal AI1 or AI2.

10-14: PID integral limit: Used to limit the integral output to prevent motor stall or damage to the system

in case of a rapid change in the feedback signal. Reduce the value of 10-14 to increase the inverter

response.

10-23: PID limit: Used to limit the output of the PID control. Maximum output frequency is 100%.

10-10: Primary delay time: Low pass filter situated after the PID limit block that can be used to prevent

PID output resonance. Increase the time constant to a value greater than the resonance frequency cycle

and reduce time constant to increase the inverter response.

10-09: PID bias: Used to adjust the offset of the PID control. The offset value is added to the frequency

reference as compensation. Use parameter 10-24 (PID output gain) to control the amount of

compensation.

In case the PID control output value goes negative, parameter 10-25 (PID reversal output selection) can

be used to reverse the motor direction.

Note: The PID output remains at zero when reverse operation is disabled.

10-26: PID target SFS: Sets the PID target value acceleration and deceleration ramp time. The PID target

SFS can be disabled by setting the multi-function digital inputs 03-00 ~ 03-05 to 36 (PID target SFS is off).

Reduce the acceleration / deceleration time in case load resonance or system instability is encountered.

PID Fine Tuning

All PID control parameters are related to each other and require to be adjusted to the appropriate values.

Therefore, the procedure achieving the minimum steady-state is shown as following:

(1) Increase or decrease the proportion (P) gain until the system is stable using the smallest possible

control change.

(2) The integral (I) reduces the system stability which is similar to increasing the gain. Adjust the integral

time so that the highest possible proportional gain value can be used without affecting the system

stability. An increase in the integral time reduces system response.

(3) Adjust the differential time if necessary to reduce overshoot on startup. The acceleration / deceleration

time can also be used for the same purpose.

Fine-tuning PID control parameters:

(1) Reduce overshoot

In case overshoot occurs, reduce the derivative time

(D) and increase the integral time (I).

Reverse output decreases when target increases.10-04feedbackgain plus analog scaling.10-14lowerlimit increases response;10-23limit100%=maximumfreq.10-10timeconstant>resonancecycle prose despite percent unit282.10-09bias then10-24gain.10-25negativeclampedzero when disabled,reverse enabled otherwise.10-26SFSoffDI03-00..05=36. Overshoot diagram before greater/after less;source advice reduceD/increaseI retained with context.

Manual — PID fine tuning and feedback loss — page 287

(2) Stabilize PID control

To quickly stabilize the PID control, reduce the

integral time (I) and increase the differential time (D)

in case overshoot occurs.

(3) Reduce long-period oscillation

Adjust the integral time (I) in case of long-periodical

system oscillation.

(4) Reduce short-period oscillation

Adjusting the differential time (D) and proportional (P)

gain when experiencing short-periodical oscillation.

The PID control function provides closed-loop system control. In case PID feedback is lost, the inverter

output frequency may be increase to the maximum output frequency.

It is recommended to enable to the PID feedback loss when the PID function is used.

PID feedback loss detection

10-11=0: Disable

10-11=1: Warning

A feedback loss condition is detected when the PID feedback value falls below the value set in parameter

10-12 (PID feedback loss detection level) for the time set in parameter 10-13 (PID feedback loss detection

time). PID feedback loss warning message "Fb" will be displayed on the keypad and the inverter will

continue to operate.

10-11=2: Fault

time). PID feedback loss fault message "Fb” will be displayed on the keypad, the inverter stops and the

fault contact is activated.

Stabilize PID diagram After greater overshoot/Before less;prose reduceI/increaseD in overshoot, opposite286 advice. Longperiod adjustI,shortperiodD/P;unlabelled curve magnitudes not inferred.10-11loss0off,1Fbwarningcontinue,2Fbfaultstop/contact;feedbackbelow10-12 continuously10-13 triggers. Warning may cause maximumfrequency per source.

PID fine tuning and feedback loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

PID fine tuning and feedback loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-11

PID fine tuning and feedback loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-12

PID fine tuning and feedback loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-13

PID fine tuning and feedback loss table1 — PDF page 287

Source row Source row label Source value or description
1 10-11 PID Feedback Loss Detection Selection
2 Range 【0】: Disable 【1】: Warning 【2】: Fault
3 10-12 PID Feedback Loss Detection Level
4 Range 【0~100】%
5 10-13 PID Feedback Loss Detection Time
6 Range 【0.0~10.0】Sec

Manual — PID feedback loss and sleep settings — page 288

Figure 4.4.73 PID feedback loss detection

The PID Sleep function is used to stop the inverter when the PID output falls below the PID sleep level

(10-17) for the time specified in the PID sleep delay time parameter (10-18).

The inverter wakes up from a sleep condition when the PID output (Reference frequency) rises above the

PID wake-up frequency (10-19) for the time specified in the PID wake-up delay time (10-20).

Use parameter 10-29 to enable / disable PID sleep function.

10-29 =0: PID Sleep function is disabled.

10-29 =1: PID sleep operation is based on parameters of 10-17 and 10-18.

10-29 =2: PID sleep mode is enabled by multi-function digital input

Refer to Fig.4.4.74 (a), (b) and (c) for PID sleep / wakeup operation.

Note: Parameter 10-17 is the general start frequency of PID sleep, and it is not applied to the sleep

frequency of constant pressure (parameter 23-10) by PUMP.

*: (When the motor’s maximum output frequency is over than 300Hz, the frequency resolution is

0.1Hz.)

Fig4.4.73 below10-12 dip t1<10-13 does not trigger;longdip triggers after13.10-17sleepfreq0–599Hz,18delay0–255.5s,19wakefreq0–599Hz,20delay0–255.5s,29sleep0off1on2DI,40compensation0off1on. Sleepoutputbelow17for18;wakePIDreferenceabove19for20.10-17 is not pump constant-pressure23-10. Resolution.1Hz if motor max>300Hz.

PID feedback loss and sleep settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

PID feedback loss and sleep settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-17

PID feedback loss and sleep settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-18

PID feedback loss and sleep settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-19

PID feedback loss and sleep settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-20

PID feedback loss and sleep settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-29

PID feedback loss and sleep settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-40

PID feedback loss and sleep settings table1 — PDF page 288

Source row Source row label Source value or description
1 10-17 *Start Frequency of PID Sleep
2 Range 【0.00~599.00】Hz
3 10-18 Delay Time of PID Sleep
4 Range 【0.0~255.5】Sec
5 10-19 *Frequency of PID Waking up
6 Range 【0.00~599.00】Hz
7 10-20 Delay Time of PID Waking up
8 Range 【0.0~255.5】Sec
9 10-29 PID Sleep Selection
10 Range 【0】: Disable 【1】: Enable 【2】: Set by DI
11 10-40 Compensation Frequency Selection of PID Sleep
12 Range 【0】: Disable 【1】: Enable

Manual — Sleep and compensation diagrams — page 289

Figure 4.4.74: (a) PID control bock diagram

Figure 4.4.74: (b) Timing diagram PID sleep / wakeup

Figure 4.4.74: (c) Timing diagram of PID sleep compensation frequency/ wakeup

Notes:

-

Refer to Fig. 4.4.74: (b) for parameter 10-40=0. The PID sleep timer is enabled when the output

frequency (Fout) falls below the PID sleep frequency (10-17). When the sleep timer reaches the

set PID sleep delay time (10-18) the inverter will decelerate to a stop and enter the sleep mode.

Refer to Fig.4.4.74: (c) for parameter 10-40=1. The PID sleep timer is enabled when the output

frequency (Fout) falls below the PID sleep frequency (10-17). The output frequency changes with

the reference frequency (Fref) when the sleep timer reaches the set PID sleep delay time (10-18),

the motor will run gradually to PID sleep frequency set by 10-17. (It is applicated in the occasion of

fixed frequency.)

While sleep mode is active and the motor has stopped, the internal PID control is still in operating.

When the reference frequency increases and exceeds the wakeup frequency parameter 10-19 for

the time specified in the wakeup delay time parameter 10-20, the inverter will restart and the

output frequency will ramp up to the reference frequency.

Ex:

If wakeup frequency < sleep frequency, start upon sleep frequency and the inverter gets into sleep

mode by wakeup frequency.

If wakeup frequency > sleep frequency, start upon wakeup frequency and the inverter gets into

Fig4.4.74a target minus feedback→PID→sleep/wake→softstart→Fout;PIDOFF bypass. b40=0outputbelow17 starts18timer thenstop;PIDreference continues,above19for20 ramps again. c40=1after18output brieflyfalls then rises to17plateau until wake. Examplewake<sleep starts at sleep/sleeps at wake;wake>sleep starts at wake/sleeps at sleep, sentence continues290.

Manual — Sleep restrictions and feedback scaling — page 290

sleep mode by sleep frequency.

Ex1:

Sleep mode is only allowed in positive direction and if 10-25=1 (Allow Reversal Output), the sleep

mode needs to be turned off.

-

Parameter 10-00 and 10-01 can not be set in the same source. If they are set in the same value,

“SE05” (PID selection error message) will be displayed in the keypad.

When PID sleep selection is enabled or set by DI (10-29= 1 or 2) and PID reversal output selection

(10-25)=1 (allow reversal output), “SE05” (PID selection error message) will be displayed in the

keypad.

When PID sleep selection is enabled ot set by DI (10-29= 1or 2) and PID control mode (10-03) =

1xxxb, “SE05” (PID selection error message) will be displayed in the keypad.

Note: When 23-00=1 (Pump), if PID sleep disable, most pump function will be affected.

Parameter 10-22 will be enabled when 23-00=1 (PUMP) and 10-03=xxx1b:PID enable.

When output frequency ≧ 10-22, PID Group 1 control the function, (P) Proportional Gain, (I) Integral

Time, and (D) Differential Time are 10-05 / 10-06 and 10-07, to reduce the error between command and

actual value.

When output frequency <10-22, PID Group 2 controls the function, (P) Proportional Gain, (I) Integral

Time, and (D) Differential Time are 10-36 / 10-37 and 10-38, to reduce the error between command and

PID Feedback Display Scaling

The PID feedback signal can be scaled to represent actual engineering units. Use parameter 10-33 to set

the feedback signal gain for the feedback signal range maximum and parameter 10-27 to the feedback

signal minimum.

Example: 0-10V or 4-20mA feedback will be displayed as pressure, use 10-27 to set the pressure for 0V or

4mA feedback signal and use 10-33 to set the pressure for 10V or 20mA.

Refer to the Fig.4.4.75 for displaying the unit conversion.

Figure 4.4.75 Feedback signal scaling

Example: Feedback signal: 0V = 0% = 1.0 PSI

10V = 100% = 20.0 PSI

Parameter setting: 10-27 = 10 (0% feedback)

10-33 = 200 (100% feedback)

Completes289. Sleeppositiveonly;reverse10-25=1requiresdisable. SE05sameinputtarget/feedback;29=1/2plus25=1;29=1/2plus03=1xxxb. Pump23-00=1sleepdisable affects most pump functions.10-22range0–599 has no printed unit;with pump/PIDenabled frequency≥22 usesPID1 gains05/06/07,below usesPID2 36/37/38. Fig4.4.75 displaylinear0V/4mA→10-27bias and10V/20mA→10-33max. Example1.0PSI/20.0PSI requires27=10,33=200.

Sleep restrictions and feedback scaling. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

Sleep restrictions and feedback scaling. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-22

Sleep restrictions and feedback scaling. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-27

Sleep restrictions and feedback scaling table1 — PDF page 290

Source row Source row label Source value or description
1 10-22 Start Level of PID Enable
2 Range 【0~599.00】

Sleep restrictions and feedback scaling table2 — PDF page 290

Source row Source row label Source value or description
1 10-27 PID Feedback Display Bias
2 Range 【0~9999】

Manual — PID limits switching and display — page 291

PID target value will be limited to the upper and lower limit range of PID target.

10-32=0: PID 1 function is enabled.

PID target value is set by 10-02 and proportional gain, integral time and differential time are set by 10-05,

10-06 and 10-07.

10-32=1: PID 2 function is enabled.

PID target value is set by 10-02 and proportional gain, integral time and differential time are set by 10-36,

10-37 and 10-38.

10-32=2: Set by Digital Input

If the digital input terminal is enabled (digital multi-function terminal is set to 54), PID1 will switch to PID2.

10-32=3: Set by RTC

When RTC timer is enabled, PID1 will switch to PID2.

Function of PID maximum feedback value is the 100% corresponding value of 10-02.

Function of PID decimal width enables the user to set the decimal point.

For example, if it is set to 1, the keypad displays the first decimal place XXX.X. If it is set to 2, the keypad

displays the second decimal place XX.XX.

PID unit enables the user to select the unit for PID target vaule.

When 10-35=0, parameter of 12-38 will be used by the unit of %.

10-30upper/31lower0–100%.32selection0PID1,1PID2,2DI54,3RTC;both use target10-02. Group1gains05/06/07,group2gains36/37/38.33maxfeedback1–10000;34decimals0–4 with1XXX.X/2XX.XX;35LCDunit0–24,0displays12-38percentage. Unit codes remain source cells,not expanded beyond source.

PID limits switching and display. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

PID limits switching and display. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-30

PID limits switching and display. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-31

PID limits switching and display. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 32

PID limits switching and display. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 33

PID limits switching and display. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 34

PID limits switching and display. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 35

PID limits switching and display table1 — PDF page 291

Source row Source row label Source value or description
1 10-30 Upper Limit of PID Target
2 Range 【0 ~ 100】%
3 10-31 Lower Limit of PID Target
4 Range 【0 ~ 100】%

PID limits switching and display table2 — PDF page 291

Source row Source row label Source value or description
1 10- 32 PID Switching Function
2 Range 【0】: PID1 【1】: PID2 【2】: Set by DI 【3】: Set by RTC

PID limits switching and display table3 — PDF page 291

Source row Source row label Source value or description
1 10- 33 PID Maximum Feedback Value
2 Range 【1~10000】

PID limits switching and display table4 — PDF page 291

Source row Source row label Source value or description
1 10- 34 PID Decimal Width
2 Range 【0~4】

PID limits switching and display table5 — PDF page 291

Source row Source row label Source value or description
1 10- 35 PID Unit (Only display in LCD Keypad)
2 Range 【0~24】

Manual — PID2 loss frequency and precharge — page 292

Refer to the PID function for more details of PID2 description.

*1: It is new added in inverter software V1.4.

*: (When the motor’s maximum output frequency is over than 300Hz, the frequency resolution is

0.1Hz.)

When the warning of PID feedback disconnection occurs (10-11=1), frequency command output depends

on the parameter 10-39. When the disconnection warning is removed, PID control restores.

When parameter 10-44 is set to precharge frequency and PID control mode is set to be 10-03=XXX1B

(PID enable), the inverter runs by the precharge frequency and stops by the end of precharge time set by

parameter 10-45. When the precharge time stops, the inverter runs by PID control. If PID feedback signal

is equal or higher than the level of precharge target (parameter 10-46), it is not required to wait for the end

of precharge time and the inverter can run by PID control. Refer to the following figure.

Hz

Sec

Fbk

or

PID control

The setting description of parameter 10-00=4 can be referred by parameter 10-46. According to the the

setting value of parameter 10-33, change the upper limit of setting value (parameter 10-46), determine the

decimal places (parameter 10-34) and unit display (parameter 10-35).

36P2gain0–10,37I2time0–100s,38D2time0–10s.39lossfrequency0–599Hz newV1.4;warning11=1 uses39untilrestored;resolution.1ifmax>300.44prechargefreq0–120Hz,45time0–250s,46target0–10000.03xxx1b run44until45expires thenPID;earlyPIDwhenfeedback≥46. Prose stops at endprecharge versus diagram continuesPID retained as ambiguity. Topdiagram frequency44plateau→PIDafter45;bottom earlyPIDatfeedback46.46displaymaximum/decimal/unit via33/34/35.

PID2 loss frequency and precharge. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

PID2 loss frequency and precharge. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 36

PID2 loss frequency and precharge. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 37

PID2 loss frequency and precharge. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 38

PID2 loss frequency and precharge. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 39

PID2 loss frequency and precharge. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-44

PID2 loss frequency and precharge. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-45

PID2 loss frequency and precharge. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10-46

PID2 loss frequency and precharge table1 — PDF page 292

Source row Source row label Source value or description
1 10- 36 PID2 Proportional Gain (P)
2 Range 【0.00~10.00】
3 10- 37 PID2 Integral Time (I)
4 Range 【0.0~100.0】Sec
5 10- 38 PID2 Differential Time (D)
6 Range 【0.00~10.00】Sec

PID2 loss frequency and precharge table2 — PDF page 292

Source row Source row label Source value or description
1 10- 39 *PID Output Frequency Setting during disconnection *1
2 Range 【0.00~599.00】Hz

PID2 loss frequency and precharge table3 — PDF page 292

Source row Source row label Source value or description
1 10-44 Precharge Frequency
2 Range 【0~120.0】Hz
3 10-45 Precharge Time
4 Range 【0~250】Sec
5 10-46 Precharge Target Level
6 Range 【0~10000】

Manual — Fire-mode PID gains — page 293

PID functions of ire mode, please refer to parameter group 08.

10-47Pfiregain0–10,48Ifire0–100s,49Dfire0–10s;group08fire conditions,not interchangeable with generalPID orPID2.

Fire-mode PID gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

Fire-mode PID gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 47

Fire-mode PID gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 48

Fire-mode PID gains. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 10- 49

Fire-mode PID gains table1 — PDF page 293

Source row Source row label Source value or description
1 10- 47 Proportioanl Gain (P) of Fire Mode
2 Range 【0.00~10.00】
3 10- 48 Integral Time (I) of Fire Mode
4 Range 【0.0~100.0】Sec
5 10- 49 Differential Time (D) of Fire Mode
6 Range 【0.00~10.00】Sec

Manual — Direction carrier and cable-length limits — page 294

Group 11: Auxiliary Parameters

If motor operation direction is set to 1 or 2, the motor can only operate in that specific direction. Run

commands in the opposite direction are not accepted.

Forward or reverse commands can be issued via the control terminals or keypad.

Note: The reverse rotation selection can be used in fan and pump application where reverse rotation is

prohibited.

Notes:

(1) Value 1 to 16 represents KHz.

(2) When 11-01=0, variable carrier frequency is used see parameter 11-30~11-32.

(3) For SLV mode, the minimum value of 11-01 is 2 kHz, due to the sample rate, suggest to use 4KHz,

and the motor cable used within 100m.

(4) Setting range is determined by the inverter rating (13-00).

(5) Refer to section 3 inverter derating based on carrier frequency.

(6) A low carrier frequency increases motor noise but reduces motor losses and temperature.

(7) A low carrier frequency decreases RFI, EMI interference and motor leakage current.

Refer to the carrier frequency Table 4.4.11.

Table 4.4.11 Carrier frequency settings

If wire length between the inverter and the motor is too long, the high-frequency leakage current will cause

an increase in inverter output current, which might affect peripheral devices. Adjust the carrier frequency to

avoid this as shown in Table 4.4.12.

Table 4.4.12 Wire length and carrier frequency

-

Reduce the carrier frequency if the torque does not match the speed.

In V/F control mode, the carrier frequency is determined by parameters 11-30 (Carrier frequency

max. limit), 11-31 (Carrier frequency lower limit) and 11-32 (Carrier frequency proportional gain)

after parameter 11-01 is setted to be 0.

11-00=0both,1FWD,2REV;oppositeRUN ignored.11-01=0variable,1–16kHzfixed;SLVminimum2/recommended4,cablewithin100m;rating13-00affectsrange. Table4.4.11 highercarrier lowersmotornoise,increasesinterference/leakage/heat,currentwaveformbad→good→bad. Table4.4.12 <30m(98ft)max16kHz;up to50m(164ft)max10;up to100m(328ft)max5;>100m(>328ft)max2. Preserve up-to wording,do not invent disjoint intervals. V/Fvariable uses30/31/32.

Direction carrier and cable-length limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

Direction carrier and cable-length limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 00

Direction carrier and cable-length limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 01

Direction carrier and cable-length limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Motor noise

Direction carrier and cable-length limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Output current waveform (similar to

sinusoidal wave)

Direction carrier and cable-length limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Noise interference

Direction carrier and cable-length limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Leakage current

Direction carrier and cable-length limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Heat losses

Direction carrier and cable-length limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Carrier frequency

(11-01 value )

Direction carrier and cable-length limits table1 — PDF page 294

Source row Source row label Source value or description
1 11- 00 Direction Lock Selection
2 Range 【0】: Allow Forward and Reverse Rotation 【1】: Only Allow Forward Rotation 【2】: Only Allow Reverse Rotation

Direction carrier and cable-length limits table2 — PDF page 294

Source row Source row label Source value or description
1 11- 01 Carrier Frequency
2 Range 【0】: Carrier Output Frequency Tuning 【1~16】KHz

Direction carrier and cable-length limits table3 — PDF page 294

Source row Carrier frequency 1KHz--6KH—10KHz—16KHz
1 Motor noise High ---------------------- low
2 Output current waveform (similar to sinusoidal wave) Bad ------ Good ------- Bad
3 Noise interference Low ---------------------- high
4 Leakage current Low ---------------------- high
5 Heat losses Low ---------------------- high

Direction carrier and cable-length limits table4 — PDF page 294

Source row Wire length < 30 Meter (98ft) up to 50 Meter (164 ft) up to 100 Meter (328ft) > 100 Meter > 328ft
1 Carrier frequency (11-01 value ) Max. value 16KHz (11-01=16KHz) Max. value 10KHz (11-01=10KHz) Maxi. value 5KHz (11-01=5KHz) Max. value 2KHz (11-01=2KHz)

Manual — Soft PWM settings and interactions — page 295

11-02=0: Soft -PWM control disabled.

11-02=1: Soft -PWM control enabled. Soft-PWM 1 control can reduce the ‘metal’ noise produced by the

motor, more comfortable for the human ear. At the same time, Soft-PWM also limits RFI noise to a

minimum level. The default setting of Soft-PWM control is disabled. When Soft-PWM 1 is enabled, the

maximum carrier frequency is limited to 8 kHz.

When 11-02=2 (Soft PWM 2 enables), users adjusts 2 Phase/ 3 Phase PWM Switch Frequency

(parameter 11-66), detection range at Soft PWM function 2 (parameter 11-67), and detecting start

frequency at Soft PWM function 2 (parameter 11-68) by the sensitivity to the sound.

When the inverter’s output frequency is higher than the setting value of parameter 11-66, the modulation

mode will be switched.

When the inverter’s output frequency is higher than the setting value of parameter 11-68, the inverter

starts the function of noise detection and it adjusts electromagnetic noise coming from the motor run upon

the setting value of parameter 11-67.

Note: When 11-02 = 2, the sum values of parameter 11-01 and parameter 11-67 can not be higher

than the inverter’s upper limit of carrier. For the inverter’s proper run, there is affecting mechanism

among these parameters (11-01, 11-02 and 11-67).

a) If the error occurs in setting value of parameter 11-01, it is because parameter 11-02=2 and

the setting value of parameter 11-01 + that of parameter 11-67 > upper limit of the inverter’s

carrier frequency. Thus, adjust the setting value of parameter 11-02 or that of parameter

11-67.

b) If the error occurs in setting value of parameter 11-67, it is because parameter 11-02=2 and

11-01.

c) When 11-02=2, the error occurs in setting value of parameter 11-01 or parameter 11-67.

Please check the setting values of parameter 11-01 + that of parameter 11-67 > upper limit

of the inverter’s carrier frequency.

d) If the error occurs in setting parameter 11-02=2, it is because the setting value of parameter

11-01 + that of parameter 11-67 > upper limit of the inverter’s carrier frequency. Thus, adjust

the setting value of parameter 11-01 or that of parameter 11-67. Then set parameter 11-02

=2.

11-02=0off,1softPWM1max8kHz/defaultoff,2uses66/67/68.66switchfreq6–60,67detection0–12000,68startfreq6–60;no units printed. Output>66 switchesmodulation;output>68noisedetection67.02=2requires01+67≤uppercarrier per source despite01kHz/67unspecifiedunit;retainfour stated error conditions without inventing conversion.

Soft PWM settings and interactions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

Soft PWM settings and interactions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 02

Soft PWM settings and interactions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 66

Soft PWM settings and interactions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 67

Soft PWM settings and interactions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 68

Soft PWM settings and interactions table1 — PDF page 295

Source row Source row label Source value or description
1 11- 02 Soft PWM Function Selection
2 Range 【0】: Disable 【1】: Soft PWM 1 【2】: Soft PWM 2

Soft PWM settings and interactions table2 — PDF page 295

Source row Source row label Source value or description
1 11- 66 2 Phase/ 3 Phase PWM Switch Frequency
2 Range 【6.00~60.00】

Soft PWM settings and interactions table3 — PDF page 295

Source row Source row label Source value or description
1 11- 67 Detection Range at Soft PWM Function 2
2 Range 【0~12000】
3 11- 68 Detecting Start Frequency at Soft PWM Function 2
4 Range 【6.00~60.00】

Manual — S-curve and jump frequencies — page 296

11-03=0: Automatic carrier frequency reduction during an overheat condition is disabled.

11-03=1: Carrier frequency is automatically lowered in case the inverter heatsink overheats and returns to

carrier frequency set in parameter 11-01 when the inverter temperature returns to normal. See section 3.5

for more information.

The S curve function for acceleration / deceleration is used to reduce mechanical impact caused by the

load during momentary starting and stopping of the inverter. To use the S curve function set the time for

acceleration start point (11-04), acceleration end point (11-05), deceleration start point (11-06) and

deceleration end point (11-07). Refer to Fig.4.4.76 for more information.

Figure 4.4.76 S curve characteristic

Total acceleration and deceleration time when the S curve is used:

Accelerating time = Accelerating time 1 (or 2) + (11-04) + (11-05)

Deceleration time = Deceleration time 1 (or 2) + (11-06) + (11-07)

These parameters allow “jumping over” of certain frequencies that can cause unstable operation due to

resonance within certain applications.

Note: Prohibit any operation within the jump frequency range. During acceleration and deceleration the

frequency is continuous without skipping the jump frequency.

To enable jump frequency 1 – 3 (11-08 – 11-10) set the frequency to a value greater than 0.0 Hz.

Use the jump frequency width (11-11) to create a jump frequency range. Refer to Fig.4.4.77.

11-03=0off,1lowercarrieronoverheat/restore01aftercool.11-04..07share0–2.5s;Fig4.4.76S1startaccel04,S2endaccel05,S3startdecel06,S4enddecel07. Totalaccel=time1or2+(04+05)/2;decel=time1or2+(06+07)/2.11-08..10share0–599Hzjump1..3;11width0–25.5Hz. No steadyoperationinsideband;accel/decel continuous,not frequencyjump. Enableeachfrequency>0.

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 03

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 04

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 05

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 06

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 07

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Shared Range for11-04,11-05,11-06,11-07;0.00–2.50s

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 08

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 09

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11-10

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Shared Range for11-08,11-09,11-10

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11-11

S-curve and jump frequencies. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Range for11-11 jump width

S-curve and jump frequencies table1 — PDF page 296

Source row Source row label Source value or description
1 11- 03 Automatic Carrier Lowering Selection
2 Range 【0】: Disable 【1】: Enable

S-curve and jump frequencies table2 — PDF page 296

Source row Source row label Source value or description
1 11- 04 S-curve Time Setting at the Start of Acceleration
2 11- 05 S-curve Time Setting at the End of Acceleration
3 11- 06 S-curve Time Setting at the Start of Deceleration
4 11- 07 S-curve Time Setting at the End of Deceleration
5 Range 【0.00~2.50】Sec

S-curve and jump frequencies table3 — PDF page 296

Source row Source row label Source value or description
1 11- 08 Jump Frequency 1
2 11- 09 Jump Frequency 2
3 11-10 Jump Frequency 3
4 Range 【0.0~599.0】Hz
5 11-11 Jump Frequency Width
6 Range 【0.0~25.5】Hz

Manual — Jump overlap and manual energy saving — page 297

Figure 4.4.77 Jump frequency operation

Jump frequency via Analog Input.

Set parameter 04-05 (AI2 function selection) or 04-10 (AI2 function selection) to 9 (frequency jump setting

4) for controlling the jump frequency via analog input AI2. Refer to Fig. 4.4.38.

Note: When jump frequency overlap the sum of the overlapped jump frequencies will be used as the jump

frequency range. Refer to Fig.4.4.78.

Figure 4.4.78 Jump frequency overlap

If the keypad is not pressed within the time set by 11-13, it will automatically return to the mode screen.

When it is set to 0, function of automatic return key is off. Press the return key to return to the previous

directory.

Manual energy savings reduces the output voltage for the purpose of saving energy.

To enable manual energy savings set one of the multi-function digital input (03-00 to 03-05) to 20 and

activate the input or use parameter 11-18 to set the manual energy savings activation frequency.

When the output frequency rises above the value set in parameter 11-18 manual energy savings function

is enabled. Setting parameter 11-18 manual energy savings frequency to 0.0 Hz disables the manual

Fig4.4.77 bottom11-10,middle09,top08 withwidth11 andascending/descendinghysteresisarrows;no numeric thresholds inferred. Analogjump4 04-05or04-10=9both calledAI2 bysource. Fig4.4.78overlap shownouterunion;sum-overlap wording retained without arithmeticinference.11-13return0–120s,0off.11-12manualenergygain0–100%;18activation0–599Hz;DI03-00..05=20or18threshold;18=0disables threshold,continues298.

Jump overlap and manual energy saving. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

Jump overlap and manual energy saving. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 13

Jump overlap and manual energy saving. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 12

Jump overlap and manual energy saving. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 18

Jump overlap and manual energy saving table1 — PDF page 297

Source row Source row label Source value or description
1 11- 13 Automatic Return Time
2 Range 【0~120】Sec

Jump overlap and manual energy saving table2 — PDF page 297

Source row Source row label Source value or description
1 11- 12 Manual Energy Saving Gain
2 Range 【0~100】%
3 11- 18 Manual Energy Saving Frequency
4 Range 【0.00~599.00】Hz

Manual — Manual and automatic energy saving — page 298

energy savings frequency activation function. Refer to figure 4.4.88 for more information.

Note: Only use manual energy savings functions in combination with light loads.

Manual energy saving gain (11-12) determines the output voltage of the inverter when manual energy

savings is enabled. Output voltage is percentage gain times the V/F voltage.

Manual energy saving control uses the voltage recovery time (07-23) to change the output voltage

Figure 4.4.79 Manual energy saving operation

In the V/F control mode the automatic energy saving (AES) function automatically adjusts the output

voltage and reduces the output current of the inverter to optimize energy savings based on the load. The

output power changes proportional to the motor load. Energy savings is minimal when the load exceeds

70% of the output power and savings become greater when the load decreases.

AES function is suitable for the load is stable, just like fan or windmill. If the load is variable, please do not

use this function to avoid the output torque is not enough.

The parameter of automatic energy saving function has been set at the factory before shipment. In general,

it is no need to adjust. If the motor characteristic has significant difference from the TECO standard, please

refer to the following commands for adjusting parameters:

Enable Automatic Energy Savings Function

(1) To enable automatic energy saving function set 11-19 to 1.

(2) Filter time of automatic energy saving (11-20)

(3) Commissioning parameter of energy saving (11-21 to 11-22)

In AES mode, the optimum voltage value is calculated based on the load power requirement but is also

affected by motor temperature and motor characteristic.

Completes297. Manual lightloadonly;voltage=V/F×11-12,restores via07-23. Fig4.4.79 RUN ON throughout;energycommandON lowersvoltage atsteadyfrequency,OFFrestores;reference≥18. Text references4.4.88,captions4.4.79.11-19AES0off1on;20filter0–200ms;21voltagelimit0–100%;22adjusttime0–5000ms;23detect0–100%;24coefficient0–655.34. V/Fonly stablelightload;variableloadtorquerisk. Little savingsabove70%outputpower is sourceclaim,notverifiedperformance. Factorynormallynoadjust.

Manual and automatic energy saving. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

Manual and automatic energy saving. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 19

Manual and automatic energy saving. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 20

Manual and automatic energy saving. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 21

Manual and automatic energy saving. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 22

Manual and automatic energy saving. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 23

Manual and automatic energy saving. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 24

Manual and automatic energy saving table1 — PDF page 298

Source row Source row label Source value or description
1 11- 19 Automatic Energy Saving Function
2 Range 【0】: Automatic Energy Saving is Disabled. 【1】: Automatic Energy Saving is Enabled.
3 11- 20 Filter Time of Automatic Energy Saving
4 Range 【0~200】msec
5 11- 21 Voltage Upper Limit of Energy Saving Tuning
6 Range 【0~100】%
7 11- 22 Adjustment Time of Automatic Energy Saving
8 Range 【0~5000】msec
9 11- 23 Detection Level of Automatic Energy Saving
10 Range 【0~100】%
11 11- 24 Coefficient of Automatic Energy Saving
12 Range 【0.00~655.34】

Manual — Automatic energy-saving adjustment — page 299

In certain applications the optimum AES voltage needs to be adjusted in order to achieve optimum energy

savings. Use the following AES parameters for manual adjustment:

11-21: Voltage limit value of AES commissioning operation

Set the voltage upper limit during automatic energy saving. 100% corresponds to the settings of parameter

01-03 (Maximum Output Voltage) depending on the inverter class used. Refer to the Fig.4.4.80.

Figure 4.4.80 Voltage limit value of commissioning operation

11-22: Adjustment time of automatic energy saving

Set sample time constant for measuring output power.

Reduce the value of 11-22 to increase response when the load changes.

Note: If the value of 11-22 is too low and the load is reduced the motor may become unstable.

11-23: Detection level of automatic energy saving

Set the automatic energy saving output power detection level.

11-24: Coefficient of automatic energy saving

The coefficient is used to tune the automatic energy saving. Adjust the coefficient while running the

inverter on light load while monitoring the output power. A lower setting means lower output voltage.

Notes:

not match the inverter rating.

11-21=100%maximum01-03voltage,voltageclasscontextretained. Fig4.4.80 linear throughzero clipped±21;negativeplateau label11-21 withoutminus.22lower samplingtime fasterresponse butlowtime/lightloadunstable.23detectlevel;24lowercoeff lowersvoltage/lightload,too lowstall;defaultbased13-00rating. Fragment Set parameter13-00 and power mismatch retained,not completed by inference.

Manual — Thermal derating and variable carrier — page 300

The automatic de-rating function automatically reduces the output frequency by 30% of the nominal motor

speed when the inverter detects an overheat condition (heatsink).

Automatic de-rating function depends on the automatic carried frequency reduction selection (11-03).

If automatic carrier frequency reduction is disabled (11-03=0), the output frequency is reduced by 30% of

the nominal motor speed when an overheat condition is detected.

If automatic carrier frequency reduction is enabled (11-03=1), the output frequency is reduced by 30% of

the nominal motor speed when the carrier frequency is at its minimum setting.

11-29=0: Auto de-rating selection disabled, carrier frequency is based on 11-01 or 11-03.

11-29=1: Auto de-rating selection is enabled.

Carrier frequency method depends on the selected control mode.

Variable carrier frequency can be adjust with parameter 11-30 ~ 11-32.

K is a coefficient; the value of K is based on the following based on the maximum carrier frequency:

K=1: when 11-30 < 5 KHz

K=2: when 10 KHz > 11-30 ≥ 5 KHz

K=3: when 11-30 ≥ 10KHz

11-29=1reducesfrequency by30%nominalspeed onoverheat,not to30%;03=0immediate,03=1afterminimumcarrier.30max2–16kHz,31min1–16,32gain00–99. TableV/Fvariable+fixedavailable,SLVvariableunavailable/fixedavailable;fixedheader01=2–16. Graphcarrier clipped31/30,slopeFout×32×K;K=1if30<5kHz,2if5≤30<10,3if≥10;Fmax01-02axis.

Thermal derating and variable carrier. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

Thermal derating and variable carrier. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 29

Thermal derating and variable carrier. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 30

Thermal derating and variable carrier. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 31

Thermal derating and variable carrier. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 32

Thermal derating and variable carrier. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: V/F

Thermal derating and variable carrier. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: SLV

Adjacent source context — repeated to preserve continuation:

Thermal derating and variable carrier table1 — PDF page 300

Source row Source row label Source value or description
1 11- 29 Auto De-rating Selection
2 Range 【0】: Disable 【1】: Enable

Thermal derating and variable carrier table2 — PDF page 300

Source row Source row label Source value or description
1 11- 30 Variable Carrier Frequency Max. Limit
2 Range 【2~16】KHz
3 11- 31 Variable Carrier Frequency Min. Limit
4 Range 【1~16】KHz
5 11- 32 Variable Carrier Frequency Proportional Gain
6 Range 【00~99】

Thermal derating and variable carrier table3 — PDF page 300

Source row Control Mode Variable Carrier Frequency (11-01 = 0) Fixed Carrier Frequency (11-01 = 2-16 kHz)
1 V/F Available Available
2 SLV Not available Available

Manual — Carrier restrictions and overvoltage settings — page 301

Notes:

can be selected to reduce the carrier frequency based on output frequency.

range will appear on the keypad.

ignored and the carrier frequency will be set at the highest limit (11-30).

Overvoltage suppression is used for the application of likely causing to energy recharge.

Example: there are two situations causing excessive energy to recharge the inverter in stamping

application

(1) When cam clutch is not engaged, the motor will accelerate and start flywheel. When motor decelerates,

the rotation speed will higher than motor speed owing to the large flywheel’s inertia and then recharge

the inverter.

(2) When cam clutch is engaged, the motor will start flywheel and compress the spring. When the highest

point of the cam moves beyond its center, the spring will release the power to the flywheel and

excessive energy output recharge the inverter.

VariableV/Fconstant speed/torque.32>6and30<31→SE01;31>30 ignoresmin/clampsmax. Fixed01=2–16ignores30..32;SLVmaxfixed30 statement retained despite this.11-28OVP2gain1–200%,33rise.1–10V,34fall.1–10V,35deadband0–99V,36gain0–1,37freqlimit0–599Hz;38decelstart200V200–400V/400V400–800V,39decelend200V300–400V/400V600–800V;40off0,modes1/2/3. Resolution.1ifoutput>300. Stampingcamdisengaged flywheeloverrun/engagedspringreturnsenergy are exampleconditions.

Carrier restrictions and overvoltage settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

Carrier restrictions and overvoltage settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 28

Carrier restrictions and overvoltage settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 33

Carrier restrictions and overvoltage settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 34

Carrier restrictions and overvoltage settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 35

Carrier restrictions and overvoltage settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 36

Carrier restrictions and overvoltage settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 37

Carrier restrictions and overvoltage settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 38

Carrier restrictions and overvoltage settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 39

Carrier restrictions and overvoltage settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 40

Adjacent source context — repeated to preserve continuation:

Carrier restrictions and overvoltage settings table1 — PDF page 301

Source row Source row label Source value or description
1 11- 28 Frequency Gain of Overvoltage Prevention 2
2 Range 【1~200】%
3 11- 33 Rise Amount of DC Voltage Filter
4 Range 【0.1~10.0】V
5 11- 34 Fall Amount of DC Voltage Filter
6 Range 【0.1~10.0】V
7 11- 35 Dead band Level of DC Voltage Filter
8 Range 【0.0~99.0】V

Carrier restrictions and overvoltage settings table2 — PDF page 301

Source row Source row label Source value or description
1 11- 36 Frequency gain of OV prevention
2 Range 【0.000~1.000】
3 11- 37 * Frequency limit of OV prevention
4 Range 【0.00~599.00】Hz
5 11- 38 Deceleration start voltage of OV prevention
6 Range 200V :【200~400】V 400V :【400~800】V
7 11- 39 Deceleration end voltage of OV prevention
8 Range 200V :【300~400】V 400V :【600~800】V
9 11- 40 OV prevention selection
10 Range 【0】: Disable 【1】: OV prevention Mode 1 【2】: OV prevention Mode 2 【3】: OV Prevention Mode 3

Manual — Stamping regeneration and OVP diagram — page 302

Figure 4.4.80.a Stamping Operation

Over-voltage prevention (OVP) function monitors the DC-bus voltage and adjusts the speed reference,

acceleration and deceleration rate, to prevent the inverter from tripping on an overvoltage.

When the speed reference is reduced, the motor will start to decelerate. When the inverter is operating at a

fixed output frequency and excessive regenerative energy back to the inverter is detected the inverter will

accelerate the motor in order to reduce the DC-bus voltage. Refer to figure 4.4.80.b.

Figure 4.4.80.b operation

When 11-40=1: OV prevention Mode 1

1) DC voltage filter is used to provide a stable reference value for determining the change in DC voltage

change during regenerative operation.

the DC voltage exceeds 11-33 +11-35 (DC Voltage Filter Deadband Level), the output of the filter will

increase.

DC voltage exceeds 11-33 +11-35 (DC Voltage Filter Deadband Level), the output of the filter will

decrease.

Fig4.4.80a inverter→motor→gearbox→flywheel/cam/spring;motoringFout>Fmotor,overhaulFout<Fmotor. bmode1 rawDCminusfiltered33/34/35→gain36→limit37→OVPaccel/decel;mode2rawbus/gain28→OVP2time→limit37. ChosenaddedtoSFSfreq,40=0bypass.12-20shownbeforefilter yet303describesfilteroutput. Bothriseandfallproseconditions exceed11-33+11-35 althoughfall34;retainconflict.

Manual — OVP voltage/time relationship — page 303

filtering increase rate (11-33).

2) When the inverter is operation at a fixed output frequency, the OVP function will monitor the DC-bus

voltage to detect regenerative operation.

In case of a regenerative condition the inverter calculates the delta DC bus voltage value and multiplies

the value with parameter 11-36, the result is added to the frequency reference accelerating the motor to

prevent on an overvoltage condition.

When the regenerative energy decreases, the inverter output frequency will return to the actual frequency

reference. Deceleration rate is based on the DC voltage, as shown in Figure 4.4.80.c.

Figure 4.4.80.c OVP deceleration time

3) When the inverter is stopped, the deceleration rate can be set with parameter 00-15 (Tdec1). In case

the DC voltage is too high, the inverter will decelerate based on the OVP deceleration time as shown in

Figure 4.4.92.

rate in 00-22 (Tdec3).

delta DC voltage of becoming too large.

based on the set value of 00-24 (Tdec4)

4). Enable the OVP function with parameter 11-40 set to 1 or 2. The following parameter default values will

be changed when the OVP function is enabled:

00-14(Tacc1)= 5.0 Sec(the frequency reference acceleration rate when DC voltage is too high.)

00-22(Tdec3)= 20.0 Sec(low setting point of OVP deceleration rate).

00-24(Tdec4)= 100.0 Sec(high setting point of OVP deceleration rate).

Note: S curve should be disabled when using the OVP function (11-04~11-07=0.0sec).

Prosefilteroutput12-20,34>33recommended;deltaV×36 addedfrequency. Fig4.4.80c example700Vstart38→Tdec3 00-22,750Vstop39→Tdec4 00-24,linearbetween;examplevoltagepointsnotuniversalbothclasses. STOPnormally00-15,highVusesOVPtime;proseFig4.4.92versus80c.40=1/2changesdefaults00-14accel5s,00-22decel3=20s,00-24decel4=100s.11-04..07=0disablesScurves.

Manual — OVP modes and frequency loss — page 304

When 11-40=2: OV prevention Mode 2

The process of OV prevention mode 2 is the same as that of OV prevention mode 1 but it strengthens

more the part of DC BUS over the deceleration stop voltage of OV prevention (11-39) in Fig.4.4.80.c. It can

accelerate frequency compensation to avoid OV protection by increasing frequency gain of OV prevention

2 (11-28).

When 11-40 =3 (OV Prevention Mode 3), user can temporarily increase output frequency to avoid OV

occurring and it will be not higher than the maximum output frequency of motor 1. Thus, adjust parameter

01-02 (maximum output frequency of motor 1) depending on the application.

Adjustment modes

If OV still occurs in OV prevention mode 3, increase the setting value of parameter 11-64 in 0.1 units.

When the setting value of parameter 11-64 is higher, the speed and the current increase more.

A reference frequency loss is detected when the frequency command falls 90% within 360ms.

When 11-41=1, main frequency command continuously compares with the previous value occurring in 360

ms.

When the frequency loss occurs, inverter will operate depending on the following estimated frequency

command.

Frequency command after frequency loss = the maximum output frequency of motor 1 (01-02) × the level

set in parameter 11-42

Descriptions of frequency loss function:

1) When inverter is on operation and source of selected analog command disappears, the command acts

depending on the setting of parameter 11-42.

2) When reference command restores to the level prior to frequency loss, inverter will restore to the

previous state.

Notes:

  1. Frequency command (11-42) is corresponding to the maximum output frequency of motor 1 (01-02)

when reference frequency disappears.

  1. The disappearance of reference frequency is only for the use of analog signal (1: AI1; 7:AI2) from the

selection of main frequency source (00-05).

Refer to Fig.4.4.81 for the process diagram of multi-function digital output (03-11~03-12) when reference

frequency loss occurs.

40=2strongerabove39;increase28gain.11-64accelgain.1–10,65targetV200V200–400V/400V400–800V.40=3temporarilyincreasesfrequencycapped01-02;OVincrease64by.1,highergainincreasesspeed/current.11-41=0decelstop,1use42level0–100%;losscommandfalls90%within360ms;frequency=01-02×42%;restoreswhencommandreturnspriorlevel. Onlyanalog00-05=1AI1or7AI2. Fig4.4.81 relay03-11/12 continues PDF305 outsidepart.

OVP modes and frequency loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval.

OVP modes and frequency loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 64

OVP modes and frequency loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 65

OVP modes and frequency loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 41

OVP modes and frequency loss. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Page-specific source conflicts and visual associations retained; not engineering approval. Row group: Parameter 11- 42

OVP modes and frequency loss table1 — PDF page 304

Source row Source row label Source value or description
1 11- 64 Acceleration Speed Gain Adjustment
2 Range 【0.1~10.0】
3 11- 65 Target Main Circuit Voltage
4 Range 200V :【200~400】V 400V :【400~800】V

OVP modes and frequency loss table2 — PDF page 304

Source row Source row label Source value or description
1 11- 41 Reference Frequency Loss Detection
2 Range 【0】 : Deceleration to Stop when Reference Frequency Disappears 【1】 : Operation is Set by 11-42 when Reference Frequency Disappears
3 11- 42 Reference Frequency Loss Level
4 Range 【0.0~100.0】%

Manual — Frequency-loss continuation and hold controls — page 305

Figure 4.4.81 Operation for reference frequency loss

The hold function is used to temporarily hold the reference frequency in order to prevent stalling the motor

or preventing an over current condition during starting or stopping due to load conditions.

During start the inverter will operate at the hold frequency at start for the time specified in the parameter

11-44 in order to establish the magnetic flux.

Note: The acceleration of deceleration time does not include the start and stop hold time. Refer to the Fig.

4.4.82.

Figure 4.4.82 Reserved function

When the inverter is in stop mode, this function can also be used to prevent wind milling. In addition, it can

be used for the purpose of braking using the motor to consume the braking energy resulting in a better

controlled stop. Refer to the DC brake parameter 07-16 for DC braking during start.

Notes:

Fmin (01-08).

Completes PDF304 Fig4.4.81:frequency100% falls through10% tozero over20ms asprinted,not360ms previousprose. Relay03-11/12/39=26 turnsON atfallend/OFFwhenrisebegins,notwhen100%restored.11-43/45holdfreq0–599Hz,44/46times0–10s;accel/decel excludesholdtime. Fig4.4.82 RUNON→ramp→43plateaufor44→rampcommand;RUNOFF→rampdown→45plateaufor46→zero. Caption Reservedfunction despite activefeature. Startdisabledif43<01-08;stopconditionnextpage.

Frequency-loss continuation and hold controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Frequency-loss continuation and hold controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 43

Frequency-loss continuation and hold controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 43

Frequency-loss continuation and hold controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 44

Frequency-loss continuation and hold controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 44

Frequency-loss continuation and hold controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 45

Frequency-loss continuation and hold controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 45

Frequency-loss continuation and hold controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 46

Frequency-loss continuation and hold controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 46

Frequency-loss continuation and hold controls table1 — PDF page 305

Source row Source row label Source value or description
1 11- 43 Hold Frequency at Start
2 Range 【0.0~599.0】Hz
3 11- 44 Frequency Hold Time at Start
4 Range 【0.0~10.0】Sec
5 11- 45 Hold Frequency at Stop
6 Range 【0.0~599.0】Hz
7 11- 46 Frequency Hold Time at Stop
8 Range 【0.0~10.0】Sec

Manual — Kinetic energy backup — page 306

Fmin (01-08).

KEB function can be used to keep the inverter from tripping on a under voltage condition due to a

momentary power-loss. To enable the KEB function set parameter 11-47 to a value greater than 0.0 sec.

Upon detection of a power-loss the inverter uses the KEB deceleration time (11-47) to decelerate the

motor and using the regenerative energy from the motor to maintain the DC-bus at a nominal level.

11-48: KEB detection level

If the DC-bus voltage falls below the value set in 11-48, the KEB is activated and the inverter starts

decelerating according to the value set in 11-47.

To accelerate back to the original output frequency one of the digital inputs (03-00 to 03-05) set for 48

(KEB acceleration) has to be activated and the DC voltage has to rise above 11-48 + delta V (Delta V =

+10V for 200V series, Delta V = +20 V for 400V series).

Refer to the example in Fig.4.4.83.

DC Bus

KEB Detection Level

10V for 200V series

20V for 400V series

Output

Frequency

Run

Command

KEB

Re-acceleration

operation

Figure 4.4.83 KEB operation

Completes305:stopholdinactive45<01-08.11-47KEB0–25.5s,enabled>0;48level200V190–210V,400V380–420V. Busbelow48startdecel47usingregenerativeenergy. RecoveryrequiresDI03-00..05=48 ANDbus>48+10V200V/+20V400V. Fig4.4.83 RUNremainsON;frequencydeceleratesduringbusdip;KEBreaccelcommandstartsrecovery afterbusupperhysteresis,returnsoriginalfrequency;no unnamedtimeinferred.

Kinetic energy backup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Kinetic energy backup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 47

Kinetic energy backup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 47

Kinetic energy backup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 48

Kinetic energy backup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 48

Kinetic energy backup table1 — PDF page 306

Source row Source row label Source value or description
1 11- 47 KEB Deceleration Time
2 Range 【0.0~25.5】Sec
3 11- 48 KEB Detection Level
4 Range 200V :【190~210】V 400V :【380~420】V

Manual — Zero-speed braking energy reset and STOP — page 307

11-51: Operation selection of zero-speed braking

In V/F control mode, the DC braking operation can be used to the motor shaft.

Set 11-51 to select zero-speed braking operation to 1 to enable this function.

To use DC braking operation set parameter 00-02 (operation command selection) to 1 and parameter

00-05 (frequency reference selection) to 1, the operation command and frequency reference are now set

for external control. When the frequency reference is 0V (or less than 4mA), and the operation command is

turned on, the zero-speed ‘DC’ braking operation is activated and holding torque is generated using DC

braking.

Refer to Fig.4.4.84 for more information on zero-speed DC braking operation.

Note: DC braking 07-07 is limited to 20% of the inverter rated current.

Figure 4.4.84 Zero-speed braking operation

Reset the cumulative energy (KWHr) (12-67) and the cumulative energy (MWHr) (12-68) via parameter

11-54.

11-55= 0: Stop button disabled when operation command is set for terminals (00-02=1) or communication

(00-02=3).

11-55= 1: Stop button enabled.

11-51=1 V/F;00-02=1externalRUN,00-05=1externalfreq;0V/<4mAwithRUNONholdsDCbrake07-07limited20%inverterratedcurrent. Fig4.4.84 zerolevellargerof01-08/07-06;DCinjectionONduringRUNonlybeforefreqriseandafterfreqfall.11-54=1resets12-67KWHr/12-68MWHr;0retains.11-55=0STOPdisabledfor00-02=1terminals/3communications;1enabled.

Zero-speed braking energy reset and STOP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Zero-speed braking energy reset and STOP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 51

Zero-speed braking energy reset and STOP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 51

Zero-speed braking energy reset and STOP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 54

Zero-speed braking energy reset and STOP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 54

Zero-speed braking energy reset and STOP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 55

Zero-speed braking energy reset and STOP. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 55

Zero-speed braking energy reset and STOP table1 — PDF page 307

Source row Source row label Source value or description
1 11- 51 Braking Selection of Zero Speed
2 Range 【0】: Disable 【1】: Enable

Zero-speed braking energy reset and STOP table2 — PDF page 307

Source row Source row label Source value or description
1 11- 54 Initialization of Cumulative Energy
2 Range 【0】: Do not Clear Cumulative Energy 【1】: Clear Cumulative Energy

Zero-speed braking energy reset and STOP table3 — PDF page 307

Source row Source row label Source value or description
1 11- 55 STOP Key Selection
2 Range 【0】: Stop Key is Disabled when the Operation Command is not Provided by Keypad. 【1】: Stop Key is Enabled when the Operation Command is not Provided by Keypad.

Manual — Keypad change and reference retention — page 308

11-56= 0: Changing the reference frequency on the keypad in UP/DOWN control requires the ENTER

button to be pressed for the inverter to accept the modified reference frequency.

11-56= 1: Changing the reference frequency on the keypad in UP/DOWN control immediately changes the

reference frequency and there for the output frequency.

Note: The reference frequency can be changed (up or down) via the keypad or by setting one of

multi-functional digital input terminals (03-00 to 03-05) to 8 and 9. Refer to instructions of

(03-00 to 03-05 = 8 or 9).

This function is enabled only when one of multi-function digital input terminals (03-00 to 03-07) is set to 11

(ACC / DEC Inhibition command).

11-58= 0: When ACC / DEC inhibition command is enabled, the motor will stop accelerating or

decelerating and the frequency at the moment will be used as frequency command. If ACC / DEC inhibition

command is disabled or stop command enabled, the frequency command will set to original frequency.

Besides, when stop command enabled, or the power is cut off and reset. The frequency will be set to 0 Hz

Note: If ACC/DEC inhibition command is enabled before running, it will display STP0 after running, due to

there is no reference frequency record.

11-58= 1: When ACC / DEC inhibition command is enabled, the output frequency will be recorded and to

be used as frequency command. When it switches to stop or the power is cut off and reset, the ACC / DEC

inhibition command is still enabled, the frequency command is still recorded and the frequency command

is set to the frequency that was recorded.

Please refer to the following figure.

11-56=0ENTERrequiredtoapplykeypadfrequencychange;1immediate;DI03-00..05=8/9alternative.11-58onlywithinhibitionDI03-00..07=11asprinted.0holdswhileinhibitedbutreleasedcommandreturnsoriginal;stop/powerresetzero. InhibitbeforerunwithoutrecordSTP0.1retainsrecordthroughstop/powercycleifinhibitremains. Diagramfirstinhibitcreatesaccelplateau,secondcreatesdecelplateau;RUNOFFstops;powerOFF/ONthenRUNONrampsbacktoheldfrequencyalthoughreferencechanged.

Keypad change and reference retention. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Keypad change and reference retention. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 56

Keypad change and reference retention. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 56

Keypad change and reference retention. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 58

Keypad change and reference retention. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 58

Keypad change and reference retention table1 — PDF page 308

Source row Source row label Source value or description
1 11- 56 UP/DOWN Selection
2 Range 【0】: When UP/DOWN in Keypad is Disabled, it will be Enabled if Pressing ENTER after Frequency Modification. 【1】: When UP/DOWN in Keypad is Enabled, it will be Enabled upon Frequency Modification.

Keypad change and reference retention table2 — PDF page 308

Source row Source row label Source value or description
1 11- 58 Record Reference Frequency
2 Range 【0】: Disable 【1】: Enable

Manual — Oscillation and flux-strengthening — page 309

Gradually increase the setting value with the unit of 0.01 when the motor is driven leading to the

occurrence of oscillation under the state of normal duty.

Function of prevention of oscillation upper limit is required to be within the setting value.

Adjust the response of oscillation function. That is, adjust once delay time parameter of prevention

oscillation function.

When 11-62 is set to 0 and 1, the response to prevention oscillation is slower.

When 11-62 is set to 2, the response to prevention oscillation is faster.

11-63=0: It has no function of flux-strengthening, the no-load current of high speed and low speed are the

same.

11-63=1: It has function of flux-strengthening, the torque of low speed is higher, but the no-load current is

also higher, it is suitable for big load in low speed.

Adjust the response of Gain of Preventing Oscillation 3

If vibration with motor in ND mode occurs, please increase by 0.01 unit to set.

It is required to limit the preventing oscillation 3 upper limit within the setting value.

Adjust the response of oscillation 3 function. (Time parameter of adjust preventing oscillation function

delay.)

Refer to the following figure for the setting of parameters 11-72 and 11-73.

11-59gain0–2.50increment.01normalduty;60upper0–100%;61time0–100no unitprinted.62=0/1slower,2faster modes1/2/3.63offequalhigh/lowspeednoloadcurrent,onhigherlowspeedtorque/currentforhighload.69gain3 0–200%,70limit.01–100%,71time0–30000ms;72/73freq.01–300Hz;gaincurvecontinues310.

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 59

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 59

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 60

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 60

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 61

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 61

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 62

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 62

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 63

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 63

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 69

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 69

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 70

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 70

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 71

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 71

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 72

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 72

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 11- 73

Oscillation and flux-strengthening. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 11- 73

Oscillation and flux-strengthening table1 — PDF page 309

Source row Source row label Source value or description
1 11- 59 Gain of Preventing Oscillation
2 Range 【0.00~2.50】

Oscillation and flux-strengthening table2 — PDF page 309

Source row Source row label Source value or description
1 11- 60 Upper Limit of Preventing Oscillation
2 Range 【0~100】%

Oscillation and flux-strengthening table3 — PDF page 309

Source row Source row label Source value or description
1 11- 61 Time Parameter of Preventing Oscillation
2 Range 【0~100】

Oscillation and flux-strengthening table4 — PDF page 309

Source row Source row label Source value or description
1 11- 62 Prevention of Oscillation Selection
2 Range 【0】: Mode 1 【1】: Mode 2 【2】: Mode 3

Oscillation and flux-strengthening table5 — PDF page 309

Source row Source row label Source value or description
1 11- 63 Flux- Strengthening Selection
2 Range 【0】: Disable 【1】: Enable

Oscillation and flux-strengthening table6 — PDF page 309

Source row Source row label Source value or description
1 11- 69 Gain of Preventing Oscillation 3
2 Range 0.00~200.00 %

Oscillation and flux-strengthening table7 — PDF page 309

Source row Source row label Source value or description
1 11- 70 Upper Limit of Preventing Oscillation 3
2 Range 0.01~100.00 %

Oscillation and flux-strengthening table8 — PDF page 309

Source row Source row label Source value or description
1 11- 71 Time Parameter of Preventing Oscillation 3
2 Range 0~30000 ms

Oscillation and flux-strengthening table9 — PDF page 309

Source row Source row label Source value or description
1 11- 72 Switch Frequency 1 for Preventing Oscillation Gain
2 Range 0.01~300.00 Hz
3 11- 73 Switch Frequency 2 for Preventing Oscillation Gain
4 Range 0.01~300.00 Hz

Manual — LED display controls — page 310

Group 12: Monitoring Parameters

Note: The highest bit is used for power-up monitor. The 4 least significant bits can be used to customize

the display sequence see section 4.1.3.

When 12-00= xxx5, PID Feedback is displayed in LED keypad. Parameter 12-01 will take the value of

parameter 10-33 to convert to be five digits display XXX.XX.

For example, when parameter 10-33= 9999,

12-01=0, the default display is 99;

12-01=1, the default display is 99.9;

12-01=2, the default display is 99.99;

if with the setting value of parameter 12-02, when 12-01=1 and 12-02=1, it displays 99.9Pb five

digits; when 12-01=2 and 12-02=2, it displays 9.99FL and tenth digit 9 will be concealed.

Completes309:gain11-69flatuntilfreq11-72,linearfalltozeroat11-73.12-00fivepositions0–7;highestpowerupmonitor,lowestfourcustomsequence. Evenchoicesleft0none2voltage4heatsink6AI1,oddright1current3DCbus5PID7AI2.12-01integer/one/twodecimals;12-02none/Pbpressure/FLflow. Sourceexample10-33=9999 gives99,99.9,99.99 for01=0/1/2;01=1+02=1 displays99.9Pb;01=2+02=2 displays9.99FL,hidesdigit9. Examples not silently normalized.

LED display controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

LED display controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 12- 00

LED display controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Range

Shared source cells (coordinates refer to this table):

LED display controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 12- 01

LED display controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 12- 01

LED display controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 12- 02

LED display controls. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 12- 02

LED display controls table1 — PDF page 310

Source row Parameter/range label Description or even-numbered selection Odd-numbered selection
1 12- 00 Display Screen Selection (LED) ⟦null: no independent source value⟧
2 Range Highest bit => 0 0 0 0 0 <= lowest bit The value range of each bit is 0~7 from the highest bit to the lowest bit, ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ 【0】: No display 【2】: Output Voltage 【4】: heatsink Temperature 【6】: AI1 Value 【1】: Output Current 【3】: DC Bus Voltage 【5】: PID Feedback 【7】: AI2 Value

LED display controls table2 — PDF page 310

Source row Source row label Source value or description
1 12- 01 PID Feedback Display Mode (LED)
2 Range 【0】: Display the Feedback Value by Integer (xxx) 【1】: Display the Feedback Value by the Value with First Decimal Place (xx.x) 【2】: Display the Feedback Value by the Value with Second Decimal Places (x.xx)
3 12- 02 PID Feedback Display Unit Setting (LED)
4 Range 【0】: xxxxx(no unit) 【1】: xxxPb(pressure) 【2】: xxxFL(flow)

Manual — Line speed and digital terminal status — page 311

12-04=0

Inverter displays the line speed at stop, operation or the modification of frequency.

12-04≠0

12-03 is set to the maximum line speed and corresponds to the maximum output frequency.

For example, if the line speed display of 12-03 is 1800, the keypad display is 900 when frequency output is

30Hz.

Terminals S1-S6 are represented using two segments of each digit. Segment turns on when input is active.

The bottom segments of each of the first three digits are used to represent the digital outputs (R1, R2, R3).

Segments turn on when output is active.

When operation command is changed to PLC, press RUN key and it will light up.

Example1: S1~S6, R1, R2 and R3 are ON

Example2: S1~S6, R1, R2 and R3 are OFF

Input Terminal(S6)

Input Terminal(S5)

Input Terminal(S4)

Input Terminal(S3)

Input Terminal(S2)

Input Terminal(S1)

0:OPEN

1:CLOSE

Output Terminal(R3)

Output Terminal(R2)

Output Terminal(R1)

12-03range0–60000RPM;12-04=0outputfreqtablebutline-speedprose;1/2/3/4integer/one/two/threedecimals.03maxlinespeedmatchesmaxoutputfreq;example1800→900at30Hzwithoutmaxfreqspecified.12-05readonly. UppersegmentsS1..S6 activeONlefttoright;bottomfirstthreedigitsR1/R2/R3. LCDninepositionslefttorightR1,R2,R3,S1,S2,S3,S4,S5,S6;0OPEN1CLOSE. PLCcommandRUNkeylightsindicator.

Line speed and digital terminal status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Line speed and digital terminal status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 12- 03

Line speed and digital terminal status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 12- 03

Line speed and digital terminal status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 12- 04

Line speed and digital terminal status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 12- 04

Line speed and digital terminal status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 12- 05

Line speed and digital terminal status. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 12- 05

Line speed and digital terminal status table1 — PDF page 311

Source row Source row label Source value or description
1 12- 03 Line Speed Display (LED)
2 Range 【0~60000】RPM
3 12- 04 Line Speed Display Mode (LED)
4 Range 【0】: Display Inverter Output Frequency 【1】: Line Speed Display at Integer.(xxxxx) 【2】: Line Speed Display at One Decimal Place. (xxxx.x) 【3】: Line Speed Display at Two Decimal Places. (xxx.xx) 【4】: Line Speed Display at Three Decimal Places. (xx.xxx)

Line speed and digital terminal status table2 — PDF page 311

Source row Source row label Source value or description
1 12- 05 Status Display of Digital Input Terminal (LED/LCD)
2 Range Read-only

Manual — Relay-card status displays — page 312

Please refer to parameter group 24.

10-03=xxx1b

1 to 8 Relay card is installed.

24-00=1

24-07=0: Relay is ON and RUN.

Display sequency:

LED display (without output):

LCD display:

0 0

Realy Card(R8)

Realy Card(R7)

Realy Card(R6)

Realy Card(R5)

Realy Card(R4)

Realy Card(R3)

Realy Card(R2)

Realy Card(R1)

0:OPEN

1:CLOSE

LED display (when input and output is active):

R1 R2 R3 R4R5 R6R7 R8

Control board Relay is installed.

24-07=1: Relay is ON and RUN.

Display sequence:

Output Terminal(R3)

Output Terminal(R2)

Output Terminal(R1)

12-81readonlykeypad;10-03xxx1b,24-00=1.24-07=0eight-relaycard:LEDdashesOFF,uppersegmentsR1..R8lefttorightON;LCDrightmosteightpositionsR1..R8lefttoright,0OPEN1CLOSE.24-07=1controlboardrelays:LCDR1/R2/R3 atthreepositionsbeforefive trailingpositions;LEDONexamplecontinues313. No unnamedbits assigned.

Relay-card status displays. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Relay-card status displays. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 12- 81

Relay-card status displays. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 12- 81

Relay-card status displays table1 — PDF page 312

Source row Source row label Source value or description
1 12- 81 Relay Card Display (LED/LCD)
2 Range Readable only (only for keypad)

Manual — Monitor continuation — page 313

LED display (when input and output is active):

R1 R2 R3

Note: Refer to section 4.3 for other monitor parameters 12-11~12-82.

Monitor parameters 12-67 (KWHr) and 12-68 (MWHr) is the display of accumulative energy.

Note: Parameter 11-54 can clear the monitor parameter.

Monitor parameter 12-76 (No-load voltage) is required to refer to the descriptons of parameter

02-09(Motor 1 excitation current) and 17-09 (Motor excitation current).

Completes312:controlboardLEDfirstthreeuppersegmentsR1/R2/R3ON. Monitor12-11..82see4.3.12-67KWHr/68MWHraccumulativeenergyreset11-54.12-76calledNo-loadvoltage refers02-09Motor1excitationcurrent/17-09Motorexcitationcurrent;quantityconflictretained.

Manual — Rating codes and operating hours — page 314

Group 13 Maintenance Function Group

Inverter model

13- 00 display

When 13-02 set to 1, the value of 13-03/13-04 will be cleared.

13-05= 0: Inverter logs the time while the inverter is powered-up.

13-05= 1: Inverter logs the time when the inverter is running.

13-00range00H–FFH separatefromdisplaycodes. Unruledmapping18F510-2xxxmodels and26F510-4xxxmodels transcribed into44 model/codepairs;code201 distinctmodel2001 andhigher2100remains2100. No power inferredfromcode.13-01version0.00–9.99;02=1clears03hours0–23and04days0–65534.05=0counts poweredtime,1counts runningtime.

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 00

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 00

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 01

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 01

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 02

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 02

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 03

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 03

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 04

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 04

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 05

Rating codes and operating hours. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 05

Printed unruled mapping; model and displayed code are distinct; exact source spelling retained. Source mode/version conditions and conflicts retained;not engineering approval.

Printed unruled mapping; model and displayed code are distinct; exact source spelling retained. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 200V series

Printed unruled mapping; model and displayed code are distinct; exact source spelling retained. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 400V series

Rating codes and operating hours table1 — PDF page 314

Source row Source row label Source value or description
1 13- 00 Inverter Rating Selection
2 Range 00H~FFH

Rating codes and operating hours table2 — PDF page 314

Source row Source row label Source value or description
1 13- 01 Software Version
2 Range 0.00-9.99
3 13- 02 Clear Cumulative Operation Hours Function
4 Range 【0】: Disable to Clear Cumulative Operation Hours 【1】: Clear Cumulative Operation Hours
5 13- 03 Cumulative Operation Hours 1
6 Range 【0~23】hours
7 13- 04 Cumulative Operation Hours 2
8 Range 【0~65534】days
9 13- 05 Selection of Accumulative Operation Time
10 Range 【0】: Accumulative time in power on 【1】: Accumulative time in operation

Inverter model to13-00 display 200V series — PDF page 314

Source row Inverter model 13-00 display
1 F510-2001-XXX 201
2 F510-2002-XXX 202
3 F510-2003-XXX 203
4 F510-2005-XXX 205
5 F510-2008-XXX 208
6 F510-2010-XXX 210
7 F510-2015-XXX 215
8 F510-2020-XXX 220
9 F510-2025-XXX 225
10 F510-2030-XXX 230
11 F510-2040-XXX 240
12 F510-2050-XXX 250
13 F510-2060-XXX 260
14 F510-2075-XXX 275
15 F510-2100-XXX 2100
16 F510-2125-XXX 2125
17 F510-2150-XXX 2150
18 F510-2175-XXX 2175

Inverter model to13-00 display 400V series — PDF page 314

Source row Inverter model 13-00 display
1 F510-4001-XXX 401
2 F510-4002-XXX 402
3 F510-4003-XXX 403
4 F510-4005-XXX 405
5 F510-4008-XXX 408
6 F510-4010-XXX 410
7 F510-4015-XXX 415
8 F510-4020-XXX 420
9 F510-4025-XXX 425
10 F510-4030-XXX 430
11 F510-4040-XXX 440
12 F510-4050-XXX 450
13 F510-4060-XXX 460
14 F510-4075-XXX 475
15 F510-4100-XXX 4100
16 F510-4125-XXX 4125
17 F510-4150-XXX 4150
18 F510-4175-XXX 4175
19 F510-4215-XXX 4215
20 F510-4250-XXX 4250
21 F510-4300-XXX 4300
22 F510-4375-XXX 4375
23 F510-4425-XXX 4425
24 F510-4535-XXX 4535
25 F510-4670-XXX 4670
26 F510-4800-XXX 4800

Manual — Parameter locks and password setup — page 315

When 13-06=0, only parameter 13-06 and frequency command parameter in main screen can be set but

other parameters are read-only.

When 13-06=1, only user parameters (00-41~00-56) are enabled. Please refer to the instruction of

parameters 00-41~00-56.

Note: it is only enabled in LCD keypad.

When 13-06=2, all parameters are writable except for the read-only parameters.

Note:

Main frequency setting is 12-16. The value is equal to frequency setting of speed-stage 0 (05-01) in LCD

keypad.

LED Main Frequency can be set in the main frequency display

When the setting value of parameter 13-07 is enabled (13-07 > 0), all the parameters can not be

adjusted except the frequency in main screen so user needs to input the password to adjust it.

Password setting:

First step:

Enter the

function

setting at

1st time

▲

▼

or

READ/

ENTER

DSP/

FUN

13-06=0only13-06/mainfrequencywritable;1user00-41..56LCDonly;2all exceptreadonly. Main12-16equalsstage005-01LCD;LEDmainfreqdisplay.13-07>0locksparameters exceptmainfrequency. Firstsetupdiagram13-07→READ/ENTER→00000→UP/DOWNexample12345→READ/ENTER→End→12345→DSP/FUN13-07. Example12345notdefaultpassword.

Parameter locks and password setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Parameter locks and password setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 06

Parameter locks and password setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 06

Parameter locks and password setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 07

Parameter locks and password setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 07

Parameter locks and password setup table1 — PDF page 315

Source row Source row label Source value or description
1 13- 06 Parameters Locked
2 Range 【0】: Only parameter 13-06 and frequency command parameters in main screen are writable 【1】: Only user parameter is enabled. 【2】: All parameters are writable.

Parameter locks and password setup table2 — PDF page 315

Source row Source row label Source value or description
1 13- 07 Parameter Password Function
2 Range 【00000~65534】

Manual — Password verification diagrams — page 316

Second step:

Enter the

function

setting at

2nd time

▲

▼

or

READ/

ENTER

DSP/

FUN

Password Input:

Password

input

Correct password input

Secondsetup13-07→ENTER00001;example10000wrong→ENTERErr2→10000→DSP/FUN13-07;matching12345→ENTERLOC→12345→DSP/FUN13-07. Passwordinput13-07→ENTER00002;wrong10000→LOC;correct12345→End;bothreturnexamplevalueandDSP/FUNparameter. DistinguishsettingconfirmationErr2fromfailedunlockLOC;no newpasswordset.

Manual — Factory reset selections — page 317

Note: Main frequency setting is 12-16. The value is equal to frequency setting of speed-stage 0 (05-01)

Use parameter 13-08 to initialize the inverter to factory default. It is recommended to write down the

modified parameters before initializing the inverter. After initialization, the value of 13-08 will return to zero

automatically.

13-08=2: 2-wire initialization (220V/440V)

Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse

operation / stop command. Refer to Fig.4.4.1.

Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class).

When 01-00 (V/F curve) set to F, Inverter maximum frequency (01-12) is automatically set to 60Hz.

13-08=3: 3-wire initialization (220V/440V)

Multi-function digital input terminal S5 controls the forward / reverse direction, and terminals S1 and S2 are

set for 3-wire start operation and stop command.Refer to Figure 4.4.2 and Figure 4.4.3 for 3-wire type

operation mode.

13-08=4: 2-wire initialization (230V/415V)

Inverter input voltage (01-14) is automatically set to 230V (200V class) or 415V (400V class).

When 01-00 (V/F curve) set to F, Inverter maximum frequency (01-12) is automatically set to 50Hz.

13-08=5: 3-wire initialization (230V/415V)

13-08choicesretainwirecount,voltage/frequency:2/3=220/44060Hz;4/5=230/41550;6/7=200/38050;8PLC;9/10=230/46060;11/12=230/40060;13/14=230/40050;15/16=220/38050;0none1reservedothersreserved. Autozerosafterreset.2wireS1forwardstop/S2reversestop;3wire3usesS5direction/S1start/S2stop. If01-00=F,01-12set60Hzfor2/3or50Hz4.13-08=5continues318. Originalcalls01-12maximumfrequency although elsewherebasefrequency;retainreference.

Factory reset selections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Factory reset selections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 08

Factory reset selections. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 08

Factory reset selections table1 — PDF page 317

Source row Source row label Source value or description
1 13- 08 Restore Factory Setting
2 Range 【0】: No Initialization 【1】: Reserved 【2】: 2 Wire Initialization (220/440V, 60Hz) 【3】: 3 Wire Initialization (220/440V, 60Hz) 【4】: 2 Wire Initialization (230/415V, 50Hz) 【5】: 3 Wire Initialization (230/415V, 50Hz) 【6】: 2 Wire Initialization (200/380V, 50Hz) 【7】: 3 Wire Initialization (200/380V, 50Hz) 【8】: PLC Initialization 【9】: 2 Wire Initialization (230V/460V, 60Hz) 【10】: 3 Wire Initialization (230V/460V, 60Hz) 【11】: 2 wire Initialization (230V/400V, 60Hz) 【12】: 3 wire Initialization (230V/400V, 60Hz) 【13】: 2 wire Initialization (230V/400V, 50Hz) 【14】: 3 wire Initialization (230V/400V, 50Hz) 【15】: 2 wire Initialization (220V/380V, 50Hz) 【16】: 3 wire Initialization (220V/380V, 50Hz) 【Others】: Reserved

Manual — Reset selection continuation — page 318

Multi-function digital input terminal S5 controls the forward / reverse direction, and terminals S1 and S2 are

set for 3-wire start operation and stop command.

Inverter input voltage (01-14) is automatically set to 230V (200V class) or 415V (400V class).

When 01-00 (V/F curve) set to F, Inverter maximum frequency (01-12) is automatically set to 50Hz.

13-08=6: 2-wire initialization (200V/380V)

Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse

operation / stop command. Refer to Fig.4.4.1.

Inverter input voltage (01-14) is automatically set to 200V (200V class) or 380V (400V class).

13-08=7: 3-wire initialization (200V/380V)

13-08=8: PLC initialization

Clear built-in PLC ladder logic and related values.

13-08=9: 2 wire initialization (230V/460V, 60Hz)

operation / stop command. Refer to Figure 4.4.1. The input voltage (01-14) will be set to 230V (200V class)

or 460V (400V class) automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of

01-12 will be set to 60Hz automatically.

13-08=10: 3 wire initialization (230V/460V, 60Hz)

Multi-function digital input terminal S7 controls the forward / reverse direction, and terminals S1 and S2 are

set for 3-wire start operation and stop command. Refer to Figure 4.4.2 and Figure 4.4.3 for 3-wire type

operation mode. The input voltage (01-14) will be set to 230V (200V class) or 460V (400V class)

automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of 01-12 will be set to 60Hz

automatically.

13-08=11: 2 wire initialization (230V/400V, 60Hz)

or 400V (400V class) automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of

13-08=12: 3 wire initialization (230V/460V, 60Hz)

operation mode. The input voltage (01-14) will be set to 230V (200V class) or 400V (400V class)

13-08=13: 2 wire initialization (230V/400V, 50Hz)

Completes317mode5S5direction,S1/S2startstop,230/41550Hz.6/7=200/38050Hz;7S5direction.8clearsPLC ladder/values.9=230/46060Hz2wire;10same3wirebutS7directionasprinted.11=230/40060Hz2wire.12heading230/46060Hz butbody230/40060Hz/table317400;S7direction. Allfrequencychangesconditional01-00=F;13headingcontinues319.

Manual — Reset exclusions and maintenance — page 319

Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse

operation / stop command. Refer to Figure 4.4.1. The input voltage (01-14) will be set to 230V (200V class)

or 400V (400V class) automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of

01-12 will be set to 50Hz automatically.

13-08=14: 3 wire initialization (230V/460V, 50Hz)

Multi-function digital input terminal S7 controls the forward / reverse direction, and terminals S1 and S2 are

set for 3-wire start operation and stop command. Refer to Figure 4.4.2 and Figure 4.4.3 for 3-wire type

operation mode. The input voltage (01-14) will be set to 230V (200V class) or 400V (400V class)

automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of 01-12 will be set to 50Hz

automatically.

13-08=15: 2 wire initialization (220V/380V, 50Hz)

operation / stop command. Refer to Fig.4.4.1. The input voltage (01-14) will be set to 220V (200V class) or

380V (400V class) automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of 01-12

will be set to 50Hz automatically.

13-08=16: 3 wire initialization (220V/380V, 50Hz)

operation mode. The input voltage (01-14) will be set to 220V (200V class) or 380V (400V class)

Note: Restore factory setting (13-08) will not modify the setting of 01-00 (V/F curve).

Parameter List: parameters that are not affected by default value

13-09=1: Clear inverter fault history including (12-11~12-15/12-45~12-64)

This parameter displays CPLD version on the control board.

Completes318mode13body230/40050Hz2wire.14heading230/46050Hz butbody230/40050Hz/table400;S7direction.15/16=220/38050Hz,16S7direction. Resetpreserves00-00control,00-04language,01-00V/F,13-00rating,13-03/04hours/days,13-05countmode.13-09=1clearsfault12-11..15/12-45..64.13-10password2range0–9999no behaviourdetails.13-11C/BCPLDversion0–9.99star1linkedV1.4nextpage.

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 00-00

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 00-04

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 01-00

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 13-00

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 13-03

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 13-04

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 13-05

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 09

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 09

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 10

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 10

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 11

Reset exclusions and maintenance. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 11

Reset exclusions and maintenance table1 — PDF page 319

Source row No. Parameter Name
1 00-00 Control Mode Selection
2 00-04 Language Selection
3 01-00 V/F Curve Selection
4 13-00 Inverter Rating Selection
5 13-03 Cumulative Operation Hours 1
6 13-04 Cumulative Operation Hours 2
7 13-05 Selection of Accumulative Operation Time

Reset exclusions and maintenance table2 — PDF page 319

Source row Source row label Source value or description
1 13- 09 Fault History Clearance Function
2 Range 【0】: Do not Clear Fault History 【1】: Clear Fault History

Reset exclusions and maintenance table3 — PDF page 319

Source row Source row label Source value or description
1 13- 10 Parameter Password Function 2
2 Range 0 ~ 9999

Reset exclusions and maintenance table4 — PDF page 319

Source row Source row label Source value or description
1 13- 11 C/B CPLD Ver. *1
2 Range 【0.00~9.99】

Manual — Option cards and fault history — page 320

This parameter displays option card Id on the control board and it is enabled only with the option card.

【0】: None

【8】: IO-8DO

*1: It is new added in inverter software V1.4.

This parameter displays option card CPLD version on the control board and it is enabled only with option

card.

13-14=0,

Fault messages are not saved in fault history (12-46~12-49 & 13-21~13-50) during the process when auto

restart function is active.

13-14=1,

Fault messages are saved in fault history (12-46~12-49 & 13-21~13-50) during the process when auto

Note: Parameters 13-21~13-50 are 30 Fault History: When it detect fault, inverter will store to fault history.

If the fault occurs again, parameter 13-21 will change to parameter 13-22.

13-12ID0–255optioncardonly:0none,8IO-8DO;13-13optionCPLDversion0–9.99optiononly;star1newV1.4also13-11previouspage.13-14=0doesnotsaveautorestartfaults,1saves;history12-46..49and13-21..50. Thirtyhistoryentries13-21..50 shift21to22atnextfault. Distinctfrom13-09clearlist,notassumedequivalent.

Option cards and fault history. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Option cards and fault history. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 12

Option cards and fault history. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 12

Option cards and fault history. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 13

Option cards and fault history. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 13

Option cards and fault history. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 13- 14

Option cards and fault history. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 13- 14

Option cards and fault history table1 — PDF page 320

Source row Source row label Source value or description
1 13- 12 Option Card Id *1
2 Range 【0~255】

Option cards and fault history table2 — PDF page 320

Source row Source row label Source value or description
1 13- 13 Option Card CPLD Ver. *1
2 Range 【0.00~9.99】

Option cards and fault history table3 — PDF page 320

Source row Source row label Source value or description
1 13- 14 Fault Storage Selection
2 Range 【0】: Auto Restart Fault Messages are not saved in fault history during Auto-Restart. 【1】: Auto Restart Fault Messages are saved in fault history during Auto-Restart.

Manual — PLC setting values — page 321

Group 14: PLC Setting Parameters

Group14settings:14-00..15timerT1..T8pairedvalues1/2,secondMode7only,shared0–9999.14-16..23C1..C8shared0–65534.14-24..35AS1..4threevalues eachshared0–65534.14-36..40MD1three/MD2firsttwo;continued322withremainingMDandsharedrange,notomitted.

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-00

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-01

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-02

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-03

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-04

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-05

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-06

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-07

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-08

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-09

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-10

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-11

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-12

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-13

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-14

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-15

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 14-00,14-01,14-02,14-03,14-04,14-05,14-06,14-07,14-08,14-09,14-10,14-11,14-12,14-13,14-14,14-15

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-16

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-17

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-18

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-19

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-20

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-21

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-22

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-23

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 14-16,14-17,14-18,14-19,14-20,14-21,14-22,14-23

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-24

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-25

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-26

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-27

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-28

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-29

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-30

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-31

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-32

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-33

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-34

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-35

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 14-24,14-25,14-26,14-27,14-28,14-29,14-30,14-31,14-32,14-33,14-34,14-35

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Shared range0–65534printedPDF322firsttable applies14-36..47.

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Shared range0–65534printedPDF322firsttable applies14-36..47. Row group: Parameter 14-36

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Shared range0–65534printedPDF322firsttable applies14-36..47. Row group: Parameter 14-37

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Shared range0–65534printedPDF322firsttable applies14-36..47. Row group: Parameter 14-38

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Shared range0–65534printedPDF322firsttable applies14-36..47. Row group: Parameter 14-39

PLC setting values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Shared range0–65534printedPDF322firsttable applies14-36..47. Row group: Parameter 14-40

PLC setting values table1 — PDF page 321

Source row Source row label Source value or description
1 14-00 T1 Set Value 1
2 14-01 T1 Set Value 2(Mode 7)
3 14-02 T2 Set Value 1
4 14-03 T2 Set Value 2(Mode 7)
5 14-04 T3 Set Value 1
6 14-05 T3 Set Value 2(Mode 7)
7 14-06 T4 Set Value 1
8 14-07 T4 Set Value 2(Mode 7)
9 14-08 T5 Set Value 1
10 14-09 T5 Set Value 2(Mode 7)
11 14-10 T6 Set Value 1
12 14-11 T6 Set Value 2(Mode 7)
13 14-12 T7 Set Value 1
14 14-13 T7 Set Value 2(Mode 7)
15 14-14 T8 Set Value 1
16 14-15 T8 Set Value 2(Mode 7)
17 Range 【0~9999】

PLC setting values table2 — PDF page 321

Source row Source row label Source value or description
1 14-16 C1 Set Value
2 14-17 C2 Set Value
3 14-18 C3 Set Value
4 14-19 C4 Set Value
5 14-20 C5 Set Value
6 14-21 C6 Set Value
7 14-22 C7 Set Value
8 14-23 C8 Set Value
9 Range 【0~65534】

PLC setting values table3 — PDF page 321

Source row Source row label Source value or description
1 14-24 AS1 Set Value 1
2 14-25 AS1 Set Value 2
3 14-26 AS1 Set Value 3
4 14-27 AS2 Set Value 1
5 14-28 AS2 Set Value 2
6 14-29 AS2 Set Value 3
7 14-30 AS3 Set Value 1
8 14-31 AS3 Set Value 2
9 14-32 AS3 Set Value 3
10 14-33 AS4 Set Value 1
11 14-34 AS4 Set Value 2
12 14-35 AS4 Set Value 3
13 Range 【0~65534】

PLC setting values table4 — PDF page 321

Source row Source row label Source value or description
1 14-36 MD1 Set Value 1
2 14-37 MD1 Set Value 2
3 14-38 MD1 Set Value 3
4 14-39 MD2 Set Value 1
5 14-40 MD2 Set Value 2

Manual — PLC monitoring values — page 322

Please refer to section 4.5 for more details of built-in PLC function.

Group 15: PLC Monitoring Parameters

Completes321:14-41MD2value3;42..44MD3values1..3;45..47MD4values1..3;shared0–65534applies14-36..47acrosspages. Group15monitors15-00..15T1..8pairedcurrent1/2Mode7shared0–9999;16..23C1..8shared0–65534;24..27AS1..4results,28..31MD1..4results,32TDcurrent,shared0–65534. SettingandmonitorIDsremainseparate.

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-41

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-42

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-43

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-44

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-45

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-46

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 14-47

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range14-36..47includingPDF321previousfiveparameters

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 00

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 01

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 02

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 03

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 04

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 05

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 06

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 07

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 08

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 09

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 10

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 11

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 12

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 13

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 14

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15- 15

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 15- 00,15- 01,15- 02,15- 03,15- 04,15- 05,15- 06,15- 07,15- 08,15- 09,15- 10,15- 11,15- 12,15- 13,15- 14,15- 15

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-16

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-17

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-18

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-19

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-20

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-21

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-22

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-23

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 15-16,15-17,15-18,15-19,15-20,15-21,15-22,15-23

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-24

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-25

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-26

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-27

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-28

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-29

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-30

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-31

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 15-32

PLC monitoring values. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 15-24,15-25,15-26,15-27,15-28,15-29,15-30,15-31,15-32

PLC monitoring values table1 — PDF page 322

Source row Source row label Source value or description
1 14-41 MD2 Set Value 3
2 14-42 MD3 Set Value 1
3 14-43 MD3 Set Value 2
4 14-44 MD3 Set Value 3
5 14-45 MD4 Set Value 1
6 14-46 MD4 Set Value 2
7 14-47 MD4 Set Value 3
8 Range 【0~65534】

PLC monitoring values table2 — PDF page 322

Source row Source row label Source value or description
1 15- 00 T1 Current Value 1
2 15- 01 T1 Current Value 2(Mode 7)
3 15- 02 T2 Current Value 1
4 15- 03 T2 Current Value 2(Mode 7)
5 15- 04 T3 Current Value 1
6 15- 05 T3 Current Value 2(Mode 7)
7 15- 06 T4 Current Value 1
8 15- 07 T4 Current Value 2(Mode 7)
9 15- 08 T5 Current Value 1
10 15- 09 T5 Current Value 2(Mode 7)
11 15- 10 T6 Current Value 1
12 15- 11 T6 Current Value 2(Mode 7)
13 15- 12 T7 Current Value 1
14 15- 13 T7 Current Value 2(Mode 7)
15 15- 14 T8 Current Value 1
16 15- 15 T8 Current Value 2(Mode 7)
17 Range 【0~9999】

PLC monitoring values table3 — PDF page 322

Source row Source row label Source value or description
1 15-16 C1 Current Value
2 15-17 C2 Current Value
3 15-18 C3 Current Value
4 15-19 C4 Current Value
5 15-20 C5 Current Value
6 15-21 C6 Current Value
7 15-22 C7 Current Value
8 15-23 C8 Current Value
9 Range 【0~65534】

PLC monitoring values table4 — PDF page 322

Source row Source row label Source value or description
1 15-24 AS1 Results
2 15-25 AS2 Results
3 15-26 AS3 Results
4 15-27 AS4 Results
5 15-28 MD1 Results
6 15-29 MD2 Results
7 15-30 MD3 Results
8 15-31 MD4 Results
9 15-32 TD Current Value
10 Range 【0~65534】

Manual — LCD monitor and units — page 323

Group 16: LCD Function Parameters

At power-up the inverter shows two monitor section on the display, main monitor section and the

sub-screen monitor section (smaller font).

Choose the monitor signal to be displayed as the main-screen monitor screen in parameter 16-00, and the

monitor signals to be displayed on the sub-screen monitor in parameters 16-01 and 16-02, similar to

monitor parameters 12-5 ~ 12-82.

Note: The setting value of 16-00, 16-01 and 16-02 can be modified. It also can reset except PID modes

(refer to the setting description of parameter 10-03) and PUMP modes (refer to the setting

description of parameter 23-00), but these two modes can be modified in inverter software V1.4.

16-00main/01sub1/02sub2each5–82correspond12-05..82;subscreenfontsmaller. PID/PUMPmodificationexceptionscanmodifyinV1.4.16-03=0Hz.01,1%.01,2RPMusingIMpoles02-07orPM22-03;3..39reserved;40..9999integer,10001..19999one decimal,20001..29999two,30001..39999three;excludedboundaryvalues10000/20000/30000notfilled.16-04units0..22here,23/24continue324;21RPM22Barstar1.

LCD monitor and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

LCD monitor and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 00

LCD monitor and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 00

LCD monitor and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 01

LCD monitor and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 01

LCD monitor and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 02

LCD monitor and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 02

LCD monitor and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 03

LCD monitor and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 03

LCD monitor and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 04

LCD monitor and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 04

LCD monitor and units table1 — PDF page 323

Source row Source row label Source value or description
1 16- 00 Main Screen Monitoring
2 Range 【5~82】
3 16- 01 Sub-Screen Monitoring 1
4 Range 【5~82】
5 16- 02 Sub-Screen Monitoring 2
6 Range 【5~82】

LCD monitor and units table2 — PDF page 323

Source row Source row label Source value or description
1 16- 03 Selection of Display Unit
2 Range 【0】: Display unit is Hz (Resolution is 0.01Hz) 【1】: Display unit is % (Resolution is 0.01%) 【2】: Rpm display; motor rotation speed is set by the control modes to select IM (02-07)/ PM (22-03) motor poles to calculate. 【3~39】: Reserved 【40~9999】: 100% is XXXX with no decimals (integer only) 【10001~19999】: 100% is XXX.X with 1 decimal 【20001~29999】: 100% is XX.XX with 2 decimals 【30001~39999】: 100% is X.XXX with 3 decimals
3 16- 04 Selection of Engineering Unit
4 Range 【0】: No Unit 【1】: FPM 【2】: CFM 【3】: PSI 【4】: GPH 【5】: GPM 【6】: IN 【7】: FT 【8】: /s 【9】: /m 【10】: /h 【11】: °F 【12】: inW 【13】: HP 【14】: m/s 【15】: MPM 【16】: CMM 【17】: W 【18】: KW 【19】: m 【20】: °C 【21】: RPM *1 【22】: Bar *1

Manual — LCD scaling examples — page 324

*1: It is new added in inverter software V1.4.

16-03: Display unit of digital operator

Set the units of the following items to be displayed, the frequency reference (05-01, 00-18, 06-01~06-15)

and the monitoring frequency 12-16, 12-17 (Output frequency)

16-04: Display unit of engineering

When 16-03 = 00040-39999, engineering units are enabled. The displayed set range and the frequency

range of unit (05-01, 06-01~06-15) as well as the monitoring frequency (12-16, 12-17) are changed by

parameters 16-04 and 16-03.

Completes32316-04=23Pa,24KPa;star1V1.4also21RPM/22Bar. RPM=120×referencefrequency/poles,02-07V/FSLV,22-03PMSLV. Displayapplies05-01,00-18,06-01..15and12-16/17asprinted. Fifthdigitdecimalcount,lastfourfullscale;examples00200+unit0=0200at100%;12000+unit2=200.0CFM/120.0at60%;26500+unit20=65.00°C/39.00at60%;32555+unit14=2.555m/s/1.533at60%. Nestedrange00040–39999overallwithdetailfourbands;16-04mergedunitappliesallfourrows. Examples06-01..15 reference retained,notrewrittento05.

LCD scaling examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Continuation16-04engineeringunitchoicesfromPDF323;blankleftcellretained.

LCD scaling examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Continuation16-04engineeringunitchoicesfromPDF323;blankleftcellretained. Row group: Parameter

LCD scaling examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

LCD scaling examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 0

LCD scaling examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 1

LCD scaling examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 2

LCD scaling examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 3-39

LCD scaling examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 00040

-

Shared source cells (coordinates refer to this table):

LCD scaling examples table1 — PDF page 324

Source row Source row label Source value or description
1 ⟦blank source cell⟧ 【23】: Pa *1 【24】: KPa

LCD scaling examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: 00040 — PDF page 324

Source row 16-03 overall selection Set/displayed contents or detailed16-03 Display format Display unit Display example
1 0 0.01 Hz ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 1 0.01 % (maximum output frequency 01-02=100%) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 2 RPM (RPM = 120 x reference frequency / numbers of motor pole. The numbers of motor pole is set by 02-07 in the control modes of V/F or SLV and is set by 22-03 in PMSLV.) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 3-39 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 00040 - 39999 Set the decimal point by using the fifth place. i.e. □ □□□□ Sets full display scaling excluding decimals Set the number of decimal places 00040 - 09999 : □□□□ (Integer only e.g. 1000) 10001 - 19999 : □□□. □ (1 decimal place e.g. 10.0) 20001 - 29999 : □□. □□ (2 decimal places, e.g. 10.00) 30001 - 39999 : □. □□□ (3 decimal places, e.g. 10.000) <example> ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ 16-03 Display Display unit Display example
7 ⟦null: no independent source value⟧ 00040 - 09999 □□□□ use 16-04 setting Example: 100 % speed is 0200 > set 16-03=00200 (from 05-01, 06-01 to 06-15, set range from 0040 to 9999). > set 16-04=0 (no unit)
8 ⟦null: no independent source value⟧ 10001 – 19999 □□□. □ ⟦null: no independent source value⟧ Example: 100 % speed is 200.0 CFM > set 16-03=12000 (05-01, 06-01 to 06-15, set range from 0000 to 9999). > set 16-04=2 (CFM) > 60% speed will be displayed as 120.0 CFM
9 ⟦null: no independent source value⟧ 20001 – 29999 □□. □□ ⟦null: no independent source value⟧ Example: 100 % speed is 65.00ºC > set 16-03=26500 (05-01, 06-01 to 06-15, set range from 0000 to 9999) > set 16-04=20 (ºC) > 60% of speed is displayed as 39.00 ºC
10 ⟦null: no independent source value⟧ 30001 - 39999 □. □□□ ⟦null: no independent source value⟧ Example: 100 % speed is 2.555 m/s > set 16-03=32555 > set 16-04=14 (m/s) > 60% speed is displayed as 1.533 m/s

Manual — LCD copying prerequisites — page 325

Adjust the screen contrast of the digital operator. If it is set to 0, the screen backlight is turned off.

LCD digital operator with built-in memory (EEPROM) can be used to store and retrieve parameters:

(1) Read: Save inverter parameters to the digital operator (INV → OP).

(2) Write: Write the parameters from the digital operator to the inverter and save (OP → INV).

(3) Verify: Compare the inverter parameters against the parameters in the digital operator.

16-07=0: No action

16-07=1: Read (all parameters are copied from the inverter to the keypad).

16-07=2: Write (all parameter are copied from the keypad to the inverter).

16-07=3: Verify (Compare the set value of the inverter to the parameter of the digital operator).

Set 16-08 = 0, to prevent the saved parameter data stored in the digital operator from accidentally being

overwritten.

When parameter 16-08=0 and the read operation is executed (16-07=1) a warning message of "RDP

Read Prohibited" will be displayed on the keypad and the read operation is cancelled.

Refer to the following steps for copy function operation.

For the write-in operation requires the following items to match.

(1) Software version

(2) Control method

(3) Inverter type

(4) Inverter rated capacity and voltage

Set one of the parameters 03-00 to 03-05 (multi-function digital input selection) to 49 (Enable the

parameter write-in function) to enable or disable the parameter write-in function.

When terminal is active, parameters can be copied from the digital operator to the inverter. When the

terminal is not active inverter parameters are prohibited from write-in, excluding the reference frequency

(00-05).

Note: Parameter 16-11 (RTC date setting) and 16-12 (RTC time setting) require resetting, after parameter

setting in the keypad is written and saved in the inverter (OP→INV).

16-05backlight0–7,0off;prosecallscontrast.16-07=0none,1readINV→OP,2writeOP→INV,3compare.16-08=0protectoperatorfromoverwrite,read1givesRDPandcancel;1allow. Write requires matchingsoftwareversion/controlmethod/type/ratedcapacity+voltage. DI03-00..05=49allowswritewhenactive;inactiveblocks exceptreference00-05asprinted. AfterOP→INVresetRTC16-11/12.

LCD copying prerequisites. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

LCD copying prerequisites. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 05

LCD copying prerequisites. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 05

LCD copying prerequisites. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 07

LCD copying prerequisites. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 07

LCD copying prerequisites. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 08

LCD copying prerequisites. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 08

LCD copying prerequisites table1 — PDF page 325

Source row Source row label Source value or description
1 16- 05 LCD Backlight
2 Range 【0~7】

LCD copying prerequisites table2 — PDF page 325

Source row Source row label Source value or description
1 16- 07 Copy Function Selection
2 Range 【0】: Do not copy parameters 【1】: Read inverter parameters and save to the operator. 【2】: Write the operator parameters to inverter. 【3】: Compare parameters of inverter and operator.
3 16- 08 Selection of Allowing Reading
4 Range 【0】: Do not allow to read inverter parameters and save to the operator. 【1】: Allow to read inverter parameters and save to the operator.

Manual — READ and WRITE sequences — page 326

READ:Copy inverter parameters to the keypad

WRITE: Copy Keypad parameters to the Inverter

Readsteps1Group14PLCSetting/15PLCMonitor/16LCDKeypadFuncselected;2PARA16-07CopySel/-08READSel/-09KeypadLossSel;3Edit16-07CopySel0Normal(0–3)<0>;4value1READ;5-ADV-READ INV→OPprogress;6READCOMPLETEorRDP ReadProhibited,anykeyclears;7Edit1READ,DSP/FUNreturns16-07. Write1..3samegroup/parameter/normal;4value2WRITE;remaining327. Screenshotcellsimageonly,capturedexplicitly,notemptydata.

READ and WRITE sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

READ and WRITE sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 1;image labels transcribed in visual association

READ and WRITE sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 2;image labels transcribed in visual association

READ and WRITE sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 3;image labels transcribed in visual association

READ and WRITE sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 4;image labels transcribed in visual association

READ and WRITE sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 5;image labels transcribed in visual association

READ and WRITE sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 6;image labels transcribed in visual association

READ and WRITE sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 7;image labels transcribed in visual association

Shared source cells (coordinates refer to this table):

READ and WRITE sequences table1 — PDF page 326

Source row Steps LCD Display (English); image transcribed separately Description
1 1 ⟦blank source cell⟧ Select the copy function group (16) from the group menu.
2 2 ⟦blank source cell⟧ Press the Read / Enter key and select parameter (16-07) copy sel.
3 3 ⟦blank source cell⟧ Press the Read / Enter key to display the data setting / read screen (LCD display is inversed).
4 4 ⟦blank source cell⟧ Change the set value to 1 (read) by using the up arrow key.
5 5 ⟦blank source cell⟧  Use Read / Enter key to enable the read operation, the display is shown as the left.  The bottom of LCD display will show a bar to indicate the read progress s.
6 6 ⟦blank source cell⟧ “READ COMPLETE” will be displayed on the keypad when reading was successful.
7 ⟦null: no independent source value⟧ ⟦blank source cell⟧  The error message of "RDP Read Prohibited" may occur on the keypad when reading parameters from the inverter is prohibited.  If the error is displayed, press any key to remove the error message and go back to parameter 16-07.
8 7 ⟦blank source cell⟧ When DSP/FUN key is pressed, the display returns to parameter 16-07.

READ and WRITE sequences table2 — PDF page 326

Source row Steps LCD Display (English); image transcribed separately Description
1 1 ⟦blank source cell⟧ Select the copy function group (16) from the group menu.
2 2 ⟦blank source cell⟧ Press the Read / Enter key and select parameter (16-07) copy sel.
3 3 ⟦blank source cell⟧ Press the Read / Enter key to display the data setting / read screen (LCD display is inversed).
4 4 ⟦blank source cell⟧ Change the set value to 2 (write) by using the up arrow key.

Manual — WRITE and VERIFY sequences — page 327

Verify: Compare Inverter Parameters against Keypad Parameters.

Completes326write5screenshot-ADV-WRITE INV→OP despitewriteOP→INVprose325;descriptionincorrectlyreadoperation/readprogress.6WRITECOMPLETEthenSysInitpoweroffrestart,orWRE WriteError;7Edit2WRITEreturn16-07. Verifysteps1Group14/15/16selected;2PARA16-07/08/09;3Edit0Normal;4value3VERIFY;5-ADV-VERIFY INV→OPprogress;6VERIFYCOMPLETEorimageVERY VerifyErrorversusproseVRYE VerifyError;7Edit3VERIFYreturn. Read/write wordingcopiedintoverifydescriptionsretainedasflag.

WRITE and VERIFY sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

WRITE and VERIFY sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 5;image labels transcribed in visual association

WRITE and VERIFY sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 6;image labels transcribed in visual association

WRITE and VERIFY sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 7;image labels transcribed in visual association

Shared source cells (coordinates refer to this table):

WRITE and VERIFY sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 1;image labels transcribed in visual association

WRITE and VERIFY sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 2;image labels transcribed in visual association

WRITE and VERIFY sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 3;image labels transcribed in visual association

WRITE and VERIFY sequences. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Step 4;image labels transcribed in visual association

WRITE and VERIFY sequences table1 — PDF page 327

Source row Steps LCD Display (English); image transcribed separately Description
1 5 ⟦blank source cell⟧  Use Read / Enter key to enable the read operation, the display is shown as the left.  The bottom of LCD display will show a bar to indicate the read progress.
2 6 ⟦blank source cell⟧ “WRITE COMPLETE” will be displayed on the keypad when writing was successful.  Until the subsequent display of "SysInit", please power off and restart.
3 ⟦null: no independent source value⟧ ⟦blank source cell⟧  The error message of “WRE Write Error " may occur on the keypad when writing parameters to the inverter is prohibited.  If the error is displayed, press any key to remove the error message and go back to parameter 16-07.
4 7 ⟦blank source cell⟧ When DSP/FUN key is pressed, the display returns to parameter 16-07.

WRITE and VERIFY sequences table2 — PDF page 327

Source row Steps LCD Display (English); image transcribed separately Description
1 1 ⟦blank source cell⟧ Select the copy function group (16) from the group menu.
2 2 ⟦blank source cell⟧ Press the Read / Enter key and select parameter (16-07) copy sel.
3 3 ⟦blank source cell⟧ Press the Read / Enter key to display the data setting / read screen (LCD display is inversed).
4 4 ⟦blank source cell⟧ Change the set value to 3 (verify) by using the up arrow key.
5 5 ⟦blank source cell⟧  Use Read / Enter key to enable the read operation, the display is shown as the left.  The bottom of LCD display will show a bar to indicate the read progress.
6 6 ⟦blank source cell⟧ “VERIFY COMPLETE” will be displayed on the keypad when writing was successful.
7 ⟦null: no independent source value⟧ ⟦blank source cell⟧  The error message of “VRYE Verify Error " may occur on the keypad when writing parameters to the inverter is prohibited.  If the error is displayed, press any key to remove the error message and go back to parameter 16-07.
8 7 ⟦blank source cell⟧ When DSP/FUN key is pressed, the display returns to parameter 16-07.

Manual — Keypad loss and RTC setup — page 328

Monitor 00:00

Freq Ref

12-16 = 000.00 Hz

12-17 = 000.00 Hz

12-18 = 0000.0A

16-09=0: Continue operating when keypad is removed.

16-09=1: Trip inverter when keypad is removed while operating in local mode.

Set the internal clock before using the function of Real Time Clock (RTC).

RTC date setting is determined by parameter 16-11 and RTC time setting is determined by parameter

16-12.

RTC is displayed in the top of the keypad and refer to Fig.4.4.85 for the selection of RTC time display

(16-10) is set to 1.

Figure 4.4.85 RTC Time Display (Example)

Notes:

-

RTC is not enabled if keypad does not connect with the inverter.

The counting time continues running regardless of the function being hide or display in the

paramerer 16-10 (RTC Time Display Setting).

Users can apply the parameters 12-72 and 12-73 to monitor the specific RTC date and time.

RTC has the following characteristics:

Four times a day

Four weeks

Timer offset function (preset time)

Timrer enables via multi-function digital input

Selection for contant time and speed

Timer enables multi-function digital output

16-09=0continue,1tripifLCDremovedwhilelocaloperation;tableomitslocalcondition.16-10hide0/show1;11date12.01.01–99.12.31;12time00:00–23:59. Fig4.4.85time00:00top,main12-16000.00Hz,sub12-17000.00Hz/12-180000.0A;illustrativevalues. RTCneedsconnectedkeypad;countsregardlesshidden/display;monitor12-72/73. Claimsfourtimesaday/fourweeks,offset,DIenable,time/speedandDO;exactfourweekswordingnotconverted.

Keypad loss and RTC setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

Keypad loss and RTC setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 09

Keypad loss and RTC setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 09

Keypad loss and RTC setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 10

Keypad loss and RTC setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 10

Keypad loss and RTC setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 11

Keypad loss and RTC setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 11

Keypad loss and RTC setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 12

Keypad loss and RTC setup. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 12

Keypad loss and RTC setup table1 — PDF page 328

Source row Source row label Source value or description
1 16- 09 Selection of Operator Removed (LCD)
2 Range 【0】: Keep operating when LCD operator is removed. 【1】: Display fault to stop when LCD operator is removed

Keypad loss and RTC setup table2 — PDF page 328

Source row Source row label Source value or description
1 16- 10 RTC Time Display Setting
2 Range 【0】: Hide 【1】: Display
3 16- 11 RTC Date Setting
4 Range 【12.01.01 ~ 99.12.31】
5 16- 12 RTC Time Setting
6 Range 【00:00 ~ 23:59】

Manual — RTC timers and sources — page 329

16-13off0/on1/DI2. P1..4start/stoptime14/15,18/19,22/23,26/27shared00:00–23:59. P1..4start/stopdate16/17,20/21,24/25,28/29sharedMon1..Sun7.30offset0off1on2DI;31offsettime00:00–23:59.32..35timer1..4sourceshared0–31Table4.4.13.36speed0off1timer1,2timer2,3timer3,4timer4,5timer1+2.37directionxxx0BRun1forward/xxx1Breverse;furtherbits/RTCdetailscontinue330outsidepart.

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval.

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 13

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 13

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 14

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 15

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 18

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 19

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 22

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 23

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 26

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 27

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 14,16- 15,16- 18,16- 19,16- 22,16- 23,16- 26,16- 27

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 16

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 17

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16-20

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 21

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 24

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 25

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 28

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 29

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 16,16- 17,16-20,16- 21,16- 24,16- 25,16- 28,16- 29

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 30

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 30

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 31

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 31

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 32

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 33

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 34

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 35

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 32,16- 33,16- 34,16- 35

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 36

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 36

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Parameter 16- 37

RTC timers and sources. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source mode/version conditions and conflicts retained;not engineering approval. Row group: Shared Range for 16- 37

RTC timers and sources table1 — PDF page 329

Source row Source row label Source value or description
1 16- 13 RTC Timer Function
2 Range 【0】: Disable 【1】: Enable 【2】: Set by DI
3 16- 14 P1 Start Time
4 16- 15 P1 Stop Time
5 16- 18 P2 Start Time
6 16- 19 P2 Stop Time
7 16- 22 P3 Start Time
8 16- 23 P3 Stop Time
9 16- 26 P4 Start Time
10 16- 27 P4 Stop Time
11 Range 【00:00 ~ 23:59】
12 16- 16 P1 Start Date
13 16- 17 P1 Stop Date
14 16-20 P2 Start Date
15 16- 21 P2 Stop Date
16 16- 24 P3 Start Date
17 16- 25 P3 Stop Date
18 16- 28 P4 Start Date
19 16- 29 P4 Stop Date
20 Range 【1】: Mon 【2】: Tue 【3】: Wed 【4】: Thu 【5】: Fri 【6】: Sat 【7】: Sun
21 16- 30 Selection of RTC Offset
22 Range 【0】: Disable 【1】: Enable 【2】: Set by DI
23 16- 31 RTC Offset Time Setting
24 Range 【00:00 ~ 23:59】
25 16- 32 Source of Timer 1
26 16- 33 Source of Timer 2
27 16- 34 Source of Timer 3
28 16- 35 Source of Timer 4
29 Range 【0~31】: Refer to Table 4.4.13
30 16- 36 Selection of RTC Speed
31 Range 【0】: Off 【1】: By Timer 1 【2】: By Timer 2 【3】: By Timer 3 【4】: By Timer 4 【5】: By Timer 1+2
32 16- 37 Selection of RTC Rotation Direction
33 Range 【xxx0 B】: RTC Run1 Forward Rotation 【xxx1 B】: RTC Run1 Reverse Rotation

Manual — RTC direction and timer combinations — page 330

Source of timer can be selected to link multiple time periods and one time period can be set to multiple

timers.

Timer is set by the following steps:

 Start the timer:

Timer starts via the setting of RTC timer function (16-13).

 Set the time period:

Set the start & stop time and date. If the setting of start time is equal to that of stop time, timing period is

off.

 The timer is enabled:

Arrange time period to the specific timer (16-32~16-35).

 Link to parameters:

The timer can be linked to the relay output. One relay output can be only linked to one timer( ex. 03-11,

03-12 and 03-39, 16-36).

Note: If the stop time is set to 12:00, Motor start to stop from 12:01.

Refer to Fig.4.4.86 for RTC structure.

Step 1

Step 2

Step 3

Step 4

(Start the Timer)

( Set the Time Interval)

( Timer is Enabled)

( Link to Parameters)

Start/Stop

Timer

(G16- 13)

Time period 1

(G16- 14 - 17)

Time period 2

(G16- 18 - 21)

Time period 3

(G16- 22 - 25)

Time period 4

(G16- 26 -29)

Offset Time

(G16- 31)

Offset Time is

On/Off

(G16- 30)

Timer 1

(G16- 32)

Timer 2

(G16- 33)

Timer 3

(G16- 34)

Timer 4

(G16- 35)

.G16- 36 (RTC Speed Selection)

.G03- 11:Relay output (R1A - R1C)

.G03- 12:Relay output (R2A - R2C)

.G03- 39:Relay output (R3A - R3C)

Figure 4.4.86 RTC structure

Refer to the following Table 4.4.13 for the selection of timer operation cycle.

Table 4.4.13 Arrange time period to the timer function

Completes PDF329 parameter16-37: Run2 xx0x forward/xx1x reverse;Run3 x0xx/x1xx;Run4 0xxx/1xxx.16-13 enables P1(14–17),P2(18–21),P3(22–25),P4(26–29);offset30→31;timer32–35 combines periods/offset then36 selects speed or relay03-11/12/39. One relay accepts one timer;one period may enter several timers. Equal start/stop disables period;stop12:00 actually stops12:01. Table4.4.13 starts codes0–11, O/P4/P3/P2/P1 columns retained.

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Continuation of16-37 RTC direction from329.

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Continuation of16-37 RTC direction from329. Row group: Parameter

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval.

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 0

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 1

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 2

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 3

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 4

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 5

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 6

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 7

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 8

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 9

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 10

RTC direction and timer combinations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 11

RTC direction and timer combinations table1 — PDF page 330

Source row Source row label Source value or description
1 ⟦blank source cell⟧ 【xx0x B】: RTC Run2 Forward Rotation 【xx1x B】: RTC Run2 Reverse Rotation 【x0xx B】: RTC Run3 Forward Rotation 【x1xx B】: RTC Run3 Reverse Rotation 【0xxx B】: RTC Run4 Forward Rotation 【1xxx B】: RTC Run4 Reverse Rotation

RTC direction and timer combinations table3 — PDF page 330

Source row 16-32 ~ 16-35 O P4 P3 P2 P1 Timer Function Display
1 0 0 0 0 0 0 Without the selection of timer None
2 1 0 0 0 0 1 Time Period 1 P1
3 2 0 0 0 1 0 Time Period 2 P2
4 3 0 0 0 1 1 Time Period 1 and 2 P1+P2
5 4 0 0 1 0 0 Time Period 3 P3
6 5 0 0 1 0 1 Time Period 1 and 3 P1+P3
7 6 0 0 1 1 0 Time Period 2 and 3 P2+P3
8 7 0 0 1 1 1 Time Period 1 , 2 and 3 P1+P2+P3
9 8 0 1 0 0 0 Time Period 4 P4
10 9 0 1 0 0 1 Time Period 1 and 4 P1+P4
11 10 0 1 0 1 0 Time Period 2 and 4 P2+P4
12 11 0 1 0 1 1 Time Period 1 , 2 and 4 P1+P2+P4

Manual — Timer combinations continuation and control — page 331

Reference frequency and motor rotation direction are controlled by RTC function.

16-36=0: RTC speed selection is disabled.

16-36=1: Timer 1 is enabled.

Reference frequency = Frequency Setting of Speed-Stage 0 (05-01)

16-36=2: Timer 2 is enabled.

16-36=3: Timer 3 is enabled.

16-36=4: Timer 4 is enabled.

16-36=5: Timer 1 and 2 are enabled.

Reference frequency is enabled by the simultaneous operation of timer 1 and 2.

Notes:

-

The inverter runs via the start of the specific timer without the influence of other timers.

The selection of RTC speed setting (16-36) is affected by the action of time period 1 to 4 (P1~P4)

which is corresponding to the selection of RTC rotation direction (16-37).

For example:

When the selection of RTC speed is set to 5 (by timer 1+2), source of run command (00-02) and

source of frequecny command (00-05) are required to set to RTC. Thus, reference frequency is

controlled by RTC timer 1 and 2 and the inverter continues running.

Refer to Table 4.4.14 for the control of reference frequency.

Note: Selection of RTC Rotation Direction (16-37) is limited by the Motor Direction Lock Selection(11-00).

Note: The offset 16-37 running direction will select by the direction of the timer 1.

Table4.4.13 continues codes12–31;16 offset only,31 offset plus all four periods.16-36=1/2/3/4 selects timer1/2/3/4 with stage0 frequency05-01.36=5 timer1+timer2 combined;both command00-02 and frequency00-05 must use RTC for continuous example.16-37 direction limited by11-00;offset direction uses timer1.

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval.

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 12

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 13

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 14

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 15

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 16

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 17

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 18

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 19

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 20

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 21

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 22

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 23

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 24

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 25

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 26

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 27

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 28

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 29

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 30

Timer combinations continuation and control. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 31

Timer combinations continuation and control table1 — PDF page 331

Source row 16-32 ~ 16-35 O P4 P3 P2 P1 Timer Function Display
1 12 0 1 1 0 0 Time Period 3 and 4 P3+P4
2 13 0 1 1 0 1 Time Period 1 , 3 and 4 P1+P3+P4
3 14 0 1 1 1 0 Time Period 2 , 3 and 4 P2+P3+P4
4 15 0 1 1 1 1 Time Period 1 , 2 , 3 and 4 P1+P2+P3+P4
5 16 1 0 0 0 0 Offset selection Offset (O)
6 17 1 0 0 0 1 Offset and time period 1 O+P1
7 18 1 0 0 1 0 Offset and time period 2 O+P2
8 19 1 0 0 1 1 Offset and time period 1 and 2 O+P1+P2
9 20 1 0 1 0 0 Offset and time period 3 O+P3
10 21 1 0 1 0 1 Offset and time period 1 and 3 O+P1+P3
11 22 1 0 1 1 0 Offset and time period 2 and 3 O+P2+P3
12 23 1 0 1 1 1 Offset and time period 1 , 2 and 3 O+P1+P2+P3
13 24 1 1 0 0 0 Offset and time period 4 O+P4
14 25 1 1 0 0 1 Offset and time period 1 and 4 O+P1+P4
15 26 1 1 0 1 0 Offset and time period 2 and 4 O+P2+P4
16 27 1 1 0 1 1 Offset and time period 1 , 2 an 4 O+P1+P2+P4
17 28 1 1 1 0 0 Offset and time period 3 and 4 O+P3+P4
18 29 1 1 1 0 1 Offset and time period 1 , 3 and 4 O+P1+P3+P4
19 30 1 1 1 1 0 Offset and time period 2 , 3 and 4 O+P2+P3+P4
20 31 1 1 1 1 1 Offset and time period 1 , 2 , 3 and 4 O+P1+P2+P3+P4

Manual — RTC command mappings and schedule example — page 332

Mon

Tue

Wed

Thu

Fri

Sat

Sun

24: 00

22: 00

20: 00

18: 00

16: 00

14: 00

12: 00

10: 00

08: 00

06: 00

04: 00

02: 00

00: 00

Time

Day

weekdays

weekends

Time period 2

(P2)

period 4

(P4)

period 3

(P3)

period 1

(P1)

Table 4.4.14 Reference frequency is determined by timer 1 and 2

RTC function can not run normally when:

-

When multi-function terminal (03-00~03-05) is set to the fire mode.

When KEB function is enabled

Source of main frequency of RTC function is according to Table 4.4.14 and also can refer to

main and alternative frequency command modes (00-07).

If main run command source selection (00-02) is set to 0~3 (0: keypad, 1: external terminal, 2:

communication control, 3: PLC), refer to Table 4.4.15 for the relationship between main run

command and RTC timer status.

Table 4.4.15 Relationship between main run command and RTC timer status

Take an example for RTC timer connecting with different parameters:

The work time on Monday is 6:00 AM to 10:00 PM.

The work time on Tuesday to Friday is 8:00 AM to 8:00 PM.

The work time on Saturday is 8:00 AM to 6:00 PM.

The work time on Sunday is 8:00 AM to 12:00 PM.

Motor runs on weekdays (Mon. to Fri.) at speed 1 and on weekends at speed 2.

Figure 4.4.87 RTC timer (example)

Table4.4.14: timer1/timer2 00→05-01 stage0 RTC1 direction;10→05-02 stage1 RTC2;01→05-03 stage2 RTC3;11→05-04 stage3 RTC4. Fire mode and KEB exclude normal RTC action. Table4.4.15:00-02 0..3 cannot run without RUN regardless RTC;4/RTC0 cannot run;4/RTC1 runs16-37direction. Prose communication2/PLC3 differs earlier communication3. Fig4.4.87 example Monday06–22,Tuesday–Friday08–20,Saturday08–18,Sunday08–12;weekdays speed1/weekends speed2. Example only.

RTC command mappings and schedule example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval.

RTC command mappings and schedule example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 0

RTC command mappings and schedule example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 1

RTC command mappings and schedule example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 0~3

RTC command mappings and schedule example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 4

RTC command mappings and schedule example table1 — PDF page 332

Source row Timer 1 Timer 2 Main Frequency Command Source Selection (00-05) Source of frequency setting Selection of rotation direction
1 0 0 6(RTC) Set by frequency setting of speed-stage 0 (05-01) By RTC 1 (16-37)
2 1 0 6(RTC) Set by frequency setting of speed-stage 1 (05-02) By RTC 2 (16-37)
3 0 1 6(RTC) Set by frequency setting of speed-stage 2 (05-03) By RTC 3 (16-37)
4 1 1 6(RTC) Set by frequency setting of speed-stage 3 (05-04) By RTC 4 (16-37)

RTC command mappings and schedule example table2 — PDF page 332

Source row Main run command 00-02 RTC timer x status Inverter status
1 0~3 0 Inverter can not run (without run command)
2 0~3 1 Inverter can not run (without run command)
3 4 0 Inverter can not run (RTC timer is disabled)
4 4 1 Inverter runs and rotates depending on the function of 16-37.

Manual — RTC worked configuration — page 333

 Start up the timer in the parameter group 16 (Set the internal time first to enable this function).

Set the correct date and time in the parameters 16-11 and 16-12 and set parameter 16-13 to

1(enable RTC timer function).

 Set time period 1 (P1)

Start time 1: 16-14 = 06:00:00 (6:00 AM)

Stop time 1: 16-15 = 22:00:00 (10:00 PM)

Start date 1: 16-16 = 1 (Monday)

Stop date 1: 16-17 = 1 (Monday)

 Set time period 2 (P2)

Start time 2: 16-18 = 08:00:00 (8:00 AM)

Stop time 2: 16-19 = 20:00:00 (8:00 PM)

Start date 2: 16-20 = 2 (Tuesday)

Stop date 2: 16-21 = 5 (Friday)

 Set time period 3 (P3)

Start time 3: 16-22 = 08:00:00 (8:00 AM)

Stop time 3: 16-23 = 18:00:00 (6:00 PM)

Start date 3: 16-24 = 6 (Saturday)

Stop date 3: 16-25 = 6 (Saturday)

 Set time period 4 (P4)

Start time 4: 16-26 = 08:00:00 (8:00 AM)

Stop time 4: 16-27 = 12:00:00 (12:00 AM)

Start date 4: 16-28 = 7 (Sunday)

Stop date 4: 16-29 = 7 (Sunday)

 Timer 1 is enabled to set all the time periods (P1, P2, P3, P4)

16-32 = 15: Source of timer 1 = P1 + P2 + P3 + P4)

 Selection of RTC speed is determined by timer 1

16-36 = 1: Timer 1 is enabled.

Frequency setting is speed-stage 0 (05-01).

Rotation direction (16-37) is set to 0000b.

Then, the rotation direction of time period 1~4 (P1~P4) is corresponding to the setting of 16-37.

 Choose two constant speeds (speed 1 & speed 2)

16-36 = 5: Timer 1+2 is enabled.

When timer 1 is enabled, frequency setting is speed-stage 1; while timer 2 is enabled, frequency

setting is speed-stage 2.

Then, when timer 1 and timer 2 are active, direction of motor rotation is forward rotation.

Note: Select RTC offset (16-30) and set RTC offset time (16-31) to enable the offset time. Inverter runs

depending on the arranging time period to timer function. Refer to the following Fig.4.4.88.

Worked example16-13=1;P1 14=06:00,15=22:00,16=17=1;P2 18=08:00,19=20:00,20=2,21=5;P3 22=08:00,23=18:00,24=25=6;P4 26=08:00,27=12:00 with parenthesis12:00AM as printed,28=29=7.32=15 all periods;36=1 stage0;37=0000b.36=5 example timer1 stage1/timer2 stage2;simultaneous stage3 remains332. Offset30/31 continues334.

Manual — RTC offset and accuracy — page 334

Time gap

(G16- 31)

t

Multi-function digital input

(G03- 00 to 03- 05 = 56)

Offset Time

Figure 4.4.88 Operation of offset time

For example:

Inverter runs at the time period exclusive P1:

When 16-36=1 (selection of RTC speed is set to timer 1) and 16-32=17 (offset + PI), RTC offset (16-30) is

set by DI and the offset time is set via 16-31. Switch on DI and RTC will immediately start up.

If the source of timer is set to 15 (P1+P2+P3+P4), press “STOP” key at the time period 1 (P1). Normally,

RTC will start automatically at the next time period (P2) but it can also start via the setting of 16-30 to 2 (set

by DI). Inverter re-runs when switching on DI and RTC will immediately start up.

Notes:

If press “STOP” key at the time period and inverter can re-run at this time, user can:

-

Set the selection of RTC offset (16-30) to 2 (set by DI) and set DI to 56 (RTC Offset Enable).

Switch the selection of RTC offset (16-30) to be enabled.

Note:

RTC Accuracy:

Fig4.4.88 DI03-00..05=56 rising pulse starts16-31 offset time;offset remains active after input pulse falls. Example36=1,32=17 offset+P1,30DI enables immediate run. STOP during P1 normally waits P2;30=2 DI56 or30enabled may restart same period. Accuracy table25°C77°F ±3sec/day;−20/+50°C(−4/122°F) ±6sec/day;slash notation retained without invented test conditions.

RTC offset and accuracy. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval.

RTC offset and accuracy. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: +25℃(77℉)

RTC offset and accuracy. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: -20 / +50 ℃ (-4/ 122℉)

RTC offset and accuracy table2 — PDF page 334

Source row Temperature Deviation
1 +25℃(77℉) +/-3 sec./ day
2 -20 / +50 ℃ (-4/ 122℉) +/-6 sec./ day

Manual — IM auto-tuning ranges — page 335

Group 17: IM Motor Automatic Tuning Parameters

*1. Values of motor rated voltage are for 200V class, double the values for 400V class.

*2. The setting range of motor rated frequency is 0.0 to 599.0 Hz.

17-00 modes0 rotation,1 static,2 stator resistance,4 loop,5 combined4+2+0,6 combined4+2+1;3 reserved explained336. Motor current17-02 V/F10–200%,SLV25–200% inverter rated.17-04 table4.8–599Hz conflicts footnote0–599.17-06 even2–16poles. All table ranges, voltage classes, units and error codes retained;footnote double400V not applied again to already explicit400V row.

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval.

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17- 00

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17- 01

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17- 02

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17- 03

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17- 04

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17- 05

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17- 06

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17- 08

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17- 09

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17- 10

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17- 11

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17-12

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17-13

IM auto-tuning ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 17-14

IM auto-tuning ranges table1 — PDF page 335

Source row Source row label Source value or description
1 17- 00 Mode Selection of Automatic Tuning
2 Range 【0】: Rotation Auto-tune 【1】: Static Auto-tune 【2】: Stator Resistance Measurement 【4】: Loop Tuning 【5】: Rotational Auto-tuning Combination (Item: 4+2+0) 【6】: Static Auto-tuning Combination (Item: 4+2+1)
3 17- 01 Motor Rated Output Power
4 Range 【0.00~600.00】KW
5 17- 02 Motor Rated Current
6 Range 10%~200% of the inverter rated current in V/F control mode 25%~200% of the inverter rated current in SLV control mode
7 17- 03 Motor Rated Voltage*1
8 Range 200V:【50.0~240.0】V 400V:【100.0~480.0】V
9 17- 04 Motor Rated Frequency*2
10 Range 【4.8~599.0】Hz
11 17- 05 Motor Rated Speed
12 Range 【0~24000】rpm
13 17- 06 Pole Number of Motor
14 Range 【2~16】pole (Even)
15 17- 08 Motor No-load Voltage
16 Range 200V:【50~240】V 400V:【100~480】V
17 17- 09 Motor Excitation Current
18 Range 【0.01~600.00】A (15%~70% motor rated current)
19 17- 10 Automatic Tuning Start
20 Range 【0】: Disable 【1】: Enable
21 17- 11 Error History of Automatic Tuning
22 Range 【0】: No Error 【1】: Motor Data Error 【2】: Stator Resistance Tuning Error 【3】: Leakage Induction Tuning Error 【4】: Rotor Resistance Tuning Error 【5】: Mutual Induction Tuning Error 【6】: Reserved 【7】: DT Error 【8】: Motor Acceleration Error 【9】: Warning
23 17-12 Leakage Inductance Ratio
24 Range 【0.1~15.0】%
25 17-13 Slip Frequency
26 Range 【0.10~20.00】Hz
27 17-14 Rotational Tuning Mode Selection
28 Range 【0】: VF Mode 【1】: Vector Mode

Manual — IM tuning modes and inputs — page 336

Auto-tuning

Based on the motor nameplate set the motor rated output power (17-01), motor output rated current

(17-02), motor rated voltage (17-03), motor rated frequency (17-04), motor rated speed (17-05) and

number of motor poles (17-06) to perform an auto-tune.

Automatic tuning mode selection (17-00)

17-00=0: Perform rotational auto-tune (High performance auto-tune)

After executing Rotational auto-tuning (17-00), Excitation current (02-09), Core saturation coefficient

1 (02-10), Core saturation coefficient 2 and Core saturation coefficient 3 will renew the value.

17-00=1: Perform a static non-rotational auto-tune

Motor does not rotate during auto-tuning and this tuning causes lower power at low speed.

After executing Static auto-tuning (17-00=1), Proportion of motor leakage inductance (02-33) and

Motor slip (02-34) will renew the value.

17-00=2: Perform stator resistance non-rotational auto-tune (V/F mode) when using long motor leads.

This tuning causes lower power at low speed.

After executing Stator resistance measurement (17-00=2), Resistance between wires (02-15) will

renew the value.

17-00=3: Reserved

17-00=4: Loop tuning makes optimization for current loop response to improve the bandwidth of urrent

and torque.

17-00=5: Rotational auto-tuning combination is three-in-one auto-tuning, including loop tuning

(17-00=4), stator resistance measurement (V / F) (17-00=2), and rotation auto-tuning (17-00=0).

17-00=6: Static auto-tuning combination () is three-in-one auto-tuning, including loop tuning (17-00=4),

stator resistance measurement (V / F) (17-00=2) and static auto-tuning (17-00=1).

Motor rated output power (17-01)

Set by inverter capacity (13-00)

Motor rated current (17-02)

Set the range to 10 %~200 % of the inverter rated current.

Motor rated voltage (17-03)

Motor rated frequency (17-04)

Motor rated speed (17-05)

When tuning a special motor (e.g. constant power motor, high-speed spindle motor), with a motor rated

voltage or rated motor frequency that is lower than a standard AC motor, it is necessary to confirm the

motor nameplate information or the motor test report.

Prevent the inverter output voltage from saturation when the motor rated voltage is higher than the inverter

input voltage (see Example 1).

Example 1: Motor rated voltage (440V/60Hz) is higher than the inverter input voltage (380V/50 Hz).

17-00=0 updates02-09 excitation and02-10 core coefficient1 plus unnumbered coefficients2/3. Mode1 updates02-33 leakage and02-34slip, verified by second visual reading;mode2 updates02-15wire resistance;3reserved;4loop;5=4+2+0;6=4+2+1.17-02 prose10–200% generic versus SLV minimum335. Special motor requires nameplate/test report. Example1 motor440V60Hz,input380V50Hz continues337.

Manual — Voltage-frequency examples and no-load voltage — page 337

Figure 4.4.89 Rated voltage and frequency settings

Step 1: Set motor rated voltage, 17-03=440V.

Step 2: Set no-load voltage, 17-08=360V, lower the input voltage by 20V when operating in torque control.

Step 3: Set motor rated frequency:

Step 4: Automatically tuning

Parameter 01-12 (Fbase) is automatically set during auto-tuning. Parameter 01-12 (Fbase) is set to the

motor rated frequency.

Step 5: Set the 01-12 (Fbase) to the motor rated frequency on the motor nameplate. If the maximum

output frequency (01-02, Fmax) and base frequency (01-12, Fbase) are different, set the maximum output

frequency when the auto- tuning (01-02, Fmax) is completed.

When the inverter input voltage (or frequency) is higher than the motor rated voltage (or frequency), set the

motor rated voltage (17-03) and the motor rated frequency (17-04) to the rated frequency on the motor

nameplate.

Example 2: The inverter input voltage and frequency (440V/50Hz) are higher than the motor rated voltage

and frequency (380V/33Hz), set 17-03 to 380V (rated motor voltage) and 17-04 to 33Hz (motor rated

frequency).

■ Number of poles (17-06)

Set the motor pole number with its range is 2, 4, 6, 8 and 16 poles. (It is only 2~8 poles in inverter

software V1.3.

■ Motor no-load voltage (17-08)

a) Motor no-load voltage is mainly used in SLV mode, set to value 10~50V lower than the input

voltage to ensure good torque performance at the motor rated frequency.

b) Set to 85 ~ 95% of the motor rated voltage. In general, the no-load voltage can be closer to the

motor rated voltage for larger motors, but cannot exceed the motor rated voltage.

c) The motor no-load voltage can be set to a value greater than the actual input voltage. In this case,

the motor can only operates under relatively low frequency. If the motor operates at the rated

frequency an over voltage condition may occur.

d) The higher the motor power is, the higher the no-load voltage is.

e) A smaller no-load voltage will reduce the no-load current.

f) When load is applied the magnetic flux is weakened and the motor current increases.

g) A higher no-load voltage results in a higher the no-load current.

h) When load is applied the magnetic flux weakens and the motor current increases. Increasing the

magnetic flux generates back EMF and results in poor torque control.

Fig4.4.89 shows17-03 below440V and17-04 below60Hz, while step1 sets17-03=440V. Step2 example17-08=360V input minus20V. Formula17-04= rated frequency × input voltage / denominator printed rated frequency of motor nameplate;numeric60Hz×380V/440V=51.8Hz. Retain wrong denominator label,do not silently repair. Auto-tune sets01-12 then restores nameplate frequency,adjust01-02 ifdifferent. Example2 input440V50Hz/motor380V33Hz uses17-03380 and17-0433. Poles list2,4,6,8,16;softwareV1.3only2–8.17-08 SLV10–50V belowinput,85–95%rated;aboveinput restricted lowfreq/OV risk. No example applied universally.

Manual — Tuning sequence and mode conditions — page 338

■ Motor excitation current (17-09)

a) Only the static-type or stator resistance measurement auto-tuning (17-00=1 or 17-00=2) can be

set. This data can be obtained by manual tuning. Normally, it does not require adjusting.

b) Motor excitation current is used for non-rotational auto-tuning.

c) The setting range of motor excitation current is 15%~70% of the motor rated current.

d) If this parameter is not set, the inverter calculates the motor related parameters.

■ Automatic tuning start (17-10)

Set parameter 17-10 to 1 and press ENTER the inverter will display “Atrdy” for Auto-tune ready. Next,

press RUN key to start the auto-tune procedure. During auto-tuning the keypad will display “Atune “for

Auto-tune in progress. When the motor is successfully tuned, the keypad shows "AtEnd".

■ Error history of automatic tuning (17-11)

If auto-tuning fails the keypad will display the AtErr" message and the auto-tune cause is shown in

parameter 17-11. Refer to section 5 for troubleshooting and possible automatic tuning error causes.

Note: The motor tuning error history (17-11) shows the tuning result of the last auto-tune. No error is

displayed when auto-tune is aborted or when the last auto-tune was successful.

■ Motor Leakage Inductance Ratio (17-12)

a) Only stator resistance measurement auto-tuning (17-00=2) can be set and this data can be

obtained by manual tuning. Normally, it does not require adjustment.

b) It is mainly for non-rotational auto-tuning. The default setting is 3.4%. It is required to tune to make

the adjusted parameter value saved into the group 02-33.

c) If this parameter is not set, the inverter calculates the motor related parameters.

■ Motor Slip Frequency (17-13)

b) It is mainly for non-rotational auto-tuning. The default setting is 1Hz. It is required to tune to make

the adjusted parameter value saved into the group 02-34.

Notes:

longer than 167ft (50m).

(using short motor leads between the inverter and motor) and a “Stator resistance measurement”

(17-00=2) next.

excitation current (02-09), core saturation compensation factor 1-3 (02-11 - 02-13).

■ Rotational Tuning Mode Selection (17-14)

It is only enabled in rotation auto-tuning (17-00=0) and rotational auto-tuning combination (17-00=5).

17-14=0,

Under VF control mode, no-loading can drive general standard induction motors without oscillation.

And it is the most widely used mode.

Note: If VF mode rotational tuning is failed, try Vector mode rotational tuning to run again.

17-09 only static1/stator2,15–70%rated.17-10=1 ENTER Atrdy→RUN Atune→AtEnd success;AtErr failure17-11. NoError also aborted,not proof success.17-12 onlymode2 default3.4%,saved02-33;13 only2 default1Hz saved02-34. Leads>167ft(50m) mode2;source advises rotation0shortleads then2,or manual02-18/09/core02-11..13 ifrotation impossible.17-14 enabled0/5;0VF standardIM no-load,tryvectorifVF fails. Mode1continues339.

Manual — Slip compensation settings and formula — page 339

17-14=1,

Under VF control mode, no-loading drives particular induction motor with oscillation. And such kinds of

motors mostly are high-speed type.

Note: Because Vector mode measures no-load current of motor by internal current vector structure, so

the particular induction motor can avoid the oscillated problem in the VF control mode.

Group 18: Slip Compensation Parameters

Slip compensation automatically adjusts the output frequency based on the motor load to improve the

speed accuracy of the motor mainly in V/F mode.

The slip compensation function compensates for the motor slip to match the actual motor speed to the

reference frequency.

Slip compensation adjustment in V/F mode

18-00: Slip compensation gain at low speed

The adjustment of slip compensation gain at low speed follows the below procedure:

  1. Set the rated slip and the motor no-load current (02-00).

  2. Set the slip compensation (18-00) to1.0 (factory default setting is 0.0 in V / F control mode)

  3. For the operation with a load attached, measure the speed and adjust the slip gain (18-00)

accordingly (increase in steps of 0.1).

-

If the motor speed is lower than frequency reference, increase the value of 18-00.

If the motor speed is higher than frequency reference, decrease the value of 18-00.

When the output current is greater than the no-load current (02-00), the slip compensation is enabled and

the output frequency increases from f1 to f2. Refer to Fig.4.4.90., the slip compensation value is calculated

as follows:

[Output current (12-08) – motor no-load current (02-00)]

Slip compensation value = Motor rated sync induction rotation difference x

[Motor output rated current (02-01) –motor no-load current (02-00)]

17-14=1 vector for particular high-speedIM oscillation duringVF tuning. Group18 ranges preserve lowgain0–2.5,highgain−1..1,limit0–250%,filter0–10s,regen0/1,FOC1–1000ms/gain0–2. VF procedure sets no-load02-00,18-00=1(default0VF),adjust.1. Formula slipvalue=motor rated sync induction rotation difference × [(outputcurrent12-08−no-load02-00)/(ratedcurrent02-01−no-load02-00)]. References retained despite other sections differing.

Slip compensation settings and formula. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval.

Slip compensation settings and formula. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 18- 00

Slip compensation settings and formula. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 18- 01

Slip compensation settings and formula. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 18- 02

Slip compensation settings and formula. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 18- 03

Slip compensation settings and formula. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 18- 04

Slip compensation settings and formula. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 18- 05

Slip compensation settings and formula. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 18- 06

Slip compensation settings and formula table1 — PDF page 339

Source row Source row label Source value or description
1 18- 00 Slip Compensation Gain at Low Speed
2 Range 【0.00~2.50 】
3 18- 01 Slip Compensation Gain at High Speed
4 Range 【-1.00~1.00】
5 18- 02 Slip Compensation Limit
6 Range 【0~250】%
7 18- 03 Slip Compensation Filter Time
8 Range 【0.0~10.0】sec
9 18- 04 Regenerative Slip Compensation Selection
10 Range 【0】: Disable 【1】: Enable
11 18- 05 FOC Delay Time
12 Range 【1~1000】msec
13 18- 06 FOC Gain
14 Range 【0.00~2.00】

Manual — Slip limits and regeneration — page 340

Figure 4.4.90 Slip compensation output frequency

18-02: Slip compensation limit

Sets slip compensation limit in constant torque and the constant power operation (Fig.4.4.91).

If 18-02 is 0%, the slip compensation limit is disabled.

Figure 4.4.91 Slip compensation limit

When the slip compensation gain 18-00 at low speed is adjusted, and the actual motor speed is still lower

than the reference frequency, the motor may be limited by the slip compensation limit.

Note: Make sure that the slip compensation limit 18-02 does not exceed the maximum allowed system

limit.

18-03: Slip compensation filter

Set slip compensation filter time in V/F mode

18-04: Regenerating slip compensation selection

The selections to enable or disable the slip compensation function during regeneration.

To enable slip compensation during regeneration caused by deceleration (SLV mode), set 18-04 to 1 in

case speed accuracy is required. When the slip compensation function is used regenerative energy might

increase temporarily (18-04= 1) therefore a braking module might be required.

SLV mode adjustment

18-00: Slip compensation gain

a) Slip compensation can be used to control the full rang speed accuracy under load condition.

b) If the speed is lower than 2 Hz and the motor speed decreases, increase the value of 18-00.

c) If the speed is lower than 2 Hz and the motor speed increases, reduce the value of 18-00.

Slip compensation gain uses a single value for the whole speed range. As a result the slip compensation

accuracy at low speed is high but slight inaccuracies might occur at high speeds.

Adjust parameter 18-02 together with the compensation value or continue to adjust 18-00 if the speed

accuracy at higher speed is not acceptable. Please note adjusting these parameters might impact the

accuracy at lower speeds.

The impact of 18-00 on the torque and the speed are shown in Fig.4.4.92.

Fig4.4.90 load torque vs speed: smallerloadf1/largerloadf2 shift curves,no unlabelled magnitudes inferred.18-02=0 disableslimit. Fig4.4.91 plateau18-04 toFbase01-12,then rises to(01-02/01-12)×18-04atFmax01-02 despite18-02 section.18-03 VFfilter;18-04 regenSLVdecel may needbrake.18-00 whole range;below2Hz speedfallsincrease/speedrisesdecrease;higher-speed improvements may affectlow-speed.

Manual — Slip gains and torque-speed diagrams — page 341

Figure 4.4.92 18-00 Effect on the torque and speed

18-01: Slip compensation gain at high speed

It is not required to adjust the Slip compensation gain at high speed if the motor is loaded. After adjusting

parameter 18-00 it is recommended to increase the reference frequency and check the motor speed. In

case of a speed error increase the value of 18-01 to adjust the compensation. Increase the motor rated

frequency (01-12 base frequency) and increase the value of 18-01 to reduce the speed error. If the speed

accuracy becomes worse due to an increase in motor temperature it is recommended to use a

combination of 18-00 and 18-01 for adjustment.

Compared to 18-00, 18-01 serves as a variable gain for the full speed range. Parameter 18-01 determines

the slip compensation at the motor rated speed and is calculated follows:

[Slip compensation gain at high speed x frequency reference]

Slip compensation gain = Slip compensation gain at low speed +

[Motor rated frequency]

Figure 4.4.93 18-00/18-01 Slip compensation gain versus frequency reference

Figure 4.4.94 18-01 Effect on torque speed curve

Fig4.4.92 18-00 decrease left-sloping/increase right-sloping torque-speed curve. Formula total gain=low-speedgain + high-speedgain×frequencyreference/motorratedfrequency. Fig4.4.93 baseline18-00,increment18-01 at marked reference;no numeric breakpoint shown. Fig4.4.94 high-speed18-01 shifts/tilts curves more at higher speeds;source prose conditional retained,not autonomous tuning advice.

Manual — FOC adjustment — page 342

18-05: FOC (Flux Orient Control) delay time

In the SLV mode, the slip compensation of the magnetic flux depends on the torque current and excitation

current. If the motor load rises above 100% while running at the motor rated frequency, the motor voltage

and resistance drops sharply, which may cause the inverter output to saturate and current jitter occur. The

magnetic flux slip compensation will independently control the torque current and the excitation current to

prevent current jitter. For slow speed or fixed speed operation, 18-05 may be increased. For fast operation

adjust 18-06.

18-06: Slip compensation gain

If the motor is jittering at the rated frequency under full load, the value of 18-06 may gradually be reduced

to zero to reduce current jitter.

SLV loadabove100%atratedfrequency may causevoltage saturation/currentjitter per source.18-05 independently controls torque/excitation current;slow/fixedspeedincrease05,fastoperationadjust06. Full-loadrated-frequencyjitter may reduce06towardzero. Source explanation retained,no guaranteed performance.

Manual — ASR speed control settings — page 343

Group 20 Speed Control Parameters

The following figure an overview of the automatic speed regulator (ASR) block.

SLV control mode:

The ASR function adjusts the output frequency to control the motor speed to minimize the difference

between the frequency reference and actual motor speed.

The ASR controller in SLV mode uses a speed estimator to estimate the motor speed. In order to reduce

speed feedback signal interference, a low-pass filter and speed feedback compensator can be enabled.

Group20 ASR gain00/02,integral01/03,limit04,P/PI07,delay08;observerP09/11,I10/12;filters13/14,switch15/16,torquecomp17/18,constantdetect33. Matrix preserves seconds/milliseconds/Hz/percent distinctions,including20-18−10..10%. SLV speed estimator and low-pass feedback scope.

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval.

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 00

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 01

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 02

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 03

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 04

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 07

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 08

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 09

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 10

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 11

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 12

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 13

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 14

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 15

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 16

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 17

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 18

ASR speed control settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20-33

ASR speed control settings table1 — PDF page 343

Source row Source row label Source value or description
1 20- 00 ASR Gain 1
2 Range 【0.00~250.00】
3 20- 01 ASR Integral Time 1
4 Range 【0.001~10.000】Sec
5 20- 02 ASR Gain 2
6 Range 【0.00~250.00】
7 20- 03 ASR Integral Time 2
8 Range 【0.001~10.000】Sec
9 20- 04 ASR Integral Time Limit
10 Range 【0~300】%
11 20- 07 Selection of Acceleration and Deceleration of P/PI
12 Range 【0】: PI speed control will be enabled only in constant speed. For accel/decel, only use P control. 【1】: Speed control is enabled either in constant speed or accel/decal.
13 20- 08 ASR Delay Time
14 Range 【0.000~0.500 】Sec
15 20- 09 Speed Observer Proportional (P) Gain 1
16 Range 【0.00~2.55】
17 20- 10 Speed Observer Integral(I) Time 1
18 Range 【0.01~10.00】Sec
19 20- 11 Speed Observer Proportional (P) Gain 2
20 Range 【0.00~2.55】
21 20- 12 Speed Observer Integral(I) Time 2
22 Range 【0.01~10.00】Sec
23 20- 13 Low-pass Filter Time Constant of Speed Feedback 1
24 Range 【1~1000】mSec
25 20- 14 Low-pass Filter Time Constant of Speed Feedback 2
26 Range 【1~1000】mSec
27 20- 15 ASR Gain Change Frequency 1
28 Range 【0.0~599.0】Hz
29 20- 16 ASR Gain Change Frequency 2
30 Range 【0.0~599.0】Hz
31 20- 17 Torque Compensation Gain at Low Speed
32 Range 【0.00~2.50】
33 20- 18 Torque Compensation Gain at High Speed
34 Range 【-10~10】%
35 20-33 Constant Speed Detection Level
36 Range 【0.1~5.0】%

Manual — ASR block and gain switching — page 344

The ASR integrator output can be disabled or limited. The ASR output is passed through a low-pass filter.

Frequency

Reference

Speed

Observer

Motor Voltage

Motor Current

P

I

I Limit

Feedback

Compensator

LP Filter

Error

20-07 = 1 (during accel/decel)

20-07 = 0

Speed Control Integral Reset

03-00 to 03-05 = 43

Primary

delay time

Torque

Limit

+

-

Figure 4.4.95 ASR block diagram (SLV mode)

ASR setting (SLV control mode)

In SLV mode the ASR gain is divided into a high-speed and low-speed section. The speed controller has a

high-speed gain 20-00/20-01 and a low-speed gain 20-02/20-03 that can be set independently.

a) The high/low switch frequency can be set with parameter 20-15 and 20-16. Similar to the ASR

gain, the speed estimator has a high-speed gain 20-09/20-10 and a low-speed gain 20-11/20-12.

b) The speed estimator has a low-pass filter to reduce the speed feedback interference, parameter

20-13 and 20-14 are active at high speed as well as low speed. The switch between the

high-speed and the low-speed is set by parameter 20-15 and 20-16.

c) 20-17 sets the low-speed compensation gain of the speed feedback.

d) 20-18 sets the high-speed compensation gain of the speed feedback.

e) When the frequency reference is rises above the value set in 20-16, the ASR gain used is set by

parameters 20-00 and 20-01.

f)

When the frequency reference falls below the value set in 20-15, the ASR gain used is set by

parameters 20-02 and 20-03.

g) Gain time constant is adjusted linearly when the speed command falls within the range of 20-15 to

20-16, for a smooth operation.

Figure 4.4.96 ASR gain setting (SLV mode)

Fig4.4.95 reference minus feedback→P00/02 andI01/03→Ilimit→07switch→positiveP+I→delay08→torquelimit→torquereference;DI03-00..05=43 resetsintegral. Motorvoltage/current→observer→compensator17/18→LP13/14→negativefeedback;observererrorP09/11+I10/12feedsobserver. HighASR00/01,low02/03;observerhigh09/10,low11/12. Below15low,above16high,linearbetween. Fig4.4.96 firsttwoP/Igraphs repeat00/01 labels;filter falls14→13 between15/16. Duplicategraphlabels retained.

Manual — ASR gain tuning — page 345

Tune the speed control gain

Refer to the following steps:

a. Gain adjustment of minimum output frequency

50% of inverter rated current, decrease the setting value of parameter 20-02 and increase that of

20-03.

b. Gain adjustment of maximum output frequency

c. Gain adjustment of accel./ decel. integral control

decel..

overshooting or oscillation. Refer to Fig. 4.4.97 & Fig.4.4.98.

When 20-07=1, start ASR Proportion (P) and Integer (I) control during accel/ decel. and steady state

When 20-07=0, start ASR Proportion (P) and Integer (I) control only during steady state and use ASR P

control during accel/ decel..

Parameter 20-33 (Constant Speed Detection Level) is active mainly for the setting value of 20-07 to be 0

and frequency command source to be analog input because there will be problems occur in analog input

signal if the noise causes the system judgment in not reaching the constant speed. Thus, adjust the setting

value of parameter 20-33 to avoid the occurrence of the problems.

During ASR gain tuning, the multi-function analog output (AO1 and AO2 terminal) can be used to monitor

the output frequency and motor speed (as shown in Fig.4.4.96).

SLV mode gain tuning (20-00~20-03, 20-09~20-18)

a) Complete the parameter tuning in normal operation.

b) Increase ASR proportional gain 1 (20-00), ASR proportional gain 2 (20-02), carefully monitor

system stability.

Use parameter 20-00 and 20-02 to adjust the speed response for each cycle. Tuning the settings of 20-00,

20-02 can increase system response, but may cause system instability. See Fig.4.4.97.

Figure 4.4.97 System response of ASR proportion gain

a) Reduce ASR integral time 1(20-01), ASR integral time 2 (20-02) and carefully monitor system

stability.

  1. A long integral time will result in poor system response.

  2. If the integral time setting is too short, the system may become unstable Refer to the following

figure.

AtFmin01-08 P2=20-02,I2=20-03;outputcurrent<50%inverterrated. AtFmax01-02 P1=20-00,but I1 printed20-02;laterI2 also20-02.07=1 PIall,0 Paccel/decel+PIsteady.33analognoisedetection context. Fig4.4.97 curve1 gain00too high oscillates,curve2too low slow;Ishortoscillates/longslow follows346. Parameter inconsistencies not corrected.

Manual — ASR integral and feedback filter — page 346

While tuning ASR P and I gain the system may overshoot and an over voltage condition can occur. A

braking unit (braking resistor) can be used to avoid an over voltage condition.

t

Motor

Speed

1 :

20-01 setting is too short(oscillation occurs)

2 :

20-01 setting is too long(slow response)

Figure 4.4.98 The response of ASR integral time

Both low-speed ASR gain and the high-speed gain can be set to the same values and only require to be

adjusted in case of system instability.

In case tuning of the ASR P and I gain 20-00~20-03 does not improve the system response, reduce the

low-pass filter time constant 20-13~20-14 to increase the bandwidth of the feedback system and re-tune

the ASR gain.

 Tune low-speed low-pass filter time constant 20-14, make sure the reference frequency is below

parameter 20-15 value.

 Tune high-speed low-pass filter time constant 20-13 at frequency reference, make sure the reference

frequency is above parameter 20-16 value.

 Increasing the low-pass filter time constant can limit the bandwidth of the speed feedback system and

may reduce the system response. Increasing the low-pass time reduces the speed feedback signal

interference but may results in sluggish system response when the load suddenly changes. Adjust the

low-pass filter time if the load stays fairly constant during normal operation. The low bandwidth of the

speed feedback must be supported by the low gain of ASR to ensure the stable operation.

 Decreasing the low-pass filter time constant may increase the bandwidth of the speed feedback and the

system response. Decreasing the low-pass time may increase the speed feedback interference

resulting in system instability when the load suddenly changes. Decrease the low-pass filter time is a

quick system response is required for rapidly changing loads. The high bandwidth of the speed

feedback allows for a relative high ASR gain.

 In case tuning 20-00 ~ 20-03 and the low-pass filter time constant 20-13 do not improve the system

response time, tuning the PI gain 20-09 ~ 20-12 of the speed estimator may be required.

 Setting a high gain for the speed estimator (high proportion (P) gain and small integral (I) time)

increases the bandwidth of the speed feedback, but may cause speed feedback interference resulting

in system instability.

 Setting a low gain for the speed estimator (small proportion (P) gain and high integral (I) time)

decreases the bandwidth of the speed feedback, may improve speed feedback interference resulting in

a more stable system.

 The default values for the ASR can be used in most applications, no adjustment is required. Adjusting

the low-pass filter time and speed estimator gains requires a good understanding of the overall system.

 Parameter 20-15 sets the gain switch frequency at low-speed and parameter 20-16 sets the gain switch

frequency at high-speed.

 Operating at a speed below 20-15 will result in a larger excitation current for low-speed operation

accuracy. When the frequency reference rises above 20-16, the inverter will output the rated excitation

current at the no-load voltage (02-19).

 For general purpose applications parameter 20-15 should be set to a value of 5 ~ 50% of the motor

base frequency.

Fig4.4.98 curve1 integral20-01too short oscillates/overshoots,curve2too longslow. Brake suggestion retainedsource. Filters13/14smaller faster/noisier,larger slower/morestable;low14below15/high13above16. ObserverhighPsmallI faster/noisier,lowPhighI slower/stable. Defaultsmostapps statementnot universal.15 recommended5–50%motorbase;above16ratedexcitationat no-loadvoltage02-19asprinted.

Manual — ASR compensation and derating — page 347

 If this value is too high, the inverter output may saturate. Parameter 20-16 should be set to a value of

4Hz or more above the value of 20-08.

 When experiencing speed jitter at high speed and stable operation during mid-range speed while

operating a heavy load (>100%), it is recommended to reduce the no-load voltage (02-19) or tune the

FOC parameters (18-05 ~ 18-06).

 Parameter 20-17 and 20-18 are for compensating speed feedback at low speed and high speed.

 Use parameter 20-17 to adjust the torque compensation gain for the low speed range. By tuning

20-17an offset is added to the torque-speed curve. Increase 20-17 when the no-load speed is lower

than the frequency reference. Decrease 20-17 when the no-load speed is higher than the frequency

reference. The effect on the torque-speed curve from 20-17 is shown as the following figure:

Figure 4.4.99 Effect on the torque-speed curve from 20-17

 Use parameter 20-18 to adjust the torque compensation gain for middle to high speed range. For most

general purpose applications it is not necessary to adjust the 20-18. By tuning 20-18an offset is added

to the torque-speed curve. Increase 20-18 when the no-load speed is lower than the frequency

reference. Decrease 20-18 when the no-load speed is higher than the frequency reference. The effect

on the torque-speed curve from 20-18 is shown as the following Fig.4.4.100.

Figure 4.4.100 Effect on the torque-speed curve from 20-17

ASR main delay time (20-08).

a) Does not required to be adjusted for general purpose applications

b) When the set value of 20-08 is set high, the speed response will and therefore system response

will decrease improving system stability.

ASR Integral Time Limit (20-04)

a) Setting a small value may prevent system response when the load suddenly changes.

Note:

bandwidth decrease slightly in application.

Source16 at least4Hzabove20-08(timeparameter). Fig4.4.99 17decrease shiftsleft/increase right;Fig4.4.100 labels18butcaption17. Heavyload>100%highspeedjitter reduce02-19orFOC18-05/06per source.08higherdelay slower/stable;04smalllimit limitsresponse. Bandwidthclaims50HzSV/PMSV,10HzSLV/PMSLV affectedkp,inertia,load,temp.20-34range0–25600;35title rangecontinues348.

ASR compensation and derating. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval.

ASR compensation and derating. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 34

ASR compensation and derating. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 20- 35

ASR compensation and derating table1 — PDF page 347

Source row Source row label Source value or description
1 20- 34 Derating of Compensation Gain
2 Range 【0.00~25600】
3 20- 35 Derating of Compensation Time

Manual — Torque quadrants and derating continuation — page 348

Derating of torque compensation function can reduce derating effect of ASR at shock load. Refer to Fig.

4.4.97 & Fig. 4.4.98.

20-34 Derating of Compensation Gain:

This gain effect is the same as the proportional gain of ASR (20-00, 20-02), but it is required to be with the

derating compensation time (20-35) of larger speed tolerance to prevent the inverter from oscillation.

20-35 Derating of Compensation Time:

This time constant is used for the inhibition of oscillation caused from parameter 20-34, but excessive

compensation time constant leading to slower output response is unfavorable to derating compensation.

The recommended setting value of 20-34 is 30~50 and that of 20-35 is 50~100ms.

Group 21 Torque Control Parameters

Torque limit can be set in two ways:

There are four torque limits that can be set separately, one for each quadrant:

(I) Positive torque limit in forward direction (21-05 positive torque limit)

(II) Positive torque limit of reverse direction (21-08 negative torque limit)

(III) Negative torque limit in reverse direction (21-06 forward regenerating torque limit)

(IV) Negative torque limit in forward direction (21-07 reversal regenerating torque limit)

Refer to Fig.4.4.101.

Figure 4.4.101 Torque limit setting

Torque limit setting by using multi-function analog input AI2 (04-05)

Completes347 20-35range0–30000mSec.34likeP with35;recommended34=30–50,35=50–100ms.21-05positive/06negative/07forwardregen/08reverseregen each0–160%. Fig4.4.101 torquepositiveup/speedforwardright:Iupperright05forwarddrive;IIupperleft08reverseregen;IIIlowerleft06reversedrive;IVlowerright07forwardregen. Prose parenthetical names08negative,06forwardregen,07reversalregen differ;retain both.

Torque quadrants and derating continuation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval.

Torque quadrants and derating continuation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter20-35 range continued from347

Torque quadrants and derating continuation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 21- 05

Torque quadrants and derating continuation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 21- 06

Torque quadrants and derating continuation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 21- 07

Torque quadrants and derating continuation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 21- 08

Torque quadrants and derating continuation table1 — PDF page 348

Source row Source row label Source value or description
1 Range 【0~30000】mSec

Torque quadrants and derating continuation table2 — PDF page 348

Source row Source row label Source value or description
1 21- 05 Positive Torque Limit
2 Range 【0~160】%
3 21- 06 Negative Torque Limit
4 Range 【0~160】%
5 21- 07 Forward Regenerative Torque Limit
6 Range 【0~160】%
7 21- 08 Reversal Regenerative Torque Limit
8 Range 【0~160】%

Manual — Analog torque limits — page 349

Table 4.4.16 Torque limit analog input

Set the analog input terminal (AI2) signal level (04-00), gain (04-07) and bias (04-08)

The default setting for the analog input AI2 is 0 -10V representing 0 – 100% of the motor rated torque).

Fig.4.4.102 shows the relationship between the output torque and the torque limit.

Figure 4.4.102 Analog input torque limit (AI2)

When the analog input is set to positive torque limit (value = 11) the torque limit is active in the third and

fourth quadrant.in the reverse direction (regenerative torque in the second quadrant).

When the analog input is set to negative torque limit (value = 12) the torque limit is active in the third and

fourth quadrant.

When the analog input is set to regenerative torque limit (value = 13) the torque limit is active in the second

and fourth quadrant can be controlled.

When the analog input is set to positive/negative torque limit (value = 14) the torque limit is active in all four

quadrants.

When the analog input is at maximum (10V or 20mA), the torque limit is 100% of the motor rated torque. In

order to increase the torque limit above 100% the analog input gain (04-07) has to set to a value greater

than 100%. For example: 160.0% of the gain will result in the torque limit of 160% of motor rated torque at

10V (20mA) analog input level.

Table4.4.16 AI2 04-05 codes11positive,12negative,13regenboth,14positive+negative. Signallevelreference04-00,gain07,bias08 asprinted;default0–10V=0–100%ratedtorque. Fig4.4.102 I05,II08,III06,IV07;positive11/14upper,negative12/14lower,regen13hatchedII/IV. Positive11 prose erroneously saysIII/IV and reverseII;not reconciled.12III/IV,13II/IV,14all.10V/20mA100%,gain160%→160%example only.

Analog torque limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval.

Analog torque limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 11

Analog torque limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 12

Analog torque limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 13

Analog torque limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: 14

Analog torque limits table1 — PDF page 349

Source row 04-05 (AI2) Function
1 11 Positive torque limit
2 12 Negative torque limit
3 13 Regenerative torque limit (for both forward and reversal directions).
4 14 Positive/negative torque limit (positive and negative detection torque limit )

Manual — PM nameplate parameters — page 350

Group 22: PM Motor Parameters-

only available when PM Control Mode is selected

The PM parameter group can be restored to factory default be initializing the inverter (13-08).

1.

PM motor rated power (22-00); PM motor rated voltage (22-01); PM motor rated current (22-02)

Setting the motor nameplate value.

2.

PM motor pole number (22-03); PM motor rated rotation speed (22-04); PM motor rated frequency

(22-06). Setting the motor nameplate value. For the PM motor rated rotation speed (22-04) and the

PM motor rated frequency (22-06), just set one of the two and the program will automatically

calculate the other. When setting the PM motor rated rotation speed (22-04), the PM motor’s

maximum rotation speed (22-05) will synchronize and update to the same setting. When using the

flux-weakening function, the PM motor’s maximum rotation speed (22-05) setting value must be

revised. The formula is as follows:

Group22onlyPMcontrol. Everyrange retains voltageclass and motor/inverter currentbasis;03poles2–96,04/05speed6–60000rpm,06freq4.8–599Hz,07SPM0/IPM1.13-08resetcontext. Setting04or06 calculatesother;04also sets05same,weakeningneeds05revised. Formula N=120×f/P withf22-06andP22-03;not measuredspeed.

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval.

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 00

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22-01

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 02

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 03

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 04

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 05

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 06

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 07

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 10

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 11

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 14

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 15

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 16

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 17

PM nameplate parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 18

Adjacent source context — repeated to preserve continuation:

PM nameplate parameters table1 — PDF page 350

Source row Source row label Source value or description
1 22- 00 Rated Power of PM Motor
2 Range 【0.00~600.00】Kw
3 22-01 PM motor rated voltage
4 Range 200V: 【50 ~ 240】V 400V: 【100 ~ 480】V
5 22- 02 Rated Current of PM Motor
6 Range 25%~200% of inverter’s rated current
7 22- 03 Pole Number of PM Motor
8 Range 【2~96】Poles
9 22- 04 Rated Rotation Speed of PM Motor
10 Range 【6~60000】rpm
11 22- 05 Maximum Rotation Speed of PM Motor
12 Range 【6~60000】rpm
13 22- 06 PM Motor Rated Frequency
14 Range 【4.8~599.0】Hz
15 22- 07 PM type selection
16 Range 【0】SPM 【1】IPM
17 22- 10 PM SLV Start Current
18 Range 【20 ~ 200】%
19 22- 11 I/F Mode Start Frequency Switching Point
20 Range 【10 ~ 100】%
21 22- 14 PM Motor Armature Resistance
22 Range 【0.001 ~ 30.000】Ω
23 22- 15 PM Motor D-axis Inductance
24 Range 【0.01 ~ 300.00】mH
25 22- 16 PM Motor Q-axis Inductance
26 Range 【0.01 ~ 300.00】mH
27 22- 17 PM No-Load Voltage
28 Range 200V: 【0 ~ 250】V 400V: 【0 ~ 500】V
29 22- 18 Flux-weakening Current Command Restriction
30 Range 【0 ~ 120】%

Manual — PM start and flux weakening — page 351

3.

PM motor’s maximum rotation speed (22-05)

When using the flux-weakening function, the PM motor’s maximum rotation speed (22-05) must be

set higher than the PM motor’s rated rotation speed (22-04).

4.

PM type selection (22-07)

When using the SPM motor, the recommended setting is 0. Related adjustable parameters are the

speed estimated gain (22-30) and the speed estimated filter value (22-31).

When using the IPM motor, the recommended setting is 1. Related adjustable parameters are the

speed estimated gain (22-34) and the speed estimated filter value (22-35).

5.

PM SLV Start Current (22-10)

Set the torque current at start up and the unit is % of motor rated current.

6.

I/F Mode Start Frequency Switching Point (22-11)

This function is for the switching point from open-loop to close-loop in PMSLV mode. The unit is

percentage for rated speed of motor .It recommends that over 5% for 400V and over 10% for 200V.

7.

PM Armature Resistance (22-14)

Set the moto rresistance per phase in unit of 0.001Ω. This parameter is automatically set under the

motor auto-tuning (22-21).

Note: The motor resistance is different from the line resistance.

8.

PM Motor D-axis Inductance (22-15)

Set motor D-axis inductance in unit of 0.01mH. This parameter is automatically set under the motor

auto-tuning (22-21).

9.

PM Motor Q-axis Inductance (22-16)

Set motor Q-axis inductance in unit of 0.01mH. This parameter is automatically set under the motor

  1. Flux-weakening Current Command Restriction (22-18)

(1) When the MTPA’s selected (22-32) setting is 0, the setting parameter’s (22-05) maximum motor

rotation speed is higher than the parameter’s (22-04) motor rated rotation speed. This will

automatically activate the flux-weakening control. Set this parameter to restrict the maximum

flux-weakening capability. The unit is the motor’s rated current percentage.

(2) When the MTPA’s (22-32) selected setting is 2 or 3, and the output voltage is too high, the

flux-weakening voltage command restriction setting value must be raised.

Weakening05>04;SPM07=0uses30/31,IPM1uses34/35.10unit%motorcurrent.11unit%ratedspeed recommends>5%400V/>10%200V despitetable10–100%.14phase notline resistance,.001Ω;15D/16Q .01mH,auto21.18%motorcurrent when32=0 and05>04. Paragraphreferences32=2/3 despite352/354only0/1;retainconflict.

Adjacent source context — repeated to preserve continuation:

Manual — PM tuning and estimator ranges — page 352

SLV PM Motor Tuning (22-21)

WARNING!

Sudden start: The inverter and motor may start unexpectedly during Auto-Tuning, which could result in

death or serious injury. Make sure the area surrounding of the motor and load are clear before proceeding

with Auto-Tuning.

WARNING! Electric Shock Hazard

High voltage is supplied to the motor when performing an auto-tune, even when the motor is stopped,

which could result in death or serious injury. Do not touch the motor before performing the auto-tuning

procedure is completed.

WARNING! Holding Brake

Do not perform an auto-tuning procedure when the motor is connected to a brake this may result in

incorrect motor data calculation. Disconnect the motor and the load and confirm that the motor can freely

run.

  1. Before selecting PM motor tuning, enter the motor data (22-00) - (22-06) according to the motor

22-21disable/enable;22faultcodes0/5/7/9/11;25anglebeforestop/mode1/mode2;26PMSLV0–1;27voltage5–120%;28divider0–8;29weakening80–110%;30gain1–150%;31filter1–2000Hz;32MTPA0/1;33gain000–400%;34IPMgain1–300withnounit. Sourcewarningsunexpectedstart,shockevenstopped,holdingbrakeinvaliddata anddisconnectload/free-run preserved. Nameplatedata22-00..06sentencecontinues353.

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval.

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 21

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 22

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 25

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22-26

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 27

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 28

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22- 29

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22-30

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22-31

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22-32

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22-33

PM tuning and estimator ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source conflicts and visual associations retained; source fidelity only, not engineering approval. Row group: Parameter 22-34

PM tuning and estimator ranges table1 — PDF page 352

Source row Source row label Source value or description
1 22- 21 SLV PM Motor Tuning
2 Range 【0】: Disable 【1】: Enable
3 22- 22 Fault History of SLV PM Motor Tuning
4 Range 【0】: No Error 【5】: Circuit tuning time out 【7】: Other motor tuning errors 【9】: Current Abnormity Occurs while Loop Adjustment 【11】: Stator Resistance Measurement is Timeout
5 22- 25 Detection Mode Selection of Default Magnetic Pole
6 Range 【0】: Upon the angle before stopping 【1】: Mode 1 【2】: Mode 2
7 22-26 Estimator Mode
8 Range 【0~1】 (in PMSLV mode)
9 22- 27 Voltage Command of Mode 2
10 Range 【5~120】%
11 22- 28 Divider Ratio of Mode 2
12 Range 【0~8】
13 22- 29 Flux-weakening Voltage Command Restriction
14 Range 【80~110】%
15 22-30 Speed Estimated Gain
16 Range 【1~150】%
17 22-31 Speed Estimated Filter Value
18 Range 【1~2000】Hz
19 22-32 MTPA Selection
20 Range 【0】: Disabled 【1】: Mode 1
21 22-33 MTPA Gain
22 Range 【000~400】%
23 22-34 IPM Estimator Gain
24 Range 【1 ~300】

Manual — PM tuning sequence and rotor detection — page 353

nameplate.

2.

a) Use parameter 22-21 to select tuning mode.

b) Next press the enter key to go to the PM motor tuning screen. The keypad will display the

message of "IPrdy" (Ready to Tune).

c) Press run to start the PM motor tuning. The keypad will display the “IPtun" message during

auto-tune.

d) If the motor is successfully tuned, the message of "IPEnd " will be displayed. If auto-tune is

aborted with the stop key, the operator will display the message of " IPbrd " (PM motor tuning

aborted).

Notes:

  1. Perform a magnetic pole alignment auto-tune before adjusting the speed loop.

  2. It is not required to perform a magnetic pole alignment auto-tune each time the inverter is powered up.

Fault History of SLV PM Motor Tuning (22-22)

If PM motor tuning has failed, the “IPErr” message is shown on the keypad (PM motor tuning failure). Refer

to section 10 for the possible error causes and trouble shooting.

PM motor tuning fault history (22-22) only stores the result of the last auto-tune performed .If auto-tuning

was successful or aborted, no error will be displayed.

Detection Mode Selection of Default Magnetic Pole (22-25)

Select the motor activation’s rotor position detection method

Method 0: Do not detect rotor position, start by directly using the angle when the motor was previously

stopped

Method 1: Use input pulse signal to detect rotor position.

Method 2: Use input continuous variable frequency signal to detect rotor position.

Selection of rotor position detection mode when the motor starts:

22-25=0: Angle before Stop

The rotor position is not detected and the motor starts by the angle before Stop

22-25=1: Mode 1

Pulse input signals detect the rotor position and there is jitter in the detection process.

22-25=2, Mode 2

Input continuously variable frequency signals to detect the rotor position.

Estimator Mode (22-26)

 It is suggested to set 22-26=0 when SPM motor is used. Inverter starts in I/f mode and the relevant

adjustable parameters are 22-10 & 22-11.

 It is suggested to set 22-26=1 when IPM motor is used and speed control mode is performed by the

speed control ratio 1:50. Inverter will input the continuously variable frequency signal to motor and the

relevant adjustable parameters are 22-27 & 22-28.

Completes352 nameplate.21ENTER IPrdy→RUN IPtun→IPEndsuccess;STOP IPbrdabort;IPErrfailurehistory22. NoError successORabort,notproofsuccess. Polealignmentbeforespeedloop,notrequired eachpowerup.25=0priorangle/nodetection;1pulse+jitter;2continuousvariablefreq.26=0SPM I/F10/11;1IPM source speedcontrolratio1:50 and27/28;notguaranteedallvariants.

Manual — PM estimator and MTPA adjustment — page 354

Mode 2 Voltage Command (22-27)

When 22-25=2 (Mode 2), if the rotor jitters at start, it is required to tune up the set value of mode 2 voltage

command to ensure the accuracy of the detection angle.

Note: When the voltage value is set too high, an overcurrent error may be occurs.

Mode 2 Frequency Division Ratio (22-28)

When 22-25=2 (Mode 2), the input continuous signal frequency by mode 2 depends on the carrier

frequency setting (parameter 11-01). It is recommended that the higher the carrier frequency is required to

increase appropriately the frequency ratio to reduce the input continuous signal frequcncy so as to ensure

the accuracy of the detection angle.

Field-Weakening Voltage Control (22-29)

It is set to prevent the output voltage’s saturation. This setting value performs field-weakening control

depending on the inverter’s input power supply and voltage to be the limitation of output voltage command.

If parameter 22-18 (Flux-Weakening Control) is set too low, the inverter’s output voltage will exceed the

voltage command control.

Speed Estimated Gain (22-30), Speed Estimated Filter Value (22-31)

When Estimator Mode 22-26 set to 0, adjust the speed response performance, the higher the setting value,

the faster the motor reacts, however, if the setting value is too high, the control object will generate

vibrations and become unstable, also, if the setting value is lower, the speed deviation will increase.

Please adjust to the appropriate setting value according to the field equipment.

MTPA Selection (22-32)

0: MTPA invalid

1: Distribute D-Q-axis current command according to the torque command.

MTPA Gain (22-33)

When the default value is 200%, revising the PM motor’s D-axis inductance (22-15) or Q-axis inductance

(22-16) (such as completing the PM motor adjustment or directly changing the inductance value) will

re-calculate the MTPA Gain (22-33).

IPM Estimator Gain (22:34)

When the estimator mode (22-26) setting is 1, the estimator gain is the multiple of the bandwidth. The

larger the setting value, the faster the motor response. However, if the value is too high, the control item

will exhibit vibration and become unstable. The smaller the setting value, the greater the speed deviation.

Please adjust the appropriate setting value according to the site equipment.

25=2jitteradjust27buttoo highOC;28divisiondependscarrier11-01,highercarrierincreasefrequencyratio.29preventsvoltage saturation;18toolowexceedsvoltagecommandcontrol.26=0adjust30/31,higherfasterbutunstable/lowerdeviation.32=0invalid/1DQcurrentdistribution.33default200%;changingD15/Q16recalculates33.26=1IPMgain34bandwidthmultiplier;higherresponse/instabilitytradeoff. RemainingPMparameters from355outsidepacket.

Manual — Pump/HVAC functions and pressure — page 355

Group 23 Pump & HVAC Function Parameters

*1: It is new added in firmware V1.4

Select function of pump or HVAC via parameter 23-00. This function is enabled if PID control mode (10-03)

is enabled. Function of pump or HVAC affects PID target value and if parameter group 23 are enabled.

When 23-00=1, LCD keypad switches automatically the main screen monitoring (16-00) to operating

pressure setting (12-74), the sub-screen monitoring 1 (16-01) to pressure feedback value (12-75) and

sub-screen monitoring 2 (16-02) to output frequency (12-17).

When 23-00=2, LCD keypad switches automatically the main screen monitoring (16-00) to flow meter

target setting (12-77), the sub-screen monitoring 1 (16-01) to flow meter feedback (12-71) and sub-screen

monitoring 2 (16-02) to output frequency (12-17).

When 23-00=3, selection of main frequency command source (00-05) can be set except PID mode and

V/F curve is limited to F (01-00). Middle output voltage (01-07) is automatically set to the half of maximum

output voltage and parameter 01-00 will be hidden.

Notes:

disabled. (It is new added in inverter software V1.4.)

Remarks 3: 23-00 and 24-00 are interlocked. If selecting function selection 23-00, then you

cannot select Pump Control Function Selection 24-00. Vice versa. (V1.51 Newly Added)

Set the inverter as the Master or Slave 1~3 via parameter 23-01. Refer to Fig.4.4.111 for the functional

process of dual pump start to enable multiple pumps in parallel. It is required to reconnect to write in the

parameter after it is set.

Set the pressure value depending on the pressure transmitter of pump system after setting 10-00 to 0

(keypad given).

PDF355 starts Group23 Pump/HVAC,not a continuation of Group22 PM parameters. This corrects the part14 prospective boundary note only;354values remain unchanged.23-00=0off/1pump/2HVAC/3compressor(newV1.4);PID10-03 required forpump/HVAC. PumpLCDmain12-74,sub12-75/output12-17;HVACmain12-77,sub12-71/output12-17. Compressor excludesPIDfrequency,curveF01-00,midvoltage01-07halfmax;curveparameterhidden. Note00-00≠0(V/F) disablespump/compressor retainedliteral.23-00and24-00interlockedV1.51.23-01single0/master1/slave1=2/slave2=3/slave3=4;reconnectafterchange.02pressure.10–650PSI,10-00=0.

Pump/HVAC functions and pressure. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Pump/HVAC functions and pressure. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 00

Pump/HVAC functions and pressure. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 01

Pump/HVAC functions and pressure. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 02

Pump/HVAC functions and pressure table1 — PDF page 355

Source row Source row label Source value or description
1 23- 00 Function Selection
2 Range 【0】: Disable 【1】: Pump 【2】: HVAC 【3】: Compressor *1

Pump/HVAC functions and pressure table2 — PDF page 355

Source row Source row label Source value or description
1 23- 01 Setting of Single & Multiple Pumps and Master & Alternative
2 Range 【0】: Single Pump 【1】: Master 【2】: Slave 1 【3】: Slave 2 【4】: Slave 3

Pump/HVAC functions and pressure table3 — PDF page 355

Source row Source row label Source value or description
1 23- 02 Operation Pressure Setting
2 Range 【0.10 ~ 650.00】PSI

Manual — Pressure scaling and units — page 356

Set the maximum preesure value depending on the pressure transmitter of pump system. Parameter

23-02 is limited to this maximum value.

Pressure command source is given the value set by 23-02 (Operation Pressure Setting) or AI. Refer to

parameter 10-00 for the setting of AI terminal.

Note: Refer to section 3.3.4.1 for single/ Multi-pump wiring diagram.

23-02 (Operation pressure setting) is limited by 23-71 (Maximum pressure setting). 23-71 is limited by

23-03 (Maximum Pressure of Pressure Transmitter)

When 23-20=1,

Parameters 23-09, 23-24, 23-34, 23-38 and 23-39 are proceeding to switch percentage on the basis of

parameter 23-02 and parameters 23-12 & 23-15 are on the basis of parameter 23-03.

When 23-20=0,

Parameters 23-09, 23-24, 23-34, 23-38, 23-39, 23-12 and 23-15 is displayed and set via pressure mode.

For example, 23-02=4.00PSI, 23-03=10.00PSI, 23-09=0.5PSI, 23-12=5.00PSI

When 23-20=01,

((23-09)/ (23-02))*100 => 23-09 = 13% (Rounded to integer)

((23-15)/ (23-03))*100 => 23-15 = 50% (Rounded to integer)

When 23-20=10,

((23-09)/100)* 23-02 => 23-09 = 0.52PSI

((23-15)/100)* 23-03 => 23-15 = 5.00PSI

When 23-00=1 and 23-20=0, the LCD keypad dispays the unit upon the setting value by parameter 23-36

and unit diplay of parameters 12-74, 12-75, 23-02, 23-03, 23-09, 23-12, 23-15, 23-23, 23-24, 23-34, 23-38,

23-39 is switched at the same time.

23-02≤23-71≤23-03;04=0parameter02/1AIvia10-00.20=1percent:09/24/34/38/39 based02;12/15based03.20=0pressure. Workedexample02=4PSI,03=10PSI,09=.5PSI,12=5PSI but formulasuse15:09round13%,15=50%;reverse09=.52PSI,15=5PSI. Rounding is lossy,not normalized.36LCDunits0PSI/1inW/2Bar/3Pa,pump00=1and20=0;listedparameterdisplaysswitchtogether.

Pressure scaling and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Pressure scaling and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 03

Pressure scaling and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 04

Pressure scaling and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-71

Pressure scaling and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 20

Pressure scaling and units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 36

Pressure scaling and units table1 — PDF page 356

Source row Source row label Source value or description
1 23- 03 Maximum Pressure of Pressure Transmitter
2 Range 【0.10 ~ 650.00】PSI

Pressure scaling and units table2 — PDF page 356

Source row Source row label Source value or description
1 23- 04 Pump Pressure Command Source
2 Range 【0】: Set by 23-02 【1】: Set by AI
3 23-71 Maximum Pressure Setting
4 Range 【0.10 ~ 650.00】PSI

Pressure scaling and units table3 — PDF page 356

Source row Source row label Source value or description
1 23- 20 Switching of Pressure and Percentage
2 Range 【0】: Pressure 【1】: Percentage

Pressure scaling and units table4 — PDF page 356

Source row Source row label Source value or description
1 23- 36 PUMP Unit Display (only for LCD)
2 Range 【0】: PSI 【1】: inW 【2】: Bar 【3】: Pa

Manual — Displays and PID ranges — page 357

This function can have the common display of target and feedback pressure or display separately.

 when 23-05=0000:Led keypad displays pressure setting value and pressure feedback value.

Two-digit in the left is the pressure value setting and two-digit in the right is the pressure feedback value

in the seven-segment monitor.

Note: When 23-00=2 (HVAC), the unit will be multiplied by 1000 times. If the display value is 5.0, it

means 5000GPM (It is only displayed in inverter software V1.4.)

 when 23-05=0001:Led keypad only displays the pressure setting value.

 when 23-05=0002:Led keypad only displays the pressure feedback value.

Notes:

decimal." 10-33 is lower than 1000 and 10-34=1 in the PID modes.

23-05=0target+feedback:sevensegmentleft2.0/right1.8;1targetonlydisplay02.0;2feedbackonlyunderscore01.8. HVAC00=2 display×1000,5.0=5000GPM,onlysoftwareV1.4. Target>10integerdisplay;PID10-33<1000/10-34=1. PumpV1.3 requires23-03≤9.9PSI.06P0–10,07I0–100s,08D0–10s.

Displays and PID ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Displays and PID ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 05

Displays and PID ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 06

Displays and PID ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 07

Displays and PID ranges. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 08

Displays and PID ranges table1 — PDF page 357

Source row Source row label Source value or description
1 23- 05 Display Mode Selection
2 Range 【0】: Display of Target and Preesure Feedback 【1】: Only Display Target Pressure 【2】: Only Display Pressure Feedback

Displays and PID ranges table2 — PDF page 357

Source row Source row label Source value or description
1 23- 06 Proportion Gain (P)
2 Range 【0.00~10.00】
3 23- 07 Integral Time (I)
4 Range 【0.0~100.0】Sec
5 23- 08 Differential Time (D)
6 Range 【0.00~10.00】Sec

Manual — PID adjustment guide — page 358

Figure 4.4.103 Diagram of pressure feedback value

Table 4.4.17 Guide for PID parameter adjustment

Notes:

Figure 4.4.104 Diagram for PID parameter adjustment

Stablized deviation

Overshooting

23-02: Target Pressure Value

Pressure Feedback

Signal

Stablized Time

Output after PID

adjustment

Output before PID

Fig4.4.103 pressurefeedbackovershoots23-02target thenundershoots andsettlesbelow;arrows denoteovershoot,stabilizedtime/deviationwithoutnumericvalues. Table4.4.17 pairspros/cons for eachP/I/D;source P increase response time and mainfeature increase stabilized time retainedliteral. IncreasingI smooth/slower,decreasingI faster/rapidfrequency;increasingDavoidovershoot/instability,decreasingDstability/overshoot. Fig4.4.104topafterloweroscillation,bottombeforehigher. Supplierguideonly.

PID adjustment guide. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

PID adjustment guide. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Proportional Gain (P)

PID adjustment guide. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Integral Time (I)

PID adjustment guide. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Differential Time (D)

Shared source cells (coordinates refer to this table):

PID adjustment guide table2 — PDF page 358

Source row ⟦blank source cell⟧ Increase Setting Value Decrease Setting Value Main Feature
1 Proportional Gain (P) (Pros) Increase response time (Pros) Reduce jittering Increase stabilized time
2 ⟦null: no independent source value⟧ (Cons) Might cause pump jittering (Cons) Slow down response ⟦null: no independent source value⟧
3 Integral Time (I) (Pros) Smooth output frequency (Pros) Fast response For smooth feedback variations
4 ⟦null: no independent source value⟧ (Cons) Slow down response (Cons) Change rapidly output frequency ⟦null: no independent source value⟧
5 Differential Time (D) (Pros) Avoid overshooting (Pros) System stability Respond to system rapid variations
6 ⟦null: no independent source value⟧ (Cons) System instability or motor jittering (Cons) Overshooting easily ⟦null: no independent source value⟧

Manual — Constant-pressure sleep — page 359

*1: 23-20=0, presents the unit and range.

*2: 23-20=1, presents the unit and range.

When pressure feedback value is higher than 23-02 (operation pressure setting), inverter output frequency

will decrease downward into sleep status. PID starts (output frequency will increase) when pressure

feedback value is less than (23-02) – (23-09).

*: (When the motor’s maximum output frequency is over than 300Hz, the frequency resolution is

0.1Hz.)

When inverter output frequency falls below 23-10 (sleep frequency of constant pressure), it starts to count

the sleep time (23-11).

When the inverter finishes counting the sleep time (23-11), the output frequency falls downward at the

deceleration time (00-15) and gets into sleep status.

Note: Parameter 23-10 (sleep frequency of constant pressure) is dedicated by the pump and it is

not applied to parameter 10-17 (start frequency of PID sleep).

Bar

Hz

time

Sleep Delay Time

Target Pressure

Value

Sleep Tolerance

Range

Pressure

Feedback

Signal

Output

Frequency

Sleep Tolerance Range: |(23-02) – PID Feedback| < 23-09

Sleep Frequency

Figure 4.4.105 Diagram for stop time of constant pressure

Note: The purpose of stop time of constant pressure is energy saving.

09and34.01–650PSI when20=0/1–100%when20=1. Feedback>target02outputdecreases;feedback<02−09PIDincreases. Sleep10=0–599Hz,11=0–255.5s;resolution.1HzifmotorFmax>300. Below10for11then00-15decelstop. Pump10distinctfromgeneralPID10-17. Fig4.4.105 tolerance |02−feedback|<09 aroundtarget,lowertracecrosses10then11delayanddecel. Energy-savingpurposeclaimretained.

Constant-pressure sleep. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03.

Constant-pressure sleep. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03. Row group: Parameter 23- 09

Constant-pressure sleep. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03. Row group: Parameter 23- 34

Constant-pressure sleep. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03. Row group: Parameter 23- 10

Constant-pressure sleep. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03. Row group: Parameter 23- 11

Constant-pressure sleep table1 — PDF page 359

Source row Source row label Source value or description
1 23- 09 Tolerance Range of Constant Pressure
2 Range 【0.01~650.00】PSI *1 【1~100】% *2
3 23- 34 Tolerance Range of Constant Pressure 2
4 Range 【0.01 ~ 650.00】PSI *1 【1~100】% *2

Constant-pressure sleep table2 — PDF page 359

Source row Source row label Source value or description
1 23- 10 *Sleep Frequency of Constant Pressure
2 Range 【0.00~599.00】Hz

Constant-pressure sleep table3 — PDF page 359

Source row Source row label Source value or description
1 23- 11 Sleep Time of Constant Pressure
2 Range 【0.0~255.5】Sec

Manual — Pressure limits and high warning — page 360

*1: 23-20=0, presents the unit and range.

*2: 23-20=1, presents the unit and range.

It is convenient for user to limit maximum pressure. When pressure feedback value is higher than

maximum pressure limit, the inverter displays warning signal and then stops.

It is convenient for user to limit minimum pressure. When pressure feedback value is lower than minimum

pressure limit, the inverter displays warning signal and then stops.

Figure 4.4.106 Diagram for pressure feedback limit

Note: The pressure under the control of PID is between the maximum pressure limit (23-12) and

minimum pressure limit (23-15).

When pressure feedback value is higher than maximum pressure limit, warning time of high pressure

starts to count. If pressure feedback value is lower than maximum pressure limit during counting time, the

warning time will recount and the inverter will display the warning signal of HIPb when the warning time

ends.

When the warning signal of high pressure occurs and pressure feedback value is higher than maximum

pressure limit, stop time of high pressure starts to count. If pressure feedback value is lower than

maximum pressure limit during counting time, the stop time will recount and the inverter will display stop

error signal of OPbFt when the stop time ends.

Note: When user does not want the inverter to be restricted by the maximum pressure, set 23-74=0

(disable) to disable the function of high pressure limit.

23-02 Target Pressure Value

23-12 Maximum Pressure Limit

23-15 Minimum Pressure Limit

Pressure Feedback

Signal

12max.10–650PSI/0–100%,15min0–650PSI/0–100%,mode20selects. Fig4.4.106 target02between12upperand15lower,feedbackoscillatesaroundtarget.13warning0–600s,14stop0–600s;above12 continuously13→HIPb,then14→OPbFt andstop;dropbelow12resetscounts.74=0disableshighlimit. Generalstopstatementreadwith74laterchoices.

Pressure limits and high warning. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03.

Pressure limits and high warning. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03. Row group: Parameter 23- 12

Pressure limits and high warning. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03. Row group: Parameter 23- 15

Pressure limits and high warning. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03. Row group: Parameter 23- 13

Pressure limits and high warning. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03. Row group: Parameter 23- 14

Pressure limits and high warning table1 — PDF page 360

Source row Source row label Source value or description
1 23- 12 Maximum Pressure Limit
2 Range 【0.10 ~ 650.00】PSI *1 【0~100】% *2

Pressure limits and high warning table2 — PDF page 360

Source row Source row label Source value or description
1 23- 15 Minimum Pressure Limit
2 Range 【0.00 ~650.00】PSI *1 【0~100】% *2

Pressure limits and high warning table3 — PDF page 360

Source row Source row label Source value or description
1 23- 13 Warning Time of High Pressure
2 Range 【0.0 ~ 600.0】Sec

Pressure limits and high warning table4 — PDF page 360

Source row Source row label Source value or description
1 23- 14 Stop Time of High Pressure
2 Range 【0.0 ~ 600.0】Sec

Manual — High-pressure timing and low warning — page 361

Figure 4.4.107 Diagram for warning to stop at high pressure limit

When 23-74=0, High pressure warning or error is disabled.

When 23-74=1, High pressure warning is enabled. High pressure error is disabled.

When 23-74=2, High pressure warning or error is enabled. Refer to the instruction of Fig. 4.4.107.

When pressure feedback value is lower than minimum pressure limit, warning time of low pressure starts

to count. If pressure feedback value is higher than minimum pressure limit during counting time, the

warning time will recount and the inverter will display the warning signal of LoPb when the warning time

ends.

23-12 Maximum Pressure Limit

Bar

23-02 Target Pressure Value

23-15 Minimum Pressure Limit

Pressure Feedback Output

Stop along the deceleration time (00-15)

time

Hz

HIPb

T1 < (23-13); Recounting after T1

T2 = (23-13); Keypad flashes and displays HIPb

T3 = (23-14); Keypad flashes and displays OPbFt

T1

T2

T3

OPbFt

Fig4.4.107 T1<13resets;T2=13HIPb;T3=14OPbFt,deceleration00-15startsafterT3. Yellowtraceabove12;target02andmin15separate.74=0off/1warningonlynoerror/2warningorerror.16lowwarning0–600s;below15continuously16→LoPb,above15resets.

High-pressure timing and low warning. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

High-pressure timing and low warning. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 74

High-pressure timing and low warning. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 16

High-pressure timing and low warning table1 — PDF page 361

Source row Source row label Source value or description
1 23- 74 High Pressure Setting
2 Range 【0】 Disable 【1】 High Pressure Warning 【2】 High Pressure Warning or Error

High-pressure timing and low warning table2 — PDF page 361

Source row Source row label Source value or description
1 23- 16 Warning Time of Low Pressure
2 Range 【0.0 ~ 600.0】Sec

Manual — Low-pressure timing — page 362

When the warning signal of low pressure occurs and pressure feedback value is lower than minimum

pressure limit, stop time of low pressure starts to count. If pressure feedback value is higher than minimum

pressure limit during counting time, the stop time will recount and the inverter will display stop error signal

of LPbFt when the stop time ends.

Note: When user does not want the inverter to be restricted by the minimum pressure, set 23-75=0

(disable) to disable the function of low pressure limit.

Figure 4.4.108 Diagram for warning to stop at low pressure limit

When 23-75=0, Low pressure warning or error is disabled.

When 23-75=1, Low pressure warning is enabled. Low pressure error is disabled.

When 23-75=2, Low pressure warning or error is enabled. Refer to the instruction of Fig. 4.4.108.

23-12 Maximum Pressure Limit

23-02 Target Pressure Value

23-15 Minimum Pressure Limit

Pressure Feedback Output

Stop along the deceleration time (00-15)

機

time

Bar

Hz

LoPb

T1 < (23-16); Recounting after T1

T2 = (23-16); Keypad flashes and displays LoPb

T3 = (23-17); Keypad flashes and displays LPbFt

T1

T2

T3

LPbFt

17lowfault0–600s followswarning16;below15for17→LPbFt,above15resets. Fig4.4.108 T1<16resets,T2=16LoPb,T3=17LPbFt followed00-15decel;feedbacklowerlimit15,upper12,target02.75=0off/1warningonly/2warningorerror. Prior reviewed363–365 water-pressure detection fields remain separate,not duplicated.

Low-pressure timing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Low-pressure timing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 17

Low-pressure timing. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 75

Low-pressure timing table1 — PDF page 362

Source row Source row label Source value or description
1 23- 17 Fault Stop Time of Low Pressure
2 Range 【0.0 ~ 600.0】Sec

Low-pressure timing table3 — PDF page 362

Source row Source row label Source value or description
1 23- 75 Low Pressure Setting
2 Range 【0】Disable 【1】Low Pressure Warning 【2】Low Pressure Warning or Error

Manual — Loss-pressure and water-pressure detection parameters — page 363

When23-19=0 or23-78=0, function of loss pressure detection is disabled.

When23-19>0, if feedback pressure is lower than【(23-02) x (23-19)】and detection time of loss pressure(23-18) passes, the inverter jumps to fault signal(FBLSS).

When23-78=1, the inverter displays a warning signal when detecting loss of pressure. When23-78=2, it displays an error signal.

Acceleration time of water pressure detection(23-26) and deceleration time of water pressure detection(23-27) correspond to acceleration time2(00-16) and deceleration time2(00-17), so the setting of23-26 changes with the setting of00-16. Avoid using the multi-speed application function while using PUMP function.

Hyphenated codes are parameter identifiers. Loss-pressure and water-pressure detection functions remain separate. Footnote-conditioned PSI/% ranges are not interchangeable.

Source wording couples23-26/23-27 to00-16/00-17, then explicitly mentions setting changes only for23-26/00-16. Preserve wording without extending the assertion.

Distinct labels Warning versus Low Pressure Error retained.

Condition is an editorial context column carrying the source footnotes; no row-specific condition stated means absence of a stated qualifier, not a blank source cell. No unit conversion or recommended setpoint.

Loss-pressure parameters — PDF page 363

Source row Parameter Source name Source range/options
1 23-18 Time of Loss Pressure Detection 【0.0 ~ 600.0】 Sec
2 23-19 Proportion of Loss Pressure Detection 【0 ~ 100.0】 %
3 23-78 Selection of Loss Pressure Detection 【0】 Disable; 【1】 Loss Pressure Warning; 【2】 Low Pressure Error

Water-pressure detection parameters — PDF page 363

Source row Parameter Source name Source range/options Condition
1 23-23 Direction of Water Pressure Detection 【0】: Upward Detection; 【1】: Downward Detection [no row-specific condition stated]
2 23-24 Range of Water Pressure Detection 【0.0 ~ 65.00】 PSI *1:23-20=0 presents the unit and range
3 23-24 Range of Water Pressure Detection 【0~10】 % *2:23-20=1 presents the unit and range
4 23-25 Period of Water Pressure Detection 【0.0 ~ 200.0】 Sec [no row-specific condition stated]
5 23-26 Acceleration Time of Water Pressure Detection 【0.1 ~ 600.0】 Sec [no row-specific condition stated]
6 23-27 Deceleration Time of Water Pressure Detection 【0.1 ~ 600.0】 Sec [no row-specific condition stated]

Manual — Figure4.4.109 Diagram for upward detection of water pressure — page 364

Diagram label associations only; pressure/frequency traces, exact boundaries and time relationships remain original-only geometry. No numeric pressure, frequency or duration read from the drawing.

Axis Bar retained literally; parameter23-24 onPDF363 uses conditionalPSI/%. Do not silently convert or assert equivalence.

Direction-specific labels: upward23-26 acceleration; downward23-27 deceleration. Original figure remains authority for traces.

Direction and axes — PDF page 364

Source row Source label/context Source value
1 Direction selector 23-23=0
2 Direction label Upward Detection of Water Pressure
3 Upper vertical axis Bar
4 Lower vertical axis Hz
5 Horizontal axes time
6 Upper trace Pressure Feedback Value
7 Lower trace Output Frequency
8 Consumption regions Water Consumption Continues; Water Consumption Stops

Parameter-to-label associations — PDF page 364

Source row Parameter Printed label
1 23-24 Range of Water Pressure Detection
2 23-02 Target Pressure Value
3 23-26 Accel. Time of Water Pressure Detection
4 23-25 Period of Water Pressure Detection
5 23-11 Sleep Time of Constant Pressure
6 23-10 Sleep Frequency

Manual — Figure4.4.110 Diagram for downward detection of water pressure and operating context — page 365

23-25=0.0(sec) disables the function of water pressure detection. This statement appears both above and below the downward diagram.

When water pressure detection is enabled, it can shorten the time of jumping into sleep without water consumption or with mild water consumption. Source repeats this explanation above and below the diagram.

If water consumption frequently continues, source recommends extending the detection cycle(23-25) to reduce detection times and avoid fluttering or instability during water-pressure detection in constant-pressure operation. Repeated above and below diagram.

When upward detection starts, water pressure slightly increases. If water consumption continues this may cause brief pressure fluttering or instability. Source recommends reducing detection range(23-24), but this extends the time of jumping into sleep without water consumption or with mild consumption.

When downward detection starts, output frequency decelerates with deceleration time of water pressure detection(23-27). Water pressure reduces with deceleration when consumption continues; pressure feedback rises if the value is lower than target pressure(23-02) minus detection range(23-24).

Diagram label associations only; pressure/frequency traces, exact boundaries and time relationships remain original-only geometry. No numeric pressure, frequency or duration read from the drawing.

Operating explanations paraphrased faithfully with explicit source parameter IDs; these are supplier statements, not new engineering advice. No numerical operating settings chosen.

Axis Bar retained literally; parameter23-24 onPDF363 uses conditionalPSI/%. Do not silently convert or assert equivalence.

Direction-specific labels: upward23-26 acceleration; downward23-27 deceleration. Original figure remains authority for traces.

Direction and axes — PDF page 365

Source row Source label/context Source value
1 Direction selector 23-23=1
2 Direction label Downward Detection of Water Pressure
3 Upper vertical axis Bar
4 Lower vertical axis Hz
5 Horizontal axes time
6 Upper trace Pressure Feedback Value
7 Lower trace Output Frequency
8 Consumption regions Water Consumption Continues; Water Consumption Stops

Parameter-to-label associations — PDF page 365

Source row Parameter Printed label
1 23-24 Range of Water Pressure Detection
2 23-02 Target Pressure Value
3 23-27 Decel. Time of Water Pressure Detection
4 23-25 Period of Water Pressure Detection
5 23-11 Sleep Time of Constant Pressure
6 23-10 Sleep Frequency

Manual — Water detection comparison and forced run — page 366

Note: It may cause shortly fluttering or instability during water detection process. User can appropriately

adjust the range of water pressure detection (23-24) to avoid the occurrence of severe flutter.

Mild water consumption result in pressure reducing during deceleration and the inverter’s output frequency

may decrease to sleep frequency. But if pressure feedback value is lower than that of target pressure

value (23-02) - range of water pressure detection (23-24), the output frequency will accelerate again.

Table 4.4.18 Guide for comparison of water pressure detection direction

*: (When the motor’s maximum output frequency is over than 300Hz, the frequency resolution is 0.1Hz.)

This function is enabled when PID mode (10-03) is selected.

Pump will not depend on the feedback to make any PID output adjustment and runs the frequency of

00-05 (Frequency command) when multi-function digital input (S1~S6) is set to 16 (PID control disable).

And when the other digital input is set to 57(forced frequency run), inverter sets the frequency to run

depending on the parameter 23-28 (forced run command). If PID function disable is removed, the inverter

is controlled by PID.

Forced run command is applied to the situation when pressure sensor disconnects, control inverter output

via the external pressure sensor (ex. differential pressure switch).

Continues prior-reviewed365 downwardwaterdetection:iffeedback<02−24accelerateagain;flutteradjust24. Table4.4.18 upward maintainsabove-target/precision buthighlift impedes sleep;downward encourages sleep/energy,possiblepressurefluctuation via24/27. Startupmaster,slave1,2,3;sleep slave1,2,3,master.28forced0–599Hz,.1resolutionifFmax>300,PID10-03enabled;DI16bypassesPIDto00-05,DI57uses28,removebypasstorestorePID.29switchtime0–240hour/min;72=0hour/1minute;35headingcontinues367.

Water detection comparison and forced run. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Water detection comparison and forced run. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Upward

detection of

water

pressure

Water detection comparison and forced run. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Downward

Water detection comparison and forced run. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 28

Water detection comparison and forced run. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-29

Water detection comparison and forced run. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-72

Water detection comparison and forced run. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-35

Water detection comparison and forced run table1 — PDF page 366

Source row ⟦blank source cell⟧ Pros Cons
1 Upward detection of water pressure  Keep the pressure above the target pressure during this process.  For strict and precise applications  If “Pump lift” is too high, operation frequency is higher without water consumption or with mild water consumption. So this detection effect is too restricted to jump into sleep.  Energy-saving of water flow is not obvious and Slave is not easy to sleep under the multiple pumps in parallel.
2 Downward detection of water pressure  Jump into sleep status without water consumption or with mild water consumption.  For energy-saving purpose, under the multiple pumps in parallel regulate the pumps to the optimum operation state during this process.  Startup sequency is by Master, Slave 1, Slave 2, and Slave 3. Sleep sequency is by Slave 1, Slave 2, and Slave 3 and Master. After the switching time is allowable, alternate Master and Slave reach the average of life expectancy.  Pressure fluctuations may occur during this process if user inappropriately regulates the range of water pressure detection (23-24) and the deceleration time of water pressure detection (23-27).

Water detection comparison and forced run table2 — PDF page 366

Source row Source row label Source value or description
1 23- 28 *Foreced Run Command
2 Range 【0.00 ~ 599.00】Hz

Water detection comparison and forced run table3 — PDF page 366

Source row Source row label Source value or description
1 23-29 Switching Time of Multiple Pumps in Parallel
2 Range 【0 ~ 240】hour/min
3 23-72 Switching Time of Alternation in Parallel
4 Range 【0】: Hour 【1】: Minute
5 23-35 Selection of Multiple Pumps Shift Operation

Manual — Parallel-pump alternation and sync — page 367

If function of multiple pumps in parallel is enabled, the switching way is MasterSlave1 Slave2Slave3

 Master  … and the switching time is set via parameter 23-29.

Parameter 23-72 Switching Time of Alternation in Parallel

23-72=0, parameter 23-29 (Switching Time of Multiple Pumps in Parallel) will be in the unit of hour.

23-72=1, parameter 23-29 (Switching Time of Multiple Pumps in Parallel) will be in the unit of minute.

Note: It will recount the time if parameter 23-29 change time and the inverter re-power up.

Selection of Multiple Pumps Shift Operation (23-35)

23-35=1: Timer Alternative Selection

The Master and Slave of multiple pumps in parallel will be exchange, after the switching time of multiple

pumps in parallel.

23-35=2: Sleep Stop Alternative Selection

When the Master and Slave of multiple pumps in parallel are both in sleep mode, and after the detecting

time (23-30), the Master and Slave of multiple pumps in parallel will be exchange. Every time the multiple

pumps start, the exchange will be processed. Please refer to the diagram of sleep stop alternative

selection action.

23-35=3: Timer and Sleep Stop Alternative Selection

Timer alternately selected and sleep stop alternately selected will be enabled at the same time.

23-35=4: Multiple Pumps Test Mode

When master stop running and the slave need to run, please set 23-35=4, and no exchange between

Master and Slave.

When parameter 23-31 is set to 1 or 3, detection time of multiple pumps in parallel running start is enabled.

If water pressure can not reach the error range of constant pressure and water flow time is over the

detection time (23-30), Master will inform Slave of running start.

23-31=0: Disabled

23-31=1: Pressure Setting and Run/ Stop

Set 23-01 to 1, Pressure setting and Run/ Stop command are modified by Master and Slave follows

Master’s command. Run/Stop command from Slave can be regarded as the emergency stop command

with the highest priority.

23-31=2: Pressure Setting

Set 23-01 to 2, Pressure setting is modified by Master and Slave follows Master’s command to update

synchronously.

Completes36635range0none/1timer/2sleep/3both/4test. Rotationmaster→slave1→2→3→master after29;72unit,change29/re-powerresetscount. Sleepmodebothasleepafter30;test4masterstop/slaverunnoexchange.30detect0–30s enabled31=1/3.31sync0off/1pressure+runstop/2pressure/3runstop;prose repeatedlysets23-01ratherthan23-31;retain. Slaveemergencystopprioritysourceclaim.

Parallel-pump alternation and sync. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Parallel-pump alternation and sync. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter23-35 range continued from366

Parallel-pump alternation and sync. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 30

Parallel-pump alternation and sync. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 31

Parallel-pump alternation and sync table1 — PDF page 367

Source row Source row label Source value or description
1 Range 【0】: No function 【1】: Timer Alternative Selection 【2】: Sleep Stop Alternative Selection 【3】: Timer and Sleep Stop Alternative Selection 【4】: Multiple Pumps Test Mode

Parallel-pump alternation and sync table2 — PDF page 367

Source row Source row label Source value or description
1 23- 30 Detection Time of Multiple Pumps in Parallel Running Start
2 Range 【0.0 ~ 30.0】Sec

Parallel-pump alternation and sync table3 — PDF page 367

Source row Source row label Source value or description
1 23- 31 Synchronous Selection of Multiple Pumps in Parallel
2 Range 【0】: Disable 【1】: Pressure Setting and Run/ Stop 【2】: Pressure Setting 【3】: Run/Stop

Manual — Dual-pump startup — page 368

23-31=3: Run/Stop

Set 23-01 to 3, Run/ Stop command is set by Master and Slave follows Master’s command. Run/Stop

command from Slave can be regarded as the emergency stop command with the highest priority.

Notes:

1.

When Master modifies the pressure setting, it requires pressing ENTER key to modify the

pressure setting of Slave.

2.

When the switching time of multiple pumps in parallel (23-29) changes and reconnection, it will

recount the time.

Bar

Hz

time

Master

Slave

Pressure Feedback

Value

Target Pressure

Tolerance Range of

Constant Pressure

Output

Frequency

A

B

C

D

Detection

Time

Output Frequency

60Hz

Figure 4.4.111 Dual pumps start up process

A:Dual pumps are enabled during this time. Master starts up first and Slave is in standby to enter

constant-pressure operation.

B:Large water consumption results in the higher operation frequency of Master. If water pressure is not

lower than the tolerance range of constant-pressure and the operation time is not over the detection

time (23-30), Slave is still in standby.

C:If it is over the detection time (23-30), and Master runs at 60Hz, Master informs Slave of auxiliary

kicking water. After Slave operates, the operation frequency of Master and Slave reduces to the

operation of constant-pressure if water consumption is stable.

D:If water consumption is mild, the operation frequency of Master and Slave reduces. Because the water

consumption is less than that of the operation of dual pumps, Slave stops to sleep (please refer to

parameter 23-22 for dual pump slave sleep requirements) and only Master runs to reach

operation of dual pumps, the dominance between Master and Slave will exchange to operate.

That is, the parameter 23-01 of one inverter is set to 1 and that of the other inverter should be set to 2

and vice versa.

Completes31=3prose againsets23-01=3. MasterpressureENTERupdatesSlave;29change/reconnectresets. Fig4.4.111 A masterstarts/slavestandby;B highwaterdemandmasterfreqrises,belowpressuretolerance09for30needed;C after30at60Hzslavestarts andbothsettle;D milddemandreducesfreq,slave23-22sleep/mastercontinues.60Hzexample notuniversalrating.35=3timeorsleepexchanges;paired23-01mustone1other2. SourceBwordingnotlowerthan tolerance retained.

Manual — Sleep alternation sequence — page 369

Bar

Hz

time

Master

Slave

Pressure

Feedback Signal

Operation

Pressure Setting

Tolerance Range of

Constant Pressure

Output

Frequency

A

B

C

D

60Hz

E

F

Detection

Time

Sleep Frequency

of Constant

Slave Trip

Diagram of sleep stop alternative selection action

Note:

A:Dual pumps are enabled during this time. Higher operation pressure occurs, Master keeps operation

and Slave output frequency decreases.

B:Master operation frequency maintains 60Hz. If water pressure doesn’t decrease to the target constant

pressure and Slave continuously decreases to the set trip frequency (23-22), Slave detection time

(23-30) starts and Slave decelerates to stop.

C:If milder water consumption and higher water pressure occur and Slave operation command is in sleep

status, Master output frequency decreases to let the water pressure be in constant status when the

detection time (23-30) is over.

D:When Master operation frequency decreases to the sleep frequency of constant pressure (23-10),

Master will decrease to stop, water consumption is continuously mild and water pressure will reduce

slowly.

E:When water consumption stops, Master jumps into sleep and the pressure remains the same. And

Slave’s detection time (23-30) starts.

Diagrampressure02±09;master60Hzlevelthen23-10sleepthreshold;slave60Hzlevelthen23-22tripthreshold. A highpressuremasterholds/slavefalls;Bslavecrossestrip,30detectionthenstops;Cmasterfallsafterdetection;Dmastercrosses10andstops;Ebothsleep,slave30detection;Fslaveacceleratesafter30ascontinued370. No inferred numericstage durations.

Manual — Slave wakeup and trip frequency — page 370

F:When the detection time (23-30) is over, shift operation stops and virtual Master starts to become

Slave. The inverter operates in constant pressure under the target pressure value.

When multiple pumps are in parallel and the requirements of slave wake-up can not be achieved in

tolerance range, user can set parameter 23-73=1 and refer to the following conditions to wake up Slave.

  1. Master is in full speed operation (01-02 maximum output frequency) but pressure feedback value can

not achieve the target pressure value.

  1. Slave is forced to start after 30 seconds + time of (23-30) (even if the requirement of sleep to wake-up

is not achieved and the pressure feedback value is under the tolerance range of constant pressure)

and keeps operations to achieve the target pressure value.

  1. It is required to follow the formula (the set method 1) and refer to the following diagram to set the

wake-up requirements.

----------------------- set method 1

23- 22

T

加速時間1

副機跳脫頻率

最大輸出頻率

NG

F

當23-22(副機跳脫頻率)設定值太大

或23-30(並聯輔助打水偵測時間)太

短,會使副機進入休模式,使之設定

失效。

Diagram of requirements for waking up Slave

If Master and Slave start to run at the same time, Slave will stop depend on the condition listed as below.

When 23-22=0 Hz, if output frequency of Slave is lower than 23-10 (Sleep Frequency of Constant

Pressure) and after the time of 23-11 (Sleep Time of Constant Pressure), the Slave will be stop

automatically.

When 23-22 = 1 ~ 400 Hz (The maximum frequency follow 01-02), if the output frequency of Slave is lower

Maximum Output Frequency

Slave Disconnect Frequency

Acceleration Time

When the 23-22 (Slave Disconnect Frequency) setting

value is too high or 23-30 (Parallel Start Pump Detection

Time) is too short, it will make the Slave enter the Sleep

Mode, to make the setting ineffective.

Completes369F:after30shiftexchange,virtualmasterstartsasSlave asprinted.73=1whenmasterat01-02andfeedbackbelowtarget forcesSlaveafter30seconds+23-30. Formula(23-30)/(00-14)≥(23-22)/(01-02). Graphratio22/30<01-02/00-14labelssteeptrace;equalmiddle;>labelshallowNG,retainedgeometryandlabels despite slope mismatch. High22orlow30mayforcesleep.22table0–599Hz;0uses10and11sleep;prose1–400Hzcontinues371. Enlargedformulaimage retained.

Slave wakeup and trip frequency. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Slave wakeup and trip frequency. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-73

Slave wakeup and trip frequency. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 22

Slave wakeup and trip frequency table1 — PDF page 370

Source row Source row label Source value or description
1 23-73 Slave Wake-up Selection
2 Range 【0】Disable 【1】Enable

Slave wakeup and trip frequency table2 — PDF page 370

Source row Source row label Source value or description
1 23- 22 Slave Trip Frequency
2 Range 【0.00~599.00】Hz

Manual — Leakage variation detection — page 371

than 23-22, Master will inform Slave to stop and enter sleep mode, or output frequency of Slave is lower

than 23-10 (Sleep Frequency of Constant Pressure) and after the time of 23-11 (Sleep Time of Constant

Pressure), the Slave will be stop automatically.

*1: 23-20=0, presents the unit and range.

*2: 23-20=1, presents the unit and range.

*3: It is new added in inverter software V1.4.

Bar

Hz

time

Operation Pressure

Setting

Pressure Feedback

Value

Output

Frequency

Leakage

Detection

Time

∆P1

∆P2

Sleep

Leakage Detection Restart

Leakage Detection Case1: Pressure Variation > 23-38

Pressure Variation of Leakage Detection Restart

∆P1 < 23-38

∆P2 > 23-38

Notes:

pressure variation is larger than the value of parameter 23-38 in every detection time (23-37).

Completes370:nonzero22stopifbelow22 OR below10for11.37leakagedetect0–100s;38variation.01–65PSI/1–10%;39tolerance.01–650PSI/1–100%,20selectsunits;V1.4. Singlepump only,37=0off. Case1graphΔP1<38firstinterval37stayssleep;ΔP2>38secondintervalrestarts,frequencyramprestores02target. No numericΔP inferred.

Leakage variation detection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03.

Leakage variation detection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03. Row group: Parameter 23-37

Leakage variation detection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03. Row group: Parameter 23-38

Leakage variation detection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Pressure 1 applies23-20=0;percentage 2 applies23-20=1. Percentagebasis:23-09/24/34/38/39 use23-02;23-12/15 use23-03. Row group: Parameter 23-39

Leakage variation detection table1 — PDF page 371

Source row Source row label Source value or description
1 23-37 Leakage Detection Time *3
2 Range 【0.0~100.0】Sec
3 23-38 Pressure Variation of Leakage Detection Restart *3
4 Range 【0.01~65.00】PSI *1 【1~10】% *2
5 23-39 Pressure Tolerance Range of Leakage Detection Restart *3
6 Range 【0.01~650.00】PSI *1 【1~100】% *2

Manual — Leakage tolerance and local key — page 372

Bar

Hz

time

Pressure

Feedback Value

Output

Frequency

Leakage

Detection

Time

∆P1

Sleep

Leakage Detection Case2: Pressure Variation <23-38

Pressure Variation of Leakage Detection Restart

∆P1 < 23-38

∆P2 < 23-38

∆P3 < 23-38

∆P2

∆P3

Pressure Tolerance

Range of Leakage

Detection Restart

Operation

Pressure Setting

Notes:

state if pressure variation is lower than the value of parameter 23-38 in every detection time (23-37) and

pump will restart if pressure variation is larger than that of 23-38 or pressure tolerance range is over the

value of parameter 23-39 in the detection time.

condition of frequenct pump start and stop caused from the dropping pressure of water system due to

leakage.

User can switch reference frequency of the inverter and give the run command in the local or remote

mode.

Input source selection is determined by the source of frequency command (00-05) and the operation

modes (00-02).

23-41=0: Disable

Frequency command is controlled by terminal Al1 and Al2 when SEQ and REFsignal light up and run

command is controlled by terminal S1, S2 or RS485.

Case2ΔP1/2/3each<38;separate37intervals;accumulateddropbeyond39restarts,frequencyramprestores02.37=0off,singlepump only,variation>38 ORtolerance>39triggers.41localremote0disable/1enable;source00-05freq/00-02operation.41=0SEQ/REFlitonAI1/AI2freqandS1/S2orRS485run. Enablecontinues373.

Leakage tolerance and local key. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Leakage tolerance and local key. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-41

Leakage tolerance and local key table2 — PDF page 372

Source row Source row label Source value or description
1 23-41 Local/ Remote Key
2 Range 【0】∶ Disable 【1】∶ Enable

Manual — Energy and flow feedback — page 373

23-41=1: Enable

User can control FWD/REV key for the switch of Local / Remote key.

Frequency command is controlled by the keypad when SEQ and REF signal light off.

Note: Local mode is controlled by the keypad and remote mode is controlled by control circuit terminals or

RS485 connection.

When the inverter starts up, user can learn the motor accumulative output energy from parameter 12-67

(unit: kWHr) and 12-68 (unit: MWHr). User recalculates energy via the setting of parameter 23-42 to 1.

User caculates electricity price via the setting of electricity price per kWh (23-43) and learn the

accumulative electricity price from parameter 12-69 and 12-70.

Unit of accumulative electricity pulse output signal (23-44) is for kWh. When accumulating the electricity to

the setting unit of parameter 23-44, the pulse output signal of the electric meter or PLC is on lasting 200

msec.

Accumulative

Electricity Pulse

Output (PO)

Electricity Energy

the Unit Setting of

Accumulation

(23-44)

200mSec

off

on

Figure 4.4.112 Diagram for accumulative electricity pulse output

41=1FWD/REVtoggleslocal/remote;SEQ/REFoffkeypadlocal,terminal/RS485remote.42=0accumulate/1recalculate;12-67kWh/68MWh,price43range0–5nocurrency stated,cost69/70.44=0off,1.1kWh,2one,3ten,4hundred,5thousandkWh. Fig4.4.112 eachenergythreshold44 produces200ms ON pulse drawnlow,OFFhigh;activepolarityassociationretained.45feedback0off/1AI/2pulse;46headingcontinues374.

Energy and flow feedback. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Energy and flow feedback. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-42

Energy and flow feedback. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-43

Energy and flow feedback. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-44

Energy and flow feedback. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-45

Energy and flow feedback. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 46

Energy and flow feedback table1 — PDF page 373

Source row Source row label Source value or description
1 23-42 Energy Recaculating
2 Range 【0】: Disable (Energy Accumulating) 【1】: Enable
3 23-43 Electricity Price per kWh
4 Range 【0.000~5.000】

Energy and flow feedback table2 — PDF page 373

Source row Source row label Source value or description
1 23-44 Selection of Accumulative Electricity Pulse Output Unit
2 Range 【0】: Disable 【1】: Unit for 0.1kWh 【2】: Unit for 1kWh 【3】: Unit for 10kWh 【4】: Unit for 100kWh 【5】: Unit for 1000kWh

Energy and flow feedback table3 — PDF page 373

Source row Source row label Source value or description
1 23-45 Given Modes of Flow Meters Feedback
2 Range 【0】: Disable 【1】: Analog Input 【2】: Pulse Input
3 23- 46 Maximum Value of Flow Meters

Manual — HVAC flow range and limits — page 374

23-00=2: HVAC

HVAC is enabled when the source of main frequency command (00-05) is set to 5 (PID given) and

PID mode is enabled (10-03).

23-45: Given Modes of Flow Meters Feedback

Modes of flow meters feedback is given by analog input (AI) or pulse input (PI) and flow meter

(12-71) displays feedback value. Refer to the instruction of parameter 23-05 for PID display.

23-46: Maximum Value of Flow Meters

Maximum value of flow meters is the maximum value set by the target value of flow meters for HVAC

system.

23-47: Target Value of Flow Meters

This function sets the target value of flow meters for HVAC system depending on the setting of

10-00 to 0 (PID target value source is set by keypad.)

When 23-00=2, the LCD keypad dispays the unit upon the setting value by parameter 23-60 and unit

display of parameters 12-71,12-77,23-46,23-47 is switched at the same time.

It is convenient for user to limit the maximum flow value depending on the different situations. When flow

feedback value is higher than the maximum flow value, the inverter will display warning signal and then

stops.

When flow feedback is higher than the maximum flow limit, warning time of high flow starts to count. If the

flow feedback is lower than the maximum flow limit during counting time, the warning time will recount and

the inverter will display the warning signal of HFPb when the warning time ends.

When the warning signal of high flow occurs and flow feedback is higher than maximum flow limit, stop

time of high flow starts to count. If flow feedback is lower than maximum flow limit during counting time, the

stop time will recount and the inverter will display stop error signal of HIbFt when the stop time ends.

Note: When user does not want the inverter to be restricted by the maximum flow, set 23-76=0 (disable) to

disable the function of high flow limit.

Completes37346range1–50000GPM;47same. HVAC00=2,00-05=5PID,10-03enabled;45AI/pulse,feedback12-71,target47when10-00=0.60LCD0GPM/1FPM/2CFM/3GPH switches12-71/77/23-46/47.48max.01–99%;49warning0–255s→HFPb;50stop0–255s→HIbFt asprinted;below48resets.76=0disables.

HVAC flow range and limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

HVAC flow range and limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter23-46 range continued from373

HVAC flow range and limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 47

HVAC flow range and limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 60

HVAC flow range and limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-48

HVAC flow range and limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 49

HVAC flow range and limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 50

HVAC flow range and limits table1 — PDF page 374

Source row Source row label Source value or description
1 Range 【1~50000】GPM
2 23- 47 Target Value of Flow Meters
3 Range 【1~50000】GPM

HVAC flow range and limits table2 — PDF page 374

Source row Source row label Source value or description
1 23- 60 HVAC Unit Display (only for LCD)
2 Range 【0】: GPM 【1】: FPM 【2】: CFM 【3】: GPH

HVAC flow range and limits table3 — PDF page 374

Source row Source row label Source value or description
1 23-48 Maximum Flow Value of Feedback
2 Range 【0.01~99.00】%

HVAC flow range and limits table4 — PDF page 374

Source row Source row label Source value or description
1 23- 49 Maximum Flow Warning Time of Feedback
2 Range 【0~255】Sec

HVAC flow range and limits table5 — PDF page 374

Source row Source row label Source value or description
1 23- 50 Maximum Flow Stop Time of Feedback
2 Range 【0~255】Sec

Manual — High-flow timing and low-flow limits — page 375

FB

time

Target Value of Flow

Meters

Maximum Flow Value of

Feedback

T1

T2

T3

Stop along the

Deceleration Time

(00-15)

F

Flow Feedback

Output

HIPbt

HFPb

Figure 4.4.113 Diagram for warning to stop at high flow limit

When 23-76=0, High flow warning or error is disabled.

When 23-76=1, High flow warning is enabled. High flow error is disabled.

When 23-76=2, High flow warning or error is enabled. Refer to the instruction of Fig. 4.4.113.

It is convenient for user to limit the minimum flow value depending on the different situations. When flow

feedback value is lower than the minimum flow value, the inverter will display warning signal and then

stops.

When flow feedback is lower than the minimum flow limit, warning time of low flow starts to count. If the

flow feedback is higher than the minimum flow limit during counting time, the warning time will recount and

the inverter will display the warning signal of LFPb when the warning time ends.

When the warning signal of low flow occurs and flow feedback is lower than minimum flow limit, stop time

of low flow starts to count. If flow feedback is higher than minimum flow limit during counting time, the stop

time will recount and the inverter will display stop error signal of LObFt when the stop time ends.

Note: When user does not want the inverter to be restricted by the minimum flow, set 23-77=0 (disable) to

T1 < (23-49): Recounting after T1.

T2 = (23-49): Keypad flashes and displays HFPb

T3 = (23-50): Keypad flashes and displays HIPbt

Fig4.4.113 above48:T1<49resets,T2=49HFPb,T3=50HIPbt asprinted→00-15decel.76=0off/1warningonly/2warningorerror.51min.01–99%;52lowwarning0–255s→LFPb;53lowstop0–255s→LObFt asprinted;above51resets.77=0disablescontinued376. Faultlabel spellingsnot silently unified.

High-flow timing and low-flow limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

High-flow timing and low-flow limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 76

High-flow timing and low-flow limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-51

High-flow timing and low-flow limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 52

High-flow timing and low-flow limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 53

High-flow timing and low-flow limits table2 — PDF page 375

Source row Source row label Source value or description
1 23- 76 High Flow Setting
2 Range 【0】Disable 【1】High Flow Warning 【2】High Flow Warning or Error

High-flow timing and low-flow limits table3 — PDF page 375

Source row Source row label Source value or description
1 23-51 Minimum Flow Value of Feedback
2 Range 【0.01~99.00】%

High-flow timing and low-flow limits table4 — PDF page 375

Source row Source row label Source value or description
1 23- 52 Minimum Flow Warning Time of Feedback
2 Range 【0~255】Sec

High-flow timing and low-flow limits table5 — PDF page 375

Source row Source row label Source value or description
1 23- 53 Minimum Flow Stop Time of Feedback
2 Range 【0~255】Sec

Manual — Low-flow timing and low suction — page 376

disable the function of low flow limit.

FB

time

Target Value of Flow

Meters

Minimum Flow Value of

Feedback

T1

T2

T3

Stop along the

Deceleration Time

(00-15)

F

Flow

Output

LFPb

LOPbt

Figure 4.4.114 Diagram for low flow limited warning of stop

When 23-77=0, Low flow warning or error is disabled.

When 23-77=1, Low flow warning is enabled. Low flow error is disabled.

When 23-77=2, Low flow warning or error is enabled. Refer to the instruction of Fig. 4.4.114.

The hydraulic application can detect insufficient water in the tank resulting in low suction via HVAC

function. User can select the reaction of low suction (23-58) to run command. Low suction is detected by

parameter 23-54. Refer to Fig.4.4.115 for the process of low suction.

T1 < (23-52): Recounting after T1.

T2 = (23-52): Keypad flashes and displays LFPb

T3 = (23-53): Keypad flashes and displays LOPbt

Completes375disablelowlimit. Fig4.4.114 below51:T1<52resets,T2=52LFPb,T3=53LOPbt asprinted→00-15decel.77=0off/1warningonly/2warningorerror.54low-suction0off/1PIDerror/2current/3both;55detect0–30s;56PIDerror0–30%;57current0–100%motorrated;58reaction0disable/1warning/2fault/3faultrestart. HVACwater-shortage sourcecontext.

Low-flow timing and low suction. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Low-flow timing and low suction. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 77

Low-flow timing and low suction. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-54

Low-flow timing and low suction. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 55

Low-flow timing and low suction. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 56

Low-flow timing and low suction. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 57

Low-flow timing and low suction. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 58

Low-flow timing and low suction table2 — PDF page 376

Source row Source row label Source value or description
1 23- 77 Low Flow Setting
2 Range 【0】Disable 【1】Low Flow Warning 【2】Low Flow Warning or Error

Low-flow timing and low suction table3 — PDF page 376

Source row Source row label Source value or description
1 23-54 Detection Function of Low Suction
2 Range 【0】: Disable 【1】: PID Error Value 【2】: Current 【3】: Current and PID Error Value
3 23- 55 Detection Time of Low Suction
4 Range 【0~30.0】Sec
5 23- 56 PID Error Level of Low Suction
6 Range 【0 ~ 30】%
7 23- 57 Current Level of Low Suction (Motor Rated Current)
8 Range 【0 ~ 100】%
9 23- 58 Reaction of Low Suction
10 Range 【0】: Disable 【1】: Warning 【2】: Fault 【3】: Fault & Restart

Manual — Low-suction logic and response — page 377

PID Error Level

Reaction

of Low

Suction

Detection

Time

PID Error

Output Current

Detection of

Both of Two

PID Enable

Figure 4.4.115 Diagram for the process of low suction

When 23-54=0, detection function of low suction is disabled.

And refer to Table 4.4.19 for the detection logic of parameter 23-54 to select PID error of output current as

the detection signal.

Table 4.4.19 the detection logic of low suction

The detection level is required to be set by PID error level of low suction (23-56) and output current signal

(23-57) after selecting the detection signal.

The state of low suction experiences the detection time of low suction (23-55); when it is over the detection

time, low suction is active.

The reaction of low suction (23-58) is set by user to act. Refer to Table 4.4.20 for the detection signal of

water used.

When 23-58=3, refer to the instruction of parameter 07-01~07-02. Set fault auto-restart time by parameter

07-01 and the maximum number of fault auto-restart attempts is 10 by parameter 07-02.

Table 4.4.20 Detection signal of water used

Note: Low suction state is detected by if the signal is higher than PID error level or lower than output

current.

*3: It is new added in inverter software V1.4.

Fig4.4.115 comparatorPIDerror>56 AND PIDenable;current<57;54selectPID/current/bothAND→55time→58reaction. Table4.4.19 detection columnsPIDerror/current:1=1/0,2=0/1,3=1/1;notORfor3. Table4.4.20 58=0continuous/noindication,1continuousLSCFTflashwarning,2stopLSCFTfault,3stoprestartLSCFTfaultrestart.07-01time/07-02max10attempts. Bottomnote OR wording retainedwith54selectioncontext.59HVACtarget0parameter47/1AI,newV1.4;continued378.

Low-suction logic and response. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Low-suction logic and response. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: 1

Low-suction logic and response. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: 2

Low-suction logic and response. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: 3

Low-suction logic and response. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: 0

Low-suction logic and response. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 59

Low-suction logic and response table1 — PDF page 377

Source row 23-54 Detection Signal / PID Error Detection Signal / Output Current
1 1 1 0
2 2 0 1
3 3 1 1

Low-suction logic and response table2 — PDF page 377

Source row 23-58 Inverter Status Keypad Signal Error Signal
1 0 Continous Running None None
2 1 Continous Running LSCFT(Flash) Warning of Low Suction
3 2 Stop LSCFT Jump to Error for Low Suction
4 3 Stop and Restart LSCFT Jump to Error for Low Suction and Restart

Low-suction logic and response table3 — PDF page 377

Source row Source row label Source value or description
1 23- 59 Source of HVAC Pressure Command *3
2 Range 【0】: Set by 23-47 【1】: Set by AI

Manual — Compressor protection — page 378

23-59=0: Target value depends on parameter 23-47.

23-59=1: Convert the proportional target value of flow meters via AI1 input voltage value. Refer to

parameter 10-00 for the setting of AI terminal.

*3: It is new added in inverter software V1.4.

The application of water-cooled chiller is when the rated current of compressor operates for 1 to 2 minutes

easily to cause damage to compressor so the inverter is required to be set two- stage protection to protect

the compressor.

Protection of first stage:

When the inverter is at constant speed and the current is higher than the derating of current level (23-66)

(this is the percentage for the rated current of compressor), it will start to count the derating of delay time

(23-67). After the counting time is over the delay one, frequency command can reach the derating of

output frequency and reduce the current load via being multiplied by the derating of frequency gain (23-68).

When the current is lower than the derating of current level, output frequency will be restored to the

frequency command. The action of derating to restore is counted one time. When it repeats more than

three times, the output frequency will stop at the last derating frequency until the current is lower than the

derating of current level (23-66).

For example: Set 23-66=80%, 23-67=10sec, 23-68=90%, the frequency command=60Hz and the rated

current of compressor=30A, then,

when the output current=27A, higher than 24A (30A*80%), 10 sec (the derating of delay time) passes, and

the output frequency=54Hz (frequency command 60Hz*90%), the output current decreases to 25A, also

higher than 24A; then another 10 sec passes, 60Hz*81%=48.6Hz, the output current decreases to 23A,

lower than 24A, so the output frequency is restored to 60Hz and the current rises to 27A. When it repeats

more than three times, the output frequency will stop at 48.6Hz and the output current decreases to 23A.

Protection of second stage:

After the current reaches OL4 current level (23-69), the inverter will count the time at the setting value of

OL4 delay time (23-70). When the counting time ends, it will decelerate to stop automatically and display

the warning signal (fault signal, OL4 Compressor Overload).

If fault occurs, PLC can read if the inverter is running from the digital output terminals. If the inverter stops,

terminate the RUN command. If 00-02=0, user can press Reset key; if 00-02=1, terminate the RUN

command of digital input terminal to reach the effect of Reset. Then PLC can be restored to give RUN

command.

Note: It is recommended that the rated current of compressor is required to be lower than that of inverter.

59=1AI1proportionaltargetvia10-00.66current10–200%compressorrated,67delay1–20s,68freqgain1–100%,69OL4current10–200%,70delay0–20s,newV1.4. Firststageabove66for67multipliesfrequency68;below66restores;>3cyclesholdsfinalderatedfreq. Example66=80%,67=10s,68=90%,60Hz,30A;24Athreshold,27A→54Hz25A→48.6Hz23A→60Hz27A;repeats>3hold48.6. Secondstage69for70decelstopOL4. SourceResetproceduresretain00-02scope;recommendcompressorrated<inverterrated. Examplecurrentnotproductrating.

Compressor protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Compressor protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 66

Compressor protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 67

Compressor protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 68

Compressor protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23- 69

Compressor protection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 23-70

Compressor protection table1 — PDF page 378

Source row Source row label Source value or description
1 23- 66 Derating of Current Level (for Compressor Current) *3
2 Range 【10 ~ 200】%
3 23- 67 Derating of Delay Time *3
4 Range 【1.0 ~ 20.0】Sec
5 23- 68 Derating of Frequency Gain *3
6 Range 【1~100】%
7 23- 69 OL4 Current Level *3
8 Range 【10~200】%
9 23-70 OL4 Delay Time *3
10 Range 【0.0 ~ 20.0】Sec

Manual — Pump-card mode selection — page 379

Group 24 Pump Control Function Parameters

The inverter with built-in PID controller and simple programmable logic controller (PLC) is widely applied to

water supply industry. 1 to 8 pump card, mainly applied to the situation of water supply of constant

pressure, dispenses the inverter from the need of an external controller.

The inverter provides the power supply of variable frequency for pump to implement the continuously

variable transmission (CRT) and makes the water pressure being satbly controlled via the built-in PID

controller.

There are two basic operation modes in 1 to 8 pump card:

 Fixed modes of inverter pump:

Pump drived by the inverter is fixed to 1 set and maximum to 8 sets.

MC1(RY2)

INV

Figure 4.4.116 Fixed modes of inverter pump

24-00modes0–9retainedexact. Fixedpumpcardmax8,oneinverter-fed. Fig4.4.116 3phase→INV→MC0(RY1)→M1;commercialbranchesMC1(RY2)→M2 throughMC7(RY8)→M8. BuiltinPID/PLCclaims notallmodescapacity. CRT wordingretained;drawinggeometryremainsauthoritative.

Pump-card mode selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Pump-card mode selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 24- 00

Pump-card mode selection table1 — PDF page 379

Source row Source row label Source value or description
1 24- 00 Selection of Pump Control Function
2 Range 【0】: Function of 1 to 8 Pump Card and 1 to 3 Relay are Disabled. 【1】: Fixed Modes of Inverter Pump: First on and Last off; then Stop All. 【2】: Fixed Modes of Inverter Pump: Only Stop Inverter Pump. 【3】: Fixed Modes of Inverter Pump: First on and First Off; then Stop All. 【4】: Cycle Modes of Inverter Pump: First on and First Off; then Stop All. 【5】: Cycle Modes of Inverter Pump: Only Stop Inverter Pump. 【6】: 1 to 3 Relay of Cycle Modes of Inverter Pump: First on and First off; then Stop All. 【7】: 1 to 3 Relay of Cycle Modes of Inverter Pump: First on and First Off; then Stop All. And First Boot Relay in Cycling. 【8】: Cycle Modes of Inverter Pump: First on and First Off; then Stop All. And First Boot Relay in Cycling. 【9】: 1 to 3 Relay of Cycle Modes of Inverter Pump: Only Stop Inverter Pump. And First Boot Relay in Cycling.

Manual — Pump-card wiring and fixed modes — page 380

 Cycle modes of inverter pump:

Pump drived by the inverter is not fixed to 1 set and maximum to 4 sets.

Figure 4.4.117 Cycle modes of inverter pump

In addition to the two basic operation modes provided from 1 to 8 pump card, it can only use the Relay in

the control board to enable the cycle modes of inverter pump.

modes of inverter pump.

Figure 4.4.118 Cycle modes of inverter pump in the control board

24-00=0: Function of 1 to 8 pump card and 1 to 3 Relay are disabled.

24-00 = 1: in the fixed modes of inverter pump, first on and last off; then stop all.

Pump (motor) drived by the inverter is fixed. Switching off the pump (motor) is by the sequence of the last

on and this mode is applicable to different pump (motor) ratings.

24-00=2: only inverter pump stops in the fixed modes of inverter pump.

When the inverter sends the stop command, only the pump (motor) stops but the Relay keeps on.

24-00=3: in the fixed modes of inverter pump, first on and first off; then stop all.

Switching off the pump (motor) is by the sequence of the first on (longer operation time) to make the pump

(motor) be used for the eq ual frequency and this mode is applicable to the same pump (motor) ratings.

INV

M1

M2

M3

M4

MC0(RY1)

MC2(RY3)

MC4(RY5)

MC6(RY7)

MC1(RY2)

MC3(RY4)

MC5(RY6)

MC7(RY8)

3 Ø

Power Supply

F510

R1A

R2A

R3A

3φ power

MC0

MC2

MC4

MC1

MC3

MC5

External Control Lines

Cyclepumpcardmax4. Fig4.4.117 M1 inverterMC0(RY1)/lineMC1(RY2),M2MC2/3(RY3/4),M3MC4/5(RY5/6),M4MC6/7(RY7/8). Fig4.4.118controlboardR1A/R2A/R3Aexternalcontrol;M1MC0/1,M2MC2/3,M3MC4/5alternateinverter/line.0disabled;1fixedfirstonlastoffstopall allowsdifferentratings;2onlyinverterstoprelaysstay;3fixedfirstonfirstoffstopall sameratings. No inferredwiringinstructions.

Manual — Cycle mode conditions — page 381

24-00=4: in the cycle modes of inverter pump, first on and first off; then stop all.

All the motors besides the pump are drived by the inverter and switching off the pump (motor) is by the

sequence of the first on.

24-00=5: only inverter pump stops in the cycle modes of inverter pump.

When the inverter sends the stop command, only the pump (motor) stops but the Relay keeps on.

24-00=6 : 1 to 3 Relay of Cycle Modes of Inverter Pump: First on and First off; then Stop All.

This mode runs via a Relay with a pump in the cycle modes of inverter pumps. If 24-07=1, only Relay in

the control board is enabled in 1 to 3 Relay of cycle modes and can switch the drive sequence of every

pump.

24-00=7: Cycle Modes of Inverter Pump: First on and First Off; then Stop All. And First Boot Relay

in Cycling.

The first inverter drives the motor depending on the Relay switching time (24-08) to change the inverter’s

position.

24-00=8: Cycle Modes of Inverter Pump 1 to 3 Relay: First on and First Off; then Stop All. And First

Boot Relay in Cycling.

The inverter drives the motor at the first time depending on the Relay switching time (24-08) to change the

inverter’s position. That is, at this mode, the inverter runs in a Relay with a pump. Users can switch the

orders of each pump driving at this cycle mode of 1 to 3 Relay with the setting of parameter 24-07.

24-00=9:Cycle Modes of Inverter Pump 1 to 3 Relay: Only Stop Inverter Pump. And First Boot

Relay in Cycling.

As the fixed modes, first on and first off, but only stop the inverter pump. The inverter drives the motor at

the first time depending on the Relay switching time (24-08) to change the inverter’s position. (The Relay

switching is enabled only in one motor.)

Notes:

function disable) and 57 (forced frequency run) are disabled.

cards, or it is still forced to be disabled.

parameter 24-00.

PID function is enabled via the setting of PID control mode (10-03) to xxx1b (PID enable). Set PID

target value source (10-00) to 4 (10-02 given) and the target value is determined by 10-02. If the

feedback value source (10-01) is set to 2 (AI2 given) and AI input signal type (04-00) is set to 0 (AI2:

0~10V), it requires to set the dip switch to V in the control board.

4cyclefirstonfirstoffstopall;5onlyinverterstoprelaysstay;6relay1–3cyclewith24-07=1;7firstbootrelaycycle;8descriptionexplicit1–3relays whereas379table7has1–3/8not;9onlyinverterstopfirstbootcycle. Relayrotation24-08. No cardforces00=0,but07=1controlboardrelayexceptiongiven. Enabled00disablesDI16/57. PID10-03xxx1b,target10-00=4via10-02,feedback10-01=2AI2,sourcecallsAI2signal04-00andDIPV. Sourceconflictsretained.

Manual — Relay selections and frequency durations — page 382

Fixed modes of inverter pump:

In the fixed modes of inverter pump, RY1 is permanently used and RY2~RY8 is arbitrarily selected to be

used.

Inverter decelerates/ accelerates to lower/ upper limit frequency when user increases/ decreases pumps

and function of PID is temporarily disabled. When the inverter reaches lower/ upper limit frequency,

function of PID restores and the inverter output is determined by the feedback.

Cycle modes of inverter pump:

In the cycle modes of inverter pump, RY2 and RY1 are always used. The rest (RY3~RY8) is a group of two,

RY3/RY4, RY5/RY6, and RY7/RY8. If any one of the group is set to be disabled, this group is disabled.

The inverter output disconnects when user increases pumps. When a motor originally drived by the

inverter is switched by commercial AC power supply, it requires the switching time of magnetic contactor

(24-05) to allow the AC power supply input. Then the inverter output drives the next motor, which is

determined by the feedback.

Switch off the motor of the first on when user decreases pumps to make the pump (motor) be the equal

using frequency.

Cycle modes of inverter pump in the control board:

In the cycle modes of inverter pump, RY1 is permanently used and RY2~RY3 is arbitrarily selected to be

used. 24-01 can only set 0xxx (Relay 4 can not be set.) and 24-02 can only set 0000 (Relay 5-8 can not be

set.) so this parameter will be hidden.

Set the inverter output frequency controlled by PID reaches the upper limit frequency (the proportion

setting by parameter 00-12) via parameter 24-03. 1 to 8 pump card controls the time required for

increasing pumps.

The setting value of duration of upper limit frequency (24-03) is determined by the changing time speed of

system pressure. The setting value of 24-03 is the fewer the better in the range without producing

oscillation of system pressure.

Set the inverter output frequency controlled by PID reaches the lower limit frequency (the proportion

setting by parameter 00-13) via parameter 24-04. 1 to 8 pump card controls the time required for

decreasing pumps.

24-01bit0reserved,bits1/2/3relay2/3/4;24-02bits0..3relay5..8,0disable1enable. FixedRY1always/2–8optional;addingpumpsdecelto lowerlimit,removingacceltoupper,PIDtemporarilyoffthenrestored. CycleRY1/2always,3/4,5/6,7/8paired,oneoffdisablespair;24-05switchtimeoriginalauthoritative. ControlboardRY1always2/3optional,01only0xxx,02only0000hidden.03upperduration1–600s/00-12ratioadds pumps;04lowerduration1–600s/00-13ratioremoves. Group24continues383.

Relay selections and frequency durations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval.

Relay selections and frequency durations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 24- 01

Relay selections and frequency durations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 24- 02

Relay selections and frequency durations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 24- 03

Relay selections and frequency durations. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Source claims with page-level qualifiers/conflicts; no engineering approval. Row group: Parameter 24- 04

Relay selections and frequency durations table1 — PDF page 382

Source row Source row label Source value or description
1 24- 01 Selection of Relay 2-4 Function
2 Range 【xxx0b】: Reserved 【xxx1b】: Reserved 【xx0xb】: Relay 2 Disable 【xx1xb】: Relay 2 Enable 【x0xxb】: Relay 3 Disable 【x1xxb】: Relay 3 Enable 【0xxxb】: Relay 4 Disable 【1xxxb】: Relay 4 Enable
3 24- 02 Selection of Relay 5-8 Function
4 Range 【xxx0b】: Relay 5 Disable 【xxx1b】: Relay 5 Enable 【xx0xb】: Relay 6 Disable 【xx1xb】: Relay 6 Enable 【x0xxb】: Relay 7 Disable 【x1xxb】: Relay 7 Enable 【0xxxb】: Relay 8 Disable 【1xxxb】: Relay 8 Enable

Relay selections and frequency durations table2 — PDF page 382

Source row Source row label Source value or description
1 24- 03 Duration of Upper Limit Frequency
2 Range 【1.0 ~ 600.0】Sec

Relay selections and frequency durations table3 — PDF page 382

Source row Source row label Source value or description
1 24- 04 Duration of Lower Limit Frequency
2 Range 【1.0 ~ 600.0】Sec

Manual — Pump switch time and bias — page 383

The setting value of duration of lower limit frequency (24-04) is determined by the changing time speed of

system pressure. The setting value of 24-04 is the fewer the better in the range without producing

oscillation of system pressure.

When a motor originally drived by the inverter is switched by the commercial AC power supply or originally

drived by the commercial AC power supply is switched by the inverter, function of parameter 24-05 is used

to avoid the delay of external magnetic contactor resulting in a short circuit of the inverter output and AC

power supply.

The setting value of 24-05 requires being larger than the time from the switch of the inverter Relay signal to

the action of external magnetic contactor. Generally, the off to on time of magnetic contactor is longer than

the on to off time. Set parameter 24-05 depending on the longer time.

Figure 4.4.119 Diagram for the single cycle modes of inverter pump

When increasing or decreasing pumps with PID control to operate in coordination with Relay card, user

has to determine if it is required to increase or decrease allowable value of pump in the situation of inverter

output frequency being closed to upper limit frequency (00-12) or lower limit frequency (00-13).

The setting unit is 0.1% and if the setting is 0.0%, inverter output frequency needs to reach the upper limit

or lower limit value to increase or decrease pump (motor).

For example, 00-12 = 80%, and 00-13 = 20%, then:

period of time reach the Duration of Upper Limit Frequency (24-03), the pump (motor)

increase; when the output frequency needs to reach 20% of the minimum frequency and the

period of time reach the Duration of Lower Limit Frequency (24-04), the pump (motor)

decrease.

increase; when the output frequency needs to reach 25% of the minimum frequency and the

24-07 = 0: 1 to 8 Pump Card

It is Relay in the 1 to 8 pump card used for function of inverter pump.

Inverter

IM

MC1

MC2

AC Power Supply

Continues 382:24-04 shorter preferred without pressure oscillation.24-05 .1–20s must exceed longer external contactor on/off action after inverter relay signal; source says off-to-on usually longer. Fig4.4.119 AC supply branches through inverter/MC1 versus bypass MC2 to IM; original drawing authoritative, no inferred simultaneous contact.24-06 0–20%,.1% unit;0 requires exact limits00-12/13. Example upper80/lower20:0bias adds at80% maximum/removes at20% minimum frequency;5bias adds75% maximum/removes25% minimum. Minimum wording preserved with flag.24-07=0 card1–8 /1 builtin1–3;1 conditions continue384.

Pump switch time and bias. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

Pump switch time and bias. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 05

Pump switch time and bias. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 06

Pump switch time and bias. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 07

Pump switch time and bias table1 — PDF page 383

Source row Source row label Source value or description
1 24- 05 Switching Time of Magnetic Contactor
2 Range 【0.1 ~ 20.0】Sec

Pump switch time and bias table3 — PDF page 383

Source row Source row label Source value or description
1 24- 06 Allowable Bias of Pump Switch
2 Range 【0.0~20.0】%

Pump switch time and bias table4 — PDF page 383

Source row Source row label Source value or description
1 24- 07 Pump Control Source Selection
2 Range 【0】: 1 to 8 Pump Card 【1】: Built-in 1 to 3 Control Mode

Manual — Relay capacity and rotation — page 384

24-07 = 1: Built-in 1 to 3 Control Mode

It is Relay in the control board used for function of inverter pump.

Only R1A~R3A in the control board can be used and Relay in 1 to 8 pump card cannot be used.

It is required for the following conditions to enable this control mode.

 24-00 is only set to 1~3 and 6.

 24-01 is only set to 0xxx (Relay 4 is disabled).

 24-02 is only set to 0000 (Relay 5~8 are disabled).

Note: If user does not follow the above requirements (24-00, 24-01, 24-02, and 24-07), errors will coour

when user give commands to the inverter.

Refer to the following table for controlling the maximum value of pump under the different setting values of

24-00 and 24-07.

If 24-07=1, R1A is fixed to support Relay 1 controlled by pump and function of parameter 03-11

is disabled.

If 24-07=1 and 24-01= xx1x, R2A supports Relay 2 controlled by pump and function of

parameter 03-12 is disabled.

If 24-07 = 1,24-01 = x1xx, R3A supports Relay 3 controlled by pump and function of

parameter 03-39 is disabled.

Relay switching time is required to be with modes 7 or 8 of parameter 24-00. When the power is on, the

first run motor is the motor 1. If the switching time reaches and all motor are at sleep mode, the motor 2 will

start up and the inverter drives the motor 2. Refer to the following figure for motors change when the Relay

switching time reaches.

Note: It will recount time when parameter 24-00 is enabled or parameter 24-08 changes the Relay

switching time or the power reconnects.

24-07=1 only R1A–R3A; prose conditions24-00=1–3 or6,24-01=0xxx,24-02=0000. Capacity table additionally permits00=7/9. Fixed1/2/3 one relay per pump:8card/3board. Cycle4/5/8 two relays:4card/no board. Cycle6/7/9 one relay:no card/3board. Board R1A relay1 disables03-11;01xx1x R2A relay2 disables03-12;01x1xx R3A relay3 disables03-39.24-08 0–240hour; prose only00=7/8,earlier9 wording retained separately. Power-on first IM1; after switching time and all asleep IM2 becomes first. Recount on00 enable,08 change or repower.

Relay capacity and rotation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

Relay capacity and rotation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 1,2,3

Relay capacity and rotation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 4,5,8

Relay capacity and rotation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 6,7,9

Relay capacity and rotation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 08

Relay capacity and rotation table1 — PDF page 384

Source row Setting value of 24-00 Inverter pump Modes One pump with Relay 24-07=0 (Relay in 1 to 8 pump Option card) 24-07=1 (Relay in the control board)
1 1,2,3 Fixed Modes 1 8 PUMP 3 PUMP
2 4,5,8 Cycle Modes 2 4 PUMP None
3 6,7,9 Cycle Modes 1 None 3 PUMP

Relay capacity and rotation table2 — PDF page 384

Source row Source row label Source value or description
1 24- 08 Relay Switching Time
2 Range 【0 ~ 240】hour

Manual — Pump control and pressure limits — page 385

When 24-09=0, action of reducing pump starts from the output frequency after PID control agreeing the

level of lower limit frequency and the delay time of lower limit frequency.

When 24-09=1, action of reducing pump starts when PID feedback (12-39)>PID setting (12-38).

When 24-10=1, all relays disconnect at stop and first relay starts to run at operation.

Note: 24-10 is enabled only when 24-00=6, 7, 9.

24-17=0: When increasing / decreasing the pump, in order to balance the current water usage, the Inverter

will decelerate to the Frequency Lower Limit when increasing the pump, conversely, the Inverter will

increase to Frequency Upper Limit when decreasing the pump, then the Inverter will switch back to the

speed required by the PID Control.

24-17=1: When using water at the extreme switch when increasing / decreasing the pump, and in order to

balance the water usage, the Inverter Increasing / Decreasing Pump All Sections can be selected to use

PID to control the Inverter Speed.

24-11 High Pressure Limit Level:

When pressure feedback value is higher than the set value of highp pressure limit level, the alarm signal

occurs and then inverter stops the operation.

24-14 Low Pressure Limit Level:

When pressure feedback value is lower than the set value of low pressure limit level, the alarm signal

User can refer to the setting of 10-00=4 to set the value of parameters 24-11& 24-14. Revise the upper

limit value by the setting of parameter 10-33, determine the decimal position by adjusting the setting of

parameter 10-34, and the unit display by parameter 10-35.

24-09=0 lower-frequency/duration reduction,1 PID feedback12-39>target12-38 reduction.24-10=1 disconnect all relays at stop and first relay starts at operation,only00=6/7/9.24-17=0 addpump decel lower/remove accel upper then PID restored;1 PID throughout.24-11 high/14 low level0–10000; units not intrinsically PSI:10-00=4,upper10-33,decimal10-34,unit10-35. Subsequent warning delays apply.

Pump control and pressure limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

Pump control and pressure limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 09

Pump control and pressure limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 10

Pump control and pressure limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 17

Pump control and pressure limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 11

Pump control and pressure limits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 14

Pump control and pressure limits table1 — PDF page 385

Source row Source row label Source value or description
1 24- 09 Frequency/ Target Switch
2 Range 【0】Disable 【1】Enable
3 24- 10 Stop Mode Selection on Mode 6/7/9
4 Range 【0】Disable 【1】Enable

Pump control and pressure limits table2 — PDF page 385

Source row Source row label Source value or description
1 24- 17 Increase and Decrease Pump Interval PID Control
2 Range 【0】Increasing / Decreasing Pump Section without PID Control 【1】Increasing / Decreasing Pump Section with PID Control

Pump control and pressure limits table3 — PDF page 385

Source row Source row label Source value or description
1 24- 11 High Pressure Limit Level
2 Range 【0~10000】
3 24- 14 Low Pressure Limit Level
4 Range 【0~10000】

Manual — Pressure levels diagram — page 386

Diagram of pressure feedback value limit

Note: Pressure feedback value will be between the high pressure limit level (24-11) and the low

pressure limit level.

12-38 PID Setting

24-11 High Pressure Limit Level

24-14 Low Pressure Limit Level

Pressure Feedback Value

Diagram pressure-feedback blue curve oscillates around12-38 PID target between24-11 high and24-14 low horizontal levels. Axes Pb/time; no numeric rating inferred. Source note states feedback will be between limits; this is source language,not performance guarantee.

Manual — High-pressure timers — page 387

24-12 Delay Time of High pressure Warning

When pressure feedback value is higher than the high pressure limit level, high pressure warning time will

start to count. If the value is lower than the high pressure limit level during the counting time, the warning

time will recount. It will jump to the warning signal “HIPb” when the counting time is over.

24-13 Delay Time of High Pressure Error

When the warning signal of high pressure occurs and pressure feedback value is higher than the high

pressure limit level, high pressure shutdown time will start to count. If the value is lower than the high

pressure limit level during the counting time, the shutdown time will recount. It will jump to the error signal

“OPbFt” when the counting time is over.

Note: If user wouldn’t like to limit to the high pressure level, the high pressure warning time can be set to

zero, and then the high pressure limit function is disabled.

Diagram of high pressure limit warning to shutdown

24-11 High Pressure Limit Level

PSI

12-38 PID Setting

24-14: Low Pressure Limit Level

Pressure Feedback Value Output

Free Operation to Shutdown

time

Hz

HIPb

OPbFt

T1 < (24-12 Delay Time of High Pressure Warning); recount it after T1.

T2 = (24-12 Delay Time of High Pressure Warning); keypad flashes and displays “HIPb.”

T3 = (24-13 Delay Time of High Pressure Error); keypad flashes and displays “OPbFt.”

T1

T2

T3

24-12 warning and13 error each0–600s. Above11 continuously12 gives HIPb; then13 gives OPbFt. Below11 restarts respective count.12=0 disables high-limit function. Diagram T1<12 resets,T2=12 HIPb,T3=13 OPbFt. Pressure axis PSI; frequency falls afterT3,caption Free Operation to Shutdown. No assumed00-15 deceleration from Group23.

High-pressure timers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

High-pressure timers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 12

High-pressure timers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 13

High-pressure timers table1 — PDF page 387

Source row Source row label Source value or description
1 24- 12 Delay Time of High Pressure Warning
2 Range 【0.0 ~600.0】Sec
3 24- 13 Delay Time of High Pressure Error
4 Range 【0.0 ~ 600.0】Sec

Manual — Low-pressure timers — page 388

24-15 Delay Time of Low Pressure Warning

When pressure feedback value is lower than the low pressure limit level, low pressure warning time will

start to count. If the value is higher than the low pressure limit level during the counting time, the warning

time will recount. It will jump to the warning signal “LoPb” when the counting time is over.

24-16 Delay Time of Low Pressure Error

When the warning signal of low pressure occurs and pressure feedback value is lower than the low

pressure limit level, low pressure shutdown time will start to count. If the value is higher than the low

pressure limit level during the counting time, the shutdown time will recount. It will jump to the error signal

“LPbFt” when the counting time is over.

Note: If user wouldn’t like to limit to the low pressure level, the low pressure warning time can be set to

zero, and then the low pressure limit function is disabled.

Diagram of low pressure limit warning to shutdown

Pressure Feedback Value Output

Free Operation to Shutdown

time

PSI

Hz

LoPb

LPbFt

T1 < (24-15 Delay Time of Low Pressure Warning); recount it after T1.

T2 = (24-15 Delay Time of Low Pressure Warning); keypad flashes and displays “LoPb.”

T3 = (24-16 Delay Time of Low Pressure Error); keypad flashes and displays “LPbFt.”

T1

T2

T3

12-38 PID Setting

24-11 High Pressure Limit Level

24-14: Low Pressure Limit Level

24-15 warning and16 error0–600s. Below14 continuously15 gives LoPb,then16 LPbFt; above14 resets.15=0 disables low-limit function. Diagram T1<15 resets,T2=15 LoPb,T3=16 LPbFt; falling frequency afterT3 labelled Free Operation to Shutdown. Thresholds11/12-38/14 separate.

Low-pressure timers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

Low-pressure timers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 15

Low-pressure timers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter 24- 16

Low-pressure timers table1 — PDF page 388

Source row Source row label Source value or description
1 24- 15 Delay Time of Low Pressure Warning
2 Range 【0.0 ~ 600.0】Sec
3 24- 16 Delay Time of Low Pressure Error
4 Range 【0.0 ~ 600.0】Sec

Manual — Fixed-mode pump addition — page 389

The following examples are for the actions of increasing / decreasing pumps in the fixed modes of inverter

pump. Relay 1~Relay 4 in 1 to 8 pump card is set to be enabled. Motor 1 is connected to inverter and

motor 2~4 are connected to AC power supply. MC of AC power supply is mainly controlled by the external

circuit control. Refer to Fig. 4.4.126.

When 24-00=1, 24-06=0 and depending on the above PID setting, the following status occurs.

Output frequency (Fout) reaches the upper limit frequency (00-12) and Fout time is over than the

duration of upper limit frequency (24-03). Then Relay 2 is power on and the connected motor starts

to accelerate.

Figure 4.4.120 Diagram of increasing pump in the fixed modes of inverter pump

T1 = 24-03 Duration of

Upper Limit Frequency

Example24-00=1,06=0,card relays1–4 enabled,M1 inverter,M2–4 commercial AC external MC,Fig4.4.126. Fig4.4.120:upper00-12 for T1=24-03 activatesRY2/M2,thenRY3/M3,thenRY4/M4. RY1/M1 inverter stays on. M1 frequency falls/rises as pumps added;M2–4 line frequency ramps to steady. TopFout segments namedMotor1/2/3/4 despiteM1 inverter continuing;source labels preserved.

Manual — Fixed-mode pump removal — page 390

Output frequency (Fout) decreases to the lower limit frequency (00-13) and the Fout time is over than

the duration of lower limit frequency (24-04). Then Relay 4 is power off and the inverter accelerates

to the upper limit frequency (00-12).

When Fout reaches to the upper limit frequency (00-12), the inverter starts to decelerate.

Figure 4.4.121 Diagram of decreasing pump in the fixed modes of inverter pump

T1 = 24-04 Duration of Lower Limit

Frequency

Fig4.4.121:lower00-13 forT1=24-04 turnsRY4 off;M4 coasts;M1 frequency accelerates00-12 then decreases. SubsequentRY3/M3 thenRY2/M2 stop;RY1 last. Motor1 frequency repeated triangles;Motor1 row labelled AC Power Supply despite prior inverter connection. Starttrace remains high in depicted interval; no invented duration.

Manual — Cycle pump transfer — page 391

The following examples are for the actions of increasing / decreasing pumps in the cycle modes of inverter

pump. Relay 1~Relay 4 in 1 to 8 pump card is set to be enabled. Refer to Fig.4.4.119 for switching of the

motor connected to the inverter or AC power supply. MC of AC power supply is mainly controlled by the

external circuit control. Refer to Fig.4.4.127.

When 24-00=1, 24-06=0 and depending on the above PID setting, the following status occurs.

Output frequency (Fout) reaches the upper limit frequency (00-12) and Fout time is over than the

duration of upper limit frequency (24-03). Then Relay 1 is power off and output frequency of the

inverter does not occur.

Relay 1 and Relay 2 is power on and the inverter starts to accelerate after the switching time of MC

(24-05) ends.

Figure 4.4.122 Diagram of increasing pump in the cycle modes of inverter pump

T1 = 24-03 Duration of Upper Limit Frequency

T2 = 24-05 Switching Time of Magnetic

Contactor (MC)

Cycle example states24-00=1,06=0 though1 defined fixed. Fig4.4.122:upper00-12 forT1=24-03 switchesRY1/inverterM1 off;T2=24-05 thenRY2 AC M1 andRY3 inverterM2 on. RY4 remains off. Prose instead says Relay1 andRelay2 on. M1 frequency dips during transfer then line supply;M2 ramps. Both prose and diagram retained,not harmonised.

Manual — Cycle removal diagram — page 392

Output frequency (Fout) reaches the lower limit frequency (00-13) and Fout time is over than the

duration of lower limit frequency (24-04). Then Relay 1 and Relay 2 is power off

Relay 1 is power on and the inverter starts to decelerate after the switching time of MC (24-05) ends.

Figure 4.4.123 Diagram of decreasing pump in the fixed modes of inverter pump

T1 = 24-04 Duration of Lower Limit Frequency

T2 = 24-05 Switching Time of Magnetic

Contactor (MC)

Continuation Fig4.4.123 caption says fixed modes. Prose lower00-13 for24-04 turnsRY1/2 off thenRY1 on after24-05. Diagram showsRY1 constantly off,RY2 AC M1 drops afterT1,RY3 inverterM2 stays until final stop;M1 coasts,M2 frequency triangle. T1=24-04,T2=24-05. Source disagreement retained.

Manual — Builtin relay pump addition — page 393

The following examples are for the actions of increasing / decreasing pumps in 1 to 3 Relay modes. Relay

1~Relay 3 is corresponding to R1A-R3A. Refer to Fig.4.4.118 for switching of the motor connected to the

inverter or AC power supply. MC of AC power supply is mainly controlled by the external circuit control.

Refer to Fig.4.4.128.

When 24-00=1, 24-06=0 and depending on the above PID setting, the following status occurs.

Output frequency (Fout) reaches the upper limit frequency (00-12) and Fout time is over than the

duration of upper limit frequency (24-03). Then Relay 1 is power off and output frequency of the

inverter does not occur.

Relay 2 is power on and output frequency of the inverter does not still occur after the switching time

of MC (24-05) ends.

Relay 1 is power on and the inverter starts to accelerate after the switching time of MC (24-05) ends.

Figure 4.4.124 Diagram of increasing pump in 1 to 3 Relay modes

T1 = 24-05 Switching Time of

Magnetic Contactor

(MC)

T2 = 24-03 Duration of Upper Limit

Frequency

Example relay1–3=R1A–R3A,Fig4.4.128 external control,again00=1/06=0. Fig4.4.124:upper00-12 forT2=24-03 turnsRY1 off/output zero;T1=24-05 thenRY2 on/output still zero;anotherT1 thenRY1 on/output rises forM2. Next transfer similarly makesM2 line andM3 inverter. RY1/2 change role inverter→AC. M3 AC row stays off. T1/T2 definitions differ from391 and must stay figure-specific.

Manual — Builtin relay pump removal — page 394

When pressure feedback value is larger than the target value, output frequency (Fout) decreases.

Relay 1 is power off when the output frequency reaches to the lower limit frequency (00-13) and Fout

time is over than the duration of lower limit frequency (24-04).

Figure 4.4.125 Diagram of decreasing pump in 1 to 3 Relay modes

T1 = 24 -04 Duration of Lower

Limit Frequency

Fig4.4.125 feedback>target decreasesFout;lower00-13 forT1=24-04 dropsRY1/M1 AC first,thenRY2/M2 AC,thenRY3/M3 inverter. Start falls before finalRY3 drop. M1/M2 coast while M3 frequency cycles then stops. No numeric time or pressure added.

Manual — Fixed-mode wiring — page 395

Wiring for 1 to 8 Pump Card and 1 to 3 Relay Modes

M8

TH7

MC7

M7

TH6

MC6

M6

TH5

MC5

M5

TH4

MC4

M4

TH3

MC3

M3

TH2

MC2

M2

TH1

MC1

M1

MC0

PRESSURE

COMMAND

SENSOR

RUN

STOP

ON

OFF

MC *

TH8

U

V

W

S1

24VG

S2

10V

GND

E

AI2

RY2

RY1

RY-Card

COM1-4

R

S

T

MCCB2

MCCB1

R3A

R3C

N

MCCB3

B2

ALARM

MC*

AUTO OPERATE

MANUAL

OPERATE

AUTO

F510

RY6

RY7

RY8

RY5

RY4

RY3

24V

AI1

NPN

PN

P

Figure 4.4.126 Wiring for the fixed modes of inveter pump

Fig4.4.126 full-page wiring plus enlarged crops. R/S/T feedsMCCB2→F510R/S/T;MCCB1→commercial bus M2–M8. N/control viaMCCB3. F510U/V/W→MC0→M1;commercialMC1/TH1→M2 throughMC7/TH7→M8. Control S1RUN,S2STOP,24VG;24V,10V/AI1/GND pressure command,E shield,AI2 pressure sensor. LeftR3A/R3C,TH1–7 contacts,alarmB2,MC0–7 lamps andPNP/NPN selector. RY-CardRY1–8 andCOM1-4;auto/manual selector,MC* auto relay,manual ON/OFF seal-in contactsMC1–7. Bottom coilMC7 protection readsTH8 although motor/alarm labelsTH7. Source geometry authoritative; no wiring netlist,contact-state safety or installation approval inferred. Already-reviewed396–397 not duplicated.

Manual — Figure4.4.127 Wiring for the cycle modes of inverter pump — page 396

Labels and contact-legend inventory only. Complete wiring topology, interlocks, symbols, conductor routes and relay logic remain original-only; this is not an installation wiring substitute.

Motor symbols counted from this specific figure only; not a maximum capacity claim for all F510 configurations.

RepeatedMC1 labels in all four lower contact-legend columns are a supplier-source discrepancy retained verbatim. No inferred correction.

Literal label list; no electrical connections inferred from labels alone. TH4 is present in upper-left list on both pages, despite only three motor symbols on397.

Page396 only; distinguish from397 control-board relay labels and lamp-row83–84.

Four lower legend columns each printMC1; retain all four positions, do not renameMC3/MC5/MC7. Contact open/closed symbol meanings and complete circuit remain original-only.

Diagram scope and labels — PDF page 396

Source row Source label/context Source value
1 Figure 4.4.127
2 Caption Wiring for the cycle modes of inverter pump
3 Controller F510
4 Motor symbols M1; M2; M3; M4
5 Supply labels R; S; T; N
6 Circuit breakers MCCB1; MCCB2; MCCB3
7 Drive power terminals R; S; T; E; U; V; W
8 Control terminal labels S1; 24VG; S2; 24V; 10V; AI1; GND; E; AI2
9 Control labels RUN; STOP; PRESSURE COMMAND; PRESSURE SENSOR
10 Switch labels SW3; PNP; NPN
11 Mode labels AUTO OPERATE; MANUAL OPERATE
12 Alarm text ALARM
13 Lower control labels ON; OFF
14 Upper-left thermal-contact labels TH1; TH2; TH3; TH4

RY-card and contactor identifiers — PDF page 396

Source row Source label/context Source value
1 Card RY-Card
2 Card outputs RY1; RY2; RY3; RY4; RY5; RY6; RY7; RY8
3 Common label COM1-4
4 Relay labels R3A; R3C
5 Contactor identifiers MC0; MC1; MC2; MC3; MC4; MC5; MC6; MC7; MC*
6 Lamp-row contact pairs 13–14
7 Motor-side thermal labels TH1; TH2; TH3; TH4

Contact legend as printed — PDF page 396

Source row Position in legend Printed contactor label Contact pairs top-to-bottom
1 Upper1 MC0 13–14;21–22;61–62;71–72;81–82
2 Upper2 MC2 13–14;21–22;61–62;71–72;81–82
3 Upper3 MC4 13–14;21–22;61–62;71–72;81–82
4 Upper4 MC6 13–14;21–22;61–62;71–72;81–82
5 Lower1 MC1 13–14;53–54;21–22
6 Lower2 MC1 13–14;53–54;21–22
7 Lower3 MC1 13–14;53–54;21–22
8 Lower4 MC1 13–14;53–54;21–22
9 Right MC* 13–14;53–54;63–64;73–74;21–22;61–62;71–72;81–82

Manual — Figure4.4.128 Wiring for the cycle modes of inverter pump in the control board — page 397

Labels and contact-legend inventory only. Complete wiring topology, interlocks, symbols, conductor routes and relay logic remain original-only; this is not an installation wiring substitute.

Motor symbols counted from this specific figure only; not a maximum capacity claim for all F510 configurations.

Literal label list; no electrical connections inferred from labels alone. TH4 is present in upper-left list on both pages, despite only three motor symbols on397.

Page397 only; noRY-Card label present. Upper-leftTH4 retained separately from three motor-side thermal labels.

Source contact-pair labels only; contact symbols and wiring connections preserved in original.

Diagram scope and labels — PDF page 397

Source row Source label/context Source value
1 Figure 4.4.128
2 Caption Wiring for the cycle modes of inverter pump in the control board
3 Controller F510
4 Motor symbols M1; M2; M3
5 Supply labels R; S; T; N
6 Circuit breakers MCCB1; MCCB2; MCCB3
7 Drive power terminals R; S; T; E; U; V; W
8 Control terminal labels S1; 24VG; S2; 24V; 10V; AI1; GND; E; AI2
9 Control labels RUN; STOP; PRESSURE COMMAND; PRESSURE SENSOR
10 Switch labels SW3; PNP; NPN
11 Mode labels AUTO OPERATE; MANUAL OPERATE
12 Alarm text ALARM
13 Lower control labels ON; OFF
14 Upper-left thermal-contact labels TH1; TH2; TH3; TH4

Control-board relay and contactor identifiers — PDF page 397

Source row Source label/context Source value
1 Relay pairs R1A; R1C; R2A; R2C; R3A; R3C
2 Contactor identifiers MC0; MC1; MC2; MC3; MC4; MC5; MC*
3 Lamp-row contact pairs 83–84
4 Motor-side thermal labels TH1; TH2; TH3

Contact legend as printed — PDF page 397

Source row Position in legend Printed contactor label Contact pairs top-to-bottom
1 Upper1 MC0 13–14;53–54;83–84;21–22;61–62;71–72
2 Upper2 MC2 13–14;53–54;83–84;21–22;61–62;71–72
3 Upper3 MC4 13–14;53–54;83–84;21–22;61–62;71–72
4 Upper4 MC* 13–14;53–54;83–84;21–22;61–62;71–72
5 Lower1 MC1 13–14;53–54;83–84;21–22
6 Lower2 MC3 13–14;53–54;83–84;21–22
7 Lower3 MC5 13–14;53–54;83–84;21–22

Manual — PLC basic commands and registers — page 398

4.5 Built-in PLC Function

The PLC ladder logic can be created and downloaded using the TECO drive link software.

4.5.1 Basic Command

Description of registers

PLC ladder uses TECO drive link. Basic matrix columns:function;normal bracket coil;SET upward symbol;RESET downward symbol;P;NO contact;NC contact;NO/NC address range. I1–I6/i1–i6,Q1–Q2/q1–q2,M1–MF/m1–mF,V1–V8,C/T/G/F1–8 lower-case NC,AS1–4,MD1–4. Blank symbol cells mean absent in source. RegistersV1/V2 .1–400Hz,V3/V4/V5 0–1000,V6 .1–999.9A,V7 .1–200%,V8PIDtarget .1–400Hz. DifferentialD/d;SETup/RESETdown/P. Open circuit blank quote/short--. Connection symbols left-right;left-right-top;four-way;left-right-bottom. Graphic headers translated descriptively;raw glyphs retained.

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Inputs

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Outputs

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Auxiliary command

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Special registers

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Counter function

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Timer function

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Analog comparison function

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Operation control function

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: summation and subtraction

function

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Multiplication and division

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter V1:Set frequency

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter V2:Operation frequency

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter V3:AI1 input value

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter V4:AI2 input value

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter V5:Keypad input value

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter V6:Operation current

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter V7:Torque value

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter V8:PID Target Value

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Differential command

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: SET command

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: RESET command

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: P command

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Open circuit

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Short circuit

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: ─

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: ┴

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: ┼

PLC basic commands and registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: ┬

PLC basic commands and registers table1 — PDF page 398

Source row Function Normal bracket coil SET upward symbol RESET downward symbol P Normally open contact Normally closed contact NO / NC address range
1 Inputs ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ I i I1I6 / i1i6
2 Outputs Q Q Q Q Q q Q1Q2 / q1q2
3 Auxiliary command M M M M M m M1MF / m1mF
4 Special registers ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ V1~V8
5 Counter function C ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ C c C1~C8 / c1~c8
6 Timer function T ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ T t T1T8 / t1t8
7 Analog comparison function G ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ G g G1G8 / g1g8
8 Operation control function F ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ F f F1~F8 / f1~f8
9 summation and subtraction function AS ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ AS1~4
10 Multiplication and division function MD ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ MD1~4

PLC basic commands and registers table2 — PDF page 398

Source row Register and meaning Source range and units
1 V1:Set frequency Range:0.1~400.0Hz
2 V2:Operation frequency Range:0.1~400.0Hz
3 V3:AI1 input value Range:0~1000
4 V4:AI2 input value Range:0~1000
5 V5:Keypad input value Range:0~1000
6 V6:Operation current Range:0.1~999.9A
7 V7:Torque value Range:0.1~200.0%
8 V8:PID Target Value Range:0.1~400.0Hz

PLC basic commands and registers table3 — PDF page 398

Source row Command Upper Differential Lower Differential Other command symbol
1 Differential command D d ⟦blank source cell⟧
2 SET command ⟦blank source cell⟧ ⟦blank source cell⟧
3 RESET command ⟦blank source cell⟧ ⟦blank source cell⟧
4 P command ⟦blank source cell⟧ ⟦blank source cell⟧ P

PLC basic commands and registers table4 — PDF page 398

Source row Circuit state Source symbol Printed blank column
1 Open circuit “ “ ⟦blank source cell⟧
2 Short circuit “--” ⟦blank source cell⟧

PLC basic commands and registers table5 — PDF page 398

Source row Connection symbol Definition
1 ─ Connect components on the left and right side
2 ┴ Connects components on the left , right and top side
3 ┼ Connects components on the left , right , top and bottom side
4 ┬ Connects components on the left , right and bottom side

Manual — PLC command timing — page 399

4.5.2 Basic Command Function

◎ D(d)command function

Example 1: I1─D ───[ Q1

Example 2: i1─d ───[ Q1

◎ NORMAL( -[ ) output

I1───[Q1

◎ SET()output

I1───  Q1

◎ RESET()output

I1───  Q1

I1

OFF

ON

Q1

◎ P output

i1───PQ1

D example I1 rising gives D andQ1 one new-scanning-cycle pulse;d example i1 falling (I1 inverse rising) givesd1/Q1 pulse. Normal Q1 followsI1. SET latchesQ1 on afterI1 rise;RESET turnsQ1 off and holds afterI1 rise. P command i1→PQ1 illustration continues400. These are source examples,not tested PLC execution.

Manual — Counter functions — page 400

4.5.3 Application Functions

1: Counter Function

Counter modes:

Mode 1: Counter value is locked to the set value. The value will not be retained when the power is cut off.

Mode 2: Counter value is not locked. The value will not be retained when the power is cut off.

Mode 3: Counter value is locked. The value will be retained when the power is cut off.

Mode 4: Counter value is not locked. The value will be retained when the power is cut off.

Counter mode 1

Example:

Counter input pulse

OFF

ON

Continues399 P output:three successivei1 falling edges alternateQ1 ON,OFF,ON;I1-primeinverse shown. Counter positions1mode,2up/down,3reset,4internal,5compare,6output.2OFFup/ONdown;3ONreset+outputOFF,OFFretain. EightC1–8;compareAS/MD/T/C/V/constant. Modes1locked/no power-retention,2unlocked/no retention,3locked/retention,4unlocked/retention. Mode1 compare20;internal sequence0,0,0,1,1,2,2,1,1,0,blank,19,19,20,20,20,0,20,20. Blankjump not filled. Direction/reset/input/output traces retainednative andsource image; no numeric clock scale inferred.

Counter functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

Counter functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Counter functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Counter functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Counter functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Counter functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Counter functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Shared source cells (coordinates refer to this table):

Counter functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Counter mode1 timing example;row5compare20 spansvaluecolumns,row4internalcounter;blankjump preserved,no elapsedtimeassumed.

Counter functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Counter mode1 timing example;row5compare20 spansvaluecolumns,row4internalcounter;blankjump preserved,no elapsedtimeassumed. Row group: Symbol5 counter compare value

Counter functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Counter mode1 timing example;row5compare20 spansvaluecolumns,row4internalcounter;blankjump preserved,no elapsedtimeassumed. Row group: Symbol4 internal counter value

Adjacent source context — repeated to preserve continuation:

Counter functions table1 — PDF page 400

Source row Symbol Description
1 Counter mode (1 ~ 4)
2 UP/Down counting modes can be set by (I1 ~ f8).
3 ⟦null: no independent source value⟧ OFF: Count up (0, 1, 2, 3…)
4 ⟦null: no independent source value⟧ ON: Count down (…3,2,1,0)
5 Use (I1~f8) to reset counting value
6 ⟦null: no independent source value⟧ ON: Internal count value is reset and counter output  is OFF
7 ⟦null: no independent source value⟧ OFF: Internal counter value retained
8 Internal counter value
9 Counter compare value (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8,constant)
10 Counter output (C1 to C8, there are a total of 8 counters)

Counter functions table2 — PDF page 400

Source row Symbol index Example position 1 Example position 2 Example position 3 Example position 4 Example position 5 Example position 6 Example position 7 Example position 8 Example position 9 Example position 10 Example position 11 Example position 12 Example position 13 Example position 14 Example position 15 Example position 16 Example position 17 Example position 18 Example position 19
1 5 20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 4 0 0 0 1 1 2 2 1 1 0 ⟦blank source cell⟧ 19 19 20 20 20 0 20 20

Manual — Counter examples and retention — page 401

Counter mode 2

Note: In this mode the internal counter may increase past the counter compare value, unlike mode 1

where the internal counter value is limited to the counter compare value.

(1) Counter mode 3 is similar to the counter mode 1, with the exception that the counter value is saved

when the drive is powered down and reloaded at power up.

(2) Counter mode 4 is similar to the counter mode 2, with the exception that the counter value is saved

LadderI1+i2→C3;C3→Q1,m1+q1→M2. FunctionM2 direction,I3reset,internal0000,compare0020,outputC3;ON atsetvalue also enablesC3ladder input. Mode2 internal sequence0,19,19,20,20,21,21,20,20,19,20,18,18,19,19,20,0,20,20 vscompare20. Counter may exceedcompare unlikeMode1. Modes3/4 preserve power-down counter and reload. BottomMode1/2 sequence1,1,2,2,blankinterval,0,1,1,2,2;Mode3/4 1,1,2,3,blankinterval,3,4,4,5,5. Preserve printed3 before outage,do not normalize equal timing.

Adjacent source context — repeated to preserve continuation:

Manual — Timer function — page 402

2: Timer Function

Timer mode description:

Example:

[T5]

T5

000.0

010.0

I1

[Q1]

When I1=ON, the 5th timer

starts

When the time reaches the

set value of 10.0 seconds,

output T5 is turned ON.

Input under function Program Mode

Input from the Ladder Program

Timer set value

Present timing value

Timing unit is 0.1 second

Timer Mode1

Timer positions1mode0–7,2unit,3reset,4internalvalue,5setvalue,6outputT1–8. Unit1=0.0–999.9second,2=0–9999second,3=0–9999minute. ResetONinternalreset/outputOFF,OFFinternalstaysrunning. SetAS/MD/T/C/V/constant. Example ladderI1→T5,T5→Q1;mode1,unit.1second,present000.0,set010.0. T5turnsON at10seconds. Source diagram arrows distinguish set from present.

Timer function. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

Timer function. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Timer function. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Timer function. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Timer function. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Timer function. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Timer function. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Shared source cells (coordinates refer to this table):

Timer function table1 — PDF page 402

Source row Symbol Description
1 Timer mode (0-7)
2 Timing unit: 1:0.0~999.9 second
3 ⟦null: no independent source value⟧ 2:0~9999 second
4 ⟦null: no independent source value⟧ 3:0~9999 minute
5 Use (I1~f8) to reset timing value
6 ⟦null: no independent source value⟧ ON: Internal timing value is reset and timer output  is OFF
7 ⟦null: no independent source value⟧ OFF: Internal timer stays running
8 Internal timer value
9 Timer set value (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8,constant)
10 Timer output (T1 to T8, there are a total of 8 timers)

Manual — Timer modes zero to three — page 403

(1) Timer mode description 0 (ON-RTC Mode)

Timer start

OFF

ON

When the set value is reached, the

timer output turns on (T1 to T8)

Timer reset

Internal timer value = 0

RTC Mode Time Set

Reset internal timer

value and output

(2) Timer mode 1 (ON-delay Timer mode 1)

(3) Timer mode 2 (ON-delay Timer mode 2)

(4) Timer mode 3 (OFF-delay Timer mode 1)

Mode0ON-RTC:output on withtimerstart acrossRTCtime interval,resetatend. Mode1ONdelay:outputON aftercontinuousT fromstart,OFFwithstart. Mode2ONdelayaccumulates t1+t2=T across interruptedstart;outputON thenresetinputON resets. Mode3OFFdelay1:outputONimmediatelyonstart,remainsT afterstartOFF thenOFF;resetlineOFF. Mode3continued404. Repeatedcaption When set value reached output turns on does notreplace specific traces.

Manual — Timer modes four to seven — page 404

Timer start

OFF

When the set value is reached, the

timer output turns on (T1 to T8)

T= timer set value

ON

Reset timer and output

T

(5) Timer mode 4 (OFF-delay Timer mode 2)

(6) Timer mode 5 (FLASH Timer mode 1)

(7) Timer mode 6 (FLASH Timer mode 2)

(8) Timer mode 7 (FLASH Timer mode 3)

Timer reset

Internal timer value = 0

Internal timer value

t1 t2

Reset internal timer

value and output

t1= 1st timer set value

t2= 2nd timer set value

TopcontinuesMode3 withreset andmultiplepulses:resetforcesoutputOFF,retrigger extends offdelay. Mode4OFFdelay2 outputstarts atstartfall andstaysT. Mode5FLASH1 oscillatesalternatingT while startON,stopswhenstartOFF. Mode6FLASH2 triggeredbybriefstart thenoscillatesT untilresetON. Mode7FLASH3 while startON alternates t1=firsttimerset/t2=secondtimerset,endswithstartOFF. Timingvaluesillustrative intervals,no duration inferred.

Manual — Analog comparator and operation — page 405

3: Analog comparator function

The description of analog comparison mode:

(1) Analog comparison mode 1 ( ≤ ,  ON)

(2) Analog comparison mode 2 ( ≥ ,  ON)

(3) Analog comparison mode 3 ( ≤  ≤ ,  ON)

Input comparison value selection (V1~V7)

(1) Input comparison value selection = V1: Set frequency

(2) Input comparison value selection = V2: Operation frequency

(3) Input comparison value selection = V3: AI1 input value

(4) Input comparison value selection = V4: AI2 input value

(5) Input comparison value selection = V5: Keypad input value

(6) Input comparison value selection = V6: Operation current

(7) Input comparison value selection = V7: Torque value

(8) Input comparison value selection = V8: PID Target Value

4: Operation control function

Analog positions1mode1–3,2input,3currentinput,4upper,5lower,6G1–8output. InputAS/MD/T/C/V;limits additionallyconstant. Mode1 outputON when3≤5;Mode2 when3≥4;Mode3 when5≤3≤4. HeadingV1–V7 but list includesV8PIDtarget;all eight retained. Operation diagram positions1direction,2speedselection,3setfreq,4speedfreq,5ACC,6DEC,7Foutput;descriptionscontinue406.

Analog comparator and operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

Analog comparator and operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Analog comparator and operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Analog comparator and operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Analog comparator and operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Analog comparator and operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Analog comparator and operation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Analog comparator and operation table2 — PDF page 405

Source row Symbol Description
1 Analog comparator mode (1~3)
2 Input comparison value selection (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8)
3 Current analog input value
4 Set the reference comparison value (Upper limit) (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant )
5 Set the reference comparison value (lower limit) (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant )
6 Comparator output (G1 to G8, there are a total of 8 comparators)

Manual — Operation control and arithmetic — page 406

Example:

5: Summation and subtraction functions

RESULT (calculation result) = V1+ V2- V3

Operation1OFFforward/ONreverse;2OFFfrequency3/ONfrequency4. FrequenciesconstantorV3/V4/V5/V8;5ACCtime,6DECtime;F1–8output. ExampleI1ON/OFF determinesF1RUN/STOP;F1ladderinputalsoON. FunctionblockshowsM1/M2inputs,two n labels,10.00/10.00/60.0/30.0values;do not reassociate using assumed UIorder. Arithmeticblockpositions1result,2addendV1,3addendV2,4subtrahendV3,5errorcoil,6ASmode;formulaRESULT=V1+V2−V3. Tablecontinues407.

Operation control and arithmetic. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

Operation control and arithmetic. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Operation control and arithmetic. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Operation control and arithmetic. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Operation control and arithmetic. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Operation control and arithmetic. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Operation control and arithmetic. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Operation control and arithmetic. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Operation control and arithmetic table1 — PDF page 406

Source row Symbol Description
1 Forward /Reversal control can be set by ( I1~f8 ) OFF: Forward(FWD) ON: Reversal(REV)
2 Speed terminal control can be set by ( I1~f8 )
3 ⟦blank source cell⟧ OFF: Operation based on  set frequency
4 ⟦blank source cell⟧ ON: Operation based on frequency of speed 
5 Set frequency (can be constant or V3, V4, V5, V8 )
6 Speed frequency (can be constant or V3, V4, V5, V8)
7 Acceleration time (ACC Time)
8 Deceleration time (DEC Time)
9 Operation command output (F1 to F8, there are a total of 8 operation control functions)

Manual — Arithmetic functions — page 407

6: Multiplication and division modes

RESULT(calculation result)=V1*V2/V3

Addition/subtraction table completes406:operandsAS1–4,MD1–4,T1–8,C1–8,V1–8 orconstant;errorcoilM1–MF;AS1–AS4. Multiplication/division hassamepositions1result,2multiplierV1,3multiplierV2,4divisorV3,5errorcoilM1–MF,6MD1–MD4;RESULT=V1*V2/V3. No invented zero-division behavior.

Arithmetic functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

Arithmetic functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Arithmetic functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Arithmetic functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Arithmetic functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Arithmetic functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Arithmetic functions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 

Arithmetic functions table1 — PDF page 407

Source row Symbol Description
1 Calculation result : RESULT
2 Addend V1(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant )
3 Addend V2(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant )
4 Subtrahend V3(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant )
5 Coil output of error signal (M1~MF)
6 Addition and subtraction modes number (AS1~AS4)

Arithmetic functions table2 — PDF page 407

Source row Symbol Description
1 Calculation result : RESULT
2 Multiplier V1(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant )
3 Multiplier V2(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant )
4 Divisor V3(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant )
5 Coil output of error signal(M1~MF)
6 Multiplication and division modes number (MD1~ MD4)

Manual — Modbus network and connector — page 408

4.6 Modbus Protocol Descriptions

4.6.1 Communication Connection and Data Frame

The inverter can communicate with a PC or PLC via RS485 or RS232 using the Modbus RTU or

Modbus ACSII protocol. The maximum frame length is 80 bytes.

 Network Connection

Controller

(PLC / HMI or

PC )

F510

Node

Address 01

Address 02

Address 03

Address 1F

CN6

RS-485

Interface

S(+)

S(-)

Receiver

Sender

**When several inverters are connected togerher by Modbus, please turn on the terminal resistor

switch on the end inverter.

**The distance of communication line with above 200m should have terminal resistors, which ought

to be placed at both ends, so as to eliminate reflection phenomenon.

Use S (+) and S (-) terminals (only for RS-485) or CN6 connector to connect.

CN6 Connector:

For RS-485 communication, use pin 1 or pin 3 for S (+) and pin 2 or pin 6 for S (-).

8 7 6 5 4 3 2 1

120Ω

1/4w

RS485/RS232 ModbusRTU/ASCII,maxframe80bytes. Networkcontroller→F510nodes01/02/03…1F drawnwithCN6S+/S− and120ohm1/4W terminationatbothends. Severalinvertersuseendterminalswitch;lineabove200mresistorsbothends. ModeltableSW5:220V1–50HP/440V1–75HP;220V60–175HP/440V100–800HP useSW4standardH&C orSW5enhancedE&G. CN6facepinorder8,7,6,5,4,3,2,1lefttoright. Pin1/3S+,2/6S−,4Rx,5Tx,7isolated5VVCC,8isolated5VGND. Source describesconnection,not fieldverifiednetworklimits.

Modbus network and connector. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

Modbus network and connector. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 220V 1HP~50HP

Modbus network and connector. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 440V 1HP~75HP

Modbus network and connector. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 220V 60HP~175HP

Modbus network and connector. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 440V 100HP~800HP

Shared source cells (coordinates refer to this table):

Modbus network and connector. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 1

Modbus network and connector. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 2

Modbus network and connector. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 3

Modbus network and connector. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: 4

Modbus network and connector table5 — PDF page 408

Source row Inverter Model Terminal resistor switch
1 220V 1HP~50HP SW5
2 440V 1HP~75HP ⟦null: no independent source value⟧
3 220V 60HP~175HP SW4 (Standard H & C) SW5 (Enhanced E & G)
4 440V 100HP~800HP ⟦null: no independent source value⟧

Modbus network and connector table6 — PDF page 408

Source row Pin Signal Pin Signal
1 1 RS-485 S+ signal 5 Tx signal
2 2 RS-485 S- signal 6 RS-485 S- signal
3 3 RS-485 S+ signal 7 VCC of isolated 5V power supply
4 4 Rx signal 8 GND of isolated 5V power supply

Manual — Modbus frame and function codes — page 409

 Data Format Frame

Data Frame for ASCII Mode

 Data Frame for RTU Mode

Master (PLC etc.) sends request to follower (inverter), and the follower sends a response to the

master (PC, PLC). The data received is illustrated here.

The data length varies depending on the command (Function).

Node Address

Function Code

DATA

CRC CHECK

Signal Interval

** The inverter response time is 10ms.

 Node Address

00H: Broadcast to all the drivers

01H: to the No. 01 inverter

0FH: to the No.15 inverter

10H: to the No.16 inverter and so on...., max to No. 254 (FEH)

 Function Code

03H: Read the register contents

06H: Write a WORD to register

08H: Loop test

10H: Write several data to register (complex number register write)

ASCII table orderSTX3AH,2addressASCII,2functionASCII,4command-startASCII,4lengthASCII,2LRCASCII,ENDHiCR0DH/ENDLoLF0AH;source says END Li in description. Repeatedstart/length rowsareindividualcharacters notduplicates. RTU verticalsequenceNodeAddress/FunctionCode/DATA/CRCCHECK/SignalInterval. Response10ms sourceclaim. Node00Hbroadcast,01Hno1,0FHno15,10Hno16,max254FEH;networkfigure1Fnotglobalmax. Functions03Hread,06HwriteWORD,08Hlooptest,10Hmultipleregisterwrite. Protocol details continue410outsidepart.

Modbus frame and function codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval.

Modbus frame and function codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter STX(3AH)

Modbus frame and function codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter Address Hi

Modbus frame and function codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter Address Lo

Modbus frame and function codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter Function Hi

Modbus frame and function codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter Function Lo

Modbus frame and function codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter Command Start Address

Modbus frame and function codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter Data length

Modbus frame and function codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter LRC Check Hi

Modbus frame and function codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter LRC Check Lo

Modbus frame and function codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter END Hi

Modbus frame and function codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain conditions and source conflicts; no engineering approval. Row group: Source row / parameter END Lo

Shared source cells (coordinates refer to this table):

Modbus frame and function codes table1 — PDF page 409

Source row Source row label Source value or description
1 STX(3AH) Start Bit = 3AH
2 Address Hi Communication Address (Station): 2-digit ASCII Code
3 Address Lo ⟦null: no independent source value⟧
4 Function Hi Function Code (command): 2-digit ASCII Code
5 Function Lo ⟦null: no independent source value⟧
6 Command Start Address Command Start Byte: 4-digit ASCII Code
7 Command Start Address ⟦null: no independent source value⟧
8 Command Start Address ⟦null: no independent source value⟧
9 Command Start Address ⟦null: no independent source value⟧
10 Data length The length of the command: 4-digit ASCII Code
11 Data length ⟦null: no independent source value⟧
12 Data length ⟦null: no independent source value⟧
13 Data length ⟦null: no independent source value⟧
14 LRC Check Hi LRC Check Code: 2-digit ASCII Code
15 LRC Check Lo ⟦null: no independent source value⟧
16 END Hi End Bit: END Hi = CR(0DH) , END Li = LF(0AH)
17 END Lo ⟦null: no independent source value⟧

Manual — Modbus checksum calculation — page 410

 Checksum Calculation

LRC

ex. NODE ADDRESS

01H

FUNCTION

03H

COMMAND

00H

+

DATA LENGTH 0AH


0FH------------2’s complement

Checksum =

F1H

CS(H) =

46H (ASCII)

CS(L) =

31H (ASCII)

CRC

CRC Check: CRC code covers the content from Slave address to DATA. Please calculate it

according to the following methods.

(1) Load a 16-bit register with FFFF hex (all1’s). Call this CRC register.

(2) Exclusive OR the first 8-bit byte of the message, the low-order byte of the 16-bit CRC register,

putting the result in the CRC register.

(3) Shift the CRC register one bit to the right (toward the LSB), Zero-filling the MSB, Extract and

examines the LSB.

(4) (If the LSB was 0): Repeat Steps (3) (another shift)

(If the LSB was 1): Exclusive OR the CRC register with the polynomial value A001 hex (1010

0000 0000 0001), putting the result in CRC register.

(5) Repeat Steps (3) and (4) until 8 shifts been performed. When this is done, a complete 8-bit

byte will be processed.

(6) Repeat Steps (2) through (5) for next 8-bit byte of the message, Continue doing this until all

bytes have been processed. The final content in the CRC register is the CRC value. When

sending the CRC value, the Low-order byte should be sent firstly, then the High-order byte.

For example, CRC value: 1241 Hex, the high-order byte should be set to 41hex and low-order

byte 12hex.

 CRC Calculate Program (C language)

UWORD ch_sum (UBYTE long , UBYTE *rxdbuff ) {

BYTE i = 0;

UWORD wkg = 0xFFFF;

while ( long-- ) {

wkg ^= rxdbuff++;

for ( i = 0 ; i < 8; i++ ) {

if ( wkg & 0x0001 ) {

wkg = ( wkg >> 1 ) ^ 0xa001;

}

else {

wkg = wkg >> 1;

return( wkg );

LRC example node01,function03,command01/00,length0A sums0F, two-complementF1; ASCII high46/low31. CRC initializesFFFF, XOR byte, shifts8times usingA001, sendsloworderfirst. Example1241 calls high-order41/low12, contrary numeric byte naming. Source C code retained verbatim; uses reserved word long as identifier and rxdbuff++ without dereference. Not compiled or executed. Source examples are not verified communication instructions.

Manual — Modbus exceptions — page 411

 Exception Code

During a communication error, the inverter will respond with an Exception Code and send a

message back to the main system consisting of a Function Code that is “ANDED (and 80h)” with 80

Hex.

ASCII error frame colon,address01,function86,exception51,LRC28,CR/LF. RTU slave02,function83,exception52,CRC HighC0/LowCD. Text says function code ANDED with80hex; examples86/83 do not result from that AND. Listed exception meanings01function code error,02register number error,03number error,04DATA setting error; illustrated51/52 outside this list. Retain rather than normalise.

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: STX

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Address

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Function

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Exception

code

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: LRC Check

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: END

Shared source cells (coordinates refer to this table):

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: SLAVE Address

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Exception code

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: CRC-16

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 01

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 02

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 03

Modbus exceptions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 04

Modbus exceptions table1 — PDF page 411

Source row ASCII frame component Printed character or byte
1 STX ‘:’
2 Address ‘0’
3 ⟦null: no independent source value⟧ ‘1’
4 Function ‘8’
5 ⟦null: no independent source value⟧ ‘6’
6 Exception code ‘5’
7 ⟦null: no independent source value⟧ ‘1’
8 LRC Check ‘2’
9 ⟦null: no independent source value⟧ ‘8’
10 END ‘CR’
11 ⟦null: no independent source value⟧ ‘LF’

Modbus exceptions table2 — PDF page 411

Source row RTU frame component Byte order within CRC Printed hexadecimal byte
1 SLAVE Address ⟦null: no independent source value⟧ 02H
2 Function ⟦null: no independent source value⟧ 83H
3 Exception code ⟦null: no independent source value⟧ 52H
4 CRC-16 High C0H
5 ⟦null: no independent source value⟧ Low CDH

Modbus exceptions table3 — PDF page 411

Source row Exception Code Content
1 01 Function code error
2 02 Register number error
3 03 Number error
4 04 DATA setting error

Manual — Command read-write registers — page 412

4.6.2 Register and Data Format

 Command Data (Read / Write)

Note: Write a zero into the register for not used bit; do not write data to a reserved register.

2500reserved. 2501 operation bits0run1/stop0,1reverse1/forward0,2externalfault1,3reset1;4/5reserved;6S1,7S2,8S3,9S4,AS5,BS6 each1ON;C/Dreserved;Econtrollermode1ON;Freserved. 2502frequency .01Hz;2503reserved;2504speedlimit ±120 corresponds ±120%;2505AO1/2506AO2 range0–1000 corresponds0–10V or4–20mA;2507DO;2508–250Freserved;2510G12-00HWORD,2511LWORD. Unusedbitswrite0; do not write reserved registers. Physical merged cells and multiline bit groups retained without fabricating extra rows.

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2500H

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2501H

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2502H

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2503H

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2504H

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2505H

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2506H

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2507H

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2508H

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2509H

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 250AH

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 250BH

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 250CH

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 250DH

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 250EH

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 250FH

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2510H

Command read-write registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2511H

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c2, r2c2, r3c2, r4c2, r5c2, r6c2, r20c2, r21c2. A header spans across these blank regions in the native text; no header value is propagated into them.

Command read-write registers table1 — PDF page 412

Source row Register number Printed spacer / merged register Signal or merged description Bit or merged description Content
1 2500H ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 2501H ⟦null: no independent source value⟧ Operation Signal 0 1 2 3 Operation Command 1 : Run 0 : Stop Reverse Command 1 : Reverse 0 : Forward External Fault 1 : Fault Fault Reset 1 : Reset
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4 5 6 7 8 9 A B C D E Reserved Reserved Multi-function Comm S1 1 :“ON” Multi-function Comm S2 1 :“ON” Multi-function Comm S3 1 :“ON” Multi-function Comm S4 1 :“ON” Multi-function Comm S5 1 :“ON” Multi-function Comm S6 1 :“ON” Reserved Reserved Controller Mode 1 : “ON”
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ F Reserved
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧
6 2502H ⟦null: no independent source value⟧ ⟦blank source cell⟧ Frequency Command (Unit: 0.01Hz) ⟦null: no independent source value⟧
7 2503H ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved ⟦null: no independent source value⟧
8 2504H ⟦blank source cell⟧ ⟦blank source cell⟧ Speed Limit (+/- 120 correspond to +/-120%) ⟦null: no independent source value⟧
9 2505H ⟦blank source cell⟧ ⟦blank source cell⟧ AO1 (0 ~ 1000): Voltage (0.00V ~ 10.00V); Current (4mA~20mA) ⟦null: no independent source value⟧
10 2506H ⟦blank source cell⟧ ⟦blank source cell⟧ AO2 (0 ~ 1000): Voltage (0.00~10.00V); Current (4mA~20mA) ⟦null: no independent source value⟧
11 2507H ⟦blank source cell⟧ ⟦blank source cell⟧ DO ⟦null: no independent source value⟧
12 2508H ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved ⟦null: no independent source value⟧
13 2509H ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved ⟦null: no independent source value⟧
14 250AH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved ⟦null: no independent source value⟧
15 250BH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved ⟦null: no independent source value⟧
16 250CH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved ⟦null: no independent source value⟧
17 250DH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved ⟦null: no independent source value⟧
18 250EH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved ⟦null: no independent source value⟧
19 250FH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved ⟦null: no independent source value⟧
20 2510H ⟦null: no independent source value⟧ ⟦blank source cell⟧ G12-00 H-WORD ⟦null: no independent source value⟧
21 2511H ⟦null: no independent source value⟧ ⟦blank source cell⟧ G12-00 L-WORD ⟦null: no independent source value⟧

Manual — Read-only status and faults — page 413

 Monitor Data (Read only)

2520 state bits0run/stop,1reverse/forward,2ready/unready,3fault,4warning,5zero speed,6printed Ls440,7frequency agreement,8set frequency agreement,9frequency detection1,Adetection2,Bundervoltage,Cbase block,Dfrequencyreference notfromcommunication,Esequence notfromcommunication,Fovertorque. 2521fault codes arranged two side-by-side code/meaning pairs:0–27left,31–58right. Fault28–30/59–61 continue414 without repeatedregister label. All reservedcodes retained. Codes17–22 externalEF1–6;25FB PID feedback;36low suction,37low suction retry;40HIPBT highflow;42LPBFTlowpressure,43OPBFThighpressure;46OH4;50OCA/51OCD/52OCC;54PTCLS55PF56TOL57STO2. Printed source spelling/capitalization retained.

Read-only status and faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Read-only status and faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2520H

Read-only status and faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2521H

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c2, r2c2, r3c2, r4c2, r5c2, r6c2, r7c2, r8c2, r9c2, r10c2, r11c2, r12c2, r13c2, r14c2, r15c2, r16c2, r17c2, r19c2, r20c2, r21c2, r22c2, r23c2, r24c2, r25c2, r26c2, r27c2, r28c2, r29c2, r30c2, r31c2, r32c2, r33c2, r34c2, r35c2, r36c2, r37c2, r38c2, r39c2, r40c2, r41c2, r42c2, r43c2, r44c2, r45c2. A header spans across these blank regions in the native text; no header value is propagated into them.

Read-only status and faults table1 — PDF page 413

Source row Register number Printed spacer / merged register Signal class Bit or first fault code First meaning Second fault code Second meaning
1 2520H ⟦null: no independent source value⟧ State Signal 0 Operation 1 : Run 0 : Stop ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1 Direction 1 : Reverse 0 : Forward ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2 Inverter ready 1 : Ready 0 : Unready ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3 Fault 1 : Abnormal ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4 Warning 1 :“ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5 Zero Speed 1 :“ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6 Ls 440 1 :“ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7 Frequency Agree 1 :“ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8 Set Frequency Agree 1 :“ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9 Frequency Detection 1 1 :“ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ A Frequency Detection 2 1 :“ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ B Under Voltage 1 :“ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ C Baseblock 1 :“ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ D Freq Ref. not from Comm. 1 :“ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ E Seq. not from Comm. 1 :“ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ F Over Torque 1 :“ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 2521H ⟦blank source cell⟧ Error Description 0 Reserved 31 Reserved
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1 UV 32 Reserved
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2 OC 33 Reserved
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3 OV 34 Reserved
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4 OH1 35 Reserved
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5 OL1 36 Low Suction Fault
24 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6 OL2 37 Low Suction Fault (with retry)
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7 OT 38 CF07
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8 UT 39 LOPBT(Low Flow Fault)
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9 SC 40 HIPBT(High Flow Fault)
28 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10 GF(Ground Fault) 41 Reserved
29 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 11 FU(Fuse Broken) 42 LPBFT(Low Pressure Fault)
30 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 12 IPL(Input Phase Loss) 43 OPBFT(High Pressure Fault)
31 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 13 OPL(Output Phase Loss) 44 FBLSS(PID Feedback Loss)
32 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 14 Reserved 45 Reserved
33 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 15 Reserved 46 Motor Overheat (OH4)
34 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 16 Reserved 47 SS1
35 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 17 EF1(External terminal S1 Fault) 48 CF20
36 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 18 EF2(External terminal S2 Fault) 49 Reserved
37 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 19 EF3(External terminal S3 Fault) 50 OCA(Overcurrent in acceleration)
38 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 20 EF4(External terminal S4 Fault) 51 OCD(Overcurrent in deceleration)
39 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 21 EF5(External terminal S5 Fault) 52 OCC(Overcurrent in constant speed)
40 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 22 EF6(External terminal S6 Fault) 53 Reserved
41 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 23 Reserved 54 PTCLS (PTC signal loss)
42 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 24 Reserved 55 PF (Protection Fault)
43 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 25 FB(PID Feedback Fault) 56 TOL (External Overload)
44 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 26 Keypad Removed 57 STO2
45 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 27 Reserved 58 Reserved

Manual — Read-only faults and warnings — page 414

Top continues2521 from413:28CE29STO30reserved;59–61reserved. 2522DI bits0–5CommS1–S6,6–Freserved. 2523frequencycommand .01Hz,2524outputfrequency .01Hz,2525reserved,2526DCVoltageCommand .1V,2527outputcurrent .1A. 2528warnings four simultaneouscode/meaningpairs0–19,20–39,40–59,60–79. LoPb appears57and60;HIPb58and64;39HPERR and46HP_ER distinct printedlabels. 2529DOstate,252A/BAO1/2 range0–1000→0–10V or4–20mA,252C/DAI1/2 .1%,252Ereserved. Blank physicalspacers and merged signalclass columns retained,not a numeric rating.

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group:

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2522H

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2523H

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2524H

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2525H

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2526H

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2527H

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2528H

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2529H

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 252AH

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 252BH

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 252CH

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 252DH

Read-only faults and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 252EH

Shared source cells (coordinates refer to this table):

Read-only faults and warnings table1 — PDF page 414

Source row Register number Printed spacer / merged register Signal class Bit or first warning code First warning meaning Merged monitor meaning Second warning code Second warning meaning Third warning or continued fault code Third warning or continued fault meaning Fourth warning code Fourth warning meaning
1 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 28 ⟦null: no independent source value⟧ CE ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 59 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 29 ⟦null: no independent source value⟧ STO ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 60 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 30 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 61 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 2522H ⟦blank source cell⟧ DI State 0 ⟦null: no independent source value⟧ Multi-function Comm S1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1 ⟦null: no independent source value⟧ Multi-function Comm S2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2 ⟦null: no independent source value⟧ Multi-function Comm S3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3 ⟦null: no independent source value⟧ Multi-function Comm S4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4 ⟦null: no independent source value⟧ Multi-function Comm S5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5 ⟦null: no independent source value⟧ Multi-function Comm S6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ A ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ B ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ C ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ D ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ E ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ F ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
20 2523H ⟦blank source cell⟧ ⟦blank source cell⟧ Frequency Command (0.01Hz) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 2524H ⟦blank source cell⟧ ⟦blank source cell⟧ Output Frequency (0.01Hz) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 2525H ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 2526H ⟦blank source cell⟧ ⟦blank source cell⟧ DC Voltage Command (0.1V) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
24 2527H ⟦blank source cell⟧ ⟦blank source cell⟧ Output Current (0.1A) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
25 2528H ⟦blank source cell⟧ Warning Description 0 No alarm ⟦null: no independent source value⟧ 20 EF4 40 EF 60 LOPb
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1 OV ⟦null: no independent source value⟧ 21 EF5 41 Reserved 61 RETRY
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2 UV ⟦null: no independent source value⟧ 22 EF6 42 Reserved 62 Reserved
28 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3 OL2 ⟦null: no independent source value⟧ 23 Reserved 43 RDP 63 Reserved
29 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4 OH2 ⟦null: no independent source value⟧ 24 Reserved 44 Reserved 64 HIPb
30 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5 Reserved ⟦null: no independent source value⟧ 25 Reserved 45 OL1 65 OH1
31 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6 OT ⟦null: no independent source value⟧ 26 CLB 46 HP_ER 66 FIRE
32 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7 Reserved ⟦null: no independent source value⟧ 27 Reserved 47 SE10 67 ES
33 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8 Reserved ⟦null: no independent source value⟧ 28 CT 48 COPUP 68 STP1
34 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9 UT ⟦null: no independent source value⟧ 29 USP 49 BB1 69 BDERR
35 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10 Reserved ⟦null: no independent source value⟧ 30 RDE 50 BB2 70 EPERR
36 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 11 Reserved ⟦null: no independent source value⟧ 31 WRE 51 BB3 71 ADCER
37 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 12 Reserved ⟦null: no independent source value⟧ 32 FB 52 BB4 72 OL4
38 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 13 CE ⟦null: no independent source value⟧ 33 VRYE 53 BB5 73 STP0
39 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 14 CALL ⟦null: no independent source value⟧ 34 SE01 54 BB6 74 Reserved
40 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 15 Reserved ⟦null: no independent source value⟧ 35 SE02 55 Reserved 75 STP2
41 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 16 EF0 ⟦null: no independent source value⟧ 36 SE03 56 Reserved 76 RUNER
42 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 17 EF1 ⟦null: no independent source value⟧ 37 Reserved 57 LOPb 77 LOC
43 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 18 EF2 ⟦null: no independent source value⟧ 38 SE05 58 HIPb 78 PTCLS
44 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 19 EF3 ⟦null: no independent source value⟧ 39 HPERR 59 LSCFT 79 FBLSS
45 2529H ⟦blank source cell⟧ ⟦blank source cell⟧ DO State ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
46 252AH ⟦blank source cell⟧ ⟦blank source cell⟧ AO1 (0 ~ 1000): Voltage (0.00V ~ 10.00V); Current (4mA~20mA) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
47 252BH ⟦blank source cell⟧ ⟦blank source cell⟧ AO2 (0 ~ 1000): Voltage (0.00~10.00V); Current (4mA~20mA) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
48 252CH ⟦blank source cell⟧ ⟦blank source cell⟧ Analog Input 1 (0.1%) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
49 252DH ⟦blank source cell⟧ ⟦blank source cell⟧ Analog Input 2 (0.1%) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
50 252EH ⟦blank source cell⟧ ⟦blank source cell⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Register read examples — page 415

Note: Do not write data to a reserved register.

 Read Holding Register [03H]

Read consecutive holding registers. The address of the first holding register is specified in the

protocol.

Example: Read frequency command from the inverter with node address 1.

 ASCII Mode

Command message Response Message (Normal) Response Message (Error)

+

 RTU Mode

Command Message Response Message (Normal) Response Message (Error)

252F modelcheckF510/A510/L510/E510;2532relaycardstatus. 2530/31notlisted here. Read03 command example node01,register0C10,count0001. ASCII command LRCDF;normal data1770,length02,LRC73;error01/83/04 printedLRC40. RTU command CRCrowHigh86/Low9F;normal B6/50;error40/F3. PhysicalCRC order resembleslowbytefirst while rowlabels sayHighthenLow. LRC error40 conflicts with two-complement calculation78; originalretained withdiagnostic flag. No liveprotocoltest.

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 252FH

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2532H

Blank continuation bodies at r1c2, r2c2. A header spans across these blank regions in the native text; no header value is propagated into them.

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions.

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 3AH

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 30H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 31H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 33H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 43H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 44H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 46H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 0DH

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 0AH

Shared source cells (coordinates refer to this table):

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions.

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 3AH

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 30H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 31H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 33H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 32H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 37H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 0DH

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 0AH

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions.

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 3AH

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 30H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 31H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 38H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 33H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 34H

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 0DH

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 0AH

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions.

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Node Address

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Function Code

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Starting

Register

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Number of

Registers

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: CRC-16

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions.

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Node Address

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Function Code

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: DATA Length

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Data

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: CRC-16

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions.

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: Node Address

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: Function Code

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: Exception Code

Register read examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: CRC-16

Register read examples table1 — PDF page 415

Source row Register number Printed spacer / merged register Printed blank Content
1 252FH ⟦null: no independent source value⟧ ⟦blank source cell⟧ F510/A510/L510/E510 Check
2 2532H ⟦null: no independent source value⟧ ⟦blank source cell⟧ Relay card status display

Register read examples table2 — PDF page 415

Source row Printed hexadecimal ASCII byte Frame component
1 3AH STX
2 30H Node Address
3 31H ⟦null: no independent source value⟧
4 30H Function Code
5 33H ⟦null: no independent source value⟧
6 30H Starting Register
7 43H ⟦null: no independent source value⟧
8 31H ⟦null: no independent source value⟧
9 30H ⟦null: no independent source value⟧
10 30H Number of Registers
11 30H ⟦null: no independent source value⟧
12 30H ⟦null: no independent source value⟧
13 31H ⟦null: no independent source value⟧
14 44H LRC CHECK
15 46H ⟦null: no independent source value⟧
16 0DH END
17 0AH ⟦null: no independent source value⟧

Register read examples table3 — PDF page 415

Source row Printed hexadecimal ASCII byte Frame component
1 3AH STX
2 30H Node Address
3 31H ⟦null: no independent source value⟧
4 30H Function Code
5 33H ⟦null: no independent source value⟧
6 30H DATA Length
7 32H ⟦null: no independent source value⟧
8 31H Data
9 37H ⟦null: no independent source value⟧
10 37H ⟦null: no independent source value⟧
11 30H ⟦null: no independent source value⟧
12 37H LRC CHECK
13 33H ⟦null: no independent source value⟧
14 0DH END
15 0AH ⟦null: no independent source value⟧

Register read examples table4 — PDF page 415

Source row Printed hexadecimal ASCII byte Frame component
1 3AH STX
2 30H Node Address
3 31H ⟦null: no independent source value⟧
4 38H Function Code
5 33H ⟦null: no independent source value⟧
6 30H Exception Code
7 34H ⟦null: no independent source value⟧
8 34H LRC CHECK
9 30H ⟦null: no independent source value⟧
10 0DH END
11 0AH ⟦null: no independent source value⟧

Register read examples table5 — PDF page 415

Source row Frame component CRC byte order label Printed hexadecimal byte
1 Node Address ⟦null: no independent source value⟧ 01 H
2 Function Code ⟦null: no independent source value⟧ 03H
3 Starting Register High 0CH
4 ⟦null: no independent source value⟧ Low 10H
5 Number of Registers High 00H
6 ⟦null: no independent source value⟧ Low 01H
7 CRC-16 High 86H
8 ⟦null: no independent source value⟧ Low 9FH

Register read examples table6 — PDF page 415

Source row Frame component CRC byte order label Printed hexadecimal byte
1 Node Address ⟦null: no independent source value⟧ 01H
2 Function Code ⟦null: no independent source value⟧ 03H
3 DATA Length ⟦null: no independent source value⟧ 02H
4 Data High 17H
5 ⟦null: no independent source value⟧ Low 70H
6 CRC-16 High B6H
7 ⟦null: no independent source value⟧ Low 50H

Register read examples table7 — PDF page 415

Source row Frame component CRC byte order label Printed hexadecimal byte
1 Node Address ⟦null: no independent source value⟧ 01H
2 Function Code ⟦null: no independent source value⟧ 83H
3 Exception Code ⟦null: no independent source value⟧ 04H
4 CRC-16 High 40H
5 ⟦null: no independent source value⟧ Low F3H

Manual — Loopback examples — page 416

 Loop Back Test [08H]

Check the communication between the master and the follower (inverter). The data used can be

arbitrary.

 ASCII Mode

Command Message Response Message (Normal) Response Message (Error)

 RTU Mode

Command Message Response Message (Normal) Response Message (Error)

ASCII command andnormal:01/08/test0000/dataA537/LRC1B. Error01/88/03 printedLRC06. RTU command/normal CRCDA/8D;error06/01. ASCII errorLRC06 conflicts with calculation74; originals retained. RepeatedASCIIcharacters andblank/mergedrows are individualpositions,notdeduplicated.

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions.

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 3AH

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 30H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 31H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 38H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 41H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 35H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 33H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 37H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 42H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 0DH

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 0AH

Shared source cells (coordinates refer to this table):

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions.

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 3AH

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 30H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 31H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 38H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 41H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 35H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 33H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 37H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 42H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 0DH

0AH

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions.

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 3AH

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 30H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 31H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 38H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 33H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 36H

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 0DH

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 0AH

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions.

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Node Address

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Function Code

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Test Code

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: DATA

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: CRC-16

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions.

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Node Address

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Function Code

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Test Code

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: DATA

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: CRC-16

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions.

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: Node Address

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: Function Code

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: Exception Code

Loopback examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: CRC-16

Loopback examples table1 — PDF page 416

Source row Printed hexadecimal ASCII byte Frame component
1 3AH STX
2 30H Node Address
3 31H ⟦null: no independent source value⟧
4 30H Function Code
5 38H ⟦null: no independent source value⟧
6 30H Test Code
7 30H ⟦null: no independent source value⟧
8 30H ⟦null: no independent source value⟧
9 30H ⟦null: no independent source value⟧
10 41H DATA
11 35H ⟦null: no independent source value⟧
12 33H ⟦null: no independent source value⟧
13 37H ⟦null: no independent source value⟧
14 31H LRC CHECK
15 42H ⟦null: no independent source value⟧
16 0DH END
17 0AH ⟦null: no independent source value⟧

Loopback examples table2 — PDF page 416

Source row Printed hexadecimal ASCII byte Frame component
1 3AH STX
2 30H Node Address
3 31H ⟦null: no independent source value⟧
4 30H Function Code
5 38H ⟦null: no independent source value⟧
6 30H Test Code
7 30H ⟦null: no independent source value⟧
8 30H ⟦null: no independent source value⟧
9 30H ⟦null: no independent source value⟧
10 41H DATA
11 35H ⟦null: no independent source value⟧
12 33H ⟦null: no independent source value⟧
13 37H ⟦null: no independent source value⟧
14 31H LRC CHECK
15 42H ⟦null: no independent source value⟧
16 0DH 0AH END

Loopback examples table3 — PDF page 416

Source row Printed hexadecimal ASCII byte Frame component
1 3AH STX
2 30H Node Address
3 31H ⟦null: no independent source value⟧
4 38H Function Code
5 38H ⟦null: no independent source value⟧
6 30H Exception Code
7 33H ⟦null: no independent source value⟧
8 30H LRC CHECK
9 36H ⟦null: no independent source value⟧
10 0DH END
11 0AH ⟦null: no independent source value⟧

Loopback examples table4 — PDF page 416

Source row Frame component CRC byte order label Printed hexadecimal byte
1 Node Address ⟦null: no independent source value⟧ 01 H
2 Function Code ⟦null: no independent source value⟧ 08H
3 Test Code High 00H
4 ⟦null: no independent source value⟧ Low 00H
5 DATA High A5H
6 ⟦null: no independent source value⟧ Low 37H
7 CRC-16 High DAH
8 ⟦null: no independent source value⟧ Low 8DH

Loopback examples table5 — PDF page 416

Source row Frame component CRC byte order label Printed hexadecimal byte
1 Node Address ⟦null: no independent source value⟧ 01H
2 Function Code ⟦null: no independent source value⟧ 08H
3 Test Code High 00H
4 ⟦null: no independent source value⟧ Low 00H
5 DATA High A5H
6 ⟦null: no independent source value⟧ Low 37H
7 CRC-16 High DAH
8 ⟦null: no independent source value⟧ Low 8DH

Loopback examples table6 — PDF page 416

Source row Frame component CRC byte order label Printed hexadecimal byte
1 Node Address ⟦null: no independent source value⟧ 01H
2 Function Code ⟦null: no independent source value⟧ 88H
3 Exception Code ⟦null: no independent source value⟧ 03H
4 CRC-16 High 06H
5 ⟦null: no independent source value⟧ Low 01H

Manual — Single register write examples — page 417

 Write Single Holding Register [06H]

Write single holding register. The register address of the holding register is specified in the

message.

Example: Write a 60.00Hz frequency command to node address 1.

 ASCII Mode

Command Message Response Message (Normal) Response Message (Error)

RTU Mode

Command Message Response Message (Normal) Response Message (Error)

Example60.00Hz uses node01,function06,register2502,data1770 (6000hundredthsHz). ASCII command/normalLRC4B;error01/86/03 printedLRC02. RTU command/normalCRC2D/12;error02/61. ASCII error02 conflicts with calculation76. This is illustrativecommanddata,not modelratedfrequency or executedsetting.

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions.

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 3AH

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 30H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 31H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 36H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 32H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 35H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 37H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 34H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 42H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 0DH

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 0AH

Shared source cells (coordinates refer to this table):

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions.

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 3AH

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 30H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 31H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 36H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 32H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 35H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 37H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 34H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 42H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 0DH

0AH

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions.

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 3AH

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 30H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 31H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 38H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 36H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 33H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 32H

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 0DH

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 0AH

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions.

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Node Address

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Function Code

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Starting

Register

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: DATA

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: CRC-16

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions.

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Node Address

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Function Code

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Starting

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: DATA

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: CRC-16

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions.

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: Node Address

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: Function Code

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: Exception Code

Single register write examples. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: CRC-16

Single register write examples table1 — PDF page 417

Source row Printed hexadecimal ASCII byte Frame component
1 3AH STX
2 30H Node Address
3 31H ⟦null: no independent source value⟧
4 30H Function Code
5 36H ⟦null: no independent source value⟧
6 32H Starting Register
7 35H ⟦null: no independent source value⟧
8 30H ⟦null: no independent source value⟧
9 32H ⟦null: no independent source value⟧
10 31H DATA
11 37H ⟦null: no independent source value⟧
12 37H ⟦null: no independent source value⟧
13 30H ⟦null: no independent source value⟧
14 34H LRC CHECK
15 42H ⟦null: no independent source value⟧
16 0DH END
17 0AH ⟦null: no independent source value⟧

Single register write examples table2 — PDF page 417

Source row Printed hexadecimal ASCII byte Frame component
1 3AH STX
2 30H Node Address
3 31H ⟦null: no independent source value⟧
4 30H Function Code
5 36H ⟦null: no independent source value⟧
6 32H Starting Register
7 35H ⟦null: no independent source value⟧
8 30H ⟦null: no independent source value⟧
9 32H ⟦null: no independent source value⟧
10 31H DATA
11 37H ⟦null: no independent source value⟧
12 37H ⟦null: no independent source value⟧
13 30H ⟦null: no independent source value⟧
14 34H LRC CHECK
15 42H ⟦null: no independent source value⟧
16 0DH 0AH END

Single register write examples table3 — PDF page 417

Source row Printed hexadecimal ASCII byte Frame component
1 3AH STX
2 30H Node Address
3 31H ⟦null: no independent source value⟧
4 38H Function Code
5 36H ⟦null: no independent source value⟧
6 30H Exception Code
7 33H ⟦null: no independent source value⟧
8 30H LRC CHECK
9 32H ⟦null: no independent source value⟧
10 0DH END
11 0AH ⟦null: no independent source value⟧

Single register write examples table4 — PDF page 417

Source row Frame component CRC byte order label Printed hexadecimal byte
1 Node Address ⟦null: no independent source value⟧ 01 H
2 Function Code ⟦null: no independent source value⟧ 06H
3 Starting Register High 25H
4 ⟦null: no independent source value⟧ Low 02H
5 DATA High 17H
6 ⟦null: no independent source value⟧ Low 70H
7 CRC-16 High 2DH
8 ⟦null: no independent source value⟧ Low 12H

Single register write examples table5 — PDF page 417

Source row Frame component CRC byte order label Printed hexadecimal byte
1 Node Address ⟦null: no independent source value⟧ 01H
2 Function Code ⟦null: no independent source value⟧ 06H
3 Starting Register High 25H
4 ⟦null: no independent source value⟧ Low 02H
5 DATA High 17H
6 ⟦null: no independent source value⟧ Low 70H
7 CRC-16 High 2DH
8 ⟦null: no independent source value⟧ Low 12H

Single register write examples table6 — PDF page 417

Source row Frame component CRC byte order label Printed hexadecimal byte
1 Node Address ⟦null: no independent source value⟧ 01H
2 Function Code ⟦null: no independent source value⟧ 86H
3 Exception Code ⟦null: no independent source value⟧ 03H
4 CRC-16 High 02H
5 ⟦null: no independent source value⟧ Low 61H

Manual — Multiple register ASCII write — page 418

 Write Multiple Holding Register [10H]

Write multiple holding registers. The address of the first holding register is specified in the

message.

Example: Write a 60.00Hz frequency command to node address 1 and enable FWD run

command.

 ASCII Mode

Command Message Response Message (Normal) Response Message (Error)

Command01/10/start2501/count0002/bytecount04/data0001+1770/LRC3B. Normal01/10/start2501/count0002/LRCC7. Error01/90/03 printedLRC0C versus arithmetic6C. Bytes equalregistercount×2;example setsforwardrun plus60Hz. RTU continues419; no autonomous devicewrite.

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions.

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 3AH

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 30H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 31H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 32H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 35H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 34H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 37H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 33H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 42H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 0DH

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Command; repeated characters represent distinct serialized positions. Row group: 0AH

Shared source cells (coordinates refer to this table):

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions.

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 3AH

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 30H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 31H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 32H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 35H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 43H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 37H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 0DH

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Normal response; repeated characters represent distinct serialized positions. Row group: 0AH

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions.

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 3AH

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 30H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 31H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 39H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 33H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 43H

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 0DH

Multiple register ASCII write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. ASCII Error response; repeated characters represent distinct serialized positions. Row group: 0AH

Multiple register ASCII write table1 — PDF page 418

Source row Printed hexadecimal ASCII byte Frame component
1 3AH STX
2 30H Node Address
3 31H ⟦null: no independent source value⟧
4 31H Function Code
5 30H ⟦null: no independent source value⟧
6 32H Starting Register
7 35H ⟦null: no independent source value⟧
8 30H ⟦null: no independent source value⟧
9 31H ⟦null: no independent source value⟧
10 30H Number of Registers
11 30H ⟦null: no independent source value⟧
12 30H ⟦null: no independent source value⟧
13 32H ⟦null: no independent source value⟧
14 30H Number of Bytes *
15 34H ⟦null: no independent source value⟧
16 30H DATA 1
17 30H ⟦null: no independent source value⟧
18 30H ⟦null: no independent source value⟧
19 31H ⟦null: no independent source value⟧
20 31H DATA 2
21 37H ⟦null: no independent source value⟧
22 37H ⟦null: no independent source value⟧
23 30H ⟦null: no independent source value⟧
24 33H LRC CHECK
25 42H ⟦null: no independent source value⟧
26 0DH END
27 0AH ⟦null: no independent source value⟧

Multiple register ASCII write table2 — PDF page 418

Source row Printed hexadecimal ASCII byte Frame component
1 3AH STX
2 30H Node Address
3 31H ⟦null: no independent source value⟧
4 31H Function Code
5 30H ⟦null: no independent source value⟧
6 32H Starting Register
7 35H ⟦null: no independent source value⟧
8 30H ⟦null: no independent source value⟧
9 31H ⟦null: no independent source value⟧
10 30H Number of Registers
11 30H ⟦null: no independent source value⟧
12 30H ⟦null: no independent source value⟧
13 32H ⟦null: no independent source value⟧
14 43H LRC CHECK
15 37H ⟦null: no independent source value⟧
16 0DH END
17 0AH ⟦null: no independent source value⟧

Multiple register ASCII write table3 — PDF page 418

Source row Printed hexadecimal ASCII byte Frame component
1 3AH STX
2 30H Node Address
3 31H ⟦null: no independent source value⟧
4 39H Function Code
5 30H ⟦null: no independent source value⟧
6 30H Exception Code
7 33H ⟦null: no independent source value⟧
8 30H LRC CHECK
9 43H ⟦null: no independent source value⟧
10 0DH END
11 0AH ⟦null: no independent source value⟧

Manual — Multiple register RTU write — page 419

RTU Mode

Command Message Response Message (Normal) Response Message (Error)

Command01/10/2501/0002/04/0001/1770 CRC60/27;normal01/10/2501/0002 CRC1B/04;error01/90/03 CRC0C/01. Preserve sourceCRCHighthenLowlabels and actual orderedbytes; arithmetic checks do not certify implementation.

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions.

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Node Address

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Function Code

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Starting

Register

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Number of

Registers

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: Number of Bytes *

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: DATA 1

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: DATA 2

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Command; repeated characters represent distinct serialized positions. Row group: CRC-16

Shared source cells (coordinates refer to this table):

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions.

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Node Address

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Function Code

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Starting

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: Number of

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Normal response; repeated characters represent distinct serialized positions. Row group: CRC-16

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions.

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: Node Address

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: Function Code

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: Exception Code

Multiple register RTU write. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. RTU Error response; repeated characters represent distinct serialized positions. Row group: CRC-16

Multiple register RTU write table1 — PDF page 419

Source row Frame component CRC byte order label Printed hexadecimal byte
1 Node Address ⟦null: no independent source value⟧ 01H
2 Function Code ⟦null: no independent source value⟧ 10H
3 Starting Register High 25H
4 ⟦null: no independent source value⟧ Low 01H
5 Number of Registers High 00H
6 ⟦null: no independent source value⟧ Low 02H
7 Number of Bytes * ⟦null: no independent source value⟧ 04H
8 DATA 1 High 00H
9 ⟦null: no independent source value⟧ Low 01H
10 DATA 2 High 17H
11 ⟦null: no independent source value⟧ Low 70H
12 CRC-16 High 60H
13 ⟦null: no independent source value⟧ Low 27H

Multiple register RTU write table2 — PDF page 419

Source row Frame component CRC byte order label Printed hexadecimal byte
1 Node Address ⟦null: no independent source value⟧ 01H
2 Function Code ⟦null: no independent source value⟧ 10H
3 Starting Register High 25H
4 ⟦null: no independent source value⟧ Low 01H
5 Number of Registers High 00H
6 ⟦null: no independent source value⟧ Low 02H
7 CRC-16 High 1BH
8 ⟦null: no independent source value⟧ Low 04H

Multiple register RTU write table3 — PDF page 419

Source row Frame component CRC byte order label Printed hexadecimal byte
1 Node Address ⟦null: no independent source value⟧ 01H
2 Function Code ⟦null: no independent source value⟧ 90H
3 Exception Code ⟦null: no independent source value⟧ 03H
4 CRC-16 High 0CH
5 ⟦null: no independent source value⟧ Low 01H

Manual — Groups0 and1 register map — page 420

 Parameter Data and Corresponding Register No.

Three function/registercolumnpairs. Group0left00–44→0000–002C,middle45–56→002D–0038;Group1right00–15→0100–010F. AlladdressesprintedhexwithH suffix. Blankcells retained; absenceofrows notusedtoinfer unavailableparameters.

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Group 0

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 00

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 01

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 02

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 03

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 04

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 05

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 06

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 07

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 08

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 09

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 10

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 11

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 12

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 13

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 14

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 15

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 16

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 17

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 18

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 19

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 20

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 21

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 22

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 23

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 24

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 25

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 26

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 27

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 28

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 29

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 30

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 31

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 32

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 33

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 34

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 35

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 36

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 37

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 38

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 39

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 40

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 41

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 42

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 43

Groups0 and1 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 0 – 44

Shared source cells (coordinates refer to this table):

Groups0 and1 register map table1 — PDF page 420

Source row Function Code Register No. Function Code Register No. Function Code Register No.
1 Group 0 ⟦null: no independent source value⟧ Group 0 ⟦null: no independent source value⟧ Group 1 ⟦null: no independent source value⟧
2 0 – 00 0000H 0 – 45 002DH 1 – 00 0100H
3 0 – 01 0001H 0 – 46 002EH 1 – 01 0101H
4 0 – 02 0002H 0 – 47 002FH 1 – 02 0102H
5 0 – 03 0003H 0 – 48 0030H 1 – 03 0103H
6 0 – 04 0004H 0 – 49 0031H 1 – 04 0104H
7 0 – 05 0005H 0 – 50 0032H 1 – 05 0105H
8 0 – 06 0006H 0 – 51 0033H 1 – 06 0106H
9 0 – 07 0007H 0 – 52 0034H 1 – 07 0107H
10 0 – 08 0008H 0 – 53 0035H 1 – 08 0108H
11 0 – 09 0009H 0 – 54 0036H 1 – 09 0109H
12 0 – 10 000AH 0 – 55 0037H 1 – 10 010AH
13 0 – 11 000BH 0 – 56 0038H 1 – 11 010BH
14 0 – 12 000CH ⟦blank source cell⟧ ⟦blank source cell⟧ 1 – 12 010CH
15 0 – 13 000DH ⟦blank source cell⟧ ⟦blank source cell⟧ 1 – 13 010DH
16 0 – 14 000EH ⟦blank source cell⟧ ⟦blank source cell⟧ 1 – 14 010EH
17 0 – 15 000FH ⟦blank source cell⟧ ⟦blank source cell⟧ 1 – 15 010FH
18 0 – 16 0010H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
19 0 – 17 0011H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
20 0 – 18 0012H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
21 0 – 19 0013H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
22 0 – 20 0014H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 0 – 21 0015H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
24 0 – 22 0016H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
25 0 – 23 0017H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
26 0 – 24 0018H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
27 0 – 25 0019H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
28 0 – 26 001AH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
29 0 – 27 001BH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
30 0 – 28 001CH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
31 0 – 29 001DH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
32 0 – 30 001EH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
33 0 – 31 001FH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
34 0 – 32 0020H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
35 0 – 33 0021H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
36 0 – 34 0022H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
37 0 – 35 0023H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
38 0 – 36 0024H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
39 0 – 37 0025H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
40 0 – 38 0026H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
41 0 – 39 0027H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
42 0 – 40 0028H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
43 0 – 41 0029H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
44 0 – 42 002AH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
45 0 – 43 002BH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
46 0 – 44 002CH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Groups2 and3 register map — page 421

Group2left00–19→0200–0213 then33/34→0221/0222. 20–32notlisted; nofilledsequence. Group3middle00–32→0300–0320,right33–53→0321–0335.

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Group 2

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 00

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 01

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 02

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 03

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 04

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 05

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 06

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 07

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 08

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 09

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 10

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 11

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 12

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 13

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 14

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 15

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 16

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 17

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 18

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 19

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 33

Groups2 and3 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 2 – 34

Shared source cells (coordinates refer to this table):

Groups2 and3 register map table1 — PDF page 421

Source row Function Code Register No. Function Code Register No. Function Code Register No.
1 Group 2 ⟦null: no independent source value⟧ Group 3 ⟦null: no independent source value⟧ Group 3 ⟦null: no independent source value⟧
2 2 – 00 0200H 3 – 00 0300H 3 – 33 0321H
3 2 – 01 0201H 3 – 01 0301H 3 – 34 0322H
4 2 – 02 0202H 3 – 02 0302H 3 – 35 0323H
5 2 – 03 0203H 3 – 03 0303H 3 – 36 0324H
6 2 – 04 0204H 3 – 04 0304H 3 – 37 0325H
7 2 – 05 0205H 3 – 05 0305H 3 – 38 0326H
8 2 – 06 0206H 3 – 06 0306H 3 – 39 0327H
9 2 – 07 0207H 3 – 07 0307H 3 – 40 0328H
10 2 – 08 0208H 3 – 08 0308H 3 – 41 0329H
11 2 – 09 0209H 3 – 09 0309H 3 – 42 032AH
12 2 – 10 020AH 3 – 10 030AH 3 – 43 032BH
13 2 – 11 020BH 3 – 11 030BH 3 – 44 032CH
14 2 – 12 020CH 3 – 12 030CH 3 – 45 032DH
15 2 – 13 020DH 3 – 13 030DH 3 – 46 032EH
16 2 – 14 020EH 3 – 14 030EH 3 – 47 032FH
17 2 – 15 020FH 3 – 15 030FH 3 – 48 0330H
18 2 – 16 0210H 3 – 16 0310H 3 – 49 0331H
19 2 – 17 0211H 3 – 17 0311H 3 – 50 0332H
20 2 – 18 0212H 3 – 18 0312H 3 – 51 0333H
21 2 – 19 0213H 3 – 19 0313H 3 – 52 0334H
22 2 – 33 0221H 3 – 20 0314H 3 – 53 0335H
23 2 – 34 0222H 3 – 21 0315H ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 – 22 0316H ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 – 23 0317H ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 – 24 0318H ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 – 25 0319H ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 – 26 031AH ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 – 27 031BH ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 – 28 031CH ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 – 29 031DH ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 – 30 031EH ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 – 31 031FH ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 – 32 0320H ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
46 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Groups4 and5 register map — page 422

Group4left00–20→0400–0414;Group5middle00–32→0500–0520,right33–48→0521–0530. Hexregisters retained separatefromdecimal parameterindices.

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Group 4

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 00

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 01

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 02

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 03

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 04

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 05

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 06

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 07

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 08

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 09

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 10

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 11

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 12

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 13

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 14

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 15

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 16

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 17

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 18

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 19

Groups4 and5 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 4 – 20

Shared source cells (coordinates refer to this table):

Groups4 and5 register map table1 — PDF page 422

Source row Function Code Register No. Function Code Register No. Function Code Register No.
1 Group 4 ⟦null: no independent source value⟧ Group 5 ⟦null: no independent source value⟧ Group 5 ⟦null: no independent source value⟧
2 4 – 00 0400H 5 – 00 0500H 5 – 33 0521H
3 4 – 01 0401H 5 – 01 0501H 5 – 34 0522H
4 4 – 02 0402H 5 – 02 0502H 5 – 35 0523H
5 4 – 03 0403H 5 – 03 0503H 5 – 36 0524H
6 4 – 04 0404H 5 – 04 0504H 5 – 37 0525H
7 4 – 05 0405H 5 – 05 0505H 5 – 38 0526H
8 4 – 06 0406H 5 – 06 0506H 5 – 39 0527H
9 4 – 07 0407H 5 – 07 0507H 5 – 40 0528H
10 4 – 08 0408H 5 – 08 0508H 5 – 41 0529H
11 4 – 09 0409H 5 – 09 0509H 5 – 42 052AH
12 4 – 10 040AH 5 – 10 050AH 5 – 43 052BH
13 4 – 11 040BH 5 – 11 050BH 5 – 44 052CH
14 4 – 12 040CH 5 – 12 050CH 5 – 45 052DH
15 4 – 13 040DH 5 – 13 050DH 5 – 46 052EH
16 4 – 14 040EH 5 – 14 050EH 5 – 47 052FH
17 4 – 15 040FH 5 – 15 050FH 5 – 48 0530H
18 4 – 16 0410H 5 – 16 0510H ⟦blank source cell⟧ ⟦blank source cell⟧
19 4 – 17 0411H 5 – 17 0511H ⟦blank source cell⟧ ⟦blank source cell⟧
20 4 – 18 0412H 5 – 18 0512H ⟦blank source cell⟧ ⟦blank source cell⟧
21 4 – 19 0413H 5 – 19 0513H ⟦blank source cell⟧ ⟦blank source cell⟧
22 4 – 20 0414H 5 – 20 0514H ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 21 0515H ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 22 0516H ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 23 0517H ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 24 0518H ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 25 0519H ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 26 051AH ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 27 051BH ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 28 051CH ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 29 051DH ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 30 051EH ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 31 051FH ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 – 32 0520H ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Groups6 and7 register map — page 423

Group6left00–32→0600–0620,middle33–47→0621–062F;Group7right00–45→0700–072D. Preserve sourcecolumnorder andblanks.

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Group 6

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 00

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 01

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 02

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 03

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 04

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 05

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 06

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 07

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 08

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 09

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 10

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 11

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 12

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 13

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 14

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 15

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 16

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 17

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 18

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 19

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 20

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 21

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 22

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 23

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 24

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 25

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 26

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 27

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 28

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 29

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 30

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 31

Groups6 and7 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 6 – 32

Shared source cells (coordinates refer to this table):

Groups6 and7 register map table1 — PDF page 423

Source row Function Code Register No. Function Code Register No. Function Code Register No.
1 Group 6 ⟦null: no independent source value⟧ Group 6 ⟦null: no independent source value⟧ Group 7 ⟦null: no independent source value⟧
2 6 – 00 0600H 6 – 33 0621H 7 – 00 0700H
3 6 – 01 0601H 6 – 34 0622H 7 – 01 0701H
4 6 – 02 0602H 6 – 35 0623H 7 – 02 0702H
5 6 – 03 0603H 6 – 36 0624H 7 – 03 0703H
6 6 – 04 0604H 6 – 37 0625H 7 – 04 0704H
7 6 – 05 0605H 6 – 38 0626H 7 – 05 0705H
8 6 – 06 0606H 6 – 39 0627H 7 – 06 0706H
9 6 – 07 0607H 6 – 40 0628H 7 – 07 0707H
10 6 – 08 0608H 6 – 41 0629H 7 – 08 0708H
11 6 – 09 0609H 6 – 42 062AH 7 – 09 0709H
12 6 – 10 060AH 6 – 43 062BH 7 – 10 070AH
13 6 – 11 060BH 6 – 44 062CH 7 – 11 070BH
14 6 – 12 060CH 6 – 45 062DH 7 – 12 070CH
15 6 – 13 060DH 6 – 46 062EH 7 – 13 070DH
16 6 – 14 060EH 6 – 47 062FH 7 – 14 070EH
17 6 – 15 060FH ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 15 070FH
18 6 – 16 0610H ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 16 0710H
19 6 – 17 0611H ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 17 0711H
20 6 – 18 0612H ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 18 0712H
21 6 – 19 0613H ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 19 0713H
22 6 – 20 0614H ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 20 0714H
23 6 – 21 0615H ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 21 0715H
24 6 – 22 0616H ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 22 0716H
25 6 – 23 0617H ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 23 0717H
26 6 – 24 0618H ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 24 0718H
27 6 – 25 0619H ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 25 0719H
28 6 – 26 061AH ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 26 071AH
29 6 – 27 061BH ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 27 071BH
30 6 – 28 061CH ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 28 071CH
31 6 – 29 061DH ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 29 071DH
32 6 – 30 061EH ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 30 071EH
33 6 – 31 061FH ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 31 071FH
34 6 – 32 0620H ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 32 0720H
35 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 33 0721H
36 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 34 0722H
37 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 35 0723H
38 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 36 0724H
39 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 37 0725H
40 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 38 0726H
41 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 39 0727H
42 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 40 0728H
43 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 41 0729H
44 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 42 072AH
45 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 43 072BH
46 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 44 072CH
47 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 7 – 45 072DH

Manual — Groups8 through10 register map — page 424

Fourpairs:Group8left00–43→0800–082B,next44–60→082C–083C;Group9third00–10→0900–090A;Group10right00–43→0A00–0A2B continues425. Headergroup rowsretained.

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Group 8

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 00

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 01

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 02

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 03

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 04

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 05

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 06

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 07

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 08

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 09

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 10

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 11

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 12

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 13

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 14

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 15

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 16

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 17

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 18

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 19

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 20

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 21

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 22

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 23

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 24

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 25

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 26

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 27

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 28

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 29

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 30

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 31

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 32

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 33

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 34

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 35

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 36

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 37

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 38

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 39

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 40

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 41

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 42

Groups8 through10 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 8 – 43

Shared source cells (coordinates refer to this table):

Groups8 through10 register map table1 — PDF page 424

Source row Function Code Register No. Function Code Register No. Function Code Register No. Function Code Register No.
1 Group 8 ⟦null: no independent source value⟧ Group 8 ⟦null: no independent source value⟧ Group 9 ⟦null: no independent source value⟧ Group 10 ⟦null: no independent source value⟧
2 8 – 00 0800H 8 – 44 082CH 9 – 00 0900H 10 – 00 0A00H
3 8 – 01 0801H 8 – 45 082DH 9 – 01 0901H 10 – 01 0A01H
4 8 – 02 0802H 8 – 46 082EH 9 – 02 0902H 10 – 02 0A02H
5 8 – 03 0803H 8 – 47 082FH 9 – 03 0903H 10 – 03 0A03H
6 8 – 04 0804H 8 – 48 0830H 9 – 04 0904H 10 – 04 0A04H
7 8 – 05 0805H 8 – 49 0831H 9 – 05 0905H 10 – 05 0A05H
8 8 – 06 0806H 8 – 50 0832H 9 – 06 0906H 10 – 06 0A06H
9 8 – 07 0807H 8 – 51 0833H 9 – 07 0907H 10 – 07 0A07H
10 8 – 08 0808H 8 – 52 0834H 9 – 08 0908H 10 – 08 0A08H
11 8 – 09 0809H 8 – 53 0835H 9 – 09 0909H 10 – 09 0A09H
12 8 – 10 080AH 8 – 54 0836H 9 – 10 090AH 10 – 10 0A0AH
13 8 – 11 080BH 8 – 55 0837H ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 11 0A0BH
14 8 – 12 080CH 8 – 56 0838H ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 12 0A0CH
15 8 – 13 080DH 8 – 57 0839H ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 13 0A0DH
16 8 – 14 080EH 8 – 58 083AH ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 14 0A0EH
17 8 – 15 080FH 8 – 59 083BH ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 15 0A0FH
18 8 – 16 0810H 8 – 60 083CH ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 16 0A10H
19 8 – 17 0811H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 17 0A11H
20 8 – 18 0812H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 18 0A12H
21 8 – 19 0813H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 19 0A13H
22 8 – 20 0814H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 20 0A14H
23 8 – 21 0815H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 21 0A15H
24 8 – 22 0816H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 22 0A16H
25 8 – 23 0817H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 23 0A17H
26 8 – 24 0818H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 24 0A18H
27 8 – 25 0819H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 25 0A19H
28 8 – 26 081AH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 26 0A1AH
29 8 – 27 081BH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 27 0A1BH
30 8 – 28 081CH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 28 0A1CH
31 8 – 29 081DH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 29 0A1DH
32 8 – 30 081EH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 30 0A1EH
33 8 – 31 081FH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 31 0A1FH
34 8 – 32 0820H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 32 0A20H
35 8 – 33 0821H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 33 0A21H
36 8 – 34 0822H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 34 0A22H
37 8 – 35 0823H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 35 0A23H
38 8 – 36 0824H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 36 0A24H
39 8 – 37 0825H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 37 0A25H
40 8 – 38 0826H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 38 0A26H
41 8 – 39 0827H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 39 0A27H
42 8 – 40 0828H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 40 0A28H
43 8 – 41 0829H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 41 0A29H
44 8 – 42 082AH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 42 0A2AH
45 8 – 43 082BH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 10 – 43 0A2BH

Manual — Groups10 and11 register map — page 425

Group10left44–49→0A2C–0A31;Group11middle00–43→0B00–0B2B,right44–73→0B2C–0B49. Group10continuation explicit.

Groups10 and11 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Groups10 and11 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Group 10

Groups10 and11 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 10 – 44

Groups10 and11 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 10 – 45

Groups10 and11 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 10 – 46

Groups10 and11 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 10 – 47

Groups10 and11 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 10 – 48

Groups10 and11 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 10 – 49

Shared source cells (coordinates refer to this table):

Groups10 and11 register map table1 — PDF page 425

Source row Function Code Register No. Function Code Register No. Function Code Register No.
1 Group 10 ⟦null: no independent source value⟧ Group 11 ⟦null: no independent source value⟧ Group 11 ⟦null: no independent source value⟧
2 10 – 44 0A2CH 11 – 00 0B00H 11 – 44 0B2CH
3 10 – 45 0A2DH 11 – 01 0B01H 11 – 45 0B2DH
4 10 – 46 0A2EH 11 – 02 0B02H 11 – 46 0B2EH
5 10 – 47 0A2FH 11 – 03 0B03H 11 – 47 0B2FH
6 10 – 48 0A30H 11 – 04 0B04H 11 – 48 0B30H
7 10 – 49 0A31H 11 – 05 0B05H 11 – 49 0B31H
8 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 06 0B06H 11 – 50 0B32H
9 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 07 0B07H 11 – 51 0B33H
10 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 08 0B08H 11 – 52 0B34H
11 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 09 0B09H 11 – 53 0B35H
12 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 10 0B0AH 11 – 54 0B36H
13 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 11 0B0BH 11 – 55 0B37H
14 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 12 0B0CH 11 – 56 0B38H
15 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 13 0B0DH 11 – 57 0B39H
16 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 14 0B0EH 11 – 58 0B3AH
17 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 15 0B0FH 11 – 59 0B3BH
18 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 16 0B10H 11 – 60 0B3CH
19 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 17 0B11H 11 – 61 0B3DH
20 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 18 0B12H 11 – 62 0B3EH
21 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 19 0B13H 11 – 63 0B3FH
22 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 20 0B14H 11 – 64 0B40H
23 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 21 0B15H 11 – 65 0B41H
24 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 22 0B16H 11 – 66 0B42H
25 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 23 0B17H 11 – 67 0B43H
26 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 24 0B18H 11 – 68 0B44H
27 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 25 0B19H 11 – 69 0B45H
28 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 26 0B1AH 11 – 70 0B46H
29 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 27 0B1BH 11 – 71 0B47H
30 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 28 0B1CH 11 – 72 0B48H
31 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 29 0B1DH 11 – 73 0B49H
32 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 30 0B1EH ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 31 0B1FH ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 32 0B20H ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 33 0B21H ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 34 0B22H ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 35 0B23H ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 36 0B24H ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 37 0B25H ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 38 0B26H ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 39 0B27H ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 40 0B28H ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 41 0B29H ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 42 0B2AH ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧ 11 – 43 0B2BH ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Group12 register map — page 426

Left00–40→0C00–0C28;middle41–73→0C29–0C49 then repeats70–73→0C46–0C49 before74–80→0C4A–0C50;right81/82→0C51/0C52. Fourduplicatepairs are visiblyprinted andretained withtheir ownrow/cellprovenance. No filename orvalue deduplication.

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Group 12

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 00

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 01

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 02

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 03

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 04

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 05

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 06

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 07

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 08

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 09

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 10

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 11

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 12

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 13

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 14

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 15

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 16

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 17

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 18

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 19

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 20

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 21

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 22

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 23

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 24

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 25

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 26

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 27

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 28

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 29

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 30

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 31

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 32

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 33

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 34

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 35

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12– 36

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 37

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 38

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 39

Group12 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 12 – 40

Shared source cells (coordinates refer to this table):

Group12 register map table1 — PDF page 426

Source row Function Code Register No. Function Code Register No. Function Code Register No.
1 Group 12 ⟦null: no independent source value⟧ Group 12 ⟦null: no independent source value⟧ Group 12 ⟦null: no independent source value⟧
2 12 – 00 0C00H 12 – 41 0C29H 12 – 81 0C51H
3 12 – 01 0C01H 12 – 42 0C2AH 12 – 82 0C52H
4 12 – 02 0C02H 12 – 43 0C2BH ⟦blank source cell⟧ ⟦blank source cell⟧
5 12 – 03 0C03H 12 – 44 0C2CH ⟦blank source cell⟧ ⟦blank source cell⟧
6 12 – 04 0C04H 12 – 45 0C2DH ⟦blank source cell⟧ ⟦blank source cell⟧
7 12 – 05 0C05H 12 – 46 0C2EH ⟦blank source cell⟧ ⟦blank source cell⟧
8 12 – 06 0C06H 12 – 47 0C2FH ⟦blank source cell⟧ ⟦blank source cell⟧
9 12 – 07 0C07H 12 – 48 0C30H ⟦blank source cell⟧ ⟦blank source cell⟧
10 12 – 08 0C08H 12 – 49 0C31H ⟦blank source cell⟧ ⟦blank source cell⟧
11 12 – 09 0C09H 12 – 50 0C32H ⟦blank source cell⟧ ⟦blank source cell⟧
12 12 – 10 0C0AH 12 – 51 0C33H ⟦blank source cell⟧ ⟦blank source cell⟧
13 12 – 11 0C0BH 12 – 52 0C34H ⟦blank source cell⟧ ⟦blank source cell⟧
14 12 – 12 0C0CH 12 – 53 0C35H ⟦blank source cell⟧ ⟦blank source cell⟧
15 12 – 13 0C0DH 12 – 54 0C36H ⟦blank source cell⟧ ⟦blank source cell⟧
16 12 – 14 0C0EH 12 – 55 0C37H ⟦blank source cell⟧ ⟦blank source cell⟧
17 12 – 15 0C0FH 12 – 56 0C38H ⟦blank source cell⟧ ⟦blank source cell⟧
18 12 – 16 0C10H 12 – 57 0C39H ⟦blank source cell⟧ ⟦blank source cell⟧
19 12 – 17 0C11H 12 – 58 0C3AH ⟦blank source cell⟧ ⟦blank source cell⟧
20 12 – 18 0C12H 12 – 59 0C3BH ⟦blank source cell⟧ ⟦blank source cell⟧
21 12 – 19 0C13H 12 – 60 0C3CH ⟦blank source cell⟧ ⟦blank source cell⟧
22 12 – 20 0C14H 12 – 61 0C3DH ⟦blank source cell⟧ ⟦blank source cell⟧
23 12 – 21 0C15H 12 – 62 0C3EH ⟦blank source cell⟧ ⟦blank source cell⟧
24 12 – 22 0C16H 12 – 63 0C3FH ⟦blank source cell⟧ ⟦blank source cell⟧
25 12 – 23 0C17H 12 – 64 0C40H ⟦blank source cell⟧ ⟦blank source cell⟧
26 12 – 24 0C18H 12 – 65 0C41H ⟦blank source cell⟧ ⟦blank source cell⟧
27 12 – 25 0C19H 12 – 66 0C42H ⟦blank source cell⟧ ⟦blank source cell⟧
28 12 – 26 0C1AH 12 – 67 0C43H ⟦blank source cell⟧ ⟦blank source cell⟧
29 12 – 27 0C1BH 12 – 68 0C44H ⟦blank source cell⟧ ⟦blank source cell⟧
30 12 – 28 0C1CH 12 – 69 0C45H ⟦blank source cell⟧ ⟦blank source cell⟧
31 12 – 29 0C1DH 12 – 70 0C46H ⟦blank source cell⟧ ⟦blank source cell⟧
32 12 – 30 0C1EH 12 – 71 0C47H ⟦blank source cell⟧ ⟦blank source cell⟧
33 12 – 31 0C1FH 12 – 72 0C48H ⟦blank source cell⟧ ⟦blank source cell⟧
34 12 – 32 0C20H 12 – 73 0C49H ⟦blank source cell⟧ ⟦blank source cell⟧
35 12 – 33 0C21H 12 – 70 0C46H ⟦blank source cell⟧ ⟦blank source cell⟧
36 12 – 34 0C22H 12 – 71 0C47H ⟦blank source cell⟧ ⟦blank source cell⟧
37 12 – 35 0C23H 12 – 72 0C48H ⟦blank source cell⟧ ⟦blank source cell⟧
38 12– 36 0C24H 12 – 73 0C49H ⟦blank source cell⟧ ⟦blank source cell⟧
39 12 – 37 0C25H 12 – 74 0C4AH ⟦blank source cell⟧ ⟦blank source cell⟧
40 12 – 38 0C26H 12 – 75 0C4BH ⟦blank source cell⟧ ⟦blank source cell⟧
41 12 – 39 0C27H 12 – 76 0C4CH ⟦blank source cell⟧ ⟦blank source cell⟧
42 12 – 40 0C28H 12 – 77 0C4DH ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧ 12 – 78 0C4EH ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧ 12 – 79 0C4FH ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧ 12 – 80 0C50H ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Group13 register map — page 427

00–13→0D00–0D0D;14also0D0D,15→0D0E through47→0D2E;middle48→0D2F,49→0D30,50→0D31. 14–50areonebelow index-basedpattern and13/14shareaddress. Values retainedexactly; pattern diagnosticdoesnot authorize correction or infer firmwarebehavior.

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Group 13

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 00

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 01

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 02

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 03

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 04

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 05

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 06

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 07

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 08

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 09

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 10

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 11

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 12

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 13

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 14

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 15

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 16

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 17

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 18

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 19

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 20

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 21

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 22

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 23

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 24

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 25

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 26

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 27

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 28

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 29

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 30

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 31

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 32

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 33

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 34

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 35

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 36

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 37

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 38

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 39

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 40

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 41

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 42

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 43

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 44

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 45

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 46

Group13 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 13 – 47

Shared source cells (coordinates refer to this table):

Group13 register map table1 — PDF page 427

Source row Function Code Register No. Function Code Register No. Function Code Register No.
1 Group 13 ⟦null: no independent source value⟧ Group 13 ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧
2 13 – 00 0D00H 13 – 48 0D2FH ⟦blank source cell⟧ ⟦blank source cell⟧
3 13 – 01 0D01H 13 – 49 0D30H ⟦blank source cell⟧ ⟦blank source cell⟧
4 13 – 02 0D02H 13 – 50 0D31H ⟦blank source cell⟧ ⟦blank source cell⟧
5 13 – 03 0D03H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
6 13 – 04 0D04H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
7 13 – 05 0D05H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
8 13 – 06 0D06H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
9 13 – 07 0D07H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
10 13 – 08 0D08H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
11 13 – 09 0D09H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
12 13 – 10 0D0AH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
13 13 – 11 0D0BH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
14 13 – 12 0D0CH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
15 13 – 13 0D0DH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
16 13 – 14 0D0DH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
17 13 – 15 0D0EH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
18 13 – 16 0D0FH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
19 13 – 17 0D10H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
20 13 – 18 0D11H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
21 13 – 19 0D12H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
22 13 – 20 0D13H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 13 – 21 0D14H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
24 13 – 22 0D15H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
25 13 – 23 0D16H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
26 13 – 24 0D17H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
27 13 – 25 0D18H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
28 13 – 26 0D19H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
29 13 – 27 0D1AH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
30 13 – 28 0D1BH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
31 13 – 29 0D1CH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
32 13 – 30 0D1DH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
33 13 – 31 0D1EH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
34 13 – 32 0D1FH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
35 13 – 33 0D20H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
36 13 – 34 0D21H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
37 13 – 35 0D22H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
38 13 – 36 0D23H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
39 13 – 37 0D24H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
40 13 – 38 0D25H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
41 13 – 39 0D26H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
42 13 – 40 0D27H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
43 13 – 41 0D28H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
44 13 – 42 0D29H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
45 13 – 43 0D2AH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
46 13 – 44 0D2BH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
47 13 – 45 0D2CH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
48 13 – 46 0D2DH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
49 13 – 47 0D2EH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Groups14 through16 register map — page 428

Group14left00–47→0E00–0E2F;Group15middle00–32→0F00–0F20;Group16right00–37→1000–1025.

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Group 14

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 00

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 01

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 02

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 03

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 04

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 05

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 06

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 07

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 08

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 09

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 10

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 11

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 12

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 13

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 14

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 15

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 16

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 17

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 18

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 19

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 20

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 21

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 22

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 23

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 24

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 25

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 26

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 27

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 28

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 29

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 30

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 31

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 32

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 33

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 34

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 35

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 36

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 37

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 38

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 39

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 40

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 41

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 42

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 43

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 44

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 45

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 46

Groups14 through16 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 14 – 47

Shared source cells (coordinates refer to this table):

Groups14 through16 register map table1 — PDF page 428

Source row Function Code Register No. Function Code Register No. Function Code Register No.
1 Group 14 ⟦null: no independent source value⟧ Group 15 ⟦null: no independent source value⟧ Group 16 ⟦null: no independent source value⟧
2 14 – 00 0E00H 15 – 00 0F00H 16 – 00 1000H
3 14 – 01 0E01H 15 – 01 0F01H 16 – 01 1001H
4 14 – 02 0E02H 15 – 02 0F02H 16 – 02 1002H
5 14 – 03 0E03H 15 – 03 0F03H 16 – 03 1003H
6 14 – 04 0E04H 15 – 04 0F04H 16 – 04 1004H
7 14 – 05 0E05H 15 – 05 0F05H 16 – 05 1005H
8 14 – 06 0E06H 15 – 06 0F06H 16 – 06 1006H
9 14 – 07 0E07H 15 – 07 0F07H 16 – 07 1007H
10 14 – 08 0E08H 15 – 08 0F08H 16 – 08 1008H
11 14 – 09 0E09H 15 – 09 0F09H 16 – 09 1009H
12 14 – 10 0E0AH 15 – 10 0F0AH 16 – 10 100AH
13 14 – 11 0E0BH 15 – 11 0F0BH 16 – 11 100BH
14 14 – 12 0E0CH 15 – 12 0F0CH 16 – 12 100CH
15 14 – 13 0E0DH 15 – 13 0F0DH 16 – 13 100DH
16 14 – 14 0E0EH 15 – 14 0F0EH 16 – 14 100EH
17 14 – 15 0E0FH 15 – 15 0F0FH 16 – 15 100FH
18 14 – 16 0E10H 15 – 16 0F10H 16 – 16 1010H
19 14 – 17 0E11H 15 – 17 0F11H 16 – 17 1011H
20 14 – 18 0E12H 15 – 18 0F12H 16 – 18 1012H
21 14 – 19 0E13H 15 – 19 0F13H 16 – 19 1013H
22 14 – 20 0E14H 15 – 20 0F14H 16 – 20 1014H
23 14 – 21 0E15H 15 – 21 0F15H 16 – 21 1015H
24 14 – 22 0E16H 15 – 22 0F16H 16 – 22 1016H
25 14 – 23 0E17H 15 – 23 0F17H 16 – 23 1017H
26 14 – 24 0E18H 15 – 24 0F18H 16 – 24 1018H
27 14 – 25 0E19H 15 – 25 0F19H 16 – 25 1019H
28 14 – 26 0E1AH 15 – 26 0F1AH 16 – 26 101AH
29 14 – 27 0E1BH 15 – 27 0F1BH 16 – 27 101BH
30 14 – 28 0E1CH 15 – 28 0F1CH 16 – 28 101CH
31 14 – 29 0E1DH 15 – 29 0F1DH 16 – 29 101DH
32 14 – 30 0E1EH 15 – 30 0F1EH 16 – 30 101EH
33 14 – 31 0E1FH 15 – 31 0F1FH 16 – 31 101FH
34 14 – 32 0E20H 15 – 32 0F20H 16 – 32 1020H
35 14 – 33 0E21H ⟦blank source cell⟧ ⟦blank source cell⟧ 16 – 33 1021H
36 14 – 34 0E22H ⟦blank source cell⟧ ⟦blank source cell⟧ 16 – 34 1022H
37 14 – 35 0E23H ⟦blank source cell⟧ ⟦blank source cell⟧ 16 – 35 1023H
38 14 – 36 0E24H ⟦blank source cell⟧ ⟦blank source cell⟧ 16 – 36 1024H
39 14 – 37 0E25H ⟦blank source cell⟧ ⟦blank source cell⟧ 16 – 37 1025H
40 14 – 38 0E26H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
41 14 – 39 0E27H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
42 14 – 40 0E28H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
43 14 – 41 0E29H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
44 14 – 42 0E2AH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
45 14 – 43 0E2BH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
46 14 – 44 0E2CH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
47 14 – 45 0E2DH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
48 14 – 46 0E2EH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
49 14 – 47 0E2FH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Groups17 and18 register map — page 429

Group17left00–14→1100–110E;Group18middle00–06→1200–1206. Rightpairblank. No Group19 mapping isprinted between thispage and430.

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Group 17

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 00

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 01

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 02

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 03

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 04

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 05

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 06

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 07

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 08

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 09

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 10

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 11

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 12

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 13

Groups17 and18 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 17 – 14

Shared source cells (coordinates refer to this table):

Groups17 and18 register map table1 — PDF page 429

Source row Function Code Register No. Function Code Register No. Function Code Register No.
1 Group 17 ⟦null: no independent source value⟧ Group 18 ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧
2 17 – 00 1100H 18 – 00 1200H ⟦blank source cell⟧ ⟦blank source cell⟧
3 17 – 01 1101H 18 – 01 1201H ⟦blank source cell⟧ ⟦blank source cell⟧
4 17 – 02 1102H 18 – 02 1202H ⟦blank source cell⟧ ⟦blank source cell⟧
5 17 – 03 1103H 18 – 03 1203H ⟦blank source cell⟧ ⟦blank source cell⟧
6 17 – 04 1104H 18 – 04 1204H ⟦blank source cell⟧ ⟦blank source cell⟧
7 17 – 05 1105H 18 – 05 1205H ⟦blank source cell⟧ ⟦blank source cell⟧
8 17 – 06 1106H 18 – 06 1206H ⟦blank source cell⟧ ⟦blank source cell⟧
9 17 – 07 1107H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
10 17 – 08 1108H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
11 17 – 09 1109H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
12 17 – 10 110AH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
13 17 – 11 110BH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
14 17 – 12 110CH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
15 17 – 13 110DH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
16 17 – 14 110EH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Groups20 through22 register map — page 430

Group20left00–18→1400–1412 then33–35→1421–1423;19–32notlisted. Group21middle00–08→1500–1508. Group22right00–35→1600–1623;32–35blueprinted. Colorretainedascontext,notinferredrevisionorcompatibility.

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Group 20

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 00

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 01

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 02

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 03

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 04

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 05

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 06

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 07

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 08

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 09

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 10

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 11

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 12

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 13

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 14

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 15

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 16

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 17

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 18

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 33

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 34

Groups20 through22 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 20 – 35

Shared source cells (coordinates refer to this table):

Groups20 through22 register map table1 — PDF page 430

Source row Function Code Register No. Function Code Register No. Function Code Register No.
1 Group 20 ⟦null: no independent source value⟧ Group 21 ⟦null: no independent source value⟧ Group 22 ⟦null: no independent source value⟧
2 20 – 00 1400H 21 – 00 1500H 22 – 00 1600H
3 20 – 01 1401H 21 – 01 1501H 22 – 01 1601H
4 20 – 02 1402H 21 – 02 1502H 22 – 02 1602H
5 20 – 03 1403H 21 – 03 1503H 22 – 03 1603H
6 20 – 04 1404H 21 – 04 1504H 22 – 04 1604H
7 20 – 05 1405H 21 – 05 1505H 22 – 05 1605H
8 20 – 06 1406H 21 – 06 1506H 22 – 06 1606H
9 20 – 07 1407H 21 – 07 1507H 22 – 07 1607H
10 20 – 08 1408H 21 – 08 1508H 22 – 08 1608H
11 20 – 09 1409H ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 09 1609H
12 20 – 10 140AH ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 10 160AH
13 20 – 11 140BH ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 11 160BH
14 20 – 12 140CH ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 12 160CH
15 20 – 13 140DH ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 13 160DH
16 20 – 14 140EH ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 14 160EH
17 20 – 15 140FH ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 15 160FH
18 20 – 16 1410H ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 16 1610H
19 20 – 17 1411H ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 17 1611H
20 20 – 18 1412H ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 18 1612H
21 20 – 33 1421H ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 19 1613H
22 20 – 34 1422H ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 20 1614H
23 20 – 35 1423H ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 21 1615H
24 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 22 1616H
25 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 23 1617H
26 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 24 1618H
27 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 25 1619H
28 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 26 161AH
29 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 27 161BH
30 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 28 161CH
31 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 29 161DH
32 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 30 161EH
33 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 31 161FH
34 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 32 1620H
35 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 33 1621H
36 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 34 1622H
37 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 22 – 35 1623H

Manual — Groups23 and24 register map — page 431

Group23left00–46→1700–172E,middle47–78→172F–174E. Group24right00–17→1800–1811. Group19notinvented; parameterinventoryand firmware mayrequire supplierclarification.

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Group 23

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 00

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 01

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 02

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 03

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 04

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 05

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 06

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 07

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 08

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 09

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 10

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 11

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 12

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 13

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 14

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 15

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 16

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 17

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 18

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 19

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 20

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 21

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 22

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 23

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 24

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 25

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 26

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 27

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 28

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 29

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 30

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 31

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 32

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 33

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 34

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 35

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 36

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 37

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 38

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 39

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 40

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 41

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 42

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 43

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 44

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 45

Groups23 and24 register map. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: 23 – 46

Shared source cells (coordinates refer to this table):

Groups23 and24 register map table1 — PDF page 431

Source row Function Code Register No. Function Code Register No. Function Code Register No.
1 Group 23 ⟦null: no independent source value⟧ Group 23 ⟦null: no independent source value⟧ Group 24 ⟦null: no independent source value⟧
2 23 – 00 1700H 23 – 47 172FH 24 – 00 1800H
3 23 – 01 1701H 23 – 48 1730H 24 – 01 1801H
4 23 – 02 1702H 23 – 49 1731H 24 – 02 1802H
5 23 – 03 1703H 23 – 50 1732H 24 – 03 1803H
6 23 – 04 1704H 23 – 51 1733H 24 – 04 1804H
7 23 – 05 1705H 23 – 52 1734H 24 – 05 1805H
8 23 – 06 1706H 23 – 53 1735H 24 – 06 1806H
9 23 – 07 1707H 23 – 54 1736H 24 – 07 1807H
10 23 – 08 1708H 23 – 55 1737H 24 – 08 1808H
11 23 – 09 1709H 23 – 56 1738H 24 – 09 1809H
12 23 – 10 170AH 23 – 57 1739H 24 – 10 180AH
13 23 – 11 170BH 23 – 58 173AH 24 – 11 180BH
14 23 – 12 170CH 23 – 59 173BH 24 – 12 180CH
15 23 – 13 170DH 23 – 60 173CH 24 – 13 180DH
16 23 – 14 170EH 23 – 61 173DH 24 – 14 180EH
17 23 – 15 170FH 23 – 62 173EH 24 – 15 180FH
18 23 – 16 1710H 23 – 63 173FH 24 – 16 1810H
19 23 – 17 1711H 23 – 64 1740H 24 – 17 1811H
20 23 – 18 1712H 23 – 65 1741H ⟦blank source cell⟧ ⟦blank source cell⟧
21 23 – 19 1713H 23 – 66 1742H ⟦blank source cell⟧ ⟦blank source cell⟧
22 23 – 20 1714H 23 – 67 1743H ⟦blank source cell⟧ ⟦blank source cell⟧
23 23 – 21 1715H 23 – 68 1744H ⟦blank source cell⟧ ⟦blank source cell⟧
24 23 – 22 1716H 23 – 69 1745H ⟦blank source cell⟧ ⟦blank source cell⟧
25 23 – 23 1717H 23 – 70 1746H ⟦blank source cell⟧ ⟦blank source cell⟧
26 23 – 24 1718H 23 – 71 1747H ⟦blank source cell⟧ ⟦blank source cell⟧
27 23 – 25 1719H 23 – 72 1748H ⟦blank source cell⟧ ⟦blank source cell⟧
28 23 – 26 171AH 23 – 73 1749H ⟦blank source cell⟧ ⟦blank source cell⟧
29 23 – 27 171BH 23 – 74 174AH ⟦blank source cell⟧ ⟦blank source cell⟧
30 23 – 28 171CH 23 – 75 174BH ⟦blank source cell⟧ ⟦blank source cell⟧
31 23 – 29 171DH 23 – 76 174CH ⟦blank source cell⟧ ⟦blank source cell⟧
32 23 – 30 171EH 23 – 77 174DH ⟦blank source cell⟧ ⟦blank source cell⟧
33 23 – 31 171FH 23 – 78 174EH ⟦blank source cell⟧ ⟦blank source cell⟧
34 23 – 32 1720H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
35 23 – 33 1721H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
36 23 – 34 1722H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
37 23 – 35 1723H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
38 23 – 36 1724H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
39 23 – 37 1725H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
40 23 – 38 1726H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
41 23 – 39 1727H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
42 23 – 40 1728H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
43 23 – 41 1729H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
44 23 – 42 172AH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
45 23 – 43 172BH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
46 23 – 44 172CH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
47 23 – 45 172DH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
48 23 – 46 172EH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — BACnet layers and services — page 432

4.7 BACnet Protocol Descriptions

BACnet is in compliance with four-layer of seven-layer structure models in OSI (Open Systems

Interconnection) of International Standard Organization (ISO). These four-layer structure models

are application layer, network layer, data link layer and physical layer. Besides, BACnet is definced

by the view of standard “object” and “property.” All BACnet devices are controlled via the property of

objects. Every controller with BACnet devices is considered an object collector so that every

controller device can execute different kinds of functions of objects to achieve the communication

control and monitor control.

4.7.1 BACnet Services

Services provide some commands to save or control information and some functions to achieve

the purpose of monitoring and control. Namely, one BACnet device reveive certain information or

command to complete specific work from other BACnet device so the two devices need to support

the same service to complete communication. To complete the exchange of these service

messages, these communication requirements are specified in the communication protocol of

application layer by BACnet. Thus, services are parts of the communication protocol data unit

(PDU) in the application layer and build the communication modes via the relationship of Server –

Client. Client will send the message of sevice requirements to Server and Server needs to respond

to Client to execute this service. Refer to the following fugure.

Application

Layer

Network Layer

Data Link Layer

Physical Layer

Application Layer of BACnet

Network Layer of BACnet

ISO- 8802-2

(IEEE802.2)

ISO- 8802-3

(IEEE802.3)

ARCNET

MS/TP

PTP

EIA-485

EIA-232

LonkTalk

OSI Corresponding Model

BACnet Simple Model

R e q u e s t fo r P D U

R e s p o n d to P D U

R e c e iv e

S e n d

R e q u e s t

R e s p o n d

C lie n t

S e r v e r

Source saysfourOSI layersapplication/network/datalink/physical. DiagramISO8802-2 IEEE802.2 spansEthernetISO8802-3 IEEE802.3 andARCNET;MS/TP aboveEIA485,PTPaboveEIA232;printedLonkTalk spanslowerlayers. ClientSend→RequestforPDU→ServerReceive,thenServerSend→RespondtoPDU→ClientReceive. Bothdevicesneed supportsame service. Sourceclaims only; no BACnetcertificationinferred.

Manual — BACnet protocol stack — page 433

All BACnet devices have the application programs to manage the requirements of device motion

and executing services. Take work station for example, the application program needs to keep the

display value of every input so it requires sending the service request to the object of other device

to update the display value of input. The application program of the device needs to respond to the

service requiremtents. Refer to the following fugure.

4.7.2 BACnet Protocol Structure

BACnet is the communication protocol by way of protocol stack so the pocket is composed of

stacked layer types. Refer to the following figure.

When application program sends the BACnet service request for the pocket, it requires requesting

for executing BACnet request program in the application layer via application program interface.

The requirements of the program are sent to the application layer and application protocol data unit

(APDU) consists of Application Protocol Control Information (APCI) and Servie Data of application

program. Then APDU passes its messages downward to BACnet request program in the network

layer. APDU becomes Network Layer Protocol Data Unit (NPDU) composed of Network Service

Data Unit (NSDU) and Network Protocol Control Information (NPCI). And so forth for the data link

layer and physical layer to complete the full service for the packet.

BACnet Service Request

Application Program

Application Layer

Network Layer

Data Link Layer

Physical Layer

A-BACnet.Request

N-UNITDATA.Request

DL-UNITDATA.Request

MA-UNITDATA.Request

P-UNITDATA.Request

APCI

Service Data

APDU

NSDU

NPCI

NPDU

LSDU

LPDU

LPCI

MSDU

MPCI

PSDU

PPCI

MPDU

PPDU

Application

Program

Object

BACnet Device

Request for

Service

Respond to

Network

Service request

Read property

Service Reply?

Diagramobjectsconnectapplicationprogram;incomingService requestReadproperty, outgoingServiceReply? retainsquestionmark. StackA-BACnet.Request;APCI+ServiceData=APDU;N-UNITDATA.Request,NPCI+NSDU=NPDU;DL-UNITDATA.Request,LPCI+LSDU=LPDU;MA-UNITDATA.Request,MPCI+MSDU=MPDU;P-UNITDATA.Request,PPCI+PSDU=PPDU. Preserve labelsandarrowassociations; sourceprosepocketspelling retained,notinventedprotocolcapability.

Manual — BACnet object support — page 434

4.7.3 BACnet Specifications

Inverter F510 model is built-in standard BACnet MS/TP communication protocol structure to meet

the demand of automatic communication equipment. Control or monitor F510 via BACnet to be

allowable to read and modify specific parameter. F510 includes the following supports of standard

objects:

■ Inverter Objects

■ Analog Input

■ Analog Output

■ Analog Value

■ Digital Input

■ Digital Output

■ Digital Value

Refer to Table 4.7.3.1 for F510 supporting the property information of object classification. User can

collect related properties of objects required via the dedicated communication software of BACnet

to give control or monitor command for each object.

Table 4.7.3.1 Object and property supporting list

Sourcebuilt-inMS/TPclaim. ColumnsDEV,AI,AO,AV,BI,BO,BV. Identifier/Name/Type Vforall7. DEV-onlysystem/vendor/model/firmware/protocol/objectlist/APDU/segmentation/timeouts/retries/masters/frames/addressbinding. PrintedApplocation_Software_Supported retained. PresentValue/StatusFlags/EventState VforallsixnonDEV;OutOfServiceVforAI/AO/AV/BO only;UnitsAI/AO/AV;PriorityArray/RelinquishDefaultAO/BO;PolarityBI/BO/BV. Location,Reliability,InactiveText,ActiveTextrowsblank. Blankretainedasunmarked,notgeneralunsupportedclaim. BACnetcontinues435outsidepacket.

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval.

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Object_Identifier

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Object_Name

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Object_Type

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: System_Status

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Vendor_Name

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Vendor_ Identifier

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Model_Name

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Firmware_Revision

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Applocation_Software_Supported

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Protocol_Version

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Protocol_Revision

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Protocol_Services_Supported

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Protocol_Object_Type_Supported

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Object_List

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Max_APDU_Length_Accepted

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Segmentation_Supported

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: APDU_Timeout

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Number_Of_APDU_Retries

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Max_Masters

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Max_Info_Frames

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Device_Address_Binding

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Location

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Presnent_Value

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Status_Flags

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Event_State

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Relibility

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Out_Of_Service

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Units

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Priority_Array

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Relinquish_Default

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Polarity

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Inactive_Text

BACnet object support. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain physicalcolumnpairs,registercontext,units,blankstates andsourceconflicts;noengineeringapproval. Row group: Active_Text

BACnet object support table1 — PDF page 434

Source row Proerty Inverter (DEV) Analog Input (AI) Analog Output (AO) Analog Value (AV) Digital Input (BI) Digital Output (BO) Digital Value (BV)
1 Object_Identifier V V V V V V V
2 Object_Name V V V V V V V
3 Object_Type V V V V V V V
4 System_Status V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
5 Vendor_Name V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
6 Vendor_ Identifier V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
7 Model_Name V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
8 Firmware_Revision V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
9 Applocation_Software_Supported V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
10 Protocol_Version V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
11 Protocol_Revision V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
12 Protocol_Services_Supported V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
13 Protocol_Object_Type_Supported V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
14 Object_List V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
15 Max_APDU_Length_Accepted V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
16 Segmentation_Supported V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
17 APDU_Timeout V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
18 Number_Of_APDU_Retries V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
19 Max_Masters V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
20 Max_Info_Frames V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
21 Device_Address_Binding V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
22 Location ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 Presnent_Value ⟦blank source cell⟧ V V V V V V
24 Status_Flags ⟦blank source cell⟧ V V V V V V
25 Event_State ⟦blank source cell⟧ V V V V V V
26 Relibility ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
27 Out_Of_Service ⟦blank source cell⟧ V V V ⟦blank source cell⟧ V ⟦blank source cell⟧
28 Units ⟦blank source cell⟧ V V V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
29 Priority_Array ⟦blank source cell⟧ ⟦blank source cell⟧ V ⟦blank source cell⟧ ⟦blank source cell⟧ V ⟦blank source cell⟧
30 Relinquish_Default ⟦blank source cell⟧ ⟦blank source cell⟧ V ⟦blank source cell⟧ ⟦blank source cell⟧ V ⟦blank source cell⟧
31 Polarity ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ V V V
32 Inactive_Text ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
33 Active_Text ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — BACnet inverter and analog input properties — page 435

4.7.4 BACnet Object Properties

This section provides the predetermined configuration of the inverter. User can achieve the

optimizazed situation at any necessary modification.

Refer to Table 4.7.4.1 for the property information of inverter objects and user can learn the inverter

messages from the inverter objects.

Refer to Table 4.7.4.2 ~ Table 4.7.4.7 for the related object information that inverter supports. User can

control/ read each object with the application requirements.

Table 4.7.4.1 – Inverter property list

Table 4.7.4.2 Analog input property list (READ)

Inverter property list: DEV; name/vendor/model VFD; type8; status0; vendor461; firmware and printed Applocation_Software_Supported both0.14; protocol1/revision5; services readProperty,writeProperty,who is; seven object types; masters127,infoframes1. These are this manual edition claims,not current firmware verification. AI0–15 are READ: AI0/1 analog input0–10Volt; AI2 error0–45; AI3/4 frequency0–60Hz; AI5 current blankrange; AI6 mode0–2; AI7–10 motor voltage/power/rpm/Hz blankranges. AI11 carrier4–16KiloHertz; AI12station1–254; AI13baud0–3; AI14BacnetSel0–1; AI15instance1–254. AI0 description AI1 inpur preserved. No blank limits filled.

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Object_Identifier

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Object_Name

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Object_Type

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: System_Status

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Vendor_Name

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Vendor_ Identifier

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Model_Name

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Firmware_Revision

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Applocation_Software_Supported

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Protocol_Version

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Protocol_Revision

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Protocol_Services_Supported

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Protocol_Object_Type_Supported

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Max_Masters

BACnet inverter DEV property list4.7.4.1. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Max_Info_Frames

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI0

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI1

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI2

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI3

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI4

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI5

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI6

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI7

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI8

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI9

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI10

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI11

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI12

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI13

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI14

BACnet AI0–15 read property list4.7.4.2. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI15

BACnet inverter and analog input properties table1 — PDF page 435

Source row Property Inverter
1 Object_Identifier DEV
2 Object_Name VFD
3 Object_Type 8
4 System_Status 0
5 Vendor_Name VFD
6 Vendor_ Identifier 461
7 Model_Name VFD
8 Firmware_Revision 0.14
9 Applocation_Software_Supported 0.14
10 Protocol_Version 1
11 Protocol_Revision 5
12 Protocol_Services_Supported { readProperty , writeProperty , who is }
13 Protocol_Object_Type_Supported { Analog_Input , Analog_Output, Analog_Value Binary_ Input, Binary_Output, Binary_Value, Device}
14 Max_Masters 127
15 Max_Info_Frames 1

BACnet inverter and analog input properties table2 — PDF page 435

Source row No. Object Name Description Unit Classification Range
1 AI0 TM2 AIN AI1 inpur Volt R 0 - 10
2 AI1 TM2 AIN2 AI2 input Volt R 0 - 10
3 AI2 Error code Recent fault message No Units R 0 – 45
4 AI3 Freq cmd Frequency command HZ R 0 - 60
5 AI4 Frequency Output frequency HZ R 0 - 60
6 AI5 Current Output current Amps R ⟦blank source cell⟧
7 AI6 Control Mode Control mode No Units R 0 - 2
8 AI7 Motor R-Volt Motor rated voltage Volt R ⟦blank source cell⟧
9 AI8 Motor R-HP Motor rated power horsepower R ⟦blank source cell⟧
10 AI9 Motor R-RPM Motor rated rotation speed No Units R ⟦blank source cell⟧
11 AI10 Motor R-Hz Motor rated frequency HZ R ⟦blank source cell⟧
12 AI11 CarrierFreq Carrier frequency KiloHertz R 4 - 16
13 AI12 Comm Station INV communication station No Units R 1 - 254
14 AI13 BaudRate Baudrate setting No Units R 0 - 3
15 AI14 BacnetSel Communication mode selection No Units R 0 - 1
16 AI15 DevInstance Inverter number No Units R 1 - 254

Manual — BACnet analog output properties — page 436

Table 4.7.4.3 – Analog output property list (READ/ WRITE)

AO0–24 followed by AO25–30 on437. AO0 frequency0–60Hz R/W; AO1/2 analog voltage0–10Volt R; AO3 motorcurrent0–65535Amps R/W; AO4 powerloss selection0–1 R; AO5 restart attempts0–10 R; AO6 restartdelay0–7200seconds R. AO7–21 speedstages0–14 each0–400Hz R/W. AO22 stage15 prints No Units/0–2,unlike priorstages. AO23 runsource0–2; AO24 directionlock0–1 R/W. READ/WRITE tableheading doesnot override each rowclassification.

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO0

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO1

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO2

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO3

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO4

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO5

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO6

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO7

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO8

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO9

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO10

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO11

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO12

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO13

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO14

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO15

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO16

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO17

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO18

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO19

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO20

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO21

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO22

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO23

BACnet AO0–24 list4.7.4.3;continues437. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO24

BACnet analog output properties table1 — PDF page 436

Source row No. Object Name Description Unit Classification Range
1 AO0 Set frequency Frequency command HZ R/W 0 - 60
2 AO1 TB2 AO1 Analog output voltage 1 Volt R 0 - 10
3 AO2 TB2 AO2 Analog output voltage 2 Volt R 0 - 10
4 AO3 Motor R-Amp Motor rated current Amps R/W 0-65535
5 AO4 PwrL Sel Momentary Power Loss/ Fault Restart Selection No Units R 0 - 1
6 AO5 RestartSel Number of Fault Auto-Restart Attempts No Units R 0 – 10
7 AO6 RestartDelay Fault Auto-Restart Time seconds R 0 - 7200
8 AO7 FreqCommand1 Speed frequency setting-stage 0 HZ R/W 0 - 400
9 AO8 FreqCommand2 Speed frequency setting-stage 1 HZ R/W 0 - 400
10 AO9 FreqCommand3 Speed frequency setting-stage 2 HZ R/W 0 - 400
11 AO10 FreqCommand4 Speed frequency setting-stage 3 HZ R/W 0 - 400
12 AO11 FreqCommand5 Speed frequency setting-stage 4 HZ R/W 0 - 400
13 AO12 FreqCommand6 Speed frequency setting-stage 5 HZ R/W 0 - 400
14 AO13 FreqCommand7 Speed frequency setting-stage 6 HZ R/W 0 - 400
15 AO14 FreqCommand8 Speed frequency setting-stage 7 HZ R/W 0 - 400
16 AO15 FreqCommand9 Speed frequency setting-stage 8 HZ R/W 0 - 400
17 AO16 FreqCommand10 Speed frequency setting-stage 9 HZ R/W 0 - 400
18 AO17 FreqCommand11 Speed frequency setting-stage 10 HZ R/W 0 - 400
19 AO18 FreqCommand12 Speed frequency setting-stage 11 HZ R/W 0 - 400
20 AO19 FreqCommand13 Speed frequency setting-stage 12 HZ R/W 0 - 400
21 AO20 FreqCommand14 Speed frequency setting-stage 13 HZ R/W 0 - 400
22 AO21 FreqCommand15 Speed frequency setting-stage 14 HZ R/W 0 - 400
23 AO22 FreqCommand16 Speed frequency setting-stage 15 No Units R/W 0 - 2
24 AO23 RunMode Main run command source selection No Units R/W 0 - 2
25 AO24 ReverseOper Direction locked command No Units R/W 0 - 1

Manual — BACnet remaining object properties — page 437

Table 4.7.4.4 Analog value property list (READ/ WRITE)

Table 4.7.4.5 Digital input property list (READ)

Table 4.7.4.6 Digital output property list (READ/ WRITE)

Table 4.7.4.7 Digital value property list (READ/ WRITE)

AO25stop0–1;26frequency source0–5;27/28 frequencylimits0–400Hz;29/30 acceleration/deceleration0–3600seconds,all R/W. AV0P0–10,AV1I0–100,AV2D0–10 allNoUnits R/W. BI0–9 allR,0–1:run,dir,printed ststus,error,S1–S6. BO0–2 RY1–3 allR despite READ/WRITEheading. BV0run/stop,BV1forward/reverse R/W0–1. Object indices are BACnet-specific and mustnot merge with one-based MetaSys indices.

BACnet AO25–30 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

BACnet AO25–30 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO25

BACnet AO25–30 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO26

BACnet AO25–30 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO27

BACnet AO25–30 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO28

BACnet AO25–30 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO29

BACnet AO25–30 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO30

BACnet AV0–2 list4.7.4.4. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

BACnet AV0–2 list4.7.4.4. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AV0

BACnet AV0–2 list4.7.4.4. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AV1

BACnet AV0–2 list4.7.4.4. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AV2

BACnet BI0–9 list4.7.4.5. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

BACnet BI0–9 list4.7.4.5. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI0

BACnet BI0–9 list4.7.4.5. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI1

BACnet BI0–9 list4.7.4.5. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI2

BACnet BI0–9 list4.7.4.5. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI3

BACnet BI0–9 list4.7.4.5. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI4

BACnet BI0–9 list4.7.4.5. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI5

BACnet BI0–9 list4.7.4.5. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI6

BACnet BI0–9 list4.7.4.5. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI7

BACnet BI0–9 list4.7.4.5. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI8

BACnet BI0–9 list4.7.4.5. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI9

BACnet BO0–2 list4.7.4.6. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

BACnet BO0–2 list4.7.4.6. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BO0

BACnet BO0–2 list4.7.4.6. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BO1

BACnet BO0–2 list4.7.4.6. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BO2

BACnet BV0–1 list4.7.4.7. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

BACnet BV0–1 list4.7.4.7. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BV0

BACnet BV0–1 list4.7.4.7. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BV1

BACnet remaining object properties table1 — PDF page 437

Source row No. Object Name Description Unit Classification Range
1 AO25 StoppingSel Stop modes selection No Units R/W 0 - 1
2 AO26 FrequenceComm Main frequency command source selection No Units R/W 0 - 5
3 AO27 FreqUpperLim Upper limit frequency HZ R/W 0 - 400
4 AO28 FreqLowerLim Lower limit frequency HZ R/W 0 - 400
5 AO29 Acc Time1 Acceleration time 1 seconds R/W 0 - 3600
6 AO30 Dec Time1 Deceleration time 1 seconds R/W 0 - 3600

BACnet remaining object properties table2 — PDF page 437

Source row No. Object Name Description Unit Classification Range
1 AV0 PID – P Gain Proportional gain (P) No Units R/W 0 - 10
2 AV1 PID – I Time Integral time (I) No Units R/W 0 - 100
3 AV2 PID – D Time Differential time (D) No Units R/W 0 – 10

BACnet remaining object properties table3 — PDF page 437

Source row No. Object Name Description Unit Classification Range
1 BI0 Run/Stop Operation status Stop / Run R 0 - 1
2 BI1 Direction Operation direction FWD/REV R 0 - 1
3 BI2 ststus Inverter status OK/Fault R 0 - 1
4 BI3 Abnormal Error occurs Close/ Open R 0 - 1
5 BI4 DI_1 status S1 status Close/ Open R 0 - 1
6 BI5 DI_2 status S2 status Close/ Open R 0 - 1
7 BI6 DI_3 status S3 status Close/ Open R 0 - 1
8 BI7 DI_4 status S4 status Close/ Open R 0 - 1
9 BI8 DI_5 status S5 status Close/ Open R 0 - 1
10 BI9 DI_6 status S6 status Close/ Open R 0 - 1

BACnet remaining object properties table4 — PDF page 437

Source row No. Object Name Description Unit Classification Range
1 BO0 RY1 status Relay output 1 status Close/Open R 0 - 1
2 BO1 RY2 status Relay output 2 status Close/Open R 0 - 1
3 BO2 RY3 status Relay output 3 status Close/Open R 0 - 1

BACnet remaining object properties table5 — PDF page 437

Source row No. Object Name Description Unit Classification Range
1 BV0 RUN/STOP RUN/STOP Stop / Run R/W 0 - 1
2 BV1 FWD/REV FWD/REV FWD/REV R/W 0 - 1

Manual — MetaSys N2 introduction and specifications — page 438

4.8 MetaSys N2 Communication Protocol

4.8.1 Introduction and Setting

This section mainly describes the communication modes of MetaSys N2 communication protocol.

Connect terminal S+ and S- of hardware line RS485 and check if Baudrate setting of parameter

09-02 is 9600bps. If not, inverter requires reconnecting after the communication mode selection of

parameter 09-01 is set to 2 (MetaSys).

4.8.2 MetaSys N2 Specification

RS485S+/S−,09-02 baud9600,09-01=2MetaSys and reconnect. Table255slave connections,9600BPS; literal Data byte:8byte and Stop byte:1byte,no parity. Access15AI/10DI/34AO/5DO. Commands0/0time,0/4+0/5poll,0/8warmreset,1read,2write,Fidentify. AO7/2/3 andBO7/2/4 override enabled butnot automatically cleared after10minutes. Removeoverride7/3,AIoverride7/2/1 andBIoverride7/2/2 respond without executing. Preserve byte wording and limits; not protocol execution proof.

MetaSys N2 introduction and specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext.

MetaSys N2 introduction and specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Serial

Communication

Interface

MetaSys N2 introduction and specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Maximum Numbers

of Connection

MetaSys N2 introduction and specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Communication

Speed

MetaSys N2 introduction and specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Data Format

MetaSys N2 introduction and specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Access to Data

MetaSys N2 introduction and specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Supporting

Command

Shared source cells (coordinates refer to this table):

MetaSys N2 introduction and specifications table1 — PDF page 438

Source row Source row label Source value or description
1 Serial Communication Interface RS-485
2 Maximum Numbers of Connection 255 MetaSys N2 slave standard
3 Communication Speed 9600 (BPS)
4 Data Format  Data byte: 8 byte  Stop byte: 1 byte  No parity
5 Access to Data  15 Analog input  10 Digital input  34 Analog Output  5 Digital output
6 Supporting Command Support the following command 0/0 : Time Setting Command 0/4, 0/5 : Poll Command 0/8 : Warm Reset Command 1 : Read Command 2 : Write Command F : Identify Device Command
7 ⟦null: no independent source value⟧  The following Override command is enabled but it will not clear automatically after 10 minutes. 7/2/3 : AO Override command 7/2/4 : BO Override command  The following command will respond but not execute this action. 7/3 : Remove Override command 7/2/1 : AI Override command 7/2/2 : BI Override command

Manual — MetaSys N2 object and protocol definitions — page 439

4.8.3 Definition of MetaSys N2 Communication Protocol

MetaSys N2 is the communication protocol developed by Johnson Control Company. MetaSys N2

communication protocol uses the configuration of Master/ Slave. Every N2 Slave device can set N2

address and the range is 1-255.

The data of N2 Slave is displayed by the object and Network Point Type (NPT) is classified to seven

kinds of objects:

The input and output are mainly for N2 network. The input is the data from N2 Slave to N2 network

and the output is the data from N2 network to N2 Slave.

Virtual Object

Analog Outputs

Binary Outputs

Analog Inputs

Binary Inputs

Byte

Float

Integer

The object of N2 Slave has grouping and every group data can set the address of 0-255,

abbreviated for NPA (Network Point Address).

Every object has its property which includes data contens (AI and AO object), object status (BI and

BI object data), planning approach (if COS can respond or not) and so on. The property can read or

write command but the data value of analog output and digital output requires the Override

command to write in.

The object of N2 support function of COS (output in the change of status) and if COS starts, object

of AO, BI, and BO will automatically record under the data change and respond under the poll.

N2 Slave device waits for the indentify command after the inverter starts and starts for the

communication with network after receiving the indentify command.

General N2 objects AI/AO/ADF32-bit IEEEfloat,BI/BO1-bit,ADI16-bit,DB8-bit. Slave address1–255; NPAgroup address0–255. Inputs flow slave→network,outputs network→slave; diagram shows Analog/BinaryInputs leaving virtualobject,Analog/BinaryOutputs entering,Float/Integer/Byte bidirectional. Source says status BI andBI,retained. AO andDO values requireOverride; COS records AO,BI,BO changes/responds topoll. Slave awaitsIdentify afterpowerup. F510actualsupport restricted on440; not all seven generic types supported.

MetaSys N2 object and protocol definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext.

MetaSys N2 object and protocol definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 1

MetaSys N2 object and protocol definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 2

MetaSys N2 object and protocol definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 3

MetaSys N2 object and protocol definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 4

MetaSys N2 object and protocol definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 5

MetaSys N2 object and protocol definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 6

MetaSys N2 object and protocol definitions. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 7

MetaSys N2 object and protocol definitions table1 — PDF page 439

Source row No. NPT Name NPT (abbreviation) Description
1 1 Analog input AI 32-bit, IEEE- Standard floating-point
2 2 Binary input BI 1-bit
3 3 Analog output AO 32-bit, IEEE- Standard floating-point
4 4 Binary output BO 1-bit
5 5 Internal floating-point ADF 32-bit, IEEE- Standard floating-point
6 6 Internal integer ADI 16-bit
7 7 Internal Bytes DB 8-bit

Manual — F510 MetaSys N2 supported properties — page 440

4.8.4. MetaSys N2 Communication Protocol in F510 Model

F510 models support four NPT, AI, AO, BI and BO but DO NOT support the following functions:

Do not support only for the property or field that JCI used.

Do not support functions of Analog Alarm and Analog Warning in AI. The related fields can

read or write but do not have corresponding action.

Do not support functions of OverRide in AI and BI. The inverter does not have error message

for giving the OverRide command in AI and BI but do not have corresponding action.

Support functions of OverRide in AO and BO but values of AO and BO do not restore to defult

value when removing OverRide function.

The followings are the supporting properties list in AI, AO, BI and BO for F510 models:

(1) AI Property List

(2) BI Property List

(3) AO Property List

(4) BO Property List

F510 supports AI,AO,BI,BO only. JCI-specific fields unsupported; AIalarm/warning fields readable/writable butno action. AI/BI override gives noerror butno action. AO/BO override supported; removal doesnot restoredefault. AI configbyteR/W,statusbyteR,valuefloatR. BI configR/W,statusR. AO configR/W,statusR,currentfloatREAD/Override. BO configbyteR/W,statusREAD/Override; integerrows3/4 bothprinted MinimumOn-time; row5maximumcycles/hour R/W. Duplicate On-time preserved,not inferredOff-time.

MetaSys AI property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

MetaSys AI property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 1

MetaSys AI property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 2

MetaSys AI property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 3

MetaSys BI property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

MetaSys BI property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 1

MetaSys BI property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 2

MetaSys AO property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

MetaSys AO property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 1

MetaSys AO property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 2

MetaSys AO property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 3

MetaSys BO property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

MetaSys BO property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 1

MetaSys BO property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 2

MetaSys BO property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 3

MetaSys BO property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 4

MetaSys BO property definitions. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 5

F510 MetaSys N2 supported properties table1 — PDF page 440

Source row No. Data Type Description Notes
1 1 Byte Object Configuration READ/ WRITE
2 2 Byte Object Status Only READ
3 3 Float Analog Input Value Only READ

F510 MetaSys N2 supported properties table2 — PDF page 440

Source row No. Data Type Description Notes
1 1 Byte Object Configuration READ/ WRITE
2 2 Byte Object Status Only READ

F510 MetaSys N2 supported properties table3 — PDF page 440

Source row No. Data Type Description Notes
1 1 Byte Object Configuration READ/ WRITE
2 2 Byte Object Status Only READ
3 3 Float Current Value READ/ OverRide

F510 MetaSys N2 supported properties table4 — PDF page 440

Source row No. Data Type Description Notes
1 1 Byte Object Configuration READ/ WRITE
2 2 Byte Object Status READ/ OverRide
3 3 Integer Minimum On-time READ/ WRITE
4 4 Integer Minimum On-time READ/ WRITE
5 5 Integer Maximum Cycles/Hour READ/ WRITE

Manual — MetaSys N2 analog input and output mapping — page 441

The followings are parameters F510 models can read and write via MetaSys communication.

Analog input property list (READ)

Analog output property list (READ/ Write)

AI1–15 allR retain parameter references/units/ranges. AI1rpm0–60000NoUnits;AI2voltage0–240/0–480;AI3ratedpower0–600horsepower;AI4frequency0–599Hz;AI5station1–254;AI6mode0–3;AI7baud0–5;AI8carrier0–16kHz;AI9/10frequency0–599Hz;AI11current0–6553.5A;AI12mode0–5;AI13/14 analoginputs0–100Volt;AI15error0–45. AO1frequency2502H0–599Hz R/W,AO2/3analog2505/6H0–100Volt/Amps R. AO4run00-02range0–4;AO5frequency00-05range0–6;AO6/7limits00-12/13 printed0–109Hz;AO8/9times00-14/15 0–6000s;AO10motorcurrent02-01 1–999.9A. AO11stage0 uses05-01;AO12/13stage1/2 use06-01/02. Preserve protocol-specificclaims,not normalized toBACnet.

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI1

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI2

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI3

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI4

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI5

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI6

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI7

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI8

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI9

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI10

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI11

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI12

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI13

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI14

MetaSys AI1–15 parameter mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AI15

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO1

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO2

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO3

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO4

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO5

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO6

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO7

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO8

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO9

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO10

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO11

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO12

MetaSys AO1–13 mapping;continues442. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO13

MetaSys N2 analog input and output mapping table1 — PDF page 441

Source row No. Object Name F510 Parameters Unit Classification Range
1 AI1 Motor R-RPM 02-03 Motor Rated Rotation Speed No Units R 0 ~ 60000
2 AI2 Motor R-Volt 02-04 Motor Rated Voltage Volt R 0~240.0/0~480.0
3 AI3 Motor R-HP 02-05 Motor Rated Power horsepower R 0~600.00
4 AI4 Motor R-Hz 02-06 Motor Rated Frequency HZ R 0.00 ~ 599.00
5 AI5 Comm Station 09-00 INV Communication Station Address No Units R 1 - 254
6 AI6 CommSel 09-01 Communication Mode Selection No Units R 0 ~ 3
7 AI7 BaudRate 09-02 Baud Rate Setting No Units R 0 ~ 5
8 AI8 CarrierFreq 11-01 Carrier Frequency KiloHertz R 0 ~ 16
9 AI9 Freq cmd 12-16 Frequency Command HZ R 0.00 ~ 599.00
10 AI10 Frequency 12-17 Output Frequency HZ R 0.00 ~ 599.00
11 AI11 Current 12-18 Output Current Amps R 0.0~6553.5
12 AI12 Control Mode 12-24 Control Mode No Units R 0 ~ 5
13 AI13 TM2 AIN 12-25 AI1 Input Volt R 0 ~ 100.0
14 AI14 TM2 AIN2 12-26 AI2 Input Volt R 0 ~ 100.0
15 AI15 Error code 12-45 Recent Fault Message No Units R 0 ~ 45

MetaSys N2 analog input and output mapping table2 — PDF page 441

Source row No. Object Name F510 Parameters Unit Classification Range
1 AO1 Set frequency Register 2502H HZ R/W 0.00 ~ 599.00
2 AO2 AO1 Register 2505H Volt/ Amps R 0.00 ~ 100.00
3 AO3 AO2 Register 2506H Volt/ Amps R 0 .00 ~ 100.00
4 AO4 RunSource 00-02 Main Run Command Source Selection No Units R/W 0 ~ 4
5 AO5 FrequenceComm 00-05 Main Frequency Command Source Selection No Units R/W 0 ~ 6
6 AO6 FreqUpperLim 00-12 Upper Limit Frequency HZ R/W 0 – 109
7 AO7 FreqLowerLim 00-13 Lower Limit Frequency HZ R/W 0 - 109
8 AO8 Acc Time1 00-14 Acceleration Time 1 seconds R/W 0 ~ 6000.0
9 AO9 Dec Time1 00-15 Deceleration Time 1 seconds R/W 0 ~ 6000.0
10 AO10 Motor R-Amp 02-01 Motor Rated Current Amps R/W 1 ~ 999.9
11 AO11 FreqCommand1 05-01 Frequency Setting of Speed-Stage 0 HZ R/W 0.00 ~ 599.00
12 AO12 FreqCommand2 06-01 Frequency Setting of Speed-Stage 1 HZ R/W 0.00 ~ 599.00
13 AO13 FreqCommand3 06-02 Frequency Setting of Speed-Stage 2 HZ R/W 0.00 ~ 599.00

Manual — MetaSys N2 analog output continuation — page 442

AO14–26 speedstages3–15 map06-03..06-15,0–599Hz R/W. AO27powerloss07-00 range0–1R,AO28restartdelay07-01 0–7200sR,AO29restartcount07-02 0–10R;AO30stop07-09 0–1R/W;AO31/32/33PID10-05/06/07 ranges0–10/100/10 NoUnits R/W;AO34direction11-00 0–2R/W. Together441–442 exactly34AO. No parameterreference correction inferred.

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO14

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO15

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO16

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO17

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO18

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO19

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO20

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO21

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO22

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO23

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO24

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO25

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO26

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO27

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO28

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO29

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO30

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO31

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO32

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO33

MetaSys AO14–34 continuation. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: AO34

MetaSys N2 analog output continuation table1 — PDF page 442

Source row No. Object Name F510 Parameters Unit Classification Range
1 AO14 FreqCommand4 06-03 Frequency Setting of Speed-Stage 3 HZ R/W 0.00 ~ 599.00
2 AO15 FreqCommand5 06-04 Frequency Setting of Speed-Stage 4 HZ R/W 0.00 ~ 599.00
3 AO16 FreqCommand6 06-05 Frequency Setting of Speed-Stage 5 HZ R/W 0.00 ~ 599.00
4 AO17 FreqCommand7 06-06 Frequency Setting of Speed-Stage 6 HZ R/W 0.00 ~ 599.00
5 AO18 FreqCommand8 06-07 Frequency Setting of Speed-Stage 7 HZ R/W 0.00 ~ 599.00
6 AO19 FreqCommand9 06-08 Frequency Setting of Speed-Stage 8 HZ R/W 0.00 ~ 599.00
7 AO20 FreqCommand10 06-09 Frequency Setting of Speed-Stage 9 HZ R/W 0.00 ~ 599.00
8 AO21 FreqCommand11 06-10 Frequency Setting of Speed-Stage 10 HZ R/W 0.00 ~ 599.00
9 AO22 FreqCommand12 06-11 Frequency Setting of Speed-Stage 11 HZ R/W 0.00 ~ 599.00
10 AO23 FreqCommand13 06-12 Frequency Setting of Speed-Stage 12 HZ R/W 0.00 ~ 599.00
11 AO24 FreqCommand14 06-13 Frequency Setting of Speed-Stage 13 HZ R/W 0.00 ~ 599.00
12 AO25 FreqCommand15 06-14 Frequency Setting of Speed-Stage 14 HZ R/W 0.00 ~ 599.00
13 AO26 FreqCommand16 06-15 Frequency Setting of Speed-Stage 15 HZ R/W 0.00 ~ 599.00
14 AO27 PwrL Sel 07-00 Momentary Power Loss/Fault Restart Selection No Units R 0 ~ 1
15 AO28 RestartDelay 07-01 Fault Auto-Restart Time seconds R 0 ~ 7200
16 AO29 RestartSel 07-02 Number of Fault Auto-Restart Attempts No Units R 0 ~ 10
17 AO30 StoppingSel 07-09 Stop Mode Selection No Units R/W 0 - 1
18 AO31 PID – P Gain 10-05 Proportional Gain (P) No Units R/W 0 ~ 10.00
19 AO32 PID – I Time 10-06 Integral Time (I) No Units R/W 0 ~ 100.00
20 AO33 PID – D Time 10-07 Differential Time (D) No Units R/W 0 – 10.00
21 AO34 ReverseOper 11-00 Direction Lock Selection No Units R/W 0 ~ 2

Manual — MetaSys N2 binary mapping and errors — page 443

Binary input property list (READ)

Binary output property list (READ/ WRITE)

MetaSys N2 Error Code List

BI1–10 allR0–1:run/stop,forward/reverse,OK/fault,abnormal andDI1–6. BO1run/stop andBO2direction R/W;BO3–5RY1–3 R,all0–1. Error00noIdentifyatpowerup;01unsupportedcommand;02checkcodeerror;03dataover256bits;05wronglength;10outofrange;11undefined/JCI dedicatedfields;12readonlyposition. Gaps04/06–09notfilled. Reconciles15AI,34AO,10BI,5BOspecification.

MetaSys BI1–10 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

MetaSys BI1–10 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI1

MetaSys BI1–10 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI2

MetaSys BI1–10 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI3

MetaSys BI1–10 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI4

MetaSys BI1–10 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI5

MetaSys BI1–10 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI6

MetaSys BI1–10 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI7

MetaSys BI1–10 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI8

MetaSys BI1–10 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI9

MetaSys BI1–10 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BI10

MetaSys BO1–5 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

MetaSys BO1–5 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BO1

MetaSys BO1–5 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BO2

MetaSys BO1–5 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BO3

MetaSys BO1–5 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BO4

MetaSys BO1–5 mapping. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: BO5

MetaSys N2 error codes. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext.

MetaSys N2 error codes. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 00

MetaSys N2 error codes. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 01

MetaSys N2 error codes. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 02

MetaSys N2 error codes. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 03

MetaSys N2 error codes. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 05

MetaSys N2 error codes. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 10

MetaSys N2 error codes. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 11

MetaSys N2 error codes. Exactsourceunits,range and R/RW/Overrideclassification apply; noengineeringapproval. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 12

MetaSys N2 binary mapping and errors table1 — PDF page 443

Source row No. Object Name No Action / Action Classification Range
1 BI1 Run/ Stop Stop/ Run R 0 - 1
2 BI2 Direction Forward/ Reverse R 0 - 1
3 BI3 Status OK/ Fault R 0 - 1
4 BI4 Abnormal Off/ On R 0 - 1
5 BI5 DI_1 Status Off/ On R 0 - 1
6 BI6 DI_2 Status Off/ On R 0 - 1
7 BI7 DI_3 Status Off/ On R 0 - 1
8 BI8 DI_4 Status Off/ On R 0 - 1
9 BI9 DI_5 Status Off/ On R 0 - 1
10 BI10 DI_6 Status Off/ On R 0 - 1

MetaSys N2 binary mapping and errors table2 — PDF page 443

Source row No. Object Name No Action / Action Classification Range
1 BO1 Run/ Stop Stop/ Run R/W 0 - 1
2 BO2 Forward/ Reverse Forward/ Reverse R/W 0 - 1
3 BO3 RY1 Status Off/ On R 0 - 1
4 BO4 RY2 Status Off/ On R 0 - 1
5 BO5 RY3 Status Off/ On R 0 - 1

MetaSys N2 binary mapping and errors table3 — PDF page 443

Source row Error Code Cause
1 00 Without receving Identify command at power up
2 01 Receive the non-support command
3 02 Check Code occurs error
4 03 Receive the data of more than 256 bits
5 05 Incorrect command length
6 10 Data is out of the range
7 11 Save the undefined fields or the fields that JCI dedicated
8 12 The parameter position is only for read command.

Manual — LED keypad motor rotation test — page 444

Chapter 5 Check Motor Rotation and Direction

This test is to be performed solely from the inverter keypad. Apply power to the inverter after all the

electrical connections have been made and protective covers have been re-attached.

Important: Motor rotation and direction only applies to standard AC motors with a base frequency of

60Hz. For 50Hz or other frequency AC motors please set the max frequency and base frequency in group

01 accordingly before running the motors.

 LED Keypad Display

At this point, DO NOT RUN THE MOTOR, the LED keypad should display as shown below in Fig. 5.1 and all

LEDs are flashing. Next press the RUN key, all LEDs light on. See Fig 5.2. The motor should now be operating at

low speed running in forward (clockwise) direction. The value shown in the screen will change from 000.00Hz to

005.00Hz. Next press STOP key to stop the motor.

Fig 5.1: LED Keypad (Stopped) Fig 5.2: LED Keypad (Running)

Chapter5 source test onlyfromkeypad afterelectricalconnections andcoversreattached; statedstandardAC60Hzbase. 50Hz/other requireGroup01maximum/basefrequencies beforeoperation. Source initiallyDO NOT RUN,thenRUN forforward(clockwise)lowspeed,STOP afterward. Prose display000.00→005.00Hz,whilebothstopped/runningLEDimages visibly show5.00;retain distinction. FWDindicatorredboth,STOPredleft/RUNredright. No viewing-end direction or universal motorcompatibility inferred.

Manual — LCD keypad motor rotation test — page 445

 LCD Keypad Display

At this point, DO NOT RUN THE MOTOR, the LCD keypad should display as shown below in Fig. 5.3 and the

speed reference 12-16=005.00Hz should be blinking at the parameter code “12-16”. Next press the RUN key, see

Fig 5.4. The motor should now be operating at low speed running in forward (clockwise) direction. The parameter

code 12-17 shown at the bottom left corner of the screen will change from 12-17=000.00Hz to 12-17=005.00Hz.

Next press STOP key to stop the motor.

Fref Ref

12-16=005.00Hz

Monitor

12-17=000.00Hz

12-18=0000.0A

12-17=005.00Hz

12-18=0001.2A

Fig 5.3: Keypad (Stopped)

Fig 5.4: Keypad (Running)

Notes:

-

If the motor rotation is incorrect, power down the inverter.

extinguishes completely before touching any wiring, circuit boards or components.

leads to the motor (U/T1, V/T2 and W/T3). After the wiring change, repeat this step and

recheck motor direction.

LCD leftstopped/right running both12-16=005.00Hz;left12-17=000.00Hz,12-18=0000.0A;right12-17=005.00Hz,12-18=0001.2A. Values illustrative,notratedcurrent. Sourceincorrectrotation:powerdown;afterOFF waitatleast10minutes untilchargeindicator completelyextinguished beforetouching wiring/boards/components;refersection3.8,exchangeanytwoU/T1,V/T2,W/T3leads andretostdirection. Retained assupplierprocedure; not standaloneinstallationapproval.

Manual — Speed reference command and keypad — page 446

Chapter 6 Speed Reference Command Configuration

The inverter offers users several choices to set the speed reference source. The most commonly used

methods are described in the next sections.

Frequency reference command is selected with parameter 00-05.

00-05: Main Frequency Command (Frequency Source)

This function sets the frequency command source.

Setting Range: 0 to 5

To set parameter 00-05:

In the parameter list move cursor to 00-05 with the UP/DOWN keys and press READ/ ENTER key to

select.

6.1 Reference from Keypad

Speed reference from the keypad is the default setting. Press the READ/ ENTER key first and use the

</RESET, ▲ and ▼ keys to change the speed reference.

00-05 frequency source. Prose settingrange0–5 buttable0keypad,1AI1,2UP/DOWN,3RS485,4/5reserved,6RTC,7AI2auxiliary. Defaultkeypad; DSP/FUN→00BasicFun→READ/ENTER→05 thenREAD/ENTER; changefrequencywithREAD/ENTER,RESET,left/up/downkeys. Retain sourceoptionrange disagreement.

Speed reference command and keypad. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext.

Speed reference command and keypad. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 00-05

Speed reference command and keypad. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Range

Speed reference command and keypad table1 — PDF page 446

Source row Source row label Source value or description
1 00-05 Main Frequency Command Source Selection
2 Range 0: Keypad 1: External Terminal (Analog AI1) 2: Terminal Command UP / DOWN 3: Communication control (RS-485) 4: Reserved 5: Reserved 6: RTC 7: AI2 Auxiliary Frequency

Manual — AI1 voltage and potentiometer wiring — page 447

6.2 Reference from External Analog Signal (0-10V / 4-20mA)

Analog Reference: 0 – 10 V (Setting 00-05 = 1)

(S+)

(S-)

S1

S3

S5

24V

+10V

MT

GND

AI1

AI2

E

24VG

S2

S4

S6

F1

F2

PO

PI

AO1

AO2

Connect shield to

control ground terminal

0 – 10 V

+

-

Analog

Input AI1

Common/0V, GND

Control Terminals /

User Terminals

Analog Reference: Potentiometer / Speed Pot (Setting 00-05 = 1)

Potentiometer

1 ~ 5K Ohm

00-05=1 bothfigures. Top0–10V positive(red)→AI1,negative(black)→GND;shield dashedtoE/controlground. Bottom1–5kOhmpotentiometer:oneend+10Vred,otherendGNDblack,wiperAI1blue;shieldtoE. Terminalstrip top(S+),(S−),S1,S3,S5,24V,+10V,MT,GND,GND,AI1,AI2;bottomE,24VG,S2,S4,S6,F1,F2,PO,PI,AO1,AO2,E. Originalgeometrygoverns; parsedfalse terminaltablesexcludedbutalllabelsandassociations retained.

Manual — AI2 current reference wiring — page 448

Analog Reference: 4 – 20mA (Setting 00-05 = 7)

(S+)

(S-)

S1

S3

S5

24V

+10V

MT

GND

AI1

AI2

S6

E

24VG

S2

S4

F1

F2

PO

PI

AO1

AO2

Connect shield to

control ground terminal

4 – 20mA

+

-

Analog Input AI2

Common, GND

Control Terminals /

User Terminals

SW2

I

V

Set switch SW2 to ‘I’

(Factory Default)

00-05=7;4–20mA positive(red)→AI2,negative(black)→GND;shieldtoE/controlground. SW2setI describedfactorydefault;later451tablecallsVdefault. Same12top/12bottomterminalstripas447; nativeoverlayextractsS56wherevisiblelabelS6,rawnative retained withflag. No physicalswitchchangeexecuted.

Manual — RS485 frequency reference — page 449

6.3 Reference from Serial Communication RS485 (00-05=3)

RS485 PLC / Computer Connection -

+

S-

S+

Cable

Shield

RS485 Port

8 7 6 5 4 3 2 1

CN6

Control board

To set the speed reference for the inverter via serial communication parameter 00-05 has be set to “3”

for frequency command via serial communication.

Default Communication Setting is: Address “1”, 9600 Bits/sec, 1 Start Bit, 1 Stop Bit, and No Parity

The serial communication link function uses RS485 Modbus RTU protocol and allows for:

1) Monitoring (data monitoring, function data check).

2) Frequency setting.

3) Operation command (FWD, REV, and other commands for digital input).

4) Write function data.

Frequency Reference Command Register

Inverter Frequency Reference Register: 2502 (Hexadecimal) - Bit 0 – Bit 15: 0.00 ~ 599.00 Hz

00-05=3;CN6connectorpinorder8..1lefttoright;redS+pin1,blueS−pin2,shieldshown. Source defaultaddress1,9600bits/sec,1startbit,1stopbit,noparity. ModbusRTUmonitoring,frequency,operationcommands,functionwrites. Frequencyregister2502hex bits0–15 range0–599Hz. Diagramoriginal remainsauthoritative; no wiringorprotocoltest.

Manual — RS485 frequency command examples — page 450

Examples:

Frequency Reference Command: 10.00 Hz (Inverter Node Address: 01)

Command String (hexadecimal): 01 06 25 02 03 E8 23 B8

To set the frequency reference to 10.00, a value of ‘1000’ (03E8h) has to be send to the inverter.

Frequency Reference Command: 30.00 Hz (Inverter Node Address: 01)

Command String (hexadecimal): 01 06 25 02 0B B8 24 44

To set the frequency reference to 30.00, a value of ‘3000’ (0BB8h) has to be send to the inverter.

Frequency Reference Command: 60.00 Hz (Inverter Node Address: 01)

Command String (hexadecimal): 01 06 25 02 17 70 2D 12

To set the frequency reference to 60.00, a value of ‘6000’ (1770h) has to be send to the inverter

Note: The last 2 bytes of the command strings consist of a CRC16 checksum, please refer to section

4.5 of the instruction manual for additional information.

Node01write06to2502:10Hz data03E8 decimal1000,frame01 06 25 02 03 E8 23 B8;30Hz0BB8 decimal3000,frame01 06 25 02 0B B8 24 44;60Hz1770 decimal6000,frame01 06 25 02 17 70 2D 12. LasttwobytesCRC16; sourcecrossreference4.5 althoughModbussection4.6. Stored as examples,notexecutedcommands.

Adjacent source context — repeated to preserve continuation:

Manual — Dual analog references and display units — page 451

6.4 Reference from two Analog Inputs

Analog input AI1 is used as master frequency reference and analog input AI2 is used as auxiliary

frequency reference.

Analog Reference AI1: 0 – 10 V (Setting 00-05 = 1)

Analog Reference AI2: 0 – 10 V (Setting 00-06 = 1, 04-05 = 1)

(S+)

(S-)

S1

S3

S5

24V

+10V

MT

GND

AI1

AI2

E

24VG

S2

S4

S6

F1

F2

PO

PI

AO1

AO2

Connect shield to

control ground terminal

0 – 10 V

+

-

Analog Input AI1

Common/0V, GND

Control Terminals /

User Terminals

Analog Input AI2

6.5 Change Frequency Unit from Hz to rpm

Enter the number of motor poles in 16-03 to change the display units from Hz to rpm.

Example: Motor poles 4, 02-07 or 22-03 = 4.

AI1master00-05=1;AI2auxiliary00-06=1,04-05=1. Tableheading04-00 default1; AI1voltage/AI2voltage requires0/SW2V;AI1voltage/AI2current requires1/SW2I. SW2headerdefaultV conflicts448defaultI. DiagramAI1red/AI2bluepositive0–10V,commonGNDblack,shieldE. 16-03prosesaysenterpoles;table0Hz.01resolution,1percent.01,2rpmusingIM02-07/PM22-03poles;3–39reserved;40–9999integer,10001–19999one decimal,20001–29999two,30001–39999three. Gaps10000/20000/30000unfilled. Example4poles02-07or22-03=4.

Dual analog references and display units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext.

Dual analog references and display units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 0 ~ 10V

Dual analog references and display units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 16-03

Dual analog references and display units. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Range

Adjacent source context — repeated to preserve continuation:

Dual analog references and display units table1 — PDF page 451

Source row AI1 – Analog Input 1 AI2 – Analog Input 2 04-00 Setting (Default = 1) Dipswitch SW2 (Default ‘V’)
1 0 ~ 10V 0 ~ 10V 0 Set to ‘V’
2 0 ~ 10V 4 ~ 20mA 1 Set to ‘I’

Dual analog references and display units table3 — PDF page 451

Source row Source row label Source value or description
1 16-03 Display unit
2 Range 0: Display unit is Hz (Resolution is 0.01Hz) 1: Display unit is % (Resolution is 0.01%) 2: Rpm display; motor rotation speed is set by the control modes to select IM (02-07)/ PM (22-03) motor poles to calculate 3~39: Reserved 40~9999: 100% is XXXX with no decimals (integer only) 10001~19999: 100% is XXX.X with 1 decimal 20001~29999: 100% is XX.XX with 2 decimals 30001~39999: 100% is X.XXX with 3 decimals

Manual — Run stop source and keypad — page 452

Chapter 7 Operation Method Configuration (Run / Stop)

The inverter offers users several choices to run and stop from different sources. The most commonly

used methods are described in the next sections.

Operation command is selected with parameter 00-02.

00-02: Run Command Selection

This function sets the frequency command source.

Setting Range: 0 to 3

To set parameter 00-01:

In the parameter list move cursor to 00-01 with the UP/DOWN keys and press READ/ ENTER key to

select.

7.1 Run/Stop from the Keypad (00-02=0) – Default Setting

Use the RUN key to run the drive in forward direction and the

FWD/REV key to change the motor direction. (Note: to disable

reverse direction set parameter 11-01 to 1)

Press STOP key to stop the inverter. (Note: Stop method can be set

with parameter 07-09, default is deceleration to stop).

Fref Ref

12-16=005.00Hz

Monitor

12-17=000.00Hz

12-18=0000.0A

00-02runselection table0keypad,1external,2communication,3PLC,4RTC. Prose callsfrequencycommandsource andrange0–3; menuinstructions repeatedly00-01 instead00-02. Keypaddefault00-02=0,RUNforward,FWD/REVdirection,STOP;source reverse-disable11-01=1 differs11-00directionmapping442. Stopmethod07-09 defaultdeceleration. LCDreference005Hz/output000Hz/current0000.0Aillustration. Retainconflicts ratherthan choosecorrectparameter.

Run stop source and keypad. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext.

Run stop source and keypad. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: 00-02

Run stop source and keypad. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain sourceconflicts,continuations andexamplecontext. Row group: Range

Run stop source and keypad table1 — PDF page 452

Source row Source row label Source value or description
1 00-02 Run Command Selection
2 Range 0: Keypad control 1: External terminal control 2: Communication control 3: PLC 4: RTC

Manual — External maintained run switch — page 453

7.2 Run/Stop from External Switch / Contact or Pushbutton

(00-02=1)

Use an external contact or switch to Run and Stop the inverter.

Permanent Switch / Contact

(S+)

(S-)

S1

S3

S5

24V

+10V

MT

GND

AI1

AI2

E

24VG

S2

S4

S6

F1

F2

PO

PI

AO1

AO2

Start / Stop Switch

(Maintained)

Connect

shield to

control

ground

terminal

Forward Command/FWD

Common/

Control Terminals /

User Terminals

00-02=1. Figure maintainedstart/stopswitch electricallybetweenS1and24VGcommon;shielddashedtoE/controlground. Same12+12terminalstripas447. Captionincludespushbuttonbutactualshownswitchmaintained;no3wiremomentarywiring inferred. No installationvalidation.

Manual — RS485 run stop command — page 454

7.3 Run/Stop from Serial Communication RS485 (00-02=3)

RS485 PLC / Computer Connection -

+

S-

S+

Cable

Shield

RS485 Port

8 7 6 5 4 3 2 1

CN6

Control board

To control (Run/Stop) the inverter via serial communication parameter 00-02 has be set to either a “3”

for communication control.

Default Communication Setting is: Address “1”, 9600 Bits/sec, 1 Start Bit, 1 Stop Bit, and No Parity

The serial communication link function uses RS485 Modbus RTU protocol and allows for:

1) Monitoring (data monitoring, function data check).

2) Frequency setting.

3) Operation command (FWD, REV, and other commands for digital input).

4) Write function data.

Command Register

Inverter Command Register: 2501 (Hexadecimal)

Bit 0: Run Forward

Bit 1: Run Reverse

Bit 2 ~ Bit 15: Refer to the chapter XX of this manual

Headingandprose00-02=3communication conflicts452table2communication/3PLC. CN6S+pin1/S−pin2 anddefaultaddress1/9600/1start/1stop/noparity as449. Register2501hex;bit0printedRunForward,bit1RunReverse,bit2–15referchapterXXplaceholder. Earlier412definesbit0run/stopandbit1direction;455examplesuse0003forreverse(run+direction). Preservebothdescriptions; no operationalrecommendation.

Manual — RS485 run stop examples — page 455

Examples:

Run Forward Command (Inverter Node Address: 01)

Command String (hexadecimal): 01 06 25 01 00 01 12 C6

Run Reverse Command (Inverter Node Address: 01)

Command String (hexadecimal): 01 06 25 01 00 03 93 07

Stop Command (Inverter Node Address: 01)

Command String (hexadecimal): 01 06 25 01 00 00 D3 06

Note: The last 2 bytes of the command strings consist of a CRC16 checksum, please refer to section

4.5 of the instruction manual for additional information.

Node01function06register2501:forwarddata0001 frame01 06 25 01 00 01 12 C6;reversedata0003 frame01 06 25 01 00 03 93 07;stopdata0000 frame01 06 25 01 00 00 D3 06. LasttwoCRC;refer4.5printed. Examplesnotexecuted; sourcebitsconflict454flagged.

Manual — Motor nameplate settings — page 456

Chapter 8 Motor and Application Specific Settings

It is essential that before running the motor, the motor nameplate data matches the motor data in the

inverter.

8.1 Set Motor Nameplate Data (02-01, 02-05)

02-05 Rated power of motor 1

The nominal motor rated capacity is set at the factory. Please verify that the motor name plate data

matches the motor rated capacity shown in parameter 02-05. The setting should only be changed when

driving a motor with a different capacity.

Range: 0.00 to 600.00 kW (1HP = 0.746 kW)

To set parameter 02-05:

Default values vary based on the inverter model.

02-01 Rated current of motor

The motor rated current is set at the factory based on the inverter model. Enter the motor rated current

from the motor nameplate if it does not match the value shown in parameter 02-01.

Setting range: 0.01 to 600.00A

To set parameter 02-01:

Source requiresmotornameplate matchinverter beforeoperation. 02-05ratedpowerfactorymodeldependent,changeonlydifferentcapacity;range0–600kW,1HP=.746kW. Instructionunder02-05 mistakenlyselects-01. 02-01ratedcurrentfactorymodeldependent,enternameplateifdifferent,range.01–600A. This differsprotocoltables4360–65535A and4411–999.9A,while441powerunitshorsepower. Preservecontextspecificvalues,notoneuniversalrating.

Manual — Acceleration and deceleration — page 457

8.2 Acceleration and Deceleration Time (00-14, 00-15)

Acceleration and Deceleration times directly control the system dynamic response. In general, the

longer the acceleration and deceleration time, the slower the system response, and the shorter time,

the faster the response. An excessive amount of time can result in sluggish system performance while

too short of a time may result in system instability.

The default values suggested normally result in good system performance for the majority of general

purpose applications. If the values need to be adjusted, caution should be exercised, and the changes

should be in small increments to avoid system instability.

00-14 Acceleration time 1

00-15 Deceleration time 1

These parameters set the acceleration and deceleration times of the output frequency from 0 to

maximum frequency and from maximum frequency to 0.

To set parameter 00-14 or 00-15:

Acceleration and deceleration times are represented by the three most significant (high order) digits.

Set acceleration and deceleration times with respect to maximum frequency. The relationship between

the set frequency value and acceleration/deceleration times is as follows:

Set Frequency = Maximum Frequency Set Frequency < Maximum Frequency

Note: If the set acceleration and deceleration times are set too low, the torque limiting function or stall prevention

function can become activated if the load torque and or inertia are relatively high. This will prolong the

acceleration and or deceleration times and not allow the set times to be followed. In this case the acceleration and

or the deceleration times should be adjusted.

00-14accel/00-15decel set0→maxfrequency/max→0. Source longtimes slowresponse,shorttimespotentialinstability;adjustsmallincrements. Two diagrams:leftset=max fullramptime;rightset<max solidramps reachlowerfrequencyearlier than dashedmaximumline. No numerictime inferred. Notehighloadtorque/inertia mayactivate torquelimit/stallprevention andprolongactualtime;settimeisnotguaranteed elapsedtime.

Manual — Torque compensation — page 458

8.3 Torque Compensation Gain (01-10)

This parameter sets the relationship between output frequency and output voltage. Constant torque

applications have the same torque requirements at low speed as well as at high speed.

Initial Setup

For Variable Torque / Normal Duty applications set parameter 01-10 to an initial value of 0.5.

For Constant Torque / Heavy Duty applications set parameter 01-10 to an initial value of 1.0.

01-10 Torque compensation gain

This parameter sets the torque boost for motor.

Setting range: 0.0 to 2.0

To set parameter 01-10:

Increase value when:

 The wiring between the inverter and the motor very too long

 The motor size is smaller than the inverter size

Note: Gradually increase the torque compensation value and make sure the output current does not exceed

inverter rated current.

Reduce value when:

 Experiencing motor vibration

 Over Current Fault

 Overload Fault

Important: Confirm that the output current at low speed does not exceed the rated output current of the inverter.

Warning: A larger than required torque compensation gain value creates over-excitation at low

speeds, continued operation may cause the motor to overheat. Check the characteristics of the

motor for additional information.

01-10range0–2;initialvariabletorque/normalduty.5,constanttorque/heavyduty1.0. Increaseforlongwiring/smallermotorrelativeinverter;reduceforvibration,overcurrent,overload. Graduallyadjustandkeepoutputcurrent≤inverterratedcurrent,especiallylowspeed. Warningexcessgaincreatesoverexcitation andmayoverheatmotor;checkmotorcharacteristics. Supplierprocedure scope retained,not a universal recommendedsetting.

Manual — Automatic energy saving — page 459

8.4 Automatic Energy Savings Function (11-19)

In the V/F control mode the automatic energy saving (AES) function automatically adjusts the output

voltage and reduces the output current of the inverter to optimize energy savings based on the load.

The output power changes proportional to the motor load. Energy savings is minimal when the load

exceeds 70% of the output power and savings become greater when the load decreases.

The parameter of automatic energy saving function has been set at the factory before shipment. In

general, it is no need to adjust. If the motor characteristic has significant difference from TECO

standard, please refer to the following commands for adjusting parameters:

Enable Automatic Energy Savings Function

To set parameters 11-19 to 11-24:

(1) To enable automatic energy saving function set 11-19 to 1.

(2) Filter time of automatic energy saving (11-20)

(3) Commissioning parameter of energy saving (11-21 to 11-22)

In AES mode, the optimum voltage value is calculated based on the load power requirement but is also

affected by motor temperature and motor characteristic.

In certain applications the optimum AES voltage needs to be adjusted in order to achieve optimum

energy savings. Use the following AES parameters for manual adjustment:

11-21: Voltage limit value of AES commissioning operation

Sets the voltage upper limit during automatic energy saving. 100% corresponds to 230V or 460V

depending on the inverter class used.

Voltage limit value of commissioning operation

V/F AESadjustsoutputvoltage/currentbasedload. Sourceclaim savingsminimalabove70%outputpower andgreaterwithlowerload; not guaranteedmeasuredsavings. Factorysetparameters;motorcharacteristicsandtemperatureaffect optimum. Enable11-19=1,filter11-20,commissioning11-21/22;menuinstructionrange11-19..24. 11-21voltagelimit100%=230Vor460Vdependingclass. Diagramvoltagelimitvertical/outputvoltagehorizontal withclippedpositive/negative11-21bounds,notnumericcurve. Continued460outsidepacket.

Manual — Automatic energy saving continuation — page 460

11-22: Adjustment time of automatic energy saving

Sets sample time constant for measuring output power.

Reduce the value of 11-22 to increase response when the load changes.

Note: If the value of 11-22 is too low and the load is reduced the motor may become unstable.

11-23: Detection level of automatic energy saving

Sets the automatic energy saving output power detection level.

11-24: Coefficient of automatic energy saving

The coefficient is used to tune the automatic energy saving. Adjust the coefficient while running the

inverter on light load while monitoring the output power. A lower setting means lower output voltage.

Notes:

match the inverter rating.

11-22 sets output-power sampling time constant. Lower time increases response but too low with reduced load can destabilize motor. 11-23 sets power detection level. 11-24 coefficient adjusted under light load while monitoring power; lower means lower voltage and too low can stall. Default is inverter-rating based; source says set 13-00 when motor power differs. Retain this reference, no corrected parameter inferred. Continues prior PDF459.

Manual — Emergency stop time and input wiring — page 461

8.5 Emergency Stop

The emergency stop time is used in combination with multi-function digital input function #14

(Emergency stop). When emergency stop input is activated the inverter will decelerate to a stop using

the Emergency stop time (00-26) and display the [EM STOP] condition on the keypad.

Note: To cancel the emergency stop condition the run command has to be removed and emergency stop input

deactivated.

Example: Emergency Stop Switch set for input terminal S5 (03-04 = 14).

(S+)

(S-)

S1

S3

S5

24V

+10V

MT

GND

AI1

AI2

E

24VG

S2

S4

S6

F1

F2

PO

PI

AO1

AO2

Emergency

Stop Switch

Connect shield

to control

ground

terminal

Emergency Stop

Common/

Control Terminals /

User Terminals

Digital-input function14 invokes deceleration using 00-26, range0.1–6000.0seconds, displaying EM STOP. Cancellation requires BOTH remove run command AND deactivate emergency-stop input. Example S5=03-04=14: maintained switch between S5 and24VG common; dashed cable shield to E/control ground. Terminal top(S+),(S−),S1,S3,S5,24V,+10V,MT,GND,GND,AI1,AI2; bottomE,24VG,S2,S4,S6,F1,F2,PO,PI,AO1,AO2,E. No safety rating inferred from function name.

Emergency stop time and input wiring. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations.

Emergency stop time and input wiring. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 00-26

Emergency stop time and input wiring. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Range

Emergency stop time and input wiring table2 — PDF page 461

Source row Source row label Source value or description1
1 00-26 Emergency stop time
2 Range 0.1~6000.0 Sec

Manual — Unexpected startup protection timing — page 462

8.6 Direct / Unattended Startup

The unattended startup function prevents the inverter from starting automatically when a run command

is present at time of power-up. To use USP command set one of the multi-function digital input

functions to #50 (USP Startup).

Unattended Startup Protection

USP input function50 inhibits automatic starting when run already present at power-up. Six traces: power,run,fault alarm,fault reset,USP,output frequency. First panel USP active at power-up: fault clears when run removed; output remains off. Second panel caption says USP not active,reset then automatically restarts; diagram nevertheless has fault pulse at power-up while USP trace low. Third panel run off at power-up,USP active: subsequent run starts normally. Dotted markers denote ordering only; no numeric timing inferred. Source ambiguity retained.

Manual — Analog output function selection — page 463

8.7 Analog Output Setup

Signal: Use parameter 04-11 to select the analog output signal for AO1 and parameter 04-16 to select

the analog output signal for AO2.

Gain: Use parameter 04-12 to adjust the gain for AO1 and parameter 04-17 to adjust the gain for AO2.

Adjust the gain so that the analog output (10V/20mA) matches 100% of the selected analog output

signal (04-11 for AO1 and 04-16 for AO2).

Bias: Use parameter 04-13 to adjust the bias for AO1 and parameter 04-18 to adjust the bias for AO2.

Adjust the bias so that the analog output (0V/4mA) matches 0% of the selected analog output signal

(04-11 for AO1 and 04-16 for AO2).

Example: Analog Output 1 Wiring

(S+)

(S-)

S1

S3

S5

24V

+10V

MT

GND

AI1

AI2

24VG

S2

S4

F1

F2

PO

PI

AO1

AO2

E

Connect shield

to control

ground terminal

Common/

Control Terminals /

User Terminals

S6

Analog

Output 1

+

-

AO1 function04-11,gain04-12,bias04-13; AO2 function04-16,gain04-17,bias04-18. Gain maps10V/20mA to100%; bias maps0V/4mA to0%. Diagram AO1 positive/red,GND negative/black,shield E; terminals as461. Parameter04-11 list split across two parallel value columns:0–13 left,14–28 right; reserved14,16,19–20,26–27 remain reserved.25 is printed output frequency of the soft starter,28 communication control. Original wiring governs physical geometry.

Analog output function selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations.

Analog output function selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 04-11

Analog output function selection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Range

Shared source cells (coordinates refer to this table):

Analog output function selection table2 — PDF page 463

Source row Source row label Source value or description1 Source value or description2
1 04-11 AO1 function Setting ⟦null: no independent source value⟧
2 Range 0: Output frequency 1: Frequency command 2: Output voltage 3: DC voltage 4: Output current 5: Output power 6: Motor speed 7: Output power factor 8: AI1 input 9: AI2 input 10: Torque command 11: q -axis current 12: d-axis current 13: Speed deviation 14: Reserved 15: ASR output 16: Reserved 17: q-axis voltage 18: d-axis voltage 19~20: Reserved 21: PID input 22: PID output 23: PID target value 24: PID feedback value 25: Output frequency of the soft starter 26~27: Reserved 28: Communication control

Manual — Analog output gain bias signal type and filter — page 464

Analog output level adjustment

AO1/2 gain0–1000%,bias−100..100%; AO2 functions refer04-11. 04-19 title AO2 Output Signal Type nevertheless specifies both AO1 andAO2:0V/V,1V/I,2I/V,3I/I,with0–10V/4–20mA. 04-20 filter0–0.50s. Graph monitor signal0–100% horizontal,analog output vertical; bias offsets positive and negative branches; solid lines clip at±10V, dotted limits±10V×Gain;20mA aligns10V and4mA aligns0V. Graph is an illustration, not an additional inferred rating.

Analog output gain bias signal type and filter. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations.

Analog output gain bias signal type and filter. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 04-12

Analog output gain bias signal type and filter. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Range

Analog output gain bias signal type and filter. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 04-13

Analog output gain bias signal type and filter. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 04-16

Analog output gain bias signal type and filter. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 04-17

Analog output gain bias signal type and filter. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 04-18

Analog output gain bias signal type and filter. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 04-19

Analog output gain bias signal type and filter. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 04-20

Analog output gain bias signal type and filter table1 — PDF page 464

Source row Source row label Source value or description1
1 04-12 AO1 gain value
2 Range 0.0~1000.0%

Analog output gain bias signal type and filter table2 — PDF page 464

Source row Source row label Source value or description1
1 04-13 AO1 bias-voltage value
2 Range -100.0~100.0%

Analog output gain bias signal type and filter table3 — PDF page 464

Source row Source row label Source value or description1
1 04-16 AO2 function Setting
2 Range See parameter 04-11

Analog output gain bias signal type and filter table4 — PDF page 464

Source row Source row label Source value or description1
1 04-17 AO2 gain value
2 Range 0.0~1000.0%

Analog output gain bias signal type and filter table5 — PDF page 464

Source row Source row label Source value or description1
1 04-18 AO2 bias-voltage value
2 Range -100.0~100.0%

Analog output gain bias signal type and filter table6 — PDF page 464

Source row Source row label Source value or description1
1 04-19 AO2 Output Signal Type
2 Range 0: AO1:0~10V AO2:0~10V 1: AO1:0~10V AO2:4~20mA 2: AO1:4~20mA AO2:0~10V 3: AO1:4~20mA AO2: 4~20mA

Analog output gain bias signal type and filter table7 — PDF page 464

Source row Source row label Source value or description1
1 04-20 Filter Time of AO Signal Scan
2 Range 0.00~0.50s

Manual — PID control block diagram — page 465

Chapter 9 Using PID Control for Constant Flow / Pressure

Applications

9.1 What is PID Control?

The PID function in the inverter can be used to maintain a constant process variable such as pressure,

flow, temperature by regulating the output frequency (motor speed). A feedback device (transducer)

signal is used to compare the actual process variable to a specified setpoint. The difference between

the set-point and feedback signal is called the error signal.

The PID control tries to minimize this error to maintain a constant process variable by regulating the

output frequency (motor speed).

The amplitude of the error can be adjusted with the Proportional Gain parameter 10-05 and is directly

related to the output of the PID controller, so the larger gain the larger the output correction.

Pressure/flow/temperature maintained using output frequency. Setpoint10-00 minus feedback10-01 through feedback gain10-04 forms deviation. Feedback branch10-03=x0xxb direct orx1xxb through D10-07. Deviation→P10-05→I10-06→I-limit10-14; D10-07 branch selected for10-03=1,3,5,7 versus grounded path2,4,6,8. Integral reset is a multifunction digital input. Integral limiter has100% at both upper and lower labels, no minus visible; preserve. Summed result→PID limit10-23±100%→primary delay10-10→sign selection10-03xx0xb×1/xx1xb×−1→bias10-09→gain10-24→±200%limit. Target added for10-03=3,4,7,8 versus1,2,5,6; output limiter10-25=0 positive+109% or1±109%; printed109 retained. PID OFF bypasses target directly to Fref when10-03=0,Jog,or03-00..03-07=29. Source mixes bit and integer mode notations; not converted or resolved.

Manual — PID gains and control-mode bit fields — page 466

Example 1:

Example 2:

Gain = 1.0

Gain = 2.0

Set-Point = 80%

Feedback = 78%

Error = Set-point - Feedback = 2%

Control Error = Gain x Error = 2%

Control Error = Gain x Error = 4%

Please note that an excessive gain can make the system unstable and oscillation may occur.

The response time of the system can be adjusted with the Integral Gain set by parameter 10-06.

Increasing the Integral Time will make the system less responsive and decreasing the Integral Gain

Time will increase response but may result in instability of the total system.

Slowing the system down too much may be unsatisfactory for the process. The end result is that these

two parameters in conjunction with the acceleration (00-14) and deceleration (00-15) times are

adjusted to achieve optimum performance for a particular application.

For typical fan and pump applications a Proportional Gain (10-05) of 2.0 and an Integral Time

(10-06) of 5.0 sec is recommended.

10-03 PID control mode

PID control can be enabled by setting parameter 10-03 to ‘xxx1b’

Example1 gain1,target80%,feedback78%,error2%,control2%; example2 gain2,same target/feedback,error2%,control4%. Excess gain can cause instability/oscillation. Increase integral time10-06 slows response; decrease may destabilize. Tune with acceleration00-14/deceleration00-15. Source typical fan/pump recommendation P10-05=2.0 and I10-06=5.0s is conditional, not universal. Mode10-03 bits xxx0/1b disable/enable; xx0/1xb positive/negative; x0/1xxb D oferror/feedback;0/1xxxb PID/PID+target.

PID gains and control-mode bit fields. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations.

PID gains and control-mode bit fields. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 10-03

PID gains and control-mode bit fields. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Range

PID gains and control-mode bit fields table1 — PDF page 466

Source row Source row label Source value or description1
1 10-03 PID control mode
2 Range xxx0b: PID disable xxx1b: PID enable xx0xb: PID positive characteristic xx1xb: PID negative characteristic x0xxb: PID error value of D control x1xxb: PID feedback value of D control 0xxxb: PID output 1xxxb: PID output +target value

Manual — PID reference and current feedback wiring — page 467

Commonly used PID control modes

0001b: Forward operation: PID operation enabled, motor speeds increases when feedback signal is

smaller than set-point (most fan and pump applications)

0011b: Reverse operation: PID operation enabled, motor slows down when feedback signal is smaller

than set-point (e.g. level control applications)

To set parameter 10-03:

Important: To use the PID function parameter 00-05 (Main Frequency Command Source Selection)

has to be set to 5 for PID reference.

9.2 Connect Transducer Feedback Signal (10-01)

The PID function in the inverter

Depending on the type of feedback transducer used, the inverter can be setup for either 0-10V or a

4-20mA feedback transducer.

Feedback Signal 4 – 20mA (10-01 = 2) – SW2 = I

(S+)

(S-)

S1

S3

S5

24V

+10V

MT

GND

AI1

AI2

E

24VG

S2

S4

S6

F1

F2

PO

PI

AO1

AO2

Connect shield to

control ground

terminal

4 – 20mA

+

-

Analog Input AI2

Common, GND

Control Terminals /

User Terminals

SW2

I

V

Set switch SW2 to ‘I’

Modes0001b forward speeds up when feedback below setpoint;0011b reverse slows down below setpoint. Menu10PID,parameter03. Important instruction00-05=5 forPID reference conflicts PDF446 table5reserved. Current feedback10-01=2,SW2=I,4–20mA: positive/redAI2,negative/blackGND,shieldE. Terminal strip as461. Preserve source configuration rather than choose from conflicting settings.

Manual — PID voltage feedback and engineering units — page 468

Feedback Signal 0 – 10V (10-01 = 1) – SW2 = V

(S+)

S1

S3

S5

24V

+10V

MT

GND

AI1

AI2

E

24VG

S2

S4

S6

F1

F2

PO

PI

AO1

AO2

Connect shield to

control ground terminal

0 – 10Vdc

+

-

Analog Input AI2

Common, GND

Control Terminals /

User Terminals

SW2

I

V

Set switch SW2 to ‘V’

9.3 Engineering Units (only for LCD)

The PID setpoint scaling can be selected with parameter 16-03 and 16-04.

Example: 0 – 200.0 PSI Setpoint, set 16-03 to 12000 (1 decimal, range 0 – 200) and 16-04 to 2 (PSI).

Heading0–10V feedback10-01=1,SW2=V; diagram positive/red toAI2,negative/blackGND,shieldE. Top first two terminals both(S+),source duplicate preserved; no inferred(S−). LCD-only units via16-03/16-04. Example0–200.0PSI set16-03=12000(one decimal,range0–200),16-04=2(PSI). No conversion or universal pressure rating inferred.

Manual — PID sleep and wakeup operation — page 469

9.4 Sleep / Wakeup Function

The PID Sleep function can be used to prevent a system from running at low speeds and is frequently

used in pumping application. The PID Sleep function is turned on by parameter 10-29 set to 1. The

inverter output turns off when the PID output falls below the PID sleep level (10-17) for the time

specified in the PID sleep delay time parameter (10-18).

The inverter wakes up from a sleep condition when the PID output (Reference frequency) rises above

the PID wake-up frequency (10-19) for the time specified in the PID wake-up delay time (10-20).

10-29 =0: PID Sleep function is disabled.

10-29 =1: PID sleep operation is based on parameters of 10-17 and 10-18.

10-29 =2: PID sleep mode is enabled by multi-function digital input

Refer to figure 4.4.74 (a) and (b) for PID sleep / wakeup operation.

PID Sleep Function

10-29=0disabled,1sleep based10-17/18,2DI enabled. Below sleep level10-17 for delay10-18 stops output; above wake frequency10-19 for delay10-20 wakes. Block target minus feedback→PID→sleep→soft start→Fout; PID OFF target bypass;10-29=0 sleep bypass. Graph thinFref vs thickFout, thresholds wake10-19/sleep10-17/minimum01-08. A short initial crossing does not finish delay; sustained crossing starts delay then output ramp. Numeric times/frequencies not supplied.

Manual — Fault handling and overcurrent faults — page 470

Chapter 10 Troubleshooting and Fault Diagnostics

10.1 General

Inverter fault detection and early warning / self-diagnosis function. When the inverter detects a fault, a

fault message is displayed on the keypad. The fault contact output energizes and the motor will coast to

stop (The stop method can be selected for specific faults).

When the inverter detects a warning / self-diagnostics error, the digital operator will display a warning or

self-diagnostic code, the fault output does not energize in this case. Once the warning is removed, the

system will automatically return to its original state.

10.2 Fault Detection Function

When a fault occurs, please refer to Table 10.2.1 for possible causes and take appropriate measures.

Use one of the following methods to restart:

  1. Set one of multi-function digital input terminals (03-00, 03-05) to 17 (Fault reset); activate input

  2. Press the reset button on the keypad and clear fault message.

  3. Power down inverter wait until keypad goes blank and power-up the inverter again.

When a fault occurs, the fault message is stored in the fault history (see group 12 parameters).

Table 10.2.1 Fault information and possible solutions

Fault energizes contact and coasts motor to stop, with selectable stop method for specific faults; warning/self-diagnostic does not energize contact. Reset source: DI03-00,03-05=17(as printed comma),keypad RESET,or power cycle after keypad blank; storedGroup12. Table faults OC/OCA/OCC/OCD/GF retain separate cause/solution rows and image glyphs. OC about200%inverter rated current; GF>50%rated output current enabled08-23=1. OCD cause short deceleration but solution longer acceleration,retained conflict. Supplier remedies not engineering endorsement.

Source legend OC

over current corresponds to rendered display OC; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OCA

over current corresponds to rendered display OCA; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OCC

over current corresponds to rendered display OCC; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OCD

over current corresponds to rendered display OCd; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend GF

Ground fault corresponds to rendered display GF; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Fault handling and overcurrent faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Fault handling and overcurrent faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OC

over current

Fault handling and overcurrent faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OCA

Fault handling and overcurrent faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OCC

Fault handling and overcurrent faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OCD

Fault handling and overcurrent faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: GF

Ground fault

Shared source cells (coordinates refer to this table):

Fault handling and overcurrent faults table1 — PDF page 470

Source row LED display Description Cause Possible solutions
1 OC over current The inverter output current exceeds the overcurrent level (around 200% of the inverter rated current).  Acceleration time is too short.  Contactor at the inverter output side.  A special motor or applicable capacity is greater than the inverter rated value.  Short circuit or ground fault.  Extend acceleration time.  Check the motor wiring.  Disconnect motor and try running inverter.
2 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 OCA over current The inverter output current exceeds the overcurrent level in acceleration time  Acceleration time is too short  Capacity of motor is bigger than inverter  Short circuit between winding and shell of motor  Short circuit between wire and ground of motor  IGBT broken module  Set the longer acceleration time  Change to bigger capacity of inverter  Examine motor  Check the wire  Replace IGBT module
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 OCC over current The inverter output current exceeds the overcurrent level in constant speed  Instantaneous change of load  Instantaneous change of current  Change to bigger capacity of inverter  Add reactor to power source
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 OCD over current The inverter output current exceeds the overcurrent level in deceleration time  Deceleration time is too short  Set the longer acceleration time
8 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 GF Ground fault The current to ground exceeds 50% of the inverter rated output current (08-23 = 1, GF function is enabled).  Motor damaged (insulation).  Wire damage or deterioration.  Inverter DCCT sensors defect.  Replace motor.  Check the motor wiring.  Disconnect motor and try running inverter.  Check resistance between cables and ground.  Reduce carrier frequency.
10 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Voltage phase thermal faults — page 471

OV410Vdc200Vclass/820Vdc400Vclass;400class with01-14<400V uses730Vdc. UV190/380Vdc or inactive precharge contactor,07-13adjustment. IPL08-09=1;OPL08-10=1 with cause motor current<10%inverter rating. OH1 three occurrences within five minutes requires10minutes before reset. OH4PTCoverheat,MT/GNDwiring. OL1active08-05=xxx1. Fault section distinct from warning thresholds on476.

Source legend OV

Over voltage corresponds to rendered display OV; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend UV

Under voltage corresponds to rendered display UV; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend IPL

input phase

loss corresponds to rendered display IPL; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OPL

output phase

loss corresponds to rendered display OPL; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OH1

Heatsink

overheat corresponds to rendered display OH1; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OH4

Motor

overheating corresponds to rendered display OH4; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OL1

overload corresponds to rendered display OL1; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Voltage phase thermal faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Voltage phase thermal faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OV

Over voltage

Voltage phase thermal faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: UV

Under voltage

Voltage phase thermal faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: IPL

loss

Voltage phase thermal faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OPL

Voltage phase thermal faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OH1

overheat

Voltage phase thermal faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OH4

overheating

Voltage phase thermal faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OL1

overload

Shared source cells (coordinates refer to this table):

Voltage phase thermal faults table1 — PDF page 471

Source row LED display ⟦null: no independent source value⟧ Description Cause Possible solutions
1 OV Over voltage ⟦null: no independent source value⟧ DC bus voltage exceeds the OV detection level: 410Vdc: 200V class 820Vdc: 400V class (For 400V class, if input voltage 01-14 is set lower than 400V, the OV detection value will is decreased to 730Vdc).  Deceleration time set too short, resulting in regenerative energy flowing back from motor to the inverter.  The inverter input voltage is too high.  Use of power factor correction capacitors.  Excessive braking load.  Braking transistor or resistor defective.  Speed search parameters set incorrectly.  Increase deceleration time  Reduce input voltage to comply with the input voltage requirements or install an AC line reactor to lower the input voltage.  Remove the power factor correction capacitor.  Use dynamic braking unit.  Replace braking transistor or resistor.  Adjust speed search parameters.
2 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 UV Under voltage ⟦null: no independent source value⟧ DC bus voltage is lower than the UV detection level or the pre-charge contactor is not active while the inverter is running. 190Vdc: 200V class; 380Vdc: 400V class (The detection value can be adjusted by 07-13).  The input voltage is too low.  Input phase loss.  Input voltage fluctuation.  Pre-charge contactor damaged.  DC bus voltage feedback signal value not incorrect.  Check the input voltage.  Check input wiring.  Check power source  Replace pre-charge contactor  Replace control board or complete inverter.
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 IPL input phase loss ⟦null: no independent source value⟧ Phase loss at the input side of the inverter or input voltage imbalance, active when 08-09 = 1 (enabled).  IPL occurs.  Terminal screws of R/L1, S/L2 or T/L3 are loose or lost.  Input voltage fluctuation is too big.  Input Voltage is imbalance per phase  Aging of the capacity on main circuit inside inverter  Check if the main wiring connection is correct.  Check if the terminal screw gets loose.  Make sure having stable input voltage or turn off IPL detection function.  Replace the circuit board or inverter
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 OPL output phase loss ⟦null: no independent source value⟧ Phase loss at the output side of the inverter, active when 08-10 = 1 (enabled).  Wiring loose in inverter output terminal.  Motor rated current is less than 10% of the inverter rated current.  Check output wiring / faster screws.  Check motor & inverter rating.
8 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 OH1 Heatsink overheat ⟦null: no independent source value⟧ The temperature of the heat sink is too high. Note: when OH1 fault occurs three times within five minutes, it is required to wait 10 minutes before resetting the fault.  Ambient temperature too high.  cooling fan failed  Carrier frequency set too high.  Load too heavy.  Install fan or AC to cool surroundings.  Replace cooling fan.  Reduce carrier frequency.  Reduce load / Measure output current
10 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 OH4 Motor overheating ⟦null: no independent source value⟧ Motor overheating : The input of PTC (Positive Temperature Coefficient ) exceeds the overheat protection level  The surrounding temperature of motor is too high.  The input of PTC ( Positive Temperature Coefficient ) exceeds the overheat protection level.  Check the surrounding temperature of motor.  Check MT and GND terminal wiring be correct.
12 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 OL1 Motor overload ⟦null: no independent source value⟧ Internal motor overload protection tripped, active when protection curve 08-05 = xxx1.  Voltage setting V/F mode too high, resulting in over-excitation of the motor.  Motor rated current (02-01) set incorrectly.  Load too heavy.  Check V/f curve.  Check motor rated current  Check and reduce motor load, check and operation duty cycle.
14 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Overload communication feedback and safety faults — page 472

OL2 four occurrences within five minutes requires4minutes before reset. OTlevel08-15,time08-16,activation08-14=0or2; UTlevel08-19,time08-20,08-18=0or2. CEtimeout09-06,09-07=0..2. FBthreshold10-12/time10-13,10-11=2. STO andSTO2 share merged description/causes/solutions:standardH&C F1/F2;enhancedE&G SF1/SF2+SG. Cause08-30=1free-coast plus openDI03-00..07=58; solution says check08-30=0. SS1cause08-30=0deceleration andDI58turned on. EF0cause and reset solution both Modbus0x2501bit2=1. Preserve contradictory conditions, no safety validation.

Source legend OL2

Inverter

overload corresponds to rendered display OL2; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OT

Over torque

detection corresponds to rendered display Ot; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend UT

Under torque

detection corresponds to rendered display Ut; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend CE

communication

error corresponds to rendered display CE; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend FB

PID feedback

loss corresponds to rendered display Fb; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend STO

Safety switch corresponds to rendered display StO; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend STO2

Safety switch corresponds to rendered display StO2; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend SS1

Safety switch corresponds to rendered display SS1; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EF0

External fault 0 corresponds to rendered display EF0; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Overload communication feedback and safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Overload communication feedback and safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OL2

overload

Overload communication feedback and safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OT

detection

Overload communication feedback and safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: UT

Overload communication feedback and safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: CE

error

Overload communication feedback and safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: FB

loss

Overload communication feedback and safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: STO

Safety switch

Overload communication feedback and safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: STO2

Overload communication feedback and safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: SS1

Overload communication feedback and safety faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF0

External fault 0

Shared source cells (coordinates refer to this table):

Overload communication feedback and safety faults table1 — PDF page 472

Source row LED display Description Cause Possible solutions
1 OL2 Inverter overload Inverter thermal overload protection tripped. If an inverter overload occurs 4 times in five minutes, it is required to wait 4 minutes before resetting the fault.  Voltage setting V/F mode too high, resulting in over-excitation of the motor.  Inverter rating too small.  Load too heavy.  Check V/f curve.  Replace inverter with larger rating.  Check and reduce motor load, check and operation duty cycle.
2 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 OT Over torque detection Inverter output torque is higher than 08-15 (over torque detection level) for the time specified in 08-16. Parameter 08-14 = 0 or 2 to activate.  Load too heavy.  Check over torque detection parameters (08-15 / 08-16).  Check and reduce motor load, check and operation duty cycle.
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 UT Under torque detection Inverter output torque is lower than 08-19 (under torque detection level) for the time specified in 08-20. Parameter 08-18 = 0 or 2 to activate.  Sudden drop in load.  Belt break.  Check under torque detection parameters (08-19 / 08-20).  Check load / application.
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 CE communication error No Modbus communication received in for the time specified in 09-06 (communication error detection time). Active when 09-07(= 0 to 2).  Connection lost or wire broken.  Host stopped communicating.  Check connection  Check host computer / software.
8 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 FB PID feedback loss PID feedback signal falls below level specified in 10-12 (PID feedback loss detection level) for the time specified in 10-13 (Feedback loss detection time). Active when parameter (10-11 = 2).  Feedback signal wire broken  Feedback sensor broken.  Check feedback wiring  Replace feedback sensor.
10 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 STO Safety switch Inverter safety switches open.  Terminal board Input F1 and F2 are not connected (For standard H & C type)  Terminal board Input SF1 / SF2 and SG are not connected (For enhanced E & G type)  08-30 set to 1,free run to stop, and digital terminal is open, when 03-00~03-07=58  Check F1 and F2 connection. (For standard H & C type)  Check SF1 / SF2 and SG connection (For enhanced E & G type)  Check if 08-30 =0 and 03-00~03-07=58
12 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 STO2 Safety switch ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 SS1 Safety switch Inverter safety switches open.  When 08-30 is set to 0: Deceleration to stop, and digital terminal switch(58) is turned on.  Check digital terminal(58) is turned on.
16 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 EF0 External fault 0 External fault (Modbus) Modbus communication 0x2501 bit 2= "1"  Reset Modbus communication 0x2501 bit 2= "1"
18 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — External motor tuning and pump faults — page 473

EF1–6 correspondS1–6,03-00..05=25or68,08-24=0or1; merged common causes/solutions span all six. CF07SLV cannot run:source rotational/stationary tuning and01-08;CF08PMSLVstart/run:22-10,22-21,torquelimit. FUapplies DCfuse230V50HP+ or460V75HP+. LOPBT lowflow23-51;HIPBT highflow23-48;LPBFT lowpressure23-15 butcause says minimumflow. Source spelling/code distinction preserved.

Source legend EF1

External fault

(S1) corresponds to rendered display EF1; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EF2

(S2) corresponds to rendered display EF2; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EF3

(S3) corresponds to rendered display EF3; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EF4

(S4) corresponds to rendered display EF4; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EF5

(S5) corresponds to rendered display EF5; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EF6

(S6) corresponds to rendered display EF6; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend CF07

Motor control

fault corresponds to rendered display CF07; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend CF08

fault corresponds to rendered display CF08; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend FU

fuse open corresponds to rendered display Fu; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend LOPBT

Low flow fault corresponds to rendered display LOPbt; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend HIPBT

High flow fault corresponds to rendered display HIPbt; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend LPBFT

Low pressure

fault corresponds to rendered display LPbFt; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF1

(S1)

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF2

(S2)

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF3

(S3)

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF4

(S4)

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF5

(S5)

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF6

(S6)

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: CF07

fault

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: CF08

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: FU

fuse open

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: LOPBT

Low flow fault

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: HIPBT

High flow fault

External motor tuning and pump faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: LPBFT

Shared source cells (coordinates refer to this table):

External motor tuning and pump faults table1 — PDF page 473

Source row LED display ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Description Cause Possible solutions
1 EF1 External fault (S1) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ External fault (Terminal S1) Active when 03-00= 25 or 68, and Inverter external fault selection 08-24=0 or 1.  Multifunction digital input external fault active.  Multi-function input function set incorrectly.  Check wiring
2 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 EF2 External fault (S2) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ External fault (Terminal S2) Active when 03-01= 25 or 68, and Inverter external fault selection 08-24=0 or 1. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 EF3 External fault (S3) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ External fault (Terminal S3) Active when 03-02= 25 or 68, and Inverter external fault selection 08-24=0 or 1. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 EF4 External fault (S4) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ External fault (Terminal S4) Active when 03-03= 25 or 68, and Inverter external fault selection 08-24=0 or 1. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 EF5 External fault (S5) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ External fault (Terminal S5) Active when 03-04= 25 or 68, and Inverter external fault selection 08-24=0 or 1. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 EF6 External fault (S6) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ External fault (Terminal S6) Active when 03-05= 25 or 68, and Inverter external fault selection 08-24=0 or 1. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 CF07 Motor control fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Motor control fault  SLV mode is unable to run motor.  Perform rotational or stationary auto-tune  Increase minimum output frequency (01-08)
14 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 CF08 Motor control fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Motor control fault  Start or Run fault in PMSLV mode.  Increase the value of 22-10 properly.  Re auto-tune (22-21)  Check if the load is too heavy to raise torque output limit.
16 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 FU fuse open ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ DC bus fuse blown DC fuse (Models 230V 50HP and above, 460V 75HP and above) open circuit.  IGBT damaged.  Short circuit output terminals.  Check IGBTs  Check for short circuit at inverter output.  Replace inverter.
18 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 LOPBT Low flow fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Low flow fault  The feedback signal is not connected.  Due to HVAC feedback value is lower than the limit of minimum flow.  Check feedback signal is correct and with right connection.  Ensure that the feedback value is higher than the limit of minimum flow (23-51).
20 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 HIPBT High flow fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ High flow fault  Since HVAC feedback value is higher than the limit of maximum flow.  Check feedback signal is correct.  Ensure that the feedback value is lower than the limit of maximum flow (23-48).
22 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 LPBFT Low pressure fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Low pressure fault  The feedback signal is not connected.  Since feedback value of pump pressure is lower than limit of minimum flow.  Check feedback signal is correct and with connection.  Check if feedback value of pressure is lower than limit of minimum pressure (23-15).
24 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Pressure communication hardware and feedback faults — page 474

OPBFT highpressure cause says pressure lower than maximumflow,solution maximumpressure23-12. LSCFTinsufficient suction,PIDdifference high orcurrent low. CF00no keypad communication5secondsafterpowerup;CF01errors>2seconds. CTfaultvoltage/noise/controlboard. CF20double communication usesProfibusandModbus simultaneously. PTCsignal lossdisconnection>10secondsMT/GND. OPRkeypadrun00-02=0operatorremoved;16-09selectsstoporfault. FBLSSwhen23-19>0,feedback<operationpressure23-02×23-19,time23-18elapsed,23-78=2. SCshort/ground08-23=1. No merged pressure/flow concepts inferred.

Source legend OPBFT

High pressure

fault corresponds to rendered display OPbFt; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend LSCFT

Low suction fault corresponds to rendered display LSCFt; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend CF00

Operator

Communication

Error corresponds to rendered display CF00; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend CF01

Error 2 corresponds to rendered display CF01; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend CT Fault corresponds to rendered display CtEr; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend Double

Error corresponds to rendered display CF20; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend PTC Signal

Loss corresponds to rendered display PtCLS; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OPR

Disconnection corresponds to rendered display OPr; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend FBLSS

PID Feedback

Signal Loss corresponds to rendered display FbLSS; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend SC

Short Circuit corresponds to rendered display SC; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Pressure communication hardware and feedback faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Pressure communication hardware and feedback faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OPBFT

fault

Pressure communication hardware and feedback faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: LSCFT

Low suction fault

Pressure communication hardware and feedback faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: CF00

Error

Pressure communication hardware and feedback faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: CF01

Error 2

Pressure communication hardware and feedback faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: CT Fault

Pressure communication hardware and feedback faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Double

Pressure communication hardware and feedback faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: PTC Signal

Loss

Pressure communication hardware and feedback faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OPR

Disconnection

Pressure communication hardware and feedback faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: FBLSS

Signal Loss

Pressure communication hardware and feedback faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: SC

Short Circuit

Shared source cells (coordinates refer to this table):

Pressure communication hardware and feedback faults table1 — PDF page 474

Source row LED display ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Description Cause Possible solutions
1 OPBFT High pressure fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ High pressure fault  Since feedback value of pump pressure is lower than limit of maximum flow.  Check feedback signal is correct.  Check if feedback value of pressure is lower than limit of maximum pressure (23-12).
2 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 LSCFT Low suction fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Low suction fault  Insufficient water supply of effluent channel leads to insufficient suction  PID difference is higher than its level or current is lower than output current level  Check if water of effluent channel is enough, and water supply is regular.  Check PID difference is higher than its level or current is lower than output current level
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 CF00 Operator Communication Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Errors of data transmission occur in keypad  Keypad and inverter cannot transmit data after power on 5 seconds  Disconnect the operator and then reconnect.  Replace the control board
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 CF01 Operator Communication Error 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Errors of data transmission occur in keypad  Keypad and inverter can transmit data but transmission error occurs for more than 2 seconds  Disconnect the operator and then reconnect.  Replace the control board
8 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 CT Fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Fault occurs in voltage level of three-phase input  Abnormal input voltage, too much noise or malfunctioning control board  Check input voltage signal and the voltage on the control board.
10 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 Double Communication Error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Redundant Profibus and Modbus protocol  User may use two communication mechanisms simultaneously  Check only one communication mechanism is used.
12 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 PTC Signal Loss ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ PTC Signal Loss detecting triggers error message  PTC connection trips and has lasted for more than 10 seconds  Check if MT terminal and GND terminal are connected.
14 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 OPR Disconnection ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Run command is set to keypad mode (00-02=0). But when the inverter runs, the operator is disconnected. Selection of operator removed (16-09) determines if the inverter stops or displays fault signal.  The inverter runs at keypad mode (00-02=0), but warning of operator being disconnected/ removed occurs.  Check if the operator is disconnected or removed.
16 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 FBLSS PID Feedback Signal Loss ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ When 23-19 > 0, the inverter will display fault signal on the basis of the value of feedback pressure < operation pressure setting (23-02) x detection proportion of loss pressure (23-19) and detection time of loss pressure (23-18) passed, and 23-78=2 in the meanwhile.  Since proportion of loss pressure (23-19) is enabled and over high, the inverter trips to fault. Thus, feedback sensor cannot operate properly or is not installed correctly.  Check if the proportion of loss pressure (23-19) is set correctly.  Make sure the feedback sensor is installed correctly and PID feedback signal operates normally.
18 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
19 SC Short Circuit ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ The inverter output or load is at short circuit.  Short circuit or grounding fault (08-23=1) occurs from the damage to motor, insulation deterioration or cable breakage.  Check if the load is at correct wiring.
20 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Protection and firemode thermal faults — page 475

PF:OH1 three times in five minutes withDIruncommandnotremoved;removeRun. TOLexternaloverload enabled only withfiremode active,not generalexternaloverload applicability. Displayglyphs and conditional scope retained.

Source legend PF

Protection Fault corresponds to rendered display PF; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend TOL

External

Overload corresponds to rendered display tOL; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Protection and firemode thermal faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Protection and firemode thermal faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: PF

Protection Fault

Protection and firemode thermal faults. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.2.1 fault conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: TOL

Overload

Shared source cells (coordinates refer to this table):

Protection and firemode thermal faults table1 — PDF page 475

Source row LED display Description Cause Possible solutions
1 PF Protection Fault OH1 error occurs for 3 times in 5 minutes when run command in multi-function digital input terminals is not removed.  Run command in multi-function digital input terminals is not removed.  Remove run command in multi-function digital input terminals.
2 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 TOL External Overload External overload (enabled only when firemode activated  External overload in multi-function digital input terminals. (Ex. Fan overheat)  Check external overload.  Reset external overload of digital input.
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Warning and self-diagnosis overview — page 476

10.3 Warning / Self-diagnosis Detection Function

When the inverter detects a warning, the keypad displays a warning code (flash).

Note: The fault contact output does not energize on a warning and the inverter continues operation.

When the warning is no longer active the keypad will return to its original state.

When the inverter detected a programming error (for example two parameters contradict each other of

are set to an invalid setting), the keypad displays a self-diagnostics code.

Note: The fault contact output does not energize on a self-diagnostics error. While a self-diagnostics

code is active the inverter does not accept a run command until the programming error is

corrected.

Note: When a warning or self- diagnostic error is active the warning or error code will flash on the

keypad.

Refer to Table 10.3.1 for and overview, cause and corrective action for inverter warnings and

self-diagnostic errors.

Table 10.3.1 Warning / self-diagnosis and corrective actions

Warning flashes,contactdoesnotenergize,invertercontinues;clearswhenwarningremoved. Programming/self-diagnostic erroralsoflash/contactoff butrunnotaccepteduntilcorrected. OVwarning410/820Vdc,printed440Vclass01-14<400V→700Vdc;fault471400class→730Vdc. UV190/380 and07-13;OH1threeinfive requires10minutesbeforereset. Do not harmonize warning/fault thresholds orinfer warningneverstops because laterOL4decelerates.

Source legend OV

(flash)

Over voltage corresponds to rendered display OV; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend UV

under voltage corresponds to rendered display UV; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OH1

Heat sink

overheating corresponds to rendered display OH1; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Warning and self-diagnosis overview. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Warning and self-diagnosis overview. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OV

Over voltage

Warning and self-diagnosis overview. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: UV

under voltage

Warning and self-diagnosis overview. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OH1

overheating

Shared source cells (coordinates refer to this table):

Warning and self-diagnosis overview table1 — PDF page 476

Source row LED display Description Cause Possible solutions
1 OV (flash) Over voltage DC bus voltage exceeds the OV detection level: 410Vdc: 200V class 820Vdc: 400V class (for 440V class, if input voltage 01-14 is set lower than 400V, the OV detection value will is decreased to 700Vdc)  Deceleration time set too short, resulting in regenerative energy flowing back from motor to the inverter.  The inverter input voltage is too high.  Use of power factor correction capacitors.  Excessive braking load.  Braking transistor or resistor defective.  Speed search parameters set incorrectly.  Increase deceleration time  Reduce input voltage to comply with the input voltage requirements or install an AC line reactor to lower the input voltage.  Remove the power factor correction capacitor.  Use dynamic braking unit.  Replace braking transistor or resistor.  Adjust speed search parameters.
2 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 UV (flash) under voltage DC bus voltage is lower than the UV detection level or the pre-charge contactor is not active while the inverter is running. 190Vdc: 200V class; 380Vdc: 400V class (the detection value can be adjusted by 07-13)  The input voltage is too low.  Input phase loss.  Input voltage fluctuation.  Magnetic contactor damaged.  DC bus voltage feedback signal value not incorrect.  Check the input voltage.  Check input wiring.  Check power source  Replace magnetic contactor  Replace control board or complete inverter.
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 OH1 Heat sink overheating Heat sink is overheating : The temperature of the heat sink is too high. If heat sink overheating fault has occurred with three times in five minutes, it is required to wait for 10 minutes before resetting the fault.  Ambient temperature is too high.  The cooling fan has stopped.  Carrier frequency setting is too high.  Check the ambient temperature of the inverter.  Check the fan or dust and dirt in the heat sink.  Check the carrier frequency setting.
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Thermal torque and external baseblock warnings — page 477

OH2description says function32 then03-00..03-05=31;conflictretained. OTwarning08-14=0;UTwarning08-18=0. bb1–bb5 correspondS1–S5;commoncause/solutionmergedacrossfive entries,bb6continues478. Flash symbols retained independently from fault entries.

Source legend OH2

(flash)

Inverter over

heating warning corresponds to rendered display OH2; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OT

over torque

detection corresponds to rendered display Ot; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend UT

under torque

detection corresponds to rendered display Ut; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend bb1

External

baseblock corresponds to rendered display bb1; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend bb2

baseblock corresponds to rendered display bb2; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend bb3

baseblock corresponds to rendered display bb3; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend bb4

baseblock corresponds to rendered display bb4; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend bb5

baseblock corresponds to rendered display bb5; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Thermal torque and external baseblock warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Thermal torque and external baseblock warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OH2

heating warning

Thermal torque and external baseblock warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OT

detection

Thermal torque and external baseblock warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: UT

Thermal torque and external baseblock warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: bb1

baseblock

Thermal torque and external baseblock warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: bb2

Thermal torque and external baseblock warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: bb3

Thermal torque and external baseblock warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: bb4

Thermal torque and external baseblock warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: bb5

Shared source cells (coordinates refer to this table):

Thermal torque and external baseblock warnings table1 — PDF page 477

Source row LED display Description Cause Possible solutions
1 OH2 (flash) Inverter over heating warning Inverter overheat warning: Multi-function digital input set to 32. (Terminal S1 ~ S6) Active when 03-00 ~ 03-05 =31).  Multifunction digital input overheat warning active.  Multi-function input function set incorrectly.  Check wiring
2 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 OT (flash) over torque detection Inverter output torque is higher than 08-15 (over torque detection level) for the time specified in 08-16. Parameter 08-14 = 0 to activate.  Load too heavy.  Check over torque detection parameters (08-15 / 08-16).  Check and reduce motor load, check and operation duty cycle.
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 UT (flash) under torque detection Inverter output torque is lower than 08-19 (under torque detection level) for the time specified in 08-20. Parameter 08-18 = 0 to activate.  Sudden drop in load.  Belt break.  Check under torque detection parameters (08-19 / 08-20).  Check load / application.
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 bb1 (flash) External baseblock External base block (Terminal S1)  Multifunction digital input external baseblock active.  Multi-function input function set incorrectly.  Check wiring
8 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 bb2 (flash) External baseblock External base block (Terminal S2) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 bb3 (flash) External baseblock External base block (Terminal S3) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 bb4 (flash) External baseblock External base block (Terminal S4) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 bb5 (flash) External baseblock External base block (Terminal S5) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Overload communication and external fault warnings — page 478

bb6S6continues477. OL1/OL2 have a shared cause/solution cell: preserve entire shared list,do notforceeachbullettoonecode. OL2fourinfiveminuteswait4minutes. CEwarning noModbus2seconds09-07=3;distinct fault472uses09-06timeout. CLBcurrentprotectionlevelB. Retry shown during07-01period when07-01and07-02nonzero. EF1–3flash03-00..02=25or68,08-24=2operationcontinues;duplicatedsolutionbulletsretained,EF4–6continue479.

Source legend bb6

(flash)

External

baseblock corresponds to rendered display bb6; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OL1

Motor overload corresponds to rendered display OL1; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend OL2

Inverter overload corresponds to rendered display OL2; No flash markers on this row; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend CE

communication

error corresponds to rendered display CE; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend CLB

over current

protection

level B corresponds to rendered display CLb; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend Retry

retry corresponds to rendered display rEtrY; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EF1

( flash )

External fault

(S1) corresponds to rendered display EF1; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EF2

(S2) corresponds to rendered display EF2; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EF3

(S3) corresponds to rendered display EF3; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Overload communication and external fault warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Overload communication and external fault warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: bb6

baseblock

Overload communication and external fault warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OL1

Motor overload

Overload communication and external fault warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: OL2

Inverter overload

Overload communication and external fault warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: CE

error

Overload communication and external fault warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: CLB

level B

Overload communication and external fault warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Retry

retry

Overload communication and external fault warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF1

(S1)

Overload communication and external fault warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF2

(S2)

Overload communication and external fault warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF3

(S3)

Shared source cells (coordinates refer to this table):

Overload communication and external fault warnings table1 — PDF page 478

Source row LED display ⟦null: no independent source value⟧ Description Cause Possible solutions
1 bb6 (flash) External baseblock ⟦null: no independent source value⟧ External base block (Terminal S6)  Multifunction digital input external baseblock active.  Multi-function input function set incorrectly.  Check wiring
2 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 OL1 Motor overload ⟦null: no independent source value⟧ Internal motor overload protection tripped, active when protection curve 08-05 = xxx1.  Voltage setting V/F mode too high, resulting in over-excitation of the motor.  Motor rated current (02-01) set incorrectly.  Load too heavy.  Voltage setting V/F mode too high, resulting in over-excitation of the motor.  Inverter rating too small.  Load too heavy.  Check V/f curve.  Check motor rated current  Check and reduce motor load, check and operation duty cycle.  Check V/f curve.  Replace inverter with larger rating.  Check and reduce motor load, check and operation duty cycle
4 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 OL2 Inverter overload ⟦null: no independent source value⟧ Inverter thermal overload protection tripped. If an inverter overload occurs 4 times in five minutes, it is required to wait 4 minutes before resetting the fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 CE (flash) communication error ⟦null: no independent source value⟧ No Modbus communication received for 2 sec. Active when 09-07=3.  Connection lost or wire broken.  Host stopped communicating.  Check connection  Check host computer / software.
8 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 CLB over current protection level B ⟦null: no independent source value⟧ Inverter current reaches the current protection level B.  Inverter current too high.  Load too heavy.  Check load and duty cycle operation.
10 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 Retry (flash) retry ⟦null: no independent source value⟧ Automatic reset has activated, and it displays before the period of 07-01 automatic reset terminates.  The period of 07-01 automatic reset≠0.  The times of 07-02 automatic reset≠0.  It will disappear after the period of automatic reset.
12 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 EF1 ( flash ) External fault (S1) ⟦null: no independent source value⟧ External fault (Terminal S1) Active when 03-00= 25 or 68, and Inverter external fault selection 08-24=2.  Multifunction digital input external fault active and parameter 08-24 = 2 for operation to continue.  Multi-function input function set incorrectly.  Check wiring  Multi-function input function set incorrectly.  Check wiring
14 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 EF2 (flash) External fault (S2) ⟦null: no independent source value⟧ External fault (Terminal S2) Active when 03-01= 25 or 68, and Inverter external fault selection 08-24=2. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 EF3 (flash) External fault (S3) ⟦null: no independent source value⟧ External fault (Terminal S3) Active when 03-02= 25 or 68, and Inverter external fault selection 08-24=2. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
18 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — External fault and parameter assignment warnings — page 479

EF4–6flash03-03..05=25or68,08-24=2;sharedcauses/solutions withduplicatebullets retained. EF9fwd/revbothwithin0.5seconds,stopmethod07-09. SE01sourceexamples02-00>02-01,00-12<00-13,00-07=1and00-05=00-06,20-16<=20-15. SE02sameDIfunctionexceptunused/externalfault;UP/DOWNmusttogether;08/09and11conflict;speedsearch19and34conflict;2wireand3wirecannotbothassigned03-00..07. Source inequality signs retained literally.

Source legend EF4

(flash)

External fault

(S4) corresponds to rendered display EF4; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EF5

(S5) corresponds to rendered display EF5; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EF6

(S6) corresponds to rendered display EF6; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EF9

error of

forward/reversal

rotation corresponds to rendered display EF9; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend SE01

Rang setting

error corresponds to rendered display SE01; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend SE02

Digital input

terminal error corresponds to rendered display SE02; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

External fault and parameter assignment warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

External fault and parameter assignment warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF4

(S4)

External fault and parameter assignment warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF5

(S5)

External fault and parameter assignment warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF6

(S6)

External fault and parameter assignment warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EF9

rotation

External fault and parameter assignment warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: SE01

error

External fault and parameter assignment warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: SE02

terminal error

Shared source cells (coordinates refer to this table):

External fault and parameter assignment warnings table1 — PDF page 479

Source row LED display Description Cause Possible solutions
1 EF4 (flash) External fault (S4) External fault (Terminal S4) Active when 03-03= 25 or 68, and Inverter external fault selection 08-24=2.  Multifunction digital input external fault active and parameter 08-24 = 2 for operation to continue.  Multi-function input function set incorrectly.  Check wiring  Multi-function input function set incorrectly.  Check wiring
2 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 EF5 (flash) External fault (S5) External fault (Terminal S5) Active when 03-04= 25 or 68, and Inverter external fault selection 08-24=2. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 EF6 (flash) External fault (S6) External fault (Terminal S6) Active when 03-05= 25 or 68, and Inverter external fault selection 08-24=2. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 EF9 (flash) error of forward/reversal rotation Forward run and reverse run are active within 0.5 sec of each other. Stop method set by parameter 07-09.  Forward run and reverse run active (see 2-wire control).  Check run command wiring
8 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 SE01 Rang setting error Parameter setting falls outside the allowed range.  Some parameter ranges are determined by other inverter parameters which could cause an out of range warning when the dependency parameter is adjusted. For example: 02-00>02-01, 00-12<00-13 or when 00-07 = 1, 00-05 is the same with 00-06 or 20-16 <= 20-15.  Check parameter setting.
10 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 SE02 Digital input terminal error Multi-function input setting error.  Multi-function digital input terminals (03-00 to 03-07) are set to the same function (not including ext. fault and not used.) or UP/DOWN commands are not set at the same time( they must be used together).  UP/DOWN commands (08 and 09) and ACC/DEC commands (11) are set at the same time.  Speed search 1(19, maximum frequency) and Speed search 2 (34,from the set frequency)are set at the same time.  2-wire sequence and 3-wire sequence set at the same time in 03-00~03-07  Check multi-function input setting.
12 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Parameter PID startup and flow warnings — page 480

SE03cause lists01-02>01-12>01-06>01-08(Fmax,Fbase,Fmid1,Fmin);do notflipinequalities. SE05sameAI1/2for10-00and10-01 or23-05=0with10-33>=1000or10-34≠1. HPErr13-00capacity/voltage. SE09pulse03-30conflicts10-00/01. FBwarning10-11=1vsfault2. USPDI50powerupinhibit;source resetsremoveRun/DI17/keypad/activeUSPthenpoweragain. LFPBlowflow. HFPBhighflowcause nevertheless says lower thanmaximumflow;retain.

Source legend SE03

V/f curve error corresponds to rendered display SE03; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend SE05

PID selection

error corresponds to rendered display SE05; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend HPErr

Model selection

error corresponds to rendered display HPErr; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend SE09

PI setting error corresponds to rendered display SE09; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend FB

(flash)

PID feedback

breaking corresponds to rendered display Fb; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend USP

Unattended

Start Protection corresponds to rendered display USP; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend LFPB

Low flow error corresponds to rendered display LFPb; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend HFPB

High flow error corresponds to rendered display HFPb; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Parameter PID startup and flow warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Parameter PID startup and flow warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: SE03

V/f curve error

Parameter PID startup and flow warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: SE05

error

Parameter PID startup and flow warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: HPErr

Parameter PID startup and flow warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: SE09

PI setting error

Parameter PID startup and flow warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: FB

breaking

Parameter PID startup and flow warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: USP

Start Protection

Parameter PID startup and flow warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: LFPB

Low flow error

Parameter PID startup and flow warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: HFPB

High flow error

Shared source cells (coordinates refer to this table):

Parameter PID startup and flow warnings table1 — PDF page 480

Source row LED display Description Cause Possible solutions
1 SE03 V/f curve error V/f curve setting error.  V/F curve setting error. 01-02 > 01-12 > 01-06 (Fmax) (Fbase) (Fmid1) >01-08; (Fmin)  Check V/F parameters
2 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 SE05 PID selection error PID selection error.  10-00 and 10-01are set to 1 (AI1) or 2 (AI2) simultaneously.  When 23-05=0 and 10-33>= 1000 or 10-34≠1.  Check the setting value of parameters 10-00 and 10-01.  Check the setting value of 10-33, 10-34 and 23-05.
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 HPErr Model selection error Inverter capacity setting error: Inverter capacity setting 13-00 does not match the rated voltage.  Inverter capacity setting does not match voltage class (13-00).  Check inverter capacity setting 13-00.
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 SE09 PI setting error Inverter PI setting error  Inverter pulse input selection (03-30) selection conflicts with PID source (10-00 and 10-01).  Check pulse input selection (03-30) and PID source (10-00 and 10-01).
8 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 FB (flash) PID feedback breaking PID feedback signal falls below level specified in 10-12 (PID feedback loss detection level) for the time specified in 10-13 (Feedback loss detection time). Active when parameter (10-11 = 1).  Feedback signal wire broken  Feedback sensor broken.  Check feedback wiring  Replace feedback sensor.
10 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 USP (flash) Unattended Start Protection Unattended Start Protection (USP) is enabled (enabled at power-up.)  USP at power-up (activated by multi-function digital input) is enabled. The inverter will not accept a run command.  While the warning is active the inverter does not accept a run command. (See parameter 03-00 - 03-05 = 50).  Remove run command or reset inverter via multi-function digital input (03-00 to 03-07 = 17) or use the RESET key on the keypad to reset inverter.  Activate USP input and re-apply the power.
12 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 LFPB Low flow error Low flow error  The feedback signal is not connected.  Due to HVAC feedback value is lower than limit of minimum flow.  Check feedback signal is correct and with right connection.  Check if feedback value is lower than limit of minimum flow.
14 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 HFPB High flow error High flow error  Due to HVAC feedback value is lower than limit of maximum flow.  Check feedback signal is correct.  Check if feedback value is lower than limit of maximum flow.
16 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Pressure suction firemode and startup warnings — page 481

L0PB source heading uses zero-shaped0,lowpressurecause minimumflow; HIPBhighpressurecause lowerthanmaximumflow;retainboth. LSCFTsuction. FIREoverrideactive:solutionNone andexplicitnotakindofwarning despitewarningtable. SE10pump23-02>23-03 orHVAC23-46<23-47. COPUPcascadecommunicationbroken. ParameterSettingError displayPArEr; DirectStart displayStP1,07-04=1:removeDIrunandreconnectafter07-05delay. Segment displaycase is visual, not independent parameteridentity.

Source legend L0PB

Low pressure

error corresponds to rendered display LOPb; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend HIPB

High pressure

error corresponds to rendered display HIPb; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend LSCFT

Low suction

error corresponds to rendered display LSCFt; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend FIRE

Fire override

mode corresponds to rendered display FirE; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend SE10

PUMP/HVAC

Setting error corresponds to rendered display SE10; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend COPUP

PUMP

communication

breaking error corresponds to rendered display COPUP; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend Parameter

Setting Error corresponds to rendered display PArEr; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend Warning of

Direct Start corresponds to rendered display StP1; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Pressure suction firemode and startup warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Pressure suction firemode and startup warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: L0PB

error

Pressure suction firemode and startup warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: HIPB

Pressure suction firemode and startup warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: LSCFT

Pressure suction firemode and startup warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: FIRE

mode

Pressure suction firemode and startup warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: SE10

Setting error

Pressure suction firemode and startup warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: COPUP

breaking error

Pressure suction firemode and startup warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Parameter

Setting Error

Pressure suction firemode and startup warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Warning of

Direct Start

Shared source cells (coordinates refer to this table):

Pressure suction firemode and startup warnings table1 — PDF page 481

Source row LED display Description Cause Possible solutions
1 L0PB Low pressure error Low pressure error  The feedback signal is not connected.  Due to feedback value of pump pressure is lower than limit of minimum flow.  Check feedback signal is correct and with connection.  Check if feedback value of pressure is lower than limit of minimum pressure.
2 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 HIPB High pressure error High pressure error  Due to feedback value of pump pressure is lower than limit of maximum flow.  Check feedback signal is correct.  Check if feedback value of pressure is lower than limit of maximum pressure.
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 LSCFT Low suction error Inadequate suction error  Insufficient water of supply tank leads to insufficient suction.  PID difference is higher than its level or current is lower than output current level.  Check if water of supply tank is enough, and water supply is regular.  Check PID difference is higher than its level or current is lower than output current level
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 FIRE Fire override mode Fire override mode  Fire override mode is active  None  (Fire override mode is not a kind of warning).
8 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 SE10 PUMP/HVAC Setting error PUMP/HVAC settings of inverter error  PUMP selection of inverter (23-02)> (23-03).  HVAC selection of inverter (23-46)< (23-47).  Check pump selection of inverter (23-02) and (23-03) settings.  Check HVAC selection of inverter (23-46) and (23-47) settings.
10 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 COPUP PUMP communication breaking error Breaking error of multiple pumps communication  Communication breaking or disconnection of pump cascade control.  Check if it has setting issue or is not properly connected.
12 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 Parameter Setting Error Parameter setting error  Error of Parameter setting occurs.  Refer to the instruction manual or this parameter is selected to be disabled.
14 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 Warning of Direct Start When 07-04 is set to 1, the inverter can not start directly but displays the warning signal.  Set the digital input terminal (S1~S6) to run and simultaneously set 07-04=1.  Check the digital input terminal and disconnect it. Then reconnect the DI terminal after the setting delay time (07-05) ends.
16 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Control keypad password and operator warnings — page 482

Externalterminalstop displayStP2,00-02=1andkeypadSTOP;removeexternalRun. AdCErcontrolvoltage. EPErrEEPROMpoorarchivingatboot,source reconnect/replace/contactTECO. bdErrboardprogrammismatch. rUnErwrongdirectionwhileone-directiononly. PtCLSconnection>10secondsMT/GND. LOC13-07passwordlock. Err2secondpassword differsfirst. RDE*operatorreadingerror;starfootnote483 restrictsLCDonly,notLEDdespitecolumnheading.

Source legend External

Terminal Stop

Error corresponds to rendered display StP2; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend ADC Voltage

Error corresponds to rendered display AdCEr; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend EEPROM

Archiving Error corresponds to rendered display EPErr; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend Control Board

Error corresponds to rendered display bdErr; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend Wrong running

direction Error corresponds to rendered display rUnEr; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend PTC Signal

Loss corresponds to rendered display PtCLS; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend Parameters

Locked corresponds to rendered display LOC; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend Password

Setting Error corresponds to rendered display Err2; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend Operator

Reading Error corresponds to rendered display RDE*; No flash markers on this row; LCD only. Segment typography is represented approximately; source legend governs identity.

Control keypad password and operator warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Control keypad password and operator warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: External

Error

Control keypad password and operator warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: ADC Voltage

Control keypad password and operator warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: EEPROM

Archiving Error

Control keypad password and operator warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Control Board

Control keypad password and operator warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Wrong running

direction Error

Control keypad password and operator warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: PTC Signal

Loss

Control keypad password and operator warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Parameters

Locked

Control keypad password and operator warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Password

Setting Error

Control keypad password and operator warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Operator

Reading Error

Control keypad password and operator warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: RDE*

Shared source cells (coordinates refer to this table):

Control keypad password and operator warnings table1 — PDF page 482

Source row LED display ⟦null: no independent source value⟧ Description Cause Possible solutions
1 External Terminal Stop Error ⟦null: no independent source value⟧ External Terminal is main run command source selection (00-02=1) and run command executes but executes stop command from keypad.  Run command executes from external terminal but executes stop command from keypad.  Remove the run command from external terminal
2 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ADC Voltage Error ⟦null: no independent source value⟧ Abnormal voltage level on the control board  Abnormal input voltage, too much noise or malfunctioning control board.  Check the input voltage signal and the voltage on the control board.
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 EEPROM Archiving Error ⟦null: no independent source value⟧ EEPROM Poor archiving  EEPROM poor peripheral circuit  It occurs in parameters check at inverter boot.  Reconnect and if the warning signal appears again, replace the circuit board.  Contact TECO for more information.
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 Control Board Error ⟦null: no independent source value⟧ The control board is not correspondent with the program.  The control board is not correspondent with the program.  Replace the control board.
8 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 Wrong running direction Error ⟦null: no independent source value⟧ Only for run in one direction, another direction command is not allowed.  Run command for another direction on the terminal of control board is active.  Cancel the run command for another direction on the terminal of control board.
10 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 PTC Signal Loss ⟦null: no independent source value⟧ PTC Signal Loss detecting triggers error message  PTC connection trips and has lasted for more than 10 seconds.  Check if MT terminal and GND terminal are connected.
12 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 Parameters Locked ⟦null: no independent source value⟧ Parameter password have been locked  Parameter password function (13-07) starts.  Correct password input at parameter 13-07
14 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 Password Setting Error ⟦null: no independent source value⟧ Password input at the second time is different from that at the first time when the password lock function enables.  Password input at the second time is different from that at the first time when the password lock function enables.  Password input at the second time is the same as that at the first time when the password lock function enables.
16 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 Operator Reading Error ⟦null: no independent source value⟧ Operator cannot read the inverter’s information.  Since signals from the inverter’s control board are transmitted error, the inverter cannot normally transmit the data to operator.  Check if the inverter is normally connected to the operator.
18 RDE* ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Operator emergency stop and feedback warnings — page 483

WRE operatorwrite mode/model/firmwaremismatch;VRYE verifydatamismatch;EFrepeatRunreversewhileone-direction;RDP*16-08=0readprohibit,set1. ESexternalemergencystopDI03-00..03-08=14(asprinted). StP0runenabledfrequency<01-08andDCbrakedisabled. OL4compressorcurrent23-69/time23-70causesdecelerationstopandwarning,qualifiedexceptionto476generalcontinuedoperation. FBLSSwarning23-19>0,feedback<transmittermaximumpressure23-03×23-19,time23-18elapsed,23-78=1;fault474usesoperationpressure23-02. Footnote RDE/WRE/VRYE/RDP LCDkeypadonly.

Source legend Operator

Writing Error corresponds to rendered display WRE*; No flash markers on this row; LCD only. Segment typography is represented approximately; source legend governs identity.

Verifying Error corresponds to rendered display VRYE*; No flash markers on this row; LCD only. Segment typography is represented approximately; source legend governs identity.

Source legend Repeat Run

Command corresponds to rendered display EF; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend Operator Read

Prohibit corresponds to rendered display RDP*; No flash markers on this row; LCD only. Segment typography is represented approximately; source legend governs identity.

Source legend External

Emergency

Stop corresponds to rendered display ES; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend Zero Speed

Stop Warning corresponds to rendered display StP0; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend Overload of Air

Compressor corresponds to rendered display OL4; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Source legend PID feedback

signal loss corresponds to rendered display FbLSS; Warning section glyphs with radiating markers; Source segment display. Segment typography is represented approximately; source legend governs identity.

Operator emergency stop and feedback warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Operator emergency stop and feedback warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Operator

Writing Error

Operator emergency stop and feedback warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: WRE*

Verifying Error

Operator emergency stop and feedback warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: VRYE*

Operator emergency stop and feedback warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Repeat Run

Command

Operator emergency stop and feedback warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Operator Read

Prohibit

Operator emergency stop and feedback warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: RDP*

Operator emergency stop and feedback warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: External

Stop

Operator emergency stop and feedback warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Zero Speed

Stop Warning

Operator emergency stop and feedback warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: Overload of Air

Compressor

Operator emergency stop and feedback warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.3.1 warning/self-diagnosis conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: PID feedback

signal loss

Shared source cells (coordinates refer to this table):

Operator emergency stop and feedback warnings table1 — PDF page 483

Source row LED display Description Cause Possible solutions
1 Operator Writing Error Operator cannot write the information into the inverter.  Data control mode in operator is not consistent with that in the inverter.  Data models in operator are not consistent with that in the inverter.  Data firmware version in operator is not consistent with that in the inverter.  Check the inverter’s firmware version/ control mode/ models
2 WRE* ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 Operator Verifying Error After operator reads or writes data in the inverter, user can verify it. If the data are not consistent, the inverter displays the signal of verifying error.  The data in the operator and the inverter is not consistent.  Check if the inverter is normally connected to the operator.
4 VRYE* ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 Repeat Run Command The inverter is only allowed unidirectional operation and cannot operate in reverse direction simultaneously.  Check if the external terminal is given a run command in reverse direction.  Cancel the run command in reverse direction from the external terminal.
6 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 Operator Read Prohibit Selection of allowing reading (16-08) is set to 0 (Do not allow to read inverter parameters and save it to the operator).  Set parameter 16-08 to 0.  Set parameter 16-08 to 1 (Allow to read inverter parameters and save it to the operator).
8 RDP* ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 External Emergency Stop Function of external emergency stop starts.  Parameter 03-00~03-08 is set to 14 (Function of emergency stop is enabled.)  Remove & shutdown the run command of external emergency stop and reset it to multi-function digital input.
10 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 Zero Speed Stop Warning The operation signal is enabled but frequency command is lower than the minimum output frequency (01-08) and DC brake is disabled.  The frequency command is not set up.  Set up the frequency command.
12 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 Overload of Air Compressor If the inverter’s output current reaches OL4 current level (23-69), OL4 Delay Time (23-70) passed. When the count is reached, the inverter will automatically decelerate to stop and displays a warning signal.  Since the current level (23- 69) is set to be over low, the inverter’s output current is higher than the standard one or compressor’s current is used to be over high.  Check if the compressor load used is higher than the standard one.
14 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 PID feedback signal loss When 23-19 > 0, the inverter will according to feedback pressure is less than (pressure transmitter maximum pressure (23-03) x proportion of loss pressure detection (23-19)) value, if the pressure loss detection time (23-18) passed and 23-78 = 1 (loss of pressure detection function) will jump warning signal  23-19 proportion of loss pressure detection is too big  Feedback sensor install failure or not work normal.。  Check 23-19 setting.  Make sure correct installation and PID feedback signal.
16 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — Autotune error codes — page 484

10.4 Auto-tuning Error

When a fault occurs during auto-tuning of a standard AC motor, the display will show the “AtErr” fault and

the motor stops. The fault information is displayed in parameter 17-11.

Note: The fault contact output does not energize with an auto-tuning fault. Refer to Table 10.4.1, for fault

information during tuning, cause and corrective action.

Table 10.4.1 Auto-tuning fault and corrective actions

StandardACmotorautotunefault displaysAtErr,stopsmotor;17-11detail;faultcontactdoesnotenergize. Codes01,02,03,04,05,07,08,09listed;06notinvented. 01inputdata/currentmismatch;02R1/03leakageinductance/04R2/05Lm/07deadtime sharecauses/solutions. 08rotationaltuningonly:accelerationfailure,time00-14=20seconds,increase00-14/disconnectload. 09noloadcurrent>70%rated,torquereference>100%,otherthanATE01–08. Remediesassupplierclaims,notexecuted.

Autotune error codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.4.1 autotuning error conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations.

Autotune error codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.4.1 autotuning error conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 01

Autotune error codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.4.1 autotuning error conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 02

Autotune error codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.4.1 autotuning error conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 03

Autotune error codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.4.1 autotuning error conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 04

Autotune error codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.4.1 autotuning error conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 05

Autotune error codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.4.1 autotuning error conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 07

Autotune error codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.4.1 autotuning error conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 08

Autotune error codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Table10.4.1 autotuning error conditions. Shared merged causes and solutions retain full physical extent; blank display cells can hold image glyphs recorded in visual display ledger. Source legends govern identity. Full-page notes retain source conflicts,qualifiers and continuations. Row group: 09

Shared source cells (coordinates refer to this table):

Autotune error codes table1 — PDF page 484

Source row Error Description Cause Corrective action
1 01 Motor data input error.  Motor Input data error during auto-tuning.  Inverter output current does not match motor rated current.  Check the motor tuning data (17-00 to 17-09).  Check inverter capacity
2 02 Motor lead to lead resistance R1 tuning error.  Auto-tuning is not completed within the specified time  Auto-tuning results fall outside parameter setting range.  Motor rated current exceeded.  Motor was disconnected.  Check the motor tuning data (17-00 to 17-09).  Check motor connection.  Disconnect motor load. ‧ Check inverter current detection circuit and DCCTs. ‧ Check motor installation.
3 03 Motor leakage inductance tuning error. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 04 Motor rotor resistance R2 tuning error. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 05 Motor mutual inductance Lm tuning error. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 07 Deadtime compensation detection error ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 08 Motor acceleration error (Rotational type auto-tuning only).  Motor fails to accelerate in the specified time (00-14= 20sec).  Increase acceleration time (00-14).  Disconnect motor load.
8 09 Other auto-tuning errors  No load current is higher than 70% of the motor rated current.  Torque reference exceeds 100%.  Errors other than ATE01~ATE08.  Check the motor tuning data (17-00 to 17-09). ‧ Check motor connection.

Manual — PM motor autotuning errors — page 485

10.5 PM Motor Auto-tuning Error

When a fault occurs during auto-tuning of a PM motor, the display will show the “IPErr” fault and the

motor stops. The fault information is displayed in parameter 22-22.

Note: The fault contact output does not energize with an auto-tuning fault. Refer to Table 10.5.1, for fault

information during tuning, cause and corrective action.

Table 10.5.1 Auto-tuning fault and corrective actions for PM motor

PM autotune fault displays IPErr, stops motor;22-22 contains details; fault contact does not energize. Codes01static pole alignment,05circuit timeout,07other tuning,09current mismatch,11parameter tuning/detection timeout. Reserved02–04,06,08,10 retained. Data reference22-02;11solution22-11 too low but cannot exceed100%ofinverter. Distinct from AC AtErr17-11 on484.

PM motor autotuning errors. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

PM motor autotuning errors. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 01

PM motor autotuning errors. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 02~04

PM motor autotuning errors. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 05

PM motor autotuning errors. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 06

PM motor autotuning errors. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 07

PM motor autotuning errors. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 08

PM motor autotuning errors. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 09

PM motor autotuning errors. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 10

PM motor autotuning errors. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 11

Shared source cells (coordinates refer to this table):

PM motor autotuning errors table1 — PDF page 485

Source row Error Description Cause Corrective action
1 01 Magnetic pole alignment tuning failure (static).  Inverter output current does not match motor current.  Check the motor tuning data (22-02).  Check inverter capacity
2 02~04 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 05 Circuit tuning time out.  System abnormality during circuit tuning.  Check for active protection functions preventing auto-tuning.
4 06 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 07 Other motor tuning errors.  Other tuning errors.  Check the motor tuning data (22-02).  Check motor connection.
6 08 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 09 Current out of range during circuit tuning.  Inverter output current does not match motor current.  Check the motor tuning data (22-02).  Check inverter capacity
8 10 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 11 Parameter tuning and detecting time out.  Error relationship between voltage and current.  Check if the setting value of parameter 22-11 is too low, but its value cannot exceed 100% of the inverter.  Check motor connection.

Manual — General motor troubleshooting — page 486

10.6 General troubleshooting

Five status groups: wrong direction, speed not regulated, speed too high/low, unusual speed variation, motor cannot run. Every check/remedy retains merged status. Unstable power remedy distinguishes single-phase AC input reactor from three-phase wiring check. Motor-not-run abnormality and forward/reverse command rows share error-description remedy. Source diagnostic actions only, no performed tests.

General motor troubleshooting. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

General motor troubleshooting. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Motor runs in

wrong

direction

General motor troubleshooting. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: The motor

speed can not

be regulated.

General motor troubleshooting. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Motor running

speed too

high or too

low

General motor troubleshooting. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Motor speed

varies

unusually

General motor troubleshooting. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Motor can not

run

Shared source cells (coordinates refer to this table):

General motor troubleshooting table1 — PDF page 486

Source row Status Checking point Remedy
1 Motor runs in wrong direction Is the wiring for the output terminals correct? Wiring must match U, V, and W terminals of the motor.
2 ⟦null: no independent source value⟧ Is the wiring for forward and reverse signals correct? Check for correct wiring.
3 The motor speed can not be regulated. Is the wiring for the analog frequency inputs correct? Check for correct wiring.
4 ⟦null: no independent source value⟧ Is the setting of operation mode correct? Check the Frequency Source set in parameters 00-05/00-06.
5 ⟦null: no independent source value⟧ Is the load too excessive? Reduce the load.
6 Motor running speed too high or too low Check the motor specifications (poles, voltage…) correct? Confirm the motor specifications.
7 ⟦null: no independent source value⟧ Is the gear ratio correct? Confirm the gear ratio.
8 ⟦null: no independent source value⟧ Is the setting of the highest output frequency correct? Confirm the highest output frequency
9 Motor speed varies unusually Is the load too excessive? Reduce the load.
10 ⟦null: no independent source value⟧ Does the load vary excessively? 1.Minimize the variation of the load. 2.Consider increasing the capacities of the inverter and the motor.
11 ⟦null: no independent source value⟧ Is the input power unstable or is there a phase loss ? 1.Consider adding an AC reactor at the power input side if using single-phase power.
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2.Check wiring if using three-phase power
13 Motor can not run Is the power connected to the correct L1, L2, and L3 terminals? is the charging indicator lit ? 1.Is the power applied? 2.Turn the power OFF and then ON again. 3.Make sure the power voltage is correct. 4.Make sure screws are secured firmly.
14 ⟦null: no independent source value⟧ Is there voltage across the output terminals T1, T2, and T3? Turn the power OFF and then ON again.
15 ⟦null: no independent source value⟧ Is overload causing the motor to stall? Reduce the load so the motor will run.
16 ⟦null: no independent source value⟧ Are there any abnormalities in the inverter? See error descriptions to check wiring and correct if necessary.
17 ⟦null: no independent source value⟧ Is there a forward or reverse run command ? ⟦null: no independent source value⟧
18 ⟦null: no independent source value⟧ Has the analog frequency signal been input? 1.Is analog frequency input signal wiring correct? 2.Is voltage of frequency input correct?
19 ⟦null: no independent source value⟧ Is the operation mode setting correct? Operate through the digital keypad

Manual — Quick troubleshooting flowchart — page 487

10.7 Troubleshooting of the Inverter

10.7.1 Quick troubleshooting of the Inverter

INV Fault

Visually check controller

and Drive boards

*to next page

Check burnt and

damaged parts

Consult with the supplier

Replace fuse

Check according to

displayed fault messages

Replace the pre-charge

resistor

Check terminals and

wiring

Perform detailed check and

consult with the supplier

Is fault known?

Symptoms other than burn

out, damage, or fuse

meltdown in the inverter?

Any Symptoms of burn

out and damage?

Is the main circuit DM

intact?

Fault signal?

Is the fuse intact?

Is the main circuit

I.G.B.T intact?

Any visual

abnormalities?

Are displays and

indicators of the

operating unit working

normally?

Is +5V control voltage

correct?

Is the DC input voltage

controlling the power

correct

Any fault display?

What the message

?

Is LED lit?

Replace control board

and digital operating unit

Is the error eliminated

after replacing control

board?

YES

NO

Apply the power

INVfault→known?YES→symptoms other than burnout/damage/fuse meltdown?YES→faultsignal?YES→check displayed messages;NO→mainDMintact. KnownNO or symptomsNO→burnout/damage?YES→check damaged parts;NO→DMintact. DMNO→supplier;YES→fuseintact?NOreplacefuse/YES→IGBTintact?NOsupplier/YES→visualcontroller/driveboards→visualabnormality?YESsupplier/NOapplypower. Normaldisplay?YES→faultdisplay?YES→whatmessage→checkdisplayedmessages;NO→next488. NormaldisplayNO→LEDlit?NOreplaceprechargeresistor/YES→DCcontrolvoltagecorrect?NOcheckterminals/wiring/YES→+5Vcorrect?NOsupplier/YESreplacecontrolboardandoperator→erroreliminated?YESloopapplypower/NOdetailedcheck+supplier. Retain literal branch labels; supplier flowchart,not validatedrepairsequence.

Manual — Quick troubleshooting continuation — page 488

Check Inverter parameters

Replace the control

board

Perform parameter

initializations

Specify operation

control mode

Does the FWD or REV

LED light flash?

Is the frequency value

displayed on the display?

Are there voltage outputs at

terminals U, V and W

Is there any fault display?

Are output

currents of each

phase even?

The inverter is OK

Perform detailed check and

consult with the supplier.

Does the control Board

function after replacement

YES

NO

From previous page

Set up frequency command

Connect the motor to run

From487→checkparameters→initialize→specifycontrolmode→FWD/REVLEDflashes?NOreplaceboard/YESsetfrequency→frequencydisplay?NOreplaceboard/YESoutputU,V,Wvoltage?NOreplaceboard→boardfunctions?YESconnectmotor/NOdetailedcheck+supplier; voltageYESconnectmotor. Connectmotor→faultdisplay arrow printedNO despiteactionnode. FaultdisplayYES→detailedcheck;NO→phasecurrentseven?NOdetailedcheck/YESinverterOK. All apparently odd branch labels retained.

Manual — Overcurrent overload troubleshooting — page 489

10.7.2 Troubleshooting for OC, OL error displays

The inverter displays OC, OL errors

The inverter output is OK

Is the output current of each

phase even?

Any fault values displayed?

Is there Voltage at U,V and W

output terminals?

Is the output frequency of the

operating unit displayed?

Is FWD LED illuminated?

Is the main circuit I.G.B.T

working

Any visual abnormalities?

Is the current detector

OK?

Any abnormal indications?

Is the inverter operation OK

after board replacement ?

Replace the current

controller

Replace control board

Replace faulty circuit

board

Replace I.G.B.T

The inverter is faulted

(Perform detailed check)

YES

NO

Apply power

Input operation command

Input frequency command

Connect the motor to run

OC/OL→IGBTworking?NOreplaceIGBT/YESvisualabnormality?YESreplacefaultyboard/NOapplypower→abnormalindications?YEScurrentdetectorOK?YESreplacecurrentcontroller/NOreplacecontrolboard. Abnormalindications downward branch unlabelled→inputoperation→FWDLEDlit?NOreplaceboard/YESinputfrequency→outputfreqdisplayed?NOreplaceboard/YESvoltageU,V,W?NOreplaceboard→operationOKafterreplacement?YESconnectmotor/NOdetailedfaultcheck. Voltage downward branch unlabelled→connectmotor→faultvalues?YESdetailedfaultcheck/NOphasecurrentseven?NOdetailedfaultcheck/YESoutputOK. Counterintuitive currentdetectorYESreplacement retained,not flipped.

Manual — Overvoltage lowvoltage troubleshooting — page 490

10.7.3 Troubleshooting for OV, LV error

The inverter displays OV, LV

The inverter’s output is OK

Is the current on all phases

even?

Any abnormal value?

Is there Voltage at T1,T2,T3

output terminals?

Is the output frequency of the

operating unit displayed?

Is FWD LED still illuminated after flash

Is the main circuit fuse intact?

Any visual abnormalities?

Any abnormal indications?

Is the inverter operation OK

after board replacement?

Replace the control

board

Perform detailed check and

consult with the supplier

YES

NO

Connect the motor to run

Input frequency commands

Input operation command

Apply power

Consult with the supplier

Replace the control board

Heading uses LV,earlier tablesUV. Fuseintact?NOsupplier/YESvisualabnormality?YESsupplier/NOapplypower→abnormalindication?YESsupplier/downwardunlabelledinputoperation→FWDLEDstilllitafterflash?NOsupplier/YESfrequencycommand→outputfreqdisplay?NOreplaceboard/YESvoltageT1,T2,T3?NOreplaceboard→operationOKafterreplacement?YESconnectmotor/NOdetailedcheck+supplier; voltageYESconnectmotor. Actionconnectmotor has downwardNO label→abnormalvalue?YESdetailedcheck/NOphasecurrentseven?NOdetailedcheck/YESoutputOK. No repaired branch logic inferred.

Manual — Motor cannot run troubleshooting — page 491

Source limitation for this page: Operation-switch question has missing letters in source; do not infer RUN from adjacent outcome.

10.7.4 The motor can not run

The motor can not run

Is MCCB On?

Can MCCB be turned On?

Are voltages between power

terminals correct?

Is LED lit?

Is the operation switch in

UN?

?

Are there outputs between the U,V,

and W terminals of the motor?

Are outputs between U,V,W the

same?

  1. Motor

  2. Motor faults

  3. Incorrect wiring

INVfault

The operation switch is set to

“RUN” position

1.The power is abnormal

2.Incorrect wiring

Short circuited wiring

NO

YES

MCCBon?YESbypasstonextvoltagecheck;NOcanMCCBturnon?NOshortcircuitwiring/YESvoltagecorrect?NOabnormalpowerorwiring/YESLEDlit?NOINVfault/YESoperationswitchin UN??(source label) ?NOsetRUN/YESoutputbetweenU,V,W?NOINVfault/YESoutputsequal?NOINVfault/YESendpoint1Motor,2Motorfaults,3Incorrectwiring. Missing letters in switch question retained in native evidence; outcomeRUNclear.

Manual — Motor overheating troubleshooting — page 492

10.7.5 Motor Overheating

YE S

Y ES

N O

YES

Is load or current exceeding

the specified value ?

C onsider reducing the load and increasing

the capacities of the inverter and m otor

M otor O verheating

Is m otor running at low speed

for a long tim e?

Is m otor voltage betw een U -

V,V -W ,W -U correct?

Is there any deterrence

preventing cooling of the

m otor

Bad connection betw een drive

and the m otor

S elect the m otor again

IN V faults

C lear the deterrence

C orrect the bad connection

Load/currentexceed?YESreduce load/increaseinverter+motorcapacities;NOlongtimelowspeed?YESselectmotoragain;NOmotorvoltageU-V,V-W,W-Ucorrect?NOINVfault;YEScoolingobstruction?YESclear;NObadconnectiondrive/motor?YEScorrect. NoNOpathafterlastnode printed; no invented outcome.

Manual — Uneven motor operation troubleshooting — page 493

10.7.6 Motor runs unbalanced

NO

YES

Does it happen

during eceleration?

Motor runs unevenly

Is the acceleration

time correct?

Are the output voltages

between U-V,V-W,W-U

balanced?

Is the load fluctuating?

Any mechanical vibration or

gear backlash

Increase the Acc/ Dec time

Reduce the load.Increase

capacities of INV and the motor.

INV faults

Reduce the load fluctuation

or add a flywheel.

Inspect the mechanical

system

Happensduring eceleration (source typo)?YESaccelerationtimecorrect?NOincreaseAcc/Dectime/YESreduceload,increaseINV/motor. FirstNO→outputvoltagesbalanced?NOINVfault/YESloadfluctuating?YESreducefluctuation/addflywheel/NOmechanicalvibration/gearbacklash?YESinspectmechanical/NOINVfault. Supplier diagnostic wording retained.

Manual — Routine and periodic inspection — page 494

10.8 Routine and periodic inspection

To ensure stable and safe operations, check and maintain the inverter at regular intervals.

Use the checklist below to carry out inspection.

Disconnect power after approximately 5 minutes to make sure no voltage is present on the output terminals

before any inspection or maintenance.

Intro prints disconnectpower afterapproximately5minutes toensure novoltage beforeinspection;495 sayspoweroffthenwaitminimum5,445atleast10minutes/chargeindicatorout. Preserveconflict. TablecolumnsDaily and1Year:dailyambient,inputvoltage,fandust,heatsinkdust,ventilation;yearlygrounding,threeconnectionchecks,twowiringchecks,boardcondition,powercomponentdust/terminalresistance,fanvibration. Five sectionheaders. Ambient−10..40°C/50°C with14..104°F/122°F alternatives unqualifiedhere,humiditybelow95%RH. Groundingcriterion200Vclassbelow100ohm;no400Vvalueinvented. Circlemarkversusblank retained.

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Environment & Ground connection

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Ambient

conditions at

the installation

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Installation

Grounding

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Terminals & Wiring

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Connection

terminals

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Wiring

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: voltage

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Input power

voltage

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Circuit boards and components

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Printed circuit

board

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Power

component

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Cooling System

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Cooling fan

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Heat sink

Routine and periodic inspection. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: Ventilation

Path

Shared source cells (coordinates refer to this table):

Routine and periodic inspection table1 — PDF page 494

Source row Items Details Checking period Daily Checking period 1Year Methods Criteria Remedies
1 Environment & Ground connection ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 Ambient conditions at the installation Confirm the temperature and humidity at the machine ◎ ⟦blank source cell⟧ Measure with thermometer and hygrometer Temperature: -10 ~40°C/50°C (14~104°F)/(122°F) Humidity: Below 95%RH Improve the ambient or relocate the drive to a better area.
3 Installation Grounding Is the grounding resistance correct? ⟦blank source cell⟧ ◎ Measure the resistance with a multi-tester 200Vclass: below 100Ω Improve the grounding if needed.
4 Terminals & Wiring ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 Connection terminals Any loose parts or terminals? ⟦blank source cell⟧ ◎ Visual check Check with a screwdriver Correct installation requirement Secure terminals and remove rust
6 ⟦null: no independent source value⟧ Any damage to the base ? ⟦blank source cell⟧ ◎ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ Any corroded Terminals? ⟦blank source cell⟧ ◎ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 Wiring Any broken wires? ⟦blank source cell⟧ ◎ Visual check Correct wiring requirement Rectify as necessary
9 ⟦null: no independent source value⟧ Any damage to the wire insulation? ⟦blank source cell⟧ ◎ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 voltage ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 Input power voltage Is the voltage of the main circuit correct? ◎ ⟦blank source cell⟧ Measure the voltage with a multi-tester Voltage must conform with the spec. Improve input voltage if necessary.
12 Circuit boards and components ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 Printed circuit board Any contamination or damage to printed circuit board? ⟦blank source cell⟧ ◎ Visual check Correct component condition Clean or replace the circuit board
14 Power component Any dust or debris ⟦blank source cell⟧ ◎ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Clean component s
15 ⟦null: no independent source value⟧ Check resistance between terminals ⟦blank source cell⟧ ◎ Measure with a multi-tester No short circuit or broken circuit in three phase output Consult with the supplier
16 Cooling System ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 Cooling fan Unusual vibration and noise? ⟦blank source cell⟧ ◎ Visual and sound check Correct cooling Consult with the supplier
18 ⟦null: no independent source value⟧ Excessive dust or debris ◎ ⟦blank source cell⟧ Visual check ⟦null: no independent source value⟧ Clean the fan
19 Heat sink Excessive dust or debris ◎ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Clean up debris or dust
20 Ventilation Path Is the ventilation path blocked? ◎ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Clear the path

Manual — Maintenance and insulation-test diagrams — page 495

10.9 Maintenance

To ensure long-term reliability, follow the instructions below to perform regular inspection. Turn the power off

and wait for a minimum of 5 minutes before inspection to avoid potential shock hazard from the charge stored

in high-capacity capacitors.

  1. Maintenance Check List.

 Ensure that temperature and humidity around the inverters is as required in the

instruction manual, installed away from any sources of heat and the correct

ventilation is provided..

 For replacement of a failed or damaged inverter consult with the local supplier.

 Ensure that the installation area is free from dust and any other contamination.

 Check and ensure that the ground connections are secure and correct.

 Terminal screws must be tight, especially on the power input and output of the

inverter.

 Do not perform any insulation test on the control circuit.

  1. Insulation test Method .

Single Phase

INV

L1(L)

L3(N)

T1

T2

T3

Dielectric

Withstand

Voltage Test

Power

Source

Motor

Three Phase

L2

PowerOFF thenwaitminimum5minutes;storedcapacitor shockhazard. Checklisttemperature/humidity/ventilation,consultlocalsupplierforreplacement,cleaninstallation,secureground,tightterminalsespeciallypowerI/O;doNOTinsulationtestcontrolcircuit. Singlephase diagramL1(L),L3(N)left,T1/T2/T3rightmotor;threephaseaddsL2. CurvedjumperslinkallpowerterminalsaroundINVoutline; dielectricwithstandtestboxconnectstiedpowerterminalnetandchassisground. Diagrams stillshowpowersourceandmotor connections;noisolationsequence/testvoltage/current/durationgiven. Originalschematicgoverns;notstandaloneenergizedtestinstruction.

Manual — IP20 braking resistor selection — page 496

Chapter 11 Inverter Peripheral devices and Options

11.1 Braking Resistors and Braking Units

Inverters ratings 200V 1~30HP/400V 1~40HP (IP20) and 400V 1~25HP (IP55) have a built-in braking

transistor. For applications requiring a greater braking torque an external braking resistor can be

connected to terminals B1 / P and B2 in protection level of IP20 and to terminals B1 and B2 in

protection level of IP55; for inverter ratings above 200V 40HP/400V 50HP (IP20) or 400V 30HP (IP55),

external braking units (connected to  -  of the inverter) and braking resistors (connected to two ends

of the detection module B-P0) are required.

Table 11.1.1 List of braking resistors and braking units (IP20)

Built-intransistor200V1–30HP/400V1–40HPIP20,400V1–25HPIP55. ExternalresistorB1/PandB2IP20,B1/B2IP55. Proseabove200V40HP/400V50HPIP20or400V30HPIP55requireexternalunitDC+/-andresistorB-P0;tableincludesboundary40/50/30,retainwording. IP20table13columns preserves inputphase/voltage,HP,KW,unitmodel/unitquantity,resistorpart/spec/setquantity,individualresistorspec+L W Hmm,piecequantityandseries/parallel,brakingtorquePeak/Continues10%ED,minohm/minW. 30HPunitmodelandqtyblankversus precedingdashes;retain. Alternate60HP/75HProwsnotdeduplicated.100HPcontinues497.

IP20 braking resistor/unit table11.1.1 beginning;200V phasegroups and alternate selections. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

IP20 braking resistor/unit table11.1.1 beginning;200V phasegroups and alternate selections. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 1 Ø /3

Ø

200V

IP20 braking resistor/unit table11.1.1 beginning;200V phasegroups and alternate selections. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 3 Ø

Shared source cells (coordinates refer to this table):

IP20 braking resistor selection table1 — PDF page 496

Source row Inverter input voltage Inverter HP Inverter KW Braking unit model Braking unit quantity required Braking resistor part number Braking resistor specification Braking resistor quantity required (set) Resistor specification (W/ohm) and dimensions (L*W*H)mm Quantity required (pieces) Braking torque (Peak/Continues)10%ED Minimum resistance (ohm) Minimum resistance (W)
1 1 Ø /3 Ø 200V 1 0.75 - - JNBR-100W200 100W/200Ω 1 100W/200Ω (196*28*60) 1 119% 17Ω 1000W
2 ⟦null: no independent source value⟧ 2 1.5 - - JNBR-200W100 200W/100Ω 1 200W/100Ω (274*35*76) 1 119% 17Ω 1000W
3 ⟦null: no independent source value⟧ 3 2.2 - - JNBR-260W70 260W/70Ω 1 260W/70Ω (274*40*78) 1 115% 17Ω 1000W
4 3 Ø 200V 5 3.7 - - JNBR-450W40 450W/40Ω 1 450W/40Ω (320*40*78) 1 119% 23Ω 780W
5 ⟦null: no independent source value⟧ 7.5 5.5 - - JNBR-600W28 600W/28Ω 1 600W/28Ω (395*40*78) 1 115% 17Ω 1000W
6 ⟦null: no independent source value⟧ 10 7.5 - - JNBR-900W20 900W/20Ω 1 900W/20Ω (470*50*100) 1 119% 17Ω 1000W
7 ⟦null: no independent source value⟧ 15 11 - - JNBR-1R5KW13R6 1500W/13.6Ω 1 1500W/13.6Ω (615*60*110) 1 117% 10.0Ω 1800W
8 ⟦null: no independent source value⟧ 20 15 - - JNBR-2KW10 2000W/10Ω 1 2000W/10Ω (722*65*115) 1 119% 10.0Ω 1800W
9 ⟦null: no independent source value⟧ 25 18.5 - - JNBR-2R4KW8 2400W/8Ω 1 1200W/16Ω (535*60*110) 2 in parallel 119% 6.8Ω 2600W
10 ⟦null: no independent source value⟧ 30 22 ⟦blank source cell⟧ ⟦blank source cell⟧ JNBR-3KW6R8 3000W/6.8Ω 1 1500W/13.6Ω (615*60*110) 2 in parallel 117% 6.8Ω 2600W
11 ⟦null: no independent source value⟧ 40 30 JNTBU-230 2 JNBR-2KW10 2000W/10Ω 2 2000W/10Ω (722*65*115) 1 122% 5.5Ω 3300W
12 ⟦null: no independent source value⟧ 50 37 JNTBU-230 2 JNBR-2KW10 2000W/10Ω 2 2000W/10Ω (722*65*115) 1 102% 5.5Ω 3300W
13 ⟦null: no independent source value⟧ 60 45 JNTBU-230 2 JNBR-3KW6R8 3000W/6.8Ω 2 1500W/13.6Ω (615*60*110) 2 in parallel 120% 5.5Ω 3300W
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-260 1 JNBR-7R5KW4 7500W/4Ω 1 1500W/20Ω 5 in parallel 106% 3.8Ω 4500W
15 ⟦null: no independent source value⟧ 75 55 JNTBU-230 2 JNBR-3KW6R8 3000W/6.8Ω 2 1500W/13.6Ω (615*60*110) 2 in parallel 100% 5.5Ω 3300W
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-260 2 JNBR-4R5KW6R6 4500W/6.6Ω 2 1500W/20Ω (615*60*110) 3 in parallel 106% 3.8Ω 4500W
17 ⟦null: no independent source value⟧ 100 75 JNTBU-230 3 JNBR-3KW6R8 3000W/6.8Ω 3 1500W/13.6Ω (615*60*110) 2 in parallel 110% 5.5Ω 3300W

Manual — IP20 braking selection continuation — page 497

Toprowleftvoltage/HP/KWblank: tablecontinuation following496100HP75kW200Vrow; rawblanknotfilled,associationmarkedpagebreakcontextonly. Top200V175HPuses130KW,400V175HPon498uses132KW. After200Valternatives,explicit3phase400Vsection1..125HP. For400V30HPresistor2inseries;40HP2inparallel;125HP2inseries. Parallel/series and set/piecequantities are separate.125HP90KWcontinues498.

IP20 table11.1.1 continuation;top200Vthenexplicit3phase400V;leadingHP/KWblank. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

IP20 table11.1.1 continuation;top200Vthenexplicit3phase400V;leadingHP/KWblank. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group:

IP20 table11.1.1 continuation;top200Vthenexplicit3phase400V;leadingHP/KWblank. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 3 Ø

400V

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c1, r1c2, r1c3, r2c1, r3c1, r4c1, r5c1, r6c1, r7c1. A header spans across these blank regions in the native text; no header value is propagated into them.

IP20 braking selection continuation table1 — PDF page 497

Source row Inverter input voltage Inverter HP Inverter KW Braking unit model Braking unit quantity required Braking resistor part number Braking resistor specification Braking resistor quantity required (set) Resistor specification (W/ohm) and dimensions (L*W*H)mm Quantity required (pieces) Braking torque (Peak/Continues)10%ED Minimum resistance (ohm) Minimum resistance (W)
1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-260 2 JNBR-6KW5 6000W/5Ω 2 1500W/20Ω (615*60*110) 4 in parallel 107% 3.8Ω 4500W
2 ⟦null: no independent source value⟧ 125 90 JNTBU-230 4 JNBR-3KW6R8 3000W/6.8Ω 4 1500W/13.6Ω (615*60*110) 2 in parallel 116% 5.5Ω 3300W
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-260 2 JNBR-7R5KW4 7500W/4Ω 2 1500W/20Ω (615*60*110) 5 in parallel 110% 3.8Ω 4500W
4 ⟦null: no independent source value⟧ 150 110 JNTBU-230 4 JNBR-3KW6R8 3000W/6.8Ω 4 1500W/13.6Ω (615*60*110) 2 in parallel 100% 5.5Ω 3300W
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-260 2 JNBR-7R5KW4 7500W/4Ω 2 1500W/20Ω (615*60*110) 5 in parallel 92% 3.8Ω 4500W
6 ⟦null: no independent source value⟧ 175 130 JNTBU-230 5 JNBR-3KW6R8 3000W/6.8Ω 5 1500W/13.6Ω (615*60*110) 2 in parallel 106% 5.5Ω 3300W
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-260 3 JNBR-6KW5 6000W/5Ω 3 1500W/20Ω (615*60*110) 4 in parallel 94% 3.8Ω 4500W
8 3 Ø 400V 1 0.75 - - JNBR-100W750 100W/750Ω 1 100W/750Ω (196*28*60) 1 126% 100Ω 700W
9 ⟦null: no independent source value⟧ 2 1.5 - - JNBR-200W400 200W/400Ω 1 200W/400Ω (274*35*76) 1 120% 100Ω 700W
10 ⟦null: no independent source value⟧ 3 2.2 - - JNBR-300W250 300W/250Ω 1 300W/250Ω (320*40*78) 1 126% 68Ω 1000W
11 ⟦null: no independent source value⟧ 5 3.7 - - JNBR-500W150 500W/150Ω 1 500W/150Ω (400*50*100) 1 126% 60Ω 1200W
12 ⟦null: no independent source value⟧ 7.5 5.5 - - JNBR-700W110 700W/110Ω 1 700W/110Ω (530*50*100) 1 117% 60Ω 1200W
13 ⟦null: no independent source value⟧ 10 7.5 - - JNBR-900W80 900W/80Ω 1 900W/80Ω (470*50*100) 1 120% 43Ω 1600W
14 ⟦null: no independent source value⟧ 15 11 - - JNBR-1R6KW50 1600W/50Ω 1 1600W/50Ω (615*60*110) 1 126% 43Ω 1600W
15 ⟦null: no independent source value⟧ 20 15 - - JNBR-2KW40 2000W/40Ω 1 2000W/40Ω (722*65*115) 1 120% 39Ω 1800W
16 ⟦null: no independent source value⟧ 25 18.5 - - JNBR-2R4KW32 2400W/32Ω 1 1200W/64Ω (535*60*110) 2 in parallel 120% 20.5Ω 3500W
17 ⟦null: no independent source value⟧ 30 22 - - JNBR-3KW27R2 3000W/27.2Ω 1 1500W/13.6Ω (615*60*110) 2 in series 118% 13.5Ω 5200W
18 ⟦null: no independent source value⟧ 40 30 - - JNBR-4KW20 4000W/20Ω 1 2000W/40Ω (722*65*115) 2 in parallel 120% 13.5Ω 5200W
19 ⟦null: no independent source value⟧ 50 37 JNTBU-430 2 JNBR-2R4KW32 2400W/32Ω 2 1200W/64Ω (535*60*110) 2 in parallel 122% 19.2Ω 3800W
20 ⟦null: no independent source value⟧ 60 45 JNTBU-430 2 JNBR-3KW27R2 3000W/27.2Ω 2 1500W/13.6Ω (615*60*110) 2 in series 120% 19.2Ω 3800W
21 ⟦null: no independent source value⟧ 75 55 JNTBU-430 2 JNBR-4KW20 4000W/20Ω 2 2000W/40Ω (722*65*115) 2 in parallel 129% 19.2Ω 3800W
22 ⟦null: no independent source value⟧ 100 75 JNTBU-430 3 JNBR-3KW27R2 3000W/27.2Ω 3 1500W/13.6Ω (615*60*110) 2 in series 110% 19.2Ω 3800W
23 ⟦null: no independent source value⟧ 125 90 JNTBU-430 3 JNBR-4KW20 4000W/20Ω 3 2000W/10Ω (722*65*115) 2 in series 118% 19.2Ω 3800W

Manual — IP20 braking selection continuation — page 498

Toprowvoltage/HP/KWblank following497400V125HP90KW;no invented cellvalues. Remaining3phase400V150..800HP,alternatives kept. ModelstringsincludeJNTBU-4120andTBU-4120;notnormalized.175HP132KWherevs200V130KW497.250HP11200W7.2ohmrowbrakingtorque106%hastrailingdot. Minimum7.6ohmwhileactual7.2ohm appears topand250HP; apparent supplierconflictretained. Entirephysicalrows retained not deduped byresistorpart.

IP20 table11.1.1 continuation3phase400V;leadingHP/KWblank. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

IP20 table11.1.1 continuation3phase400V;leadingHP/KWblank. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group:

Shared source cells (coordinates refer to this table):

Blank continuation bodies at r1c1, r1c2, r1c3, r2c1, r3c1, r4c1, r5c1, r6c1, r7c1, r8c1, r9c1, r10c1, r11c1, r12c1, r13c1, r14c1, r15c1, r16c1, r17c1, r18c1, r19c1, r20c1, r21c1. A header spans across these blank regions in the native text; no header value is propagated into them.

IP20 braking selection continuation table1 — PDF page 498

Source row Inverter input voltage Inverter HP Inverter KW Braking unit model Braking unit quantity required Braking resistor part number Braking resistor specification Braking resistor quantity required (set) Resistor specification (W/ohm) and dimensions (L*W*H)mm Quantity required (pieces) Braking torque (Peak/Continues)10%ED Minimum resistance (ohm) Minimum resistance (W)
1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-4120 1 JNBR-11R2KW7R2 11200W/7.2Ω 1 1600W/50Ω (615*60*110) 7 in parallel 107% 7.6Ω 9000W
2 ⟦null: no independent source value⟧ 150 110 JNTBU-430 4 JNBR-4KW20 4000W/20Ω 4 2000W/10Ω (722*65*115) 2 in series 129% 19.2Ω 3800W
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-4120 2 JNBR-6R4KW12R5 6400W/12.5Ω 2 1600W/50Ω (615*60*110) 4 in parallel 102% 7.6Ω 9000W
4 ⟦null: no independent source value⟧ 175 132 JNTBU-430 4 JNBR-4KW20 4000W/20Ω 4 2000W/10Ω (722*65*115) 2 in series 113% 19.2Ω 3800W
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-4120 2 JNBR-8KW10 8000W/10Ω 2 1600W/50Ω (615*60*110) 5 in parallel 108% 7.6Ω 9000W
6 ⟦null: no independent source value⟧ 215 160 JNTBU-430 5 JNBR-4KW20 4000W/20Ω 5 2000W/10Ω (722*65*115) 2 in series 115% 19.2Ω 3800W
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-4120 2 JNBR-9R6KW8R3 9600W/8.3Ω 2 1600W/50Ω (615*60*110) 6 in parallel 106% 7.6Ω 9000W
8 ⟦null: no independent source value⟧ 250 185 JNTBU-430 6 JNBR-4KW20 4000W/20Ω 6 2000W/10Ω (722*65*115) 2 in series 118% 19.2Ω 3800W
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ TBU-4120 2 JNBR-11R2KW7R2 11200W/7.2Ω 2 1600W/50Ω (615*60*110) 7 in parallel 106% 7.6Ω 9000W
10 ⟦null: no independent source value⟧ 300 220 JNTBU-430 6 JNBR-4KW20 4000W/20Ω 6 2000W/10Ω (722*65*115) 2 in series 102% 19.2Ω 3800W
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-4120 3 JNBR-9R6KW8R3 9600W/8.3Ω 3 1600W/50Ω (615*60*110) 6 in parallel 112% 7.6Ω 9000W
12 ⟦null: no independent source value⟧ 375 280 JNTBU-430 8 JNBR-4KW20 4000W/20Ω 8 2000W/10Ω (722*65*115) 2 in series 107% 19.2Ω 3800W
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-4120 3 JNBR-9R6KW8R3 9600W/8.3Ω 3 1600W/50Ω (615*60*110) 6 in parallel 105% 7.6Ω 9000W
14 ⟦null: no independent source value⟧ 425 315 JNTBU-430 9 JNBR-4KW20 4000W/20Ω 9 2000W/10Ω (722*65*115) 2 in series 107% 19.2Ω 3800W
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ JNTBU-4120 4 JNBR-8KW10 8000W/10Ω 4 1600W/50Ω (615*60*110) 5 in parallel 104% 7.6Ω 9000W
16 ⟦null: no independent source value⟧ 535 400 JNTBU-430 10 JNBR-4KW20 4000W/20Ω 10 2000W/10Ω (722*65*115) 2 in series 96% 19.2Ω 3800W
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ TBU-4120 5 JNBR-8KW10 8000W/10Ω 5 1600W/50Ω (615*60*110) 5 in parallel 113% 7.6Ω 9000W
18 ⟦null: no independent source value⟧ 670 500 JNTBU-430 12 JNBR-4KW20 4000W/20Ω 12 2000W/10Ω (722*65*115) 2 in series 94% 19.2Ω 3800W
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ TBU-4120 7 JNBR-8KW10 8000W/10Ω 7 1600W/50Ω (615*60*110) 5 in parallel 112% 7.6Ω 9000W
20 ⟦null: no independent source value⟧ 800 600 JNTBU-430 14 JNBR-4KW20 4000W/20Ω 14 2000W/10Ω (722*65*115) 2 in series 92% 19.2Ω 3800W
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ TBU-4120 8 JNBR-8KW10 8000W/10Ω 8 1600W/50Ω (615*60*110) 5 in parallel 108% 7.6Ω 9000W

Manual — IP55 braking selection — page 499

IP55 煞車電阻及煞車檢出模組一覽表

Note 1: Keep sufficient space between inverter, braking unit and braking resistor and ensure proper cooling

is provided for.

IP55heading Chinese retained.3phase400V1..100HP15rows. Resistor columns erroneouslyheadedV/HP/KW/Model although cellscontainpartnumber,W/ohm,setquantity,spec/dimensions. Keep literal sourceheaders andflag; do not silentlysubstituteIP20headings. Source differences fromIP20minimumresistance,power,brakingunitquantities retained. Note1adequatespace/cooling betweeninverter,unit,resistor. HeaderPeak/Continues10%ED notseparatepeakandcontinuousfigures.

IP55 3phase400V braking selections;literal erroneous resistor headers retained. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

IP55 3phase400V braking selections;literal erroneous resistor headers retained. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 3 Ø

400V

Shared source cells (coordinates refer to this table):

IP55 braking selection table1 — PDF page 499

Source row Inverter V Inverter HP Inverter KW Braking unit model Braking unit quantity required Braking resistor V [literal source header] Braking resistor HP [literal source header] Braking resistor KW [literal source header] Braking resistor Model [literal source header] Braking resistor quantity required Braking torque (Peak/Continues)10%ED Minimum resistance (ohm) Minimum resistance (W)
1 3 Ø 400V 1 0.75 - - JNBR-100W750 100W/750Ω 1 100W/750Ω (196*28*60) 1 126% 100Ω 700W
2 ⟦null: no independent source value⟧ 2 1.5 - - JNBR-200W400 200W/400Ω 1 200W/400Ω (274*35*76) 1 120% 100Ω 700W
3 ⟦null: no independent source value⟧ 3 2.2 - - JNBR-300W250 300W/250Ω 1 300W/250Ω (320*40*78) 1 126% 100Ω 700W
4 ⟦null: no independent source value⟧ 5 3.7 - - JNBR-500W150 500W/150Ω 1 500W/150Ω (400*50*100) 1 126% 68Ω 1000W
5 ⟦null: no independent source value⟧ 7.5 5.5 - - JNBR-700W110 700W/110Ω 1 700W/110Ω (530*50*100) 1 117% 68Ω 1000W
6 ⟦null: no independent source value⟧ 10 7.5 - - JNBR-900W80 900W/80Ω 1 900W/80Ω (470*50*100) 1 120% 41Ω 1800W
7 ⟦null: no independent source value⟧ 15 11 - - JNBR-1R5KW50 1500W/50Ω 1 1500W/50Ω (615*60*110) 1 126% 41Ω 1800W
8 ⟦null: no independent source value⟧ 20 15 - - JNBR-2KW40 2000W/40Ω 1 2000W/40Ω (722*65*115) 1 120% 20.5Ω 3500W
9 ⟦null: no independent source value⟧ 25 18.5 - - JNBR-2R4KW32 2400W/32Ω 1 1200W/64Ω (535*60*110) 2 in parallel 120% 20.5Ω 3500W
10 ⟦null: no independent source value⟧ 30 22 JNTBU-430 1 JNBR-3KW27R2 3000W/27.2Ω 1 1500W/13.6Ω (615*60*110) 2 in series 118% 19.2Ω 3800W
11 ⟦null: no independent source value⟧ 40 30 JNTBU-430 1 JNBR-4KW20 4000W/20Ω 1 2000W/40Ω (722*65*115) 2 in parallel 120% 19.2Ω 3800W
12 ⟦null: no independent source value⟧ 50 37 JNTBU-430 2 JNBR-2R4KW32 2400W/32Ω 2 1200W/64Ω (535*60*110) 2 in parallel 122% 19.2Ω 3800W
13 ⟦null: no independent source value⟧ 60 45 JNTBU-430 2 JNBR-3KW27R2 3000W/27.2Ω 2 1500W/13.6Ω (615*60*110) 2 in series 120% 19.2Ω 3800W
14 ⟦null: no independent source value⟧ 75 55 JNTBU-430 2 JNBR-4KW20 4000W/20Ω 2 2000W/40Ω (722*65*115) 2 in parallel 129% 19.2Ω 3800W
15 ⟦null: no independent source value⟧ 100 75 JNTBU-430 3 JNBR-3KW27R2 3000W/27.2Ω 3 1500W/13.6Ω (615*60*110) 2 in series 110% 19.2Ω 3800W

Manual — AC line reactor selection — page 500

11.2 AC Line Reactors

An AC line reactor can be used for any of the following:

-

Capacity of power system is much larger than the inverter rating.

Inverter mounted close to the power system (in 33ft / 10 meters).

Reduce harmonic contribution (improve power factor) back to the power line.

Protect inverter input diode front-end by reducing short-circuit current.

Minimize overvoltage trips due to voltage transients.

Please select the AC line reactor based on the inverter rating according to the following table.

Table11.2.1 List of AC Line Reactors

Supplieruseslargepowersystemrelativeinverter,proximity33ft/10m,harmonics,powerfactor,inputdiodeprotection/transients. Table37rows:1/3phase200V1–3HP;3phase200V5–175HP;3phase400Vgroups1/2,3,5/7.5,...375/425. SlashHPgroupsretainedasprinted,notfractionsorroundednominal. mH andAexplicit. Continued501.

AC input reactors:phase/voltagegroups preserved;mH/Aexplicit. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

AC input reactors:phase/voltagegroups preserved;mH/Aexplicit. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 1/3

200V

AC input reactors:phase/voltagegroups preserved;mH/Aexplicit. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 3

400V

Shared source cells (coordinates refer to this table):

Adjacent source context — repeated to preserve continuation:

AC line reactor selection table1 — PDF page 500

Source row Voltage HP Inductance Value (mH) Rated Current (A)
1 1/3 200V 1 1.7 15
2 ⟦null: no independent source value⟧ 2 1.1 20
3 ⟦null: no independent source value⟧ 3 0.85 25
4 3 200V 5 0.7 17
5 ⟦null: no independent source value⟧ 7.5 0.46 25
6 ⟦null: no independent source value⟧ 10 0.34 40
7 ⟦null: no independent source value⟧ 15 0.24 50
8 ⟦null: no independent source value⟧ 20 0.18 70
9 ⟦null: no independent source value⟧ 25 0.15 85
10 ⟦null: no independent source value⟧ 30 0.13 95
11 ⟦null: no independent source value⟧ 40 0.09 140
12 ⟦null: no independent source value⟧ 50 0.07 170
13 ⟦null: no independent source value⟧ 60 0.06 210
14 ⟦null: no independent source value⟧ 75 0.05 250
15 ⟦null: no independent source value⟧ 100 0.04 310
16 ⟦null: no independent source value⟧ 125 0.03 390
17 ⟦null: no independent source value⟧ 150 0.03 490
18 ⟦null: no independent source value⟧ 175 0.02 550
19 3 400V 1/2 4.9 5
20 ⟦null: no independent source value⟧ 3 3.7 6.5
21 ⟦null: no independent source value⟧ 5/7.5 1.7 15
22 ⟦null: no independent source value⟧ 10 1.2 25
23 ⟦null: no independent source value⟧ 15 0.88 30
24 ⟦null: no independent source value⟧ 20 0.65 40
25 ⟦null: no independent source value⟧ 25 0.53 50
26 ⟦null: no independent source value⟧ 30 0.46 55
27 ⟦null: no independent source value⟧ 40 0.35 70
28 ⟦null: no independent source value⟧ 50 0.28 90
29 ⟦null: no independent source value⟧ 60 0.23 110
30 ⟦null: no independent source value⟧ 75 0.2 130
31 ⟦null: no independent source value⟧ 100 0.14 180
32 ⟦null: no independent source value⟧ 125 0.12 210
33 ⟦null: no independent source value⟧ 150 0.1 260
34 ⟦null: no independent source value⟧ 175/215 0.07 360
35 ⟦null: no independent source value⟧ 250 0.06 400
36 ⟦null: no independent source value⟧ 300 0.05 550
37 ⟦null: no independent source value⟧ 375/425 0.04 720

Manual — AC reactor continuation and limitations — page 501

Note: AC reactors listed in this table can only be used for the inverter input side. Do not connect AC reactor

to the inverter output side. 200V class 60~175HP (IP20), 400V class 100HP~425HP (IP20 standard H

& C type), 400V class 125HP~425HP (IP20 enhanced E & G type) and 5HP~100HP (IP55) have

built-in DC reactors. If required by the application an AC reactor may be added.

Threecontinuationrows535/670/800HP all0.02mH,862/1050/1200A;voltagecellblank,continuationafter500400Vsectionbutnotfilled. ACreactorsinputsideonly,notoutput. BuiltinDCreactor:200V60–175HPIP20;400V100–425HPIP20standardH&C;400V125–425HPIP20enhancedE&G;5–100HPIP55. Noextrapolationtounlistedcapacity/model. ACreactorcanbeaddedifapplicationrequires.

AC input reactor continuation;voltageblank atpagebreak. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

AC input reactor continuation;voltageblank atpagebreak. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group:

Shared source cells (coordinates refer to this table):

Adjacent source context — repeated to preserve continuation:

AC reactor continuation and limitations table1 — PDF page 501

Source row Voltage HP Inductance Value (mH) Rated Current (A)
1 ⟦blank source cell⟧ 535 0.02 862
2 ⟦null: no independent source value⟧ 670 0.02 1050
3 ⟦null: no independent source value⟧ 800 0.02 1200

Manual — Input noise filters and zero-phase core — page 502

11.3 Input Noise Filters

A. Input Noise Filter on Specifications & Ratings

Install a noise filter on power supply side to eliminate noise transmitted between the power line and the

inverter. The inverter noise filter shown in Table 11.3.1 and Table 11.3.2 below meets the EN61800-3

class A specification. 400V inverter class models can be ordered with integrated noise filter.

Table 11.3.1 Input Noise Filter Specifications and Ratings (IP20)

B. Input or Output Noise Filter (EMI Suppression Zero Phase Core)

-

Part Number: 4H000D0250001

Select a matched ferrite core to suppress EMI noise according to the required power rating and wire

size.

The ferrite core can attenuate high frequencies in the range of 100 kHz to 50 MHz, as shown in figure

11.4.1 below, and therefore should minimize the RFI generated by the inverter.

The zero-sequence noise ferrite core can be installed either on the input side or on the output side. The

wire around the core for each phase should be wound by following the same convention and in one

direction. The more turns without resulting in saturation the better the attenuation. If the wire size is too

large to be wound, all the wiring can be grouped and put through several cores together in one direction.

IP20inputfiltertable19physicalrows;1phase200V,3phase200V,3phase400Vmaintained. Dimensioncolumncontains3numbersbutunit/ordernotexplicitonthispage;notassumedfrombrakingtable. ClaimEN61800-3classAand400Vintegratedfilterorderoption aresourceclaims,notcertificationverification. ReferencesTable11.3.2andFigure11.4.1unresolvedhere,next503caption11.3.1. Corepart4H000D0250001,sourceattenuation100kHz–50MHz;matchedrating/wire;inputoroutputallowedforcore,unlikeACreactor;samewindingdirectionandavoid saturation;oversizewiremaypassthroughmultiplecores.

IP20 input noise filter selection;dimensions unit/order unstatedhere. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

IP20 input noise filter selection;dimensions unit/order unstatedhere. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 1200V

IP20 input noise filter selection;dimensions unit/order unstatedhere. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: 3

200V

400V

Shared source cells (coordinates refer to this table):

Input noise filters and zero-phase core table1 — PDF page 502

Source row Input voltage HP Model Dimension
1 1200V 1HP/2HP/3HP FN3258-30-47 240*50*85
2 3 200V 1HP/2HP/3HP FN3258-16-45 264*45*70
3 ⟦null: no independent source value⟧ 5HP/7.5HP FS32124-23-99 290*50*85
4 ⟦null: no independent source value⟧ 10HP/15HP FS32123-40-99 330*85*90
5 ⟦null: no independent source value⟧ 20HP FS32125-56-99 318*80*135
6 ⟦null: no independent source value⟧ 25HP/30HP FS32125-79-99 360*95*90
7 ⟦null: no independent source value⟧ 40HP/50HP FS32125-138-99 320*226.5*86
8 ⟦null: no independent source value⟧ 60HP/75HP FS32125-211-99 320*226.5*86
9 ⟦null: no independent source value⟧ 100HP/125HP FS32125-312-99 320*226.5*86
10 ⟦null: no independent source value⟧ 150HP/175HP FN3270H-1000-99 610*230*132
11 3 400V 1HP/2HP/3HP JN5-FLT-8A-02 102*130*92
12 ⟦null: no independent source value⟧ 5HP/7.5HP/10HP JN5-FLT-19A 123*141*92
13 ⟦null: no independent source value⟧ 15HP/20HP JN5-FLT-33A 132*206*124
14 ⟦null: no independent source value⟧ 25HP/30HP/40HP JN5-FLT-63A 127*260*131
15 ⟦null: no independent source value⟧ 50HP/60HP/75HP JN5-FLT-112A 186*284*128
16 ⟦null: no independent source value⟧ 100HP/125HP FS32126-165-99 320*226.5*86
17 ⟦null: no independent source value⟧ 150HP/175HP/215HP/250HP FS32126-361-99 320*226.5*86
18 ⟦null: no independent source value⟧ 300HP/375HP/425HP FN3270H-1000-99 610*230*132
19 ⟦null: no independent source value⟧ 535HP/670HP/800HP FN3270H-1000-99 610*230*132

Manual — EMI core attenuation and wiring — page 503

Source limitation for this page: Rightmost graph frequency exponent is clipped in source; no endpoint inferred.

-40

-30

-20

-10

Interference Frequency (kHz)

atteuatoin value (dB)

Attenuation (dB)

Figure 11.3.1 Frequency attenuation characteristics (10 windings case)

Figure 11.3.2 Example of EMI Suppression Zero Phase Core Application

Note: All the wiring of phases U/T1, V/T2, W/T3 must pass through the same zero-phase core without

crossing over.

Induction Motor

Ground

Figure11.3.1 tenwindingscase:verticalattenuationdB0,−10,−20,−30,−40;horizontalinterferencefrequencykHzlogticks10^1,10^2,10^3,10^4;rightmostlabelclippedshowing10withoutcompleteexponent. Curvefallsfromnear0tonear−30thenrisesright;notdigitizedandnoexactpointsinferred. Figure11.3.2allthreeU/T1,V/T2,W/T3conductorspassthroughsamezero-phasecorewithoutcrossover;inverterandinductionmotorseparatelygrounded. Exampleoutputsideplacement,notuniversalwiringapproval.

Manual — IP20 input current and fuse ratings — page 504

11.4 Input Current and Fuse Specifications

IP20 200V class

IP20 400V class

IP20 200V18modelrows,1–175HP;firstthree1phaseinput9.4/14.1/19.6,subsequentXretainednotzero. Separate3phaseinputandfusecolumns. IP20400V22rows1–375HPcontinued505. Models retain□placeholderand(F)variants.100%ratedoutputcurrentlabelisnotaratingforalloverloadmodes;current/fuseunitnotspelledoutinheaderonthispage. No cross-enclosuremerge.

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2001-□

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2002-□

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2003-□

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2005-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2008-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2010-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2015-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2020-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2025-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2030-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2040-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2050-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2060-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2075-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2100-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2125-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2150-□3

IP20 200V current/fuse;separate1phase/3phasecolumns. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-2175-□3

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4001-□3

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4002-□3

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4003-□3

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4005-□3(F)

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4008-□3(F)

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4010-□3(F)

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4015-□3(F)

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4020-□3(F)

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4025-□3(F)

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4030-□3(F)

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4040-□3(F)

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4050-□3(F)

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4060-□3(F)

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4075-□3(F)

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4100-□3

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4125-□3

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4150-□3

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4175-□3

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4215-□3

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4250-□3

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4300-□3

IP20 400V current/fuse continued505. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4375-□3

IP20 input current and fuse ratings table1 — PDF page 504

Source row Model Horse power KVA 100% of rated output current Rated input current (3) Fuse rating (3) Rated input current (1)
1 F510-2001-□ 1 1.9 5.0 5.4 20 9.4
2 F510-2002-□ 2 2.9 7.5 8.1 30 14.1
3 F510-2003-□ 3 4.0 10.6 11.4 50 19.6
4 F510-2005-□3 5 5.5 14.5 16 50 X
5 F510-2008-□3 7.5 8.0 22 22.3 50 X
6 F510-2010-□3 10 11.4 30 31.6 63 X
7 F510-2015-□3 15 15 42 41.7 100 X
8 F510-2020-□3 20 21 56 60.9 120 X
9 F510-2025-□3 25 26 69 75 150 X
10 F510-2030-□3 30 30 80 85.9 200 X
11 F510-2040-□3 40 42 110 119.6 250 X
12 F510-2050-□3 50 53 138 150 300 X
13 F510-2060-□3 60 64 169 186 400 X
14 F510-2075-□3 75 76 200 232 500 X
15 F510-2100-□3 100 95 250 275 600 X
16 F510-2125-□3 125 119 312 343 700 X
17 F510-2150-□3 150 152 400 440 800 X
18 F510-2175-□3 175 172 450 495 800 X

IP20 input current and fuse ratings table2 — PDF page 504

Source row Model Horse power KVA 100% of rated output current Rated input current Fuse rating
1 F510-4001-□3 1 2.6 3.4 3.7 10
2 F510-4002-□3 2 3.1 4.1 4.5 16
3 F510-4003-□3 3 4.1 5.4 5.9 16
4 F510-4005-□3(F) 5 7.0 9.2 9.6 16
5 F510-4008-□3(F) 7.5 8.5 12.1 11.6 25
6 F510-4010-□3(F) 10 13.3 17.5 18.2 40
7 F510-4015-□3(F) 15 18 23 24 50
8 F510-4020-□3(F) 20 24 31 32.3 63
9 F510-4025-□3(F) 25 29 38 41.3 80
10 F510-4030-□3(F) 30 34 44 47.8 100
11 F510-4040-□3(F) 40 41 58 63 120
12 F510-4050-□3(F) 50 55 73 78.3 150
13 F510-4060-□3(F) 60 67 88 95.7 200
14 F510-4075-□3(F) 75 79 103 112 250
15 F510-4100-□3 100 111 145 159 300
16 F510-4125-□3 125 126 168 181 400
17 F510-4150-□3 150 159 208 229 500
18 F510-4175-□3 175 191 250 275 600
19 F510-4215-□3 215 226 296 325 700
20 F510-4250-□3 250 250 328 361 700
21 F510-4300-□3 300 332 435 478 800
22 F510-4375-□3 375 393 515 566 800

Manual — IP20 continuation and IP55 fuse ratings — page 505

IP55 400V class

Fuse type: Choose semiconductor fuse to comply with UL.

Voltage Range:

For 200V class inverter, use 300V class fuse.

For 400V class inverter, use 500V class fuse.

TopfourIP20400V425/535/670/800HPcontinue504. BelowIP55400V15rows1–100HP,exactC3(F)N4andC3N4models. CommonHPdoesnotimplyequalinput/fuse/outputvalues:IP2040HPoutput58 vsIP5554;IP2050HPinput78.3 vsIP5568. Source choose semiconductor fuse tocomplywithUL;200Vinverter300Vclassfuse,400Vinverter500Vclassfuse. Requirementsare notproofactualcertificateorinstallationcompliance.

IP20 400V continuationfrom504. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

IP20 400V continuationfrom504. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4425-□3

IP20 400V continuationfrom504. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4535-□3

IP20 400V continuationfrom504. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4670-□3

IP20 400V continuationfrom504. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4800-□3

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4001-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4002-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4003-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4005-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4008-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4010-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4015-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4020-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4025-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4030-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4040-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4050-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4060-C3(F)N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4075-C3N4

IP55 400V current/fuse:distinctN4variants. Exact source values and column/row scope apply. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: F510-4100-C3N4

IP20 continuation and IP55 fuse ratings table1 — PDF page 505

Source row Model Horse power KVA 100% of rated output current Rated input current Fuse rating
1 F510-4425-□3 425 446 585 643 1000
2 F510-4535-□3 535 526 700 750 1400
3 F510-4670-□3 670 640 875 913 1800
4 F510-4800-□3 800 732 960 1044 2200

IP20 continuation and IP55 fuse ratings table2 — PDF page 505

Source row Model Horse power KVA 100% of rated output current Rated input current Fuse rating
1 F510-4001-C3(F)N4 1 2.6 3.4 3.7 10
2 F510-4002-C3(F)N4 2 3.1 4.1 4.5 16
3 F510-4003-C3(F)N4 3 4.1 5.4 5.9 16
4 F510-4005-C3(F)N4 5 7.0 9.2 9.6 20
5 F510-4008-C3(F)N4 7.5 8.5 12.1 11.6 20
6 F510-4010-C3(F)N4 10 13.3 17.5 18.2 30
7 F510-4015-C3(F)N4 15 18 23 24 40
8 F510-4020-C3(F)N4 20 24 31 34 50
9 F510-4025-C3(F)N4 25 29 38 41 70
10 F510-4030-C3(F)N4 30 34 44 48 80
11 F510-4040-C3(F)N4 40 41 54 59 100
12 F510-4050-C3(F)N4 50 55 72 68 125
13 F510-4060-C3(F)N4 60 67 88 96 150
14 F510-4075-C3N4 75 79 103 112 200
15 F510-4100-C3N4 100 111 145 140 250

Manual — LCD keypad option — page 506

11.5 Other options

A. JN5-OP-F02 (LCD keypad)

LED keypad is standard for F510 IP20 model and it is optional for LCD keypad. Refer to the

following figure.

JN5-OP-F02LCDkeypad;LEDstandardF510IP20,LCDoptional. ImageindicatorsFAULT,FWD,REV,SEQ,REF;REMOTEbracketoverSEQ/REF. KeysLOC/REM,up,DSP/FUN,leftRESET,down,READ/ENTER,RUNgreen,STOPred. Fourcornermountingholes. No imageapparentdimensions measured.

Manual — Remote keypad cables and blank panel — page 507

B. Blank operation box and digital operator wire

‧Digital operator can detach inverter itself and users apply digital operator wire for remote

operation. Wires have four specifications, inclusive of 1m, 2m, 3m, and 5m.

‧For digital operation remote control, separately blank operation box installed in the original

position of the operator to prevent the entry of foreign matter.

Remote control installation diagram blank operation box

Detachedoperatorremote cablelengths1,2,3,5m. Originalslotblankpanelpreventsforeignmatter;JN5-OP-A03BlackPanel. Wire-onlyJN5-CB-01M/02M/03M/05M;wire+blankoperationboxJN5-CB-01MK/02MK/03MK/05MK. Imageconnectsremovedkeypadtodriveandblankplateatpreviousopening. Nineproductrowsretainedseparately; no inferredLCDcompatibilityfromLEDlabel.

Remote keypad cables and blank panel. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

Remote keypad cables and blank panel. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: blank

operation

box

Remote keypad cables and blank panel. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: LED digital

operator

wire

with blank

Shared source cells (coordinates refer to this table):

Remote keypad cables and blank panel table1 — PDF page 507

Source row Name Model specification
1 blank operation box JN5-OP-A03 Black Panel

Remote keypad cables and blank panel table2 — PDF page 507

Source row Name Model specification
1 LED digital operator wire with blank operation box JN5-CB-01MK 1m
2 ⟦null: no independent source value⟧ JN5-CB-02MK 2m
3 ⟦null: no independent source value⟧ JN5-CB-03MK 3m
4 ⟦null: no independent source value⟧ JN5-CB-05MK 5m

Remote keypad cables and blank panel table3 — PDF page 507

Source row Name Model specification
1 LED digital operator wire JN5-CB-01M 1m
2 ⟦null: no independent source value⟧ JN5-CB-02M 2m
3 ⟦null: no independent source value⟧ JN5-CB-03M 3m
4 ⟦null: no independent source value⟧ JN5-CB-05M 5m

Manual — IP20 and IP55 keypad dimensions — page 508

Dimensions of LED/LCD keypad (IP20):

Figure 11.5.2 Dimensions of LED keypad

Dimensions of LCD keypad (IP55):

Figure 11.5.3 Dimensions of LCD keypad (IP55)

Twoindependentfront/side/backdrawings. UpperheadingLED/LCDIP20butcaptionLEDonly;lowerLCDIP55. Bothfront85.0width130.0height,mountspacing74.0×119.0;side15.5body+9.9projection. Upperonly4-M3callout;backconnector20.6width21.5height,leftoffset9.0,bottomoffset21.2. Lowerbackconnector23.0width22.5height,leftoffset7.8,bottomoffset20.8;no4-M3labelrepeatedlower. Unitsnotprintedonpage; no unitinferredoroveralldepthaddition. Separate25boundedprintedlabelsrecorded. Originalgeometrygoverns.

85.0 (printed label). Unit not stated on page. Exact IP20 geometry and source drawing govern applicability.

74.0 (printed label). Unit not stated on page. Exact IP20 geometry and source drawing govern applicability.

130.0 (printed label). Unit not stated on page. Exact IP20 geometry and source drawing govern applicability.

119.0 (printed label). Unit not stated on page. Exact IP20 geometry and source drawing govern applicability.

4-M3 (printed label). Unit not stated on page. Exact IP20 geometry and source drawing govern applicability.

15.5 (printed label). Unit not stated on page. Exact IP20 geometry and source drawing govern applicability.

9.9 (printed label). Unit not stated on page. Exact IP20 geometry and source drawing govern applicability.

21.5 (printed label). Unit not stated on page. Exact IP20 geometry and source drawing govern applicability.

21.2 (printed label). Unit not stated on page. Exact IP20 geometry and source drawing govern applicability.

9.0 (printed label). Unit not stated on page. Exact IP20 geometry and source drawing govern applicability.

20.6 (printed label). Unit not stated on page. Exact IP20 geometry and source drawing govern applicability.

85.0 (printed label). Unit not stated on page. Exact IP55 geometry and source drawing govern applicability.

74.0 (printed label). Unit not stated on page. Exact IP55 geometry and source drawing govern applicability.

130.0 (printed label). Unit not stated on page. Exact IP55 geometry and source drawing govern applicability.

119.0 (printed label). Unit not stated on page. Exact IP55 geometry and source drawing govern applicability.

15.5 (printed label). Unit not stated on page. Exact IP55 geometry and source drawing govern applicability.

9.9 (printed label). Unit not stated on page. Exact IP55 geometry and source drawing govern applicability.

22.5 (printed label). Unit not stated on page. Exact IP55 geometry and source drawing govern applicability.

20.8 (printed label). Unit not stated on page. Exact IP55 geometry and source drawing govern applicability.

7.8 (printed label). Unit not stated on page. Exact IP55 geometry and source drawing govern applicability.

23.0 (printed label). Unit not stated on page. Exact IP55 geometry and source drawing govern applicability.

Manual — Relay output pump card and copy unit — page 509

C. 1 to 8 Pump Card

Refer to instruction manual of the option card to install.

JN5-IO-8DO Card: 8 Relay Output Card.

Terminals of JN5-IO-8DO:

Wiring of JN5-IO-8DO (Example):

D. Copy Unit (JN5-CU)

The copy unit is used to copy an inverter parameter setup to another inverter.

RY1

RY2

CM1

RY3

RY4

CM2

RY5

RY6

CM3

RY7

RY8

CM4

JN5-IO-8DO8relayoutputcard;installationreferoptionmanual. RY1–RY8Aterminaloutputs,CM1–CM4commonterminaloutputs. Diagramtop-to-bottomRY1,RY2,CM1,RY3,RY4,CM2,RY5,RY6,CM3,RY7,RY8,CM4;drawnlefthandverticalbustiescommons andswitchcommons;do notinferisolatedpairsfromnames. PCBphotoproductillustration,notseparaterating. JN5-CUcopiesparametersbetweeninverters;connectionillustrationtopoperatorport. VisiblecopyunitindicatorsSEQ,FRQ,FWD,REV,Hz/RPM,VOLT,FUN,AMP;keysINV>COPY,COPY>INV,MODE,left,RUN/CLEAR,STOP/RESET,OK/ENTER. No crossmodelcompatibilityclaiminferred.

Relay output pump card and copy unit. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval.

Relay output pump card and copy unit. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: RY1~RY8

Relay output pump card and copy unit. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Full-page visual notes retain supplier conflicts and pagebreaks; no inferred engineering approval. Row group: CM1~CM4

Relay output pump card and copy unit table1 — PDF page 509

Source row Terminal Description
1 RY1~RY8 Relay1~Relay8 A terminal output
2 CM1~CM4 Common terminal output

Manual — USB to RS485 cable — page 510

E. RJ45 to USB connecting Cable (1.8m)

JN5-CM-USB has the function of converting USB communication format to RS485 to achieve the

inverter communication control being similar with PC or other control equipment with USB port.

 Exterior:

 Connecting:

JN5-CM-USB converts USB to RS485; headline RJ45 to USB cable1.8m. Exterior drawing actually prints180.0±1.5 for cable span,20 USB housing height,12 USB plug length,45.5 USB housing length,12.3 RJ45 length,11.6 RJ45 height. Units not printed on drawing; do not change180.0 to1800 or infer mm. Magnified source and second rendering confirm label. Connecting image shows cable at exposed control area; no unsupported pinout inferred.

180.0±1.5 (printed label). Drawing unit unstated; headline1.8m preserved separately.

20 (printed label). Drawing unit unstated; headline1.8m preserved separately.

12 (printed label). Drawing unit unstated; headline1.8m preserved separately.

45.5 (printed label). Drawing unit unstated; headline1.8m preserved separately.

12.3 (printed label). Drawing unit unstated; headline1.8m preserved separately.

11.6 (printed label). Drawing unit unstated; headline1.8m preserved separately.

Manual — Communication option modules — page 511

11.6 Communication Options

(a) PROFIBUS communication interface module (JN5-CM-PDP)

For wiring example and communication setup refer to JN5-CM-PDP communication option manual.

(b) DEVICENET communication interface module (JN5-CM-DNET)

For wiring example and communication setup refer to JN5-CM-DNET communication option

manual.

(c) CANopen communication interface module (JN5-CM-CAN)

For wiring example and communication setup refer to JN5-CM-CAN communication option manual.

(d) TCP-IP communication interface module (JN5-CM-TCPIP)

For wiring example and communication setup refer to JN5-CM-TCPIP communication option

Four separate standard options: JN5-CM-PDP PROFIBUS; JN5-CM-DNET DEVICENET; JN5-CM-CAN CANopen; JN5-CM-TCPIP TCP-IP. Each refers its own option manual. Distinct from CMHI high-speed modules on512; no equivalence assumed.

Manual — Protective covers and expansion cards — page 512

11.7 Others Options

A. Protective Cover

If inverter is around the environment of dust or metal shavings, it is recommended to purchase the

protective covers positioned on both sides of the inverter to prevent unknown objects from

invading.

Protective Cover Installation of Protective Cover Inverter with Protective Cover

B. High-speed communication expansion card & I/O expansion card &

Middle layer case

If frame 1~4 of the inverter need to install high-speed communication expansion card or

I/O expansion card, middle layer case is necessary, which is option, to install between the

top cover and the bottom case, for adding extra space to install the expansion card.

Table 1. Expansion card model number

Table 2. Middle layer case model number

Protective covers fit both sides for dust/metal-shaving environment; only frames1,2,4 listed withJN5-CR-A01/A02/A04; no frame3 product invented. Frame1–4 high-speed or I/O card requires optional middle layer between top cover and bottom case. Four expansion rows CMHI-PDP/CAN/ECAT andIO-2DO1AI; references6.9–6.12 conflict with actual11.9+chapter headings, retained. Middle casesMD-A01..A04 map frames1..4. Diagrams illustrate covers on side vents; not universal ingress certification.

Protective covers and expansion cards. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

Protective covers and expansion cards. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1

Protective covers and expansion cards. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2

Protective covers and expansion cards. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 4

Protective covers and expansion cards. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: PROFIBUS high-speed comm.

Protective covers and expansion cards. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: CANopen high-speed comm.

Protective covers and expansion cards. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: EtherCAT high-speed comm.

Protective covers and expansion cards. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: I/O expansion

Protective covers and expansion cards. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 3

Protective covers and expansion cards table1 — PDF page 512

Source row Frame Model
1 1 JN5-CR-A01
2 2 JN5-CR-A02
3 4 JN5-CR-A04

Protective covers and expansion cards table2 — PDF page 512

Source row Expansion card type Model number Reference chapter
1 PROFIBUS high-speed comm. JN5-CMHI-PDP 6.9
2 CANopen high-speed comm. JN5-CMHI-CAN 6.10
3 EtherCAT high-speed comm. JN5-CMHI-ECAT 6.11
4 I/O expansion JN5-IO-2DO1AI 6.12

Protective covers and expansion cards table3 — PDF page 512

Source row Frame Middle layer case model number
1 1 JN5-MD-A01
2 2 JN5-MD-A02
3 3 JN5-MD-A03
4 4 JN5-MD-A04

Manual — Middle layer and NEMA1 kits — page 513

Middle layer case outline Middle layer case installation diagram

Communication card installation diagram

11.8 NEMA1 Kit

If NEMA1 or IP20 protective level is necessary to upgrade, it is recommended to purchase the

NEMA1 kit positioned on top and bottom sides of the inverter. The drawings installed in the inverter,

please refer to chapter 3.7.

Comm. card

Middle layer inserted between drive body and operator/front cover; communication card locations shown separately for compact and larger chassis. Stray Chinese fragment under left drawing not treated as specification. NEMA1kit top/bottom positioning; frames6/7/8/9 mapJN5-NK-A06/A07/A08/A09,reference3.7. Wording NEMA1 or IP20 upgrade does not prove installed certification or rating for other frames.

Middle layer and NEMA1 kits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

Middle layer and NEMA1 kits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 6

Middle layer and NEMA1 kits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 7

Middle layer and NEMA1 kits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 8

Middle layer and NEMA1 kits. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 9

Middle layer and NEMA1 kits table1 — PDF page 513

Source row Frame Model
1 6 JN5-NK-A06
2 7 JN5-NK-A07
3 8 JN5-NK-A08
4 9 JN5-NK-A09

Manual — PROFIBUS high-speed module specifications — page 514

11.9 PROFIBUS high speed communication expansion card

11.9.1 Communication hardware and data structure

This product is the PROFIBUS high-speed communication expansion module; it can perform

remote setting and communication functions through the PROFIBUS bus. It is used on the TECO

A510s/F510 AC motor driver (hereinafter referred to as the “driver”), and allows the driver to

operate on the PROFIBUS network.

11.9.2 Product specifications

PROFIBUS ports

AC motor driver port

A510s/F510 applicability explicitly stated. DB-9,9.6Kbit/s to12Mbit/s auto transmission detection; control-sideCN2 supplies power and SPI high-speed TECO protocol. Keep standardCM-PDP and high-speedCMHI-PDP distinct.

PROFIBUS high-speed module specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

PROFIBUS high-speed module specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Connector

PROFIBUS high-speed module specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Transmission

rate

PROFIBUS high-speed module specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Network

protocols

method

PROFIBUS high-speed module specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Terminal

functions

PROFIBUS high-speed module specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Communication

PROFIBUS high-speed module specifications table1 — PDF page 514

Source row Item Specifications
1 Connector DB-9
2 Transmission rate 9.6Kbit/s to 12Mbit/s (automatic detection of transmission rate)
3 Network protocols PROFIBUS communication protocol

PROFIBUS high-speed module specifications table2 — PDF page 514

Source row Item Specifications
1 Connector Control board CN2 connector
2 Transmission method SPI high speed communication
3 Terminal functions 1. The communication module communicates with the AC motor driver through this interface. 2. The AC motor driver provides power to the communication module through this interface.
4 Communication protocols TECO communication protocol

Manual — PROFIBUS pinout and address switches — page 515

11.9.3 Installation instructions

PROFIBUS network connection

Definitions of PROFIBUS DP communication port pins are as shown in the figure below.

As shown in the figure below, ID addresses (1~125) correspond to SW1 b1~b7.

Network address switch setting range: 1~125 (0, 128~255 cannot be used).

DB9 pictured orientation pins1–5 right bottom-to-top,6–9 left bottom-to-top. Pin3B-line RXD/TXD-P;8A-line RXD/TXD-N;5DGND2M. Pins1–2,4,6–7,9not assigned; dash notground. Network address1..125,tablebitorderb1..b7:1000000→1,0100000→2,1100000→3,1011111→125;b8no function. Footerexcludes0,128..255 butdoesnotexplicitlyaccount126/127althoughrange1..125; retain gap,do notassumeallowed. IllustrationDIPONdirectionnotreversebitstring.

PROFIBUS pinout and address switches. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

PROFIBUS pinout and address switches. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group:

r1c1: Source continuation context: Header-spanning image-only DB9 connector region; pin geometry separately transcribed, not blank engineering data.

r2c1: Source continuation context: Header-spanning image-only DB9 connector region; pin geometry separately transcribed, not blank engineering data.

r3c1: Source continuation context: Header-spanning image-only DB9 connector region; pin geometry separately transcribed, not blank engineering data.

r4c1: Source continuation context: Header-spanning image-only DB9 connector region; pin geometry separately transcribed, not blank engineering data.

r5c1: Source continuation context: Header-spanning image-only DB9 connector region; pin geometry separately transcribed, not blank engineering data.

r6c1: Source continuation context: Header-spanning image-only DB9 connector region; pin geometry separately transcribed, not blank engineering data.

r7c1: Source continuation context: Header-spanning image-only DB9 connector region; pin geometry separately transcribed, not blank engineering data.

PROFIBUS pinout and address switches. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Network

address

setting

PROFIBUS pinout and address switches. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: No function

Shared source cells (coordinates refer to this table):

PROFIBUS pinout and address switches table1 — PDF page 515

Source row Connector drawing region Pin Definition Description
1 ⟦null: no independent source value⟧ 1~2 Not assigned -
2 ⟦null: no independent source value⟧ 3 RXD/TXD-P (B- Line) Receive/Send data -P
3 ⟦null: no independent source value⟧ 4 Not assigned -
4 ⟦null: no independent source value⟧ 5 DGND (2M) Data reference potential
5 ⟦null: no independent source value⟧ 6~7 Not assigned -
6 ⟦null: no independent source value⟧ 8 RXD/TXD-N (A-Line) Receive/Send data -N
7 ⟦null: no independent source value⟧ 9 Not assigned -

PROFIBUS pinout and address switches table2 — PDF page 515

Source row Function DIP switch position DIP switch status Description
1 Network address setting b1~b7 1000000 Network address is 1
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0100000 Network address is 2
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1100000 Network address is 3
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ............ …….
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1011111 Network address is 125
6 No function b8 - -

Manual — PROFIBUS termination and module status LEDs — page 516

PROFIBUS bus terminal resistor

The first and last station of the PROFIBUS bus must be connected to the bus, and

the bus terminal resistor must be turned on.

11.9.4 LED indicator descriptions

The module has two dual-color LED indicators built-in used to quickly diagnose and monitor

the communication statuses between the module itself and the bus.

Module status LED (RUN LED & ERR LED)

Used to monitor whether the equipment is operating normally.

Termination diagram5V→390ohm→B+ node→220ohm→A− node→390ohm→V−. Two SW DIP-2 switches connect bias network to bus B+/A−; ON arrow upward in drawing. First/laststations terminationON. PhotoONlabel left,levers1/2; original physical orientation governs. Module LED six states:off,orange,red1Hz,red4Hz,green4Hz,solidgreen. Red1Hzdrivecommunicationerror;red4Hzaddress;green4HzDPnotestablished. Not generalized to CANopen.

PROFIBUS termination and module status LEDs. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

PROFIBUS termination and module status LEDs. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Does not light

up

PROFIBUS termination and module status LEDs. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Orange light

lights up

PROFIBUS termination and module status LEDs. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Red light flashes

(1 Hz)

(4 Hz)

PROFIBUS termination and module status LEDs. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Green light

flashes (4 Hz)

PROFIBUS termination and module status LEDs table2 — PDF page 516

Source row Indicator statuses Description
1 Does not light up Power not supplied
2 Orange light lights up Communication with the frequency converter not established
3 Red light flashes (1 Hz) Communication error with the frequency converter
4 Red light flashes (4 Hz) Flip-switch ID address error
5 Green light flashes (4 Hz) Power supply normal but DP communication not established
6 Green light lights up DP communication normal

Manual — PROFIBUS network LEDs and parameters — page 517

Network status LED (COMM LED)

Used to monitor the operability of the communication module PROFIBUS network.

11.9.5 Driver parameter setting descriptions

Users must first confirm related parameter settings on the driver in order to ensure that the

communication module can connect normally.

COMM off means DPnotestablished,solidgreen normal. Required source settings00-02=2operation,00-05=3frequency communicationcontrol. Do not replace values using unrelated module or illustrative response on521.

PROFIBUS network LEDs and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

PROFIBUS network LEDs and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Does not light

up

PROFIBUS network LEDs and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Green light

lights up

PROFIBUS network LEDs and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 00-02

PROFIBUS network LEDs and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 00-05

PROFIBUS network LEDs and parameters table1 — PDF page 517

Source row Indicator statuses Description
1 Does not light up DP communication not established
2 Green light lights up DP communication established and normal

PROFIBUS network LEDs and parameters table2 — PDF page 517

Source row Parameters Parameter name Settings Settings descriptions
1 00-02 Operation command source 2 Communication control
2 00-05 Frequency command source 3 Communication control

Manual — PROFIBUS PPO structure and register mapping — page 518

11.9.6 Connection instructions

PPO communication

PZD Structure default

User parameters of the communication module configured through the GSD file. Default

values of the PZD structure are as follows:

STW1 Control word; mapped to the MODBUS address 0x2501 of the driver.

HSW Main setting value; mapped to the MODBUS address 0x2502 of the driver.

ZSW1 Status word; mapped to the MODBUS address 0x2520 of the driver.

HIW Main actual value; mapped to the MODBUS address 0x2524 of the driver.

PLC Master station driver slave station

PZD3/ PZD4: Not used.

Driver slave station PLC master station

Driver output status; mapped to the MODBUS addresses 0x2520~0x252F of the driver.

The default values of PZD3/PZD4/PZD5/PZD6 are set as follows:

PZD3: Default multi-function terminal block on/off status; mapped to the MODBUS

address 0x2522 of the driver.

PZD4: Default output current; mapped to the MODBUS address 0x2527 of the driver.

PZD5: Default output current; mapped to the MODBUS address 0x2521 of the driver.

PZD6: Default output current; mapped to the MODBUS address 0x2528 of the driver.

PPO1PKW4words+PZD1–2;PPO2PKW4+PZD1–6;PPO3PZD1–2only;PPO4PZD1–6only;PPO5PKW4+PZD1–10. Blank non-bar regions are not supported words. PKWword1PKE,word2IND,words3/4PWE. PZD1STW/ZSW,PZD2HSW/HIW. DefaultsSTW1→2501,HSW→2502,ZSW1→2520,HIW→2524. PLC→drivePZD3/4notused;drive→PLCPZD3→2522DI,PZD4→2527current,PZD5→2521labelledcurrent,PZD6→2528labelledcurrent. Later532/533identify2521error and2528warning, source contradiction retained. GSDconfigurable mapping; no fixed universal mapping inferred.

PKW 4 words; PZD1 through PZD2. Exact graphic support-bar span, not configured device proof.

PKW 4 words; PZD1 through PZD6. Exact graphic support-bar span, not configured device proof.

PKW 0 words; PZD1 through PZD2. Exact graphic support-bar span, not configured device proof.

PKW 0 words; PZD1 through PZD6. Exact graphic support-bar span, not configured device proof.

PKW 4 words; PZD1 through PZD10. Exact graphic support-bar span, not configured device proof.

PROFIBUS PPO structure and register mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

PROFIBUS PPO structure and register mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: PPO1; graphical bar spans only printed supported words, other regions absent.

PROFIBUS PPO structure and register mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: PPO2; graphical bar spans only printed supported words, other regions absent.

PROFIBUS PPO structure and register mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: PPO3; graphical bar spans only printed supported words, other regions absent.

PROFIBUS PPO structure and register mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: PPO4; graphical bar spans only printed supported words, other regions absent.

PROFIBUS PPO structure and register mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: PPO5; graphical bar spans only printed supported words, other regions absent.

Shared source cells (coordinates refer to this table):

PROFIBUS PPO structure and register mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: PKW: Parameter address/value

PROFIBUS PPO structure and register mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: PZD: Process data

PROFIBUS PPO structure and register mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: PKE: Parameter address

PROFIBUS PPO structure and register mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: IND: Subindex

PROFIBUS PPO structure and register mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: PWE: Parameter value

PROFIBUS PPO structure and register mapping table1 — PDF page 518

Source row PKW word1 PKE PKW word2 IND PKW word3 PWE PKW word4 PWE PZD1 STW/ZSW PZD2 HSW/HIW PZD3 PZD4 PZD5 PZD6 PZD7 PZD8 PZD9 PZD10
1 PPO1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 PPO2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ PPO3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ PPO4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 PPO5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

PROFIBUS PPO structure and register mapping table2 — PDF page 518

Source row Source row label Source value or description1
1 PKW: Parameter address/value STW: Control word
2 PZD: Process data ZSW: Status word
3 PKE: Parameter address HSW: Main settings
4 IND: Subindex HIW: Main actual value
5 PWE: Parameter value ⟦blank source cell⟧

Manual — PROFIBUS control and status characters — page 519

11.9.7 Meanings of each character

Control character

Status character

15 control rows cover0..F including combined4–5reserved;16statusrows. ControlFONvalue1 but0blank,notOFFinferred. Status6literalModel440;ESeqNotFromComm. Keep bitrange and hexadecimalA..F labels, distinct from laterdecimalerrorcodes.

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 0

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 3

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 4~5

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 6

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 7

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 8

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 9

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: A

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: B

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: C

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: D

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: E

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: F

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 4

PROFIBUS control and status characters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 5

PROFIBUS control and status characters table1 — PDF page 519

Source row Bit Description 1 0
1 0 Operation command Operate Stop
2 1 Reverse command Reverse Forward
3 2 External error Error -
4 3 Error reset Reset -
5 4~5 Reserved - -
6 6 Multi-function terminal S1 ON OFF
7 7 Multi-function terminal S2 ON OFF
8 8 Multi-function terminal S3 ON OFF
9 9 Multi-function terminal S4 ON OFF
10 A Multi-function terminal S5 ON OFF
11 B Multi-function terminal S6 ON OFF
12 C Multi-function terminal S7 ON OFF
13 D Multi-function terminal S8 ON OFF
14 E Controller mode ON OFF
15 F Communication setting torque command ON ⟦blank source cell⟧

PROFIBUS control and status characters table2 — PDF page 519

Source row Bit Meaning 1 0
1 0 Operation status Operate Stop
2 1 Direction status Reverse Forward
3 2 Frequency converter operation preparation status Preparation complete Not yet prepared
4 3 Error Abnormal Normal
5 4 Warning ON OFF
6 5 Zero speed ON OFF
7 6 Model 440 ON OFF
8 7 Frequency reached ON OFF
9 8 Any frequency reached ON OFF
10 9 Frequency detection 1 ON OFF
11 A Frequency detection 2 ON OFF
12 B Low voltage ON OFF
13 C Frequency converter no output ON OFF
14 D Frequency not according to communication ON OFF
15 E SeqNotFromComm ON OFF
16 F Over-torque ON OFF

Manual — PROFIBUS PKW structure and request response codes — page 520

11.9.8 PKW regional access parameters

The driver can provide request and response information. Due to the request and

response mechanism, the master station must send requests until a communication

response is received. The 4 characters of the PKW region are as follows:

PKE

Bit 0~11 (PNU): Parameter address/MODBUS address that includes related parameters.

Parameter address/MODBUS address: Please refer to the MODBUS communication

protocol description chapter in the driver manual for the register numbers, registers and

data format that corresponds to the operation parameters.

Bit 12~15 (AK): Includes the identification characters of requests or responses.

Request character AK

PLC master station driver slave station

Response character AK

Driver slave station PLC master station

Word1PKE:bits15..12AK,bits11..0PNU. Word2INDreserved. Word3PWE1:bits15..8reserved,bits7..0faultnumber. Word4PWE2read/writeparameters. RequestAK0none,1read,2modify;response0none,1processed,7cannotprocess. Response table stillheadedRequestIdentifier; preserved. Master repeats requests untilresponse; no implementation performed.

PROFIBUS PKW structure and request response codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

PROFIBUS PKW structure and request response codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Word 1

PROFIBUS PKW structure and request response codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: bit

PROFIBUS PKW structure and request response codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Word 2

PROFIBUS PKW structure and request response codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Word 3

PROFIBUS PKW structure and request response codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Word 4

Shared source cells (coordinates refer to this table):

PROFIBUS PKW structure and request response codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 0

PROFIBUS PKW structure and request response codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1

PROFIBUS PKW structure and request response codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2

PROFIBUS PKW structure and request response codes. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 7

PROFIBUS PKW structure and request response codes table1 — PDF page 520

Source row Source row label Source value or description1 Source value or description2 Source value or description3
1 Word 1 Parameter ID(PKE) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 bit 15 12 AK 11 0 Parameter number(PNU) ⟦null: no independent source value⟧
3 Word 2 IND Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 Word 3 PWE1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 bit 15 8 Reserved ⟦null: no independent source value⟧ 7 0 Fault number
6 Word 4 PWE2 Read/Write parameters ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

PROFIBUS PKW structure and request response codes table2 — PDF page 520

Source row Request Identifier Description
1 0 No request
2 1 Read parameter value
3 2 Modify parameter value

PROFIBUS PKW structure and request response codes table3 — PDF page 520

Source row Request Identifier Description
1 0 No response
2 1 Request parameter value processed
3 7 Request parameter value cannot process

Manual — PROFIBUS errors and PKW example — page 521

Error character

If the request parameter value was not processed, then the error codes that will be kept in

the low-bit PWE1 set are as follows:

PWE

Driver parameters are sent through PWE2 (4th word). In the following example, PWEI (3rd

word) must be set as 0 in the PROFIBUS master station.

Example of the PKW mechanism:

For example: Read parameters 00-05 (frequency command source).

Read the values of 00-05; first set the request identification character as 1, and then refer

to the MODBUS communication protocol description chapter in the driver manual to find

out that the address of 00-05 is 0x0005, then the data sequences are as follows:

PLC master station driver slave station: 1000 0005 0000 0000

Driver slave station PLC master station: 1000 0005 0000 0004

Errorcodes0nonexistent,1currentstatuscannotR/W,2outofrange,101otherSPtimeout. PWE2fourthworddata,PWE1thirdword0inexample. Read00-05address0x0005 example request1000 0005 0000 0000,response1000 0005 0000 0004. Tablesput0005inINDword2 while520placesparameteraddressinPKEPNUword1 andINDreserved. Preserveboth withoutfix. Response4illustrative notrequiredcommunicationselection3on517.

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 0

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 101

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1st word

(PKE)

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2nd word

(IND)

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 3rd word

(PWE1)

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 4th word

(PWE2)

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1st word (PKE)

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2nd word (IND)

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 3rd word (PWE1)

PROFIBUS errors and PKW example. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 4th word (PWE2)

PROFIBUS errors and PKW example table1 — PDF page 521

Source row Error code Description
1 0 Parameter does not exist
2 1 The current status parameter cannot be read/written
3 2 Parameter value not within range
4 101 Other SP communication error occurred, such as: response timeout

PROFIBUS errors and PKW example table2 — PDF page 521

Source row Word designation Request value
1 1st word (PKE) 1000
2 2nd word (IND) 0005
3 3rd word (PWE1) 0000
4 4th word (PWE2) 0000

PROFIBUS errors and PKW example table3 — PDF page 521

Source row Word designation Response value
1 1st word (PKE) 1000
2 2nd word (IND) 0005
3 3rd word (PWE1) 0000
4 4th word (PWE2) 0004

Manual — PROFIBUS troubleshooting and GSD — page 522

11.9.9 Troubleshooting

There are two indicators on top of the PROFIBUS communication module; when malfunction occurs,

the cause of the malfunction can be confirmed based on the indicator statuses, and troubleshoot

the error by following the descriptions below.

Indicator troubleshooting

Module status LED

Network status LED

11.9.10 GSD File

When using the Profibus communication module, if the GSD description file

(JN5-CMHI-PDP_V (latest version).GSD) is needed, please download it from the TECO

official website or request for it from your purchasing sales channel.

Moduleoffpower;alternatingred/greenself-check requiresconnectionparameters19200,8,N,1;greenflashstandby notconnecteddrive. Networkoffhas two rows(powernot supplied orstandbyhostnotconnected). These descriptions differ from516green4HzDPnotestablished andSPI description514;retain,notmergeprotocolsettings. GSD filenameJN5-CMHI-PDP_V(latestversion).GSD fromsupplierwebsite/sales; latestversionnotverifiedhere.

PROFIBUS troubleshooting and GSD. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

PROFIBUS troubleshooting and GSD. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Does not light

up

PROFIBUS troubleshooting and GSD. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Red and green

light flashes

alternately

PROFIBUS troubleshooting and GSD. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Green light

flashes

Shared source cells (coordinates refer to this table):

PROFIBUS troubleshooting and GSD table1 — PDF page 522

Source row Indicator statuses Status name Troubleshooting method
1 Does not light up Power not supplied to the communicat ion module 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver.
2 Red and green light flashes alternately Self-check 1. The host is under self-check; if it flashes continuously, disconnect the power and then reconnect it. 2. Confirm whether the driver communication connection parameters are properly set (19200, 8, N, 1)
3 Green light flashes the communicat ion module Standby 1. Not yet connected with the driver.

PROFIBUS troubleshooting and GSD table2 — PDF page 522

Source row Indicator statuses Status name Description
1 Does not light up Power not supplied 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver.
2 ⟦null: no independent source value⟧ Standby 1. Not yet connected with the PROFIBUS host terminal.

Manual — CANopen specifications — page 523

11.10 CANopen high speed communication expansion card

11.10.1 Communication hardware and data structure

This product is the CANopen high-speed communication expansion module; it can perform remote

setting and communication functions through the CANopen bus. It can only be used with the TECO

A510s/F510 AC motor driver (hereinafter referred to as the “driver”), and allow the driver to operate

on the CANopen network.

11.10.2 Product specifications

CANopen ports

AC motor driver port

11.10.3 Installation instructions

Communication module contact description

As shown in the figure below, A – Terminal block (TB1)

B, C – Mounting holes

D - RUN LED

E - ERR LED

F – Control board connector (CN2)

OnlyA510s/F510 per source.5-pin5.08mmpluggable connector;rates10/20/50/125/250/500/800kbpsand1Mbps;CN2SPIpower+TECOprotocol. LegendAterminalTB1,B/Cmountingholes,DRUN, EERR,FcontrolCN2. Nextphoto524labelsconnectorE notF; no repaired attribution.

CANopen specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

CANopen specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Connector

CANopen specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Transmission

rate

CANopen specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Network

protocols

method

CANopen specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Terminal

functions

CANopen specifications. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Communication

CANopen specifications table1 — PDF page 523

Source row Item Specifications
1 Connector 5-pin open pluggable connector; pin spacing 5.08mm
2 Transmission rate 10kbps, 20kbps, 50kbps, 125kbps, 250kbps, 500kbps, 800kbps, 1Mbps
3 Network protocols CANopen communication protocol

CANopen specifications table2 — PDF page 523

Source row Item Specifications
1 Connector Control board CN2 connector
2 Transmission method SPI high speed communication
3 Terminal functions 1. The communication module communicates with the AC motor driver through this interface. 2. The AC motor driver provides power to the communication module through this interface.
4 Communication protocols TECO communication protocol

Manual — CANopen connectors and switches — page 524

Terminal block definition

As shown in the figure below, the contact definitions in the order from left to right are

GND, CAN_L, NC, CAN_H and NC.

ID address setting description

As shown in the figure below, ID addresses (1~127) correspond to SW1 b1~b7.

Transmission rate corresponds to SW2 b1~b3.

PhotoAterminal,B/Cnearholes,DLEDregion,Econnectorinset;Fnotvisible. Contradicts523EERR/Fconnector legend. Terminalleft→rightGND,CAN_L,NC,CAN_H,NC; blanklabelslots inphoto matchNCprose,notpowerconnections. SW1eightphysicalswitches,addressusesb1..b7;SW2fourphysicalswitches,rateusesb1..b3. Noadditionalfunctionassignedunusedswitches.

Manual — CANopen DIP settings — page 525

Network address switch setting range: 1~127 (0, 128~255 cannot be used).

Transmission rate switch setting range: 0~7 (8~15 cannot be used).

11.10.4 LED indicator descriptions

The module has RUN (green) and ERR (red) indicators built-in used to quickly diagnose

and monitor the communication statuses between the module itself and the bus.

Networktableorder7654321 (b7..b1),oppositereadingorderPROFIBUS515.0000000invalid,1/2/3examplebinary,1111110→126,1111111→127. Range1..127,0and128..255invalid. SW2b3..b1rates00010K,00120K,01050K,011125K,100250K,101500K,110800K,1111M. Range0..7,8..15invalid. RUNgreen/ERRred. No omittedbitstatesinvented.

CANopen DIP settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

CANopen DIP settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Network

address

Setting

CANopen DIP settings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: CANopen

Transmission

rate setting

Shared source cells (coordinates refer to this table):

CANopen DIP settings table1 — PDF page 525

Source row Function DIP switch position DIP switch status 7654321 Description
1 Network address Setting SW1 b7—b1 0000000 Cannot be used
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0000001 Network address is 1
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0000010 Network address is 2
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 0000011 Network address is 3
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ............ ............
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1111110 Network address is 126
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1111111 Network address is 127
8 CANopen Transmission rate setting SW2 b3—b1 000 10K
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 001 20K
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 010 50K
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 011 125K
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 100 250K
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 101 500K
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 110 800K
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 111 1M

Manual — CANopen LED status and parameters — page 526

Module status LED (RUN LED)

Used to monitor whether the equipment is operating normally.

Error status LED (ERR LED)

Used to monitor the operability of the communication module CANopen network.

11.10.5 Driver parameter setting descriptions

Users must first confirm related parameter settings on the driver in order to ensure that

the communication module can connect normally.

RUNoffinitialnopower,continuousflashpreoperation,singleflashstop,solidgreenoperation. ERRoffnormal,singleflashpacketwarning,doubleflashguard/heartbeaterror,solidredbusclosed.00-02=2,00-05=3communication. No flashfrequency invented from PROFIBUS.

CANopen LED status and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

CANopen LED status and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Does not light

up

CANopen LED status and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Continuous

flashing

CANopen LED status and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Single flash

CANopen LED status and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Green light

lights up

CANopen LED status and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Double flash

CANopen LED status and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: Red light lights

CANopen LED status and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 00-02

CANopen LED status and parameters. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 00-05

CANopen LED status and parameters table1 — PDF page 526

Source row Indicator statuses Status name Description
1 Does not light up Initial status Power not supplied
2 Continuous flashing Pre-operation Preparation status
3 Single flash Stop Stopping
4 Green light lights up Operation Operating

CANopen LED status and parameters table2 — PDF page 526

Source row Indicator statuses Status name Description
1 Does not light up No error Operating
2 Single flash Warning Packet error
3 Double flash Error Guard/Heartbeat error
4 Red light lights up Disconnected Bus closed

CANopen LED status and parameters table3 — PDF page 526

Source row Parameters Parameter name Settings Settings descriptions
1 00-02 Operation command source 2 Communication control
2 00-05 Frequency command source 3 Communication control

Manual — CANopen SDO byte structures — page 527

11.10.6 Connection instructions

Service data object (SDO)

This module supports 1 SDO server, which means it can provide SDO service, and the

SDO uses the sending and receiving COB-ID of the predefined connection, 0x580 +

NodeID (sending) and 0x600 + NodeID (receiving).

Each SDO message includes a set of COB-ID (request SDO and response SDO); it

allows performing of access actions within two nodes. SDO can transmit any size of data,

but segment transmission must be used once it exceeds 4 bytes.

The COB IDs of SDO communication are as follows:

Read: Master to slave (request code 0x40) / Master to slave: 600H + Node ID

Read: Slave response / slave to master: 580H + Node ID

Response code:

43H: Read 4-byte data / 4BH: read 2-byte data / 4FH: read 1-byte data

Write: Master to slave (4-byte data maximum)

Request code:

23H: Write a 4-byte data entry

2BH: Write a 2-byte data entry

2FH: Write a 1-byte data entry

OneSDOserver,sends580H+NodeID,receives600H+NodeID;largerthan4bytesrequiressegmentation. Readrequest40H;response43H4byte,4BH2byte,4FH1byte. Writerequest23H4byte,2BH2byte,2FH1byte. Byte0code;byte1indexLSB,byte2MSB;byte3subindex;bytes4..7dataLSBthroughMSB orreservedreadrequest. Response tablesstilllabelRequestcode/Requestdata;literalheadingsretained.

CANopen SDO byte structures. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

CANopen SDO byte structures. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: (600H) + Node

ID

Shared source cells (coordinates refer to this table):

CANopen SDO byte structures. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: (580H) + Node

CANopen SDO byte structures table1 — PDF page 527

Source row COB-ID Byte0 Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7
1 (600H) + Node ID Reque st code Object index ⟦null: no independent source value⟧ Object subind ex Request data ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ LSB MSB ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

CANopen SDO byte structures table2 — PDF page 527

Source row COB-ID Byte0 Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7
1 (580H) + Node ID Reque st code Object index ⟦null: no independent source value⟧ Object subind ex Request data ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ LSB MSB ⟦null: no independent source value⟧ bit0~ bit7 Bit8~ bit15 Bit16~ bit23 Bit24~ bit31

CANopen SDO byte structures table3 — PDF page 527

Source row COB-ID Byte0 Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7
1 (600H) + Node ID Reque st code Object index ⟦null: no independent source value⟧ Object subind ex Request data ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ LSB MSB ⟦null: no independent source value⟧ bit0~ bit7 Bit8~ bit15 Bit16~ bit23 Bit24~ bit31

Manual — CANopen SDO response and index mapping — page 528

Write: Slave to master (response code 0x60H)

When we use SDO to perform control to the group 25H of the driver control group,

corresponding rules are as follows:

Index

25xxH (register

address)

For example, when we want to perform write/read to 2501H of the control group, the

corresponding SDO object index is the control group register address 2501H.

Perform operation with index 2501H directly and the module will automatically convert to

the A510s 2501H control group register address to perform operation.

Writeresponse60H,sends580H+NodeID;byte0code,1indexLSB,2MSB,3subindex,4..7reserved. Group25Hindex=25xxHregister;2501Hexampledirectmapping. TextcallsA510sregister althoughmanualF510andmodulescopeA510s/F510; no universalotherdrivecompatibility.

CANopen SDO response and index mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

CANopen SDO response and index mapping. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: (580H) + Node

ID

Shared source cells (coordinates refer to this table):

CANopen SDO response and index mapping table1 — PDF page 528

Source row COB-ID Byte0 Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7
1 (580H) + Node ID Reque st code Object index ⟦null: no independent source value⟧ Object subind ex Request data ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ LSB MSB ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — CANopen basic object indices — page 529

11.10.7 Object index list

Basic index

30physicalrows;allIndex/Sub/default/access/size/remarks retained.1008Hmanufacturerd evicenameA510 andU32source literal,notF510normalized.1016Hsub1consumerheartbeatRW/U32butNot supportedremark retained.1200sub1clientserver600H+,sub2clientserver580H+samewording.1600map60400010H/60420010H;3/4zero. No validationofactualdeviceOD.

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1000H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1001H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1005H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1006H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1008H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1009H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 100AH

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1014H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1015H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1016H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1017H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1018H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1200H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1400H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1401H

CANopen basic object indices. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1600H

Shared source cells (coordinates refer to this table):

CANopen basic object indices table1 — PDF page 529

Source row Index Sub Name Default value R/W Size Remarks
1 1000H 0 Device type 00010192H R U32 ⟦blank source cell⟧
2 1001H 0 Error register 0 R U8 ⟦blank source cell⟧
3 1005H 0 COB-ID SYNC message 80H R U32 ⟦blank source cell⟧
4 1006H 0 Communication cycle period 0 RW U32 ⟦blank source cell⟧
5 1008H 0 Manufacturer device name A510 R U32 ⟦blank source cell⟧
6 1009H 0 Manufacturer hardware version 1.0 R U32 ⟦blank source cell⟧
7 100AH 0 Manufacturer software version 1.00 R U32 ⟦blank source cell⟧
8 1014H 0 COB-ID emergency 00000080H+Node-I D R U32 ⟦blank source cell⟧
9 1015H 0 Inhibit time EMCY 0 RW U16 ⟦blank source cell⟧
10 1016H 0 number of entries 1 R U8 ⟦blank source cell⟧
11 ⟦null: no independent source value⟧ 1 Consumer heartbeat time 0 RW U32 Not supported
12 1017H 0 Producer heartbeat time 0 RW U16 ⟦blank source cell⟧
13 1018H 0 number of entries 3 R U8 ⟦blank source cell⟧
14 ⟦null: no independent source value⟧ 1 Vender ID 00000373H R U32 ⟦blank source cell⟧
15 ⟦null: no independent source value⟧ 2 Product code 00000100H R U32 ⟦blank source cell⟧
16 ⟦null: no independent source value⟧ 3 Revision 00010000H R U32 ⟦blank source cell⟧
17 1200H 0 Server SDO Parameter 2 R U8 ⟦blank source cell⟧
18 ⟦null: no independent source value⟧ 1 COB-ID Client Server 0000600H+Node-ID R U32 ⟦blank source cell⟧
19 ⟦null: no independent source value⟧ 2 COB-ID Client Server 0000580H+Node-ID R U32 ⟦blank source cell⟧
20 1400H 0 Number of entries 2 R U8 ⟦blank source cell⟧
21 ⟦null: no independent source value⟧ 1 COB-ID used by PDO 00000200H+Node-I D RW U32 ⟦blank source cell⟧
22 ⟦null: no independent source value⟧ 2 Transmission Type 0xFF RW U8 ⟦blank source cell⟧
23 1401H 0 Number of entries 2 R U8 ⟦blank source cell⟧
24 ⟦null: no independent source value⟧ 1 COB-ID used by PDO 00000300H+Node-I D RW U32 ⟦blank source cell⟧
25 ⟦null: no independent source value⟧ 2 Transmission Type 0xFF RW U8 ⟦blank source cell⟧
26 1600H 0 Number of entries 2 RW U8 ⟦blank source cell⟧
27 ⟦null: no independent source value⟧ 1 1.Mapped Object 60400010H RW U32 ⟦blank source cell⟧
28 ⟦null: no independent source value⟧ 2 2.Mapped Object 60420010H RW U32 ⟦blank source cell⟧
29 ⟦null: no independent source value⟧ 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
30 ⟦null: no independent source value⟧ 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧

Manual — CANopen object indices continuation — page 530

33physicalrows.1801Hsub4and5repeatedthree times;sub2and3twice,unchangedvalues. Allphysicalrowidentitiesretained;do notdeduplicateorattributeextras1802.1601map604F0010H/60500010H.1A00map60400010/60420010withoutHsuffix;1A01map604F0010/60500010.0x64inhibit/eventtime;unitnotstatedlocally. No inferredcorrection.

CANopen object indices continuation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

CANopen object indices continuation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1601H

CANopen object indices continuation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1800H

CANopen object indices continuation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1801H

CANopen object indices continuation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1A00H

CANopen object indices continuation. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 1A01H

Shared source cells (coordinates refer to this table):

CANopen object indices continuation table1 — PDF page 530

Source row Index Sub Name Default value R/W Size Remarks
1 1601H 0 Number of entries 2 RW U8 ⟦blank source cell⟧
2 ⟦null: no independent source value⟧ 1 1.Mapped Object 604F0010H RW U32 ⟦blank source cell⟧
3 ⟦null: no independent source value⟧ 2 2.Mapped Object 60500010H RW U32 ⟦blank source cell⟧
4 ⟦null: no independent source value⟧ 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
5 ⟦null: no independent source value⟧ 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧
6 1800H 0 Number of entries 5 R U8 Number of entries
7 ⟦null: no independent source value⟧ 1 COB-ID used by PDO 180H+Node-ID RW U32 ⟦blank source cell⟧
8 ⟦null: no independent source value⟧ 2 Transmission Type 0xFF RW U8 Transmission type
9 ⟦null: no independent source value⟧ 3 Inhibit time 0x64 RW U16 Inhibit time
10 ⟦null: no independent source value⟧ 4 CMS-Priority Group 0 RW U8 ⟦blank source cell⟧
11 ⟦null: no independent source value⟧ 5 Event timer 0x64 RW U16 Event timer
12 1801H 0 Number of entries 5 R U8 Number of entries
13 ⟦null: no independent source value⟧ 1 COB-ID used by PDO 00000280H+Node-I D RW U32 ⟦blank source cell⟧
14 ⟦null: no independent source value⟧ 2 Transmission Type 0xFF RW U8 ⟦blank source cell⟧
15 ⟦null: no independent source value⟧ 3 Inhibit time 0x64 RW U16 Inhibit time
16 ⟦null: no independent source value⟧ 4 CMS-Priority Group 0 RW U8 ⟦blank source cell⟧
17 ⟦null: no independent source value⟧ 5 Event timer 0x64 RW U16 Event time
18 ⟦null: no independent source value⟧ 4 CMS-Priority Group 0 RW U8 ⟦blank source cell⟧
19 ⟦null: no independent source value⟧ 5 Event timer 0x64 RW U16 Event time
20 ⟦null: no independent source value⟧ 2 Transmission Type 0xFF RW U8 ⟦blank source cell⟧
21 ⟦null: no independent source value⟧ 3 Inhibit time 0x64 RW U16 Inhibit time
22 ⟦null: no independent source value⟧ 4 CMS-Priority Group 0 RW U8 ⟦blank source cell⟧
23 ⟦null: no independent source value⟧ 5 Event timer 0x64 RW U16 Event time
24 1A00H 0 Number of entries 2 RW U8 ⟦blank source cell⟧
25 ⟦null: no independent source value⟧ 1 1.Mapped Object 60400010 RW U32 ⟦blank source cell⟧
26 ⟦null: no independent source value⟧ 2 2.Mapped Object 60420010 RW U32 ⟦blank source cell⟧
27 ⟦null: no independent source value⟧ 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
28 ⟦null: no independent source value⟧ 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧
29 1A01H 0 Number of entries 2 RW U8 ⟦blank source cell⟧
30 ⟦null: no independent source value⟧ 1 1.Mapped Object 604F0010 RW U32 ⟦blank source cell⟧
31 ⟦null: no independent source value⟧ 2 2.Mapped Object 60500010 RW U32 ⟦blank source cell⟧
32 ⟦null: no independent source value⟧ 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
33 ⟦null: no independent source value⟧ 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧

Manual — CANopen DS402 and control registers — page 531

DS402 part

Driver control group command index

Command DATA (allows reading and writing)

SevenDS402entries603F6040604160426043604F6050;velocityHzsignedS16,rampsdefault100unit0.1S. Commandregistersread/write:2500reserved,2501operationbits0..F,2502frequencyunit0.01Hz,2505AO10..10V,2510G12-00HWORD,2511LWORD. PreserveHzversus0.01Hzscope;nofactortransfer. Externalerror/reset only1functionshown,0behaviornotinvented.

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 603F

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 6040

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 6041

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 6042

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 6043

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 604F

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 6050

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2500H

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2501H

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2502H

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2505H

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2510H

CANopen DS402 and control registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2511H

Shared source cells (coordinates refer to this table):

CANopen DS402 and control registers table1 — PDF page 531

Source row Index Sub- Index Name Default value R/W Size Unit PDO MAP
1 603F 0 Error code 0 RO U16 ⟦blank source cell⟧ Yes
2 6040 0 Control word 0 RW U16 ⟦blank source cell⟧ Yes
3 6041 0 Status word 0 RO U16 ⟦blank source cell⟧ Yes
4 6042 0 vl target velocity 0 RW S16 Hz Yes
5 6043 0 vl velocity demand 0 RO S16 Hz Yes
6 604F 0 vl ramp function time Acceleration time 100 RW U16 0.1S Yes
7 6050 0 vl slow down time Deceleration time 100 RW U16 0.1S Yes

CANopen DS402 and control registers table2 — PDF page 531

Source row Register address Continued merged content column 2 Bit Content
1 2500H Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 2501H Operation signal 0 Operation command 1: Operate 0: Stop
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1 Reverse command 1: Reverse 0: Forward
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2 External error 1: Error
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3 Error reset 1: Reset
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4 Reserved
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5 Reserved
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6 Multi-function terminal S1 1: “ON”
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7 Multi-function terminal S2 1: “ON”
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8 Multi-function terminal S3 1: “ON”
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9 Multi-function terminal S4 1: “ON”
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ A Multi-function terminal S5 1: “ON”
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ B Multi-function terminal S6 1: “ON”
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ C Multi-function terminal S7 1: “ON”
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ D Multi-function terminal S8 1: “ON”
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ E Controller mode 1: “ON”
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ F Communication setting torque command 1: “ON”
18 2502H ⟦blank source cell⟧ *Frequency command (Unit: 0.01Hz) ⟦null: no independent source value⟧
19 2505H ⟦blank source cell⟧ AO1 (0.00V ~ 10.00V) ⟦null: no independent source value⟧
20 2510H ⟦blank source cell⟧ G12-00 H-WORD ⟦null: no independent source value⟧
21 2511H ⟦blank source cell⟧ G12-00 L-WORD ⟦null: no independent source value⟧

Manual — CANopen status and error register — page 532

Monitor DATA (read only)

Read-onlymonitor2520statusbits0..F;6Model440literal.2521errordescriptionstarts0..15left and31..46right,continues533. TableheaderBitbuterrornumbersup to61;keepcodeswithoutassumingbitmasks. Errorcode0Reserved unlikewarning0Noalarm. ValuespreserveOH1/OH4andFOexactstrings.

Code 0: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 31: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 1: UV (Under-voltage). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 32: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 2: OC (Over-current). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 33: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 3: OV (Over-voltage). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 34: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 4: OH1 (Heat sink

overheat). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 35: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 5: OL1 (Motor overload). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 36: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 6: OL2 (Frequency

converter overload). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 37: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 7: OT (Over-torque). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 38: CF07 (Motor control fault). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 8: UT (Under-torque). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 39: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 9: SC (Short circuit). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 40: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 10: GF (Ground fault). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 41: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 11: FO. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 42: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 12: IPL (Input phase loss). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 43: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 13: OPL (Output phase

loss). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 44: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 14: OS. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 45: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 15: PGO. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 46: OH4 (Motor overheat). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

CANopen status and error register. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

CANopen status and error register. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2520H

CANopen status and error register. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2521H

Shared source cells (coordinates refer to this table):

CANopen status and error register table1 — PDF page 532

Source row Register address Continued merged content column 2 Bit Content Continued merged content column 5 Continued merged content column 6
1 2520H Status signal 0 Operation status 1: Operate 0: Stop ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1 Direction status 1: Reverse 0: Forward ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2 Frequency converter operation preparation status 1: Preparation complete 0: Preparation not yet complete ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3 Error 1: Abnormal ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4 Warning 1: “ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5 Zero speed 1: “ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6 Model 440 1: “ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7 Frequency reached 1: “ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8 Any frequency reached 1: “ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9 Frequency detection one 1: “ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ A Frequency detection two 1: “ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ B Low voltage 1: “ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ C Frequency converter no output 1: “ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ D Frequency not according to communication 1: “ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ E Operation not according to communication 1: “ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ F Over-torque 1: “ON” ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
17 2521H Error description 0 Reserved 31 Reserved
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1 UV (Under-voltage) 32 Reserved
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2 OC (Over-current) 33 Reserved
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3 OV (Over-voltage) 34 Reserved
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4 OH1 (Heat sink overheat) 35 Reserved
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5 OL1 (Motor overload) 36 Reserved
23 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6 OL2 (Frequency converter overload) 37 Reserved
24 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7 OT (Over-torque) 38 CF07 (Motor control fault)
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8 UT (Under-torque) 39 Reserved
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9 SC (Short circuit) 40 Reserved
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10 GF (Ground fault) 41 Reserved
28 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 11 FO 42 Reserved
29 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 12 IPL (Input phase loss) 43 Reserved
30 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 13 OPL (Output phase loss) 44 Reserved
31 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 14 OS 45 Reserved
32 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 15 PGO 46 OH4 (Motor overheat)

Manual — CANopen errors DI status and warnings — page 533

Topblankregistercontextcontinues2521from532,decimalcodes16..30leftand47..61right;explicitcontextonly,blankrawcellsunchanged.2522DIbits0..7S1..S8,8..Freserved.2523frequencycommand0.01Hz,2524outputfrequency0.01Hz,2526DCvoltagecommand0.1V,2527outputcurrent0.1A.2528warningcodes0..7,30..37,60..67continue534. Multi-columnnumericpairsseparate,notconcatenated.2521/2528notcurrentdespite518text.

Code 16: DEV. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 47: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 17: EF1. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 48: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 18: EF2. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 49: MtrSw (DI Motor Switch Fault). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 19: EF3. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 50: OCA (Acceleration over-current). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 20: EF4. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 51: OCD (Deceleration

over-current). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 21: EF5. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 52: OCC (Operation over-current). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 22: EF6. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 53: CF08. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 23: EF7. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 54: PTCLS. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 24: EF8. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 55: PF (Protection fault). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 25: FB (PID feedback

signal error). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 56: TOL. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 26: OPR(Keypad

Removed). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 57: STO2 (Safety switch 2). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 27: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 58: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 28: CE. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 59: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 29: STO (Safety switch 1). Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 60: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 30: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 61: Reserved. Read-only 2521H; code classification follows the source list headed Bit; no bitmask inferred.

Code 0: No alarm. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 30: RDE. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 60: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 1: OV. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 31: WRE. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 61: RETRY. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 2: UV. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 32: FB. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 62: SE07. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 3: OL2. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 33: VRYE. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 63: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 4: OH2. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 34: SE01. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 64: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 5: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 35: SE02. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 65: OH1. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 6: OT. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 36: SE03. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 66: FIRE. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 7: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 37: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 67: ES. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

CANopen errors DI status and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

CANopen errors DI status and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2521H Error description; continuation from PDF532

CANopen errors DI status and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2522H

CANopen errors DI status and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2523H

CANopen errors DI status and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2524H

CANopen errors DI status and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2526H

CANopen errors DI status and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2527H

CANopen errors DI status and warnings. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2528H

Shared source cells (coordinates refer to this table):

CANopen errors DI status and warnings table1 — PDF page 533

Source row Register address Continued merged content column 2 Bit Content Continued merged content column 5 Continued merged content column 6 Continued merged content column 7 Continued merged content column 8 Continued merged content column 9 Continued merged content column 10 Continued merged content column 11 Continued merged content column 12 Continued merged content column 13
1 ⟦blank source cell⟧ ⟦blank source cell⟧ 16 DEV ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 47 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 17 EF1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 48 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 18 EF2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 49 ⟦null: no independent source value⟧ MtrSw (DI Motor Switch Fault) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 19 EF3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 50 ⟦null: no independent source value⟧ OCA (Acceleration over-current) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 20 EF4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 51 ⟦null: no independent source value⟧ OCD (Deceleration over-current) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 21 EF5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 52 ⟦null: no independent source value⟧ OCC (Operation over-current) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 22 EF6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 53 ⟦null: no independent source value⟧ CF08 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 23 EF7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 54 ⟦null: no independent source value⟧ PTCLS ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 24 EF8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 55 ⟦null: no independent source value⟧ PF (Protection fault) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 25 FB (PID feedback signal error) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 56 ⟦null: no independent source value⟧ TOL ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 26 OPR(Keypad Removed) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 57 ⟦null: no independent source value⟧ STO2 (Safety switch 2) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 27 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 58 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 28 CE ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 59 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 29 STO (Safety switch 1) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 60 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 30 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 61 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
16 2522H DI status 0 Multi-function terminal S1 ⟦null: no independent source value⟧ 4 Multi-function terminal S5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 8~F Reserved
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1 Multi-function terminal S2 ⟦null: no independent source value⟧ 5 Multi-function terminal S6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2 Multi-function terminal S3 ⟦null: no independent source value⟧ 6 Multi-function terminal S7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3 Multi-function terminal S4 ⟦null: no independent source value⟧ 7 Multi-function terminal S8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
20 2523H ⟦blank source cell⟧ Frequency command (0.01Hz) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 2524H ⟦blank source cell⟧ Output frequency (0.01Hz) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
22 2526H ⟦blank source cell⟧ DC voltage command (0.1V) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
23 2527H ⟦blank source cell⟧ Output current (0.1A) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
24 2528H Warning description 0 No alarm 30 RDE ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 60 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
25 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 1 OV 31 WRE ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 61 ⟦null: no independent source value⟧ RETRY ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 2 UV 32 FB ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 62 ⟦null: no independent source value⟧ SE07 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
27 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 3 OL2 33 VRYE ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 63 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
28 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 4 OH2 34 SE01 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 64 ⟦null: no independent source value⟧ Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
29 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 5 Reserved 35 SE02 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 65 ⟦null: no independent source value⟧ OH1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
30 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 6 OT 36 SE03 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 66 ⟦null: no independent source value⟧ FIRE ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
31 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 7 Reserved 37 Reserved ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 67 ⟦null: no independent source value⟧ ES ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — CANopen warnings and monitor registers — page 534

Topblankregistercontinuation2528codes8..29,38..59,68..80;lastthirdcolumnblankbelow80notreservedcodes81+. Total81warningcodes0..80withReservedexplicit.2529DOstatus,252AAO1,252BAO2unitsunstatedhere;252C/D AI1/2unit0.1%;252F L510(s)/E510(s)/A510(s)/F510Check source textnotuniversalmodulecompatibility. Do notsupplymissing2525/252Eaddresses.

Code 8: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 38: SE05. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 68: STP1. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 9: UT. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 39: HPERR. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 69: BDERR. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 10: OS. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 40: EF. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 70: EPERR. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 11: PGO. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 41: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 71: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 12: DEV. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 42: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 72: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 13: CE. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 43: RDP. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 73: STP0. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 14: CALL. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 44: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 74: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 15: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 45: OL1. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 75: STP2. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 16: EF0. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 46: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 76: RUNER. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 17: EF1. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 47: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 77: LOC. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 18: EF2. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 48: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 78: PTCLS. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 19: EF3. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 49: BB1. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 79: Sys Init. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 20: EF4. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 50: BB2. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 80: FBLSS. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 21: EF5. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 51: BB3. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 22: EF6. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 52: BB4. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 23: EF7. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 53: BB5. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 24: EF8. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 54: BB6. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 25: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 55: BB7. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 26: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 56: BB8. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 27: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 57: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 28: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 58: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 29: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

Code 59: Reserved. Read-only 2528H; code classification follows the source list headed Bit; no bitmask inferred.

CANopen warnings and monitor registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility.

CANopen warnings and monitor registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2528H Warning description; continuation from PDF533

CANopen warnings and monitor registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 2529H

CANopen warnings and monitor registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 252AH

CANopen warnings and monitor registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 252BH

CANopen warnings and monitor registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 252CH

CANopen warnings and monitor registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 252DH

CANopen warnings and monitor registers. Exact source units/model/enclosure and qualifiers govern applicability; source claims only. Distinct protocol, register, units, bit ordering and source flags govern; no inferred compatibility. Row group: 252FH

Shared source cells (coordinates refer to this table):

CANopen warnings and monitor registers table1 — PDF page 534

Source row Register address Continued merged content column 2 Bit Content Continued merged content column 5 Continued merged content column 6 Continued merged content column 7 Continued merged content column 8
1 ⟦blank source cell⟧ ⟦blank source cell⟧ 8 Reserved 38 SE05 68 STP1
2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 9 UT 39 HPERR 69 BDERR
3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 10 OS 40 EF 70 EPERR
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 11 PGO 41 Reserved 71 Reserved
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 12 DEV 42 Reserved 72 Reserved
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 13 CE 43 RDP 73 STP0
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 14 CALL 44 Reserved 74 Reserved
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 15 Reserved 45 OL1 75 STP2
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 16 EF0 46 Reserved 76 RUNER
10 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 17 EF1 47 Reserved 77 LOC
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 18 EF2 48 Reserved 78 PTCLS
12 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 19 EF3 49 BB1 79 Sys Init
13 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 20 EF4 50 BB2 80 FBLSS
14 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 21 EF5 51 BB3 ⟦blank source cell⟧ ⟦null: no independent source value⟧
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 22 EF6 52 BB4 ⟦blank source cell⟧ ⟦null: no independent source value⟧
16 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 23 EF7 53 BB5 ⟦blank source cell⟧ ⟦null: no independent source value⟧
17 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 24 EF8 54 BB6 ⟦blank source cell⟧ ⟦null: no independent source value⟧
18 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 25 Reserved 55 BB7 ⟦blank source cell⟧ ⟦null: no independent source value⟧
19 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 26 Reserved 56 BB8 ⟦blank source cell⟧ ⟦null: no independent source value⟧
20 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 27 Reserved 57 Reserved ⟦blank source cell⟧ ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 28 Reserved 58 Reserved ⟦blank source cell⟧ ⟦null: no independent source value⟧
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ 29 Reserved 59 Reserved ⟦blank source cell⟧ ⟦null: no independent source value⟧
23 2529H ⟦blank source cell⟧ DO status ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
24 252AH ⟦blank source cell⟧ AO1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
25 252BH ⟦blank source cell⟧ AO2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
26 252CH ⟦blank source cell⟧ AI 1 input (0.1%) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
27 252DH ⟦blank source cell⟧ AI 2 input (0.1%) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
28 252FH ⟦blank source cell⟧ L510(s)/ E510(s)/ A510(s)/ F510 Check ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — CANopen troubleshooting — page 535

11.10.8 Troubleshooting

There are two indicators on top of the CANopen communication module; when malfunction occurs,

the cause of the malfunction can be confirmed based on the indicator statuses, and troubleshoot

the error by following the descriptions below.

Indicator troubleshooting

Module status LED (RUN LED)

Error status LED (ERR LED)

RUN LED off: check drive power and module power connection. ERR single flash: packet error, including poor host connection or host absent at power-on; continued transmission can recover or continue errors/disconnect. With power off, check TB1 and cable, transmission rate/distance/length against literal ODVA specifications. Double flash: guard/heartbeat error, disconnect power and check node if periodic heartbeat absent. Solid red: disconnected, power off and check TB1/cable/rate/distance/length. Source references ODVA even in CANopen section; not corrected to another standard. Object1016 consumer heartbeat was marked Not supported on529; this difference retained, not resolved by inference.

CANopen RUN LED troubleshooting. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

CANopen RUN LED troubleshooting. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Does not

light up

CANopen ERR LED troubleshooting. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

CANopen ERR LED troubleshooting. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Single

flash

CANopen ERR LED troubleshooting. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Double

CANopen ERR LED troubleshooting. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Red light

lights up

CANopen troubleshooting table1 — PDF page 535

Source row Indicator statuses Status name Troubleshooting method
1 Does not light up Power not supplied to the communication module 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver.

CANopen troubleshooting table2 — PDF page 535

Source row Indicator statuses Status name Description
1 Single flash CANopen packet error Poor connection quality with the CANopen host terminal or host not connected when powered on. Continue transmission or power off inspection can be selected. Two results can be expected with continue transmission 1) Packet transmission returns to normal and the red light no longer flashes 2) Packet continues to have errors causing disconnection. When the power is off, check whether the TB1 terminal and cable are firmly connected, and whether the transmission rate, maximum transmission distance and cable length comply with ODVA specifications.
2 Double flash Guard/Heartbeat error User sends periodic heartbeat messages. If a message is not received after a specific time, please disconnect the power and check the connection status of that node.
3 Red light lights up Disconnected Cannot connect with the CANopen host terminal; disconnect the power and check whether the TB1 terminal and cable is firmly connected, and whether the transmission rate, maximum transmission distance and cable length comply with ODVA specifications.

Manual — CANopen EDS reference — page 536

11.10.9 EDS file

When using the CANopen communication module, if the EDS description file (JN5-CMHI-CAN_V

(latest version).eds) is needed, please download it from the TECO official website or request for it

from your purchasing sales channel.

Source refers to JN5-CMHI-CAN_V(latest version).eds from TECO official website or purchasing sales channel. Version and availability are not verified in this local packet; no EDS contents inferred.

Manual — EtherCAT specifications — page 537

11.11 Introduction to the EtherCAT high speed communication

expansion module

11.11.1 Communication hardware and data structure

This product is the EtherCAT high-speed communication expansion module (hereinafter referred to

as communication module); it can perform remote setting and communication functions through the

EtherCAT network environment. It can only be used with the TECO A510s/F510 AC motor driver

(hereinafter referred to as a driver), and allow the driver to operate on the EtherCAT network.

11.11.2 Product specifications

EtherCAT ports

AC motor driver port

EtherCAT high-speed expansion for remote settings/communications; source explicitly only TECO A510s/F510. Dual-port network socket, EtherCAT protocol; control board CN2 carries both data and module power. No numeric transmission speed specified here.

EtherCAT network ports;A510s/F510 only. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

EtherCAT network ports;A510s/F510 only. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Connector

EtherCAT network ports;A510s/F510 only. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Network

protocols

EtherCAT drive CN2 data/power. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

EtherCAT drive CN2 data/power. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Connector

EtherCAT drive CN2 data/power. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Terminal

functions

EtherCAT specifications table1 — PDF page 537

Source row Item Specifications
1 Connector Dual-port network socket
2 Network protocols EtherCAT communication protocol

EtherCAT specifications table2 — PDF page 537

Source row Item Specifications
1 Connector Control board CN2 connector
2 Terminal functions 1. The communication module communicates with the AC motor driver through this interface. 2. The AC motor driver provides power to the communication module through this interface.

Manual — EtherCAT connectors and parameters — page 538

11.11.3 Installation instructions

Communication module contact description

As shown in the figure below, the framed part is the CN2 connector that connects to the

driver.

Communication module network socket

As shown in the figure below, the left socket is input and the right socket is output.

Driver parameter setting description

Users must first confirm related parameter settings on the driver in order to ensure that the

communication module can connect normally.

Input

Output

Framed connector in rear board photograph is CN2. In the front-facing two-socket photograph, left socket is Input and right socket Output. Orientation is tied to this image, not to an arbitrary rear view. Parameter00-02 operation command source=2;00-05 frequency command source=3, both communication control. No pin numbers or electrical ratings inferred from photograph.

EtherCAT required driver settings. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

EtherCAT required driver settings. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 00-02

EtherCAT required driver settings. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 00-05

EtherCAT connectors and parameters table1 — PDF page 538

Source row Parameters Parameter name Settings Settings descriptions
1 00-02 Operation command source 2 Communication control
2 00-05 Frequency command source 3 Communication control

Manual — EtherCAT LED indicators — page 539

11.11.4 LED indicator descriptions

The module has two dual-color LED indicators built-in used to quickly diagnose and monitor

the communication statuses between the module itself and the EtherCAT network.

Module status LED2

Used to monitor whether the communication module is operating normally.

Network status LED1

Used to monitor the operability of the communication module EtherCAT network.

Two dual-colour indicators: LED2 module off=no power; red flashing=data transmitting; red/green lit=driver/module data error. LED1 network off=not connected/INIT; green flashing=Standby/Pre-OP; green lit=Operation/OP; red lit=driver/module data transmission error. No blink frequency specified; CANopen or PROFIBUS blink timings not imported.

EtherCAT LED2 module status. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

EtherCAT LED2 module status. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Does not

light up

EtherCAT LED2 module status. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Red light

flashes

EtherCAT LED2 module status. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Red/green

light lights

up

EtherCAT LED1 network status. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

EtherCAT LED1 network status. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Does not

EtherCAT LED1 network status. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Green light

lights up

EtherCAT LED1 network status. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Red light

EtherCAT LED indicators table1 — PDF page 539

Source row Indicator statuses Status name Description
1 Does not light up Power not supplied Power not supplied
2 Red light flashes Data transmitting Driver and communication expansion module data transmitting
3 Red/green light lights up Driver data transmission error Data transmission error between the driver and communication expansion module

EtherCAT LED indicators table2 — PDF page 539

Source row Indicator statuses Status name Description
1 Does not light up Not connected / INIT EtherCAT network not connected (INIT)
2 Green light flashes Standby Preparation status (Pre-OP)
3 Green light lights up Operation status Operation status (OP)
4 Red light lights up Driver data transmission error Data transmission error between the driver and communication expansion module

Manual — EtherCAT basic object dictionary — page 540

11.11.5 Object index list

Basic index

29 physical data rows preserved.1000 device type00000192H,U32;1001error0,U8;1008 default literal JN5-CM-CAN despite EtherCAT context;1009/100A default Version without a number.1018 count4 but only subindices1–3 follow: vendor0000081BH, product00000001H,revision00000001H.1600 count2 mapping60400010H/60420010H/0/0.1601 count2 mapping604F0010H/60500010H/0/0.1A00 count3 mapping60400010/60420010/604F0020/0.1A01 count3 mapping604F0020/60500020/0/0. Missing H suffixes retained; zero third map with count3 retained. Native merged object labels kept as merged, not repeated invented cells. EtherCAT mapping sizes and defaults not replaced by similar CANopen rows529–530.

EtherCAT object dictionary;distinct fromCANopen. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

EtherCAT object dictionary;distinct fromCANopen. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 1000H

EtherCAT object dictionary;distinct fromCANopen. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 1001H

EtherCAT object dictionary;distinct fromCANopen. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 1008H

EtherCAT object dictionary;distinct fromCANopen. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 1009H

EtherCAT object dictionary;distinct fromCANopen. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 100AH

EtherCAT object dictionary;distinct fromCANopen. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 1018H

EtherCAT object dictionary;distinct fromCANopen. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 1600H

EtherCAT object dictionary;distinct fromCANopen. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 1601H

EtherCAT object dictionary;distinct fromCANopen. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 1A00H

EtherCAT object dictionary;distinct fromCANopen. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 1A01H

Shared source cells (coordinates refer to this table):

EtherCAT basic object dictionary table1 — PDF page 540

Source row Index Sub- Index Name Default value R/W Size Remarks
1 1000H 0 Device type 00000192H R U32 ⟦blank source cell⟧
2 1001H 0 Error register 0 R U8 ⟦blank source cell⟧
3 1008H 0 Manufacturer device name JN5-CM-CA N R U32 ⟦blank source cell⟧
4 1009H 0 Manufacturer hardware version Version R U32 ⟦blank source cell⟧
5 100AH 0 Manufacturer software version Version R U32 ⟦blank source cell⟧
6 1018H 0 number of entries 4 R U8 ⟦blank source cell⟧
7 ⟦null: no independent source value⟧ 1 Vender ID 0000081BH R U32 ⟦blank source cell⟧
8 ⟦null: no independent source value⟧ 2 Product code 00000001H R U32 ⟦blank source cell⟧
9 ⟦null: no independent source value⟧ 3 Revision 00000001H R U32 ⟦blank source cell⟧
10 1600H 0 Number of entries 2 RW U8 ⟦blank source cell⟧
11 ⟦null: no independent source value⟧ 1 1.Mapped Object 60400010H RW U32 ⟦blank source cell⟧
12 ⟦null: no independent source value⟧ 2 2.Mapped Object 60420010H RW U32 ⟦blank source cell⟧
13 ⟦null: no independent source value⟧ 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
14 ⟦null: no independent source value⟧ 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧
15 1601H 0 Number of entries 2 RW U8 ⟦blank source cell⟧
16 ⟦null: no independent source value⟧ 1 1.Mapped Object 604F0010H RW U32 ⟦blank source cell⟧
17 ⟦null: no independent source value⟧ 2 2.Mapped Object 60500010H RW U32 ⟦blank source cell⟧
18 ⟦null: no independent source value⟧ 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
19 ⟦null: no independent source value⟧ 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧
20 1A00H 0 Number of entries 3 RW U8 ⟦blank source cell⟧
21 ⟦null: no independent source value⟧ 1 1.Mapped Object 60400010 RW U32 ⟦blank source cell⟧
22 ⟦null: no independent source value⟧ 2 2.Mapped Object 60420010 RW U32 ⟦blank source cell⟧
23 ⟦null: no independent source value⟧ 3 3.Mapped Object 604F0020 RW U32 ⟦blank source cell⟧
24 ⟦null: no independent source value⟧ 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧
25 1A01H 0 Number of entries 3 RW U8 ⟦blank source cell⟧
26 ⟦null: no independent source value⟧ 1 1.Mapped Object 604F0020 RW U32 ⟦blank source cell⟧
27 ⟦null: no independent source value⟧ 2 2.Mapped Object 60500020 RW U32 ⟦blank source cell⟧
28 ⟦null: no independent source value⟧ 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
29 ⟦null: no independent source value⟧ 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧

Manual — EtherCAT object units/defaults — page 541

Object part

Seven exact object rows603F,6040,6041,6042,6043,604F,6050.603Ferror/6040control/6041status U16; velocity6042/6043 S16Hz.604F acceleration and6050 deceleration are U32,Driver default value,0.1S in this source section, unlike CANopen U16/default100 on531. All PDO MAP=Yes. No source correction or protocol-equivalence assumption.

EtherCAT object part;size/default/unit specific. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

EtherCAT object part;size/default/unit specific. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 603F

EtherCAT object part;size/default/unit specific. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 6040

EtherCAT object part;size/default/unit specific. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 6041

EtherCAT object part;size/default/unit specific. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 6042

EtherCAT object part;size/default/unit specific. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 6043

EtherCAT object part;size/default/unit specific. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 604F

EtherCAT object part;size/default/unit specific. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 6050

EtherCAT object units/defaults table1 — PDF page 541

Source row Index Sub- Index Name Default value R/W Size Unit PDO MAP
1 603F 0 Error code 0 RO U16 ⟦blank source cell⟧ Yes
2 6040 0 Control word 0 RW U16 ⟦blank source cell⟧ Yes
3 6041 0 Status word 0 RO U16 ⟦blank source cell⟧ Yes
4 6042 0 vl target velocity 0 RW S16 Hz Yes
5 6043 0 vl velocity demand 0 RO S16 Hz Yes
6 604F 0 vl ramp function time Acceleration time Driver default value RW U32 0.1S Yes
7 6050 0 vl slow down time Deceleration time Driver default value RW U32 0.1S Yes

Manual — EtherCAT troubleshooting and XML reference — page 542

11.11.6 Troubleshooting

There are two indicators on top of the EtherCAT communication module. When a malfunction

occurs, the cause of the malfunction can be confirmed based on the indicator statuses, and

troubleshoot the error by following the descriptions below.

Indicator troubleshooting

Module status LED2

Network status LED1

11.11.7 xml file

When using the EtherCAT communication module, if the xml description file (JN5-CMHI-ECAT_V

(latest version).xml) is needed, please download it from the TECO official website or request for it

from your purchasing sales channel.

LED2 off: check driver power and module power terminal. Red/green: check module contact, reconnect driver power and confirm elimination. LED1 off: check driver power and INIT mode; red lit: module contact and reconnect power. These are source procedures, not performed checks. XML reference JN5-CMHI-ECAT_V(latest version).xml, website or purchasing sales channel; no current-version guarantee.

EtherCAT LED2 troubleshooting. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

EtherCAT LED2 troubleshooting. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Does not

light up

EtherCAT LED2 troubleshooting. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Red/green

light lights

up

EtherCAT LED1 troubleshooting. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

EtherCAT LED1 troubleshooting. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Does not

EtherCAT LED1 troubleshooting. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Red light

lights up

EtherCAT troubleshooting and XML reference table1 — PDF page 542

Source row Indicator statuses Status name Troubleshooting method
1 Does not light up Power not supplied 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver.
2 Red/green light lights up Driver data transmission error 1. Confirm whether the communication module has proper contact. 2. Reconnect the power of the driver and confirm whether the error has been eliminated.

EtherCAT troubleshooting and XML reference table2 — PDF page 542

Source row Indicator statuses Status name Description
1 Does not light up Not connected / INIT 1. Confirm whether the driver power is normal. 2. If connected to EtherCAT, confirm whether it is in INIT mode.
2 Red light lights up Driver data transmission error 1. Confirm whether the communication module has proper contact. 2. Reconnect the power of the driver and confirm whether the error has been eliminated.

Manual — I/O expansion specifications and analog inputs — page 543

11.12 I/O expansion card

11.12.1 Hardware and data structure

This product is an I/O expansion module; it allows performing of I/O expansion functions through

the SPI bus. Used with the TECO A510s/F510 AC motor driver (hereinafter referred to as a driver).

11.12.2 Product specifications

I/O ports

AC motor driver port

11.12.3 Installation instructions

Contact description

SPI I/O expansion with TECO A510s/F510; TB1 seven external contacts; control board CN2/CN5. AI3 main speed command switched by SW7 between−10..+10V at500KΩ and4..20mA at500Ω,12-bit resolution. GND analog shared terminal, signal level printed---. Preserve voltage/current input resistances separately and do not infer additional terminal counts.

I/O expansion TB1 ports. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

I/O expansion TB1 ports. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Connector

I/O expansion CN2/CN5 SPI. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

I/O expansion CN2/CN5 SPI. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Connector

I/O expansion CN2/CN5 SPI. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Transmission

method

I/O expansion CN2/CN5 SPI. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Terminal

functions

I/O analog input contacts. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

I/O analog input contacts. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Analog input signal

Shared source cells (coordinates refer to this table):

I/O expansion specifications and analog inputs table1 — PDF page 543

Source row Item Specifications
1 Connector TB1 7 external contacts

I/O expansion specifications and analog inputs table2 — PDF page 543

Source row Item Specifications
1 Connector Control board CN2 connector/CN5 connector
2 Transmission method SPI high speed communication
3 Terminal functions TB1 7 external contacts

I/O expansion specifications and analog inputs table3 — PDF page 543

Source row Type Terminal Terminal functions Signal level
1 Analog input signal AI3 Main speed command input; SW7 can be used to switch between voltage or current input (-10~10V)/(4-20mA) -10V to +10V, (Input resistance 500KΩ) 4 to 20 mA (Input resistance: 500Ω) (12bit resolution)
2 ⟦null: no independent source value⟧ GND Analog signal shared terminal ----

Manual — I/O expansion relay and digital outputs — page 544

11.12.4 Driver parameter setting descriptions

Please refer to group 3, 4 parameter descriptions in the manual

R4A/R4B/R4C relay A contact/B contact/shared terminal respectively.250Vac10mA–1A;30Vdc10mA–1A. DO2 multifunction open-collector,48Vdc2–50mA,optical coupling. Source function list retained in bounded cell: operating,zero speed,frequency consistent,any frequency consistent,output frequency,preparation complete,low-voltage detection,output occlusion,operation/frequency commands,over-torque,abnormal,low voltage,overheat,motor/drive overload,retrying,signal abnormal,chronograph output. DOG is literal open-collector shared-terminal label; blank signal level remains blank. Group3/4 parameter references.

I/O relay and digital output contacts. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

I/O relay and digital output contacts. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Relay Output

I/O relay and digital output contacts. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Digital Output

Shared source cells (coordinates refer to this table):

I/O expansion relay and digital outputs table1 — PDF page 544

Source row Type Terminal Terminal functions Signal level
1 Relay Output R4A- R4B- R4C Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) Relay shared terminal; please refer to the manual for its functions. Terminal capacity: At 250Vac, 10 mA~1A At 30Vdc, 10 mA~1A
2 Digital Output DO2 Multi-function (open collector transistor) output: Operating, zero speed, frequency consistent, any frequency consistent, output frequency, preparation complete, low-voltage detection, output occlusion, operation and frequency commands, over-torque detection, abnormal, low-voltage, overheat, motor over-load, frequency converter over-load output, retrying, signal abnormal, chronograph output… 48Vdc, 2 mA~50mA Optical coupling output
3 ⟦null: no independent source value⟧ DOG Open collector transistor shared terminal ⟦blank source cell⟧

Manual — DC reactor selection — page 545

11.13 DC reactor

Installing a DC reactor at the DC terminal of the frequency converter provides the following

advantages:

• Improves the input current waveform distortion caused by the rectifier in the frequency

converter while maintaining continuous rectified current.

• Suppresses instantaneous current surges and prevents related overheating

phenomenon caused by the rectifier and voltage regulator components due to

instantaneous current surges.

• Reduces harmonic interference problems generated by the frequency converter.

• Improves and increase power factor and reduces AC component pulses at the DC

terminal.

• Compared to AC reactors, the size of DC reactors are smaller and the costs are also

lower.

Table 6.13 DC reactor list

Five source benefit statements concern waveform distortion,instantaneous surges/overheating,harmonics,power factor/DC pulses,size/cost versus AC reactors; not quantified tests. Caption Table6.13 appears in11.13.22 rows:200V1/3-phase1–3HP,200V3-phase5–175HP,400V3-phase1–5HP. Distinct model rated current(A),DC inductance(mH),reactor rated current(A).200V50HP is labelled built-in here, while501 says60–175HP IP20. All source labels retained without choosing which governs.175HP450A drive with0.05mH/800A reactor retained.

DC reactor table6.13;voltage/phasegroups explicit. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

DC reactor table6.13;voltage/phasegroups explicit. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 200V 1 Ø /3 Ø

DC reactor table6.13;voltage/phasegroups explicit. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 200V 3 Ø

DC reactor table6.13;voltage/phasegroups explicit. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 400V 3 Ø

Shared source cells (coordinates refer to this table):

DC reactor selection table1 — PDF page 545

Source row Model voltage and phase Model HP Model rated current(A) DC reactor inductance(mH) DC reactor rated current(A)
1 200V 1 Ø /3 Ø 1 5 2.9 10
2 ⟦null: no independent source value⟧ 2 7.5 2 15
3 ⟦null: no independent source value⟧ 3 10.6 1.2 20
4 200V 3 Ø 5 14.5 0.78 35
5 ⟦null: no independent source value⟧ 7.5 22 0.78 35
6 ⟦null: no independent source value⟧ 10 30 0.57 45
7 ⟦null: no independent source value⟧ 15 42 0.39 65
8 ⟦null: no independent source value⟧ 20 56 0.29 85
9 ⟦null: no independent source value⟧ 25 69 0.23 105
10 ⟦null: no independent source value⟧ 30 80 0.2 120
11 ⟦null: no independent source value⟧ 40 110 0.14 165
12 ⟦null: no independent source value⟧ 50 (built-in) 138 0.12 210
13 ⟦null: no independent source value⟧ 60 (built-in) 169 0.1 200
14 ⟦null: no independent source value⟧ 75 (built-in) 200 0.08 260
15 ⟦null: no independent source value⟧ 100 (built-in) 250 0.08 390
16 ⟦null: no independent source value⟧ 125 (built-in) 312 0.08 390
17 ⟦null: no independent source value⟧ 150 (built-in) 400 0.065 520
18 ⟦null: no independent source value⟧ 175 (built-in) 450 0.05 800
19 400V 3 Ø 1 3.4 10.2 6.5
20 ⟦null: no independent source value⟧ 2 4.1 7 8.5
21 ⟦null: no independent source value⟧ 3 5.4 4.2 11
22 ⟦null: no independent source value⟧ 5 9.2 2.8 20

Manual — DC reactor continuation — page 546

Note: When using DC reactors, please first remove the short-circuit copper sheet between

the P1 and P2 terminals, and then fix the current reactor on these two terminals.

22 rows7.5–800HP; voltage/phase column physically blank, continuing400V3-phase group from545. Raw blanks/merged placeholders retained with pagebreak context.100–425HP labels built-in.175HP0.22mH after150HP0.15mH;215HP and270HP literal, not rounded or relabelled.535/670/800HP drive currents700/875/960A and reactors0.05/0.04/0.03mH,1000/1200/1400A. Note remove P1/P2 short-circuit copper sheet before fixing DC reactor; source installation statement, not work performed.

DC reactor table6.13 continuation;voltageblank after400V3phase545. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

DC reactor table6.13 continuation;voltageblank after400V3phase545. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 400V 3phase continuation fromPDF545;voltage cell blank on this page

Shared source cells (coordinates refer to this table):

DC reactor continuation table1 — PDF page 546

Source row Model voltage and phase Model HP Model rated current(A) DC reactor inductance(mH) DC reactor rated current(A)
1 ⟦blank source cell⟧ 7.5 12.1 2.8 20
2 ⟦null: no independent source value⟧ 10 17.5 2.1 30
3 ⟦null: no independent source value⟧ 15 23 1.4 35
4 ⟦null: no independent source value⟧ 20 31 1.0 50
5 ⟦null: no independent source value⟧ 25 38 0.83 60
6 ⟦null: no independent source value⟧ 30 44 0.7 70
7 ⟦null: no independent source value⟧ 40 58 0.51 90
8 ⟦null: no independent source value⟧ 50 73 0.41 115
9 ⟦null: no independent source value⟧ 60 88 0.34 140
10 ⟦null: no independent source value⟧ 75 103 0.28 160
11 ⟦null: no independent source value⟧ 100 (built-in) 145 0.2 230
12 ⟦null: no independent source value⟧ 125 (built-in) 168 0.18 240
13 ⟦null: no independent source value⟧ 150 (built-in) 208 0.15 240
14 ⟦null: no independent source value⟧ 175 (built-in) 250 0.22 290
15 ⟦null: no independent source value⟧ 215 (built-in) 296 0.15 370
16 ⟦null: no independent source value⟧ 270 (built-in) 328 0.15 370
17 ⟦null: no independent source value⟧ 300 (built-in) 435 0.12 520
18 ⟦null: no independent source value⟧ 375 (built-in) 515 0.08 800
19 ⟦null: no independent source value⟧ 425 (built-in) 585 0.08 800
20 ⟦null: no independent source value⟧ 535 700 0.05 1000
21 ⟦null: no independent source value⟧ 670 875 0.04 1200
22 ⟦null: no independent source value⟧ 800 960 0.03 1400

Manual — Sinusoidal output reactor selection — page 547

11.14 Sinusoidal output reactor

The parasitic inductance and capacitance that exist in the frequency converter and motor

wiring are determined by the component switching speed and wiring of the frequency

converter. The voltage of the motor terminal will reach as high as twice the DC voltage of

the frequency converter. LC resonance may cause surge voltages at the motor terminal

and cause danger. Installing an AC reactor at the frequency converter output can suppress

voltages (dv/dt). If the wiring length is too long, suppression of surge voltages will become

more difficult. Installing a sinusoidal output filter at the output terminal of the frequency

converter can prevent the motor terminal voltage from generating surges.

Table 6.14 Sinusoidal output reactor list

Source describes parasiticLC and motor-terminal surge up to twice drive DC voltage, AC output reactor dv/dt reduction and sinusoidal filter benefit; actual installation behavior unverified. Caption Table6.14 within11.14.25 rows:200V1/3phase1–3HP,200V3phase5–175HP,400V3phase1–15HP.400V row literal5.4HP with9.2A,0.58mH,12.1A; no silent correction to5HP.200V30HP model80A versus reactor79A retained as source conflict. HD/ND applies one model-current column, not two inferred ratings. This output accessory is distinct from AC input reactors on500–501.

Output reactor table6.14;not AC input reactor. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

Output reactor table6.14;not AC input reactor. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 200V 1 Ø /3 Ø

Output reactor table6.14;not AC input reactor. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 200V 3 Ø

Output reactor table6.14;not AC input reactor. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 400V 3 Ø

Shared source cells (coordinates refer to this table):

Sinusoidal output reactor selection table1 — PDF page 547

Source row Model voltage and phase Model HP Model rated current(A) HD/ND Output reactor inductance(mH) Output reactor rated current(A)
1 200V 1 Ø /3 Ø 1 5 0.61 6
2 ⟦null: no independent source value⟧ 2 7.5 0.38 9.6
3 ⟦null: no independent source value⟧ 3 10.6 0.31 12
4 200V 3 Ø 5 14.5 0.17 22
5 ⟦null: no independent source value⟧ 7.5 22 0.17 22
6 ⟦null: no independent source value⟧ 10 30 0.12 30
7 ⟦null: no independent source value⟧ 15 42 0.09 42
8 ⟦null: no independent source value⟧ 20 56 0.07 56
9 ⟦null: no independent source value⟧ 25 69 0.05 69
10 ⟦null: no independent source value⟧ 30 80 0.05 79
11 ⟦null: no independent source value⟧ 40 110 0.03 110
12 ⟦null: no independent source value⟧ 50 138 0.03 138
13 ⟦null: no independent source value⟧ 60 169 0.02 169
14 ⟦null: no independent source value⟧ 75 200 0.017 200
15 ⟦null: no independent source value⟧ 100 250 0.013 250
16 ⟦null: no independent source value⟧ 125 312 0.013 312
17 ⟦null: no independent source value⟧ 150 400 0.008 400
18 ⟦null: no independent source value⟧ 175 450 0.008 450
19 400V 3 Ø 1 3.4 1.7 4.1
20 ⟦null: no independent source value⟧ 2 4.1 1.29 5.4
21 ⟦null: no independent source value⟧ 3 5.4 1.01 6.9
22 ⟦null: no independent source value⟧ 5.4 9.2 0.58 12.1
23 ⟦null: no independent source value⟧ 7.5 12.1 0.58 12.1
24 ⟦null: no independent source value⟧ 10 17.5 0.4 17.5
25 ⟦null: no independent source value⟧ 15 23 0.3 23

Manual — Output reactor continuation — page 548

Note: 1. The frequency converter has improved IGBT equipment and soft-switching

driver circuit; compared to previous models, it can improve dv/dt by

approximately 50% terminal voltage.

  1. The purposes of installing sinusoidal output filters are as follows:

‧ Prolong motor life.

‧ Reduce motor interference.

‧ Reduce frequency converter pulse load.

‧ Improve system stability and efficiency.

19 rows20–800HP; blank voltage group continues400V3phase from547 without filling raw cells.215/270HP retained.535HP0.01mH,670HP0.08mH,800HP0.07mH source values non-monotonic, not changed to0.008/0.007. Source comparative dv/dt improvement approximately50% terminal voltage versus previous models has no named comparison or test conditions. Benefits motor life,interference,pulse load,stability and efficiency remain supplier claims.

Output reactor table6.14 continuation;voltageblank after400V3phase547. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

Output reactor table6.14 continuation;voltageblank after400V3phase547. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 400V 3phase continuation fromPDF547;voltage cell blank on this page

Shared source cells (coordinates refer to this table):

Output reactor continuation table1 — PDF page 548

Source row Model voltage and phase Model HP Model rated current(A) HD/ND Output reactor inductance(mH) Output reactor rated current(A)
1 ⟦blank source cell⟧ 20 31 0.23 31
2 ⟦null: no independent source value⟧ 25 38 0.18 38
3 ⟦null: no independent source value⟧ 30 44 0.16 44
4 ⟦null: no independent source value⟧ 40 58 0.12 58
5 ⟦null: no independent source value⟧ 50 73 0.1 73
6 ⟦null: no independent source value⟧ 60 88 0.08 88
7 ⟦null: no independent source value⟧ 75 103 0.07 103
8 ⟦null: no independent source value⟧ 100 145 0.05 145
9 ⟦null: no independent source value⟧ 125 168 0.04 168
10 ⟦null: no independent source value⟧ 150 208 0.032 208
11 ⟦null: no independent source value⟧ 175 250 0.027 250
12 ⟦null: no independent source value⟧ 215 296 0.023 296
13 ⟦null: no independent source value⟧ 270 328 0.021 328
14 ⟦null: no independent source value⟧ 300 435 0.015 435
15 ⟦null: no independent source value⟧ 375 515 0.012 515
16 ⟦null: no independent source value⟧ 425 585 0.012 585
17 ⟦null: no independent source value⟧ 535 700 0.01 700
18 ⟦null: no independent source value⟧ 670 875 0.08 875
19 ⟦null: no independent source value⟧ 800 960 0.07 960

Manual — External24V power card — page 549

11.15 DC24V power expansion card

This product allows parts of the communication or driver functions to operate normally

before connecting power to the frequency converter.

11.15.1 JN5-PS-DC24V product specifications

Connection terminal

JN5-PS-DC24V allows parts of communication or driver functions before drive main power connection.24V input24V±5%,0.6A;0V reference ground. Isolation note explicitly says above terminals cannot connect to power/terminals on frequency converter itself. No universal compatibility or powered operation procedure inferred.

JN5-PS-DC24V external supply/isolation. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

JN5-PS-DC24V external supply/isolation. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Input

terminal

JN5-PS-DC24V external supply/isolation. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: Notes

External24V power card table1 — PDF page 549

Source row Item Specifications
1 Input terminal 24V: 24V±5%, 0.6A 0V: 24V reference ground
2 Notes The terminals above cannot be connected to the power and terminals on the frequency converter itself in order to achieve the goal of safety isolation.

Manual — UL appendix safety precautions — page 550

A-1

Appendix-A Instructions for UL

◆ Safety Precautions

DANGER

Electrical Shock Hazard

Do not connect or disconnect wiring while the power is on.

Failure to comply will result in death or serious injury.

WARNING

Do not operate equipment with covers removed.

Failure to comply could result in death or serious injury.

The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or

shields before operating the drives and run the drives according to the instructions described in this manual.

Always ground the motor-side grounding terminal.

Improper equipment grounding could result in death or serious injury by contacting the motor case.

Do not touch any terminals before the capacitors have fully discharged.

Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power

supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching any

components.

Do not allow unqualified personnel to perform work on the drive.

Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with installation,

adjustment, and maintenance of AC drives.

Do not perform work on the drive while wearing loose clothing, jewelry, or lack of eye protection.

Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the

drive.

Do not remove covers or touch circuit boards while the power is on.

Fire Hazard

Tighten all terminal screws to the specified tightening torque.

Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.

Do not use an improper voltage source.

Failure to comply could result in death or serious injury by fire.

Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.

Do not use improper combustible materials.

Attach the drive to metal or other noncombustible material.

NOTICE

Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.

Failure to comply may result in ESD damage to the drive circuitry.

Never connect or disconnect the motor from the drive while the drive is outputting voltage.

Improper equipment sequencing could result in damage to the drive.

Do not use unshielded cable for control wiring.

Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires and

ground the shield to the ground terminal of the drive.

All safety prose preserved as source instructions: no energized wiring; reinstall removed covers/shields before operation; ground motor-side terminal; disconnect all power and wait at least time specified on drive before touching any components; only authorized personnel; no loose clothing/jewelry and eye protection required; no live circuit-board contact; tighten specified torque; match drive/supply voltage; attach to noncombustible metal/material;ESD precautions; never connect/disconnect motor while drive outputs voltage; shielded twisted-pair control wiring grounded to drive. No fixed discharge time substituted for local wording or earlier conflicting5/10-minute source instructions.

Adjacent source context — repeated to preserve continuation:

Manual — UL claim conditions and crimp terminals — page 551

A-2

NOTICE

Do not modify the drive circuitry.

Failure to comply could result in damage to the drive and will void warranty.

Teco is not responsible for any modification of the product made by the user. This product must not be modified.

Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices.

Failure to comply could result in damage to the drive.

◆ UL Standards

The UL/cUL mark applies to products in the United States and Canada and it means that UL has performed product testing and

evaluation and determined that their stringent standards for product safety have been met. For a product to receive UL

certification, all components inside that product must also receive UL certification.

UL/cUL Mark

◆ UL Standards Compliance

This drive is tested in accordance with UL standard UL508C and complies with UL requirements. To ensure continued compliance

when using this drive in combination with other equipment, meet the following conditions:

■ Installation Area

Do not install the drive to an area greater than pollution severity 2 (UL standard).

■ Main Circuit Terminal Wiring

UL approval requires crimp terminals when wiring the drive’s main circuit terminals. Use crimping tools as specified by the crimp

terminal manufacturer. Teco recommends crimp terminals made by NICHIFU for the insulation cap.

The table below matches drives models with crimp terminals and insulation caps. Orders can be placed with a Teco

representative or directly with the Teco sales department.

Closed-Loop Crimp Terminal Size

Source says no drive modification/warranty and check all wiring. UL/cUL listed logo and UL508C compliance wording are source claims, not certificate/standard-currency verification. Installation pollution severity no greater than2. Crimp terminals required for main circuit, manufacturer-specified tools; Nichifu recommended.23 body rows: model groups, common input/output wire gauge, screw,crimp/tool/cap. Merged wire cells apply both R/L1 S/L2 T/L3 and U/T1 V/T2 W/T3. Source300(4/0) 2 for2125/4150–4250,152(300) 2 for2175,150(3/0) for4100/4125 retained despite unusual gauge forms.4535/4670:152(300) 4,M10,R150-10 4,Nichifu NOP150H,TIC150.4800:203(400) 4,M10,R200-10S 4,Nichifu NOH300K,TIC200. No conversion of AWG/mm2 or correction of hardware matching.

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2001/2002/ 2003

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2005/2008

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2010/2015

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2030

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2050

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2075

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2125

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2175

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4001/4002/ 4003

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4005/4008/ 4010

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4015/4020

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4025/4030/ 4040

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4050/4060/ 4075

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4100/4125

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4150/4175/ 4215/4250

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4300

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4375/4425

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4535/4670

Appendix UL closed-loop crimp terminal selection;literal wire-gauge and model groups. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4800

Shared source cells (coordinates refer to this table):

Adjacent source context — repeated to preserve continuation:

UL claim conditions and crimp terminals table1 — PDF page 551

Source row Drive model F510 Wire gauge mm2(AWG):R/L1 S/L2 T/L3 Wire gauge mm2(AWG):U/T1 V/T2 W/T3 Terminal screws Crimp terminal model Tool machine model Insulation cap model
1 2001/2002/ 2003 2 (14) ⟦null: no independent source value⟧ M4 R2-4 Nichifu NH 1 / 9 TIC 2
2 ⟦null: no independent source value⟧ 3.5 (12) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ R5.5-4 ⟦null: no independent source value⟧ TIC 3.5
3 ⟦null: no independent source value⟧ 5.5 (10) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ TIC 5.5
4 2005/2008 5.5 (10) ⟦null: no independent source value⟧ M4 R5.5-4 Nichifu NH 1 / 9 TIC 5.5
5 2010/2015 14 (6) ⟦null: no independent source value⟧ M4 R14-6 Nichifu NOP 60 TIC 8
6 2030 38 (2) ⟦null: no independent source value⟧ M6 R38-6 Nichifu NOP 60 / 150H TIC 22
7 2050 80 (3/0) ⟦null: no independent source value⟧ M8 R80-8 Nichifu NOP 60 / 150H TIC 60
8 2075 150 (4/0) ⟦null: no independent source value⟧ M8 R150-8 Nichifu NOP 150H TIC 80
9 2125 300 (4/0)*2 ⟦null: no independent source value⟧ M10 R150-10 Nichifu NOP 150H TIC 100
10 2175 152 (300)*2 ⟦null: no independent source value⟧ M12 R150-12*2 Nichifu NOP 150H TIC 150
11 4001/4002/ 4003 2 (14) ⟦null: no independent source value⟧ M4 R2-4 Nichifu NH 1 / 9 TIC 2
12 ⟦null: no independent source value⟧ 3.5 (12) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ R5.5-4 ⟦null: no independent source value⟧ TIC 3.5
13 ⟦null: no independent source value⟧ 5.5 (10) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ TIC 5.5
14 4005/4008/ 4010 5.5 (10) ⟦null: no independent source value⟧ M4 R5.5-4 Nichifu NH 1 / 9 TIC 5.5
15 4015/4020 8 (8) ⟦null: no independent source value⟧ M6 R8-6 Nichifu NOP 60 TIC 8
16 4025/4030/ 4040 22 (6) ⟦null: no independent source value⟧ M6 R22-6 Nichifu NOP 60 / 150H TIC 14
17 4050/4060/ 4075 60 (2) ⟦null: no independent source value⟧ M8 R60-8 Nichifu NOP 60 / 150H TIC 38
18 4100/4125 150 (3/0) ⟦null: no independent source value⟧ M8 R150-8 Nichifu NOP 150H TIC 80
19 4150/4175/ 4215/4250 300 (4/0)*2 ⟦null: no independent source value⟧ M10 R150-10 Nichifu NOP 150H TIC 100
20 4300 203 (400)*2 ⟦null: no independent source value⟧ M12 R200-12S*2 Nichifu NOH 300K TIC 200
21 4375/4425 253 (500)*2 ⟦null: no independent source value⟧ M12 R325-12S*2 Nichifu NOH 300K TIC 325
22 4535/4670 152 (300)*4 ⟦null: no independent source value⟧ M10 R150-10*4 Nichifu NOP 150H TIC 150
23 4800 203 (400)*4 ⟦null: no independent source value⟧ M10 R200-10S *4 Nichifu NOH 300K TIC 200

Manual — UL input fuse selection — page 552

A-3

◆Type 1

During installation, all conduit hole plugs shall be removed, and all conduit holes shall be used.

PS : About 2175 and 4300~4425, please see additional data page.

Recommended Input Fuse Selection

Type1: all conduit-hole plugs removed,all holes used. Source refers2175 and4300–4425 to additional data page, not explicitly identified here; no claim that referenced page was acquired.18 200V-class three-phase and26 400V-class three-phase fuse rows. Separate fuse model and printed voltage/current.2020 alternatives Bussmann120FEE690V120A/FERRAZ A50QS150-4 500V150A.4030 alternatives Bussmann100FE690V100A/FERRAZ A50QS100-4 500V100A.4535/4670/4800 Bussmann170M6217 690V1400A. Preserve FERRAZ SHAWMUT spelling and grouped alternatives. Recommendations distinct from chapter11 fuse tables504–505; no collapse by drive HP.

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2001

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2002

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2003

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2005

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2008

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2010

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2015

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2020

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2025

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2030

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2040

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2050

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2060

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2075

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2100

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2125

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2150

UL recommended fuses:200Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 2175

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4001

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4002

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4003

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4005

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4008

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4010

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4015

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4020

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4025

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4030

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4040

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4050

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4060

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4075

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4100

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4125

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4150

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4175

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4215

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4250

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4300

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4375

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4425

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4535

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4670

UL recommended fuses:400Vclass three-phase. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 4800

UL input fuse selection table1 — PDF page 552

Source row Drive model F510 Fuse manufacturer/model Fuse voltage and ampere rating(A)
1 2001 Bussmann 20CT 690V 20A
2 2002 Bussmann 20CT 690V 20A
3 2003 Bussmann 30FE 690V 30A
4 2005 Bussmann 50FE 690V 50A
5 2008 Bussmann 50FE 690V 50A
6 2010 Bussmann 63FE 690V 63A
7 2015 FERRAZ SHAWMUT A50QS100-4 500V 100A
8 2020 Bussmann 120FEE / FERRAZ A50QS150-4 690V 120A / 500V 150A
9 2025 FERRAZ SHAWMUT A50QS150-4 500V 150A
10 2030 FERRAZ SHAWMUT A50QS200-4 500V 200A
11 2040 FERRAZ SHAWMUT A50QS250-4 500V 250A
12 2050 FERRAZ SHAWMUT A50QS300-4 500V 300A
13 2060 FERRAZ SHAWMUT A50QS400-4 500V 400A
14 2075 FERRAZ SHAWMUT A50QS500-4 500V 500A
15 2100 FERRAZ SHAWMUT A50QS600-4 500V 600A
16 2125 FERRAZ SHAWMUT A50QS700-4 500V 700A
17 2150 Bussmann 170M5464 690V 800A
18 2175 Bussmann 170M5464 690V 800A

UL input fuse selection table2 — PDF page 552

Source row Drive model F510 Fuse manufacturer/model Fuse voltage and ampere rating(A)
1 4001 Bussmann 10CT 690V 10A
2 4002 Bussmann 10CT 690V 10A
3 4003 Bussmann 16CT 690V 16A
4 4005 Bussmann 16CT 690V 16A
5 4008 Bussmann 25ET 690V 25A
6 4010 Bussmann 40FE 690V 40A
7 4015 Bussmann 50FE 690V 50A
8 4020 Bussmann 63FE 690V 63A
9 4025 Bussmann 80FE 690V 80A
10 4030 Bussmann 100FE / FERRAZ A50QS100-4 690V 100A / 500V 100A
11 4040 Bussmann 120FEE 690V 120A
12 4050 FERRAZ SHAWMUT A50QS150-4 500V 150A
13 4060 FERRAZ SHAWMUT A50QS200-4 500V 200A
14 4075 FERRAZ SHAWMUT A50QS250-4 500V 250A
15 4100 FERRAZ SHAWMUT A50QS300-4 500V 300A
16 4125 FERRAZ SHAWMUT A50QS400-4 500V 400A
17 4150 FERRAZ SHAWMUT A50QS500-4 500V 500A
18 4175 FERRAZ SHAWMUT A50QS600-4 500V 600A
19 4215 FERRAZ SHAWMUT A50QS700-4 500V 700A
20 4250 FERRAZ SHAWMUT A50QS700-4 500V 700A
21 4300 Bussmann 170M5464 690V 800A
22 4375 Bussmann 170M5464 690V 800A
23 4425 Bussmann 170M5466 690V 1000A
24 4535 Bussmann 170M6217 690V 1400A
25 4670 Bussmann 170M6217 690V 1400A
26 4800 Bussmann 170M6217 690V 1400A

Manual — UL end-use protection and short-circuit table — page 553

A-4

◆ Motor Over temperature Protection

Motor over temperature protection shall be provided in the end use application.

■ Field Wiring Terminals

All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the proper connections

that are to be made to each terminal and indicate that copper conductors, rated 75°C are to be used.

■ Drive Short-Circuit Rating

This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current flow will

not rise above value. Please see electrical ratings for maximum voltage and table below for current.

• The MCCB and breaker protection and fuse ratings (refer to the preceding table) shall be equal to or greater than the short-circuit

tolerance of the power supply being used.

• Suitable for use on a circuit capable of delivering not more than ( A ) RMS symmetrical amperes for ( Hp ) Hp in 240 / 480 V class

drives motor overload protection.

•

End-use motor overtemperature protection required. Non-motor-circuit input/output field terminals marked for connections and75°C copper conductors. UL short-circuit-test wording is a source claim, not independent certification. MCCB/breaker/fuse ratings equal or exceed supply short-circuit tolerance. Table1–50HP5000A,51–200HP10000A,201–400HP18000A,401–600HP30000A; each240/480V. No row above600HP despite larger drive models elsewhere; do not extend30000A to670/800HP. SCCR not continuous motor current.

UL short-circuit rating;HP/current/voltage;maximum600HP. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

UL short-circuit rating;HP/current/voltage;maximum600HP. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 1 - 50

UL short-circuit rating;HP/current/voltage;maximum600HP. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 51 - 200

UL short-circuit rating;HP/current/voltage;maximum600HP. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 201 - 400

UL short-circuit rating;HP/current/voltage;maximum600HP. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 401 - 600

UL end-use protection and short-circuit table table1 — PDF page 553

Source row Horse Power ( Hp ) Current ( A ) Voltage ( V )
1 1 - 50 5,000 240 / 480
2 51 - 200 10,000 240 / 480
3 201 - 400 18,000 240 / 480
4 401 - 600 30,000 240 / 480

Manual — Motor overload parameter selection — page 554

A-5

◆ Drive Motor Overload Protection

Set parameter 02-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor overload

protection is UL listed and in accordance with the NEC and CEC.

■ 02-01 Motor Rated Current

Setting Range: Model Dependent

Factory Default: Model Dependent

The motor rated current parameter (02-01) protects the motor and allows for proper vector control when using open loop vector or

flux vector control methods (00-00 = 2 or 3). The motor protection parameter 08-05 is set as factory default. Set 02-01 to the full load

amps (FLA) stamped on the nameplate of the motor.

The operator must enter the rated current of the motor (17-02) in the menu during auto-tuning. If the auto-tuning operation completes

successfully (17-00 = 0), the value entered into 17-02 will automatically write into 02-01.

■ 08-05 Motor Overload Protection Selection

The drive has an electronic overload protection function (OL1) based on time, output current, and output frequency, which protects the

motor from overheating. The electronic thermal overload function is UL-recognized, so it does not require an external thermal overload

relay for single motor operation.

This parameter selects the motor overload curve used according to the type of motor applied.

Overload Protection Settings

Sets the motor overload protection function in 08-05 according to the applicable motor.

Setting 08-05 = ---0B. Disables the motor overload protection function when two or more motors are connected to a single inverter.

Use an alternative method to provide separate overload protection for each motor such as connecting a thermal overload relay to the

power line of each motor.

Setting 08-05 = --1-B. The motor overload protection function should be set to hot start protection characteristic curve when the

power supply is turned on and off frequently, because the thermal values are reset each time when the power is turned off.

Setting 08-05 = -0--B. For motors without a forced cooling fan (general purpose standard motor), the heat dissipation capability is

lower when in low speed operation.

Setting 08-05 = -1--B. For motors with a forced cooling fan (inverter duty or V/F motor), the heat dissipation capability is not

dependent upon the rotating speed.

To protect the motor from overload by using electronic overload protection, be sure to set parameter 02-01 according to the rated

current value shown on the motor nameplate.

Refer to the following "Motor Overload Protection Time" for the standard motor overload protection curve example : Setting 08-05 = -0--B.

02-01 rated current setting/default model dependent; set motor FLA. Vector methods00-00=2or3; successful17-00=0 autotune copies17-02 into02-01. UL-listed/recognized NEC/CEC statements source-only.08-05 six bit patterns:---0B disable,---1B enable,--0-B cold,--1-B hot,-0--B standard,-1--B special. Multiple motors disable internal overload and provide separate each-motor protection. Frequent power cycling hot characteristic because thermal values reset on power-off. Standard without forced fan loses cooling at low speed; forced-fan inverter/VF motor heat dissipation not speed dependent. Graph is standard-motor example -0--B: x motor current% with02-01=100%, ticks100/150/200%; y protection time(min). Printed time labels from top5.5,3.0,3.5,1.0 are non-monotonic; preserve, no assumed2.5/1.5 correction. Cold Start dashed upper curve,Hot Start solid lower; low speed<60Hz/high speed>60Hz, no exact60Hz assignment or digitized points inferred.

{"PDF_page": 554, "bbox": [192.05999755859375, 535.9200439453125, 420.427978515625, 646.260009765625], "source_kind": "embedded raster image", "x_axis": "Motor Load Current (%) (02-01 = 100%)", "x_ticks": ["100%", "150%", "200%"], "y_axis": "Overload Protect Time (min)", "y_ticks_top_to_bottom": ["5.5", "3.0", "3.5", "1.0"], "curves": {"upper_dashed": "Cold Start", "lower_solid": "Hot Start"}, "speed_labels": ["Low Speed (<60 Hz)", "High Speed (>60 Hz)"], "interpretation_limit": "Printed numeric axis contradicts monotonic time; no interpolated or exact trip times inferred.", "method": "Two full renders plus4x enlargement; image labels explicitly read,not parser-derived"}

08-05 bit-pattern motor overload selection. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

08-05 bit-pattern motor overload selection. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: ---0B

08-05 bit-pattern motor overload selection. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: ---1B

08-05 bit-pattern motor overload selection. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: --0-B

08-05 bit-pattern motor overload selection. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: --1-B

08-05 bit-pattern motor overload selection. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: -0--B

08-05 bit-pattern motor overload selection. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: -1--B

Motor overload parameter selection table1 — PDF page 554

Source row Setting Description
1 ---0B Motor Overload Protection is disabled
2 ---1B Motor Overload Protection is enabled
3 --0-B Cold Start of Motor Overload
4 --1-B Hot Start of Motor Overload
5 -0--B Standard Motor
6 -1--B Special motor

Manual — Motor overload response mode — page 555

A-6

Motor Overload Protection Time

■ 08-06 Start-up mode of overload protection operation

08-06=0: When the inverter detects a motor overload the inverter output is turned off and the OL1 fault message will flash on the

keypad. Press RESET button on the keypad or activate the reset function through the multi-function inputs to reset the OL1 fault.

08-06=1: When the inverter detects a motor overload the inverter will continue running and the OL1 alarm message will flash on the

keypad until the motor current falls within the normal operating range.

Motor over temperature protection shall be provided in the end use application.

08-06=0 stop output after overload; OL1 fault flashes, reset by keypad RESET or multifunction-input reset.08-06=1 continues operation with OL1 alarm until motor current within normal range. End-use motor overtemperature protection still required. No default setting printed here; no default inferred.

08-06 overload response options. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred.

08-06 overload response options. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 0

08-06 overload response options. Exact source values, header units and physical row/column scope apply. No supplier conflict corrected or engineering approval inferred. Row group: 1

Motor overload response mode table1 — PDF page 555

Source row Setting Description
1 0 Stop Output after Overload Protection
2 1 Continuous Operation after Overload Protection

Manual — Manufacturer contacts and edition — page 556

TECO Electric & Machinery Co., Ltd.

This manual may be modified when necessary because of improvement of the product, modification, or changes in specifications. This manual is subject to change without notice.

Historical source contacts; no current validity asserted. Distributor box blank. Two local QR decodes agree on http://globalsa.teco.com.tw, which differs from printed http://industrialproducts.teco.com.tw/. Both retained; no URLs fetched.

F510 back-cover edition only; no later currency asserted.

Two local Vision decodes agree, at full-page and cropped scales. Payload differs from printed URL; neither fetched or assessed for currency.

Printed contacts and edition — PDF page 556

Source row Source label/context Source value
1 Address 10F., No.3-1, Yuancyu St., Nangang District, Taipei City 115, Taiwan
2 Tel +886-2-6615-9111
3 Fax +886-2-6615-0933
4 Web http://industrialproducts.teco.com.tw/
5 Manual number 4KA72X662T41
6 Version 09
7 Date 2020.01
8 Distributor [blank in source]

QR code payload — PDF page 556

Source row Source label/context Decoded payload
1 QR code http://globalsa.teco.com.tw

Quick setup guide — guide-SRC-3cc81701b120c961-teco-f510-quick-set-up-guide-p0001-0002

Source edition: TECO-F510-Quick-Set-up-Guide.pdf. Source key: SRC-3cc81701b120c961. Collected product associations: P002. These attachments do not establish applicability of every model or instruction to every linked product.

Supplier source reference(s):

Use the instructions, warnings, model/voltage/duty conditions and safety requirements of this complete source edition together. Historical dates, contact information and certification statements are preserved as source claims, not confirmation of current validity. Diagram geometry remains in the original document; descriptions do not reconstruct wiring. Navigation headings may combine source words with organisational context and are not uniformly verbatim supplier quotations.

Editorial note: source prose, reviewed tables and bounded diagram-label descriptions are presented together, with their roles identified. Paragraph line wrapping and bullet formatting are normalized. Source wording, source contradictions and edition-specific contacts are retained. References are editorial and do not establish wiring topology.

TECO F510 Enhanced - QUICK SET-UP GUIDE

This is a quick set-up guide for configuring the TECO E510s for either of the following control requirements:

Highlighted in the table below are the main parameter groups that are involved in this list of control requirements.

The visible introduction names TECO E510s although this source is titled F510 Enhanced. Both strings are preserved; this is not evidence of cross-product applicability.

Source table (SRC-3cc81701b120c961-SS17-P1-T1). Generic column labels below are editorial; the first data row retains the supplier headings.

Short Press DSP/FUN to change to Parameter Group

Press ▼ Twice

Cursor Movement: </RESET to move across, Up: ▲ Down: ▼

Short Press READ/ENTER, press DSP/FUN

Source labels and bounded description (SRC-3cc81701b120c961-F0051; PDF 1):

Motor parameter group02: -01 Motor Rated Current(A); -03 Motor Rated Speed(RPM); -05 Motor Rated Power(kW); -06 Motor Rated Frequency(Hz). Short press DSP/FUN to select group; press down twice to02; </RESET cursor; READ/ENTER then DSP/FUN per shown flow.

Original drawing geometry remains authoritative. This description does not reconstruct wiring connections.

Short Press READ/ENTER

Source labels and bounded description (SRC-3cc81701b120c961-F0052; PDF 1):

Group00 /00-02: Keypad0; External Switch1 (Default); Communication2. Labels0DigitalOp,1Terminal,2RS-485Comm; short READ/ENTER.

For additional support, please contact us at:

TECO VSD Tech Support: 0433 215 642

Email Address: vsdsupport@teco.com.au

Page - 1

Applicable when

Source labels and bounded description (SRC-3cc81701b120c961-F0053; PDF 2):

Group00 Basic Func / -02RUNSource =1Terminal.

Two external switches are required, one for forward direction and the other for reverse.

Switch type: two positions, maintained type.

Wiring Diagram:

Source labels and bounded description (SRC-3cc81701b120c961-F0054; PDF 2):

Heading says Forward/Stop – Reverse/Stop(Default), but figure labels S1(RUN/STOP), S2(REV/FWD),24V and SW6 Source(PNP)/Sink(NPN). Keep heading/figure mismatch unresolved.

The heading states Forward/Stop – Reverse/Stop (Default); its figure instead labels S1 (RUN/STOP) and S2 (REV/FWD). Both are retained. No inferred correction or wiring topology is supplied.

In this mode, two separated momentary push buttons are used for start and stop functions.

For S1 to initiate the Run command. Push button connected to S2 must be connected by a normally closed type contact (NC).

Parameter Setup: Initialize the 3-Wire.

Source labels and bounded description (SRC-3cc81701b120c961-F0055; PDF 2):

13 Drive Status / -08Initialize =005 3-Wire,230V/415V(50Hz). S1(RUN),S2(STOP),S3(FWD/REV),24V; SW6 Source(PNP)/Sink(NPN). Prose requires S2 normally closed contact.

Parameter Setup

Source labels and bounded description (SRC-3cc81701b120c961-F0056; PDF 2):

00 Basic Func / -05FreqSource: Keypad(Default)=0DigitalOp; External Terminal(2KΩPot)=1Analog; CommunicationControl=3RS-485Comm. Keypad operation example12-16=005.00Hz;12-17=000.00Hz;12-18=0000.0A; source illustration, not recommended operating values.

Cursor Movement: </RESET to move across, Up: ▲ Down: ▼ to set the Frequency Reference Value.

Source labels and bounded description (SRC-3cc81701b120c961-F0057; PDF 2):

-05FreqSource=1Analog;2kΩ potentiometer; +10V;AI1 MainSpeed FrequencyReferenceCommand(VoltageInput);AI2 MainSpeed FrequencyReferenceCommand(CurrentInput);GND;-10V;AI1/SW3 andAI2/SW4 V/I switches. Original wiring geometry authoritative.

Page - 2

The product photograph contains tiny label or nameplate text that has not been transcribed. The original PDF is preserved. Source wording and historical contacts are retained without a claim of current applicability or contact validity.

Parameter groups — PDF page 1

Source column 1 Source column 2
PARAMENTER GROUP No. Description
Group 00 Basic parameter
Group 01 V/F Control parameters
Group 02 IM Motor parameters
Group 03 External digital input and output parameters
Group 04 External analog input and output parameters
Group 05 Multi speed parameters
Group 06 Automatic program operation parameters
Group 07 Start/Stop parameters
Group 08 Protection parameters
Group 09 Communication parameters
Group 10 PID parameters
Group 11 Auxiliary parameters
Group 12 Monitoring parameters
Group 13 Maintenance parameters
Group 14 PLC parameters
Group 15 PLC monitoring parameters
Group 16 LCD parameters
Group 17 IM Motor Automatic Tuning Parameters
Group 18 Slip compensation parameters
Group 19 Speed control parameters
Group 20 Torque and control parameters
Group 21 PM motor parameters
Group 22 Pump & HVAC
Group 23 1 to 8 pump card function group

Technical source 001 — Variable speed drive F510-4001 -C3FN4-IP55, 0.75KW, 1HP, 380-460V

Source download: datasheet-1.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4001 -C3FN4-IP55, 0.75KW, 1HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 1 / 1 Variable Torque (kW/A): 0.75 / 3.4; Supply: 380-480V 3PH; IP Rating: 55; kW Rating: 0.75 Datasheet PDF / datasheet-1.pdf

P002 / Variable speed drive F510-4001 -C3FN4-IP55, 0.75KW, 1HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 1 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 2.6 as printed in field/value —
Output Rated / Rated Output Current(A) 3.4 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 1 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 0.75 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4001 -C3FN4-IP55, 0.75KW, 1HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Inverter Overload Inverter will be stopped when the output higher than 120% rated current as printed in field/value —
Protection Functions / Protection(OL2) for 1min, carrier frequency is 2~ 4KHZ *2 as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Over Voltage If the main circuit DC voltage rises over 820V (400V class), the motor as printed in field/value —
Protection Functions / Protection(OV) stops running. as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Momentary power loss Power loss exceeds 15ms. You can set the function of momentary power as printed in field/value —
Protection Functions / restart loss restart up to 2sec as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —

P002 / Variable speed drive F510-4001 -C3FN4-IP55, 0.75KW, 1HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4001 -C3FN4-IP55, 0.75KW, 1HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4001-C3FN4 189 (7.44) mm (inch) 284 (11.18) mm (inch) 186 (7.32) mm (inch) 171 (6.73) mm (inch) 266 (10.47) mm (inch) 1.2 (0.05) mm (inch) M5 mm (inch) 7 (15.43) kg (lbs) —

Technical source 002 — Variable speed drive F510-4002 -C3FN4-IP55, 1.5KW, 2HP, 380-460V

Source download: DataSheet_of_F510-4002-C3FN4-IP55.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4002 -C3FN4-IP55, 1.5KW, 2HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 2 / 2 Variable Torque (kW/A): 1.5 / 4.1; Supply: 380-480V 3PH; IP Rating: 55; kW Rating: 1.50 Datasheet PDF / DataSheet_of_F510-4002-C3FN4-IP55.pdf

P002 / Variable speed drive F510-4002 -C3FN4-IP55, 1.5KW, 2HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 2 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 3.1 as printed in field/value —
Output Rated / Rated Output Current(A) 4.1 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 2 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 1.5 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4002 -C3FN4-IP55, 1.5KW, 2HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Inverter Overload Inverter will be stopped when the output higher than 120% rated current as printed in field/value —
Protection Functions / Protection(OL2) for 1min, carrier frequency is 2~ 4KHZ *2 as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Over Voltage If the main circuit DC voltage rises over 820V (400V class), the motor as printed in field/value —
Protection Functions / Protection(OV) stops running. as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Momentary power loss Power loss exceeds 15ms. You can set the function of momentary power as printed in field/value —
Protection Functions / restart loss restart up to 2sec as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —

P002 / Variable speed drive F510-4002 -C3FN4-IP55, 1.5KW, 2HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4002 -C3FN4-IP55, 1.5KW, 2HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4002-C3FN4 189 (7.44) mm (inch) 284 (11.18) mm (inch) 186 (7.32) mm (inch) 171 (6.73) mm (inch) 266 (10.47) mm (inch) 1.2 (0.05) mm (inch) M5 mm (inch) 7 (15.43) kg (lbs) —

Technical source 003 — Variable speed drive F510-4003 -C3FN4-IP55, 2.2KW, 3HP, 380-460V

Source download: datasheet-3.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4003 -C3FN4-IP55, 2.2KW, 3HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 3 / 3 Variable Torque (kW/A): 2.2 / 5.4; Supply: 380-480V 3PH; IP Rating: 55; kW Rating: 2.20 Datasheet PDF / datasheet-3.pdf

P002 / Variable speed drive F510-4003 -C3FN4-IP55, 2.2KW, 3HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 3 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 4.1 as printed in field/value —
Output Rated / Rated Output Current(A) 5.4 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 3 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 2.2 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4003 -C3FN4-IP55, 2.2KW, 3HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Inverter Overload Inverter will be stopped when the output higher than 120% rated current as printed in field/value —
Protection Functions / Protection(OL2) for 1min, carrier frequency is 2~ 4KHZ *2 as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Over Voltage If the main circuit DC voltage rises over 820V (400V class), the motor as printed in field/value —
Protection Functions / Protection(OV) stops running. as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Momentary power loss Power loss exceeds 15ms. You can set the function of momentary power as printed in field/value —
Protection Functions / restart loss restart up to 2sec as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —

P002 / Variable speed drive F510-4003 -C3FN4-IP55, 2.2KW, 3HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4003 -C3FN4-IP55, 2.2KW, 3HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4003-C3FN4 189 (7.44) mm (inch) 284 (11.18) mm (inch) 186 (7.32) mm (inch) 171 (6.73) mm (inch) 266 (10.47) mm (inch) 1.2 (0.05) mm (inch) M5 mm (inch) 7 (15.43) kg (lbs) —

Technical source 004 — Variable speed drive F510-4005 -C3FN4-IP55, 4KW, 5HP, 380-460V

Source download: datasheet-4.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4005 -C3FN4-IP55, 4KW, 5HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 4 / 4 Variable Torque (kW/A): 4 / 9.2; Supply: 380-480V 3PH; IP Rating: 55; kW Rating: 4.00 Datasheet PDF / datasheet-4.pdf

P002 / Variable speed drive F510-4005 -C3FN4-IP55, 4KW, 5HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 5 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 7 as printed in field/value —
Output Rated / Rated Output Current(A) 9.2 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 5 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 4 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4005 -C3FN4-IP55, 4KW, 5HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4005 -C3FN4-IP55, 4KW, 5HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4005 -C3FN4-IP55, 4KW, 5HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4005-C3FN4 189 (7.44) mm (inch) 284 (11.18) mm (inch) 186 (7.32) mm (inch) 171 (6.73) mm (inch) 266 (10.47) mm (inch) 1.2 (0.05) mm (inch) M5 mm (inch) 7 (15.43) kg (lbs) —

Technical source 005 — Variable speed drive F510-4008 -C3FN4-IP55, 5.5KW, 7.5HP, 380-460V

Source download: datasheet-5.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4008 -C3FN4-IP55, 5.5KW, 7.5HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 5 / 5 Variable Torque (kW/A): 5.5 / 12.1; Supply: 380-480V 3PH; IP Rating: 55; kW Rating: 5.50 Datasheet PDF / datasheet-5.pdf

P002 / Variable speed drive F510-4008 -C3FN4-IP55, 5.5KW, 7.5HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 7.5 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 8.4 as printed in field/value —
Output Rated / Rated Output Current(A) 12.1 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 7.5 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 5.5 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4008 -C3FN4-IP55, 5.5KW, 7.5HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4008 -C3FN4-IP55, 5.5KW, 7.5HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4008 -C3FN4-IP55, 5.5KW, 7.5HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4008-C3FN4 189 (7.44) mm (inch) 284 (11.18) mm (inch) 186 (7.32) mm (inch) 171 (6.73) mm (inch) 266 (10.47) mm (inch) 1.2 (0.05) mm (inch) M5 mm (inch) 7 (15.43) kg (lbs) —

Technical source 006 — Variable speed drive F510-4010 -C3FN4-IP55, 7.5KW, 10HP, 380-460V

Source download: datasheet-6.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4010 -C3FN4-IP55, 7.5KW, 10HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 6 / 6 Variable Torque (kW/A): 7.5 / 17.5; Supply: 380-480V 3PH; IP Rating: 55; kW Rating: 7.50 Datasheet PDF / datasheet-6.pdf

P002 / Variable speed drive F510-4010 -C3FN4-IP55, 7.5KW, 10HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 10 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 13 as printed in field/value —
Output Rated / Rated Output Current(A) 17.5 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 10 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 7.5 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4010 -C3FN4-IP55, 7.5KW, 10HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4010 -C3FN4-IP55, 7.5KW, 10HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4010 -C3FN4-IP55, 7.5KW, 10HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4010-C3FN4 230 (9.06) mm (inch) 320 (12.60) mm (inch) 210 (8.27) mm (inch) 210 (8.27) mm (inch) 305 (12.01) mm (inch) 2 (0.08) mm (inch) M5 mm (inch) 10.5 (23.15) kg (lbs) —

Technical source 007 — Variable speed drive F510-4015 -C3FN4-IP55, 11KW, 15HP, 380-460V

Source download: datasheet-7.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4015 -C3FN4-IP55, 11KW, 15HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 7 / 7 Variable Torque (kW/A): 11 / 23; Supply: 380-480V 3PH; IP Rating: 55; kW Rating: 11.00 Datasheet PDF / datasheet-7.pdf

P002 / Variable speed drive F510-4015 -C3FN4-IP55, 11KW, 15HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 15 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 18 as printed in field/value —
Output Rated / Rated Output Current(A) 23 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 15 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 11 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4015 -C3FN4-IP55, 11KW, 15HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4015 -C3FN4-IP55, 11KW, 15HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4015 -C3FN4-IP55, 11KW, 15HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4015-C3FN4 230 (9.06) mm (inch) 320 (12.60) mm (inch) 210 (8.27) mm (inch) 210 (8.27) mm (inch) 305 (12.01) mm (inch) 2 (0.08) mm (inch) M5 mm (inch) 10.5 (23.15) kg (lbs) —

Technical source 008 — Variable speed drive F510-4020 -C3FN4-IP55, 15KW, 20HP, 380-460V

Source download: datasheet-8.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4020 -C3FN4-IP55, 15KW, 20HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 8 / 8 Variable Torque (kW/A): 15 / 31; Supply: 380-480V 3PH; IP Rating: 55; kW Rating: 15.00 Datasheet PDF / datasheet-8.pdf

P002 / Variable speed drive F510-4020 -C3FN4-IP55, 15KW, 20HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 20 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 24 as printed in field/value —
Output Rated / Rated Output Current(A) 31 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 20 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 15 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4020 -C3FN4-IP55, 15KW, 20HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4020 -C3FN4-IP55, 15KW, 20HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4020 -C3FN4-IP55, 15KW, 20HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4020-C3FN4 265 (10.43) mm (inch) 396 (15.59) mm (inch) 227 (8.94) mm (inch) 249 (9.80) mm (inch) 380 (14.96) mm (inch) 2 (0.08) mm (inch) M5 mm (inch) 17 (37.48) kg (lbs) —

Technical source 009 — Variable speed drive F510-4025 -C3FN4-IP55, 18.5KW, 25HP, 380-460V

Source download: datasheet-9.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4025 -C3FN4-IP55, 18.5KW, 25HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 9 / 9 Variable Torque (kW/A): 18.5 / 38; Supply: 380-480V 3PH; IP Rating: 55; kW Rating: 18.50 Datasheet PDF / datasheet-9.pdf

P002 / Variable speed drive F510-4025 -C3FN4-IP55, 18.5KW, 25HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 25 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 28.9 as printed in field/value —
Output Rated / Rated Output Current(A) 38 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 25 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 18.5 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4025 -C3FN4-IP55, 18.5KW, 25HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4025 -C3FN4-IP55, 18.5KW, 25HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4025 -C3FN4-IP55, 18.5KW, 25HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4025-C3FN4 265 (10.43) mm (inch) 396 (15.59) mm (inch) 227 (8.94) mm (inch) 249 (9.80) mm (inch) 380 (14.96) mm (inch) 2 (0.08) mm (inch) M5 mm (inch) 17 (37.48) kg (lbs) —

Technical source 010 — Variable speed drive F510-4030 -C3FN4-IP55, 22KW, 30HP, 380-460V

Source download: datasheet-10.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4030 -C3FN4-IP55, 22KW, 30HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 10 / 10 Variable Torque (kW/A): 22 / 44; Supply: 380-480V 3PH; IP Rating: 55; kW Rating: 22.00 Datasheet PDF / datasheet-10.pdf

P002 / Variable speed drive F510-4030 -C3FN4-IP55, 22KW, 30HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 30 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 34 as printed in field/value —
Output Rated / Rated Output Current(A) 44 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 30 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 22 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4030 -C3FN4-IP55, 22KW, 30HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4030 -C3FN4-IP55, 22KW, 30HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4030 -C3FN4-IP55, 22KW, 30HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4030-C3FN4 224 (8.82) mm (inch) 527 (20.75) mm (inch) 311 (12.24) mm (inch) 180 (7.09) mm (inch) 505 (19.88) mm (inch) 2 (0.08) mm (inch) M10 mm (inch) 32.5 (71.65) kg (lbs) —

Technical source 011 — Variable speed drive F510-4125-C3-IP00, 90KW, 125HP, 380-460V

Source download: datasheet-16.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4125-C3-IP00, 90KW, 125HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 11 / 11 Variable Torque (kW/A): 90 / 168; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 90.00 Datasheet PDF / datasheet-16.pdf

P002 / Variable speed drive F510-4125-C3-IP00, 90KW, 125HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 125 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 125 as printed in field/value —
Output Rated / Rated Output Current(A) 168 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 125 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 90 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4125-C3-IP00, 90KW, 125HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4125-C3-IP00, 90KW, 125HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4125-C3-IP00, 90KW, 125HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4125-C3 344 (13.54) mm (inch) 580 (22.83) mm (inch) 300 (11.81) mm (inch) 250 (9.84) mm (inch) 560 (22.05) mm (inch) 1.6 (0.06) mm (inch) M10 mm (inch) 40.5 (89.29) kg (lbs) —

Technical source 012 — Variable speed drive F510-4150-C3-IP00, 110KW, 150HP, 380-460V

Source download: datasheet-17.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4150-C3-IP00, 110KW, 150HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 12 / 12 Variable Torque (kW/A): 110 / 208; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 110.00 Datasheet PDF / datasheet-17.pdf

P002 / Variable speed drive F510-4150-C3-IP00, 110KW, 150HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 150 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 158 as printed in field/value —
Output Rated / Rated Output Current(A) 208 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 150 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 110 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4150-C3-IP00, 110KW, 150HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4150-C3-IP00, 110KW, 150HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4150-C3-IP00, 110KW, 150HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4150-C3 459 (18.07) mm (inch) 790 (31.10) mm (inch) 324.5 (12.78) mm (inch) 320 (12.60) mm (inch) 760 (29.92) mm (inch) 1.6 (0.06) mm (inch) M10 mm (inch) 74 (163.14) kg (lbs) —

Technical source 013 — Variable speed drive F510-4175-C3-IP00, 132KW, 175HP, 380-460V

Source download: datasheet-18.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4175-C3-IP00, 132KW, 175HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 13 / 13 Variable Torque (kW/A): 132 / 250; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 132.00 Datasheet PDF / datasheet-18.pdf

P002 / Variable speed drive F510-4175-C3-IP00, 132KW, 175HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 175 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 190 as printed in field/value —
Output Rated / Rated Output Current(A) 250 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 175 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 132 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4175-C3-IP00, 132KW, 175HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4175-C3-IP00, 132KW, 175HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4175-C3-IP00, 132KW, 175HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4175-C3 459 (18.07) mm (inch) 790 (31.10) mm (inch) 324.5 (12.78) mm (inch) 320 (12.60) mm (inch) 760 (29.92) mm (inch) 1.6 (0.06) mm (inch) M10 mm (inch) 74 (163.14) kg (lbs) —

Technical source 014 — Variable speed drive F510-4215-C3-IP00, 160KW, 215HP, 380-460V

Source download: datasheet-19.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4215-C3-IP00, 160KW, 215HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 14 / 14 Variable Torque (kW/A): 160 / 296; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 160.00 Datasheet PDF / datasheet-19.pdf

P002 / Variable speed drive F510-4215-C3-IP00, 160KW, 215HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 215 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 225 as printed in field/value —
Output Rated / Rated Output Current(A) 296 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 215 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 160 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4215-C3-IP00, 160KW, 215HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4215-C3-IP00, 160KW, 215HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4215-C3-IP00, 160KW, 215HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4215-C3 459 (18.07) mm (inch) 790 (31.10) mm (inch) 324.5 (12.78) mm (inch) 320 (12.60) mm (inch) 760 (29.92) mm (inch) 1.6 (0.06) mm (inch) M10 mm (inch) 74 (163.14) kg (lbs) —

Technical source 015 — Variable speed drive F510-4250-C3-IP00, 185KW, 250HP, 380-460V

Source download: datasheet-20.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4250-C3-IP00, 185KW, 250HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 15 / 15 Variable Torque (kW/A): 185 / 328; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 185.00 Datasheet PDF / datasheet-20.pdf

P002 / Variable speed drive F510-4250-C3-IP00, 185KW, 250HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 250 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 250 as printed in field/value —
Output Rated / Rated Output Current(A) 328 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 250 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 185 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4250-C3-IP00, 185KW, 250HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4250-C3-IP00, 185KW, 250HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4250-C3-IP00, 185KW, 250HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
F510-4250-C3 459 (18.07) mm (inch) 790 (31.10) mm (inch) 324.5 (12.78) mm (inch) 320 (12.60) mm (inch) 760 (29.92) mm (inch) 1.6 (0.06) mm (inch) M10 mm (inch) 74 (163.14) kg (lbs) —

Technical source 016 — Variable speed drive F510-4300-C3-IP00, 220KW, 300HP, 380-460V

Source download: datasheet-21.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4300-C3-IP00, 220KW, 300HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 16 / 16 Variable Torque (kW/A): 220 / 435; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 220.00 Datasheet PDF / datasheet-21.pdf

P002 / Variable speed drive F510-4300-C3-IP00, 220KW, 300HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 300 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 331 as printed in field/value —
Output Rated / Rated Output Current(A) 435 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 300 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 220 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4300-C3-IP00, 220KW, 300HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4300-C3-IP00, 220KW, 300HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4300-C3-IP00, 220KW, 300HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 W2 H1 t d NW in kg(lbs) Conditions
F510-4300-C3 690 (27.17) mm (inch) 1000 (39.37) mm (inch) 410 (16.14) mm (inch) 530 (20.87) mm (inch) 265 (10.43) mm (inch) 960 (37.80) mm (inch) 1.6 (0.06) mm (inch) M12 mm (inch) 184 (405.65) kg (lbs) —

Technical source 017 — Variable speed drive F510-4375-C3-IP00, 280KW, 375HP, 380-460V

Source download: datasheet-22.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4375-C3-IP00, 280KW, 375HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 17 / 17 Variable Torque (kW/A): 280 / 515; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 280.00 Datasheet PDF / datasheet-22.pdf

P002 / Variable speed drive F510-4375-C3-IP00, 280KW, 375HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 375 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 392 as printed in field/value —
Output Rated / Rated Output Current(A) 515 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 375 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 280 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4375-C3-IP00, 280KW, 375HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4375-C3-IP00, 280KW, 375HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4375-C3-IP00, 280KW, 375HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 W2 H1 t d NW in kg(lbs) Conditions
F510-4375-C3 690 (27.17) mm (inch) 1000 (39.37) mm (inch) 410 (16.14) mm (inch) 530 (20.87) mm (inch) 265 (10.43) mm (inch) 960 (37.80) mm (inch) 1.6 (0.06) mm (inch) M12 mm (inch) 184 (405.65) kg (lbs) —

Technical source 018 — Variable speed drive F510-4425-C3-IP00, 315KW, 425HP, 380-460V

Source download: datasheet-23.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4425-C3-IP00, 315KW, 425HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 18 / 18 Variable Torque (kW/A): 315 / 585; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 315.00 Datasheet PDF / datasheet-23.pdf

P002 / Variable speed drive F510-4425-C3-IP00, 315KW, 425HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 425 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 445 as printed in field/value —
Output Rated / Rated Output Current(A) 585 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 425 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 315 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4425-C3-IP00, 315KW, 425HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4425-C3-IP00, 315KW, 425HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4425-C3-IP00, 315KW, 425HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 W2 H1 t d NW in kg(lbs) Conditions
F510-4425-C3 690 (27.17) mm (inch) 1000 (39.37) mm (inch) 410 (16.14) mm (inch) 530 (20.87) mm (inch) 265 (10.43) mm (inch) 960 (37.80) mm (inch) 1.6 (0.06) mm (inch) M12 mm (inch) 184 (405.65) kg (lbs) —

Technical source 019 — Variable speed drive F510-4535-C3-IP00, 400KW, 535HP, 380-460V

Source download: datasheet-24.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4535-C3-IP00, 400KW, 535HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 19 / 19 Variable Torque (kW/A): 400 / 700; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 400.00 Datasheet PDF / datasheet-24.pdf

P002 / Variable speed drive F510-4535-C3-IP00, 400KW, 535HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 535 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 525 as printed in field/value —
Output Rated / Rated Output Current(A) 700 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 535 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 400 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4535-C3-IP00, 400KW, 535HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4535-C3-IP00, 400KW, 535HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4535-C3-IP00, 400KW, 535HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 W2 W3 H1 H2 H3 t d NW in kg(lbs) Conditions
F510-4535-C3 958 (37.72) mm (inch) 1356 (53.38) mm (inch) 507 (19.96) mm (inch) 916 (36.06) mm (inch) 158 (6.22) mm (inch) 600 (23.62) mm (inch) 1200 (47.24) mm (inch) 300 (11.81) mm (inch) 63.5 (2.50) mm (inch) 6.2 (0.24) mm (inch) M12 mm (inch) 335 (739) kg (lbs) —

Technical source 020 — Variable speed drive F510-4670-C3-IP00, 500KW, 670HP, 380-460V

Source download: datasheet-25.pdf.

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P002, Variable speed drive F510-4670-C3-IP00, 500KW, 670HP, 380-460V, page 5

Website associations for this source

Table / row / row ID Listed specification Document role / member
91 / 20 / 20 Variable Torque (kW/A): 500 / 875; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 500.00 Datasheet PDF / datasheet-25.pdf

P002 / Variable speed drive F510-4670-C3-IP00, 500KW, 670HP, 380-460V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name F510 as printed in field/value —
Inverter Capacity(HP) 670 as printed in field/value —
Output Rated / Rated Output Capacity(KVA) 640 as printed in field/value —
Output Rated / Rated Output Current(A) 875 as printed in field/value —
Output Rated / Maximum Applicable Motor / (HP) 670 as printed in field/value —
Output Rated / Maximum Applicable Motor / (KW) 500 as printed in field/value —
Output Rated / Maximum Output Voltage(V) Three Phase, 380~480V as printed in field/value —
Output Rated / Maximum Output / Frequency(Hz) Based on parameter setting 0.1~400.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V~480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage / Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Control characteristics / Display LCD keypad(HOA LCD keypad option) as printed in field/value —
Control characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed in field/value —
Control characteristics / Output Frequency 0.1Hz~400.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy Digital references: ±0.01%(-10~+40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), as printed in field/value —
Control characteristics / Speed Control Accuracy ±0.5%(sensorless Vector Control Mode)*1 as printed in field/value —
Control characteristics / Frequency setting Resolution Digital references: 0.01Hz, Analog refrences:0.06Hz/60Hz as printed in field/value —
Control characteristics / Output Frequency / Resolution 0.01Hz as printed in field/value —
Control characteristics / Overload Tolerance 120%/1min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V / 0~ 20 mA or 4~ 20mA as printed in field/value —

P002 / Variable speed drive F510-4670-C3-IP00, 500KW, 670HP, 380-460V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 0.0~ 6000.0 second(separately set acceleration and deceleration time) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Can arbitrarily set V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 20% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over-voltage protection, Dynamic braking, Speed search, Momentary power loss restart, 2 sets of PID control, Slide difference Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch as printed in field/value —
Control characteristics / Other Functions Records of power on and operation time, 4 fault history records and latest fault record state, Energy-saving function, Phase loss protection, Smart braking, DC braking, Dwell , S curve acceleration and deceleration, Up/Down operation, Modbus, BACnet MS/TP and Metasys N2 communication protocol, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without protection) as printed in field/value —
Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 160% of the inverter rated current as printed in field/value —
Protection Functions / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Under Voltage Protection(UV) If the main circuit DC voltage falls below 380V (400V class), the motor stops running as printed in field/value —
Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed in field/value —
Protection Functions / Ground Fault / Protection(GF) Protection by current detection circuit as printed in field/value —
Protection Functions / Charge Indicator When main circuit Dc voltage ≧50V, the CHARGE LED is on as printed in field/value —
Protection Functions / Output Phase Loss / Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature -10~ +40℃ (IP20/NEMA1 and IP55/NEMA12), -10~+50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ as printed in field/value —
Environment Specification / Storage Temperature -20~ +70℃ as printed in field/value —
Environment Specification / Humidity 95%RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower,1.0G, in compliance with IEC 60068-2-6 as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet/ Metasys N2) as printed in field/value —
PLC Function Built-in as printed in field/value —
Protection Functions / Inverter Overload Protection(OL2) Inverter will be stopped when the output higher than 120% rated current for 1min, carrier frequency is 2~4KHZ *2 as printed in field/value C1
Protection Functions / Over Voltage Protection(OV) If the main circuit DC voltage rises over 820V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed in field/value —

P002 / Variable speed drive F510-4670-C3-IP00, 500KW, 670HP, 380-460V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Electromagnetic Meet EN61800-3 standard, IP20 400V 75HP or below and IP55 400V as printed in field/value —
Interference(EMI) 60HP can be built in as printed in field/value —

P002 / Variable speed drive F510-4670-C3-IP00, 500KW, 670HP, 380-460V — source page 5 — PDF page 5

Configuration / printed row W H D W1 W2 W3 H1 H2 H3 t d NW in kg(lbs) Conditions
F510-4670-C3 958 (37.72) mm (inch) 1356 (53.38) mm (inch) 507 (19.96) mm (inch) 916 (36.06) mm (inch) 158 (6.22) mm (inch) 600 (23.62) mm (inch) 1200 (47.24) mm (inch) 300 (11.81) mm (inch) 63.5 (2.50) mm (inch) 6.2 (0.24) mm (inch) M12 mm (inch) 335 (739) kg (lbs) —

Technical source 021 — F510-EnhancedEn20210330.pdf

Source download: F510-EnhancedEn20210330.pdf.

Product-level attachment; no technical website row association was collected for this source.

Source differences and limitations

Source page context / 1 — P002, F510-EnhancedEn20210330.pdf, page 1

Conditions for this section:

F510 Enhanced. Family booklet; publication code GJ-91-01, 2021-03-30 (back cover).

Source page context / 2 — P002, F510-EnhancedEn20210330.pdf, page 2

Conditions for this section:

Mechanical features. F510 has a modular design for applications requiring a high protection level and for equipment maintenance, including a hot-plug display, communication card and removable fan. The enclosure illustration is labelled IP20/IP21/NEMA1; model/frame restrictions remain source-specific.

Source page context / 3 — P002, F510-EnhancedEn20210330.pdf, page 3

Conditions for this section:

Hand/Auto/Off. Hand/Auto selection is intended for system failure, test and inspection. This function requires the optional HOA digital operator. Illustrated features: easy assembly and hot-plug digital keypad; LED/LCD keypad with LCD for multiple languages; easy-assembly terminal cover to save installation time; quick-install fan for maintenance. Display screenshots are illustrations, not selected operating setpoints or model ratings.

Source page context / 4 — P002, F510-EnhancedEn20210330.pdf, page 4

Conditions for this section:

Energy-efficient pump control. Built-in PID and simple PLC support constant-pressure water-supply applications, with quick parameter setting. Pump cascade control uses an optional pump card. A 1-to-8 pump card is available for larger water-supply and constant-pressure applications. F510 supplies variable-frequency power for continuously variable pump speed and stable pressure through its PID controller. Up to eight pumps require the 1-to-8 pump option card.

Source page context / 5 — P002, F510-EnhancedEn20210330.pdf, page 5

Conditions for this section:

Excellent pump control. Built-in multi-pump control coordinates pumps according to water-system load and distributes running hours evenly across master and slave pumps to improve system efficiency and extend drive life. Blockage inspection detects a clogged pump and gives an alarm to prevent excess pressure damaging pipes. Sleep mode detects low or zero flow and can stop the system to save energy and extend drive life. Dry-pump protection evaluates system pressure and detects dry running; it shuts off the pump immediately to protect it from heat and friction damage.

Source page context / 6 — P002, F510-EnhancedEn20210330.pdf, page 6

Conditions for this section:

Fan control. The booklet describes hardware safe torque off and fire override for emergencies. Fire override is intended for smoke extraction by an air conditioner or fume extractor. In Fire mode the drive operates at full load, forward or reverse, and ignores all software protection until hardware protection operates or the drive is damaged. This limitation is part of the function. Skip frequency uses quick parameter setting to avoid resonance and prevent mechanical damage to the system and fans.

Source page context / 7 — P002, F510-EnhancedEn20210330.pdf, page 7

Conditions for this section:

Robust design. PCB coating for all series is described for harsh environments against IEC 60721-3-3 Class 3C3. Other features are a vibration-resistant structure with wire cable for C/B and M/B, an external heatsink for improved cooling, and isolation of airflow from all PCB boards to prevent dust or oil-mist penetration. These are statements from the booklet edition.

Source page context / 8 — P002, F510-EnhancedEn20210330.pdf, page 8

Conditions for this section:

Communication network protocols. Building-automation network functions include BACnet, Metasys N2 and Modbus; the booklet describes reduced installation cost for automatic central air conditioning. Metasys N2 was developed by Johnson Controls Inc. for building users and managers. It is described as easy to install, use, adjust and maintain, and able to collect, record, preserve and manage system messages and data for automatic management and energy saving. Contact TECO sales if Metasys N2 is to be used.

Source page context / 9 — P002, F510-EnhancedEn20210330.pdf, page 9

Conditions for this section:

BACnet is described as a communications protocol for building automation and control networks and an ASHRAE, ANSI and ISO standard protocol. It supports communication for heating, ventilation, air conditioning, lighting, access control, fire detection and associated equipment, allowing devices to exchange information regardless of building service. Modbus is described as a de facto standard communications protocol and a commonly available way to connect industrial electronic devices.

Source page context / 10 — P002, F510-EnhancedEn20210330.pdf, page 10

Conditions for this section:

Permanent-magnet motor control technology is described as reducing energy waste and supporting energy saving and emission reduction. Ultra-low motor noise: Soft PWM reduces common-mode voltage to restrain EMI and reduce audible motor noise for a quieter industrial environment. Traditional and Soft PWM waveforms are illustrations, not tabulated performance guarantees. The booklet states conformity with the RoHS directive, UL/cUL approval and CE/RCM certification. These are edition-specific printed claims, not confirmation of current certification.

Source page context / 11 — P002, F510-EnhancedEn20210330.pdf, page 11

Conditions for this section:

Saving energy. The booklet positions F510 energy-saving technologies in the context of energy saving and emission reduction. RTC function / simple PLC: built-in simple PLC with Real Time Clock supports load control, reducing unnecessary expense and human-resource cost, and modulating load for daylight saving. RTC is only for the LCD keypad. Automatic Energy Saving adjusts output voltage and lowers drive output current automatically according to load; output power changes with load, and AES is described as most efficient at light duty. The 25% saving illustration was tested at 20% load using a 30 HP VFD to drive a motor of the same rating. It is not an unconditional installation saving.

Source page context / 12 — P002, F510-EnhancedEn20210330.pdf, page 12

Conditions for this section:

Communication, I/O expansion and DC24V power cards. Expansion Slot 1 (CN3): JN5-IO-8DO 1-to-8 pump card supports larger water-supply and constant-pressure applications with up to eight pumps; JN5-PS-DC24V allows communication with the inverter and parameter setup or copying without main power. Expansion Slot 1 (CN2): communication cards extend support for the upper controller protocol; see the accessory table for specifications. JN5-IO-2DO1AI is described here as adding one relay, one transistor and one analogue output with -10V ~ 10V / 4~20mA. The page 21 accessory table instead says analogue input; direction remains unresolved. CN3 and CN2 both carry the printed label Expansion Slot 1. Built-in Safety Torque Off (STO) is stated to comply with EN ISO 13849-1 Cat/PLd, EN60204-1 Category 0, EN61508 SIL2 and EN62061 SIL CL2. The booklet says this can save contactor cost and installation space and provide quick reliable protection. The comparison sketches are not a substitute for the source wiring/safety instructions; no wiring topology is reconstructed.

Conditions for this section:

Wiring diagram and associated notes: refer to the original page; connections are not reconstructed from text.

Conditions for this section:

Dimensions — P002, F510-EnhancedEn20210330.pdf, page 16

Conditions for this section:

Dimensions — P002, F510-EnhancedEn20210330.pdf, page 17

Conditions for this section:

Dimensions — P002, F510-EnhancedEn20210330.pdf, page 18

Conditions for this section:

Dimensions — P002, F510-EnhancedEn20210330.pdf, page 19

Conditions for this section:

Dimensions — P002, F510-EnhancedEn20210330.pdf, page 20

Conditions for this section:

Conditions for this section:

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Source page context / 24 — P002, F510-EnhancedEn20210330.pdf, page 24

Conditions for this section:

TECO Electric & Machinery Co., Ltd. Back-cover website: http://www.teco.com.tw. Publication code/date: GJ-91-01 2021-03-30. This is the printed edition information, not a current contact or revision verification.

P002 / F510-EnhancedEn20210330.pdf — source page 13 — PDF page 13

Specification Value Unit / basis Conditions
200 V class / 1 HP / Inverter capacity (HP) 1 as printed C1
200 V class / 1 HP / Rated output capacity (kVA) 1.9 as printed C1
200 V class / 1 HP / Rated output current (A) 5.0 as printed C1
200 V class / 1 HP / Maximum applicable motor (HP) 1 as printed C1
200 V class / 1 HP / Maximum applicable motor (kW) 0.75 as printed C1
200 V class / 2 HP / Inverter capacity (HP) 2 as printed C1
200 V class / 2 HP / Rated output capacity (kVA) 2.9 as printed C1
200 V class / 2 HP / Rated output current (A) 7.5 as printed C1
200 V class / 2 HP / Maximum applicable motor (HP) 2 as printed C1
200 V class / 2 HP / Maximum applicable motor (kW) 1.5 as printed C1
200 V class / 3 HP / Inverter capacity (HP) 3 as printed C1
200 V class / 3 HP / Rated output capacity (kVA) 4.0 as printed C1
200 V class / 3 HP / Rated output current (A) 10.6 as printed C1
200 V class / 3 HP / Maximum applicable motor (HP) 3 as printed C1
200 V class / 3 HP / Maximum applicable motor (kW) 2.2 as printed C1
200 V class / 5 HP / Inverter capacity (HP) 5 as printed C1
200 V class / 5 HP / Rated output capacity (kVA) 5.5 as printed C1
200 V class / 5 HP / Rated output current (A) 14.5 as printed C1
200 V class / 5 HP / Maximum applicable motor (HP) 5 as printed C1
200 V class / 5 HP / Maximum applicable motor (kW) 3.7 as printed C1
200 V class / 7.5 HP / Inverter capacity (HP) 7.5 as printed C1
200 V class / 7.5 HP / Rated output capacity (kVA) 8 as printed C1
200 V class / 7.5 HP / Rated output current (A) 22 as printed C1
200 V class / 7.5 HP / Maximum applicable motor (HP) 7.5 as printed C1
200 V class / 7.5 HP / Maximum applicable motor (kW) 5.5 as printed C1
200 V class / 10 HP / Inverter capacity (HP) 10 as printed C1
200 V class / 10 HP / Rated output capacity (kVA) 11.4 as printed C1
200 V class / 10 HP / Rated output current (A) 30 as printed C1
200 V class / 10 HP / Maximum applicable motor (HP) 10 as printed C1
200 V class / 10 HP / Maximum applicable motor (kW) 7.5 as printed C1
200 V class / 15 HP / Inverter capacity (HP) 15 as printed C1
200 V class / 15 HP / Rated output capacity (kVA) 15.2 as printed C1
200 V class / 15 HP / Rated output current (A) 42 as printed C1
200 V class / 15 HP / Maximum applicable motor (HP) 15 as printed C1
200 V class / 15 HP / Maximum applicable motor (kW) 11 as printed C1
200 V class / 20 HP / Inverter capacity (HP) 20 as printed C1
200 V class / 20 HP / Rated output capacity (kVA) 21.3 as printed C1
200 V class / 20 HP / Rated output current (A) 56 as printed C1
200 V class / 20 HP / Maximum applicable motor (HP) 20 as printed C1
200 V class / 20 HP / Maximum applicable motor (kW) 15 as printed C1
200 V class / 25 HP / Inverter capacity (HP) 25 as printed C1
200 V class / 25 HP / Rated output capacity (kVA) 26.2 as printed C1
200 V class / 25 HP / Rated output current (A) 69 as printed C1
200 V class / 25 HP / Maximum applicable motor (HP) 25 as printed C1
200 V class / 25 HP / Maximum applicable motor (kW) 18.5 as printed C1
200 V class / 30 HP / Inverter capacity (HP) 30 as printed C1
200 V class / 30 HP / Rated output capacity (kVA) 30 as printed C1
200 V class / 30 HP / Rated output current (A) 80 as printed C1
200 V class / 30 HP / Maximum applicable motor (HP) 30 as printed C1
200 V class / 30 HP / Maximum applicable motor (kW) 22 as printed C1
200 V class / 40 HP / Inverter capacity (HP) 40 as printed C1
200 V class / 40 HP / Rated output capacity (kVA) 41.9 as printed C1
200 V class / 40 HP / Rated output current (A) 110 as printed C1
200 V class / 40 HP / Maximum applicable motor (HP) 40 as printed C1
200 V class / 40 HP / Maximum applicable motor (kW) 30 as printed C1
200 V class / 50 HP / Inverter capacity (HP) 50 as printed C1
200 V class / 50 HP / Rated output capacity (kVA) 52.5 as printed C1
200 V class / 50 HP / Rated output current (A) 138 as printed C1
200 V class / 50 HP / Maximum applicable motor (HP) 50 as printed C1
200 V class / 50 HP / Maximum applicable motor (kW) 37 as printed C1
200 V class / 60 HP / Inverter capacity (HP) 60 as printed C1
200 V class / 60 HP / Rated output capacity (kVA) 64.3 as printed C1
200 V class / 60 HP / Rated output current (A) 169 as printed C1
200 V class / 60 HP / Maximum applicable motor (HP) 60 as printed C1
200 V class / 60 HP / Maximum applicable motor (kW) 45 as printed C1
200 V class / 75 HP / Inverter capacity (HP) 75 as printed C1
200 V class / 75 HP / Rated output capacity (kVA) 76.2 as printed C1
200 V class / 75 HP / Rated output current (A) 200 as printed C1
200 V class / 75 HP / Maximum applicable motor (HP) 75 as printed C1
200 V class / 75 HP / Maximum applicable motor (kW) 55 as printed C1
200 V class / 100 HP / Inverter capacity (HP) 100 as printed C1
200 V class / 100 HP / Rated output capacity (kVA) 95.2 as printed C1
200 V class / 100 HP / Rated output current (A) 250 as printed C1
200 V class / 100 HP / Maximum applicable motor (HP) 100 as printed C1
200 V class / 100 HP / Maximum applicable motor (kW) 75 as printed C1
200 V class / 125 HP / Inverter capacity (HP) 125 as printed C1
200 V class / 125 HP / Rated output capacity (kVA) 119 as printed C1
200 V class / 125 HP / Rated output current (A) 312 as printed C1
200 V class / 125 HP / Maximum applicable motor (HP) 125 as printed C1
200 V class / 125 HP / Maximum applicable motor (kW) 90 as printed C1
200 V class / 150 HP / Inverter capacity (HP) 150 as printed C1
200 V class / 150 HP / Rated output capacity (kVA) 152 as printed C1
200 V class / 150 HP / Rated output current (A) 400 as printed C1
200 V class / 150 HP / Maximum applicable motor (HP) 150 as printed C1
200 V class / 150 HP / Maximum applicable motor (kW) 110 as printed C1
200 V class / 175 HP / Inverter capacity (HP) 175 as printed C1
200 V class / 175 HP / Rated output capacity (kVA) 171 as printed C1
200 V class / 175 HP / Rated output current (A) 450 as printed C1
200 V class / 175 HP / Maximum applicable motor (HP) 175 as printed C1
200 V class / 175 HP / Maximum applicable motor (kW) 130 as printed C1
200 V class / 1 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 2 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 3 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 5 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 7.5 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 10 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 15 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 20 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 25 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 30 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 40 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 50 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 60 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 75 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 100 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 125 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 150 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 175 HP / Maximum Output Voltage (V) Three Phase, 200V~240V as printed C2
200 V class / 1 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 2 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 3 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 5 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 7.5 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 10 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 15 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 20 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 25 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 30 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 40 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 50 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 60 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 75 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 100 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 125 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 150 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 175 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0 Hz as printed C2
200 V class / 1 HP / Rated Voltage, Frequency 1-Phase/3-Phase as printed C2
200 V class / 2 HP / Rated Voltage, Frequency 1-Phase/3-Phase as printed C2
200 V class / 3 HP / Rated Voltage, Frequency 1-Phase/3-Phase as printed C2
200 V class / 5 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 7.5 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 10 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 15 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 20 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 25 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 30 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 40 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 50 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 60 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 75 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 100 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 125 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 150 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 175 HP / Rated Voltage, Frequency Three Phase, 200V ~ 240V, 50/60Hz as printed C2
200 V class / 1 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 2 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 3 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 5 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 7.5 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 10 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 15 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 20 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 25 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 30 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 40 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 50 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 60 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 75 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 100 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 125 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 150 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 175 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
200 V class / 1 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 2 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 3 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 5 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 7.5 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 10 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 15 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 20 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 25 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 30 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 40 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 50 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 60 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 75 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 100 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 125 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 150 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 175 HP / Allowable Frequency Fluctuation ±5% as printed C2
200 V class / 1 HP / Braking Transistor Built-in as printed C2
200 V class / 2 HP / Braking Transistor Built-in as printed C2
200 V class / 3 HP / Braking Transistor Built-in as printed C2
200 V class / 5 HP / Braking Transistor Built-in as printed C2
200 V class / 7.5 HP / Braking Transistor Built-in as printed C2
200 V class / 10 HP / Braking Transistor Built-in as printed C2
200 V class / 15 HP / Braking Transistor Built-in as printed C2
200 V class / 20 HP / Braking Transistor Built-in as printed C2
200 V class / 25 HP / Braking Transistor Built-in as printed C2
200 V class / 30 HP / Braking Transistor Built-in as printed C2
200 V class / 40 HP / Braking Transistor Option (Braking Module) as printed C2
200 V class / 50 HP / Braking Transistor Option (Braking Module) as printed C2
200 V class / 60 HP / Braking Transistor Option (Braking Module) as printed C2
200 V class / 75 HP / Braking Transistor Option (Braking Module) as printed C2
200 V class / 100 HP / Braking Transistor Option (Braking Module) as printed C2
200 V class / 125 HP / Braking Transistor Option (Braking Module) as printed C2
200 V class / 150 HP / Braking Transistor Option (Braking Module) as printed C2
200 V class / 175 HP / Braking Transistor Option (Braking Module) as printed C2
200 V class / 1 HP / DC reactor None as printed C2
200 V class / 2 HP / DC reactor None as printed C2
200 V class / 3 HP / DC reactor None as printed C2
200 V class / 5 HP / DC reactor Option as printed C2
200 V class / 7.5 HP / DC reactor Option as printed C2
200 V class / 10 HP / DC reactor Option as printed C2
200 V class / 15 HP / DC reactor Option as printed C2
200 V class / 20 HP / DC reactor Option as printed C2
200 V class / 25 HP / DC reactor Option as printed C2
200 V class / 30 HP / DC reactor Option as printed C2
200 V class / 40 HP / DC reactor Option as printed C2
200 V class / 50 HP / DC reactor Option as printed C2
200 V class / 60 HP / DC reactor Built-in as printed C2
200 V class / 75 HP / DC reactor Built-in as printed C2
200 V class / 100 HP / DC reactor Built-in as printed C2
200 V class / 125 HP / DC reactor Built-in as printed C2
200 V class / 150 HP / DC reactor Built-in as printed C2
200 V class / 175 HP / DC reactor Built-in as printed C2
200 V class / 1 HP / Frame 1 as printed C2
200 V class / 2 HP / Frame 1 as printed C2
200 V class / 3 HP / Frame 1 as printed C2
200 V class / 5 HP / Frame 2 as printed C2
200 V class / 7.5 HP / Frame 2 as printed C2
200 V class / 10 HP / Frame 2 as printed C2
200 V class / 15 HP / Frame 3 as printed C2
200 V class / 20 HP / Frame 4 as printed C2
200 V class / 25 HP / Frame 4 as printed C2
200 V class / 30 HP / Frame 4 as printed C2
200 V class / 40 HP / Frame 5 as printed C2
200 V class / 50 HP / Frame 5 as printed C2
200 V class / 60 HP / Frame 6 as printed C2
200 V class / 75 HP / Frame 6 as printed C2
200 V class / 100 HP / Frame 7 as printed C2
200 V class / 125 HP / Frame 7 as printed C2
200 V class / 150 HP / Frame 8 as printed C2
200 V class / 175 HP / Frame 8 as printed C2
400 V class / 1 HP / Inverter capacity (HP) 1 as printed C1
400 V class / 1 HP / Rated output capacity (kVA) 2.6 as printed C1
400 V class / 1 HP / Rated output current (A) 3.4 as printed C1
400 V class / 1 HP / Maximum applicable motor (HP) 1 as printed C1
400 V class / 1 HP / Maximum applicable motor (kW) 0.75 as printed C1
400 V class / 2 HP / Inverter capacity (HP) 2 as printed C1
400 V class / 2 HP / Rated output capacity (kVA) 3.1 as printed C1
400 V class / 2 HP / Rated output current (A) 4.1 as printed C1
400 V class / 2 HP / Maximum applicable motor (HP) 2 as printed C1
400 V class / 2 HP / Maximum applicable motor (kW) 1.5 as printed C1
400 V class / 3 HP / Inverter capacity (HP) 3 as printed C1
400 V class / 3 HP / Rated output capacity (kVA) 4.1 as printed C1
400 V class / 3 HP / Rated output current (A) 5.4 as printed C1
400 V class / 3 HP / Maximum applicable motor (HP) 3 as printed C1
400 V class / 3 HP / Maximum applicable motor (kW) 2.2 as printed C1
400 V class / 5 HP / Inverter capacity (HP) 5 as printed C1
400 V class / 5 HP / Rated output capacity (kVA) 7 as printed C1
400 V class / 5 HP / Rated output current (A) 9.2 as printed C1
400 V class / 5 HP / Maximum applicable motor (HP) 5 as printed C1
400 V class / 5 HP / Maximum applicable motor (kW) 3.7 as printed C1
400 V class / 7.5 HP / Inverter capacity (HP) 7.5 as printed C1
400 V class / 7.5 HP / Rated output capacity (kVA) 8.4 as printed C1
400 V class / 7.5 HP / Rated output current (A) 12.1 as printed C1
400 V class / 7.5 HP / Maximum applicable motor (HP) 7.5 as printed C1
400 V class / 7.5 HP / Maximum applicable motor (kW) 5.5 as printed C1
400 V class / 10 HP / Inverter capacity (HP) 10 as printed C1
400 V class / 10 HP / Rated output capacity (kVA) 13 as printed C1
400 V class / 10 HP / Rated output current (A) 17.5 as printed C1
400 V class / 10 HP / Maximum applicable motor (HP) 10 as printed C1
400 V class / 10 HP / Maximum applicable motor (kW) 7.5 as printed C1
400 V class / 15 HP / Inverter capacity (HP) 15 as printed C1
400 V class / 15 HP / Rated output capacity (kVA) 18 as printed C1
400 V class / 15 HP / Rated output current (A) 23 as printed C1
400 V class / 15 HP / Maximum applicable motor (HP) 15 as printed C1
400 V class / 15 HP / Maximum applicable motor (kW) 11 as printed C1
400 V class / 20 HP / Inverter capacity (HP) 20 as printed C1
400 V class / 20 HP / Rated output capacity (kVA) 24 as printed C1
400 V class / 20 HP / Rated output current (A) 31 as printed C1
400 V class / 20 HP / Maximum applicable motor (HP) 20 as printed C1
400 V class / 20 HP / Maximum applicable motor (kW) 15 as printed C1
400 V class / 25 HP / Inverter capacity (HP) 25 as printed C1
400 V class / 25 HP / Rated output capacity (kVA) 28.9 as printed C1
400 V class / 25 HP / Rated output current (A) 38 as printed C1
400 V class / 25 HP / Maximum applicable motor (HP) 25 as printed C1
400 V class / 25 HP / Maximum applicable motor (kW) 18.5 as printed C1
400 V class / 30 HP / Inverter capacity (HP) 30 as printed C1
400 V class / 30 HP / Rated output capacity (kVA) 34 as printed C1
400 V class / 30 HP / Rated output current (A) 44 as printed C1
400 V class / 30 HP / Maximum applicable motor (HP) 30 as printed C1
400 V class / 30 HP / Maximum applicable motor (kW) 22 as printed C1
400 V class / 40 HP / Inverter capacity (HP) 40 as printed C1
400 V class / 40 HP / Rated output capacity (kVA) 41 as printed C1
400 V class / 40 HP / Rated output current (A) 58 as printed C1
400 V class / 40 HP / Maximum applicable motor (HP) 40 as printed C1
400 V class / 40 HP / Maximum applicable motor (kW) 30 as printed C1
400 V class / 50 HP / Inverter capacity (HP) 50 as printed C1
400 V class / 50 HP / Rated output capacity (kVA) 55 as printed C1
400 V class / 50 HP / Rated output current (A) 73 as printed C1
400 V class / 50 HP / Maximum applicable motor (HP) 50 as printed C1
400 V class / 50 HP / Maximum applicable motor (kW) 37 as printed C1
400 V class / 60 HP / Inverter capacity (HP) 60 as printed C1
400 V class / 60 HP / Rated output capacity (kVA) 67 as printed C1
400 V class / 60 HP / Rated output current (A) 88 as printed C1
400 V class / 60 HP / Maximum applicable motor (HP) 60 as printed C1
400 V class / 60 HP / Maximum applicable motor (kW) 45 as printed C1
400 V class / 75 HP / Inverter capacity (HP) 75 as printed C1
400 V class / 75 HP / Rated output capacity (kVA) 78 as printed C1
400 V class / 75 HP / Rated output current (A) 103 as printed C1
400 V class / 75 HP / Maximum applicable motor (HP) 75 as printed C1
400 V class / 75 HP / Maximum applicable motor (kW) 55 as printed C1
400 V class / 100 HP / Inverter capacity (HP) 100 as printed C1
400 V class / 100 HP / Rated output capacity (kVA) 110 as printed C1
400 V class / 100 HP / Rated output current (A) 145 as printed C1
400 V class / 100 HP / Maximum applicable motor (HP) 100 as printed C1
400 V class / 100 HP / Maximum applicable motor (kW) 75 as printed C1
400 V class / 125 HP / Inverter capacity (HP) 125 as printed C1
400 V class / 125 HP / Rated output capacity (kVA) 125 as printed C1
400 V class / 125 HP / Rated output current (A) 168 as printed C1
400 V class / 125 HP / Maximum applicable motor (HP) 125 as printed C1
400 V class / 125 HP / Maximum applicable motor (kW) 90 as printed C1
400 V class / 150 HP / Inverter capacity (HP) 150 as printed C1
400 V class / 150 HP / Rated output capacity (kVA) 158 as printed C1
400 V class / 150 HP / Rated output current (A) 208 as printed C1
400 V class / 150 HP / Maximum applicable motor (HP) 150 as printed C1
400 V class / 150 HP / Maximum applicable motor (kW) 110 as printed C1
400 V class / 175 HP / Inverter capacity (HP) 175 as printed C1
400 V class / 175 HP / Rated output capacity (kVA) 190 as printed C1
400 V class / 175 HP / Rated output current (A) 250 as printed C1
400 V class / 175 HP / Maximum applicable motor (HP) 175 as printed C1
400 V class / 175 HP / Maximum applicable motor (kW) 132 as printed C1
400 V class / 215 HP / Inverter capacity (HP) 215 as printed C1
400 V class / 215 HP / Rated output capacity (kVA) 225 as printed C1
400 V class / 215 HP / Rated output current (A) 296 as printed C1
400 V class / 215 HP / Maximum applicable motor (HP) 215 as printed C1
400 V class / 215 HP / Maximum applicable motor (kW) 160 as printed C1
400 V class / 250 HP / Inverter capacity (HP) 250 as printed C1
400 V class / 250 HP / Rated output capacity (kVA) 250 as printed C1
400 V class / 250 HP / Rated output current (A) 328 as printed C1
400 V class / 250 HP / Maximum applicable motor (HP) 250 as printed C1
400 V class / 250 HP / Maximum applicable motor (kW) 185 as printed C1
400 V class / 300 HP / Inverter capacity (HP) 300 as printed C1
400 V class / 300 HP / Rated output capacity (kVA) 331 as printed C1
400 V class / 300 HP / Rated output current (A) 435 as printed C1
400 V class / 300 HP / Maximum applicable motor (HP) 300 as printed C1
400 V class / 300 HP / Maximum applicable motor (kW) 220 as printed C1
400 V class / 375 HP / Inverter capacity (HP) 375 as printed C1
400 V class / 375 HP / Rated output capacity (kVA) 392 as printed C1
400 V class / 375 HP / Rated output current (A) 515 as printed C1
400 V class / 375 HP / Maximum applicable motor (HP) 375 as printed C1
400 V class / 375 HP / Maximum applicable motor (kW) 280 as printed C1
400 V class / 425 HP / Inverter capacity (HP) 425 as printed C1
400 V class / 425 HP / Rated output capacity (kVA) 445 as printed C1
400 V class / 425 HP / Rated output current (A) 585 as printed C1
400 V class / 425 HP / Maximum applicable motor (HP) 425 as printed C1
400 V class / 425 HP / Maximum applicable motor (kW) 315 as printed C1
400 V class / 535 HP / Inverter capacity (HP) 535 as printed C1
400 V class / 535 HP / Rated output capacity (kVA) 525 as printed C1
400 V class / 535 HP / Rated output current (A) 700 as printed C1
400 V class / 535 HP / Maximum applicable motor (HP) 535 as printed C1
400 V class / 535 HP / Maximum applicable motor (kW) 400 as printed C1
400 V class / 670 HP / Inverter capacity (HP) 670 as printed C1
400 V class / 670 HP / Rated output capacity (kVA) 640 as printed C1
400 V class / 670 HP / Rated output current (A) 875 as printed C1
400 V class / 670 HP / Maximum applicable motor (HP) 670 as printed C1
400 V class / 670 HP / Maximum applicable motor (kW) 500 as printed C1
400 V class / 800 HP / Inverter capacity (HP) 800 as printed C1
400 V class / 800 HP / Rated output capacity (kVA) 731 as printed C1
400 V class / 800 HP / Rated output current (A) 960 as printed C1
400 V class / 800 HP / Maximum applicable motor (HP) 800 as printed C1
400 V class / 800 HP / Maximum applicable motor (kW) 600 as printed C1
400 V class / 1 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 2 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 3 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 5 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 7.5 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 10 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 15 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 20 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 25 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 30 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 40 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 50 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 60 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 75 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 100 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 125 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 150 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 175 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 215 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 250 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 300 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 375 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 425 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 535 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 670 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 800 HP / Maximum Output Voltage (V) Three Phase, 380V~480V as printed C2
400 V class / 1 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 2 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 3 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 5 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 7.5 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 10 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 15 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 20 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 25 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 30 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 40 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 50 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 60 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 75 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 100 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 125 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 150 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 175 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 215 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 250 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 300 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 375 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 425 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 535 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 670 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 800 HP / Maximum Output Frequency (Hz) Based on parameter setting 0.1~599.0Hz as printed C2
400 V class / 1 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 2 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 3 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 5 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 7.5 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 10 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 15 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 20 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 25 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 30 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 40 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 50 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 60 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 75 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 100 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 125 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 150 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 175 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 215 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 250 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 300 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 375 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 425 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 535 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 670 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 800 HP / Rated Voltage, Frequency Three Phase, 380V ~ 480V, 50/60Hz as printed C2
400 V class / 1 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 2 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 3 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 5 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 7.5 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 10 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 15 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 20 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 25 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 30 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 40 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 50 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 60 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 75 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 100 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 125 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 150 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 175 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 215 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 250 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 300 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 375 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 425 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 535 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 670 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 800 HP / Allowable Voltage Fluctuation -15% ~ +10% as printed C2
400 V class / 1 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 2 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 3 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 5 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 7.5 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 10 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 15 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 20 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 25 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 30 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 40 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 50 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 60 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 75 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 100 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 125 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 150 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 175 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 215 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 250 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 300 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 375 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 425 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 535 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 670 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 800 HP / Allowable Frequency Fluctuation ±5% as printed C2
400 V class / 1 HP / Braking Transistor Built-in as printed C2
400 V class / 2 HP / Braking Transistor Built-in as printed C2
400 V class / 3 HP / Braking Transistor Built-in as printed C2
400 V class / 5 HP / Braking Transistor Built-in as printed C2
400 V class / 7.5 HP / Braking Transistor Built-in as printed C2
400 V class / 10 HP / Braking Transistor Built-in as printed C2
400 V class / 15 HP / Braking Transistor Built-in as printed C2
400 V class / 20 HP / Braking Transistor Built-in as printed C2
400 V class / 25 HP / Braking Transistor Built-in as printed C2
400 V class / 30 HP / Braking Transistor Built-in as printed C2
400 V class / 40 HP / Braking Transistor Built-in as printed C2
400 V class / 50 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 60 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 75 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 100 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 125 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 150 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 175 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 215 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 250 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 300 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 375 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 425 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 535 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 670 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 800 HP / Braking Transistor Option (Braking Module) as printed C2
400 V class / 1 HP / DC reactor None as printed C2
400 V class / 2 HP / DC reactor None as printed C2
400 V class / 3 HP / DC reactor None as printed C2
400 V class / 5 HP / DC reactor Option as printed C2
400 V class / 7.5 HP / DC reactor Option as printed C2
400 V class / 10 HP / DC reactor Option as printed C2
400 V class / 15 HP / DC reactor Option as printed C2
400 V class / 20 HP / DC reactor Option as printed C2
400 V class / 25 HP / DC reactor Option as printed C2
400 V class / 30 HP / DC reactor Option as printed C2
400 V class / 40 HP / DC reactor Option as printed C2
400 V class / 50 HP / DC reactor Option as printed C2
400 V class / 60 HP / DC reactor Option as printed C2
400 V class / 75 HP / DC reactor Option as printed C2
400 V class / 100 HP / DC reactor Option as printed C2
400 V class / 125 HP / DC reactor Built-in as printed C2
400 V class / 150 HP / DC reactor Built-in as printed C2
400 V class / 175 HP / DC reactor Built-in as printed C2
400 V class / 215 HP / DC reactor Built-in as printed C2
400 V class / 250 HP / DC reactor Built-in as printed C2
400 V class / 300 HP / DC reactor Built-in as printed C2
400 V class / 375 HP / DC reactor Built-in as printed C2
400 V class / 425 HP / DC reactor Built-in as printed C2
400 V class / 535 HP / DC reactor Option as printed C2
400 V class / 670 HP / DC reactor Option as printed C2
400 V class / 800 HP / DC reactor Option as printed C2
400 V class / 1 HP / Frame 1 as printed C2
400 V class / 2 HP / Frame 1 as printed C2
400 V class / 3 HP / Frame 1 as printed C2
400 V class / 5 HP / Frame 2 as printed C2
400 V class / 7.5 HP / Frame 2 as printed C2
400 V class / 10 HP / Frame 2 as printed C2
400 V class / 15 HP / Frame 3 as printed C2
400 V class / 20 HP / Frame 3 as printed C2
400 V class / 25 HP / Frame 3 as printed C2
400 V class / 30 HP / Frame 4 as printed C2
400 V class / 40 HP / Frame 4 as printed C2
400 V class / 50 HP / Frame 5 as printed C2
400 V class / 60 HP / Frame 5 as printed C2
400 V class / 75 HP / Frame 5 as printed C2
400 V class / 100 HP / Frame 5 as printed C2
400 V class / 125 HP / Frame 6 as printed C2
400 V class / 150 HP / Frame 6 as printed C2
400 V class / 175 HP / Frame 7 as printed C2
400 V class / 215 HP / Frame 7 as printed C2
400 V class / 250 HP / Frame 7 as printed C2
400 V class / 300 HP / Frame 8 as printed C2
400 V class / 375 HP / Frame 8 as printed C2
400 V class / 425 HP / Frame 8 as printed C2
400 V class / 535 HP / Frame 9 as printed C2
400 V class / 670 HP / Frame 9 as printed C2
400 V class / 800 HP / Frame 9 as printed C2

P002 / F510-EnhancedEn20210330.pdf — source page 15 — PDF page 15

Specification Value Unit / basis Conditions
General specifications / Control Characteristics / Display LED keypad with 5-digits seven-segment display or LCD keypad (HOA LCD keypad option)all LCD keypad with parameter copy function as printed C1
General specifications / Control Characteristics / Control Modes V/F, SLV, PMSLV with Space Vector PWM Mode as printed C1
General specifications / Control Characteristics / Output Frequency 0.01Hz~599.0Hz as printed C1
General specifications / Control Characteristics / Frequency Accuracy Digital references : ±0.01%(-10 ~ +40℃), Analog references : ±0.1% (25℃ ±10℃) as printed C1
General specifications / Control Characteristics / Speed Control Accuracy ±0.5% (Sensorless Vector Control Mode)*1 as printed C1
General specifications / Control Characteristics / Frequency Setting Resolution Digital references : 0.01Hz, Analog references : 0.06Hz/60Hz as printed C1
General specifications / Control Characteristics / Output Frequency Resolution 0.01Hz as printed C1
General specifications / Control Characteristics / Overload Tolerance 120% /1 min as printed C1
General specifications / Control Characteristics / Frequency Setting Signal DC 0~+10V o r 4~20mA as printed C1
General specifications / Control Characteristics / Acceleration / Deceleration Time 0.0~6000.0 second (separately set acceleration and deceleration time ) as printed C1
General specifications / Control Characteristics / Voltage / Frequency Characteristics Can arbitrarily set V / F curve based on parameters as printed C1
General specifications / Control Characteristics / Braking Torque About 20% as printed C1
General specifications / Control Characteristics / Main Control Functions Auto Tuning, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Momentary Power Loss Restart, 2 Sets of PID Control, Slide Difference Compensation, RS-485 Communication Standard, Simple PLC Function, 2 Sets of Analog Output, Safety Switch as printed C1
General specifications / Control Characteristics / Other Functions Records of Power On and Operation Time, 4 Fault History Records and Latest Fault Record State, Energy- Saving Function, Phase Loss protection, Smart Braking, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus, BACNet MS/TP, and Metasys N2 Communication Protocol, Display of Multi- Engineering Unit, Local / Remote Switch, SINK / SOURCE Input Selection, User Parameter Settings as printed C1
General specifications / Protection Functions / Stall Protection Current level can be set (in acceleration or constant speed, it can be set separately. In deceleration, it can be set with or without protection) as printed C1
General specifications / Protection Functions / Over Current (OC) and Output Short-circuit (SC) Protection It stops when the current exceeds 160% of the inverter rated current as printed C1
General specifications / Protection Functions / Inverter Overload Protection (OL2) Inverter will be stopped when the output higher than 120% rated current for 1 min, Carrier frequency is 2~4KHZ*2 as printed C1
General specifications / Protection Functions / Motor Overload Protection (OL1) Electrical overload protection curve as printed C1
General specifications / Protection Functions / Over Voltage Protection (OV) If the main circuit DC voltage is over 410V (200V class) / 820V (400V class), the motor stops running as printed C1
General specifications / Protection Functions / Under Voltage Protection (UV) If the main circuit DC voltage is under 190V (200V class) / 380V (400V class), the motor stops running as printed C1
General specifications / Protection Functions / Momentary Power Loss Restart Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec as printed C1
General specifications / Protection Functions / Overheat Protection(OH) Thermistor sensor on heatsink as printed C1
General specifications / Protection Functions / Ground Fault Protection(GF) Protection by current detection circuit as printed C1
General specifications / Protection Functions / Charge Indicator When main circuit DC voltage ≧50V, the CHARGE LED is on as printed C1
General specifications / Protection Functions / Input/Output Phase Loss Protection (IPL/OPL) If the IPL/OPL function acts, the motor stops rotation automatically as printed C1
General specifications / Protection Functions / Short-circuit Current Rating(SCCR) Per UL 508C,the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms)when protected by fuses given in the fuse table as printed C1
General specifications / Environment Specification / Location Indoor (protected from corrosive gases and dust) as printed C1
General specifications / Environment Specification / Ambient Temperature -10~+40℃ (IP20/IP21), -10~50℃ (IP00 or top anti-dust cover removed), with de-rating, the maximum is 60 ℃. (Frame 5 is 50℃ without de-rating) as printed C1
General specifications / Environment Specification / Storage Temperature -20~+70℃ as printed C1
General specifications / Environment Specification / Humidity 95%RH or less ( no condensation ) as printed C1
General specifications / Environment Specification / Altitude and Vibration Altitude of 1000 meters or lower, 1.0G, in compliance with IEC 60068-2-6 as printed C1
General specifications / Environment Specification / Pollution Degree IP00/IP20/IP21 models meet IEC 60721-3-3 Class 3C3 as printed C1
General specifications / General / Communication Function Built-in RS-485 as standard (Modbus protocol with RJ45 / BACnet / Metasys N2) (If Metasys N2 protocol will be used, please contact with TECO sales) as printed C1
General specifications / General / Electromagnetic Interference (EMI) Meet EN61800-3 Standard, IP20 400V 75HP or below can be built-in as printed C1
General specifications / General / Electromagnetic Susceptibility (EMS) Meet EN61800-3 Standard as printed C1
General specifications / General / Certification / CE Meet EN61800-3(CE & RE) and EN61800-5-1(LVD) as printed C1
General specifications / General / Certification / UL UL508C as printed C1

P002 / F510-EnhancedEn20210330.pdf — source page 16 — PDF page 16

Configuration / printed row figure frame W H D W1 H1 t d kg Conditions
F510-2001-□ / IP20 A 1 130 mm 215 mm 150 mm 118 mm 203 mm 5 mm M5 thread designation 2.2 kg C1
F510-2002-□ / IP20 A 1 130 mm 215 mm 150 mm 118 mm 203 mm 5 mm M5 thread designation 2.2 kg C1
F510-2003-□ / IP20 A 1 130 mm 215 mm 150 mm 118 mm 203 mm 5 mm M5 thread designation 2.2 kg C1
F510-4001-□3 / IP20 A 1 130 mm 215 mm 150 mm 118 mm 203 mm 5 mm M5 thread designation 2.2 kg C1
F510-4002-□3 / IP20 A 1 130 mm 215 mm 150 mm 118 mm 203 mm 5 mm M5 thread designation 2.2 kg C1
F510-4003-□3 / IP20 A 1 130 mm 215 mm 150 mm 118 mm 203 mm 5 mm M5 thread designation 2.2 kg C1
F510-2005-□3 / IP20 A 2 140 mm 279 mm 181 mm 122 mm 267 mm 1.2 mm M6 thread designation 3.8 kg C1
F510-2008-□3 / IP20 A 2 140 mm 279 mm 181 mm 122 mm 267 mm 1.2 mm M6 thread designation 3.8 kg C1
F510-2010-□3 / IP20 A 2 140 mm 279 mm 181 mm 122 mm 267 mm 1.2 mm M6 thread designation 3.8 kg C1
F510-4005-□3 / IP20 A 2 140 mm 279 mm 181 mm 122 mm 267 mm 1.2 mm M6 thread designation 3.8 kg C1
F510-4008-□3 / IP20 A 2 140 mm 279 mm 181 mm 122 mm 267 mm 1.2 mm M6 thread designation 3.8 kg C1
F510-4010-□3 / IP20 A 2 140 mm 279 mm 181 mm 122 mm 267 mm 1.2 mm M6 thread designation 3.8 kg C1
F510-2015-□3 / IP20 B 3 210 mm 300 mm 215 mm 192 mm 286 mm 1.6 mm M6 thread designation 6.2 kg C1
F510-4015-□3 / IP20 B 3 210 mm 300 mm 215 mm 192 mm 286 mm 1.6 mm M6 thread designation 6.2 kg C1
F510-4020-□3 / IP20 B 3 210 mm 300 mm 215 mm 192 mm 286 mm 1.6 mm M6 thread designation 6.2 kg C1
F510-4025-□3 / IP20 B 3 210 mm 300 mm 215 mm 192 mm 286 mm 1.6 mm M6 thread designation 6.2 kg C1
F510-2020-□3 / IP20 B 4 265 mm 360 mm 225 mm 245 mm 340 mm 1.6 mm M8 thread designation 10 kg C1
F510-2025-□3 / IP20 B 4 265 mm 360 mm 225 mm 245 mm 340 mm 1.6 mm M8 thread designation 10 kg C1
F510-2030-□3 / IP20 B 4 265 mm 360 mm 225 mm 245 mm 340 mm 1.6 mm M8 thread designation 10 kg C1
F510-4030-□3 / IP20 B 4 265 mm 360 mm 225 mm 245 mm 340 mm 1.6 mm M8 thread designation 10 kg C1
F510-4040-□3 / IP20 B 4 265 mm 360 mm 225 mm 245 mm 340 mm 1.6 mm M8 thread designation 10 kg C1
F510-2040-□3 / IP20 C 5 286.5 mm 525 mm 272 mm 220 mm 505 mm 3.3 mm M8 thread designation 24 kg C1
F510-2050-□3 / IP20 C 5 286.5 mm 525 mm 272 mm 220 mm 505 mm 3.3 mm M8 thread designation 24 kg C1
F510-4050-□3 / IP20 C 5 286.5 mm 525 mm 272 mm 220 mm 505 mm 3.3 mm M8 thread designation 24 kg C1
F510-4060-□3 / IP20 C 5 286.5 mm 525 mm 272 mm 220 mm 505 mm 3.3 mm M8 thread designation 24 kg C1
F510-4075-□3 / IP20 C 5 286.5 mm 525 mm 272 mm 220 mm 505 mm 3.3 mm M8 thread designation 24 kg C1
F510-4100-□3 / IP20 C 5 286.5 mm 525 mm 272 mm 220 mm 505 mm 3.3 mm M8 thread designation 24 kg C1

P002 / F510-EnhancedEn20210330.pdf — source page 17 — PDF page 17

Configuration / printed row figure frame W H D W1 W2 H1 H2 t d kg Conditions
F510-2060-□3 / IP00 D 6 344 mm 580 mm 300 mm 250 mm N/A mm 560 mm N/A mm 3.2 mm M8 thread designation 40 kg C1
F510-2075-□3 / IP00 D 6 344 mm 580 mm 300 mm 250 mm N/A mm 560 mm N/A mm 3.2 mm M8 thread designation 40 kg C1
F510-4125-□3 / IP00 D 6 344 mm 580 mm 300 mm 250 mm N/A mm 560 mm N/A mm 3.2 mm M8 thread designation 40 kg C1
F510-4150-□3 / IP00 D 6 344 mm 580 mm 300 mm 250 mm N/A mm 560 mm N/A mm 3.2 mm M8 thread designation 40 kg C1
F510-2100-□3 / IP00 D 7 459 mm 790 mm 324.5 mm 320 mm N/A mm 760 mm N/A mm 3.2 mm M10 thread designation 74 kg C1
F510-2125-□3 / IP00 D 7 459 mm 790 mm 324.5 mm 320 mm N/A mm 760 mm N/A mm 3.2 mm M10 thread designation 74 kg C1
F510-4175-□3 / IP00 D 7 459 mm 790 mm 324.5 mm 320 mm N/A mm 760 mm N/A mm 3.2 mm M10 thread designation 74 kg C1
F510-4215-□3 / IP00 D 7 459 mm 790 mm 324.5 mm 320 mm N/A mm 760 mm N/A mm 3.2 mm M10 thread designation 74 kg C1
F510-4250-□3 / IP00 D 7 459 mm 790 mm 324.5 mm 320 mm N/A mm 760 mm N/A mm 3.2 mm M10 thread designation 74 kg C1
F510-2150-□3 / IP00 E 8 690 mm 1000 mm 410 mm 530 mm 265 mm 960 mm N/A mm 4.2 mm M12 thread designation 184 kg C1
F510-2175-□3 / IP00 E 8 690 mm 1000 mm 410 mm 530 mm 265 mm 960 mm N/A mm 4.2 mm M12 thread designation 184 kg C1
F510-4300-□3 / IP00 E 8 690 mm 1000 mm 410 mm 530 mm 265 mm 960 mm N/A mm 4.2 mm M12 thread designation 184 kg C1
F510-4375-□3 / IP00 E 8 690 mm 1000 mm 410 mm 530 mm 265 mm 960 mm N/A mm 4.2 mm M12 thread designation 184 kg C1
F510-4425-□3 / IP00 E 8 690 mm 1000 mm 410 mm 530 mm 265 mm 960 mm N/A mm 4.2 mm M12 thread designation 184 kg C1
F510-4535-□3 / IP00 F 9 958 mm 1356 mm 507 mm 916 mm N/A mm 1200 mm 300 mm 6.2 mm M12 thread designation 335 kg C1
F510-4670-□3 / IP00 F 9 958 mm 1356 mm 507 mm 916 mm N/A mm 1200 mm 300 mm 6.2 mm M12 thread designation 335 kg C1
F510-4800-□3 / IP00 F 9 958 mm 1356 mm 507 mm 916 mm N/A mm 1200 mm 300 mm 6.2 mm M12 thread designation 335 kg C1

P002 / F510-EnhancedEn20210330.pdf — source page 18 — PDF page 18

Configuration / printed row figure frame W H D W1 W2 H1 H2 t d kg Conditions
F510-2060-□3 / IP20 G 6 348.5 mm 740 mm 300 mm 250 mm N/A mm 560 mm N/A mm 3.2 mm M8 thread designation 44 kg C1
F510-2075-□3 / IP20 G 6 348.5 mm 740 mm 300 mm 250 mm N/A mm 560 mm N/A mm 3.2 mm M8 thread designation 44 kg C1
F510-4125-□3 / IP20 G 6 348.5 mm 740 mm 300 mm 250 mm N/A mm 560 mm N/A mm 3.2 mm M8 thread designation 44 kg C1
F510-4150-□3 / IP20 G 6 348.5 mm 740 mm 300 mm 250 mm N/A mm 560 mm N/A mm 3.2 mm M8 thread designation 44 kg C1
F510-2100-□3 / IP20 G 7 463.5 mm 1105 mm 324.5 mm 320 mm N/A mm 760 mm N/A mm 4.2 mm M10 thread designation 81 kg C2
F510-2125-□3 / IP20 G 7 463.5 mm 1105 mm 324.5 mm 320 mm N/A mm 760 mm N/A mm 4.2 mm M10 thread designation 81 kg C2
F510-4175-□3 / IP20 G 7 463.5 mm 1105 mm 324.5 mm 320 mm N/A mm 760 mm N/A mm 4.2 mm M10 thread designation 81 kg C2
F510-4215-□3 / IP20 G 7 463.5 mm 1105 mm 324.5 mm 320 mm N/A mm 760 mm N/A mm 4.2 mm M10 thread designation 81 kg C2
F510-4250-□3 / IP20 G 7 463.5 mm 1105 mm 324.5 mm 320 mm N/A mm 760 mm N/A mm 4.2 mm M10 thread designation 81 kg C2
F510-2150-□3 / IP20 H 8 692 mm 1313 mm 410 mm 530 mm 265 mm 960 mm N/A mm 4.2 mm M12 thread designation 194 kg C3
F510-2175-□3 / IP20 H 8 692 mm 1313 mm 410 mm 530 mm 265 mm 960 mm N/A mm 4.2 mm M12 thread designation 194 kg C3
F510-4300-□3 / IP20 H 8 692 mm 1313 mm 410 mm 530 mm 265 mm 960 mm N/A mm 4.2 mm M12 thread designation 194 kg C3
F510-4375-□3 / IP20 H 8 692 mm 1313 mm 410 mm 530 mm 265 mm 960 mm N/A mm 4.2 mm M12 thread designation 194 kg C3
F510-4425-□3 / IP20 H 8 692 mm 1313 mm 410 mm 530 mm 265 mm 960 mm N/A mm 4.2 mm M12 thread designation 194 kg C3
F510-4535-□3 / IP20 I 9 958 mm 1756 mm 507 mm 916 mm N/A mm 1200 mm 300 mm 6.2 mm M12 thread designation 350 kg C4
F510-4670-□3 / IP20 I 9 958 mm 1756 mm 507 mm 916 mm N/A mm 1200 mm 300 mm 6.2 mm M12 thread designation 350 kg C4
F510-4800-□3 / IP20 I 9 958 mm 1756 mm 507 mm 916 mm N/A mm 1200 mm 300 mm 6.2 mm M12 thread designation 350 kg C4

P002 / F510-EnhancedEn20210330.pdf — source page 19 — PDF page 19

Configuration / printed row figure frame W H D W1 H1 H2 t d kg Conditions
F510-4001-□3F / IP20 L 1 130 mm 306 mm 150 mm 118 mm 203 mm 215 mm 5 mm M5 thread designation 3.5 kg C1
F510-4002-□3F / IP20 L 1 130 mm 306 mm 150 mm 118 mm 203 mm 215 mm 5 mm M5 thread designation 3.5 kg C1
F510-4003-□3F / IP20 L 1 130 mm 306 mm 150 mm 118 mm 203 mm 215 mm 5 mm M5 thread designation 3.5 kg C1
F510-4005-□3F / IP20 L 2 140 mm 400 mm 177 mm 122 mm 267 mm 279 mm 1.2 mm M6 thread designation 5.5 kg C1
F510-4008-□3F / IP20 L 2 140 mm 400 mm 177 mm 122 mm 267 mm 279 mm 1.2 mm M6 thread designation 5.5 kg C1
F510-4010-□3F / IP20 L 2 140 mm 400 mm 177 mm 122 mm 267 mm 279 mm 1.2 mm M6 thread designation 5.5 kg C1

P002 / F510-EnhancedEn20210330.pdf — source page 20 — PDF page 20

Configuration / printed row figure frame W H D W1 H1 H2 t d kg Conditions
F510-4015-□3F / IP20 M 3 210 mm 416.5 mm 215 mm 192 mm 286 mm 300 mm 1.6 mm M6 thread designation 8.0 kg C1
F510-4020-□3F / IP20 M 3 210 mm 416.5 mm 215 mm 192 mm 286 mm 300 mm 1.6 mm M6 thread designation 8.0 kg C1
F510-4025-□3F / IP20 M 4 265 mm 500 mm 225 mm 245 mm 340 mm 360 mm 1.6 mm M8 thread designation 12.5 kg C1
F510-4030-□3F / IP20 M 4 265 mm 500 mm 225 mm 245 mm 340 mm 360 mm 1.6 mm M8 thread designation 12.5 kg C1
F510-4040-□3F / IP20 M 4 265 mm 500 mm 225 mm 245 mm 340 mm 360 mm 1.6 mm M8 thread designation 12.5 kg C1
F510-4050-□3F / IP20 N 5 286.5 mm 679 mm 252 mm 220 mm 505 mm 525 mm 3.3 mm M8 thread designation 29.5 kg C1
F510-4060-□3F / IP20 N 5 286.5 mm 679 mm 252 mm 220 mm 505 mm 525 mm 3.3 mm M8 thread designation 29.5 kg C1
F510-4075-□3F / IP20 N 5 286.5 mm 679 mm 252 mm 220 mm 505 mm 525 mm 3.3 mm M8 thread designation 29.5 kg C1

P002 / F510-EnhancedEn20210330.pdf — source page 21 — PDF page 21

Specification Value Unit / basis Conditions
Accessory / JN5-CB-01M / Category Cables as printed C1
Accessory / JN5-CB-01M / Description IP20 Digital operator extention cable as printed C1
Accessory / JN5-CB-01M / Catalogue JN5-CB-01M as printed C1
Accessory / JN5-CB-01M / Note 1 meter as printed C1
Accessory / JN5-CB-02M / Category Cables as printed C1
Accessory / JN5-CB-02M / Description IP20 Digital operator extention cable as printed C1
Accessory / JN5-CB-02M / Catalogue JN5-CB-02M as printed C1
Accessory / JN5-CB-02M / Note 2 meter as printed C1
Accessory / JN5-CB-03M / Category Cables as printed C1
Accessory / JN5-CB-03M / Description IP20 Digital operator extention cable as printed C1
Accessory / JN5-CB-03M / Catalogue JN5-CB-03M as printed C1
Accessory / JN5-CB-03M / Note 3 meter as printed C1
Accessory / JN5-CB-05M / Category Cables as printed C1
Accessory / JN5-CB-05M / Description IP20 Digital operator extention cable as printed C1
Accessory / JN5-CB-05M / Catalogue JN5-CB-05M as printed C1
Accessory / JN5-CB-05M / Note 5 meter as printed C1
Accessory / JN5-CM-USB / Category Cables as printed C1
Accessory / JN5-CM-USB / Description RJ45 to USB connecting cable as printed C1
Accessory / JN5-CM-USB / Catalogue JN5-CM-USB as printed C1
Accessory / JN5-CM-USB / Note 1.8 meter as printed C1
Accessory / JN5-CM-PDP / Category Communication Gateways as printed C1
Accessory / JN5-CM-PDP / Description Profibus DP module as printed C1
Accessory / JN5-CM-PDP / Catalogue JN5-CM-PDP as printed C1
Accessory / JN5-CM-PDP / Note Not stated (blank in source) as printed C1
Accessory / JN5-CM-TCPIP / Category Communication Gateways as printed C1
Accessory / JN5-CM-TCPIP / Description TCP-IP module as printed C1
Accessory / JN5-CM-TCPIP / Catalogue JN5-CM-TCPIP as printed C1
Accessory / JN5-CM-TCPIP / Note Not stated (blank in source) as printed C1
Accessory / JN5-CM-DNET / Category Communication Gateways as printed C1
Accessory / JN5-CM-DNET / Description DeviceNet module as printed C1
Accessory / JN5-CM-DNET / Catalogue JN5-CM-DNET as printed C1
Accessory / JN5-CM-DNET / Note Not stated (blank in source) as printed C1
Accessory / JN5-CM-CAN / Category Communication Gateways as printed C1
Accessory / JN5-CM-CAN / Description CANopen module as printed C1
Accessory / JN5-CM-CAN / Catalogue JN5-CM-CAN as printed C1
Accessory / JN5-CM-CAN / Note Not stated (blank in source) as printed C1
Accessory / JN5-CM-EIP / Category Communication Gateways as printed C1
Accessory / JN5-CM-EIP / Description EtherNet/IP module as printed C1
Accessory / JN5-CM-EIP / Catalogue JN5-CM-EIP as printed C1
Accessory / JN5-CM-EIP / Note Not stated (blank in source) as printed C1
Accessory / JN5-CMHI-PDP / Category Communication Cards as printed C1
Accessory / JN5-CMHI-PDP / Description Profibus DP communication card as printed C1
Accessory / JN5-CMHI-PDP / Catalogue JN5-CMHI-PDP as printed C1
Accessory / JN5-CMHI-PDP / Note Not stated (blank in source) as printed C1
Accessory / JN5-CMHI-CAN / Category Communication Cards as printed C1
Accessory / JN5-CMHI-CAN / Description CANopen communication card as printed C1
Accessory / JN5-CMHI-CAN / Catalogue JN5-CMHI-CAN as printed C1
Accessory / JN5-CMHI-CAN / Note Not stated (blank in source) as printed C1
Accessory / JN5-CMHI-ECAT / Category Communication Cards as printed C1
Accessory / JN5-CMHI-ECAT / Description EtherCAT communication card as printed C1
Accessory / JN5-CMHI-ECAT / Catalogue JN5-CMHI-ECAT as printed C1
Accessory / JN5-CMHI-ECAT / Note Not stated (blank in source) as printed C1
Accessory / JN5-CMHI-EIP / Category Communication Cards as printed C1
Accessory / JN5-CMHI-EIP / Description EtherNet/IP communication card as printed C1
Accessory / JN5-CMHI-EIP / Catalogue JN5-CMHI-EIP as printed C1
Accessory / JN5-CMHI-EIP / Note Not stated (blank in source) as printed C1
Accessory / JN5-OP-BTH / Category Bluetooth Keypad as printed C1
Accessory / JN5-OP-BTH / Description For wireless remote connection to control the inverter, which can monitor the real-time status and diagnose faults quickly as printed C1
Accessory / JN5-OP-BTH / Catalogue JN5-OP-BTH as printed C1
Accessory / JN5-OP-BTH / Note With the smartphone APP ”BT DriveLink”, it can be downloaded from Apple APP Store or Google Play as printed C1
Accessory / JN5-IO-2DO1AI / Category Digital & Analog IO Expansion Card as printed C1
Accessory / JN5-IO-2DO1AI / Description Add one relay output, one transistor, andone -10V~10V / 4~20mA analog input after installation. as printed C1
Accessory / JN5-IO-2DO1AI / Catalogue JN5-IO-2DO1AI as printed C1
Accessory / JN5-IO-2DO1AI / Note Not stated (blank in source) as printed C1
Accessory / JN5-PS-DC24V / Category DC24V Power Card as printed C1
Accessory / JN5-PS-DC24V / Description Use DC24V to communicate with inverter, and setup or copy the parameter without using the main power after installation. as printed C1
Accessory / JN5-PS-DC24V / Catalogue JN5-PS-DC24V as printed C1
Accessory / JN5-PS-DC24V / Note Not stated (blank in source) as printed C1
Accessory / JN5-NK-A06 / Category NEMA1 Kits as printed C1
Accessory / JN5-NK-A06 / Description Mechanical device consisting of anti- dust cover on the upper part and wiring box on the bottom to meet NEMA1 as printed C1
Accessory / JN5-NK-A06 / Catalogue JN5-NK-A06 as printed C1
Accessory / JN5-NK-A06 / Note For Frame 6 as printed C1
Accessory / JN5-NK-A07 / Category NEMA1 Kits as printed C1
Accessory / JN5-NK-A07 / Description Mechanical device consisting of anti- dust cover on the upper part and wiring box on the bottom to meet NEMA1 as printed C1
Accessory / JN5-NK-A07 / Catalogue JN5-NK-A07 as printed C1
Accessory / JN5-NK-A07 / Note For Frame 7 as printed C1
Accessory / JN5-NK-A08 / Category NEMA1 Kits as printed C1
Accessory / JN5-NK-A08 / Description Mechanical device consisting of anti- dust cover on the upper part and wiring box on the bottom to meet NEMA1 as printed C1
Accessory / JN5-NK-A08 / Catalogue JN5-NK-A08 as printed C1
Accessory / JN5-NK-A08 / Note For Frame 8 as printed C1
Accessory / JN5-NK-A09 / Category NEMA1 Kits as printed C1
Accessory / JN5-NK-A09 / Description Mechanical device consisting of anti- dust cover on the upper part and wiring box on the bottom to meet NEMA1 as printed C1
Accessory / JN5-NK-A09 / Catalogue JN5-NK-A09 as printed C1
Accessory / JN5-NK-A09 / Note For Frame 9 as printed C1
Accessory / JN5-OP-F01 / Category Digital Operators as printed C1
Accessory / JN5-OP-F01 / Description IP20 LED Type as printed C1
Accessory / JN5-OP-F01 / Catalogue JN5-OP-F01 as printed C1
Accessory / JN5-OP-F01 / Note Not stated (blank in source) as printed C1
Accessory / JN5-OP-F02 / Category Digital Operators as printed C1
Accessory / JN5-OP-F02 / Description IP20 LCD Type as printed C1
Accessory / JN5-OP-F02 / Catalogue JN5-OP-F02 as printed C1
Accessory / JN5-OP-F02 / Note Not stated (blank in source) as printed C1
Accessory / JN5-OP-F03 / Category Digital Operators as printed C1
Accessory / JN5-OP-F03 / Description IP20 LCD HOA Type as printed C1
Accessory / JN5-OP-F03 / Catalogue JN5-OP-F03 as printed C1
Accessory / JN5-OP-F03 / Note With HAND/OFF/AUTO function as printed C1
Accessory / JN5-OP-A03 / Category Digital Operators as printed C1
Accessory / JN5-OP-A03 / Description IP20 Blank type as printed C1
Accessory / JN5-OP-A03 / Catalogue JN5-OP-A03 as printed C1
Accessory / JN5-OP-A03 / Note Not stated (blank in source) as printed C1
Accessory / JN5-CR-A01 / Category Protective Cover as printed C1
Accessory / JN5-CR-A01 / Description Positioned on both sides of the inverter to prevent unknown objects from invading as printed C1
Accessory / JN5-CR-A01 / Catalogue JN5-CR-A01 as printed C1
Accessory / JN5-CR-A01 / Note For Frame 1 as printed C1
Accessory / JN5-CR-A02 / Category Protective Cover as printed C1
Accessory / JN5-CR-A02 / Description Positioned on both sides of the inverter to prevent unknown objects from invading as printed C1
Accessory / JN5-CR-A02 / Catalogue JN5-CR-A02 as printed C1
Accessory / JN5-CR-A02 / Note For Frame 2 as printed C1
Accessory / JN5-CR-A04 / Category Protective Cover as printed C1
Accessory / JN5-CR-A04 / Description Positioned on both sides of the inverter to prevent unknown objects from invading as printed C1
Accessory / JN5-CR-A04 / Catalogue JN5-CR-A04 as printed C1
Accessory / JN5-CR-A04 / Note For Frame 4 as printed C1
Accessory / JN5-MD-A01 / Category Middle Layer Case as printed C1
Accessory / JN5-MD-A01 / Description For 1 to 8 pump card/ communication card/ Digital & Analog IO Expansion Card/ DC24V power card installation (For frame 2~4, if only install 1 to 8 pump card, don’t need middle layer cuse) (After installation,the Depth will add) as printed C1
Accessory / JN5-MD-A01 / Catalogue JN5-MD-A01 as printed C1
Accessory / JN5-MD-A01 / Note For Frame 1,D+44mm as printed C1
Accessory / JN5-MD-A02 / Category Middle Layer Case as printed C1
Accessory / JN5-MD-A02 / Description For 1 to 8 pump card/ communication card/ Digital & Analog IO Expansion Card/ DC24V power card installation (For frame 2~4, if only install 1 to 8 pump card, don’t need middle layer cuse) (After installation,the Depth will add) as printed C1
Accessory / JN5-MD-A02 / Catalogue JN5-MD-A02 as printed C1
Accessory / JN5-MD-A02 / Note For Frame 2,D+31mm as printed C1
Accessory / JN5-MD-A03 / Category Middle Layer Case as printed C1
Accessory / JN5-MD-A03 / Description For 1 to 8 pump card/ communication card/ Digital & Analog IO Expansion Card/ DC24V power card installation (For frame 2~4, if only install 1 to 8 pump card, don’t need middle layer cuse) (After installation,the Depth will add) as printed C1
Accessory / JN5-MD-A03 / Catalogue JN5-MD-A03 as printed C1
Accessory / JN5-MD-A03 / Note For Frame 3,D+34mm as printed C1
Accessory / JN5-MD-A04 / Category Middle Layer Case as printed C1
Accessory / JN5-MD-A04 / Description For 1 to 8 pump card/ communication card/ Digital & Analog IO Expansion Card/ DC24V power card installation (For frame 2~4, if only install 1 to 8 pump card, don’t need middle layer cuse) (After installation,the Depth will add) as printed C1
Accessory / JN5-MD-A04 / Catalogue JN5-MD-A04 as printed C1
Accessory / JN5-MD-A04 / Note For Frame 4,D+35mm as printed C1
Accessory / JN5-IO-8DO / Category Others as printed C1
Accessory / JN5-IO-8DO / Description 1 to 8 Pump card as printed C1
Accessory / JN5-IO-8DO / Catalogue JN5-IO-8DO as printed C1
Accessory / JN5-IO-8DO / Note Not stated (blank in source) as printed C1
Accessory / JN5-CU / Category Others as printed C1
Accessory / JN5-CU / Description Copy Module for 510 series as printed C1
Accessory / JN5-CU / Catalogue JN5-CU as printed C1
Accessory / JN5-CU / Note Not stated (blank in source) as printed C1

Selection checks and source differences

Website3.7–600kW versus brochure0.75–600kW; websiteIP55/IP00 versus brochureIP55/IP20 and manual multiple enclosures. BrochureIP55/NEMA4 versus manualIP55/NEMA12 unresolved; outdoor wording cannot override indoor/manual environmental restrictions.

Up to eight pumps is explicitly tied to the optional1-to-8 pump card; no inference that every standard unit controls eight pumps without hardware.

Quick-guide F510 title versus E510s introduction and forward/reverse heading versus RUN/STOP–REV/FWD figure are preserved as source discrepancies.

Enhanced catalogue frame2 filtered/unfiltered depth differs;4025 filtered version uses a different frame. Model placeholder, H/E/G example and008 HP labels remain literal.

I/O card analogue input/output description conflicts, duplicated Expansion Slot1 labels,0.1/0.01Hz lower frequency disagreement and manual2–8Hz carrier footnote retained without correction.

Fire-mode reset quantity on manualPDF274 is called output current in prose despite temperature axes/units; charge-indicator comparison operator onPDF71 is unreadable. Neither missing meaning is inferred.

The25% saving illustration is conditional, not an installation guarantee. Display/filter/safety claims remain model-, edition- and firmware-specific.

Product documents

Our company certificates and conditions of sale remain separate from the selected product’s ratings and approvals.

Talk to our team about your application, supply, motor rating and configuration.